Carrier 38QF User Manual

Page 1
Number One Air Conditioning i\Mer
^Sb Division of
^ 0 Carrier Corporation
Carrier Parkway • Syracuse, N.Y. 13221
Heat Pump — Outdoor Section
CONTENTS
Page
.............................
.. 1
. 1-5
.. 1
• UNPACK UNIT
• INSPECT EQUIPMENT
• COMPLETE OR CONSIDER SYSTEM REQUIREMENTS
Step 2 Mount Outdoor Heat Pump..................2
• ON THE GROUND; MOUNT UNIT ON A SOLID, LEVEL CONCRETE PAD
• ON THE ROOF: MOUNT UNIT ON
A LEVEL PLATFORM OR FRAME
Step 3 — Make Piping Connections
...................
3
• REPLACE THE ACCURATER™ RE FRIGERANT CONTROL PISTON IN
THE INDOOR COIL AS REQUIRED
• CONNECT REFRIGERANT LINES
Step 4 — Make Electrical Connections ... 4
• INSTALL A BRANCH CIRCUIT
DISCONNECT PER NEC
• ROUTE LINE POWER LEADS INTO UNIT
• CONNECT GROUND LEAD AND POWER WIRING
• SEE INDOOR UNIT AND ELECTRIC HEATER INSTALLATION, START-UP
AND SERVICE INSTRUCTIONS
• CONNECT CONTROL POWER WIRING (24 v)
START-UP
SERVICE................................................................. 7-14
MAINTENANCE.....................................................14-17
..............................................................
SAFETY CONSIDERATIONS
5-7
Installation and servicing of air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and quali
fied service personnel should install, repair or serv ice air conditioning equipment.
Untrained personnel can perform basic main
tenance functions of cleaning coils and cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on air conditioning equipment, observe
precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing oper ations. Have fire extinguisher available for all braz ing operations.
W.ARNING: Before performing scr\icc or maintenance operations on sxstem. turn ofl
main powci switches to indoor unit and out door unil. 1 urn ofl acccssoiA heater power switch if applicable, riectrical shock could cause personal itijur\.
INSTALLATION
Step 1 — Check Equipment and Jobsite
UNPACK UNIT — Move to final location. Lift carton off, taking special care not to damage service
valves or grilles. INSPECT EQUIPMENT — File claim with ship
ping company if shipment is damaged or incomplete. COMPLETE OR CONSIDER SYSTEM RE
QUIREMENTS before installing the 38QF.
Consult local building codes and National
Electrical Code (NEC) for special installation requirements.
When installing, allow sufficient space for air
flow clearance, wiring, refrigerant piping and serv icing. Position so water or ice from roof cannot drop directly on top of unit.
Make provisions for condensate drainage and
defrost water disposal whether unit is installed on ground or roof. (Ensure unit basepan drainage holes are not blocked.) See Step 2 for details. Roof in stallation method for 38QF depends on building construction and special requirements of local codes. Be sure that roof can support unit weight.
It is recommended that 38QF units be used with
Carrier approved indoor sections; see Table 1.
System Refrigerant Control on 38QF units and matching Carrier indoor units is a factory-installed AccuRater™ device (bypass type). Bypass-type
AccuRater components are discussed in the service section of this booklet. The AccuRater piston has a refrigerant metering hole thru it and is field replace able. Table 1 indicates indoor units for which the required replacement piston is factory supplied with specified 38QF outdoor unit. Replace piston as
described under AccuRater™ Servicing on page 13.
© Carrier Corporation 1983 Form 38QF-2SI
Page 2
Top Cover Removal — Top cover can be removed for wiring or servicing heat pump. Loosen decora tive strip and slide down off screw heads. Remove
3 screws in connector plate and 2 screws on front of unit. Loosen remaining 4 screws. Lift top from unit (see Fig. 1).

Step 2 — Mount Outdoor Heat Pump

ON THE GROUND: MOUNT UNIT ON A SOLID, LEVEL CONCRETE PAD (see Fig. I).
4-0"0VERHEAD SPACE REQUIRED
FOR SERVICE AND AIRFLOW
7"
8
DIAM HOLE FOR CONTROL WIRING
Swing 3 legs down and lock in position, except when
using accessory rack. Use accessory heat pump rack (Fig. 2) in areas where prolonged subfreezing tem peratures or heavy snow occur. (Refer to installation instructions included with rack.) Drainage holes in unit base must not be obstructed.
AIRFLOW AND SERVICE CLEARANCE
LIQUID VALVE SERVICE PORT / VAPOR VALVE SERVICE PORT
AIRFLOW SUCTION SERVICE PORT
CONCRETE MOUNTING PAD
Fig. 1 — Dimensions, Connections and
Mounting Pad (Refer to Table 2)
Fig. 2 — Accessory Mounting Rack
Table 1 — Carrier Approved 38QF Systems
OUTDOOR
UNIT 38QF
018
024 46
030
036
042
048
060
^Factory-supplied piston packages shipped in outdoor unit. Replace remain
ing indoor pistons with size indicated.
REQUIRED OUTDOOR
PISTON
SIZE
42
59
61
63
76 40QB/QH060 86*
82
INDOOR
UNIT
MODEL &
SIZE
40AQ018
28HQ/VQ018
40AQ024
28HQ/VQ024
40FS075,28HQ/VQ042
40AQ024
28HQ/VQ024
40AQ030
28HQ/VQ030
40FS075,28HQ/VQ042
40AQ030
28HQ/VQ030
40DQ030
40AQ036
28HQ/VQ036
40AQ036 28HQ/VQ036 40QB/QH042 28HQ/VQ042
40QB/QH042 28HQ/VQ048 40QB/QH048
40QB/QH048 84 28HQ/VQ048 84
40QB/QH062 28HQ/VQ060
40QB/QH060 40QB/QH062
REQUIRED
INDOOR
PISTON
SIZE
61
67
67
70* 70*
70 70 73* 73*
76 78 78
86* 86*
96
52 52 55* 55*
59 59 61* 61* 65
67
Page 3
ON THE ROOF; MOUNT UNIT ON A LEVEL
PLATFORM OR FRAME: Proper precaution must be taken for support of unit in roof design. Elevate unit for proper clearance as described under ground installation above. Plan roof design and water drainage to prevent unit from setting in water. Flash all roof openings to prevent leaks.
Roof mounted unit exposed to winds above 5 mph may require protective wind baffles (field fabricated) to achieve adequate defrost.
Step 3 — Make Piping Connections — Heat
pumps may be connected to indoor sections using
Carrier accessory tubing package (Table 3) or field-
supplied tubing of refrigerant grade, correct size and condition (Table 2). For requirements beyond 50 ft obtain information from local Carrier distributor.

