Carrier 38BNB user guide manual

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111 Catalog No. 533-80098 Printed in U.S.A. Form OM38/40-4 Pg 1 4-03 Replaces: New
Book 1 4 Ta b 3 e 2 f
OWNER’S MANUAL
38BNB,BNE018-036 40BNB,BNE018-036
Cooling Only and Heat Pump Duct-Free High Wall Systems
Page
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2,3
OPERATING MODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
REMOTE CONTROL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
REMOTE CONTROL OPERATION . . . . . . . . . . . . . . . . 3
UNIT OPERA TION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
CLEANING AND MAINTENANCE . . . . . . . . . . . . . . .8,9
AIR FIL TERS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Page
INDOOR UNIT FRONT P ANEL . . . . . . . . . . . . . . . . . . . 8
INDOOR UNIT COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
OUTDOOR UNIT COIL . . . . . . . . . . . . . . . . . . . . . . . . . . 8
CONDENSATE DRAINS . . . . . . . . . . . . . . . . . . . . . . . . . 8
SYSTEM OPERATION CHECK LIST . . . . . . . . . . . . . . 9
DIP SWITCH SETTINGS . . . . . . . . . . . . . . . . . . . . . . . . . 9
ENERGY SAVING RECOMMENDATIONS. . . . . . . . . 9
TROUBLESHOOTING GUIDE . . . . . . . . . . . . . . . . 10-12
I
I
I
I
MODE AN SWEEP
AA
START
STO
P
1 2 3 SLEEP DA LY
2
INTRODUCTION
Thank you for choosing a Streamline® Duct Free System. The same pride in craftsmanship and engineering knowledge that goes into equipment cooling the Astrodome in Texas, the Sistine Chapel in Rome, the U.S. Capitol Hall of Congress, and thousands of other installations worldwide has gone into the construction of this unit.
Duct Free Systems provide quiet, maximum comfort. In ad­dition to cooling and/or heating, the Duct Free System will fil­ter and dehumidify the air in the room to provide maximum comfort.
GENERAL
The Duct Free System can be set up and operated from the remote control (provided). See Fig. 1. If the remote is mis­placed, the system can be operated from the “Auto” setting on the unit.
Operating Modes — The duct free system has 5 operat-
ing modes:
• Cooling
•Fan Only
• Heating (if applicable)
• Dehumidification
• Auto COOL ING — In Cooling mode, the system cools, dries and
filters room air.
FAN ONLY — In Fan Only mode, the system filters and cir­culates room air without changing room air temperature.
HEATING — In Heating mode, the system heats and filters room air.
DEHUMIDIFICATION — In Dehumidification mode, the system dries, filters and slightly cools room air temperature. This mode does not take the place of a dehumidifier .
AUTO — In Auto mode, the system will automatically cool or heat room air according to a selected temperature (set point).
If temperature of room air is lower than set point, the system will operate in Heating mode. If temperature of room air is higher than set point, the system will operate in Cooling mode.
Remote Control — The remote control transmits com-
mands to set up and operate the system. The controller has a window display panel that shows the current system status. The controller can be secured to a surface when used with the mounting rack provided. See Fig. 1.
IMPORTANT: Duct Free Systems should be installed by authorized personnel only, using approved tubing and accessories. If technical assistance, service or repair is needed, contact the installer or call 1-800-227-7437.
Handle the controller with care and avoid getting the con­troller wet. Damage to the device may result.
Do not leave remote control in a drawer or near a warm/hot appliance as the system will try to cool the environment around the controller .
IMPORTANT: The remote control and unit continually
exchange information regarding room air temperature.
When operating the remote control from the mounting
rack, be sure there is a direct line of sight between the
controller and the unit. The controller can operate the
unit from a distance of up to 23 ft as long as there are not
any obstructions.
