Installing, starting up, and servicing this equipment can
be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics
should install, start up, and service this equipment.
Untrained personnel can perform basic maintenancefunctions, such as cleaning coils. All other operations should be
performed by trained service personnel.
When working on the equipment, observe precautions in
the literature, and on tags,stickers, and labels attached to the
equipment and any other safety precautions that may apply.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Use care in handling, rigging, and setting bulky
equipment.
ELECTRIC SHOCK HAZARD.
Open all remote disconnects before servicing
this equipment.
INSTALLATION
Step 1 — Rig and Place Unit —
designed for overhead rigging, and it is important that this
method be used. Lifting holes are provided in the frame base
rails, which are marked for rigging (see rigging label on the
unit and Tables 1, 2A, and 2B for rigging weights and center
of gravity). It is recommended that field-supplied pipes, of
sufficient length to extend at least 12-in. (305 mm) beyond
the frame, be passed through the holes.
To maintain unit stability while lifting, use 4 cables,
chains, or straps of equal length. Attach one end of
each cable to one pipe end and the other end of each
cable to the overhead rigging point.
Use spreader bars or frame to keep the cables, chains,
and straps clear of the unit sides. Leave standard coil pro-
tection packaging in place during rigging to provide protection to coils. Remove and discard all coil protection after
rigging cables are detached.
DOMESTIC UNITS — For units 38AH044-084, 124, and
134; standard unit packaging consists of coilprotection only.
There is no standard packaging provided for units 38AH094
and 104. Skids are not provided. If overhead rigging is not
available at the jobsite,place the unit on a skid or pad before
dragging or rolling. When rolling, use a minimum of
3 rollers. When dragging, pull the pad or skid. Do not applyforce to the unit. When in final position, raise from above to
lift unit off the pad or skid.
EXPORT UNITS — All export units are mounted on skids
with vertical coil protection. Leave the unit on the skid until
it is in final position. Whileon the skid, the unit can be rolledor skidded. Apply force to the skid, not to the unit. Use a
minimum of 3 rollers when rolling. When in final position,
raise from above to remove the skid.
PLACING UNITS
Units 38AH044-084 — RefertoFig.1and 2 for airflow clear-
ances. Recommended minimum clearances are 6 ft (1829 mm)
for unrestricted airflow and service on sides of unit, 5 ft
(1524 mm) on ends, and unrestricted clear air space above
the unit. Provide ample space to connect liquid and suction
lines to indoor unit. For multiple units, allow 8 ft(2440 mm)
separation between units for airflow and service.
Do not forklift these units unless the unit is attached to
a skid designed for forklifting.
All units are
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
Tab 3a
PC 111Catalog No. 563-704Printed in U.S.A.Form 38AH-15SIPg 110-98Replaces: 38AH-14SI
The placement area must be level and strong enough to
support the operating weight of the unit (see Table 3A or
3B). When unit is in proper location, use of mounting holes
in base rails is recommended for securing unit to supporting
structure. For mounting unit on vibration isolators, a perimeter support channel between the unit and the isolators is
recommended. Fasteners for mounting unit are field supplied. Be sure to mount unit level to ensure proper oil return
to compressors.
Units 38AH094-134 — Refer to Fig. 3-6 for airflow
clearances. Recommended minimum clearances are 6 ft
(1829 mm) for unrestricted airflow and service on sides of
unit, 5 ft (1524 mm) on ends, and unrestricted clear air space
above unit. Provide ample space to connect liquid and suction lines to indoor unit. For multiple units, allow
8 ft (2440 mm) separation between units for airflow and
service.
Do not forklift these units unless the unit is attached to
a skid designed for forklifting.
The placement area must be level and strong enough to
support the operating weight of the unit. See Table 4A
or 4B. Refer to the following paragraphs for theproperplacement of the unit.
Units 38AH094,104 — For mounting units on vibration isolators, a perimeter support channel is required between the
unit and the support isolators. The perimeter support channel must be sizedto support the fully assembled unit. Do not
support units on individual isolationsupports. Support channel, hardware, and fasteners are field supplied. When unit is
in proper location, level unit and bolt intoposition with fieldsupplied bolts.
Units 38AH124,134 — For ease of shipment and handling,
unit 38AH124 is shipped as 2 modules (124A and 124B)
and unit 38AH134 is shipped as 2 modules (134Aand 134B).
The modules must be connected at the final installation site
with thefactory-shippedpipingandsheet metal trim kit mounted
on Module 124A or 134A. See Fig. 7.
Do not move assembled 38AH124 or 134 units as a single
assembly. Always move modules individually during installation or at any other time.
Mark installation site for placement of Modules 124A and
124B or Modules 134A and 134B. See Table 4A or 4B for
final assembled dimensions. A service space of 24 in.
(610 mm) is required between the 2 modules for piping and
sheet metal trim installation.
Place Module 124Aor 134Ain position, ensuring that the
control box is at the end opposite the service space. See
Fig. 8.
