Carrier 380B User Manual

Page 1
iNjumber One AirConditbning Maker
Division of Carrier Corporation
Heat Pump — Outdoor Section
INDEX
Page
Step 1 — Check Equipment and Jobsite . 1
• UNPACKAGE UNIT
• INSPECT EQUIPMENT
• COMPLETE OR CONSIDER SYSTEM REQUIREMENTS
Step 2 — Mount Outdoor Heat Pump .. 3
• ON THE GROUND: MOUNT UNIT ON A SOLID, LEVEL CONCRETE PAD
• ON THE ROOF: MOUNT UNIT ON A LEVEL PLATFORM OR FRAME
Step 3 — Make Piping Connections
_______
3-5
• REPLACE THE ACCURATER™ RE FRIGERANT CONTROL PISTON IN
THE INDOOR COIL AS REQUIRED
• CONNECT REFRIGERANT LINES
Step 4 Make Electrical Connections .. 5-7
• INSTALL A BRANCH CIRCUIT DISCONNECT PER NEC
• ROUTE LINE POWER LEADS
INTO UNIT
• CONNECT GROUND LEAD AND POWER WIRING
• SEE INDOOR UNIT AND ELECTRIC HEATER INSTALLATION, START-UP AND SERVICE INSTRUCTIONS
• CONNECT CONTROL POWER
WIRING (24 v)
START-UP............................................................ 7
SERVICE............................................................ 7-14
MAINTENANCE................................................ 14-17
SAFETY CONSIDERATIONS
Installation and servicing of air conditioning equipment can be hazardous due to system pres sure and electrical components. Only trained and qualified service personnel should install, repair or service air conditioning equipment.
Untrained personnel can perform basic main tenance functions of cleaning coils and cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on air conditioning equipment, observe
precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing oper ations. Have fire extinguisher available for all brazing operations.
WARNING: Before performing sersice or maintenance operations on system, turn off mam power switches to indoor unit and out door unit. Turn off accessory heater power switch if applicable. Electrical shock could cause personal injury'.
INSTALLATION
Step 1 — Check Equipment and Jobsite
UNPACKAGE UNIT — Move to final location. Lift carton off, taking special care not to damage service valves or grilles.
INSPECT EQUIPMENT — File claim with ship ping company if shipment is damaged or incomplete.
COMPLETE OR CONSIDER SYSTEM RE QUIREMENTS before installing the 38QB:
Consult local building codes and National Electrical Code (NEC) for special installation requirements.
When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping and servicing. Position so water or ice from roof cannot drop directly on top of unit.
Make provisions for condensate drainage and defrost water disposal whether unit is installed on ground or roof. (Ensure unit basepan drainage holes are not blocked.) See Step 2 for details. Roof installation method for 38QB depends on building construction and special requirements of local codes. Be sure that roof can support unit weight.
It is recommended that 38 QB units be used with
Carrier approved indoor sections; see Table 1.
System Refrigerant Control on 38QB units and matching Carrier indoor units is a factory-installed AccuRater™ device (bypass type). Bypass-type AccuRater components are discussed in the service section of this booklet. The AccuRater piston has a refrigerant metering hole thru it and is field replace able. Table 2 indicates indoor units for which the
Carrier Corporation 1982
Form 38QB-1SIM
Page 2
4'-0"(l220mm) OVERHEAD SPACE REQUIRED FOR SERVICE AND AIRFLOW
^ (22 mm) DIAM HOLE
FOR CONTROL WIRING
LIQUID VALVE SERVICE PORT
AIRFLOW SUCTION SERVICE PORT
f
VAPOR VALVE SERVICE PORT
б" (152 mm) THICK
l|"(35mm) DIAM HOLE
FOR POWER
WIRING
l'-0"(305 mm) GRAVEL APRON
I'-n" (584mm) DIAM
T
б" (I52 mm) THICK
CONCRETE MOUNTING PAD FOR 38QB0I8
'MARKER TAPE
(HIDDEN)
r
12" (305mm) GRAVEL APRON
I'-n" {585mm) DIAM x б"(152 mm)THK CONCRETE
MOUNTING PAD FOR 38QB0I8
2-6" (762 mm) DIAM x б" (152mm) THK CONCRETE MOUNTING PAD FOR 38QB024-042
Fig. 1 — Dimensions, Connections and
Mounting Pad (Refer to Table 2)
2'-6"(762mm) DIAM
6" (152 mm THICK
CONCRETE MOUNTING PAD FOR 38QB024-042
Fig. 2 — Accessory Mounting Rack
Table 1 — Carrier Approved 38QB Systems
OUTDOOR
UNIT
38QB
018
024 46
030
036 61
042
‘Replace factory-installed piston with this piston size
