Carrier 42NQV060M, 42NQV050M-N, 38NYV060M, 38NYV050M, 42NQV060M-N Service Manual

...
R410A
FILE NO. SVM-08048
SERVICE MANUAL
SPLIT TYPE
Indoor Unit
<High Wall, Heat Pump Type>
42NQV050M 42NQV060M
Outdoor Unit
<Heat Pump Type>
38NYV050M 38NYV060M
– 1 –
CONTENTS
1. SAFETY PRECAUTIONS .......................................................................... 2
2. SPECIFICATIONS ..................................................................................... 4
3. REFRIGERANT R410A ............................................................................. 6
4. CONSTRUCTION VIEWS ........................................................................ 14
5. WIRING DIAGRAM .................................................................................. 16
6. SPECIFICATIONS OF ELECTRICAL PARTS ......................................... 17
7. REFRIGERANT CYCLE DIAGRAM ........................................................ 18
8. CONTROL BLOCK DIAGRAM ................................................................ 21
9. OPERATION DESCRIPTION................................................................... 23
10. INSTALLATION PROCEDURE ................................................................ 45
11. HOW TO DIAGNOSE THE TROUBLE...................................................... 58
12. HOW TO REPLACE THE MAIN PARTS................................................... 78
13. EXPLODED VIEWS AND PARTS LIST ................................................... 94
– 2 –
1. SAFETY PRECAUTIONS
For general public use
Power supply cord of outdoor unit shall be more than 1.5 mm2 (H07RN-F or 60245IEC66) polychloroprene sheathed flexible cord.
• Read this “SAFETY PRECAUTIONS” carefully before servicing.
• The precautions described below include the important items regarding safety. Observe them without fail.
• After the servicing work, perform a trial operation to check for any problem.
• Turn off the main power supply switch (or breaker) before the unit maintenance.
CAUTION
New Refrigerant Air Conditioner Installation
• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER.
R410A refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because the working pressure of R410A refrigerant is approx. 1.6 times of refrigerant R22. Accompanied with the adoption of the new refrigerant, the refrigeration machine oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigeration machine oil does not enter into the new type refrigerant R410A air conditioner circuit.
To prevent mixing of refrigerant or refrigerating machine oil, the sizes of connecting sections of charging port on main unit and installation tools are different from those used for the conventional refrigerant units.
Accordingly, special tools are required for the new refrigerant (R410A) units. For connecting pipes, use new and clean piping materials with high pressure fittings made for R410A only, so that water and/or dust does not enter. Moreover, do not use the existing piping because there are some problems with pressure fittings and possible impurities in existing piping.
CAUTION
TO DISCONNECT THE APPLIANCE FROM THE MAIN POWER SUPPLY
This appliance must be connected to the main power supply by a circuit breaker or a switch with a contact separation of at least 3 mm.
DANGER
• ASK AN AUTHORIZED DEALER OR QUALIFIED INSTALLATION PROFESSIONAL TO IN­STALL/MAINTAIN THE AIR CONDITIONER.
INAPPROPRIATE SERVICING MAY RESULT IN WATER LEAKAGE, ELECTRIC SHOCK OR FIRE.
• TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
DANGER: HIGH VOLTAGE
The high voltage circuit is incorporated. Be careful to do the check service, as the electric shock may be caused in case of touching parts
on the P.C. board by hand.
• CORRECTLY CONNECT THE CONNECTING CABLE. IF THE CONNECTING CABLE IS INCOR­RECTLY CONNECTED, ELECTRIC PARTS MAY BE DAMAGED.
• CHECK THAT THE EARTH WIRE IS NOT BROKEN OR DISCONNECTED BEFORE SERVICE AND INSTALLATION. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
– 3 –
• DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS. FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
• TO PREVENT THE INDOOR UNIT FROM OVERHEATING AND CAUSING A FIRE HAZARD, PLACE THE UNIT WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEAT REGISTORS, FURNACE, STOVES, ETC.
• WHEN MOVING THE AIR-CONDITIONER FOR INSTALLATION IN ANOTHER PLACE, BE VERY CARE­FUL NOT TO ALLOW THE SPECIFIED REFRIGERANT (R410A) TO BECOME MIXED WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CIRCUIT. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CIRCUIT WILL BECOME ABNORMALLY HIGH AND IT MAY RESULT IN THE PIPE BURSTING AND POSSIBLE PER­SONNEL INJURIES.
• IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE SERVICE WORK AND THE INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS IS HEATED, SUCH AS BY FIRE, GENERATION OF POISONOUS GAS MAY RESULT.
WARNING
• Never modify this unit by removing any of the safety guards or bypass any of the safety interlock switches.
• Do not install in a place which cannot bear the weight of the unit. Personal injury and property damage can result if the unit falls.
• After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas may generate.
• The electrical work must be perf ormed by a qualified electrician in accordance with the Installation Manual. Make sure the air conditioner uses an exclusive circuit.
An insufficient circuit capacity or inappropriate installation may cause fire.
• When wiring, use the specified cables and connect the terminals securely to prevent external forces applied to the cable from affecting the terminals.
• Be sure to provide grounding.
Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone cables.
• Conform to the regulations of the local electric company when wiring the power supply.
Inappropriate grounding may cause electric shock.
CAUTION
• Exposure of unit to water or other moisture before installation may result in an electrical short. Do not store in a wet basement or expose to rain or water.
• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify the noise level of the unit or where noise or discharged air might disturb neighbors.
• To avoid personal injury, be careful when handling parts with sharp edges.
• Perform the specified installation work to guard against an earthquake.
If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.
For Reference:
If a heating operation would be continuously performed for a long time under the condition that the outdoor temperature is 0°C or lower, drainage of defrosted water may be difficult due to freezing of the bottom plate, resulting in a trouble of the cabinet or fan.
It is recommended to procure an antifreeze heater locally for a safe installation of the air conditioner. For details, contact the dealer.
