Carrier 38AH044-084 User Manual

Page 1
Air-Cooled Condensing Units
Installation, Start-Up and
Service Instructions
38AH044-134
50/60 Hz
CONTENTS
SAFETY CONSIDERATIONS ................ 1
INSTALLATION ............................ 1-37
Step 1 — Rig and Place Unit ............... 1
• DOMESTIC UNITS
• PLACING UNITS
Step 2 — Check Compressor Mounting ..... 3
• UNITS 38AH044-084
• UNITS 38AH094-134
Step 3 — Make Refrigerant Piping
Connections .............................. 14
• UNITS 38AH044-084
• UNITS 38AH094-134
Step 4 — Make Electrical Connections ...... 23
• POWER SUPPLY
• FIELD POWER CONNECTIONS
• MAIN POWER
• CONTROL CIRCUIT WIRING
Step 5 — Install Accessories ............... 37
• LOW-AMBIENT OPERATION
• MISCELLANEOUS ACCESSORIES
PRE-START-UP .......................... 37,38
START-UP ................................38-45
SERVICE ..................................46-49
CONTROL ................................49-52
TROUBLESHOOTING ......................53,54
START-UP CHECKLIST ...............CL-1, CL-2
Page
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be hazardous due to system pressures, electrical compo­nents, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install, start up, and service this equipment.
Untrained personnel can perform basic maintenancefunc­tions, such as cleaning coils. All other operations should be performed by trained service personnel.
When working on the equipment, observe precautions in the literature, and on tags,stickers, and labels attached to the equipment and any other safety precautions that may apply.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Use care in handling, rigging, and setting bulky
equipment.
ELECTRIC SHOCK HAZARD. Open all remote disconnects before servicing
this equipment.
INSTALLATION
Step 1 — Rig and Place Unit —
designed for overhead rigging, and it is important that this method be used. Lifting holes are provided in the frame base
rails, which are marked for rigging (see rigging label on the unit and Tables 1, 2A, and 2B for rigging weights and center of gravity). It is recommended that field-supplied pipes, of sufficient length to extend at least 12-in. (305 mm) beyond the frame, be passed through the holes.
To maintain unit stability while lifting, use 4 cables, chains, or straps of equal length. Attach one end of each cable to one pipe end and the other end of each cable to the overhead rigging point.
Use spreader bars or frame to keep the cables, chains,
and straps clear of the unit sides. Leave standard coil pro-
tection packaging in place during rigging to provide protec­tion to coils. Remove and discard all coil protection after rigging cables are detached.
DOMESTIC UNITS — For units 38AH044-084, 124, and 134; standard unit packaging consists of coilprotection only. There is no standard packaging provided for units 38AH094 and 104. Skids are not provided. If overhead rigging is not available at the jobsite,place the unit on a skid or pad before dragging or rolling. When rolling, use a minimum of 3 rollers. When dragging, pull the pad or skid. Do not apply force to the unit. When in final position, raise from above to lift unit off the pad or skid.
EXPORT UNITS — All export units are mounted on skids with vertical coil protection. Leave the unit on the skid until it is in final position. Whileon the skid, the unit can be rolled or skidded. Apply force to the skid, not to the unit. Use a minimum of 3 rollers when rolling. When in final position, raise from above to remove the skid.
PLACING UNITS Units 38AH044-084 — RefertoFig.1and 2 for airflow clear-
ances. Recommended minimum clearances are 6 ft (1829 mm) for unrestricted airflow and service on sides of unit, 5 ft (1524 mm) on ends, and unrestricted clear air space above the unit. Provide ample space to connect liquid and suction lines to indoor unit. For multiple units, allow 8 ft(2440 mm) separation between units for airflow and service.
Do not forklift these units unless the unit is attached to a skid designed for forklifting.
All units are
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 Tab 3a
PC 111 Catalog No. 563-704 Printed in U.S.A. Form 38AH-15SI Pg 1 10-98 Replaces: 38AH-14SI
Page 2
The placement area must be level and strong enough to support the operating weight of the unit (see Table 3A or 3B). When unit is in proper location, use of mounting holes in base rails is recommended for securing unit to supporting structure. For mounting unit on vibration isolators, a perim­eter support channel between the unit and the isolators is recommended. Fasteners for mounting unit are field sup­plied. Be sure to mount unit level to ensure proper oil return to compressors.
Units 38AH094-134 — Refer to Fig. 3-6 for airflow clearances. Recommended minimum clearances are 6 ft (1829 mm) for unrestricted airflow and service on sides of unit, 5 ft (1524 mm) on ends, and unrestricted clear air space above unit. Provide ample space to connect liquid and suc­tion lines to indoor unit. For multiple units, allow 8 ft (2440 mm) separation between units for airflow and service.
Do not forklift these units unless the unit is attached to a skid designed for forklifting.
The placement area must be level and strong enough to support the operating weight of the unit. See Table 4A or 4B. Refer to the following paragraphs for theproperplace­ment of the unit.
Units 38AH094,104 — For mounting units on vibration iso­lators, a perimeter support channel is required between the unit and the support isolators. The perimeter support chan­nel must be sizedto support the fully assembled unit. Do not
support units on individual isolationsupports. Support chan­nel, hardware, and fasteners are field supplied. When unit is in proper location, level unit and bolt intoposition with field­supplied bolts.
Units 38AH124,134 — For ease of shipment and handling, unit 38AH124 is shipped as 2 modules (124A and 124B) and unit 38AH134 is shipped as 2 modules (134Aand 134B). The modules must be connected at the final installation site with thefactory-shippedpipingandsheet metal trim kit mounted on Module 124A or 134A. See Fig. 7.
Do not move assembled 38AH124 or 134 units as a single assembly. Always move modules individually during in­stallation or at any other time.
Mark installation site for placement of Modules 124A and 124B or Modules 134A and 134B. See Table 4A or 4B for final assembled dimensions. A service space of 24 in. (610 mm) is required between the 2 modules for piping and sheet metal trim installation.
Place Module 124Aor 134Ain position, ensuring that the control box is at the end opposite the service space. See Fig. 8.
Remove sheet metal and tubing from Module 124Aor 134A sheet metal trim kit (Fig. 7). Remove sheet metal cover pan­els from return-bend end of unit facing the service space. See Fig. 8. These panels may be discarded or saved for reinstallation if module is moved from site. See Fig. 9.
Table 1 — Rigging Center of Gravity — in. (mm)
UNIT
38AH
Dimension X 49 (1232) 48 (1224) 50 (1260) 57 (1443) 57 (1448) 66 (1676) 63 (1600) 50 (1260) 50 (1260) Dimension Y 39 (984) 39 (978) 38 (968) 39 (993) 39 (991) 31 (787) 34 (851) 38 (968) 38 (968) Dimension X-C 49 (1234) 48 (1229) 50 (1261) 56 (1425) 56 (1422) 66 (1676) 63 (1600) 50 (1260) 50 (1260) Dimension Y-C 39 (993) 39 (991) 39 (986) 40 (1006) 40 (1008) 31 (787) 34 (851) 39 (986) 39 (986) Dimension K ————————50(1260) 57 (1443) Dimension L ————————38(968) 39 (993) Dimension K-C ————————50(1260) 56 (1425) Dimension L-C ————————39(986) 40 (1006)
LEGEND
——Not Applicable C—Copper Fin Coils
044 054 064 074 084 094 104
TOP VIEW, TYPICAL
MODULE
124A
124, 134 ONLY
MODULE
124B
MODULE
134A
MODULE
134B
2
Page 3
Remove sheet metal cover panels fromreturn-bend end of Module 124B or 134B. Place Module 124B or 134B in position. The exposed return-bend ends of each module are now opposite each other and facing the service space. The compressors of each module are on opposite sidesofthe unit.
IMPORTANT: Modules must be placed 24 in. (610 mm) apart and square relative to each other.
The modules are now in position for piping installa­tion and final assembly. See Fig. 8. For mounting units on vibration isolators, a perimeter support channel is required between the assembled unit and the support isolators. The perimeter support channel must be sized to support the fully assembled unit. Do not support modules on individual iso­lation supports. Support channel, hardware, and fastenersare field supplied.
When unit is in proper location, level unit and bolt into position with field-supplied bolts.
Step 2 — Check Compressor Mounting
UNITS 38AH044-084 — Compressors are mountedon pans and are held down by 4 bolts during shipment. After unit is installed, loosen each of these bolts until the snubber washer can be moved with finger pressure. See Fig. 10.
UNITS 38AH094-134 — Units 38AH094 and104 compres­sors are mounted on rails and held down by rail bolts during shipment. After unit is installed, loosen the rail bolts to al­low the rails and compressors to float freely on the springs located under the rails. See Fig. 10.
Units 38AH124 and 134 compressors are mounted on pans and are held down by 4 bolts during shipment. After unit is installed, loosen each of these bolts untilsnubber washer can be moved with finger pressure. See Fig. 10.
Table 2A — Operational Corner Weights with
Refrigerant Charge (Approximate) — Lb
UNIT
38AH
044 3259 939 893 695 732 044C 3547 1013 967 765 802 054 3309 964 905 697 742 054C 3597 1034 978 771 814 064 3565 1018 1011 765 771 064C 3998 1125 1117 874 879 074 3812 1146 986 777 903 074C 4229 1272 1059 862 1035 084 4057 1220 1049 827 961 084C 4735 1425 1186 965 1159 094 5088 1114 2192 1182 601 094C 5813 1273 2504 1350 686 104 5435 1240 2138 1302 755 104C 6160 1405 2423 1476 856 MODULE
38AH 124A 3630 1037 1030 779 785 124A-C 4063 1144 1137 889 894 124B 3630 1037 1030 779 785 124B-C 4063 1144 1137 889 894 134A 3630 1037 1030 779 785 134A-C 4063 1144 1137 889 894 134B 3877 1167 997 789 924 134B-C 4294 1293 1080 874 1047
C—Copper Fin Coils
NOTE:Totalweight may differ fromsummationof corner weights due to rounding of numerals.
TOTAL
WEIGHT
LEGEND
OPERATIONAL CORNER WEIGHT
ABCD
Table 2B — Operational Corner Weights with
Refrigerant Charge (Approximate) — Kg
UNIT
38AH
044 1478 426 405 316 332 044C 1609 460 438 347 364 054 1501 437 411 316 337 054C 1632 469 444 350 369 064 1617 462 459 347 350 064C 1813 510 508 397 399 074 1729 520 447 352 410 074C 1918 577 481 391 470 084 1840 553 476 375 436 084C 2148 646 538 438 526 094 2308 505 994 536 272 094C 2637 577 1136 612 311 104 2465 562 970 591 342 104C 2794 637 1099 670 388 MODULE
38AH 124A 1647 470 467 353 356 124A-C 1843 519 516 403 405 124B 1647 470 467 353 356 124B-C 1843 519 516 403 405 134A 1647 470 467 353 356 134A-C 1843 519 516 403 405 134B 1759 529 452 358 419 134B-C 1948 587 490 396 475
C—Copper Fin Coils
NOTE:Totalweight may differ fromsummationof corner weights due to rounding of numerals.
TOTAL
WEIGHT
LEGEND
OPERATIONAL CORNER WEIGHT
ABCD
TOP VIEW, TYPICAL
3
Page 4
SUCTION CONNECTION(S)
LIQUID CONNECTION(S)
21⁄89 Dia [54 mm] 25⁄89 Dia [67 mm]
7
SUCTION C 28- LIQUID D 18-10 SUCTION (Ckt A) 18-7 SUCTION (Ckt B) 28- LIQUID (Ckt A) 28-5 LIQUID (Ckt B) 28-10
DUAL CKT SINGLE CKT
⁄89 Dia [22 mm] 11⁄89 Dia [29 mm]
11
⁄169 [627mm] 18-105⁄169 [567mm]
1
⁄169 [561mm] 18-105⁄169 [567mm]
13
⁄169 [503mm] 28-5⁄89 [626mm]
5
⁄89 [626mm]
3
⁄49 [756mm] 28-105⁄89 [879mm]
5
⁄89 [879mm]
Chart 1, Field Power Supply Connections
UNIT VOLTAGE Hz DIAMETER — in. [mm] QTY
044 230 50 3
044, 054
208/230 60 3
346, 380/415 50 2
044, 054, 064 460,575,380 60 2
064
C—Copper Fin Coils MTG — Mounting SAE — Society of Automotive Engineers
NOTES:
1. The approximate operating weight of the unit is: 38AH-044--- 3259 lb [1478 kg] 38AH-044--C 3547 lb [1609 kg] 38AH-054--- 3309 lb [1501 kg] 38AH-054--C 3597 lb [1632 kg] 38AH-064--- 3565 lb [1617 kg] 38AH-064--C 3998 lb [1813 kg]
2. Unit must have clearances for airflow as follows: Top — Do not restrict in any way. Ends—5ft[1524 mm] Sides—6ft[1829 mm]
3. Mounting holes may be used to mountunit to concrete pad. They are not recommended for mounting unit to spring isolators. If spring isolators are used, a perimeter support channel between the unit and the isolators is recommended.
4. One 3
5. See Table1 forrigging center ofgravity (DimensionsX,Y). SeeTable2Aand 2B for A-Dcorner weights.
6. Circled numerals in Top View refer to condenser fans by position.
208/230 60 2
346, 380/415 50 3
LEGEND
5
⁄89 (92mm) diameter holeis recommendedfor single-entry poweron size 064(208/230-v) units.
5
⁄8[92] 1
5
⁄8[92] 1
1
⁄2[63] 1
1
⁄2[63] 1
1
⁄2[63] 2
5
⁄8[92] 1
Fig. 1 — Dimensions — Units 38AH044,054,064
4
Page 5
SUCTION CONNECTION(S)
LIQUID CONNECTION(S)
21⁄89 Dia [54 mm] 25⁄89 Dia [67 mm]
7
SUCTION C 28- LIQUID D 18-10 SUCTION (Ckt A) 18-7 SUCTION (Ckt B) 28- LIQUID (Ckt A) 28-5 LIQUID (Ckt B) 28-10
DUAL CKT SINGLE CKT
⁄89 Dia [22 mm] 11⁄89 Dia [29 mm]
11
⁄169 [627mm] 18-105⁄169 [567mm]
1
⁄169 [561mm] 18-105⁄169 [567mm]
13
⁄169 [503mm] 28-5⁄89 [626mm]
5
⁄89 [626mm]
3
⁄49 [756mm] 28-105⁄89 [879mm]
5
⁄89 [879mm]
Chart 1, Field Power Supply Connections
UNIT VOLTAGE Hz DIAMETER — in. [mm] QTY
074
208/230 60 2
460 60 2
346, 380/415 50 3
074, 084
380 60 3 575 60 2
084
208/230 60 3
460 60 3
1
⁄2[63] 2
1
⁄2[63] 1
5
⁄8[92] 1
5
⁄8[92] 1
1
⁄2[63] 1
5
⁄8[92] 2
5
⁄8[92] 1
LEGEND
C—Copper Fin Coils MTG — Mounting SAE — Society of Automotive Engineers
NOTES:
1. The approximate operating weight of the unit is: 38AH-074--- 3812 lb (1729 kg) 38AH-074--C 4229 lb (1918 kg) 38AH-084--- 4057 lb (1840 kg) 38AH-084--C 4735 lb (2148 kg)
2. Unit must have clearances for airflow as follows: Top — Do not restrict in any way. Ends—5ft[1524 mm] Sides—6ft[1829 mm]
3. Mounting holes maybe used to mountunit to concrete pad. They are notrecommended for mounting unit to spring isolators. If spring isolators are used, a perimeter support channel between the unit and the iso­lators is recommended.
4. See Table 1 for rigging center of gravity (Dimensions X,Y). See Table 2A and 2B for A-D corner weights.
5. Circled numerals in Top View refer to condenser fans by position.
Fig. 2 — Dimensions — Units 38AH074,084
5
Page 6
Chart 1, Field Power Supply Connections
UNIT
38AH
VOLTAGE Hz DIAMETER — in. (mm) QUANTITY
208/230 60 3
460, 575,
094
380
346, 380/415 50 3
60 3
5
5
5
⁄8(92) 2 ⁄8(92) 1 ⁄8(92) 1
Fig. 3 — Dimensions — Unit 38AH094
LEGEND
C—Copper Fin Coils MTG — Mounting SAE — Society of Automotive Engineers
NOTES:
1. The approximate operating weight of the unit is: 38AH-094--- 5088 lb (2308 kg) 38AH-094--C 5813 lb (2637 kg)
2. Unit must have clearances for airflow as follows: Top — Do not restrict in any way. Ends—5ft[1524 mm] Sides—6ft[1829 mm]
3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting unit to spring isolators.
5
4. Two 3
5. Circled numerals in Top View refer to condenser fans by position.
6. If spring isolators are used, a perimeter support channel between the unit
7. See Table 1 for rigging center of gravity (Dimensions X,Y). See Table 2A
⁄89 (92-mm) dia holes are recommended for parallel conductors on
208/230 v units.
and the isolators is recommended. and 2B for A-D corner weights.
6
Page 7
Chart 1, Field Power Supply Connections
UNIT
38AH
VOLTAGE Hz DIAMETER — in. (mm) QUANTITY
208/230 60 3
104
460, 575,
380
60 3
346, 380/415 50 3
5
⁄8(92) 2
5
⁄8(92) 1
5
⁄8(92) 1
Fig. 4 — Dimensions — Unit 38AH104
LEGEND
C—Copper Fin Coils MTG — Mounting SAE — Society of Automotive Engineers
NOTES:
1. The approximate operating weight of the unit is: 38AH-104--- 5435 lb (2465 kg) 38AH-104--C 6160 lb (2794 kg)
2. Unit must have clearances for airflow as follows: Top — Do not restrict in any way. Ends—5ft[1524 mm] Sides—6ft[1829 mm]
3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting unit to spring isolators.
5
4. Two 3
5. Circled numerals in Top View refer to condenser fans by position.
6. If spring isolators are used, a perimeter support channel between the unit
7. See Table 1 for rigging center of gravity (Dimensions X,Y). See Table 2A
⁄89 (92-mm) dia holes are recommended for parallel conductors on
208/230 v units.
and the isolators is recommended. and 2B for A-D corner weights.
7
Page 8
Chart 1, Field Power Supply Connections
UNIT
38AH
VOLTAGE Hz
208/230 60 3
124A 124B
460, 575,
380
346, 380/415 50 3
LEGEND
C—Copper Fin Coils MTG — Mounting SAE — Society of Automotive Engineers
DIAMETER
60 2
(in.)
5
⁄8(92) 1
1
⁄2(63) 1
5
⁄8(92) 1
NOTES:
1. The approximate operating weight of the unit is:
QUANTITY
38AH-124--- 7260 lb (3293 kg) 38AH-124--C 8126 lb (3686 kg)
2. Unit must have clearances for airflow as follows: Top — Do not restrict in any way. Ends—5ft[1524 mm] Sides—6ft[1829 mm]
3. Mounting holes may be usedto mount unit to concrete pad. They are notrec­ommended for mounting unit to spring isolators.
5
4. One 3
5. Circled numerals in Top View refer to condenser fans by position.
6. If spring isolatorsare used, a perimeter support channelbetween the unit and
7. Each module ofthe unit must berigged into position separately.The unit must
8. Suction and liquid connections can exit on either side of the unit.
9. Field power supply connections are required for each module.
10. See Table 1 for rigging center of gravity (Dimensions K,L,X,Y). See Table 2A
⁄89 (92-mm) dia hole is recommended for single-entry power into each
module (124A and 124B) of the 208/230-v units.
the isolators is recommended. Do not support each module separately. not be rigged after modules have been connected.
and 2B for A-D corner weights.
