Carrier 38APD025-100, 38APS025-050 User Manual

GEMINI™ SELECT
38APS025-050,38APD025-100
Commercial Air-Cooled Condensing Units
with COMFORTLINK™ Controls
Controls, Start-Up, Operation,
Service, and Troubleshooting
50/60 Hz
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . 1,2
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Conventions Used in This Manual. . . . . . . . . . . . . . . . 2
Display Module Usage . . . . . . . . . . . . . . . . . . . . . . . . . . 17
• SCROLLING MARQUEE DISPLAY
• ACCESSORY NAVIGATOR™ DISPLAY MODULE
Main Base Board (MBB) . . . . . . . . . . . . . . . . . . . . . . . . . 18
Current Sensor Board (CSB) . . . . . . . . . . . . . . . . . . . . 18
Energy Management Module (EMM) . . . . . . . . . . . . . 18
Compressor Expansion Module (CXB) . . . . . . . . . . 19
AUX Board (AUX). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Enable/Off/Remote Contact Switch. . . . . . . . . . . . . . 19
Emergency On/Off Switch . . . . . . . . . . . . . . . . . . . . . . . 19
Board Addresses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Control Module Communication. . . . . . . . . . . . . . . . . 19
Carrier Comfort Network
OPERATING DATA. . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-33
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
• RETURN AIR TEMPERATURE (RAT) ACCESSORY
• SUPPLY AIR TEMPERATURE (SAT) ACCESSORY
• COMPRESSOR RETURN GAS TEMPERATURE SENSOR (RGT)
• OUTDOOR-AIR TEMPERATURE SENSOR (OAT)
• DISCHARGE TEMPERATURE THERMISTOR (DTT)
• SPACE TEMPERATURE SENSOR (SPT)
Fan Status Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Thermostat Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Pressure Transducer Inputs. . . . . . . . . . . . . . . . . . . . . 23
Energy Management Module . . . . . . . . . . . . . . . . . . . . 23
Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Head Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Service Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Operating Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Operation of Machine Based on Control
Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Set Point Adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Demand Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
• DEMAND LIMIT (2-Stage Switch Controlled)
• EXTERNALLY POWERED DEMAND LIMIT (4 to 20 mA Controlled)
• DEMAND LIMIT (CCN Loadshed Controlled)
Cooling Set Point (4 to 20 mA) . . . . . . . . . . . . . . . . . . 32
Digital Scroll Option. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
System Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33-49
Preliminary Charge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Adjust Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . 34
Check Compressor Oil Level . . . . . . . . . . . . . . . . . . . . 47
Final Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
®
(CCN) Interface. . . . . . . 20
Page
Oil Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Actual Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Operating Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
• AMBIENT LIMITATIONS
• VOLTAGE (ALL UNITS)
Operation Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49-59
Electronic Components . . . . . . . . . . . . . . . . . . . . . . . . . 49
• CONTROL COMPONENTS
Thermistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Pressure Transducers. . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Condenser Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Motormaster
• GENERAL OPERATION
• CONFIGURATION
• DRIVE PROGRAMMING
•EPM CHIP
• LOSS OF CCN COMMUNICATIONS
• TROUBLESHOOTING
• REPLACING DEFECTIVE MODULES
Compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59,60
Recommended Maintenance Schedule. . . . . . . . . . 59
Microchannel Heat Exchanger (MCHX) Condenser
Coil Maintenance and Cleaning
Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 60-66
Complete Unit Stoppage and Restart. . . . . . . . . . . . 60
• GENERAL POWER FAILURE
• UNIT ENABLE-OFF-REMOTE CONTACT SWITCH
IS OFF
• FAN STATUS INPUT OPEN
• OPEN 24-V CONTROL CIRCUIT BREAKER(S)
• COOLING LOAD SATISFIED
• THERMISTOR FAILURE
• COMPRESSOR SAFETIES
Alarms and Alerts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
APPENDIX A — DISPLAY TABLES . . . . . . . . . . . 67-78
APPENDIX B — CCN TABLES . . . . . . . . . . . . . . . . 79-84
START-UP CHECKLIST FOR 38AP SPLIT SYSTEM
CONDENSING UNIT . . . . . . . . . . . . . . . . . . . . CL-1-CL-5
®
V Controller . . . . . . . . . . . . . . . . . . . . . . 54
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be hazardous due to system pressures, electrical components, and equipment location (roof, elevated structures, mechanical rooms, etc.). Only trained, qualified installers and service mechanics should install, start up, and service this equipment.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53380003-01 Printed in U.S.A. Form 38AP-1T Pg 1 210 11-09 Replaces: New
When working on this equipment, observe precautions in
ENTER
ESCAPE
ENTER
the literature, and on tags, stickers, and labels attached to the equipment, and any other safety precautions that apply. Follow all safety codes. Wear safety glasses and work gloves. Use care in handling, rigging, and setting this equipment, and in handling all electrical components.
WARNING
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation and service. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.
WARNING
DO NOT VENT refrigerant relief valves within a building. Outlet from relief valves must be vented outdoors in accordance with the latest edition of ANSI/ASHRAE (American National Standards Institute/American Society of Heating, Refrigeration and Air Conditioning Engineers) 15 (Safety Code for Mechanical Refrigeration). The accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation. Provide adequate ventilation in enclosed or low overhead areas. Inhalation of high concentrations of vapor is harmful and may cause heart irregularities, unconsciousness or death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation. Decomposition products are hazardous.
WARNING
DO NOT attempt to unbraze factory joints when servicing this equipment. Compressor oil is flammable and there is no way to detect how much oil may be in any of the refrigerant lines. Cut lines with a tubing cutter as required when performing service. Use a pan to catch any oil that may come out of the lines and as a gage for how much oil to add to system. DO NOT re-use compressor oil.
CAUTION
This unit uses a microprocessor-based electronic control system. Do not use jumpers or other tools to short out components, or to bypass or otherwise depart from recom­mended procedures. Any short-to-ground of the control board or accompanying wiring may destroy the electronic modules or electrical components.
CAUTION
Puron® refrigerant (R-410A) systems operate at higher pressures than standard R-22 systems. Do not use R-22 ser­vice equipment or components on Puron refrigerant equip­ment. If service equipment is not rated for Puron refrigerant, equipment damage or personal injury may result.
CAUTION
GENERAL
This publication contains Controls Start-Up, Service, Operation, and Troubleshooting information for the Gemini™ Select 38AP condensing units with ComfortLink controls. See Table 1 for unit size information.
Table 1 — Unit Sizes
38AP UNIT SIZE
025 25 027 27 030 30 040 40 050 50 060 60 070 70 080 80 090 90 100 100
NOMINAL CAPACITY,
TONS, 60 Hz
CONTROLS
General —
the ComfortLink™ electronic control system that controls and monitors all operations of the unit.
The control system is composed of several components as listed in the sections below. See Fig. 1-3 for typical control box drawing. See Fig. 4-17 for power and control wiring.
The 38AP air-cooled condensing unit contains
Conventions Used in This Manual — The follow-
ing conventions for discussing configuration points for the local display (scrolling marquee or Navigator™ accessory) will be used in this manual.
Point names will be written with the mode name first, then any sub-modes, then the point name, each separated by an arrow symbol (. Names will also be shown in bold and italics. As an example, the Lead/Lag Circuit Select Point, which is located in the Configuration mode, Option sub-mode, would be written as Configuration OPT2LLCS.
This path name will show the user how to navigate through the local display to reach the desired configuration. The user would scroll through the modes and sub-modes using the
and keys. The arrow symbol in the path name repre­sents pressing to move into the next level of the menu structure.
When a value is included as part of the path name, it will be shown at the end of the path name after an equals sign. If the value represents a configuration setting, an explanation will be shown in parenthesis after the value. As an example, ConfigurationOPT2LLCS = 2 (Circuit A leads).
Pressing the and keys simultaneously will scroll an expanded text description of the point name or value across the display. The expanded description is shown in the local display tables but will not be shown with the path names in text.
The CCN (Carrier Comfort Network referenced in the local display tables for users configuring the unit with CCN software instead of the local display. The CCN tables are located in Appendix B of the manual.
®
) point names are also
Refrigerant charge must be removed slowly to prevent loss of compressor oil that could result in compressor failure.
