Carrier 40MAQB09B3, 40MAQB12B3, 40MAQB18B3 Product Data

Page 1
38MGQ / 40MAQ / 40MB Multi---Zone Ductless Split System Sizes 18, 27, 36 and 48
Product Data
INDUSTRY LEADING FEATURES / BENEFITS
AN INEXPENSIVE AND CREATIVE SOLUTION TO DESIGN PROBLEMS.
The different styles of indoor units can be mounted in several locations to accommodate the application. This selection of fan coils permits inexpensive and creative solutions to design problems such as:
S When adding air conditioning to spaces that are heated
by hydronic or electric heat and have no ductwork.
S Historical renovations or any application where
preserving the look of the original structure is essential.
S Commercial add--on jobs where the existing air
conditioning system cannot be stretched.
These compact indoor fan coil units take up very little space in the room and do not obstruct windows. The fan coils are attractively styled to blend with most room decors.
Advanced system components incorporate innovative technology to provide reliable cooling and heating performance at low sound levels.
Page 2
INVERTER TECHNOLOGY
The inverter driven compressor is designed to run at various input power frequencies (Hz) which controls the compressor’s motor speed.
Even Temperature – The control package, including the inverter, monitors the outdoor and indoor temperatures as they relate to the selected indoor set point and adjusts the compressor speed to match the load and keep the system operating continuously rather than cycling and creating temperature swings. This translates to higher comfort levels for the occupants.
Rapid Pull Down/Warm--Up – Comfort is increased by the inverter system’s ability to ramp up the compressor speed enabling the system to reach the user selected room temperature set point quicker.
Humidity Control – Running the system for longer periods and continuously varying the compressor speed enhances the humidity control.
INDIVIDUAL ROOM COMFORT
Maximum comfort is provided because each space can be controlled individually based on the usage pattern. The air sweep feature provided permits optimal room mixing to eliminate hot and cold spots for the occupant comfort.
LOW SOUND LEVELS
When noise is a concern, ductless split systems are the answer. The indoor units are whisper quiet. There are no compressors indoors, either in the conditioned space or directly over it, and there is none of the noise usually generated by air being forced through the ductwork.
When sound ordinances and proximity to neighbors demand quiet operation, the 38MGQ unit is the right choice. With the inverter technology, these units run at lower speeds most of the time resulting in reduced sound levels.
INVERTER TECHNOLOGY – ENHANCED ECONOMICAL OPERATION
Ductless systems are inherently economical to operate. Individual rooms are heated or cooled only when required, and since the air is delivered directly to the space, there is no need to use additional energy to move the air in the ductwork. This economical operation is enhanced further when the inverter system output matches the load resulting in a more efficient system.
EASY--TO--USE CONTROLS
The multi--zone systems have microprocessor--based controls to provide the ultimate in comfort and efficiency. The user friendly wired and wireless remote controls provide the interface between the user and the unit.
FAST INSTALLATION
This compact ductless split system is simple to install. A mounting bracket is included with the indoor units and only wires and piping need to run between the indoor and outdoor units. These units are fast and easy to install ensuring minimal disruption to customers in homes or the workplace. This makes the 38MGQ/40MAQ/40MB systems the equipment of choice for retrofit applications.
SIMPLE SERVICING AND MAINTENANCE
Removing the top panel of the outdoor unit provides immediate access to the control compartment, providing the service technician access to the diagnostic LEDs to facilitate the troubleshooting process. In addition, the draw--thru design of the outdoor unit means that dirt accumulates on the outside surface of the coil. Coils can be cleaned quickly from the inside using a pressure hose and detergent.
On the indoor units, service and maintenance expense is reduced due to the permanent easy to clean filters. Also, error codes are displayed on the front panel to alert the user to certain system malfunctions
BUILT--IN RELIABILITY
Ductless split system indoor and outdoor units are designed to provide years of trouble--free operation.
Both the indoor and outdoor units are well protec t ed. Whenever the micr opr ocessor detects abnormal conditions, the unit stops and an error code appear s.
Inverter systems provide additional reliability due to the soft start. This refers to the ability of the inverter to start the compressor motor using reduced voltage and reduced current. This feature is beneficial from an electrical standpoint (eliminates current spikes) as well as an overall reliability standpoint due to reduced stress on all associated system components.
CONDENSATE PUMP
A condensate pump accessory is available (High Wall and Floor Console) to provide installation flexibility for those applications where gravity cannot be used to dispose of the condensate. Factory installed condensate pump on the Ducted and Cassette fan coils provides installation flexibility.
AGENCY LISTINGS
All systems are listed with AHRI (Air conditioning, Heating, and Refrigeration Institute) and are ETL certified per UL 1995 standard.
SECURE OPERATION
If security is an issue, outdoor and indoor units are connected only by refrigerant piping and wiring to prevent intruders from crawling through ductwork or wall openings. In addition, since the 38MGQ can be installed close to an outside wall, coils are protected from vandals and severe weather.
2
Page 3
MODEL NUMBER NOMENCLATURE
INDOOR UNIT
40 MB 309
40 = FAN COIL UNIT
BQD
--- ---
MA =HIGHWALL MB = CASSETTE, DUCTED, FLOOR CONSOLE
SYSTEM TYPE Q =HEATPUMP
B=ALL
NOMINAL C APACITY 09 --- 3 /4 T O N 12 --- 1 T O N 18 --- 1 --- 1 /2 T O N S 24 --- 2 T O NS
38 MG 318
38 = OUTDOOR UNIT
MG =ALL
SYSTEM TYPE Q =HEATPUMP
OUTDOOR UNIT
CQ---
--- ---
VOLTAGE 3 = 208/230 ---1--- 60
NOT USED
INDOOR FAN COIL TYPE
B =HIGHWALL C =CASSETTE D =DUCTED F = FLOOR CONSOL E
VOLTAGE 3 = 208/230 ---1--- 60
MAXIMUM NUMBER OF FAN COIL UNITS THAT CAN BE CONNECTED TO THE OUTDOOR UNIT C =1:2 D =1:3 F =1:4OR1:5
NOMINAL C APACITY 18 --- 1 1 / 2 T O NS 27 --- 2 1 / 4 T O NS 36 --- 3 T O NS 48 --- 4 T O NS
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program For verification of certification for individual products, go to www.ahridirectory.org.
NOT USED
UNIT TYPE
--- = OUTDOOR UNIT
3
Page 4
STANDARD FEATURES AND ACCESSORIES
Ease of Installation
Mounting Bracket S Low Voltage Controls S
Comfort Features
Microprocessor Control S
Wired Remote Control for High Walls, Cas set te and Floor Console A
Wired Remote Control for D ucted S
Wireless Remote Control S Rapid Cooling and Heating S Automatic Air Sweep S Cold Blow Prevention S Continuous Fan S Auto Restart Function S Auto Changeover S
Follow Me S
Energy Saving Features
Inverter Driven Compressor S Sleep Mode S 24 Hour Stop/Start Timer S
46° F Heating Mode (Heating Setback) S
Safety And Reliability
Indoor Coil Freeze Protection S 3MinuteTimeDelayForCompressor S High Compressor Discharge Temperature S Low Voltage Protection S Compressor Overload Protection S Compressor Over Current Protection S IPM Modul e Protection S
Ease of Service
Cleanable Filters S Diagnostic S Error Messages Displayed On Front Panel S
Application Flexibility
Condensate Pumps For High Walls and Floor Console A Condensate Pump For Cassette and Ducted S Crankcase Heater S Basepan Heater S
Legend S St andard A Accessory
INDOOR UNITS
On high wall and floor console fan coils, the condensate pump accessory is recommended when an adequate drain line pitch cannot be provided, or when the condensate must move up to exit.
The pump has a lift capability of 12 ft. (3.6 m) on the discharge side if the pump is mounted in the fan coil or 6 ft. (1.8 m) on the suction side if the pump is remote mounted.
OUTDOOR UNITS
Standard on all unit sizes. Heater clamps around compressor oil stump.
