Carrier 38AK008, 38AKS009, 38AK012, 38AK007, 38AKS012 User Manual

...
Page 1
38AK007,008,012
Fig. 1 — Model 38AK (Size 007 Shown)
38AKS008,009,012
Air-Cooled Condensing Units
Installation, Start-Up and
Service Instructions
50/60 Hz
CONTENTS
Step 1 — Complete Pre-Installation Checks
• UNCRATE UNIT
• INSPECT SHIPMENT
• CONSIDER SYSTEM REQUIREMENTS
Step 2 — Rig and Mount the Unit
• RIGGING
• COMPRESSOR MOUNTING
Step 3 — Complete Refrigerant Piping
Connections
• SIZE REFRIGERANT LINES
• FILTER DRIER AND MOISTURE INDICATOR
Step 4 — Make Electrical Connections
• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
START-UP Preliminary Checks Compressor Rotation Evacuate and Dehydrate Refrigerant Charge Compressor Overload Cycle-LOC™ Device (CLO) Low-Pressure/Loss-of-Charge Switch (LPS) High-Pressure Switch (HPS) High Flow Valves Refrigerant Service Ports Cooling Sequence of Operation Oil Charge
SERVICE Cleaning Lubrication Condenser-Fan Adjustment Capacity Control — Unit 38AKS012 Only Compressor Removal Crankcase Heater (Except 38AK007)
TROUBLESHOOTING GUIDE START-UP CHECKLIST
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-11
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11,12
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
. . . . . . . . . . . . . . . . . . . . . . 1
. . . . . . . . . . . . . . . . . 4
. . . . . . . . . . . 6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
. . . . . . . . . . . . . . . . . . . . . . . . . 9
. . . . . . . . . . . . . . . . . . . . . . . . . . . 10
. . . . . . . . . . . . . . . . . . . . . . 10
. . . . . . . . . . . . . . . . . . . . . 10
. . . . . . . . . . . . . . . . . . . . . . . 10
. . . . . . . . . . . . . . . . . . . . . . . . . . 10
. . . . . . . . . . . . . . . . . . . . . 11
. . . . . . . . 12
. . . . . . . . . . . . . . . . . . . . . . . . . . . 12
. . . . . . . . . . . . 12
. . . . . . . . . . . . . . . . . .13,14
. . . . . . . . . . . . . . . . . . CL-1, CL-2
Page
. . . . . . 1
. . . . . 10
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thoroughly. Consult local building codes and National Electrical Code (NEC) (U.S.A. Standard) for special installation requirements.
Before installing or servicing system, always turn off main power to system and install lockout tag on disconnect. There may be more than one disconnect switch. Electrical shock can cause personal injury.
INSTALLATION
The 38AK007, 008, and 012 units use hermetic compres­sors. The 38AKS008, 009, and 012 units use semi-hermetic compressors. See Table 1A or 1B for physical data.
Step 1 — Complete Pre-Installation Checks
UNCRATE UNIT (S ee Fig. 1) — Remove unit packaging except for the top skid assembly and wood bumpers, which should be left in place until after unit is rigged into place.
INSP E C T SHI PM E N T — File claim with shipping company if shipment is damaged or incomplete.
SAFETY CONSIDERATIONS
Installing and servicing air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install or service air-conditioning equipment.
When working on air-conditioning equipment, observe pre­cautions in literature and on tags and labels attached to unit.
NOTE: Ensure voltage listed on unit data plate agrees with electrical supply to unit.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 3 a 2 a
PC 111 Catalog No. 533-80003 Printed in U.S.A. Form 38A-9SI Pg 1 5-01 Replaces: 38A-8SI
Page 2
Table 1A — Physical Data — 50/60 Hz (English)
UNIT 38 AK007 AK008 AK012 AKS008 AKS009 AKS012
OPERATING WEIGHT (lb)
Aluminum Coils (Standard) Copper Coils (Optional)
RIGGING WEIGHT (lb)
Aluminum Coils (Standard)
Copper Coils (Optional) REFRIGERANT* COMPRESSOR
Bristol, Reciprocating Copeland, Scroll Copeland, Scroll Reciprocating, Semi-Hermetic
Quantity...Type
Quantity Cylinders
Speed (rpm) — 60 Hz
— 50 Hz
Oil Charge (oz) CONDENSER FAN — 60 Hz
Quantity...Rpm
Diameter (in.)
Motor Hp (NEMA)
Nominal Airflow (cfm) CONDENSER FAN — 50 Hz
Quantity...Rpm
Diameter (in.)
Motor Hp (NEMA)
Nominal Airflow (cfm) CONDENSER COIL
Face Area (sq ft)
Storage Capacity (lb)† CONNECTIONS (sweat)
Suction (in.)
Liquid (in.)
CONTROLS
Pressurestat Settings (psig)
High Cutout
Cut-in
Low Cutout
Cut-in
LEGEND
NEMA —
*Unit is factory supplied with holding charge only. †Storage capacity of condenser coil with coil 80% full of liquid R-22 at 124 F.
National Electrical Manufacturing Association
NOTE: Unit 38AKS012 has one step of unloading. Full load is 100% capacity, and one step of unloading is 67% capacity. Unit 38AKS012 has the following unloader settings: load is 70 ± 1 psig and unload is 60
±
340 392 426 510 564 564 386 460 503 578 632 632
390 442 476 560 614 614 436 510 553 628 682 682
1...H26A72Q 1...ZR94KC 1...ZR125KC 1...06DA818 1...06DA824
2——4 6
3500 3500 3500 1750 1750
65 85 110 88 128
Propeller; Direct Drive
1...850 1...1100 26 26
1
/
3
3800 6500 7000 6500 6500 6500
Propeller; Direct Drive
3150 5400 5800 5400 5400 5400
Enhanced Copper Tubes, Aluminum Lanced Fins
12.24 15.75 20.5 18.0 18.0 18.0
11.26 14.88 18.87 16.56 16.56 16.56
1
/
1
8
1
/
2
11/
8
1
/
2
426 ± 7 320 ± 20
2 psig.
