NEVER enter an enclosed fan cabinet or reach into a unit
while the fan is running.
LOCK OPEN AND TAG the fan motor power disconnect
switch before working on a fan. Take fuses with you and
note removal on tag. Electric shock can cause personal
injury or death.
LOCK OPEN AND TAG the electric heat coil power disconnect switch before working on or near heaters.
WARNING
CHECK the assembly and component weights to be sure
that the rigging equipment can handle them safely. Note
also, the centers of gravity and any specific rigging
instructions.
CHECK for adequate ventilation so that fumes will not
migrate through ductwork to occupied spaces when welding or cutting inside air-handling unit cabinet or plenum.
WHEN STEAM CLEANING COILS be sure that the area
is clear of personnel.
DO NOT attempt to handle access covers and removable
panels on outdoor units when winds are strong or gusting
until you have sufficient help to control them. Make sure
panels are properly secured while repairs are being made to
a unit.
DO NOT remove access panel fasteners until fan is completely stopped. Pressure developed by a moving fan can
cause excessive force against the panel which can injure
personnel.
DO NOT work on dampers until their operators are
disconnected.
BE SURE that fans are properly grounded before working
on them.
SAFETY CONSIDERATIONS
Air-handling equipment is designed to provide safe and
reliable service when operated within design specifications. To
avoid injury to personnel and damage to equipment or property
when operating this equipment, use good judgment and follow
safe practices as outlined below.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53390016-01Printed in U.S.A.Form 39L-7SIPg 1816 3-14Replaces: 39L-6SI
WARNING
39LA
39LB
39LC
39LD
39LF
39LG
39LH
HORIZONTAL DRAW-THRU
VERTICAL DRAW-THRU
Fig. 1 — Unit Identification
a39-4440
CAUTION
DO NOT USE TORCH to remove any component. System
contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and goggles and proceed as follows:
a. Shut off electrical power to unit.
b. Recover refrigerant to relieve all pressure from sys-
tem using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen
and the work area should be well ventilated. Refrigerant in contact with an open flame produces toxic
gases.
d. Cut component connection tubing with tubing cutter
and remove component from unit. Use a pan to catch
any oil that may come out of the lines and as a gage
for how much oil to add to the system.
e. Carefully unsweat remaining tubing stubs when nec-
essary. Oil can ignite when exposed to torch flame.
Failure to follow these procedures may result in personal
injury or death.
CAUTION
DO NOT re-use compressor oil or any oil that has been
exposed to the atmosphere. Dispose of oil per local codes
and regulations. DO NOT leave refrigerant system open to
air any longer than the actual time required to service the
equipment. Seal circuits being serviced and charge with
dry nitrogen to prevent oil contamination when timely
repairs cannot be completed. Failure to follow these procedures may result in damage to equipment.
SECURE drive sheaves with a rope or strap before working on a fan to ensure that rotor cannot free-wheel.
DO NOT restore power to unit until all temporary walkways inside components have been removed.
NEVER pressurize equipment in excess of specified test
pressures.
PROTECT adjacent flammable material when welding or
flame cutting. Use sheet metal or asbestos cloth to contain
sparks. Have a fire extinguisher at hand and ready for
immediate use.
IMPORTANT: The installation of air-handling units and all
associated components, parts, and accessories which make
up the installation and subsequent maintenance shall be in
accordance with the regulations of ALL authorities having
jurisdiction and MUST conform to all applicable codes. It
is the responsibility of the installing contractor to determine
and comply with ALL applicable codes and regulations.
Field-supplied motors should be Underwriters Laboratories
(UL) or Canadian Standards Association (CSA) approved.
Field wiring must comply with National Electrical Code
(NEC) and all local requirements.
INTRODUCTION
Unit Identification —
the 18-digit part number listed on the serial plate. The part
number describes all component, coil, motor, drive, and control
selections. See Fig. 1-9 for unit identification.
The 39L units are identified by
2
39LC03
Fig. 2 — 39L Model Number Nomenclature
a39-4441
28N
28N – Coil Model Number
Coil Type
A – Chilled Water
Coil Orientation
S – Slant
V – Vertical
F – Full
A S 4
Rows
4
6
8
12
12
16
20
22
26
32
Tubes in Face
24
30
36
38
Q
Circuiting
Q – Quarter
H – Half
D – Double
Fin Material
Fins Per Inch
Casing Material
A – AL 8 GALV.
