38AK007
HEATING & COOLING
Installation, Start-Up and Service
Instructions
SAFETY COIMSIDERATIONS
Installing and servicing air-conditioning equipment can
be hazardous due to system pressure and electrical compo
nents. Only trained and qualified service personnel should
install or service air-conditioning equipment.
When working on air-conditioning equipment, observe
precautions in literature and on tags and labels attached to
unit.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for brazing operations. Have
fire extinguisher available. Read these instructions thor
oughly. Consult local building codes and National Electri
cal Code (NEC) for special installation requirements.
A WARNING
Before installing or servicing system, always turn off
main power to system. There may be more than one
disconnect switch. Electrical shock can cause personal
injury.
Air-Cooled Condensing Unit
INSTALLATION
Step 1 — Complete Pre-Installation Checks
UNCRATE UNIT — Remove unit packaging except for
the top skid assembly and wood bumpers, which should be
left in place until after unit is rigged into place.
INSPECT SHIPMENT — File claim with shipping com
pany if shipment is damaged or incomplete.
CONSIDER SYSTEM REQUIREMENTS
• Consult local building codes and NEC for special instal
lation requirements.
• Allow sufficient space for airflow clearance, wiring,
refrigerant piping, and servicing unit. See Eig. 1 and
Table 1.
• Locate unit so that condenser airflow is unrestricted on
all sides and above. Refer to Fig. 1.
• Unit may be mounted on a level pad directly on base
rails or mounted on raised pads at support points. See
Table 2 for weight distribution based on recommended
support points.
NOTE: If vibration isolators are required for a particular in
stallation, use data in Table 2 to make proper selection.
Table 1 — Physical Data
UNIT 38AK
OPER WEIGHT (lb)
REFRIGERANT*
COMPRESSOR
on (oz) 65
CONDENSER AIR FAN
Number...Rpm 60 Hz
Diameter (in.)
Motor Hp (NEMA)
Nominal Cfm Total
CONDENSER COIL
Face Area (sq ft)
Storage Capacity (lb)t
CONNECTIONS (sweat)
Suction (in.)
Liquid (In.)
CONTROLS
Pressurestat Settings
High Cutout
Low Cutout
FUSIBLE PLUG 200 F
‘Unit is factory supplied with holding charge only.
fStorage capacity of condenser coil with coil 80% full of liquid R-22
at 124 F
50 Hz
Cut-in
Cut-in
Propeller; Direct Drive
007
340
22
1.. .850
1.. 708
26
Vs
3800
12 24
11.264
1V8
V2
426 ± 7 psig
320 ± 20 psig
7 ± 3 psig
22 ± 5 psig
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book|1 |4 PC 111 Catalog No 633-809 Printed in U.S A Form 38AK-2SI Pg 1 6-92 Replaces: New
Tab 3a 2a
Table 2 — Weight Distribution
STD. UNIT
UNIT
38AK007
UNIT
38AK007 77
WEIGHT
lbs.
340
CORNER WEIGHT
lbs.
CORNER WEIGHT
lbs.
kg.
154
(C)
86
kg.
35
(A)
CORNER WEIGHT
kg. lbs.
39 53
CORNER WEIGHT
(D)
lbs. kg.
124 56
(B)
kg.
24
REFRIGERANT PIPING SIZES
EQUIVALENT LENGTH OF PIPING - FT
IVe V2
76-100
s
IVs
COND
UNIT
38AK007
L — Liquid Line S — Suction Line
NOTES:
1. Pipe sizes are based on a 2° F loss for liquid and suction lines
2. Pipe sizes are based on an equivalent length equal to the max
imum length of interconnecting piping plus 50 percent for fittings.
3. Charge units with R-22 in accordance with unit installation
instructions.
0-25 26-50 51-75
Line Size (in. OD)
L
V2 IVs
L s L s L
s
IVa
V2
Va
SIZE REFRIGERANT LINES - Consider length of pip
ing required between condensing unit and evaporator, amount
of liquid lift, and compressor oil return. See Table 3 and
also refer to Part 3 of Carrier System Design Manual for
design details and line sizing. Refer to evaporator installa
tion instructions for additional information.