FACTORY INSTALLED BASEPAN HEATER
Fig. 1 – Condensate Pump Accessory
ACCESSORIES
ORDERING NO. DESCRIPTION FOR MODELS
5 3 DS --- 9 0 0 --- --- --- 1 1 8
KSACN0101AAA Wired Remote Control
4 0 MBQ B 0 1 C --- --- --- Grille/Ceiling panel
5 3 DS --- 9 0 0 --- --- --- 0 0 8
5 3 DS --- 9 0 0 --- --- --- 0 8 9
Condensate Pump
(230v)
Insulated 25’ Line Set ---
1/4“ x 1/2”
Insulated 25’ Line Set ---
1/4” x 3/8”
MA, MB*F Indoo r units
MA, MB*F & MB*C
MB*C Cassette Indoo r
See Product Data fo r
See Product Data fo r
Systems
units
sizes
sizes
4
Page 5
COMBINATION TABLE
INDOOR UNIT NOMINAL UNIT BTUH INDOORMODEL NUMBER OUTDOOR MODEL NUMBER
High Wall
Cassette
Ducted
Floor Console
INDOOR UNIT NOMINAL UNIT BTUH INDOORMODEL NUMBER OUTDOOR MODEL NUMBER
High Wall
Cassette
Ducted
Floor Console
INDOOR UNIT NOMINAL UNIT BTUH INDOORMODEL NUMBER OUTDOOR MODEL NUMBER
High Wall
Cassette
Ducted
Floor Console
9,000 40MAQB09B--3
12,000 40MAQB12B--3
9,000 40MBQB09C--3
12,000 40MBQB12C--3
9,000 40MBQB09D--3
12,000 40MBQB12D--3
9,000 40MBQB09F--3
12,000 40MBQB12F--3
9,000 40MAQB09B--3 12,000 40MAQB12B--3 18,000 40MAQB18B--3
9,000 40MBQB09C--3 12,000 40MBQB12C--3 18,000 40MBQB18C--3
9,000 40MBQB09D--3 12,000 40MBQB12D--3 18,000 40MBQB18D--3
9,000 40MBQB09F--3 12,000 40MBQB12F--3
9,000 40MAQB09B--3 12,000 40MAQB12B--3 18,000 40MAQB18B--3 24,000 40MAQB24B--3
9,000 40MBQB09C--3 12,000 40MBQB12C--3 18,000 40MBQB18C--3
9,000 40MBQB09D--3 12,000 40MBQB12D--3 18,000 40MBQB18D--3 24,000 40MBQB24D--3
9,000 40MBQB09F--3 12,000 40MBQB12F--3
38MGQC18---3
38MGQD27---3
38MGQF36---3 38MGQF48---3
5
Page 6
DIMENSIONS -- INDOOR
UNIT SIZE W In. (mm) D In. (mm) H In. (mm)
9K/12K 32.9(835) 7.8(198) 11.0(280) 19.2(8.7)
18K 39.0(990) 8.6(218) 12.4(315) 26.5(12.0)
24K/30K 46.7(1186) 10.2(258) 13.4( 343) 40.8(18.5)
Fig. 2 – High Wall Dimensions
OPERATING WEIGHT
Lbs. (kg)
Fig. 3 – Cassette Dimensions
UNIT SIZE
Height in(mm) 10.24 (260) 1.97 (50) 10.24 (260) 1.97 (50) 10.24 (260) 1.97 (50)
Width in(mm) 22.44 (570) 25.47 (647) 22.44 (570) 25.47 (647) 22.44 (570) 25.47 (647) Depth in(mm) 22.44 (570) 25.47 (647) 22.44 (570) 25.47 (647) 22.44 (570) 25.47 (647)
Operating
Weight
lbs(kg) 35.27 (16) 5.51 (2.5) 35.27 (16) 5.51 (2.5) 39.68 (18) 5.51 (2.5)
body panel body panel body panel
9K 12K 18K
6
Page 7
DIMENSIONS -- INDOOR (CONTINUED)
Fig. 4 – Ducted Dimensions
OUTLINE
DIMENSIONS in(mm)
Size A B C D E F G H I J K L M H1 H2 W1 W2
27.6
(700)
27.6
(700)
36.2
(920)
36.2
(920)
8.2
(210)25(635)
8.2
(210)25(635)
8.2
(210)25(635)
10.6
(270)25(635)
9
12
18
24
22.4
(570)
22.4
(570)
22.4
(570)
22.4
(570)
AIR O UTLET
OPENING SIZE in(mm)
2.5
19.4
(65)
(493)
2.5
19.4
(65)
(493)
2.5
19.4
(65)
(493)
2.5
19.4
(65)
(493)
1.3 (35)
1.3 (35)
1.3 (35)
1.3 (35)
OPENING SIZE in(mm)
4.6
23.4
(119)
(595)
4.6
23.4
(119)
(595)
4.6
32.0
(119)
(815)
7.0
32.0
(179)
(815)
AIR RETURN
7.8
(200)
7.8
(200)
7.8
(200)
10.2
(260)
3.1
(80)
3.1
(80)
3.1
(80)
0.7
(20)
HANGER
BRACKETS
in(mm)
29.1
(740)
29.1
(740)
37.8
(960)
37.8
(960)
13.8
(350)
13.8
(350)
13.8
(350)
13.8
(350)
PIPE LOCATIONS
4.7
(120)
4.7
(120)
4.7
(120)
4.7
(120)
REFRIGERANT
in(mm)
5.6
3.7
(143)
(95)
5.6
3.7
(143)
(95)
5.6
3.7
(143)
(95)
5.6
3.7
(143)
(95)
5.9
(150)
5.9
(150)
5.9
(150)
5.9
(150)
7
OPERATING
WEIGHT Lbs. (kg)
in(mm)
39.90 (18.1)
39.90 (18.1)
50.7 (23)
57.32 (26)
Page 8
DIMENSIONS -- INDOOR (CONTINUED)
Fig. 5 – Floor Console Dimensions
UNIT SIZE 9 12
Depth in (mm) 8.27 (210) 8.27 (210) Width in (mm) 27.56 (700) 27.56 (700)
Height in (mm) 23.62 (600) 23.62 (600)
Operating Weight Lbs. (kg) 32.41 (14.7) 32.41 (14.7)
8
Page 9
DIMENSIONS -- OUTDOOR
Fig. 6 – Outdoor Dimensions Size 18
UNIT SIZE 18
Height in (mm) 27.56(700)
Width in (mm) 33.27(845) Depth in (mm) 12.60(320)
W e i g h t --- N e t lbs (kg) 114.63(52)
9
Page 10
DIMENSIONS -- OUTDOOR (CONTINUED)
Fig. 7 – Outdoor Dimensions Size 27
UNIT SIZE 27
Height in (mm) 31.89(810)
Width in (mm) 37.20(945) Depth in (mm) 15.55(395)
W e i g h t --- N e t lbs (kg) 154.76(70.2)
10
Page 11
DIMENSIONS -- OUTDOOR (CONTINUED)
Fig. 8 – Outdoor Dimensions Size 36
UNIT SIZE 36
Height in (mm) 31.89(810)
Width in (mm) 37.20(945) Depth in (mm) 15.55(395)
W e i g h t --- N e t lbs (kg) 169.75(77)
11
Page 12
DIMENSIONS -- OUTDOOR (CONTINUED)
Fig. 9 – Outdoor Dimensions Size 48
UNIT SIZE 48
Height in (mm) 36.93(1369)
Width in (mm) 53.9(938) Depth in (mm) 15.43(392)
W e i g h t --- N e t lbs (kg) 255.50(115.9)
12
Page 13
CLEARANCES -- INDOOR
NOTE: Allow sufficient space for airflow and unit servicing. See Fig. 10 thr ough 15 for minimum required clearances.
CEILING
6" (0.15m) min.
5
"
(0.13m)
min.
(1.8m)
6'
FLOOR
Fig. 10 – High Wall Clearance
5
"
(0.13m)
min.
Fig. 11 – Cassette Unit Clearance
13
Page 14
CLEARANCES -- INDOOR (CONTINUED)
19.7in
/500mm /100mm
3.9in
Fig. 12 – Ducted Clearance
39.4in
/1000mm
19.7in /500mm
9.8in
/250mm
7.9in
/200mm
9.8ft
/3m
Fig. 13 – Ducted Clearance
Fig. 14 – Floor Console Clearances
14
Page 15
CLEARANCES -- OUTDOOR
D
A
B
C
Air-outlet
Fig. 15 – Clearances Outdoor
UNIT
A 24 (609)
B 24 (609) C 24 (609) D 4 (101)
E 4 (101)
MINIMUM VALUE
in. (mm)
Air-inlet
E
15
Page 16
PHYSICAL DATA -- OUTDOOR
System
Performance
Non-Ducted
Performance
Combination
Ductedand Non-Ducted
Performance
Ducted
Operating
Range
Piping
Refrigerant
Electrical
Compressor
Outdoor
Size 18 27 36 48 Outdoor Model 38MGQC18---3 38MGQD27---3 38MGQF36---3 38MGQF48---3 Max Number of Zones 2 3 4 5 Energy Star YES YES NO YES Cooling System Tons 1.5 2.1 3.0 3.5 Cooling Rated Capacity Btu/h 18,000 25,000 36,000 42,000 Cooling Cap. Range Min - Max Btu/h 8,500~20,000 9,000~30,000 9,500~37,000 10,000~50,000 SEER 21 22 18 20 EER 12.5 12.5 8.8 12.5 Heating Rated Capacity (47°F) Btu/h 18,500 32,000 36,000 49,000 Heating Cap. Range Min - Max Btu/h 9,000~22,000 9,500~32,000 10,000~39,000 10,500~55,000 HSPF 9.6 9.6 10.0 10.0 COP W/W 3.7 3.5 3.4 3.4 Cooling Rated Capacity Btu/h 17,500 26,000 35,000 42,000 Cooling Cap. Range Min - Max Btu/h 8,500~20,000 9,000~30,000 9,500~36,500 10,000~50,000 SEER 19.5 19.25 16.5 19 EER 12.5 11 8.5 11.75 Heating Rated Capacity (47°F) Btu/h 18,250 32,000 36,000 50,000 Heating Cap. Range Min - Max Btu/h 9,000~22,000 9,500~32,000 10,000~39,000 10,500~55,000 HSPF 9.1 9.2 9.7 9.8 COP W/W 3.7 3.5 3.4 3.4 Cooling Rated Capacity Btu/h 17,000 27,000 34,000 42,000 Cooling Cap. Range Min - Max Btu/h 8,500~20,000 9,000~30,000 9,500~36,000 10000~50000 SEER 18 16.5 15 18 EER 12.5 9.5 8.2 11 Heating Rated Capacity (47°F) Btu/h 18,000 32,000 36,000 51,000 Heating Cap. Range Min - Max Btu/h 9000~22000 9500~32000 10,000~39,000 10,500~55,000 HSPF 8.5 8.8 9.3 9.5 COP W/W 3.7 3.5 3.3 3.4 Cooling Outdoor DB Min - Max °F(°C) -4~122 (-20~50) -4~122 (-20~50) -4~122 (-20~50) -4~122 (-20~50) Heating Outdoor DB Min - Max °F(°C) -4~86 (-20~30) -4~86 (-20~30) -4~86 (-20~30) -4~86 (-20~30) Total Piping Length ft (m) 98 (30) 147 (45) 196 (60) 245 (75) Piping to furthest FCU ft (m) 98 (30) 98 (30) 98(30) 98 (30) Drop (OD above ID) ft (m) 32 (10) 32 (10) 32 (10) 32 (10) Lift (OD below ID) ft (m) 49 (15) 49 (15) 49 (15) 49 (15) Pipe Connection Size - Liquid in (mm) 1/4*2 (6.35*2) 1/4*3 (6.35*3) 1/4*4 (6.35*4) 1/4*5 (6.35*5)
Pipe Connection Size - Suction in (mm) 3/8 (9.52*2) 3/8 (9.52*3) Type R410A R410A R410A R410A