REQUIRED OUTDOOR
PISTON
SIZE
42
59
63
INDOOR
UNIT
MODEL &
SIZE
28HQ,VQ024
40AQ024 40DQ024
28HQ.VQ030
40AQ030 40DQ030
28HQ,VQ036
40AQ036 40A0036
28HQ.VQ042
40QB042 40QB042
28HQ.VQ048
REQUIRED
INDOOR
PISTON
SIZE
52
61*
70*
70*
76
76*
Page 3
Table 2 — Installation Data (Fig. 1)
required replacement piston is factory supplied with specified 38QB outdoor unit. Replace piston as described under AccuRater™ Servicing on page 13.
Top Cover Removal — Top cover can be removed for wiring or servicing heat pump. Loosen decora
tive strip and slide down off screw heads. Remove 3 screws in connector plate and 2 screws on front of unit. Loosen remaining 4 screws. Lift top from unit
(See Fig. 1).
Step 2 — Mount Outdoor Heat Pump
ON THE GROUND: MOUNT ON A SOLID, LEVEL CONCRETE PAD (See Fig. 1). Swing 3 legs down and lock in position, except when using
accessory rack. Use accessory heat pump rack (Fig. 2) in areas where prolonged subfreezing tem peratures or heavy snow occur. (Refer to installation instructions included with rack.) Drainage holes in unit base must not be obstructed.
ON THE ROOF: MOUNT UNIT ON A LEVEL PLATFORM OR FRAME. Proper precaution must be taken for support of unit in roof design. Elevate unit for proper clearance as described under ground installation above. Plan roof design and water drainage to prevent unit from setting in water. Flash all roof openings to prevent leaks.
Roof mounted units exposed to winds above 5 mph (8 km/ h) may require protective wind baffles (field fabricated) to achieve adequate defrost.
Step 3 — Make Piping Connections — The
38QB can be connected to indoor units using Carrier accessory tubing package or field-supplied tubing of refrigerant grade. See Table 2 for unit piping connection type and size. See Table 3 for accessory tubing sizes. For requirements beyond 50 ft (15.2 m), obtain information from local Carrier
distributor. Isolate interconnecting tubing from framing and ductwork or where tubing runs thru
stud spaces, enclosed ceilings or pipe chases. Use isolation type hangers. Fig. 3, since rigid fastening transmits pulsations to structure creating objec tionable sound.
A capacity reduction will result if accessory tub
ing is used in 38QB042 systems. For example, when a 25-ft (7.6 m) 7/8-in. (22 mm) accessory package is
used, there is a capacity reduction of 1-1/2 percent.
Page 4
Table 3 — Accessories
PART NO.
38CQ900081
38CQ900111
38QB90002106 38HQ9000011
28VQ900011 38RQ900081 38RQ900001
38HQ900002 38CQ900172 38RQ900091 38QB90000106 38QB90001106 38HQ90014106 38CQ900141 HC95DD121* HC95DD058*
HC95DD088* HN61HB515* HN61HB496*
TUBING
PACKAGE
38LS958151 38LS958201 20 38LS958251 25 3/8 38LS958301 38LS958351 38LS958401 38LS958501
38LS934151 15 "IMd 3/8 38LS934201 38LS934251 38LS934301 30 3/8 38LS934351 38LS934401 38LS934501 50 3/8 3/8
38LS978151 38LS978201 38LS978251 25 3/8 3/8 38LS978301 30 3/8 3/8 38LS978351 38LS978401 38LS978501
•Available thru Carrier Service Parts fSuction line is insuiated and has 90° bend jpor 5/8-in (7.9-mm) evaporator connection, cut off 3/4-in. (19 05-mm) belled end
••Capacity reduction may occur when 7/8-in, (22 22-mm) accessory tubing is used on 38QB042
Length
(ft)
15
30
35 40 50
20 25
35 40
15
20
35 3/8 40 3/8
50 '^<2
Low-Voltage Control — Honeywell Thermostat HH07AT171 and Thermostat Subbase HH93AZ173 — (Automatic Changeover)
Low-Voltage Control — Honeywell Thermostat HH07AT171 and Thermostat Subbase HH93AZ175 — (Manual Changeover)
Service Sentry (Six HN65CT004)
Hot Shot® Domestic Water Preheater Twelve 3/4- x 1-1/8 in. connection adapters Bi-Flow Heat Pump Filter Drier (Six KH45LD077) Supplemental Heat Relay — (Required with 2 outdoor thermostats.)
(Service Parts) Outdoor Thermostat (Six 38HQ9000101) Optimizer Control Outdoor Thermostat (Six 38CQ900161 ref HH22AG110) Optimizer II Control Assembly (Use with HH22AG110 outdoor thermostat.)
Heat Pump Rack
Heat Pump Rack Optimizer III (Six 38HQ900141) Solid-State Time Guard It (24-volt) Start Capacitor Start Capacitor
Start Capacitor Relay Relay
Liquid
OD
(in.) (in.)
3/8 3/8 3/8
i ■ m
5/16 5/16 3/8; 5/16 3/8
1/4
ÍL
3/8 3/8 3/8
I'-^.5? r m ".
