Carrier 42NQ018N, 38NY018N Service Manual

SERVICE MANUAL
AIR CONDITIONER
SPLIT WALL TYPE
FILE NO. SVM-10035-1
42NQ018N / 38NY018N
Revised Apr, 2010
1. SPECIFICATIONS
2. CONSTRUCTION VIEWS
2-1 Indoor Unit 2-2 Outdoor Unit
3. WIRING DIAGRAM
4. SPECIFICATION OF ELECTRICAL PARTS
4-1 Indoor Unit 4-2
Outdoor Unit
5. REFRIGERATION CYCLE DIAGRAM
6. CONTROL BLOCK DIAGRAM
7. OPERATION DESCRIPTION
FILE NO. SVM-10035
7-1 Remote control 7-2 Outline of Air Conditioner Control
7-3 Description of Operation Circuit 7-4 Description of Safety and Reliability Prevention Function 7-5 ECO Operation 7-6 FILTER check lamp 7-7 Auto Restart Function
8. INSTALLATION PROCEDURE
8-1 Safety Cautions 8-2 Installation Diagram of Indoor and Outdoor Units 8-3 Installation 8-4 Indoor Unit 8-5 Outdoor Unit 8-6 Others
1
9. TROUBLESHOOTING CHART
9-1 Troubleshooting Procedure 9-2 Basic Check Items 9-3 Primary Judgement 9-4 Self-Diagnosis by Remote Control (Check Code)
9-5 Troubleshooting Flowcharts
Troubleshooting for Wiring
9-6 9-7 Troubleshooting for P.C. Board 9-8 Troubleshooting for Remote Control
HOW TO REPLACE THE MAIN PARTS
10.
10-1 Indoor Unit
Outdoor Unit
10-2
11. EXPLODED VIEWS AND PARTS LIST
11-1 Indoor Unit (E - Parts Assy) 11-2 Indoor Unit 11-3 Outdoor Unit
FILE NO. SVM-10035
2
1. SPECIFICATIONS
FILE NO. SVM-10035
MODEL
42NQ018N / 38NY018N
ITEM Cooling Heating
Capacity
kW
Phase
Power source
Hz Power consumption kW Power factor % Running Indoor A Current Outdoor A Starting current A Moisture removal lit/h Noise Indoor (H/M+/M/L+/L) dB
Outdoor dB
Refrigerant Name of refrigerant
Rated amount kg Refrigerant control Interconnection Gas side size mm pipe Connection type
Liquid side size mm
Connection type
Maximum length m
(One way)
Maximum height m
difference
INDOOR UNIT
Dimensions Height mm
Width mm
Depth mm Net weight kg Evaporator type Indoor fan type Airflow volume High fan
Medium fan
Low fan
3
m
3
m
3
m Fan motor output W Air filter
OUTDOOR UNIT
Dimensions Height mm
Width mm
Depth mm Net weight kg Condenser type Outdoor fan type Airflow volume
3
m Fan motor output W Compressor Model
Output W Safety device Louver type Usable outdoor temperature range °C
220V
5.10
V
1.58 98
7.05
56
/h /h /h
/h
2400
1000
840 750
15 ~ 43 -10 ~ 24
240V 220V 240V
5.45 5.565.12
1
220 - 240
50
1.60 96
1.51 1.55 98 97
0.30
6.65 6.70 6.35 31
2.0
44/42/39/37/35
57 57 58
R410A
1.53
Capillary tube
12.7
Flare connection
6.35
Flare connection
1
15*
2
20*
8
42NQ018N
320
1050
228
13
Finned tube
Cross flow fan
1000
900 770
30
Honeycomb woven filter with PP frame
38NY018N
715 780 290
47
Finned tube
Propeller fan
2550 2400 2550
42
PA200X2CS-4KU1
1500
Td Sensor, Fuse, IOL
Automatic louver
Note *1 Chargeless pipe
*2 Maximum pipe
3
Note : 1
Capacity is based on the following temperature conditions.
FILE NO. SVM-10035
Condition
Temperature
(DB) 27°C
Indoor unit inlet air temperature
(WB) 19°C
(DB) 35°C
Outdoor unit inlet air temperature
(WB) 24°C
Note : 2
Charge refrigerant according to the table below.