B
C – AL 14 GALV.
G – CU 8 ST. STL.
H
J – CU 14 ST. STL.
– AL 11 GALV.
– CU 11 ST. STL.
AB
Tube Size (Copper)
A – 0.016 Std. H-Pin
B – 0.025 Std. H-Pin
066
Nominal Length
Between Tube
Sheets (cm)
166
096
136
066
086
116
X
– Non-ferrousX
R
Hand
– Right Hand
– Left Hand
R
L
Fig. 3 — Chilled Water Coil Model Number Nomenclature
a39-4442
HB
-
A
A
CA
C
AHK
1
39L – 39L
Air Handler
Model
A
F
B
G
C
H
D
Unit Size
03
06
08
10
12
15
18
21
25
Draw-Thru Options
Special Order
Insulation/Suspension Package/Hand Side
N/A
Fan Discharge – Motor Frequency
Fan Speed
Motor HP – Type – Voltage
Base Unit Coil Description
Base Unit Coil Coil Type
and Arrangement
Preheat Coil
3
28N
28N – Coil Model Number
Coil Type
B – Hot Water
Coil Orientation
V – Vertical
F – Full
BV1
Rows
1
2
16
12
16
20
26
Tubes in Face
30
36
H
Circuiting
H
– Half
Fin Material
Fins Per Inch
Casing Material
A – AL 8 GALV.
B
C – AL 14 GALV.
G – CU 8 ST. STL.
H
J – CU 14 ST. STL.
– AL 11 GALV.
– CU 11 ST. STL.
AA
Tube Size (Copper)
A – 0.016 Std. H-Pin
B – 0.025 Std. H-Pin
086
Nominal Length
Between Tube
Sheets (cm)
166
096
136
066
086
116
X
– Non-ferrousX
L
Hand
– Right Hand
– Left Hand
R
L
Fig. 4 — Hot Water Coil Model Number Nomenclature
a39-4443
28N
28N – Coil Model Number
Coil Type
E – Direct Expansion
Coil Orientation
V – Vertical
B
– Face Split Half Circuit
EV4
Rows
4
6
16
12
16
20
26
Tubes in Face
30
36
H
Circuiting
A
– Face Split Quarter Circuit
Fin Material
Fins Per Inch
Casing Material
A – AL 8 GALV.
B
C – AL 14 GALV.
G – CU 8 ST. STL.
H
J – CU 14 ST. STL.
– AL 11 GALV.
– CU 11 ST. STL.
AA
Tube Size (Copper)
A – 0.016 Std. H-Pin
B – 0.025 Std. H-Pin
086
Nominal Length
Between Tube
Sheets (cm)
166
096
136
066
086
116
Z
– Standard (varies with coil)Z
L
Hand
– Right Hand
– Left Hand
R
L
S – Vertical
8
22
243238
C
– Face Split Full Circuit
D
– Double Circuit
E
– Row Split Quarter Circuit
F
– Row Split Half Circuit
G
– Row Split Full Circuit
Fig. 5 — Direct Expansion Coil Model Number Nomenclature
a39-4444
4
28L
28L – Coil Model Number
Coil Type
Z – Steam Distributing Tube (1 in. OD)
Coil Position
Z24
Rows
1
06
04
06
08
10
Tubes in Face
12
F
Circuiting
F
– Non-Freeze Full Circuit
D 3
Tub e Size (Copper)
3 – 1 in. OD x 0.030 Wall
086
Nominal Length
Between Tube
Sheets (cm)
166
096
136
066
086
116
--
[Blank]
2
14
Fin Material
Fins Per Inch
Casing Material
C – AL 6 GALV.
DE – AL 9 GALV.
– AL 12 GALV.
--
[Blank]
Fig. 6 — Steam Distributing Tube Model Number Nomenclature
a39-4445
39L
28L – Drive Package Model Number
Drive Type
V – Variable Speed
Fan Type
K212
Unit Size
Large Face Area (sq. ft.)