Remove sheet metal and tubing from Module 124Aor 134A
sheet metal trim kit (Fig. 7). Remove sheet metal cover panels from return-bend end of unit facing the service space.
See Fig. 8. These panels may be discarded or saved for
reinstallation if module is moved from site. See Fig. 9.
Remove sheet metal cover panels fromreturn-bend end of
Module 124B or 134B. Place Module 124B or 134B in
position. The exposed return-bend ends of each module are
now opposite each other and facing the service space. The
compressors of each module are on opposite sidesofthe unit.
IMPORTANT: Modules must be placed 24 in.
(610 mm) apart and square relative to each other.
The modules are now in position for piping installation and final assembly. See Fig. 8. For mounting units on
vibration isolators, a perimeter support channel is required
between the assembled unit and the support isolators. The
perimeter support channel must be sized to support the fully
assembled unit. Do not support modules on individual isolation supports. Support channel, hardware, and fastenersare
field supplied.
When unit is in proper location, level unit and bolt into
position with field-supplied bolts.
Step 2 — Check Compressor Mounting
UNITS 38AH044-084 — Compressors are mountedon pans
and are held down by 4 bolts during shipment. After unit is
installed, loosen each of these bolts until the snubber washer
can be moved with finger pressure. See Fig. 10.
UNITS 38AH094-134 — Units 38AH094 and104 compressors are mounted on rails and held down by rail bolts during
shipment. After unit is installed, loosen the rail bolts to allow the rails and compressors to float freely on the springs
located under the rails. See Fig. 10.
Units 38AH124 and 134 compressors are mounted on pans
and are held down by 4 bolts during shipment. After unit is
installed, loosen each of these bolts untilsnubber washer can
be moved with finger pressure. See Fig. 10.
NOTE:Totalweight may differ fromsummationof corner weights due
to rounding of numerals.
TOTAL
WEIGHT
LEGEND
OPERATIONAL CORNER WEIGHT
ABCD
TOP VIEW, TYPICAL
3
SUCTION
CONNECTION(S)
LIQUID
CONNECTION(S)
21⁄89 Dia [54 mm]25⁄89 Dia [67 mm]
7
SUCTION C28-
LIQUID D18-10
SUCTION (Ckt A) 18-7
SUCTION (Ckt B) 28-
LIQUID (Ckt A)28-5
LIQUID (Ckt B)28-10
DUAL CKTSINGLE CKT
⁄89 Dia [22 mm]11⁄89 Dia [29 mm]
11
⁄169 [627mm] 18-105⁄169 [567mm]
1
⁄169 [561mm] 18-105⁄169 [567mm]
13
⁄169 [503mm] 28-5⁄89[626mm]
5
⁄89[626mm]—
3
⁄49 [756mm] 28-105⁄89 [879mm]
5
⁄89 [879mm]—
Chart 1, Field Power Supply Connections
UNITVOLTAGE Hz DIAMETER — in. [mm] QTY
044230503
044, 054
208/230603
346, 380/415 502
044, 054, 064 460,575,380 602
064
C—Copper Fin Coils
MTG — Mounting
SAE — Society of Automotive Engineers
NOTES:
1. The approximate operating weight of the unit is:
38AH-044---3259 lb [1478 kg]
38AH-044--C3547 lb [1609 kg]
38AH-054---3309 lb [1501 kg]
38AH-054--C3597 lb [1632 kg]
38AH-064---3565 lb [1617 kg]
38AH-064--C3998 lb [1813 kg]
2. Unit must have clearances for airflow as follows:
Top — Do not restrict in any way.
Ends—5ft[1524 mm]
Sides—6ft[1829 mm]
3. Mounting holes may be used to mountunit to concrete pad. They are not recommended for mounting
unit to spring isolators. If spring isolators are used, a perimeter support channel between the unit and
the isolators is recommended.
4. One 3
5. See Table1 forrigging center ofgravity (DimensionsX,Y). SeeTable2Aand 2B for A-Dcorner weights.
6. Circled numerals in Top View refer to condenser fans by position.
SUCTION C28-
LIQUID D18-10
SUCTION (Ckt A) 18-7
SUCTION (Ckt B) 28-
LIQUID (Ckt A)28-5
LIQUID (Ckt B)28-10
DUAL CKTSINGLE CKT
⁄89 Dia [22 mm] 11⁄89 Dia [29 mm]
11
⁄169 [627mm] 18-105⁄169 [567mm]
1
⁄169 [561mm] 18-105⁄169 [567mm]
13
⁄169 [503mm] 28-5⁄89[626mm]
5
⁄89[626mm]—
3
⁄49 [756mm] 28-105⁄89 [879mm]
5
⁄89 [879mm]—
Chart 1, Field Power Supply Connections
UNITVOLTAGEHz DIAMETER — in. [mm] QTY
074
208/230602
460602
346, 380/415 503
074, 084
380603
575602
084
208/230603
460603
1
⁄2[63]2
1
⁄2[63]1
5
⁄8[92]1
5
⁄8[92]1
1
⁄2[63]1
5
⁄8[92]2
5
⁄8[92]1
LEGEND
C—Copper Fin Coils
MTG — Mounting
SAE — Society of Automotive Engineers
NOTES:
1. The approximate operating weight of the unit is:
38AH-074---3812 lb (1729 kg)
38AH-074--C4229 lb (1918 kg)
38AH-084---4057 lb (1840 kg)
38AH-084--C4735 lb (2148 kg)
2. Unit must have clearances for airflow as follows:
Top — Do not restrict in any way.
