Carrier 38AK024-044 User Manual

38AK024-044
HEATING A COOLING
Air-Cooled Condensing Units
Installation, Start-Up and Service Instructions
50- and 60-Hertz Air-Cooled Packages

CONTENTS

Page

SAFETY CONSIDERATIONS

BEFORE INSTALLATION
Rigging ...........................................................................l
Placing Unit .................................................................. 3
Mounting Unit Compressor Mounting
INSTALLATION
Refrigerant Piping Connections ..................................3
Single Pumpout Control
Filter Drier and Moisture Indicator...............................3
Receiver .........................................................................3
Piping Procedure ...........................................................3
Power Supply .................................................................5
Power Wiring..................................................................5
START-UP ................................................................11-16
Initial Check...................................................................11
Leak Test and Dehydration Preliminary Charge
Start Unit .......................................................................11
...............................................................
..........................................................
......................................................
.............................................
.................................................
...............................................
.........................................
1-3
3
3-10
3
11 11
1
3
Charge System .........................................................11
Operation ..................................................................11
Timer Functions ........................................................16
Sequence of Operation.............................................16
Complete Unit Stoppage SERVICE
Access for Servicing ................................................17
Fan Adjustment ........................................................18
Oil Charge
Liquid Shutoff/Charging Valve
Capacity Control .......................................................18
Oil Pressure Safety Switch (OPS) Compressor Protection
High-Pressure Switch ..............................................19
Low-Pressure Switch ...............................................19
Winter Start Control
Head Pressure Control
TROUBLESHOOTING .20
..............................................................
.................................................................
.........................................
...............................
............................................
.................................................
............................................
17-19
..........................
Page
16
18 18
19 19
19
19
SAFETY CONSIDERATIONS
Installing, starting up and servicing air conditioning equipment can be hazardous due to system pressures, electrical components and equipment location (roofs, ele vated structures, etc.)
Only trained, qualified installers and service mechanics should install, start-up and service this equipment (Fig. 1).
Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should be performed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers and labels attached to the equipment.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Keep quenching cloth and fire extinguisher nearby when
brazing.
• Use care in handling, rigging and setting bulky equipment.
• See Table 1 for Physical Data.
ELECTRIC SHOCK HAZARD
Cm
tr
Open all remote disconnects before servicing this equipment.
BEFORE INSTALLATION
Rigging — Preferred method is with spreader bars
from above the unit. Use 2-in. (50 mm) OD pipe or hooks in lifting holes. Rig with 4 cables and spreader bars. All panels must be in place when rigging. See rigging label on unit for details concerning shipping weights, distance between lifting holes, center of gravity and spreader bar dimensions. See Fig. 2.
If overhead rigging is not possible, place chiller on
skid or pad for rolling or dragging. When rolling, use
minimum 3 rollers. When dragging, pull the pad. Do
not apply force to the unit When in final position, raise
from above to lift unit off pad.

