Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for brazing operations. Have fire
extinguisher available. Read these instructions thoroughly.
Consult local building codes and National Electrical Code
(NEC) (U.S.A. Standard) for special installation requirements.
Before installing or servicing system, always turn off main
power to system and install lockout tag on disconnect.
There may be more than one disconnect switch. Electrical
shock can cause personal injury.
INSTALLATION
The 38AK007, 008, and 012 units use hermetic compressors. The 38AKS008, 009, and 012 units use semi-hermetic
compressors. See Table 1A or 1B for physical data.
Step 1 — Complete Pre-Installation Checks
UNCRATE UNIT (S ee Fig. 1) — Remove unit packaging
except for the top skid assembly and wood bumpers, which
should be left in place until after unit is rigged into place.
INSP E C T SHI PM E N T — File claim with shipping company
if shipment is damaged or incomplete.
SAFETY CONSIDERATIONS
Installing and servicing air-conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install or
service air-conditioning equipment.
When working on air-conditioning equipment, observe precautions in literature and on tags and labels attached to unit.
NOTE: Ensure voltage listed on unit data plate agrees with
electrical supply to unit.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Ta b 3 a 2 a
PC 111Catalog No. 533-80003Printed in U.S.A.Form 38A-9SIPg 15-01Replaces: 38A-8SI
*Unit is factory supplied with holding charge only.
†Storage capacity of condenser coil with coil 80% full of liquid R-22 at 124 F.
National Electrical Manufacturing Association
NOTE: Unit 38AKS012 has one step of unloading. Full load is 100% capacity, and one
step of unloading is 67% capacity. Unit 38AKS012 has the following unloader settings:
load is 70 ± 1 psig and unload is 60
*Unit is factory supplied with holding charge only.
†Storage capacity of condenser coil with coil 80% full of liquid R-22 at 51 C.
National Electrical Manufacturing Association
NOTES:
1. Unit 38AKS012 has one step of unloading. Full load is 100% capacity, and one
step of unloading is 67% capacity. Unit 38AKS012 has the following unloader
settings: load is 483 ± 6.9 kPa and unload is 414 ± 13.8 kPa.
2. Equivalent mm values for connectors are as follows:
in.
•Consult local building codes and NEC for special installation requirements.
•Allow sufficient space for airflow clearance, wiring,
refrigerant piping, and unit servicing. See Fig. 2.
•Locate unit so that condenser airflow is unrestricted on
all sides and above. Refer to Fig. 2.
•Unit may be mounted on a level pad directly on base
rails or mounted on raised pads at support points. See
Table 2 for weight distribution based on recommended
support points.
NOTE: If vibration isolators are required for a particular installation, use corner weight information in Table 2 to make
proper selection.
Raise from above to lift unit from rails or pad when unit is
in final position.
After unit is in position, remove all shipping materials and
top crating.
COMPRESSOR MOUNTING — Compressors are shipped
from the factory held down by 4 bolts. After unit is installed,
loosen each bolt until the snubber washer can be moved with
finger pressure. See Fig. 4.
cap; liquid connection is sweat with plastic cap. Refer to
Table 3A or 3B for the proper line sizes. Follow standard
piping practices.
SIZE REFRIGERANT LINES — Consider length of piping
required between condensing unit and air handler, amount of
liquid lift, and compressor oil return. See Table 4A and 4B and
also refer to Part 3 of Carrier System Design Manual for design
details and line sizing. Refer to air handle r instal lation instructions for additional information.
Table 3A — Refrigerant Piping Sizes — 60 Hz
UNIT
38
AK007
AK008
AK012
AKS008
AKS009
AKS012
LEGEND
Liquid LIne
L—
Suction Line
S—
Suction connection is sweat with plastic
LINEAR LENGTH OF PIPING — FT (M)
0-25
(0-7.6)
LSLSLSLS
1
1
/
2
1/
1
2
5
1
/
8
1
1
/
2
5
1
/
8
5
1
/
8
1
/
8
1
/
8
1
/
8
1
/
8
1
/
8
1
/
8
25-50
(7.6-15.2)
1
/
2
1
/
2
5
/
8
1
/
2
5
/
8
5
/
8
50-75
(15.2-22.9)
Line Size (in. OD)
1
1
1
/
/
8
2
1
5
1
/
/
8
8
3
5
1
/
/
8
8
1
5
1
/
/
8
8
1
5
1
/
/
8
8
1
5
1
/
/
8
8
1
1
/
1
1
/
3
1
/
1
1
/
3
1
/
3
1
/
(22.9-30.5)
1
8
5
8
5
8
5
8
5
8
5
8
75-100
/
2
/
8
/
8
/
8
/
8
/
8
1
1
1
1
1
1
1
/
8
3
/
8
3
/
8
3
/
8
3
/
8
3
/
8
NOTES:
1. Dimensions in [ ] are in millimeters.
2. See Fig. 3 for additional information.
Step 2 — Rig and Mount the Unit
Be sure unit panels are securely in place prior to rigging.
RIGG ING — These units are designed for overhead rigging.
Refer to rigging label for preferred rigging method. Spreader
bars are not required if top crating is left on unit. All panels
must be in place when rigging. (See Fig. 3.) As further protection for coil faces, plywood sheets may be placed against sides
of unit, behind cables. Run cables to a central suspension point
so that angle from the horizontal is not less than 45 degrees.
Raise and set unit down carefully.
If it is necessary to roll unit into position, mount unit on
rails, using a minimum of 3 rollers. Apply force to rails, notunit. If unit is to be skidded into position, place it on a large pad
and drag it by the pad. Do not apply any force to unit.
Table 3B — Refrigerant Piping Sizes — 50 Hz
LINEAR LENGTH OF PIPING — FT (M)
0-25
UNIT
(0-7.6)
38
LSLSLSLS
1
1
AK007
AK008
AK012
AKS008
AKS009
AKS012
/
2
1
1
/
2
5
1
/
8
1
1
/
2
5
1
/
8
5
1
/
8
LEGEND
Liquid LIne
L—
Suction Line
S—
NOTES FOR TABLES 3A AND 3B:
1. Pipe sizes are based on a 2 F (1 C) loss for liquid and suction
lines.
2. Pipe sizes are based on the maximum linear length shown for
each column, plus a 50% allowance for fittings.
3. Charge units with R-22 in accordance with unit installation
instructions.
4. Line size conversion to mm is:
mm
in.
1
/
12.7
2
5
/
15.9
8
1
/828.6
1
3
1
/834.9
1
/
8
1
/
8
1
/
8
1
/
8
1
/
8
1
/
8
25-50
(7.6-15.2)
1
/
2
1
/
2
5
/
8
1
/
2
5
/
8
5
/
8
50-75
(15.2-22.9)
Line Size (in. OD)
1
1
1
/
/
8
2
1
5
1
/
/
8
8
3
5
1
/
/
8
8
1
5
1
/
/
8
8
1
5
1
/
/
8
8
1
5
1
/
/
8
8
1
1
/
3
1
/
3
1
/
3
1
/
3
1
/
3
1
/
(22.9-30.5)
1
8
5
8
5
8
5
8
5
8
5
8
75-100
/
2
/
8
/
8
/
8
/
8
/
8
1
1
/
8
3
1
/
8
3
1
/
8
3
1
/
8
3
1
/
8
3
1
/
8
4
UNIT 38DIM. ADIM. BDIM. CDIM. DDIM. EDIM. F
AK007
AK008
AK012
AKS008
AKS009
AKS012
NOTES:
1. Dimensions in [ ] are in millimeters.
2.Center of Gravity. See chart for
3.Direction of Airflow.
4. Minimum clearance (local codes or jurisdiction
5. With the exception of the clearance for the con-
6. Units may be installed on combustible floors
dimensions.
may prevail):
a. Condenser coil, for proper airflow, 36 in. [914]
one side, 12 in. [305] the other. The left or rear
side getting the greater clearance is optional.
b. Overhead, 60 in. [1524] to assure proper con-
denser fan operation.
c. Between units, control box side, 42 in. [1067]
per NEC (National Electrical Code) (U.S.A.
Standard).
d. Between unit and ungrounded surfaces, con-
trol box side, 36 in. [914] per NEC.
e. Between unit and block or concrete walls and
other grounded surfaces, control box side,
42 in. [1067] per NEC.
denser coil as stated in Note 4b, a removable
fence or barricade requires no clearance.
made from wood or Class A, B, or C roof covering
material.