-> Table 3 — Accessories

Table 2 — Installation Data (Fig. 1)
UNIT 38QF OPER WT(lb) DIMEN (ft-in.)
DIam (A) Height (B) Mtg Pad
(Diam X Thick)*
(C) (D)
REFRIG CONN (in.)
Suction (ODF) Liquid (ODF)
REFRIG LINES (in.)
Suction (ODF) Liquid (ODF)
“■Mounting pad is fieid suppiied, fMay use Vs-'m. accessory tubing package (slight capacity loss). See Tabie 3.
024 030 036 042
018
163 181 189 209
160
2-2'V32 j 2-8Y32 [3-13/4
2- 53/32
2-6 X 0-6
1-1
1-10/2
% 1 1 Vaf
048 265
3-23/33
2-83/61 3-2’/e
3-3 X 0-6
1 -5%
34
3/s
3/8
060 298
2-7
PART NO.
99TZ90040106
99TZ90041106 38QB90002106
28VQ900011 38RQ90008106
HN61KL704 380890004106
38CQ900172 38RQ90009106
38QB90001106 38QF90000106 38QB90003106 38QF90001106t HC95DE088* HC95DD121* HC95DD121“ HC95DE070* HN61KA054*
HN61HB515* HN61HB510* HN61HB505* HN61HB504* 38EB660002*
TUBING
PACKAGE
38LS978151 38LS978201 38LS978251 38LS978301 38LS978351 38LS978401 38LS978501
■“Available thru Carrier Service Parts. fStart capacitor and relay are required when using liquid line solenoid valve.
{Suction line is insulated and has 90° bend.
“■“Capacity reduction may occur when %-in. accessory tubing is used on 38QF042.
Low-Voltage Control — Honeywell Thermostat HH07AT171 and Thermostat Subbase HH93AZ173 — Automatic Changeover (Six 99TZ900401)
Low-Voltage Control — Subbase HH93AZ175 ■
Service Sentry — Standard on 38QF060 (Six HN65CT004)
Twelve M x IVs-in. connection adapters
Bi-Flow Heat Pump Filter Drier — Ref KH45LD077 (Six 38RQ900081)
Supplemental Heat Relay ■ (Six 38RQ900001)
Outdoor Thermostat (Six 38QB900041) Optimizer Control Outdoor Thermostat — Ref HH22AG110 (Six 38CQ900161) Optimizer II Control Assembly — Use with HH22AG110 outdoor thermostat.
(Six 38RQ900091) Heat Pump Rack (Six) Heat Pump Rack (Six)
Solid-State Time Guard I
Liquid Line Solenoid (Six 38QF900011) Start Capacitor
Start Capacitor Start Capacitor Start Capacitor Start Relay Start Relay Start Relay Start Relay Start Relay
Wire Bundle for Start Capacitor and Relay
LENGTH
OD
(ft)
15
20
25 30 35 40 50
(in.)
Ve Va
%
Ye Ys Ya Ya
Honeywell Thermostat HH07AT171 and Thermostat
DESCRIPTION
Manual Changeover (Six 99TZ900411)
■ Required with 2 outdoor thermostats.
24 volt (Six 38QB900031)
Liquid
Tube End OD
(in.
Ya Ya Ya Ya Ya Ya
OD
(in.)
Ya** Ya**
Ya** Ya** Ya** Ya** Ya**
TUBING
Suction^
Tube End OD
Evap
(in.)
% 3/4 3/4
34 3/4 3/4
Ya
Cond
(in.)
Ya
3/4
3/4
Ya Ya
3/4 3/4
MODEL 38QF
All
018-048 030-060
All
018-042
048,060
All 018 024 030
036,042
018 024
030 036 042
All
MODEL
38QF
All
Page 4
WARNING: If unclcrsi7ed. damaged or elliptiv.-all\-s!iapL'd uibing is used when making Compatible bitting, leaks ma\ result.
If 1-1/8 in. tubing is used, braze it to the accessory
1-1/8 X 3/4-in. suction connection adapter (Carrier Part No. 28VQ900011) or to a correctly sized field­supplied adapter, then make Compatible Fitting connections. Isolate interconnecting tubing from
framing and ductwork or where tubing runs thru stud spaces, enclosed ceilings or pipe chases. Use isolation type hangers. Fig. 3, since rigid fastening transmits pulsations to structure creating objec tionable sound.
^ ( \l 1 ION. IK) \OI Ml \<\ MORI I II \\
'' I I ()l I INI SI I IN (.ROl N1). II .m> '•ac tion of liucsel is burictl. there must be b-in. \ertical rise to the \al\e connections on the outdoor unit. If more than the recommended
length i.s buried, refrigerant ma\ migrate to the eooler buried .section during extended periods of
unit shutdown, causing relrigerant slugging and
possibh compressor damage at start-up.
A capacity reduction will result if accessory tub ing is used in 38QF systems. For example, when a 25-ft 7/8-in. accessory package is used, there is a capacity reduction of 1-1/2 percent.
When other than 25 ft of interconnecting tubing is used, follow special requirements described in Refrigerant Charging. Do not use less than 10 ft of interconnecting tubing. Do not cut 7/8-in. suction line. Bend or coil to fit.
Do not use damaged or contaminated tubing. Always evacuate or purge evaporator coil and
tubing system (use field-supplied refrigerant, not unit refrigerant).
When making tubing connections, be sure to
provide clearance at unit for electrical connections. REPLACE THE ACCURATER™ REFRIG
ERANT CONTROL PISTON IN THE INDOOR
COIL AS REQUIRED before connecting refrig erant lines. See Table 1. Correct piston is supplied with 38QF unit. For piston replacement instruc tions, see AccuRater Servicing on page 13.
CONNECT REFRIGERANT LINES to fittings on unit suction and liquid service valves (Fig. 1).