Fig. 5 — Dimensions — Unit 38AH124
8
Page 9
Chart 1, Field Power Supply Connections
UNIT
38AH
134A
134B
C—Copper Fin Coils MTG — Mounting SAE — Society of Automotive Engineers
VOLTAGE Hz
208/230 60 3
460, 575, 380 60 2
346, 380/415 50 3
208/230 60 2
460, 575 60 2
380 60 3
346, 380/415 50 3
LEGEND
DIAMETER —
in. (mm)
5
⁄8(92) 1
1
⁄2(63) 1
5
⁄8(92) 1
1
⁄2(63) 2
1
⁄2(63) 1
5
⁄8(92) 1
5
⁄8(92) 1
Fig. 6 — Dimensions — Unit 38AH134
QUANTITY
NOTES:
1. The approximate operating weight of the unit is: 38AH-134--- 7507 lb (3405 kg) 38AH-134--C 8357 lb (3791 kg)
2. Unit must have clearances for airflow as follows: Top — Do not restrict in any way. Ends—5ft[1524 mm] Sides—6ft[1829 mm]
3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting unit to spring isolators.
5
4. One 3
5. Circled numerals in Top View refer to condenser fans by position.
6. If spring isolators are used, a perimeter support channel between the as-
7. Each module of the unit must be rigged into position separately. The unit
8. Suction and liquid connections can exit on either side of the unit.
9. Field power supply connections are required for each module.
10. See Table1A or1B for rigging centerof gravity (DimensionsK,L,X,Y). See
⁄89 (92-mm) dia hole is recommended for single-entry power into Module 134Aand 208/230-vunits.Single entry powerinto Module 134Bis not recommended.
sembled unitand theisolators isrecommended.Do notsupport eachmod­ule separately.
must not be rigged after modules have been connected.
Table 2A and 2B for A-D corner weights.
9
Page 10
Table 3A — Units 38AH044-084 Physical Data — 50/60 Hz (English)
38AH 044 054 064 074 084 OPERATING WEIGHT WITH Cu-Al 3259 3309 3565 3812 4057
REFRIGERANT (Approx) — Lb Cu-Cu 3547 3597 3998 4229 4735
SHIP WEIGHT WITH COIL PROTECTION ONLY
(Approx) — Lb Cu-Al 3250 3290 3530 3780 4000
TYPICAL OPERATING REFRIGERANT R-22
Charge (Approx) — Lb 62 72 88 104 130 Qty of Circuits Std 22222
COMPRESSOR Type...Rpm Reciprocating Semi-Hermetic...1750 @ 60 Hz; 1458 @ 50 Hz
(Qty Cylinder) Compressor* Std (4) A1 (4) B1 (4) A1 (6) B1 (6) A1 (6) B1 (6) A1 (6) B1 (6) A1 (6) B1 Model No. 06E Std 250 250 250 265 265 275 275 299 299 299 (Qty Cylinder) Compressor* Opt (4) A1 (4) A2 (6) A1 (4) A2 (6) A1 (6) A2 (6) A1 (6) A2 (6) A1 (6) A2 Model No. 06E Opt 250 250 265 250 275 265 299 275 299 299 Oil Charge (Pt) Std 17 17 17 21 21 21 21 19 19 19
Capacity Control Steps† 4
CONDENSER FANS (6 Blade) — 60 Hz
Qty...Dia (in.) 4...30 6...30 Airflow (Cfm) 35,000 52,000 51,000 Speed (Rpm) 1140 1140 Total Power (kW) 6.2 9.3
CONDENSER FANS (6 Blade) — 50 Hz
Qty...Dia (in.) 4...30 6...30 Airflow (Cfm) 35,000 52,000 51,000 Speed (Rpm) 950 950 Total Power (kW) 6.2 9.3
CONDENSER COIL Enhanced Copper Tubes, Aluminum Lanced Fin
Rows...Fins per in. 2...17 2...17 3...17 2...19 3...17 Face Area (sq ft) 80.5 80.5 80.5 116.7 116.7 Storage Capacity (Lb per Circuit) at 120 F 35 35 55 55 80
CONNECTIONS
Suction, ODF (in.)** 2 Liquid, ODF (in.)** Hot Gas Bypass, ODF (in.)
Cu-Cu 3538 3578 3963 4197 4678
Opt 11111
Opt 17 17 21 17 21 21 19 21 19 19
1
8
7
8
5
8
Table 3B — Units 38AH044-084 Physical Data — 50/60 Hz (SI)
38AH 044 054 064 074 084 OPERATING WEIGHT WITH Cu-Al 1478 1501 1617 1729 1840
REFRIGERANT (Approx) — Kg Cu-Cu 1609 1632 1813 1918 2148
SHIP WEIGHT WITH COIL PROTECTION ONLY
(Approx) — Kg Cu-Al 1474 1492 1601 1715 1814
TYPICAL OPERATING REFRIGERANT R-22
CHARGE (Approx) — Kg 28.1 32.7 39.9 47.2 58.9 Qty of Circuits Std 22222
COMPRESSOR Type...R/s Reciprocating Semi-Hermetic...29.2 @ 60 Hz; 24.3 @ 50 Hz
(Qty Cylinder) Compressor* Std (4) A1 (4) B1 (4) A1 (6) B1 (6) A1 (6) B1 (6) A1 (6) B1 (6) A1 (6) B1 Model No. 06E Std 250 250 250 265 265 275 275 299 299 299 (Qty) Cylinder) Compressor* Opt (4) A1 (4) A2 (6) A1 (4) A2 (6) A1 (6) A2 (6) A1 (6) A2 (6) A1 (6) A2 Model No. 06E Opt 250 250 265 250 275 265 299 275 299 299 Oil Charge (L) Std 8.0 8.0 8.0 9.9 9.9 9.9 9.9 9.0 9.0 9.0
Capacity Control Steps† 4
CONDENSER FANS (6 Blade) — 50 Hz
Qty...Dia (mm) 4...762 6...762 Airflow (L/s) 16,500 24,500 24,100 Speed (R/s) 15.8 15.8 Total Power (kW) 6.2 9.3
CONDENSER FANS (6 Blade) — 60 Hz
Qty...Dia (mm) 4...762 6...762 Airflow (L/s) 16,500 24,500 24,100 Speed (R/s) 19.0 19.0 Total Power (kW) 6.2 9.3
CONDENSER COIL Enhanced Copper Tubes, Aluminum Lanced Fin
Rows...Fins per m 2...669 2...669 3...669 2...782 3...669 Face Area (sq m) 7.48 7.48 7.48 10.84 10.84 Storage Capacity (Kg per Circuit) at 48.9 C 16 16 25 25 36
CONNECTIONS
Suction, ODF (in.)** 2 Liquid, ODF (in.)** Hot Gas Bypass, ODF (in.)
LEGEND
Cu-Al — Copper tubes with aluminum fins Cu-Cu — Copper tubes with copper fins ODF Outside Diameter, Female Opt Optional Single-Circuit Units Std Standard Dual-Circuit Units
*Compressor A1 is lead on standard and optional single-circuit units.
†Capacity control steps listed are for constant-volume units with no accesso-
ries. Refer to Table 19A or 19B, page 48, for additional system capacity information.
Cu-Cu 1605 1623 1798 1904 2122
Opt 11111
Opt 8.0 8.0 9.9 8.0 9.9 9.9 9.0 9.9 9.0 9.0
1
8
7
8
5
8
**For single-circuit units, suction ODF is 2
11⁄8in. (28.6 mm). Single circuits have a factory-installed manifold; no
field modification is required.
NOTES:
1. Certified dimensional drawings available on request.
2. Equivalent connection values in mm are as follows:
5
⁄8in. (66.7 mm) and liquid ODF is
in. mm
5
8
15.9
7
8
22.2
1
8
54.0
2
10
Page 11
Table 4A — Units 38AH094-134 Physical Data — 50/60 Hz (English)
38AH 094 104
OPERATING WEIGHT WITH Cu-Al 5088 5435 3630* 3630* 3630* 3877*
REFRIGERANT (Approx) — Lb Cu-Cu 5813 6160 4063* 4063* 4063* 4294*
SHIP WEIGHT WITH Cu-Al 5630 5990 3907* 3907* 3907* 4080*
COIL PROTECTION AND SKID Cu-Cu 6355 6715 4340* 4340* 4340* 4497* (Approx) — Lb
TYPICAL OPERATING
REFRIGERANT CHARGE (Approx) — Lb 148 135 88 88 88 104
Qty of Circuits 2 2 1111
COMPRESSOR Type...Rpm Reciprocating Semi-Hermetic...1750 @ 60 Hz; 1460 @ 50 Hz
(Qty Cylinder) Compressor† (6)A1 (4)A2 (6)B1 (6)A1 (4)A2 (6)B1 (6)B2 (6)A1 (6)A2 (6)A1 (6)A2 (6)A1 (6)A2 (6)A1 (6)A2 Model No. 06E −275 −250 −299 −265 −250 −265 −265 −275 −265 −275 −265 −275 −265 −299 −275 Oil Charge (Pt) 21 17 19 21 17 21 21 21 21 21 21 21 21 19 21 Capacity Control Steps** 5 6 3333
CONDENSER FANS (6 Blade) — 60 Hz
Qty...Dia (in.) 6...30 6...30 4...30 4...30 4...30 6...30 Airflow (Cfm) 52,000 52,000 35,000 35,000 35,000 52,000 Speed (Rpm) 1140 1140 1140 1140 1140 1140 Total Power (kW) 9.4 9.5 6.4 6.4 6.4 9.2
CONDENSER FANS (6 Blade) — 50 Hz
Qty...Dia (in.) 6...30 6...30 4...30 4...30 4...30 6...30 Airflow (Cfm) 52,000 52,000 35,000 35,000 35,000 52,000 Speed (Rpm) 950 950 950 950 950 950 Total Power (kW) 9.4 9.5 6.4 6.4 6.4 9.2
CONDENSER COIL Enhanced Copper Tubes, Aluminum Lanced Fin
Rows...Fins per in. 3...17 3...17 3...17 3...17 3...17 2...19 Face Area (sq ft) 128.3 128.3 80.5 80.5 80.5 116.7 Storage Capacity
(Lb per circuit) at 120 F
CONNECTIONS
Suction, ODF (in.) 2 Liquid, ODF (in.) Hot Gas Bypass, ODF (in.)
178 178 110 110 110 110
1
8
7
8
5
8
21⁄
8
7
8
5
8
R-22
124 134
124A 124B 134A 134B
25⁄
8
11⁄
8
5
8
25⁄
8
11⁄
8
5
8
25⁄
8
11⁄
8
5
8
25⁄ 11⁄
5
8 8
8
Table 4B — Units 38AH094-134 Physical Data — 50/60 Hz (SI)
38AH 094 104
OPERATING WEIGHT WITH Cu-Al 2308 2465 1647* 1647* 1647* 1759*
REFRIGERANT (Approx) — Kg Cu-Cu 2637 2794 1843* 1843* 1843* 1948*
SHIP WEIGHT WITH Cu-Al 2554 2717 1860* 1860* 1860* 1851*
COIL PROTECTION AND SKID Cu-Cu 2883 3046 1968* 1968* 1968* 1968* (Approx) — Kg
TYPICAL OPERATING
REFRIGERANT CHARGE (Approx) — Kg 67.1 61.2 39.9 39.9 39.9 47.2
Qty of Circuits 2 2 1111
COMPRESSOR Type...R/s Reciprocating Semi-Hermetic...29.2 @ 60 Hz; 24.3 @ 50 Hz
(Qty Cyliner) Compressor† (6)A1 (4)A2 (6)B1 (6)A1 (4)A2 (6)B1 (6)B2 (6)A1 (6)A2 (6)A1 (6)A2 (6)A1 (6)A2 (6)A1 (6)A2 Model No. 06E −275 −250 −299 −265 −250 −265 −265 −275 −265 −275 −265 −275 −265 −299 −275 Oil Charge (L) 10 8 9 10 8 1010101010101010 9 10 Capacity Control Steps** 5 6 3333
CONDENSER FANS (6 Blade) — 60 Hz
Qty...Dia (mm) 6...762 6...762 4...762 4...762 4...762 6...762 Airflow (L/s) 24,544 24,544 16,520 16,520 16,520 24,544 Speed (R/s) 19 19 19 19 19 19 Total Power (kW) 9.4 9.5 6.4 6.4 6.4 9.2
CONDENSER FANS (6 Blade) — 50 Hz
Qty...Dia (mm) 6...762 6...762 4...762 4...762 4...762 6...762 Airflow (L/s) 24,544 24,544 16,520 16,520 16,520 24,544 Speed (R/s) 15.8 15.8 15.8 15.8 15.8 15.8 Total Power (kW) 9.4 9.5 6.4 6.4 6.4 9.2
CONDENSER COIL Enhanced Copper Tubes, Aluminum Lanced Fin
Rows...Fins per m 3...669.3 3...669.3 3...669.3 3...669.3 3...669.3 2...781.6 Face Area (sq m) 11.9 11.9 7.5 7.5 7.5 10.8 Storage Capacity
(Kg per circuit) at 49 C
CONNECTIONS
Suction, ODF (in.) 2 Liquid, ODF (in.) Hot Gas Bypass, ODF (in.)
LEGEND
Cu-Al — Copper Tubes with Aluminum Fins Cu-Cu — Copper Tubes with Copper Fins ODF Outside Diameter, Female
*Includes piping and trim kit. †Compressors are shipped with minimum oil charge. **Capacity control steps listed are for constant volume units with no accesso-
ries. Refer to Table 20, page 48, for additional system capacity information.
81 81 50 50 50 50
1
8
7
8
5
8
21⁄
8
7
8
5
8
NOTES:
1. Unit 38AH124 consists of one 124A module and one 124B module. Unit 38AH134 consists of one 134A module and one 134B module.
2. Certified dimensional drawings available on request.
3. Equivalent connection values in mm are as follows:
R-22
in. mm
5
8
7
8
11⁄
8
1
8
2 25⁄
8
124 134
124A 124B 134A 134B
25⁄ 11⁄
5
15.9
22.2
28.6
54.0
66.7
8 8
8
25⁄
8
11⁄
8
5
8
25⁄
8
11⁄
8
5
8
25⁄ 11⁄
5
8 8
8
11
Page 12
CONTROL BOX
Fig. 7 — Modules 38AH124A or 134A — Shipping Locations of Piping
and Sheet Metal Trim Kit
SHEET METAL COVER PANEL (REMOVED)
RIG HERE
RIG HERE
RIG HERE
RIG HERE
Fig. 8 — Correct Placement of Modules Without Piping
and Sheet Metal Trim (Unit 38AH134 Shown)
12
24-in. (610-mm) SERVICE SPACE
Page 13
FACTORY­INSTALLED SUCTION LINE LOOP
Fig. 9B — Field-Installed Suction Line Loop
Fig. 9A — Typical Module with Cover
Panels Removed
SHIPMENT BOLTS
38AH044-084,124,134
MOUNTING SPRINGS
38AH094,104
SHIPMENT BOLTS
MOUNTING BOLTS
RAIL BOLT (3) (2 SHOWN)
MOUNTING BOLTS RAIL BOLT (3) (2 SHOWN)
Fig. 10 — Outer View, Compressor Mounting
13
Page 14
Step 3 — Make Refrigerant Piping Connections
The field-supplied liquid line solenoid valve must be installed at the evaporator to avoid possible compressor damage during unit operation. See Fig. 11 (for 38AH044­084 dual-circuit and 38AH094-134 units), or Fig. 12 (for 38AH044-084 optional single-circuit units).
The units have largesuctionlinestominimizefriction losses. The units also have the ability to operate at low capacity. Because of these capabilities, use special care with suction piping and suction risers to ensure proper compressor oil return under all operating conditions. Maximum allowable vertical separation between the condensing unit and the evapo­rator is shown in Table 5. Size suction lines in accordance with Tables 6A or 6B through 9A or 9B and Fig. 13. Mount liquid line solenoid valve just ahead of the TXVs (thermo­static expansion valves) which will be mounted at the evaporator. See Fig. 11 (for 38AH044-084 dual-circuit and 38AH094-134 units) or Fig. 12 (for 38AH044-084 optional single-circuit units).
T oachievegood mixing of the refrigerant leaving the evapo­rator suction header for proper sensing by the TXV bulb:
1. Install a minimum of two 90-degree elbows upstream of
the TXV bulb location. See Fig. 14 (for 38AH044-084 dual-circuit and 38AH094-134 units) or Fig. 15 (for 38AH044-084 optional single-circuit units).
2. Locate the TXV bulb on a vertical riser, where possible.
If a horizontal location is necessary, secure the bulb at approximately the 4 o’clock position.
3. Size the suction line from the evaporator to the common
suction line to achieve high refrigerant velocity. See Tables 6A or 6B through 9A or 9B and Fig. 13.
If an oil return connection at the bottom of the suction header is supplied with an evaporator, tee-in this connection ahead of first mixing elbow. See Fig. 14 (for 38AH044-084 dual-circuit and 38AH094-134 units) or Fig. 15(for38AH044­084 optional single-circuit units). When the compressor is below the evaporator, the riser at the evaporator should ex­tend to the top of the evaporator section. After the riser is installed, the suction line can elbow down immediately.
Install a field-supplied filter drier and sight glasses in each refrigerant system. Select the filter drier for maximum unit
capacity and minimum pressuredrop.Figure1 1(for 38AH044­084 dual-circuit and 38AH094-134 units) or Fig. 12 (for
38AH044-084 optional single-circuit units) shows required location of solenoid valves and recommended locations for the filter driers and sight glasses. Complete the refrigerant piping from the evaporator to the condenser before opening the liquid and suction lines at the condenser.
Table 5 — Liquid Lift
UNIT
38AH
044 69 21.0 57.5 17.5 054 75 23.0 75.0 23.0 064 75 23.0 65.0 19.8 074 45 13.7 37.5 11.4 084 75 23.0 75.0 23.0 094 55 16.7 46.0 14.0 104 50 15.2 42.0 12.8 124 75 23.0 65.0 19.8 134 45 13.7 37.5 11.4
FtMFtM
MAXIMUM LIQUID LIFT
60 Hz 50 Hz
UNITS 38AH044-084 — Relieve the pressurecaused by the holding charge into a refrigerant recovery system. Uncap the suction line and cut the run-around tube at the liquid line as close to the loop elbow as possible. This will leave approximately 2 in. (50 mm) of straight tube for liquid line connection.
IMPORTANT: Protect the liquid valves from the heat of brazing.
Leak test the entire system by using soap bubbles and
nitrogen or R-22 with an electronic leak detector.
Purge nitrogen or reclaim R-22 from system after com­pletion of leak-checking procedure. Repair leak if one is found. When finished, evacuate and dehydrate system using the methods described in CarrierGTAC II (General Training Air Conditioning II), Module 4, System Dehydration.
UNITS 38AH094-134 — Relieve the R-22 holding charge of each circuit into a refrigerant recovery system. Remove the liquid line to factory-installed suction line loop by cut­ting the loop at the liquid valve. (See Fig. 9A and 9B.) Cut as close to the 90-degree bend in the loop as possible. The remaining tube piece in the valve will be used for brazing the liquid line. Unbraze and remove the cap from the liquid line. For 38AH094 and 104 units, sweat-connect the liquid and suction lines from the evaporator. For 38AH124 and 134 units, see Piping Kit Connections on page 21.
LEGEND
LLS — Liquid Line Solenoid TXV — Thermostatic Expansion Valve
*Field-Supplied.
Fig. 11 — Required Location of Solenoid Valves and Recommended Filter Drier and
Sight Glass Locations for 38AH044-084 Dual-Circuit and 38AH094-134 Units
14
Page 15
*Field-Supplied.
Fig. 12 — Required Location of Solenoid Valves and Recommended Filter Drier and
Sight Glass Locations for 38AH044-084 Optional Single-Circuit Units
LEGEND
A—Pipe A, Suction Riser, without Trap B—Pipe B, Suction Riser with Trap C—Suction Line to Condensing Unit D—Pipe D, Suction Riser Short Lift RED. — Reducer STR — Street
NOTES:
1. Short riser, pipe D, is used when routing suction line to condens­ing unit connection. See table at right.
2. See Tables 6A-9B for values of A, B, and C.
Fig. 13 — Double Suction Riser Construction
PIPE D DIAMETER
UNIT 38AH
Dual Circuit*
AB
Single Circuit*
in. mm in. mm in. mm
5
044 1 054 15⁄841 15⁄ 064 1 074 21⁄854 21⁄ 084 21⁄854 21⁄ 094, 104 2 124, 134 25⁄867 25⁄
*Maximum length of riser is 3 ft (914 mm). †Double suction riser required if accessory unloader is field
installed.