Refrige rant
*1 No need to charge
extra refrigerant
*2 Need to charge
extra refrigerant
JIS C9612
Cooling
42NQ018N / 38NY018N
15 m or less
Over 15 m up to 20 m (20 g/m)
4
2-1 Indoor Unit
FILE NO. SVM-10035
2. CONSTRUCTION VIEWS
Grille Inlet
Front Panel
73.57
50
Knock out system
Heat exchanger
320
50
Air inlet
72
278 200 222 150
132
1050
Air outlet
200
Air filter
228
73.5
50
7
Knock out system
50
7278
78
157
Drain hose (0.5m)
320
40
525
Hanger
Connecting pipe (0.39m) (Flare
12.70)
85 23
Hanger
6
5
Hanger Hanger
262.5
786
235
215
Center line
Installation plate outline
Connecting pipe (0.49m) (Flare 6.35)
235
215
262.5
Hanger
For stud bold ( For stud bold (
6
5
10947 215.5 153.5
56
Wireless remote controller
63
Remote controller holder
6) 8~
10)
Outline of indoor unit
40
19
125
26
5
2.2 Outdoor Unit
600
50 36
R
15
FILE NO. SVM-10035
A
28
125108
6 hole
320
306
Ø
R
5.5
A Detail Drawing (Back leg)
HANDLE
290
320
Ø
Ø
715
86
25 Drain outlet
FAN-GUARD
436
275
90 600 90 69
2Ø11x14 Hole (For
Ø8-Ø
10 anchor bolt)
B
306
320
Hole
6
Ø
11x14 Hole
Ø
36 50
B Detail Drawing (Front leg)
320 342
R
15
HANDLE
COVER-PV
Z
100 or more
320
100 or more
Z View
600
Air inlet
Air out
let
00 or more
6
Installation dimension
600 or more
4x
54
129
84
11 Long holes(For
Ø
Service port
10 anchor bolt)
Ø8-Ø
Electrical part cover
Liquid side (Flare Ø6.35)
Gas-side (Flare Ø 12.70)
6
3. WIRING DIAGRAM
FILE NO. SVM-10035
OUTDOOR TERMINAL BLOCK
POWER SUPPLY 220- 240 V ~ 50 Hz
L
BLK
RED
BLK
1/L1 5/L3
2/T1 6/T3
RED
WHI PNK
COMPRESSOR
2
1
3
GRN&YEL
2
N
FERRITE CORE
RED
MAGNETIC
CONTACTOR
1
3
i
CHASSIS
A1
52C
A2
CAPACITOR CAPACITOR
S
C
BLK
R
RED
WHI RED
FAN MOTOR
TRANSFORMER
OUTDOOR UNIT
BLK BLK
BLK
BLK
RED
RED
BLK
BLK
WHI
RED
GRY
BLU
YEL
BLU
BLU COIL FOR 4 WAY VALVE
MAIN P.C. BOARD (MCC-890)
1
1 2
CN06
3
3
1
1
CN05
3
3
SG01
1
1
F01
3
3
250VAC T6. 3A
5
5
CN01
7
7
9
9
1
CN11
313
11
33
CR11
CN02
CR12
CR13
TNR R74
CN03
1 1
RY07
RY05
3
TNR R73
RY06
CN07
CN08
DISCHARGE PIPE SENSOR (TD)
BLU
1
1 2 3
3
BLU
BLK
1
1 2 3
3
BLK
HEAT EXCHANGER SENSOR (TE)
7
FILE NO. SVM-10035
4. SPECIFICATION OF ELECTRICAL PARTS
4-1. Indoor Unit
No. Parts name Type Specifications
1 Fan motor (for indoor) ICF-340-30-2B DC 340V, 30W 2 Thermo sensor (TA-sensor) 10k at 25 C 3 Switching Transformer (T01) 4 Microcontroller unit (IC15) TMP87CM40ANG-6P68 5 Heat exchanger sensor
(TC-sensor) 6 Line filter (L01) LC*SS11V-R06270 7 Bridge rectifier (DB01) 8 Capacitor (C03) 9 Fuse (F01)
10 Varistor (R09, R10) 11 Resistor (R01 ) 12 Louver motor
MP24Z3T
EKMH451VSN121MQ35S
SWT-77
D3SBA60
BET6.3A
SR561K14DO
RF-5TK1R8
DC 7V, 12V
12VDC
W
10k at 25 C
27mH, 600mA 4A, 600 V 120mF, 450 V
T6.3A, 250VAC
560 V
W
1.8 , 5 W
°
W
°
4-2. Outdoor Unit
No. Parts name Type Specifications
Output (Rated) 1500W, 2poles, 1 phase, 220 − 240V, 50Hz
1 Compressor PA200X2CS-4KU1 Winding resistance (Ω) Red-Black White-Black
(at 20°C) 1.85 2.62 Output (Rated) 42W, 4poles, 1 phase, 220 – 240V, 50Hz
2 Fan motor (for outdoor) FG-240-42A-1 Winding resistance (Ω) Red-Black White-Black
(at 20°C) 128 126
Running capacitor
3