A CAUTION

All panels must be in place when rigging. Do not fork units if no skid is supplied. If unit has skid, truck from sides only.
Book 1 Tab I 3a
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.
PC111
Catalog No 563-915
Printed in U S A Form 38AK-1SIM
Pgi
11-89
Replaces: New
3/4-IN (19mm) NOTCHES IN END OR SPREADERS
Fig. 1 - Model 38AK (024 shown)
Fig. 2 — Rigging with Spreader Bars (Field Supplied)
Table 1A — Physical Data — 60 Hertz
UNIT 38AK
COMPRESSOR Reciprocating Semi-Hermetic
No. ...Type 1 06E4250 1 06E9265
No. Cyls (ea) ...Speed, Rpm (r/s) 4 1750(29) Capacity Steps Oil Charge*, Pt (L) 14(66)
Oil Pressure Switch Setting (psid)
Crankcase Heater (watts) Protection See Note Capacity Control No. 1
Load Unload
No. 2
Load Unload
REFRIGERANT CHG, R-22
Approximate lb (kg)
CONDENSER FANS, Type Propeller Type, Direct Driven
No. ...Diameter, in. (mm)
Total Airflow, Cfm (L/s) 10,600 (5,000) 15,700 (7,400) 23,700(11,200) Speed, Rpm (r/s) 1140(19)
CONDENSER COIL, Type Horizontal, Plate Fin
Rows...Fins/in. (Fin Spacing mm) Total Face Area, sq ft (m‘)
024 028 034
1 06E9275
2
6 1750(29)
3
19(9)
180
Suction Pressure Unloader(s)
Unloader Settings (psig)
76 58
28 (12 7) 305(138)
3 ... 17 (1 49) 2 19(134)
235(218) 39 2(364) 584(543)
76 58
Unloader Settings (psig)
78 60
2 30(762)
76 76 58 58
78 78 60
435(19.7) 65(295)
3 ...30 (762)
3 17(149)
Table IB — Physical Data — 50 Hertz
UNIT 38AK 024 COMPRESSOR
No.... Type 1 06E4250
No. Cyls (ea)... Speed, Rpm (r/s) Capacity Steps Oil Charge*, Pt (L)
Oil Pressure Switch Setting (psid) Crankcase Heater (watts) Protection Capacity Control No. 1
Load Unload
No. 2
Load Unload
REFRIGERANT CHG., R-22
Approximate lb (kg)
CONDENSER FANS, Type Propeller Type, Direct Driven
No.... Diameter, in. (mm)
Total Airflow, dm (L/s) Speed, Rpm (r/s)
CONDENSER COIL, Type Horizontal, Plate Fin
Rows ... Fins/in. (Fin Spacing mm) Total Face Area, sq ft (m‘)
*See Service, Oil Charge, for Carrier-approved oil
Paid - pounds per sq in differential
4 1450(24 2)
2
14(66)
76 58
28(12 7)
10,600 (5,000)
3... 17 (149) 235(218) 39.2(364)
NOTE: Circuit breaker in main power circuit and discharge gas thermostat in control circuit
028 034 044
Reciprocating, Semi-Hermetic
1 06E9265 1 06E9275 1 06E9299
Suction Pressure Unloader(s)
Unloader Settings (psig) 76 58
Unloader Settings (psig) 78 60
305(13.8)
2 30 (762) 3... 30 (762)
15,700 (7,400) 23,700 (11,200)
950 (15 8)
2 19(134)
c
180
See Note
6 1450(24 2)
3
19(9)
76 76 58 58
78 60
435(197) 65(295)
3. 17(149)
2
044
1 06E9299
60
78 60
584(543)
Placing Unit — There must be 4 ft (1220 mm) for service and for unrestricted airflow on all sides of unit, and a minimum of 8 ft (2440 mm) clear air space above unit. For multiple units, allow 8 ft separation between units for airflow and service.
Mounting Unit — When unit is in proper location, use of
mounting holes in base rails is recommended for securing unit to supporting structure, or for mounting unit on vibration isolators if required. Fasteners for mounting unit are field supplied. Be sure to mount unit level to ensure proper oil return to compressors.
Compressor Mounting — As shipped, compressor is held down by 4 bolts. After unit is installed loosen each bolt until the snubber washer can be moved with finger pressure. See Fig. 3.
Single Pumpout Control — All units are factory wired to operate on single pumpout control. A factory-supplied liquid line solenoid valve must be installed in the liquid line ahead of the indoor coil. See Fig. 5. Wires from solenoid valve must be in conduit, and a ground wire must be provided to comply with codes.

A WARNING

Failure to properly install liquid line solenoid at the indoor unit as described, without Carrier author ization, may VOID warranty.
If unit is used with a chiller, wiring modifications may be
required.
Filter Drier And Moisture Indicator — Every unit should have a filter drier and a sight glass (moisture
indicator) field installed. Select the filter drier for maximum unit Capacity and minimum pressure drop. Figure 5 shows recommended locations of filter drier(s) and sight glass. Complete the refrigerant piping from the evaporator to the condenser before opening the liquid and suction lines at the condensing unit. One filter drier may be installed at location A in Fig. 5, or 2 filter driers may be installed at locations B.

