Installation and servicing of air conditioning
equipment can be hazardous due to system pressure
and electrical components. Only trained and quali
fied service personnel should install, repair or serv
ice air conditioning equipment.
Untrained personnel can perform basic main
tenance functions of cleaning coils and cleaning
and replacing filters. All other operations should be
performed by trained service personnel. When
working on air conditioning equipment, observe
precautions in the literature, tags and labels attached
to the unit and other safety precautions that may
apply.
Follow all safety codes. Wear safety glasses and
work gloves. Use quenching cloth for brazing oper
ations. Have fire extinguisher available for all braz
ing operations.
W.ARNING: Before performing scr\icc or
maintenance operations on sxstem. turn ofl
main powci switches to indoor unit and out
door unil. 1 urn ofl acccssoiA heater power
switch if applicable, riectrical shock could cause
personal itijur\.
INSTALLATION
Step 1 — Check Equipment and Jobsite
UNPACK UNIT — Move to final location. Lift
carton off, taking special care not to damage service
valves or grilles.
INSPECT EQUIPMENT — File claim with ship
ping company if shipment is damaged or incomplete.
COMPLETE OR CONSIDER SYSTEM RE
QUIREMENTS before installing the 38QF.
Consult local building codes and National
Electrical Code (NEC) for special installation
requirements.
When installing, allow sufficient space for air
flow clearance, wiring, refrigerant piping and serv
icing. Position so water or ice from roof cannot drop
directly on top of unit.
Make provisions for condensate drainage and
defrost water disposal whether unit is installed on
ground or roof. (Ensure unit basepan drainage holes
are not blocked.) See Step 2 for details. Roof in
stallation method for 38QF depends on building
construction and special requirements of local
codes. Be sure that roof can support unit weight.
It is recommended that 38QF units be used with
Carrier approved indoor sections; see Table 1.
System Refrigerant Control on 38QF units and
matching Carrier indoor units is a factory-installed
AccuRater™ device (bypass type). Bypass-type
AccuRater components are discussed in the service
section of this booklet. The AccuRater piston has a
refrigerant metering hole thru it and is field replace
able. Table 1 indicates indoor units for which the
required replacement piston is factory supplied with
specified 38QF outdoor unit. Replace piston as
Top Cover Removal — Top cover can be removed
for wiring or servicing heat pump. Loosen decora
tive strip and slide down off screw heads. Remove
3 screws in connector plate and 2 screws on front of
unit. Loosen remaining 4 screws. Lift top from unit
(see Fig. 1).
Step 2 — Mount Outdoor Heat Pump
ON THE GROUND: MOUNT UNIT ON A
SOLID, LEVEL CONCRETE PAD (see Fig. I).
4-0"0VERHEAD SPACE REQUIRED
FOR SERVICE AND AIRFLOW
7"
8
DIAM HOLE
FOR CONTROL
WIRING
Swing 3 legs down and lock in position, except when
using accessory rack. Use accessory heat pump rack
(Fig. 2) in areas where prolonged subfreezing tem
peratures or heavy snow occur. (Refer to installation
instructions included with rack.) Drainage holes in
unit base must not be obstructed.
AIRFLOW AND
SERVICE
CLEARANCE
LIQUID VALVE SERVICE PORT / VAPOR VALVE SERVICE PORT
AIRFLOW SUCTION SERVICE PORT
CONCRETE MOUNTING PAD
Fig. 1 — Dimensions, Connections and
Mounting Pad (Refer to Table 2)
Fig. 2 — Accessory Mounting Rack
Table 1 — Carrier Approved 38QF Systems
OUTDOOR
UNIT
38QF
018
02446
030
036
042
048
060
^Factory-supplied piston packages shipped in outdoor unit. Replace remain
ing indoor pistons with size indicated.
REQUIRED
OUTDOOR
PISTON
SIZE
42
59
61
63
7640QB/QH06086*
82
INDOOR
UNIT
MODEL &
SIZE
40AQ018
28HQ/VQ018
40AQ024
28HQ/VQ024
40FS075,28HQ/VQ042
40AQ024
28HQ/VQ024
40AQ030
28HQ/VQ030
40FS075,28HQ/VQ042
40AQ030
28HQ/VQ030
40DQ030
40AQ036
28HQ/VQ036
40AQ036
28HQ/VQ036
40QB/QH042
28HQ/VQ042
40QB/QH042
28HQ/VQ048
40QB/QH048
40QB/QH04884
28HQ/VQ04884
40QB/QH062
28HQ/VQ060
40QB/QH060
40QB/QH062
REQUIRED
INDOOR
PISTON
SIZE
61
67
67
70*
70*
70
70
73*
73*
76
78
78
86*
86*
96
52
52
55*
55*
59
59
61*
61*
65
67
ON THE ROOF; MOUNT UNIT ON A LEVEL
PLATFORM OR FRAME: Proper precaution
must be taken for support of unit in roof design.
Elevate unit for proper clearance as described under
ground installation above. Plan roof design and
water drainage to prevent unit from setting in water.