(for fan motor) Running capacitor
4
(for compressor) Solenoid coil
5
(for 4-way valve)
6 Thermo sensor TE / TD 10k at 25°C / 50k at 25°C 7 Magnetic contactor A23T 220 − 240V, 50Hz 8 Transformer TT-05 220 − 240V
9 Microcomputer TMP47C840N 10 Varistor (R73, R74) 15G471K 470V 11 Fuse (F01) TSCR T6.3A, 250V
DS451305NPQB AC 450V, 3.0 µF
B32332I5606J063 AC 450V, 50µF
VHV (STF) AC 220 − 240V
8
FILE NO. SVM-10035
5. REFRIGERATION CYCLE DIAGRAM
Indoor unit
Cooling
0.39 m (Connecting pipe)
Æ12.7
O.D.:12.7 mm O.D.:6.35 mm
Cooling
Heating
Heating
P
Packed valve
(Æ12.7)
Heating
4-way valve
Cooling
Discharge Muffler
25x160L
Compressor
Accumulator
PA200X2CS-4KU1
Heat exchanger
Cross flow fan
T1
Capillary tube Æ1.7 x 600
Packed valve
(Æ6.35)
Capillary tube
Æ2.0 x 1000
l
0.49 m
(Connecting pipe)
Æ6.35
l
Heat exchanger
Refrigerant R410A : 1.53 kg.
Cooling Heating
Propeller fan Outdoor unit
Mark ( ) means check points of Gas Leak.
Ambient temp.
50Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
Indoor Outdoor
Standard 2.53 42.0 High 20/15 7/6
Heating Overload*1 3.30 ~ 3.65 51.0 ~ 55.0 Low 27/- 24/18
Low temperature 1.75 32.0 High 20/
-
-10/-10
Standard 0.94 11.0 High 27/19 35/24
Cooling Overload 1.12 15.0 High 32/23 43/26
Low temperature 0.72 4.2 Low 21/15 21/15
Note
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
·
·
*1 During heating overload operation, a value for the high temperature limit control operation is included.
9
Heat Exchanger Sensor
6. CONTROL BLOCK DIAGRAM
Indoor Unit Control Panel
M.C.U.
Functions
Louver Control
FILE NO. SVM-10035
Operation
Display
Temperature Sensor
Infrared Rays Signal Receiver
Initiallizing Circuit
Infrared
Rays
Remote
Control
From Outdoor Unit AC 220-240V~ 50Hz
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Noise Filter
3-minute Delay at Restart for Compressor
Motor Revolution Control
Processing
(Temperature Processing)
Timer
Serial Signal Communication
Louver ON/OFF Signal
Louver Driver
Serial Signal Transmitter/Receiver
Serial Signal Communication
Timer
Display
Filter Sign
Display
PRE DEF.
Sign Display
Hi Power
Sign Display
Indoor
Fan Motor
Louver Motor
REMOTE CONTROLLER
Remote Controller
Infrared Rays, 36.7kHz
Operation [ ]
Operation Mode Selection
AUTO, COOL, DRY, HEAT,FAN ONLY
Thermo. Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver AUTO Swing
Louver Direction Setting
ECO
Hi-POWER
10
7. OPERATION DESCRIPTION
7-1. Remote control
7-1-1. Remote control and its functions
Infrared signal emitter
1 2
Start/Stop button ( ) Mode select button ( )
3
Temperature button ( )
4
Fan speed button ( )
5
Swing louver button ( )
6
Set louver button ( )
7
On timer button ( )
8
ON
13
FILE NO. SVM-10035
1
5 4
3
Off timer button ( )
9
10
Sleep timer button ( )
11
Setup button ( )
12
Clear button ( )
13
Memory and Preset button ( )
14
High power button ( )
15
Economy button ( )
16
Filter reset button ( )
17
Clock reset button ( )
18
Check button ( )
OFF
7-1-2. Operation of remote control
1. AUTOMATIC OPERATION
To automatically select cooling, heating, or fan only operation.
