Carrier 38QRR User Manual

40QAC / 38HDR 40QAQ / 38QRR Ceiling---Suspended Duct Free S plit System Sizes 018 to 060
Installation Instructions
40QAC, QAQ Unit
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and current editions of the National Electrical Code ( NEC ) NFPA 70. In Canada, refer to current editions of the Canadian electrical code CSA 22.1.
Recognize safety information. This is the safety--alert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words; DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
!
the environmentally sound refrigerant
38HDR, QRR Unit
installation.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could result in personal injury or equipment damage.
Puron refrigerant systems operate at higher pressures than standard R--22 systems. To avoid damage to the unit or possible personal injury, do not use R--22 service equipment or components on Puron refrigerant equipment.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
PERSONAL INJURY AND EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in personal injury and / or equipment damage.
DO NOT operate the unit without a filter or with grille removed.
WARNING
!
CAUTION
DIMENSIONS -- INDOOR
R
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Standard unit clearances are as follows:
• 0 in. on top and rear
• 3in.onleftside
• 12 in. on right side
• 36 in.on bottom (When facing unit discharge.)
40QAC/38HDR -- 40QAQ/38QR
A08580
UNIT SIZE
024 108 110 4 --- 2 15/16 1294 3 --- 1 0 1169 4 --- 1 5/8 1260 1 --- 9 5 /8 549 036 117 119 4 --- 1013/16 1493 4 --- 5 7/8 1368 4 --- 9 1/2 1459 2 --- 1 1/2 648 048 149 151 5 --- 119/16 1817 5 --- 6 5/8 1692 5 --- 1 0 1/4 1783 1 --- 9 7/8 555 3 --- 3 1/16 992 060 179 181 7 --- 8 2336 7 --- 3 2211 7 --- 6 5/8 2302 1 --- 1 1 5/8 601 4 --- 1 1 9/16 1512
WEIGHT (lb) A B E F G
Cooling
Only
Heat
Pump
f t --- i n . mm f t --- i n . mm f t --- i n . mm ft --- i n . mm f t --- i n . mm
Fig. 1 -- 40QA Dimensions
2
SHIPPING
DIMENSIONS (L x W x H)
SHIPPING
WEIGHT(lbs)
WEIGHT(lbs)
OPERATING
MINIMUM
DIMENSIONS
MOUNTING PAD
F, MAX. 125 F.
1. REQUIRED CLEARANCES: WITH COIL FACING WALL; ALLOW 6" MIN
CLEARANCE ON COIL SIDE AND COIL END AND 36" MIN CLEARANCE
ON COMPRESSOR END AND FAN SIDE. WITH FAN FACING WALL; ALLOW 8" MIN
CLEARANCE ON FAN SIDE AND COIL END AND 36" MIN CLEARANCE
ON COMPRESSOR END AND COIL SIDE. WITH MULTI UNIT APPLICATION;
ARRANGE UNITS SO DISCHARGE OF ONE DOES NOT ENTER INLET OF ANOTHER.
2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING
MODE IS 55
3. SERIES DESIGNATION IS THE 13TH POSITION OF THE
UNIT MODEL NUMBER.
4. CENTER OF GRAVITY
5. ALL DIMENSIONS ARE IN "INCHES" UNLESS NOTED.
18,24 23" X 42"
UNIT SIZE
30,36,48,60 24" X 50"
FIELD POWER SUPPLY CONN.
