Carrier 38AE016, 38AE012, 38AE014 User Manual

38AE012,014,016
Air-Cooled Condensing Units
Installation, Start-Up and
Service Instructions
38AKS024
50/60 Hz
CONTENTS
Page
SAFETY CONSIDERATIONS ...................1
INSTALLATION ..............................1-8
Step 1 — Complete Pre-Installation Checks ....1
Step 2 — Rig and Mount the Unit .............6
Connections .................................6
Step 4 — Install Accessories .................7
Step 5 — Complete Electrical Connections ....7
PRE-START-UP ..............................9
Evacuate and Dehydrate ......................9
Leak Test ....................................9
Turn On Crankcase Heaters ..................9
Add Preliminary Charge ......................9
Before Starting Unit ..........................9
START-UP .................................9-13
To Start Unit .................................9
Oil Charge ...................................9
Refrigerant Charge ...........................9
Check Operation ............................13
OPERATING SEQUENCE ....................13
Cooling .....................................13
Heating .....................................13
Fan Cycling .................................13
Winter Start Control .........................13
SERVICE ..................................13,14
Capacity Control ............................13
Head Pressure Control ......................13
Time GuardT II Circuit .......................13
Winter Start Control .........................13
Crankcase Heater ...........................13
Outdoor Fan ................................14
Lubrication .................................14
Cleaning Coils ..............................14
TROUBLESHOOTING ......................15,16
START-UP CHECKLIST ................CL-1,CL-2
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equip­ment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated struc­tures, etc.).
Only trained, qualified installers and service mechanics
should install, start-up, and service this equipment (Fig. 1).
Untrained personnel can perform basic maintenance func­tions such as cleaning coils. All other operations should be performed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
Follow allsafetycodes.Wear safetyglassesandworkgloves. Keep quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging and setting bulky equipment.
ELECTRIC SHOCK HAZARD Separate power sources (main and control
power circuits) are used for these units. Be sure both main and control power circuits are disconnected before servicing.
INSTALLATION
Step 1 — Complete Pre-Installation Checks
UNCRATE UNIT — Remove unit packaging except for the top skid assembly, which should be left in place until after the unit is rigged into its final location.
INSPECT SHIPMENT — File claim with shipping com­pany if shipment is damaged or incomplete.
CONSIDER SYSTEM REQUIREMENTS
• Consult local building codes and National Electrical Code
(NEC, U.S.A.) for special installation requirements.
• Allow sufficient space for airflow clearance, wiring, re-
frigerant piping, and servicing unit. See Fig. 1. See Fig. 2 for unit component locations.
• Locate unit so that outdoor coil (condenser) airflow is un-
restricted on all sides and above.
• Unit may be mounted on a level pad directly on the base
channels or mounted on raised pads at support points. See Table 1A-1D for unit operating weights. See Table 2 for weight distribution based on recommended support points.
NOTE: If vibration isolators are required for a particular installation, use the data in Table 2 to make the proper selection.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 3a 2a
PC 111 Catalog No. 563-746 Printed in U.S.A. Form 38A-4SI Pg 1 4-94 Replaces: 38AE-17SI
A—1 B—13⁄4-in. (44.5)diameterknockout for suctionlineconnections of 11⁄8in. (28.6)
C— D—2-in. (50.8) diameter knockout for unit power
1
⁄4-in. (32) diameter knockout for5⁄8-in. (16) ODM liquid line connection
(38AE012), 13⁄8in. (35) (38AE014,016), 15⁄8in. (41) (38AKS024)
7
⁄8-in. (22.2) diameter knockout for control power
Certified dimension drawings are available on request.
Fig. 1 — Dimensions (ft-in.)
LEGEND
NOTES:
1. SERVICE AREAS —Allow 3 ft (914) on both sides and 2 ft (610) on both ends of unit for servicing.
2. Dimensions in ( ) are in millimeters.
2
1
2 4567
3
LEGEND
1—Low-Voltage Fuse 5—No. 2 Fan 9—Compressor 2—No. 1 Fan 6—Terminal Block 1 (Unit Power) 10 — Low-Pressure Switch 3—High-Pressure Switch 7—Terminal Block 2 (Control Power) 11 — Hot Gas Bypass Piping Stub ( 4—Circuit Breakers 8—Wraparound Coil 12 — Muffler
Fig. 2 — Component Locations (Typical — 38AE Shown)
3
⁄8-in. ODM)
812 91011
3
Table 1A — Physical Data (English, 60 Hz)
UNIT 38AE012 38AE014 38AE016 38AKS024 OPERATING WEIGHT (lb) 732 779 789 900 REFRIGERANT* R-22 COMPRESSOR Reciprocating, Semi-Hermetic
Speed (Rpm) 1750 No. Cylinders 666 4 Model No. 06DD824 06DD328 06DD537 06E4250 Oil (pt) 10 10 10 15.5 Crankcase Heater Watts 125 125 125 180 Unloader Setting (psig)
Load 70±1 Unload 60±2
OUTDOOR-AIR FANS Axial Flow, Direct Drive
No. ...Rpm 2...1075
Diameter (in.) 24 24 24 26 Motor Hp Nominal Total Airflow (Cfm) 8800 8800 8800 11,000
OUTDOOR COIL
Face Area (sq ft) 29.2 Storage Capacity (lb)† 27.2 40.3 39.8 39.8
CONTROLS
Pressurestat Settings (psig)
High Cutout 395±10
Cut-in 295±10
Low Cutout 29±4
Cut-in. 60 +15, –0
FUSIBLE PLUG (F) 200 PIPING CONNECTIONS (in. ODM)
Suction 1 Liquid
Unit is factory supplied with holding charge only.
