Installation and servicing of air conditioning
equipment can be hazardous due to system pressure
and electrical components. Only trained and quali
fied service personnel should install, repair or serv
ice air conditioning equipment.
Untrained personnel can perform basic main
tenance functions of cleaning coils and cleaning
and replacing filters. All other operations should be
performed by trained service personnel. When
working on air conditioning equipment, observe
precautions in the literature, tags and labels attached
to the unit and other safety precautions that may
apply.
Follow all safety codes. Wear safety glasses and
work gloves. Use quenching cloth for brazing oper
ations. Have fire extinguisher available for all braz
ing operations.
W.ARNING: Before performing scr\icc or
maintenance operations on sxstem. turn ofl
main powci switches to indoor unit and out
door unil. 1 urn ofl acccssoiA heater power
switch if applicable, riectrical shock could cause
personal itijur\.
INSTALLATION
Step 1 — Check Equipment and Jobsite
UNPACK UNIT — Move to final location. Lift
carton off, taking special care not to damage service
valves or grilles.
INSPECT EQUIPMENT — File claim with ship
ping company if shipment is damaged or incomplete.
COMPLETE OR CONSIDER SYSTEM RE
QUIREMENTS before installing the 38QF.
Consult local building codes and National
Electrical Code (NEC) for special installation
requirements.
When installing, allow sufficient space for air
flow clearance, wiring, refrigerant piping and serv
icing. Position so water or ice from roof cannot drop
directly on top of unit.
Make provisions for condensate drainage and
defrost water disposal whether unit is installed on
ground or roof. (Ensure unit basepan drainage holes
are not blocked.) See Step 2 for details. Roof in
stallation method for 38QF depends on building
construction and special requirements of local
codes. Be sure that roof can support unit weight.
It is recommended that 38QF units be used with
Carrier approved indoor sections; see Table 1.
System Refrigerant Control on 38QF units and
matching Carrier indoor units is a factory-installed
AccuRater™ device (bypass type). Bypass-type
AccuRater components are discussed in the service
section of this booklet. The AccuRater piston has a
refrigerant metering hole thru it and is field replace
able. Table 1 indicates indoor units for which the
required replacement piston is factory supplied with
specified 38QF outdoor unit. Replace piston as
Top Cover Removal — Top cover can be removed
for wiring or servicing heat pump. Loosen decora
tive strip and slide down off screw heads. Remove
3 screws in connector plate and 2 screws on front of
unit. Loosen remaining 4 screws. Lift top from unit
(see Fig. 1).
Step 2 — Mount Outdoor Heat Pump
ON THE GROUND: MOUNT UNIT ON A
SOLID, LEVEL CONCRETE PAD (see Fig. I).
4-0"0VERHEAD SPACE REQUIRED
FOR SERVICE AND AIRFLOW
7"
8
DIAM HOLE
FOR CONTROL
WIRING
Swing 3 legs down and lock in position, except when
using accessory rack. Use accessory heat pump rack
(Fig. 2) in areas where prolonged subfreezing tem
peratures or heavy snow occur. (Refer to installation
instructions included with rack.) Drainage holes in
unit base must not be obstructed.
AIRFLOW AND
SERVICE
CLEARANCE
LIQUID VALVE SERVICE PORT / VAPOR VALVE SERVICE PORT
AIRFLOW SUCTION SERVICE PORT
CONCRETE MOUNTING PAD
Fig. 1 — Dimensions, Connections and
Mounting Pad (Refer to Table 2)
Fig. 2 — Accessory Mounting Rack
Table 1 — Carrier Approved 38QF Systems
OUTDOOR
UNIT
38QF
018
02446
030
036
042
048
060
^Factory-supplied piston packages shipped in outdoor unit. Replace remain
ing indoor pistons with size indicated.
REQUIRED
OUTDOOR
PISTON
SIZE
42
59
61
63
7640QB/QH06086*
82
INDOOR
UNIT
MODEL &
SIZE
40AQ018
28HQ/VQ018
40AQ024
28HQ/VQ024
40FS075,28HQ/VQ042
40AQ024
28HQ/VQ024
40AQ030
28HQ/VQ030
40FS075,28HQ/VQ042
40AQ030
28HQ/VQ030
40DQ030
40AQ036
28HQ/VQ036
40AQ036
28HQ/VQ036
40QB/QH042
28HQ/VQ042
40QB/QH042
28HQ/VQ048
40QB/QH048
40QB/QH04884
28HQ/VQ04884
40QB/QH062
28HQ/VQ060
40QB/QH060
40QB/QH062
REQUIRED
INDOOR
PISTON
SIZE
61
67
67
70*
70*
70
70
73*
73*
76
78
78
86*
86*
96
52
52
55*
55*
59
59
61*
61*
65
67
Page 3
ON THE ROOF; MOUNT UNIT ON A LEVEL
PLATFORM OR FRAME: Proper precaution
must be taken for support of unit in roof design.
