Installing, starting up, and servicing air-conditioning equipment can be hazardous due to system pressures, electrical
components, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics
should install, start-up, and service this equipment (Fig. 1).
Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should be
performed by trained service personnel.
When working on the equipment, observe precautions in
the literature and on tags, stickers, and labels attached to the
equipment.
Follow allsafetycodes.Wear safetyglassesandworkgloves.
Keep quenching cloth and fire extinguisher nearby when
brazing. Use care in handling, rigging and setting bulky
equipment.
ELECTRIC SHOCK HAZARD
Separate power sources (main and control
power circuits) are used for these units. Be
sure both main and control power circuits are
disconnected before servicing.
INSTALLATION
Step 1 — Complete Pre-Installation Checks
UNCRATE UNIT — Remove unit packaging except for the
top skid assembly, which should be left in place until after
the unit is rigged into its final location.
INSPECT SHIPMENT — File claim with shipping company if shipment is damaged or incomplete.
CONSIDER SYSTEM REQUIREMENTS
• Consult local building codes and National Electrical Code
(NEC, U.S.A.) for special installation requirements.
• Allow sufficient space for airflow clearance, wiring, re-
frigerant piping, and servicing unit. See Fig. 1. See
Fig. 2 for unit component locations.
• Locate unit so that outdoor coil (condenser) airflow is un-
restricted on all sides and above.
• Unit may be mounted on a level pad directly on the base
channels or mounted on raised pads at support points. See
Table 1A-1D for unit operating weights. See Table 2 for
weight distribution based on recommended support points.
NOTE: If vibration isolators are required for a particular
installation, use the data in Table 2 to make the proper
selection.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 3a 2a
PC 111Catalog No. 563-746Printed in U.S.A.Form 38A-4SIPg 14-94Replaces: 38AE-17SI
A—1
B—13⁄4-in. (44.5)diameterknockout for suctionlineconnections of 11⁄8in. (28.6)
C—
D—2-in. (50.8) diameter knockout for unit power
1
⁄4-in. (32) diameter knockout for5⁄8-in. (16) ODM liquid line connection
Be sure unit panels are securely in place prior to
rigging.
RIGGING — These units are designed for overhead rigging
only. For this purpose, the transverse base channels extend
beyond the sides of the unit, with holes provided in the end
plates to attach cables or hooks. Rig with top skid packaging
assembly in place to prevent unit damage by the rigging cable.
As further protection for the coil faces, plywood sheets can
be placed against the sides of the unit, behind the cables.
Run the cables to a central suspension point so that the angle
from the horizontal is not less than 45 degrees. Raise and set
the unit down carefully.
If it is necessary to roll the unit into position, mount the
unit on longitudinal rails, using a minimum of 3 rollers. Apply force to the rails, not the unit. If the unit is to be skidded
into position, place it on a large pad and drag it by the pad.
Do not apply any force to the unit.
Raise from above to lift unit from the rails or pad when
unit is in final position.
COMPRESSOR MOUNTING — As shipped, the compressor is held tightly in placebyself-lockingbolts.Before start-
ing unit, loosenself-locking bolts until the snubber
washer can be moved sideways with finger pressure. Do not remove shipping bolts. See Fig. 3.
Step3—CompleteRefrigerantPiping
Connections
IMPORTANT: A refrigerant receiver is not provided
with the unit. Do not install a receiver.
SIZE REFRIGERANT LINES — Consider the length of
piping required between outdoor unit and indoor unit
(evaporator), the amount of liquid lift, and compressor oil
return. See Tables 3, 4A, and 4B and also refer to Part 3 of
Carrier System Design Manual for design details and line
sizing. Refer to indoor installation instructions for additional information.
Table 3 — Liquid Line Data
MAXIMUM
ALLOWABLE
LIQUID LIFT
UNIT
ft (m)
60 Hz50 Hz
Maximum
Allowable
Pressure Drop
psig (kPa)
38AE01252 (15.8)
38AE01467 (20.4)
38AE01682 (25)
7 (48.3)2 (1.1)
38AKS024 87 (26.5) 86 (26)
*Inlet and outlet.