†Storage capacity is measured at liquid saturated temperatures of 125 F for 38AE012,
123 F for 38AE014, and 130 F for 38AE016 and 38AKS024.
1
8
13⁄
8
1
2
13⁄
5
8
8
15⁄
8
Table 1B — Physical Data (SI, 60 Hz)
UNIT 38AE012 38AE014 38AE016 38AKS024 OPERATING WEIGHT (kg) 333 354 359 408 REFRIGERANT* R-22 COMPRESSOR Reciprocating, Semi-Hermetic
Speed (r/s) 29.2 No. Cylinders 666 4 Model No. 06DD824 06DD328 06DD537 06E4250 Oil (L) 4.73 4.73 4.73 7.33 Crankcase Heater Watts 125 125 125 180 Unloader Setting (kPa)
Load 483 ± 6.9 Unload 414 + 103, –0
OUTDOOR-AIR FANS Axial Flow, Direct Drive
No. ...r/s 2...17.9
Diameter (mm) 610 610 610 661 Motor Hp Nominal Total Airflow (L/s) 4153 4153 4153 5566
OUTDOOR COIL
Face Area (sq m) 2.71 Storage Capacity (kg)† 12.4 18.3 18.1 18.1
CONTROLS
Pressurestat Settings (kPa)
High Cutout 2724 ± 68.9
Cut-in 2034 ± 68.9
Low Cutout 200 ± 27.6
Cut-in 414 + 103, –0
FUSIBLE PLUG (C) 93.3 PIPING CONNECTIONS (in. ODM)
Suction 1 Liquid
*Unit is factory supplied with holding charge only.
†Storage capacity is measured at liquid saturated temperatures of 51.7 C for 38AE012,
50.6 C for 38AE014, and 54.4 C for 38AE016 and 38AKS024.
1
8
13⁄
8
1
2
13⁄
5
8
8
15⁄
8
4
Table 1C — Physical Data (English, 50 Hz)
UNIT 38AE012 38AE014 38AE016 38AKS024 OPERATING WEIGHT (lb) 732 779 789 900 REFRIGERANT* R-22 COMPRESSOR Reciprocating, Semi-Hermetic
Speed (Rpm) 1460 No. Cylinders 666 4 Model No. 06DD824 06DD328 06DD537 06E4250 Oil (pt) 10 10 10 15.5 Crankcase Heater Watts 125 125 125 180 Unloader Setting (psig)
Load 70±1 Unload 60±2
OUTDOOR-AIR FANS Axial Flow, Direct Drive
No. ...Rpm 2...900
Diameter (in.) 24 24 24 26 Motor Hp Nominal Total Airflow (Cfm) 7368 7368 7368 9210
OUTDOOR COIL
Face Area (sq ft) 29.2 Storage Capacity (lb)† 27.2 40.3 39.8 39.8
CONTROLS
Pressurestat Settings (psig) High Cutout 395±10
Cut-in 295±10
Low Cutout 29±4
Cut-in 60 + 15, –0
FUSIBLE PLUG (F) 200 PIPING CONNECTIONS (in. ODM)
Suction 1 Liquid
*Unit is factory supplied with holding charge only.
†Storage capacity is measured at liquid saturated temperatures of 125 F for 38AE012,
123 F for 38AE014, and 130 F for 38AE016 and 38AKS024.
1
8
13⁄
8
1
2
13⁄
5
8
8
15⁄
8
Table 1D — Physical Data (SI, 50 Hz)
UNIT 38AE012 38AE014 38AE016 38AKS024 OPERATING WEIGHT (kg) 333 354 359 408 REFRIGERANT* R-22 COMPRESSOR Reciprocating, Semi-Hermetic
Speed (r/s) 24.3 No. Cylinders 666 4 Model No. 06DD824 06DD328 06DD537 06E4250 Oil (L) 4.73 4.73 4.73 7.33 Crankcase Heater Watts 125 125 125 180 Unloader Setting (kPa)
Load 483 ± 6.9 Unload 414 + 103, –0
OUTDOOR-AIR FANS Axial Flow, Direct Drive
No. ...r/s 2...15.0
Diameter (mm) 610 610 610 661 Motor Hp Nominal Total Airflow (L/s) 3728 3728 3728 4660
OUTDOOR COIL
Face Area (sq m) 2.71 Storage Capacity (kg)† 12.4 18.3 18.1 18.1
CONTROLS
Pressurestat Settings (kPa)
High Cutout 2724 ± 68.9
Cut-in 2034 ± 68.9
Low Cutout 200 ± 27.6
Cut-in 414 + 103, –0
FUSIBLE PLUG (C) 93.3 PIPING CONNECTIONS (in. ODM)
Suction 1 Liquid
*Unit is factory supplied with holding charge only.
†Storage capacity is measured at liquid saturated temperatures of 51.7 C for 38AE012,
50.6 C for 38AE014, and 54.4 C for 38AE016 and 38AKS024.
1
8
13⁄
8
1
2
13⁄
5
8
8
15⁄
8
5
Table2—Weight Distribution
UNIT
Total
Operating
38AE012 732 (333) 142 (65) 138 (63) 225 (102) 227(103) 38AE014 779 (354) 143 (65) 140 (64) 247 (112) 249 (113) 38AE016 789 (359) 143 (65) 143 (65) 250 (114) 253 (115)
38AKS024 900 (408) 178 (81) 168 (76) 269 (122) 285 (129)
WEIGHT — lb (kg)
Support Point
AB C D
Step 2 — Rig and Mount the Unit
Be sure unit panels are securely in place prior to rigging.
