Carrier 38GL2M48G, 38GL2M18G, 38L3M21G, 38GL3M30G, 38GL4M24G Installation Manual

...
38GL_M…G /
38YY(S)_M…G
INST ALLA TION MANUAL
38GL_M…G / 38YY(S)_M…G
Cooling only and heat pump multisplit system outdoor units
For operation and maintenance instructions of this unit as well as installation instructions of the indoor unit, refer to the relevant manuals.
Contents Page
Dimensions and weight ................................................................................................................. 2
Minimum clearances ..................................................................................................................... 3
Connections .................................................................................................................................. 3/5
Operating limits ............................................................................................................................. 5
General information....................................................................................................................... 6
Warnings: avoid............................................................................................................................. 7
Refrigerant connections................................................................................................................ 8/10
Electrical connections ................................................................................................................... 11/16
Electrical data................................................................................................................................16
Pump down and check the refrigerant charge .............................................................................. 17/18
Unit maintenance and troubleshooting......................................................................................... 19
Diagnostics and testing................................................................................................................. 20
Accessories ................................................................................................................................... 20
ENGLISH
R-410A – QUICK REFERENCE GUIDE
•R-410A refrigerant operates at 50%-70% higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with R-410A.
•R-410A refrigerant cylinders are pink.
•R-410A refrigerant cylinders have a dip tube which allows liquid to flow out of cylinder in an upright position.
•In case of maintenance, R-410A systems should be charged with refrigerant in liquid phase. Use a commercial type metering device in the manifold hose in order to vaporize the liquid refrigerant before it enters in the unit.
•The R-410A, as for other HFC, is only compatible with oils chosen by the compressor manufacturer. For this reason, for the type of oil to be used, always refer to the plate on the compressor and the unit.
•A vacuum pump is not enough to remove moisture from oil.
•POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
•Never open system to atmosphere while it is under vacuum.
•When the system must be opened for service, break vacuum with dry nitrogen and replace filter driers.
•Do not vent R-410A into the atmosphere.
•Use only Carrier matching indoor units (Table I).
GB - 1
38GL_MG / 38YY(S)_MG
Dimensions and weight
Table I
Cooling Hi-Wall Console Cassette Satellite
only
models 42PHQ-N 42PHQ-P 42VMC-N 40KMC-N 40SMC-N 40DMC