Elevate unit for proper clearance as described under
ground installation above. Plan roof design and
water drainage to prevent unit from setting in water.
Flash all roof openings to prevent leaks.
Roof mounted unit exposed to winds above 5 mph
may require protective wind baffles (field fabricated)
to achieve adequate defrost.
Step 3 — Make Piping Connections — Heat
pumps may be connected to indoor sections using
Carrier accessory tubing package (Table 3) or field-
supplied tubing of refrigerant grade, correct size and
condition (Table 2). For requirements beyond
50 ft obtain information from local Carrier
distributor.
-> Table 3 — Accessories
Table 2 — Installation Data (Fig. 1)
UNIT 38QF
OPER WT(lb)
DIMEN (ft-in.)
DIam (A)
Height (B)
Mtg Pad
(Diam X Thick)*
(C)
(D)
REFRIG CONN (in.)
Suction (ODF)
Liquid (ODF)
REFRIG LINES (in.)
Suction (ODF)
Liquid (ODF)
“■Mounting pad is fieid suppiied,
fMay use Vs-'m. accessory tubing package (slight capacity loss). See Tabie 3.
Outdoor Thermostat (Six 38QB900041)
Optimizer Control Outdoor Thermostat — Ref HH22AG110 (Six 38CQ900161)
Optimizer II Control Assembly — Use with HH22AG110 outdoor thermostat.
WARNING: If unclcrsi7ed. damaged or
elliptiv.-all\-s!iapL'd uibing is used when making
Compatible bitting, leaks ma\ result.
If 1-1/8 in. tubing is used, braze it to the accessory
1-1/8 X 3/4-in. suction connection adapter (Carrier
Part No. 28VQ900011) or to a correctly sized fieldsupplied adapter, then make Compatible Fitting
connections. Isolate interconnecting tubing from
framing and ductwork or where tubing runs thru
stud spaces, enclosed ceilings or pipe chases. Use
isolation type hangers. Fig. 3, since rigid fastening
transmits pulsations to structure creating objec
tionable sound.
^ ( \l 1 ION. IK) \OI Ml \<\ MORI I II \\
'' I I ()l I INI SI I IN (.ROl N1). II .m> '•ac
tion of liucsel is burictl. there must be b-in.
\ertical rise to the \al\e connections on the
outdoor unit. If more than the recommended
length i.s buried, refrigerant ma\ migrate to the
eooler buried .section during extended periods of
unit shutdown, causing relrigerant slugging and
possibh compressor damage at start-up.
A capacity reduction will result if accessory tub
ing is used in 38QF systems. For example, when a
25-ft 7/8-in. accessory package is used, there is a
capacity reduction of 1-1/2 percent.
When other than 25 ft of interconnecting tubing
is used, follow special requirements described in
Refrigerant Charging. Do not use less than 10 ft of
interconnecting tubing. Do not cut 7/8-in. suction
line. Bend or coil to fit.
Do not use damaged or contaminated tubing.
Always evacuate or purge evaporator coil and
tubing system (use field-supplied refrigerant, not
unit refrigerant).
When making tubing connections, be sure to
provide clearance at unit for electrical connections.
REPLACE THE ACCURATER™ REFRIG
ERANT CONTROL PISTON IN THE INDOOR
COIL AS REQUIRED before connecting refrig
erant lines. See Table 1. Correct piston is supplied
with 38QF unit. For piston replacement instruc
tions, see AccuRater Servicing on page 13.
CONNECT REFRIGERANT LINES to fittings on
unit suction and liquid service valves (Fig. 1).
Liquid service valve has flare fitting; suction service
valve has Compatible Fitting. Make suction line
connection first. Slide flare nut on liquid line, then
flare and connect liquid line. Use a maximum
torque of 15 ft-lb to tighten flare nut. (Do not dis
assemble AccuRater.) Unit Compatible Fitting
permits mechanical or sweat connection as de
scribed below.
When a 7/8-in. field-supplied suction line is
used on 38QF, a field-supplied 3/4-in. to 7/8-in.
suction line adapter must be provided (not required
if 38LS accessory tubing is used).
When a 1-1/ 8 in. field-supplied suction line is used
on 38QF, use accessory adapter 28VQ900011 or
other field-supplied connection. Sweat connect re
frigerant suction line to 1-1/8 in. end of adapter.
Connect 3/4-in. end of adapter to unit suction line
Compatible Fitting.
Mechanical Connection to Compatible Fitting
(Mate one set of connections at a time.)