NOTE: Data shown isfor units operating at 45 F (7.2C)saturated suction and
95 F (35 C) entering air.
Table 4A — Refrigerant Piping Sizes — 60 Hz
LENGTH OF INTERCONNECTING PIPING — FT (M)
0-15
UNIT
(0-4.6)
LSLSLSLSLS
1
38AE012
⁄211⁄
38AE0141⁄211⁄
38AE0161⁄213⁄
38AKS0245⁄815⁄
LEGEND
L—Liquid
S—Suction
Close coupled.
NOTES:
1. Pipe sizes are based ona2F(1.1 C) loss for liquid lines and a 1.5 F
(0.8 C) loss for suction lines.
2. Pipe sizes are basedonan equivalent length equal to the maximumlength
ofinterconnectingpiping plus50% forfittings. Amore accurate estimatemay
result in smaller sizes.
8
8
8
8
15-25
(4.6-7.6)
1
⁄211⁄
1
⁄213⁄
5
⁄813⁄
5
⁄815⁄
8
8
8
8
(7.6-15.2)
Line Size — in. OD
5
⁄813⁄
5
⁄813⁄
5
⁄815⁄
7
⁄815⁄
25-50
LIQUID LINE
Maximum
Allowable
Temp.
50-75
(15.2-22.9)
5
8
⁄813⁄
5
8
⁄815⁄
7
8
⁄815⁄
7
8
⁄821⁄
Loss
F (C)
Filter Drier
Sight Glass
Flare Conn.*
(22.9-30.5)
5
8
⁄815⁄
7
8
⁄815⁄
7
8
⁄821⁄
7
8
⁄821⁄
and
in. (mm)
5
⁄
8
75-100
8
8
8
8
Fig. 3 — Compressor Mounting
Table 4B — Refrigerant Piping Sizes — 50 Hz
LENGTH OF INTERCONNECTING PIPING — FT (M)
UNIT
0-15
(0-4.6)
15-25
(4.6-7.6)
25-50
(7.6-15.2)
50-75
(15.2-22.9)
Line Size — in. OD
LSLSLSLSLS
1
38AE012
⁄211⁄
38AE0141⁄211⁄
38AE0161⁄213⁄
38AKS0245⁄815⁄
1
8
⁄211⁄
1
8
⁄211⁄
5
8
⁄813⁄
5
8
⁄815⁄
5
8
⁄811⁄
5
8
⁄813⁄
5
8
⁄813⁄
5
8
⁄815⁄
8
8
8
8
5
⁄813⁄
5
⁄813⁄
5
⁄813⁄
7
⁄815⁄
8
8
8
8
LEGEND
L—Liquid
S—Suction
Close coupled.
NOTES:
1. Pipe sizes are based ona2F(1.1 C) loss for liquid lines and a 1.5 F
(0.8 C) loss for suction lines.
2. Pipe sizes are basedonan equivalent length equal to the maximumlength
ofinterconnectingpiping plus50% forfittings. Amore accurate estimatemay
result in smaller sizes.
6
75-100
(22.9-30.5)
5
⁄813⁄
5
⁄813⁄
5
⁄815⁄
7
⁄815⁄
8
8
8
8
INSTALL FILTER DRIER(S) AND MOISTURE INDICATOR(S) — Every unit should have a filter drier and liquidmoisture indicator(sightglass).Insome applications, depending
on space and convenience requirements, it may be desirable
to install 2 filter driers and sight glasses. One filter drier and
sight glass may be installed at A locations in Fig. 4. Or, 2
filter driers and sight glasses may be installed at B locations.
Select the filter drier for maximum unit capacity andminimum pressure drop. Complete the refrigerant piping from
indoor unit to outdoor unit before opening the liquid and suction lines at the outdoor unit.