2
Fig. 1 — Component Arrangement — Unit Sizes 025-030
LEGEND
AUX Auxiliary C—Contactor CB Circuit Breaker CCHR Crankcase Heater Relay CSB Current Sensor Board EMM Energy Management Module EQUIP GND — Equipment Ground FB Fuse Block FC Fan Contactor LON Local Operating Network MBB Main Base Board SW Switch TB Terminal Block TRAN Transformer UPC Unitary Protocol Converter
3
Fig. 2 — Component Arrangement — Unit Sizes 040-060
LEGEND
AUX Auxiliary C—Contactor CB Circuit Breaker CCH Crankcase Heater Relay CSB Current Sensor Board EMM Energy Management Module EQUIP GND — Equipment Ground FC Fan Contactor FCB Fan Circuit Breaker LON Local Operating Network MBB Main Base Board MM Motormaster
®
SW Switch TB Terminal Block TRAN Transformer UPC Unitary Protocol Converter
4
Fig. 3 — Component Arrangement — Unit Sizes 070-100
LEGEND
AUX Auxiliary C—Contactor CB Circuit Breaker CCH Crankcase Heater Relay CSB Current Sensor Board CXB Compressor Expansion Board EMM Energy Management Module EQUIP GND — Equipment Ground FC Fan Contactor FCB Fan Circuit Breaker LON Local Operating Network MBB Main Base Board SW Switch TB Terminal Block TRAN Transformer UPC Unitary Protocol Converter
5
Fig. 4 — Power Wiring Schematic — 38APS,APD025-030
6
Fig. 5 — Power Wiring Schematic — 38APS040,050
7
8
Fig. 6 — Power Wiring Schematic — 38APD040-060
9
Fig. 7 — Power Wiring Schematic — 38APD070-100
10
Fig. 8 — Control Wiring Schematic — 38APS025-050
Fig. 9 — Control Wiring Schematic — 38APD025-060
11
12
Fig. 10 — Control Wiring Schematic — 38APD070-100
Legend and Notes for Fig. 4-10
LEGEND NOTES:
ACCSY Accessory ALM Alarm AMPS Amperes AUX Auxiliary C—Contactor CB Circuit Breaker CCB Compressor Circuit Breaker CCH Crankcase Heater Relay CH Crankcase Heater COMP Compressor CSB Current Sensor Board CXB Compressor Expansion Module DGS Digital Scroll DPT Discharge Pressure Transducer DTT Discharge Temperature Thermistor DUS Digital Unloaded Solenoid EMM Energy Management Module EQUIP GND — Equipment Ground FB Fuse Block FC Fan Contactor FCB Fan Circuit Breaker FIOP Factory-Installed Option FR Fan Relay FS Fan Status FU Fuse GND Ground HPS High Pressure Switch LLSV Liquid Line Solenoid Valve LV T Low Voltage Terminal MBB Main Base Board MLV Minimum Load Valve MM Motormaster MP Modular Motor Protector NEC National Electrical Code OAT Outdoor Air Thermistor OFM Outdoor Fan Motor OPT Option PL Plug RAT Return Air Temperature RGT Return Gas Temperature RLY — SAT Supply Air Temperature SEN Sensor Terminal Block SET Set Point Terminal Block SPT Suction Pressure Transducer SW Switch TB Terminal Block TEMP Temperature TRAN Transformer UPC Unitary Protocol Converter Y—Cool Stage
Relay
1. Factory wiring is in accordance with UL (Underwriters Labora­tories) 1995 standards. Any field modifications or additions must be in compliance with all applicable codes.
2. Use 75 C minimum wire for field power supply.
3. All field interlock contacts must have a minimum rating of 2 amps at 24-vac sealed. See field interlock wiring.
4. Compressor and fan motors are thermally protected. Three­phase motors protected against single-phase conditions.
5. Terminals 13 and 14 of LVT are for field connection of remote on-off. The contact must be rated for dry circuit application capable of handling a 5-vdc, 1 mA to 20 mA load.
6. For 500 series unit operation at 208-3-60 line voltage, TRAN1 primary connections must be moved to terminals H3 and H4.
7. For 575-3-60 units, fan circuit breakers FCB1 and FCB2 are replaced with fuse blocks FB1 and FB2.
8. For units with low ambient Motormaster option or field-installed acessory, fan contactors FC1 and FC2 are replaced with fan relays FR1 and FR2.
9. MP-A1 not used in the following units: 070-100: 400-v, 460-v units without digital scroll
10. MP-A2 not used in the following units: 070-100: 400-v, 460-v
11. MP-B1 not used in the following units: 070: all units 080-100: 400-v, 460-v
12. MP-B2 not used in the following units: 070: all units 080-100: 400-v, 460-v
13. MP-A3 not used in the following units: 090,100: 400-v, 460-v
14. MP-B3 not used in the following units: 070: all units 080-100: 400-v, 460-v
15. Jumper plug required when modular motor protector is not used.
®
V factory-installed
13
OUTSIDE AIR
DUCT SUPPLY
RETURN AIR
MAT/RAT SATFS1*
FAN
EVAPORATOR COIL
Fig. 11 — Field Power Wiring
LEGEND
NOTES:
1. Factory wiring is in accordance with UL 1995 standards. Field modifications or additions must be in compliance with all applicable codes.
2. All units or modules have single point primary power connection. Main power must be supplied from a field or factory-supplied disconnect.
3. Wiring for main field supply must be rated 75 C. Use copper conductors only.
a. Incoming wire size range for terminal block with MCA (minimum circuit
amps) up to 175 amps is 14 AWG (American Wire Gage) to 2/0.
b. Incoming wire size range for terminal block with MCA from 175.1 amps to
420 amps is 2 AWG to 600 kcmil.
c. Incoming wire size range for non-fused disconnect with MCA up to
100 amps is 14 AWG to 1/0.
d. Incoming wire size range for non-fused disconnect with MCA from
100.1 amp to 200 amps is 6 AWG to 350 kcmil.
e. Incoming wire size range for non-fused disconnect with MCA from
200.1 amp to 450 amps is 3/0 to 500 kcmil.
4. Refer to certified dimensional drawings for exact locations of the main power and control power entrance locations.
EQUIP GND — Equipment Ground NEC National Electrical Code
a38-7122
LEGEND
*FS1 can be pressure differential switch (shown), motor current detection, or sail switch.
FS1 Fan Status Switch (24-v) MAT — Mixed Air Temperature Sensor RAT — Return Air Temperature Sensor SAT — Supply Air Temperature Sensor
a38-7133
Fig. 12 — MAT/RAT and SAT Sensor Layout
14
a38-7125
a38-7127
*See Fig. 12 for MAT/RAT and SAT location. †Not required for single circuit units.
Fig. 15 — Constant Volume Application Wiring Diagram Space Temperature Sensor Control, Sizes 025-100
Fig. 14 — Constant Volume Application Wiring Diagram 2-Stage Thermostat Control —
with Digital Scroll Option, Sizes 025-030 or All Sizes 040-100
Fig. 13 — Constant Volume Application Wiring Diagram 2-Stage Thermostat Control, Sizes 025-030 —
without Digital Scroll Option
*Not required for single circuit units.
25242322212019181716151413
REMOTE
ON/OFF
LV T TERMINAL STRIP
121110987654321
ALM
R
COOL 1
COOL 2
FS 1
LLSV-A
LLSV-B
*
SEE NOTE 6
a38-7126
*See Fig. 12 for MAT/RAT and SAT location. †Not required for single circuit units.
25242322212019181716151413
REMOTE
ON/OFF
LV T TERMINAL STRIP
121110987654321
ALM
R
COOL 1
FS 1
LLSV-A
LLSV-B
*
SEE NOTE 6
COOL2
121110987654321
25242322212019181716151413
LV T TERMINAL
STRIP
SAT
FS 1
SPT
*
MAT/RAT
*
SA
LLSV-B
REMOTE
ON/OFF
ALM
R
15
LLSV-A
SEE NOTE 6
25242322212019181716151413
REMOTE
ON/OFF
LV T TERMINAL STRIP
121110987654321
ALM
R
FS 1
LLSV-A
SEE NOTE 6
SAT
*
MAT/RAT
*
LLSV-B
a38-7128
Fig. 16 — Variable Air Volume Application Wiring Diagram, Sizes 025-100
*See Fig. 12 for MAT/RAT and SAT location. †Not required for single circuit units.
Fig. 17 — Optional Energy Management Module Wiring
a38-7129
Legend and Notes for Fig. 13-17
LEGEND
NOTES:
1. Factory wiring is in accordance with UL 1995 standards. Field modifications or additions must be in compliance with all appli­cable codes.
2. All units or modules have single point primary power connec­tion. Main power must be supplied from a field or factory­supplied disconnect.
3. Wiring for main field supply must be rated 75 C. Use copper conductors only.
a. Incoming wire size range for terminal block with MCA (mini-
mum circuit amps) up to 175 amps is 14 AWG (American Wire Gage) to 2/0.
b. Incoming wire size range for terminal block with MCA from
175.1 amps to 420 amps is 2 AWG to 600 kcmil.
c. Incoming wire size range for non-fused disconnect with MCA
up to 100 amps is 14 AWG to 1/0.
d. Incoming wire size range for non-fused disconnect with MCA
from 100.1 amp to 200 amps is 6 AWG to 350 kcmil.
e. Incoming wire size range for non-fused disconnect with MCA
from 200.1 amp to 450 amps is 3/0 to 500 kcmil.