⁄841 15⁄
5
⁄841 21⁄
1
⁄854 21⁄
8
41 21⁄
8
41 21⁄
8
54 21⁄
8
54 21⁄
8
54 25⁄8† 67†
8
54
8
67
8 8 8 8
15
54 54 54 54
Page 16
Table 6A — Refrigerant Piping Requirements — 38AH044-104 Dual-Circuit Units — 60 Hz
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)
UNIT 38AH
044
054
064
074
084
094
104
Ckt A
Ckt B Ckt A
Ckt B Ckt A
Ckt B Ckt A
Ckt B Ckt A
Ckt B Ckt A
Ckt B Ckt A
Ckt B
LEGEND
L—Liquid Line S—Suction Line
*Double suction riser required on units with field installed unloader
on circuit B compressor if condensing unit is elevated above evaporator.
†Double suction riser required on units with field installed unloader
on circuit B compressor if condensing unit is elevated above evaporator.
**Double suction riser required on all unit configurations if condens-
ing unit is elevated above evaporator.
NOTES:
1. Addition of 2 unloaders to circuit B compressor is not recommended.
2. 38AH094 and 38AH104 piping sizes apply only to factory sup­plied unit configurations. They do NOT take into account any field installed unloaders.
3. Piping sizes are based on unit operation above 40F(4.4C)satu­rated suction temperature (SST). When operating below 40 F (4.4 C),referto Carrier System Design Manual,E20-IIT pipingde­sign program, or ASHRAE Handbook to select proper line sizes.
4. Pipe sizes are based on the total linear length shown for each column, plus a 50% allowance for fittings.
15-25
(4.6-7.6)
25-50
(7.6-15.2)
(15.2-22.9)
LSLSL S L S L S L S
5
8
5 5
7 7
7 7
7 7
7 7
7 7
7
15⁄
8
15⁄
8
15⁄
8
15⁄
8
15⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
7
8 8
8 8
8 8
8 8
8 8
8 8
8 8
11⁄ 11⁄
11⁄ 11⁄
11⁄ 11⁄
8
7 7
7 7
7 7
7
15⁄
8
15⁄
8
15⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
7
8 8
8 8
8 8
8 8
8 8
8 8
8 8
11⁄ 11⁄
11⁄ 11⁄
11⁄ 11⁄
11⁄
8
7
8
7
8
7
8
7
8
7
8
7
8
8 8
8 8
8 8
8
50-75
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
25⁄8†11⁄825⁄8†13⁄825⁄8†13⁄831⁄8** 21⁄
8
25⁄8†11⁄825⁄8†13⁄825⁄8†13⁄831⁄8** 25⁄
8
5. Suction and liquid linesizingis based onpressuredrop equivalent
6. Double suction risers may be required if condensing unit is
7. Refer to Carrier System Design Manual or to E20-II design
8. All pipe sizes are OD inches. Equivalent sizes in millimeters
75-100
(22.9-30.5)
7
8
7
8
7
8
11⁄
7
8
11⁄ 11⁄
11⁄ 11⁄
11⁄ 11⁄ 11⁄
to 2 F (1.1 C) at nominal rating conditions. Higher pressure drop design criteria may allow selection of smaller pipe sizes, but at a penalty of decreased system capacity and efficiency.
elevated above the evaporator.Seefootnotes and double suction riser table below.
programs for further information on selecting pipe sizes for split systems.
21⁄
8
21⁄
8
21⁄
8
8 8
8 8
8
8
8
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
25⁄
8
25⁄8†13⁄825⁄8†13⁄825⁄8†
25⁄
8
25⁄
8
25⁄
8
100-150
(30.5-45.7)
7
8
7
8
7
8
11⁄
8
11⁄
8
11⁄
8
11⁄
8
13⁄
8
13⁄
8
11⁄
8
13⁄
8
11⁄ 11⁄
11⁄ 13⁄ 13⁄ 13⁄
7
8
7
8
7
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
25⁄
8
25⁄8†11⁄825⁄8† 25⁄
8
25⁄
8
25⁄
8
31⁄8** 13⁄
follow:
in. mm
5
11⁄ 1 15⁄ 2 25⁄ 31⁄
8
7
8
8
3
8 8
1
8 8 8
15.9
22.2
28.6
34.9
41.3
54.0
66.7
79.4
150-200
(45.7-61.0)
21⁄ 21⁄
21⁄
8
25⁄8*
8
25⁄8†
8
25⁄
8
25⁄
8
25⁄
8
25⁄
8
31⁄8**
8 8
8
8
8
8
8
Table 6B — Refrigerant Piping Requirements for Double Suction Risers,
38AH054-104 Dual-Circuit Units — 60 Hz
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)
UNIT
38AH
054
064
074
084
094
104
Ckt A ————————————
Ckt B —————————1
Ckt A —————————1
Ckt B ————————————
Ckt A ——————1
Ckt B ————————————
Ckt A ———1
Ckt B ————————————
Ckt A 1
Ckt B ————————————
Ckt A 1
Ckt B ——————1
LEGEND
——Not Required Pipe A — Suction Riser Without Trap Pipe B — Suction Riser With Trap Pipe C — Suction Line to Condensing Unit
NOTES:
1. See Refrigerant Piping Requirements table at top of page to determine need for double suction risers.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
50-75
(15.2-22.9)
75-100
(22.9-30.5)
ABCABCABCABC
5
⁄82
5
8
21⁄
8
25⁄
8
15⁄
8
3
8
21⁄
8
25⁄
8
13⁄
8
1
⁄82
21⁄
8
21⁄
8
5
⁄81
25⁄
8
25⁄
8
3. Suction and liquid linesizingis based onpressuredrop equivalent
4. Refer to Carrier System Design Manual or to E20-II design
5. All pipe sizes are OD inches. See Table 6A notes for metric
6. Refer to Fig. 13 for double suction riser construction.
100-150
(30.5-45.7)
5
⁄82
5
⁄82
15⁄
8
13⁄
8
3
⁄82
to 2F(1.1 C) at nominalratingconditions. Higher design pressure drop criteriamay allow selection ofsmallerpipe sizes butata pen­alty of decreased system capacity and efficiency.
programs for further information on selecting pipe sizes for split systems.
1
⁄82
1
⁄82
21⁄
8
21⁄
8
5
⁄83
5
⁄81
5
⁄81
25⁄
8
25⁄
8
1
⁄81
150-200
(45.7-61.0)
5
⁄82
5
⁄82
5
⁄82
5
⁄82
15⁄
8
15⁄
8
5
⁄82
1
⁄82
1
⁄82
1
⁄82
1
⁄82
25⁄
8
25⁄
8
5
⁄83
5
8
5
8
5
8
5
8
31⁄
8
31⁄
8
1
8
equivalents.
16
Page 17
Table 7A — Refrigerant Piping Requirements, 38AH044-104 Dual-Circuit Units — 50 Hz
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)
UNIT 38AH
044
054
064
074
084
094
104
Ckt A Ckt B
Ckt A Ckt B
Ckt A Ckt B
Ckt A Ckt B
Ckt A Ckt B
Ckt A Ckt B
Ckt A Ckt B
LEGEND
L—Liquid Line S—Suction Line
*Double suction riser required on units with field installed unloader
on circuit B compressor if condensing unit is elevated above evaporator.
†Double suction riser required on units with field installed unloader
on circuit B compressor if condensing unit is elevated above evaporator.
**Double suction riser required on all unit configurations if condens-
ing unit is elevated above evaporator.
NOTES:
1. Addition of 2 unloaders to circuit B compressor is not recommended.
2. 38AH094 and 38AH104 piping sizes apply only to factory sup­plied unit configurations. They do NOT take into account any field installed unloaders.
3. Piping sizes are based on unit operation above 40F(4.4C)satu­rated suction temperature (SST). When operating below 40 F (4.4 C),referto Carrier System Design Manual,E20-IIT pipingde­sign program, or ASHRAE Handbook to select proper line sizes.
4. Pipe sizes are based on the total linear length shown for each column, plus a 50% allowance for fittings.
15-25
(4.6-7.6)
25-50
(7.6-15.2)
(15.2-22.9)
LSLSLSLSLSLS
5
8
13⁄
5
8
13⁄
5
8
13⁄
7
8
15⁄
7
8
15⁄
7
8
15⁄
7
8
15⁄
7
8
21⁄
7
8
21⁄
7
8
21⁄
7
8
21⁄
7
8
21⁄
7
8
21⁄
7
8
21⁄
7
8 8
8 8
8 8
8 8
8 8
8 8
8 8
11⁄
11⁄
8
7 7
7 7
7 7
7 7
7
7 7
15⁄
8
15⁄
8
15⁄
8
15⁄
8
15⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
7
8
8
7
8
8
7
8
8
7
8
8
7
8
8
7
8
8
7
8
11⁄ 11⁄
11⁄ 11⁄
11⁄ 11⁄
11⁄
8
8 8
8 8
8 8
8
8 8
8 8
8 8
8
50-75
75-100
(22.9-30.5)
15⁄
8
15⁄
8
15⁄
8
21⁄
8
21⁄8† 21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄
8
25⁄8** 11⁄ 21⁄
8
21⁄
8
25⁄
8
7
8
7
8
7
8
7
8
7
8
7
8
7
8
11⁄ 11⁄
11⁄ 11⁄
11⁄ 11⁄
5. Suction and liquid linesizingis based onpressuredrop equivalent to 2 F (1.1 C) at nominal rating conditions. Higher pressure drop design criteria may allow selection of smaller pipe sizes, but at a penalty of decreased system capacity and efficiency.
6. Double suction risers may be required if condensing unit is elevated above the evaporator.Seefootnotes and double suction riser table below.
7. Refer to Carrier System Design Manual or to E20-II design programs for further information on selecting pipe sizes for split systems.
8. All pipe sizes are OD inches. Equivalent sizes in millimeters follow:
21⁄
8
21⁄
8
21⁄
8
21⁄
8
21⁄8†11⁄821⁄8†11⁄825⁄8** 21⁄
8
21⁄
8 8
8 8
8 8
8
8
25⁄
8
25⁄8†11⁄825⁄8†11⁄825⁄8† 25⁄
8
25⁄8** 11⁄
25⁄8*† 11⁄
25⁄8** 11⁄
25⁄
8
100-150
(30.5-45.7)
7
8
7
8
7
8
11⁄
8
11⁄
8
11⁄
8
11⁄
8
11⁄
8 8
8 8
13⁄
8
150-200
(45.7-61.0)
11⁄
7
8
7
8
7
8
8
21⁄ 21⁄
21⁄ 21⁄
8 8
8 8
25⁄8*11⁄82 25⁄8†11⁄825⁄8†
25⁄
8
25⁄
8
25⁄8** 13⁄ 25⁄8*† 11⁄
25⁄8** 13⁄ 25⁄
8
11⁄ 11⁄
13⁄
8
8 8
8 8
8
in. mm
5
11⁄ 1 15⁄ 2 25⁄ 31⁄
8
7
8
8
3
8 8
1
8 8 8
15.9
22.2
28.6
34.9
41.3
54.0
66.7
79.4
21⁄
8
21⁄
8
21⁄
8
25⁄8*†
5
8
25⁄
8
25⁄
8
31⁄8** 25⁄8*†
31⁄8** 31⁄8**
*
Table 7B— Refrigerant Piping Requirements for Double Suction Risers,
38AH054-104 Dual-Circuit Units — 50 Hz
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)
UNIT
38AH
054
064
074
084
094
104
Ckt A ———————————— Ckt B —————————1
Ckt A 13⁄ Ckt B ——————1
Ckt A ——————1 Ckt B ————————————
Ckt A ———1 Ckt B ————————————
Ckt A 1 Ckt B ———1
Ckt A ———1 Ckt B —————————1
LEGEND
——Not Required Pipe A — Suction Riser Without Trap Pipe B — Suction Riser With Trap Pipe C — Suction Line to Condensing Unit
NOTES:
1. See Refrigerant Piping Requirements table at top of page to determine need for double suction risers.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
50-75
(15.2-22.9)
75-100
(22.9-30.5)
ABCABCABCABC
8
15⁄
8
21⁄
8
13⁄
8
5
⁄82
3
8
21⁄
8
25⁄
8
13⁄
8
3
⁄82
3
⁄82
15⁄
8
21⁄
8
1
⁄82
21⁄
8
1
⁄82
1
⁄82
5
⁄81
25⁄
8
5
⁄81
5
⁄81
3. Suction and liquid linesizingis based onpressuredrop equivalent
4. Refer to Carrier System Design Manual or to E20-II design
5. All pipe sizes are OD inches. See Table 7A notes for metric
6. Refer to Fig. 13 for double suction riser construction.
100-150
(30.5-45.7)
15⁄
8
15⁄
8
21⁄
5
⁄82
5
⁄82
5
⁄82
15⁄
8
5
⁄82
5
⁄82
to 2F(1.1 C) at nominalratingconditions. Higher design pressure drop criteriamay allow selection ofsmallerpipe sizes butata pen­alty of decreased system capacity and efficiency.
programs for further information on selecting pipe sizes for split systems.
1
⁄82
1
⁄82
1
⁄82
21⁄
8
1
⁄82
1
⁄82
8
5
⁄81
5
⁄81
5
⁄81
25⁄
8
5
⁄81
5
⁄81
150-200
(45.7-61.0)
5
⁄82
15⁄
8
5
⁄82
5
⁄82
5
⁄82
15⁄
8
5
⁄82
5
⁄82
5
⁄82
1
⁄82
21⁄
8
1
⁄82
1
⁄82
1
⁄82
25⁄
8
1
⁄82
5
⁄83
5
⁄83
5
8
25⁄
8
5
8
5
8
5
8
31⁄
8
5
8
1
8
1
8
equivalents.
17
Page 18
Table 8A — Refrigerant Piping Requirements for 38AH044-084
Optional Single-Circuit Units and 38AH124,134
Modular Units (Dual-Circuit) — 60 Hz
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)
UNIT
38AH
044 054
064;
Modules 124A,
124B,134A
074;
Module 134B
084 1
LEGEND
CV — Constant Volume L—Liquid Line S—Suction Line VAV — Variable Air Volume
*Double suction riser required on all units configurations if condens-
ing unit is elevated above evaporator.
†Double suction riser required on units with factory installed VAV op-
tion or CV units with additional field installed unloader on circuit A1 (lead) compressor if condensing unit is elevated above evaporator.
NOTES:
1. Addition of field-installedunloadersonA2 (lag) compressor is not recommended.
2. Piping sizes are based on unit operation above 40F(4.4C)satu­rated suction temperature (SST). When operating below 40 F (4.4 C), refer to Carrier System Design Manual, E20-IIT piping design program,or ASHRAEHandbookto select properlinesizes.
3. Pipe sizes are based on the total linear length shown for each column, plus a 50% allowance for fittings.
4. Suction and liquid linesizingis based onpressuredrop equivalent to 2 F (1.1 C) at nominal rating conditions. Higher pressure drop
15-20
(4.6-6.1)
20-50
(6.1-15.2)
LSLSLSLSLSLS
7
8
7
8
1
1
1
1
1
21⁄ 21⁄
8
21⁄
8
21⁄
8
25⁄8†11⁄825⁄8†13⁄831⁄8†13⁄831⁄8†15⁄835⁄8†1
7
8 8
8
8
8
21⁄
8
11⁄
8
25⁄
8
11⁄
8
25⁄8†11⁄825⁄8†13⁄831⁄8*13⁄831⁄
11⁄
8
25⁄8†13⁄831⁄8†13⁄831⁄8†13⁄831⁄8†1
50-75
(15.2-22.9)
11⁄
8
11⁄
8
75-100
(22.9-30.5)
21⁄
8
11⁄
8
25⁄8*13⁄825⁄
25⁄
8
11⁄
8
25⁄
8
design criteria may allow selection of smaller pipe sizes, but at a penalty of decreased system capacity and efficiency.
5. Double suction risers may be required if condensing unit is elevated above the evaporator.Seefootnotes and double suction riser table below.
6. Refer to Carrier System Design Manual, E20-II design program, or ASHRAE Handbook for further information on selecting pipe sizes for split systems.
7. All pipe sizes are OD inches. Equivalent sizes in millimeters follow:
100-150
(30.5-45.7)
13⁄
8
150-200
(45.7-61.0)
8
*1
31⁄8*1
8
*1
3
⁄83
3
⁄83
3
⁄83
5
⁄83
5
⁄83
1
⁄8*
1
⁄8*
1
⁄8*
5
⁄8*
5
⁄8*
in. mm
7
⁄ 11⁄ 1 15⁄ 21⁄ 2 31⁄ 3
8
8
3
8 8 8
5
8 8
5
8
22.2
28.6
34.9
41.3
54.0
66.7
79.4
92.1
Table 8B — Refrigerant Piping Requirements for Double Suction Risers,
38AH044-084 Optional Single-Circuit Units and 38AH124,134
Modular Units (Dual-Circuit) — 60 Hz
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT
UNIT
38AH
044 ——————1 054 —————————15⁄825⁄831⁄815⁄825⁄831⁄ 064
Modules 124A,
124B,134A
074;
Module 134B
084 15⁄821⁄
LEGEND
——Not Required Pipe A — Suction Riser Without Trap Pipe B — Suction Riser With Trap Pipe C — Suction Line to Condensing Unit
NOTES:
1. See Refrigerant Piping Requirements table at top of page to de­termine need for double suction risers.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
15-50
(4.6-15.2)
50-75
(15.2-22.9)
75-100
(22.9-30.5)
100-150
(30.5-45.7)
150-200
(45.7-61.0)
ABCABCABCABCABC
5
⁄821⁄825⁄815⁄821⁄825⁄815⁄825⁄831⁄
5
1
⁄821⁄
8
25⁄
8
15⁄
8
15⁄821⁄
21⁄825⁄
8
25⁄
8
15⁄
8
25⁄831⁄
8
25⁄
8
15⁄
8
25⁄831⁄
8
15⁄825⁄831⁄
8
15⁄825⁄831⁄
8
15⁄825⁄831⁄
3. Suction and liquid linesizingis based onpressuredrop equivalent
4. Refer to Carrier System Design Manual or to E20-II design
5. All pipe sizes are OD inches. See Table 8A notes for metric
6. Refer to Fig. 13 for double suction riser construction.
8
15⁄
8
25⁄
8
31⁄
8
15⁄
8
8
15⁄
8
25⁄
8
31⁄
8
21⁄
8
8
21⁄
8
31⁄
8
35⁄
8
21⁄
8
to 2F(1.1 C) at nominalratingconditions. Higher design pressure drop criteriamay allow selection ofsmallerpipe sizes butata pen­alty of decreased system capacity and efficiency.
programs for further information on selecting pipe sizes for split systems.
equivalents.
25⁄
31⁄ 31⁄
8 8
8
31⁄
8
8
35⁄
8
8
35⁄
8
18
Page 19
Table 9A — Refrigerant Piping Requirements for 38AH044-084
Optional Single-Circuit Units and 38AH124,134
Modular Units (Dual Circuit) — 50 Hz
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)
UNIT 38AH
044 054
064;
Modules 124A,
124B, 134A
074;
Module 134B
084 1
LEGEND
CV — Constant Volume L—Liquid Line S—Suction Line VAV — Variable Air Volume
*Double suction riser required on all units configurations if condens-
ing unit is elevated above evaporator.
†Double suction riser required on units with factory installed VAV op-
tion or CV units with additional field installed unloader on circuit A1 (lead) compressor if condensing unit is elevated above evaporator.