– 4 –
2-1. Specifications
Unit model Indoor
Outdoor
Coolin
g
capacit
y
(kW)
Cooling capacity range
(kW)
Heating capacit
y
(kW)
Heating capacity range
(kW)
Power suppl
y
Electric Indoor Operation mode Coolin
g
Heatin
g
Coolin
g
Heatin
g
characteristic Running curren
t
(A)
0.30-0.28 0.30-0.28 0.38-0.35 0.38-0.35
Power consum
p
tion
(W)
40 40 50 50
Power factor
(%)
60 60 60 60
Outdoor O
p
eration mode Coolin
g
Heatin
g
Coolin
g
Heatin
g
Running curren
t
(A)
6.40-5.87 6.98-6.40 8.93-8.19 9.18-8.42
Power consum
p
tion
(W)
1380 1520 1945 2000
Power factor
(%)
98 99 99 99
Starting current (A)
COP 3.31 3.61 3.01 3.21 Sound Pressure Indoor H/M/
L
(
dB-A
)
44/38/32 44/39/32 44/41/35 47/42/35
level Outdoor H
(
dB-A
)
49 50 52 51
Sound
p
ower Indoor H/M/
L
(
dB-A
)
59/53/47 59/54/47 62/56/50 62/57/50
level Outdoor H
(
dB-A
)
64 65 67 66
Indoor uni
t
Unit model Dimension Hei
ght
(mm)
Width
(mm)
Depth
(mm)
Net weigh
t
(kg)
Fan motor outpu
t
(W)
A
ir flow rate
(
Cooling/Heatin
g)
(
m3/min
)
Outdoor unitUnit model
Dimension Hei
ght
(mm)
Width
(mm)
Depth
(mm)
Net weigh
t
(kg)
Compressor Motor outpu
t
(W)
Type Model
Fan motor out
put
(W)
A
ir flow rate
(
Cooling/Heatin
g)
(
m3/min
)
Pipin
gTyp
e
connection Indoor uni
t
Liquid side
(mm)
Gas side
(mm)
Outdoor unitLiquid side
(mm)
Gas side
(mm)
Maximum length
(m)
Maximum chargeless length
(m)
Maximum height difference
(m)
RefrigerantName of refrigeran
t
Weigh
t
(kg)
Wirin
g
Power suppl
y
connection Interconnection Usable tem
p
erature range Indoor(Cooling/Heatin
g)
(°C)
Outdoor
(
Cooling/Heatin
g)
(°C)
A
ccessor
y
Indoor unitInstallation plate
Wireless remote controller Batteries Remote controller holder Su
p
er Oxi Deo filter
Su
p
er Sterilizer filter
Mountin
g
screw Remote controller holder Pan head wood screw Plasma air
p
urifier Installation manual Owner's manual
Outdoor uni
t
Drain nipple Water-
p
roof rubber ca
p
* The specifications may be subject to change without notice for purpose of improvement.
1 1 1 2
2
6(4x25L)
2(3.1Lx16L)
-
1 2 1 2
1.40
21~32/ ~28
-10~46/-15~24 1
3Wires:includes earth(Outdoor)
4Wires:includes earth
20 15 10
R410
A
6.35
12.70
6.35
12.70
DA150A1F-20F
43
37.2/33.7
Flare connection
780 290
40
1100
30
18.0/18.3
38NYV060M
550
320
1050
228
13
7.0
1.0-7.5
9.56-8.77
42NQV060M
1Ph/50Hz/220-240
V
42NQV060M 38NYV060M
6.0
1.2-6.7
1 1 2 1
2
2(3.1Lx16L)
2
-
1
6(
4x25L)
2
2. SPECIFICATIONS
1 1
42NQV050M 38NYV050M
5.0
1.1-6.0
5.8
0.8-6.3
7.28-6.68
42NQV050M
38NYV050M
DA130A1F-27F
550 780 290
39
1100
21~32/ ~28
-10~46/-15~24
320
1050
228
13 30
15.9/16.5
Flare connection
43
31.9/31.9
Twin rotary type with DC-inverter variablespeed control
6.35
12.70
12.70
6.35
20 15 10
R410
A
1.40
5
2-2. Operation Characteristic Curve
<Coolin
g><Heating>
2-3. Capacity Variation Ratio Accordin
g to Temperature
<Coolin
g><Heating>
0.00
1.00
2.00
3.00
4.00
5.00
6.00
7.00
8.00
9.00
10.00
0 102030405060708090100110120
Compressor Speed (RPS)
Current (A)
0.00
1.00
2.00
3.00
4.00
5.00
6.00
7.00
8.00
9.00
10.00
0 102030405060708090100110120
Compressor Speed (RPS)
Current (A)
42NQV050M
50
55
60
65
70
75
80
85
90
95
100
105
32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
Outdoor Temperature (oC)
Capacity Ratio (%)
Capacity Ratio: 100%=
5.0kW (42NQV050M)
6.0kW (42NQV060M)
Condition
Indoor: DB27
o
C / WB19oC Indoor Air-Flow Volume: High Pipe Length: 7.5m
0
20
40
60
80
100
120
-15 -10 -5 0 5 10
Outdoor Temperature (oC)
Capacity Ratio (%)
Capacity Ratio: 100%=
5.8kW (42NQV050M)
7.0kW (42NQV060M)
Condition
Indoor: DB20
o
C Indoor Air-Flow Volume: High Pipe Length: 7.5m
42NQV060M
42NQV050M
42NQV060M
42NQV050M 42NQV060M
42NQV050M 42NQV060M
6
3. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refrigerat­ing oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.
The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.
3-1. Safety During Installation/Servicing
As R410A’s pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materi­als exclusive for R410A, it is necessary to carry out installation/servicing safely while taking the following precautions into consideration.
1. Never use refrigerant other than R410A in an air conditioner which is designed to operate with R410A.
If other refrigerant than R410A is mixed, pressure in the refrigeration cycle becomes abnormally high, and it may cause personal injury, etc. by a rupture.
2. Confirm the used refrigerant name, and use tools and materials exclusive for the refrigerant R410A.
The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air condi­tioner using R410A as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22.
3. If a refrigeration gas leakage occurs during installation/servicing, be sure to ventilate fully.
If the refrigerant gas comes into contact with fire, a poisonous gas may occur.
4. When installing or removing an air conditioner, do not allow air or moisture to remain in the refrig­eration cycle. Otherwise, pressure in the refrig­eration cycle may become abnormally high so that a rupture or personal injury may be caused.
5. After completion of installation work, check to make sure that there is no refrigeration gas leakage.
If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
6. When an air conditioning system charged with a large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal level.
If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result.
7. Be sure to carry out installation or removal according to the installation manual.
Improper installation may cause refrigeration trouble, water leakage, electric shock, fire, etc.
8. Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician.
Improper repair’s may result in water leakage, electric shock and fire, etc.
3-2. Refrigerant Piping Installation
3-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refrigerant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.
1. Copper Pipes
It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pres­sure higher than when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table 3-2-1. Never use copper pipes thinner than 0.8 mm even when it is available on the market.
