*Two plugged holes to accommodate charging lines Replace plugs when finished
tl nsert rubber grommet (shipped in low voltage splice box) in hole to protect wires if conduit is not used
J1-3/8 in diam on 38GF106 single-phase units
**Concrete pad should weigh 1 -1 /2 to 2 times weight of unit
Fig. 1 — Dimensions, Connections and Mounting Pad (Unit Access Panel Removed)
Table 1 — Installation Data
CO ND E NS IN G U N IT
OP ER A TI NG
WT (l b)
DIM E NS IO N S
(ft-i n. )
RE FR IG E RA N T
CO NN , (in .)
_______
j 38GF units only, field-supplied tubing sizes for oil return and refrigerant charge
*38GF006 supplied with 3/4 to 1 -1 /8 in suction valve connection adapter (field-installed)
Move condensing unit to final location. Remove top
grille. Reach between fan blades and remove 1/4-in.
hex head screws holding unit to skid. On the 145, 105,
106 units, remove the two compressor shipping brackets
attached to top of compressor and sides of unit.
PRELIMINARY SURVEY
Consult local building codes for special installa
tion requirements.
When installing unit, allow sufficient space for
air-flow clearance, wiring, refrigerant piping and
servicing unit. NEC minimum requirement is 3 ft
(see Fig. 1). Position unit so water from roof or
eaves will not pour directly on top of unit.
Install unit on a solid, level mounting pad.
Position tie-down bolts in pad. Any two holes in
unit base may be used to fasten unit to pad.
38GC,GF Condensing Units are designed for appli
cation with any Carrier or other evaporator of
proper capacity. Install each unit in accordance
with Refrigerant Piping Data, (Table 4) and the
following special requirements.
Where refrigerant line lengths exceed 25 ft, it is
recommended that a liquid line filter-drier, crank
case heater and accessory start capacitor with relay
be added to condensing unit.
Liquid line filter-drier and crankcase heater are
factory installed on 38GF units. Start capacitor
with relay is available as an accessory for
38GC101, 102, 103 and 38GF102; factory in
stalled on remaining sizes.
When evaporator is below condensing unit,
reduce liquid line size one diameter (min 114-in.
OD).
PIPING CONNECTIONS
38GC,GF Condensing Units can be connected to
evaporator sections using Carrier accessory pre
charged tubing or field-supplied tubing of refrig
erant grade. (Accessory tubing not available for
38GF106.) See Table 3 for accessory tubing sizes
and Table 4 for recommended field-supplied tubing
sizes. When over 25 ft of interconnecting tubing is
used, follow special requirements described above
in Preliminary Survey. Do not use damaged or
contaminated tubing. Do not cut 3/8-in. OD liquid
line to a length shorter than 10 ft. Bend or coil to
fit. When precharged tubing or evaporator section
has been open for more than 15 seconds per
connection, evacuate or purge evaporator coil and
tubing system (use field-supplied refrigerant, not
unit refrigerant). If necessary, refer to Carrier
System Design Manual, Part 3, for standard piping
techniques.
38GC,GF Connection Procedure — When making
piping connections, be sure to provide clearance at
unit for electrical connections.
Connect refrigerant liquid and suction lines to
condensing unit (Fig. 1). Unit Compatible Fitting
permits two methods of refrigerant line connec
tion. mechanical (quick-connect) or sweat
connection.
38GF106 UNITS — Remove suction line adapter
taped to compressor shipping bracket and connect
to suction line Compatible Fitting. Sweat connect
refrigerant suction line to adapter. Connect liquid
refrigerant line to unit.
2
(Mate one set ofMECHANICAL CONNECTION
connections at a time).
1. Loosen nut on Compatible Fitting one turn. Do
not remove. Loosen tube clamp.
2. Remove rubber plug and be sure 0-ring is in the
groove inside the Compatible Fitting.
3. Cut tubing to correct length.
4. Use gage on tag attached to service valve to
mark tube end for correct insertion depth.
Insert tube into Compatible Fitting until it
bottoms. (Tube should be inserted at least as
far as mark on tubing.)
5. Tighten nut until it bottoms on back coupling
flange. Tighten tube clamp.
SWEAT CONNECTION (use refrigerant grade
tubing).
1. Remove locking nut and rubber 0-iing from
inside of fitting. Loosen tube clamp entering
condensing unit base.
2.
Cut tubing to correct length.
3.
Insert tube into Compatible Fitting. Wrap top
and bottom of service valves in wet cloth to
prevent damage by heat. Solder with low
temperature (450 F) silver alloy solder. Tighten
tube clamp.
4.
Evacuate or purge system with field-supplied
refrigerant.
ELECTRICAL DATA AND WIRING
Wiring — Field wiring must comply with local and
national codes. Install a branch circuit fused
disconnect of adequate size to handle starting
current. When making electrical connections, pro
vide clearance at unit for refrigerant piping
connections.
LINE POWER is brought thru unit base pan flange
and thru hole provided in control box (Fig. 1). On
38GC101, 38GF106 (230-v, 1-ph) and 38GF103,
104 (208- and 230-v, 3-ph) units, line power
connections are made to pigtails supplied with
unit. Use approved splice connector. Do not use
aluminum field wire for splice connections unless
copper to aluminum adapters is used, and correct
wiring techniques are followed.
On all other models connect line power to
contactor screw power terminals as indicated on
unit label diagram, i.e., connect power leads to
contactor terminals 21 and 23 on single-phase
units, or 21, 22, and 23 on 3-phase units.
On all 3-phase units, do not connect a grounded
high voltage leg to control circuit pigtail or
terminal; connect leg to compressor pigtail or
terminal. See label diagram.
CONTROL POWER is brought thru unit base pan
(Fig. 1), and thru 7/8-in. hole into low voltage
section of control box. All connections are made
to pigtails supplied with unit (Fig. 2). Where
supply voltage exceeds 150 volts to ground, or
local codes require it, ground 24-volt control
circuit at field splice C.
Table 4 — Refrigerant Piping Data
Crankcase heater (standard on GF), liquid line filter-drier (standard on GF)
and start capacitor with relay (accessory on GC101, 102, 103 and GF102)
required Reduce liquid line size one diameter (mini /4-in OD) when evaporator
is below condensing unit
•fWire sizes and lengths based on copper wire
— Electrical data shown applicable to all models
NOTE:
Motors and controls will operate satisfactorily 10% above and 10%
below unit voltage. On 3-phase units, phases must be balanced
within 2%. Control circuit voltage is 24 volts on all units.
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.