TXV — Thermal Expansion Valve
Fig. 4 — Location of Sight Glass(es)
and Filter Drier(s)
INSTALL LIQUID LINE SOLENOID VALVE — SOLENOID DROP — It is recommended that a solenoid valve be
placed in the main liquid line (see Fig. 4) between condensing unit (38AE/AKS) and fan coil (40RR, 40RE). (A liquid
line solenoid valve is required when the liquid line length
exceeds 100 ft [30.5 m] or when the condensing unit is connected to the chiller barrel in a built-up chiller system.) This
valve prevents refrigerant migration (which causes oil dilution) to the compressor during the off cycle at low outdoor
ambient temperatures. The solenoid should be wired in parallel with the compressor contactor coil. This means of electrical control is referred to as solenoid drop control.
NOTE: 38AKS024 has a fusible plug in the liquid line.
Fig. 5 — Location of Fusible Plug (38AE)
Step 4 — Install Accessories — Field install ac-
cessories such as winter start control or low-ambient control
before proceedingwithwiring.Refertothe instructions shipped
with the accessory.
Step 5 — Complete Electrical Connections
POWER WIRING — Unit is factory wired for voltage shown
on nameplate. Provideadequatefuseddisconnectswitchwithin
sight from unit and readily accessible from unit, but out of
the reach of children. Lock switch open (off)topreventpower
from being turned on while unit is being serviced. Disconnect switch, fuses, and field wiring must comply with national and local code requirements. See Tables 5A and 5B.
Route power wires through opening in unit end panel to
connection in unit control box as shown on unit label diagram and in Fig. 6. Unit must be grounded.
Affix crankcase heater warning sticker to unit disconnect
switch.
CONTROL CIRCUIT WIRING — Control voltage is 24 v.
See Fig. 7 and unit label diagram for field-supplied wiring
details. Route control wires through opening in unit end panel
to connection in unit control box.
INSTALL LIQUID LINE SOLENOID VALVE (OPTIONAL)
— CAPACITY CONTROL — If 2-step cooling is desired,
place a solenoid valve in the location shown in Fig. 4.
MAKE PIPING CONNECTIONS — Do not remove runaround loop from suction and liquid line stubs in the compressor compartment until piping connections are ready to
be made. Pass nitrogen or other inert gas through piping while
brazing to prevent formation of copper oxide.
Install field-supplied thermostatic expansion valve(s) in indoor section. If 2 thermostatic expansion valves are installed
for 2-step cooling, install field-supplied liquid line solenoid
valve ahead of the second expansion valve.
PROVIDE SAFETY RELIEF — A fusible plug is located
on the compressor crankcase or in the liquid line (Fig. 5).
Do not cap this plug. If local code requires additional safety
devices, install them as directed.
LEGEND
EQUIP GND — Equipment Ground
NEC— National Electrical Code
FLA — Full Load Amps (Fan Motors)
ICF— Maximum Instantaneous Current Flow during start-up (LRA of compressor plus total FLA of fan motors)
kW— Total Fan Motor Input (kilowatts)
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps per NEC (U.S.A.), Section 430-24
MOCP — Maximum Overcurrent Protection (amps)
RLA — Rated Load Amps (Compressor)
*Units are suitable for use on electrical systems where voltage supplied to the unit terminals is not below or above
the listed limits.
NOTES:
1. The MCA and MOCP values are calculated in accordance with the National Electrical Code (NEC) article 440
(U.S.A. standard).
2. Motor RLA and LRA values are established in accordance with Underwriters’ Laboratories (UL) Standard 1995
(U.S.A. standard).
tem by either of the methods described in Carrier Standard
Service Techniques Manual, Chapter 1.
the entire refrigerant sys-
START-UP
To StartUnit—
temperature.After starting unit, there is a delay of at least 3
seconds before compressor starts.