Ends—5ft[1524 mm]
Sides—6ft[1829 mm]
3. Mounting holes maybe used to mountunit to concrete pad. They are notrecommended for mounting unit
to spring isolators. If spring isolators are used, a perimeter support channel between the unit and the isolators is recommended.
4. See Table 1 for rigging center of gravity (Dimensions X,Y). See Table 2A and 2B for A-D corner weights.
5. Circled numerals in Top View refer to condenser fans by position.
Fig. 2 — Dimensions — Units 38AH074,084
5
Chart 1, Field Power Supply Connections
UNIT
38AH
VOLTAGEHz DIAMETER — in. (mm) QUANTITY
208/230603
460, 575,
094
380
346, 380/415 503
603
5
5
5
⁄8(92)2
⁄8(92)1
⁄8(92)1
Fig. 3 — Dimensions — Unit 38AH094
LEGEND
C—Copper Fin Coils
MTG — Mounting
SAE — Society of Automotive Engineers
NOTES:
1. The approximate operating weight of the unit is:
38AH-094---5088 lb (2308 kg)
38AH-094--C5813 lb (2637 kg)
2. Unit must have clearances for airflow as follows:
Top — Do not restrict in any way.
Ends—5ft[1524 mm]
Sides—6ft[1829 mm]
3. Mounting holes may be used to mount unit to concrete pad. They are not
recommended for mounting unit to spring isolators.
5
4. Two 3
5. Circled numerals in Top View refer to condenser fans by position.
6. If spring isolators are used, a perimeter support channel between the unit
7. See Table 1 for rigging center of gravity (Dimensions X,Y). See Table 2A
⁄89 (92-mm) dia holes are recommended for parallel conductors on
208/230 v units.
and the isolators is recommended.
and 2B for A-D corner weights.
6
Chart 1, Field Power Supply Connections
UNIT
38AH
VOLTAGEHz DIAMETER — in. (mm) QUANTITY
208/230603
104
460, 575,
380
603
346, 380/415 503
5
⁄8(92)2
5
⁄8(92)1
5
⁄8(92)1
Fig. 4 — Dimensions — Unit 38AH104
LEGEND
C—Copper Fin Coils
MTG — Mounting
SAE — Society of Automotive Engineers
NOTES:
1. The approximate operating weight of the unit is:
38AH-104---5435 lb (2465 kg)
38AH-104--C6160 lb (2794 kg)
2. Unit must have clearances for airflow as follows:
Top — Do not restrict in any way.
Ends—5ft[1524 mm]
Sides—6ft[1829 mm]
3. Mounting holes may be used to mount unit to concrete pad. They are not
recommended for mounting unit to spring isolators.
5
4. Two 3
5. Circled numerals in Top View refer to condenser fans by position.
6. If spring isolators are used, a perimeter support channel between the unit
7. See Table 1 for rigging center of gravity (Dimensions X,Y). See Table 2A
⁄89 (92-mm) dia holes are recommended for parallel conductors on
208/230 v units.
and the isolators is recommended.
and 2B for A-D corner weights.
7
Chart 1, Field Power Supply Connections
UNIT
38AH
VOLTAGEHz
208/230603
124A
124B
460, 575,
380
346, 380/415503
LEGEND
C—Copper Fin Coils
MTG — Mounting
SAE — Society of Automotive Engineers
DIAMETER
602
(in.)
5
⁄8(92)1
1
⁄2(63)1
5
⁄8(92)1
NOTES:
1. The approximate operating weight of the unit is:
QUANTITY
38AH-124---7260 lb (3293 kg)
38AH-124--C8126 lb (3686 kg)
2. Unit must have clearances for airflow as follows:
Top — Do not restrict in any way.
Ends—5ft[1524 mm]
Sides—6ft[1829 mm]
3. Mounting holes may be usedto mount unit to concrete pad. They are notrecommended for mounting unit to spring isolators.
5
4. One 3
5. Circled numerals in Top View refer to condenser fans by position.
6. If spring isolatorsare used, a perimeter support channelbetween the unit and
7. Each module ofthe unit must berigged into position separately.The unit must
8. Suction and liquid connections can exit on either side of the unit.
9. Field power supply connections are required for each module.
10. See Table 1 for rigging center of gravity (Dimensions K,L,X,Y). See Table 2A
⁄89 (92-mm) dia hole is recommended for single-entry power into each
module (124A and 124B) of the 208/230-v units.
the isolators is recommended. Do not support each module separately.
not be rigged after modules have been connected.
and 2B for A-D corner weights.