7
Table 3-2-1 Thicknesses of annealed copper pipes
Nominal diameter
1/4
3/8
1/2
5/8
Outer diameter (mm)
6.35
9.52
12.70
15.88
Thickness (mm)
R410A R22
0.80 0.80
0.80 0.80
0.80 0.80
1.00 1.00
2. Joints
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants. a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 3-2-3 to 3-2-6 below.
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose diameter is larger than 20 mm.
Thicknesses of socket joints are as shown in Table 3-2-2.
Table 3-2-2 Minimum thicknesses of socket joints
Nominal diameter
1/4
3/8
1/2
5/8
Reference outer diameter of
copper pipe jointed (mm)
6.35
9.52
12.70
15.88
Minimum joint thickness
(mm)
0.50
0.60
0.70
0.80
3-2-2. Processing of Piping Materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil than lubricating oils used in the installed air-water heat pump is used, and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover.
1. Flare processing procedures and precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all burrs and clean the cut surface before installation.
c) Insertion of Flare Nut
8
A
ØD
d) Flare Processing
Make certain that a clamp bar and copper pipe have been cleaned.
By means of the clamp bar, perform the flare processing correctly.
Use either a flare tool for R410A or conven­tional flare tool.
Flare processing dimensions differ according to the type of flare tool. When using a con­ventional flare tool, be sure to secure “dimen­sion A” by using a gauge for size adjustment.
Fig. 3-2-1 Flare pr ocessing dimensions
Table 3-2-3 Dimensions related to flare processing for R410A
Nominal
diameter
1/4
3/8
1/2
5/8
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
A (mm)
Flare tool for R410A
clutch type
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
Conventional flare tool
Clutch type Wing nut type
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 2.0 to 2.5
1.0 to 1.5 2.0 to 2.5
Table 3-2-4 Dimensions related to flare processing for R22
Nominal
diameter
1/4
3/8
1/2
5/8
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
A (mm)
Flare tool for R22
clutch type
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
Conventional flare tool
Clutch type Wing nut type
0.5 to 1.0 1.0 to 1.5
0.5 to 1.0 1.0 to 1.5
0.5 to 1.0 1.5 to 2.0
0.5 to 1.0 1.5 to 2.0
Table 3-2-5 Flare and flare nut dimensions for R410A
Nominal
diameter
1/4
3/8
1/2
5/8
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Dimension (mm)
ABCD
9.1 9.2 6.5 13
13.2 13.5 9.7 20
16.0 16.6 12.9 23
19.0 19.7 16.0 25
Flare nut width
(mm)
17
22
26
29
9
43 to 45
45 to 46
B A
C
D
Table 3-2-6 Flare and flare nut dimensions for R22
Nominal
diameter
1/4
3/8
1/2
5/8
3/4
Outer diameter
(mm)
6.35
9.52
12.70
15.88
19.05
Thickness
(mm)
0.8
0.8
0.8
1.0
1.0
Dimension (mm)
ABCD
9.0 9.2 6.5 13
13.0 13.5 9.7 20
16.0 16.2 12.9 20
19.0 19.7 16.0 23
23.3 24.0 19.2 34
Flare nut width
(mm)
17
22
24
27
36
Fig. 3-2-2 Relations between flare nut and flare seal surface
2. Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions do not have any scar or dust, etc. b) Correctly align the processed flare surface with the union axis. c) Tighten the flare with designated torque by means of a torque wrench. The tightening torque for R410A is
the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur. When it is strong, the flare nut may crack and may be made non-removable. When choosing the tighten-
ing torque, comply with values designated by manufacturers. Table 3-2-7 shows reference values.
NOTE :
When applying oil to the flare surface, be sure to use oil designated by the manufacturer. If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
Table 3-2-7 Tightening torque of flare for R410A [Reference values]
Nominal
diameter
1/4
3/8
1/2
5/8
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Tightening torque
N•m (kgf•cm)
14 to 18 (140 to 180)
33 to 42 (330 to 420)
50 to 62 (500 to 620)
63 to 77 (630 to 770)
Tightening torque of torque
wrenches available on the market
N•m (kgf•cm)
16 (160), 18 (180)
42 (420)
55 (550)
65 (650)
– 10
3-3. Tools
3-3-1. Required T ools
The service port diameter of packed valve of the outdoor unit in the air-water heat pump using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
1. Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2. Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3. Tools commonly used for R410A and for conventional refrigerant (R22) The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
No.
1
2
3
4 5 6
7
8 9
10
Used tool
Flare tool Copper pipe gauge for
adjusting projection margin
Torque wrench (For Ø12.7)
Gauge manifold Charge hose Vacuum pump adapter
Electronic balance for refrigerant charging
Refrigerant cylinder Leakage detector Charging cylinder
Usage
Pipe flaring
Flaring by conventional flare tool
Connection of flare nut
Evacuating, refrigerant charge, run check, etc.
Vacuum evacuating
Refrigerant charge
Refrigerant charge Gas leakage check Refrigerant charge
R410A
air-water heat pump installation
Existence of new equipment for R410A
Ye s
Ye s
Ye s
Ye s
Ye s
Ye s
Ye s Ye s
*(Note 2)
Whether conven­tional equipment can be used
*(Note 1)
*(Note 1)
Conventional air-water heat pump installation
Whether new equipment can be used with conventional refrigerant
*(Note 1)
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools.
1. Vacuum pump Use vacuum pump by attaching vacuum pump adapter.
2. Torque wrench (For Ø6.35, Ø9.52)
3. Pipe cutter
4. Reamer
5. Pipe bender
6. Level vial
7. Screwdriver (+, –)
8. Spanner or Monkey wrench
9. Hole core drill (Ø65)
10. Hexagon wrench (Opposite side 4mm)
11. Tape measure
12. Metal saw
Also prepare the following equipments for other installation method and run check.
1. Clamp meter
2. Thermometer
3. Insulation resistance tester
4. Electroscope
No
No
No
No
No No No
No
No
Yes
Yes
No
Yes
No
Yes
– 11
Connect the charge hose to packed valve service port at the outdoor unit’s gas side.
Recover the refrigerant, and check no refrigerant remains in the equipment.
(For refrigerant charging, see the figure below.)
Connect the charge hose to the vacuum pump adapter.
Open fully both packed valves at liquid and gas sides.
Place the handle of the gauge manifold Low in the fully opened position, and turn on the vacuum pump’s power switch. Then, evacuating the refrigerant in the cycle.
When the compound gauge’s pointer has indicated –0.1 MPa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s power switch.
Keep the status as it is for 1 to 2 minutes, and ensure that the compound gauge’s pointer does not return.
