Carrier 30XW150-400 User Manual

4 (1)
AQUAFORCE
30XW150-400
Water-Cooled Liquid Chillers
Controls, Start-Up, Operation, Service
and Troubleshooting
®
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 2
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Display Module Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
• TOUCH PILOT™ DISPLAY
• NAVIGATOR™ DISPLAY MODULE
CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-18
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Main Base Board (MBB) . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Compressor Protection Module (CPM) . . . . . . . . . . 10
Electronic Expansion Valve (EXV) Board . . . . . . . . 13
MLV/Condenser Board . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Enable-Off-Remote Contact Switch (SW1). . . . . . . 16
Emergency On/Off Switch (SW2) . . . . . . . . . . . . . . . . 16
Energy Management Module (EMM) . . . . . . . . . . . . . 16
Local Equipment Network. . . . . . . . . . . . . . . . . . . . . . . 17
Board Addresses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Touch Pilot Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Control Module Communication. . . . . . . . . . . . . . . . . 17
•RED LED
• GREEN LED
• YELLOW LED
Carrier Comfort Network
Remote Alarm and Alert Relays . . . . . . . . . . . . . . . . . 18
CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18-46
Touch Pilot Operation Configuration Tables. . . . . 18
Machine Control Methods . . . . . . . . . . . . . . . . . . . . . . . 20
Machine On/Off Control . . . . . . . . . . . . . . . . . . . . . . . . . 20
• TOUCH PILOT MACHINE CONTROL
• NAVIGATOR DISPLAY MACHINE CONTROL
Cooling Set Point Selection . . . . . . . . . . . . . . . . . . . . . 25
• SET POINT OCCUPANCY
Chilled Water Fluid Type Selection . . . . . . . . . . . . . . 27
• FRESH WATER
• BRINE OR GLYCOL OPERATION
Cooler Pump Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
• COOLER PUMP CONTROL CONFIRGURATIONS
Machine Start Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Circuit/Compressor Staging and Loading . . . . . . . 29
• CIRCUIT/COMPRESSOR STAGING
• CIRCUIT/COMPRESSOR LOADING
Minimum Load Control . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Dual Chiller Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
• DUAL CHILLER CONTROL FOR PARALLEL APPLICATIONS
• DUAL CHILLER PUMP CONTROL FOR PARALLEL CHILLER APPLICATIONS
• DUAL CHILLER CONTROL FOR SERIES APPLICATIONS
• DUAL CHILLER PUMP CONTROL FOR SERIES CHILLER APPLICATIONS
®
(CCN) Interface. . . . . . . 18
Page
Ramp Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Temperature Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
• RETURN WATER RESET
• SPACE TEMPERATURE RESET
• 4-20 mA TEMPERATURE RESET
Demand Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
• SWITCH CONTROLLED DEMAND LIMIT
• EXTERNALLY POWERED CAPACITY BASED DEMAND LIMIT
• EXTERNALLY POWERED CURRENT BASED DEMAND LIMIT
• CCN LOADSHED CONTROLLED DEMAND LIMIT
Ice Storage Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Broadcast Configuration . . . . . . . . . . . . . . . . . . . . . . . . 41
•ACTIVATE
• BROADCAST ACKNOWLEDGER
Alarm Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
• ALARM ROUTING CONTROL
• ALARM EQUIPMENT PRIORITY
• COMMUNICATION FAILURE RETRY TIME
• RE-ALARM TIME
• ALARM SYSTEM NAME
Daylight Saving Time Configuration. . . . . . . . . . . . . 43
Head Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . . . 46
• LOW CONDENSER FLUID TEMPERATURE HEAD PRESSURE CONTROL OPTION
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46,47
System Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47-53
Actual Start-Up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Operating Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
• TEMPERATURES
•VOLTAGE
• MINIMUM FLUID LOOP VOLUME
• FLOW RATE REQUIREMENTS
OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54-59
Sequence of Operation. . . . . . . . . . . . . . . . . . . . . . . . . . 54
Dual Chiller Sequence of Operation . . . . . . . . . . . . . 54
•PUMP OPERATION
Operating Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
• THERMISTORS
• TRANSDUCERS
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59-67
Economizer Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Electronic Expansion Valve (EXV) . . . . . . . . . . . . . . . 59
• MAIN EXV CONTROL
• ECONOMIZER EXV CONTROL
• EXV TROUBLESHOOTING PROCEDURE
Compressor Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . 63
• COMPRESSOR OIL SYSTEM