Set thermostat set point belowthe space
Leak Test the entire refrigerant system by the pres-
sure method described in Carrier Standard Service Techniques Manual, Chapter 1. Use R-22 at approximately
25 psig (172.4 kPa) backed up with an inert gas to a total
pressure not to exceed 245 psig (1689 kPa).
Turn onCrankcaseHeaters for 24 hours before start-
ing the unit to be sure all the refrigerant is out of the oil. To
energize the crankcase heaters, proceed as follows.
1. Set the space thermostat set point above the space temperature so there is no demand for cooling.
2. Close the field disconnect.
3. Turn the fan circuit breaker on. Leave the compressorcircuit breakers off. The crankcase heaters are now
energized.
Add Preliminary Charge to the refrigerant system ac-
cordingly to Carrier Standard Service Techniques Manual,
Chapter 1. By the liquid charging method and charging by
weight procedure, charge the units with approximately the
amounts of R-22 refrigerant shown in Table 6.
1. Compressor oil level must be at least within sight in
the compressor sight glass. Add oil if necessary (see
Tables 1A-1D and Oil Charge section).
2. Compressor holddown bolts must be snug, but not tight.
Refer to Compressor Mounting section and tag on compressor foot.
3. All internal wiring connections must be tight; all barriers
and covers must be in place.
4. Electrical power source must agree with unit nameplate
rating.
5. All service valves must be open.
6. Crankcase heater must be firmly locked into the compressor crankcase.
Oil Charge (see Tables 1A-1D) —Allow unit to run for
about 20 minutes. Stop unit and check compressor oil level
at sight glass. Add oil if necessary to bring oil to the correct
level shown in Fig. 8. Use only Carrier-approved compres-sor oil. Approved oils are:
Do not reuse drained oil or use any oil that has been exposed to atmosphere.Procedures for adding or removing oil
are given in Carrier Standard Service Techniques Manual,
Chapter 1, Refrigerants.
If oil is added, run unit for additional 10 minutes. Stop
unit and check oil level. If level is still low,add oil only after
determining that piping system is designed for proper oil return and that the system is not leaking oil.
38AKS024
(06E COMPRESSOR)
38AE012,014,016
(06D COMPRESSOR)
Fig. 8 — Operating Oil Levels
Refrigerant Charge — Actual start-up should be done
only under supervision of a qualified refrigeration mechanic. Refer to charging charts.
See Fig. 9-11 for the particular unit being charged. Measure pressure at the liquid line service valve, being sure a
Schrader depressor is used if required. Also, measure liquid
line temperature as close to the liquid service valve as possible. Add or reduce charge until the pressure and temperature conditions of the charging charge curve are met. If liquid pressure and temperature point falls above curve, add
charge. If liquid pressure and temperature point falls below
curve, reduce the charge until the conditions match the curve.
Never charge liquid into the low-pressure side of system. Do not overcharge. During charging or removal of
refrigerant, be sure indoor fan system is operating.
9
10
Fig. 9 — 38AE012 and 38AKS024 Charging Chart
Fig. 10 — 38AE014 Charging Chart
11
Fig. 11 — 38AE016 Charging Chart
12
Check Operation — Verify operation of all safety con-
trols. Replace all service panels. Be sure that control panel
cover is closed tightly.
OPERATING SEQUENCE
Cooling—
mostat closes, the timer starts. After approximately 3 seconds, the timer activates the compressor and fan motor no.
1 contactor. When the liquid pressure builds to approximately 257 psig (1772 kPa), fan motor no. 2 is energized.
On demand for additional cooling capacity, the second stage
(TC2) of the cooling thermostat closes, energizing a fieldsupplied liquid line solenoid (LLS) valve,which opens. This
increases the suction pressure, causing the compressor tooperate at higher capacity.
When fan switch is set at AUTO, the indoor-air fan cycles
with the compressor. When the switch is set at CONT, the
indoor-air fan runs continuously.
At shutdown, the Time Guardt II timer prevents the compressor from restarting for approximately 5 minutes.