Liquid service valve has flare fitting; suction service valve has Compatible Fitting. Make suction line
connection first. Slide flare nut on liquid line, then flare and connect liquid line. Use a maximum torque of 15 ft-lb to tighten flare nut. (Do not dis assemble AccuRater.) Unit Compatible Fitting permits mechanical or sweat connection as de scribed below.
When a 7/8-in. field-supplied suction line is used on 38QF, a field-supplied 3/4-in. to 7/8-in. suction line adapter must be provided (not required if 38LS accessory tubing is used).
When a 1-1/ 8 in. field-supplied suction line is used on 38QF, use accessory adapter 28VQ900011 or other field-supplied connection. Sweat connect re
frigerant suction line to 1-1/8 in. end of adapter. Connect 3/4-in. end of adapter to unit suction line Compatible Fitting.
Mechanical Connection to Compatible Fitting (Mate one set of connections at a time.)
1. Loosen nut on Compatible Fitting one turn. Do not remove.
2. Remove plug and be sure 0-ring is in the groove inside the Compatible Fitting.
3. Cut tubing to correct length.
4. Insert tube into Compatible Fitting until it bottoms.
5. Tighten nut until it bottoms on back coupler
flange. Keep tube bottomed in Compatible Fitting while tightening nut.
Sweat Connection to Compatible Fitting (Use refrigerant grade tubing.)
1. Remove locking nut, rubber O-ring and Schrader
core from valve.
2. Cut tubing to correct length.
3. Insert tube into Compatible Fitting. Wrap top and bottom of service valves in wet cloth to pre vent damage by heat. Solder with low tempera ture (430 F) silver alloy solder.
4. Replace Schrader core.
5. Evacuate or purge system with field-supplied refrigerant.
Step 4 — Make Electrical Connections — Field
wiring must comply with local and national fire, safety and electrical codes. Voltage to unit must be
within permissible limits indicated on nameplate.
Contact local power company for correction of
improper line voltage.
W.AR.NTNG: Operation of units on improper line \oliagc constiiiitcs abuse and could affect
Carrier warrantx. See fable4.
Do not apply units in system where voltage may
fluctuate above or below permissible limits.
Page 5
Table 4 — Electrical Data (60 Hz)
OPER
UNIT
38QF
018 024
030 036 042
048 060
AWG — American Wire Gage FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration LRA — Locked Rotor Amps MCA — Minimum Circuit Amps RLA — Rated Load Amps
V/PH
230/1
208-230/1
230/1
VOLTAGE*
Max
254
254
Min LRA RLA
197
207
COMPR
50 54
69 17.7 75 90
101
130
FAN
FLA
10.8 14 30
13.0
16.8 10 50
20.0
21.2
28.6
1.1
1.7
When making electrical connections, provide clearance at unit for refrigerant piping connections. See Table 4 for recommended wire and fuse sizes.
INSTALL A BRANCH CIRCUIT DISCONNECT PER NEC of adequate size to handle unit starting current. Provide a separate disconnect for outdoor unit, indoor unit and for each accessory electric
heater circuit as required. (See Indoor Unit and
Electric Heater Installation, Start-Up and Service Instructions.) Locate disconnect(s) within sight from and readily accessible from the unit; per sec tion 440-14 of National Electrical Code (NEC).
ROUTE LINE POWER LEADS INTO UNIT — Extend leads from disconnect thru power wiring hole provided (see Fig. 1) and into unit splice area. Remove top cover to gain access to unit wiring.
CONNECT GROUND LEAD AND POWER WIRING — Connect ground lead to a ground lug in control box for safety. Then connect power wiring. See Fig. 4. Splice line power leads to yellow and
black pigtails. Use wire nuts and tape at each con nection. Connect unit wiring to copper wire only.
SEE INDOOR UNIT AND ELECTRIC HEATER INSTALLATION, START-UP AND SERVICE INSTRUCTIONS for line power wiring details. All
control wiring is shown in this booklet.
BRANCH CIRCUIT
Min Wire
(AWG)t
12 10 48
10 43 10 10
8
*Permissible limits of the voltage range at which the unit will
operate satisfactorily. tCopper wire sizes based on 60 C. Use copper wire only. fRequired when using nonmetallic conduit.
**Time-delay fuse
Max Wire Min Gnd
(ft)
41
39 46
Wire Size$
14 12
10 10
10 10
CONNECT CONTROL POWER WIRING (24 V) — Extend wiring thru hole provided (Fig. 1) and into low-voltage section of unit control ring. Connect leads to control wiring terminal board as shown in Fig. 5.
Use indoor unit transformer as 24-v supply for system. At least a 60-va transformer is recom mended. Carrier approved indoor units are equipped
with a 60-va transformer. See indoor unit data.
Use Carrier accessory indoor thermostat with
subbase, Table 3.