HOLE SIZES PROVIDED:
7/8"-1/2"TRADE
1 3/16"-3/4"TRADE
1 3/8"-1"TRADE
1 7/16"
JUNCTION BOX FOR
POWER SUPLLY AND
CONTROL CONNECTIONS
1 1/2"
H
G
8"
4 1/2"
40QAC/38HDR -- 40QAQ/38QRR
1"
L
AB C D E F G H J KLMNP
ELECTRICAL
CHARACTERISTICS
UNIT SERIES
38HDR036 1 X O X X 37 3/16" 44 9/16" 17 1/16" 18 7/16" 30 1/2" 19 5/8" 29 3/16" 34 1/16" 13 11/16" 8 1/8" 15 7/8" 3/4" 3 7/16" 6 1/2" 218 240 50 1/2" X 20 1/2" X 40 2/10"
38HDR030 1 X O O O 37 3/16" 44 9/16" 17 1/16" 18 7/16" 30 1/2" 19 5/8" 29 3/16" 34 1/16" 13 11/16" 8 1/8" 15 7/8" 3/4" 3 7/16" 6 1/2" 200 223 50 1/2" X 20 1/2" X 40 2/10"
38HDR024 1,2 X O O O 31 1/8" 36 15/16" 14 9/16" 16" 23 7/16" 17 3/16" 23 1/8" 28" 14" 6 3/4" 11 5/8" 5/8" 2 15/16" 6" 180 198 42 9/10" X 18" X 34 1/10"
38HDR018 1 X O O O 25 1/8" 36 15/16" 14 9/16" 16" 23 7/16" 17 3/16" 17 1/8" 22" 13" 6 5/8" 11 1/4" 5/8" 2 15/16" 6" 155 171 42 9/10" X 18" X 28 1/10"
X = YES
O = NO
38HDR060 1,2 X O X X 43 3/16" 44 9/16" 17 1/16" 18 7/16" 30 1/2" 19 5/8" 35 3/16" 40 1/16" 14 1/2" 8 1/2" 18 7/8" 7/8" 3 7/16" 6 1/2" 294 319 50 1/2" X 20 1/2" X 46 2/10"
38HDR048 1,2 X O X X 43 3/16" 44 9/16" 17 1/16" 18 7/16" 30 1/2" 19 5/8" 35 3/16" 40 1/16" 14 1/2" 8 1/2" 18 7/8" 7/8" 3 7/16" 6 1/2" 284 309 50 1/2" X 20 1/2" X 46 2/10"
P
AIR
460-3-60
208/230-3-60
230-1-60
208-230-1-60
2 1/2"
N
N
7 1/2"
4 3/16"
FIELD CONTROL SUPPLY
WIRE ENTRY
7/8" HOLE W/GROMMET
K
VAPOR LINE CONN.
M
FEMALE SWEAT CONN.
3/8" LIQUID LINE
FEMALE SWEAT CONN.
Fig. 2 -- 38HDR Outdoor Unit Dimensions -- English
J
AIR
E
B
11/16"
C
FD
A
3
SHIPPING
DIMENSIONS (L x W x H)
SHIPPING
WEIGHT(KG)
WEIGHT(KG)
OPERATING
FIELD POWER SUPPLY CONN.
HOLE SIZES PROVIDED:
22.22 - 12.70 TRADE
30.16 - 19.05 TRADE
34.92 - 25.40 TRADE
MINIMUM
DIMENSIONS
MOUNTING PAD
C, MAX. 51.7 C.
18,24 584.2 X 1066.8
UNIT SIZE
30,36,48,60 609.6 X 1270.0
36.5
H
40QAC/38HDR -- 40QAQ/38QRR
3. SERIES DESIGNATION IS THE 13TH POSITION OF THE
UNIT MODEL NUMBER.
4. CENTER OF GRAVITY
1. REQUIRED CLEARANCES: WITH COIL FACING WALL; ALLOW 152.4 MIN
CLEARANCE ON COIL SIDE AND COIL END AND 914.4 MIN CLEARANCE
ON COMPRESSOR END AND FAN SIDE. WITH FAN FACING WALL; ALLOW 203.2 MIN
CLEARANCE ON FAN SIDE AND COIL END AND 914.4 MIN CLEARANCE
ON COMPRESSOR END AND COIL SIDE. WITH MULTI UNIT APPLICATION;
ARRANGE UNITS SO DISCHARGE OF ONE DOES NOT ENTER INLET OF ANOTHER.
2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING
MODE IS 12.8
5. ALL DIMENSIONS ARE IN "MM" UNLESS NOTED.
106.4
63.5
K
P
N
JUNCTION BOX FOR
POWER SUPLLY AND
CONTROL CONNECTIONS
J
38.1
FIELD CONTROL SUPPLY
WIRE ENTRY
22.22 HOLE W/GROMMET
G
L
VAPOR LINE CONN.
M
FEMALE SWEAT CONN.