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300024-01 Printed in U.S.A. Form 30XW-1T Pg 1 11-09 Replaces: New
CONTENTS (cont)
Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
• SUCTION SERVICE VALVE
• LOW FLUID TEMPERATURE
• LOSS OF FLUID FLOW PROTECTION
• TUBE PLUGGING
•RETUBING
• TIGHTENING COOLER HEAD BOLTS
• INSPECTING/CLEANING HEAT EXHANGERS
• WATER TREATMENT
• CHILLED WATER FLOW SWITCH
Refrigerant Circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
• LEAK TESTING
• REFRIGERANT CHARGE
Safety Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
• COMPRESSOR PROTECTION
• COOLER PROTECTION
Relief Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
• PRESSURE RELIEF VALVES
MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Recommended Maintenance Schedule . . . . . . . . . . 67
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . 67-85
Alarms and Alerts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
• DIAGNOSTIC ALARM CODES AND POSSIBLE CAUSES
Service Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
APPENDIX A — TOUCH PILOT™
DISPLAY TABLES . . . . . . . . . . . . . . . . . . . . . . . . . . 86-104
APPENDIX B — NAVIGATOR™ DISPLAY
TAB LE S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105-117
APPENDIX C — CCN TABLES . . . . . . . . . . . . . . 118-132
APPENDIX D — 30XW150-400 CPM
DIP SWITCH ADDRESSES. . . . . . . . . . . . . . . . 133,134
APPENDIX E — PIPING AND
INSTRUMENTATION . . . . . . . . . . . . . . . . . . . . . . 135, 136
APPENDIX F — GLOBAL TIME SCHEDULE
CONFIGURATION FOR i-Vu
CONTROLLER . . . . . . . . . . . . . . . . . . . . . . . . . . . 137-139
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
START-UP CHECKLIST
FOR 30XW LIQUID CHILLERS . . . . . . . . CL-1 to CL-7
®
DEVICE AND CSM
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be hazardous due to system pressures, electrical components, and equipment location. Only trained, qualified installers and ser­vice technicians should install, start up, and service this equip­ment. When working on this equipment, observe precautions in the literature, on tags, stickers, and labels attached to the equip­ment, and any other safety precautions that apply. Follow all safety codes. Wear safety glasses and work gloves. Use care in handling, rigging, and setting this equipment, and in handling all electrical components.
WARNING
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation and ser­vice. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.
WARNING
DO NOT VENT refrigerant relief valves within a building. Outlet from relief valves must be vented in accordance with the latest edition of ANSI/ASHRAE (American National Standards Institute/American Society of Heating, Refrigerating and Air Conditioning Engineers) 15 (Safety Code for Mechanical Refrigeration). The accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation. Provide adequate ventilation in enclosed or low overhead areas. Inhalation of high concen­trations of vapor is harmful and may cause heart irregulari­ties, unconsciousness or death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen avail­able for breathing. Product causes eye and skin irritation. Decomposition products are hazardous.
WARNING
DO NOT attempt to unbraze factory joints when servicing this equipment. Compressor oil is flammable and there is no way to detect how much oil may be in any of the refrig­erant lines. Cut lines with a tubing cutter as required when performing service. Use a pan to catch any oil that may come out of the lines and as a gage for how much oil to add to system. DO NOT re-use compressor oil.
CAUTION
This unit uses a microprocessor-based electronic control system. Do not use jumpers or other tools to short out components, or to bypass or otherwise depart from rec­ommended procedures. Any short-to-ground of the con­trol board or accompanying wiring may destroy the electronic modules or electrical components.
CAUTION
To prevent potential damage to heat exchanger tubes, always run fluid through heat exchanger when adding or removing refrigerant charge. Use appropriate antifreeze solutions in evaporator and condenser fluid loops to pre­vent the freezing of heat exchangers or interconnecting pip­ing when the equipment is exposed to temperatures below 32 F (0° C). Proof of flow switch is factory installed on all models. Do NOT remove power from this chiller during winter shut down periods without taking precaution to remove all water from heat exchangers. Failure to properly protect the system from freezing may constitute abuse and may void warranty.
