Carrier 38AKS013-024 User Manual

Air-Cooled Condensing Units
Installation, Start-Up and
Service Instructions
38AKS013-024
50/60 Hz
CONTENTS
Page
SAFETY CONSIDERATIONS ...................1
INSTALLATION .............................1-12
Step 1 — Complete Pre-Installation
Checks ....................................1
Step 3 — Complete Refrigerant Piping
Connections ...............................8
Step 4 — Install Accessories ................10
Step 5 — Complete Electrical
Connections ..............................10
System Check ..............................12
Leak Test and Dehydration ..................12
Turn On Crankcase Heater ...................12
Preliminary Charge ..........................12
START-UP ................................13-16
Preliminary Checks .........................13
Preliminary Oil Charge ......................13
Adjust Refrigerant Charge ...................13
Check Compressor Oil Level ................13
OPERATING SEQUENCE ....................17
Cooling .....................................17
Winter Start Control .........................17
SERVICE ..................................17-19
Capacity Control ............................17
Head Pressure Control ......................17
Time GuardT II Circuit .......................17
Winter Start Control .........................18
Crankcase Heater ...........................18
Compressor Protection ......................18
High-Pressure Switches .....................18
Low-Pressure Switches .....................18
Outdoor Fans ...............................18
TROUBLESHOOTING ......................20,21
START-UP CHECKLIST ................CL-1,CL-2
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equip­ment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated struc­tures, etc.).
Only trained, qualified installers and service mechanics
should install, start-up, and service this equipment (Fig. 1).
Untrained personnel can perform basic maintenance func­tions such as cleaning coils. All other operations should be performed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
Follow allsafetycodes.Wear safetyglassesandworkgloves. Keep quenching cloth and fire extinguisher nearby when braz­ing. Use care in handling, rigging, and setting bulky equip­ment.
ELECTRIC SHOCK HAZARD Separate power sources (main and control
power circuits) are used for these units. Be sure both main and control power circuits are disconnected before servicing.
INSTALLATION
Step 1 — Complete Pre-Installation Checks
UNCRATE UNIT — Remove unit packaging except for the top skid assembly, which should be left in place until after the unit is rigged into its final location.
INSPECT SHIPMENT — File claim with shipping com­pany if shipment is damaged or incomplete.
CONSIDER SYSTEM REQUIREMENTS
• Consult local building codes and National Electrical Code
(NEC, U.S.A.) for special installation requirements.
• Allow sufficient space for airflow clearance, wiring,
refrigerant piping, and servicing unit. See Fig. 1. See Fig. 2 for unit component locations.
• Locate unit so that outdoor coil (condenser) airflow is un-
restricted on all sides and above.
• Unit may be mounted on a level pad directly on the base
channels or mounted on raised pads at support points. See Tables 1A-1D for unit operating weights. See T able2forweightdistributionbasedonrecommendedsup­port points.
NOTE: If vibration isolators are required for a particular installation, use the data in Table 2 to make the proper selection.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 3a 2a
PC 111 Catalog No. 563-701 Printed in U.S.A. Form 38AKS-3SI Pg 1 9-98 Replaces: 38AKS-2SI
NOTE: Service areas — Allow 3 ft (914 mm) on both sides and 2 ft (610 mm) on both ends of unit for servicing.