203.2
114.3
25.4
Fig. 3 -- 38HDR Outdoor Unit Dimensions -- SI
9.53 LIQUID LINE FEMALE SWEAT CONN.
AB C D E F G H J KLMNP
ELECTRICAL
CHARACTERISTICS
UNIT SERIES
38HDR036 1 X O X X 944.6 1131.9 433.4 468.3 774.7 498.5 741.4 865.2 347.7 206.4 403.2 19.0 87.3 165.1 99.0 109.0 1282.7 X 520.7 X 1020.7
38HDR030 1 X O O O 944.6 1131.9 433.4 468.3 774.7 498.5 741.4 865.2 347.7 206.4 403.2 19.0 87.3 165.1 90.9 101.4 1282.7 X 520.7 X 1020.7
38HDR024 1,2 X O O O 790.6 938.2 369.9 406.4 595.3 436.6 587.4 711.2 355.6 171.5 295.3 15.9 74.6 152.4 81.8 90.0 1090.2 X 457.7 X 866.7
38HDR018 1 X O O O 638.2 938.2 369.9 406.4 595.3 436.6 435.0 558.8 330.2 168.3 285.8 15.9 74.6 152.4 70.4 77.7 1090.2 X 457.7 X 714.3
X = YES
O = NO
38HDR060 1,2 X O X X 1097.0 1131.9 433.4 468.3 774.7 498.5 893.8 1017.6 368.3 215.9 479.4 22.2 87.3 165.1 133.6 145.0 1282.7 X 520.7 X 1173.1
38HDR048 1,2 X O X X 1097.0 1131.9 433.4 468.3 774.7 498.5 893.8 1017.6 368.3 215.9 479.4 22.2 87.3 165.1 129.0 140.4 1282.7 X 520.7 X 1173.1
AIR
460-3-60
208/230-3-60
230-1-60
208-230-1-60
190.5
AIR
E
B
17.5
FDC
A
4
SHIPPING
DIMENSIONS (L x W x H)
SHIPPING
WEIGHT(lbs)
WEIGHT(lbs)
OPERATING
MINIMUM
DIMENSIONS
MOUNTING PAD
F, MAX. 125 F.
18,24 23" X 42"
30,36,48,60 24" X 50"
UNIT SIZE
3. SERIES DESIGNATION IS THE 13TH POSITION OF THE
UNIT MODEL NUMBER.
4. CENTER OF GRAVITY
1. REQUIRED CLEARANCES: WITH COIL FACING WALL; ALLOW 6" MIN
CLEARANCE ON COIL SIDE AND COIL END AND 36" MIN CLEARANCE
ON COMPRESSOR END AND FAN SIDE. WITH FAN FACING WALL; ALLOW 8" MIN
CLEARANCE ON FAN SIDE AND COIL END AND 36" MIN CLEARANCE
ON COMPRESSOR END AND COIL SIDE. WITH MULTI UNIT APPLICATION;
ARRANGE UNITS SO DISCHARGE OF ONE DOES NOT ENTER INLET OF ANOTHER.
2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING
MODE IS 55
5. ALL DIMENSIONS ARE IN "INCHES" UNLESS NOTED.
FIELD POWER SUPPLY CONN.
HOLE SIZES PROVIDED:
7/8"-1/2"TRADE
1 3/16"-3/4"TRADE
1 3/8"-1"TRADE
1 7/16"
JUNCTION BOX FOR
POWER SUPLLY AND
CONTROL CONNECTIONS
1 1/2"
H
G
8"
4 1/2"
40QAC/38HDR -- 40QAQ/38QRR
1"
L
AB C D E F G H J KLMNP
ELECTRICAL
CHARACTERISTICS
UNIT SERIES
38QRR036 0 X O X X 37 3/16" 44 9/16" 17 1/16" 18 7/16" 30 1/2" 19 5/8" 29 3/16" 34 1/16" 13 11/16" 8 1/8" 15 7/8" 3/4" 3 7/16" 6 1/2" 232 255 50 1/2" X 20 1/2" X 40 2/10"
38QRR030 0 X O O O 37 3/16" 44 9/16" 17 1/16" 18 7/16" 30 1/2" 19 5/8" 29 3/16" 34 1/16" 13 11/16" 8 1/8" 15 7/8" 3/4" 3 7/16" 6 1/2" 187 210 50 1/2" X 20 1/2" X 40 2/10"
38QRR024 0 X O O O 31 1/8" 36 15/16" 14 9/16" 16" 23 7/16" 17 3/16" 23 1/8" 28" 14" 6 3/4" 11 5/8" 5/8" 2 15/16" 6" 176 194 42 9/10" X 18" X 34 1/10"
38QRR018 0 X O O O 25 1/8" 36 15/16" 14 9/16" 16" 23 7/16" 17 3/16" 17 1/8" 22" 13" 6 5/8" 11 1/4" 5/8" 2 15/16" 6" 167 183 42 9/10" X 18" X 28 1/10"
X = YES
38QRR060 0 X O X X 43 3/16" 44 9/16" 17 1/16" 18 7/16" 30 1/2" 19 5/8" 35 3/16" 40 1/16" 14 1/2" 8 1/2" 18 7/8" 7/8" 3 7/16" 6 1/2" 306 331 50 1/2" X 20 1/2" X 46 2/10"
38QRR048 0 X O X X 43 3/16" 44 9/16" 17 1/16" 18 7/16" 30 1/2" 19 5/8" 35 3/16" 40 1/16" 14 1/2" 8 1/2" 18 7/8" 7/8" 3 7/16" 6 1/2" 278 303 50 1/2" X 20 1/2" X 46 2/10"
O = NO
P
AIR
460-3-60
208/230-3-60
230-1-60
208-230-1-60
FIELD CONTROL SUPPLY
WIRE ENTRY
7/8" HOLE W/GROMMET
2 1/2"
N
7 1/2"
4 3/16"
K
VAPOR LINE CONN.