CAUTION
Compressors require specific rotation. Swap any two incoming power leads to correct compressor rotation.
2
ENTER
ESCAPE
ENTER
ALARM INDICATOR
LIGHT STA RT- STOP BUTTON
LCD TOUCH SCREEN
Fig. 1 — Touch Pilot™ Display
a30-4456 (b&w)
GENERAL
This publication contains controls, operation, start-up, ser­vice and troubleshooting information for the 30XW150-400 water-cooled liquid chillers with electronic controls. The 30XW chillers are equipped with ComfortLink™ controls and electronic expansion valves. The AquaForce
®
30XW chillers offer two different user interface devices, the Touch Pilot™ display and the Navigator ™ display.
Conventions Used in This Manual — The follow-
ing conventions for discussing configuration points for the Navigator module and Touch Pilot display will be used in this manual.
Point names for the Touch Pilot display will be shown in bold. See Appendix A for a complete list of point names. Item names for the Navigator module will be shown in bold italics. See Appendix B for the complete path name preceding the item name. The point and item names in Appendices A and B will be listed in alphabetical order and the path name for each will be written with the mode name first, then any sub-modes, each separated by an arrow symbol ( .
This path name will show the user how to navigate through the Navigator module or the Touch Pilot display to reach the desired configuration. The user would scroll through the modes and sub­modes using the and keys on the Navigator display. For the Touch Pilot display, the user would simply touch the menu item on the screen. The arrow symbol in the path name represents pressing to move into the next level of the menu struc­ture for the Navigator module, or touching the menu item on the screen for the Touch Pilot display.
When a value is included as part of the point name, it will be shown after the point name after an equals sign. If the value represents a configuration setting, an explanation will be shown in parentheses after the value. The Touch Pilot name will be shown first with the Navigator name following. As an example, (Staged Loading Sequence = 1, LLCS = Circuit A leads).
Press the and keys simultaneously on the Navigator module to display an expanded text description of the point name or value. The expanded description is shown in the Navigator display tables (Appendix B) but will not be shown with the path names in text. The Touch Pilot display will show an ex­panded description of the point name. To view the expanded point name for the Touch Pilot display go to Appendix A.
The Touch Pilot display configures the unit via the CCN (Carrier Comfort Network
®
) Tables, which are located in Ap-
pendix C of this manual.
Display Module Usage
TOUCH PILOT DISPLAY — The Touch Pilot display is the standard user interface for the AquaForce 30XW chillers with the ComfortLink control system. The display includes a large LCD (liquid crystal display) touch screen for display and user configuration, a Start/Stop button, and an Alarm Indicator LED (light-emitting diode). See Fig. 1.
The Touch Pilot display can be used to access various Carrier Comfort Network circumstances, contact your Carrier representative.
Operation of the Touch Pilot display is driven from the displays on the touch screen. The Touch Pilot display uses the following screen “buttons” to allow the user to operate the dis­play and navigate within and between screens.
“BACK” returns to the next higher screen in the hierarchy.
®
devices. For operation under these
“HOME” displays the Default Group Display screen
for Touch Pilot display. The Default Screen is a user­configured display of up to 9 points on each of 8 screens. This allows for quick access to various, frequently viewed points, without navigating through the Main Menu structure. This but­ton is available at all menu levels and returns the user to the first Default Group Display screen.
“MAIN MENU” displays the Main Menu screen. This
allows access for viewing and configuration, where possible, of all points supported by the controller. This includes points such as set point and operational configuration. This button is available at all menu levels and returns the user to the Main Menu screen.
“PREVIOUS” moves the user to the next earlier
screen in a group of sequential screens of the same type.
“NEXT” advances the user to the next screen in a
group of sequential screens of the same type.
“OK” agrees with, or says “yes” to a prompt and per-
forms the appropriate processing.
“NO” rejects, or says “no” to a prompt and performs
the appropriate processing.
“CANCEL” terminates an ongoing action and returns
to the current screen without any other processing.