4. Terminals 1 and 2 of the LVT are for the alarm relay. The maxi­mum load allowed for the alarm relay is 5-va sealed and 10-va inrush at 24-v. Field power supply is not required.
5. Refer to certified dimensional drawings for exact locations of the main power and control power entrance locations.
6. Terminals 24, 25, and 2 of the LVT are for the control of the field-supplied LLSV. The maximum load allowed for the LLSV is 15-va sealed and 30-va inrush at 24-v. Field power supply is not required.
7. LLSV (24-v) should be 15-va maximum per valve as required.
8. Installation of fan status switch (FS1) is recommended.
9. The contacts for remote ON/OFF, fan status, and demand limit options must be rated for dry circuit application capable of han­dling a 24-vac load up to 50 mA.
ALM R Alarm Relay (24-v), 5-va Maximum COOL1 Thermostat Stage 1 (24-v) COOL2 Thermostat Stage 2 (24-v) FS1 Fan Status Switch (24-v) LLSV Liquid Line Solenoid Valve LV T Low Voltage Terminal MAT Mixed Air Temperature Sensor RAT Return Air Temperature Sensor SA Set Point Adjustment (T-56, T-59) SAT Supply Air Temperature Sensor SPT Space Temperature Sensor (T-55, T-56, T-59)
Field Control Wiring
LV T TERMINAL
121110987654321
25242322212019181716151413
STRIP
+
TEMP
RESET
4-20 mA
+
+
DEMAND LIMIT STEP 1
DEMAND LIMIT STEP 2
DEMAND
LIMIT
4-20 mA
COOLING
SETPOINT/
CAPACITY
REQUESTED
4-20 mA
16
Display Module Usage
Run Status
Service Test
Temperature
Pressures
Setpoints
Inputs
Outputs
Configuration
Time Clock
Operating Modes
Alarms
Alarm Status
ENTER
MODE
ESCAPE
Fig. 18 — Scrolling Marquee Display
ESCAPE
ENTER
ESCAPE
ESCAPE
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ESCAPE
ESCAPE
ENTER
ESCAPE
ENTER
ESCAPE
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
R
un
S
ta
tu
s
S
er
vic
e
T
e
s
t
T
e
m
pe
ra
tu
r
e
s
P
res
s
u
res
S
e
tpo
ints
Inp
u
ts
O
u
tpu
ts
C
o
nfig
u
ratio
n
T
im
e
C
lo
ck
O
p
e
ra
tin
g
M
o
d
e
s
A
la
rm
s
EN
TER
ES
C
M
O
D
E
Alarm Status
Comfort
Link
Fig. 19 — Accessory Navigator Display Module
SCROLLING MARQUEE DISPLAY — This device is the keypad interface used for accessing unit information, reading sensor values, and testing the unit. See Fig. 18. The scrolling marquee display is a 4-key, 4-character, 16-segment LED (light-emitting diode) display. Eleven mode LEDs are located on the display as well as an Alarm Status LED. See Appendix A — Display Tables for further details.
The scrolling marquee display module provides the user in­terface to the ComfortLink™ control system. The display has up and down arrow keys, an key, and an key. These keys are used to navigate through the different lev­els of the display structure. See Table 2. Press the key until the display is blank to move through the top 11 mode levels indicated by LEDs on the left side of the display.
Pressing the and keys simultaneously will scroll a clear language text description across the display indicating the full meaning of each display acronym. Pressing the and keys when the display is blank (Mode LED level) will return the scrolling marquee display to its default menu of rotating display items. In addition, the pass­word will be disabled requiring that it be entered again before changes can be made to password protected items. Clear lan­guage descriptions will be displayed in English.
When a specific item is located, the display will flash show­ing the operator, the item, followed by the item value and then followed by the item units (if any). Press the key to stop the display at the item value. Items in the Configuration and Service Test modes are password protected. The display will flash PASS and WORD when required. Use the and arrow keys to enter the 4 digits of the password. The default password is 1111.
Changing item values or testing outputs is accomplished in the same manner. Locate and display the desired item. Press
to stop the display at the item value. Press the key again so that the item value flashes. Use the
arrow keys to change the value or state of an item and press the
key to accept it. Press the key and the item, value, or units display will resume. Repeat the process as required for other items.
ACCESSORY NAVIGATOR™ DISPLAY MODULE — The Navigator module provides a mobile user interface to the
ComfortLink™ control system, which is only available as a field-installed accessory. The display has up and down arrow keys, an key, and an key. These keys are used to navigate through the different levels of the display structure. Press the key until ‘Select a Menu Item’ is displayed to move through the top 11 mode levels indicated by LEDs on the left side of the display. See Fig. 19.
Once within a Mode or sub-mode, a “>” indicates the cur-
rently selected item on the display screen. Pressing the
and keys simultaneously will put the Nav­igator module into expanded text mode where the full meaning of all sub-modes, items and their values can be displayed. Press­ing the and keys when the display says ‘Select Menu Item’ (Mode LED level) will return the Navigator module to its default menu of rotating display items (those items in Run Status
VIEW). In addition, the password will be dis­abled, requiring that it be entered again before changes can be made to password protected items. Press the key to exit out of the expanded text mode.
NOTE: When the Language Selection (Configuration DISPLANG), variable is changed, all appropriate display expansions will immediately change to the new language. No power-off or control reset is required when reconfiguring languages.
When a specific item is located, the item name appears on the left of the display, the value will appear near the middle of the display and the units (if any) will appear on the far right of the display. Press the key at a changeable item and the val­ue will begin to flash. Use the up and down arrow keys to change the value, and confirm the value by pressing the key.
Changing item values or testing outputs is accomplished in the same manner. Locate and display the desired item. Press
so that the item value flashes. Use the arrow keys to change the value or state and press the key to accept it. Press the key to return to the next higher level of structure. Repeat the process as required for other items.
Items in the Configuration and Service Test modes are pass­word protected. The words Enter Password will be displayed when required, with 1111 also being displayed. The default password is 0111. Use the arrow keys to change the number and press to enter the digit. Continue with the re­maining digits of the password. The password can only be changed through CCN operator interface software such as ComfortWORKS
®
, ComfortVIEW™ and Service Tool.
17
Adjusting the Contrast
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER
— The contrast of the display can be adjusted to suit ambient conditions. To adjust the contrast of the Navigator module, press the key until the dis­play reads, “Select a menu item.” Using the arrow keys move to the Configuration mode. Press to obtain access to this mode. The display will read:
> TEST OFF METR OFF LANG ENGLISH
Pressing will cause the “OFF” to flash. Use the up or down arrow to change “OFF” to “ON”. Pressing will illuminate all LEDs and display all pixels in the view screen. Pressing and simultaneously allows the user to adjust the display contrast. Use the up or down arrows to adjust the contrast. The screen’s contrast will change with the adjustment. Press to accept the change. The Navigator module will keep this setting as long as it is plugged in to the LEN bus.
Adjusting the Backlight Brightness
— The backlight of the display can be adjusted to suit ambient conditions. The factory default is set to the highest level. To adjust the backlight of the Navigator module, press the key until the display reads, “Select a menu item.” Using the arrow keys move to the Configuration mode. Press to obtain access to this mode. The display will read:
> TEST OFF METR OFF LANG ENGLISH
Pressing will cause the “OFF” to flash. Use the up
or down arrow keys to change “OFF” to “ON”. Pressing
will illuminate all LEDs and display all pixels in the
view screen. Pressing the up and down arrow keys simultane­ously allows the user to adjust the display brightness. Use the up or down arrow keys to adjust screen brightness. Press
to accept the change. The Navigator module will
keep this setting as long as it is plugged in to the LEN bus.
Main Base Board (MBB) — See Fig. 20. The MBB is
the heart of the ComfortLink control system. It contains the major portion of operating software and controls the operation of the machine. The MBB continuously monitors input/output channel information received from its inputs and from all other modules. The MBB receives inputs from the discharge and suction pressure transducers, current sensor boards (CSB) and thermistors. See Table 3. The MBB also receives the discrete inputs from the thermostat contacts and other status switches. See Table 4. The MBB also controls several outputs. Informa­tion is transmitted between modules via a 3-wire communica­tion bus or LEN (Local Equipment Network). The CCN (Car­rier Comfort Network
®
) bus is also supported. Connections to both LEN and CCN buses are made at the LVT (low voltage terminal) terminal strip.
Current Sensor Board (CSB) — The CSB is used to
monitor the status of the compressors by measuring current and providing an analog input to the main base board (MBB) or compressor expansion module (CXB).