3/8
? ' '■
3/8
Í
3/8 3/8 3/8
\
1
3/8
DESCRIPTION
Tube End OD
3/8 3/8 3/8
3/8 3/8
3/8 3/8 3/8 3/8
3/8
3/8 3/8 3/8
10
10
ri^’ 3/4 I
I ’
I 10
i ■ W
10 10 3/4
' Í0
10 7/8^ 10 10
^0
10 7/8*
(in.)
5/8 5/8 5/8 5/8 5/8 5/8
....
: 5/8
3/4 3/4 3/4 3/4 3/4
7/8^
7/8^ 7/8^ 7/8^
7/8*
OD
TUBING
n
45.7» I
ÍS79
ism
15.7»
mm
miss
ism I
ISiíSl
WM Í0MI
15061
2a 22 I
22.a2i
2222
2ZZH i
22.22 S i
Suctionf
MODEL 38QB
All
042
All
018
024, 030, 036, 042
All
018
024, 030
036 018
024, 030, 036
024, 030
036, 042
r
Unit
38QB
018
When other than 25 ft (7,6 m) of interconnecting tubing is used, follow special requirements described in Refrigerant Charging. Do not use less than 10 ft
(3 m) of interconnecting tubing. Do not cut 5/ 16-in. (7.94 mm) or 1/4-in. (6.35 mm) liquid line due to swage at ends. Do not cut 7/8-in. (22.22 mm)
suction line. Bend or coil to fit.
Do not use damaged or contaminated tubing.
Always evacuate or purge evaporator coil and tubing system (use field-supplied refrigerant, not unit refrigerant).
When making tubing connections, be sure to
provide clearance at unit for electrical connections.
Page 5
REPLACE THE ACCURATER™ REFRIG ERANT CONTROL PISTON IN THE INDOOR
COIL AS REQUIRED before connecting refrig erant lines. See Table 1. Correct piston is supplied with 38QB unit. For piston replacement instruc
r
tions, see AccuRater Servicing on page 13.
Sweat Connection to Compatible Fitting (Use refrigerant grade tubing.)
1. Remove locking nut, rubber O-ring and Schrader core from valve.
2. Cut tubing to correct length.
3. Insert tube into Compatible Fitting. Wrap top CONNECT REFRIGERANT LINES to fittings on unit suction and liquid service valves (Fig. 1).
Liquid service valve has flare fitting; suction service valve has Compatible Fitting. Make suction line
connection first. Slide flare nut on liquid line, then
flare and connect liquid line. Use a maximum torque of 15ft-lb (20N/m) to tighten flare nut.
(Do not disassemble AccuRater.) Unit Compatible
Fitting permits mechanical or sweat connection as
described below.
When a 7/8-in. (22.22 mm) field-supplied suction line is used on 38QB036, a field-supplied 3/4-in. (19.05 mm) to 7/8-in. (22.22 mm) suction line
and bottom of service valves in wet cloth to pre vent damage by heat. Solder with low tempera ture ([430 F] [221 C]) silver alloy solder.
4. Replace Schrader core.
5. Evacuate or purge system with field-supplied refrigerant.
Step 4 — Make Electrical Connections — Field
wiring must comply with local and national fire, safety and electrical codes. Voltage to unit must be within ± 10% of voltage indicated on nameplate. Contact local power company for correction of improper line voltage.
adapter must be provided (not required if 38LS accessory tubing is used).
When a 1-1/8 in. (28.57 mm) field-supplied suc tion line is used on 38QB042, use accessory adapter 28VQ900001 or other field-supplied connection.
Sweat connect refrigerant suction line to 1-1/8 in. (28.57 mm) end of adapter. Connect 3/4-in. (19.06 mm) end of adapter to unit suction line Compatible Fitting.
Do not apply units in system where voltage may
fluctuate above or below permissible limits.
When making electrical connections, provide
clearance at unit for refrigerant piping connections.
See Table 4 for recommended wire and fuse sizes.
Mechanical Connection to Compatible Fitting
(Mate one set of connections at a time.)
1. Loosen nut on Compatible Fitting one turn. Do not remove.
2. Remove plug and be sure O-ring is in the groove inside the Compatible Fitting.
3. Cut tubing to correct length.
4. Insert tube into Compatible Fitting until it bottoms.
5. Tighten nut until it bottoms on back coupler flange. Keep tube bottomed in Compatible Fitting while tightening nut.
Fig. 4 — Urte Power Connections
UNIT
38QB
018 024 030 036
042 230-1
AWG — American Wire Gage
FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration
LRA — Locked Rotor Amps MCA — Minimum Circuit Amps RLA — Rated Load Amps
‘Permissible limits of the voltage range at which the unit will
operate satisfactorily.
V/PH
208-230/1
OPER
VOLTAGE* Max
254
254
COMPRESSOR
LRA
Min
197
207 98
48
66
82
88