“CLEAR DATA” clears the data value in a data entry
dialog box. This button is used to clear incorrect data.
“RESET DATA” zeros the data value in a data entry
dialog box.
“ADD” adds the active point to a Group Display
screen.
“REMOVE” deletes a point from a Group Display
screen.
“INCREASE” modifies the value of a field within its
defined limits or “SCROLL UP” and shifts the screen view up by one item.
“DECREASE” modifies the value of a field within its
defined limits or “SCROLL DOWN” and shifts the screen view down by one item.
“PAGE DOWN” will replace the items currently on
the screen with the next group of items if the current table or list has more data than will fit on the screen.
“PAGE UP” will replace the items currently on the
screen with the previous group of items if the current table or list has more data than will fit on the screen.
“FORCE” begins the process of forcing or overriding
the value of a point.
“AUTO” begins the process of removing a force from
a point.
“MODIFY” begins the process of modifying a config-
uration value.
3
“ALARM INDICATOR LIGHT” activates when a
Fig. 2 — Group Display Screen
Fig. 3 — Point Data Dialog Box
Fig. 4 — Main Menu Display
a30-4910.ep
a30-4471
a30-4472
PDS-XAXQXWPDS-XAXQXW
new alarm condition occurs. The alarm indicator light
LED, located on the right side of the display, remains activated until it is manually reset using the Reset button on the Main menu.
“START/STOP BUTTON” enables the user to start
or stop the chiller from the Touch Pilot™ display.
See Enable-Off-Remote Contact Switch (SW1) on page 16 for additional information.
Several items are password protected. When required, a Password dialog box will be displayed for field input of the password. The default password is 3333. The password can be changed if desired.
Power-Up Display
— When the Touch Pilot display is pow­ered up, it displays an initialization progress bar and attaches (initiates communication) to the Main Base Board. The Touch Pilot display then shows that controller’s default Group Dis­play screen. See Fig. 2. This is a user-configured display screen with up to 9 points on 8 separate screens. For more information on adding or removing points from the Group Display screen, see the Group Display Screens section on page 7.
Touch any of the screen point buttons and Point Data Dialog box will be displayed with expanded information. In the exam­ple shown, the CTRL_PNT button in the bottom left corner was selected. See Fig. 2 and 3.
To exit the box, press . Main Menu Display
— The default screen for the Touch Pilot controller is the Group Display screen. To access the Main Menu, press the button. The screen shown in Fig. 4 will be displayed. Selecting a button will display the screens associat­ed with that category. The user can also access the login screen from the Main Menu if needed.
Touch Pilot Menu Structure
— The user can navigate through the Touch Pilot display screens by selecting the buttons that ap­pear on the screen. When a button is selected, either a sub­menu or a list of point names and values will be shown. Sub­menus will display a list of associated point names. See Fig. 5 for the Touch Pilot menu structure.
If the list of point names and values are shown, the top line of the display is the table name. The line and total line counter is displayed in the upper right corner of the display. Selecting an item will cause a Point Data dialog box to appear.
Setup Menu Screen
— The Setup Menu screen, shown in Fig. 6, is accessed by pressing the Setup button from the Main Menu. This configuration allows the user to configure the basic operation and look of the display. Table 1 summarizes the Set­up Menu functions.
4
User interface
Group display x 8 Main menu
Status
GENUNIT
CIRCA_AN
CIRCA_D
CIRCB_AN
CIRCB_D
CIRCC_D
CIRCC_AN
STATEGEN
RECLAIM
MODES
STRTHOUR
FANHOURS
FREECOOL
QCK_TST1
QCK_TST2
SERV_TST
Setpoint Schedule
OCC1PO1S
OCC2PO2S
Service
FACTORY
FACTORY2
SERVICE1
CP_UNABL
UPDTHOUR
UPDHRFAN
MAINTCFG
Maint
LOADFACT
FANCTRL
M_MSTSLV
DEFROSTM
LAST_POR
PR_LIMIT
BOARD_PN
SERMAINT
EXV_CTRL
CUR_PHAS
OCCDEFCFM
Config
Ctrl-ID
DISPCONF
USER
MST_SLV
CFG_TAB1
CFG_TAB8
BRODEFS
OCCDEFCS
HOLIDAY
ALARMDEF
Alarms
ALARHIST
ALARHIS2
ALAM_CUR
Reset Time Attach Setup
Regional
Language
Contrast
Backlight
Calibrate
Password
Display
CCN
Login
Fig. 5 — Touch Pilot™ Display Menu Structure
a30-4829
5
Table 1 — Setup Menu
Fig. 6 — Setup Menu Display
a30-4474
SETUP MENU BUTTON FUNCTION
This button specifies the time and date format and the base unit of measure. Time display can be configured as
REGIONAL
LANGUAGE
CONTRAST
BACKLIGHT This button specifies whether backlighting should be kept on at all times or turned off during inactive periods.