1. Loosen nut on Compatible Fitting one turn. Do
not remove.
2. Remove plug and be sure 0-ring is in the groove
inside the Compatible Fitting.
3. Cut tubing to correct length.
4. Insert tube into Compatible Fitting until it
bottoms.
5. Tighten nut until it bottoms on back coupler
flange. Keep tube bottomed in Compatible
Fitting while tightening nut.
Sweat Connection to Compatible Fitting (Use
refrigerant grade tubing.)
1. Remove locking nut, rubber O-ring and Schrader
core from valve.
2. Cut tubing to correct length.
3. Insert tube into Compatible Fitting. Wrap top
and bottom of service valves in wet cloth to pre
vent damage by heat. Solder with low tempera
ture (430 F) silver alloy solder.
4. Replace Schrader core.
5. Evacuate or purge system with field-supplied
refrigerant.
Step 4 — Make Electrical Connections — Field
wiring must comply with local and national fire,
safety and electrical codes. Voltage to unit must be
within permissible limits indicated on nameplate.
Contact local power company for correction of
improper line voltage.
W.AR.NTNG: Operation of units on improper
line \oliagc constiiiitcs abuse and could affect
Carrier warrantx. See fable4.
Do not apply units in system where voltage may
fluctuate above or below permissible limits.
Page 5
Table 4 — Electrical Data (60 Hz)
OPER
UNIT
38QF
018
024
030
036
042
048
060
AWG — American Wire Gage
FLA — Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps
RLA — Rated Load Amps
V/PH
230/1
208-230/1
230/1
VOLTAGE*
Max
254
254
MinLRARLA
197
207
COMPR
50
54
6917.7
75
90
101
130
FAN
FLA
10.81430
13.0
16.81050
20.0
21.2
28.6
1.1
1.7
When making electrical connections, provide
clearance at unit for refrigerant piping connections.
See Table 4 for recommended wire and fuse sizes.
INSTALL A BRANCH CIRCUIT DISCONNECT
PER NEC of adequate size to handle unit starting
current. Provide a separate disconnect for outdoor
unit, indoor unit and for each accessory electric
heater circuit as required. (See Indoor Unit and
Electric Heater Installation, Start-Up and Service
Instructions.) Locate disconnect(s) within sight
from and readily accessible from the unit; per sec
tion 440-14 of National Electrical Code (NEC).
ROUTE LINE POWER LEADS INTO UNIT —
Extend leads from disconnect thru power wiring
hole provided (see Fig. 1) and into unit splice area.
Remove top cover to gain access to unit wiring.
CONNECT GROUND LEAD AND POWER
WIRING — Connect ground lead to a ground lug in
control box for safety. Then connect power wiring.
See Fig. 4. Splice line power leads to yellow and
black pigtails. Use wire nuts and tape at each con
nection. Connect unit wiring to copper wire only.
SEE INDOOR UNIT AND ELECTRIC HEATER
INSTALLATION, START-UP AND SERVICE
INSTRUCTIONS for line power wiring details. All
control wiring is shown in this booklet.
BRANCH CIRCUIT
Min Wire
(AWG)t
12
1048
104310
10
8
*Permissible limits of the voltage range at which the unit will
operate satisfactorily.
tCopper wire sizes based on 60 C. Use copper wire only.
fRequired when using nonmetallic conduit.
**Time-delay fuse
Max WireMin Gnd
(ft)
41
39
46
Wire Size$
14
12
10
10
10
10
CONNECT CONTROL POWER WIRING (24 V)
— Extend wiring thru hole provided (Fig. 1) and
into low-voltage section of unit control ring.
Connect leads to control wiring terminal board as
shown in Fig. 5.
Use indoor unit transformer as 24-v supply for
system. At least a 60-va transformer is recom
mended. Carrier approved indoor units are equipped
with a 60-va transformer. See indoor unit data.
Use Carrier accessory indoor thermostat with
subbase, Table 3.
START-UP
The 38QF unit is equipped with a crankcase
heater. It is recommended that heater be energized a
minimum of 24 hours before starting unit. To ener
gize heater only, turn the thermostat to OFF posi
tion and close electrical disconnect to heat pump.
Heat Anticipator Settings for Room Thermo
stat (HH07AT171) — Set anticipator settings for
room thermostat according to Table 5. These set
tings may be changed slightly to provide a greater
degree of comfort for a particular installation.
*Transformer (60 va) located in cooling control kit or electric heater.
fRemove factory-installed jumper (Connection B) when installing outdoor thermostats (ODT).
Fig. 5 — Control Circuit Connections
Accessory Outdoor Thermostat provides adjust
able outdoor control of accessory electric heater.