Table 4 — Electrical Data (60 Hz)

FAN
FLA
RLA 124
155 15 5 20 6
199 2 40
1.25
2.40 2 40 2 40
Min Wire
Size
(AWG)t
14 12 12 10
10
Max Wire Min Gnd
(ft)
33 32 32 39
44
tCopper wire sizes based on 60 C Use copper or copper-clad
aluminum wire only Use latest NEC for copper-clad aluminum conductor sizing
{Required when using nonmetallic conduit.
“Maximum dual element size NOTE: All units have 24-v control circuit which requires external
power source
BRANCH CIRCUIT
Wire Sizet
m
Max Fuse or
HACR Type
CktBkrAmps“
14 12 12 10
10
25 35 35 45
45
MCA
168 21 8 21 8 28 2
27.3
Page 6
THERMOSTAT
SUBBASE
HH93AZI73
OR HH93AZI75
(38QB/40AQ 0R40QB WITHOUT ELECTRIC HEATER)
40AQ OR 40QB FAN COIL COOLING CONTROL KIT
TERMINAL BOARD
COOLING AND ONE-STAGE HEATING
38QB
TERMINAL
BOARD
THERMOSTAT
SUBBASE
HH93AZI73
ORHH93AZI75
COOLING AND TWO-STAGE HEATING
(38QB WITH 40AQ.40QB OR 40FS/28HQ, VQ
SUPPLEMENTAL HEAT, ONE OUTDOOR THERMOSTAT)
EQUIPPED WITH ELECTRIC HEATER;
40AQ OR 40QB ELECTRIC HEATER TERMINAL BOARD
38QB
TERMINAL
BOARD
THERMOSTAT
SUBBASE
HH93AZI73
OR HH93AZI75
COOLING AND TWO-STAGE HEATING
(38QB WITH 40AQ,40QB OR 40FS/28HQ.VQ
SUPPLEMENTAL HEAT. NO OUTDOOR THERMOSTATS)
EQUIPPED WITH ELECTRIC HEATER;
40AQ OR 40QB
ELECTRIC HEATER
TERMINAL BOARD
B
THERMOSTAT HH07AT 171 40DQ ELEC. HEATER WITHHH93AZI73(AUT0 (ALL MODELS) CHANGEOVER) OR HH93AZI75 LOW VOLTAGE TERM. (MAN CHANGEOVER) SUBBASE SPLICE CONNECTIONS
38QB
TERMINAL
BOARD
THERMOSTAT
SUBBASE
HH93AZI73 OR
HH93AZI75
COOLING AND TWO-STAGE HEATING
EQUIPPED WITH ELECTRIC HEATER;
40AQ OR 40QB
ELECTRIC HEATER
TERMINAL BOARD
(38QB WITH 40FS/28HQ,VQ
TERMINAL
SUPPLEMENTAL HEAT, TWO OUTDOOR THERMOSTATS)
38QB
TERMINAL
BOARD
38QB
BOARD
EHR — Supplemental Heat Relay
ODT — Outdoor Thermostat
-------------
-------------
Factory Wiring
Field Wiring
SUPPLEMENTAL HEAT, NO OUTDOOR THERMOSTATS)
‘Transformer (60 va) located in cooling control kit or electric heater tRemove factory-installed jumper (Connection B) when installing outdoor thermostats (ODT)

Fig. 5 — Control Circuit Connections

Page 7
INSTALL A BRANCH CIRCUIT DISCONNECT PER NEC of adequate size to handle unit starting current. Provide a separate disconnect for outdoor unit, indoor unit and for each accessory electric
' ■ heater circuit as required. (See Indoor Unit and
Electric Heater Installation, Start-Up and Service Instructions.) Locate disconnect(s) within sight of and readily accessible from the unit; per section 440-14 of National Electrical Code (NEC).
ROUTE LINE POWER LEADS INTO UNIT ~ Extend leads from disconnect thru power wiring hole provided (see Fig. 1) and into unit splice area. Remove top cover to gain access to unit wiring.
CONNECT GROUND LEAD AND POWER WIRING — Connect ground lead to a ground lug in control box for safety. Then connect power wiring. See Fig. 4. Splice line power leads to yellow
and black pigtails. Use wire nuts and tape at each connection. Connect unit wiring to copper or copper-clad aluminum power wiring.
SEE INDOOR UNIT AND ELECTRIC HEATER
INSTALLATION, START-UP AND SERVICE INSTRUCTIONS for line power wiring details. All
control wiring is shown in this booklet. CONNECT CONTROL POWER WIRING (24 V)
— Extend wiring thru hole provided (Fig. 1) and into low-voltage section of unit control ring.
Connect leads to control wiring terminal board as shown in Fig. 5.
^ Use indoor unit transformer as 24-v supply for
system. At least a 60-va transformer is recom mended. Carrier approved indoor units are equipped with a 60-va transformer. See indoor unit data.
Use Carrier accessory indoor thermostat with
subbase. Table 3.
Accessory Outdoor Thermostat provides adjust
able outdoor control of accessory electric heater. This thermostat makes contact when a drop in out door temperature occurs. It energizes a stage of elec tric heat when the outdoor temperature setting is reached, provided the room thermostat is on the second stage of heating. One outdoor thermostat is recommended for each stage of electric heat after the first stage. Set the outdoor thermostat(s) pro gressively lower for each stage. Refer to heat load of building and unit capacity to determine the correct outdoor thermostat settings.
The accessory supplemental heat relay is required when 2 outdoor thermostats are used. It is auto matically energized by the manually operated supplemental heat switch in the indoor thermo stat subbase. The thermostat locks out compressor and the relay bypasses the outdoor thermostats for electric heater operation during heat pump shut down. When one outdoor thermostat is used, a supplemental heat relay is not required. The supplemental heat switch in the indoor thermostat subbase bypasses outdoor thermostat, locks out compressor and activates electric heater.
MOUNT OUTDOOR THERMOSTAT on control ring, to the left of the low-voltage control connec tion. See Fig. 1.
Attach brackets with short sheet metal screws to avoid contact with coil. Leave capillary tube coiled in control compartment making sure it is clear of all electrical connections and sharp metal edges.
MOUNT SUPPLEMENTAL HEAT RELAY in convenient location on indoor unit. Attach with sheet metal screw.