CALIBRATE
PASSWORDS
DISPLAY
CCN This button is used to configure the bus and element numbers and the baud rate of the control on the network.
12-hour AM/PM setting or as a 24-hour setting. The date can be formatted in one of 3 settings, MM-DD-YYYY (Month­Day-Year), DD-MM-YYYY (Day-Month-Year), or YYYY-MM-DD (Year-Month-Day). Units of measure can be either US (English) or Metric (SI).
This button selects the active language and font of the display. Available languages are English and Spanish (Espanol). If a preferred language is not available, additional software for the Main Base Board (MBB) and the Touch Pilot™ dis­play are required. Contact your Carrier representative for instructions and software.
This button adjusts the LCD contrast. Press and hold the [MOON] button to increase/darken the contrast or the [STAR] button to decrease/lighten the current contrast. NOTE: Touching the screen anywhere for 5 seconds while powering-up will prompt the user to restore contrast and calibration settings to factory defaults.
This button is used to adjust the LCD touch screen calibration. Touch the screen in the circular targets located first in the upper left and then in the lower right corner of the screen to adjust.
This button is used to configure the limited and full logged-in access system passwords. In order to change passwords, the user must be logged in with full access to view and change the passwords. All passwords must consist of 4-digits, which can be entered using the numeric keypad. Access levels and associated privileges are as follows:
Limited Logged-in Access - Provides the user with read/write access to all available tables (except service configura­tion tables, where the user will not be permitted to modify point data, and Group Display tables, where the user will not be permitted to add points.) This access level also provides read/write access to all Touch Pilot display setup properties except Display, CCN, and Password.
Full Logged-in Access - Provides user with read/write access to all available tables for the attached device and all Touch Pilot display properties.
If the user does not log in, read-only access to all tables is allowed. The user will be prompted to log in when attempting to access password-required functions.
This button is used to view the description data and part number from the Ctlr-ID Table and to specify the Operating Mode. The Operating mode can be configured for Equipment mode or Network mode. For Touch Pilot displays that are standard with the unit, Operating mode should not be changed from Equipment mode. Equipment mode provides access only to the chiller’s MBB via the Local Equipment Network (LEN) Bus. For remote access, a remote Touch Pilot display can be set to Network mode. Network mode provides access to all devices on the CCN (Carrier Comfort Net-
®
work
) bus.
NOTE: When changing the operating mode, a power cycle is required in order for the new operating mode to take effect. The user should view and correct the following CCN data: address and baud rate, alarm acknowledger, and broadcast acknowledger designation.
6
Setting the Time and Date
ENTER
ESCAPE
ESCAPE
ENTER
ESCAPE
ENTER
ESCAPE
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
— The ComfortLink™ control has a time and date function. This can be useful for diagnostics to determine when alarms occur. The control is factory config­ured for the proper date and is set for the Eastern Time Zone. The date and time zone must be checked and corrected if nec­essary, to allow the machine to function on an internal time schedule and to display a proper time and date stamp for alarms. The time and date is displayed on the Group Display Screen.
To change the Time and Date, press the Main Menu
button. Select Time. On the display, a day and date box
with a time box will be shown. To change the day and date,
press the day and date box. A calendar will be displayed. If the
correct month is displayed, touch the correct date. If the wrong
month is displayed, use the or to change to the correct
month and select the correct date. The date will highlighted.