RIGGING — These units are designed for overhead rigging only. For this purpose, the transverse base channels extend beyond the sides of the unit, with holes provided in the end plates to attach cables or hooks. Rig with top skid packaging assembly in place to prevent unit damage by the rigging cable. As further protection for the coil faces, plywood sheets can be placed against the sides of the unit, behind the cables. Run the cables to a central suspension point so that the angle from the horizontal is not less than 45 degrees. Raise and set the unit down carefully.
If it is necessary to roll the unit into position, mount the unit on longitudinal rails, using a minimum of 3 rollers. Ap­ply force to the rails, not the unit. If the unit is to be skidded into position, place it on a large pad and drag it by the pad. Do not apply any force to the unit.
Raise from above to lift unit from the rails or pad when unit is in final position.
COMPRESSOR MOUNTING — As shipped, the compres­sor is held tightly in placebyself-lockingbolts.Before start-
ing unit, loosenself-locking bolts until the snubber washer can be moved sideways with finger pres­sure. Do not remove shipping bolts. See Fig. 3.
Step 3 Complete Refrigerant Piping Connections
IMPORTANT: A refrigerant receiver is not provided with the unit. Do not install a receiver.
SIZE REFRIGERANT LINES — Consider the length of piping required between outdoor unit and indoor unit (evaporator), the amount of liquid lift, and compressor oil return. See Tables 3, 4A, and 4B and also refer to Part 3 of Carrier System Design Manual for design details and line sizing. Refer to indoor installation instructions for addi­tional information.
Table 3 — Liquid Line Data
MAXIMUM
ALLOWABLE
LIQUID LIFT
UNIT
ft (m)
60 Hz 50 Hz
Maximum Allowable
Pressure Drop
psig (kPa)
38AE012 52 (15.8) 38AE014 67 (20.4) 38AE016 82 (25)
7 (48.3) 2 (1.1)
38AKS024 87 (26.5) 86 (26)
*Inlet and outlet. NOTE: Data shown isfor units operating at 45 F (7.2C)saturated suction and
95 F (35 C) entering air.
Table 4A — Refrigerant Piping Sizes — 60 Hz
LENGTH OF INTERCONNECTING PIPING — FT (M)
0-15
UNIT
(0-4.6)
LSLSLSLSLS
1
38AE012
⁄211⁄
38AE0141⁄211⁄ 38AE0161⁄213⁄
38AKS0245⁄815⁄
LEGEND
L—Liquid S—Suction
Close coupled.
NOTES:
1. Pipe sizes are based ona2F(1.1 C) loss for liquid lines and a 1.5 F (0.8 C) loss for suction lines.
2. Pipe sizes are basedonan equivalent length equal to the maximumlength ofinterconnectingpiping plus50% forfittings. Amore accurate estimatemay result in smaller sizes.
8 8 8 8
15-25
(4.6-7.6)
1
⁄211⁄
1
⁄213⁄
5
⁄813⁄
5
⁄815⁄
8 8 8 8
(7.6-15.2)
Line Size — in. OD
5
⁄813⁄
5
⁄813⁄
5
⁄815⁄
7
⁄815⁄
25-50
LIQUID LINE
Maximum Allowable
Temp.
50-75
(15.2-22.9)
5
8
⁄813⁄
5
8
⁄815⁄
7
8
⁄815⁄
7
8
⁄821⁄
Loss F (C)
Filter Drier
Sight Glass
Flare Conn.*
(22.9-30.5)
5
8
⁄815⁄
7
8
⁄815⁄
7
8
⁄821⁄
7
8
⁄821⁄
and
in. (mm)
5
8
75-100
8 8 8 8
Fig. 3 — Compressor Mounting
Table 4B — Refrigerant Piping Sizes — 50 Hz
LENGTH OF INTERCONNECTING PIPING — FT (M)
UNIT
0-15
(0-4.6)
15-25
(4.6-7.6)
25-50
(7.6-15.2)
50-75
(15.2-22.9)
Line Size — in. OD
LSLSLSLSLS
1
38AE012
⁄211⁄
38AE0141⁄211⁄ 38AE0161⁄213⁄
38AKS0245⁄815⁄
1
8
⁄211⁄
1
8
⁄211⁄
5
8
⁄813⁄
5
8
⁄815⁄
5
8
⁄811⁄
5
8
⁄813⁄
5
8
⁄813⁄
5
8
⁄815⁄
8 8 8 8
5
⁄813⁄
5
⁄813⁄
5
⁄813⁄
7
⁄815⁄
8 8 8 8
LEGEND
L—Liquid S—Suction
Close coupled.
NOTES:
1. Pipe sizes are based ona2F(1.1 C) loss for liquid lines and a 1.5 F (0.8 C) loss for suction lines.
2. Pipe sizes are basedonan equivalent length equal to the maximumlength ofinterconnectingpiping plus50% forfittings. Amore accurate estimatemay result in smaller sizes.
6
75-100
(22.9-30.5)
5
⁄813⁄
5
⁄813⁄
5
⁄815⁄
7
⁄815⁄
8 8 8 8
INSTALL FILTER DRIER(S) AND MOISTURE INDICA­TOR(S) — Every unit should have a filter drier and liquid­moisture indicator(sightglass).Insome applications, depending on space and convenience requirements, it may be desirable to install 2 filter driers and sight glasses. One filter drier and sight glass may be installed at A locations in Fig. 4. Or, 2 filter driers and sight glasses may be installed at B locations.