1. Press MODE : Select A.
2. Press MODE : Set the desired temperature.
2. COOLING / HEATING / FAN ONLY OPERATION
10
18 16
2
14
6 7
8
15 12
9
11
17
1. Press MODE : Select Cool , Heat , or Fan only .
2. Press MODE : Set the desired temperature. Cooling: Min. 17°C, Heating : Max, 30°C, Fan Only: No temperature indication
3. Press : Select AUTO, LOW , LOW+ , MED , MED+ , or
HIGH .
3. DRY OPERATION (COOLING ONLY)
For dehumidification, a moderate cooling performance is controlled automatically.
1. Press MODE : Select Dry .
2. Press MODE : Set the desired temperature.
4. Hi-POWER OPERATION
To automatically control room temperature and airflow for faster cooling or heating operation (except in DRY and FAN ONLY mode)
Press HI-POWER : Start and stop the operation.
11
FILE NO. SVM-10035
5. ECO OPERATION
To automatically control room to save energy (except in DRY and FAN ONLY mode)
Press : Start and stop the operation.
Note: Cooling operation; the set temperature will increase automatically 1 degree/
hour for 2 hours (maximum 2 degrees increase). For heating operation the set temperature will decrease.
6. TEMPORARY OPERATION
In case of the misplaced or discharged remote control
Pressing the RESET button, the unit can start or stop without using the remote control.
Operation mode is set on AUTOMATIC operation, preset temperature is 24°C and fan operation is automatic speed.
7. TIMER OPERATION
Setting the ON Timer Setting the OFF Timer
RESET button
1
Press : Set the desired ON timer.
Press : Set the timer. Press : Set the timer.
2
3
3
Press : Cancel the timer. Press
ON
Press : Set the desired OFF timer.
OF F
: Cancel the timer
Daily timer allows the user to set both the ON & OFF timers and will be activated on a daily basis.
Setting Daily Timer
ON
1
Press
: Set the ON timer.
3
Press .
2
Press
OF F
: Set the OFF timer.
· During the daily timer is activation, both arrows are indicated.
( or )
Press button during the ( or )
4
mark flashing.
Note:
· Keep the remote control in accessible transmission to the indoor unit; otherwise, the time lag of up to 15 minutes will occur.
· The setting will be saved for the next same operation.
8. PRESET OPERATION
Set your preferred operation for future use. The setting will be memorized by the unit for future operation (except air flow direction).
1. Select your preferred operation.
2. Press and hold for 3 seconds to memorize the setting. The mark
displays.
3. Press : Operate the preset operation.
 − 12 − 
FILE NO. SVM-10035
9. AUTO RESTART OPERATION
To automatically restart the conditioner after the power failure (Power of the unit must be on.)
Setting
1. Press and hold the RESET button on the indoor unit for 3 seconds to set the operation. (3 beep sound and OPERATION lamp blink 5 time/sec for 5 secpmds)
Do not operate ON timer and OFF timer.
2. Press and hold the RESET button on the indoor unit for 3 seconds to cancel the operation. (3 beep sound but OPERATION lamp does not blink)
10. SLEEP TIMER OPERATION
To start the sleep timer (OFF timer) operation
Press : Select 1, 3, 5 or 9 hrs for OFF timer operation.
 − 13 − 
7-1-3. Name and Functions of Indications on Remote Controller
[Display]
FILE NO. SVM-10035
All indications, except for the clock time indicator, are displayed by pressing the
1
Transmission mark
This transmission mark indicates when the remote controller transmits signals to the indoor unit.
2
Mode indicator
Indicates the current operation mode. (A :
Auto, : Cool, : Heat, : Dry, : Fan only)
3
Temperature indicator
Indicates the temperature setting.
ºC ºC
(17 to 30 )
FAN speed indicator
4
Indicates the selected fan speed. AUTO or five fan speed levels
(
LOW , LOW+ , MED , MED+ , HIGH ) can be shown. Indicates AUTO when the operating mode is
either AUTO or : Dry.