NOTES:
1. Addition of field-installedunloadersonA2 (lag) compressor is not recommended.
2. Piping sizes are based on unit operation above 40F(4.4C)satu­rated suction temperature (SST). When operating below 40 F (4.4 C), refer to Carrier System Design Manual, E20-IIT piping design program,or ASHRAEHandbookto select properlinesizes.
3. Pipe sizes are based on the total linear length shown for each column, plus a 50% allowance for fittings.
4. Suction and liquid linesizingis based onpressuredrop equivalent to 2 F (1.1 C) at nominal rating conditions. Higher pressure drop
15-20
(4.6-6.1)
20-50
(6.1-15.2)
LSLSLSL S LSLS
7
8
7
7
7
21⁄
8
21⁄
8
21⁄
8
21⁄
1
8
21⁄
7
8
8
21⁄
8
11⁄
8
11⁄
8
21⁄
8
11⁄
8
11⁄
8
25⁄8†11⁄825⁄8†11⁄825⁄8†1
8
11⁄
8
25⁄8†11⁄825⁄8†13⁄831⁄8*1
8
11⁄
8
25⁄8†13⁄831⁄8*13⁄831⁄8*1
50-75
(15.2-22.9)
8
21⁄
8
8
25⁄8*11⁄825⁄8*1
5. Double suction risers may be required if condensing unit is
6. Refer to Carrier System Design Manual, E20-II design program,
7. All pipe sizes are OD inches. Equivalent sizes in millimeters
75-100
(22.9-30.5)
11⁄
8
25⁄8*1
design criteria may allow selection of smaller pipe sizes, but at a penalty of decreased system capacity and efficiency.
elevated above the evaporator.Seefootnotes and double suction riser table below.
or ASHRAE Handbook for further information on selecting pipe sizes for split systems.
follow:
100-150
(30.5-45.7)
1
⁄82
1
⁄82
3
⁄83
3
⁄83
3
⁄83
5
8
*1
5
8
*1
1
8
*1
1
8
*1
1
8
*1
in. mm
7
⁄ 11⁄ 1 15⁄ 21⁄ 2 31⁄ 3
8
8
3
8 8 8
5
8 8
5
8
22.2
28.6
34.9
41.3
54.0
66.7
79.4
92.1
150-200
(45.7-61.0)
3
⁄82
3
⁄83
3
⁄83
3
⁄83
5
⁄83
5
8
*
1
8
*
1
8
*
1
8
*
5
8
*
Table 9B — Refrigerant Piping Requirements for Double Suction Risers,
38AH044-084 Optional Single-Circuit Units and 38AH124,134
Modular Units (Dual Circuit) — 50 Hz
TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE — FT (M)
UNIT
38AH
044 —————————1 054 ——— — — — 15⁄821⁄825⁄815⁄821⁄825⁄815⁄821⁄825⁄815⁄825⁄831⁄
064;
Modules 124A,
124B, 134A
074;
Module 134B
084 ———15⁄821⁄825⁄815⁄825⁄831⁄815⁄825⁄831⁄815⁄825⁄831⁄815⁄831⁄835⁄
LEGEND
——Not Required Pipe A — Suction Riser Without Trap Pipe B — Suction Riser With Trap Pipe C — Suction Line to Condensing Unit
NOTES:
1. See Refrigerant Piping Requirements table at top of page to determine need for double suction risers.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
15-20
(4.6-6.1)
20-50
(6.1-15.2)
50-75
(15.2-22.9)
75-100
(22.9-30.5)
100-150
(30.5-45.7)
ABCABCABCABCABCABC
5
⁄821⁄825⁄815⁄825⁄825⁄815⁄825⁄825⁄
———15⁄821⁄825⁄815⁄821⁄825⁄815⁄821⁄825⁄815⁄825⁄831⁄815⁄825⁄831⁄
———1
5
⁄821⁄825⁄815⁄821⁄825⁄815⁄825⁄831⁄815⁄825⁄831⁄815⁄831⁄835⁄
3. Suction and liquid linesizingis based onpressuredrop equivalent to 2F(1.1 C) at nominalratingconditions. Higher design pressure drop criteriamay allow selection ofsmallerpipe sizes butata pen­alty of decreased system capacity and efficiency.
4. Refer to Carrier System Design Manual or to E20-II design programs for further information on selecting pipe sizes for split systems.
5. All pipe sizes are OD inches. See Table 9A notes for metric equivalents.
6. Refer to Fig. 13 for double suction riser construction.
150-200
(45.7-61.0)
8 8
8
8
8
19
Page 20
LEGEND
TXV — Thermostatic Expansion Valve TYP — Typical
NOTE: Lower split first on, last off.
Fig. 14 — Typical Piping Connections for Face Split Coils for 38AH044-084 Dual-Circuit
and 38AH094-134 Units
LEGEND
TXV — Thermostatic Expansion Valve TYP — Typical
NOTE: Lower split first on, last off.
Fig. 15 — Typical Piping Connections for Face Split Coils for 38AH044-084
Optional Single-Circuit Units
20
Page 21
Units 38AH124 and 134 Piping Kit Connections — The 38AH124 and 134 units are delivered with a factory­supplied suction and liquid piping kit for installation in the 24-in. (610-mm) service space between the 2 unit modules. The piping kit allows for a common unit side piping con­nection from the indoor unit to each of the condensing unit refrigeration circuits. Fittings are provided and shipped in the control box.
Remove the copper tubes from Module 124Aor134Acom-
pressor rails. Save the pipe clamps for later use. Cut the
5
⁄8-in. (67-mm) suction tube into 2 pieces: 28 in. (711 mm)
2 and 67 in. (1702 mm). Connect the 2 formed 11⁄8-in. (29-mm) tubes to the liquid line connection at the liquid valve. See Fig. 16.
NOTE: Piping kit is designed to allow air handler connec­tions to project from either side of the service space.
To prepare condensing unit modules for piping connec­tion, refer to beginning paragraphs of Step 3 — Make Refrigeration Piping Connections, page 14.
5
⁄8-in. (67-mm) and one 11⁄8-in. (29-mm) elbows are
Two 2 supplied for piping connections. Fit tubing to ensure proper installation. All tubes should have equal lengths projecting beyond unit corner posts. See Fig. 16. Ensure suction tube is level for oil return requirements.
Protect liquid valves from the heat of brazing.
Braze the piping connections.
Level the tubes and clamp to the cornerpostswith factory­supplied self-drilling screws and pipe clamps removed from Module 124A or 134A during piping kit removal.
Units 38AH124 and 134 Sheet Metal Trim Kit Installation — After the units are in place and the piping kit is installed, install the sheet metal trim kit.
NOTE: Install sheet metal trim kit before connection to air handler tubing in case the modules must be repositioned to accommodate the sheet metal installation.
Remove two 43-in. (1092 mm) base rail trim pieces from Module 124A or 134A base rail. Remove the 3 corner post bolts from the bottom of each corner post at the servicespace. Align the base rail trim piece holes over the bolt holes in the corner rails. See Fig. 17. Reinsert corner post bolts through the trim piece into the corner posts.
Attach Top Cover — To attach top cover, proceed as follows:
For Unit 38AH124, remove screws A from top of each of 4 corner posts at service space. See Fig. 18. Place cover on top of service space and align top cover slots with corner post screw holes. Reinsert screws A.
For Unit 38AH134, remove screws A from top of each cor­ner post on Module 134A and screws B from top of each corner post on Module 134B. See Fig. 18. Top cover is in 2 pieces: one vertical piece and one horizontal piece. Slide vertical top cover partly under Module 134B end cover flange;
align holes and reinsert screws B. Place horizontal cover on top of Module 134A end cover with opposite side resting on the horizontal flange of the installed Module B vertical top cover piece. Align holes on flange and top cover. Reinsert screwsAthrough the top cover holes into the endcover. From within the service space, insert supplied screws up through the flange and horizontal cover to make a secure connection between the horizontal and vertical cover pieces.
Insert supplied screws into each of the 2 holes in the ver­tical side flange of the top cover at each end of the service space.
Attach Side Panels — Insert side panels at the ends of the service space and hook side panel flange over the 2 screws previously inserted in the top cover flange. Fasten panels to the corner posts with supplied self-drilling screws, 3perside. See Fig. 19.
Connect Tubing from Evaporator to Unit
Protect liquid valves from the heat of brazing.
Braze the liquid and suction lines from the evaporator to the condensing unit liquid and suction lines. Leak test the entire system by the pressure method described in the Carrier Standard Service Techniques Manual, Chapter 1, Section 1-6. Use R-22 at approximately 25 psig (172 kPa) backed up with an inert gas to a total pressure not to exceed 245 psig (1689 kPa). If a leak is detected, evacuate and de­hydrate the system. Follow methods described in the Carrier Service Manual, Chapter 1, Section 1-7.
NOTES:
1. Ensure suction tube is level for oil return requirements.
2.
Protect liquid valves from heat of brazing.
Fig. 16 — Units 38AH124 and 134 with Installed
Piping Kit
21
Page 22
BASE RAIL
CORNER POST
BOLTS (6)
CORNER POST
Fig. 17 — Units 38AH124 and 134 withInstalledT rim
Kit Rails
MODULE 124B OR 134B
CORNER POST (4 PER MODULE)
FACTORY-SUPPLIED SELF-DRILLING SCREWS (4 PER CORNER POST)
SCREWS (2) FOR MOUNTING SIDE PANEL
24-in. (610-mm) SERVICE WAY
CORNER POST (4 PER MODULE)
TOP COVER FLANGE
Fig. 19 — Fully Assembled Piping and Trim Kit
(Unit 38AH134 Shown)
MODULE 124A OR 134A
SCREWS B
END COVER FLANGES
CORNER POST
TOP COVER, VERTICAL PIECE
MODULE 124B OR 134B
VERTICAL TOP COVER FLANGE (HIDDEN)
24-in. (610-mm) SERVICE WAY
TOP COVER, HORIZONTAL PIECE
CORNER POST
SCREWS A
END COVER
MODULE 124A OR 134A
Fig. 18 —Units 38AH124 and 134 with Installed Top
Cover (Unit 38AH134 Shown)
22
Page 23
Step 4 — Make Electrical Connections
POWER SUPPLY — Electrical characteristics of available power supply must agree with unit nameplate rating. Supply voltage must be within the limits shown in Tables 10A or 10B, 11 and 12. See Table 13 for control circuit data and Table 14 for fan motor electrical data.
IMPORTANT: Operation of unit on improper supply voltage or with excessive phase imbalance constitutes abuse and can affect any Carrier warranty.
FIELD POWER CONNECTIONS — All power wiring must comply with applicable local and national codes. Install field­supplied, branch circuit safety disconnect(s) of a type that can be locked off/open. Disconnects must be located within sight of, and readily accessible from, the unit in compliance with NEC (National Electrical Code) (U.S.A. Standard) Article 440-14.
All field power enters the unit through a hole in the con-
trol box shelf. Refer to Fig. 20-28 for field wiring details.
Table 10A — Electrical Data — 50/60 Hz (38AH044-084 Dual-Circuit Units)
STANDARD UNIT COMPRESSOR*
38AH
044
054
064
074
084
See page 24 for Legend and Notes.
Voltage
Designation
500 600 460-3-60 414 508 91.3 100 218.6 34.6 173 34.6 173 100 575-3-60 518 632 78.4 100 162.4 28.8 120 28.8 120 200 380-3-60 342 418 93.5 125 241.2 34.6 191 34.6 191 800 (PW) 230-3-50 198 254 180.2 225 296.7 67.9 207 67.9 207 900 380/415-3-50 342 440 91.5 100 219.6 34.6 173 34.6 173 300 (PW) 346-3-50 325 367 100.0 125 165.9 33.3 115 33.3 115
500 600 460-3-60 414 508 102.4 125 268.6 34.6 173 43.6 223 100 575-3-60 518 632 88.0 125 206.4 28.8 120 36.5 164 200 380-3-60 342 418 107.1 150 297.2 34.6 191 45.5 247 900 380/415-3-50 342 440 102.7 125 269.6 34.6 173 43.6 223 300 (PW) 346-3-50 325 367 107.0 150 198.9 33.3 115 44.9 148
500 600 460-3-60 414 508 115.5 150 307.6 43.6 223 46.8 253 100 575-3-60 518 632 100.6 125 226.1 36.5 164 40.4 176 200 380-3-60 342 418 126.9 175 341.1 45.5 247 52.6 280 900 380/415-3-50 342 440 114.1 150 335.6 43.6 223 46.8 280 300 (PW) 346-3-50 325 367 129.8 175 230.5 44.9 148 53.8 168
500 600 460-3-60 414 508 148.6 200 408.2 46.8 253 65.4 345 100 575-3-60 518 632 132.2 175 336.8 40.4 176 57.1 276 200 380-3-60 342 418 174.5 250 458.0 52.6 280 78.8 382 900 380/415-3-50 342 440 143.0 200 403.8 46.8 280 65.4 345 300 (PW) 346-3-50 325 367 170.8 250 300.4 53.8 168 79.5 229
500 600 460-3-60 414 508 167.2 225 426.8 65.4 345 65.4 345 100 575-3-60 518 632 148.9 200 353.5 57.1 276 57.1 276 200 380-3-60 342 418 200.7 250 484.2 78.8 382 78.8 382 900 380/415-3-50 342 440 167.6 225 428.4 65.4 345 65.4 345 300 (PW) 346-3-50 325 367 205.3 250 334.9 79.5 229 79.5 229
Compressor
A1/B1
Model No.
06E4250/250
06E4250/265
06E8265/275
06E8275/299
06E8299/299
Nameplate
V-Ph-Hz
208/230-3-60 187 254 179.4 225 434.7 67.9 345 67.9 345
208/230-3-60 187 254 206.6 250 535.7 67.9 345 89.7 446
208/230-3-60 187 254 249.3 350 617.5 89.7 446 106.4 506
208/230-3-60 187 254 330.5 450 829.0 106.4 506 147.4 690
208/230-3-60 187 254 371.5 500 870.0 147.4 690 147.4 690
Supply Voltage†
Min Max RLA LRA RLA LRA
MAIN POWER — Units 38AH044-104 have single-point power connection to simplify field-power wiring (all power enters at one end). Units 38AH124 and 134 require 2 con­nection points, one for each module. Units may use copper, copper-clad aluminum, or aluminum conductors at all volt­ages. The maximum wire size units can accept per terminal block is 500 kcmil.
Power must be supplied as shown in Table 15. CONTROL CIRCUIT WIRING — Control circuit wiring is
accomplished with a step-down transformer on voltage des­ignations 500, 600, and 100 in table below where the pri­mary voltage is field voltage. For 208/230-v, 3-ph, 60-Hz units, ensure that the transformer primary is wired properly for the voltage which will be applied. All control wiring must comply with applicable local and national codes. The safety circuits are 24 v on all units. The safety circuit voltage is created with a step-down transformer where main control voltage is the transformer primary voltage.
See Table 13 for control circuit information.
MCA MOCP ICF
A1 B1
23
Page 24
Table 10B — Electrical Data — 50/60 Hz (38AH044-084 Optional Single-Circuit Units)
OPTIONAL SINGLE-CIRCUIT UNIT COMPRESSOR*
38AH
044
054
064
074
084
FLA Full Load Amps ICF Maximum Instantaneous Current Flow During Starting.
kcmil — Thousand Circular Mils LRA Locked Rotor Amps Max Maximum MCA Minimum Circuit Amps (used for sizing; complies with
Min Minimum MOCP — Maximum Overcurrent Protection (used for sizing dis-
RLA Rated Load Amps PW Part Wind Only
Voltage
Designation
500 600 460-3-60 414 508 91.3 100 218.6 34.6 173 34.6 173 100 575-3-60 518 632 78.4 100 162.4 28.8 120 28.8 120 200 380-3-60 342 418 93.5 125 241.2 34.6 191 34.6 191 800 (PW) 230-3-50 198 254 180.2 225 296.7 67.9 207 67.9 207 900 380/415-3-50 342 440 91.5 100 219.6 34.6 173 34.6 173 300 (PW) 346-3-50 325 367 100.0 125 165.9 33.3 115 33.3 115
500 600 460-3-60 414 508 102.4 125 268.6 43.6 223 34.6 173 100 575-3-60 518 632 88.0 125 206.4 36.5 164 28.8 120 200 380-3-60 342 418 107.1 150 297.2 45.5 247 34.6 191 900 380/415-3-50 342 440 102.7 125 269.6 43.6 223 34.6 173 300 (PW) 346-3-50 325 367 107.0 150 198.9 44.9 148 33.3 115
500 600 460-3-60 414 508 115.5 150 307.6 46.8 253 43.6 223 100 575-3-60 518 632 100.6 125 226.1 40.4 176 36.5 164 200 380-3-60 342 418 126.9 175 341.1 52.6 280 45.5 247 900 380/415-3-50 342 440 115.7 150 335.6 46.8 280 43.6 223 300 (PW) 346-3-50 325 367 129.8 175 230.5 53.8 168 44.9 148
500 600 460-3-60 414 508 148.6 200 408.2 65.4 345 46.8 253 100 575-3-60 518 632 132.2 175 336.8 57.1 276 40.4 176 200 380-3-60 342 418 174.5 250 458.0 78.8 382 52.6 280 900 380/415-3-50 342 440 143.0 200 403.8 65.4 345 46.8 280 300 (PW) 346-3-50 325 367 170.8 250 300.4 79.5 229 53.8 168
500 600 460-3-60 414 508 167.2 225 426.8 65.4 345 65.4 345 100 575-3-60 518 632 148.9 200 353.5 57.1 276 57.1 276 200 380-3-60 342 418 200.7 250 484.2 78.8 382 78.8 382 900 380/415-3-50 342 440 167.6 225 428.4 65.4 345 65.4 345 300 (PW) 346-3-50 325 367 205.3 250 334.9 79.5 229 79.5 229
(The point in the starting sequence where the sum of the LRAforthestartingcompressors,plusthetotalRLA for all running compressors, plus the FLA for all running fan motors is maximum.)
National Electrical Code [NEC] [U.S.A. Standard], section 430-24).
connect; complies with NEC Article 440, Section 22).
Compressor
A1/A2
Model No.
06E4250/250
06E4265/250
06E8275/265
06E8299/275
06E8299/299
LEGEND
Nameplate
V-Ph-Hz
208/230-3-60 187 254 179.4 225 434.7 67.9 345 67.9 345
208/230-3-60 187 254 206.6 250 535.7 89.7 446 67.9 345
208/230-3-60 187 254 249.3 350 617.5 106.4 506 89.7 446
208/230-3-60 187 254 330.5 450 829.0 147.4 690 106.4 506
208/230-3-60 187 254 371.5 500 870.0 147.4 690 147.4 690
Supply Voltage
Min Max RLA LRA RLA LRA
MCA MOCP ICF
*All compressors are across-the-line start only except 38AH044
230 v, 3-phase, 50 Hz; and all 346 v, 3-phase, 50 Hz.
†Units are suitable for use on electrical systems where voltage sup-
plied to unit terminals is within listed minimum to maximum limits.