START-UP

The 38QB unit is equipped with a crankcase heater. It is recommended that heater be energized a minimum of 24 hours before starting unit. To ener gize heater only, turn the thermostat to OFF posi tion and close electrical disconnect to heat pump.
Heat Anticipator Settings for Room Thermo
stat (HH07AT171) — Set anticipator settings for
room thermostat according to Table 5. These settings may be changed slightly to provide a greater degree of comfort for a particular installation.
Table 5 — Thermostat Anticipator Settings
UNIT 38Qa
( 018
\ - , 024
030 036 042
FIRST­STAGE
ANTICIPATOR
SETTING
Fixed
INDOOR
UNIT WITH
ELECTRIC
HEATER
40DQ and 40AQ Fan Coil with 40AQ Htrs
or 40QB Fan Coii
with 40QB Htrs
HTR
KW
50 75
100 150
20.0 25 0
30 0
34.0
SECOND-
STAGE
ANTICIPATOR
SETTINGS
25
50
75
To Start Unit — (Make sure crankcase heater
has been energized for 24 hours.) Adjust the thermo stat as follows:
1. Set selector switch at OFF.
2. Turn on main disconnect switch(es) to indoor and outdoor units.
3. Set fan switch as desired (ON or AUTO.).
4. Set thermostat dial at desired temperature.
5. Set selector switch at HEAT or COOL.
Check system refrigerant charge. See Refrigerant
Charging.
SERVICE
Page 8
Refrigerant Charging — The 38QB units contain
correct operating charge for complete system when connected to28HQ,VQ,40QB or 40AQ indoor units
with 25 ft (7.6 m) of tubing of recommended diam eter. Charge adjustment is required on other sys tems. Adjust system charge for refrigerant line lengths and diameters that differ from 25 ft (7.6 m) and 3/8 in. (9.53 mm) OD (liquid line), respectively, using refrigerant weights below. Twenty-five ft
(7.6-m), 3/8-in. (9.53-mm) OD tubing contains
14.4 oz (.4 kg) of R-22. Add R-22 charge to system if liquid line is over 25 ft (7.6 m); remove charge if liquid line is shorter than 25 ft (7.6 m).
When recharging is necessary during heating or
cooling season, weigh in total charge indicated in
Table 6. (Charge must be weighed in during heating
season.) Remove any refrigerant remaining in system before recharging. If system has lost com plete charge, triple-evacuate system to 5000 microns
(29.7 in. [100.5 kPa] vacuum) before recharging.
Service port connections are provided on liquid and suction line service valves for evacuation and charg ing. (See Fig. 6 for correct service port location
on cooling and heating cycles.) Dial-a-charge charging cylinder is an accurate device used to re charge systems by weight. These cylinders are avail able at refrigeration supply firms.
To check and/or adjust charging during cooling
season, use correct Cooling Cycle Charging Chart (Fig. 8, 10, 12, 14, 16) and follow Charging Chart
Method below. The charging chart may also be used
as an alternate method of recharging system.
To check system operation during heating cycle, use correct Heating Cycle Operation Check Chart (Fig. 9, 11, 13, 15, 17). These charts indicate whether a correct relationship exists between system
operating pressures and air temperatures entering indoor and outdoor units. If pressure and tempera ture lines do not intersect on chart, the system refrigerant charge may not be correct or other system abnormalities may exist. Do not use Opera tion Check Charts to adjust refrigerant charge. Weigh charge into system.
LIQUID LINE
DIAM (in.)
3/8
5/16
1/4
0 AV (•<*
tm
urn
OUNCES OF R-22/FT LENGTH
OF LIQUID LINE
58
36
.21
M ' '
,08
Table 6 — Service Data
UNIT38QB I R-22 CHG (lb) i
REFRIG CONTROL | AccuRater™' (Bypass Type) FAN
Cfin
t/4
Rpm
Diam