I
I
I
I
I
I
MODE FAN SWEEP
AA
START
STOP 1 2 3 SLEEP
DAI Y
REMOTE CONTROL
MOUNTING RACK
MODE
I
I
I
I
I
I
I
I
A
COOLING FAN HEATING FUNCTION DRY AUTO
FAN
A
LOW
MEDIUM
HIGH
AUTO
SWEEP
SWEEP ON/OFF
UP
DOWN
MODE
BUTTON
UP/DOWN
BUTTON
ON/OFF BUTTON
Fig. 1 — Duct Free System
REMOTE CONTROL BUTTONS —
PROGRAMMING OPTIONS
3
The remote control can perform the following functions:
• Turn the system ON and OFF
• Select operating mode
• Adjust room air temperature and fan speed
• Set time periods for automatic system operation BATTERY INSTALLATION — Two AAA 1.5V alkaline
batteries (included) are required for operation of the remote control. See Fig. 2 for battery location.
T o install batteries:
1. Remove battery compartment cover by sliding off of remote.
2. Insert batteries being sure to follow polarity markings in­side battery compartment.
3. Replace battery compartment cover.
NOTE: Replace batteries whenever “Low battery” indicator appears on remote control display panel.
DISPLAY SCREEN — There are five operating mode indica­tors that appear on the remote control display screen. See Fig. 3.
OPERATION
Remote Control Operation —
The remote control has 3 buttons (see Fig. 4) used for operating and controlling the system:
• MODE button — changes operatin g mode
• UP/DOWN button — selects desired operating mo de
• ON/OFF button — turn s the system on or off and trans-
mits programing selections to unit.
NOTE: When transmitting a command from the controller to the unit, be sure to point the controller toward the right side of the unit. See Fig. 4. The unit will confirm receipt of a com­mand by sounding 2 audible beeps.
FAN S PEED — To select the Fan mode and change the Fan Speed, follow the steps below:
1. Press MODE button to select the Fan mode.
2. Pres s UP/ DOW N b ut ton to select desired fan sp eed o r to Auto.
3. Press ON/OFF button to send changes to unit from re­mote control.
NOTE: If unit is operating in DEHUMIDIFICATION mode the fan will only operate in Low speed and cannot be changed.
TEMPERATURE SETTINGS — The temperature settings can be easily changed by pointing the controller toward the unit and pressing the UP/DOWN button until desired temperature appears on screen. The symbol appears each time the ON/ OFF button is pressed.
Another way of changing the temperature is as follows:
1. Select the temperature display by pressing the MODE button. The degree symbol will flash next to the digits on the screen.
2. Press UP/DOWN button to select the desired tempera­ture. The available temperature range is from 54 F to 90 F .
3. Press ON/OFF button to send changes to unit from re­mote control.
AIRFLOW DIRECTION — Perform the following steps to change the direction of airflow from the unit:
1. Press MODE button to select the Sweep function.
2. Press the top of the UP/DOWN button to move the air deflector on the unit in an up and down motion. The air­flow symbol displays motion.
3. Press the bottom of the UP/DOWN button. Th e a i r f l o w deflector stops at a given angle. The airflow symbol dis­play remains in a fixed position.
4. Press ON/OFF button to send changes to unit from re­mote control.
NOTE: If placing the air deflector in a fixed position is chosen, the deflector stops at the angle in which it was located when the ON/OFF button was pressed.
SETTING CLOCK
1. Slide down front cover of controller below ON/OFF but­ton. See Fig. 4.
2. Press CLOCK button using the tip of a pen or paper clip. See Fig. 5.
3. Press UP/DOWN button to set minutes.
4. Press MODE button. The hour digits will flash.
5. Press to UP/DOWN bu tton to set the hour.
6. To confirm current clock settings, press CLOCK button once again using the tip of a pen or paper clip. The remote control will automatically go back to previous display and the clock is displayed.
IMPORTANT: If no changes are made within 10 sec­onds, the remote control will return to its previous setting.