This thermostat makes contact when a drop in out
door temperature occurs. It energizes a stage of elec
tric heat when the outdoor temperature setting is
reached, provided the room thermostat is on the
second stage of heating. One outdoor thermostat is
recommended for each stage of electric heat after the
first stage. Set the outdoor thermostat(s) progres
sively lower for each stage. Refer to heat load of
building and unit capacity to determine the correct
outdoor thermostat settings.
The accessory supplemental heat relay is required
when 2 outdoor thermostats are used. It is auto
matically energized by the manually operated sup
plemental heat switch in the indoor thermostat
subbase. The thermostat locks out compressor and
the relay bypasses the outdoor thermostats for
electric heater operation during heat pump shut
down. When one outdoor thermostat is used a
supplemental heat relay is not required. The sup
plemental heat switch in the indoor thermostat
subbase bypasses outdoor thermostat, locks out
compressor and activates electric heater.
Page 7
MOUNT OUTDOOR THERMOSTAT on control
ring, to the left of the low-voltage control connec
tion. See Fig. 1.
Attach brackets with short sheet metal screws to
avoid contact with coil. Leave capillary tube coiled
in control compartment making sure it is clear of all
electrical connections and sharp metal edges.
MOUNT SUPPLEMENTAL HEAT RELAY in
convenient location on indoor unit. Attach with
sheet metal screw.
To Start Unit — (Make sure crankcase heater
has been energized for 24 hours.) Adjust the thermo
stat as follows:
1. Set selector switch at OFF.
2. Turn on main disconnect switch(es) to indoor
and outdoor units.
3. Set fan switch as desired (ON or AUTO.).
4. Set thermostat dial at desired temperature.
5. Set selector switch at HEAT or COOL.
Check system refrigerant charge. See Refrigerant
Charging.
When recharging is necessa^ during heating or
cooling season, weigh in total charge indicated in
Table 6. (Charge must be weighed in during heating
season.) Remove any refrigerant remaining in
system before recharging. If system has lost com
plete charge, triple-evacuate system to 5000 microns
(29.7 in. vacuum) before recharging. Service port
connections are provided on liquid and suction line
service valves for evacuation and charging (See
Fig. 6 for correct service port location on cooling
and heating cycles.) Dial-a-charge charging cylinder
is an accurate device used to recharge systems by
weight. These cylinders are available at refrigeration
supply firms.
Table 6 — Service Data
UNIT38QF018
R-22 CHARGE (lb)
REFRIG CONTROL
FAN
Cfm
Rpm
Diam (in.)
024
030036042048
5.76.16.77.48.7
AccuRater™ (Bypass Type)
24002750
840
20
060
9.39.8
4500
26
SERVICE
CM'llON: Unit has high-picssiire piping
whicli ma\ also be lu)t to touch, cncrgi/.ed elec
trical components and a rotating fan. Before
ser\icing or checking unit, be sure all s\stem
power is off and tubing is cool.
( \l ll()\ III pu\..il pei'oiul in, !i\. weai
satety glasses and glcues when handling
Do not overeharge system. \n o\erchargeean
cause compressor flooding.
Refrigerant Charging — The 38QF units contain
correct operating charge for complete system when
connected to 28VQ, 40QB/ QH or 40AQ indoor
units with 25 ft of tubing of recommended diameter.
Charge adjustment is required on other systems.
Adjust system charge for refrigerant line lengths and
diameters that differ from 25 ft and 3/8 in. OD
(liquid line), respectively, using refrigerant weights
below. Twenty-five ft 3/8-in. OD tubing contains
14.4 oz of R-22. Add R-22 charge to system if liquid
line is over 25 ft; remove charge if liquid line is
shorter than 25 feet.
be used as an alternate method of recharging system.
To check system operation during heating cycle,
use correct Heating Cycle Operation Check Chart
(Fig. 8, 10, 12, 14, 16, 18, 20).These charts indicate
whether a correct relationship exists between system
operating pressures and air temperatures entering
indoor and outdoor units. If pressure and tempera
ture lines do not intersect on chart, the system re
frigerant charge may not be correct or other system
abnormalities may exist. Do not use Operation
Check Charts to adjust refrigerant charge. Weigh
charge into system.
COOLING CYCLE CHARGING CHART
METHOD
1. Operate unit a minimum of 10 minutes before
checking charge, and after each charge
adjustment.
2. Measure suction pressure by attaching a gage to
outdoor unit suction service port. (See Fig. 6 for
correct service port location on cooling cycle.)
3. Measure outdoor (coil inlet) air dry-bulb tem
perature with service thermometer.
4. Using a sling psychrometer, measure wet-bulb
temperature of air entering indoor unit.