Press to accept the change. The previous screen will be
displayed with the corrected day and date shown. To correct
the time, use the or on the left to change the hour. Use
touching the or will sequence the numbers. The time is
shown in a 24-hour format. To accept the changes, press the
or buttons. A “Save” dialog box is displayed with the
words, “Do you wish to save changes?” Press to accept
the changes.
Group Display Screens
— The Touch Pilot™ display sup­ports up to eight Group Display screens. Group Display screens show status information along the top of the screens and 9 buttons that display 9 point names and point values that are chosen by the user. All Group Display screen points are user configurable. The bottom line of the screen contains navi­gation buttons that can be used to move between the Group Display screens.
Pressing a point button will show that point’s Point Data dialog box. See Fig. 2 and 3. This box contains buttons that remove the point from the group display and apply or remove a force (point override). When touching any button in the display screen, the button will be outlined to acknowledge input. There may be a delay in response to input, but if the button is out­lined, do NOT press any other button until the previous input has been processed.
If there is a communication failure with the MBB (Main Base Board), all point buttons will be displayed in inverse vid­eo and the message Communication Failure will be displayed in the top left line of the screen.
Default Group Designation — The default group is the first of the 8 Group Display screens. This is the default screen of the display. Information on this screen as well as the other 7 screens can be user-modified to meet the needs of the site.
To Add A Point To A Group Display — From the Main Menu, press the desired menu button (Status, Setpoint, Service, Maint, or Config) and, if necessary, the sub-menu button to access the point to be added. Press the point button to show the source point’s Point Data dialog box. See Fig. 3. From the Point Data dialog box, press the ADD button. The display will show the last Group Display accessed. Use the navigation but­tons to access the destination Group Display. Press an existing point button or a blank button to update the highlighted button with the source point’s name. Press to add the highlighted point to the group and return to the table display.
To Remove A Point From A Group Display — From the Point Data Dialog box, press the REMOVE button and follow the prompts. The display will return to the Group Display screen from which the point was removed, and the button correspond­ing to the deleted point will be blank and disabled.
NAVIGATOR™ DISPLAY MODULE — The Navigator dis­play module provides a mobile user interface to the ComfortLink control system. The display has up and down ar­row keys, an key, and an key. These keys are used to navigate through the different levels of the display structure. Press the key until ‘Select a Menu Item’ is displayed. Use the up and down arrow keys to move through the top 11 mode levels indicated by LEDs on the left side of the display. See Fig. 7. See Table 2 and Appendix B for more de­tails about the display menu structure.
Once within a mode or sub-mode, a “>” indicates the
currently selected item on the display screen. Pressing the
and keys simultaneously will put the Navigator module into expanded text mode where the full meaning of all sub-modes, items, and their values can be dis­played. Pressing the and keys when the display says ‘Select Menu Item’ (Mode LED level) will return the Navigator module to its default menu of rotating display items (those items in Run StatusVIEW). In addition, the password will be disabled, requiring that it be entered again be­fore changes can be made to password protected items. Press the key to exit out of the expanded text mode.
When a specific item is located, the item name appears on the left of the display, the value will appear near the middle of the display and the units (if any) will appear on the far right of the display. Press the key at a changeable item and the value will begin to flash. Use the up and down arrow keys to change the value, and confirm the value by pressing the
key.
Changing item values or testing outputs is accomplished in the same manner. Locate and display the desired item. Press
so that the item value flashes. Use the arrow keys to change the value or state and press the key to accept it. Press the key to return to the next higher level of structure. Repeat the process as required for other items.
Items in the Configuration and Service Test modes are pass­word protected. The words Enter Password will be displayed when required, with 1111 also being displayed. The default password is 0111. Use the arrow keys to change each number and press to accept the digit. Continue with the remaining digits of the password. The password can only be changed through CCN operator interface software such as ComfortWORKS
Power-Up Display
®
, ComfortVIEW™ and Service Tool.