M
FEMALE SWEAT CONN.
J
AIR
Fig. 4 -- 38QRR Outdoor Unit Dimensions -- English
3/8" LIQUID LINE
MALE FLARE CONN.
E
B
11/16"
FDC
A
5
SHIPPING
DIMENSIONS (L x W x H)
SHIPPING
WEIGHT(KG)
FIELD POWER SUPPLY CONN.
HOLE SIZES PROVIDED:
22.22 - 12.70 TRADE
30.16 - 19.05 TRADE
34.92 - 25.40 TRADE
40QAC/38HDR -- 40QAQ/38QRR
WEIGHT(KG)
OPERATING
355.6 171.5 295.3 15.9 74.6 152.4 80.0 88.2 1090.2 X 457.7 X 866.7
330.2 168.3 285.8 15.9 74.6 152.4 75.9 83.2 1090.2 X 457.7 X 714.3
711.2
558.8
85.0 95.4 1282.7 X 520.7 X 1020.7
139.0 150.4 1282.7 X 520.7 X 1173.1
126.4 137.7 1282.7 X 520.7 X 1173.1
105.4 115.9 1282.7 X 520.7 X 1020.7
165.1
165.1
165.1
87.3 165.1
347.7 206.4 403.2 19.0
741.4 865.2
1. REQUIRED CLEARANCES: WITH COIL FACING WALL; ALLOW 152.4 MIN
CLEARANCE ON COIL SIDE AND COIL END AND 914.4 MIN CLEARANCE
215.9 479.4 22.2 87.3
215.9 479.4 22.2 87.3
347.7 206.4 403.2 19.0 87.3
893.8 1017.6 368.3
893.8 1017.6 368.3
741.4 865.2
MINIMUM
DIMENSIONS
C, MAX. 51.7 C.
ON COMPRESSOR END AND FAN SIDE. WITH FAN FACING WALL; ALLOW 203.2 MIN
CLEARANCE ON FAN SIDE AND COIL END AND 914.4 MIN CLEARANCE
ON COMPRESSOR END AND COIL SIDE. WITH MULTI UNIT APPLICATION;
ARRANGE UNITS SO DISCHARGE OF ONE DOES NOT ENTER INLET OF ANOTHER.
2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING
MODE IS 12.8
3. SERIES DESIGNATION IS THE 13TH POSITION OF THE
UNIT MODEL NUMBER.
4. CENTER OF GRAVITY
5. ALL DIMENSIONS ARE IN "MM" UNLESS NOTED.
63.5
MOUNTING PAD
18,24 584.2 X 1066.8
30,36,48,60 609.6 X 1270.0
UNIT SIZE
106.4
36.5
JUNCTION BOX FOR
POWER SUPLLY AND
CONTROL CONNECTIONS
38.1
FIELD CONTROL SUPPLY
WIRE ENTRY
22.22 HOLE W/GROMMET
H
G
203.2
114.3
25.4
L
Fig. 5 -- 38QRR Outdoor Unit Dimensions -- SI
AB C D E F G H J KLMNP
ELECTRICAL
CHARACTERISTICS
UNIT SERIES
38QRR018 0 X O O O 638.2 938.2 369.9 406.4 595.3 436.6 435.0
38QRR024 0 X O O O 790.6 938.2 369.9 406.4 595.3 436.6 587.4
38QRR030 0 X O O O 944.6 1131.9 433.4 468.3 774.7 498.5
38QRR036 0 X O X X 944.6 1131.9 433.4 468.3 774.7 498.5
38QRR048 0 X O X X 1097.0 1131.9 433.4 468.3 774.7 498.5
38QRR060 0 X O X X 1097.0 1131.9 433.4 468.3 774.7 498.5
X = YES
O = NO
AIR
460-3-60
208/230-3-60
230-1-60
208-230-1-60
K
P
N
N
190.5
J
AIR
VAPOR LINE CONN.