5. Refer to correct Charging Chart. Locate on
curves where outdoor air dry-bulb and indoor
air wet-bulb temperature lines intersect.
6. From intersect point, project vertically down
ward to chart suction pressure line. Compare
chart suction pressure to unit suction pressure
(Step 2).
7. If unit suction pressure is lower than chart pres
sure, add refrigerant to system until chart
pressure is reached. If unit suction pressure is
higher than chart pressure, remove refrigerant
until chart pressure is reached.
Unit Single-Phase Compressors
COMPRESSORS OF THE SPLIT CAPACITOR
(PSC) TYPE require an equalized system pressure
to start. When supply voltage is within nameplate
limit and compressor does not start, give com
pressor a temporary capacitance boost. See Carrier
Standard Service Techniques Manual, Chapter 2,
for details.
WARNING: C’apacilance boost or installation
of start capacitor and slaii relay should be per
formed b\ trained personnel. Improper pro
cedure could cause personal injur\ or equipment
CHARGING AND PRESSURE CHECK CHARTS
160
66 68 70 72 74 76 78 80 82 84 86 88
PRESSURE AT SUCTION SERVICE VALVE (PSIG)
Fig. 7 — 38QF018 with 40AQ018,024,
28HQ,VQ018 or 024, 40FS075 with
28HQ,VQ042 Cooling Cycle Charging Chart
Fig. 8 — 38QF018 with 40AQ018,024,
28HQ,VQ018 or 024, 40FS075 with 28HQ,
VQ042 Heating Cycle Operation Check Chart
Page 9
COOLING CYCLE
CFM-860
320
m
62 f:
67 F
172 F
II5F
300
in
a.
lU
>
%
:WET BULB TEMP AIR
280
ENT INDOOR UNIT
o
>
260
□:
UJ
to
o
■D
240
O
_l
^ 220
15
cn
</)
UJ
tc
Q.
200
180
160
:75F
66 68 70 72 74 76 78 80 82 84 86 88
PRESSURE AT SUCTION SERVICE VALVE (PSIG)
85 F^
DRY BULB TEMP AIR
ENT OUTDOOR UNIT
Fig. 9 — 38QF024 with 40AQ024,030.
28HQ,VQ024 or 030, 40FS075 with
28HQ,VQ042 Cooling Cycle Charging Chart
105 F
95 F:
Fig. 10 — 38QF024 with 40AQ024,030,
28HQ,VQ024 or 030, 40FS075 with 28HQ,
VQ042 Heating Cycle Operation Check Chart
if)
Q.
UJ
%
UJ
O
ui
V)
9
q:
3
05
O)
UJ
01
a.
CFM-1020
340
WET BULB TEMP AIR
ENT INDOOR UNIT
5 320
300
^ 280
o 260
240
220
62 F
DRY BULB TEMP AIR:
ENT OUTDOOR UNIT
85 F
200
75 F
180
66 70 74 78 82 86 90
PRESSURE AT SUCTION SERVICE VALVE(PSIG)
Fig. 11 — 38QF030 with 28AR036,
28HQ,VQ036 or 40AQ036, 40DQ030
Cooling Cycle Charging Chart
:67F:
95 F
72 F:
II5F±
I05F
Fig. 12 — 38QF030 with 28AR036,
28HQ,VQ036 or 40AQ036, 40DQ030
Heating Cycle Operation Check Chart
Page 10
'®° 70 74 78 82 86 90
PRESSURE AT SUCTION SERVICE VALVE (PSIG)
Fig 13 — 38QF036 with 28HQ.VQ042,
40AQ036 or 40QB/QH042
Cooling Cycle Charging Chart
Fig. 14 — 38QF036 with 28HQ,VQ042,
40AQ036 or 40QB/QH042
Heating Cycle Operation Check Chart
67 F
DRY BULB TEMP AIR:
ENT OUTDOOR UNIT!
o 320
</)
0.
UJ
>
%
UJ
o
>
q:
UJ
CO
a
o
UJ
o:
o
(/)
u
a:
Q.
