Carrier 38TA, 40TA, 40TY, 40BZ, 38TY Installation Instructions Manual

...
50TA/TZ/TY/YZ 40TA/TZ/TY/BZ-38TA/FZ/TY/BZ
Electric Heaters
Installation instructions
NOTE: This manual refers to accessories and options with „D“ as the nal letter in the ordering code.
1 - SAFETY CONSIDERATIONS
Installation, servicing and maintenance of air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualied service personnel should install, start-up or service air conditioning equipment.
Untrained personnel can perform the basic maintenance functions of cleaning and replacing lters. All other operations should be performed by trained service personnel. When working on air conditioning equipment, observe precautions in the manual and stickers on the unit and other safety precautions that may apply locally, regionally and nationally, as well as all applicable laws.
Follow all safety codes. Wear safety glasses and work gloves suitable for the work carried out.
Disconnect the unit electrically at the main switch before carrying out any work inside the unit. All procedures that do not require unit operation, as well as all cleaning and maintenance operations must be done with the unit de-energised.
WARNING: Before performing service or maintenance operations on the unit turn off the main power switch to the unit. Electric shocks could cause serious injuries.
2 - RECEIVING THE ELECTRIC HEATER
2.1 - Inspect the shipment
Inspect the shipment to check for transport damage. If there are signs of damage the transport managers must inspect the component before it is installed. Immediately le a claim with the shipping company or note the damage in the shipping documents. The manufacturer is not responsible for damage incurred during transport.
Check that all components listed on the shipping documents have been supplied. If any item is missing, immediately inform the nearest Carrier ofce and make a note on the shipping documents. To prevent damage and/or loss keep all components in their original packaging until they are installed by qualied personnel.
3 – UNIT INSTALLATION
The electric heaters (accessory/option) are supplied for installa­tion in the units and have not been factory-installed; they must be installed as described in this manual. The manual only applies to heaters with the ordering code ending in the letter „D“ (e.g. X40TY04B09D (50TY/YZ 024 with 1.5 kW capacity).
A - The electric heaters are always installed outside the unit
and are xed to the panel of the indoor fan air discharge, as shown in Figs. 1, 2 and 3.
B - Whether the unit is installed or not, the heater must be
attached by xing it to the panel of the indoor fan outlet, using the four threaded sheet metal screws supplied with the heater. The electric heater is installed so that the control box is above or below depending on the position of the indoor fan air discharge outlet (see Figs. 2 and 3).
C - If the unit is already installed and connected to the air
discharge duct, this must be cut in accordance with the depth of the heater so that this can be installed. Next attach the duct to the heater.
D - The heater thermal protection devices must always be
located in the upper part, whatever the position of the heater control box.
E - The heater must be xed to the unit as shown in the
following gures: Fig. 4: View of the electric heater Fig. 5: View of the indoor fan outlet panel Fig. 6: View of the installation of the heater in the unit
Fig. 1 - Front view
Fig. 2 - Side view: Unit with indoor fan situated on top
of the panel
Fig. 3 - Side view: Unit with indoor fan situated below
the panel
Indoor fan air discharge panelAir intake lter
UnitElectric heater
Indoor fan
Air ow
Indoor fan
Electric heater
Control box
Unit
Control box
Air ow
Fig. 4 - Electric heater (front view)
F - Changing the electric heater control box from its standard
position as supplied to the alternative position is possible if the indoor fan air discharge is located in the lower part of the casing.
Proceed to change the control box position so that it is located in the upper part when mounted in the unit (see Fig. 3).
Figs. 4, 5 and 6 show the heater with the control box in the lower part and the thermal switches in the upper part. To change the position it is enough to remove the four screws that secure the frame of the electric heaters and the thermal switches as shown below.
Fig. 7
Fig. 5 - Fan panel (front view)
The electric heater must be xed to the discharge air panel. Align holes 1 of the heater with holes 1 of the panel. Secure the heater as shown in Fig. 6, using the screws supplied.
Fig. 6 - View of the unit and electric heater
1 Holes and xing points of the electric heater to the unit,
with xing screws.
Fig. 8
Thermal switches
Thermal switches
Control box
Once the electric heater frame and the thermal switches have been disconnected, turn the heater 180°, removing the strip that covers them.
Insert the thermal switches in the hole below the control box so that the manually reset thermal switch is accessible.
Gather the connection cables from the heaters and thermal switches so that they are protected and hidden by the frame that has been removed.
Re-insert the screws that were previously removed.
The control box and the thermal switches must be located in the same zone of the heater, contrary to what is shown in Figs. 4 and 7 so that they can be installed in the unit when the fan is located with its air discharge section in the lower part of the unit (Fig. 3).