Flash all roof openings to prevent leaks.
Roof mounted unit exposed to winds above 5 mph
may require protective wind baffles (field fabricated)
to achieve adequate defrost.
Step 3 — Make Piping Connections — Heat
pumps may be connected to indoor sections using
Carrier accessory tubing package (Table 3) or field-
supplied tubing of refrigerant grade, correct size and
condition (Table 2). For requirements beyond
50 ft obtain information from local Carrier
distributor.
-> Table 3 — Accessories
Table 2 — Installation Data (Fig. 1)
UNIT 38QF
OPER WT(lb)
DIMEN (ft-in.)
DIam (A)
Height (B)
Mtg Pad
(Diam X Thick)*
(C)
(D)
REFRIG CONN (in.)
Suction (ODF)
Liquid (ODF)
REFRIG LINES (in.)
Suction (ODF)
Liquid (ODF)
“■Mounting pad is fieid suppiied,
fMay use Vs-'m. accessory tubing package (slight capacity loss). See Tabie 3.
Outdoor Thermostat (Six 38QB900041)
Optimizer Control Outdoor Thermostat — Ref HH22AG110 (Six 38CQ900161)
Optimizer II Control Assembly — Use with HH22AG110 outdoor thermostat.
WARNING: If unclcrsi7ed. damaged or
elliptiv.-all\-s!iapL'd uibing is used when making
Compatible bitting, leaks ma\ result.
If 1-1/8 in. tubing is used, braze it to the accessory
1-1/8 X 3/4-in. suction connection adapter (Carrier
Part No. 28VQ900011) or to a correctly sized fieldsupplied adapter, then make Compatible Fitting
connections. Isolate interconnecting tubing from
framing and ductwork or where tubing runs thru
stud spaces, enclosed ceilings or pipe chases. Use
isolation type hangers. Fig. 3, since rigid fastening
transmits pulsations to structure creating objec
tionable sound.
^ ( \l 1 ION. IK) \OI Ml \<\ MORI I II \\
'' I I ()l I INI SI I IN (.ROl N1). II .m> '•ac
tion of liucsel is burictl. there must be b-in.
\ertical rise to the \al\e connections on the
outdoor unit. If more than the recommended
length i.s buried, refrigerant ma\ migrate to the
eooler buried .section during extended periods of
unit shutdown, causing relrigerant slugging and
possibh compressor damage at start-up.
A capacity reduction will result if accessory tub
ing is used in 38QF systems. For example, when a
25-ft 7/8-in. accessory package is used, there is a
capacity reduction of 1-1/2 percent.
When other than 25 ft of interconnecting tubing
is used, follow special requirements described in
Refrigerant Charging. Do not use less than 10 ft of
interconnecting tubing. Do not cut 7/8-in. suction
line. Bend or coil to fit.
Do not use damaged or contaminated tubing.
Always evacuate or purge evaporator coil and
tubing system (use field-supplied refrigerant, not
unit refrigerant).
When making tubing connections, be sure to
provide clearance at unit for electrical connections.
REPLACE THE ACCURATER™ REFRIG
ERANT CONTROL PISTON IN THE INDOOR
COIL AS REQUIRED before connecting refrig
erant lines. See Table 1. Correct piston is supplied
with 38QF unit. For piston replacement instruc
tions, see AccuRater Servicing on page 13.
CONNECT REFRIGERANT LINES to fittings on
unit suction and liquid service valves (Fig. 1).
Liquid service valve has flare fitting; suction service
valve has Compatible Fitting. Make suction line
connection first. Slide flare nut on liquid line, then
flare and connect liquid line. Use a maximum
torque of 15 ft-lb to tighten flare nut. (Do not dis
assemble AccuRater.) Unit Compatible Fitting
permits mechanical or sweat connection as de
scribed below.
When a 7/8-in. field-supplied suction line is
used on 38QF, a field-supplied 3/4-in. to 7/8-in.
suction line adapter must be provided (not required
if 38LS accessory tubing is used).
When a 1-1/ 8 in. field-supplied suction line is used
on 38QF, use accessory adapter 28VQ900011 or
other field-supplied connection. Sweat connect re
frigerant suction line to 1-1/8 in. end of adapter.
Connect 3/4-in. end of adapter to unit suction line
Compatible Fitting.
Mechanical Connection to Compatible Fitting
(Mate one set of connections at a time.)
1. Loosen nut on Compatible Fitting one turn. Do
not remove.
2. Remove plug and be sure 0-ring is in the groove
inside the Compatible Fitting.
3. Cut tubing to correct length.
4. Insert tube into Compatible Fitting until it
bottoms.
5. Tighten nut until it bottoms on back coupler
flange. Keep tube bottomed in Compatible
Fitting while tightening nut.
Sweat Connection to Compatible Fitting (Use
refrigerant grade tubing.)
1. Remove locking nut, rubber O-ring and Schrader
core from valve.