10 B A 1250
Position 12 is 0 if rpm is 3 digits
1
Motor Horsepower
– Constant SpeedK
– Forward Curve without VFD
2 – Forward Curve with VFD
03
06
08
10
12
15
18
21
25
01
02
03
04
05
06
07
08
09
10
11
12
13
– ½ hp
– ¾ hp
– 1 hp
– 1 ½ hp
– 2 hp
– 3 hp
– 5 hp
– 7 ½ hp
– 10 hp
– 15 hp
– 20 hp
– 25 hp
– 30 hp
1. Check items received against packing list. Notify Carrier
of any discrepancy.
2. Refer to Fig. 10 for service area requirements.
3. To transfer unit from truck to storage site, refer to rigging
details in Fig. 11 and section on unit rigging for proper
handling. See Tables 1 and 2 for section and component
weights.
CAUTION
If a fork lift truck is used, lift only from heavy end of skid.
Minimum recommended fork length is 48 inches.
4. Do not stack unit components or accessories during storage. Stacking can cause damage or deformation.
5. If unit is to be stored for more than 2 weeks prior to installation, observe the following precautions:
a. Choose a dry storage site that is reasonably level
and sturdy to prevent undue stress or permanent
damage to the unit structure or components. Do not
store unit on vibrating surface. Damage to stationary bearings can occur. Set unit off ground if in
heavy rain area.
b. Remove all fasteners and other small parts from
jobsite to minimize theft. Tag and store parts in a
safe place until needed.
c. Cover entire unit with a tarp or plastic coverall.
Extend cover under unit if stored on ground.
Secure cover with adequate tiedowns or store
indoors. Be sure all coil connections have protective shipping caps.
d. Monthly — Remove tarp from unit, enter fan
section through access door or through fan inlet,
and rotate fan and motor slowly by hand to redistribute the bearing grease and to prevent bearing
corrosion.
Rigging (Fig. 11) — All 39L units can be rigged by
means of the lifting brackets on bottom of unit.
Units are shipped fully assembled. Do not remove shipping
skids or protective covering until unit is ready for final placement. Use slings and spreader bars as applicable to lift unit. Do
not lift unit by coil connections or headers.
Do not remove protective caps from coil piping connections
until ready to connect piping.
Do not remove protective cover or grease from fan shaft until ready to install sheave.
Lay rigid temporary protection such as plywood walkways
in unit to prevent damage to insulation or bottom panel during
installation.
Suspended Units — Figure 12 shows overhead suspen-
sion of unit using optional factory-supplied suspension
channels.
Each support channel consists of 2 pieces, the smaller of
which fits inside the larger one. This allows the channel to be
adjusted to the required length for installation.
Channels are shipped on top of the unit. The 2 sections of
each channel are shipped one inside the other, and are held in
place during shipping by the panel screws in the top panel.
Hardware required for installation of suspension channels is
shipped in a package inside the fan section.
At least 2 suspension channels are shipped with each fan
and coil unit. One or more extra channels will be supplied
depending on the number of accessories ordered. Be sure to
install all the suspension channels shipped with a unit. Refer to
39L Isolator Mounting (Suspended Unit) certified drawing for
details.
To install suspension channels:
1. Remove panel screws to free suspension channels for installation. Replace screws in top panel.
2. Adjust channel to required length by sliding one channel
section inside the other. The channel must extend at least
9 in. but not more than 12 in. beyond the edge of the unit.
Set length of channel by installing factory-supplied bolts
through the overlapping channel sections.
3. Mount unit to suspension channel using factory-supplied
nuts and bolts through
ing bracket.
4. Install field-supplied suspension rods through
ameter holes provided at outer edges of channel. Be sure
hanger rods are securely fastened in place.
7
/16-in. diameter holes in unit lift-
9
/16-in. di-
Service Clearance — Provide adequate space for unit
service access (fan shaft and coil removal, filter removal, motor access, damper linkage access, etc.) as shown in Fig. 10.
Condensate Drain — To prevent excessive build-up of
condensate in drain pan, adequate trap clearance must be provided beneath the unit. See Installation, Condensate Drain section on page 16 for additional details.
lators per certified drawings, and in accordance with the job
specifications and the instructions of the vibration isolator
manufacturer. The coil piping must be isolated or have a flexible connection to avoid coil header damage because of unit
motion. A flexible connection should be installed at the fan discharge.