Set the refrigerant cylinder to the electronic balance, connect the connecting hose to the cylinder and the connecting port of the electronic balance, and charge liquid refrigerant.
(Indoor unit)
(Outdoor unit)
Opened
Opened
Refrigerant cylinder
(with siphon)
Check valve
Open/close valve for charging
Electronic balance for refrigerant charging
Opened
Closed
Service port
3-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps.
1. Never charge refrigerant exceeding the specified amount.
2. If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
3. Do not carry out additional charging. When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury.
Fig. 3-4-1 Configuration of refrigerant charging
– 12
Gauge manifold
[ Cylinder with siphon ] [ Cylinder without siphon ]
OUTDOOR unit
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Electronic
balance
Refrigerant
cylinder
Electronic
balance
Siphon
1. Be sure to make setting so that liquid can be charged.
2. When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
R410A refrigerant is HFC mixed refrigerant. Therefore, if it is charged with gas, the composi­tion of the charged refrigerant changes and the characteristics of the equipment varies.
3-5. Brazing of Pipes
3-5-1. Materials for Brazing
1. Silver brazing filler
Silver brazing filler is an alloy mainly composed of silver and copper. It is used to join iron, copper or copper alloy, and is relatively expensive though it excels in solderability.
2. Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used to join copper or copper alloy.
3. Low temperature brazing filler
Low temperature brazing filler is generally called solder, and is an alloy of tin and lead. Since it is weak in adhesive strength, do not use it for refrigerant pipes.
1. Phosphor bronze brazing filler tends to react with sulfur and produce a fragile compound water solution, which may cause a gas leakage. Therefore, use any other type of brazing filler at a hot spring resort, etc., and coat the surface with a paint.
2. When performing brazing again at time of servicing, use the same type of brazing filler.
3-5-2. Flux
1. Reason why flux is necessary
• By removing the oxide film and any foreign matter on the metal surface, it assists the flow of brazing filler.
• In the brazing process, it prevents the metal surface from being oxidized.
• By reducing the brazing filler’s surface tension, the brazing filler adheres better to the treated metal.
Fig. 3-4-2
– 13
Nitrogen gas
cylinder
Pipe
Flow meter
M
Stop valve
From Nitrogen cylinder
Nitrogen gas
Rubber plug
2. Characteristics required for flux
• Activated temperature of flux coincides with the brazing temperature.
• Due to a wide effective temperature range, flux is hard to carbonize.
• It is easy to remove slag after brazing.
• The corrosive action to the treated metal and brazing filler is minimum.
• It excels in coating performance and is harm­less to the human body.
As the flux works in a complicated manner as described above, it is necessary to select an adequate type of flux according to the type and shape of treated metal, type of brazing filler and brazing method, etc.
3. Types of flux
• Noncorrosive flux
Generally, it is a compound of borax and boric acid. It is effective in case where the brazing tem­perature is higher than 800°C.
• Activated flux
Most of fluxes generally used for silver brazing are this type. It features an increased oxide film removing capability due to the addition of compounds such as potassium fluoride, potassium chloride and sodium fluoride to the borax-boric acid compound.
4. Piping materials for brazing and used brazing filler/flux
1. Do not enter flux into the refrigeration cycle.
2. When chlorine contained in the flux remains within the pipe, the lubricating oil deteriorates. Therefore, use a flux which does not contain chlorine.
3. When adding water to the flux, use water which does not contain chlorine (e.g. distilled water or ion-exchange water).
4. Remove the flux after brazing.
3-5-3. Brazing
As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified.
In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry Nitrogen gas (N2) flow.
Never use gas other than Nitrogen gas.
1. Brazing method to prevent oxidation
1) Attach a reducing valve and a flow-meter to the Nitrogen gas cylinder.
2) Use a copper pipe to direct the piping mate­rial, and attach a flow-meter to the cylinder.
3) Apply a seal onto the clearance between the piping material and inserted copper pipe for Nitrogen in order to prevent backflow of the Nitrogen gas.
4) When the Nitrogen gas is flowing, be sure to keep the piping end open.
5) Adjust the flow rate of Nitrogen gas so that it is lower than 0.05 m
3
/Hr or 0.02 MPa
(0.2kgf/cm2) by means of the reducing valve.
6) After performing the steps above, keep the Nitrogen gas flowing until the pipe cools down to a certain extent (temperature at which pipes are touchable with hands).
7) Remove the flux completely after brazing.
Fig. 3-5-1 Prevention of oxidation during brazing
Piping material
Copper - Copper
Copper - Iron
Iron - Iron
Used brazing filler
Phosphor copper
Silver
Silver
Used flux
Do not use
Paste flux
Vapor flux
4.CONSTRUCTION VIEWS
4-1. Indoor Unit
42NQV050M 42NQV060M
-14-
100 or more
Intake
50 or more
Intake
250 or more
Outside line of product
Minimum distance from wall
200 or more
Outlet
A leg part
B leg part
dia.11-14U-shape hole
8-dia.7 hole
Charging port
B
C
D
A
(for dia.8-10 anchor bolt)
dia.7 hole pitch
Drain hole
(for dia.8-10 anchor bolt)
dia.11x14 long hole
2
-
d
i
a
.
7
h
o
l
e
2-dia.7 hole
(2-dia.11x14 U-shape hole)
Fin guard
When installing the outdoor unit, leave open in at least two of directions (A),(B),(C)and(D) shown in the figure below.
Packed valve cover
Fan guard
4-dia.4.5 embossment
)(
(for fixing outdoor unit)
C
L
Anchor bolt
long hole pitch
Mounting dimensions of anchor bolt
Detailed B leg part
31
145
79
5
4
143
342
38 54
11
108
R
5
.
5
Detailed A leg part
600
320
Outside line of product
600
R
5
.
5
Outside line of product
320
R
1
5
483
449
32 500
52
88
20
30
28
125108
60
d
i
a
.