2
Fig. 1 — Dimensions
1324567
12 91011
LEGEND
1—No. 1 Fan 5—No. 2 Fan 9—Compressor 2—High-Pressure Switch 6—Terminal Block 1 (Unit Power) 10 — Low-Pressure Switch 3—Circuit Breaker — Control Circuit 7—Terminal Block 2 (Control Power) 11 — Hot Gas Bypass Piping Stub ( 4—Circuit Breakers — Power Circuits 8—Wraparound Coil 12 — Muffler
Fig. 2 — Component Locations (Typical)
8
3
⁄8-in. ODM)
3
Table 1A — Physical Data (English, 60 Hz)
UNIT 38AKS 013 014 016 024 OPERATING WEIGHT (lb)
With Aluminum-Fin Coil 732 779 789 900 With Copper-Fin Coil 825 919 929 1040
REFRIGERANT* R-22
Shipping Charge (lb) 2.1 3.1 3.1 3.1 Operating Charge, Typical (lb)† 22 23 23 28
COMPRESSOR Reciprocating, Semi-Hermetic
Model 06DD824 06DD328 06DD537 06EA250 No. Cylinders 6664 Speed (rpm) 1750 Capacity Steps (%)
Accessory 33**,66,100 33**,66,100 33**,66,100 Standard 66,100 66,100 66,100 50,100
Crankcase Heater Watts 125 Unloader Setting (psig)
Load 70±1
Unload 60±2 OIL CHARGE (pt) 10 10 10 15.5 CONDENSER FANS Axial Flow, Direct Drive
Quantity...Diameter (in.) 2...26 Nominal Hp Nominal Airflow (cfm, total) 11,000 Speed (rpm) 1,075 Watts (total) 1,460
CONDENSER COIL Copper Tubes, Aluminum Fins
Rows...Fins/in. 2...15 3...15 3...15 3...15 Total Face Area (sq ft) 29.2 29.2 29.2 29.2 Storage Capacity (lb)†† 27.2 40.3 39.8 39.8
CONTROLS
Pressurestat (psig)
High Pressure
Cutout 395±10 Cut-in 295±20
Low Pressure
Cutout 27±4 Cut-in 67+7
FAN CYCLING CONTROLS
No 2 Fan:
Close (psig) 255±10
Open (psig) 160±10 PRESSURE RELIEF Fusible Plug
Location Compressor Compressor Compressor Liquid Line Temperature (F) 200 200 200 210
PIPING CONNECTIONS (in. ODM)
Suction 1 Liquid Hot Gas Stub
*Unit is factory supplied with holding charge only.
†With 25 ft of interconnecting piping. Operating charge is approximate for maximum system capacity.
**Indicates capacity step (%) with electric unloader accessory.
††Storage capacity is measured at liquid saturated temperatures of 125 F for 38AKS013, 123 F for
38AKS014, and 130 F for 38AKS016 and 024.
1
8
13⁄
8
1
2
13⁄
5
8
3
8
8
15⁄
8
4
Table 1B — Physical Data (SI, 60 Hz)
UNIT 38AKS 013 014 016 024 OPERATING WEIGHT (kg)
With Aluminum-Fin Coil 332 353 358 408 With Copper-Fin Coil 374 417 421 472
REFRIGERANT* R-22
Shipping Charge (kg) 0.95 1.40 1.40 1.40 Operating Charge, Typical (kg)† 10.0 10.4 10.4 12.7
COMPRESSOR Reciprocating, Semi-Hermetic
Model 06DD824 06DD328 06DD537 06EA250 No. Cylinders 6664 Speed (r/s) 29.2 Capacity Steps
Accessory 33**,66,100 33**,66,100 33**,66,100 Standard 66,100 66,100 66,100 50,100
Crankcase Heater Watts 125 Unloader Setting (kPa)
Load 483 ± 6.9
Unload 414 ± 13.8 OIL CHARGE (L) 4.73 4.73 4.73 7.33 CONDENSER FANS Axial Flow, Direct Drive
Quantity...Diameter (mm) 2...660 Nominal kW 0.37 Nominal Airflow (L/s, total) 5566 Speed (r/s) 17.9 Watts (total) 1460
CONDENSER COIL Copper Tubes, Aluminum Fins
Rows...Fins/m 2...590 3...590 3...590 3...590 Total Face Area (sq m) 2.71 2.71 2.71 2.71 Storage Capacity (kg)†† 12.3 18.3 18.1 18.1
CONTROLS
Pressurestat (kPa)
High Pressure
Cutout 2724 ± 69 Cut-in 2034 ± 138
Low Pressure
Cutout 186 ± 28 Cut-in 462 + 48
FAN CYCLING CONTROLS
No 2 Fan:
Close (kPa) 1758 ± 69
Open (kPa) 1103±69 PRESSURE RELIEF Fusible Plug
Location Compressor Compressor Compressor Liquid Line Temperature (C) 93.3 93.3 93.3 98.9
PIPING CONNECTIONS (in. ODM)
Suction 1 Liquid Hot Gas Stub
*Unit is factory supplied with holding charge only.
†With 7.6mof interconnecting piping. Operatingchargeisapproximate for maximum systemcapacity.
**Indicates capacity step (%) with electric unloader accessory.
††Storage capacity is measured at liquid saturated temperatures of 51.7 C for 38AKS013, 50.6 C for
38AKS014, and 54.4 C for 38AKS016 and 024.