When installed, a field-supplied solenoid valve (wired in
parallel with the compressor contactor coil), shuts off the liquid line to prevent refrigerant migration back to the compressor during the off cycle.
When the first stage (TC1) of the cooling ther-
Heating— The heating thermostat (TH) energizes a field-
supplied relay which operates heating controls and energizes the indoor-fanrelay. When the fan switch issetatAUTO,
the indoor-air fan cycles with the heating control. The indoorair fan runs continuously when the fan switch is set at CONT.
Fan Cycling — Head pressure control is accomplished
by cycling the fans. The no. 2 fan responds to liquid line
pressure, cycling on at approximately 257 psig (1772 kPa)
and off at approximately 126 psig (869 kPa).
WinterStart Control (If Installed) — When the com-
pressor starts, the control’s bypass timer contacts close for
150 seconds, thereby bypassing the low-pressure switch during start-up. After 150 seconds, the bypass timer contacts
open and the low-pressure switch is restored to the safety
circuit.
Head Pressure Control — Fan cycling is a standard
feature. The no. 2 fan cycles in response to changes in liquid
pressure. The switch cycles the fan off at 126 ± 4 psig (869
± 28 kPa) as pressure decreases, and cycles it back on at 257
(+5, −0) psig (1772 [+103, −0] kPa).
Fig. 12 — Compressor Capacity Control Unloader
TimeGuardII Circuit — Prevents short-cycling by pro-
viding a delay of approximately 5 minutes before restarting
compressor after shutdown from safety device action.
On start-up, the Time Guard II timer causes a delay of
approximately 3 seconds after thermostat closes.
On compressor shutdown, the timer recycles for approximately 5 minutes. During this time, the compressor cannot
restart.
Refer to Fig. 13 and to label diagram on unit.
SERVICE
Capacity Control —
loader controls 2 cylinders and provides capacity control. Unloaders are factory set (see Tables 1A-1D), but can be field
adjusted as described in the 2 following sections.
CONTROL SET POINT (cylinder load point) is adjustable
from 0 to 85 psig (586 kPa). To adjust, turn control set point
adjustment nut (Fig. 12) clockwise to its bottom stop. In this
position, set point is 85 psig (586 kPa). Next, turn adjustment counterclockwise to desired control set point. Every
full turn counterclockwise decreases set point by
7.5 psig (51.7 kPa).
PRESSURE DIFFERENTIAL (difference between cylinder
load and unload points) is adjustable from 6 to 22 psig (41.4
to 152 kPa). To adjust, turn pressure differential adjustment
screw (Fig. 12) counterclockwise to its back stop position.
In this position, differential is 6 psig (41.4 kPa). Next, turn
adjustment clockwise to desired pressure differential setting.
Every full turn clockwise increases differential by 1.5 psig
(10.3 kPa).
A suction pressure-actuated un-
Fig. 13 — Timer Sequence Chart
Winter-Start Control (If Required) — Install Ac-
cessory Package 38AE900021.
Crankcase Heater — The heater prevents refrigerant
migration and compressor oil dilution during shutdown whenever compressor is not operating. It is wired into the control
circuit, and cycles with the compressor; the heater is off when
compressor is running, and on when compressor is off.
Both compressor service valves must be closed whenever
the crankcase heater is deenergized for more than 6 hours.
The crankcase heater is operable as long as the control circuit is energized.
13
Outdoor Fans — Each fan is supported by a formed-
wire mount bolted to the fan deck and covered with a wire
guard. The exposed end of the motor shaft is covered with
a rubber boot. In case a fan motor must be repaired or replaced, be sure the rubber boot is put back on when the fan
is reinstalled and be sure the fan guard is in place before
starting the unit. Figure 14 shows the proper position of the
mounted fan. Fan motors have permanently lubricated
bearings.
38AE012,014,016
(38AE014,016, 38AKS024) and restrict outdoor airflow.Use
a flashlight to determine if dirt or debris has collected between coil sections. Clean coil as follows:
1. Turn off unit power.
2. Remove screws holding rear corner posts and top
cover in place. Pivot top cover up 12 to 18 in. (305 to
457 mm) and support with a rigid support. See Fig. 15.