Select the filter drier for maximum unit capacity andmini­mum pressure drop. Complete the refrigerant piping from indoor unit to outdoor unit before opening the liquid and suc­tion lines at the outdoor unit.
TXV — Thermal Expansion Valve
Fig. 4 — Location of Sight Glass(es)
and Filter Drier(s)
INSTALL LIQUID LINE SOLENOID VALVE — SOLE­NOID DROP — It is recommended that a solenoid valve be placed in the main liquid line (see Fig. 4) between condens­ing unit (38AE/AKS) and fan coil (40RR, 40RE). (A liquid line solenoid valve is required when the liquid line length exceeds 100 ft [30.5 m] or when the condensing unit is con­nected to the chiller barrel in a built-up chiller system.) This valve prevents refrigerant migration (which causes oil dilu­tion) to the compressor during the off cycle at low outdoor ambient temperatures. The solenoid should be wired in par­allel with the compressor contactor coil. This means of elec­trical control is referred to as solenoid drop control.
NOTE: 38AKS024 has a fusible plug in the liquid line.
Fig. 5 — Location of Fusible Plug (38AE)
Step 4 — Install Accessories — Field install ac-
cessories such as winter start control or low-ambient control before proceedingwithwiring.Refertothe instructions shipped with the accessory.
Step 5 — Complete Electrical Connections
POWER WIRING — Unit is factory wired for voltage shown on nameplate. Provideadequatefuseddisconnectswitchwithin sight from unit and readily accessible from unit, but out of the reach of children. Lock switch open (off)topreventpower from being turned on while unit is being serviced. Discon­nect switch, fuses, and field wiring must comply with na­tional and local code requirements. See Tables 5A and 5B.
Route power wires through opening in unit end panel to connection in unit control box as shown on unit label dia­gram and in Fig. 6. Unit must be grounded.
Affix crankcase heater warning sticker to unit disconnect switch.
CONTROL CIRCUIT WIRING — Control voltage is 24 v. See Fig. 7 and unit label diagram for field-supplied wiring details. Route control wires through opening in unit end panel to connection in unit control box.
INSTALL LIQUID LINE SOLENOID VALVE (OPTIONAL) — CAPACITY CONTROL — If 2-step cooling is desired, place a solenoid valve in the location shown in Fig. 4.
MAKE PIPING CONNECTIONS — Do not remove run­around loop from suction and liquid line stubs in the com­pressor compartment until piping connections are ready to be made. Pass nitrogen or other inert gas through piping while brazing to prevent formation of copper oxide.
Install field-supplied thermostatic expansion valve(s) in in­door section. If 2 thermostatic expansion valves are installed for 2-step cooling, install field-supplied liquid line solenoid valve ahead of the second expansion valve.
PROVIDE SAFETY RELIEF — A fusible plug is located on the compressor crankcase or in the liquid line (Fig. 5). Do not cap this plug. If local code requires additional safety devices, install them as directed.
LEGEND
EQUIP GND — Equipment Ground NEC National Electrical Code
Factory Wiring Field Wiring
Fig. 6 — Main Power Supply Wiring
7
UNIT
38AE012
38AE014
38AE016
38AKS024
LEGEND
C—Compressor Contactor R—Relay HD Heating Device IFC Indoor-Fan Contactor Field Wiring LLSV — Liquid Line Solenoid Valve
NOTES:
1. Combination LLSV plus IFC va should not exceed 30 va.
2. Do not exceed 5 va (24 vac) per coil.
3. If va values shown in Notes 1 and 2 must be exceeded, use accessory relay transformer package 38AE900001.
Fig. 7 — Remote Thermostat Wiring
Table 5A — Electrical Data (3 Ph/60 Hz)
Model
501 208-230 187 253 62.5 178 100 43.6 170 201 380 342 418 35.0 101 50 24.0 93 4.3 3.7 601 460 414 528 29.1 81 40 20.0 77 2.3 1.9 101 575 518 660 22.8 67 35 15.7 62 1.8 1.8
501 208-230 187 253 69.3 199 100 49.3 191 201 380 342 418 38.0 112 60 26.5 104 4.3 3.7 601 460 414 528 31.7 84 50 22.1 80 2.3 1.9 101 575 518 660 25.6 73 40 17.9 69 1.8 1.8
501 208-230 187 253 87.5 274 125 63.6 266 201 380 342 418 49.3 153 80 36.0 145 4.3 3.7 601 460 414 528 40.7 124 60 29.3 120 2.3 1.9 101 575 518 660 33.0 100 50 23.8 96 1.8 1.8
501 208-230 187 254 93.4 353 150 67.9 345 201 380 342 418 49.7 199 80 34.6 191 4.3 3.7 601 460 414 508 48.1 177 80 34.7 173 2.3 1.9 101 575 518 632 40.1 124 60 28.8 120 1.8 1.8
Nameplate
Volts
UNIT COMPR FAN MOTORS (Single Phase)
Supplied*
Min Max 12
MCA ICF
MOCP (Fuse)
RLA LRA
Total Fans
2
2
2
2
FLA (ea)
Fan No.