BACK OF REMOTE CONTROL
2 AAA 1.5V BATTERIES
BATTERY COMPARTMENT COVER
A
COOLING
HEATING
FAN ONLY
DEHUMIDIFICATION
AUTO
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Fig. 2 — Location of Batteries on Remote Control
Fig. 3 — Operating Mode Indicators on
Remote Control
4
PROGRAMMING TIME PERIODS — The duct free sys­tem can be programmed to operate at desired levels. Be sure to set the clock before programming the system.
• Increments of time are in 10-m inute intervals.
• The Timer Start/Stop indicator light on the unit is on when a time period is set. See Fig. 4.
• The remote control displays the Start/Stop time of the time period that is closest to the current time. If the unit is ON, “STOP” and the time period is displayed. If the unit is OFF, “START” and the time period is displayed.
Setting Start/Stop Time
— Timer feature is used to set unit operation Start/Stop times. Three different time periods up to 10 hours apart and within 24 hours can be programmed using this feature.
1. Slide down front cover of controller below ON/OFF but­ton. See Fig. 4.
IMPORTANT: Be sure to point the remote control toward the unit while pressing the TIMER or SET buttons.
TEMPERATURE SENSOR
TRANSMISSION INDICATOR
LOW BATTERY INDICATOR
UP/DOWN BUTTON
DESIRED TEMPERATURE
SENSOR ACTIVE INDICATOR
SWEEP INDICATOR
ON/OFF BUTTON
CLOCK BUTTON*
ROOM TEMPERATURE BUTTON*
DELAY BUTTON*
LOCAL SENSING BUTTON*
INFRARED SIGNAL TRANSMITTER WINDOW
CLOCK
TIMER START/STOP ONE-TIME/DAILY INDICATORS
MODE BUTTON
OPERATION MODE INDICATORS ­COOLING, FAN, HEATING, DEHUMIDIFICATION, AUTO
FAN INDICATORS ­LOW, MEDIUM, HIGH, AUTO
TIMER SET BUTTONS*
SLIDE DOWN PANEL
I
I
I
I
I
I
I
I
I
I
MODE
FAN
SWEEP
AA
START
STOP 1 2 3 SLEEP DAILY
TIMER
SET
CLEAR
DELAY
SENSE
ROOM
CLOCK
Fig. 4 — Remote Control
*Buttons located behind slide down panel.
I
I
I
I
I
I
I
I
I
MODE FAN SWEEP
AA
START
STOP 1 2 3 SLEEP DAILY
TIMER
SET
CLEAR
DELAY
SENSE
ROOM
CLOCK
Fig. 5 — Location of Clock Set Button
on Remote Control
5
2. Press the TIMER button. Each time the button is pressed the next Start or Stop set time appears on the display . See Fig. 6 and 7.
3. Press UP/DOWN button to set the time.
4. T o set another time period, press the TIMER button t o go to another time period and repeat steps 2 and 3 above.
5. Press the SET button to set the displayed time when done. See Fig. 4.
NOTE: If changes are not made within 10 seconds, the remote control will return to its previous display. To correct an error, the programmed Timer settings must be cancelled and re­entered. See Canceling Daily Timer section.
Sleep Timer
— The Sleep Timer function allows the desired temperature to be updated while the occupant is sleeping. The temperature in the room air gradually rises until this time peri­od is exited. The unit will then return to the previous tempera­ture set point. T o set the Sleep Timer, follow the steps below:
1. Slide down front cover of controller below ON/OFF but­ton. See Fig. 4.
2. Press the TIMER button until Sleep function is reached.
3. Select the “SLEEP” timer period. See Fig. 8.
4. Press UP/D OWN butt on to set the start time and press TIMER button to set stop time.
5. Press the SET button to set the display time when done. See Fig. 4.
Setting Daily Timer
— Time periods can be programmed to operate the system at set times during a 24-hour period. This timer function can be used for all 3 time periods and sleep peri­od described above.
NOTE: The daily timer operates only when there is a direct line of sight between the controller and the unit.