START-UP

The 38QF unit is equipped with a crankcase heater. It is recommended that heater be energized a minimum of 24 hours before starting unit. To ener
gize heater only, turn the thermostat to OFF posi tion and close electrical disconnect to heat pump.
Heat Anticipator Settings for Room Thermo
stat (HH07AT171) — Set anticipator settings for
room thermostat according to Table 5. These set tings may be changed slightly to provide a greater degree of comfort for a particular installation.
Max Fuse or
HACR Type
Ckt Bkr Amps**
25 14.6 30
40 35 22.0 45
45 60
MCA
17.3
23.1
26.0
28.1
37.5
1 PHASE
CONN. TO -
DISCONNECT PE.R NEC
.<1
_______
Field '.Virinq
_______
Fditory Wiiinq
---------------
Splicii Cfjnnpctions
GROUND _EAD-|(^ GROUNDING LUG
-BLK
I-PHASE rCND UNIT

Fig. 4 — Line Power Connections

-------------
Table 5 — Thermostat Anticipator Settings
UNIT
38QF
018
024 030 036 042 048 060
FIRST-
STAGE
ANTICIPATOR
SETTING
Fixed
INDOOR UNIT WITH ELECTRIC
HEATER
40AQ Fan Coil
with 40AQ Htrs
or 40QB/QH Fan Coil
with 40QB Htrs
HTR
KW
5.0
7.5
10.0
15.0
20.0
25.0
30.0
34.0
ANTICIPATOR
SETTINGS
SECOND-
STAGE
.25
.50
.75
Page 6
THERMOSTAT
SUBBASE
HH93AZI73
OR HH93AZI75
40AQ.40FQ OR 40QB FAN COIL 38QF
COOLING CONTROL KIT TERM INAL
TERMINAL BOARD BOARD
THERMOSTAT
SUBBASE
HH93AZI73
OR HH93AZI75
40AQ,40FQ OR 40QB
ELECTRIC HEATER TERMINAL BOARD
38QF
TERMINAL
BOARD
(38QF/40AQ 0R40QB/QB WITHOUT ELECTRIC HEATER)
COOLING AND ONE-STAGE HEATING
A
THERMOSTAT
SUBBASE
HH93AZ173
(38QF WITH 40AQ, 40QB/QH OR 40FS/28VQ
SUPPLEMENTAL HEAT, NO OUTDOOR THERMOSTATS)
40AQ,40FQ OR 40QB
ELECTRIC HEATER
TERMINAL BOARD
COOLING AND TWO-STAGE HEATING
EQUIPPED WITH ELECTRIC HEATER;
B
38QF
TERMINAL
BOARD
EQUIPPED WITH ELECTRIC HEATER;
SUPPLEMENTAL HEAT, ONE OUTDOOR THERMOSTAT)
THERMOSTAT
SUBBASE
COOLING AND TWO-STAGE HEATING
EQUIPPED WITH ELECTRIC HEATER;
SUPPLEMENTAL HEAT, TWO OUTDOOR THERMOSTATS)
40AQ,40FQ OR 40QB ELECTRIC HEATER
(38QF WITH 40FS/28VQ
38QF
TERMINAL
SHR — Supplemental Heat Relay ODT — Outdoor Thermostat _______
_______
Factory Wiring
Field Wiring
*Transformer (60 va) located in cooling control kit or electric heater. fRemove factory-installed jumper (Connection B) when installing outdoor thermostats (ODT).

Fig. 5 — Control Circuit Connections

Accessory Outdoor Thermostat provides adjust
able outdoor control of accessory electric heater. This thermostat makes contact when a drop in out door temperature occurs. It energizes a stage of elec tric heat when the outdoor temperature setting is reached, provided the room thermostat is on the second stage of heating. One outdoor thermostat is recommended for each stage of electric heat after the first stage. Set the outdoor thermostat(s) progres
sively lower for each stage. Refer to heat load of building and unit capacity to determine the correct outdoor thermostat settings.
The accessory supplemental heat relay is required when 2 outdoor thermostats are used. It is auto matically energized by the manually operated sup plemental heat switch in the indoor thermostat subbase. The thermostat locks out compressor and the relay bypasses the outdoor thermostats for electric heater operation during heat pump shut
down. When one outdoor thermostat is used a supplemental heat relay is not required. The sup plemental heat switch in the indoor thermostat subbase bypasses outdoor thermostat, locks out compressor and activates electric heater.
Page 7
MOUNT OUTDOOR THERMOSTAT on control ring, to the left of the low-voltage control connec tion. See Fig. 1.
Attach brackets with short sheet metal screws to avoid contact with coil. Leave capillary tube coiled in control compartment making sure it is clear of all electrical connections and sharp metal edges.
MOUNT SUPPLEMENTAL HEAT RELAY in convenient location on indoor unit. Attach with sheet metal screw.
To Start Unit — (Make sure crankcase heater
has been energized for 24 hours.) Adjust the thermo stat as follows:
1. Set selector switch at OFF.
2. Turn on main disconnect switch(es) to indoor
and outdoor units.
3. Set fan switch as desired (ON or AUTO.).
4. Set thermostat dial at desired temperature.
5. Set selector switch at HEAT or COOL. Check system refrigerant charge. See Refrigerant
Charging.
When recharging is necessa^ during heating or
cooling season, weigh in total charge indicated in
Table 6. (Charge must be weighed in during heating
season.) Remove any refrigerant remaining in system before recharging. If system has lost com plete charge, triple-evacuate system to 5000 microns (29.7 in. vacuum) before recharging. Service port connections are provided on liquid and suction line service valves for evacuation and charging (See Fig. 6 for correct service port location on cooling
and heating cycles.) Dial-a-charge charging cylinder is an accurate device used to recharge systems by weight. These cylinders are available at refrigeration supply firms.
Table 6 — Service Data
UNIT38QF 018 R-22 CHARGE (lb)
REFRIG CONTROL FAN
Cfm Rpm
Diam (in.)
024
030 036 042 048
5.7 6.1 6.7 7.4 8.7 AccuRater™ (Bypass Type)
2400 2750
840
20
060
9.3 9.8
4500
26