M
FEMALE SWEAT CONN.
9.53 LIQUID LINE MALE FLARE CONN.
E
B
17.5
FDC
A
6
These installation instructions cover the installation of the matched
R
systems listed in table 2.
Parts List
Indoor Unit
The following items are included with the indoor unit:
Table 1 – Installation Materials
Part No. Name of Part Qty.
1 Side Panels 2 2 Hex Head Bolts 4 3 Mounting Bracket 2 4 Pistons 1 5 Installation Template 1 6 Adapter Tubes 2
Table 2 – Matched Systems
System
Ty pe
Cooling
Heat Pumps
Heat Pumps
* Units must be configured for 1 --- 1/2 ton operation. Refer to instructions
on page 9.
Nominal
Capacity
018 3 8 H D R 0 1 8 --- --- --- 3
024 3 8 H D R 0 2 4 --- --- --- 3 4 0 Q AC024 --- --- --- 3
030 3 8 H D R 0 3 0 --- --- --- 3 4 0 Q AC036 --- --- --- 3
036 38HDR036 ------ --- 3/5/6 4 0 Q A C 0 3 6 --- --- --- 3
048 38HDR048 ------ --- 3/5/6 4 0 Q A C 0 4 8 --- --- --- 3
060 38HDR060 ------ --- 3/5/6 4 0 Q A C 0 6 0 --- --- --- 3
018 3 8 Q R R 0 1 8 --- --- --- 3 4 0 Q AQ0 2 4 --- --- --- 3
024 3 8 Q R R 0 2 4 --- --- --- 3 4 0 Q AQ0 2 4 --- --- --- 3
030 3 8 Q R R 0 3 0 --- --- --- 3 4 0 Q AQ0 3 6 --- --- --- 3
036 38QRR036 ------ --- 3/5/6 4 0 Q A Q 0 36 --- --- --- 3
048 38QRR048 ------ --- 3/5/6 4 0 Q A Q 0 48 --- --- --- 3
060 38QRR060 ------ --- 3/5/6 4 0 Q A Q 0 60 --- --- --- 3
Outdoor Unit Indoor Unit
4 0 QAC 0 2 4 --- --- --- 3
*
SYSTEM REQUIREMENTS
Clearances
Allow sufficient space around the indoor and outdoor unit for proper airflow circulation and servicing. Refer to Fig. 1 through Fig. 5 for minimum required clearances.
Piping: Piping and insulation is field supplied.
Fig. 6 -- Hanging Fan Coil Unit
Outdoor Unit
The following items are included with the outdoor unit:
Fig. 7 -- 38HDR018--036
A09532
A09536
Piping Lengths
The minimum length between the indoor and outdoor units is 10 ft (3 m). Refer to table 3 for the maximum lengths allowed.
Table 3 – Maximum Refrigerant Line Lengths
Unit Size
18K 200 (61) 65 (19.8) 200 (61) 24K 200 (61) 65 (19.8) 200 (61) 30K 200 (61) 65 (19.8) 200 (61) 36K 200 (61) 65 (19.8) 200 (61) 48K 200 (61) 65 (19.8) 200 (61) 60K 200 (61) 65 (19.8) 200 (61)
Note: For lengths greater than 25 ft (7.6 m), refer to the Duct Free Long
Max Line
Length ft(m)
Line Guide.
Max Elevation (ID
over OD) ft(m)
Max Elevation (OD
over OD) ft(m)
Pipe Sizes
Refer to table 4 for pipe sizes.
Table4–PipeSizes
PIPE SIZES (in)
Unit Size Liquid Phase
18 3/8 5/8 5/8 24 3/8 5/8 5/8 30 3/8 3/4 3/4 36 3/8 3/4 3/4 48 3/8 7/8 3/4 60 3/8 7/8 3/4
Note: On heat pumps, both lines need to be insulated using at least 1/2 inch
closed foam insulation.