R-22
1...960 26
1
/
3
11/
8
5
/
8
7 ± 3
22 ± 5
1460 1460
3
/
4
11/
1
8
/
2
11/
5
/
8
8
1...06DH824 (See Note)
11/
8
5
/
8
2
Page 3
Table 1B — Physical Data — 50/60 Hz (SI)
UNIT 38 AK007 AK008 AK012 AKS008 AKS009 AKS012
OPERATING WEIGHT (kg)
Aluminum Coils (Standard) Copper Coils (Optional)
RIGGING WEIGHT (kg)
Aluminum Coils (Standard)
Copper Coils (Optional) REFRIGERANT* COMPRESSOR
Bristol, Reciprocating Copeland, Scroll Copeland, Scroll Reciprocating, Semi-Hermetic
Quantity...Type
Quantity Cylinders
Speed (r/s) — 60 Hz
— 50 Hz
Oil Charge (L) CONDENSER FAN — 60 Hz
Quantity...R/s
Diameter (mm)
Motor Hp (NEMA)
Nominal Airflow (L/s) CONDENSER FAN — 50 Hz
Quantity...R/s
Diameter (mm)
Motor Hp (NEMA)
Nominal Airflow (L/s) CONDENSER COIL
Face Area (sq m)
Storage Capacity (kg)† CONNECTIONS (sweat)
Suction (in.)
Liquid (in.)
CONTROLS
Pressurestat Settings (kPa)
High Cutout
Cut-in
Low Cutout
Cut-in
LEGEND
NEMA —
*Unit is factory supplied with holding charge only. †Storage capacity of condenser coil with coil 80% full of liquid R-22 at 51 C.
National Electrical Manufacturing Association
NOTES:
1. Unit 38AKS012 has one step of unloading. Full load is 100% capacity, and one step of unloading is 67% capacity. Unit 38AKS012 has the following unloader settings: load is 483 ± 6.9 kPa and unload is 414 ± 13.8 kPa.
2. Equivalent mm values for connectors are as follows: in.
1
/212.7
5
/815.9
1
/828.6
1
mm
154 177 192 231 256 256 175 208 215 262 287 287
176 200 215 254 279 279 198 231 250 285 309 309
1...H26A72Q 1...ZR94KC 1...ZR125KC 1...06DA818 1...06DA824
2——4 6
58.4 58.4 58.4 29.2 29.2
48.4 48.4 48.4 24.2 24.2
1.92 2.51 3.25 2.60 3.78 Propeller; Direct Drive
1...14.2 1...18.3 660 660
1
/
3
1800 3050 3300 3050 3050 3050
Propeller; Direct Drive
1490 2550 2750 2550 2550 2550
Enhanced Copper Tubes, Aluminum Lanced Fins
1.14 1.46 1.90 1.67 1.67 1.67
5.1 6.75 8.6 7.5 7.5 7.5
1
/
1
8
1
/
2
11/
8
1
/
2
R-22
1...16.0 660
1
/
3
11/
8
5
/
8
2937 ± 48 2206 ± 138
48 ± 20
151 ± 34
1...06DH824 (See Note 1)
3
/
4
11/
8
1
/
2
11/
8
5
/
8
11/
8
5
/
8
3
Page 4
CONSIDER SYSTEM REQUIREMENTS
Consult local building codes and NEC for special instal­lation requirements.
Allow sufficient space for airflow clearance, wiring, refrigerant piping, and unit servicing. See Fig. 2.
Locate unit so that condenser airflow is unrestricted on all sides and above. Refer to Fig. 2.
Unit may be mounted on a level pad directly on base rails or mounted on raised pads at support points. See Table 2 for weight distribution based on recommended support points.
NOTE: If vibration isolators are required for a particular instal­lation, use corner weight information in Table 2 to make proper selection.
Table 2 — Weight Distribution
UNIT
38AK
007
008
012
S008
S009,S012
007
008
012
S008
S009,S012
STD UNIT
Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg
340 154 86 39 53 24 77 35 124 56 392 177 86 39 78 35 99 45 107 49 426 192 89 40 92 42 109 49 105 48 510 231 115 52 89 40 133 60 173 87 564 256 133 60 97 44 141 64 193 88
386 175 106 48 65 30 82 37 133 60 460 208 114 52 95 43 108 49 121 55 503 215 118 53 116 53 119 54 119 54 578 262 143 65 106 48 142 64 187 85 632 287 161 73 114 52 150 68 207 94
CORNERWCORNERXCORNERYCORNER
With Aluminum Coil
With Copper Coil
Z
Raise from above to lift unit from rails or pad when unit is
in final position.
After unit is in position, remove all shipping materials and
top crating. COMPRESSOR MOUNTING — Compressors are shipped
from the factory held down by 4 bolts. After unit is installed, loosen each bolt until the snubber washer can be moved with finger pressure. See Fig. 4.
Step 3 — Complete Refrigerant Piping Con­nections —
cap; liquid connection is sweat with plastic cap. Refer to Table 3A or 3B for the proper line sizes. Follow standard piping practices.
SIZE REFRIGERANT LINES — Consider length of piping required between condensing unit and air handler, amount of liquid lift, and compressor oil return. See Table 4A and 4B and also refer to Part 3 of Carrier System Design Manual for design details and line sizing. Refer to air handle r instal lation instruc­tions for additional information.
Table 3A — Refrigerant Piping Sizes — 60 Hz
UNIT
38
AK007
AK008
AK012
AKS008
AKS009
AKS012
LEGEND
Liquid LIne
L—
Suction Line
S—
Suction connection is sweat with plastic
LINEAR LENGTH OF PIPING — FT (M)
0-25
(0-7.6)
LSLSLSLS
1
1
/
2
1/
1
2
5
1
/
8
1
1
/
2
5
1
/
8
5
1
/
8
1
/
8
1
/
8
1
/
8
1
/
8
1
/
8
1
/
8
25-50
(7.6-15.2)
1
/
2
1
/
2
5
/
8
1
/
2
5
/
8
5
/
8
50-75
(15.2-22.9)
Line Size (in. OD)
1
1
1
/
/
8
2
1
5
1
/
/
8
8
3
5
1
/
/
8
8
1
5
1
/
/
8
8
1
5
1
/
/
8
8
1
5
1
/
/
8
8
1
1
/
1
1
/
3
1
/
1
1
/
3
1
/
3
1
/
(22.9-30.5)
1
8
5
8
5
8
5
8
5
8
5
8
75-100
/
2
/
8
/
8
/
8
/
8
/
8
1
1
1
1
1
1
1
/
8
3
/
8
3
/
8
3
/
8
3
/
8
3
/
8
NOTES:
1. Dimensions in [ ] are in millimeters.
2. See Fig. 3 for additional information.
Step 2 — Rig and Mount the Unit
Be sure unit panels are securely in place prior to rigging.