2
5
88
20
Connecting pipe port
(Pipe dia.12.7)
(Pipe dia.6.35)
21
38
54
R
1
5
483 257
20
6
22
25
93
137
71
35
8
21
550
320
290
600 90
306
69.5
147
600
320
780
157
11
Drain long hole
Connecting pipe port
dia.436
Z
Z View
(2-dia.11x14 long hole)
4-2. Outdoor Unit
15
5-1. 42NQV050M / 38NYV050M
42NQV060M / 38NYV060M
5. WIRING DIAGRAM
Heat Exchanger
GRN&YEL
1 1
TEMP. SENSOR)
(CONDENSER PIPE
TE
TEMP. SENSOR)
(DISCHARGE PIPE
1
2
212
TD
CN602
5
5
44
22
1
1
33
66
TEMP. SENSOR)
TEMP. SENSOR)
(OUTDOOR
121
2
TO
(SUCTION PIPE
121
3 3
TS
PMV
Q200 205
P06
BLK
2 2
CM
P23
P25
P21
P34
P35
YEL
BRW
YEL
3
YEL
3
C13
L03
POWER RELAY
CT
AC250V
P24
R220
R219
R221
WHI
RED
COMPRESSOR
1 1
P05
P04
3 3
CN601
CN600
COIL FOR 4WAY VALVE
3 3
121
2
2
PUR
1
21
1 1
RELAY
P20
P22
IGBT
– 16 –
– 17
6. SPECIFICATIONS OF ELECTRICAL PARTS
6-1. Indoor Unit
6-2. Outdoor Unit
No.
1 Reactor L = 10mH, 16A 2 Outdoor fan motor DC140V, 43W 3 Suction temp. sensor (TS sensor)
10k (25°C)
4 Discharge temp. sensor (TD sensor)
62k (20°C)
5 Outside air temp. sensor (TO sensor)
10k (25°C)
6 Heat exchanger temp. sensor (TE sensor)
10k (25°C)
7 Terminal block
(6P) 20A, AC250V
38NYV050M
38NYV060M
9 COIL FOR P.M.V. DC12V
10 Coil for 4-way valve AC220-240V
CAM-MD12TF-10
STF
Compressor 3-phases 4-poles
1100W
(Inverter attached) (Inverter attached) (Inverter attached)
8
(Inverter attached)
DA130A1F-27F DA150A1F-20F
Parts name Model name Rating
CH-57
ICF-140-43-4R
No.
Fan motor
42NQV060M
(for indoor)
2 Room temp. sensor (TA-sensor)
10kΩ at 25°C
3 Heat exchanger temp. sensor (TC-sensor)
10kat 25°C
4 Louver motor Output (Rated) 1W, 16 poles, DC12V
( )
( − )
MP24Z3T
ICF-340-30-2* DC-340V,30W
Parts name
1
SpecificationsType
42NQV050M
18
NOTE :
• The maximum pipe length of this air conditioner is 20 m. When the pipe length exceeds 15m, the additional
Max. : 20m
Deoxidized copper pipe
Outer dia. : 12.7mm
Thickness : 0.8mm
NOTE :
Gas leak check position Refrigerant flow (Cooling) Refrigerant flow (Heating)
INDOOR UNIT
T1
TO
Temp. measurement
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe Outer dia. : 6.35mm Thickness : 0.8mm
Sectional shape of heat insulator
Allowable height
difference : 10m
Allowable pipe length
P
Pressure measurement Gauge attaching port
Vacuum pump connecting port
Strainer
Pulse Modulating valve at liquid side (CAM-B22YGTF-3)
TD
4-way valve (STF-0108Z)
Compressor DA130A1F-27F
Propeller fan
Refrigerant amount : 1.40kg
OUTDOOR UNIT
Muffler
TC
TA
Min. : 2m Chargeless : 15m
Charge : 20g/m (16 to 20m)
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 100g)
2 - Dia 1.2 x 80
Outdoor heat
exchanger
Split capillary
TE
Muffler
Accumulater tank
7. REFRIGERANT CYCLE DIAGRAM
7-1. Refrigerant Cycle Diagram
42NQV050M / 38NYV050M
TS
TO
DISTRIBUTOR
19
NOTE :
• The maximum pipe length of this air conditioner is 15 m. When the pipe length exceeds 15m, the additional
Max. : 20m
Deoxidized copper pipe
Outer dia. : 12.7mm
Thickness : 0.8mm
NOTE :
Gas leak check position Refrigerant flow (Cooling) Refrigerant flow (Heating)
INDOOR UNIT
T1
TO
Temp. measurement
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe Outer dia. : 6.35mm Thickness : 0.8mm
Sectional shape of heat insulator
Allowable height
difference : 10m
Allowable pipe length
P
Pressure measurement Gauge attaching port
Vacuum pump connecting port
Strainer
Pulse Modulating valve at liquid side (CAM-B22YGTF-3)
TD
4-way valve (STF-0213Z)
Compressor DA150A1F-20F
Outdoor heat
exchanger
Split capillary
Propeller fan
Refrigerant amount : 1
.40kg
OUTDOOR UNIT
Muffler
TC
TA
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 100g)
Min. : 2m Chargeless : 15m
Charge : 20g/m (16 to 20m)
42NQV060M / 38NYV060M
Muffler
Accumulater tank
4-Dia 2 x 66
TS
TE
DISTRIBUTOR
– 20
7-2. Operation Data
<Cooling>
Tempeature Model name Standard Heat exchanger Indoor Outdoor Compressor
condition(°C) pressure pipe temp. fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
27/19 35/- 42NQV050M 0.9 to 1.1 11 to 13 40 to 42 High High 67
42NQV060M 0.9 to 1.1 11 to 13 41 to 43 High High 77
<Heating>
Tempeature Model name Standard Heat exchanger Indoor Outdoor Compressor
condition(°C) pressure pipe temp. fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
20/- 7/6 42NQV050M 2.5 to 2.6 40 to 42 1 to 3 High High 79
42NQV060M 2.6 to 2.8 42 to 44 0 to 2 High High 84
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition 7.5 m
– 21
8. CONTROL BLOCK DIAGRAM
8-1. Indoor Unit
42NQV050M, 42NQV060M
M.C.U.
Indoor Unit Control Unit
From Outdoor Unit
220-240V
~
50Hz
Serial Signal Communication
(Operation Command and Information)
Serial Signal Transmitter/Receiver
Converter
(D.C circuit)
Noise Filter
Indoor
Fan Motor
Louver
Motor
Louver Motor Drive Control
Indoor Fan
Motor Control
Initializing Circuit
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Infrared Rays, 36.7kHz
Remote Controller
Thermo. Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver AUTO Swing
Louver Direction Setting
Operation Mode Selection
AUTO, COOL, DRY, HEAT, FAN
REMOTE CONTROLLER
ECO
Hi-POWER
Heat Exchanger Sensor (Tc)
Room Temperature Sensor (Ta)
Infrared Rays Signal Receiver
and Indication
Functions
• Cold draft preventing Function
• 3-minute Delay at Restart for Compressor
• Fan Motor Starting Control
• Processing (Temperature Processing)
• Timer
• Serial Signal Communication
Operation (START/STOP)
QUIET
SLEEP (1,3,5,9 OFF TIMER)
220-230V ~60Hz
– 22
8-2. Outdoor Unit (Inverter Assembly)
220–240 V ~50Hz
MICRO-COMPUTER BLOCK DIAGRAM
Driver circuit
of P.M.V.