4.3 3.7
4.3 3.7
4.3 3.7
4.3 3.7
Factory Wiring
kW
1.41
1.41
1.41
1.41
Table 5B — Electrical Data (3 Ph/50 Hz)
UNIT
38AE012
38AE014
38AE016
38AKS024
FLA — Full Load Amps (Fan Motors) ICF Maximum Instantaneous Current Flow during start-up (LRA of compressor plus total FLA of fan motors) kW Total Fan Motor Input (kilowatts) LRA — Locked Rotor Amps MCA — Minimum Circuit Amps per NEC (U.S.A.), Section 430-24 MOCP — Maximum Overcurrent Protection (amps) RLA — Rated Load Amps (Compressor)
*Units are suitable for use on electrical systems where voltage supplied to the unit terminals is not below or above
the listed limits. NOTES:
1. The MCA and MOCP values are calculated in accordance with the National Electrical Code (NEC) article 440 (U.S.A. standard).
2. Motor RLA and LRA values are established in accordance with Underwriters’ Laboratories (UL) Standard 1995 (U.S.A. standard).
Model
803 230 198 264 47.5 134 75 32.9 128 903 400 342 457 31.4 80 50 20.0 74
803 230 198 264 51.0 149 75 35.7 143 903 400 342 457 34.0 89 50 22.1 83
803 230 198 264 66.9 206 100 47.9 200 903 400 342 457 43.0 121 60 29.3 115
803 230 198 254 91.8 213 150 67.9 207 903 400 342 440 50.2 179 80 34.6 173
Nameplate
Volts
UNIT COMPR FAN MOTORS 230 v (Single Phase)
Supplied*
Min Max 12
MCA ICF
MOCP (Fuse)
RLA LRA
LEGEND
8
Total Fans
2 2.9 3.5 1.20 2 2.9 3.5 1.20 2 2.9 3.5 1.20
2 2.9 3.5 1.20303 346 311 380 51.5 121 80 33.3 115
FLA (ea)
Fan No.
kW
PRE-START-UP
Evacuate and Dehydrate
tem by either of the methods described in Carrier Standard Service Techniques Manual, Chapter 1.
the entire refrigerant sys-
START-UP
To StartUnit—
temperature.After starting unit, there is a delay of at least 3 seconds before compressor starts.
Set thermostat set point belowthe space
Leak Test the entire refrigerant system by the pres-
sure method described in Carrier Standard Service Tech­niques Manual, Chapter 1. Use R-22 at approximately 25 psig (172.4 kPa) backed up with an inert gas to a total pressure not to exceed 245 psig (1689 kPa).
Turn onCrankcaseHeaters for 24 hours before start-
ing the unit to be sure all the refrigerant is out of the oil. To energize the crankcase heaters, proceed as follows.
1. Set the space thermostat set point above the space tem­perature so there is no demand for cooling.
2. Close the field disconnect.
3. Turn the fan circuit breaker on. Leave the compressorcir­cuit breakers off. The crankcase heaters are now energized.
Add Preliminary Charge to the refrigerant system ac-
cordingly to Carrier Standard Service Techniques Manual, Chapter 1. By the liquid charging method and charging by weight procedure, charge the units with approximately the amounts of R-22 refrigerant shown in Table 6.
Table 6 — Charging Data (R-22)
REFRIGERANT CHARGE - lb (kg)
UNIT
38AE012 3.0 (1.4) 22 (10) 125 (51.7) 38AE014 4.8 (2.2) 23 (10.5) 123 (50.6) 38AE016 3.4 (1.5) 23 (10.5) 130 (54.4)
38AKS024 3.4 (1.5) 28 (12.7) 131 (54.8)
Required Charge
Above Clear
Sight Glass
Outdoor Unit Total Charge
(Approx)
CONDENSING
TEMP
DURING
CHARGING-F(C)
Before Starting Unit ensure the following:
1. Compressor oil level must be at least within sight in the compressor sight glass. Add oil if necessary (see Tables 1A-1D and Oil Charge section).
2. Compressor holddown bolts must be snug, but not tight. Refer to Compressor Mounting section and tag on com­pressor foot.
3. All internal wiring connections must be tight; all barriers and covers must be in place.
4. Electrical power source must agree with unit nameplate rating.
5. All service valves must be open.
6. Crankcase heater must be firmly locked into the com­pressor crankcase.
Oil Charge (see Tables 1A-1D) —Allow unit to run for
about 20 minutes. Stop unit and check compressor oil level at sight glass. Add oil if necessary to bring oil to the correct level shown in Fig. 8. Use only Carrier-approved compres- sor oil. Approved oils are:
Witco Chemical Corp. ................Suniso 3GS
Texaco, Inc. ...........................WF32
Petroleum Specialties Co. ...............Cryol 150
Do not reuse drained oil or use any oil that has been ex­posed to atmosphere.Procedures for adding or removing oil
are given in Carrier Standard Service Techniques Manual, Chapter 1, Refrigerants.
If oil is added, run unit for additional 10 minutes. Stop unit and check oil level. If level is still low,add oil only after determining that piping system is designed for proper oil re­turn and that the system is not leaking oil.
38AKS024
(06E COMPRESSOR)
38AE012,014,016
(06D COMPRESSOR)
Fig. 8 — Operating Oil Levels
Refrigerant Charge — Actual start-up should be done
only under supervision of a qualified refrigeration me­chanic. Refer to charging charts.
See Fig. 9-11 for the particular unit being charged. Mea­sure pressure at the liquid line service valve, being sure a Schrader depressor is used if required. Also, measure liquid line temperature as close to the liquid service valve as pos­sible. Add or reduce charge until the pressure and tempera­ture conditions of the charging charge curve are met. If liq­uid pressure and temperature point falls above curve, add charge. If liquid pressure and temperature point falls below curve, reduce the charge until the conditions match the curve.
Never charge liquid into the low-pressure side of sys­tem. Do not overcharge. During charging or removal of refrigerant, be sure indoor fan system is operating.