CFM-1400
340
WET BULB TEMP AIR
ENT INDOOR UNIT
300
280
260
240
220
200
180
70 74 78 82 86 90 94
PRESSURE AT SUCTION SERVICE VALVE(PSIG)
62 F
75 F
Fig. 15 — 38QF042 with 28HQ.VQ048,
or 40QB/QH042,048
Cooling Cycle Charging Chart
85 F
72 f:
95 F:
II5F+
I05F
Fig. 16 — 38QF042 with 28HQ.VQ048,
or 40QB/QH042,048
Heating Cycle Operation Check Chart
10
Page 11
66 68 70 72 74 76 78 80 82 84 86 88
PRESSURE AT SUCTION SERVICE VALVE (PSIG)
Fig. 17 — 38QF048 with
40QB/QH048,060,062. 28HQ,VQ048 or060
Cooling Cycle Charging Chart
Fig. 18 — 38QF048 with
40QB/QH048,060,062, 28HQ,VQ048 or 060
Heating Cycle Operation Check Chart
Fig. 19 — 38QF060 with 40QB/QH060,062
Cooling Cycle Charging Chart
Fig. 20 — 38QB060 with 40QB/QH060,062
Heating Cycle Operation Check Chart
11
Page 12
Compressor Removal — See Table? for com
pressor information and Fig. 21 for component
location. Shut off power to unit. Remove refrigerant
from unit using refrigerant removal methods de
scribed in Carrier Standard Service Techniques
Manual, Chapter 1, Refrigerants.
*Refer to Carrier Service Parts Catalog for replacement com
pressor model numbers.
STRAINER VAPOR REVERSING
V/PH
230/1H22B173ABCA
230/1PC4616CD
230/1PC6016BD
\ LINE VALVE
\
PRODUCTION COMPRESSOR
Model*
CRC2-0175-PFV
CRF1-0250-PFV
OUTDOOR COIL
Oil Recharge
Ounces
37
51
51
51
51
66
66
ACCUMULATOR
pull them thru the wire access opening into the
coil section. Lift fan orifice/control ring after
pinching and pressing down on 3 plastic pins of
tube supports.
5. Remove louvered casing by taking out screws
securing it to the cabinet and sliding it away
from the coil.
Using a midget tubing cutter, cut liquid and
6.
discharge lines on the coil and suction and dis
charge lines at a convenient place near the com
pressor for easy reassembly with copper slip
couplings.
C.\LTJO\: F.xcvssivc movement of copper
lines at compressor may cause a break where
lines connect to condenser coil.
7. After plugging connections, remove condenser
coil by pinching plastic pins of tube supports
that extend into basepan and lift vertically. Set
coil on a clean, flat surface.
8. Remove compressor holddown bolts and slide
out compressor. Remove crankcase heater.
WARNING: For bra/ing and unbrazing
have lire extinguisher and or quenching
cloth available in case oil vapor ignites.
MUFFLER SOLENOID
COIL
HOT GAS
DISCHARGE LINE
COMPRESSOR
Fig. 21 — Component Location
Follow safety codes. Wear safety glasses and
work gloves. Have quenching cloth available.
CATTIO.N; .'Mumimim tubing is used in unit
coils. Do not o\erlieat or place c.xcessi\c .strain
on lubinii or damce inav result.
Remove top cover as described in Installation,
1.
Step I.
Disconnect high- and low-voltage field wiring
2.
and fan motor leads from capacitor and
contactor.
Remove screws holding discharge grille in place.
3.
Lift grille from unit.
Disconnect compressor leads (crankcase heater,
low-pressure switch, defrost thermostat and
solenoid coil) from electrical components and
9. Carefully unbraze suction and discharge line
piping stubs from compressor after noting posi
tion of stubs to assist when reinstalling.
10. Install new compressor, placing crankcase
heater around compressor. Be sure compressor
holddown bolts are in place.
11. Replace coil; braze suction and discharge lines
to compressor piping stubs (at points where cut.
Step 6); rewire compressor and leak test.
12. Replace fan orifice/control ring; connect com
pressor wires after feeding them thru control
ring; replace fan/grille assembly and rewire;
connect high- and low-voltage power wiring;
and replace louvered casing.
13. Replace top cover by running 4 screws into
orifice loosely (2 on each side of unit) and
tighten when cover is in place. Replace remain
ing screws.
(Table 3) in system liquid line when refrigerant
system is opened for service as described under
Compressor Removal. Position drier in liquid line
at convenient location.
Pumpdown Procedure — The system may be
pumped down in order to make repairs on low side
without losing complete refrigerant charge.
1. Attach pressure gage to suction service valve
gage port.
2. Frontseat the liquid line valve.
12
Page 13
3. Start unit and run until suction pressure reaches
5 psig (see Caution).
4. Shut unit off and frontseat suction valve.
5. Vent remaining pressure to atmosphere.
C.Al'llOX; 3SQP unit coils will hold onl>
lactoi>-supplied amount of refrigerant. Addi
tional rd'rigeranl ma\ cause units to reliese
pressure thru internal pressuie relief sake (indi
cated b\ a sudden rise of suetion pressure) be
fore suction pressure reaehes 5 psig. [1 this
occurs, shut off unit irnmediateK: Iront.seat
suction \al\c and \ent remaining piessiire to
Unit Controls and Safety Devices
HIGH-PRESSURE RELIEF VALVE is located in
compressor. Relief valve opens at a pressure differ
ential of approximately 500 psig between suction
(low side) and discharge (high side) to allow pressure
equalization.