TIMER and clock time indicator
5
The time setting for timer operation or the clock time is indicated.
The current time is always indicated except during TIMER operation.
6
Hi-POWER indicator
Indicates when the Hi-POWER operation starts. Press the Hi-POWER button to start and press it
again to stop the operation.
7
(PRESET) indicator
Flashes for 3 seconds when the PRESET button is pressed during operation.
The button for more than 3 seconds while the mark is
blinks.
Press another button to turn off the mark.
ECO indicator
8
Indicates when the ECO is in activated. Press the ECO button to start and press it again
to stop operation.
A, B change indicator remote controller
9
When the remote controller switching function is set, "B" appears in the remote controller display. (When the remote controller setting is "A", there is no indication at this position.)
10
Swing
Indicates when louver is swing. Press swing button to start the swing operation and press it again to stop the swing operation.
mark is shown when holding down the
button.
1
6
9
3
8
7
2
10
5
4
14
FILE NO. SVM-10035
7-2. Outline of Air Conditioner Control
This is a fixed capacity type air conditioner, which uses a DC motor for an indoor fan. The DC motor drive circuit is mounted in the indoor unit. And electrical parts which operate the compressor and the outdoor fan motor, are mounted in the outdoor unit. The air conditioner is mainly controlled by the indoor unit controller. The controller operates the indoor fan motor based upon commands transmitted by the remote control and transfers the operation commands to the outdoor unit. The outdoor unit receives operation commands from the indoor unit, and operates the outdoor fan motor and the compressor.
(1) Role of indoor unit controller
The indoor unit controller receives the operation commands from the remote control and executes them.
Temperature measurement at the air inlet of the
indoor heat exchanger by the indoor
temperature sensor
Temperature measurement of the indoor heat
exchanger by the heat exchanger sensor
Louver motor control
Indoor fan motor operation control
LED display control
Transferring of operation commands to the
outdoor unit
Receiving of information of the operation status
and judging of the information or indication of error
(2) Role of outdoor unit controller
The outdoor unit controller receives the operation commands from the indoor controller and executes them.
Compressor operation
control
Operation control of
outdoor fan motor
Operations according to the commands
from the indoor unit
Turning off the compressor and outdoor fan
when the outdoor unit receives the shutdown command
7-2-1. Louver control
(1) Vertical air flow louver
Position of veritcal air flow louver is automatically controlled according to the operation mode. Besides, position of vertical air flow louver can be arbitrarily set by pressing [FIX] button. The louver position which is set by [FIX] button is stored in the microcomputer, and the louver is automatically set at the stored position for the next operation.
(2) Swing
If [SWING] button is pressed when the indoor unit is in operation, the vertical air flow louver starts swinging. When [SWING] button is pressed, it stops swinging.
7-2-2. Indoor Fan Control
The operation controls the fan speed at indoor unit side. The indoor fan (cross flow fan) is operated by
the phase control induction motor. The fan rotates in 3 stages in MANUAL mode, and in 3 stages in AUTO mode, respectively. (Table 7-2-2)
1) When setting the fan speed to L, M or H on the remote controller, the operation is performed with the constant speed shown in Fig. 7-2-1
Table (7-2-1)
Indication
L L+
M M+
H
Fan speed
Low
(L + M) / 2
Med
(M + H) / 2
High
2) When setting the fan speed to AUTO on the remote controller, revolution of the fan motor is controlled to the fan speed level shown in Table 7-2-2 according to the setup temperature, room temperature, and heat exchanger temperature.
Table 7-2-1 Indoor fan and air flow rate
Cooling
OPERATION
MODE
42NQ018N
Model
Fan only
Dry M L L- UL SL
Heat
rpm
3
Air flow volume (m
/h)
3) When setting the fan speed to QUIET on the remote controller, revolution of the fan motor is controlled to the fan speed level is L-.
FAN TAP
UH H M L L- UL SL
HM LL-
UH H M L L- UL SL
1100
1000
1100 1000 940 870 850 850 750 640 550 550 550
1000 900 840 770 750 750 650 540 450 450 450
15
FILE NO. SVM-10035
7-3. Description of Operation Mode
(1) When turning on the breaker, the operation lamp
blinks. This means that the power is on (or the power supply is cut off.)
(2) When pressing [START/STOP] button on the
remote control, receiving beep sounds from the indoor unit, and the next operation is performed together with opening the vertical air flow louver.