9
10
Fig. 9 — 38AE012 and 38AKS024 Charging Chart
Fig. 10 — 38AE014 Charging Chart
11
Fig. 11 — 38AE016 Charging Chart
12
Check Operation — Verify operation of all safety con-
trols. Replace all service panels. Be sure that control panel cover is closed tightly.
OPERATING SEQUENCE
Cooling—
mostat closes, the timer starts. After approximately 3 sec­onds, the timer activates the compressor and fan motor no. 1 contactor. When the liquid pressure builds to approxi­mately 257 psig (1772 kPa), fan motor no. 2 is energized.
On demand for additional cooling capacity, the second stage (TC2) of the cooling thermostat closes, energizing a field­supplied liquid line solenoid (LLS) valve,which opens. This increases the suction pressure, causing the compressor toop­erate at higher capacity.
When fan switch is set at AUTO, the indoor-air fan cycles with the compressor. When the switch is set at CONT, the indoor-air fan runs continuously.
At shutdown, the Time Guardt II timer prevents the com­pressor from restarting for approximately 5 minutes.
When installed, a field-supplied solenoid valve (wired in parallel with the compressor contactor coil), shuts off the liq­uid line to prevent refrigerant migration back to the com­pressor during the off cycle.
When the first stage (TC1) of the cooling ther-
Heating— The heating thermostat (TH) energizes a field-
supplied relay which operates heating controls and ener­gizes the indoor-fanrelay. When the fan switch issetatAUTO, the indoor-air fan cycles with the heating control. The indoor­air fan runs continuously when the fan switch is set at CONT.
Fan Cycling — Head pressure control is accomplished
by cycling the fans. The no. 2 fan responds to liquid line pressure, cycling on at approximately 257 psig (1772 kPa) and off at approximately 126 psig (869 kPa).
WinterStart Control (If Installed) — When the com-
pressor starts, the control’s bypass timer contacts close for 150 seconds, thereby bypassing the low-pressure switch dur­ing start-up. After 150 seconds, the bypass timer contacts open and the low-pressure switch is restored to the safety circuit.
Head Pressure Control — Fan cycling is a standard
feature. The no. 2 fan cycles in response to changes in liquid pressure. The switch cycles the fan off at 126 ± 4 psig (869 ± 28 kPa) as pressure decreases, and cycles it back on at 257 (+5, −0) psig (1772 [+103, −0] kPa).
Fig. 12 — Compressor Capacity Control Unloader
TimeGuardII Circuit — Prevents short-cycling by pro-
viding a delay of approximately 5 minutes before restarting compressor after shutdown from safety device action.
On start-up, the Time Guard II timer causes a delay of
approximately 3 seconds after thermostat closes.
On compressor shutdown, the timer recycles for approxi­mately 5 minutes. During this time, the compressor cannot restart.
Refer to Fig. 13 and to label diagram on unit.
SERVICE
Capacity Control —
loader controls 2 cylinders and provides capacity control. Un­loaders are factory set (see Tables 1A-1D), but can be field adjusted as described in the 2 following sections.
CONTROL SET POINT (cylinder load point) is adjustable from 0 to 85 psig (586 kPa). To adjust, turn control set point adjustment nut (Fig. 12) clockwise to its bottom stop. In this position, set point is 85 psig (586 kPa). Next, turn adjust­ment counterclockwise to desired control set point. Every full turn counterclockwise decreases set point by
7.5 psig (51.7 kPa). PRESSURE DIFFERENTIAL (difference between cylinder
load and unload points) is adjustable from 6 to 22 psig (41.4 to 152 kPa). To adjust, turn pressure differential adjustment screw (Fig. 12) counterclockwise to its back stop position. In this position, differential is 6 psig (41.4 kPa). Next, turn adjustment clockwise to desired pressure differential setting. Every full turn clockwise increases differential by 1.5 psig (10.3 kPa).
A suction pressure-actuated un-
Fig. 13 — Timer Sequence Chart
Winter-Start Control (If Required) — Install Ac-
cessory Package 38AE900021.
Crankcase Heater — The heater prevents refrigerant
migration and compressor oil dilution during shutdown when­ever compressor is not operating. It is wired into the control circuit, and cycles with the compressor; the heater is off when compressor is running, and on when compressor is off.
Both compressor service valves must be closed whenever the crankcase heater is deenergized for more than 6 hours. The crankcase heater is operable as long as the control cir­cuit is energized.
13
Outdoor Fans — Each fan is supported by a formed-
wire mount bolted to the fan deck and covered with a wire guard. The exposed end of the motor shaft is covered with a rubber boot. In case a fan motor must be repaired or re­placed, be sure the rubber boot is put back on when the fan is reinstalled and be sure the fan guard is in place before starting the unit. Figure 14 shows the proper position of the mounted fan. Fan motors have permanently lubricated bearings.
38AE012,014,016
(38AE014,016, 38AKS024) and restrict outdoor airflow.Use a flashlight to determine if dirt or debris has collected be­tween coil sections. Clean coil as follows:
1. Turn off unit power.
2. Remove screws holding rear corner posts and top cover in place. Pivot top cover up 12 to 18 in. (305 to 457 mm) and support with a rigid support. See Fig. 15.
3. Remove clips securing tube sheets together at the return bend end of the coil. Carefully spread the ends of the coil rows apart by moving the outer sections. See Fig. 16.