SERVICE

CM'llON: Unit has high-picssiire piping whicli ma\ also be lu)t to touch, cncrgi/.ed elec trical components and a rotating fan. Before ser\icing or checking unit, be sure all s\stem power is off and tubing is cool.
( \l ll()\ III pu\..il pei'oiul in, !i\. weai
satety glasses and glcues when handling
Do not overeharge system. \n o\erchargeean
cause compressor flooding.
Refrigerant Charging — The 38QF units contain
correct operating charge for complete system when connected to 28VQ, 40QB/ QH or 40AQ indoor units with 25 ft of tubing of recommended diameter. Charge adjustment is required on other systems. Adjust system charge for refrigerant line lengths and diameters that differ from 25 ft and 3/8 in. OD
(liquid line), respectively, using refrigerant weights
below. Twenty-five ft 3/8-in. OD tubing contains
14.4 oz of R-22. Add R-22 charge to system if liquid line is over 25 ft; remove charge if liquid line is shorter than 25 feet.
COOLING CYCLE
LIQUID LINE
DIAM (in.)
%
OUNCES OF R-22/FT LENGTH
OF LIQUID LINE
.58
AT SERVICE VALVE (CLG CYCLE) (BYPASSING)
piÌBilÌÌlBSB«Eip0IipÌ*®Ì5!SEBÌ
Fig. 6 — 38QF Refrigerant Flow Diagrams
SWITCH
Page 8
To check and/or adjust charging during cooling
season, use correct Cooling Cycle Charging Chart
(Fig. 7, 9, 11, 13, 15, 17, 19) and follow Charging
Chart Method below. The charging chart may also
be used as an alternate method of recharging system.
To check system operation during heating cycle, use correct Heating Cycle Operation Check Chart (Fig. 8, 10, 12, 14, 16, 18, 20).These charts indicate whether a correct relationship exists between system operating pressures and air temperatures entering indoor and outdoor units. If pressure and tempera
ture lines do not intersect on chart, the system re frigerant charge may not be correct or other system abnormalities may exist. Do not use Operation
Check Charts to adjust refrigerant charge. Weigh charge into system.
COOLING CYCLE CHARGING CHART METHOD
1. Operate unit a minimum of 10 minutes before checking charge, and after each charge
adjustment.
2. Measure suction pressure by attaching a gage to outdoor unit suction service port. (See Fig. 6 for correct service port location on cooling cycle.)
3. Measure outdoor (coil inlet) air dry-bulb tem perature with service thermometer.
4. Using a sling psychrometer, measure wet-bulb temperature of air entering indoor unit.
5. Refer to correct Charging Chart. Locate on curves where outdoor air dry-bulb and indoor
air wet-bulb temperature lines intersect.
6. From intersect point, project vertically down ward to chart suction pressure line. Compare
chart suction pressure to unit suction pressure (Step 2).
7. If unit suction pressure is lower than chart pres sure, add refrigerant to system until chart pressure is reached. If unit suction pressure is higher than chart pressure, remove refrigerant until chart pressure is reached.
Unit Single-Phase Compressors
COMPRESSORS OF THE SPLIT CAPACITOR (PSC) TYPE require an equalized system pressure to start. When supply voltage is within nameplate limit and compressor does not start, give com pressor a temporary capacitance boost. See Carrier Standard Service Techniques Manual, Chapter 2,
for details.
WARNING: C’apacilance boost or installation of start capacitor and slaii relay should be per formed b\ trained personnel. Improper pro cedure could cause personal injur\ or equipment