(3) Once the operation mode is set, it is memorized in
the microcomputer so that the previous operation can be effected thereafter simply by pressing [START/STOP] button.
7-3-1. Fan only operation
([MODE] button on the remote control is set to the fan only operation.)
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-1. When [FAN] button is set to LOW, MED, or HIGH, the motor operates with a constant air flow.
°C
7-3-2. Cooling operation
([MODE] button on the remote control is set to the cooling operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in Fig. 7-3-2.
° C
ON ON
OFF OFF OFF ON
4-way valve
Compressor
Outdoor fan
(Room temp.) (Preset temp.)
Preset temp.
0.5
0
Fig. 7-3-2
display lamp
OPERATION
+3 +2.5 +2
+1.5 +1 +0.5
(Room temp.) (Preset temp.)
Preset temp.
0
(Preset temp.: 24 °C)
NOTE 1 : *1 : Fan speed = (M + L) x 3/4 + L
*2 : Fan speed = (M + L) x 2/4 + L *3 : Fan speed = (M + L) x 1/4 + L
2 : The ECO operation can not be set
(Linear approximation from M+ and L)
Fig. 7-3-1 Setting of air flow [FAN:AUTO]
M+
*1 *2 *3
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-3. When [FAN] button is set to LOW, MED or HIGH, the motor operates with a constant air flow.
°C
(Room temp.) (Preset temp.)
Preset temp.
+3 +2.5 +2 +1.5 +1 +0.5
0
-0.5
M+
*1 *2 *3
NOTE1 : *1 : Fan speed = (M + − L) x 3/4 + L
*2 : Fan speed = (M + − L) x 2/4 + L *3 : Fan speed = (M + L) x 1/4 + L
(Linear approximation from M+ and L)
-
16
Fig. 7-3-3 Setting of air flow [FAN:AUTO]
-
FILE NO. SVM-10035
7-3-3. Dry operation
([MODE] button on the remote control is set to the dry operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in Fig. 7-3-4.
° C
ON:6min.
OFF:4min.
ON
ON:5min.
OFF:5min.
OFF
4-way valve
Outdoor fan
(Room temp.) (Preset temp.)
Preset temp.
+3
+2
+1
ON:6min.
OFF:4min.
OFF
ON:5min.
OFF:5min.
OFF
0
Compressor
Fig. 7-3-4
7-3-4. Heating operation
(1) The compressor, 4-way valve, outdoor fan and
Preset temp.
display lamp
OPERATION
([MODE] button on the remote control is set to the heating operation.)
operation display lamp are controlled as shown in Fig. 7-3-6.
° C
0
0.5
(Room temp.) (Preset temp.)
ON
OFF
ON
Compressor
ON
OFF
ON
4-way valve
Outdoor fan
OPERATION
display lamp
Fig. 7-3-6
(2) The microprocessor turns the compressor on and
off at the regular intervals (4 to 6 minutes). While the compressor is turning off, the indoor fan motor operates in the SUPER LOW position. The pattern of operation depending on the relation between room temperature and preset temperatures is shown in Fig. 7-3-5.
Room temp.
Preset temp.+1
Preset temp.
Compressor
Outdoor fan
Indoor fan
ON ON ON ON
OFF OFF OFF
L. *S.L. S.L.L. L. S.L. L.
*Super Low
Fig. 7-3-5
(3) [FAN] button on the remote control is set to AUTO
only.
(4) The ECO operations can not be set.
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-7. When [FAN] button is set to LOW, LOW+, MED, MED+ or HIGH, the motor operates with a constant air flow.
Preset temp.
°C
0
-0.5
-1
-1.5
-2
-5.0
-5.5
[FAN AUTO]
(Room temp.) (Preset temp.)
L
*1 *2
*3
+
M
*1 : Fan speed = (M + L) x 1/4 + L
*2 : Fan speed = (M + − L) x 2/4 + L *3 : Fan speed = (M + L) x 3/4 + L
(Calculated with Linear approximation from M+ and L)
Fig. 7-3-7
-
17
-
FILE NO. SVM-10035-1
y.
c
e
(3) The indoor heat exchanger restricts revolving
speed of the fan motor to prevent a cold draft. The upper limit of the revolving speed is shown in Fig. 7-3-8
Fan speed AUTO Fan speed MANUAL
46Tc34 45 33
33 21 32 20
*A+0 *A+0
*A-8 *A-8
Fan speed MANUAL or AUTO in starting Fan speed AUTO in stability
* No limitation while fan speed MANUAL mode is in stabilit * A: When Tsc 24, A is 24, and when Tsc < 24, A is Ts
Tsc: Set valu
Normal AUTO
Line-approximate H and SL with Tc.