INSTALL FILTER DRIER AND MOISTURE INDICA
TOR — The filter drier is factory supplied and field in
stalled. Moisture indicator is a field-installed option and should
be installed just after liquid line shutoff valve. Do not use a
receiver; there is none provided with unit and one should
not be used.
NOTE: Unit is shipped with R-22 holding charge. System
pressure must be relieved before removing caps.
Pass nitrogen or other inert gas through piping while braz
ing to prevent formation of copper oxide.
Install field-supplied thermostatic expansion valve to evap
orator section. It is recommended that a field supplied liq
uid line solenoid be positioned in the main liquid line close
to the evaporator coil, and wired to close when compressor
stops to minimize refrigerant migration during the “OFF”
cycle.
Step 2 - Rig and Mount the Unit
ik CAUtlON
Be sure unit panels are securely in place prior to
rigging.
RIGGING — These units are designed for overhead rig
ging. Refer to rigging label for preferred rigging method.
Spreader bars are not required if top crating is left on unit.
All panels must be in place when rigging. (See Fig. 2) As
further protection for coil faces, plywood sheets may be
placed against sides of unit, behind cables. Run cables to a
central suspension point so that angle from the horizontal is
not less than 45 degrees. Raise and set unit down carefully.
If it is necessary to roll unit into position, mount unit on
rails, using a minimum of 3 rollers. Apply force to rails,
not unit. If unit is to be skidded into position, place it on a
large pad and drag it by the pad. Do not apply any force to
unit.
Raise from above to lift unit from rails or pad when unit
is in final position.
After unit is in position, remove all shipping wrapping
and top crating.
Step 3 — Complete Refrigerant Piping Connec
tions — Suction connection is 1-1/8-in. sweat with plas
tic cap; liquid connection is 1/2-in. sweat with plastic cap.
Follow standard piping practices.
Table 3 — Liquid Line Data
MAX
UNIT 38AK007
60 Hz
50 Hz
NOTE: Values shown are for units operating at 45 F saturated suc
tion and 95 F entering air
ALLOWABLE
LIQUID
LIFT (ft)
86 7
72
Max Allowable
Pressure Drop
LIQUID LINE
(psi)
7
Max Allowable
Temp Loss
(F)
2
2
Step 4 — Make Electrical Connections
A WARNING
Unit cabinet must have an uninterrupted, unbroken elec
trical ground to minimize the possibility of personal in
jury if an electrical fault should occur. This ground may
consist of electrical wire connected to unit ground lug
in control compartment, or conduit approved for elec
trical ground when installed in accordance with NEC
ANSI (American National Standards Institute)/NFPA
(National Fire Protection Association) 70-1987 and lo
cal electrical codes. Failure to follow this warning could
result in the installer being liable for personal injury of
others.
NOTES:
1. Dimensions in are in miiiimeters.
Center of gravity.
3
4 Minimum ciearance (locai codes or jurisdiction may
5. With the exception of the clearance for the condenser
6 Units may be installed on combustible floors made from
Direction of air fiow.
prevaii):
a Bottom to combustibie surfaces 0 in.
b Condenser coil, for proper air flow, 36 in. one side,
12 in the other The side getting the greater ciear
ance is optionai
c Overhead, 60 in to assure proper condenser fan op
eration.
d Between units, controi box side, 42 in per NEC.
e Between unit and ungrounded surfaces, control box
side, 36 in per NEC
f Between unit and block or concrete walls and other
grounded surfaces, control box side, 42 in per NEC
coil as stated in notes 5a, b, and c, a removable fence
or barricade requires no clearance
wood or class A, B, or C roof covering material
A 1%” DIA. [35] FIELD POWER SUPPLY HOLE
CONNECTION SIZES
B 2” DIA. [51] POWER SUPPLY KNOCK-OUT
c 2V2'’ dia [64] POWER SUPPLY KNOCK-OUT
Ve" DIA [22] FIELD CONTROL WIRING HOLE
D
rxp ÍKMSr
► -0'-2 9/16
LEFT SIDE
-3’-S 3/IS"
Fig. 1 -
FORIC TRUX SLOTS
<3 SlOeS ÚM.W
u 3'-3 1/2'
0003}
-------------------
FRONT
Dimensions (ft-in.)
0*-2 Ì/4'DJA Í57J
(TYP 0 PLACES)
RIGHT SIDE
Fig. 2 - Rigging Label