INTERNAL CURRENT AND TEMPERATURE
SENSITIVE OVERLOAD resets automatically
when internal compressor motor temperature drops
to a safe level (overloads may require up to 45
minutes to reset). When an internal overload is sus
pected of being open, check by using an ohmmeter
or continuity tester. If necessary, refer to Carrier
Standard Service Techniques Manual, Chapter 2,
for complete instructions.
LIQUID LINE LOW-PRESSURE SWITCH
(LLPS) is connected in liquid line to work with
compressor internal thermostat in providing loss-ofcharge protection during the heating cycle. Control
is mounted on liquid line.
With a high-side leak, pressure gradually de
creases until low-pressure control stops the com
pressor. (Low-pressure control settings are shown
in Table 8.)
^ Table 8 — Pressure Switch Settings
UNIT
38QF
018
024
030
036
042
048
060
Cut-in
22 ±5 psig
LIQUID LINE
LOW-PRESSURE SWITCH
Cutout
7 ± 3 psig
With a low-side leak there is always some pressure
in the liquid line. However, compressor motor tem
perature increases because of insufficient suction
gas cooling. This causes internal thermostat to
actuate and stop compressor. When compressor
stops, system pressure equalizes and contacts on
pressure control open. The compressor cannot re
start until leak is repaired and system recharged.
CRANKCASE HEATER is connected across line
side of contactor and operates continuously.
The purpose of the heater is to keep the crankcase
warm during the off cycle and thus prevent dilution
of the oil with refrigerant. This assures good lubri
cation and prevents loss of oil from crankcase
during start-up.
To energize crankcase heater, turn thermostat to
OFF position and close electrical disconnect to heat
pump.
If the electrical disconnect switch to the outside
unit has been off for an extended period of time, the
crankcase heater should be energized for 24 hours
before starting the compressor.
DEFROST CONTROL, consisting of defrost
control board and defrost thermostat, interrupts
normal system heating operation every 90 minutes
to defrost outdoor coil, if the coil saturated suction
temperature indicates freezing temperatures.
Defrost control simultaneously stops outdoor fan,
energizes reversing valve solenoid to return system
to cooling cycle (outdoor unit as condenser, indoor
unit as evaporator), and activates accessory electric
heater.
For the heat pump to defrost, 2 conditions are
necessary:
1. Defrost timer contacts must be closed.
2. Refrigerant temperature from outdoor unit must
be cold enough to cause defrost thermostat con
tacts to close. Contacts close at 31 ±4 F.
Every 90 minutes of elapsed running time, the de
frost timer contacts close for 10 seconds. If the
defrost thermostat contacts are closed, the unit
defrosts. The defrost timer limits defrosting period
to 10 minutes. Normally, the frost is removed and
the defrost thermostat contacts open to terminate
defrosting before 10 minutes have elapsed. Defrost
thermostat contacts open at 80 ± 6 F liquid refrig
erant temperature. When defrosting is terminated,
the outdoor fan motor is energized and reversing
valve solenoid is de-energized, returning unit to
heating cycle.
HEAT PUMP CIRCUITS shown in Fig. 6 are re
frigerant flow diagrams for heating and cooling
cycles.
AccuRater™ (Bypass Type) Servicing — See
Fig. 22 for bypass type AccuRater components. The
piston has a refrigerant metering hole thru it. The
retainer forms a stop for the piston in the refrigerant
bypass mode, and a sealing surface for liquid line
flare connection. To check, clean or replace piston:
1. Shut off power to unit.
2. Pump unit down using Pumpdown Procedure
described previously.
3. Remove liquid line flare connection from
AccuRater.
4. Pull retainer out of body, being careful not to
scratch flare sealing surface. If retainer does not
pull out easily, carefully use Vise Grip pliers to
remove retainer.
13
Page 14
rLARE NUT
FLARE
CONNECTION
RETAINER
Fig. 22 — AccuRater™ (Bypass Type)
Components
5. Slide piston out by inserting a small soft wire,
with small kinks, thru metering hole. Ensure
metering hole, sealing surface around piston
cones and fluted portion of piston are not
damaged.
6. Clean piston refrigerant metering hole.
7. Replace retainer O-ring before reassembling by
pass type AccuRater. Carrier O-ring part no. is
99CC501052.
LIQUID LINE STRAINER (protects AccuRater)
made of wire mesh is located in the liquid line inside
38QF unit behind liquid line service valve. Liquid
line is belled and sweat connected where strainer is
located. If strainer is plugged, unsweat belled liquid
line connection and replace strainer. See Fig. 21.