Fig. 12 and 13 show isolation location for overhead suspen-
COOLING COILS
Chilled Water
(4, 6 Row) Large Face Area
Face Area (sq ft)3.635.907.909.5411.1814.9117.7121.625.0
Number of Tubes/Face162024242432383844
Finned Tube Length (in.)26.134.037.945.853.753.753.765.565.5
Chilled Water
(4, 6, 8 Row) Small Face Area
Face Area (sq ft)2.724.726.587.959.3212.1213.9817.120.5
Number of Tubes/Face121620202026303036
Finned Tube Length (in.)26.134.037.945.853.753.753.765.565.5
1
DX
/
-in. OD Tube
2
(4, 6 Row) Large Face Area
Face Area (sq ft)3.635.907.909.5411.1814.9117.7121.625.0
Finned Tube Length (in.)26.134.037.945.853.753.753.765.565.5
1
DX
/
-in. OD Tube
2
(4, 6, 8 Row) Small Face Area
Face Area (sq ft)2.724.726.587.959.3212.1213.9817.120.5
Finned Tube Length (in.)26.134.037.945.853.753.753.765.565.5
HEATING COILS
Hot Water
U-Bend (1, 2 Row)
Face Area (sq ft)2.724.726.587.959.3212.1213.9817.120.5
Number Tubes/Face121620202026303036
Finned Tube Length (in.)26.134.037.945.853.753.753.765.565.5
Steam 1-in. OD (1 Row)
Face Area (sq ft)2.134.186.227.538.8511.0613.2816.218.9
Number Tubes/Face4688 8 10121214
Finned Tube Length (in.)25.533.437.345.253.153.153.153.164.9
LEGEND
DX — Direct Expansion
FPI — Fins Per Inch
1
/
2
1
/
-in. OD Tube,
2
1
/
-in. OD Tube,
2
1
/
-in. OD Tube
2
1
/
-in. OD Tube,
2
1
/
-in. OD Tube
2
1
/
-in. OD Tube,
2
-in. OD*
1
/
2
1
/
8
5
12
/
1
9
/
2
3
/
16
5
12
/
8
1
11
3
1
/
151518
8
/
16
1
11
8
/
8
3
1
/
16
151513
3
1
/
16
1
/
7
1
/
16
202025
8
1
/
2
7
1
/
16
1815
7
1
/
16
11
1
/
16
*Coils have 14 aluminum fins per inch on copper tubes.
NOTE: See Table 1 for section weights and dimensions.
11
SPREADER
BAR
LIFTING
BRACKET
Fig. 11 — Unit Rigging Details
NOTE: Lift in one piece. Use slings and
spreader bars at each lifting bracket.
a39-4449
LIFTING BRACKET
DETAILS
7
16
/
IN. DIAM. HOLE
VIBRATION ISOLATORS
(FIELD SUPPLIED)
SUSPENSION ROD
(FIELD SUPPLIED)
SUSPENSION CHANNEL
(FACTORY-SUPPLIED OPTION)
MOUNT UNIT TO SUSPENSION CHANNELS
THROUGH
PROVIDED IN LIFTING BRACKET
7
16
/
IN. DIAM. HOLES
FACTORY-SUPPLIED BOLTS
CONNECTING SUSPENSION
CHANNEL SECTIONS
OVERHEAD SUSPENSION
Fig. 12 — Unit Support Details, Overhead Suspension
a39-4450
SPRING ISOLATOR
ISOLATION BRACKET
7
16
/
IN. DIAM. HOLE
ISOLATION DETAIL – FLOOR MOUNT
Fig. 13 — Unit Support Details, Floor Mount
a38-4451
12
INSTALLATION
T-BRACKET
LIFTING LUG
Fig. 14 — Base Rail Split — T-Bracket
a39-4453
FLANGES
FLANGES
Fig. 15 — Base Rail Split — Flanges
a39-4454
Fig. 16 — Base Rail Split — Screws
a39-4455
Base Rail Split —
coil/fan section and the accessory sections is optional. If this
option has ben selected, the 39L unit will arrive at the job site
assembled as one piece. The split allows the unit to be separated at the joint.
If the unit must be separated in the field, follow this procedure:
1. Remove the lifting lugs on the inlet side of the coil/fan
section and those on the outlet side of the accessory section to liberate the T-bracket. See Fig 14.
2. Unscrew the flanges (top and sides) around the coil/fan
section and the accessory section. See Fig. 15.
A base rail split between the primary
CAUTION
Ensure that a good seal is created between both sections
before continuing. A poor seal may result in equipment
damage.