38GL2M12G 009 - 012 009 - 012 009 - 012 012 009 - 012 ­38GL2M18G 009 009 009 - 009 ­38GL2M24G 012 012 012 012 012 ­38GL2M36G 018 018 018 018 018 018 38GL2M48G 024 024 024 024 024 024 38GL3M21G 009 - 012 009 - 012 009 - 012 012 009 - 012 ­38GL3M30G 009 - 012 - 018 009 - 012 - 018 009 - 012 - 018 012 - 018 009 - 012 - 018 ­38GL4M24G 009 - 012 009 - 012 009 - 012 012 009 - 012 -
Heat Hi-Wall Console Cassette Satellite
pump
models 42PHQ-N 42PHQ-P 42VMC-N 40KMC-N 40SMC-N 40DMC 38YY2M18G 009 009 009 - 009 ­38YY2M21G 009 - 012 009 - 012 009 - 012 012 009 - 012 ­38YY2M24G 012 012 012 012 012 - 230V ~ 50Hz
38YY(S)2M36G 018 018 018 018 018 018 38YY(S)2M48G 024 024 024 024 024 024
Power supply
230V ~ 50Hz
Power
supply
Dimensions and weight
A
A
F
B
EED
C
B
EED
C
Cooling only
models
Ø 8,5
38GL2M12G
38GL2M12G 38GL2M18G 38GL2M24G 38GL3M21G 38GL3M30G 38GL4M24G 38GL2M36G 38GL2M48G
A mm 660 800 800 800 800 800 800 800 B mm 504 590 590 590 803 803 1264 1264 C mm 220 300 300 300 300 300 300 300 D mm 390 508 508 508 508 508 508 508 E mm 135 146 146 146 146 146 146 146 F mm 250 330 330 330 330 330 330 330
kg
kg 39 55 58 58 75 69 109 112
A
Ø 8,5
38GL2M18G 38GL2M24G 38GL3M21G 38YY2M18G
F
B
EED
C
A
38GL3M30G 38GL4M24G 38YY2M21G 38YY2M24G
Ø 8,5
F
38GL2M36G 38GL2M48G
B
EED
C
38YY(S)2M36G 38YY(S)2M48G
F
GB - 2
Heat pump
models
38YY(S)2M36G 38YY(S)2M48G 38YY2M18G 38YY2M21G 38YY2M24G
A mm 800 800 800 800 800 B mm 1264 1264 590 803 803 C mm 300 300 300 300 300 D mm 508 508 508 508 508 E mm 146 146 146 146 146 F mm 330 330 330 330 330
kg
kg 112 119 59 69 71
38GL_MG / 38YY(S)_MG
Minimum clearances and connections
Minimum clearances
A
B
C
A
F
F
38GL2M18G 38GL2M36G 38GL2M24G 38GL2M48G
Models
38GL2M12G
38GL3M21G 38YY2M21G 38GL3M30G 38YY2M24G 38GL4M24G 38YY(S)2M36G 38YY2M18G 38YY(S)2M48G
A mm 50 100 100 B mm 250 250 250 C mm 500 500 500 D mm 50 50 100 E mm 470 470 670 F mm 400 400 400
D
E
DE
ENGLISH
Connections
A B
A1 A2
38GL2M12G
A B
38GL2M18G 38GL2M24G
A1 A2
B
38GL3M21G 38GL4M24G38GL3M30G
A B
A1 A2
B
A1 A2 B1 B2
A B
A B
38GL2M36G 38GL2M48G
38YY2M18G
38YY2M21G 38YY2M24G
38YY(S)2M36G 38YY(S)2M48G
GB - 3
38GL_MG / 38YY(S)_MG
Connections
Model Liquid Gas
Pipe diameter
38GL Indoor (Liquid) (Suction)
unit mm (inches) mm (inches)
2M12G
2M18G
2M24G
3M21G A2 6.35 (1/4") 12.70 (1/2")
3M30G A2 6.35 (1/4") 12.70 (1/2")
A1 6.35 (1/4") 9.52 (3/8") A2 6.35 (1/4") 12.70 (1/2")
A 6.35 (1/4") 9.52 (3/8") B 6.35 (1/4") 9.52 (3/8")
A 6.35 (1/4") 12.70 (1/2") B 6.35 (1/4") 12.70 (1/2")
A1 6.35 (1/4") 9.52 (3/8")
B 6.35 (1/4") 9.52 (3/8")
A1 6.35 (1/4") 9.52 (3/8")
(note 1)
(note 1)
(note 1)
Model Liquid Gas
38YY(S) Indoor (Liquid) (Suction)
unit mm (inches) mm (inches)
2M18G
2M21G
2M24G
2M36G
2M48G
A 6.35 (1/4") 9.52 (3/8") B 6.35 (1/4") 9.52 (3/8")
A 6.35 (1/4") 9.52 (3/8") B 6.35 (1/4") 12.70 (1/2")
A 6.35 (1/4") 12.70 (1/2") B 6.35 (1/4") 12.70 (1/2")
A 6.35 (1/4") 12.70 (1/2") B 6.35 (1/4") 12.70 (1/2")
A 6.35 (1/4") 12.70 (1/2") B 6.35 (1/4") 12.70 (1/2")
Pipe diameter
B 6.35 (1/4") 12.70 (1/2")
A1 6.35 (1/4") 9.52 (3/8")
4M24G
A2 6.35 (1/4") 12.70 (1/2") B1 6.35 (1/4") 9.52 (3/8") B2 6.35 (1/4") 12.70 (1/2")
2M36G
2M48G
Notes
1) When the indoor unit is as large as 009, use Ø 9,52 mm (3/8") pipes supplied with the flare tap adapter. Important: do not connect the indoor unit size 012 to circuit B.
2) When the indoor unit is provided with a 15.87 mm (5/8") refrigerant connection, use Ø 12.70 mm pipes supplied with flare tap adapter.