4. Using a water hose,orothersuitableequipment,flushdown between the sections of coil to remove dirt and debris.
5. Clean the remaining surfaces in the normal manner.
6. Reposition outer coil sections.
7. Reinstall clips which secure tube sheets.
8. Replace top cover and rear corner posts.
38AKS024
Fig. 14 — Outdoor Fan
Lubrication
F A NMOTORS have sealed bearings. No provisions are made for lubrication.
COMPRESSOR has its own oil supply. Loss of oil due to a leak in the system should be the only reason for adding oil after the system has been in operation. See Oil Charge section.
CleaningCoils— The coils can be cleaned with a vacuum
cleaner,washed out with water, blown out with low-pressure compressed air, or brushed (do not use wire brush). Fan mo- tors are drip-proof but not waterproof.
Clean outdoor coil annually or as required by location or outdoor air conditions. Inspect coil monthly, and clean as required. Fins are not continuous through coil sections; dirt and debris may pass through first section, become trapped between the 2 rows of fins (38AE012) or 3 rows of fins
Fig. 15 — Pivot and Support Top Cover
Fig. 16 — Coil Cleaning (Typical)
14
TROUBLESHOOTING
PROBLEM SOLUTION
COMPRESSOR DOES NOT RUN Contactor Open
1. Power off. 1. Restore power.
2. Fuses blown in field power circuit. 2. After finding cause and correcting, replace with correct size fuse.
3. No control power. 3. Check secondary fuse(s); replace with correct type and size.
4. Thermostat circuit open. 4. Check thermostat setting.
5. Time GuardT II device not operating. 5. Check Time Guard II devices.
6. Compressor circuit breaker tripped. 6. Check for excessive compressor current draw. Reset breaker;
7. Safety device lock-out circuit active. 7. Reset lock-out circuit at thermostat or circuit breaker.
8. Low-pressure switch open. 8. Check for refrigerant undercharge, obstruction of indoor airflow, or
9. High-pressure switch open. 9. Check for refrigerant overcharge, obstruction of outdoor airflow, air in
10. Compressor overtemperature switch open. 10. Check for open condition. Allow for reset. Replace if defective.
11. Loose electrical connections. 11. Tighten all connections.
12. Compressor stuck. 12. See compressor service literature. Contactor Closed
1. Compressor leads loose. 1. Check connections.
2. Motor windings open. 2. See compressor service literature.
3. Single phasing. 3. Check for blown fuse. Check for loose connection at compressor terminal. COMPRESSOR STOPS ON HIGH-PRESSURE SWITCH
Outdoor Fan On
1. High-pressure switch faulty. 1. Replace switch.
2. Reversed fan rotation. 2. Confirm rotation, correct if necessary.
3. Airflow restricted. 3. Remove obstruction.
4. Air recirculating. 4. Clear airflow area.
5. Noncondensables in system. 5. Purge and recharge as required.
6. Refrigerant overcharge. 6. Purge as required.
7. Line voltage incorrect. 7. Consult power company.
8. Refrigerant system restrictions. 8. Check or replace filter drier, expansion valve, etc. Check that compressor Outdoor Fan Off
1. Fan slips on shaft. 1. Tighten fan hub setscrews.
2. Motor not running. 2. Check power and capacitor.
3. Motor bearings stuck. 3. Replace bearings.
4. Motor overload open. 4. Check overload rating. Check for fan blade obstruction.
5. Motor burned out. 5. Replace motor. COMPRESSOR CYCLES ON LOW-PRESSURE SWITCH
Indoor-Air Fan Running
1. Compressor suction service valve partially closed.
2. Liquid line solenoid valve(s) fails to open. 2. Check liquid line solenoid valve(s) for proper operation. Replace if
3. Filter drier plugged. 3. Replace filter drier.
4. Expansion valve power head defective. 4. Replace power head.
5. Low refrigerant charge. 5. Add charge. Check low-pressure switch setting.
Replace transformer if primary windings receiving power.
replace if defective.
whether compressor suction shutoff valve is fully open. Make sure liquid line solenoid valve(s) is open.
system, or whether compressor discharge valve is fully open. Be sure outdoor fans are operating correctly.
discharge service valve is fully open.
1. Open valve fully.
necessary.
15
TROUBLESHOOTING (cont)
PROBLEM SOLUTION
COMPRESSOR CYCLES ON LOW-PRESSURE SWITCH (cont) Airflow Restricted
1. Coil iced up. 1. Check refrigerant charge.
2. Coil dirty. 2. Clean coil fins.
3. Air filters dirty. 3. Clean or replace filters.
4. Dampers closed. 4. Check damper operation and position. Indoor-Air Fan Stopped
1. Electrical connections loose. 1. Tighten all connections.
2. Fan relay defective. 2. Replace relay.
3. Motor overload open. 3. Power supply.
4. Motor defective. 4. Replace motor.
5. Fan belt broken or slipping. 5. Replace or tighten belt. COMPRESSOR RUNNING BUT COOLING INSUFFICIENT
Suction Pressure Low
1. Refrigerant charge low. 1. Add refrigerant.
2. Head pressure low. 2. Check refrigerant charge.
3. Air filters dirty. 3. Clean or replace filters.
4. Expansion valve power head defective. 4. Replace power head.
5. Indoor coil partially iced. 5. Check low-pressure setting.
6. Indoor airflow restricted. 6. Remove obstruction. Suction Pressure High
1. Unloaders not functioning. 1. Check unloader adjustments.
2. Compressor valve defective. 2. See compressor service literature.
3. Heat load excessive. 3. Check for open doors or windows in vicinity of fan coil. UNIT OPERATES TOO LONG OR CONTINUOUSLY