Energy Management Module (EMM) — The EMM
module is available as a factory-installed option or as a field­installed accessory. The EMM module receives 4 to 20 mA inputs for the percent capacity, temperature reset, cooling set point, and demand limit functions. The EMM module also re­ceives the switch inputs for the field-installed 2-stage demand limit and when two thermostats are used for one unit. The EMM module communicates the status of all inputs with the MBB, and the MBB adjusts the control point, capacity limit, and other functions according to the inputs received.
Table 2 — Scrolling Marquee Display Menu Structure*
MODE
SUB-MODE
LEGEND
Ckt — Circuit
*Throughout this text, the location of items in the menu structure will be described in
the following format: Item Expansion (Mode Name Sub-mode N ame ITEM)
RUN
STATUS
Auto Display (VIEW)
Machine
Hours/Starts
(RUN)
Compressor
Run Hours
(HOUR)
Compressor
Starts
(STRT)
Preventive
Maintenance
(PM)
Software
Ver si on (VERS)
SERVICE
TEST
Manual
Mode
On/Off
(TEST)
Unit Outputs (OUTS)
Ckt A Comp
Tests
(CMPA)
Ckt B Comp
Tests
(CMPB)
TEMPERATURES PRESSURES
Unit
Temperatures
(UNIT)
Ckt A
Temperatures
(CIR.A)
Ckt B
Temperatures
(CIR.B)
Ckt A
Pressures
(PRC.A)
Ckt B
Pressures
(PRC.B)
SET
POINTS
Cooling (COOL)
Head
Pressure
(HEAD)
INPUTS OUTPUTS CONFIGURATION
Unit
Discrete
(GEN.I)
Ckt A/B (CRCT)
Unit
Analog
(4-20)
Unit
Discrete
(GEN.O)
Ckt A
(CIR.A)
Ckt B
(CIR.B)
Display
(DISP)
Unit Configuration
(UNIT)
CCN Network
(CCN)
Options 1
(OPT1)
Options 2
(OPT2)
Motormaster
(M.MST)
Reset Cool
Temperature
(RSET)
Set Point Select
(SLCT) Service
Configuration
(SERV)
Broadcast
Configuration
(BCST)
TIME
CLOCK
Unit Time
(TIME)
Unit Date
(DATE)
Daylight
Saving
Time
(DST)
Local
Holiday
Schedules
(HOL.L)
Schedule
Number
(SCH.N)
Local
Schedule
Number
(SCH.L)
Schedule
Overide
(OVR)
OPERATING
MODES
Modes
(MODE)
Task State
(TSKS)
ALARMS
Current (CRNT)
Reset
Alarms
(RCRN)
Alarm
History
(HIST)
18
Table 3 — Thermistor Designations
CEPL130346-01
STATUS
LEN
J1
J2
J4
J3
J5
J6
J7
J8
J9
J10
CCN
RED LED - STATUS GREEN LED -
LEN (LOCAL EQUIPMENT NETWORK)
YELLOW LED ­CCN (CARRIER COMFORT NETWORK)
INSTANCE JUMPER
K11
K10 K9
K8
K7
K6
K5
K4
K3 K2
K1
Fig. 20 — Main Base Board
THERMISTOR INPUT PIN CONNECTION POINT
Return Air (Accessory) MBB J8-11,12; LVT 19,20 Supply Air (Accessory) MBB J8-12,13; LVT 11,19 Compressor Return Gas
Temperature A Compressor Return Gas
Temperature B Outdoor Air Temperature MBB J8-7,8 Discharge Temperature
(Digital Option Only) Space Temperature (Accessory) MBB J8-5,6; LVT 21,22
Table 4 — Switch Inputs
Thermostat Y1 (Accessory) LVT 12,18 Thermostat Y2 (Accessory) LVT 15,18 Fan Status 1 (Accessory) LVT 16,18 Fan Status 2 (Accessory) LVT 17,18 Remote On/Off LVT 13,14 High Pressure Switch A MBB J6-4 High Pressure Switch B MBB J6-6
SWITCH INPUT PIN CONNECTION POINT
Compressor Expansion Module (CXB) — The
CXB is only used on unit sizes 070-100 to provide additional inputs and outputs for fans and compressors when the unit has more than 4 compressors.
AUX Board (AUX) — The AUX is used with the digital
scroll option and the low ambient head pressure option. It pro­vides additional inputs and outputs for digital scroll control along with analog outputs to control head pressure control fan speeds.
Enable/Off/Remote Contact Switch — The Enable/
Off/Remote Contact switch is a 3-position switch used to control the unit. When switched to the Enable position, the unit is under its own control. Move the switch to the Off position to shut the unit down. Move the switch to the Remote Contact po­sition and a field-installed dry contact can be used to start the unit. The contacts must be capable of handling a 24 vac, 50 mA load. In the Enable and Remote Contact (dry contacts closed)
MBB J8-1,2
MBB J8-3,4
AUX J6- 1, 2
positions, the unit is allowed to operate and respond to the scheduling configuration, CCN configuration and set point data. See Fig. 21.
Emergency On/Off Switch — The Emergency On/Off
switch should only be used when it is required to shut the unit off immediately. Power to the MBB, CXB, AUX, EMM, and scrolling marquee display is interrupted when this switch is off and all outputs from these modules will be turned off.
Board Addresses — The main base board (MBB) has a
3-position Instance jumper that must be set to ‘1.’ All other boards have 4-position DIP switches. All switches are set to ‘On’ for all boards.
Control Module Communication
RED LED — Proper operation of the control boards can be visually checked by looking at the red status LEDs (light-emitting diodes). When operating correctly, the red status LEDs should be blinking in unison at a rate of once every 2 seconds. If the red LEDs are not blinking in unison, verify that correct power is being supplied to all modules. Be sure that the main base board (MBB) is supplied with the current soft­ware. If necessary, reload current software. If the problem still persists, replace the MBB. A red LED that is lit continuously or blinking at a rate of once per second or faster indicates that the board should be replaced.
GREEN LED — The MBB has one green LED. The Local Equipment Network (LEN) LED should always be blinking whenever power is on. All other boards have a LEN LED which should be blinking whenever power is on. Check LEN connections for potential communication errors at the board J3 and/or J4 connectors. Communication between modules is accomplished by a 3-wire sensor bus. These 3 wires run in parallel from module to module. The J4 connector on the MBB provides both power and communication directly to the marquee display only.
YELLOW LED — The MBB has one yellow LED. The Carrier Comfort Network (CCN) LED will blink during times of network communication.
19
Carrier Comfort Network® (CCN) Interface —
CB1
REMOTE
CONTROL
ENABLE
SCROLLING MARQUEE
DISPLAY
ENABLE/OFF/REMOTE CONTACT SWITCH
EMERGENCY ON-OFF SWITCH
SW1 OFF
OFF
ON
SW2
CB2 CB3
Fig. 21 — Scrolling Marquee, Enable/Off/Remote Contact Switch, and Emergency On/Off Switch Locations
LEGEND
CB — Circuit Breaker SW — Switch
The 38AP units can be connected to the CCN if desired. The communication bus wiring is a shielded, 3-conductor cable with drain wire and is supplied and installed in the field. See Table 5. The system elements are connected to the communi­cation bus in a daisy chain arrangement. The positive pin of each system element communication connector must be wired to the positive pins of the system elements on either side of it. This is also required for the negative and signal ground pins of each system element. Wiring connections for CCN should be made at LVT. Consult the CCN Contractor’s Manual for fur­ther information.
NOTE: Conductors and drain wire must be 20 AWG (Ameri­can Wire Gage) minimum stranded, tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of –20 C to 60 C is required. Wire manufactured by Alpha (2413 or 5463), American (A22503), Belden (8772), or Columbia (02525) meets the above mentioned requirements.
It is important when connecting to a CCN communication bus that a color coding scheme be used for the entire network to simplify the installation. It is recommended that red be used for the signal positive, black for the signal negative, and white for the signal ground. Use a similar scheme for cables contain­ing different colored wires.
At each system element, the shields of its communication bus cables must be tied together. If the communication bus is entirely within one building, the resulting continuous shield must be connected to a ground at one point only. If the commu­nication bus cable exits from one building and enters another, the shields must be connected to grounds at the lightning suppressor in each building where the cable enters or exits the building (one point per building only). To connect the unit to the network:
1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white
3. Connect the red wire to (+) terminal on LVT of the plug,
(ground), and black (–) conductors. (Substitute appropri­ate colors for different colored cables.)
the white wire to COM terminal, and the black wire to the (–) terminal.
20
4. The RJ14 CCN connector on LVT can also be used, but is only intended for temporary connection (for example, a laptop computer running Service Tool).
IMPORTANT: A shorted CCN bus cable will prevent some routines from running and may prevent the unit from start­ing. If abnormal conditions occur, unplug the connector. If conditions return to normal, check the CCN connector and cable. Run new cable if necessary. A short in one section of the bus can cause problems with all system elements on the bus.