CHARGING AND PRESSURE CHECK CHARTS

160
66 68 70 72 74 76 78 80 82 84 86 88
PRESSURE AT SUCTION SERVICE VALVE (PSIG)
Fig. 7 — 38QF018 with 40AQ018,024,
28HQ,VQ018 or 024, 40FS075 with
28HQ,VQ042 Cooling Cycle Charging Chart
Fig. 8 — 38QF018 with 40AQ018,024,
28HQ,VQ018 or 024, 40FS075 with 28HQ,
VQ042 Heating Cycle Operation Check Chart
Page 9
COOLING CYCLE
CFM-860
320
m
62 f:
67 F
172 F
II5F
300
in
a.
lU
>
%
:WET BULB TEMP AIR
280
ENT INDOOR UNIT
o >
260
□:
UJ
to
o
■D
240
O
_l
^ 220
15
cn
</)
UJ
tc
Q.
200
180
160
:75F
66 68 70 72 74 76 78 80 82 84 86 88
PRESSURE AT SUCTION SERVICE VALVE (PSIG)
85 F^
DRY BULB TEMP AIR ENT OUTDOOR UNIT
Fig. 9 — 38QF024 with 40AQ024,030.
28HQ,VQ024 or 030, 40FS075 with
28HQ,VQ042 Cooling Cycle Charging Chart
105 F
95 F:
Fig. 10 — 38QF024 with 40AQ024,030,
28HQ,VQ024 or 030, 40FS075 with 28HQ,
VQ042 Heating Cycle Operation Check Chart
if)
Q.
UJ
%
UJ
O ui
V)
9
q:
3
05
O)
UJ
01
a.
CFM-1020
340
WET BULB TEMP AIR ENT INDOOR UNIT
5 320
300
^ 280
o 260
240
220
62 F
DRY BULB TEMP AIR: ENT OUTDOOR UNIT
85 F
200
75 F
180
66 70 74 78 82 86 90
PRESSURE AT SUCTION SERVICE VALVE(PSIG)
Fig. 11 — 38QF030 with 28AR036,
28HQ,VQ036 or 40AQ036, 40DQ030
Cooling Cycle Charging Chart
:67F:
95 F
72 F:
II5F±
I05F
Fig. 12 — 38QF030 with 28AR036,
28HQ,VQ036 or 40AQ036, 40DQ030
Heating Cycle Operation Check Chart
Page 10
'®° 70 74 78 82 86 90
PRESSURE AT SUCTION SERVICE VALVE (PSIG)
Fig 13 — 38QF036 with 28HQ.VQ042,
40AQ036 or 40QB/QH042
Cooling Cycle Charging Chart
Fig. 14 — 38QF036 with 28HQ,VQ042,
40AQ036 or 40QB/QH042
Heating Cycle Operation Check Chart
67 F
DRY BULB TEMP AIR: ENT OUTDOOR UNIT!
o 320
</)
0.
UJ >
%
UJ
o >
q:
UJ
CO a
o
UJ
o:
o
(/) u
a:
Q.
CFM-1400
340
WET BULB TEMP AIR ENT INDOOR UNIT
300
280
260
240
220
200
180
70 74 78 82 86 90 94
PRESSURE AT SUCTION SERVICE VALVE(PSIG)
62 F
75 F
Fig. 15 — 38QF042 with 28HQ.VQ048,
or 40QB/QH042,048
Cooling Cycle Charging Chart
85 F
72 f:
95 F:
II5F+
I05F
Fig. 16 — 38QF042 with 28HQ.VQ048,
or 40QB/QH042,048
Heating Cycle Operation Check Chart
10
Page 11
66 68 70 72 74 76 78 80 82 84 86 88
PRESSURE AT SUCTION SERVICE VALVE (PSIG)
Fig. 17 — 38QF048 with
40QB/QH048,060,062. 28HQ,VQ048 or060
Cooling Cycle Charging Chart
Fig. 18 — 38QF048 with
40QB/QH048,060,062, 28HQ,VQ048 or 060
Heating Cycle Operation Check Chart
Fig. 19 — 38QF060 with 40QB/QH060,062
Cooling Cycle Charging Chart
Fig. 20 — 38QB060 with 40QB/QH060,062
Heating Cycle Operation Check Chart
11
Page 12
Compressor Removal — See Table? for com
pressor information and Fig. 21 for component location. Shut off power to unit. Remove refrigerant from unit using refrigerant removal methods de scribed in Carrier Standard Service Techniques Manual, Chapter 1, Refrigerants.
Be sure system pressure is 0 psig before
proceeding.
Table 7 — Compressor Data (60 Hz)
UNIT 38QF
018
024 208-230/1
030 208-230/1 036 208-230/1 CRG1-0251-PFV 042 208-230/1 CRJ1-0301-PFV 048 060
*Refer to Carrier Service Parts Catalog for replacement com
pressor model numbers.
STRAINER VAPOR REVERSING
V/PH
230/1 H22B173ABCA
230/1 PC4616CD
230/1 PC6016BD
\ LINE VALVE
\
PRODUCTION COMPRESSOR
Model*
CRC2-0175-PFV
CRF1-0250-PFV
OUTDOOR COIL
Oil Recharge
Ounces
37 51 51 51 51 66 66
ACCUMULATOR
pull them thru the wire access opening into the coil section. Lift fan orifice/control ring after pinching and pressing down on 3 plastic pins of tube supports.
5. Remove louvered casing by taking out screws securing it to the cabinet and sliding it away
from the coil.
Using a midget tubing cutter, cut liquid and
6.
discharge lines on the coil and suction and dis charge lines at a convenient place near the com pressor for easy reassembly with copper slip couplings.
C.\LTJO\: F.xcvssivc movement of copper lines at compressor may cause a break where lines connect to condenser coil.
7. After plugging connections, remove condenser coil by pinching plastic pins of tube supports that extend into basepan and lift vertically. Set coil on a clean, flat surface.
8. Remove compressor holddown bolts and slide out compressor. Remove crankcase heater.
WARNING: For bra/ing and unbrazing have lire extinguisher and or quenching cloth available in case oil vapor ignites.
MUFFLER SOLENOID
COIL
HOT GAS DISCHARGE LINE
COMPRESSOR
Fig. 21 — Component Location
Follow safety codes. Wear safety glasses and
work gloves. Have quenching cloth available.
CATTIO.N; .'Mumimim tubing is used in unit coils. Do not o\erlieat or place c.xcessi\c .strain on lubinii or damce inav result.
Remove top cover as described in Installation,
1.
Step I. Disconnect high- and low-voltage field wiring
2.
and fan motor leads from capacitor and contactor.
Remove screws holding discharge grille in place.
3.
Lift grille from unit. Disconnect compressor leads (crankcase heater,
low-pressure switch, defrost thermostat and solenoid coil) from electrical components and
9. Carefully unbraze suction and discharge line piping stubs from compressor after noting posi tion of stubs to assist when reinstalling.
10. Install new compressor, placing crankcase heater around compressor. Be sure compressor holddown bolts are in place.
11. Replace coil; braze suction and discharge lines to compressor piping stubs (at points where cut. Step 6); rewire compressor and leak test.
12. Replace fan orifice/control ring; connect com
pressor wires after feeding them thru control ring; replace fan/grille assembly and rewire; connect high- and low-voltage power wiring; and replace louvered casing.
13. Replace top cover by running 4 screws into orifice loosely (2 on each side of unit) and tighten when cover is in place. Replace remain ing screws.
14. Evacuate and recharge system.
Filter Drier — Install field-supplied filter drier
(Table 3) in system liquid line when refrigerant system is opened for service as described under Compressor Removal. Position drier in liquid line at convenient location.
Pumpdown Procedure — The system may be
pumped down in order to make repairs on low side without losing complete refrigerant charge.
1. Attach pressure gage to suction service valve gage port.
2. Frontseat the liquid line valve.
12
Page 13
3. Start unit and run until suction pressure reaches 5 psig (see Caution).
4. Shut unit off and frontseat suction valve.
5. Vent remaining pressure to atmosphere.
C.Al'llOX; 3SQP unit coils will hold onl> lactoi>-supplied amount of refrigerant. Addi tional rd'rigeranl ma\ cause units to reliese
pressure thru internal pressuie relief sake (indi cated b\ a sudden rise of suetion pressure) be fore suction pressure reaehes 5 psig. [1 this occurs, shut off unit irnmediateK: Iront.seat suction \al\c and \ent remaining piessiire to