RIGG ING — These units are designed for overhead rigging. Refer to rigging label for preferred rigging method. Spreader bars are not required if top crating is left on unit. All panels must be in place when rigging. (See Fig. 3.) As further protec­tion for coil faces, plywood sheets may be placed against sides of unit, behind cables. Run cables to a central suspension point so that angle from the horizontal is not less than 45 degrees. Raise and set unit down carefully.
If it is necessary to roll unit into position, mount unit on rails, using a minimum of 3 rollers. Apply force to rails, not unit. If unit is to be skidded into position, place it on a large pad and drag it by the pad. Do not apply any force to unit.
Table 3B — Refrigerant Piping Sizes — 50 Hz
LINEAR LENGTH OF PIPING — FT (M)
0-25
UNIT
(0-7.6)
38
LSLSLSLS
1
1
AK007
AK008
AK012
AKS008
AKS009
AKS012
/
2
1
1
/
2
5
1
/
8
1
1
/
2
5
1
/
8
5
1
/
8
LEGEND
Liquid LIne
L—
Suction Line
S—
NOTES FOR TABLES 3A AND 3B:
1. Pipe sizes are based on a 2 F (1 C) loss for liquid and suction lines.
2. Pipe sizes are based on the maximum linear length shown for each column, plus a 50% allowance for fittings.
3. Charge units with R-22 in accordance with unit installation instructions.
4. Line size conversion to mm is:
mm
in.
1
/
12.7
2
5
/
15.9
8
1
/828.6
1
3
1
/834.9
1
/
8
1
/
8
1
/
8
1
/
8
1
/
8
1
/
8
25-50
(7.6-15.2)
1
/
2
1
/
2
5
/
8
1
/
2
5
/
8
5
/
8
50-75
(15.2-22.9)
Line Size (in. OD)
1
1
1
/
/
8
2
1
5
1
/
/
8
8
3
5
1
/
/
8
8
1
5
1
/
/
8
8
1
5
1
/
/
8
8
1
5
1
/
/
8
8
1
1
/
3
1
/
3
1
/
3
1
/
3
1
/
3
1
/
(22.9-30.5)
1
8
5
8
5
8
5
8
5
8
5
8
75-100
/
2
/
8
/
8
/
8
/
8
/
8
1
1
/
8
3
1
/
8
3
1
/
8
3
1
/
8
3
1
/
8
3
1
/
8
4
Page 5
UNIT 38 DIM. A DIM. B DIM. C DIM. D DIM. E DIM. F
AK007
AK008
AK012
AKS008
AKS009
AKS012
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Center of Gravity. See chart for
3. Direction of Airflow.
4. Minimum clearance (local codes or jurisdiction
5. With the exception of the clearance for the con-
6. Units may be installed on combustible floors
dimensions.
may prevail):
a. Condenser coil, for proper airflow, 36 in. [914]
one side, 12 in. [305] the other. The left or rear side getting the greater clearance is optional.
b. Overhead, 60 in. [1524] to assure proper con-
denser fan operation.
c. Between units, control box side, 42 in. [1067]
per NEC (National Electrical Code) (U.S.A. Standard).
d. Between unit and ungrounded surfaces, con-
trol box side, 36 in. [914] per NEC.
e. Between unit and block or concrete walls and
other grounded surfaces, control box side, 42 in. [1067] per NEC.
denser coil as stated in Note 4b, a removable fence or barricade requires no clearance.
made from wood or Class A, B, or C roof covering material.
1
1-6 [470.0]
1-8
[508.0]
1-9
[533.4]
1-6
[457.2]
1-7
[482.6]
1-7
[482.6]
/2″
1-23/4″
[375.0]
1
/2″
1-6
[470.0]
1-8
[508.0]
3
1-4
/4″
[425.5]
1-5
[431.8]
1-5
[431.8]
— —
— —
2-0
[609.6]
2-913/16″
[858.8]
13
2-9
/
16
[858.8]
13
2-9
/16″
[858.8]
1-21/4″
[362] 1-3
[381] 1-3
[381] 1-3
[381] 1-3
[381] 1-3
[381]
1-45/16″
[415]
5
/16″
2-
[613]
5
/16″
2-
[613]
2-5/16″
[613]
5
2-
/
[613]
2-5/16″
[613]
ELECTRICAL CONNECTIONS
2-95/16″
[846.5]
7
/16″
3-5 [1052.5]
3-57/16″ [1052.5]
3-57/16″ [1052.5]
7
3-5
16
/
16
[1052.5] 3-57/16″
[1052.5]
AA 1
BB 2 Dia [51] Power Supply Knockout
CC 2
DD
SERVICE VALVE CONNECTIONS — 50/60 Hz
UNIT 38 SUCTION LIQUID
AK007 1
AK008 1
AK012 1
AKS008 1
AKS009 1
AKS012 1
CONNECTION SIZES
3
/8″ Dia [35] Field Power Supply Hole
1
/2″ Dia [64] Power Supply Knockout
7
/8″ Dia [22] Field Control Wiring Hole
1
/8″ [28.6] 11/2″ [12.7]
1
[28.6] 1
/
8
1
[28.6] 1
/
8
1
[28.6] 1
/
8
1
[28.6] 1
/
8
1
[28.6] 1
/
8
1
/
2
5
/
8
1
/
2
5
/
8
5
/
8
[12.7]
[15.9]
[12.7]
[15.9]
[15.9]
Fig. 2 — Dimensions (ft-in.)