Table 5 — CCN Communication Bus Wiring
MANUFACTURER
Alpha 1895 American A21451 A48301 Belden 8205 884421 Columbia D6451 Manhattan M13402 M64430 Quabik 6130
Regular Wiring Plenum Wiring
PART N O.
OPERATING DATA
Sensors — The electronic control uses 3 to 7 thermistors to
sense temperatures for controlling unit operation. See Table 3. These sensors are outlined below. Three different thermistor curves are utilized depending on the thermistor and the config­uration of the input. The three different types are 5 kat 77 F (25 C), 10 kat 77 F (25 C), and 86 k at 77 F (25 C). See Thermistors section on page 49 for additional information.
RETURN AIR TEMPERATURE (RAT) ACCESSORY (Part No. 33ZCSENSAT) — A return air temperature sensor is required for unit sizes 040-100 and all units equipped with the digital scroll option. The sensor is field installed in the indoor unit and wired to the LVT of the unit to measure the air temperature entering the evaporator coil. The sensor should be located directly in front of the evaporator coil after an outside air intake.
The RAT sensor consists of a thermistor encased within a stainless steel probe. See Fig. 22. The sensor probe is 6 in. nominal length with 114 in. of unshielded, 2-conductor 18 AWG twisted-pair cables. The sensor temperature range is –40 to 245 F with a nominal resistance of 10,000 ohms at 77 F. The sensor has with an accuracy of ±0.36 F.
Fig. 22 — 33ZCSENSAT Sensor
.39
.08
FOAM GASKET
.40'' O.D.
.250 ±.01 Dia
5.5 ±.5
PLENUM RATED CABLE 114'' ±6
3.00
3.90
.175 DIA x .600
NOTE: All dimensions shown in inches.
2
3
45
61
SW1
SEN
BRN (GND)
BLU (SPT)
RED(+)
WHT(GND)
BLK(-)
CCN COM
SENSOR WIRING
Fig. 23 — Space Temperature Sensor
Typical Wiring (33ZCT55SPT)
2
3
45
61
SW1
SEN
SET
Cool Warm
BRN (GND) BLU (SPT)
RED(+)
WHT(GND)
BLK(-)
CCN COM
SENSOR WIRING
JUMPER TERMINALS AS SHOWN
BLK (T56)
Fig. 24 — Space Temperature Sensor
Typical Wiring (33ZCT56SPT)
SUPPLY AIR TEMPERATURE (SAT) ACCESSORY (33ZCSENSAT) — A supply air temperature sensor is required for unit sizes 040-100 and all units equipped with the digital scroll option. The SAT sensor consists of a thermistor encased within a stainless steel probe. See Fig. 22. The SAT sensor probe is 6 in. nominal length with 114 in. of unshielded, 2-conductor 18 AWG twisted-pair cables. The sensor tempera­ture range is –40 to 245 F with a nominal resistance of 10,000 ohms at 77 F. The sensor has an accuracy of ±0.36 F.
NOTE: The sensor must be mounted in the discharge of the unit, downstream of the cooling coil and before any heating coil or heat exchanger if reheat is utilized. Be sure the probe tip does not come in contact with any of the unit surfaces.
COMPRESSOR RETURN GAS TEMPERATURE SEN­SOR (RGT) — These sensors are factory installed in a fric­tion fit well located in the suction line of each circuit. They are a 5 k thermistor connected to the main base board.
OUTDOOR-AIR TEMPERATURE SENSOR (OAT) — This sensor is factory installed on a bracket which is inserted through the base pan of the unit on the unit sizes 025-060 and mounted to the back of the control box on the unit sizes 070-
100. This sensor is a 5 k thermistor connected to the main base board.
DISCHARGE TEMPERATURE THERMISTOR (DTT) — This sensor is only used on units with a digital compressor. The sensor is mounted on the discharge line close to the discharge of the digital compressor. It attaches to the dis­charge line using a spring clip and protects the system from high discharge gas temperature when the digital compressor is used. This sensor is a 86 k thermistor connected to the AUX board.
SPACE TEMPERATURE SENSOR (SPT) — The space temperature sensors are used to measure the interior temperature of a building. The following three types of SPT sensors are available:
• Space temperature sensor (33ZCT55SPT) with timed override button (see Fig. 23)
• Space temperature sensor (33ZCT56SPT) with timed override button and set point adjustment (see Fig. 24)
• Space temperature sensor (33ZCT59SPT) with occu­pancy override button, set point adjustment slidebar, and LCD (liquid crystal display) display
The sensor should be mounted approximately 5 ft from the floor in an area representing the average temperature in the space. Allow at least 4 ft between the sensor and any corner. Mount the sensor at least 2 ft from an open doorway.
To connect the space temperature sensor (Fig. 25):
1. Use a 20 gage wire to connect the sensor to the controller. The wire is suitable for distances of up to 500 ft. Use a three-conductor shielded cable for the sensor and set point adjustment connections. The standard CCN communication cable may be used. If the set point adjustment (slidebar) is not required, then an unshielded, 18 or 20 gage, two-conductor, twisted pair cable may be used. Connect one wire of the twisted pair to one SEN terminal and connect the other wire to the other SEN ter­minal located under the cover of the space temperature sensor.
2. Connect the other ends of the wires to terminals 21 and 22 on LVT located in the unit control box.
3. Connect the T56 set point adjustment between the SET terminal and LVT terminal 23.
21
Units on the CCN can be monitored from the space using
Fig. 25 — Typical SPT Wiring
T-55 SPACE SENSOR
CCN+
CCN GND
CCN-
TO CCN COMM 1 BUS (PLUG) AT UNIT
1
2
3
4
5
6
Fig. 26 — CCN Communications Bus Wiring to
Optimal Space Sensor RJ11 Connector
J6
6
7
RED
BLK
RED
RED
BLK
BLK
BLK
RED
BLK
RED
SENSOR 1 SENSOR 2 SENSOR 3 SENSOR 4
J6
6
7
RED
BLK
RED
BLK
SENSOR 2
SENSOR 1
RED
RED
BLK
SENSOR 3
SENSOR 4
BLK
BLK
RED
RED
RED
BLK
BLK
SENSOR 8
SENSOR 9
SENSOR 5
RED
BLK
SENSOR 6
SENSOR 7
BLK
RED
SPACE TEMPERATURE AVERAGING — 4 SENSOR APPLICATION
Fig. 27 — Space Temperature Averaging
LEGEND
Factory Wiring
Field Wiring
SPACE TEMPERATURE AVERAGING — 9 SENSOR APPLICATION
the RJ11 connector provided with the space sensor, if desired. To wire the RJ11 connector into the CCN (Fig. 26):
IMPORTANT: The cable selected for the RJ11 connector wiring MUST be identical to the CCN communication bus wire used for the entire network. Refer to Table 5 for acceptable wiring.
1. Cut the CCN wire and strip ends of the red (+), white (ground), and black (–) conductors. (If another wire color scheme is used, strip ends of appropriate wires.)
2. Insert and secure the red (+) wire to terminal 5 of the space temperature sensor terminal block.
3. Insert and secure the white (ground) wire to terminal 4 of the space temperature sensor.
4. Insert and secure the black (–) wire to terminal 2 of the space temperature sensor.
5. Connect the other end of the communication bus cable to the remainder of the CCN communication bus.
NOTE: See Fig. 27 for space temperature averaging.
SEN
SPT
SENSOR
SEN
SET
LVT
21
22
23
22
Fan Status Input — A proof-of-fan operation is recom-
CEBD430351-0396-01C
TEST 1
CEPL130351-01
PWR
TEST 2
J1
J2
J4 J3
J5
J6
J7
LEN
STATUS
RED LED - STATUS
GREEN LED ­LEN (LOCAL EQUIPMENT NETWORK)
ADDRESS DIP SWITCH
Fig. 28 — Energy Management Module
mended and needs to be field installed in the indoor unit. Sev­eral different types of switches can be utilized, such as a differ­ential pressure switch located across the indoor fan or auxiliary contacts on an indoor fan contactor.
Thermostat Input — A two-stage thermostat can be
used for constant volume applications to provide Y1 and Y2 cooling inputs.
Pressure Transducer Inputs — Each refrigerant cir-
cuit is equipped with a suction and discharge pressure trans­ducer. The suction pressure transducers have a yellow body with a pressure range of -6.7 to 420 psig while the discharge transducers have a red body with a pressure range of 14.5 to 667 psig. These inputs connect to the MBB (main base board) and are used to monitor the status of the unit and to ensure the unit operates within the compressor envelope. The transducers are used to protect the compressor from operating at too low or too high of a pressure condition. In some cases, the unit may not be able to run at full capacity. The MBB will automatically reduce the capacity of a circuit as needed to maintain specified maximum/minimum operating pressures.