Metering Device EEV EEV EEV EEV Charge lbs (kg) .19 (1.9) 6.17 (2.8) 7.94 (3.6) 10.14 (4.6) Voltage, Phase, Cycle V/Ph/Hz 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 Power Supply Indoor unit powered from outdoor unit MCA A. 15 19 27 29 MOCP - Fuse Rating A. 20 25 40 50 Type RotaryInverter Rotary Inverter Rotary Inverter Rotary Inverter Model DA150S1C-20FZ DA250S2C-30MT TNB306FPGMC-L MNB36FAAMC-L Oil Type ESTEROIL VG74 ESTER OILVG74 FV50S FV50S Oil Charge Fl. Oz. 16.9 27.7 36.2 47.3 Rated Current RLA 10 12.3 22 22 Unit Width in (mm) 33.27 (845) 37.20 (945) 37.20 (945) 53.9 (938) Unit Height in (mm) 27.56 (700) 31.89 (810) 31.89 (810) 36.93 (1369) Unit Depth in (mm) 12.60 (320) 15.55 (395) 15.55 (395) 15.43 (392) Net Weight lbs (kg) 105.82 (48) 143.29(65) 158.72 (72) 227.72 (103.3) Airflow CFM 1,390 2,130 2,130 3,500 Sound Pressure dB(A) 60 63 63 64
HEAT PUMP
1/2 *1+ 3/8*3
(12.7*1+9.52*3)
1/2 *2+ 3/8*3
(12.7*2+9.52*3)
16
Page 17
PHYSICAL DATA -- INDOOR
SIZE 9 12 18 24
Model 40MAQB09B------3 40MAQB12B------3 40MAQB18B------3 40MAQB24B--- ---3 Unit Width In. 32.9 32.9 39 46.7 Unit Height In. 11 11 12.4 13.4 Unit Depth In. 7.8 7.8 8.6 10.2 Net Weight Lbs. 19.2 19.2 26.5 40.1
High Wall
Indoor Unit
Cassette
Indoor Unit
Pipe Connection Size --- Liquid In. 1/4 1/4 1/4 3/8 Pipe Connection Size --- Suction In. 3/8 1/2 1/2 5/8 Number of Fan Speeds 4 4 4 4 Airflow (lowest to highest) CFM 210/290/360/380 210/300/360/380 310/ 450/650/680 520/620/780/870 Sound Pressure (lowest to highest) dB(A) 27/34/42 27/34/42 33/40/46 39/45/50 Air throw Data Ft. 23 23 30 36 Wireless Remote Controller (° F/° C Convertible) Standard Wired Remote Controller (° F/° C Convertible) Optional
SIZE 9 12 18
Model 40MBQB09C --- ---3 40MBQB12C --- ---3 40MBQB18C --- --- 3 Unit Width In. 22.4 22.4 22.4 Unit Height In. 10.2 10.2 10.2 Unit Depth In. 22.4 22.4 22.4 Net Weight Lbs. 35.3 35.3 39.7 Pipe Connection Size --- Liquid In. 1/4 1/4 1/4 Pipe Connection Size --- Suction In. 3/8 1/2 1/2 Number of Fan Speeds 3 3 3 Airflow (lowest to highest) CFM 260/320/380 280/340/400 290/350/420 Sound Pressure (lowest to highest) dB(A) 34/39/44 36/39/42 46/48/50 Wireless Remote Controller (° F/° C Convertible) Standard Wired Remote Controller (° F/° C Convertible) Optional
Ducted
Indoor Unit
Floor Console
Indoor Unit
SIZE 9 12 18 24
Model 40MBQB09D--- ---3 40MBQB12D --- ---3 40MBQB18D --- --- 3 40MBQB24D --- --- 3 Unit Width In. 27.6 27.6 36.2 36.2 Unit Height In. 8.3 8.3 8.3 10.6 Unit Depth In. 25 25 25 25 Net Weight Lbs. 39.9 39.9 50.7 57.3 Pipe Connection Size --- Liquid In. 1/4 1/4 1/4 3/8 Pipe Connection Size --- Suction In. 3/8 1/ 2 1/2 5/8 Number of Fan Speeds 3 3 3 3 Airflow (lowest to highest) CFM 290/340/380 290/340/380 400/440/480 590/650/810 Sound Pressure (lowest to highest) dB(A) 30/33/36 30/34/38 34/37/38 43/45/48 Max Static Pressure In.WG. 0.18 0.18 0.40 0.40 Wireless Remote Controller (° F/° C Convertible) Standard Wired Remote Controller (° F/° C Convertible) Standard
SIZE 9 12
Model 40MBQB09F------3 40MBQB12F --- ---3 Unit Width In. 27.6 27.6 Unit Height In. 8.3 8.3 Unit Depth In. 23.6 23.6 Net Weight Lbs. 32.4 32.4 Pipe Connection Size --- Liquid In. 1/4 1/4 Pipe Connection Size --- Suction In. 3/8 1/2 Number of Fan Speeds 3 3 Airflow (lowest to highest) CFM 220/250/280 220/250/280 Sound Pressure (lowest to highest) dB(A) 37/38/41 34/41/45 Wireless Remote Controller (° F/° C Convertible) Standard Wired Remote Controller (° F/° C Convertible) Optional
17
Page 18
COOLING PERFORMANCE
COOLING OUTDOOR CONDITIONS (DB)
MODEL
18
27
36
48
Indoor Conditions DB
DB WB
69.8F(21C) 59F(15C)
80.6F(27C) 66.2F(19C)
69.8F(21C) 59F(15C)
80.6F(27C) 66.2F(19C)
69.8F(21C) 59F(15C)
80.6F(27C) 66.2F(19C)
69.8F(21C) 59F(15C)
80.6F(27C) 66.2F(19C)
75F(24C) 85F(29.5C) 95F(35C) 105F(40.5C)
TC 18.07 18.74 17.22 13.28 SC 15.00 15.37 14.64 13.01
Input 1.17 1.54 1.72 1.88
TC 20.75 21.48 20.43 16.42 SC 15.97 16.33 15.93 14.62
Input 1.16 1.56 1.76 1.59
TC 23.99 27.20 24.55 19.31 SC 22.67 24.08 22.56 19.31
Input 1.50 2.42 2.67 2.39
TC 27.40 31.78 29.90 23.85 SC 23.72 25.06 25.12 22.94
Input 1.51 2.52 2.83 2.51
TC 28.80 32.69 30.25 23.15 SC 26.32 28.18 27.02 23.15
Input 2.17 3.45 3.81 2.99
TC 33.47 38.11 36.60 28.42 SC 28.83 30.55 32.94 26.99
Input 2.21 3.57 3.94 3.25
TC 44.06 42.04 38.95 34.05 SC 37.89 36.57 35.44 33.37
Input 3.32 3.78 4.19 4.45
TC 46.88 49.74 45.99 41.31 SC 40.32 43.27 41.85 40.07
Input 2.64 3.90 4.33 4.61
LEGEND
DB --- Dry Bulb WB --- Wet Bulb TC --- Total Net Cooling Capacity (1000 Btu/hour) SC --- Sensible Capacity (1000 Btu/hour) Input --- Total Power (kW)
HEATING PERFORMANCE
MODEL
18
27
36
48
HEATING OUTDOOR CONDITIONS (DB)
Indoor Conditions (DB) 57F(13.9C) 47F(8.3C) 35F(1.7C) 17F( ---8.3C) 5F( ---15C) --- 4 F ( --- 2 0 C )
55F(12.7C)
70F(21.1C)
55F(12.7C)
70F(21.1C)
55F(12.7C)
70F(21.1C)
55F(12.7C)
70F(21.1C)
TC 23.27 20.85 16.80 13.29 10.92 8.63 Input 1.25 1.33 1.30 1.42 1.35 1.31 COP 5.45 4.59 3.78 2.75 2.38 1.94
TC 21.69 20.19 16.19 12.32 9.09 7.70 Input 1.45 1.51 1.49 1.56 1.48 1.41 COP 4.39 3.93 3.18 2.31 1.80 1.60
TC 37.85 34.34 28.36 22.77 19.38 16.23 Input 2.27 2.29 2.29 2.46 2.44 2.40 COP 4.89 4.39 3.63 2.71 2.33 1.98
TC 36.29 3.23 27.54 20.09 16.37 13.42 Input 2.68 2.64 2.51 2.53 2.39 2.29 COP 3.97 0.36 3.21 2.32 2.00 1.72
TC 41.10 38.52 28.84 28.16 22.87 19.43 Input 3.17 3.31 2.92 3.22 2.97 2.91 COP 3.80 3.41 2.89 2.56 2.26 1.96
TC 40.86 38.83 29.89 26.02 20.15 16.70 Input 3.62 3.73 3.37 3.38 3.05 2.90 COP 3.30 3.05 2.60 2.26 1.93 1.69
TC 60.91 53.30 42.81 33.02 26.16 20.01 Input 4.26 4.04 3.78 3.82 3.56 3.42 COP 4.19 3.87 3.32 2.53 2.15 1.71
TC 55.22 50.58 40.56 31.81 23.48 17.17 Input 4.64 4.59 4.20 4.27 3.98 3.88 COP 3.49 3.23 2.83 2.19 1.73 1.30
LEGEND
DB --- Dry Bulb TH --- Total Net Heating Capacity (1000 Btu/hour) Input --- Total Power (kW)
18
Page 19
PIPING REQUIREMENTS
SYSTEM SIZE 18K 27K 36K 48K
Min. Piping Length per each indoor unit ft (m) 10 (3) 10 (3) 10 (3) 10 (3) Standard Piping Length per each indoor unit ft (m) 25 (7.5) 25 (7.5) 25 (7.5) 25 (7.5)
Piping
Refrigerant
Max. outdoor---indoor height difference (OU higher than IU) Max. outdoor---indoor height difference (IU higher than OU) Max. height different between indoor units ft (m) 32(10) 32(10) 32( 10) 32(10) Max. Length per each indoor unit ft (m) 66(20) 82(25) 98(30) 98(30) Max. Piping Length with no additional refrigerant charge per System (Standard Piping length x No. of Zones) Total Maximum Piping Length per system Ft. (m) 98(30) 147(45) 196(60) 245(75) Additional refrigerant charge (between Standard – Max piping length)
Gas Pipe Size in (mm) 3/8*2 (9.52*2) 3/8*2 (9.52*3)
Liquid Pipe Size in (mm) 1/4 *2 (6.35*2) 1/4 *3 ( 6.35*3) 1/4 *4 (6.35*4) 1/4 *5 (6.35*5) Refrigerant Type R410A R410A R410A R410A Charge Amount Lbs (kg) 4.19 (1.9) 6.17 (2.8) 7.94 (3.6) 10.14 (4.6)
ft (m) 32(10) 32(10) 32(10) 32(10)
ft (m) 49(15) 49(15) 49(15) 49(15)
ft (m) 49(15) 74(22.5) 98(30) 123(37.5)
Oz/ft (g/m) 0.16(15) 0.16(15) 0.16(15) 0.16(15)
1/2 *1 (12.7*1)
+3/8*3(9.5*3)
1/2 *2 (12.7*2)
+3/8*3(9.5*3)
NOTE: The refrigerant charge included is adequate for the number of zones multiplied by the maximum piping length per zone with no additional refrigerant.