SL (W2)
Stop
L-H (Up to setting speed)
Line-approximate H and SL with Tc.
SL (W2)
Stop
[In starting and in stability]
In starting
FAN Until 12 minutes
AUTO
passed after operation start
When 12 to 25 minutes passed after operation
start and room temp. is 3°C or lower than set temp.
In stability
When 12 to 25 minutes passed after opeartion
start and room temp. is than (set )
between preset
When 25 minutes or more passed after operation start
3°C
7-3-5. Automatic operation
([MODE] button on the remote control is set to the automatic operation.)
(1) One of 3 operations (Cooling, Fan only or Heating)
is selected according to difference between the preset temperature and the room temperature at which the automatic operation has started, as shown in Fig. 7-3-9. The Fan only operation continues until the room temperature reaches a level at which another mode is selected.
(2) Temporary Auto
When the [RESET] button on the indoor unit
is pushed, the preset temperature is fixed at 24°C and the indoor unit is controlled as shown in Fig. 7-3-9.
°C
Cooling operation
0
Fan only operation
-1
Heating operation
(Room temp.) (Preset temp.)
FAN Room temp. < Set
Manual
temp.–4°C
Room temp. Set temp. –3.5°C
Fig. 7-3-8 Cold draft preventing control
(4) In order to prevent cold draft when compressor
during heating operation.Then louver will move to upper position and fan speed will reduce or OFF.
-
18
Fig. 7-3-9
-
7-4. Drescription of Safety and Reliability Prevention Function
FILE NO. SVM-10035
7-4-1. Low-Temperature Limit Control
The microcontroller detects the indoor heat exchanger temperature to prevent the indoor heat exchanger from freezing. The compressor and outdoor fan motor are controlled as shown in Fig. 7-4-1.
Heat exchanger temperature
(°C)
6
2
Compressor Outdoor fan
ON
Less than 2°C continues
for 5 minutes
OFF
Fig. 7-4-1
7-4-2 High-Temperature Limit Control
(Heat pump model only)
The microcontroller detects the indoor heat exchanger temperature to prevent pressure of a refrigerating cycle from increasing excessively. The compressor and outdoor fan motor are controlled as shown in Fig. 7-4-2.
7-4-3. Defrost Operation *Heat pump model only
When the indoor unit is in heating operation, if the refrigerant evaporation temperature detected by the outdoor heat exchanger sensor is under the specified temperature, the outdoor unit starts the defrosting operation. At this time, the 4-way valve relay and the outdoor fan motor are turned off. The indoor fan motor is also turned off by the cold draft preventing control of the indoor microcomputer. Then, [PRE. DEF.] lamp on the indoor unit comes on. The defrosting operation stops and the 4-way valve relay, outdoor fan motor and the indoor fan motor are turned on automatically when the refrigerant evaporation increases to the specified temperature, or when the defrosting time is over 12 minutes.
7-4-3-1. Defrost starting condition
A-Zone : If -10°C > Teo ≥ − 18°C, defrost will
start when. Teo - Te 2.5°C at teat 20 sec or
~ 30 min after operation.
B-Zone : If Te ≤ −18°C, defrost start instantaneously
(Suddenly) 00 ~ 25 min ofter operation
C-Zone : If -2ºC Teo ≥ −10°C defrost will start when
Teo - Te ≤ −3°C at least 20 sec or ~ 60 min after operation.
Compressor
OFF
ON
ON
Outdoor fan
OFF
OFF
ON
Fig. 7-4-2
Heat exchanger temp.
(°C) 62
55 54
7-4-3-2. Defrost finish condition.
1) If Te 3°C at least 60 sec -->4 way value on.
2) If Te 8°C --> 4 way value on.
Timing
Operation time (4 Loops = Tt)
Td1
Td2
Td3 Td4
Finish time recordStart time record
Defrost time rate : (Td/Tt) x 100 Heating time rate : (Tt - Td) x Tt
Fig. 7-4-3
-
19
-