Installing, starting up and servicing air conditioning
equipment can be hazardous due to system pressures,
electrical components and equipment location (roofs, ele
vated structures, etc.)
Only trained, qualified installers and service mechanics
should install, start-up and service this equipment (Fig. 1).
Untrained personnel can perform basic maintenance
functions such as cleaning coils. All other operations should
be performed by trained service personnel.
When working on the equipment, observe precautions in
the literature and on tags, stickers and labels attached to the
equipment.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Keep quenching cloth and fire extinguisher nearby when
brazing.
• Use care in handling, rigging and setting bulky equipment.
• See Table 1 for Physical Data.
ELECTRIC SHOCK HAZARD
Cm
tr
Open all remote disconnects before
servicing this equipment.
BEFORE INSTALLATION
Rigging — Preferred method is with spreader bars
from above the unit. Use 2-in. (50 mm) OD pipe or
hooks in lifting holes. Rig with 4 cables and spreader
bars. All panels must be in place when rigging. See
rigging label on unit for details concerning shipping
weights, distance between lifting holes, center of
gravity and spreader bar dimensions. See Fig. 2.
If overhead rigging is not possible, place chiller on
skid or pad for rolling or dragging. When rolling, use
minimum 3 rollers. When dragging, pull the pad. Do
not apply force to the unit When in final position, raise
from above to lift unit off pad.
A CAUTION
All panels must be in place when rigging. Do not fork
units if no skid is supplied. If unit has skid, truck from
sides only.
Book 1
Tab I 3a
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.
PC111
Catalog No 563-915
Printed in U S AForm 38AK-1SIM
Pgi
11-89
Replaces: New
3/4-IN (19mm) NOTCHES
IN END OR SPREADERS
Fig. 1 - Model 38AK (024 shown)
Fig. 2 — Rigging with Spreader Bars (Field Supplied)
Rows ... Fins/in. (Fin Spacing mm)
Total Face Area, sq ft (m‘)
*See Service, Oil Charge, for Carrier-approved oil
Paid - pounds per sq in differential
4 1450(24 2)
2
14(66)
76
58
—
—
28(12 7)
10,600 (5,000)
3... 17 (149)
235(218)39.2(364)
NOTE: Circuit breaker in main power circuit and discharge gas thermostat in control circuit
028034044
Reciprocating, Semi-Hermetic
1 06E92651 06E92751 06E9299
Suction Pressure Unloader(s)
Unloader Settings (psig)
76
58
Unloader Settings (psig)
78
60
305(13.8)
2 30 (762)3... 30 (762)
15,700 (7,400)23,700 (11,200)
950 (15 8)
2 19(134)
c
180
See Note
6 1450(24 2)
3
19(9)
7676
5858
78
60
435(197)65(295)
3. 17(149)
2
044
1 06E9299
60
78
60
584(543)
Placing Unit — There must be 4 ft (1220 mm) for service
and for unrestricted airflow on all sides of unit, and a
minimum of 8 ft (2440 mm) clear air space above unit. For
multiple units, allow 8 ft separation between units for
airflow and service.
Mounting Unit — When unit is in proper location, use of
mounting holes in base rails is recommended for securing
unit to supporting structure, or for mounting unit on
vibration isolators if required. Fasteners for mounting unit
are field supplied. Be sure to mount unit level to ensure
proper oil return to compressors.
Compressor Mounting — As shipped, compressor is
held down by 4 bolts. After unit is installed loosen each bolt
until the snubber washer can be moved with finger pressure.
See Fig. 3.
Single Pumpout Control — All units are factory wired
to operate on single pumpout control. A factory-supplied
liquid line solenoid valve must be installed in the liquid line
ahead of the indoor coil. See Fig. 5. Wires from solenoid
valve must be in conduit, and a ground wire must be
provided to comply with codes.
A WARNING
Failure to properly install liquid line solenoid at the
indoor unit as described, without Carrier author
ization, may VOID warranty.
If unit is used with a chiller, wiring modifications may be
required.
Filter Drier And Moisture Indicator — Every unit
should have a filter drier and a sight glass (moisture
indicator) field installed. Select the filter drier for maximum
unit Capacity and minimum pressure drop. Figure 5 shows
recommended locations of filter drier(s) and sight glass.
Complete the refrigerant piping from the evaporator to the
condenser before opening the liquid and suction lines at the
condensing unit. One filter drier may be installed at location
A in Fig. 5, or 2 filter driers may be installed at locations B.