A 6.35 (1/4") 12.70 (1/2") B 6.35 (1/4") 12.70 (1/2")
A 6.35 (1/4") 12.70 (1/2") B 6.35 (1/4") 12.70 (1/2")
(note 1)
(note 1)
(note 2) (note 2)
(note 2) (note 2)
3) All fittings are flare type.
4) Use only refrigeration grade pipes, (Cu DHP type according to ISO 1337), seamless, degreased, deoxidized and suitable for operating pressures of at least 4200 kPa. Under no circumstances must sanitary type annealed copper pipe be used.
B2
L4
H
A2
L1
1
A
/
A
A2
B / B1
L3
L2
H
H
H
H
L3
L4
H
B2
H
L2
H
H
L1
1
/ A
A
A2
B / B1
Outdoor unitIndoor unit circuit AIndoor unit circuit AIndoor unit circuit BIndoor unit circuit B
GB - 4
38GL_MG / 38YY(S)_MG
Connections and operating limits
ENGLISH
Table II: Connections
Model 38GL 2M12G 2M18G 2M24G 3M21G 3M30G 4M24G 2M36G 2M48G
(1)
Max. height difference Max.
pipe L1 m 15 15 –––30 40
length L2 m ––––––30 40
H m5 5 5 5 5
L3 m 15 15 15 30 ––– L1 + L2 m15 ––15 15 30 60 80 L3 + L4 m –––––30 ––
Min.
pipe L1 m 1.5 1.5 –––3.0 3.0
length L2 m – ––– –– ––
L3 m 1.5 1.5 1.5 1.5 3.0 3.0 L1 + L2 m 1.5 ––1.5 1.5 1.5 –– L3 + L4 m –––––1.5 ––
Difference max L1 - L2 m5 –– 555––
L3 - L4 m –––––5 ––
Model YY(S) 2M36G 2M48G 2M18G 2M21G 2M24G
Max. height difference Max.
pipe length L1 m30 40 15 15 15
H m10 15 5 5 5
L2 m30 40 15 15 15
L1 + L2 m60 80 30 30 30
Min.
pipe length L1 m 3,0 3,0 3,0 3,0 3,0
L2 m 3,0 3,0 3,0 3,0 3,0
Note (1): Circuit A1 and A2
(2): Circuit B
/ 10
(2)
51015
T able III: Operating limits
Cooling (2)
Maximum conditions
Minimum conditions
Heating
Notes:
(2)
Maximum conditions Minimum conditions
(1)
Data referred to the outdoor unit only.
(2)
According to prEN 14511-5.
(3)
Thanks to the high pressure regulation kit, the unit can also be used with outdoor temperatures up to +10°C (see table VI
"Accessories" for kit availability).
(4)
Thanks to the high pressure regulation kit, the unit can also be used with outdoor temperatures up to -10°C ( see table VI
"Accessories" for kit availability). d.b. - dry bulb ; w.b. - wet bulb
(1)
Outdoor temperature °C
d.b. w.b. d.b. w.b.
Indoor temperature °C
Applicable
43 32 23 All multisplit units
(3)
21
21 15 38GL2M18G; 38GL2M24G; 38GL3M21G
15 21 15 38GL2M36G
38YY2M18G; 38YY2M36G;38YY2M48G;
38GL2M12G
38GL3M30G; 38GL4M24G
(4)
; 38GL2M48G
38YY2M21G;38YY2M24G.
-10 21 15 38YYS2M36G;38YYS2M48G. 24 18 27 All heat pump
-15 -17 20 multisplit units
WARNING:
During heat pump operation unit will undergo several defrost cycles to eliminate ice that might possibly collect on the outdoor unit in very low ambient temperatures. In these cycles, fan speed will automatically reduce and cannot be varied until defrost cycle is completed.
(4)
;
GB - 5
38GL_MG / 38YY(S)_MG
General information
Unit installation
Read this instruction manual thoroughly before starting the installation.
R-410A systems operate at higher pressures than standard R-22 systems. Do not use R-22 service equipment or components on R-410A equipment.
This unit complies with low-voltage (EEC/73/23) and electro­magnetic compatibility (EEC/89/336) directives.