APPLICATION DATA
UNIT SELECTION
When selecting a variable speed system match the system capacity range to the anticipated load range. Since a variable speed system can accommodate a wide range of loads it is important to understand the percentage of time that the system will be required to run at both the maximum and the minimum load points. This differential is most evident when a residential application is compared with a commercial application.
Generally there will be more load diversification in the residential application (shifting from low load to high load).
The commercial application tends to be more steady during the normal day time hours, and will go to low load levels after normal business hours. If it is anticipated that the system needs to run at the maximum load point for the majority of the time, the next larger system capacity should be selected.
19
Page 20
APPLICATION DATA
OUTDOOR UNIT MODEL COOLING CAPACITY (Btu/h) HEATING C APACITY (Btu/h)
3 8 MG Q C 1 8 --- --- --- 3 Typ e Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 1 Zone 2 Zone 3 Zone 4 Zone 5
9K+9K
9K+12K 8,500 10,500 9,000 11,000
12K+12K 9,500 9,500 10,000 10,000
3 8 MG Q D 2 7 --- --- --- 3 Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 1 Zone 2 Zone 3 Zone 4 Zone 5
9K+9K 9K+12K 9,500 12,000 10,000 13,000 9K+18K 8,400 16,600 9,000 18,000
12K+12K 12,000 12,000 13,000 13,000 12K+18K 10,000 15,000 11,200 16,800
9+9+9 9+9+12 8,667 8,667 11,667 9,500 9,500 12,000 9+9+18 8,333 8,333 13,333 9,000 9,000 14,000
9+12+12 8,500 10,000 10,000 8,500 11,000 11,000
12+12+12 9,667 9,667 9,667 10,667 10,667 10,667
3 8 MG Q F 3 6 --- --- --- 3 Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 1 Zone 2 Zone 3 Zone 4 Zone 5
9+18 12+12 12,000 12,000 13,000 13,000 12+18 12,000 18,000 13,000 18,000 18+18 16,500 16,500 17,000 17,000
9+24 8,500 22,500 9,500 22,500 12+24 10,500 21,000 11,000 22,000
9+9+9 9+9+12 9,000 9,000 12,000 9,500 9,500 12,500 9+9+18 8,000 8,000 16,000 8,500 8,500 17,000
9+12+12 8,500 11,500 11,500 9,000 12,000 12,000 9+12+18 8,000 11,000 15,000 8,500 11,500 16,000
9+18+18 8,000 14,000 14,000 8,500 14,500 14,500 12+12+12 11,333 11,333 11,333 12,000 12,000 12,000 12+12+18 11,000 11,000 14,000 12,000 12,000 15,000 12+18+18 9,333 13,333 13,333 9,500 14,000 14,000
9+9+9+9 9+9+9+12 8,500 8,500 8,500 11,500 9,000 9,000 9,000 12,000 9+9+9+18 8,000 8,000 8,000 14,000 8,500 8,500 8,500 14,000
9+9+12+12 8,000 8,000 10,500 10,500 8,500 8,500 11,000 11,000 9+9+12+18 7,500 7,500 9,000 14,000 8,000 8,000 9,500 14,500
9+12+12+12 7,000 10,000 10,000 10,000 8,000 10,500 10,500 10,500
12+12+12+12 9,500 9,500 9,500 9,500 10,000 10,000 10,000 10,000
3 8 MG Q F 4 8 --- --- --- 3 Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 1 Zone 2 Zone 3 Zone 4 Zone 5
18+18 18+24 17,500 22,500 18,000 23,000 24+24 21,000 21,000 22,000 22,000
9+24 9,000 23,000 10,000 23,000
9+18 9,500 18,500 10,500 19,000 9+9+18 9+9+24 9,000 9,000 22,500 9,500 9,500 23,500
9+12+12 9,500 12,500 12,500 10,000 10,000 13,000 9+12+18 9,000 12,000 18,000 9,500 9,500 19,000 9+12+24 9,000 12,000 21,500 9,500 12,500 22,000 9+18+18 9,000 18,000 18,000 9,500 18,500 18,500 9+18+24 8,500 15,500 21,000 9,000 16,000 21,500
9+24+24 8,000 20,000 20,000 8,500 21,000 21,000 12+12+12 12,000 12,000 12,000 13,000 13,000 13,000 12+12+18 12,000 12,000 17,000 12,500 12,500 18,000 12+12+24 11,000 11,000 22,000 11,500 11,500 23,000 12+18+18 11,000 16,500 16,500 11,500 17,000 17,000 12+18+24 10,500 15,500 21,500 11,000 16,000 22,000 12+24+24 10,000 20,000 20,000 11,000 20,500 20,500 18+18+18 16,000 16,000 16,000 16,500 16,500 16,500 18+18+24 15,000 15,000 20,000 15,500 15,500 21,000
9+9+9+9 9+9+9+12 9,000 9,000 9,000 12,000 9,500 9,500 9,500 12,500 9+9+9+18 9,000 9,000 9,000 17,000 9,500 9,500 9,500 17,500 9+9+9+24 8,500 8,500 8,500 20,500 9,000 9,000 9,000 21,000
9+9+12+12 9,000 9,000 12,000 12,000 9,500 9,500 13,000 13,000 9+9+12+18 9,000 9,000 11,000 17,000 9,500 9,500 11,500 17,500 9+9+12+24 8,500 8,500 10,500 20,500 9,000 9,000 11,100 21,000 9+9+18+18 8,500 8,500 15,500 15,500 9,000 9,000 16,000 16,000
9+9+18+24 8,000 8,000 14,500 20,000 8,500 8,500 15,000 20,000 9+12+12+12 9,000 12,000 12,000 12,000 9,500 12,500 12,500 12,500 9+12+12+18 9,000 11,000 11,000 16,000 9,500 11,500 11,500 16,500 9+12+12+24 8,500 10,000 10,000 20,000 9,000 10,500 10,500 20,500 9+12+18+18 8,500 10,000 15,000 15,000 9,000 10,500 15,500 15,500 9+18+18+18 8,000 14,000 14,000 14,000 8,500 14,500 14,500 14,500
12+12+12+12 12,000 12,000 12,000 12,000 12,500 12,500 12,500 12,500 12+12+12+18 11,000 11,000 11,000 16,000 11,500 11,500 11,500 16,500 12+12+12+24 10,000 10,000 10,000 20,000 10,500 10,500 10,500 20,500 12+12+18+18 10,000 10,000 15,000 15,000 10,500 10,500 15,500 15,500
9+9+9+9+9 9+9+9+9+12 9,000 9,000 9,000 9,000 12,000 9,500 9,500 9,500 9,500 13,000 9+9+9+9+18 8,500 8,500 8,500 8,500 16,000 9,000 9,000 9,000 9,000 16,500 9+9+9+9+24 7,750 7,750 7,750 7,750 19,500 8,000 8,000 8,000 8,000 20,000
9+9+9+12+12 9,000 9,000 9,000 11,500 11,500 9,500 9,500 9,500 12,000 12,000 9+9+9+12+18 8,000 8,000 8,000 11,000 16,000 8,500 8,500 8,500 11,500 16,500
9+9+9+18+18 8,000 8,000 8,000 11,000 16,000 8,500 8,500 8,500 16,500 16,500 9+9+12+12+12 8,500 8,500 11,000 11,000 11,000 9,000 9,000 12,000 12,000 12,000 9+9+12+12+18 8,500 8,500 10,000 10,000 15,000 8,500 8,500 10,500 10,500 15,500
9+12+12+12+12 8,000 11,000 11,000 11,000 11,000 8,500 11,500 11,500 11,500 11,500 9+12+12+12+18 7,500 10,000 10,000 10,000 14,500 8,000 10,500 10,500 10,500 15,000
12+12+12+12+12 10,500 10,500 10,500 10,500 10,500 11,000 11,000 11,000 11,000 11,000
2 --- Z one
2 --- Z one
3 --- Z one
2 --- Z one
3 --- Z one
4 --- Z one
2 --- Z one
3 --- Z one
4 --- Z one
5 --- Z one
9,000 9,000 9,500 9,500
9,500 9,500 10,000 10,000
9,000 9,000 9,000 9,500 9,500 9,500
9,500 17,500 10,000 18,000
9,333 9,333 9,333 9,667 9,667 9,667
9,000 9,000 9,000 9,000 9,500 9,500 9,500 9,500
18,500 18,500 19,000 19,000
9,500 9,500 18,000 10,000 10,000 19,000
9,250 9,250 9,250 9,250 9,500 9,500 9,500 9,500
9,000 9,000 9,000 9,000 9,000 9,500 9,500 9,500 9,500 9,500
20
Page 21
UNIT MOUNTING (INDOOR)
Mounting Bracket – The fan coil units are furnished with
mounting brackets or dedicated mounting holes to hang the unit. Support – Adequate support must be provided to handle the
weight of all fan coils. Refer to the Physical Data section for weights, and the base unit dimensional drawings.
Unit Leveling – For reliable operation, units should be level in all planes.
Clearances – Minimum clearance as shown in Fig. 14--15. Unit location – Select a location which provides the best air
circulation for the room. These units should be positioned as high as possible to provide adequate air circulation. The unit return and discharge should not be obstructed by furniture, curtains, or anything which may cause the unit to short cycle or air to recycle.