Fig. 5 — Dimensions — Unit 38AH124
8
Chart 1, Field Power Supply Connections
UNIT
38AH
134A
134B
C—Copper Fin Coils
MTG — Mounting
SAE — Society of Automotive Engineers
VOLTAGEHz
208/230603
460, 575, 380602
346, 380/415503
208/230602
460, 575602
380603
346, 380/415503
LEGEND
DIAMETER —
in. (mm)
5
⁄8(92)1
1
⁄2(63)1
5
⁄8(92)1
1
⁄2(63)2
1
⁄2(63)1
5
⁄8(92)1
5
⁄8(92)1
Fig. 6 — Dimensions — Unit 38AH134
QUANTITY
NOTES:
1. The approximate operating weight of the unit is:
38AH-134---7507 lb (3405 kg)
38AH-134--C8357 lb (3791 kg)
2. Unit must have clearances for airflow as follows:
Top — Do not restrict in any way.
Ends—5ft[1524 mm]
Sides—6ft[1829 mm]
3. Mounting holes may be used to mount unit to concrete pad. They are not
recommended for mounting unit to spring isolators.
5
4. One 3
5. Circled numerals in Top View refer to condenser fans by position.
6. If spring isolators are used, a perimeter support channel between the as-
7. Each module of the unit must be rigged into position separately. The unit
8. Suction and liquid connections can exit on either side of the unit.
9. Field power supply connections are required for each module.
10. See Table1A or1B for rigging centerof gravity (DimensionsK,L,X,Y). See
⁄89 (92-mm) dia hole is recommended for single-entry power into
Module 134Aand 208/230-vunits.Single entry powerinto Module 134Bis
not recommended.
Qty...Dia (in.)6...306...304...304...304...306...30
Airflow (Cfm)52,00052,00035,00035,00035,00052,000
Speed (Rpm)114011401140114011401140
Total Power (kW)9.49.56.46.46.49.2
CONDENSER FANS (6 Blade) — 50 Hz
Qty...Dia (in.)6...306...304...304...304...306...30
Airflow (Cfm)52,00052,00035,00035,00035,00052,000
Speed (Rpm)950950950950950950
Total Power (kW)9.49.56.46.46.49.2
CONDENSER COILEnhanced Copper Tubes, Aluminum Lanced Fin
Rows...Fins per in.3...173...173...173...173...172...19
Face Area (sq ft)128.3128.380.580.580.5116.7
Storage Capacity
(Lb per circuit) at 120 F
CONNECTIONS
Suction, ODF (in.)2
Liquid, ODF (in.)
Hot Gas Bypass, ODF (in.)
178178110110110110
1
⁄
8
7
⁄
8
5
⁄
8
21⁄
8
7
⁄
8
5
⁄
8
R-22
124134
124A124B134A134B
25⁄
8
11⁄
8
5
⁄
8
25⁄
8
11⁄
8
5
⁄
8
25⁄
8
11⁄
8
5
⁄
8
25⁄
11⁄
5
⁄
8
8
8
Table 4B — Units 38AH094-134 Physical Data — 50/60 Hz (SI)
Qty...Dia (mm)6...7626...7624...7624...7624...7626...762
Airflow (L/s)24,54424,54416,52016,52016,52024,544
Speed (R/s)191919191919
Total Power (kW)9.49.56.46.46.49.2
CONDENSER FANS (6 Blade) — 50 Hz
Qty...Dia (mm)6...7626...7624...7624...7624...7626...762
Airflow (L/s)24,54424,54416,52016,52016,52024,544
Speed (R/s)15.815.815.815.815.815.8
Total Power (kW)9.49.56.46.46.49.2
CONDENSER COILEnhanced Copper Tubes, Aluminum Lanced Fin
Rows...Fins per m3...669.33...669.33...669.33...669.33...669.32...781.6
Face Area (sq m)11.911.97.57.57.510.8
Storage Capacity
(Kg per circuit) at 49 C
CONNECTIONS
Suction, ODF (in.)2
Liquid, ODF (in.)
Hot Gas Bypass, ODF (in.)
LEGEND
Cu-Al — Copper Tubes with Aluminum Fins
Cu-Cu — Copper Tubes with Copper Fins
ODF— Outside Diameter, Female
*Includes piping and trim kit.
†Compressors are shipped with minimum oil charge.
**Capacity control steps listed are for constant volume units with no accesso-
ries. Refer to Table 20, page 48, for additional system capacity information.
818150505050
1
⁄
8
7
⁄
8
5
⁄
8
21⁄
8
7
⁄
8
5
⁄
8
NOTES:
1. Unit 38AH124 consists of one 124A module and one 124B module. Unit
38AH134 consists of one 134A module and one 134B module.