NOTE: If the section-to-section gasket installed at the factory
is damaged while splitting the unit, obtain the required length
1
of
/8 in. x 1 1/4 in. foam gasketing locally.
1
After rejoining the split sections, fully tighten all AB
/4 in.-3/
in. screws on the flanges and the AB 1/4 in-5/8 in. screws on the
flanges. See Fig. 16.
4
AB ¼-
5
SCREWS
8
/
13
AB ¼-¾ SCREWS
Mixing Box
MXB — Mixing Box
Fig. 18 — Mixing Box Ductwork Attachment
Fig. 17 — Typical Mixing Box Actuator Mounting
DAMPER ACTUATORS — The 39L mixing boxes are supplied with low leak dampers and blade and edge seals. Damper
operating torques are shown in Table 3.
The actuator and mounting brackets are field supplied and
may be mounted inside or outside the unit. A typical inside
mounting bracket is shown in Fig. 17. For external mounting of
actuators, drill or punch a hole in the exterior panel.
NOTE: If the unit is shipped with AirManager™ controls,
actuator(s) are factory-supplied. Refer to Table 4.
To ensure torque is transmitted equally to both damper sections, actuator must be connected to the 1-in. hollow jackshaft
that drives the interconnecting linkage bar. Connection to any
other shaft is not recommended.
DUCTWORK ATTACHMENT — Ductwork should be
flanged out and attached to the mixing box panels as shown in
Fig. 18. See Fig. 19 for duct connection sizes.
Table 3 — Mixing Box Damper Operating Torque
(in.-lb)
39L UNIT SIZETORQUE
0320
0620
0826
1029
1233
1541
1852
2156
2576
NOTES:
1. Torque values are based on interconnected dampers driven by
one operator. For units with separate operators for each
damper, calculate torque as follows: Table values x .80 = torque
per damper section.
2. Damper shaft moves 90 degrees from open to closed position.
14
Table 4 — Recommended Actuators
DIMENSIONS (ft-in.)
Fig. 19 — Mixing Box Duct Connections
UNIT
39L-
ABCDEFGHJKL
032- 39/
16
3-17/
8
2-01/
4
1- 51-50- 15/
8
0-61/
16
0-101/
2
1-43/
4
1-51/
4
1- 51/
4
062- 39/
16
3-93/
4
2-43/
16
1-111-50- 41/
8
0-61/
16
0-113/
8
1-811/
16
2-11/
4
1- 71/
4
082- 39/
16
4-111/
16
2-81/
8
3- 11-50- 61/
16
0-61/
16
0- 63/
8
2-05/
8
3-31/
4
1- 71/
4
102- 39/
16
4-99/
16
2-81/
8
3- 51-50- 61/
16
0-61/
16
0- 85/
16
2-05/
8
3-71/
4
1- 71/
4
122- 39/
16
5-57/
16
2-81/
8
3-111-50- 61/
16
0-61/
16
0- 91/
4
2-05/
8
4-11/
4
1- 71/
4
152- 39/
16
5-57/
16
3-43-111-90- 80-41/
16
0- 91/
4
2-81/
2
4-11/
4
1-111/
4
182-117/
16
5-57/
16
3-715/
16
3-112-30- 70-50- 91/
4
3-07/
16
4-11/
4
2- 51/
4
212-117/
16
6-51/
4
3-715/
16
3-112-50- 60-41- 31/
8
3-07/
16
4-11/
4
2- 71/
4
252-117/
16
6-51/
4
4-313/
16
5- 42-50- 97/
8
0-40- 65/
8
3-85/
16
5-61/
4
2- 71/
4
NOTES:
1. Hand is determined by the location of the fan drive and/or coil connection when viewed
while facing the direction toward which air is flowing.
2. Dimensions are in inches, ( ) are in millimeters.
1. All actuators are direct coupled type, designed to be directly
mounted into jackshaft assembly.
2. All actuators are equipped with a plenum rated cable, factoryterminated to the actuator. Part No. HF27BB035 and 034 are
16 ft, HF27BB033 is 9.5 ft.
3. Damper areas are nominal and based on low leakage type
dampers.
4. For larger damper assemblies, multiple activators may be used.
5. Part No. HF27BB033 and 034 are designed for inlet guide vane
and face and bypass applications, but may be used for external
relief dampers if spring return is not required.
(ft)
15
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.