Energy Management Module (Fig. 28) — The
energy management module (EMM) is a factory-installed op­tion (FIOP) or field-installed accessory used for the following types of temperature reset, demand limit, and capacity control features:
• 4 to 20 mA temperature reset
• 4 to 20 mA cooling set point
• 4 to 20 mA desired capacity set point
• 4 to 20 mA demand limit
• Discrete inputs for 2-step demand limit (requires field­supplied dry contacts capable of handling a 24 vac, 50 mA load)
• Discrete inputs for units with dual thermostats
NOTE: A field-supplied 4 to 20 mA signal generator is re­quired for use with the EMM.
See VAV Supply Air Temperature Reset and Demand Limit
sections on pages 29 and 31 for further details.
CAUTION
Care should be taken when interfacing with other manufac­turer’s control systems due to possible power supply differences, full wave bridge versus half wave rectification. The two different power supplies cannot be mixed. ComfortLink™ controls use half wave rectification. A signal isolation device should be utilized if a full wave bridge signal generating device is used.
Control — When mechanical cooling is required, the MBB
has the capability to control the unit capacity by staging multi­ple scroll compressors and controlling the digital scroll com­pressor operation. The control also checks on various other op­eration parameters in the unit to make sure that safeties are not exceeded and the compressors are reliably operated.
The ComfortLink™ control system offers two basic control approaches to mechanical cooling; constant volume operation for 2 stages of cooling or VAV operation for multiple stages of cooling. In addition to these methods of control, the ComfortLink control offers the ability to run multiple stages of cooling for either a space temperature sensor or thermostat control by controlling the unit to either a low or high cool set point. The control type Configuration OPT2 C.TYP de­termines the selection of the type of cooling control as well as the method for selecting a cooling mode.
SETTING UP THE SYSTEM Machine Control Type (
— The most important cooling control configuration is located under Configuration OPT2. This configuration defines the method and control source responsible for selecting a cooling mode. The configuration also determines the method by which compressors are staged. Control types are:
C.TYP = 1 (VAV-RAT) configuration refers to standard
VAV operation.
Configuration OPT2 C.TYP)
23
Fig. 29 — Space Temperature vs.
Space Temperature Set Point
A48-7701
C.TYP = 3 (TSTAT-MULTI) configuration will force the MBB to monitor the thermostat inputs to make a determination of mode. Unlike traditional 2-stage ther­mostat control, the unit is allowed to use multiple stages of cooling control and perform VAV style operation. The control will be able to call out a low set point or a high set point to maintain supply air temperature. (Required for 025-030 units with digital scroll option and 040-100 units with two-stage thermostat control.)
C.TYP = 4 (TSTAT-2STG) configuration will force the MBB to monitor the thermostat inputs to make a deter­mination of mode.
C.TYP = 5 (SPT-MULTI) configuration will force the MBB to monitor a space temperature sensor to make a determination of mode. Unlike traditional 2-stage space temperature control, the unit is allowed to use multiple stages of cooling control and perform VAV style opera­tion. The control will be able to call out a low set point or a high set point to maintain supply air temperature.
C.TYP = 7 (% CAPACITY) configuration will force the MBB to monitor the 4-20 cooling demand CL.MA input and translate this into desired % capacity for the unit.
C.TYP = 9 (VAV-SETPOINT) configuration will force the MBB to monitor the 4-20 cooling demand CL.MA input. This value will be translated into a desired leav­ing-air set point ranging from 40 to 80 F. The control will translate the input linearly with 4 ma equal to 40 F set point and 20 mA equal to 80 F set point.
Unit Capacity Control Based on Unit Type
— The MBB uses several set points to control capacity depending on unit type. The set points are located in the set point area of the dis­play SetPoints COOL. Refer to Table 6 and the following descriptions.
Table 6 — Unit Capacity Control
ITEM DESCRIPTION RANGE UNITS DEFAULT CSP1 Cooling Set Point 1 40-80 F 65 CSP2 Cooling Set Point 2 40-80 F 55
SPS.P Space Temperature Cooling Set
Poin t
L.C.ON Demand Level Low Cool On –1-2 ^F 1.5
H.C.ON Demand Level (+) High Cool On 0.5-20.0 ^F 0.5
L.C.OF Demand Level (–) Low Cool Off 0.5-2 ^F 1
65-80 F 74
C.TYP = 1 (VAV-RAT) is a capacity control routine that controls compressor capacity to supply air temperature. The MBB will attempt to control leaving temperature to the control point (CTPT) which equals CSP1 plus any reset which is being applied.
C.TYP = 3 (TSTAT-MULTI) configuration will force the MBB to monitor the thermostat inputs to make a deter­mination of control point (CTPT). The control will vary the control point based on Y1 and Y2 inputs. When Y1 is closed CSP1 will be used and when Y2 is closed CSP2 will be used as the supply air temperature set point. CSP1 should be greater than CSP2.
C.TYP = 4 (TSTAT-2STG) configuration will force the MBB to monitor the thermostat inputs to make a deter­mination of mode and capacity. If Y1 input is closed, 50% of the unit capacity will be energized and if Y2 is closed, 100% of the unit capacity will be energized.
NOTE: This is not a preferred method of control for units with greater than 2 stages of capacity
C.TYP = 5 (SPT-MULTI) configuration will force the MBB to monitor the thermostat inputs to determine mode and cooling set point as the unit is controlled by space temperature vs space temperature set point SPS.P. Unlike traditional 2-stage thermostat control, the unit is allowed to use multiple stages of cooling control and per­form VAV style operation. The control will be able to call out a low set point (CSP1) or high set point (CSP2) for
supply air depending on space temperature vs space temperature set point. The control uses SPS.P, LC.ON,
HC.ON, and LC.OF to determine the leaving set point. LC.ON and HC.ON are added to the space temperature
set point to determine when cooling mode will begin and when CSP1 and CSP2 will be used for leaving set point.
Based on LC.OF, the control point transitions between CSP1 and CSP2. LC.OF is used to calculate the space tem­perature at which control point is raised based on space tem­perature vs space temperature set point (SPS.P) plus
LC.ON minus LC.OF. The control point transition from CSP2 to CSP1 occurs when space temperature is below LC.OF divided by 2.
For example (see Fig. 29):
Given: SPS.P = 72 F, LC.ON = 1, HC.ON = 3,
LC.OF = 2 F, CSP1 = 60 F, and CSP2 = 55 F
If space temperature equals 73 F (72+1) (Low Cool)
cooling will begin and control set point equals 60 F
(CSP1).
If space temperature is greater than 76 F (72+1+3 = 76)
(High Cool), control point set point would equal 55 F
(CSP2).
If space temperature falls below 72 F (73-2/2) (Low
Cool minus LC.OF/2), control point transitions back to
60 F CSP1 if space continues to fall below 71 F (73-2)
(Low Cool minus LC.OF), the unit is shut off.
76 F
H.C.ON
73 F
L.C.ON
L.C. OF
Cooling Setpoint
L.C. OF/2
Hi Cool End 72 F72 F
Lo Cool End 71 F
C.TYP = 7 (% CAPACITY) configuration will force the MBB to monitor the input 4-20 cooling demand CL.MA and translate this into desired % capacity for the unit. The control will attempt to match the desired capacity insuring the unit operates the compressor within com­pressor safeties and timeguards. (Requires the EMM option or accessory.)
C.TYP = 9 (VAV-SETPOINT) configuration will force the MBB to operate as a VAV unit and control capacity to meet supply air temperature. The control point is devel­oped from the 4-20 cooling demand CL.MA input value. The 4 to 20 mA input will be translated into a desired control point ranging from 40 to 80 F. The control will translate the input linearly with 4 mA equal to 40 F set point and 20 mA equal to 80 F set point. (Requires the EMM option or accessory.)
Capacity Control Logic when Control is Controlling to Sup­ply Temperature — The control system cycles compressors, hot gas bypass and the digital compressor to maintain the sup­ply temperature at or close to the control point of the unit. The SAT and RAT sensors are used by the main base board (MBB) to determine the temperature drop across the evaporator and are used in determining the optimum time to add or subtract ca­pacity stages. The CSP set points can be automatically reset by
24
Hi Cool Start
Lo Cool Start
the return temperature, space, or outdoor-air temperature reset features. It can also be reset from an external 4 to 20 mA signal (requires energy management module factory-installed option or field-installed accessory).
The control has an automatic lead-lag feature built in which determines the wear factor (combination of starts and run hours) for each compressor. If all compressors are off and less than 30 minutes has elapsed since the last compressor was turned off, the wear factor is used to determine which compres­sor to start next. As additional stages of compression are re­quired, the processor control will add them. If a circuit is to be stopped, the compressor with the lowest wear factor will be
The capacity control algorithm runs every 30 seconds. The algorithm attempts to maintain the control point at the desired set point. Each time it runs, the control reads the entering and leaving temperatures. The control determines the rate at which conditions are changing and calculates 2 variables based on these conditions. Next, a capacity ratio is calculated using the 2 variables to determine whether or not to make any changes to the current stages of capacity. This ratio value ranges from –100 to +100%. If the next stage of capacity is a compressor, the control starts (stops) a compressor when the ratio reaches +100% (-100%). A delay of 90 seconds occurs after each ca­pacity step change. Refer to Table 8.
shut off first. See Table 7 for compressor size information and Table 8 for compressor loading sequence.