UNIT MOUNTING (OUTDOOR)
Support – A location which can bear the weight of outdoor unit.
Refer to the Physical Data section for weights, and base dimensional drawings.
Unit Leveling – For reliable operation, units should be level in all planes.
Clearances – Minimum clearances, as shown in Fig. 15, must be provided for airflow. The outdoor units are designed for free--blow applications. Air inlets and outlets should not be restricted.
Unit location – A location which is convenient to installation and not exposed to strong wind.
SYSTEM OPERATING CONDITIONS
Cooling operating range:
OPERATING RANGE (Min / Max ° F (° C))
Cooling Heating
Outdoor DB ---4 / 122 ( ---20 / 50) ---4 / 86 ( ---20 / 30)
Indoor DB 63 / 90 (17 / 32) 32 / 86 (0 / 30)
Indoor WB 59 / 84 (15 / 29)
Heating operating range:
NON---OPERATING TEMPERATURE RANGE (Min / Max ° F (° C))
Indoor/Outdoor DB 32 / 86 (0 / 30)
METERING DEVICES
The outdoor unit has multiple electronic expansion valves to manage the refrigerant flow to the different indoor fan coils connected to that unit.
REFRIGERANT LINES
General Guidelines:
1. The outdoor units are shipped with a full charge of R--410A refrigerant. All charges, line sizing, and capacities are based on runs of 25 ft. (7.6 m). For runs over 25 ft. (7.6m), consult long--line section on this page for proper charge adjustments.
2. Refrige rant lines should not be buried in the ground. If it is necessary to bury the lines, do not bury more than 36 inches (914 mm). Provide a minimum of 6 inch (152 mm) vertic al rise to the servi ce valves to prevent refrigerant migration.
3. Both lines must be insulated. Use a minimum of ½-- i n c h (12.7 mm) thick insulation. Closed --cell insulation is recommended in all long--line applications.
4. Special consideration should be given to isolating the interconnecting tubing from the building structure. Isolate the tubing so vibration or noise does not transmit into the structure.
Long Line Applications:
S No change in line sizing is required.
TOTAL
MAX.
PIPING
LENGTH
FT. (m.)
UNIT SIZE
18 2
27 3
36 4
48 5
ZONES
CHARGE
oz. (kg.)
67.02 (1.9)
98.76 (2.8)
126.98 (3.6)
162.26 (4.6)
ADDITIONAL
CHARGE
REQUIRED
AFTER FT. (m)
49 (15) 0.16 (15) 98 (30)
74 (22.5) 0.16 (15) 147 (45)
98 (30) 0.16 (15) 196 (60)
123 (37.5) 0.16 (15) 245 (75)
ADDITIONAL
CHARGE
oz./ft. (g/m)
NOTE: Additional Refrigerant Calculation Sum Total Liquid Pipe ft. (m) Additional Charge Required After ft. (m.) x Additional Charge oz./ft. (g/m) 0.16 (15).
NOTE: If the calculation results in a negative number, no additional refrigerant is required.
DRAIN CONNECTIONS
Install drains that meet the local sanitation codes. If adequate gravity drainage cannot be provided, a field installed condensate pump accessory should be used. Refer to the condensate pump Installation Instructions for detailed specifications.
NOTE: Condensate Pump is built--in on Ducted and Cassette indoor units.
NOTE: The high wall fan coils have an internal condensate trap therefore an external trap is not required.
WIRING
The main power is supplied to the outdoor unit. Four field supplied connecting cables from the outdoor unit to each of the indoor units are: L1, L2, Ground, and S for communication between the outdoor unit and each indoor unit.
CONTROL SYSTEM
The 38MGQ/40MAQ/40MB unit is equipped with a microproce ssor control to operate the system and give optimum levels of comfort and operating effi ciency. There are microproc essor boards and therm i stors located in both the indoor and outdoor units. The therm i stors monitor the syste m operat ion and control the operating mode. To change the settings or the modes of operat i on, use the factory supplied wirel ess remote control.
The 38MGQ/40MAQ/40MB unit has the following operating modes:
S Fan Only S Auto S Heating (on Heat Pumps only) S Cooling S Dehumidification (Dry)
FAN ONLY -- In Fan Only mode, the system filters and circulates the room air without changing the room air temperature.
AUTO -- In Auto mode, the system automatically selects one of the following operating modes: COOLING, HEATING or FA N ONLY based on the difference between the room temperature and the set point temperature.
HEATING -- I n t h e HEATING mode, the system heats and filters room air.
COOLING -- W h e n i n COOLING mode, the fan runs all the time and the system cools, dries and filters room air.
DEHUMIDIFICATION (DRY) -- In Dehumidification (Dry) mode, the system dries, filters and slightly cools room temperature. This mode does not take place of a dehumidifier.
In addition to the above modes that are selected by using the remote control, the unit can run in emergency mode by using the manual button. This mode is used when the remote is misplaced or the batteries in the remote have died. In this mode, the unit runs in AUTO mode with a predetermined set point (76_F/24.4_C).
21
Page 22
WIRELESS REMOTE CONTROL
1. A wireless remote control is supplied for system operation.
2. Each battery--operated wireless remote control can be used to control more than one unit.
3. The wireless remote control has a range of 25 ft. (7.6 m).
Fig. 16 – Wireless Remote Control
WIRED REMOTE CONTROL (STANDARD ON DUCTED UNITS)
1. Optional wired remote controller used for system operation of all high-- wall, cassette and floor console units.
2. Kit includes a wired remote controller and a connecting cable.
3. Connect with wire terminal between remote controller and indoor unit.
4. Display in _For_C and temperature increments every 1_F or every 1_C.
Fig. 17 – Wired Remote Co ntrol
SEQUENCE OF OPERATION
NOTE: Simultaneous heating and cooling is not allowed.
At start--up, the first indoor unit to call for operation (heating or cooling) will control from the preset position, the mode of operation for the rest of the indoor units connected to the same outdoor unit. If the other units conflict in mode with the first unit an error message appears on those units.
When a unit is set to COOL, HEAT or the DRY mode, the electronic expansion valve is first initialized (closed) and then is opened to a preset position.
Superheat heating for each fan coil (the ones that are energized) is monitored and the position of the electronic expansion valve is adjusted to ensure that each fan coil gets the appropriate amount of refrigerant to maintain the requir ed superhe at. After the set point is satisfied and the fan coil shuts off, the electronic expansion valve stays open for a spec i fied time to ensure the system pressur es equali ze.
When the system is set for COOL, HEAT or DRY mode, the compressor speed is varied by comparing the indoor air temperature with the set point and continuously adjusting the compressor speed (to keep the compressor running as long as possible) in an effort to maintain the greatest comfort possible.
The indoor fan can run in either the MANUAL or AUTO mode. When the fan is runs in the AUTO mode, the speed is determined by comparing the room temperature to the set point.
In the COOLING mode, when the set point is satisfied, the fan continues to run. In HEATING mode, when the set point is satisfied, the fan speed is reduced and then runs continuously until the coil temperature drops to a point cold air is blown on the occupants in the space, at which time the indoor fan is de--energized.
When the unit goes through the defrost cycle, the indoor fans are de--energized and the refrigerant is circulated through all the fan coils (even if they were off or on standby before the defrost cycle) to maximize the heat transfer surface area available for defrost operation.