Unit Controls and Safety Devices

HIGH-PRESSURE RELIEF VALVE is located in compressor. Relief valve opens at a pressure differ ential of approximately 500 psig between suction (low side) and discharge (high side) to allow pressure equalization.
INTERNAL CURRENT AND TEMPERATURE SENSITIVE OVERLOAD resets automatically when internal compressor motor temperature drops to a safe level (overloads may require up to 45 minutes to reset). When an internal overload is sus pected of being open, check by using an ohmmeter or continuity tester. If necessary, refer to Carrier Standard Service Techniques Manual, Chapter 2,
for complete instructions. LIQUID LINE LOW-PRESSURE SWITCH
(LLPS) is connected in liquid line to work with compressor internal thermostat in providing loss-of­charge protection during the heating cycle. Control
is mounted on liquid line.
With a high-side leak, pressure gradually de
creases until low-pressure control stops the com pressor. (Low-pressure control settings are shown in Table 8.)
^ Table 8 — Pressure Switch Settings
UNIT
38QF
018 024 030 036 042 048 060
Cut-in
22 ±5 psig
LIQUID LINE
LOW-PRESSURE SWITCH
Cutout
7 ± 3 psig
With a low-side leak there is always some pressure in the liquid line. However, compressor motor tem perature increases because of insufficient suction
gas cooling. This causes internal thermostat to
actuate and stop compressor. When compressor stops, system pressure equalizes and contacts on
pressure control open. The compressor cannot re start until leak is repaired and system recharged.
CRANKCASE HEATER is connected across line side of contactor and operates continuously.
The purpose of the heater is to keep the crankcase
warm during the off cycle and thus prevent dilution
of the oil with refrigerant. This assures good lubri cation and prevents loss of oil from crankcase during start-up.
To energize crankcase heater, turn thermostat to
OFF position and close electrical disconnect to heat
pump.
If the electrical disconnect switch to the outside
unit has been off for an extended period of time, the
crankcase heater should be energized for 24 hours before starting the compressor.
DEFROST CONTROL, consisting of defrost control board and defrost thermostat, interrupts normal system heating operation every 90 minutes to defrost outdoor coil, if the coil saturated suction
temperature indicates freezing temperatures.
Defrost control simultaneously stops outdoor fan, energizes reversing valve solenoid to return system
to cooling cycle (outdoor unit as condenser, indoor unit as evaporator), and activates accessory electric heater.
For the heat pump to defrost, 2 conditions are
necessary:
1. Defrost timer contacts must be closed.
2. Refrigerant temperature from outdoor unit must be cold enough to cause defrost thermostat con tacts to close. Contacts close at 31 ±4 F.
Every 90 minutes of elapsed running time, the de frost timer contacts close for 10 seconds. If the defrost thermostat contacts are closed, the unit defrosts. The defrost timer limits defrosting period to 10 minutes. Normally, the frost is removed and the defrost thermostat contacts open to terminate defrosting before 10 minutes have elapsed. Defrost
thermostat contacts open at 80 ± 6 F liquid refrig erant temperature. When defrosting is terminated, the outdoor fan motor is energized and reversing valve solenoid is de-energized, returning unit to heating cycle.
HEAT PUMP CIRCUITS shown in Fig. 6 are re frigerant flow diagrams for heating and cooling cycles.
AccuRater™ (Bypass Type) Servicing — See
Fig. 22 for bypass type AccuRater components. The piston has a refrigerant metering hole thru it. The retainer forms a stop for the piston in the refrigerant bypass mode, and a sealing surface for liquid line flare connection. To check, clean or replace piston:
1. Shut off power to unit.
2. Pump unit down using Pumpdown Procedure described previously.
3. Remove liquid line flare connection from AccuRater.
4. Pull retainer out of body, being careful not to scratch flare sealing surface. If retainer does not pull out easily, carefully use Vise Grip pliers to remove retainer.
13
Page 14
rLARE NUT
FLARE CONNECTION
RETAINER
Fig. 22 — AccuRater™ (Bypass Type)
Components
5. Slide piston out by inserting a small soft wire, with small kinks, thru metering hole. Ensure metering hole, sealing surface around piston
cones and fluted portion of piston are not
damaged.
6. Clean piston refrigerant metering hole.
7. Replace retainer O-ring before reassembling by
pass type AccuRater. Carrier O-ring part no. is 99CC501052.
LIQUID LINE STRAINER (protects AccuRater)
made of wire mesh is located in the liquid line inside
38QF unit behind liquid line service valve. Liquid line is belled and sweat connected where strainer is located. If strainer is plugged, unsweat belled liquid line connection and replace strainer. See Fig. 21.
LEAKING SWEAT CONNECTION — Frontseat service valves and relieve refrigerant pressure in tubing. Clean and flux area around leak and apply low-temperature solder (430 F).
Condenser Fan Motor Removal
1. Shut off power to unit. Failure to do so may result in electric shock or injury from rotating
fan blade.
2. Remove top cover as described on page 2.
3. Disconnect fan motor leads from controls.
4. Remove 6 screws holding fan motor/discharge grille in place and lift assembly from unit.
5. Remove Carrier nameplate by straightening tabs.
6. Remove 4 nuts holding fan motor to discharge grille. Remove motor and leads.
7. Reverse procedure for reassembly. Before replac ing metal fan, be sure rain shield is in place on motor shaft. Seal with Permagum sealer around hub to prevent entry of water between hub and shaft. Make sure fan is positioned correctly as shown in Fig. 24.
MSCHARGl SPi.Lf
Rf (048- 060)
FROM DISCHARGE GRILLE
TO TOP OF FAN BLADE
■ .',‘J •-I .'.OF r.S'l'FW
MOTOR