Heat exchanger
temp.sensor
Suction temp.
sensor
Outdoor air
temp. sensor
Discharge
temp. sensor
Indoor unit
send/receive
circuit
Relay
circuit
Noise
Filter
Converter
(AC DC)
Clock
frequency
4MHz
High Power
factor Correction
circuit
Input current
sensor
• PWM synthesis function
• Input current release control
• IGBT over-current detect control
• Outdoor fan control
• High power factor correction control
• Inverter output frequency control
• A/D converter function
• P.M.V. control
• Discharge temp. control
• 4-way valve control
• Signal communication to indoor unit
P.M.V. : Pulse Motor Valve
M.C.U. : Micro Control Unit
M.C.U
For INDOOR UNIT
4-way
valve
P.M.V.
Inverter
(DC AC)
Gate drive
circuit
Gate drive
circuit
Inverter
(DC AC)
Outdoor
Fan motor
Compressor
MCC5009 (P.C.B) OUTDOOR UNIT
Current
detect
Current
detect
220− 230 V ~60Hz
– 23
  
9. OPERATION DESCRIPTION
9-1. Outline of Air Conditioner Control
This air conditioner is a capacity-variable type air conditioner, which uses DC motor for the indoor for motor and the outdoor fan motor. And the capacity­proportional control compressor which can change the motor speed in the range from 11 to 120 rps is mounted. The DC motor drive circuit is mounted to the indoor unit. The compressor and the inverter to control fan motor are mounted to the outdoor unit.
The entire air conditioner is mainly controlled by the indoor unit controller.
The indoor unit controller drives the indoor fan motor based upon command sent from the remote controller, and transfers the operation command to the outdoor unit controller.
The outdoor unit controller receives operation com­mand from the indoor unit side, and controls the outdoor fan and the pulse Modulating valve. (P.M.V) Besides, detecting revolution position of the compres­sor motor, the outdoor unit controller controls speed of the compressor motor by controlling output voltage of the inverter and switching timing of the supply power (current transfer timing) so that motors drive according to the operation command. And then, the outdoor unit controller transfers reversely the operating status information of the outdoor unit to control the indoor unit controller.
As the compressor adopts four-pole brushless DC motor, the frequency of the supply power from inverter to compressor is two-times cycles of the actual number of revolution.
1. Role of indoor unit controller
The indoor unit controller judges the operation commands from the remote controller and assumes the following functions.
• Judgment of suction air temperature of the indoor heat exchanger by using the indoor temp. sensor. (TA sensor)
• Judgment of the indoor heat exchanger tempera­ture by using heat exchanger sensor (TC sensor) (Prevent-freezing control, etc.)
• Louver motor control
• Indoor fan motor operation control
• LED (Light Emitting Diode) display control
• Transferring of operation command signal (Serial signal) to the outdoor unit
• Reception of information of operation status (Serial signal including outside temp. data) to the outdoor unit and judgment/display of error
• Air purifier operation control
2. Role of outdoor unit controller
Receiving the operation command signal (Serial signal) from the indoor unit controller, the outdoor unit performs its role.
• Compressor operation control
• Operation control of outdoor fan motor
• P.M.V. control
• 4-way valve control
Operations followed to judgment of serial signal from indoor side.
• Detection of inverter input current and current release operation
• Over-current detection and prevention operation to IGBT module (Compressor stop function)
• Compressor and outdoor fan stop function when serial signal is off (when the serial signal does not reach the board assembly of outdoor control by trouble of the signal system)
• Transferring of operation information (Serial signal) from outdoor unit controller to indoor unit controller
• Detection of outdoor temperature and operation revolution control
• Defrost control in heating operation (Temp. measurement by outdoor heat exchanger and control for 4-way valve and outdoor fan)
3. Contents of operation command signal (Serial signal) from indoor unit controller to outdoor unit controller
The following three types of signals are sent from the indoor unit controller.
• Operation mode set on the remote controller
• Compressor revolution command signal defined
by indoor temperature and set temperature (Correction along with variation of room tempera­ture and correction of indoor heat exchanger temperature are added.)
• Temperature of indoor heat exchanger
• For these signals ([Operation mode] and [Com-
pressor revolution] indoor heat exchanger tem­perature), the outdoor unit controller monitors the input current to the inverter, and performs the followed operation within the range that current does not exceed the allowable value.
4. Contents of operation command signal (Serial signal) from outdoor unit controller to indoor unit controller
The following signals are sent from the outdoor unit controller.
• The current operation mode
• The current compressor revolution
• Outdoor temperature
• Existence of protective circuit operation
For transferring of these signals, the indoor unit controller monitors the contents of signals, and judges existence of trouble occurrence.
Contents of judgment are described below.
• Whether distinction of the current operation status meets to the operation command signal
• Whether protective circuit operates When no signal is received from the outdoor
unit controller, it is assumed as a trouble.
– 24
9-2. Operation Description
1. Basic operation ........................................................................................................... 25
1. Operation control ................................................................................................... 25
2. Cooling/Heating operation ..................................................................................... 26
3. AUTO operation .....................................................................................................
29
4. DRY operation........................................................................................................ 26
2. Indoor fan motor control ............................................................................................. 27
3. Outdoor fan motor control........................................................................................... 29
4. Capacity control .......................................................................................................... 30
5. Current release control ............................................................................................... 30
6. Release protective control by temperature of indoor heat exchanger........................ 31
7. Defrost control (Only in heating operation) ................................................................ 32
8. Louver control ............................................................................................................. 33
1) Louver position....................................................................................................... 33
2) Air direction adjustment ......................................................................................... 33
3) Swing ..................................................................................................................... 33
9. ECO operation ............................................................................................................ 34
10. Temporary operation................................................................................................... 35
11. Pulse Modulating valve (P.M.V.) control ...................................................................... 35
12. Self-Cleaning function ................................................................................................. 36
13. Remote-A or B selection ............................................................................................ 37
9-3. Auto Restart Function ................................................................................................39
9-3-1. How to Set the A uto Restart Function .............................. ........................................ 39
9-3-2. How to Cancel the Au to Restar t Function ................................................................ .40
9-3-3. Power Failure During Timer Operation ................................................................... .40
9-4. Remote Controller and Its Fuctions ...................................................................... 41
9-4-1. Parts Name of Remote Contr oller ............................................................................... 41
9-4-2. Operation of remote control ....................................................................................... 41
14. Short Timer ................................................................................................................ 38
15. Hi-POWER Mode ...................................................................................................... 38
9-4-3. Name and Functions of Indications on Remote Contr oller .........................................44
– 25
Item
1. Basic operation
Operation flow and applicable data, etc.