NOTES:
1. Maximum allowable phase imbalance: voltage - 2%; amps - 10%.
2. Maximum incoming wire size for terminal block is 500 kcmil.
A1 A2
24
Page 25
Table 11 — Electrical Data — 50/60 Hz (Units 38AH094,104)
UNIT
38AH
094
104
——Not Applicable FLA Full Load Amps ICF Maximum Instantaneous Current Flow During Starting.
kcmil — Thousand Circular Mils LRA Locked Rotor Amps MCA Minimum Circuit Amps (used for sizing; complies with
MOCP — Maximum Overcurrent Protection (used for sizing
RLA Rated Load Amps
VOLTAGE
DESIGNATION
500 208/230-3-60 187 253 398.5 500 897 106.4 506 67.9 345 147.7 690 — 600 460-3-60 414 506 183.1 225 443 46.8 253 34.6 173 65.4 345 — 100 575-3-60 518 633 160.9 200 366 40.4 176 28.8 120 57.1 276 — 200 380-3-60 342 418 209.1 250 493 52.6 280 34.6 191 78.8 382 — 900 380/415-3-50 342 440 183.6 225 444 46.8 280 34.6 173 65.4 345 — 300 (PW) 346-3-50 325 380 212.9 250 343 53.8 168 33.3 115 79.5 229 — 500 208/230-3-60 187 253 399.4 450 722 89.7 446 67.9 345 89.7 446 89.7 446 600 460-3-60 414 506 196.3 225 361 43.6 223 34.6 173 43.6 223 43.6 223 100 575-3-60 518 633 168.0 200 286 36.5 164 28.8 120 36.5 164 36.5 164 200 380-3-60 342 418 205.9 250 396 45.5 247 34.6 191 45.5 247 45.5 247 900 380/415-3-50 342 440 196.7 225 363 43.6 223 34.6 173 43.6 223 43.6 223 300 (PW) 346-3-50 325 380 205.6 250 298 44.9 148 33.3 229 44.9 148 49.9 148
(The point in the starting sequence where the sum of the LRAforthestartingcompressors,plusthetotalRLA for all running compressors, plus the FLA for all running fan motors is maximum.)
National Electrical Code [NEC] [U.S.A. Standard], section 430-24).
disconnect; complies with NEC [U.S.A. Standard], section 440-22).
NAMEPLATE
V-Ph-Hz
LEGEND
SUPPLY
VOLTAGE*
Min Max RLA LRA RLA LRA RLA LRA RLA LRA
MCA MOCP ICF
COMPRESSOR†
A1 A2 B1 B2
*Units are suitable for use on electrical systems where voltage sup-
plied to unit terminals is within listed minimum to maximum limits.
†All compressors are across-the-line start only except 346-V, 3-ph,
50-Hz units.
NOTES:
1. Maximum allowable phase imbalance: voltage - 2%; amps - 10%.
2. Maximum incoming wire size for terminal block is 500 kcmil.
3. For units 38AH094and104 compressor modelnumbers,see table
below:
UNIT
38AH
CKT A1 A2 B1 A1 A2 B1 B2
MODEL
NO. 06E
−275 −250 −299 −265 −250 −265 −265
094 104
25
Page 26
Table 12 — Electrical Data — 50/60 Hz (Units 38AH124, 134)
UNIT
38AH
MODULE
124A 124B 134A
134B
FLA Full Load Amps ICF Maximum Instantaneous Current Flow During Starting.
kcmil — Thousand Circular Mils LRA Locked Rotor Amps MCA Minimum Circuit Amps (used for sizing; complies with
MOCP — Maximum Overcurrent Protection (used for sizing
PW Part Wind RLA Rated Load Amps
VOLTAGE
DESIGNATION
500 600 460-3-60 414 508 115.5 150 307.6 46.8 253 43.6 223 100 575-3-60 518 632 100.6 125 226.1 40.4 176 36.5 164 200 380-3-60 342 418 126.9 175 341.1 52.6 280 45.5 247 900 380/415-3-50 342 440 115.7 150 335.6 46.8 280 43.6 223 300 (PW) 346-3-50 325 367 129.8 175 230.5 53.8 168 44.9 148 500 600 460-3-60 414 508 148.6 200 408.2 65.4 345 46.8 253 100 575-3-60 518 632 132.2 175 336.8 57.1 276 40.4 176 200 380-3-60 342 418 174.5 250 458.0 78.8 382 52.6 280 900 380/415-3-50 342 440 149.0 200 403.8 65.4 345 46.8 280 300 (PW) 346-3-50 325 367 170.8 250 300.4 79.5 229 53.8 168
(The point in the starting sequence where the sum of the LRAforthestartingcompressors,plusthetotalRLA for all running compressors, plus the FLA for all running fan motors is maximum.)
National Electrical Code [NEC] [U.S.A. Standard], section 430-24).
disconnect; complies with NEC [U.S.A. Standard], section 440- 22).
COMPRESSOR
A1/A2
MODEL NO.
06E8275/
06E8299/
LEGEND
265
275
NAMEPLATE
V-Ph-Hz
208/230-3-60 187 254 249.3 350 617.5 106.4 506 89.7 446
208/230-3-60 187 254 330.5 450 829.0 147.4 690 106.4 506
SUPPLY
VOLTAGE*
Min Max RLA LRA RLA LRA
MCA MOCP ICF
*Units are suitable for use on electrical systems where voltage sup-
plied to unit terminals is within listed minimum to maximum limits.
†All compressors are across-the-line start only except 346-v, 3-ph,
50 Hz unit.
NOTES:
1. Maximum allowable phase imbalance: voltage - 2%; amps - 10%.
2. Maximum incoming wire size for terminal block is 500 kcmil.
COMPRESSOR†
A1 A2
Table 13 — Control Circuit Electrical Data — 50/60 Hz
UNIT
DESIGNATION
−500 208/230-3-60 115-1-60 103 127 4.1
−600 460-3-60 115-1-60 103 127 4.1
−100 575-3-60 115-1-60 103 127 4.1
−200 380-3-60 230-1-60 207 253 2.0
−800 230-3-50 230-1-50 207 253 2.0
−900 380/415-3-50 230-1-50 207 253 2.0
−300 346-3-50 200-1-50 180 220 2.4
NOTE: Units 38AH124 and 134 have 2 control boxes per unit, one in each module.
UNIT POWER CONTROL POWER
V-Ph-Hz V-Ph-Hz Min Max
AMPS
26
Page 27
Table 14 — Fan Motor Electrical Data
UNIT
38AH
044
054
064
074
084
094
104
UNIT 38AH
MODULE
124A 124B 134A
134B
LEGEND
FLA — Full Load Amps LRA — Locked Rotor Amps
Nameplate
208/230-3-60
380/415-3-50 (1-4) 3.4 (1-4) 30.0
208/230-3-60
380/415-3-50 (1-4) 3.4 (1-4) 30.0
208/230-3-60
380/415-3-50 (1-4) 3.4 (1-4) 30.0
208/230-3-60
380/415-3-50 (1-6) 3.4 (1-6) 30.0
208/230-3-60
380/415-3-50 (1-6) 3.4 (1-6) 30.0
208/230-3-60
380/415-3-50 (1-6) 3.4 (1-6) 30.0
208/230-3-60
380/415-3-50 (1-6) 3.4 (1-6) 30.0
208/230-3-60
380/415-3-50 (1-4) 3.4 (1-4) 30.0
208/230-3-60
380/415-3-50 (1-6) 3.4 (1-6) 30.0
CONDENSER FAN
V-Ph-Hz
460-3-60 (1,2) 2.8 (3,4) 3.3 (1,2) 30.0 (3,4) 31.6 575-3-60 (1-4) 3.4 (1-4) 30.0 380-3-60 (1-4) 3.9 (1-4) 20.9 230-3-50 (1,2) 5.5 (3,4) 6.8 (1,2) 30.0 (3,4) 31.6
346-3-50 (1-4) 4.4 (1-4) 20.9
460-3-60 (1,2) 2.8 (3,4) 3.3 (1,2) 30.0 (3,4) 31.6 575-3-60 (1-4) 3.4 (1-4) 30.0 380-3-60 (1-4) 3.9 (1-4) 20.9
346-3-50 (1-4) 4.4 (1-4) 20.9
460-3-60 (1,2) 2.8 (3,4) 3.3 (1,2) 30.0 (3,4) 31.6 575-3-60 (1-4) 3.4 (1-4) 30.0 380-3-60 (1-4) 3.9 (1-4) 20.9
346-3-50 (1-4) 4.4 (1-4) 20.9
460-3-60 (1,2) 2.8 (3-6) 3.3 (1,2) 30.0 (3-6) 31.6 575-3-60 (1-6) 3.4 (1-6) 30.0 380-3-60 (1-6) 3.9 (1-6) 20.9
346-3-50 (1-6) 4.4 (1-6) 20.9
460-3-60 (1,2) 2.8 (3-6) 3.3 (1,2) 30.0 (3-6) 31.6 575-3-60 (1-6) 3.4 (1-6) 30.0 380-3-60 (1-6) 3.9 (1-6) 20.9
346-3-50 (1-6) 4.4 (1-6) 20.9
460-3-60 (1-2) 2.8 (3-6) 3.3 (1,2) 30.0 (3-6) 31.6 575-3-60 (1-6) 3.4 (1-6) 30.0 380-3-60 (1-6) 3.9 (1-6) 20.9
346-3-50 (1-6) 4.4 (1-6) 20.9
460-3-60 (1,2) 2.8 (3-6) 3.3 (1,2) 30.0 (3-6) 31.6 575-3-60 (1-6) 3.4 (1-6) 30.0 380-3-60 (1-6) 3.9 (1-6) 20.9
346-3-50 (1-6) 4.4 (1-6) 20.9
460-3-60 (1,2) 2.8 (3,4) 3.3 (1,2) 30.0 (3,4) 31.6 575-3-60 (1-4) 3.4 (1-4) 30.0 380-3-60 (1-4) 3.9 (1-4) 20.9
346-3-50 (1-4) 4.4 (1-4) 20.9
460-3-60 (1,2) 2.8 (3-6) 3.3 (1,2) 30.0 (3-6) 31.6 575-3-60 (1-6) 3.4 (1-6) 30.0 380-3-60 (1-6) 3.9 (1-6) 20.9
346-3-50 (1-6) 4.4 (1-6) 20.9
Qty
4
4
4
6
6
6
6
4
6
Hp
(kW)
1
(0.746)
1
(0.746)
1
(0.746)
1
(0.746)
1
(0.746)
1
(0.746)
1
(0.746)
1
(0.746)
1
(0.746)
Total
kW
6.2
6.2
6.2
9.3
9.3
9.4
9.5
6.4
9.2
*Refers to condenser fans by position: See circled numbers on top
views of units in Fig. 1-6.
NOTE: All fans are protected by a single circuit breaker.
(No.*) FLA Each (No.*) LRA Each
(1,2) 5.5 (3,4) 6.6 (1,2) 30.0 (3,4) 31.6
(1,2) 5.5 (3,4) 6.6 (1,2) 30.0 (3,4) 31.6
(1,2) 5.5 (3,4) 6.6 (1,2) 30.0 (3,4) 31.6
(1,2) 5.5 (3-6) 6.6 (1,2) 30.0 (3-6) 31.6
(1,2) 5.5 (3-6) 6.6 (1,2) 30.0 (3-6) 31.6
(1,2) 5.5 (3-6) 6.6 (1,2) 30.0 (3-6) 31.6
(1,2) 5.5 (3-6) 6.6 (1,2) 30.0 (3-6) 31.6
(1,2) 5.5 (3,4) 6.6 (1,2) 30.0 (3,4) 31.6
(1,2) 5.5 (3-6) 6.6 (1,2) 30.0 (3-6) 31.6
27
Page 28
*To control heatingdevice andprovide automaticindoor-
fan operation on heating.
†Jumper removed only when separate 24-v trans-
formerpowersource isused topower the33CSUCE-06 relay pack.
**Field-supplied.
NOTES:
1. Liquid linesolenoid valve LLS-Aisusedfor so­lenoiddropon circuitA. Liquidlinesolenoid valve LLS-B is used for solenoid drop for circuit B.
2. Solenoid drop is a safety feature which pre­ventsrefrigerantmigration tothecompressor dur­ing the OFF cycle. It is recommended on all systems andrequiredonsystems where piping exceeds 75 ft (22.9 m) in length.
3. The 33CSUCE-06 relay pack requires 10 va.
4. Factory wiring is in accordance with NEC; field modifications or additions must be in compli­ance with all applicable codes.
5. Wiring for field power supply must be rated 75 Cminimum.Usecopper, copper-clad alumi­num, or aluminum conductors. Maximum in­coming wire size for each terminal block is 500 kcmil.
6. Terminal blocks TB3 and TB4 are for external field control connections. Control connections are to be Class 1 wiring.
7. Field-supplied components (IFC, LLS-A, and LLS-B) must have a maximum sealed coil rat­ing of 30 va each (0.25 amp at 120 vac and
Fig. 20 — Field Wiring, One 2-Stage Thermostat — 38AH044-084 Dual-Circuit Units
Internal 33CSUCE-06relay contacts are ratedfor1 amp/24 vac.
0.13 amp at 230 vac). Thermostats must have a minimum pilot duty rating of 300 va (2.5 amps at 120 vac and 1.3 amps at 230 vac).
8. Replacement of factory wires must be with type 105 C wire or its equivalent.
9. Field-supplied liquid line solenoid valves installed at the evaporator are required on all units.
10. Units have 175 va of power available for field­installed accessories.
11. To minimize voltage drop, the following wire sizes
are recommended:
LENGTH —
Ft (M)
Up to 50 (15.2)
50-75 (15.2-22.9)
More Than 75 (22.9)
INSULATED WIRE — AWG
(35 C Minimum)
No. 18 No. 16 No. 14
LEGEND
AWG — American Wire Gage CR Control Relay HD Heating Device IFC Indoor-Fan Contactor IFR Indoor-Fan Relay kcmil — Thousand Circular Mils LLS Liquid Line Solenoid NEC — National Electrical Code
R—Heating Relay (field-
RV Reversing Valve TB Terminal Block
(U.S.A. Standard) supplied 24-v sealed coil,
10 va maximum rating)
Factory Wiring Field Wiring
28
Page 29
*To control heatingdevice andprovide automaticindoor-
fan operation on heating.
†Jumper removed only when separate 24-v trans-
formerpowersource isused topower the33CSUCE-06 relay pack.
**Field-supplied. NOTES:
1. Liquid linesolenoid valves LLS-A1and A2are used for solenoid drops.
2. Solenoid drop is a safety feature which prevents refrigerant migration to the compressor during the OFF cycle. It is recommended on all systems and required on systems where piping exceeds 75 ft (22.9 m) in length.
3. The 33CSUCE-01 relay pack requires 10 va.
4. Factory wiringis inaccordance with NEC;field modi­fications or additions must be in compliance with all applicable codes.
5. Wiring for field power supply must be rated 75 C minimum. Use copper, copper-clad aluminum, or aluminumconductors.Maximum incomingwire size for each terminal block is 500 kcmil.
6. Terminal blocks are for external field control con­nections. Control connections are to be Class 1 wiring.
7. Field-supplied components (IFC, LLS-A1, and LLS-A2) must have a maximum sealed coil rating of 30 va each (0.25 amp at 120 vac and 0.13 amp
Internal 33CSUCE-06 relay contacts are rated for 1 amp/24 vac.
at 230 vac).Thermostats must have a minimum pilot duty rating of 300 va (2.5 amps at 120 vac and
1.3 amps at 230 vac).
8. Replacement of factory wires must be with type 105 C wire or its equivalent.
9. Field-supplied liquid line solenoid valves installed at the evaporator are required on all units.
10. Units have 175 va of power available for field­installed accessories.
11. Tominimize voltage drop,the following wiresizes are
recommended:
LENGTH —
Ft (M)
Up to 50 (15.2)
50-75 (15.2-22.9)
More Than 75 (22.9)
INSULATED WIRE — AWG
(35 C Minimum)
No. 18 No. 16 No. 14
LEGEND
AWG — American Wire Gage CR Control Relay HD Heating Device IFC Indoor-Fan Contactor IFR Indoor-Fan Relay kcmil — Thousand Circular Mils LLS Liquid Line Solenoid NEC — National Electrical Code
R—Heating Relay (field-
RV Reversing Valve TB Terminal Block
(U.S.A. Standard) supplied 24-v sealed coil,
10 va maximum rating)
Factory Wiring Field Wiring
Fig. 21 — Field Wiring, One 2-Stage Thermostat — 38AH044-084 Optional Single-Circuit Units
29
Page 30
*To control heatingdevice andprovide automaticindoor-
fan operation on heating.
†Jumper removed only when separate 24-v trans-
formerpowersource isused topower the33CSUCE-06 relay pack.
**Field-supplied. NOTES:
1. Liquid line solenoid valve LLS-A1 is used for solenoid drop on circuit A. Liquid line solenoid valve LLS-B1 is used for solenoid drop for circuit B.
2. Solenoid drop is a safety feature which prevents refrigerant migration to the compressor during the OFF cycle. It is rec­ommended on all systems and required on systems where piping exceeds 75 ft (22.9 m) in length.
3. The 33CSUCE-06 relay pack requires 10 va.
4. Factory wiring is in accordance with NEC; field modifications or additions must be in compliance with all applicable codes.
5. Wiring for field power supply must be rated 75 C mini­mum. Use copper, copper-clad aluminum, or aluminum con­ductors. Maximumincomingwire size for eachterminalblock is 500 kcmil.
6. Terminalblocks arefor external fieldcontrol connections.Con­trol connections must be Class 1 wiring.
7. Field-supplied components (IFC, LLS-A1, and LLS-B1) must have a maximum sealed coil rating of 30 va each (0.25 amp at 120vac and 0.13ampat 230 vac).Thermostats must have a minimum pilot duty rating as follows:
38AH
094 275
104 325
VA
(Ea Stage)
AMPS VAC
2.29 120
1.15 240
2.70 120
1.35 240
Internal 33CSUCE-06 relay contacts are rated for 1 amp/24 vac.
8. Replacement of factory wires must be with type 105 C wire or its equivalent.
9. Field-supplied liquidlinesolenoid valves in­stalled at theevaporatorare required on all units.
10. Units 38AH094has 140va andunit 38AH104 has 130 va of power available for field­installed accessories.
11. Tominimize voltage drop,the following wire sizes are recommended:
LENGTH —
Ft (M)
Up to 50 (15.2)
50-75 (15.2-22.9)
More Than 75 (22.9)
INSULATED WIRE —
AWG
(35 C Minimum)
No. 18 No. 16 No. 14
LEGEND
AWG — American Wire Gage CR Control Relay HD Heating Device IFC Indoor-Fan Contactor IFR Indoor-Fan Relay kcmil — Thousand Circular Mils LLS Liquid Line Solenoid NEC — National Electrical Code
R—Heating Relay (field-
RV Reversing Valve TB Terminal Block
(U.S.A. Standard) supplied 24-v sealed coil,
10 va maximum rating)
Factory Wiring Field Wiring
Fig. 22 — Field Wiring, One 2-Stage Thermostat — Units 38AH094 and 104
30
Page 31
*Jumper removed only when separate 24-v trans-
formerpowersource isused topowerthe 33CSUCE-06 relay pack.
†Field-supplied. NOTES:
1. Liquid linesolenoid valves LLS-A1and A2are used for solenoid drop on Module 124A or 134A on cir­cuit A. Liquid line solenoid valves LLS-B1 and B2 areusedfor solenoiddrop forModule124B or134B. Solenoid drop is a safety feature which prevents refrigerant migration to the compressor during the OFF cycle. It is recommended on all systems and required on systems where piping exceeds 75 ft (22.9 m) in length.
2. Disconnectblackwire fromCR2 terminal 6;cap loose end and secure. Connect new field-supplied wire from CR2 terminal 6 to TB3 terminal 1 on module 124B or 134B.
3. The 33CSUCE-06 relay pack requires 10 va.
4. Factory wiringis inaccordance with NEC;field modi­fications or additions must be in compliance with all applicable codes.
5. Wiring for field power supply must be rated 75 C minimum. Use copper, copper-clad aluminum, or aluminumconductors.Maximum incomingwire size for each terminal block is 500 kcmil.
6. Terminalblocks (TB3) are for external field control connections. Control connections must be Class1 wiring.
Fig. 23 — Field Wiring, One 2-Stage Thermostat — Units 38AH124 and 134
Internal 33CSUCE-06 relay contacts are rated for 1 amp/24 vac.
7. Field-supplied components (IFC, LLS-A1,A2, and LLS-B1,B2) must have a maximum sealed coil rating of 30 va each (0.25 amp at 120 vac and
0.13 amp at 230 vac). Thermostats must have a minimum pilot duty rating of 300 va (2.5 amps at 120 vac).