UNIT
38
AK007 390 176 45.0 1143 38.5 978 35.5 904 AK008 442 200 45.0 1143 38.5 978 43.5 1105 AK012 476 215 45.0 1143 38.5 978 43.5 1105 AKS008 560 254 45.0 1143 38.5 978 43.5 1105 AKS009 614 279 45.0 1143 38.5 978 43.5 1105 AKS012 614 279 45.0 1143 38.5 978 43.5 1105
*Weights are for aluminum coils.
Fig. 3 — Rigging Label
5
RIGGING WEIGHT*
ABC
lb kg in. mm in. mm in. mm
Page 6
Fig. 4 — Typical Compressor Mounting
208/230-3-60 380-3-60 460-3-60 575-3-60 220-3-50 400-3-50
LEGEND
Fig. 5 — Power Wiring Connections
C—
Contactor
NEC
National Electrical Code Field Wiring Factory Wiring
Splice Connection (Factory Supplied)
(38AKS Units)
FILTER DRIER AND MOISTURE INDICATOR — The fil­ter drier is factory installed. Moisture indicator is field-supplied and should be installed just after liquid line shutoff valve. Do not use a receiver; there is none provided with unit and one should not be used.
NOTE: Unit is shipped with R-22 holding charge. System pressure must be relieved before removing caps. Recover refrigerant prior to brazing.
Pass nitrogen or other inert gas through piping while braz-
ing to prevent formation of copper oxide.
Install field-supplied thermostatic expansion valve to evap-
orator section. It is recommended that a field-supplied liquid line solenoid be positioned in the main liquid line close to the evaporator coil, and wired to close when compressor stops to minimize refrigerant migration during the ‘‘OFF’’ cycle.
Table 4A — Liquid Line Data — 60 Hz
LIQUID LINE
Max Allowable
Temp Los s
UNIT
38
AK007 AK008 AK012 AKS008 AKS009 AKS012
MAX
ALLOWABLE
LIQUID LIFT
Ft M psi kPa F C
86 26.2 7 48.3 2 1 60 18.3 7 48.3 2 1 70 21.3 7 48.3 2 1 60 18.3 7 48.3 2 1 65 19.8 7 48.3 2 1 65 19.8 7 48.3 2 1
Max Allowable Pressure Drop
Step 4 — Make Electrical Connections
Unit cabinet must have an uninterrupted, unbroken electri­cal ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control com­partment, or conduit approved for electrical ground when installed in accordance with NEC ANSI (American National Standards Institute)/NFPA (National Fire Protec­tion Association) 70 (U.S.A. Standards) and local electrical codes. Failure to follow this warning could result in the installer being liable for personal injury of others.
FIELD PO WER S UPPLY — All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the tr ansformer must be rewired by moving the black wire from the 230-v and connecting it to the 200-v transformer.
Refer to unit label diagram for additional information. Pigtails are provided for field wire connections. Use factory­supplied splices or UL (Underwriters’ Laboratories) (U.S.A. Standard) approved copper/aluminum connector.
When installing units, provide a disconnect per NEC. All field wiring must comply with NEC and local requirements.
Install field wiring as follows:
1. Install conduit through side panel openings.
2. Install power lines to connections as shown in Fig. 5. Wrap connections with electrical tape.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (also see Ta­ble 5). Voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in Table 5, Note 2, to determine the percent voltage imbalance Operation
on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical compo­nents. Such operation would invalidate any applicable Carrier warranty.
1
/4-in. spade terminal on the transformer
1
/4-in. spade terminal from the
NOTE: Values shown are for units operating at 45 F (7.2 C) satu­rated suction and 95 F (35 C) entering air.
UNIT
AK007 AK008 AK012 AKS008 AKS009 AKS012
NOTE: Values shown are for units operating at 45 F (7.2 C) satu­rated suction and 95 F (35 C) entering air.
Table 4B — Liquid Line Data — 50 Hz
LIQUID LINE
Max Allowable
38
MAX
ALLOWABLE
LIQUID LIFT
Ft M psi kPa F C
76 23.2 7 48.3 2 1 50 15.2 7 48.3 2 1 57 17.4 7 48.3 2 1 50 15.2 7 48.3 2 1 52 15.8 7 48.3 2 1 52 15.8 7 48.3 2 1
Max Allowable Pressure Drop
Temp Loss
6
Page 7
Table 5 — Electrical Data
UNIT
38
AK007
AK008
AK012
AKS008
AKS009
AKS012
NOMINAL VOLTAGE
(V-Ph-Hz)
208/230-3-60 187 254 21.8 158 1.9 30.1 40
460-3-60 414 508 10.0 79 1.0 13.6 20 575-3-60 518 632 9.0 65 1.9 14.1 20 220-3-50 198 242 21.8 158 1.0 28.8 35 400-3-50 360 440 10.0 79 1.0 14.0 20
208/230-3-60 187 254 28.8 195 3.8 39.8 50
460-3-60 414 508 14.7 95 1.9 20.3 25 575-3-60 518 632 10.8 80 1.9 15.4 20 220-3-50 198 242 28.8 195 1.5 37.5 45 400-3-50 360 440 14.7 95 1.5 19.9 25
208/230-3-60 187 254 37.8 239 3.8 39.8 20
460-3-60 414 508 17.2 125 2.2 20.3 30 575-3-60 518 632 14.3 90 1.9 15.4 25 220-3-50 198 242 37.8 239 1.4 48.8 60 400-3-50 360 440 17.2 125 1.4 23.0 30
208/230-3-60 187 254 31.5 160 3.1 42.5 50
380-3-60 342 418 19.0 75 2.2 26.0 35 460-3-60 414 508 15.7 80 1.4 21.0 25 575-3-60 518 632 12.6 64 1.4 17.2 20 220-3-50 198 253 31.5 160 1.4 42.5 50 400-3-50 342 460 15.7 80 1.4 21.0 25
208/230-3-60 187 254 39.7 198 3.1 52.7 70
380-3-60 342 418 24.0 93 2.2 32.2 40 460-3-60 414 508 19.9 99 1.4 26.3 35 575-3-60 518 632 15.9 79 1.4 21.3 25 220-3-50 198 253 39.7 198 1.4 52.7 70 400-3-50 342 460 19.9 99 1.4 26.3 35
208/230-3-60 187 254 39.7 198 3.1 52.7 70
380-3-60 342 418 24.0 93 2.2 32.2 40 460-3-60 414 508 19.9 99 1.4 26.3 35 575-3-60 518 632 15.9 79 1.4 21.3 25 220-3-50 198 253 39.7 198 1.4 52.7 70 400-3-50 342 460 19.9 99 1.4 26.3 35
VOLTAGE RANGE COMPRESSOR OFM POWER SUPPLY MIN MAX RLA LRA FLA MCA MOCP
LEGEND
CSA — FLA — HACR — LRA — MCA — MOCP — NEC — OFM — RLA — UL
NOTES:
1. In compliance with NEC requirements for multimotor and combi­nation load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt­age is greater than 2%.