2. Certified dimensional drawings available on request.
3. Equivalent connection values in mm are as follows:
R-22
in.mm
5
⁄
8
7
⁄
8
11⁄
8
1
⁄
8
2
25⁄
8
124134
124A124B134A134B
25⁄
11⁄
5
15.9
22.2
28.6
54.0
66.7
8
8
⁄
8
25⁄
8
11⁄
8
5
⁄
8
25⁄
8
11⁄
8
5
⁄
8
25⁄
11⁄
5
⁄
8
8
8
11
CONTROL
BOX
Fig. 7 — Modules 38AH124A or 134A — Shipping Locations of Piping
and Sheet Metal Trim Kit
SHEET METAL COVER
PANEL (REMOVED)
RIG
HERE
RIG
HERE
RIG
HERE
RIG
HERE
Fig. 8 — Correct Placement of Modules Without Piping
and Sheet Metal Trim (Unit 38AH134 Shown)
12
24-in. (610-mm)
SERVICE SPACE
FACTORYINSTALLED
SUCTION
LINE LOOP
Fig. 9B — Field-Installed Suction Line Loop
Fig. 9A — Typical Module with Cover
Panels Removed
SHIPMENT BOLTS
38AH044-084,124,134
MOUNTING SPRINGS
38AH094,104
SHIPMENT BOLTS
MOUNTING
BOLTS
RAIL BOLT (3) (2 SHOWN)
MOUNTING
BOLTSRAIL BOLT (3) (2 SHOWN)
Fig. 10 — Outer View, Compressor Mounting
13
Step 3 — Make Refrigerant Piping
Connections
The field-supplied liquid line solenoid valve must be
installed at the evaporator to avoid possible compressor
damage during unit operation. See Fig. 11 (for 38AH044084 dual-circuit and 38AH094-134 units), or Fig. 12 (for
38AH044-084 optional single-circuit units).
The units have largesuctionlinestominimizefriction losses.
The units also have the ability to operate at low capacity.
Because of these capabilities, use special care with suction
piping and suction risers to ensure proper compressor oil
return under all operating conditions. Maximum allowable
vertical separation between the condensing unit and the evaporator is shown in Table 5. Size suction lines in accordance
with Tables 6A or 6B through 9A or 9B and Fig. 13. Mount
liquid line solenoid valve just ahead of the TXVs (thermostatic expansion valves) which will be mounted at the
evaporator. See Fig. 11 (for 38AH044-084 dual-circuit and
38AH094-134 units) or Fig. 12 (for 38AH044-084 optional
single-circuit units).
T oachievegood mixing of the refrigerant leaving the evaporator suction header for proper sensing by the TXV bulb:
1. Install a minimum of two 90-degree elbows upstream of
the TXV bulb location. See Fig. 14 (for 38AH044-084
dual-circuit and 38AH094-134 units) or Fig. 15 (for
38AH044-084 optional single-circuit units).
2. Locate the TXV bulb on a vertical riser, where possible.
If a horizontal location is necessary, secure the bulb at
approximately the 4 o’clock position.
3. Size the suction line from the evaporator to the common
suction line to achieve high refrigerant velocity. See
Tables 6A or 6B through 9A or 9B and Fig. 13.
If an oil return connection at the bottom of the suction
header is supplied with an evaporator, tee-in this connection
ahead of first mixing elbow. See Fig. 14 (for 38AH044-084
dual-circuit and 38AH094-134 units) or Fig. 15(for38AH044084 optional single-circuit units). When the compressor is
below the evaporator, the riser at the evaporator should extend to the top of the evaporator section. After the riser is
installed, the suction line can elbow down immediately.
Install a field-supplied filter drier and sight glasses in each
refrigerant system. Select the filter drier for maximum unit
capacity and minimum pressuredrop.Figure1 1(for 38AH044084 dual-circuit and 38AH094-134 units) or Fig. 12 (for
38AH044-084 optional single-circuit units) shows required
location of solenoid valves and recommended locations for
the filter driers and sight glasses. Complete the refrigerant
piping from the evaporator to the condenser before opening
the liquid and suction lines at the condenser.
UNITS 38AH044-084 — Relieve the pressurecaused by the
holding charge into a refrigerant recovery system. Uncap
the suction line and cut the run-around tube at the liquid line
as close to the loop elbow as possible. This will leave
approximately 2 in. (50 mm) of straight tube for liquid line
connection.
IMPORTANT: Protect the liquid valves from the heat
of brazing.
Leak test the entire system by using soap bubbles and
nitrogen or R-22 with an electronic leak detector.
Purge nitrogen or reclaim R-22 from system after completion of leak-checking procedure. Repair leak if one is
found. When finished, evacuate and dehydrate system using
the methods described in CarrierGTAC II (General Training
Air Conditioning II), Module 4, System Dehydration.
UNITS 38AH094-134 — Relieve the R-22 holding charge
of each circuit into a refrigerant recovery system. Remove
the liquid line to factory-installed suction line loop by cutting the loop at the liquid valve. (See Fig. 9A and 9B.) Cut
as close to the 90-degree bend in the loop as possible. The
remaining tube piece in the valve will be used for brazing
the liquid line. Unbraze and remove the cap from the liquid
line. For 38AH094 and 104 units, sweat-connect the liquid
and suction lines from the evaporator. For 38AH124 and 134
units, see Piping Kit Connections on page 21.