3. Remove clips securing tube sheets together at the return
bend end of the coil. Carefully spread the ends of the coil
rows apart by moving the outer sections. See Fig. 16.
4. Using a water hose,orothersuitableequipment,flushdown
between the sections of coil to remove dirt and debris.
5. Clean the remaining surfaces in the normal manner.
6. Reposition outer coil sections.
7. Reinstall clips which secure tube sheets.
8. Replace top cover and rear corner posts.
38AKS024
Fig. 14 — Outdoor Fan
Lubrication
F A NMOTORS have sealed bearings. No provisions are made
for lubrication.
COMPRESSOR has its own oil supply. Loss of oil due to a
leak in the system should be the only reason for adding oil
after the system has been in operation. See Oil Charge
section.
CleaningCoils— The coils can be cleaned with a vacuum
cleaner,washed out with water, blown out with low-pressure
compressed air, or brushed (do not use wire brush). Fan mo-
tors are drip-proof but not waterproof.
Clean outdoor coil annually or as required by location or
outdoor air conditions. Inspect coil monthly, and clean as
required. Fins are not continuous through coil sections; dirt
and debris may pass through first section, become trapped
between the 2 rows of fins (38AE012) or 3 rows of fins
Fig. 15 — Pivot and Support Top Cover
Fig. 16 — Coil Cleaning (Typical)
14
TROUBLESHOOTING
PROBLEMSOLUTION
COMPRESSOR DOES NOT RUN
Contactor Open
1. Power off.1. Restore power.
2. Fuses blown in field power circuit.2. After finding cause and correcting, replace with correct size fuse.
3. No control power.3. Check secondary fuse(s); replace with correct type and size.
6. Indoor airflow restricted.6. Remove obstruction.
Suction Pressure High
1. Unloaders not functioning.1. Check unloader adjustments.
2. Compressor valve defective.2. See compressor service literature.
3. Heat load excessive.3. Check for open doors or windows in vicinity of fan coil.
UNIT OPERATES TOO LONG OR CONTINUOUSLY
1. Low refrigerant charge.1. Add refrigerant.
2. Control contacts fused.2. Replace control.
3. Air in system.3. Purge and evacuate system.
4. Partially plugged expansion valve or filter drier.4. Clean or replace.
SYSTEM IS NOISY
1. Piping vibration.1. Support piping as required.
2. Compressor noisy.2. Check valve plates for valve noise. Replace compressor if
COMPRESSOR LOSES OIL
1. Leak in system.1. Repair leak.
2. Crankcase heaters not energized during shutdown.2. Check wiring and relays. Check heater and replace if
3. Improper interconnecting piping design.3. Check piping for oil return. Replace if necessary.
FROSTED SUCTION LINE
Expansion valve admitting excess refrigerant.Adjust expansion valve.
HOT LIQUID LINE
1. Shortage of refrigerant due to leak.1. Repair leak and recharge.
2. Expansion valve opens too wide.2. Adjust expansion valve.
FROSTED LIQUID LINE
1. Restricted filter drier.1. Remove restriction or replace.
2. Liquid line solenoid valve partially closed.2. Replace valve.
COMPRESSOR WILL NOT UNLOAD
1. Defective unloader.1. Replace unloader.
2. Defective capacity control solenoid valve (if used).2. Replace valve.
3. Miswired capacity control liquid line solenoid (if used).3. Rewire correctly.
4. Weak, broken, or wrong valve body spring.4. Replace spring.
COMPRESSOR WILL NOT LOAD
1. Miswired capacity control liquid line solenoid (if used).1. Rewire correctly.
2. Defective capacity control solenoid valve (if used).2. Replace valve.
3. Plugged strainer (high side).3. Clean or replace strainer.
4. Stuck or damaged unloader piston or piston ring(s).4. Clean or replace the necessary parts.
Check outdoor-air fan thermostat settings.