INSTALLATION
Refrigerant Piping Connections — Line sizes depend
on length of piping required between condensing unit and
evaporator. See Table 2. It is important to consider liquid
lift and compressor oil return. Refer to Part 3 of Carrier
System Design Manual for line sizing information, and
Fig. 4 for recommended piping details.
NOTES:
1 Suction line is connected to coil on same side as the entering air.
2 For coils having only one section, use upper section piping; for coiis
having 2 sections, use upper and middle section piping
3 Lower section is first on and last off.
4 For more complete piping information, refer to Carrier System
Design Manual, Part 3
Fig. 4 — Suction Line Piping to Unit
with 3 Section Coil Split
FACTORY SUPPLIED
SOLENOID VALVE
FIELD SUPPLIED
CAPACITY CONTROL
Fig. 5 — Liquid Line Solenoid Valve,
Filter Drier(s) and Sight Glass Locations
Receiver — No receiver is provided with the unit; it is
recommended that one not be used.
Piping Procedure — Do not remove run-around pipe
from suction and liquid line stubs until piping connections are
ready to be made. Pass nitrogen or other inert gas through
piping while brazing, to prevent formation of copper oxide.
Install field-supplied thermostatic expansion valve in
liquid line ahead of each evaporator section. For 2-step
cooling, the fleld-supplkd solenoid used must be wired to be
opened by control from a 2-step thermostat
For example: 2 solenoids may be used with 3 TXVs —one
of the solenoids serving a liquid line feeding 2 of the TXVs.
Table 2 — Refrigerant Piping Sizes
SINGLE SUCTION RISERS
MODEL
38AK
0245/81-5/8
0287/81-5/8
034
044
L-Liquid Line S-Suction Line
* IMPORTANT — Requires a double suction riser, see below:
NOTE: Liquid and suction iine sizes are OD (in)
(a) - SUCTION RISER WITHOUT TRAP
(b) - SUCTION RISER WITH TRAP
(^- SUCTION LINE TO CONDENSING UNIT
7/8
7/8
16-25
L
SLS
2-1 /8
2-1/87/82-1/8
LENGTH OF INTERCONNECTING PIPING (FT)
26-50
7/81-5/8
7/8
7/8
2-1 /87/8
2-1/87/8
DOUBLE SUCTION RISERS
51-75
L
7/8
1-1/8
UNIT 38AK
02486
028
03467
04476
76-100
S
2-1/87/8
2-1/87/8
2-1/8
*
L
1-1 /8
1-1/8
2-1/8
2-1/8
MAXIMUM LIQUID LIFT
60 Hz50 Hz
Ft
M
2672
76
23
20
23
S
*
*
101-200
LS
7/82-1/8
7/82-1/8
1-1/8
1-1/8
Ft
21
6620
60
18
6620
*
*
M
MODEL
38AK
034
044
NOTE: A, B, C dimensions relate to reference diagram
2-1/8
51-7576-100
A
BC
1-5/8
SUCTION PIPING AT EVAPORATOR AND TXV
BULB LOCATION (See Fig. 5)
The purpose of these recommendations is to achieve good
mixing of the refrigerant leaving the evaporator suction
header for proper sensing by the TXV bulb.
1. A minimum of two 90° elbows must be installed
upstream of the expansion valve bulb location.
2. The TXV sensing bulb should be located on a vertical
riser where possible. If a horizontal location is neces
sary, secure the bulb at approximately the 4 o’clock
position.
3. Size the suction line from the evaporator through the
riser for high velocity. Enter the suction pipe sizing charts
in the Carrier System Design Manual at design tons and
equivalent length (for 2 degree F loss). If reading falls
between 2 sizes on chart, choose the smaller pipe size.
LENGTH OF INTERCONNECTING PIPING (FT)
ABCA
2-5/8
1-5/8
1-5/8
2-1/8
2-1/8
2-5/8
2-5/8
1-5/8
1-5/8
Suction piping for the high velocity section should be
selected for about 0.5 degree F friction loss. If a 2 degree
F loss is allowed for the entire suction line, 1.5 degree F
is left for the balance of the suction line and it should be
sized on that basis. Check that the high-velocity sizing is
adequate for oil return up the riser.
If an oil return connection at the bottom of this
suction header is supplied with an evaporator, this
connection must be teed-in ahead of first mixing elbow.