1. Slide down front cover of controller below ON/OFF but­ton. See Fig. 4.
2. Press the TIMER button to select the time period that will be activated daily .
3. Press and hold the SET button until the word “DAILY” appears on the display . See Fig. 9.
4. Press the SET button again to confirm the daily operation for the selected time period. Be sure to point remote con­trol toward the unit while pressing the SET button.
Canceling Daily Timer
— This function will cancel the se-
lected Daily Timer program.
1. Slide down front cover of controller below ON/OFF but­ton. See Fig. 4.
2. Press the TIMER button to select the time period that will be activated daily.
3. Press the SET button and hold until the word “DAILY” disappears on the display.
4. Press the SET button again to remove the daily operation from the selected time period. Be sure to point remote control toward the unit while pressing the SET button.
Canceling Specific Start/Stop Time Period
— One or more
timers can be cancelled by performing the following steps:
1. Slide down front cover of controller below ON/OFF but­ton. See Fig. 4.
2. Press the TIMER button and select desired Timer to can­cel (1,2,3 or Sleep).
3. Press CLEAR button to cancel the selected Timer period. The Start/Stop times will disappear from the display .
4. Press the SET button to confirm the cancellation. Be sure to point remote control toward the unit while pressing the SET button.
Canceling All Time Period
s — All timers can be cancelled by
performing the following steps:
1. Slide down front cover of controller below ON/OFF but­ton. See Fig. 4.
2. Press the TIMER button.
3. Press and hold the CLEAR button until all Start/Stop times disappear from the display.
4. Check to be sure timer light is off on unit.
5. Press the SET button to confirm the cancellation. Be sure to point the remote control toward the unit while pressing the SET button.
ROOM AIR TEMPERATURE DISPLA Y — The current room air temperature is automatically displayed when the remote controller is powered off. To display the room air temperature when the unit is powered on:
1. Slide down front cover of controller below ON/OFF button. See Fig. 4.
2. Press the ROOM button. The current room air tempera­ture will be displayed for several seconds, then disappear.
See Fig. 10.
STOP 1
STOP 2
START
3
STOP
START
1
START
2
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
MODE FAN SWEEP
A
A
START
STOP 1 2 3 SLEEP
DAILY
TIMER INDICATOR
Fig. 6 — Timer Display Set Up on Remote
Fig. 7 — Set Timer Indicator on
Remote Control Display
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
MODE FAN SWEEP
A
A
START
STOP 1 2 3 SLEEP
DAILY
SLEEP TIMER INDICATOR
Fig. 8 — Sleep Timer Indicator on
Remote Control Display
6
DELAYED START/STOP — This function will delay the Start/Stop function in increments of 1 hour. Delayed Start/Stop can be programmed with the unit turned ON or OFF.
With the unit turned ON:
1. Slide down front cover of controller below ON/OFF button. See Fig. 4.
2. Press the DELAY button. The clock will advance 1 hour and the word “STOP” and number “3” will flash. See Fig. 11.
3. Press the DELA Y button once to advance the clock an ad­ditional hour until desired delayed time is reached. Be sure to point the remote control toward the unit while pressing the DELAY button.
4. The word “STOP” will stop flashing when the command has been transmitted and received by the unit.
With the unit turned OFF:
1. Slide down front cover of controller below ON/OFF button. See Fig. 4.
2. Press the DELAY button. The clock will advance 1 hour and the word “START” and number “3” will flash. See Fig. 11.
3. Press the DELA Y button once to advance the clock an ad­ditional hour until desired delayed time is reached. Be sure to point the remote control toward the unit while pressing the DELAY button.
4. The word “START” will stop flashing when the com­mand has been transmitted and received by the unit.
Canceling Delayed Start/Stop
— T o cancel the Delayed S tart/ Stop function, follow the instructions in Canceling Specific Start/Stop T ime Period section.