Fig. 6 — 38QB Refrigerant Flow Diagrams

(in.)
018
1 1
4,5
1 72
3,04
m Ì
i 1 1 Ml#
1
\ 1 ' ' '
1
1800 i
14-3/4 1 ,
107S
030 1
.7,3
036 1 042
! 7,8 1 8,5
3000
20
COOLING CYCLE CHARGING CHART METHOD
1. Operate unit a minimum of 10 minutes before checking charge, and after each charge adjustment.
2. Measure suction pressure by attaching a gage to outdoor unit suction service port. (See Fig. 6
for correct service port location on cooling cycle.)
3. Measure outdoor (coil inlet) air dry-bulb tem perature with service thermometer.
4. Using a sling psychrometer, measure wet-bulb temperature of air entering indoor unit.
5. Refer to correct Charging Chart. Locate on curves where outdoor air dry-bulb and indoor air wet-bulb temperature lines intersect.
Page 9
6. From intersect point, project vertically down ward to chart suction pressure line. Compare chart suction pressure to unit suction pressure (Step 2).
7. If unit suction pressure is lower than chart pres sure, add refrigerant to system until chart pressure is reached. If unit suction pressure is higher than chart pressure, remove refrigerant until chart pressure is reached.
Unit Single-Phase Compressors
COMPRESSORS OF THE SPLIT CAPACITOR (PSC) TYPE require an equalized system pressure
to start. When supply voltage is within 10% limit and compressor does not start, give compressor a tem porary capacitance boost. See Carrier Standard Service Techniques Manual, Chapter 2, for details.
mm.
Compressor Removal — See Table 7 for com
pressor information and Fig. 7 for component location. Shut off power to unit. Remove refrigerant from unit using refrigerant removal methods de
scribed in Carrier Standard Service Techniques Manual, Chapter 1, Refrigerants.
Be sure system pressure is 0 psig before proceeding.
Table 7 — Compressor Data (60 Hz)
STRAINER VAPOR REVERSING "e" COIL
MUFFLER

Fig. 7 — Component Location

HOT GAS DISCHARGE LINE
ACCUMULATOR
COMPRESSOR
coil section. Lift fan orifice/control ring after pinching and pressing down on 3 plastic pins of tube supports.
5. Remove louvered casing by taking out 16 screws securing it to the cabinet and sliding it away from the coil.
6. Using a midget tubing cutter, cut liquid and discharge lines on the coil and suction and discharge lines at a convenient place near the compressor for easy reassembly with copper slip couplings.
UNIT i
38QB i
018
024 I
030 I MD3214GE 44
V/PH
208-230/1
036,1
042 1
‘Refer to Service Parts catalog for replacement compressor model
numbers
230/1
PRODUCTION COMPRESSOR
Model*
CRA1-0150-PFV 51 1
MD2314GE 44
MD3514GE 44
PC4616BD
Oil Recharge
Ounces i
64
""TM""
1,3
1,3
Follow safety codes. Wear safety glasses and
work gloves. Have quenching cloth available.
CAUTION: Aíuíiwíusííj ititsing h m&á ir? uiüí
^ m 'phm
Oil líífesííg Of damage may result.
1. Remove top cover as described in Installation, Step 1.
2. Disconnect high- and low-voltage field wiring and fan motor leads from capacitor and contactor.
3. Remove screws holding discharge grille in place. Lift grille from unit.
4. Disconnect compressor leads (crankcase heater, low-pressure switch, defrost thermostat and solenoid coil) from electrical components and pull them thru the wire access opening into the
CAliXiOK: Excmive cmpp&t
7. After plugging connections, remove condenser coil by pinching plastic pins of tube supports that extend into basepan and lift vertically. Set coil on a clean, flat surface.
8. Remove compressor holddown bolts and slide out compressor. Remove crankcase heater.
have ftm extiugaisfeef âïtdior qtjieucbifig
cîoîît m oil vapor igastes,
9. Carefully unbraze suction and discharge line piping stubs from compressor after noting posi tion of stubs to assist when reinstalling.
10. Install new compressor, placing crankcase heater around compressor. Be sure compressor holddown bolts are in place.
11. Replace coil; braze suction and discharge lines to compressor piping stubs (at points where cut.
Step 6); rewire compressor and leak test.
12. Replace fan orifice/control ring; connect com pressor wires after feeding them thru control ring; replace fan/grille assembly and rewire;
Page 10
connect high- and low-voltage power wiring; and replace louvered casing.
13. Replace top cover by running 4 screws into orifice loosely (2 on each side of unit) and