1
8
13⁄
8
5
8
3
8
13⁄
8
15⁄
8
5
Table 1C — Physical Data (English, 50 Hz)
UNIT 38AKS 013 014 016 024 OPERATING WEIGHT (lb)
With Aluminum-Fin Coil 732 779 789 900 With Copper-Fin Coil 825 919 929 1040
REFRIGERANT* R-22
Shipping Charge (lb) 2.1 3.1 3.1 3.1 Operating Charge, Typical (lb)† 22 23 23 28
COMPRESSOR Reciprocating, Semi-Hermetic
Model 06DD824 06DD328 06DD537 06EA250 No. Cylinders 6664 Speed (rpm) 1450 Capacity Steps
Accessory 33**,66,100 33**,66,100 33**,66,100 Standard 66,100 66,100 66,100 50,100
Crankcase Heater Watts 125 Unloader Setting (psig)
Load 70±1
Unload 60±2 OIL CHARGE (pt) 10 10 10 15.5 CONDENSER FANS Axial Flow, Direct Drive
Quantity...Diameter (in.) 2...26 Nominal Hp Nominal Airflow (cfm, total) 9210 Speed (rpm) 900 Watts (total) 1050
CONDENSER COIL Copper Tubes, Aluminum Fins
Rows...Fins/in. 2...15 3...15 3...15 3...15 Total Face Area (sq ft) 29.2 29.2 29.2 29.2 Storage Capacity (lb)†† 27.2 40.3 39.8 39.8
CONTROLS
Pressurestat (psig)
High Pressure
Cutout 395±10 Cut-in 295±20
Low Pressure
Cutout 27±4 Cut-in 67+7
FAN CYCLING CONTROLS
No 2 Fan:
Close (psig) 255±10
Open (psig) 160±10 PRESSURE RELIEF Fusible Plug
Location Compressor Compressor Compressor Liquid Line Temperature (F) 200 200 200 210
PIPING CONNECTIONS (in. ODM)
Suction 1 Liquid Hot Gas Stub
*Unit is factory supplied with holding charge only.
†With 25 ft of interconnecting piping. Operating charge is approximate for maximum system capacity.
**Indicates capacity step (%) with electric unloader accessory.
††Storage capacity is measured at liquid saturated temperatures of 125 F for 38AKS013, 123 F for
38AKS014, and 130 F for 38AKS016 and 024.
1
8
13⁄
8
1
2
13⁄
5
8
3
8
8
15⁄
8
6
Table 1D — Physical Data (SI, 50 Hz)
UNIT 38AKS 013 014 016 024 OPERATING WEIGHT (kg)
With Aluminum-Fin Coil 332 353 358 408 With Copper-Fin Coil 374 417 421 472
REFRIGERANT* R-22
Shipping Charge (kg) 0.95 1.40 1.40 1.40 Operating Charge, Typical (kg)† 10.0 10.4 10.4 12.7
COMPRESSOR Reciprocating, Semi-Hermetic
Model 06DD824 06DD328 06DD537 06EA250 No. Cylinders 6664 Speed (r/s) 24.2 Capacity Steps
Accessory 33**,66,100 33**,66,100 33**,66,100 Standard 66,100 66,100 66,100 50,100
Crankcase Heater Watts 125 Unloader Setting (kPa)
Load 483 ± 6.9
Unload 414 ± 13.8 OIL CHARGE (L) 4.73 4.73 4.73 7.33 CONDENSER FANS Axial Flow, Direct Drive
Quantity...Diameter (mm) 2...660 Nominal kW 0.37 Nominal Airflow (L/s, total) 4660 Speed (r/s) 15.0 Watts (total) 1050
CONDENSER COIL Copper Tubes, Aluminum Fins
Rows...Fins/m 2...590 3...590 3...590 3...590 Total Face Area (sq m) 2.71 2.71 2.71 2.71 Storage Capacity (kg)†† 12.3 18.3 18.1 18.1
CONTROLS
Pressurestat (kPa)
High Pressure
Cutout 2724 ± 69 Cut-in 2034 ± 138
Low Pressure
Cutout 186 ± 28 Cut-in 462 + 48
FAN CYCLING CONTROLS
No 2 Fan:
Close (kPa) 1758 ± 69
Open (kPa) 1103±69 PRESSURE RELIEF Fusible Plug
Location Compressor Compressor Compressor Liquid Line Temperature (C) 93.3 93.3 93.3 98.9
PIPING CONNECTIONS (in. ODM)
Suction 1 Liquid Hot Gas Stub
*Unit is factory supplied with holding charge only.