NOTE: The Delay setting is stored in Time period 3. LOCAL SENSE FUNCTION (2-Way Remote Control) —
The local sense function allows the remote control to operate by transmitting the room air temperature to the unit at regular intervals from wherever the controller is located in the room. The unit will then operate to make the air near the remote con­trol reach the desired temperature.
To set Local Sense function:
1. Slide down front cover of controller below ON/OFF button. See Fig. 4.
2. Press the SENSE button. The “House” symbol will ap­pear on the display screen. See Fig. 12.
3. Place the remote control in desired location in room. Be sure there is a direct line between the remote control and the unit.
To Cancel Local Sense function
— While in “Loca l Se nse” func tio n, press the SENSE button. The “House” symbol will disappear from the display screen and Local Sense function will be canceled.
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
MODE FAN SWEEP
A
A
START
STOP 1 2 3
DAILY
DAILY TIMER INDICATOR
Fig. 9 — Daily Timer Indicator on
Remote Control Display
Fig. 10 — Room Air Temperature Indicator on
Remote Control Display
STOP
DAILY
3
START
3
DAILY
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
MODE FAN SWEEP
A
A
LOCAL SENSE INDICATOR
Fig. 11 — Delayed Start/Stop Indicators on
Remote Control Display
Fig. 12 — Local Sense Indicator on Remote
Control Display
PROGRAMMING DISPLAY WITH UNIT ON
PROGRAMMING DISPLAY WITH UNIT OFF
Unit Operation (Fig. 13) — In the event that the remote
control is not working or has been misplaced, the unit will operate as follows:
40BN018,024,030 — Units always operate by the remote control. If you lose or break the remote, the unit will continue to operate but settings cannot be changed until you get a new remote control.
To Turn Unit Off under the front cover. See Item I, Fig. 13. The AUTO/OFF indicator light will go off.
To Turn Unit On the front cover. See Item I, Fig. 13. The AUTO/OFF indicator
— Push the Operation Push Button located
— Push the Auto/Off button located under
light will light. The unit will operate at the settings that have been programmed using the remote control.
40BN036 — Unit will operate according to predetermined factory settings.
To Turn Unit Off
— Slide the Operation Switch on the unit
(Item I, Fig. 13) to the OFF position. To Turn Unit On
— Slide the Operation Switch on the unit (Item I, Fig. 13) to the AUTO position. The unit will operate at a temperature setting of 74 F and will automatically select the required operation mode and fan speed to maintain this setting.
40BN018,024,030
40BN036
FEATURE DESCRIPTION A Infrared Receiver Receives transmissions from the remote controller. B FILTER Indicator Light Lights when the air filters require cleaning. C (ON)/(AIR COND Indicator Light Lights when the air conditioner operates. Flashes when defrosting. D TIMER Indicator Light Lights when a TIMER Start or Stop time is set.
POWER Indicator Light Lights when the air conditioner is connected to the electricity supply of the proper
E
SERVICE Indicator Light Lights or flashes accordingly to the malfunction. (See further information on
G
Operation Push Button (40BN018,024,030)
Operation Slide Switch
I
(40BN036)
line voltage.
page 11).
• Turns the air conditioner ON (Auto) Mode and OFF without Remote Control.
• Resets unit after malfunctions and resets the Filter indicator light. (Press the but­ton continuously for 5 seconds.)
• Turns the air conditioner ON (Auto) Mode and OFF without Remote Control.
• Resets unit after malfunctions and resets the Filter indicator light. (Slide Operation Switch to OFF position for 5 seconds and then return the switch to remote.)
• Operates the air conditioner using the remote controller when the operation switch is in REMOTE position.
Fig. 13 — Indoor Unit Display Panel Features
7
8
CLEANING AND MAINTENANCE
Air Filters —
Remove and clean the air filters when the Filter indicator light on the unit display panel is lit. See Fig. 13 and 14.
NOTE: If air filters show signs of excessive wear or are torn, they must be replaced. Contact your local dealer for replace­ment filters.