8. Replacement of factory wires must be with type 105 C wire or its equivalent.
9. Field-supplied liquid line solenoid valves installed at the evaporator are required on all units.
10. Units have 175 va of power available for field­installed accessories.
11. To minimize voltage drop, the following wire sizes
are recommended:
LENGTH —
Ft (M)
Up to 50 (15.2)
50-75 (15.2-22.9)
More Than 75 (22.9)
INSULATED WIRE — AWG
(35 C Minimum)
No. 18 No. 16 No. 14
LEGEND
AWG — American Wire Gage C—Compressor Contactor CCPS — Capacity Control Pressure
CR Control Relay HD Heating Device IFC Indoor-Fan Contactor IFR Indoor-Fan Relay kcmil — Thousand Circular Mils LLS Liquid Line Solenoid NEC National Electrical Code
R—Heating Relay (field-
RV Reversing Valve SDR Solenoid Drop Relay TB Terminal Block TR Timer Relay
Switch
(U.S.A. Standard) supplied 24-v sealed coil,
10 va maximum rating)
Factory Wiring Field Wiring
31
Page 32
32
*Field-supplied. NOTES:
1. Factory wiring is in accordance with NEC; field modifications or addi­tions must be in compliance with all applicable codes.
2. Wiring for field power supply must be rated 75 C minimum. Use cop­per, copper-clad aluminum, or aluminum conductors. Maximum incoming wire size for each terminal block is 500 kcmil.
3. Terminal blocks TB3 and TB4 are for external field control connec­tions. Control connections are to be Class 1 wiring.
4. Field-supplied components(IFC, LLS-A, andLLS-B) must havea maxi­mum sealed coil rating of 30 va each (.25 amp at 120 vac, .13 amp at 230 vac). AHMS IFC-AUX must have a minimum pilot duty rating of 200 va (1.7 amps at 120 vac, 0.9 amps at 230 vac) each.
5. Replacement of factory wires must be with type 105 C wire or its equivalent.
6. Field-supplied liquidlinesolenoid valvesinstalledat theevaporatorare required on all units.
7. Units have 175 va of power available for field-installed accessories.
AHMS — Air Handler Motor AUX Auxiliary
C—Compressor Contactor FU Fuse GND Equipment Ground IFC Indoor Fan Control kcmil — Thousand Circular Mils LLS Liquid Line Solenoid NEC National Electrical Code
Starter
(U.S.A. Standard)
LEGEND
SDR Solenoid Drop Relay TB Terminal Block TBX Terminal Block for Variable
TM Timer Motor TR Timer Relay TRAN — Transformer U—Unloader Solenoid
Air Volume Units
Factory Wiring Field Wiring
Fig. 24 — Field Wiring, Single ModuPanel™ Control, 38AH044-084 Dual-Circuit Units
Page 33
33
*Field-supplied. NOTES:
1. Factory wiring is in accordance with NEC; field modifications or addi­tions must be in compliance with all applicable codes.
2. Wiring for field power supply must be rated 75 C minimum. Use cop-
LEGEND
AHMS — Air Handler Motor AUX Auxiliary
C—Compressor Contactor FU Fuse GND Equipment Ground IFC Indoor Fan Control kcmil — Thousand Circular Mils LLS Liquid Line Solenoid NEC National Electrical Code
Starter
(U.S.A. Standard)
SDR Solenoid Drop Relay TB Terminal Block TBX Terminal Block for
TM Timer Motor TR Timer Relay TRAN — Transformer U—Unloader Solenoid
VariableAir Volume Units
Factory Wiring Field Wiring
per,copper-clad aluminum,oraluminum conductors.Maximumin com­ing wire size for each terminal block is 500 kcmil.
3. Terminalblocks TB3,TBX1, andTBX2 are forexternal field controlcon­nections. Control connections are to be Class 1 wiring.
4. Field-supplied components (IFC, LLS-A1, and LLS-A2) must have a maximum sealed coil rating of 30 va each (0.25 amp at 120 vac, 13 amp at 230 vac). AHMS IFC-AUX must have minimum pilot duty rating of400 va each(3.4 amps at120 vac, 1.8amps at 230vac) each.
5. Replacement of factory wires must be with type 105 C wire or its equivalent.
6. Field-supplied liquidlinesolenoid valvesinstalledat theevaporatorare required on all units.
7. Control has 175 va of power available for field-installed accessories.
Fig. 25 — Field Wiring, Single ModuPanel™ Control, 38AH044-084 Optional Single-Circuit Units
Page 34
*Field-supplied. NOTES:
1. Factory wiring is in accordance with NEC. Field modifications or additions must be in compliance with all applicable codes.
2. Wiring for fieldpower supply mustberated 75 Cminimum.Use copper,copper-clad aluminum, or aluminum conductors. Maxi­mum incoming wire size for each terminal block is 500 kcmil.
3. Terminal blocks TB3, TB4, TBX1, and TBX2 are for external field control connections. Control connections are to be Class 1 wiring.
4. Field-supplied components(IFC,LLS-A1,A2,B1, andB2)must have a maximum sealed coil rating of 30 va each (0.25 amp at 120 vac, 0.13 amp at 230 vac). AHMS IFC-AUX contact must have minimum pilot duty rating of 325 va each (2.7 amps at 120 vac, 1.4 amps at 230 vac).
5. Replacement of factory wires must be with type 105 C wire or its equivalent.
6. Field-supplied liquid linesolenoid valves installedatthe evapo­rator are required on all units.
7. Control has 25 va of power available for field-installed accessories.
Fig. 26 — Field Wiring, Single ModuPanel™ Control, Unit 38AH094
AHMS — Air Handler Motor Starter AUX Auxiliary C—Compressor Contactor FU Fuse GND Equipment Ground IFC Indoor Fan Control kcmil — Thousand Circular Mils LLS Liquid Line Solenoid NEC National Electrical Code
(U.S.A. Standard)
34
LEGEND
SDR Solenoid Drop Relay TB Terminal Block TBX Terminal Block for Variable
TM Timer Motor TR Timer Relay TRAN — Transformer U—Unloader Solenoid
Air Volume Units
Factory Wiring Field Wiring
Page 35
*Field-supplied. NOTES:
1. Factory wiring is in accordance with NEC. Field modifications or additions must be in compliance with all applicable codes.
2. Wiring for field power supply must be rated 75 C minimum. Use copper, copper-clad aluminum, or aluminum conductors. Maxi­mum incoming wire size for each terminal block is 500 kcmil.
3. Terminal blocks TB3, TB4, TBX1, and TBX2 are for external field control connections. Control connections are to be Class 1 wiring.
4. Field-supplied components (IFC, LLS-A1, A2, B1, and B2) must have a maximum sealed coil rating of 30 va each (0.25 amp at 120 vac,0.13amp at 230 vac).AHMS IFC-AUX contactmust have minimum pilot duty rating of 375 va each (3.1 amps at 120 vac,
1.6 amps at 230 vac).
5. Replacement of factory wires must be with type 105 C wire or its equivalent.
6. Field-supplied liquid line solenoid valves installed at the evapora­tor are required on all units.
7. Control has35va of poweravailable for field-installedaccessories.
Fig. 27 — Field Wiring, Single ModuPanel™ Control, Unit 38AH104
AHMS — Air Handler Motor Starter AUX Auxiliary C—Compressor Contactor FU Fuse GND Equipment Ground IFC Indoor Fan Control kcmil — Thousand Circular Mils LLS Liquid Line Solenoid NEC National Electrical Code
SDR Solenoid Drop Relay
(U.S.A. Standard)
35
LEGEND
TB Terminal Block TBX Terminal Block for
TM Timer Motor TR Timer Relay TRAN — Transformer U—Unloader Solenoid
VariableAir Volume Units
Factory Wiring Field Wiring
Page 36
*Field-supplied. NOTES:
1. Factory wiring is in accordance with NEC. Field modifications or additions must be in compliance with all applicable codes.
2. Wiring for field power supply must be rated 75 C minimum. Use copper, copper-clad aluminum, or aluminum conductors. Maxi­mum incoming wire size for each terminal block is 500 kcmil.
3. Terminal blocks TB3 and TBX1 are for external field control con­nections. Control connections are to be Class 1 wiring.
4. Field-supplied components(IFC, LLS-A1 andA2)musthave amaxi­mum sealed coil rating of 30 va each (0.25 amp at 120 vac,
0.13 amp at 230 vac). AHMS IFC-AUX contact must have mini­mum pilot duty rating of 400 va each (3.4 amps at 120 vac,
1.8 amps at 230 vac).
5. Replacement of factory wires must be with type 105 C wire or its equivalent.
6. Field-supplied liquid line solenoid valves installed at the evapora­tor are required on all units.
7. Units have 175 va of power available for field-installed accessories.
Fig. 28 — Field Wiring, Single ModuPanel™ Control, Units 38AH124 and 134
AHMS — Air Handler Motor Starter AUX Auxilliary C—Compressor Contactor FU Fuse GND Equipment Ground IFC Indoor Fan Control kcmil — Thousand Circular Mils LLS Liquid Line Solenoid NEC National Electrical Code
(U.S.A. Standard)
36
LEGEND
SDR Solenoid Drop Relay TB Terminal Block TBX Terminal Block for Variable
TM Timer Motor TR Timer Relay TRAN — Transformer U—Unloader Solenoid
Air Volume Units
Factory Wiring Field Wiring
Page 37
Table 15 — Main Power Connection and Control Circuit Wiring
MAIN POWER CONNECTION CONTROL CIRCUIT
Electrical
Characteristics
(V-Ph-Hz)
208/230-3-60 1 6 500 115† 24
460-3-60 575-3-60
230-3-50 1 6 500 230 24 380-3-60
380/415-3-50
346-3-50 1 3 500 200 24
LEGEND
kcmil — Thousand Circular Mils
*Conductors are from the safety disconnect.
†Control power is accomplished with a step-down transformer where primary voltage is field voltage.
Qty
Terminal
Blocks
1 3 500 115† 24
1 3 500 230 24
Qty
Parallel
Conductors*
Max Wire
Size
(kcmil)
Control Power
(V)
Safety Circuit
(V)
Step 5 — Install Accessories
LOW-AMBIENT OPERATION Units 38AH044-084, 124, and 134 — If operating tempera-
tures below 55 F (13 C) are expected, Motormastert III fan motor control is recommended. Refer to separate installa­tion instructions for low-ambient operation guidelines.
Units 38AH094 and 104 — If operating temperatures below 45 F (7 C) are expected, Motormaster III fan motor control is recommended. Refer to separate installation instructions for low-ambient operation guidelines.
MISCELLANEOUS ACCESSORIES — For applications requiring special accessories, the following packages are available: condenser coil hail guard package, gage panel, unloader package, unloader conversion kits, sound reduc­tion package, condenser coil protective grilles, compressor security grilles, ModuPanel™ control, and thermostat trans­former relay package.
PRE-START-UP
IMPORTANT:Beforebeginning Pre-Start-Up or Start­Up, review Start-Up Checklist at the back of this pub­lication. The Checklist assures proper start-up of aunit and provides a record of unit condition, application re­quirements, system information, and operation at ini­tial start-up.
Do not attempt to start the air-conditioning system until
following checks have been completed.
System Check
1. Check all system components, including the air­handling equipment. Consult manufacturer’s instruc­tions. If the unit has field-installed accessories, be sure all are properly installed and wired correctly. Refer to unit wiring diagrams.
2. Backseat (open) compressor suction and discharge shut­offvalves.Closevalvesoneturntoallowrefrigerantpres­sure to reach the test gages.
3. Open liquid line service valves.
4. Check tightness of all electrical connections.
5. Oil should be visible in the compressor sight glasses. See Fig. 29. An acceptable oil level in the compressor is from
1
⁄8to1⁄3of sight glass. Adjust the oil level as required. No oil should be removed unless the crank­case heater has been energized for at least 24 hours. See Preliminary Oil Charge section on page 38, for Carrier­approved oils.
6. Electrical power source must agree with unit nameplate.
Crankcase heaters on all units are wired into the control circuit, so theyare always operable as long as the main power supply disconnect is on (closed), even if any safety device is open. Compressor heat­ers must be on for 24 hours prior to the start-up of any compressor.
7. Crankcase heaters must be firmly locked into compres-
sors, and must be on for 24 hours prior to start-up.
8. Fan motors are 3-phase. Check rotation of fans during first start-up check. Fan rotation is clockwise as viewed from top of unit. If fan is not turning clockwise, reverse 2 of the power wires.
9. Check compressor suspension. On units 38AH044-084, 124, and 134, snubber washers (for noise suppression) can be moved with finger pressure. On units 38AH094 and 104, rails allow compressors to float freely on com­pressor rail springs.
10. On 38AH074,084 single-circuit units and Module 38AH134B, ensure that the packaging block located be­tween the oil equalization tube and the compressor cross­brace has been removed.
37
Page 38
DISCHARGE GAS THERMOSTAT
CYLINDER HEADS
OIL PRESSURE SWITCH AND CAPACITY CONTROL PRESSURE SWITCH CAPILLARIES
MUFFLER
HIGH­PRESSURE SWITCH
FAN CYCLING PRESSURE SWITCH
DISCHARGE GAS THERMOSTAT
PRESSURE RELIEF VALVE
NOTE: Units 38AH044-084and38AH124,134 compressors are pan mounted. Units38AH094 and 104 compressorsare mounted on rails.
SIGHT GLASS
RAIL
CRANKCASE HEATER
Fig. 29 — 06E Compressors, Typical
START-UP
Compressor crankcase heaters must be on for 24 hours before start-up. To energize the crankcase heaters, set the space thermostat above the ambient so there will be no de­mand for cooling. Close the field disconnect and turn on the fan circuit breakers. Leave the compressor circuit breakers off/open. The crankcase heaters are now energized.
Preliminary Checks
1. Ensure that compressor service valves are backseated.
2. Verify that each compressor on units 38AH044-084, 124,
and 134 floats freely on its mounting springs. Verify that each compressor on units 38AH094 and 104 floats freely on its rails.
3. Check that electric power supply agrees with unit name-
plate data.
4. Verify that compressor crankcase heaters are securely in
place.
5. Check that compressor crankcase heaters have been on at
least 24 hours.
6. Note that compressor oil level is visible in the sight glass.
7. Recheck for leaks using same procedure as previously out-
lined in Step 3 — Make Refrigerant Piping Connections, page 14.
OIL EQUALIZER LINE
8. If any leaks are detected, evacuate and dehydrate as pre-
Preliminary Oil Charge — Each compressor is fac-
tory charged with oil (see Table 3A, 3B, 4A, or 4B). When oil is checked at start-up, it may be necessary to add or re­move oil to bring it to the proper level. One recommended oil level adjustment method is as follows:
ADD OIL — Close suction shutoff valve and pump down crankcase to 2 psig (14 kPa). (Low-pressure cutout must be jumped.) Wait a few minutes and repeat until pressure re­mains steady at 2 psig (14 kPa). Remove oil fill plug above the oil level sight glass, add oil through plug hole, and re­place plug. Run compressor for 20 minutes and check oil level.
LOW­PRESSURE SWITCH
SIGHT GLASS
MOUNTING SPRING (HIDDEN)
viously outlined in Step 3 — Make Refrigerant Piping Connections, page 14.
IMPORTANT: For units with 2 compressors per re­frigeration circuit, both compressors must be running to adjust the oil level. Two oil level equalizer lines between compressors distribute the oil to each compressor.
38
Page 39
NOTE: Use only Carrier approved compressor oil. Ap­proved sources are: Petroleum Specialties Inc. (Cryol 150A), Texaco, Inc. (CapellaWF-32-150), and Witco Chemical Co. (Suniso 3GS). Do not reuse oil that has been drained out, or oil that has been exposed to atmosphere.
REMOVE OIL — Pump down compressor to 2 psig (14 kPag). Loosen the1⁄4-in. (6.4-mm) pipe plug at the com­pressor base and allow the oil to seep out past the threads of the plug.
NOTE: The crankcase will be slightly pressurized. Do not remove the plug, or the entire oil charge will be lost.
Small amounts of oil can be removed throughtheoil pump
discharge connection while the compressor is running.
PreliminaryCharge— RefertoGTAC II (General Train-
ing Air Conditioning), Module 5, Charging, Recovery, Recycling, and Reclamation for charging procedures. Using the liquid charging method and charging by weight proce­dure, charge each circuit with the amount of R-22 listed in Table 3A, 3B, 4A, or 4B.
Never charge liquid into the low-pressure side of sys­tem. Do not overcharge. During charging or removal of refrigerant, be sure indoor-fan system is operating.
Start Unit — The field disconnect is closed, the fan cir-
cuit breaker is closed, and the space thermostats are setabove ambient so that there is no demand for cooling. Only the crankcase heaters are energized.
Close the compressor circuit breakers and then reset both space thermostats below ambient so that a call for stage one cooling is ensured. Lead refrigeration circuit ther-
mostat TC1 must be set to call for cooling at a lower tem­perature than lag refrigeration circuit thermostat TC2.
See Table 16 for lead/lag circuits on all units. Now set TC2 for cooling.
NOTE: Do not use circuit breakers to start and stop the com­pressor except in an emergency.
38AH044-084 DUAL-CIRCUIT UNITS — Start-up of lead compressor A1 (Table 16) will be delayed from 12 seconds
1
⁄2minutes from the time the call for cooling is initiated
to 5 by TC1.Afterthe lead compressor starts, close the TC2 ther­mostat to start lag circuit compressor B1. Compressor B1 will start a minimum of 60 seconds after thermostat TC2 is closed.
38AH044-084 OPTIONAL SINGLE CIRCUIT UNITS — Start-up of lead compressor A1 (Table 16) is delayed from 12 seconds to 5 is initiated by TC1. Closure of TC2 will actuate LLS-A2. Lag compressorA2 is controlled by D-D2 timer contacts and capacity control pressure switches (CCPSs) which monitor compressor suction pressure. The lag compressor starts ap­proximately 21⁄2minutes after the lead compressor starts if the suction pressure is above the CCPS set point.
38AH094,104 UNITS — Start-up of lead circuit A, compressor A1 (Table 16) is delayed from 12 seconds to 51⁄2minutes from the time the call for cooling is initiated. After lead circuit A, compressor A1 starts, close refrig­eration circuit thermostat TC2 to start lag circuit B, lead
1
⁄2minutes from the time the call for cooling
compressor B1. Start-up of compressor B1 is delayed from 12 seconds to 5
1
⁄2minutes. (Circuit B of unit 38AH094 has
only one compressor.)
Each circuit’s lead compressor start-up is controlled by the unit control timer. The circuit’s lag compressor start-up is controlled by the D-D2 timer contacts and capacity control pressure switches (CCPSs) which monitor compres­sor suction pressure. The circuit’s lag compressor will start approximately 2
1
⁄2minutes after a call for cooling if com-
pressor pressure is above CCPS set point. 38AH124,134 UNITS — Start-up of the lead circuit
(Module 124A or 134A) lead compressor A1 (Table 16) is delayed from 12 seconds to 51⁄2minutes from the time the call for cooling is initiated by TC1. Lag compressor A2 is controlled by D-D2 timer contacts and capacitycontrol pres­sure switches (CCPSs) which monitor compressor suction pressure. The lag compressor starts approximately 21⁄2min­utes after the lead compressor starts if the suction pressure is above the CCPS set point.
After the lead circuit (Module 124A or 134A) lead com­pressorA1(Table 16) starts,closetheTC2 thermostat to start the lag circuit (Module 124B or 134B) lead compressor(A1). Lag circuit compressor A1 start-up is delayed from 12 sec­onds to 5
1
⁄2minutes from the time the call for cooling is initiated by TC2. Lag compressor A2 is controlled by D-D2 timer contacts and CCPSs which monitor compressor suc­tion pressure. Lag compressor A2 starts approximately 21⁄ minutes after lead compressor A1 starts if the suction pres­sure is above the CCPS set point.