LEAKING SWEAT CONNECTION — Frontseat
service valves and relieve refrigerant pressure in
tubing. Clean and flux area around leak and apply
low-temperature solder (430 F).
Condenser Fan Motor Removal
1. Shut off power to unit. Failure to do so may
result in electric shock or injury from rotating
fan blade.
2. Remove top cover as described on page 2.
3. Disconnect fan motor leads from controls.
4. Remove 6 screws holding fan motor/discharge
grille in place and lift assembly from unit.
5. Remove Carrier nameplate by straightening tabs.
6. Remove 4 nuts holding fan motor to discharge
grille. Remove motor and leads.
7. Reverse procedure for reassembly. Before replac
ing metal fan, be sure rain shield is in place on
motor shaft. Seal with Permagum sealer around
hub to prevent entry of water between hub and
shaft. Make sure fan is positioned correctly as
shown in Fig. 24.
MSCHARGl SPi.Lf
Rf (048- 060)
FROM DISCHARGE GRILLE
TO TOP OF FAN BLADE
■ .',‘J •-I .'.OF r.S'l'FW
MOTOR
Compatible Fitting Repair
LEAKING MECHANICAL CONNECTION —
Frontseat outdoor section service valves after reliev
ing refrigerant pressure in system. Back locknut off
Carrier Compatible Fitting onto tube. Cut fitting
between threads and O-ring shown in Fig. 23.
Remove tubing section remaining in threaded por
tion of fitting. Discard locknut.
CARRIER
V ■■ .•
.........
Clean, flux, and insert new tube end into remain
ing portion of Carrier Compatible Fitting. Wrap valve base in wet rag. Heat and apply lowtemperature solder (430 F).
Fig. 24 — Outdoor Fan Position
MAINTENANCE
CM'IION: Before pertorming recoinmended
maintenance, be sure unit main power switch is
turned oil. Failure to do so ma\ result in electric
shock or injtiiy from iota ting fan blade.
Lubrication
FAN MOTOR BEARINGS — Oiling holes are
provided at each end of condenser fan motor. Re
move fan motor and lubricate motor with 32 drops
(16 drops per hole) of SAE-10 nondetergent oil at
intervals described below.
a. Annually, when environment is very dirty,
ambient temperature is higher than 105 F, and
average unit operating time exceeds 15 hours a
day.
b. Every 3 years when environment is reasonably
clean, ambient temperature is less than 105 F
and unit operating time averages 8 to 15 hours
a day.
c. Every 5 years when environment is clean,
ambient temperature is less than 105 F and unit
operating time averages less than 8 hours a day.
14
Page 15
COIL REPAIR — A flare-union coupling is used
for E-coil repair. A kit is available, with instructions,
thru Carrier Service Parts.
COMPRESSOR contains factory oil charge. If oil
requires replenishment, see Table 7 for oil recharge
and Carrier Standard Service Techniques Manual,
Chapter 1, Refrigerants, page 1-21, for instructions.
Use Carrier PP33-1, Texaco WFI-32 or Suniso3GS
oil.
Coil Cleaning to be done at the beginning of each
cooling season or more often if required.
C.'M'TION: Fin damage or remo\al can result
in higher operating costs or compressor damage.
Do not use flame, high-pressure water, steam
or volatile or corrosive cleaners »m fins and
tubing. Follow these tnstruetions carefulh.
Contact voiii dealer i1 vou encounter problems.
1. Shut off power to unit.
2. Remove louvered casing by taking out 16 screws
securing it to the cabinet and sliding it away from
the coil.
Clean coil using vacuum cleaner and its crevice
3.
tool (see Fig. 25). Work crevice tool vertically
making sure tool only touches dirt on fins. To
prevent fin removal, do not “scrub”fins with tool
or move tool horizontally.
6. Reinstall louvered casing being careful not to
damage coil.
7. Restore power to unit.
4. If oil deposits are present, spray coil with house
hold detergent (Fantastic, Lestoil, 409, or any
similar type). Wait 10 minutes then proceed to
step 5.
5. Using garden hose, spray coil vertically down
ward with a constant stream of water at moderate
pressure (see Fig. 26). Keep nozzle at a 15 to 20
degree angle, about 3 in. from coil face and 18 in.
from tube. Spray so debris is washed out and
away from coil.
15
Page 16
ON
TROUBLESHOOTING CHART — COOLING CYCLE
Page 17
TROUBLESHOOTING CHART — HEATING CYCLE
Page 18
For replacement items use Carrier Specified Parts.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
1 4
Book
Tab5a
5a
Form 38QF-2SI Supersedes 38QF-1 SIM
Printed in U.S.A.
4-83
PC 101Catalog No. 563-816
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.