INSTALLATION

Refrigerant Piping Connections — Line sizes depend
on length of piping required between condensing unit and evaporator. See Table 2. It is important to consider liquid lift and compressor oil return. Refer to Part 3 of Carrier System Design Manual for line sizing information, and Fig. 4 for recommended piping details.
NOTES: 1 Suction line is connected to coil on same side as the entering air. 2 For coils having only one section, use upper section piping; for coiis
having 2 sections, use upper and middle section piping 3 Lower section is first on and last off. 4 For more complete piping information, refer to Carrier System
Design Manual, Part 3
Fig. 4 — Suction Line Piping to Unit
with 3 Section Coil Split
FACTORY SUPPLIED SOLENOID VALVE
FIELD SUPPLIED
CAPACITY CONTROL
Fig. 5 — Liquid Line Solenoid Valve,
Filter Drier(s) and Sight Glass Locations
Receiver — No receiver is provided with the unit; it is
recommended that one not be used.
Piping Procedure — Do not remove run-around pipe
from suction and liquid line stubs until piping connections are
ready to be made. Pass nitrogen or other inert gas through
piping while brazing, to prevent formation of copper oxide.
Install field-supplied thermostatic expansion valve in
liquid line ahead of each evaporator section. For 2-step cooling, the fleld-supplkd solenoid used must be wired to be
opened by control from a 2-step thermostat
For example: 2 solenoids may be used with 3 TXVs —one
of the solenoids serving a liquid line feeding 2 of the TXVs.
Table 2 — Refrigerant Piping Sizes
SINGLE SUCTION RISERS
MODEL
38AK
024 5/8 1-5/8 028 7/8 1-5/8 034 044
L-Liquid Line S-Suction Line
* IMPORTANT — Requires a double suction riser, see below:
NOTE: Liquid and suction iine sizes are OD (in)
(a) - SUCTION RISER WITHOUT TRAP (b) - SUCTION RISER WITH TRAP
(^- SUCTION LINE TO CONDENSING UNIT
7/8 7/8
16-25
L
S L S
2-1 /8 2-1/8 7/8 2-1/8
LENGTH OF INTERCONNECTING PIPING (FT) 26-50
7/8 1-5/8 7/8 7/8
2-1 /8 7/8 2-1/8 7/8
DOUBLE SUCTION RISERS
51-75
L
7/8
1-1/8
UNIT 38AK
024 86 028 034 67 044 76
76-100
S
2-1/8 7/8 2-1/8 7/8 2-1/8
*
L
1-1 /8
1-1/8
2-1/8 2-1/8
MAXIMUM LIQUID LIFT
60 Hz 50 Hz
Ft
M
26 72
76
23 20 23
S
* *
101-200
L S
7/8 2-1/8
7/8 2-1/8 1-1/8 1-1/8
Ft
21 66 20 60
18
66 20
* *
M
MODEL
38AK
034 044
NOTE: A, B, C dimensions relate to reference diagram
2-1/8
51-75 76-100
A
B C
1-5/8

SUCTION PIPING AT EVAPORATOR AND TXV BULB LOCATION (See Fig. 5)