Adjust Refrigerant Charge
Never charge liquid into the low-pressure side of sys­tem. Do not overcharge. During charging or removal of refrigerant, be sure indoor-fan system is operating.
With all fans operating, and all compressors on the cir-
cuit being serviced operating at full capacity, adjust the
refrigerant charge in accordance with the unit charging charts located on the inside of the control box doors and in Fig. 30-43. Charge vapor into compressor low-side service port located above oil pump crankshaft housing. Measure pressure at the liquid lineservicevalve,makingsureaSchrader depressor is used if required. Also, measure liquid line tem­perature as close to the liquid service valve as possible.Add charge until the pressure and temperature conditions of the charging chart curve are met. If liquid pressure and tempera­ture point fall above curve, add charge. If liquid pressure and temperature point fall below curve, reduce the charge until the conditions match the curve.
If the sight glass at location A (Fig. 11 and 12) is cloudy, check refrigerant charge again. Ensure all fans and com- pressors on the circuit being serviced are operating. Also ensure maximum allowable liquid lift has not been exceeded.
If the sight glass at location A is clear and the sight glass at location B is cloudy, a restriction exists in the line between the 2 sight glasses. Check for a plugged filter drier or partially open solenoid valve. Replace or repair, as needed.
2
39
Page 40
Table 16 — Index of Lead/Lag Circuits and Compressors
UNIT
38AH
LEAD CIRCUIT AAAA
Compressor, Lead A1 A1 A1 A1 A1 A1 Compressor; Lag *A2A2A2A2A2
LAG CIRCUIT B†BB
Compressor, Lead B1 B1 B1 A1 A1 Compressor; Lag * * B2 A2 A2
LEGEND
OPT — Optional Single-Circuit Units STD — Standard Dual-Circuit Units
*Circuit has only one compressor. †Units have only one circuit.
044-084
STD
044-084
OPT
094 104 124 134
Module
124A
Module
124B
Module
134A
Module
134B
Check Compressor Oil Level— After adjusting the
refrigerant charge, allow each circuit to run fully loaded for 20 minutes. Running oil level should be1⁄8to1⁄3up on the sight glass. Stop the compressors at the field power supply disconnect and check the crankcase oil level. Add oil only if necessary to bring the oil into view in the sight glass. If oil is added, run the circuit for an additional 10 minutes, then stop and check oil level. If the level remains low, check the piping system for proper design for oil return; also, check the system for leaks.
If the initial check shows too much oil (too high in the sight glass) remove oil to proper level. See Preliminary Oil Charge for proper procedure for adding and removing oil.
When the above checks are complete, repeat the proce­dure with the unit operating at minimum load conditions.
UNITS 38AH044-084,124, AND 134 — For this minimum load check, run the lead compressor ofeach refrigeration cir­cuit fully unloaded with the lag compressor not operating.
Unload the compressor(s) by turning the control set point adjustment nut counterclockwise until the adjustment nut stops. The unloader is now at 0 psig (0 kPag) set point. If
electrically actuated unloaders are installed, energizethe so­lenoid to unload the compressor. Recheck the compressor oil level as described inCheck Compressor Oil Level above.
Return unloader to original setting after checks are
complete. UNITS 38AH094,104 — For this minimum load check, the
lead compressor (A1, B1) of each refrigeration circuit is un­loaded. See T able16. The lag compressor(A2,B2 [38AH104 only]) of each refrigeration circuit must not be operating.
Unload the compressor(s) by turning the control set point adjustment nut counterclockwise untiltheadjustmentnutstops. The unloader is now at 0 psig (0 kPag) set point. If electri­cally actuated unloaders are installed, energize the solenoid to unload the compressor.
Return unloader to original setting after checks are complete.
Final Checks — Ensure all safety controls are operat-
ing, control panel covers are on, and the service panels are in place.
40
Page 41
Fig. 30 — Charging Chart — Unit 38AH044; 50/60 Hz — Dual Circuit
Fig. 31 — Charging Chart — Unit 38AH054; 50/60 Hz — Dual Circuit
41
Page 42
Fig. 32 — Charging Chart — Unit 38AH064; 50/60 Hz — Dual Circuit
Fig. 33 — Charging Chart — Unit 38AH074; 50/60 Hz — Dual Circuit
42
Page 43
Fig. 34 — Charging Chart — Unit 38AH084; 50/60 Hz — Dual Circuit
Fig. 35 — Charging Chart — Unit 38AH044;
50/60 Hz — Optional Single Circuit
Fig. 36 — Charging Chart — Unit 38AH054;
50/60 Hz — Optional Single Circuit
43
Page 44
Fig. 37 — Charging Chart — Unit 38AH064;
50/60 Hz — Optional Single Circuit
Fig. 38 — Charging Chart — Unit 38AH074;
50/60 Hz — Optional Single Circuit
Fig. 39 — Charging Chart — Unit 38AH084;
50/60 Hz — Optional Single Circuit
44
Page 45
Fig. 40 — Charging Chart — Unit 38AH094; 50/60 Hz
Fig. 41 — Charging Chart — Unit 38AH104; 50/60 Hz
Fig. 42 — Charging Chart — Modules 124A, 124B,
and 134A; 50/60 Hz
Fig. 43 — Charging Chart — Module 134B;
50/60 Hz
45
Page 46
SERVICE
ELECTRIC SHOCK HAZARD Turn off all power to unit before servicing.
The ON-OFF switch on control panel does not shut off control power; use field
disconnect.
CoilCleaning — Clean the coils with a vacuum cleaner,
compressed air, water, or a non-wire bristle brush.
Refrigerant Circuit
LEAK TESTING — Units are shipped with a holding charge of R-22 (see Table 3A, 3B, 4A, or 4B) and should be under sufficient pressure to conduct a leak test. If there is no pres­sure in the system, introduce enough nitrogen to search for the leak. Repair the leak using good refrigeration prac­tices.Afterleaks are repaired, system must be evacuated and dehydrated using methods described inGTAC II ,Module 4, System Dehydration.
REFRIGERANT CHARGE (Refer to Table 3A, 3B, 4A, or 4B) —At the liquid line connection point on each circuit is a factory-installed liquid line service valve. On each valve is a1⁄4-in. Schrader connection for charging liquid refrigerant.
Charging with Unit Off and Evacuated — Close liquid line service valve before charging. Weigh in charge shown in Table 3A, 3B, 4A, or 4B. Open liquid line service valve; start unit and allow it to run several minutes fully loaded. Check for a clear sight glass. Be sure clear condition is liq­uid and not vapor. Complete charging the unit in accordance with Start-Up, Adjust Refrigerant Charge, page 39.
Charging with Unit Running —Ifchargeistobeaddedwhile unit is operating, it is necessary to have all condenser fans and compressors operating. It may be necessary to block con­denser coils at low-ambient temperatures to raise condens­ing pressure to approximately 280 psig (1931 kPag) to turn all condenser fans on. Do not totally block a coil to do this. Partially block all coils in uniform pattern. Charge vapor into compressor low-side service port located above oil pump crankshaft housing. Charge each circuit until sight glass shows clear liquid.
Troubleshooting— Refer toTroubleshooting chart lo-
cated at back of book.
Oil Pressure Safety Switch (OPS) — An oil pres-
sure safety switch for each of the independent refrigerant circuits shuts off the compressor in thatcircuit if oil pressure is not established at start-up or maintained during operation. If the OPS stops the unit, determine and correct the cause before restarting the unit. Failure to do so constitutes equip-
ment abuse and could affect the warranty.
Compressor Motor Protection
CIRCUIT BREAKER —Amanual reset, calibrated trip cir­cuit breaker for each compressor protects against overcur­rent. Do not bypass connections or increase size of circuit
breakerforany reason.Iftrouble occurs, determine the cause and correct it before resetting the breaker.
DISCHARGE GAS THERMOSTAT — A sensor in the cylinder head of each compressor (Fig. 29) shuts down the compressor if excessively high discharge gas temperature is sensed. If the discharge gas thermostat shuts the unit down, it may be reset by the thermostat orpower disconnect switch.
CRANKCASE HEATER (See Fig. 29) — Each compressor has an electric crankcase heater located in the bottom cover.
The heater is held in place by a clip and bracket and must be tightly connected since exposure to the air causes the heater to burn out. Each heater is wired into the compressor control circuit through a relay which energizes only when the com­pressor is off. The heater keeps the oil at a temperature that prevents excessive absorption of refrigerant during shut­down periods.
Energize the crankcase heaters when the unit is not run­ning except during prolonged shutdown or servicing. Ener-
gize the heaters at least 24 hours before restarting the unit after prolonged shutdown.
TIME GUARDt FUNCTION —Thisfunctionpreventscom­pressors from short-cycling.
Fan Motor Protection — Fan motors are protected
by a single circuit breaker for all motors.
Head Pressure Control— Head pressure control re-
duces condenser capacity under low-ambient conditions. This is achieved by fan cycling control (standard, all units) and Motormastert III control accessory (field installed).
FAN CYCLING —All condensing units have standard pro­vision for fully automatic intermediate season head pressure control through fan cycling (see Table 17).
38AH044-084 Dual-Circuit Units — Fans no. 3 and 4 are cycled by pressure control on all units. On 38AH074 and 084, fans no. 5 and 6 are also cycled by pressure control.
38AH044-084 Optional Single Circuit Units — Fans no. 3 and 4 are cycled by pressure control on all units. On 38AH074 and 084, fans no. 5 and 6 are cycled by an air-temperature switch located in the bottom shelf of the control box.
Units 38AH094,104 — Fans no. 3 through 6 are cycled by pressure control.
Units 38AH124,134 — Fans no. 3 and 4 on each unit mod­ule are cycled by pressure control. On module 134B only, fans no. 5 and 6 are cycled by an air-temperature switch lo­cated in the bottom shelf of the control box.
Pressure control is achievedviaafancyclingpressureswitch located on the cylinder head of the unit or circuit lead com­pressor (see Fig. 29).
The air-temperature switch used to control fans no. 5 and 6 on 38AH074,084 optional single-circuitunits and on mod­ule 134B is closed and cycles the fans on when the ambient­air temperature is above 70 F (21 C).
Table 17 — Fan Cycling Control — Psig (kPag)
Control by Pressure* ±10 (69) Switch Opens 160 (1103) Switch Closes 255 (1758)
*On all units, fans no. 3 and 4; also on unit 38AH074, 084 (dual-
circuit units only) and 38AH094,104, fans no. 5 and 6.
NOTE: Fansno.1 and 2 arenoncycling.Units 38AH074,084 optional single-circuit units and module 134B fans no. 5 and 6 are cycled by an air-temperature switch which operates above 70 F (21 C) ambient-air temperature.
38AH044-064,
Modules 124A, 124B,
134A
38AH074-104,
Module 134B
46
Page 47
WinterStartControl— A2
1
⁄2-minute low-pressure switch (LPS) bypass function in the timer prevents nuisance LPS trips during start-up in low-ambient conditions.
High-Pressure Switch — This switch has nonadjust-
able settings. Figure 29 shows connection on acylinderhead. See Table 18 for pressure switch settings.
NOTE: High-pressure switch must be removed from cylin­der head before removing compressor from the unit.
TO CHECK — Slowly close the discharge shutoff valve un­til the compressor shuts down. This should be at approxi­mately 426 psig (2935 kPag). Slowly open the valve. When the pressure drops to approximately 320 psig (2205 kPag), the pressure switch resets. To reenergize the control circuit, manually switch the fan circuit breaker off and then on. The compressor starts again under Time Guardt controls.
Low-PressureSwitch— Thelow-pressureswitch(LPS)
has fixed nonadjustable settings. It is located at the pump end of the compressor above the bearing head. See Table 18 for pressure switch settings.
TO CHECK — Slowly close the suction cut-off valve and allow the compressor to shut down. This should occur at approximately 27 psig (186 kPag). Slowly open the valve. The compressor restarts under Time Guard control when the pressure builds to approximately 67 psig (462 kPag).
38AH094,104 — Capacity control is achieved bya pressure­actuated cylinder bank unloader on the lead compressor (A1, B1) on each of the 2 refrigeration circuits.As the cool­ing load decreases and the suction pressure drops, the un­loader actuates at the pre-set suction pressure and unloads the cylinder bank. (See Fig.44 and Table 20.)The unloading of the compressor cylinder bank has no effect on the opera­tion of the circuit lag compressor (A2,B2 [except 38AH094, circuit B]) which is controlled by fixed setting capacity con­trol pressure switches (CCPSs) as follows:
CUT-IN —
Psi (kPa)
CCPS 1 83 (572) 63 (531) CCPS 2 80 (551) 53 (365)
CCPS — Capacity Control Pressure Switch
CUTOUT —
Psi (kPa)
Pressure Relief — High-side pressure relief is pro-
vided by a fusible plug in the liquid line at the service valve. For low-side pressure relief, a fusible plug is inserted in the side of the accumulator (all units except38AH044-084 dual­circuit, constant-volume units). See Fig. 45. The 38AH044­084 dual-circuit, constant-volume units have a fusible plug in the suction tubing. A pressure relief valve installed on the compressor relieves at 450 psig (3102 kPag) (see Fig. 1-6).
Table 18 — Pressure Switch Settings,
Psig (kPag)
SWITCH CUTOUT CUT-IN
High
Low
426 ± 7 320 ± 20
(2935 ± 48) (2205 ± 138)
27 ± 4 67 ± 7
(186 ± 28) (462 ± 48)
Capacity Control
38AH044-084 DUAL-CIRCUIT UNITS — Capacity con­trol is achieved by a pressure-actuated cylinder bank un­loader on lead compressor A1.As the cooling load decreases and the suction pressure drops, the unloader actuates at the pre-set suction pressure and unloads the cylinder bank. (See Fig. 44 and Table 19A.) The unloading of the compressor cylinder bank has no effect on the operation of lag compres­sor B2, which is controlled by TC2.
38AH044-084 SINGLE-CIRCUIT UNITS AND MOD­ULES 124A, 124B, 134A, AND 134B — Capacity control is achieved by a pressure-actuated cylinder bank unloader on lead compressor A1. See Table 16. As the cooling load decreases and the suction pressure drops, the unloader actuates at the pre-set suction pressure and unloads the cyl­inder bank. (See Fig. 44 and Table 19B and 20.) Lag com­pressorA2 is controlled by fixed settingcapacitycontrolpressure switches (CCPSs) as follows:
CUT-IN —
Psi (kPa)
CCPS 1 83 (572) 63 (531) CCPS 2 80 (551) 53 (365)
CCPS — Capacity Control Pressure Switch
If suction pressure continues to drop after lead compres­sor A1 unloads and lag compressor A2 is operating, A2 will stop operating when the suction pressure drops to the CCPS cutout point.
CUTOUT —
Psi (kPa)
Unloader Settings
Unload, psig (kPag) 56 (386) Load, psig (kPag) 76 (524)
*Unloader location.
Fig. 44 — Unloader Location and Settings
47
Page 48
Table 19A — One 2-Stage Thermostat Capacity
Control for 38AH044-084 Dual-Circuit Units
QUANTITY OF LOADED
UNIT
38AH
044
054
064
074
084
*Requires units with VAV (variable air volume) factory-supplied
option.
NOTE:Unitshave 2 independentrefrigerationcircuits. CircuitA islead circuit.
COMPRESSOR CYLINDERS
Circuit
A
4 4 8 100 24675 40450 20225
4 6 10 100 26879 2 4 6* 59 40442 20221
6 6 12 100 4 6 10 84 2 6 8* 68 60648 40432 2 0 2* 16
6 6 12 100 4 6 10 86 2 6 8* 72 60643 40429 2 0 2* 15
6 6 12 100 4 6 10 83 2 6 8* 66 60650 40433 2 0 2* 17
Circuit
B
Total
SYSTEM
CAPACITY
(%)
Table 19B — One 2-Stage Thermostat Capacity
Controlfor38AH044-084OptionalSingle-CircuitUnits
UNIT
38AH
044
054
064
074
084
*Requires accessory unloader on lead 06E-265 compressor (A1).
†Requires VAV (variable air volume) factory-installed option or ac-
cessory unloader.
QUANTITY OF
LOADED CYLINDERS
8 100 675 450 225
10 100
881 660 656 437 2* 19*
12 100 10 82
864 656 436 2† 18
12 100 10 81
862 657 438 2† 19
12 100 10 83
866 650 433 2† 17
SYSTEM
CAPACITY
(%)
Table 20 — One 2-Stage Thermostat Capacity
Control for 38AH094-134 Units
UNIT
38AH
094 80844
104
124
134
*RequiresVAV(variableair volume) unitoraccessory unloader(s)field
installed oncircuit lead compressor.Lead compressor is identifiedin Table 16, page 40.
†Requires field-installedaccessory unloader on circuitleadcompres-
sor. Lead compressor is identified in Table 16, page 40.
NOTES:
1. Temperatures calculated with the minimum number of fans oper­ating per circuit.
2. See Table 16, page 40, for information on lead and lag circuits.
QUANTITY OF LOADED
COMPRESSOR CYLINDERS
Ckt A Ckt B Total
10 6 16 100 10 4 14 85 10 2 12 70* 10 0 10 55
60633 40422
10 12 22 100
81220 91 81018 82
10 6 16 73
6 6 12 55 6 4 10 45 06627 40418 04418 2† 0 2 9†
12 12 24 100 10 12 22 92 10 10 20 83
8* 10 18 75* 61016 67 6 8* 14 58* 6 6 12 50 4 6 10 42 60625 40417 2* 0 2 8*
12 12 24 100 10 12 22 92 10 10 20 83
8* 10 18 75* 61016 67 6 8* 14 58* 6 6 12 50 4 6 10 42 60625 40417 2* 0 2 8*
SYSTEM
CAPACITY
(%)
CONTROL SET POINT — Control set point (cylinder load point) is adjustable from 0 to 85 psig (0 to 586 kPag). To adjust the set point, turn the control set point adjust­ment nut clockwise to bottom stop. (See Fig. 46.) In this position, load-up set point is 85 psig (586 kPag). Turn adjustment counterclockwise to desired control set point. Every full turn clockwise decreases the load-up set point by
7.5 psig (52 kPag).
PRESSURE DIFFERENTIAL — Pressure differential (difference between cylinder load and unload points) is adjustable from 6 to 22 psig (41 to 152 kPag). To adjust, turn pressure differential adjustment screw counterclock­wise to back stop position. The differential pressure is now adjusted to 6 psig (41 kPag). Turntheadjustmentscrewclock­wise to adjust the differential pressure. Every full clockwise turn increases the differential by 1.5 psig (10 kPag).
48
Page 49
CONDENSER COIL
FUSIBLE PLUG
SUCTION LINE
ACCUMULATOR
DISCHARGE LINE
COMPRESSOR RAIL
Fig. 45 — Accumulator and Fusible Plug
Timer Functions — (See Timer Cycle, Fig. 47.) Each
refrigeration circuit is controlled by an independent timer which allows for the independent operation of each refrig­eration circuit.
NOTE: Unit 38AH044-084 optional single-circuit units have one timer which controls the lead compressor. Lag compres­sor is controlled by CCPS (capacity controlpressure switch).
SWITCHA— The timer is energized through contacts A-A1 or A-A2. This establishes the Time Guardt function which prevents compressor short-cycling. Start of compressor is delayed approximately 5.5 minutes after shutdown.
SWITCH B — The compressor is initially energized through contacts B-B1.
1
SWITCH D — Contacts D-D1 provide a 2
⁄2-minute bypass of the low-pressure switch at start-up for winter-start con­trol. On 38AH044-084 optional single-circuit units, contacts D-D2 control start-up of compressor A2.
SWITCH E — Contacts E-E1 provide a 40-second bypass of the oil pressure switch at start-up. If oil pressure does not build to the required minimum pressure in 40 seconds, the compressor shuts down and the control circuit locks out.
On 38AH044-084 dual-circuit and 38AH094,104 units, lag circuit B start-up is delayed 60 seconds after a call for cool­ing is made to the circuit. This prevents compressor(s) in both lead and lag circuits from starting at the same time.