CHARGING AND PRESSURE CHECK CHARTS

tighten when cover is in place. Replace remain
ing screws.
14. Evacuate and recharge system.
PSIG
(kPa)
(469) (483) (496) (510) (524) (538) (552) (565) (579) (593) (609)
Fig. 8 — 38QB018 with 28HQ.VQ024,
PRESSURE AT SUCTION SERVICE VALVE
40AQ024 or 40DQ024
Cooling Cycle Charging Chart
PSIG (kPo)
(455)(469 (483)(496)(510) (524)(538) (552)(565)(579)(593)(607)
PRESSURE AT SUCTION SERVICE VALVE
Fig. 10 — 38QB024 with 28HQ,VQ030,
40AQ030 or 40DQ030
Cooling Cycle Charging Chart
(kPa) SUCTION PRESSURE AT SERVICE PORT
Fig. 9 — 38QB018 with 28HQ,VQ024,
40AQ024 or 40DQ024
Heating Cycle Operation Check Chart
Fig. 11 — 38QB024 with 28HQ,VQ030,
40AQ030 or 40DQ030
Heating Cycle Operation Check Chart
10
Page 11
PSIG
(kPa)
(427) (441) (455)(469) (483) (496)(5I0) (524)(538)(552) (565)(579)
PRESSURE AT SUCTION SERVICE VALVE
Fig. 12 — 38QB030 with 28HQ,VQ036
or 40AQ036
Cooling Cycle Charging Chart
Fig. 14 — 38QB036 with 40AQ036,
28HQ,VQ042 or 40QB042
Cooling Cycle Charging Chart
(kPa)
SUCTION PRESSURE AT SERVICE PORT
Fig. 13 — 38QB030 with 28HQ,VQ036
or 40AQ036
Heating Cycle Operation Check Chart
Fig. 15 — 38QB036 with 40AQ036,
28HQ,VQ042 or 40QB042
Heating Cycle Operation Check Chart
11
Page 12
PSIG
(kPa)
220
(1517)
68 72 76 80 84
(469) (496) (524) (552) (579)
PRESSURE AT SUCTION SERVICE VALVE
f
Fig. 16 — 38QB042 with 40QB042
or 28HQ,VQ048
Cooling Cycle Operation Check Chart
Filter Drier — Install field-supplied filter drier
(Table 3) in system liquid line when refrigerant
system is opened for service as described under Compressor Removal. Position drier in liquid line at convenient location.
Pumpdown Procedure — The system may be
pumped down in order to make repairs on low side without losing complete refrigerant charge.
1. Attach pressure gage to suction service valve gage port.
2. Frontseat the liquid line valve.
3. Start unit and run until suction pressure reaches 5 psig (35 kPa) (see Caution).
4. Shut unit off and frontseat suction valve.
5. Vent remaining pressure to atmosphere.
Fig. 17 — 38QB042 with 40QB042
or 28HQ.VQ048
Heating Cycle Operation Check Chart
suction (low side) and discharge (high side) to allow pressure equalization.
INTERNAL CURRENT AND TEMPERATURE SENSITIVE OVERLOAD resets automatically when internal compressor motor temperature drops
to a safe level (overloads may require up to 45
minutes to reset). When an internal overload is suspected of being open, check by using an ohm­meter or continuity tester. If necessary, refer to Carrier Standard Service Techniques Manual, Chapter 2, for complete instructions.
LIQUID LINE LOW-PRESSURE SWITCH (LLPS) is connected in liquid line to work with compressor internal thermostat in providing loss-of­charge protection during the heating cycle. Control is mounted on liquid line.
With a high-side leak, pressure gradually de creases until low-pressure control stops the com pressor. (Low-pressure control settings are shown in Tables.)

Unit Controls and Safety Devices

HIGH-PRESSURE RELIEF VALVE is located in compressor. Relief valve opens at a pressure differ ential of approximately 500 psig (3448 kPa) between
12
Table 8 — Pressure Switch Settings
UNIT
018 024 030 036
042
Cut-in Cutout
22 ± 5 psig
LIQUID LINE
LOW-PRESSURE SWITCH
7 ± 3psig
Page 13
With a low-side leak there is always some pressure in the liquid line. However, compressor motor tem perature increases because of insufficient suction gas cooling. This causes internal thermostat to actuate and stop compressor. When compressor stops, system pressure equalizes and contacts on pressure control open. The compressor cannot re start until leak is repaired and system recharged.
CRANKCASE HEATER is connected across line side of contactor and operates continuously.
The purpose of the heater is to keep the crankcase warm during the off cycle and thus prevent dilution of the oil with refrigerant. This assures good lubri
cation and prevents loss of oil from crankcase during start-up.
To energize crankcase heater, turn thermostat to
OFF position and close electrical disconnect to heat
pump.
If the electrical disconnect switch to the outside unit has been off for an extended period of time, the crankcase heater should be energized for 24 hours before starting the compressor.
DEFROST CONTROL, consisting of defrost
control board and defrost thermostat, interrupts
normal system heating operation every 90 minutes
to defrost outdoor coil, if the coil saturated suc
tion temperature indicates freezing temperatures. Defrost control simultaneously stops outdoor fan, energizes reversing valve solenoid to return system to cooling cycle (outdoor unit as condenser, indoor unit as evaporator), and activates accessory electric heater.
For the heat pump to defrost, 2 conditions are necessary:
1. Defrost timer contacts must be closed.
2. Refrigerant temperature from outdoor unit must be cold enough to cause defrost thermostat con tacts to close. Contacts close at 31 (± 4) F
(-.5 ± 2.2 C).
Every 90 minutes of elapsed running time, the de frost timer contacts close for 10 seconds. If the defrost thermostat contacts are closed, the unit defrosts. The defrost timer limits defrosting period to 10 minutes. Normally, the frost is removed and
the defrost thermostat contacts open to terminate defrosting before 10 minutes have elapsed. Defrost thermostat contacts open at 80 (± 6)F(26.7± 3.3 C) liquid refrigerant temperature. When defrosting is terminated, the outdoor fan motor is energized and reversing valve solenoid is de-energized, returning unit to heating cycle.
HEAT PUMP CIRCUITS shown in Fig. 6 are re
frigerant flow diagrams for heating and cooling
cycles.
AccuRater™ (Bypass Type) Servicing — See
Fig. 18 for bypass type AccuRater components. The piston has a refrigerant metering hole thru it. The retainer forms a stop for the piston in the refrigerant
Fig. 18 — AccuRater™ (Bypass Type)
Components
bypass mode, and a sealing surface for liquid line
flare connection. To check, clean or replace piston:
1. Shut off power to unit.
2. Pump unit down using Pumpdown Procedure described previously.
3. Remove liquid line flare connection from AccuRater.
4. Pull retainer out of body, being careful not to scratch flare sealing surface. If retainer does not pull out easily, carefully use Vise Grip pliers to remove retainer.
5. Slide piston out by inserting a small soft wire, with small kinks, thru metering hole. Ensure metering hole, sealing surface around piston cones and fluted portion of piston are not damaged.
6. Clean piston refrigerant metering hole.
7. Replace retainer O-ring before reassembling bypass type AccuRater. Carrier O-ring part no. is 99CC501052.
LIQUID LINE STRAINER (protects AccuRater) made of wire mesh is located in the liquid line inside 38QB unit behind liquid line service valve. Liquid line is belled and sweat connected where strainer is lo cated . If strainer is plugged, unsweat belled liquid line
connection and replace strainer. See Fig. 7.
Compatible Fitting Repair
LEAKING MECHANICAL CONNECTION — Frontseat outdoor section service valves after reliev
ing refrigerant pressure in system. Back locknut off
Carrier Compatible Fitting onto tube. Cut fitting
between threads and O-ring shown in Fig. 19.
Fig. 19 — Carrier Compatible Fitting
13
Page 14
Remove tubing section remaining in threaded
portion of fitting. Discard locknut.
Clean, flux, and insert new tube end into remain ing portion of Carrier Compatible Fitting. Wrap valve base in wet rag. Heat and apply low-
temperature solder (430 F [221 C]).
LEAK SWEAT CONNECTION — Frontseat service valves and relieve refrigerant pressure in tubing. Clean and flux area around leak and apply low-temperature solder (430 F [221 C]).