the percent of voltage imbalance.
Canadian Standards Association Full Load Amps Heating, Air Conditioning and Refrigeration Locked Rotor Amps Minimum Circuit Amps Maximum Overcurrent Protection National Electrical Code (U.S.A. Standard) Outdoor (Condenser) Fan Motor Rated Load Amps Underwriters’ Laboratories
Use the following formula to determine
= 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
3. The 575-v units are CSA only.
4. the 380 v, 60 Hz units and all 50 Hz units are listed.
= 1.53%
452 + 464 + 455
1371
=
3
= 457
7 457
3
not
UL or CSA
7
Page 8
FIELD CONTR OL WIRING — Install a Carrier-approved accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense aver­age temperature in accordance with thermostat installation instructions.
Route thermostat cable or equivalent single leads of colored wire from subbase terminals to low-voltage connections on unit (shown in Fig. 6) as described in Steps 1 through 3 below.
NOTE: For wire runs, use the following insulated wire:
LENGTH
Ft M AWG sq mm
0-50 0-15.2
50-75 15.2-22.9
Over 75 Over 22.9
LEGEND
AWG —
American Wire Gage
INSULATION
RATING (C)
35 18 0.82 35 16 1.30 35 14 2.08
SIZE
All wire larger than no. 18 AWG cannot be directly con­nected to the thermostat and will require a junction box and splice at the the rmo stat .
1. Connect thermostat wires to screw terminals of low­voltage connection board.
2. Pass the control wires through the hole provided in the corner post. (See Fig. 7.)
3. Feed wire t hrough the raceway built i nto the corner post and into the 24 v thermostat connection board. The 24 v thermostat connection is located on the left side of the low-voltage connection compartment. The raceway pro­vides the UL required clearance between hi gh- and low­voltage wiring.
24-V BARRIER
LOW-VOLTAGE THERMOSTAT CONNECTION BOARD
RACEWAY
CORNER POST
Fig. 7 — Field Control Wiring Raceway
(38AKS Unit Shown)
Total combined amperage drain of the field-installed liquid line solenoid valve and indoor (evaporator) fan contactor must not exceed 22 va. If the specified va must be exceeded , use a remote relay to switch the load.
LEGEND
AHA Adjustable Heat Anticipator C—Contactor, Compressor CAP Capacitor CB Circuit Breaker CC Cooling Compensator CLO Compressor Lockout COMP — Compressor Motor HPS High-Pressure Switch IFC Indoor (Evaporator) Fan Contactor LLSV — Liquid Line Solenoid Valve LPS Low-Pressure Switch NEC National Electrical Code OFC Outdoor-Fan Contactor OFM Outdoor-Fan Motor QT Quadruple Terminal TB Te r m i na l B l oc k TRAN — Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Te r mi na l Bl oc k
Splice
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring To indicate common
potential only. Not to represent wiring.
Ground
Fig. 6 — Typical Control Wiring Connections/Component Arrangement (38AK Shown)
8
Page 9
START-UP
Fig. 8A — Cooling Charging Chart — 38AK007
(60 Hz)
Fig. 8B — Cooling Charging Chart — 38AK007
(50 Hz)
Preliminary Checks
1. Field electrical power source must agree with unit name­plate rating.
2. Check that all internal wi ring connections are tight and that all barriers, covers, and panels are in place. Ensure no electrical wires are in contact with refrigerant tubing.
3. Ensure all service valves are open. On 38AKS units, be sure all compressor service valves are backseated.
4. Verify that compre ssor holddown bolts for units 38AKS have been loosened and that flat/snubber washers can be rotated by applying finger pressure (snug, but not tight).
5. Verify compressor crankcase heater is securely in place. Crankcase heater must operate for at least 24 hours before start-up. The 38AK unit size 007 does not require a crankcase heater.
6. Note that compressor oil level is visible in the sight glass (38AKS units only).
7. Check for leaks in refrigerant system by using soap bub­bles and/or electronic leak detector.
8. Check that liquid line solenoid valve is located at evapo­rator coil as shown in Filter Drier and Moisture Indicator section, page 6.
9. Check voltage imbalance as shown in Ta ble 5, Note 2.
10. Check that both outdoor and indoor units are properly mounted in accordance with installation instructions and applicable codes.
Compressor Rotation —
compressors, it is important to be certain compressor is rotating in the proper direction. To determine whether or not compres­sor is rotating in the proper direction:
1. Connect service gages to suction and discharge pressure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pres­sure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge
pressure does not rise to normal levels:
1. Note that the condenser fan is probably also rotating in the wrong direction.
2. Turn off power to the unit, tag disconnect.
3. Reverse any two of the unit power leads.
4. Reapply power to the compressor, verify correct pressures.
The suction and discharge pressure levels should now move
to their normal start-up levels.
Evacuate and Dehydrate —
entire refrigerant system by use of the methods described in Carrier GTAC II, Module 4, System Dehydration. Evacuate system down to 500 microns and ensure vacuum hold for 15 minutes. If vacuum does not hold, pressurize system and locate leak and repair.