Control Circuit Reset— The control circuit locks out
if the unit shuts down because of low oil pressure, high discharge gas temperature (DGT), or excessive high-side pres­sure. To reset the control circuit, open and close the fan circuit breaker (FCB). This resets the timer, and the unit restarts under Time Guard control. At start-up, if the low­pressure switch (LPS) does not close after 21⁄2minutes, the unit shuts down. When the pressure builds enough for the LPS to cut in, the control circuit is energized automatically and start-up proceeds under Time Guard control.
Fig. 46 — Pressure-Actuated Capacity Control Valve
CONTROL
Sequence of Operation —
electromechanical components. Each refrigeration circuit (except 38AH044-084 optional single-circuit units) is oper­ated by an independent timer which controls the operation sequence of each circuit.
On a call for cooling, first stage cooling thermostat TC1 closes. Condenser fans and timer (TM) are energized. After approximately 7 seconds, timer contacts E-E1 close. Approximately 12 seconds after TC1 closes, normally-open timer contacts B-B1 close for 1 second. This energizes compressor A1 contacts CA1 and starts the compressor. At the same time, solenoid drop relays (SDRs) and liquid line solenoid valve no. 1 (LLS-A for 38AH044-084 dual-circuit units; LLS-A1 for all other units) open, and timer relay no. 1 (TR2) is energized. Normally openTR2contactsclose, completing a circuit around B-B1 and through compressor A1 contactors to maintain compressor operation when B-B1 contacts open. Contacts E-E1 remain closed for approxi­mately 40 seconds to bypass the oil pressure switch (OPS). If oil pressure is insufficient when contacts E-E1 open, the compressor stops, the timer cycles off, and the control cir­cuit locks out. At start-up, timer contacts D-D1 are closed, bypassing low-pressure relay contacts LPR-A for 2 utes. This provides a winter start-up feature.
1
Approximately 2 tacts D-D1 open and D-D2 close. If pressure is insufficient to close the low-pressure switch, the low-pressure switch relay is open, the compressor shuts down, and the Time Guard control is initiated. (Time Guard control prevents compres­sor from restarting for 5 minutes after the demand for cool­ing is satisfied.)
⁄2minutes after TC1 closes, timer con-
Units are controlled with
1
⁄2min-
49
Page 50
38AH044-084 DUAL-CIRCUIT UNITS; 38AH094,104 — If circuit A operation is insufficient for the cooling require­ments, the thermostat second stage TC2 closes to bring cir­cuit B on-line for cooling. This circuit follows the same se­quence of operation as the lead circuit, except a 60-second time delay relay (TDR) delays compressor start-up for 60 seconds after the call for cooling.
38AH044-084 OPTIONALSINGLE-CIRCUIT UNITS: MOD­ULES 124A, 124B, 134A, AND 134B
NOTE: This sequence of operation assumes that 2 thermo­stats control units 38AH124 or 134with one thermostat con­trolling each module.
If compressor A1 is insufficient for the cooling require­ments, the thermostat second stage closes, which opens the liquid line solenoid valve LLS-A2. CompressorA2starts only after D-D2 contacts in the timer close and the suction pres­sure is sufficient to close the capacity control switches.
ALL UNITS — When the fan switch is set for automatic (AUTO) operation, the indoor-fan contactor (IFC) is cycled with the lead compressor. If the fan switch is set for con­tinuous (CONT), the IFC is energized as long as the unit power is on.
RestartAfterStoppage by Safety Control— The
high-pressure switch, compressor discharge gas thermostats, and the oil pressure switch must be reset manually by break­ing the control power supply at any of the following points: control circuit fuse, fan motor circuit breaker, or the ther­mostat. Restart follows the Time Guardt control delay.
Stoppage by low-pressure switch results in Time Guard control delay, then unit attempts normal restart.
The compressor motor overcurrent protectors are manual­reset circuit breakers. Reset of control circuit may also be necessary.
IndependentRefrigerant Circuit Controls — Each
refrigeration circuit is controlled by independent circuitry. Therefore, it is possible to maintain partial cooling capabil­ity even if one compressor is inoperable.
NOTE: The 38AH044-084 optional single-circuit units do not have independent control circuitry.
NOTE: Black denotes closed contacts.
Fig. 47 — Timer Cycle
Unit Control Box — (See Fig. 48.) Viewed facing com-
pressors, the control box is at left end of the unit. All in­coming power enters through the control box. The control box contains power components and electronic controls. Outer panels are hingedandlatchedforeasyopening.Removescrews to remove inner panels. Outer panels can be held open for service and inspection by using door retainer on each panel. Remove bottom pin from door retainer assembly, swing re­tainer out horizontally, and engage pin in one of the retainer ears and the hinge assembly.
Condenser Fans — Each fan is supported by a formed
wire mount bolted to fan deck and coveredwitha wire guard. The exposed end of fan motor shaft is protected fromweather by grease. If fan motor must be removed for service or re­placement, be sure to regrease fan shaft, and reinstall fan guard. For proper performance, fan should be7⁄8in. (22 mm) below top of venturi on the fan deck to top of the fan hub for 60-Hz units, and1⁄2in. (13 mm) for 50-Hz units. (See Fig. 49.) Tighten set screws to 15 ± 1 ft-lbs (20 ± 1.3 N-m). Figure 49shows proper position of mounted fan.
IMPORTANT: Check for proper fan rotation (clock­wise viewed from above). If necessary to reverse, switch leads.
50
Page 51
TRANSFORMERS
TIMERS
TIME-DELAY RELAY
OIL PRESSURE SWITCHES
FUSE HOLDERS
TERMINAL BLOCKS
Fig. 48 — Unit Control Box
FAN CONTACTORS
COMPRESSOR CIRCUIT BREAKERS
FAN CIRCUIT BREAKER
TERMINAL BLOCKS
COMPRESSOR CONTACTORS
RequiredCompressor Modification for 38AH044­084 Optional Single-Circuit Units, When Com­pressorA1 is Out —
pressor no.1 mustbeoperable.Ifitis not operable, the following temporary modifications must be made to keep the unit running:
1. Change the oil pressure switch connections from com­pressor A1 to compressor A2.
2. Connect compressor A2 into the Time Guardt circuit as compressor A1 was originally.
3. Open compressor A1 circuit breaker.
NOTE: Make sure the crankcase heaters are energized when compressors are off.
To maintain unit operation, com-
NOTE: Fan rotation is clockwise when viewed from top of unit.
Fig. 49 — Condenser Fan Adjustment
51
Page 52
Compressor Removal — Access to the pump end
of the compressor is from the compressor side of the unit. Access to the motor end of the compressor is from the inside of the unit. All compressors can be removed from the com­pressor side of the unit.
IMPORTANT:All compressor mounting hardwareand support brackets removed during servicing mustbe re­installed prior to start-up.
1. Disconnect power to unit; lockout power to compressor.
2. Close suction and discharge service valves.
3. Relieve refrigerant pressure into a refrigerant recovery system.
4. Remove: a. Fan-cycling pressure switch (FCPS) b. High-pressure switch c. Low-pressure switch d. Oil-pressure switch e. Discharge gas temperature switch.
5. Disconnect power wires at terminal box and disconnect conduit.
6. Disconnect wires from crankcase heater.
7. Disconnect service valves from compressor. NOTE: On 38AH044-084 optional single-circuit units and
units with 2 compressors per circuit, disconnect both oil equalizer lines located on the motor barrel and on the oil pump sump.
8. Units 38AH044-084, 124, and 134: a. Remove 4 large screws securing compressor mount-
ing pan to unit base rail.
b. Slide compressor (on mounting pan) to outside of unit
frame; support and/or lower to ground.
c. Unbolt compressor from mounting pan and remove.
9. Units 38AH094, 104: a. Remove4largescrewssecuringcompressortothecom-
pressor rails.
b. Lift compressor off mounting bolts and remove.
CompressorReplacement — Perform the following:
1. Reverse procedure in Compressor Removal section to end of Step 4.
2. Reinstall service valves and safety switches, and tighten to torques as listed:
Torque
Tighten discharge valves to —
20-25 ft-lbs ( 27- 34 N-m) 06E-250 80-90 ft-lbs (109-122 N-m) 06E-265,275,299
Tighten suction valves to —
80- 90 ft-lbs (109-122 N-m) 06E-250 90-120 ft-lbs (122-163 N-m) 06E-265,275,299
Tighten the following fittings as specified —
60 ft-lbs (81 N-m) Discharge Gas Thermostat
120 in.-lbs (13.5 N-m) High-Pressure Switch, Fan-
Cycling Pressure Switch
120 in.-lbs (13.5 N-m) Low-Pressure Switch
3. Leak-check and evacuate system, reclaim refrigerant.
4. Recharge system per pre-start-up and start-up sequences. Recheck oil levels.
5. Energize crankcase heater for 24 hours prior to restart of system.
OIL CHARGE — (Refer to Table 3A, 3B, 4A, or 4B.) All units are factory charged with oil. Acceptable oil level for each compressor is from
1
⁄8to1⁄3of sight glass (see Fig. 29,
page 38).
When additional oil or a complete charge is required, use
only Carrier-approved compressor oil. Approved oils are: Petroleum Specialties, Inc. — Cryol 150A(factoryoil charge)
Texaco, Inc. — Capella WF-32-150 Witco Chemical Co. — Suniso 3GS
COMPRESSOR
06E-250 17 8.0 06E-265 21 9.9 06E-275 21 9.9 06E-299 19 9.0
OIL REQUIRED
Pts L
Compressor(s)
Do not reuse drained oil, and do not use any oil that has
been exposed to atmosphere.
Adjust oil level in accordance with Start-Up, Preliminary
Oil Charge, page 38.
52
Page 53
TROUBLESHOOTING
PROBLEM SOLUTION COMPRESSOR DOES NOT RUN Contactor Open
1. Power off. 1. Restore power.
2. Fuses blown in field power circuit. 2. After finding cause and correcting, replace with correct
3. No control power. 3. Check secondary fuse(s); replace with correct type and
4. Thermostat circuit open. 4. Check thermostat setting.
5. Multi-function timer not operating. 5. Check timer for proper operation; replace if defective.
6. Compressor circuit breaker tripped. 6. Check for excessive compressor current draw. Reset
7. Safety device lockout circuit active. 7. Reset lockout circuit at thermostat or circuit breaker.
8. Low-pressure switch open. 8. Check for refrigerant undercharge, obstruction of indoor
9. High-pressure switch open. 9. Check for refrigerant overcharge, obstruction of outdoor
10. Discharge gas temperature switch open. 10. Check for open condition. Allow for reset. Replace if
11. Loose electrical connections. 11. Tighten all connections.
12. Compressor stuck. 12. See 06E compressor service literature. Contactor Closed
1. Compressor leads loose. 1. Check connections.
2. Motor windings open. 2. See 06E compressor service literature.
3. Single phasing. 3. Check for blown fuse. Check for loose connection at
COMPRESSOR STOPS ON HIGH-PRESSURE SWITCH Outdoor Fan On
1. High-pressure switch faulty. 1. Replace switch.
2. Airflow restricted. 2. Remove obstruction.
3. Air recirculating. 3. Clear airflow area.
4. Noncondensables in system. 4. Purge and recharge as required.
5. Refrigerant overcharge. 5. Purge as required.
6. Line voltage incorrect. 6. Consult power company.
7. Refrigerant system restrictions. 7. Check or replace filter drier, expansion valve, etc. Check
Outdoor Fan Off
1. Fan slips on shaft. 1. Tighten fan hub setscrews.
2. Motor not running. 2. Check power and capacitor.
3. Motor bearings stuck. 3. Replace bearings.
4. Motor overload open. 4. Check overload rating. Check for fan blade obstruction.
5. Motor burned out. 5. Replace motor. COMPRESSOR CYCLES ON LOW-PRESSURE SWITCH Indoor-Air Fan Running
1. Filter drier plugged. 1. Replace filter drier.
2. Expansion valve power head defective. 2. Replace power head.
3. Low refrigerant charge. 3. Add charge. Check low-pressure switch setting. Airflow Restricted
1. Coil iced up. 1. Check refrigerant charge.
2. Coil dirty. 2. Clean coil fins.
3. Air filters dirty. 3. Clean or replace filters.
4. Dampers closed. 4. Check damper operation and position. Indoor-Air Fan Stopped
1. Electrical connections loose. 1. Tighten all connections.
2. Fan relay defective. 2. Replace relay.
3. Motor overload open. 3. Power supply.
4. Motor defective. 4. Replace motor.
5. Fan belt broken or slipping. 5. Replace or tighten belt.
size fuse. size. Replace transformer if primary windings receiving
power.
breaker; replace if defective.
airflow, or whether compressor suction shutoff valve is fully open. Make sure liquid line solenoid valve(s) is open.
airflow, air in system or whether compressor discharge valve is fully open. Be sure outdoor fans are operating correctly.
defective.
compressor terminal.
that compressor discharge valve is fully open.
53
Page 54
TROUBLESHOOTING (cont)
PROBLEM SOLUTION
COMPRESSOR STOPS ON OIL PRESSURE SWITCH
1. Oil level too low or too high. 1. Check oil level requirements; adjust oil level until sight
glass is filled
2. Compressor is short cycling. 2. Check for a) Thermostat location and operation. b) Safety device lockout circuit operation. c) End-of-cycle control and timer operation. d) Low-pressure switch and relay operation.
3. Crankcase heater off. 3. Check relay operation; replace crankcase heater(s), if defective.
4. Low refrigerant charge. 4. Adjust charge as required.
5. Refrigerant floodback. 5. Adjust TXV superheat.
6. Evaporator coil is blocked or iced. 6. Check and correct as required.
7. Evaporator fan not operating. 7. Check and correct as required.
8. Distributor and/or TXV too large. 8. Check sizing at design conditions; change if incorrect
9. Suction riser too large. 9. Check line sizing at minimum design condition; change
10. Defective oil pressure switch. 10. Check switch for proper operation; check capillary lines
for current application. piping if incorrect. for plugged lines.
11. Plugged oil pump inlet screen. 11. Clean oil pump screen.
12. Faulty oil pump drive segment. 12. Replace drive segment.
13. Worn oil pump. 13. Replace bearing head assembly.
14. Worn compressor bearings. 14. Replace compressor; see 06E service instructions. COMPRESSOR RUNNING BUT COOLING INSUFFICIENT Suction Pressure Low
1. Refrigerant charge low. 1. Add refrigerant.
2. Head pressure low. 2. Check refrigerant charge.
Check outdoor-air fan thermostat settings.
3. Air filters dirty. 3. Clean or replace filters.
4. Expansion valve power head defective. 4. Replace power head.
5. Indoor coil partially iced. 5. Check low-pressure setting.
6. Indoor airflow restricted. 6. Remove obstruction. Suction Pressure High
1. Unloaders not functioning. 1. Check unloader adjustments.
Check unloader setting.
2. Compressor valve defective. 2. See 06E compressor service literature.
3. Heat load excessive. 3. Check for open doors or windows in vicinity of fan coil. UNIT OPERATES TOO LONG OR CONTINUOUSLY
1. Low refrigerant charge. 1. Add refrigerant.
2. Control contacts fused. 2. Replace control.
3. Air in system. 3. Purge and evacuate system.
4. Partially plugged expansion valve or filter drier. 4. Clean or replace. SYSTEM IS NOISY
1. Piping vibration. 1. Support piping as required.
2. Compressor noisy. 2. Check valve plates for valve noise. Replace compressor
if bearings are worn.
COMPRESSOR LOSES OIL
1. Leak in system. 1. Repair leak.
2. Crankcase heaters not energized during shutdown. 2. Check wiring and relays. Check heater and replace if
defective.
3. Improper interconnecting piping design. 3. Check piping for oil return. Replace if necessary. FROSTED SUCTION LINE
1. Expansion valve admitting excess refrigerant. 1. Adjust expansion valve. HOT LIQUID LINE
1. Shortage of refrigerant due to leak. 1. Repair leak and recharge.
2. Expansion valve opens too wide. 2. Adjust expansion valve. FROSTED LIQUID LINE
1. Restricted filter drier. 1. Remove restriction or replace. COMPRESSOR WILL NOT UNLOAD
1. Defective unloader. 1. Replace unloader.
2. Defective capacity control solenoid valve (if used). 2. Replace valve.
3. Miswired capacity control liquid line solenoid (if used). 3. Rewire correctly.
4. Weak, broken, or wrong valve body spring. 4. Replace spring. COMPRESSOR WILL NOT LOAD
1. Miswired capacity control liquid line solenoid (if used). 1. Rewire correctly.
2. Defective capacity control solenoid valve (if used). 2. Replace valve.
3. Plugged strainer (high side). 3. Clean or replace strainer.
4. Stuck or damaged unloader piston or piston ring(s). 4. Clean or replace the necessary parts.
1
⁄8to1⁄3when running.
Copyright 1998 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 Tab 3a
PC 111 Catalog No. 563-704 Printed in U.S.A. Form 38AH-15SI 54 10-98 Replaces: 38AH-14SI
Page 55
START-UP CHECKLIST
A. Preliminary Information
OUTDOOR:MODELNO. SERIALNO. INDOOR: AIR HANDLER MANUFACTURER
MODEL NO. SERIAL NO.
ADDITIONAL ACCESSORIES
B. Pre-Start-Up
OUTDOOR UNIT
IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE:
WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N) CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? (Y/N) HAS THE GROUND WIRE BEEN CONNECTED? (Y/N) HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (Y/N) ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (Y/N) HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED? (Y/N)
CONTROLS
ARE THERMOSTAT(S) AND INDOOR FAN CONTROL WIRING
CONNECTIONS MADE AND CHECKED? (Y/N) ARE ALL WIRING TERMINALS (including main power supply) TIGHT? (Y/N) HAVE CRANKCASE HEATERS BEEN ENERGIZED FOR 24 HOURS? (Y/N)
INDOOR UNIT
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? (Y/N) ARE PROPER AIR FILTERS IN PLACE? (Y/N) HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? (Y/N) DO THE FAN BELTS HAVE PROPER TENSION? (Y/N)
PIPING
ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE EVAPORATOR COILS AS REQUIRED? (Y/N) HAVE LEAK CHECKS BEEN MADE AT COMPRESSORS, CONDENSERS, EVAPORATORS,
TXVs (Thermostatic Expansion Valves) SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS WITH A LEAK DETECTOR? (Y/N)
LOCATE, REPAIR, AND REPORT ANY LEAKS. HAVEALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED)? (Y/N) ARE THE COMPRESSOR OIL SIGHT GLASSES SHOWING ABOUT1⁄2FULL? (Y/N)
CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS: AB V AC V BC V (AB + AC + BC)/3 = AVERAGE VOLTAGE = V MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = V VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = % IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.
CL-1
Page 56
C. Start-Up
CHECK EVAPORATOR FAN SPEED AND RECORD. CHECK CONDENSER FAN SPEED AND RECORD. AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
COMP A1 COMP A2 COMP B1 COMP B2
OIL PRESSURE SUCTION PRESSURE SUCTION LINE TEMP DISCHARGE PRESSURE DISCHARGE LINE TEMP ENTERING CONDENSER AIR TEMP LEAVING CONDENSER AIR TEMP EVAP ENTERING AIR DB TEMP EVAP ENTERING AIR WB TEMP EVAP LEAVING AIR DB TEMP EVAP LEAVING AIR WB TEMP COMPRESSOR AMPS (L1) COMPRESSOR AMPS (L2) COMPRESSOR AMPS (L3)
CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES; ARE THE SIGHT GLASSES SHOWING OIL LEVEL AT1⁄8TO1⁄3FULL? (Y/N)
NOTES:
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
Copyright 1998 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 Tab 3a
PC 111 Catalog No. 563-704 Printed in U.S.A. Form 38AH-15SI CL-2 10-98 Replaces: 38AH-14SI
----------------------------------------------------------------------------------------
Loading...