The purpose of these recommendations is to achieve good mixing of the refrigerant leaving the evaporator suction header for proper sensing by the TXV bulb.
1. A minimum of two 90° elbows must be installed upstream of the expansion valve bulb location.
2. The TXV sensing bulb should be located on a vertical riser where possible. If a horizontal location is neces sary, secure the bulb at approximately the 4 o’clock position.
3. Size the suction line from the evaporator through the riser for high velocity. Enter the suction pipe sizing charts in the Carrier System Design Manual at design tons and equivalent length (for 2 degree F loss). If reading falls between 2 sizes on chart, choose the smaller pipe size.
LENGTH OF INTERCONNECTING PIPING (FT)
A B C A
2-5/8
1-5/8 1-5/8
2-1/8 2-1/8
2-5/8 2-5/8
1-5/8 1-5/8
Suction piping for the high velocity section should be selected for about 0.5 degree F friction loss. If a 2 degree F loss is allowed for the entire suction line, 1.5 degree F is left for the balance of the suction line and it should be sized on that basis. Check that the high-velocity sizing is
adequate for oil return up the riser.
If an oil return connection at the bottom of this suction header is supplied with an evaporator, this connection must be teed-in ahead of first mixing elbow.
When the compressor is below the evaporator, the riser at the evaporator does not have to extend as high as the
top level. After a 15-diameter riser has been provided,
the suction line may elbow down immediately.
SAFETY RELIEF — A fusible plug is located on unit liquid line before the liquid valve.
101-200
B
2-1/8 2-1/8
C
2-5/8 2-5/8
Power Supply — Electrical characteristics of available
power supply must agree with unit nameplate rating. Supply voltage must be within limits shown in Table 3.
IMPORTANT: Operating unit on improper supply voltage, or with excessive phase imbalance, constitutes abuse and may affect Carrier warranty. See Unbal anced 3-Phase Supply Voltage, page 6.
Power Wiring — All power wiring must comply with applicable local and national codes. Install field-supplied branch circuit fused disconnect(s) per NEC (National Electri cal Code) of a type that can be locked OFF or OPEN. Disconnect(s) must be within sight from and readily acces sible from unit in compliance with NEC Article 440-14.
Table 3 — Electrical Data
60 HERTZ
MODEL
OfiAtr
024
028
034
044
500 200 600 100
500 200 600 100
500 200 600 100
500 200 600
100
Volts
3 Ph, 60 Hz
208/230
380 342 418 51 1 80 194.9 346 191 3.9 460 414 508 575
208/230
380 460 575 518 632
208/230
380 460 575 518
230 380 460 575
SuDolied*
Min. Max. (Fuse)
187
518 632 187 254
342 414
187 342 414
187 254 342 414 518
UNIT COMPRESSOR
MCA
254 92.1 150 348.6
46.9
42.9 70
124.6 200 418 64.7 110 508 60 7 100 226.1
52.5 80
254
145 5 250 418 72.5 125 508 687 110 632
418 508 91 0 150 632 81.5 125 282.8
54.9 90
2030 350
111 1
50 HERTZ
MODEL
38AK
024
034
044 300
800 230 300 346 900
800
028 300 346
900 400
800 230
300
900 800 230 900
Volts
3 Ph, 50 Hz
400 230
346 400
346 400
Supplied*
Min. Max.
198 254 311 342
198 254 109 175 348.4 76.9 342 311 342
198 254 1202 311 342
198 254 311 342
UNIT
MCA
380 50.5 80 400 49.3 80 1740 347 173 1.0
380 64.9 100 400 605 100 226.0 436 223 30
88.1 125
380 76.1 125 400 68.5
1506 250 380 112.6 175 400 90.8 150 351 0
GENERAL WIRING NOTES
1. A crankcase heater is wired in the control circuit so it is always operable as long as power supply disconnect is on, even if any safety device is open or unit stop-start switch is off. It is protected by a 5-amp circuit breaker in control power.
2. The power circuit field supply disconnect should never be
open except when unit is being serviced or is to be down for a
prolonged period When operation is resumed crankcase
heater should be energtedfor 24 hours before start-up. If unit is to be shut down for a prolonged period it is recommended that the suction arid discharge valves be closed to prevent an excessive accumulation of refrigerant in the compressor oil
3. Power entry is at one end only.
MOCP
ICF RLA LRA FLA (ea)
68
80 1748
175
MOCP (Fuse)
123.4
452.2 89.8 446 6.2
250.9 45.5 247 3.9
167.4 36.5 164 3.4
512.2 106.5 506 6.2
283.9 52.6 280
256.1 50 253 3.1
179.4 38.5 176 3.4
702.4 3898 79.5 382 39 351 2 65.4 345 3.1
ICF RLA LRA FLA (ea)
256.4 60.3 2044
34 7
28.9 120 3.4
43.6 223 31
147 5 690
57.1 276 3.4 3
COMPRESSOR
333 200
263.4 44.9
200 110
372.4 2984 2560 50.0 253 3.0
5578 105.1
408.8 79.5
859 366 539 294
65.4
FAN MOTORS!
345
3.6
173 1 8
3.9
62 3
FAN MOTORS!
250
259
545 400
345 30
6.4 2 44 2
64 2
4.4 2
6.4
4.4 2
6.4 3
4.4
Qty
2 2 2 2
2 2 2 2