LEGEND
LLS — Liquid Line Solenoid
TXV — Thermostatic Expansion Valve
*Field-Supplied.
Fig. 11 — Required Location of Solenoid Valves and Recommended Filter Drier and
Sight Glass Locations for 38AH044-084 Dual-Circuit and 38AH094-134 Units
14
*Field-Supplied.
Fig. 12 — Required Location of Solenoid Valves and Recommended Filter Drier and
Sight Glass Locations for 38AH044-084 Optional Single-Circuit Units
LEGEND
A—Pipe A, Suction Riser, without Trap
B—Pipe B, Suction Riser with Trap
C—Suction Line to Condensing Unit
D—Pipe D, Suction Riser Short Lift
RED. — Reducer
STR — Street
NOTES:
1. Short riser, pipe D, is used when routing suction line to condensing unit connection. See table at right.
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)
UNIT
38AH
044
054
064
074
084
094
104
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
LEGEND
L—Liquid Line
S—Suction Line
*Double suction riser required on units with field installed unloader
on circuit B compressor if condensing unit is elevated above
evaporator.
†Double suction riser required on units with field installed unloader
on circuit B compressor if condensing unit is elevated above
evaporator.
**Double suction riser required on all unit configurations if condens-
ing unit is elevated above evaporator.
NOTES:
1. Addition of 2 unloaders to circuit B compressor is not
recommended.
2. 38AH094 and 38AH104 piping sizes apply only to factory supplied unit configurations. They do NOT take into account any field
installed unloaders.
3. Piping sizes are based on unit operation above 40F(4.4C)saturated suction temperature (SST). When operating below 40 F
(4.4 C),referto Carrier System Design Manual,E20-IIT pipingdesign program, or ASHRAE Handbook to select proper line sizes.
4. Pipe sizes are based on the total linear length shown for each
column, plus a 50% allowance for fittings.
15-25
(4.6-7.6)
25-50
(7.6-15.2)
(15.2-22.9)
LSLSL S L S L S L S
5
⁄
8
5
5
7
7
7
7
7
7
7
7
7
7
7
15⁄
⁄
8
15⁄
⁄
8
15⁄
⁄
8
15⁄
⁄
8
15⁄
⁄
8
21⁄
⁄
8
21⁄
⁄
8
21⁄
⁄
8
21⁄
⁄
8
21⁄
⁄
8
21⁄
⁄
8
21⁄
⁄
8
21⁄
⁄
8
21⁄
7
8
8
8
8
8
8
8
8
8
8
8
8
8
8
11⁄
11⁄
11⁄
11⁄
11⁄
11⁄
⁄
8
7
7
7
7
7
7
7
15⁄
⁄
8
15⁄
⁄
8
15⁄
⁄
8
21⁄
⁄
8
21⁄
⁄
8
21⁄
⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
⁄
8
21⁄
8
21⁄
8
21⁄
7
8
8
8
8
8
8
8
8
8
8
8
8
8
8
11⁄
11⁄
11⁄
11⁄
11⁄
11⁄
11⁄
⁄
8
7
⁄
8
7
⁄
8
7
⁄
8
7
⁄
8
7
⁄
8
7
⁄
8
8
8
8
8
8
8
8
50-75
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
25⁄8†11⁄825⁄8†13⁄825⁄8†13⁄831⁄8**
21⁄
8
25⁄8†11⁄825⁄8†13⁄825⁄8†13⁄831⁄8**
25⁄
8
5. Suction and liquid linesizingis based onpressuredrop equivalent
6. Double suction risers may be required if condensing unit is
7. Refer to Carrier System Design Manual or to E20-II design
8. All pipe sizes are OD inches. Equivalent sizes in millimeters
75-100
(22.9-30.5)
7
⁄
8
7
⁄
8
7
⁄
8
11⁄
7
⁄
8
11⁄
11⁄
11⁄
11⁄
11⁄
11⁄
11⁄
to 2 F (1.1 C) at nominal rating conditions. Higher pressure drop
design criteria may allow selection of smaller pipe sizes, but at a
penalty of decreased system capacity and efficiency.
elevated above the evaporator.Seefootnotes and double suction
riser table below.
programs for further information on selecting pipe sizes for split
systems.