Table 7 — Compressor Size Information
UNIT SIZE
38APS025 11 11 38APD025 11 11 38APS027 13 13 38APD027 13 13 38APS030 15 15 38APD030 15 15 38APS040 13 13 13 38APD040 10 10 9 9 38APS050 15 15 15 38APD050 12 12 13 13 38APD060 13 13 15 15 38APD070 15 15 11 11 11 38APD080 15 15 15 15 15 38APD090 13 13 13 15 15 15 38APD100 15 15 15 15 15 15
Compressor A1 Compressor A2 Compressor A3 Compressor B1 Compressor B2 Compressor B3
CIRCUIT A (Nominal hp) CIRCUIT B (Nominal hp)
Table 8 — Part Load Data Percent
38AP UNIT SIZE
38APS025-030
38APD025-030
38APS040,050
38APD040
38APD050,060
38APD070
38APD080
38APD090
38APD100
NOTES:
1. These capacity steps may vary due to different capacity staging sequences.
CONTROL
STEPS
150A1—— 2 100 A1,A2
1 50A150B1 2 100 A1, B1 100 A1,B1
133A1—— 267A1,A2—— 3 100 A1,A2,A3
127A123B1 2 50 A1,B1 50 A1,B1 3 77A1,A2,B1 73A1,B1,B2 4 100 A1,A2,B1,B2 100 A1,A2,B1,B2
123A127B1 2 50 A1,B1 50 A1,B1 3 73A1,A2,B1 77A1,B1,B2 4 100 A1,A2,B1,B2 100 A1,A2,B1,B2
1 15A115B1 2 42 A1,B1 42 A1,B1 3 57A1,A2,B157A1,B1,B2 4 85 A1,A2,B1,B2 85 A1,A2,B1,B2 5 100 A1,A2,B1,B2,B3 100 A1,A2,B1,B2,B3
1 20A120B1 2 40 A1,B1 40 A1,B1 3 60A1,A2,B160A1,B1,B2 4 80 A1,A2,B1,B2 80 A1,A2,B1,B2 5 100 A1,A2,B1,B2,B3 100 A1,A2,B1,B2,B3
1 15A118B1 2 32 A1,B1 32 A1,B1 3 48A1,A2,B151A1,B1,B2 4 66 A1,A2,B1,B2 66 A1,A2,B1,B2 5 82 A1,A2,A3,B1,B2,B3 85 A1,A2,B1,B2,B3 6 100 A1,A2,A3,B1,B2,B3 100 A1,A2,A3,B1,B2,B3
1 17A117B1 2 33 A1,B1 33 A1,B1 3 50A1,A2,B150A1,B1,B2 4 67 A1,A2,B1,B2 67 A1,A2,B1,B2 5 83A1,A2,A3,B1,B283A1,A2,B1,B2,B3 6 100 A1,A2,A3,B1,B2,B3 100 A1,A2,A3,B1,B2,B3
% Displacement Compressor % Displacement Compressor
LOADING SEQUENCE A LOADING SEQUENCE B
2. When unit is equiped with digital scroll option, sequence A is always used.
25
MINUTES LEFT FOR START — This value is displayed

only in the network display tables (using Service Tool, ComfortVIEW™ or ComfortWORKS
®
software) and represents the amount of time to elapse before the unit will start its initialization routine. This value can be zero without the machine running in many situations. This can include being unoccupied, ENABLE/OFF/REMOTE CONTACT switch in the OFF position, CCN not allowing unit to start, Demand Limit in effect, no call for cooling due to no load, and alarm or alert conditions present. If the machine should be running and none of the above are true, a minimum off time (DELY, see below) may be in effect. The machine should start normally once the time limit has expired.
MINUTES OFF TIME (Configuration OPT2
DELY) — This user-configurable time period is used by the control to determine how long unit operation is delayed after power is applied/restored to the unit. Typically, this time period is configured when multiple machines are located on a single site. For example, this gives the user the ability to pre­vent all the units from restarting at once after a power failure. A value of zero for this variable does not mean that the unit should be running. NOTE: If the unit has digital scroll or hot gas bypass, circuit A is always lead.
LEAD/LAG DETERMINATION — This is a configurable choice and is factory set to be automatic for all units. The value can be changed to Circuit A or Circuit B leading as desired. Set at automatic, the control will sum the current number of logged circuit starts and one-quarter of the current operating hours for each circuit. The circuit with the lowest sum is started first. Changes to which circuit is the lead circuit and which is the lag are also made when total machine capacity is at 100% or when there is a change in the direction of capacity (increase or decrease) and each circuit’s capacity is equal.
CAPACITY CONTROL OVERRIDES — The following over­rides will modify the normal operation of the routine.
Deadband Multiplier
— The user configurable deadband mul-
tiplier (Configuration SLCT Z.GN) has a default value of
1.0. The range is from 1.0 to 4.0. When set to other than 1.0, this factor is applied to the capacity Load/Unload Factor. The larger this value is set, the longer the control will delay between adding or removing stages of capacity.
First Stage Override
— If the current capacity stage is zero, the control will modify the routine with a 1.2 factor on adding the first stage to reduce cycling. This factor is also applied when the control is attempting to remove the last stage of capacity.
Slow Change Override
— This control prevents the capacity
stages from being changed when the supply temperature is
Table 9 — Fan Stages
38AP UNIT SIZE
025-030
040,050
060
070
080
090,100
* Fan Stage 1 on unit size 070 is used only when ambient temperature is less than 32 F.
CIRCUIT A STAGES/COMMON FAN STAGES CIRCUIT B FAN STAGES
Fan Stage Contactor Energized Fans Operating Fan Stage Contactor Energized Fans Operating
Stage 1 Stage 2
Stage 1 Stage 2 Stage 3
Stage 1 Stage 2 Stage 3 Stage 4
Stage 1* Stage 2 Stage 3
Stage 1 Stage 2
Stage 1 Stage 2 Stage 3 Stage 4 Stage 5 Stage 6
FC1
FC1,2
FC1 FC2
FC1,2
FC1 FC2
FC1,2
FC1,2,3
FC2,4
FC1
FC1,3
FC1
FC1,3
FC4
FC1 FC4,1 FC4,3 FC1,3
FC4,1,3
OFM1
OFM1,2
OFM3
OFM1,2
OFM1,2,3
OFM3
OFM1,2
OFM1,2,3
OFM1,2,3,4
OFM1,2
OFM3
OFM3,4
OFM5
OFM5,6,(2)
OFM3 OFM5
OFM3,5 OFM3,(2),4,6 OFM5,(2),4,6
OFM3,5,(2),4,6
close to the set point (within an adjustable deadband) and mov­ing toward the set point.
Ramp Loading
— The ramp loading control (Configuration
SLCT CRMP) limits the rate of change of supply temper­ature. If the unit is in a Cooling mode and configured for Ramp Loading, the control makes 2 comparisons before deciding to change stages of capacity. The control calculates a temperature difference between the control point and supply temperature. If the difference is greater than 4° F (2.2° C) and the rate of change (°F or °C per minute) is more than the configured Cool­ing Ramp Loading value (CRMP), the control does not allow any changes to the current stage of capacity.
Minimum Load Control
— If equipped, the minimum load control valve is energized only when one compressor on the circuit is running and the unit is unloading.
Low Saturated Suction Protection
— The control will try to prevent shutting a circuit down due to low saturated suction conditions by removing stages of capacity. See Alerts section.
Head Pressure Control — The main base board
(MBB) controls the condenser fans to maintain the lowest condensing temperature possible, and thus the highest unit efficiency. The MBB uses the saturated condensing tempera­ture input from the discharge pressure transducer and outside air temperature sensor to control the fans. If OAT is greater than 70 F before a circuit is starting, then all condenser fan stages will be energized. A fan stage is increased based on SCT. When the highest SCT of both circuits is greater than fan on set point, then an additional stage of fan will be added to the current fan stage. Fan On Set Point (F. O N ) equals Head Set Point ON (115 F) except after a fan stage increase when Head Set Point is increased by Fan Stage Delta (10 F). A fan stage is decreased when the SCTs of both circuits are less than fan off set point for two minutes. Fan Off Set Point (F. O F F ) equals Head Set Point OFF (–72 F). Table 9 shows the number of fan stages, contactors energized and the fans that are on during the fan stage. Unit sizes 025 to 060 have common fan control. Unit sizes 070 to 100 have some fans that are common and some that are controlled individually. Figure 30 shows the location of each fan and compressor within the unit.