Check that the impedance of the mains power supply is in conformance with the unit power input indicated in the electric data table V (EN 61000-3-11).
The installation must be carried out by a qualified installer.
Follow all current national safety code requirements. In particular ensure that a properly sized and connected ground wire is in place.
Check that voltage and frequency of the mains power supply are those required; the available power must be adequate to operate any other possible appliances connected to the same line. Also ensure that national safety code requirements have been followed for the mains supply circuit.
The mains supply must be connected to the outdoor unit.
Connect indoor and outdoor units with field-supplied copper
pipes by means of flare connections. Use insulated seamless refrigeration grade pipe only, (Cu DHP type according to ISO1337), degreased and deoxidized, suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa. Under no circumstances must sanitary type copper pipe be used.
After installation thoroughly test the system operation and explain all system functions to the owner.
Leave this manual with the owner for consultation during future periodic maintenance.
Use this unit only for factory approved applications: the unit is suitable for outdoor installation.
This installation manual describes the installation procedures of the outdoor unit of a residential split system consisting of two units manufactured by Carrier. Consult factory or a qualified system engineer prior to connecting this unit to any other manufacturer's indoor unit. Coupling units which have different control systems, may cause irreversible damage and void the warranty protection. The manufacturer declines any liability for system malfunction resulting from unapproved coupling.
IMPORTANT: During the unit installation make first refrigerant connections and then electrical connections. If unit is uninstalled first disconnect electrical cables, then refrigerant connections. WARNING: Disconnect the mains power supply switch before servicing the system or handling any internal parts of the unit. All mains supply circuits must be disconnected.
Carefully recover refrigerant within this unit before final disposal or when servicing. Never vent refrigerant to atmosphere. Use approved recovery equipment for R-410A refrigerant. Do not use R-22 equipment.
Choosing the installation site
Positions to avoid:
Exposed to direct sun.
Too close to sources of heat radiation, vapour or flammable gas.
Particularly dusty areas.
Recommendations:
Choose a position protected from opposing winds.
Choose a position sheltered from direct sun.
Choose an area where air outlet and unit noise will not bother
your neighbours.
Choose a position that allows for the clearances required.
Floor structure should be adequately strong to support unit weight
and minimize vibration transmission.
Consider a position which will not obstruct passageways or doors.
A
mm
mm
B
Model AB
2M12G 390 250
All the other
models
508 330
Fix the unit with locally purchased bolts buried in the block to prevent overturning due to strong gusts of wind.
For heat pump models, unit must be adequately raised above floor surface.
No. 4 Ø 8 mm pins.Protrusion height from the
support surface max. 20 mm.
100 mm min20 mm gradientGravel-filled trench
The manufacturer declines any liability for damage resulting from modifications or errors in the electrical or refrigerant connections.
Failure to observe the installation instructions or use of the unit under conditions other than those indicated in Table III “Operating limits, will immediately void the unit warranty.
Failure to observe electric safety codes may cause a fire hazard in case of short circuits.
Inspect equipment for damage due to improper transportation or handling: file an immediate claim with the shipping company. Do not install or use damaged units.
In case of any malfunctioning turn the unit off, disconnect the mains power supply and contact a qualified service engineer.
This equipment contains R-410A refrigerant, a substance that is not depleting the ozone layer.
All of the manufacturing and packaging materials used for your new appliance are compatible with the environment and can be recycled.
Dispose of the packaging material in accordance with local requirements.
This equipment contains refrigerant that must be disposed of in a proper manner. When disposing of the unit after its operational life, remove it carefully. The unit must then be delivered to an appropriate disposal center or to the original equipment dealer.
GB - 6
Drain fitting
Vinyl pipe
To empty the condensate water to a drain while operating in heating mode, insert the drain fitting into the hole underneath on the centre of the base and use a vinyl pipe with a 16 mm inside diameter. It must not be used at temperatures below 0°C (not available for low temperature versions).
Snow
If the unit is installed in areas where heavy snowfalls may occur, it is necessary to raise its level at least 200 mm above the usual snow level or alternatively to use the outdoor unit bracket kit.