22
Page 23
AIR FLOW DATA
HIGH WALL
SYSTEM SIZE 9 12 18 24
Turb o 380 380 680 870
Indoor (CFM)
SYSTEM SIZE 9 12 18
Indoor (CFM)
SYSTEM SIZE 9 12 18 24
Indoor (CFM)
SYSTEM SIZE 9 12
Indoor (CFM)
SYSTEM SIZE 18 27 36 48
Outdoor (CFM) 1390 2130 2130 3500
High 360 360 650 780
Medium 290 300 450 620
Low 210 210 310 520
CASSETTE
High 380 400 420
Medium 320 340 350
Low 260 280 290
DUCTED
High 380 380 480 810
Medium 340 340 440 650
Low 290 290 400 590
FLOOR CONSOLE
High 280 280
Medium 250 250
Low 220 220
OUTDOOR MULTI---ZONE
SOUND PRESSURE
HIGH WALL
SYSTEM SIZE 9 12 18 24
Cooling operation Indoor Sound Pressure dBa (L/M/H) 42/34/27 42/34/27 46.5/40/33 50/45/39 Heating operation Indoor Sound Pressure dBa (L/M/H) 40/33/26 41/34/27 45/39/32 47/44/38
CASSETTE
SYSTEM SIZE 9 12 18
Cooling operation Indoor Sound Pressure dBa (L/M/H) 34/39/44 36/39/42 46/48/50 Heating operation Indoor Sound Pressure dBa (L/M/H) 31/37/42 36/39/42 46/47/49
DUCTED
SYSTEM SIZE 9 12 18 24
Cooling operation Indoor Sound Pressure dBa (L/M/H) 30/33/36 30/34/38 34/37/38 43/45/48 Heating operation Indoor Sound Pressure dBa (L/M/H) 30/33/36 30/34/38 34/37/39 44/45/48
FLOOR CONSOLE
SYSTEM SIZE 9 12
Cooling operation Indoor Sound Pressure dBa (L/M/H) 37/38/41 34/41/45 Heating operation Indoor Sound Pressure dBa (L/M/H) 37/38/41 34/41/45
OUTDOOR MULTI---ZONE
SYSTEM SIZE 18 27 36 48
Sound pressure level dBa 60 63 63 64
23
Page 24
ELECTRICAL DATA
HIGH WALL
UNIT SIZE
9 12 0.07 0.027 20 18 0.17 0.077 58 24 0.23 0.08 60 30 0.23 0.08 60
UNIT SIZE
9 12 1.03 0.073 55 18 0.83 0.12 90 24 0.83 0.12 90 36 1.263 0.2 150 48 2.23 0.32 240
UNIT SIZE
9 12 0.146 0.061 46 18 0.146 0.061 46
SYSTEM VOLTAGE OPERATING VOLTAGE INDOOR FAN
VOLT/PHASE/HZ MAX / MIN V --- P H --- H Z FLA HP W
0.07 0.027 20
208--- 230/1/60 253 / 187 208 ---230/1/60
DUCTED SYSTEM VOLTAGE OPERATING VOLTAGE INDOOR FAN VOLT/PHASE/HZ MAX / MIN FLA HP W
1.03 0.073 55
208--- 230/1/60 253 / 187
CASSETTE
SYSTEM VOLTAGE OPERATING VOLTAGE INDOOR FAN
VOLT/PHASE/HZ MAX / MIN V --- P H --- H Z FLA HP W
0.146 0.061 46
208--- 230/1/60 253 / 187 208 ---230/1/60
FLOOR CONSOLE
UNIT SIZE
9
12 0.21 0.027 20
UNIT SIZE
18 27 8.85 3 0.16 120 19 25 36 13.4 3 0.16 120 27 40 48 13.5 3 0.11 85 29 50
SYSTEM VOLTAGE OPERATING VOLTAGE INDOOR FAN
VOLT/PHASE/HZ MAX / MIN V --- P H --- H Z FLA HP W
208--- 230/1/60 253 / 187 208 ---230/1/60
MULTI---ZONE OUTDOOR UNIT
SYSTEM VOLTAGE
VOLT/PHASE/HZ MAX / MIN RLA FLA HP W
208--- 230/1/60 253 / 187
OPERATING
VOLTAGE
COMPRESSOR OUTDOOR FAN MCA
9.7 3 0.16 50 15 20
0.21 0.027 20
MAX STATIC PRESSURE -- DUCTED
SYSTEM SIZE 9 12 18 24
Max static pressure
Pa 45 45 70 100
In.WG 0.18 0.18 0.28 0.40
MAX
FUSE/CB
AMP
24
Page 25
FAN PERFORMANCES (DUCTED UNITS)
Static pressure curve (static pressure deducted)
SIZE 0 1 2 3 4
9&12 0.02 (5) 0.04 (10) 0.08 (20) 0.12 (30) 0.16 (40) 0 ---0.18 (0 ---45)
18 0.04 (10) 0.10 (25) 0.14 (35) 0.18 (45) 0.22 (55) 0---0.28(0 ---70)
24 0.04 (10) 0.10 (25) 0.16 (40) 0.22 (55) 0.28 (70) 0---0.40 (0 --- 100)
Factory Setting
SYSTEM SIZE 9K 12K 18K 24K
High
Medium
Low
CFM 335 370 520 820
CMH 570 629 884 1394
CFM 290 320 430 620
CMH 493 544 731 1054
CFM 240 260 360 520
CMH 408 442 612 884
Static Pressure
Range In. WG (Pa)
25
Page 26
FAN PERFORMANCES DUCTED INDOOR UNIT SIZE 9K
26
Page 27
FAN PERFORMANCES DUCTED INDOOR UNIT SIZE 12K
27
Page 28
FAN PERFORMANCES DUCTED INDOOR UNIT SIZE 18K
28
Page 29
FAN PERFORMANCES DUCTED INDOOR UNIT SIZE 24K
29
Page 30
WIRING DIAGRAM
Fig. 20 – Wiring Diagrams 18k
OUTDOOR UNIT CONTROL BOARD SIZE 18
CODE PAR T N AME
CN18/CN19/CN22 Output:Pin5&6(12V) Pin1---Pin4:Pulse waveform,(0---12V) CN17 Input:Pin3~ 4 (5V) Pin2(0V),Pin1,Pin5(0--- 5V) CN7 Input:Pin1 (0 ---5V) Pin2(5V) CN1~ CN2CN5~C N6 P1~ P2 Output: Connection of the high voltage CN3~ CN4 Input:230VAC High voltage CN14 InputPin1,Pin3(0V)Pin2,Pin40~ 5V P --- 1 , P --- 2 C onnection to the earth CN20,CN23,CN25 Output: Pin1Connection of the high voltage),Pin2~ Pin3230VAC High voltage CN15 Input: Pin1,Pin3,Pin5(5V)Pin2,Pin4,Pin60~ 5V CN37 Output: Pulse(0 ---320VDC) for DC FAN CN38 Input: Pin1~Pin217VDC N --- O U T ~ L --- O U T Output: 230VAC High voltage CN21 input: Pin1~ Pin312VDC),Pin2~Pin35VDC),Pin4~ Pin30~ 5VDC),Pin5~ Pin30~ 5VDC CN39 Input: 270~ 370VDC High voltage
OUTDOOR UNIT IPM BOARD
CN4~ CN5 Output: 230VAC High voltage CN2,CN3 Connect to Reactor, (270~ 370VDC) CN6 Output: Pin1~ Pin217VDC CN1 Output: Pin1~ Pin312VDC),Pin2~ Pin35VDC),Pin4~ Pin30~5VDC),Pin5~Pin30~5VDC), CN11~ CN12 Output: 270~ 370VDC High voltage U~ V~ W Connect to compressor voltage among phases 0~ 200VAC
Output: CN1~ CN2CN5~ CN6230VAC High voltage
30
Page 31
WIRING DIAGRAMS (CONT)
Fig. 21 – Wiring Diagrams 27k
OUTDOOR UNIT CONTROL BOARD SIZE 27
CODE PAR T N AME
CN18/CN19/CN22 Output:Pin5&6(12V) Pin1---Pin4:Pulse waveform,(0---12V) CN17 Input:Pin3~ 4 (5V) Pin2(0V),Pin1,Pin5(0--- 5V) CN7 Input:Pin1 (0 ---5V) Pin2(5V) CN1~ CN2CN5~C N6 P1~ P2 Output: Connection of the high voltage CN3~ CN4 Input:230VAC High voltage CN14 InputPin1,Pin3(0V)Pin2,Pin40~ 5V P --- 1 , P --- 2 C onnection to the earth CN20,CN23,CN25 Output: Pin1Connection of the high voltage),Pin2~ Pin3230VAC High voltage CN15 Input: Pin1,Pin3,Pin5(5V)Pin2,Pin4,Pin60~ 5V CN37 Output: Pulse(0 ---320VDC) for DC FAN CN38 Input: Pin1~Pin217VDC N --- O U T ~ L --- O U T Output: 230VAC High voltage CN21 input: Pin1~ Pin312VDC),Pin2~Pin35VDC),Pin4~ Pin30~ 5VDC),Pin5~ Pin30~ 5VDC CN39 Input: 270~ 370VDC High voltage
OUTDOOR UNIT IPM BOARD
CN4~ CN5 Output: 230VAC High voltage CN2,CN3 Connect to Reactor, (270~ 370VDC) CN6 Output: Pin1~ Pin217VDC CN1 Output: Pin1~ Pin312VDC),Pin2~ Pin35VDC),Pin4~ Pin30~5VDC),Pin5~Pin30~5VDC), CN11~ CN12 Output: 270~ 370VDC High voltage U~ V~ W Connect to compressor voltage among phases 0~ 200VAC
Output: CN1~ CN2CN5~ CN6230VAC High voltage
31
Page 32
WIRING DIAGRAMS (CONT)
Fig. 22 – Wiring Diagram 36k
OUTDOOR UNIT CONTROL BOARD SIZE 36
CODE PART N AM E
CN17/CN18/CN19/CN20/CN21 Output:Pin5&6(12V) Pin1---Pin4:Pulse waveform,(0---12V) CN8 Input:Pin3~4 (5V) Pin2(0V),Pin1,Pin5(0 --- 5V) CN33 Input:Pin1 (0---5V) Pin2(5V) CN4~ CN40CN10~CN44 Output: CN4~ CN40CN10~ CN44230VAC High voltage CN3~ CN22 Output: High voltage for 4---way control CN1~ CN2 Input:230VAC High voltage CN9 InputPin1,Pin3(0V)Pin2,Pin40~5V P --- 1 Connection to the earth CN27,CN28,CN29,CN30 Output: Pin1Connection of the high voltage),Pin2~ Pi n3230VAC High voltage CN13 Input: Pin1,Pin3,Pin5(5V)Pin2,Pin4,Pin60~5V CN12 Output: Pulse(0--- 200VAC) for DC FAN CN11 Output: Pulse(0--- 200VAC) for DC FAN CN5~ CN6 Output: 230VAC High voltage
CN7
CN4~ CN5 Output: 230VAC High voltage CN2,CN3 Connect to Reactor, (270~ 370VDC) CN6 Output: Pin1 ~Pin217VDC CN1 Output: Pin1 ~Pin312VDC),Pin2~Pin35VDC),Pin4~ Pin30~ 5VDC),Pin5~ Pin30~ 5VDC), CN11~ CN12 Output: 270~ 370VDC High voltage U~ V~W Connect to compressor voltage among phases 0~ 200VAC
input: Pin1~Pin312VDC),Pin2~ Pin3(5VDC),Pin4~ Pin30~5VDC ),Pin5~ Pin30~ 5VDC),Pin6~Pin30~ 5VDC), Pin7~ Pin30~5VDC
OUTDOOR UNIT IPM BOARD
32
Page 33
WIRING DIAGRAMS (CONT)
Fig. 23 – Wiring Diagrams 48K
OUTDOOR UNIT CONTROL BOARD SIZE 48
CODE PAR T NAME
CN1,CN3P --- 1 Power input: 230V AC CN2,CN4 Output: Power output for DRIVER BOARD (230V AC) CN5 Input: Communication Main board and IPM Board ,Pin1(5V DC ) CN6 Input: DC FAN motor1 and DC FAN motor2 control, (Pin7 5V DC) CN8,CN9 Input: Temperature sensor(5V DC) CN10 Input: Pressure test (5V DC) CN13 Input: Indoor pipe Temperature sensor,Pin1&Pin3&Pin5&Pin7&Pin9&Pin11 (5V DC) CN15,CN23,CN26, CN30,CN33 Output: PMV controlPin5(12V DC),Pin6(12V DC) CN17,CN18 Output: High voltage for 4 --- way(SV) control (230V AC) CN19,CN20 Output: High voltage for HEAT_D control (230V AC) CN13,CN16,CN21, CN29,CN37 Out put: Communication to indoor unit,Pin2 and Pin3 (230V AC ),Pin1 (S, connection to high voltage) CN24,CN25 Output: High voltage for HEAT_Y control(230V AC) CN27CN32CN34
CN28CN31CN36 CN39 Output: L2 for AC FANSV and HEAT ,High voltage (AC) P --- 5 , P --- 6 Connection to the earth
UVW Output: Pulse(0-380VDC) for COMPRESSOR CN3 CN6 ,CN8 Input: Power input for DRIVER BOARD (200-320V DC )
CN7,CN11 Output: DC FAN motor1 and DC FAN motor2 control (Pin1 310V or 380V DC) CN9 Output: Communication Main board and IPM Board Pin7(5V DC ) CN55 Output: Communication IPM Board and Main board Pin1(12V DC ) CN14CN15-- CN39, Output: High DC voltage (310V or 380V DC)
Output: Power output for AC FAN motor1 and AC FAN motor2 (230V AC)
OUTDOOR UNIT IPM BOARD
Output: Connect PFC Inductance, high DC voltage
33
Page 34
Size Range:1 1/2, 2 1/4, 3 and 4 Ton Nominal Cooling and Heating Capacity
PART1–GENERAL
1.01 System Description
A. Outdoor air--cooled split system compressor sections suitable
for on-- the--ground, rooftop, wall hung or balcony mounting. Units consist of a variable speed rotary compressor, an air--cooled coil, propeller-- type draw--through outdoor fan, reversing valve, accumulator, electronic expansion valves, multiple service valves, and controls that allows multiple indoor units to be connected to the outdoor unit. Units discharge horizontally as shown on the contract drawings. Units function as the outdoor component of an air--to--air heat pump system.