1. Operation control
Description
Receiving the user’s operation condition setup, the operation statuses of indoor/outdoor units are controlled.
1) The operation conditions are selected by the remote controller as shown in the below.
2) A signal is sent by ON button of the remote controller.
3) The signal is received by a sensor of the indoor unit and processed by the indoor controllers as shown in the below.
4) The indoor controller controls the indoor fan motor and louver motor.
5) The indoor controller sends the operation command to the outdoor controller, and sends/receives the control status with a serial signal.
6) The outdoor controller controls the operation as shown in the left, and also controls the compres­sor, outdoor fan motor, 4-way valve and pulse Modulating valve.
Remote controller
Indoor unit
Control contents of remote controller
• ON/OFF (Air conditioner/Air purifier)
• Operation select (COOL/HEAT/AUTO/DRY)
• Temperature setup
• Air direction
• Swing
• Air volume select (AUTO/LOW/LOW+/MED/MED+/HIGH)
• ECO
• ON timer setup
• OFF timer setup
• Hi-POWER
Indoor unit control
• Command signal generating function of indoor unit operation
• Calculation function (temperature calculation)
• Activation compensation function of indoor fan
• Cold draft preventive function
• Timer function
• Indoor heat exchanger release control
• Indoor fan motor
• Louver motor
Outdoor unit
Outdoor unit control
• Frequency control of inverter output
• Waveform composite function
• Calculation function (Temperature calculation)
• AD conversion function
• Quick heating function
• Delay function of compressor reactivation
• Current release function
• GTr over-current preventive function
• Defrost operation function
• Compressor
• Outdoor fan motor
• 4-way valve
• Pulse Modulating valve (P.M.V.)
Signal receiving
Indoor unit control
Operation command
Serial signal send/receive
Selection of
operation conditions
ON/OFF
Serial signal send/receive
Outdoor unit control
Inverter
~
− 26
Operation ON
Setup of remote controller
Indoor fan motor control / Louver control / Operation Hz
Control (Requierment)
Indoor unit control
Sending of operation command signal
Outdoor unit control
[ ]
Compressor revolution control / Outdoor fan motor control /
4-way valve control In cooling operation: ON In heating operation: OFF Pulse Modulating valve control
Item
1. Basic operation
Operation flow and applicable data, etc.
2. Cooling/Heating operation
Description
The operations are performed in the following parts by controls according to cooling/heating conditions.
1) Receiving the operation ON signal of the remote controller, the cooling or heating operation signal starts being transferred form the indoor controller to the outdoor unit.
2) At the indoor unit side, the indoor fan is operated according to the contents of “2. Indoor fan motor control” and the louver according to the contents of “9. Louver control”, respectively.
3) The outdoor unit controls the outdoor fan motor, compressor, pulse Modulating valve and 4-way valve according to the operation signal sent from the indoor unit.
3. AUTO operation
Selection of operation mode As shown in the following figure, the operation starts by selecting automatically the status of room temperature (Ta) when starting AUTO operation.
*1. When reselecting the operation mode, the fan
speed is controlled by the previous operation mode.
4. DRY operation
DRY operation is performed according to the difference between room temperature and the setup temperature as shown below.
In DRY operation, fan speed is controlled in order to prevent lowering of the room temperature and to avoid air flow from blowing directly to persons.
1) Detects the room temperature (Ta) when the DRY operation started.
2) Starts operation under conditions in the left figure according to the temperature difference between the room tempera­ture and the setup temperature (Tsc). Setup temperature (Tsc) = Set temperature on remote controller (Ts) + (0.0 to 1.0)
3) When the room temperature is lower 1°C or less than the setup temperature, turn off the compressor.
1) Detects the room temperature (Ta) when the operation started.
2) Selects an operation mode from Ta in the left figure.
3) Fan operation continues until an operation mode is selected.
4) When AUTO operation has started within 2 hours after heating operation stopped and if the room temperature is 20°C or more, the fan operation is performed with ”Super Ultra LOW” mode for 3 minutes. Then, select an operation mode.
5) If the status of compressor-OFF continues for 15 minutes the room temperature after selecting an operation mode (COOL/HEAT), reselect an operation mode.
Ts + 1
Ts – 1
Ta
Cooling operation
Monitoring (Fan)
Heating operation
Tsc
+
0.5
+
1.0
[ C]
Ta
Fan speed
L– (W5)
(W5+W3) / 2
SUL (W3)
Operation Hz control (Include limit control)
27
Item
2. Indoor fan motor control
Operation flow and applicable data, etc.
<In cooling operation>
(This operation controls the fan speed at indoor unit side.) The indoor fan (cross flow fan) is operated by the phase-
control induction motor. The fan rotates in 5 stages in MANUAL mode, and in 5 stages in AUTO mode, respec­tively. (Table 1)
Description
* Symbols
UH : Ultra High H : High M+ : Medium+ M : Medium L+ : Low+ L: Low L- : Low– UL : Ultra Low SUL : Super Ultra Low
* The fan speed broadly varies due
to position of the louver, etc. The described value indicates one under condition of inclining downward blowing.
1) When setting the fan speed to L, L+, M, M+ or H on the remote controller, the operation is performed with the constant speed shown in Fig. 1.
2) When setting the fan speed to AUTO on the remote controller, revolution of the fan motor is controlled to the fan speed level shown in Fig. 2 and Table 1 according to the setup tempera­ture, room temperature, and heat exchanger temperature.
(Fig. 1)
(Fig. 2)
(Table 1) Indoor fan air flow rate
+2.5
Ta
[ C]
+2.0
+1.5 +1.0
+0.5
Tsc
a
b
c
d
e
M+(WB)
*3
*4
*5
L(W6)
Air volume AUTO
L L+ M M+ H
W6
(L + M) / 2
W9
(M + H) / 2
WC
Indication
Fan speed
Fan speed setup
COOL ON
AUTO
MANUAL
*3 : Fan speed = (M + –L) x 3/4 + L
*4 : Fan speed = (M + –L) x 2/4 + L
*5 : Fan speed = (M + –L) x 1/4 + L
(Linear approximation from M+ and L)
Fan speed Air flow rate Fan speed Air flow rate
(rpm) (m3/h) (rpm) (m3/h)
WF UH 1100 991 1200 1101
WE H 1100 991 1200 1101
WD M+ 1090 980 1200 1101
WC H 1070 957 1180 1079
WB M+ 980 858 1080 968
WA 940 813
W9 M L+ 890 758 980 858
W8 L 780 636 850 713
W7 L+ L- L+ 750 603 810 669
W6 L L 740 591 800 658
W5 L- UL L- 700 547 760 614
W4 UL UL 700 547 700 547
W3 SUL SUL 650 492 650 492
W2 SUL 500 325 500 325
W1 500 325 500 325
42NQV050M
M
COOL
HEAT
DRY
Fan speed
level
1020 902
42NQV060M
28
Item
2. Indoor fan motor control
Operation flow and applicable data, etc.