When the compressor is below the evaporator, the riser
at the evaporator does not have to extend as high as the
top level. After a 15-diameter riser has been provided,
the suction line may elbow down immediately.
SAFETY RELIEF — A fusible plug is located on unit
liquid line before the liquid valve.
101-200
B
2-1/8
2-1/8
C
2-5/8
2-5/8
Power Supply — Electrical characteristics of available
power supply must agree with unit nameplate rating. Supply
voltage must be within limits shown in Table 3.
IMPORTANT: Operating unit on improper supply
voltage, or with excessive phase imbalance, constitutes
abuse and may affect Carrier warranty. See Unbal
anced 3-Phase Supply Voltage, page 6.
Power Wiring — All power wiring must comply with
applicable local and national codes. Install field-supplied
branch circuit fused disconnect(s) per NEC (National Electri
cal Code) of a type that can be locked OFF or OPEN.
Disconnect(s) must be within sight from and readily acces
sible from unit in compliance with NEC Article 440-14.
Table 3 — Electrical Data
60 HERTZ
MODEL
OfiAtr
024
028
034
044
500
200
600
100
500
200
600
100
500
200
600
100
500
200
600
100
Volts
3 Ph, 60 Hz
208/230
38034241851 180194.93461913.9
460414508
575
208/230
380
460
575518632
208/230
380
460
575518
230
380
460
575
SuDolied*
Min.Max.(Fuse)
187
518632
187254
342
414
187
342
414
187254
342
414
518
UNITCOMPRESSOR
MCA
25492.1150348.6
46.9
42.970
124.6200
41864.7110
50860 7100226.1
52.580
254
145 5250
41872.5125
508687110
632
418
50891 0150
63281.5125282.8
54.990
2030350
111 1
50 HERTZ
MODEL
38AK
024
034
044300
800230
300346
900
800
028300346
900400
800230
300
900
800230
900
Volts
3 Ph, 50 Hz
400
230
346
400
346
400
Supplied*
Min.Max.
198254
311
342
198254109175348.476.9342
311
342
1982541202
311
342
198254
311
342
UNIT
MCA
38050.580
40049.38017403471731.0
38064.9100
400605100226.043622330
88.1125
38076.1125
40068.5
1506250
380112.6175
40090.8150351 0
GENERAL WIRING NOTES
1. A crankcase heater is wired in the control circuit so it is
always operable as long as power supply disconnect is
on, even if any safety device is open or unit stop-start
switch is off. It is protected by a 5-amp circuit breaker in
control power.
2. The power circuit field supply disconnect should never be
open except when unit is being serviced or is to be down for a
prolonged period When operation is resumed crankcase
heater should be energtedfor 24 hours before start-up. If unit
is to be shut down for a prolonged period it is recommended
that the suction arid discharge valves be closed to prevent an
excessive accumulation of refrigerant in the compressor oil
3. Power entry is at one end only.
MOCP
ICFRLALRAFLA (ea)
68
801748
175
MOCP
(Fuse)
123.4
452.289.84466.2
250.945.52473.9
167.436.51643.4
512.2106.55066.2
283.952.6280
256.1502533.1
179.438.51763.4
702.4
389879.538239
351 265.43453.1
ICFRLALRAFLA (ea)
256.460.3
2044
34 7
28.91203.4
43.622331
147 5690
57.12763.43
COMPRESSOR
333200
263.444.9
200
110
372.4
2984
256050.02533.0
5578105.1
408.879.5
859366
539294
65.4
FAN MOTORS!
345
3.6
1731 8
3.9
623
FAN MOTORS!
250
259
545
400
34530
6.42
442
642
4.42
6.4
4.42
6.43
4.4
Qty
2
2
2
2
2
2
2
2
2
2
2
2
3
3
Qty
2
2
2
2
3
3
FLA — Full Load Amps
ICF — Maximum Instantaneous Current Flow during starting (the
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps (complies with National Electrical
MOCP — Maximum Overcurrent Protection
RLA — Rated Load Amps
* Units are suitable for use on electrical systems where voltage
supplied to unit terminals is not below or above listed minimum and
maximum limits
t All fans are protected by a single circuit breaker.
point in the starting sequence where the sum of the LRAfor
the starting compressor, plus the total RLA for all running
compressors, plus the total FLA for all running fan motors
is maximum).
Code [NEC], Section 430-24)
4. Maximum field wire sizes allowed by lugs on terminal
block are:
350 MCM for models 38AK028 (208/230-3-60),
38AK034 (208/230-3-60, 230-3-50), and
38AK044 (208/230-3-60, 230-3-50)
2/0 AWG for all other models.