MOTORMASTER tion, the first stage of fans is equipped with the Motormaster V head pressure controller option or accessory. For units with common fans, the control will control the Head Pressure Set­point (–10 F) and the highest SCT to try to maintain it at 100 F. Unit sizes 070 to 100 have one Motormaster V for each circuit and the control tries to maintain SCT at 100 F for the circuit. The controller is given an ON command with the first stage of fan and adjusts fan speed.
Stage 1* Stage 2 Stage 3
Stage 1 Stage 2 Stage 3
Stage 1 Stage 2 Stage 3 Stage 4 Stage 5 Stage 6
®
V OPTION — For low-ambient opera-
———
———
———
FC1,3
FC2
FC2,4
FC4
FC3,4
FC2,3,4
FC4
FC2 FC4,2 FC4,3 FC2,3
FC4,2,3
OFM3,4
OFM1
OFM1,2
OFM3
OFM3,2,(6)
OFM3,1,2,(6)
OFM3 OFM1
OFM3,1 OFM3,2,4,(6) OFM1,2,4,(6)
OFM3,1,2,4,(6)
26
Outdoor Fan Layout – Top View
Sizes 025-030 Sizes 040, 050 Sizes 060, 070
CONTROL BOX
CONTROL BOX
OFM1
OFM2 OFM2
OFM3
OFM1
CONTROL BOX
OFM3
OFM4
OFM2
OFM1
Size 080 Sizes 090, 100
CONTROL BOX
OFM2
OFM3
OFM5
OFM6
OFM1
CONTROL BOX
OFM4
OFM5
OFM6
OFM2
OFM3
OFM1
Compressor Layout Dual Circuit – Top View
Sizes 025-030 Sizes 040-060 Sizes 070, 080
CONTROL BOX
1
B1
CONTROL BOX
B1
B2
1
2
CONTROL BOX
B1
B2
2
1
B3
Sizes 090, 100
CONTROL BOX
B1
B2
B3
3
2
1
Sizes 025-030 Sizes 040, 050
CONTROL BOX
CONTROL BOX
Compressor Layout Single Circuit – Top View
1
2
1
2
3
Fig. 30 — Compressor and Fan Location
A
A
A
A
A
A
A
A
A
A
A
A
A
27
Service Test — Both main power and control circuit
ENTER
ENTER
ESCAPE


power must be on.
The Service Test function should be used to verify proper operation of condenser fan(s), compressors, minimum load valve solenoid (if installed), liquid line solenoid valve (if installed), and remote alarm relay. To use the Service Test mode, the Enable/Off/Remote Contact switch must be in the OFF position. Use the display keys and Service Test Mode and Sub-Mode Directory table in Appendix A to enter the mode and display TEST. Press twice so that OFF flashes. Enter the password if required. Use either arrow key to change the TEST value to the ON position and press . Place the Enable/Off/Remote Contact switch in the ENABLE posi­tion. The Service Test mode is now enabled. Press and the down key to enter the OUTS, COMPA or COMPB sub-mode.
Test the condenser fans, liquid line solenoid and alarm re­lay by changing the item values from OFF to ON. These dis­crete outputs are then turned off if there is no keypad activity for 10 minutes. When testing the digital output the display can be changed from 1 to 15 by using either the up or down arrow; the number represents the cycle rate out of a 15 second duty cy­cle that the output will be energized. If the cycle is set for 7, the output will be energized 7 seconds out of every 15 seconds. Test the compressor and minimum load valve solenoid (if in­stalled) outputs in a similar manner. The minimum load valve solenoids will be turned off if there is no keypad activity for 10 minutes. Compressors will stay on until they are turned off by the operator. The Service Test mode will remain enabled for as long as there is one or more compressors running. All safe­ties are monitored during this test and they will turn a compres­sor, circuit or the machine off if required. Any other mode or sub-mode can be accessed, viewed, or changed during the TEST mode. The STAT item (Run/Status VIEW) will dis­play "0" as long as the Service mode is enabled. The TEST sub-mode value must be changed back to OFF before the unit can be switched to Enable or Remote contact for normal operation.
Operating Modes
RAMP LOAD LIMITED (MD05) — Ramp load (pull­down) limiting is in effect. In this mode, the rate at which sup­ply fluid temperature is dropped is limited to a predetermined value to prevent compressor overloading. See Cooling Ramp Loading (Configuration SLCT CRMP). The pull-down limit can be modified, if desired, to any rate from 0.2 to 2° F (0.1 to 1° C) per minute.
TIMED OVERRIDE IN EFFECT (MD06) — Timed over­ride is in effect. This is a 1 to 4 hour temporary override of the programmed schedule, forcing unit to Occupied mode. Over­ride can be implemented with unit under Local (Enable) or CCN (Carrier Comfort Network ter each use.
SLOW CHANGE OVERRIDE (MD09) — Slow change override is in effect. The supply fluid temperature is close to and moving towards the control point.
MINIMUM OFF TIME ACTIVE (MD10) — Unit is being held off by Minutes Off Time (Configuration OPT2 DELY).
TEMPERATURE RESET (MD14) — Temperature reset is in effect. In this mode, unit is using temperature reset to adjust supply fluid set point upward and is currently controlling to the modified set point. The set point can be modified based on re­turn fluid, outdoor-air-temperature, space temperature, or 4 to 20 mA signal.
DEMAND LIMITED (MD15) — Demand limit is in effect. This indicates that the capacity of the unit is being limited by
®
) control. Override expires af-
demand limit control option. Because of this limitation, the unit may not be able to produce the desired supply fluid tempera­ture. Demand limit can be controlled by switch inputs or a 4 to 20 mA signal.
LOW TEMPERATURE COOLING (MD17) — Unit is in Cooling mode and the rate of change of the supply fluid is neg­ative and decreasing faster than -0.5° F per minute. Error be­tween supply fluid and control point exceeds fixed amount. Control will automatically unload the unit if necessary.
HIGH TEMPERATURE COOLING (MD18) — Unit is in Cooling mode and the rate of change of the supply fluid is pos­itive and increasing. Error between supply fluid and control point exceeds fixed amount. Control will automatically load the unit if necessary to better match the increasing load.
TIME GUARD ACTIVE (MDTG) — Compressor time guard is active, preventing the compressor from starting.
HIGH SCT CIRCUIT A (MD21) — Unit is in a Cooling mode and the saturated condensing temperature (SCT) is great­er than the calculated maximum limit. No additional stages of capacity will be added. Unit capacity may be reduced if SCT continues to rise to avoid high-pressure switch trips by reduc­ing condensing temperature.
HIGH SCT CIRCUIT B (MD22) — Unit is in a Cooling mode and the saturated condensing temperature (SCT) is great­er than the calculated maximum limit. No additional stages of capacity will be added. Unit capacity may be reduced if SCT continues to rise to avoid high-pressure switch trips by reduc­ing condensing temperature.
MINIMUM COMP ON TIME (MD23) — Cooling load may be satisfied, however control continues to operate com­pressor to ensure proper oil return. This may be an indication of oversized application, low fluid flow rate or low loop volume.
LOW SOUND MODE (MD25) — Not applicable.
Operation of Machine Based on Control Method —
the configuration of the control method (Configuration OPT2 CTRL). With the control method set to 0, simply switching the Enable/Off/Remote Contact switch to the Enable or Remote Contact position (external con­tacts closed) will put the unit in an occupied state. The control mode (Operating Modes MODE) will be 1 (OFF LOCAL) when the switch is Off and will be 5 (ON LOCAL) when in the Enable position or Remote Contact position with external con­tacts closed.
Two other control methods are available for Machine On/
Off control: OCCUPANCY SCHEDULE (CTRL=2) — The main base
board will use the operating schedules as defined under the Time Clock mode in the scrolling marquee display. These schedules are identical. The schedule number must be set to 1 for local schedule.
The schedule number can be set anywhere from 65 to 99 for operation under a CCN global schedule. The Enable/Off/ Remote Contact must be in the Enable or Remote Contact posi­tion. The control mode (Operating Modes MODE) will be 1 when the switch is Off. The control mode will be 3 when the Enable/Off/Remote Contact switch input is On and the time of day is during an unoccupied period. Similarly, the control mode will be 7 when the time of day is during an occupied period.
CCN SCHEDULE (CTRL=3) — An external CCN device controls the On/Off state of the machine. This CCN device forces the variable 'CHIL_S_S' between Start/Stop to control the unit. The control mode (Operating Modes MODE) will be 1 when the switch is Off. The control mode will be 2 when the Enable/Off/Remote Contact switch input is On and the
Machine On/Off control is determined by
28
Loading...
+ 64 hidden pages