<In heating operation>
Description
1) When setting the fan speed to L, L+, M, M+ or H on the remote controller, the operation is per­formed with the constant speed shown in Fig. 3 and Table 1.
2) When setting the fan speed to AUTO on the remote controller, revolution of the fan motor is controlled to the fan speed level shown in Fig. 5 according to the set temperature and room temperature.
3) Min air flow rate is controlled by temperature of the indoor heat exchanger (Tc) as shown in Fig. 4.
4) Cold draft prevention, the fan speed is controlled by temperature of the indoor heat exchanger (Tc) as shown in Fig. 6.
[In starting and in stability]
(Fig. 3)
(Fig. 4)
(Fig. 5)
Cold draft preventive control
(Fig. 6)
Fan speed
AUTO
Basic fan control
* No limitation while fan speed MANUAL mode is in stability. * A: When Tsc 24, A is 24, and when Tsc < 24, A is Tsc
Tsc: Set value
TSC
TA
[ C]
b
–0.5
c
–1.0
d
–1.5
e
–2.0
f
–2.5
g
–5.0
–5.5
L+ (W9)
M+ (WD)
*1
*2
*3
H (WE)
H (WE)
Line-approximate H and S
UL with Tc.
SUL (W2)
Stop
46 46
T
c
34
45 45 33
33 33 21 32 32 20
*A+4 *A+4 *A+4
*A-4 *A-4 *A-4
Fan speed MAN
UAL in starting Fan speed AUTO in stability Fan speed AUTO in starting
L L+ M M+ H
W8
(L + M) / 2
WA
(M + H) / 2
WE
Indication Fan speed
Fan speed setup
HEAT ON
AUTO
YES
NO
MANUAL
TC 42 C
Min air flow rate control
Tc
52 51
42 41
Limited to Min WD tap
*Fan speed =
(TC – – W8) + W8
No limit
*
*1: Fan speed = (M + -L+) x 1 4 + L+ *2: Fan speed = (M + -L+) x 2 4 + L+ *3: Fan speed = (M + -L+) x 3 4 + L+ (Calculated with linear approximation from M+ and L+)
FAN AUTO
FAN Manual
In starting
• Until 12 minutes passed after operation start
• When 12 to 25 minutes passed after operation start and room temp. is 3°C or lower than set temp.
• Room temp. < Set temp. –4°C
In stability
• When 12 to 25 minutes passed after operation start and room temp. is higher than (set temp. –3°C)
• When 25 minutes or more passed after operation start
• Room temp. Set temp. –3.5°C
5) In order to prevent Cold draft when compressor step during heating operation. Then louver will move to upper position and fan speed will reduce or off.
29
Item
3. Outdoor fan motor control
Operation flow and applicable data, etc.
The blowing air volume at the outdoor unit side is controlled. Receiving the operation command from the controller of
indoor unit, the controller of outdoor unit controls fan speed. * For the fan motor, a DC motor with non-stage variable
speed system is used. However, it is limited to 8 stages for reasons of controlling.
Description
1) The operation command sent from the remote controller is processed by the indoor unit controller and transferred to the controller of the outdoor unit.
2) When strong wind blows at outdoor side, the operation of air conditioner continues with the fan motor stopped.
3) Whether the fan is locked or not is detected, and the operation of air conditioner stops and an alarm is displayed if the fan is locked.
4) According to each operation mode, by the conditions of outdoor temperature (To) and compressor revolution, the speed of the outdoor fan shown in the table is selected.
2) Fan speed 400
when the motor stopped.
Air conditioner ON
(Remote controller)
YES
YES
NO
NO
Indoor unit controller
Fan motor ON
3) Fan lock
OFF status of
fan motor continues.
4) Motor operates as shown in the table below.
1) Outdoor unit operation command (Outdoor fan control)
ir
OFF
Alarm
display
MIN MAX MIN MAX MIN MAX
< 30.5 < 55.1 55.1
To38
f6 f9 f8 fB fA fE
To 10°C
f6 f8 f9
To 28
f5 f9 f7 fB f9 fE
To 25°C
f8 fA fC
To 15
f3 f7 f5 f9 f7 fB
To 5.5°C
fA fB fD
To 5
f1 f3 f1 f7 f3 f9
To 5.5°C
fA fB fD
To 0.5
f1 f3 f1 f5 f3 f7
To 10°C
f5 f7 f9
To 0.5
f0 f1 f0 f3 f1 f4
To 5°C
f7 f9 fB
To 38
f6 f9 f8 fB fA fB
To 5.5°C
f9 fA fB
To 28
f5 f9 f7 fB f9 fB
To 5.5°C
f9 fA fB
To 15
f3 f7 f5 f9 f7 fB
fD fD fD
To 5
f1 f3 f1 f7 f3 f9
To 0.5
f1 f3 f1 f5 f3 f7
To 0.5
f0 f1 f0 f3 f1 f4
f1 fF f1 fF f1 fF
To
During
ECO and
QUIET
and
comfort
sleep
To is abnormal
Compressor speed (rps)
In Heating operation
To
During
ECO mode
When To is abnormal
50.3
< 50.3< 22.1
Compressor speed
(rps)
In cooling operation
≥ ≥ ≥ ≥ ≥ ≥ ≥ ≥ ≥ ≥ ≥
≥ ≥ ≥
Outdoor fan speed (rpm)
38NYV050M 38NYV060M Tap 38NYV050M 38NYV060M
0 0 f 8 560 560 230 230 f 9 640 640 300 300 f A 670 670 350 350 f B 700 750 410 410 f C 800 840 480 480 f D 800 840 500 500 f E 800 920 530 530 f F 800 920
f 0 f 1 f 2
f 7
f 3 f 4 f 5 f 6
Tap
Air conditioner
OFF
Loading...
+ 70 hidden pages