Refrigerant Charge —
Module 5, Charging Recovery, Recycling, and Reclamation.
Unit panels must be in place when unit is operating during
charging procedure.
Unit is shipped with holding charge only. Weigh in 7 lb
(3 kg) of R-22 to start unit. CHARGE COOLING — Use Cooling Charging Charts,
Fig. 8A or 8B and 9A or 9B. Unit must be charged in cooling mode only. Vary refrigerant until the conditions of the chart are
On 3-phase units with scroll
Evacuate and dehydrate
Refer to Carrier GTAC II,
met. Note that charging charts are different from type normally used. Charts are based on charging the units to the correct sub­cooling for the various operating conditions. Accurate pressure gage and temperature sensing device are required. Connect the pressure gage to the service port on the liquid line service valve. Mount the temperature sensing device on the liquid line, close to the liquid line service valve and insulate it so that out­door ambient temperature does not affect the reading. Indoor airflow must be within the normal operating range of the unit.
Operate unit a minimum of 15 minutes. Ensure pressure and temperature readings have stabilized. Plot liquid pressure and temperature on chart and add or reduce charge to meet curve. Adjust charge to conform with charging chart, using liquid pressure and temperature to read chart.
9
Page 10
Fig. 9A — Cooling Charging Chart — 38AK008,012
Fig. 9B — Cooling Charging Chart — 38AK008,012
Compressor Overload —
power to the compressor when either the current or int ernal motor winding temperature becomes excessive, and automati­cally resets when the internal temperature drops to a safe level. This overload may require up to 60 minutes (or longer) to reset. If the internal overload is suspected of being open, disconnect the electrical power to the unit and check the circuit through the overload with an ohmmeter or continuity tester.
Cycle-LOC™ Device (CLO) —
vice prevents the compressor from starting or running in a high pressure, loss-of-charge or freezestat open situation. Reset the
and 38AKS008,009,012 (60 Hz)
and 38AKS008,009,012 (50 Hz)
This overload interrupts
The Cycle-LOC de-
Cycle-LOC device by setting the t hermostat t o elimi nate cool ­ing demand and return it to the original set point. If the system shuts down again for the same fault, determine the possible cause before attempting to reset the Cycle-LOC device.
Low-Pressure/Loss-of-Charge Switch (LPS) —
When the liquid line pressure drops below 7 psig (48 kPa), the LPS opens 24-v power to the compressor contactor and stops the compressor. When the pressure reaches 22 psig (152 kPa), the switch resets and the compressor is allowed to restart.
High-Pressure Switch (HPS) —
ant high-side pressure reaches 426 psig (2937 kPa), the HPS opens 24-v power to the compressor contactor and stops the compressor. When the pressure drops to 320 psig (2206 kPa ), the switch resets and the compressor is allowed to restart.
Refrigerant Service Ports —
3 service ports: one on the suction line, one on the liquid line, and one on the compressor discharge line. Be sure caps on t he ports are tight.
High Flow Valves —
and suction tubes are high flow valves. Large black plastic caps distinguish these valves with O-rings located inside the caps. These valves cannot be accessed for service in the field. Ensure the plastic caps are in place and tight or the possibility of refrig­erant leakage could occur.
Cooling —
system selector switch at COOL position and fan switch at AUTO. position. Adjust thermostat to a setting below room temperature. Compressor starts on closure of contactor.
Check cooling effects at a setting below room temperature. Check unit charge. Refer to Refrigerant Charge section on page 9.
Reset thermostat at a position above room temperature. Compressor will shut off.
TO SHUT OFF UNIT — Set s y stem selector switch at OFF position. (Resetting thermostat at a position above room tem­perature shuts unit off temporarily until space temperature ex­ceeds thermostat setting.) Units are equipped with Cycle­LOC™ protection device. Unit shuts down on any safety trip and remains off. Check reason for safety trip.
Compressor restart is accomplished by manual reset of the thermostat by turning the selector switch to OFF position and then to ON position.
Set space thermostat to OFF position. Set
Located on the compressor hot gas
Sequence of Operation —
calls for cooling. With all safety devices satisfied, the compres­sor contactor and fan contactor energize, causing the compres­sor and outdoor (condenser) fan motor to operate. Contacts close, allowing the field-supplied and -installed indoor (evapo­rator) fan contactor to function. The recommended field­supplied and -installed liquid line solenoid valve will also open, allowing the system to function in cooling. As cooling demand is satisfied, the thermostat contacts break, deenergiz­ing the contactor causing the system to shut off. The liquid line solenoid valve closes, minimizing the potential for refrigerant migration at this time. The compressor does not restart until the thermostat again calls for cooling. The system is protected by a Cycle-LOC device so that t he compressor will not start if a high-pressure or low-pressure fault occurs. Compressor restart is accomplished by manual reset of the thermostat by turning the selector switch to OFF position and then to ON position. This should be done only once. If system shuts down due to the same fault, determine the problem before attempting to reset the Cycle- LOC de vi ce.
When the refriger-
Each unit system has
At start-up, the the rmostat
10
Page 11
Oil Charge (Tables 1A and 1B)
Fig. 11 — Propping Up Top Panel
Fig. 12 — Separating Coil Sections
Fig. 10 — Cleaning Condenser Coil
38AKS UNITS — Allow unit to run for about 20 minutes. Stop unit and check compressor oil level. Add oil only if neces­sary to bring oil into view in sight glass. Use only Carrier-
approved compress or oil.
Approved oils are:
Suniso 3GS WF32-150
38AK UNI TS — The 38AK units do not have a sight glass and are factory charged with the correct amount of oil.
ALL UNITS — Do not reuse drained oil or use any oi l that has been exposed to atmosphere. Procedures for adding or re­moving oil are given in Carrier Standard Service Techniques Manual, Chapter 1, Refrigerants.
If oil is added, run unit for an additional 10 minutes. Stop unit and check oil level. If level is still low, add oil only after determining that piping system is designed for proper oil return and that system is not leaking oil.
SERVICE
When servicing unit, shut off all electrical power to the unit to avoid shock hazard or injury from rotating parts.