B. Units are designed to be used in a refrigeration circuit matched
to two, three, four, or five multi style heat pump fan coil units.
1.02 Agency Listings
A. Unit construction complies with ANSI/ASHRAE 15, latest
revision, and with NEC. B. Units are evaluated in accordance with UL standard 1995.
C. Units are listed in CEC directory.
D. Unit cabinet is capable of withstanding 500-hour salt spray test
per Federal Test Standard no. 141 (method 6061).
E. Air-cooled condenser coils are leak tested at 550 psig.
1.03 Delivery, Storage, And Handling
Units are shipped in one piece and are stored and handled per the manufacturer’s recommendations.
1.04 Warranty (For Inclusion By Specifying Engineer)
PART 2 – PRODUCTS
2.01 Equipment
A. General:
Factory assembled, single piece, air-cooled outdoor unit. Contained within the enclosure are the factory wiring, piping, controls, and compressor.
B. Unit Ca binet:
1. The unit cabinet is constructed of galvanized steel, bonderized and coated with baked-enamel finish on inside and outside.
2. The unit access panel is removable with the minimal screws and provides full access to the compressor, fan, and control components.
3. The outdoor compartment is isolated and has an acoustic lining to assure quiet operation.
C. Fans:
1. The outdoor fans are direct-drive propeller type, and discharge air horizontally. The fan draws air through the outdoor coil.
2. Outdoor fan motors are multi--speed, totally-enclosed, single phase motors with permanently lubricated ball bearings. The motor is protected by internal thermal overload protection.
3. The shaft has an inherent corrosion resistance.
4. Outdoor fan openings are equipped with metal/mesh PVC coated protection grille over fan.
GUIDE SPECIFICATIONS
HORIZONTAL DISCHARGE OUTDOOR UNITS
Carrier Model Number: 38MGQ
D. Compressor
1. The compressor is fully hermetic variable speed rotary type.
2. The compressor is inverter driven.
3. The compressor is equipped with an oil system, operating oil charge, and motor.
4. The motor is suitable for operation in a refrigerant and oil atmosphere.
5. The compressor assembly is installed on rubber vibration isolators.
6. The inverter and compressor are protected against over temperature and over current.
E. Outdoor Coil:
The coil is constructed of aluminum blue hydrophilic pre--coated fins mechanically bonded to seamless copper tubes, which are cleaned, dehydrated and sealed.
F. Refrigerant Components:
Refrigerant circuit components include multiple brass external liquid line service valves with service gauge connection port, multiple suction line service valves with a service gage connection port, accumulator, reversing valve, electronic expansion valves.
G. Safeties:
Operating safeties are factory selected, assembled, and tested. The minimum functions include the following:
1. Compressor discharge over temperature protection.
2. System low voltage protection.
3. Compressor overload protection.
4. Compressor over current protection.
5. IPM module protection.
H. Electrical Requirements:
1. Units shall operate on single-phase, 60 Hz power at 208/230 v.
2. The unit electrical power is a single point connection.
3. All power and control wiring must be installed per NEC and all local electrical codes.
4. Units have multiple terminal blocks to connect to multiple indoor units.
34
Page 35
PART1–GENERAL
1.01 System Description
Indoor, wall-mounted, direct expansion fan coils are matched with heat pump outdoor units.
1.02 Agency Listings
Unit is rated per AHRI Standards 210/240 and listed in the AHRI directory as a matched system.
1.03 Delivery, Storage, And Handling
Units are shipped in one piece and are stored and handled per the manufacturer’s recommendations.
1.04 Warranty (For Inclusion By Specifying Engineer)
PART 2 – PRODUCTS
2.01 Equipment
A. General:
Indoor, direct-expansion, wall-mounted fan coil. The unit is complete with cooling/heating coil, fan, fan motor, piping connectors, electrical controls, microprocessor control system, and integral temperature sensing. The unit is furnished with integral wall mounting bracket and mounting hardware.
B. Unit Ca binet:
Cabinet discharge and inlet grilles shall be attractively styled, high-impact polystyrene. The cabinet is fully insulated for improved thermal / acoustic performance.
C. Fans:
1. The fan is tangential direct-drive blower type with air intake at the top of the unit and discharge at the bottom front. An automatic, motor-driven vertical air sweep is provided standard.
2. The air sweep operation is useable selectable. The vertical sweep may be adjusted (using the remote control) and the horizontal air direction maybe be set manually.
D. Coil:
The coil is a copper tube with aluminum fins and galvanized steel tube sheets. Fins are bonded to the tubes by mechanical expansion and blue hydrophilic pre--coated for enhanced wet-- ability. A drip pan under the coil has a drain connection for a hose attachment to remove condensate. The condensate pan has an internal trap.
E. Motors:
Motors are totally enclosed, permanently lubricated ball bearing with inherent overload protection. The fan motors are 3 --speed.
F. C on trol s:
The controls consist of a microprocessor--based control system which controls space temperature, determines optimum fan speed, and runs self diagnostics. The temperature control range is 62_Fto 86_F(17_Cto30_C) in increments of 1_For1_C, and has 46_F Heating Mode (Heating Setback). The wireless remote controller can act as the temperature sensing location for room comfort.
GUIDE SPECIFICATIONS
INDOOR WALL--MOUNTED DUCTLESS UNITS
Size Range: 3/4 to 2 Ton Nominal Cooling and Heating Capacity
Carrier Model Number: 40MAQ
The unit has the following functions as a minimum:
S An automatic restart after power failure at the same
operating conditions as at failure.
S A timer function to provide a minimum 24 --hour timer
cycle for system Auto Start/Stop.
S Temperature-- sensing controls senses the return air
temperature.
S Indoor coil freeze protection. S Wireless infrared remote control to enter set points and
operating conditions.
S Automatic air sweep control to provide on or off
activation of air sweep louvers.
S Dehumidification mode provides increased latent
removal capability by modulating system operation and set point temperature.
S Fan--only operation to provide room air circulation when
no cooling is required.
S Diagnostics provide continuous checks of unit operation
and warn of possible malfunctions. Error messages appear on the unit.
S The fan speed control is user--selectable: turbo, high,
medium, low, or microprocessor controlled automatic operation during all operating modes.
S Automatic heating--to--cooling changeover in heat pump
mode. Control includes deadband to prevent rapid mode cycling between heating and cooling.
S Indoor coil high temperature protection is provided to
detect excessive indoor discharge temperature when the unit is in heat pump mode.
G. Filters:
Units have a filter track with factory-supplied cleanable filters.
H. Electrical Requirements:
The indoor fan motor operates on 208--230V. Power is supplied from the outdoor unit.
I. Operating Characteristics:
The system has a minimum SEER (Seasonal Energy Efficiency Ratio) and HSPF at AHRI conditions, as listed on the specifications table.
J. Refrigerant Lines:
All units should have refrigerant lines that can be oriented to connect from the left, right or back of unit. Both refrigerant lines need to be insulated.
K. Special Features (Field Installed):
1. Condensate Pump: The condensate pump removes condensate from the drain pan when gravity drainage cannot be used. The pump is designed for quiet operation. The pump consists of two parts: an internal reservoir/sensor assembly, and a remote sound--shielded pump assembly. A liquid level sensor in the reservoir stops the cooling operation if the liquid level in the reservoir is unacceptable.
35
Page 36
INDOOR IN--CEILING CASSETTE DUCTLESS UNITS
PART 1 -- GENERAL
1.01 System Description
Indoor, in--ceiling cassette direct--expansion fan coils are matched with heat pump outdoor unit .
1.02 Agency Listings
The unit is rated per AHRI Standards 210/240 and listed in the AHRI directory as a matched system.
1.03 Delivery, Storage, And Handling
The units are stored and handled per unit manufacturer’s recommendations.
1.04 Warranty (For Inclusion By Specifying Engineer)
PART 2 -- PRODUCTS
2.01 Equipment General:
Indoor, direct--expansion, in--ceiling cassette fan coil. The unit is complete with cooling/heating coil, fan, fan motor, piping connectors, electrical controls, microprocessor control system, and integral temperature sensing.
Unit Cabinet:
The cabinet is constructed of zinc--coated steel. Fully insulated discharge and inlet grilles is attractively styled, high--impact polystyrene. The grille has hinges and can be opened to obtain access to the cleanable filters, indoor fan motor and control box.
Fans:
The fans shall be centrifugal direct--drive blower type
S
with an air intake in the center of the unit and discharge at the perimeter. Automatic, motor--driven vertical air sweep is provided standard. Automatic motor--driven louvers are provided standard and are adjustable for 2, 3 or 4--way discharge.
S The air sweep operation is user selectable.