†With 7.6mof interconnecting piping. Operatingchargeisapproximate for maximum systemcapacity.
**Indicates capacity step (%) with electric unloader accessory.
††Storage capacity is measured at liquid saturated temperatures of 51.7 C for 38AKS013, 50.6 C for
38AKS014, and 54.4 C for 38AKS016 and 024.
1
8
13⁄
8
5
8
3
8
13⁄
8
15⁄
8
7
Table2—Weight Distribution
WEIGHT
UNIT
38AKS
013 732 332 94 43 93 42 93 42 149 68 151 68 152 69 013C 825 374 119 54 116 53 115 52 157 71 159 72 159 72 014 779 353 95 43 94 43 94 43 164 74 166 75 166 75 014C 919 417 131 59 129 59 128 58 176 80 177 80 178 81 016 789 358 95 43 95 43 96 44 167 76 168 76 168 76 016C 929 421 131 59 130 59 130 59 178 81 180 82 180 82 024 900 408 119 54 114 52 113 51 179 81 185 84 190 86 024C 1040 472 155 70 150 68 146 66 191 87 196 89 202 92
Total
Operating
lb kg lb kg lb kg lb kg lb kg lb kg lb kg
ABCDEF
Support Point
Step 2 — Rig and Mount the Unit
Be sure unit panels are securely in place prior to rigging.
RIGGING — These units are designed for overhead rigging only. For this purpose, the transverse base channels extend beyond the sides of the unit, with holes provided in the end plates to attach cables or hooks. Rig with top skid packaging assembly in place to prevent unit damage by the rigging cable. As further protection for the coil faces, plywood sheets can be placed against the sides of the unit, behind the cables. Run the cables to acentral suspension point so that the angle from the horizontal is not less than 45 degrees. Raise and set the unit down carefully.
If it is necessary to roll the unit into position, mount the unit on longitudinal rails, using a minimum of 3 rollers. Apply force to the rails, not the unit. If the unit is to be skid­ded into position, place it on a large pad and drag it by the pad. Do not apply any force to the unit.
Raise from above to lift unit from the rails or pad when unit is in final position.
COMPRESSOR MOUNTING — As shipped, the compres­sor is held tightly in place by self-locking bolts. Before start-
ing unit, loosen self-locking bolts until the snubber washer can be moved sideways with finger pressure. Do not remove shipping bolts. See Fig. 3.
Step 3 Complete Refrigerant Piping Connections
IMPORTANT:A refrigerant receiver is not provided with the unit. Do not install a receiver.
SIZE REFRIGERANT LINES — Consider the length of pip­ing required between outdoor unit and indoor unit (evapo­rator), the amount of liquid lift, and compressor oil return. See Tables 3-5B and also refer to Part 3 of Carrier System Design Manual and E20-IIt software for design details and line sizing. Refer to indoor unit installation instructions for additional information.
NOTE: Use the piping data in Tables3-5Bas a general guide only. For more precise calculations, refer to Carrier System Design manual or E20-II software.
Condensing units with multiple-step unloading may require double suction risers to assure proper oil return at minimum load operating condition. See Tables 4A-5B and Fig. 4. Reduction of evaporator coil surface should be ana­lyzed to provide sufficient refrigerant velocity to return oil to the compressor. Liquid line solenoid valves may be used in certain situations to accomplish this. Hot gas bypass, if used, should be introduced before the evaporator.
Note that refrigerant suction piping should be insulated.
Table 3 — Liquid Line Data
MAXIMUM
ALLOWABLE
LIQUID LIFT
UNIT
38AKS
013 52 (15.8)
014 67 (20.4)
016 82 (25.0
024 87 (26.5) 86 (26)
*Inlet and outlet. NOTE: Data shown is for units operating at 45 F (7.2 C) saturated
suction and 95 F (35 C) entering air.
ft (m)
60 Hz 50 Hz
Maximum Allowable
Pressure
Drop
psig (kPa)
7 (48.3) 2 (1.1)
LIQUID LINE
Maximum Allowable
Temp.
Loss F (C)
Filter Drier
and
Sight Glass
Flare Conn.*
in. (mm)
5
⁄8(15.88)
Fig. 3 — Compressor Mounting
8
Loading...
+ 16 hidden pages