Cleaning —
cooling season and as operating conditions require. CONDENSER COIL — Inspect coil monthly. Clean con-
denser coil annually and as required by location or outdoor-air conditions.
Clean coil as follows:
1. Turn off unit power and tag disconnect.
2. Remove and save top panel screws on condensing unit.
3. Remove condenser coil corner post. See Fig. 10. To hold top panel open, place coil corner post between top panel and side panel. See Fig. 11.
4. Remove bracket holding coil sections together a t return end of condenser coil. Carefully separate the outer coil section 3 to 4 in. (75 to 100 mm) from the inner coil section. See Fig. 12.
5. Use a water hose or other suitable equipment to flush down between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiff bristled brush in the normal manner.
6. Reposition the coil section and secure.
7. Remove the coil corner post fr om between the top panel and side panel.
8. Install the coil corner post and replace all screws removed in Step 2.
Inspect unit interior at the beginning of each
Lubrication
COMPRESSORS — Each compressor is charged with correct amount of oil at the factory. For additional information on 38AKS units, refer to the Oil Charge section above.
FAN MOTOR BEARING S — Fan motor bearings are of the permanently-lubricated type. No further lubrication is required.
Condenser-Fan Adjustment (Fig. 13)
1. Shut off unit power supply and tag disconnect.
2. Remove condenser-fan assembly (grille, motor, motor cover, and fan).
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 13.
5. Tighten setscrews.
6. Replace condenser-fan assembly.
11
Page 12
Capacity Control — Unit 38AKS012 Only —
A suction pressure-actuated unloader controls 2 cylinders and provides capacity control. Unloaders are factory set (see T able 1A or 1B), but may be field adjusted as follows:
CONTROL SET POINT (cylinder load point) is adjustable from 0 to 85 psig (586 kPa). To adjust, turn control set point adjustment nut (Fig. 14) clockwise to its bottom stop. In this position, set point is 85 psig (586 kPa). Then, turn adjustment counterclockwise to desired control set point. Every full turn counterclockwise decreases set point by 7.5 psig (51.7 kPa).
PRESSURE DIFFERENTIAL (difference between cylinder load and unload points) is adjustable from 6 to 22 psig (41.4 to 152 kPa). T o adjust, turn press ure dif ferential adjustment screw (Fig. 14) counterclockwise to its back stop position. In this position, differential is 6 psig (41.4 kPa). Then, turn adjust­ment clockwise to desired pressure differential. Every full turn clockwise increases differential by 1.5 psig (10.3 kPa).
NOTE: Fan height adjustments are as follows:
UNIT in. mm
38AK007 (60 Hz)
All 50-Hz Units All 60-Hz Units
(Except 38AK007)
4.50 114
6.42 163
Fig. 13 — Condenser-Fan Adjustment
Compressor Removal —
See Tables 1A and 1B for compressor information. Follow safety codes and wear safety glasses and work gloves.
1. Shut off power to unit and tag disconnect. Remove unit access panel (front of unit).
2. Remove refrigerant from system using refrigerant remov­al methods described in the Carrier GTAC-II, Module 5, Charging, Recovery, Recycling, and Reclamation.
3. Disconnect compressor wiring at compressor terminal box.
4. Remove bolts from suction flange and discharge service valves (38AKS008,009,012 units only). Loosen sweat connections (38AK007,008, and 012 units only).
Excessive movement of copper lines at compressor may cause higher levels of vibration when unit is restored to service.
5. Remove crankcase heater from compressor base (38AKS008,009,012, 38AK008,012).
6. Remove compressor holddown bolts.
7. Remove compressor from unit.
8. Clean system. Add new liquid line filter drier.
9. Install new compressor in unit.
10. Connect suction and discharge lines to compressor, as applicable. Ensure that compressor holddown bolts are in place.
11. Connect wiring.
12. Install crankcase heater on 38AKS008,009,012 and 38AK008,012 units.
13. Evacuate and recharge unit.
14. Restore unit power.
Crankcase Heater (Except 38AK007) —
The crank­case heater on the 38AK008,012 condensing units prevents refrigerant migration and c ompressor oil dilution during shut­down when compressor is not operating.
Close both compressor service valves if applicable (on 38AKS008,009,012) when crankcase heater is deenergized for more than 6 hours.
Fig. 14 — Compressor Capacity Control Unloader
12
Page 13
SYMPTOM CAUSE REMEDY
Compressor does not run — Contactor open
Compressor does not run — Contactor closed
Compressor cycles on high­pressure switch — Condenser fan on
Compressor cycles on high­pressure switch — Condenser fan off
Compressor cycles on low­pressure switch — Evaporator fan running
Airflow restricted — Low suction pressure
Indoor (evaporator) fan stopped — Low suction pressure
Compressor runs but cooling insufficient — Suction pressure low
Compressor runs but cooling insufficient — Suction pressure high
TROUBLESHOOTING GUIDE
Power off. Restore power. Fuses blown. Replace with correct fuses after finding cause and correcting. Transformer open/shorted. Replace transformer if primary windings are receiving power and
Thermostat circuit open. Check thermostat setting. Low-pressure switch open. Check for refrigerant undercharge or system leak. High-pressure switch open. Check for refrigerant overcharge or obstruction of outdoor airflow. Connections loose. Tighten all connections. Compressor motor thermostat open. Check for excessive motor temperature. Compressor leads loose, broken. Check connections with power off. Single phasing. Replace blown fuse. Compressor internal overload open. Allow compressor motor windings to cool down to reset overload.