Check unloader setting.
bearings are worn.
defective.
16
PACKAGED SERVICE TRAINING
Our packaged service training programs provide an excellent way to increase your knowledge of the
equipment discussed in this manual. Product programs cover:
• Unit Familiarization• Maintenance
• Installation Overview• Operating Sequence
A large selection of product, theory, and skills programs is available. All programs include a video
cassette and/or slides and a companion booklet. Use these for self teaching or to conduct full training
sessions.
For a free Service Training Material Catalog (STM), call 1-800-962-9212. Ordering instructions are
included.
Copyright 1994 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 3a 2a
PC 111Catalog No. 563-746Printed in U.S.A.Form 38A-4SIPg 184-94Replaces: 38AE-17SI
START-UP CHECKLIST
A. Preliminary Information
OUTDOOR: MODEL NO.SERIAL NO.
INDOOR: AIR HANDLER MANUFACTURER
MODEL NO.SERIAL NO.
ADDITIONAL ACCESSORIES
B. Pre-Start-Up
OUTDOOR UNIT
IS THERE ANY SHIPPING DAMAGE?
IF SO, WHERE:
WILL THIS DAMAGE PREVENT UNIT START-UP?(Y/N)
CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT?(Y/N)
HAS THE GROUND WIRE BEEN CONNECTED?(Y/N)
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY?(Y/N)
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY?(Y/N)
HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED (Snubber washers are snug, but not tight)?
(Y/N)
(Y/N)
CUT ALONG DOTTED LINE
CONTROLS
ARE THERMOSTAT AND INDOOR FAN CONTROL WIRING
CONNECTIONS MADE AND CHECKED?(Y/N)
ARE ALL WIRING TERMINALS (including main power supply) TIGHT?(Y/N)
HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS?(Y/N)
INDOOR UNIT
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE?(Y/N)
ARE PROPER AIR FILTERS IN PLACE?(Y/N)
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT?(Y/N)
DO THE FAN BELTS HAVE PROPER TENSION?(Y/N)
HAS CORRECT FAN ROTATION BEEN CONFIRMED?(Y/N)
PIPING
ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE EVAPORATOR COILS AS REQUIRED?(Y/N)
HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR, CONDENSER, EVAPORATOR(S),
WITH A LEAK DETECTOR?(Y/N)
LOCATE, REPAIR, AND REPORT ANY LEAKS.
HAVEALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED)?(Y/N)
HAVE LIQUID LINE SERVICE VALVES BEEN OPENED?(Y/N)
IS THE OIL LEVEL IN EACH COMPRESSOR CRANKCASE VISIBLE IN THE COMPRESSOR SIGHT GLASSES?
(Y/N)
CHECK VOLTAGE IMBALANCE
LINE-TO-LINE VOLTS:AB
(AB + AC + BC)/3 = AVERAGE VOLTAGE =
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CHECK EVAPORATOR FAN SPEED AND RECORD.
CHECK CONDENSER FAN SPEED AND RECORD.
AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:
OIL PRESSURE
SUCTION PRESSURE
SUCTION LINE TEMP
DISCHARGE PRESSURE
DISCHARGE LINE TEMP
ENTERING CONDENSER AIR TEMP
LEAVING CONDENSER AIR TEMP
EVAP ENTERING-AIR DB (dry bulb) TEMP
EVAP ENTERING AIR WB (wet bulb) TEMP
EVAP LEAVING AIR DB TEMP
EVAP LEAVING AIR WB TEMP
COMPRESSOR AMPS (L1/L2/L3)//
CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES; ARE THE SIGHT GLASSES SHOWING
OIL LEVEL IN VIEW?(Y/N)
NOTES:
Copyright 1994 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 3a 2a
PC 111Catalog No. 563-746Printed in U.S.A.Form 38A-4SIPg CL-24-94Replaces: 38AE-17SI
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.