2. Cut tubing to correct length.
3. Insert tube into Compatible Fitting. Wrap top
and bottom of service valves in wet cloth to pre
vent damage by heat. Solder with low tempera
ture (430 F) silver alloy solder.
4. Replace Schrader core.
5. Evacuate or purge system with field-supplied
refrigerant.
Step 4 — Make Electrical Connections — Field
wiring must comply with local and national fire,
safety and electrical codes. Voltage to unit must be
within permissible limits indicated on nameplate.
Contact local power company for correction of
improper line voltage.
W.AR.NTNG: Operation of units on improper
line \oliagc constiiiitcs abuse and could affect
Carrier warrantx. See fable4.
Do not apply units in system where voltage may
fluctuate above or below permissible limits.
Table 4 — Electrical Data (60 Hz)
OPER
UNIT
38QF
018
024
030
036
042
048
060
AWG — American Wire Gage
FLA — Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps
RLA — Rated Load Amps
V/PH
230/1
208-230/1
230/1
VOLTAGE*
Max
254
254
MinLRARLA
197
207
COMPR
50
54
6917.7
75
90
101
130
FAN
FLA
10.81430
13.0
16.81050
20.0
21.2
28.6
1.1
1.7
When making electrical connections, provide
clearance at unit for refrigerant piping connections.
See Table 4 for recommended wire and fuse sizes.
INSTALL A BRANCH CIRCUIT DISCONNECT
PER NEC of adequate size to handle unit starting
current. Provide a separate disconnect for outdoor
unit, indoor unit and for each accessory electric
heater circuit as required. (See Indoor Unit and
Electric Heater Installation, Start-Up and Service
Instructions.) Locate disconnect(s) within sight
from and readily accessible from the unit; per sec
tion 440-14 of National Electrical Code (NEC).
ROUTE LINE POWER LEADS INTO UNIT —
Extend leads from disconnect thru power wiring
hole provided (see Fig. 1) and into unit splice area.
Remove top cover to gain access to unit wiring.
CONNECT GROUND LEAD AND POWER
WIRING — Connect ground lead to a ground lug in
control box for safety. Then connect power wiring.
See Fig. 4. Splice line power leads to yellow and
black pigtails. Use wire nuts and tape at each con
nection. Connect unit wiring to copper wire only.
SEE INDOOR UNIT AND ELECTRIC HEATER
INSTALLATION, START-UP AND SERVICE
INSTRUCTIONS for line power wiring details. All
control wiring is shown in this booklet.
BRANCH CIRCUIT
Min Wire
(AWG)t
12
1048
104310
10
8
*Permissible limits of the voltage range at which the unit will
operate satisfactorily.
tCopper wire sizes based on 60 C. Use copper wire only.
fRequired when using nonmetallic conduit.
**Time-delay fuse
Max WireMin Gnd
(ft)
41
39
46
Wire Size$
14
12
10
10
10
10
CONNECT CONTROL POWER WIRING (24 V)
— Extend wiring thru hole provided (Fig. 1) and
into low-voltage section of unit control ring.
Connect leads to control wiring terminal board as
shown in Fig. 5.
Use indoor unit transformer as 24-v supply for
system. At least a 60-va transformer is recom
mended. Carrier approved indoor units are equipped
with a 60-va transformer. See indoor unit data.
Use Carrier accessory indoor thermostat with
subbase, Table 3.
START-UP
The 38QF unit is equipped with a crankcase
heater. It is recommended that heater be energized a
minimum of 24 hours before starting unit. To ener
gize heater only, turn the thermostat to OFF posi
tion and close electrical disconnect to heat pump.
Heat Anticipator Settings for Room Thermo
stat (HH07AT171) — Set anticipator settings for
room thermostat according to Table 5. These set
tings may be changed slightly to provide a greater
degree of comfort for a particular installation.
*Transformer (60 va) located in cooling control kit or electric heater.
fRemove factory-installed jumper (Connection B) when installing outdoor thermostats (ODT).
Fig. 5 — Control Circuit Connections
Accessory Outdoor Thermostat provides adjust
able outdoor control of accessory electric heater.
This thermostat makes contact when a drop in out
door temperature occurs. It energizes a stage of elec
tric heat when the outdoor temperature setting is
reached, provided the room thermostat is on the
second stage of heating. One outdoor thermostat is
recommended for each stage of electric heat after the
first stage. Set the outdoor thermostat(s) progres
sively lower for each stage. Refer to heat load of
building and unit capacity to determine the correct
outdoor thermostat settings.
The accessory supplemental heat relay is required
when 2 outdoor thermostats are used. It is auto
matically energized by the manually operated sup
plemental heat switch in the indoor thermostat
subbase. The thermostat locks out compressor and
the relay bypasses the outdoor thermostats for
electric heater operation during heat pump shut
down. When one outdoor thermostat is used a
supplemental heat relay is not required. The sup
plemental heat switch in the indoor thermostat
subbase bypasses outdoor thermostat, locks out
compressor and activates electric heater.
Loading...
+ 12 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.