High-pressure switch faulty. Replace switch. Airflow restricted. Dirty coil. Remove obstruction, clean condenser coil. Air recirculating. Clear airflow area. Noncondensables in system. Recover, evacuate and recharge as required. Refer to Carrier
Refrigerant overcharge. Recover as required. Refrigerant system restrictions. Check or replace filter drier, expansion valve, etc. Fan slips on shaft. Tighten fan hub screws. Motor not running. Check power and capacitor Motor bearings seized. Replace motor. Motor overload open. Check overload rating. Check for fan blade obstruction. Motor burned out, windings open. Replace motor. Filter drier plugged. Replace filter drier. Expansion valve power head
defective. Low refrigerant charge. Find leak, repair, evacuate system, and recharge. Expansion valve restricted/plugged. Remove and replace expansion valve. Evaporator coil iced up. Check refrigerant charge. Evaporator coil dirty. Clean coil fins. Indoor-air filter dirty. Clean or replace filters. Indoor-air dampers closed. Check damper operation and position. Electrical connections loose. Tighten all connections. Fan relay defective. Replace relay. Motor overload open. Check power supply. Motor defective. Replace motor. Fan belt broken or slipping. Replace or tighten belt. Refrigerant charge low. Add charge. Head pressure low. Check refrigerant charge. Indoor-air filters dirty. Clean or replace filters. Expansion valve power head
defective. Expansion valve restricted/plugged. Remove and replace expansion valve. Evaporator coil partially iced. Check low-pressure setting. Evaporator airflow restricted. Remove obstruction. Heat load excessive. Check for open doors or windows. Reverse rotation. Check compressor rotation (see page 9).
no output.
Determine cause for overload opening.
GTAC-II, Module 5, Charging, Recovery, Recycling, and Reclamation.
1
/3 and 3/4 hp motor.
Replace power head.
Replace power head.
NOTE: See Fig. 15 for component arrangements.
13
Page 14
C— CAP — CB — CLO — COMP — EQUIP — GND — NEC — OFC — OFM — QT — TB
Contactor, Compressor Capacitor Circuit Breaker Compressor Lockout Compressor Motor Equipment Ground National Electrical Code Outdoor-Fan Contactor Outdoor-Fan Motor Quadruple Terminal Terminal Block
Fig. 15 — Typical Component Arrangement
LEGEND
TRAN —
Transformer
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Factory Wiring
Field Power Wiring
Accessory or Optional Wiring
Copyright 2001 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 3 a 2 a
PC 111 Catalog No. 533-80003 Printed in U.S.A. Form 38A-9SI Pg 14 5-01 Replaces: 38A-8SI
Page 15
I. Preliminary Information
START-UP CHECKLIST
OUTDOOR:
INDOOR:
ADDITIONAL ACCESSORIES ______________________________________________________________________________
MODEL NO. _______________________________ SERIAL NO. ____________________________________
AIR HANDLER MANUFACTURER __________________________________________________________________
MODEL NO.__________________________________ SERIAL NO. ____________________________________
II. Pre-Start-Up
OUTDOOR UNIT
IS THERE ANY SHIPPING DAMAGE? _______________ (Y/N) __________
IF SO, WHERE: __________________________________________________________________________________________
_______________________________________________________________________________________________________
WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N) _________
CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? (Y/N) _________
HAS THE GROUND WIRE CIRCUIT BEEN CONNECTED PER NEC GUIDELINES? (Y/N) _______
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (Y/N) __________
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (Y/N) __________
38AKS Only:
(Y/N) _________
HAS COMPRESSOR ROTATION BEEN VERIFIED (Is compressor rotating in correct direction?) (Y/N) _______
HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED (Snubber washers are snug, but not tight)?
CONTROLS
ARE THERMOSTAT AND INDOOR-FAN CONTROL WIRING CONNECTIONS MADE AND CHECKED? (Y/N) _____
ARE ALL WIRING TERMINALS (including main power supply) TIGHT? (Y/N) ______
HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS? (Y/N) ______
INDOOR UNIT
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? (Y/N) ________
ARE PROPER AIR FILTERS IN PLACE? (Y/N) __________
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? (Y/N) _______
DO THE FAN BELTS HAVE PROPER TENSION? (Y/N) _________
HAS CORRECT FAN ROTATION BEEN CONFIRMED? (Y/N) ________
PIPING
IS LIQUID LINE SOLENOID VALVE LOCATED AT THE EVAPORATOR COIL AS REQUIRED? (Y/N) ______
HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR, CONDENSER, EVAPORATOR, TXVs (Thermostatic Expansion Valves) SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS WITH A LEAK DETECTOR? (Y/N) _______
LOCATE, REPAIR, AND REPORT ANY LEAKS. ________________________________________________________________
ON 38AKS UNIT, HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED)? (Y/N) _______
HAVE LIQUID LINE SERVICE VALVE AND SUCTION LINE SERVICE VALVE BEEN OPENED? (Y/N) ______
IS THE OIL LEVEL IN THE COMPRESSOR CRANKCASE ON THE 38AKS UNIT IN VIEW IN THE COMPRESSOR SIGHT GLASS? (Y/N) __________
CL-1
Page 16
CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS: AB________ V AC________ V BC ________V
(AB + AC + BC)/3 = AVERAGE VOLTAGE = _________ V
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = _________V
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = _________ %
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.
III. Start-Up
CHECK INDOOR (EVAPORATOR) FAN SPEED AND RECORD. ___________
CHECK OUTDOOR (CONDENSER) FAN SPEED AND RECORD. _____________
AFTER AT LEAST 15 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
OIL PRESSURE (38AKS only) ___________ SUCTION PRESSURE ___________ Psig (kPa) SUCTION LINE TEMP ___________ °F (°C) DISCHARGE PRESSURE ___________ Psig (kPa) DISCHARGE LINE TEMP ___________ °F (°C) ENTERING CONDENSER-AIR TEMP ___________ DB LEAVING CONDENSER-AIR TEMP ___________ DB EVAP ENTERING-AIR DB (dry bulb) TEMP ___________ EVAP ENTERING-AIR WB (wet bulb) TEMP ___________ EVAP LEAVING-AIR DB TEMP ___________ EVAP LEAVING-AIR WB TEMP ___________
COMPRESSOR AMPS (L1/L2/L3) ______ / ______ / _______
HAS REFRIGERANT CHARGE BEEN ADJUSTED PER CHARGING CHARGE? __________
NOTES:
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
_______________________________________________________________________________________________________
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
Copyright 2001 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Ta b 3 a 2 a
PC 111 Catalog No. 533-80003 Printed in U.S.A. Form 38A-9SI Pg CL-2 5-01 Replaces: 38A-8SI
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
Loading...