Condenser Fan Motor Removal

1. Shut off power to unit. Failure to do so may result in electric shock or injury from rotating fan blade.
2. Remove top cover as described on page 3.
3. Disconnect fan motor leads from controls.
4. Remove 6 screws holding fan motor/discharge grille in place and lift assembly from unit.
5. Remove Carrier nameplate by straightening tabs.
6. Remove 4 nuts holding fan motor to discharge grille. Remove motor and leads.
7. Reverse procedure for reassembly. Before replac
ing metal fan, be sure rain shield is in place on motor shaft. Seal with Permagum around hub to
prevent entry of water between hub and shaft.
Make sure fan is positioned correctly as shown
in Fig. 20.
Fig, 20 — Condenser Fan Position

MAINTENANCE

b. Every 3 years when environment is reasonably
clean, ambient temperature is less than 105 F and unit operating time averages 8 to 15 hours a day.
c. Every 5 years when environment is clean,
ambient temperature is less than 105 F and unit operating time averages less than 8 hours a day.
COMPRESSOR contains factory oil charge. If oil requires replenishment, see Table? for oil recharge and Carrier Standard Service Techniques Manual, Chapter 1, Refrigerants, page 1-21, for instruc tions. Use Carrier PP33-1, Texaco Capella B or Suniso 3G oil.
Coil Cleaning to be done at the beginning of
each cooling season or more often if required.
1. Shut off power to unit.
2. Remove louvered casing by taking out 16 screws securing it to the cabinet and sliding it away from the coil.
3. Clean coil using vacuum cleaner and its crevice
tool (see Fig. 21). Work crevice tool vertically
making sure tool only touches dirt on fins. To prevent fin removal, do not “scrub” fins with
tool or move tool horizontally.
4. If oil deposits are present, spray coil with house hold detergent (Fantastic, Lestoil, 409, or any
similar type). Wait 10 minutes then proceed to
step 5.
5. Using garden hose, spray coil vertically down ward with a constant stream of water at moderate pressure (see Fig. 22). Keep nozzle at a 15 to 20 degree angle, about 3 in. (76 mm) from coil face and 18 in. (457 mm) from tube. Spray so debris is washed out and away from coil.
6. Reinstall louvered casing being careful not to damage coil.
7. Restore power to unit.
f

Lubrication

FAN MOTOR BEARINGS — Oiling holes are provided at each end of condenser fan motor. Re move fan motor and lubricate motor with 32 drops
(16 drops per hole) of SAE-10 nondetergent oil at
intervals described below. a. Annually, when environment is very dirty,
ambient temperature is higher than 105 F, and
average unit operating time exceeds 15 hours
a day.
c.
Fig. 21 — Crevice Cleaning Tool
14
Page 15
Fig. 22 — Positioning Hose to Spray Coil
15
n
Page 16
Os
TROUBLESHOOTING CHART — COOLING CYCLE
Page 17
TROUBLESHOOTING CHART — HEATING CYCLE
Page 18
For replacement items use Carrier Specified Parts.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book
Tab
4
1
5a 5a
Form 38QB-1 SIM New
Printed in U.S A
2-82 PC 101
Catalog No 563-807
Loading...