5. Terminals for field power supply are suitable for
copper, copper-clad aluminum or aluminum conduc
tors. Insulation must be rated 167 F (75 C) minimum.
UNBALANCED 3-PHASE SUPPLY VOLTAGE —
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the following formula to
determine the % voltage imbalance:
% Voltage Imbalance
= 100 X
max voltage deviation from average voltage
average voltage
I ^
CONDENSER FANS — The fans must rotate counter
clockwise when viewed from above. If necessary, correct
direction of fan rotation by interchanging any 2 power
input wires at disconnect switch. Affix crankcase heater
decal (located in installer’s packet) to unit disconnect switch.
FIELD CONNECTIONS
1. Main Power — Bring wires from the fused disconnect
switch through hole in bottom rail of unit to control
box (Fig. 6, 7, 8) and connect terminals 1111, [12
on line side of terminal block TBl (see Fig. 9).
13
To comply with NEC Article 440-14, the disconnect
must be located within sight from and readily acces
sible from unit.
■ 2. 24-v Control Power — Units have single point power
connections. Control circuit is directly connected inter
nally to unit. Maximum 24-v control circuit is 3 amps.
NOTE: For wire runs up to 50 ft. use no. 18 AWG
insulated wire (35 C min.). For 50 to 75 ft., use no. 16
AWG insulated wire (35 C min.). For over 75 ft. use 14
AWG insulated wire (35 C min.).
3. Control Circuit Interlock — An airflow switch may be
installed in the indoor air handler to prevent unit from
running when indoor air is not flowing. This switch (no.
HR81JE001) is available from Service Parts Center, or
equivalent can be field supplied. This should be electri
cally interlocked in the control circuit, between term
inals I 1 I and I 6 I (for flow switch) on TB2. See Fig.
9 for field wiring. This is in the 115-v circuit. Wires must
be run in conduit with ground wire.
4. Transformer Connections — See unit wiring label dia
gram, notes 1 and 2, located behind compressor com
partment end access door.
Maximum deviation is 4 volts. Determine % voltage
imbalance:
% Voltage Imbalance = 100 x —^ = 1.7%
This amount of phase imbalance is satisfactory as it is
below the maximum allowable 2%.
IMPORTANT: Contact your local electric utility
company immediately if the supply voltage phase
imbalance is more than 2%.
243 + 236 + 238 = 239 volts
239
IMPORTANT: Ensure power to the crankcase
heater is always on (except when servicing the unit).
If circuit breakers inside unit shut down the com
pressor and condenser fans, crankcase heater
remains on.
NOTES:
1
THERE MUST BE [1220 mm] 4 ft FOR SERVICE AND
FOR UNRESTRICTED AIRFLOW ON ALL SIDES OF UNIT.
THERE MUST BE MINIMUM C2440 mml 8 ft CLEAR
AIR SPACE ABOVE UNIT.
THE APPROXIMATE OPERATING WEIGHT OF THE UNIT IS:
3.
60 HZ
UNITWT LBS
38AK024
1456661
38AK024C 1580
NOTE: "C" INDICATES COPPER COIL.
2 4
WT KG
717
50 HZ
UNITWT LBSWT KG
38AK024
38AK024C 1580
60 Hz
024
024C
50 Hz
024
024c
1456661
717
APPROX. OPER. WT. (LB.)
AT SUPPORT POINTS
12
411
501
448533
587
433
626
462
245
273326
486358
518
HINGED ACCESS DOOR•
CONTROL BOX
34
299
382
TOT.
1456
1580
1864
1988
[63.5-92.1] 2 1/2'-:
FIELD MAIN POWERSU
- A
' II
HINGED ACCES
[1315]
4'-3 3/4'
[61]
2 7/16
[19.1]
3/4' dia;
MOUNTING HOLES
(TYP 4 PLACES)
[63.5-92.1]
2 1/2'-3 5/8'DIA.
FIELD POWER
ENTRY 8 LIFTING
[22.2]
7/8' DIA.
FIELD CONTROL
POWER ENTRY
Fig. 6 — Dimensioi
ECimON
PAM No. 2
5/8' DIA.
LY
[22.2] 7/8' DIA.
FIELD CONTROL CIRCUIT WIRING
TOP VIEW
1 Drawing, 38AK024
10'-7 13/16'
SIDE VIEW
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.