1. Low refrigerant charge. 1. Add refrigerant.
2. Control contacts fused. 2. Replace control.
3. Air in system. 3. Purge and evacuate system.
4. Partially plugged expansion valve or filter drier. 4. Clean or replace. SYSTEM IS NOISY
1. Piping vibration. 1. Support piping as required.
2. Compressor noisy. 2. Check valve plates for valve noise. Replace compressor if COMPRESSOR LOSES OIL
1. Leak in system. 1. Repair leak.
2. Crankcase heaters not energized during shutdown. 2. Check wiring and relays. Check heater and replace if
3. Improper interconnecting piping design. 3. Check piping for oil return. Replace if necessary. FROSTED SUCTION LINE Expansion valve admitting excess refrigerant. Adjust expansion valve. HOT LIQUID LINE
1. Shortage of refrigerant due to leak. 1. Repair leak and recharge.
2. Expansion valve opens too wide. 2. Adjust expansion valve. FROSTED LIQUID LINE
1. Restricted filter drier. 1. Remove restriction or replace.
2. Liquid line solenoid valve partially closed. 2. Replace valve. COMPRESSOR WILL NOT UNLOAD
1. Defective unloader. 1. Replace unloader.
2. Defective capacity control solenoid valve (if used). 2. Replace valve.
3. Miswired capacity control liquid line solenoid (if used). 3. Rewire correctly.
4. Weak, broken, or wrong valve body spring. 4. Replace spring. COMPRESSOR WILL NOT LOAD
1. Miswired capacity control liquid line solenoid (if used). 1. Rewire correctly.
2. Defective capacity control solenoid valve (if used). 2. Replace valve.
3. Plugged strainer (high side). 3. Clean or replace strainer.
4. Stuck or damaged unloader piston or piston ring(s). 4. Clean or replace the necessary parts.
Check outdoor-air fan thermostat settings.
Check unloader setting.
bearings are worn.
defective.
16
PACKAGED SERVICE TRAINING
Our packaged service training programs provide an excellent way to increase your knowledge of the equipment discussed in this manual. Product programs cover:
• Unit Familiarization • Maintenance
• Installation Overview • Operating Sequence
A large selection of product, theory, and skills programs is available. All programs include a video cassette and/or slides and a companion booklet. Use these for self teaching or to conduct full training sessions.
For a free Service Training Material Catalog (STM), call 1-800-962-9212. Ordering instructions are included.
Copyright 1994 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 3a 2a
PC 111 Catalog No. 563-746 Printed in U.S.A. Form 38A-4SI Pg 18 4-94 Replaces: 38AE-17SI
START-UP CHECKLIST
A. Preliminary Information
OUTDOOR: MODEL NO. SERIAL NO. INDOOR: AIR HANDLER MANUFACTURER
MODEL NO. SERIAL NO.
ADDITIONAL ACCESSORIES
B. Pre-Start-Up
OUTDOOR UNIT
IS THERE ANY SHIPPING DAMAGE? IF SO, WHERE:
WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N) CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? (Y/N)
HAS THE GROUND WIRE BEEN CONNECTED? (Y/N) HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (Y/N) ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (Y/N) HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED (Snubber washers are snug, but not tight)?
(Y/N)
(Y/N)
CUT ALONG DOTTED LINE
CONTROLS
ARE THERMOSTAT AND INDOOR FAN CONTROL WIRING
CONNECTIONS MADE AND CHECKED? (Y/N) ARE ALL WIRING TERMINALS (including main power supply) TIGHT? (Y/N) HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS? (Y/N)
INDOOR UNIT
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? (Y/N) ARE PROPER AIR FILTERS IN PLACE? (Y/N) HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? (Y/N) DO THE FAN BELTS HAVE PROPER TENSION? (Y/N) HAS CORRECT FAN ROTATION BEEN CONFIRMED? (Y/N)
PIPING
ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE EVAPORATOR COILS AS REQUIRED? (Y/N) HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR, CONDENSER, EVAPORATOR(S),
TXVs (Thermostatic Expansion Valves), SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS
WITH A LEAK DETECTOR? (Y/N) LOCATE, REPAIR, AND REPORT ANY LEAKS. HAVEALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED)? (Y/N) HAVE LIQUID LINE SERVICE VALVES BEEN OPENED? (Y/N) IS THE OIL LEVEL IN EACH COMPRESSOR CRANKCASE VISIBLE IN THE COMPRESSOR SIGHT GLASSES?
(Y/N)
CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS: AB (AB + AC + BC)/3 = AVERAGE VOLTAGE = MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.
VAC VBC V
V
V
%
CL-1
----------------------------------------------------------------------------------------
C. Start-Up
CHECK EVAPORATOR FAN SPEED AND RECORD. CHECK CONDENSER FAN SPEED AND RECORD. AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
OIL PRESSURE SUCTION PRESSURE SUCTION LINE TEMP DISCHARGE PRESSURE DISCHARGE LINE TEMP ENTERING CONDENSER AIR TEMP LEAVING CONDENSER AIR TEMP EVAP ENTERING-AIR DB (dry bulb) TEMP EVAP ENTERING AIR WB (wet bulb) TEMP EVAP LEAVING AIR DB TEMP
EVAP LEAVING AIR WB TEMP COMPRESSOR AMPS (L1/L2/L3) / / CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES; ARE THE SIGHT GLASSES SHOWING
OIL LEVEL IN VIEW? (Y/N)
NOTES:
Copyright 1994 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 3a 2a
PC 111 Catalog No. 563-746 Printed in U.S.A. Form 38A-4SI Pg CL-2 4-94 Replaces: 38AE-17SI
Loading...