Carrier 38EYA User Manual

0 (0)
Visit www.carrier.com
Installation and Start-Up Instructions
NOTE: Read the entire instruction manual before starting the
installation. This symbol indicates a change since the last issue.
SAFETY CONSIDERATIONS
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thor­oughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety-alert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU­TION. These words are used with the safety-alert symbol. DAN­GER identifies the most serious hazards which willresultinsevere personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage.
Before installing, modifying, or servicing system, main elec­trical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label. Electrical shock can cause personal injury or death.
Puron® (R-410A) systems operate at higher pressures than standard R-22 systems. Be certain that service equipment is rated for Puron®. Some R-22 service equipment may not be acceptable. Check with your distributor.
INSTALLATION RECOMMENDATIONS
NOTE: In some cases noise in the living area has been traced to
gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where unit operation sound may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate to capacity of unit.
3. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
38EYA
12 SEER Split-System
Heat Pump with Puron®
.
Fig. 1—Model 38EYA
4. Leave some slack between structure and unit to absorb vibration.
5. When passing refrigerant tubes through the wall, seal opening with RTV or other pliable silicon-based caulk. (See Fig. 2.)
6. Avoid direct tubing contact with water pipes, duct work, floor joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing. (See Fig. 2.)
8. Ensure that tubing insulation is pliable and completely sur­rounds vapor tube.
9. When necessary, use hanger straps which are 1 in. wide and conform to shape of tubing insulation. (See Fig. 2.)
10. Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation.
When outdoor unit is connected to factory-approved indoor unit, outdoor unit contains system refrigerant charge for operation with indoor unit of same size when connected by 15 ft of field-supplied or factory accessory tubing. Add (or subtract) 0.6 oz/ft of 3/8 liquid line for lengths greater (or less) than 15 ft. For proper unit operation, check refrigerant charge using charging information located on control box cover and/or in theCheckChargesection of this instruction.
IMPORTANT: Maximum liquid-line size is 3/8-in. O.D. for all residential applications including long line.
IMPORTANT: Always install the factory-supplied Puron® heat pump (bi-flow) liquid-line filter drier. If replacing the filter drier, refer to Product Data Digest for appropriate part number. Obtain replacement filter driers from your distributor or branch.
A99327
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 5a 5a
PC 101 Catalog No. 533-80006 Printed in U.S.A. Form 38EYA-3SI Pg 1 4-01 Replaces: 38EYA-2SI
Avoid contact between tubing and structureNOTE:
OUTDOOR WALL INDOOR WALL
CAULK
INSULATION
THROUGH THE WALL
HANGER STRAP
(AROUND VAPOR
TUBE ONLY)
1 MIN.
SUSPENSION
LIQUID TUBE
VAPOR TUBE
JOIST
INSULATION
VAPOR TUBE
LIQUID TUBE
A94028
Fig. 2Connecting Tubing Installation
INSTALLATION
IMPORTANT: Specifications for this unit in residential new
construction market require using the outdoor unit, indoor unit, refrigerant tubing sets, metering device, and filter drier listed in presale literature. There can be no deviation. Consult the Appli­cation Guideline and Service Manual for Residential Split-System Air Conditioners and Heat Pumps using Puron® Refrigerant to obtain required unit changes for specific applications and for R-22 retrofit.
Step 1Check Equipment and Job Site
UNPACK UNIT Move to final location. Remove carton taking care not to damage
unit. INSPECT EQUIPMENT File claim with shipping company prior to installation if shipment
is damaged or incomplete. Locate unit rating plate on unit corner panel. It contains information needed to properly install unit. Check rating plate to be sure unit matches job specifications.
Step 2Install On a Solid, Level Mounting Pad
If conditions or local codes require the unit be attached to pad, tie down bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit mounting pattern in Fig. 3 to determine base pan size and knockout hole location.
On rooftop applications, mount on level platform or frame. Place unit above a load-bearing wall and isolate unit and tubing set from structure. Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications.
C
3
⁄8″D. (9.53) TIEDOWN
A
B
KNOCKOUTS (2) PLACES
A94199
DIMENSIONS (IN.)
UNIT SIZE
018, 024, 030 22-1/2 X 22-1/2 3-11/16 18-1/8 14-3/8
036–060 30 X 30 6-1/2 23-1/2 20
MINIMUM
MOUNTING PAD
DIMENSIONS
TIEDOWN KNOCKOUT
LOCATIONS
ABC
Fig. 3Mounting Unit to Pad
Do not allow POE lubricant to come into contact with roofing material. POE may determine certain types of synthetic roofing.
Roof mounted units exposed to winds above 5 mph may require wind baffles. Consult the Application Guideline and Service Manual for Residential Split-System Air Conditioners and Heat Pumps using Puron® Refrigerant for wind baffle construction.
NOTE: Unit must be level to within ± 2° (± 3/8 in./ft) per compressor manufacturer specifications.