Compatible Fitting Repair

LEAKING MECHANICAL CONNECTION —
Frontseat outdoor section service valves after reliev ing refrigerant pressure in system. Back locknut off Carrier Compatible Fitting onto tube. Cut fitting between threads and O-ring shown in Fig. 23. Remove tubing section remaining in threaded por tion of fitting. Discard locknut.
CARRIER
V ■■ .•
.........
Clean, flux, and insert new tube end into remain ing portion of Carrier Compatible Fitting. Wrap valve base in wet rag. Heat and apply low­temperature solder (430 F).
Fig. 24 — Outdoor Fan Position

MAINTENANCE

CM'IION: Before pertorming recoinmended maintenance, be sure unit main power switch is turned oil. Failure to do so ma\ result in electric shock or injtiiy from iota ting fan blade.

Lubrication

FAN MOTOR BEARINGS — Oiling holes are provided at each end of condenser fan motor. Re move fan motor and lubricate motor with 32 drops (16 drops per hole) of SAE-10 nondetergent oil at intervals described below.
a. Annually, when environment is very dirty,
ambient temperature is higher than 105 F, and average unit operating time exceeds 15 hours a day.
b. Every 3 years when environment is reasonably
clean, ambient temperature is less than 105 F and unit operating time averages 8 to 15 hours a day.
c. Every 5 years when environment is clean,
ambient temperature is less than 105 F and unit operating time averages less than 8 hours a day.
14
Page 15
COIL REPAIR — A flare-union coupling is used for E-coil repair. A kit is available, with instructions, thru Carrier Service Parts.
COMPRESSOR contains factory oil charge. If oil requires replenishment, see Table 7 for oil recharge and Carrier Standard Service Techniques Manual, Chapter 1, Refrigerants, page 1-21, for instructions. Use Carrier PP33-1, Texaco WFI-32 or Suniso3GS oil.
Coil Cleaning to be done at the beginning of each
cooling season or more often if required.
C.'M'TION: Fin damage or remo\al can result in higher operating costs or compressor damage. Do not use flame, high-pressure water, steam or volatile or corrosive cleaners »m fins and tubing. Follow these tnstruetions carefulh.
Contact voiii dealer i1 vou encounter problems.
1. Shut off power to unit.
2. Remove louvered casing by taking out 16 screws securing it to the cabinet and sliding it away from the coil.
Clean coil using vacuum cleaner and its crevice
3. tool (see Fig. 25). Work crevice tool vertically making sure tool only touches dirt on fins. To
prevent fin removal, do not “scrub”fins with tool
or move tool horizontally.
6. Reinstall louvered casing being careful not to damage coil.
7. Restore power to unit.
4. If oil deposits are present, spray coil with house hold detergent (Fantastic, Lestoil, 409, or any similar type). Wait 10 minutes then proceed to step 5.
5. Using garden hose, spray coil vertically down ward with a constant stream of water at moderate pressure (see Fig. 26). Keep nozzle at a 15 to 20 degree angle, about 3 in. from coil face and 18 in.
from tube. Spray so debris is washed out and away from coil.
15
Page 16
ON
TROUBLESHOOTING CHART — COOLING CYCLE
Page 17
TROUBLESHOOTING CHART — HEATING CYCLE
Page 18
For replacement items use Carrier Specified Parts.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
1 4
Book
Tab 5a
5a
Form 38QF-2SI Supersedes 38QF-1 SIM
Printed in U.S.A.
4-83
PC 101 Catalog No. 563-816
Loading...