— When the Navigator display is powered
up it will display:
ComfortLink
Navigator
By
Carrier
7
This indicates an initialization period while the Navigator™
ENTER
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER
ENTER
Run Status
Service Test
Temperatures
Pressures
Setpoints
Inputs
Outputs
Configuration
Time Clock
Operating Modes
Alarms
ENTER
ESC
MODE
Alarm Status
Comfort
Link
Fig. 7 — Navigator Display Module
a30-3924
display initiates communication with the Main Base Board. Once communication is established, the default rotating dis­play will be shown. If communication is not established, the Navigator module will display:
Communication
Failure
If the Navigator module is connected to a Main Base Board without software loaded, the display will remain at the powered-up initialization display.
Setting the Time and Date
— The ComfortLink control has a time and date function. This can be useful for diagnostics to de­termine when alarms occur. The control is factory configured for the proper date and for use in the Eastern Time Zone. The control must be checked and corrected if necessary. The correct time is important if the machine is to function on an internal time schedule and display a proper time and date stamp for alarms. The time and date will be displayed on the default ro­tating display of the Navigator module. The time and date can also be checked and changed under the Time Clock mode as described below.
ITEM ITEM EXPANSION PATH VALUE
HH.MM Time of Day Time Clock TIME XX.XX
To change the time, press the arrow key to move to the cor­rect hour and press . The minutes can be changed in a similar manner.
To check or change the date, the following items must be checked and changed if necessary.
ITEM ITEM EXPANSION PATH VALUE MNTH Month of Year Time Clock DATE WW DOM Day of Month Time Clock DATE XX DAY Day of Week Time Clock DATE YY YEAR Year of Century Time Clock DATE ZZ
NOTE: WW is the current month of the controller, (01=January,
02=February, etc.). XX is the current day of the month YY is the day of the week, (01=Monday, 02-Tuesday, etc.) ZZ is the year of the century, (06=2006, 07=2007)
Changing the Unit of Measure — The Navigator display has two options for unit of measure on the display, English or SI (metric). The factory default for the units of measure is English. To change the unit of measure, the following item must be changed.
Adjusting the Contrast
— The contrast of the display can be adjusted to suit ambient conditions. To adjust the contrast, enter the LED Test mode of the device.
ITEM ITEM EXPANSION PATH VALUE
TEST Test Display LEDs Configuration DISP
Pressing will access the TEST point. Pressing
again will cause the “OFF” to flash. Use the up or down arrow to change “OFF” to “ON.” Pressing will illuminate all LEDs and display all pixels in the view screen. Pressing and simultaneously allows the user to adjust the display contrast. The display will read:
Adjust Contrast
- - - -+ - - - - - - - - - - - - - - ­Use the up or down arrows to adjust the contrast. The
screen’s contrast will change with the adjustment. Press
to accept the change. The Navigator module will keep this setting as long as it is plugged in to the LEN (Local Equipment Network) bus.
Adjusting the Backlight Brightness
— The backlight of the display can be adjusted to suit ambient conditions. The factory default is set to the highest level. To adjust the backlight of the Navigator module, enter the LED Test mode of the device.
ITEM ITEM EXPANSION PATH VALUE TEST Test Display LED’s Configuration Mode DISP
Pressing will access the TEST point. Pressing
again will cause the “OFF” to flash. Use the up or down arrow to change “OFF” to “ON.” Pressing will illuminate all LEDs and display all pixels in the view screen. Pressing the up and down arrow keys simultaneously allows the user to adjust the display brightness. The display will read:
Adjust Brightness
- - - - - - - - - - - - - - - - - +
Use the up or down arrow keys to adjust screen brightness. Press to accept the change. The Navigator module will keep this setting as long as it is plugged in to the LEN bus.
ITEM ITEM EXPANSION PATH VALUE
METR Metric Display Configuration DISP
Changing the Display Language
— The Navigator display
OFF – English ON – SI (Metric)
has five language options to select from, English, Espanol, Francais, Portugues, and Translated. The “Translated” option is not supported at this time. The factory default language is English. To change the display language, the following item must be changed.
ITEM ITEM EXPANSION PATH VALUE
LANG Language Selection Configuration DISP
NOTE: When the Language Selection (Configuration
English Espanol Francais Portugues Translated
DISP LANG) variable is changed, all appropriate display expansions will immediately change to the new language. The four letter/digit code will not change. No power-off or control reset is required when reconfiguring languages.