21⁄
8
21⁄
8
21⁄
8
8
8
8
8
8
8
8
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
25⁄
8
25⁄8†13⁄825⁄8†13⁄825⁄8†
25⁄
8
25⁄
8
25⁄
8
100-150
(30.5-45.7)
7
⁄
8
7
⁄
8
7
⁄
8
11⁄
8
11⁄
8
11⁄
8
11⁄
8
13⁄
8
13⁄
8
11⁄
8
13⁄
8
11⁄
11⁄
11⁄
13⁄
13⁄
13⁄
7
⁄
8
7
⁄
8
7
⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
25⁄
8
25⁄8†11⁄825⁄8†
25⁄
8
25⁄
8
25⁄
8
31⁄8**13⁄
follow:
in.mm
5
⁄
11⁄
1
15⁄
2
25⁄
31⁄
8
7
⁄
8
8
3
⁄
8
8
1
⁄
8
8
8
15.9
22.2
28.6
34.9
41.3
54.0
66.7
79.4
150-200
(45.7-61.0)
21⁄
21⁄
21⁄
8
25⁄8*
8
25⁄8†
8
25⁄
8
25⁄
8
25⁄
8
25⁄
8
31⁄8**
8
8
8
8
8
8
8
Table 6B — Refrigerant Piping Requirements for Double Suction Risers,
38AH054-104 Dual-Circuit Units — 60 Hz
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)
UNIT
38AH
054
064
074
084
094
104
Ckt A————————————
Ckt B—————————1
Ckt A—————————1
Ckt B————————————
Ckt A——————1
Ckt B————————————
Ckt A———1
Ckt B————————————
Ckt A1
Ckt B————————————
Ckt A1
Ckt B——————1
LEGEND
——Not Required
Pipe A — Suction Riser Without Trap
Pipe B — Suction Riser With Trap
Pipe C — Suction Line to Condensing Unit
NOTES:
1. See Refrigerant Piping Requirements table at top of page to
determine need for double suction risers.
2. Pipe sizes are based on the total linear length, shown for each
column, plus a 50% allowance for fittings.
50-75
(15.2-22.9)
75-100
(22.9-30.5)
ABCABCABCABC
5
⁄82
5
⁄
8
21⁄
8
25⁄
8
15⁄
8
3
⁄
8
21⁄
8
25⁄
8
13⁄
8
1
⁄82
21⁄
8
21⁄
8
5
⁄81
25⁄
8
25⁄
8
3. Suction and liquid linesizingis based onpressuredrop equivalent
4. Refer to Carrier System Design Manual or to E20-II design
5. All pipe sizes are OD inches. See Table 6A notes for metric
6. Refer to Fig. 13 for double suction riser construction.
100-150
(30.5-45.7)
5
⁄82
5
⁄82
15⁄
8
13⁄
8
3
⁄82
to 2F(1.1 C) at nominalratingconditions. Higher design pressure
drop criteriamay allow selection ofsmallerpipe sizes butata penalty of decreased system capacity and efficiency.
programs for further information on selecting pipe sizes for split
systems.
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)
UNIT
38AH
044
054
064
074
084
094
104
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
LEGEND
L—Liquid Line
S—Suction Line
*Double suction riser required on units with field installed unloader
on circuit B compressor if condensing unit is elevated above
evaporator.
†Double suction riser required on units with field installed unloader
on circuit B compressor if condensing unit is elevated above
evaporator.
**Double suction riser required on all unit configurations if condens-
ing unit is elevated above evaporator.
NOTES:
1. Addition of 2 unloaders to circuit B compressor is not
recommended.
2. 38AH094 and 38AH104 piping sizes apply only to factory supplied unit configurations. They do NOT take into account any field
installed unloaders.
3. Piping sizes are based on unit operation above 40F(4.4C)saturated suction temperature (SST). When operating below 40 F
(4.4 C),referto Carrier System Design Manual,E20-IIT pipingdesign program, or ASHRAE Handbook to select proper line sizes.
4. Pipe sizes are based on the total linear length shown for each
column, plus a 50% allowance for fittings.
15-25
(4.6-7.6)
25-50
(7.6-15.2)
(15.2-22.9)
LSLSLSLSLSLS
5
⁄
8
13⁄
5
⁄
8
13⁄
5
⁄
8
13⁄
7
⁄
8
15⁄
7
⁄
8
15⁄
7
⁄
8
15⁄
7
⁄
8
15⁄
7
⁄
8
21⁄
7
⁄
8
21⁄
7
⁄
8
21⁄
7
⁄
8
21⁄
7
⁄
8
21⁄
7
⁄
8
21⁄
7
⁄
8
21⁄
7
8
8
8
8
8
8
8
8
8
8
8
8
8
8
11⁄
11⁄
⁄
8
7
7
7
7
7
7
7
7
7
7
7
15⁄
⁄
8
15⁄
⁄
8
15⁄
⁄
8
15⁄
⁄
8
15⁄
⁄
8
21⁄
⁄
8
21⁄
⁄
8
21⁄
⁄
8
21⁄
⁄
8
21⁄
8
21⁄
⁄
8
21⁄
⁄
8
21⁄
8
21⁄
7
8
⁄
8
7
8
⁄
8
7
8
⁄
8
7
8
⁄
8
7
8
⁄
8
7
8
⁄
8
7
8
⁄
11⁄
11⁄
11⁄
11⁄
11⁄
11⁄
11⁄
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
50-75
75-100
(22.9-30.5)
15⁄
8
15⁄
8
15⁄
8
21⁄
8
21⁄8†
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
25⁄8**11⁄
21⁄
8
21⁄
8
25⁄
8
7
⁄
8
7
⁄
8
7
⁄
8
7
⁄
8
7
⁄
8
7
⁄
8
7
⁄
8
11⁄
11⁄
11⁄
11⁄
11⁄
11⁄
5. Suction and liquid linesizingis based onpressuredrop equivalent
to 2 F (1.1 C) at nominal rating conditions. Higher pressure drop
design criteria may allow selection of smaller pipe sizes, but at a
penalty of decreased system capacity and efficiency.