38HDR 38QRR
Vapo r
40QAC/38HDR -- 40QAQ/38QR
A09537
Fig. 8 -- 38QRR018--036
Model Filter Drier
38HDR n --- --- --­38QRR n n n n
Piston
Cap
Pistons
Flare
Connector
7
Refrigerant Charge
R
The 38HDR and 38QRR units can be matched with multiple outdoor units and thus additional charge might be required when matched with the 40QAC or 40QAQ units.
Table 5 – Additional Charge
Unit Size 38HDR 38QRR
018 0.7 (0.32) 0.7 (0.32) 024 1.3 (0.59) 0.8 (0.36) 030 1.4 (0.64) 0 036 0.2 (0.1) 0.5 (0.23) 048 0.2 (0.1) 0 060 0.5 (0.23) 0
Note: The above additional charge is required amount for line lengths up to 25 ft (7.6 m). For line lengths exceeding 25 ft (7.6 m), additional charge will be required. Refer to the Duct Free Splits Long Line Guide.
Additional Charge lb. (kg.)
Metering Device
The 40QAC and 40QAQ units use an accurator or a TXV as shown in Table 6.
Table 6 – Accurator Sizes
Unit Size
018 TVX 49 40 024 TVX 55 43 030 TVX 65 55 036 TVX 70 63 048 TVX 80 73 060 TVX TXV 80
NOTE: Pistons are supplied with either the indoor or outdoor units.
Cooling Only Heat Pumps
40QAC 40QAQ 38QRR
Power and Connecting Cables -- Field Supplied
Power:
S The main power is supplied to both the indoor and outdoor
units.
S Consult local building codes, NEC (National Electric Code) or
CEC (Canadian Electric Code) for any special requirements.
S Use Table 7 for the electrical requirements for the outdoor units
and Table 8 for the indoor units to correctly size the cables and disconnect switches.
Control Wiring
Thermostat wires should be used for control wiring between the indoor and outdoor units. A two conductor cable is required for the cooling only units and a seven conductor cable is required on heat pumps. 18 AWG is recommended for any length up to 200 ft (61.0 m).
User Interface -- Finished Goods Accessory
Any of the following three thermostats can be used depending on the type of system on hand and the desired features. Refer to Table 9 to select the proper thermostat.
40QAC/38HDR -- 40QAQ/38QR
Table 7 – 38HDR / QRR Electrical Requirements
UNIT SIZE V --- P H --- H z
018 208/230 ---1 ---60 12.1 20 12.1 20
024 208/230 ---1 ---60 17.7 25 18.8 30
030 208/230 ---1 ---60 19.1 30 17.5 30
208/230--- 1--- 60 19.1 30 20.9 30
036
048
060
208/230--- 3--- 60 13.0 20 14.1 20
4 6 0 --- 3 --- 6 0 7.9 15 7.9 15
208/230--- 1--- 60 26.4 40 34.6 50
208/230--- 3--- 60 17.9 25 22.4 30
4 6 0 --- 3 --- 6 0 8.4 15 10.0 15
208/230--- 1--- 60 34.5 60 34.5 60
208/230--- 3--- 60 21.5 30 23.6 40
4 6 0 --- 3 --- 6 0 10.6 15 10.6 15
MIN CKT AMPS
Table 8 – 40QAC / QAQ Electrical Requirements
UNIT
024 208/230--- 1 0.63 15.0 9.29 15.0
036 208/230--- 1 1.60 15.0 17.70 20.0
048 208/230--- 1 2.00 15.0 23.80 25.0
060 208/230--- 1 3.30 15.0 28.70 30.0
VOLTAGE
V --- P h --- 6 0 H z
38HDR 38QRR
FUSE/HACR BKR
AMPS
40QAC 40QAQ
MCA MOCP MCA MOCP
MIN CKT AMPS FUSE/HACR BKR AMPS
Table 9 – Thermostat Selection
Model Number
7 Day Programmable
Feature s
5+1+1 Day Programmable --- ---
Remote Room Sensor
Dry Contact Equipped
Cooling Only & HP
53DFS250--- SL
System Type
Cooling Only
53DFS250--- FS
Cooling Only 53DFST2 --- NP
---
---