Step 3Clearance Requirements
When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 30-in. clearance to service end of unit and 48 in. above unit. For proper airflow, a 6-in. clearance on 1 side of unit and 12 in. on all remaining sides must be maintained. Maintain a distance of 24 in. between units. Position so water, snow, or ice from roof or eaves cannot fall directly on unit.
On rooftop applications, locate unit at least 6 in. above roof surface.
Step 4Operating Ambients
The minimum outdoor operating ambient in cooling mode without additional accessories is 55°F, and the maximum outdoor operat­ing ambient in cooling mode is 125°F. The maximum outdoor operating ambient in heating mode is 66°F.
2
Step 5Elevate Unit
Accumulation of water and ice in base pan may cause equipment damage.
Elevate unit per local climate and code requirements to provide clearance above estimated snowfall level and ensure adequate drainage of unit.
and feeder tube going into outdoor coil. At the end of 1 of the feeder tubes, there is a 3/8-in. OD stub tube approximately 3 in. long. (See Fig. 6.) The defrost thermostat should be located on stub tube. Note that there is only 1 stub tube used with liquid header, and on most units it is the bottom circuit.
Step 8In Long-Line Applications, Install Liquid-Line Solenoid Valve (LSV)
For refrigerant piping arrangements with equivalent lengths greater than 50 ft or when elevation difference between indoor and outdoor unit is greater than ± 20 ft, follow all requirements of the Long-Line Guideline section in the Application Guideline and
COIL
THERMOSTATIC EXPANSION VALVE
SENSING BULB
EQUALIZER TUBE
A88382
Fig. 4Typical TXV Installation
Step 6Check Indoor Expansion Device
For proper unit operation and reliability, units must be installed with hard shutoff TXV specifically designed to operate with Puron®. Do not use R-22 TXV. Do not install with evaporator coils having capillary tube metering devices or pistons.
For TXV kit part number and charging instructions, refer to TXV label in outdoor unit.
FURNACE COILS If TXV installation is required, remove existing AccuRater® from
indoor coil. Refer to Fig. 4 and 5 and install TXV kit (specifically designed for Puron®) as follows:
1. Install suction tube adapter.
2. Install liquid flare-to-sweat adapter.
3. Connect external equalizer tube to fitting on suction tube adapter.
4. Position sensing bulb on horizontal portion of suction tube adapter. Secure using supplied hardware.
5. Insulate bulb after installation. (See Fig. 5.)
6. Leak check all connections.
FAN COILS If indoor unit (fan coil) comes factory equipped with a bi-flow
hard shutoff TXV specifically designed for Puron®,noTXV change is required.
If fan coil is not designed for Puron®, a Puron® TXV installation is required. Refer to TXV kit Installation Instructions for details on TXV installation.
Step 7Check Defrost Thermostat
Check defrost thermostat to ensure it is properly located and securely attached. There is a liquid header with a brass distributor
SENSING BULB
STRAP
8 O'CLOCK
4 O'CLOCK
A00399
Fig. 5Positioning of Sensing Bulb
FEEDER TUBE
STUB TUBE
DEFROST THERMOSTAT
A97517
Fig. 6Defrost Thermostat Location
Service Manual for Residential Split-System Air Conditioners and Heat Pumps Using Puron® Refrigerant.
If required by Long-Line Application Guideline, install LSV kit part No. KHALS0401LLS specifically designed for Puron® Heat Pump. LSV should be installed between filter drier and indoor coil, as close as possible to filter drier. Follow the Installation Instruc­tions included with accessory kit.
IMPORTANT: Flow arrow must point toward outdoor unit. Step 9Making Piping Connections
Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury or death. Use all service ports and open all flow-control devices, including solenoid valves.
3
Table 1Refrigerant Connections and Recommended Liquid Line and Vapor Tube Diameters (In.)
UNIT SIZE
018, 024 3/8 5/8 3/8 5/8 3/4 ACR 3/4
030 3/8 3/4 3/8 3/4 7/8 1-1/8 036 3/8 3/4 3/8 3/4 7/8 1-1/8
042, 048 3/8 7/8 3/8 7/8 7/8 3/4 and 1-1/8
060 3/8 1-1/8 3/8 1-1/8 7/8 3/4
NOTES:
1. Tube diameters are for lengths up to 50 ft. For tubing lengths greater than 50 ft, consult the Application Guideline and Service Manual Residential Split-System Air Conditioners and Heat Pumps Using Puron® Refrigerant.
2. Refrigerant tubes and indoor coils must be evacuated to 500 microns to minimize contamination and moisture in the system.
CONNECTION DIAMETER TUBE DIAMETER
Liquid Vapor Liquid Vapor Vapor Vapor
TUBE DIAMETER
(ALTERNATE)
SWEAT/FLARE ADAPTER
Do not leave system open to atmosphere any longer than minimum required for installation. POE oil in compressor is extremely susceptible to moisture absorption. Always keep
TEFLON SEAL
ends of tubing sealed during installation.