1. Open front panel on unit.
2. Pull filters down to remove. (See Fig. 14.)
3. Vacuum filters.
4. Clean with warm water.
5. Shake filter to remove excess water and dry thoroughly.
6. Replace filter by sliding filter behind front grille until fil­ter snaps in place.
7. Slide Operation Switch on unit to OFF position to reset Filter status indicator light on 40BN036 units, or press the ON/OFF button for 5 seconds on 40BN018,024 and 036 units.
8. Slide Operation Switch on unit to REMOTE position to resume remote control operation.
Indoor Unit (40BN) Front Panel — To clean the
front panel on the indoor unit, wipe the outside with a soft, dry cloth. If necessary, a mild liquid detergent can be applied and wiped off with a dry cloth.
Indoor Unit (40BN) Coil — To clean the indoor unit
coil, remove the front panel and vacuum the coil fins. Avoid bending or damaging the fins.
Outdoor Unit (38BN018-036) Coil — To clean the
outdoor unit coil follow the steps below:
1. Remove any dirt, debris or obstruction from discharge opening.
2. Use a garden hose to spray water on coil. Be sure to spray between coil fins to remove any debris that may inhibit heat transfer.
Condensate Drains — Clean all condensate drains at
the start of each cooling season. Check the flow by pouring wa­ter into the drain.
To avoid the possibility of electric shock, always turn off power to the system before performing any cleaning or maintenance to the system. Turn of f the outdoor disconnect switch located near outdoor unit. Be sure to disconnect indoor unit if on a separate switch.
Operating the system with dirty air filters may damage the indoor unit and could cause reduced cooling performance. Intermittent system operation, frost build-up on indoor coil and blown fuses may also result from system operation with dirty air filters.
When cleaning the front panel, do not use water hotter than 105 F and do not pour water onto the fan coil.
Do not use abrasive or petroleum based cleaners as they may damage the front panel.
Sharp fins and other metal parts on the outdoor unit coil can cause personal injury during cleaning.
Fig. 14 — Removing Air Filters
40BN018,024,030 40BN036
System Operation Check List — The items outlined
in the following list will help to assure proper system operation:
• Be sure unit is connected directly to electrical supply.
• Replace both remote control batteries at the same time when the Low Battery symbol appears.
• Point the remote control toward the unit display panel when transmitting a command.
• Place the remote control in a location where there is a direct line for transmission of data to the unit.
• Select a moderate temperature setting. Extreme tempera­tures waste electricity.
• Keep doors and windows closed while unit is operating.
• Close air vents in unoccupied rooms to save electricity.
• Contact an authorized service representative if a problem arises that cannot be easily resolved.
• Do not perform cleaning or m aintenance activities while unit is on.
• Keep remote control out of direct sunlight and heat.
• Keep display panel on unit away from direct sunlight and heat as this may interfere with remote control transmissions.
• Do not block air intakes and outlets on the indoor or outdoor units.
DIP Switch Settings — The remote control contains
seven DIP switches, located in the battery compartment, two of which control special system characteristics. See Fig. 15. The DIP switch default positions are set according to the model air conditioner installed, as per the following table.
SWITCH12 3 4 567
POSITION ON OFF OFF OFF OFF ON OFF
Switch No. 3 should be set as follows: OFF (default) — When only one air conditioner is installed
in the room.
ON — When there are two air conditioners with remote
controllers installed in the room, in one of the remote control­lers this switch must be in the ON position. To activate the new switch setting, simultaneously press the MODE and ROOM buttons.
Switch No. 4 should be set as follows: OFF — Displays temperature in °C, with a 24-hour clock
format.
ON — Displays temperature in °F, with a 12-hour clock
(PM indictor) format.
T o operate the special systems characteristic s:
1. Remove the batteries.
2. Set the DIP switches to the required positions.
3. Wait approximately 2 minutes and return batteries to proper position.
Energy Saving Recommendations — The follow-
ing recommendations will add greater efficiency to the duct free system:
• Select a comfortable thermostat setting and leave it at chosen setting. Avoid continually raising and lowering the setting.