6. Double suction risers may be required if condensing unit is
elevated above the evaporator.Seefootnotes and double suction
riser table below.
7. Refer to Carrier System Design Manual or to E20-II design
programs for further information on selecting pipe sizes for split
systems.
8. All pipe sizes are OD inches. Equivalent sizes in millimeters
follow:
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄8†11⁄821⁄8†11⁄825⁄8**
21⁄
8
21⁄
8
8
8
8
8
8
8
8
25⁄
8
25⁄8†11⁄825⁄8†11⁄825⁄8†
25⁄
8
25⁄8**11⁄
25⁄8*†11⁄
25⁄8**11⁄
25⁄
8
100-150
(30.5-45.7)
7
⁄
8
7
⁄
8
7
⁄
8
11⁄
8
11⁄
8
11⁄
8
11⁄
8
11⁄
8
8
8
8
13⁄
8
150-200
(45.7-61.0)
11⁄
7
⁄
8
7
⁄
8
7
⁄
8
8
21⁄
21⁄
21⁄
21⁄
8
8
8
8
25⁄8*11⁄82
25⁄8†11⁄825⁄8†
25⁄
8
25⁄
8
25⁄8**13⁄
25⁄8*†11⁄
25⁄8**13⁄
25⁄
8
11⁄
11⁄
13⁄
8
8
8
8
8
8
in.mm
5
⁄
11⁄
1
15⁄
2
25⁄
31⁄
8
7
⁄
8
8
3
⁄
8
8
1
⁄
8
8
8
15.9
22.2
28.6
34.9
41.3
54.0
66.7
79.4
21⁄
8
21⁄
8
21⁄
8
25⁄8*†
5
⁄
8
25⁄
8
25⁄
8
31⁄8**
25⁄8*†
31⁄8**
31⁄8**
*
Table 7B— Refrigerant Piping Requirements for Double Suction Risers,
38AH054-104 Dual-Circuit Units — 50 Hz
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)
UNIT
38AH
054
064
074
084
094
104
Ckt A————————————
Ckt B—————————1
Ckt A13⁄
Ckt B——————1
Ckt A——————1
Ckt B————————————
Ckt A———1
Ckt B————————————
Ckt A1
Ckt B———1
Ckt A———1
Ckt B—————————1
LEGEND
——Not Required
Pipe A — Suction Riser Without Trap
Pipe B — Suction Riser With Trap
Pipe C — Suction Line to Condensing Unit
NOTES:
1. See Refrigerant Piping Requirements table at top of page to
determine need for double suction risers.
2. Pipe sizes are based on the total linear length, shown for each
column, plus a 50% allowance for fittings.
50-75
(15.2-22.9)
75-100
(22.9-30.5)
ABCABCABCABC
8
15⁄
8
21⁄
8
13⁄
8
5
⁄82
3
⁄
8
21⁄
8
25⁄
8
13⁄
8
3
⁄82
3
⁄82
15⁄
8
21⁄
8
1
⁄82
21⁄
8
1
⁄82
1
⁄82
5
⁄81
25⁄
8
5
⁄81
5
⁄81
3. Suction and liquid linesizingis based onpressuredrop equivalent
4. Refer to Carrier System Design Manual or to E20-II design
5. All pipe sizes are OD inches. See Table 7A notes for metric
6. Refer to Fig. 13 for double suction riser construction.
100-150
(30.5-45.7)
15⁄
8
15⁄
8
21⁄
5
⁄82
5
⁄82
5
⁄82
15⁄
8
5
⁄82
5
⁄82
to 2F(1.1 C) at nominalratingconditions. Higher design pressure
drop criteriamay allow selection ofsmallerpipe sizes butata penalty of decreased system capacity and efficiency.
programs for further information on selecting pipe sizes for split
systems.
1
⁄82
1
⁄82
1
⁄82
21⁄
8
1
⁄82
1
⁄82
8
5
⁄81
5
⁄81
5
⁄81
25⁄
8
5
⁄81
5
⁄81
150-200
(45.7-61.0)
5
⁄82
15⁄
8
5
⁄82
5
⁄82
5
⁄82
15⁄
8
5
⁄82
5
⁄82
5
⁄82
1
⁄82
21⁄
8
1
⁄82
1
⁄82
1
⁄82
25⁄
8
1
⁄82
5
⁄83
5
⁄83
5
⁄
8
25⁄
8
5
⁄
8
5
⁄
8
5
⁄
8
31⁄
8
5
⁄
8
1
⁄
8
1
⁄
8
equivalents.
17
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.