2 2 2 2
3 3
Qty
2
2 2
2
3 3
FLA — Full Load Amps ICF — Maximum Instantaneous Current Flow during starting (the
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps (complies with National Electrical
MOCP — Maximum Overcurrent Protection RLA — Rated Load Amps
* Units are suitable for use on electrical systems where voltage
supplied to unit terminals is not below or above listed minimum and maximum limits
t All fans are protected by a single circuit breaker.
point in the starting sequence where the sum of the LRAfor the starting compressor, plus the total RLA for all running compressors, plus the total FLA for all running fan motors is maximum).
Code [NEC], Section 430-24)
4. Maximum field wire sizes allowed by lugs on terminal block are: 350 MCM for models 38AK028 (208/230-3-60), 38AK034 (208/230-3-60, 230-3-50), and 38AK044 (208/230-3-60, 230-3-50) 2/0 AWG for all other models.
5. Terminals for field power supply are suitable for copper, copper-clad aluminum or aluminum conduc tors. Insulation must be rated 167 F (75 C) minimum.
UNBALANCED 3-PHASE SUPPLY VOLTAGE — Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the % voltage imbalance:
% Voltage Imbalance
= 100 X
max voltage deviation from average voltage
average voltage
I ^
CONDENSER FANS — The fans must rotate counter clockwise when viewed from above. If necessary, correct direction of fan rotation by interchanging any 2 power input wires at disconnect switch. Affix crankcase heater decal (located in installer’s packet) to unit disconnect switch.
FIELD CONNECTIONS
1. Main Power — Bring wires from the fused disconnect switch through hole in bottom rail of unit to control
box (Fig. 6, 7, 8) and connect terminals 1111, [12
on line side of terminal block TBl (see Fig. 9).
13 To comply with NEC Article 440-14, the disconnect must be located within sight from and readily acces sible from unit.
■ 2. 24-v Control Power — Units have single point power connections. Control circuit is directly connected inter nally to unit. Maximum 24-v control circuit is 3 amps.
NOTE: For wire runs up to 50 ft. use no. 18 AWG insulated wire (35 C min.). For 50 to 75 ft., use no. 16 AWG insulated wire (35 C min.). For over 75 ft. use 14 AWG insulated wire (35 C min.).
3. Control Circuit Interlock — An airflow switch may be installed in the indoor air handler to prevent unit from
running when indoor air is not flowing. This switch (no. HR81JE001) is available from Service Parts Center, or equivalent can be field supplied. This should be electri
cally interlocked in the control circuit, between term inals I 1 I and I 6 I (for flow switch) on TB2. See Fig. 9 for field wiring. This is in the 115-v circuit. Wires must
be run in conduit with ground wire.
4. Transformer Connections — See unit wiring label dia
gram, notes 1 and 2, located behind compressor com partment end access door.
Example: Supply voltage is 240-3-60.
AB = 243 volts BC = 236 volts
AC = 238 volts
Average Voltage =
Determine maximum deviation from average voltage:
(AB) 243 - 239 = 4 volts (BC) 239 - 236 = 3 volts (AC) 239 - 238 = 1 volt
Maximum deviation is 4 volts. Determine % voltage imbalance:
% Voltage Imbalance = 100 x —^ = 1.7%
This amount of phase imbalance is satisfactory as it is
below the maximum allowable 2%.
IMPORTANT: Contact your local electric utility company immediately if the supply voltage phase imbalance is more than 2%.
243 + 236 + 238 = 239 volts
239
IMPORTANT: Ensure power to the crankcase heater is always on (except when servicing the unit). If circuit breakers inside unit shut down the com pressor and condenser fans, crankcase heater remains on.
NOTES:
1
THERE MUST BE [1220 mm] 4 ft FOR SERVICE AND FOR UNRESTRICTED AIRFLOW ON ALL SIDES OF UNIT.
THERE MUST BE MINIMUM C2440 mml 8 ft CLEAR AIR SPACE ABOVE UNIT.
THE APPROXIMATE OPERATING WEIGHT OF THE UNIT IS:
3. 60 HZ
UNIT WT LBS
38AK024
1456 661
38AK024C 1580
NOTE: "C" INDICATES COPPER COIL.
2 4
WT KG
717
50 HZ
UNIT WT LBSWT KG 38AK024 38AK024C 1580
60 Hz 024 024C
50 Hz 024 024c
1456 661
717
APPROX. OPER. WT. (LB.)
AT SUPPORT POINTS
1 2
411
501
448 533
587
433
626
462
245 273 326
486 358 518
HINGED ACCESS DOOR•
CONTROL BOX
3 4
299
382
TOT. 1456 1580
1864 1988
[63.5-92.1] 2 1/2'-: FIELD MAIN POWER SU
- A
' II
HINGED ACCES
[1315]
4'-3 3/4'
[61]
2 7/16
[19.1]
3/4' dia; MOUNTING HOLES
(TYP 4 PLACES)
[63.5-92.1] 2 1/2'-3 5/8'DIA. FIELD POWER ENTRY 8 LIFTING
[22.2]
7/8' DIA. FIELD CONTROL POWER ENTRY
Fig. 6 — Dimensioi
ECimON
PAM No. 2
5/8' DIA.
LY
[22.2] 7/8' DIA. FIELD CONTROL CIRCUIT WIRING

TOP VIEW

1 Drawing, 38AK024
10'-7 13/16'

SIDE VIEW

Loading...
+ 16 hidden pages