Coil:
The coil is a copper tube with aluminum fins and galvanized steel tube sheets. Fins are bonded to the tubes by mechanical expansion and blue hydrophilic pre-- coated for enhanced wet--ability. A drip pan under the coil has a factory installed condensate pump and a drain connection for hose attachment to remove condensate.
Motors:
Motors are open drip--proof, permanently lubricated ball bearing with inherent overload protection. Fan motors are 4--speed.
Controls:
Controls consist of a microprocessor-- based control system which controls space temperature, determines optimum fan speed, and runs self diagnostics. The temperature control range is 62_Fto 86_F(17_Cto30_C) in increments of 1_For1_C, and has a 46_F Heating Mode (Heating Setback). The wireless remote controller, has the ability to act as the temperature sensing location for room comfort.
GUIDE SPECIFICATIONS
Size Range: 3/4 to 1 1/2 Ton Nominal Cooling and Heating Capacity
Carrier Model Number: 40MB*C
The unit has the following functions as a minimum:
S An automatic restart after power failures at the same
operating conditions as at the failure.
S A timer function which provides a minimum 24-- hour
timer cycle for system Auto Start/Stop.
S Temperature-- sensing controls that sense return air
temperature.
S Indoor coil freeze protection. S Wireless infrared remote control to enter set points and
operating conditions.
S Automatic air sweep control to provide on or off
activation of air sweep louvers.
S Dehumidification mode provides increased latent
removal capability by modulating system operation and set point temperature.
S Fan--only operation to provide room air circulation when
no cooling is required.
S Diagnostics that provides continuous checks of unit
operation and warn of possible malfunctions. Error messages appear on the unit.
S Fan speed control is user--selectable: high, medium, low,
or microprocessor controlled automatic operation during all operating modes.
S Automatic heating--to--cooling changeover in the heat
pump mode. Control includes deadband to prevent rapid mode cycling between heating and cooling.
S Indoor coil high temperature protection is provided to
detect excessive indoor discharge temperature when the unit is in the heat pump mode.
Filters:
Unit has a filter track with factory--supplied cleanable filters.
Electrical
The indoor fan motor operates on 208--230V. Power is supplied from the outdoor unit.
Operating
The system has a minimum SEER (Seasonal Energy Efficiency Ratio) and HSPF at AHRI conditions, as listed on the specifications table.
Refrigerant
All units should have refrigerant lines that can be oriented to connect from the left, right or back of unit. Both refrigerant lines need to be insulated.
Requirements:
Characteristics:
Lines:
36
Page 37
PART 1 -- GENERAL
1.01 System Description
Indoor, ceiling--mounted, ducted style direct--expansion fan coils are matched with a heat pump outdoor unit.
1.02 Agency Listings
Unit are rated per AHRI Standards 210/240 and listed in the AHRI directory as a matched system.
1.03 Delivery, Storage, And Handling
Units are stored and handled per unit the manufacturer’s recommendations.
1.04 Warranty (For Inclusion By Specifying Engineer)
PART 2 -- PRODUCTS
2.01 Equipment General:
A.
Indoor, direct--expansion, ceiling--mounted fan coil. The unit is complete with a cooling/heating coil, fan, fan motor, piping connectors, electrical controls, microprocessor control system, and integral temperature sensing.
B, Unit Cabinet:
Unit cabinet is constructed of galvanized steel. Cabinet is fully insulated for improved thermal and acoustic performance.
C. Fans:
Fans are the tangential direct--drive blower type with an air intake at the rear or bottom of the unit and discharge at the front.
D. Coil:
The coil is a copper tube with aluminum fins and galvanized steel tube sheets. Fins are bonded to the tubes by mechanical expansion and blue hydrophilic pre-- coated for enhanced wet--ability. A drip pan under the coil has a factory installed condensate pump and drain connection for hose attachment to remove condensate.
E. Motors:
The motors are open drip--proof, permanently lubricated ball bearing with inherent overload protection. Fan motors are 3--speed.
F. Controls:
Controls consist of a microprocessor--based control system which the control space temperature, determines the optimum fan speed, and runs self diagnostics. The temperature control range is from 62_Fto86_F(17_Cto30_C) in increments of 1_For1_C, and has 46_F Heating Mode (Heating Setback). The wireless remote controller can act as the temperature sensing location for room comfort.
GUIDE SPECIFICATIONS
INDOOR DUCTED STYLE DUCTLESS UNITS
Size Range: 3/4 to 2 Ton Nominal Cooling and Heating Capacity
Carrier Model Number: 40MB*D
The unit shall have the following functions as a minimum:
1. An automatic restart after power failure at the same operating conditions as at failure.
2. A timer function that provides a minimum 24 --hour timer cycle for system Auto Start/Stop.
3. Temperature--sensing controls that senses the return air temperature.
4. Indoor coil freeze protection.
5. Wireless infrared remote control to enter set points and operating conditions.
6. De--humidification mode that provides increased latent removal capability by modulating the system operation and set point temperature.
7. Fan--only operation to provide room air circulation when no cooling is required.
8. Diagnostics provide continuous checks of unit operation and warns of possible malfunctions. Error messages appear on the unit.
9. The fan speed control is user--selectable: high, medium, low, or microprocessor controlled automatic operation during all operating modes.
10. Automatic heating--to--cooling changeover in the heat pump mode. The control includes deadband to prevent rapid mode cycling between heating and cooling.
11. Indoor coil high temperature protection is provided to detect excessive indoor discharge temperature when the unit is in heat pump mode.
G. Electrical Requirements:
Indoor fan motor to operate on 208-- 230V. Power is supplied from the outdoor unit.
H. Operating Characteristics:
The system has a minimum SEER (Seasonal Energy Efficiency Ratio) and HSPF at AHRI conditions, as listed on the specifications table.
I. Refrigerant Lines:
All units have refrigerant lines that can be oriented to connect from the side of the unit. Both refrigerant lines need to be insulated.
37
Page 38
PART 1 -- GENERAL
1.01 System Description
Indoor, wall--mounted, direct--expansion fan coils are matched with a heat pump outdoor unit.
1.02 Agency Listings
Unit is rated per AHRI Standards 210/240 and listed in the AHRI directory as a matched system.
1.03 Delivery, Storage, And Handling
Units are stored and handled per unit the manufacturer’s recommendations.
1.04 Warranty (For Inclusion By Specifying Engineer)
PART 2 -- PRODUCTS
2.01 Equipment
A. General:
Indoor, direct--expansion, floor--mounted fan coil. Unit is complete with cooling/heating coil, fan, fan motor, piping connectors, electrical controls, microprocessor control system, and integral temperature sensing. Unit is furnished with integral mounting bracket and mounting hardware.
B. Unit Cabinet:
Cabinet discharge and inlet grilles is attractively styled, high--impact polystyrene. The cabinet is fully insulated for improved thermal and acoustic performance.
CFans:
The fan is a tangential direct--drive blower type with an air intake in the center of the unit and a discharge at the top and bottom front. Automat ic, motor--driven vertica l air swee p is provided standard.
Air sweep operation is user selectable. The vertical sweep may be adjusted (using the remote control) and the horizontal air direction may be set manually.
D. Coil:
Coil are copper tube with aluminum fins and galvanized steel tube sheets. Fins are bonded to the tubes by mechanical expansion and blue hydrophilic pre--coated for enhanced wet-- ability. A drip pan under the coil has a drain connection for hose attachment to remove condensate. The condensate pan has a internal trap.
E. Motors:
The motors are open drip--proof, permanently lubricated ball bearing with inherent overload protection. The fan motors are 3--speed.
F Controls:
Controls consists of a microprocessor--based control system which control the space temperature, determine optimum fan speed, and run self diagnostics. The temperature control range is from 62_Fto 86_F(17_Cto30_C) in increments of 1_For1_C, and have 46_F Heating Mode (Heating Setback). The wireless remote controller has the ability to act as the temperature sensing location for room comfort.
GUIDE SPECIFICATIONS
INDOOR FLOOR CONSOLE DUCTLESS UNITS
Size Range: 3/4 to 1 Ton Nominal Cooling and Heating Capacity
Carrier Model Number: 40MB*F
The unit shall have the following functions as a minimum:
1. An automatic restart after a power failure at the same operating conditions as at failure.
2. A timer function to provide a minimum 24--hour timer cycle for the system Auto Start/Stop.
3. Temperature-- sensing controls that sense the return air temperature.
4. Indoor coil freeze protection.
5. Wireless infrared remote control to enter set points and operating conditions.
6. Automatic air sweep control to provide on or off activation of the air sweep louvers.
7. De--humidification mode provides increased latent removal capability by modulating the system operation and set point temperature.
8. Fan--only operation to provide 6room air circulation when cooling is not required.
9. Diagnostics provide continuous checks of unit operation and warns of possible malfunctions. Error messages are displayed at the unit.
10. Fan speed control is user--selectable: high, medium, low, or microprocessor controlled automatic operation during all operating modes.
11. Automatic heating--to--cooling changeover in heat pump mode. Control includes dead band to prevent rapid mode cycling between heating and cooling.
12. The indoor coil high temperature protection is provided to detect excessive indoor discharge temperature when the unit is in heat pump mode.
G. Filters: The unit has a filter track with factory--supplied cleanable filters.
H. Electrical Requirements: The indoor fan motor operates on 208-- 230V as specified. Power is supplied from the outdoor unit. I. Operating Characteristics: The system has a minimum SEER (Seasonal Energy Efficiency Ratio) and HSPF at AHRI conditions, as listed on the specifications table.
J. Refrigerant Lines: All units has refrigerant lines that can be oriented to connect from the left, right or back of unit. Both refrigerant lines need to be insulated.
K. Special Features (Field Installed): Condensate Pump: The condensate pump removes condensate
from the drain pan when gravity drainage cannot be used. The pump is designed for quiet operation. The pump consists of two parts: an internal reservoir/sensor assembly, and a remote sound--shielded pump assembly. A liquid level sensor in the reservoir stops the cooling operation if the liquid level in the reservoir is unacceptable.
Copyright 2016 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Manufacturer r eserves the right to change, at any ti me, specifications and designs without notice and without obligations.
Edition Date: 01/16
38