RST TUBE
DIAMETERS
NOT PERMITTED
If ANY refrigerant tubing is buried, provide a 6 in. vertical rise at service valve. Refrigerant tubing lengths up to 36 in. may be buried.
To prevent damage to unit or service valves observe the following:
Use a brazing shield
Wrap service valves with wet cloth or use a heat sink
material.
Outdoor units may be connected to indoor section using accessory tubing package or field-supplied refrigerant grade tubing of correct size and condition. For tubing requirements beyond 50 ft, substan­tial capacity and performance losses can occur. Following the recommendations in the Application Guideline and Service Manual for Residential Split-System Air Conditioners and Heat Pumps using Puron® Refrigerant to minimize losses. Refer to Table 1 for field tubing diameters. Refer to Table 2 for accessory requirements.
Refrigerant tubes and indoor coil must be evacuated to 500 microns to minimize contamination and moisture in the system.
OUTDOOR UNIT CONNECTED TO FACTORY-APPROVED INDOOR UNIT
These outdoor units are carefully evaluated and listed with specific indoor coils for proper system performance.
IMPORTANT: Do not apply indoor coils which are not factory approved to these units.
INSTALL ADAPTER TUBE
1. Remove plastic retainer holding outdoor piston in liquid service valve.
2. Check outdoor piston size with matching number listed on unit rating plate.
3. Locate plastic bag taped to unit containing adapter tube.
4. Remove teflon washer from bag and install on open end of liquid service valve. (See Fig. 7.)
5. Remove adapter tube from bag and connect threaded nut to liquid service valve. Tighten nut finger tight and then with
PISTON
PISTON BODY
LIQUID SERVICE VALVE
A99441
Fig. 7Liquid Service Valve with Sweat Adapter
Tube
LIQUID-LINE FILTER-DRIER
LIQUID
SERVICE
VALVE
A00431
Fig. 8Filter Drier with Sweat Adapter Tube and
Liquid Tube
4
Table 2Accessory Usage
ACCESSORY
Crankcase Heater Yes Yes
Evaporator Freeze Thermostat Yes No
Compressor Start AssistCapacitor and Relay Yes Yes
Puron® Low-Ambient Pressure Switch Yes No
Wind Baffle See Low-Ambient Instructions No
Support Feet Recommended No
Hard Shutoff TXV Yes Yes
Liquid-Line Solenoid Valve for Heating No
* For tubing line sets between 50 and 175 ft, or when vertical difference is greater than 20 ft, refer to Application Guideline and Service Manual Residential Split-System Air Conditioners and Heat Pumps Using Puron®. Required for all applications.
REQUIRED FOR LOW-AMBIENT
APPLICATIONS
(BELOW 55°F)
REQUIRED FOR LONG-LINE
APPLICATIONS*
(OVER 50 FT)
See Long-Line
Application Guideline
wrench an additional 1/12 turn (15 ft-lb). DO NOT OVER­TIGHTEN.
REFRIGERANT TUBING AND FILTER DRIER
Installation of filter drier in liquid line is required.
Connect vapor tubing to fittings on outdoor unit vapor service valves. Connect liquid tube to filter drier. (See Table 1 and Fig. 8.) Use refrigerant grade tubing. Connect other end of filter drier to adapter tube on liquid service valve.
SWEAT CONNECTION
To avoid valve damage while brazing, service valves must be wrapped in a heat-sink material such as a wet cloth.
Wrap service valves and filter drier with a wet cloth or heat­sinking material. Braze connections using either silver bearing or non-silver bearing brazing material. Do not use soft solder (materials which melt below 800°F.) Consult local code require­ments.
LEAK CHECKING Leak test all joints in indoor, outdoor, and refrigerant tubing. EVACUATE REFRIGERANT TUBING AND INDOOR COIL
5000 4500 4000 3500 3000 2500 2000
MICRONS
1500 1000
500
01234567
MINUTES
Fig. 9Deep Vacuum Graph
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
LEAK IN SYSTEM
VACUUM TIGHT TOO WET
TIGHT DRY SYSTEM
A95424
A95424
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used if the procedure outlined below is followed.
IMPORTANT: Never open system under vacuum to atmosphere without first breaking it open with nitrogen.
Deep Vacuum Method The deep vacuum method requires a vacuum pump capable of
pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water. (See Fig. 9.)
Triple Evacuation Method The triple evacuation method should only be used when vacuum
pump is only capable of pumping down to 28 in. of mercury vacuum and system does not contain any liquid water. Refer to Fig. 10 and proceed as follows:
WAIT
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
CHECK FOR TIGHT, DRY SYSTEM
(IF IT HOLDS DEEP VACUUM)
CHARGE SYSTEM
A95425
Fig. 10Triple Evacuation Method
5
Loading...
+ 11 hidden pages