• Keep unit filter clean. Frequent cleaning may be neces­sary depending on indoor air quality.
• Use drapes, curtains or shades to keep direct sunlight from heating room on very hot days.
• Do not obstruct front grille air intake on front panel.
• Turn on air conditioning before indoor air becomes too uncomfortable.
ON
OFF
1234567
ON
ECE
1234567
Fig. 15 — DIP Switch Location in Remote Control
9
TROUBLESHOOTING GUIDE
Your air conditioner is very reliable and requires little maintenance. However, the air conditioner’s proper operation can be interrupt­ed by a malfunction in the electrical system or by incorrect operation. You can try to overcome these simple malfunctions yourself, with the aid of the following table and the malfunction displays shown in Fig. 16.
PROBLEM POSSIBLE CAUSE SOLUTION
Air conditioner does not work. • No command is transmitted to air conditioner. • Press the On/Off (Transmission) button.
POWER indicator light is not lit. • Air conditioner is not properly connected. • Check electrical connection.
FILTER indicator light is lit. • Filters require cleaning. • Remove and clean filters.
Air conditioner is working, but does not perform the required operation.
(ON)/(AIR COND). Indicator light is continuously flashing.
Various indicator lights behave differently than shown in Fig. 13.
Air conditioner does not operate with the remote controller.
The remote controller of another air conditioner interferes with your air conditioner’s operation.
• Air conditioner did not receive transmitted command.
• Automatic interrupter switched Off. • Reset interrupter.
• Fuse burned. • Replace fuse.
• Desired temperature setting is higher than room air temperature when operating in the COOLING mode.
• Desired temperature setting is lower than room air temperature when operating in the HEATING mode.
• The control system is malfunctioning. • For 40BN036 slide the operation switch to OFF
• There is no direct line of sight between
the remote controller and the air conditioner.
• The air conditioner has reached the desired temperature and stopped the compressor oper­ation (thermostat function).
• Incorrect operation or malfunction. • For 40BN018,024,030 press the operation push
• In 40BN036 the operation push button is in AUTO or OFF. (For 40BN018,024,030 go to next bullet.)
• The remote controller batteries are weak. • Replace the batteries.
• The remote controller is malfunctioning. • Turn the air conditioner On and OFF using the
• Both remote controllers are transmitting
on the same wavelength.
• Make sure that remote controller is pointed at air conditioner during command transmission.
• For 40BN036 move operation switch to OFF position for 5 sec. and return it to REMOTE.
• For 40BN018,024,030 press the operation push button continuously for 5 seconds.
• Lower the desired temperature setting.
• Raise the desired temperature setting.
position for 5 sec. and return it to REMOTE.
• For 40BN018,024,030 press the operation push button, continuously for 5 seconds. Press once again to operate the air conditioner.
button continuously for 5 seconds.
• For 40BN036 slide the operation slide switch to OFF position for 5 sec. and return it to REMOTE.
• Restart the air conditioner, if the problem per­sists, call service personnel.
• For 40BN036 turn the operating switch to REMOTE position.
operation push button or slide switch.
• Call service personnel.
10
On each Malfunction, Indicator Light (red) will flash at a constant rate:
40BN018,024 AND 030 40BN036
40BN018,024 AND 03040BN036
Malfunction Indication Display
For 40BN036 the malfunction can be read by the rate of the flashing light on the control. (Raise the front grille list.) For 40BN018,024,030 the malfunction can be read without raising the front grille by the rate of the flashing service light.
Malfunction Display Light
TH1 Malfunction • 1 short flash TH2 Malfunction • 2 short flashes Low Pressure Malfunction • 3 short flashes High Pressure Malfunction • 4 short flashes Low Voltage Malfunction • 5 short flashes High Voltage Malfunction • 6 short flashes
Fig. 16 — Malfunction Displays
11
Loading...
+ 25 hidden pages