8
RUN
221
221
221
221
195
195
195
195
195
195
195
CH1 CH2 CH3
CH4
CH11 CH12
LOCATION OF SERIAL NUMBER
CH13
CH14
CH 15A
J4
ANALOG
INPUTS
J3
J2C
J2B
24 VAC
J1A
+ G –
DISCRETE
INPUTS
J5A
CH
15a
11
C16
J2A
TR1 TR2 TR3 TR4 TR5
CH19 CH20 CH21 CH22 CH23 CH24 CH25 CH26
J8
CH17
CH18
J5B
J5C
THERMISERS PRESSURES
CH5
CH6 CH7 CH8
CH9
J7A J7B
J7C
J7D
RELAY
OUTPUTS
MOV1
C41
C42 C43
C32
C33
C34
C35
12/11
12/11
J10
LEN
+ G -
STATUS
J9A
K1
K2
D15
J6
CCN
CH10
+ G –
SIO
(LEN)
J9C
J9B
+ G –
LEN
LEN
CCN J13 J9D
+C+CCH
16a+CCH16b
Fig. 8 — Main Base Board
a30-4255
STATUS
Auto Display
(VIEW)
Machine
Starts/Hours
(RUN)
Compressor
Run Hours
(HOUR)
Compressor
Starts
(STRT)
Fan Run
Hours
(FAN)
Compressor
Disable
(CP.UN)
Predictive
Maintenance
(MAIN)
Software Versions
(VERS)
SERVICE
TEST
Manual
Test Mode
(TEST)
Quick
Test Mode
(QUIC)
Table 2 — ComfortLink™ Navigator™ Display Menu Structure
MODE
TEMPERATURES PRESSURES
Unit
Temperatures
(UNIT)
Circuit A
Temperatures
(CIR.A)
Circuit B
Temperatures
(CIR.B)
Circuit C
Temperatures
(CIR.C)
Circuit A
Pressures
(PRC.A) Circuit B
Pressures
(PRC.B) Circuit C
Pressures
(PRC.C)
SET
POINTS
Cooling
Setpoints
(COOL) Heating
Setpoints
(HEAT)
Misc.
Setpoints
(MISC)
INPUTS OUTPUTS CONFIGURATION
General
Inputs
(GEN.I)
Circuit A
Outputs (CIR.A)
Circuit B
Outputs (CIR.B)
Circuit C
Outputs (CIR.C)
General Outputs
(GEN.O)
Display
Configuration
(DISP)
Unit
Configuration
(UNIT)
Service
Configurations
(SERV) Options
Configuration
(OPTN)
Reset,
Demand Limit,
Master/Slave
(RSET)
TIME
CLOCK
Time of Day
(TIME)
Day, Date
(DATE)
Schedule 1
(SCH1)
Schedule 2
(SCH2)
Holidays
(HOLI)
Service
Maintenance
Configuration
(MCFG)
OPERATING
MODES
Operating
Control Type
(SLCT)
Operating
Modes
(MODE)
ALARMS
Reset Current
Alarms
(R.ALM)
Current Alarms
(ALRM)
Alarm
History
(H.ALM)
CONTROLS
General —
the ComfortLink™ electronic control system that controls and monitors all operations of the chiller. The control system is composed of several components as listed in the following sec­tions. All machines have a Main Base Board (MBB), Touch Pi­lot™ module or Navigator™ device, electronic expansion valve board (EXV), auxiliary board, Compressor Protection board, Emergency On/Off switch, and an Enable-Off-Remote Contact switch.
The 30XW water-cooled liquid chillers contain
Main Base Board (MBB) — The MBB is the core of
the ComfortLink control system. It contains the major portion
machine. See Fig. 8. The MBB continuously monitors input/ output channel information received from its inputs and from all other modules. The MBB receives inputs from status and feedback switches, pressure transducers and thermistors. The MBB also controls several outputs. Some inputs and outputs that control the chiller are located on other boards, but are transmitted to or from the MBB via the internal communica­tions bus. Information is transmitted between modules via a 3-wire communication bus or LEN (Local Equipment Net­work). The CCN (Carrier Comfort Network
®
) bus is also sup­ported. Connections to both LEN and CCN buses are made at TB3. For a complete description of Main Base Board inputs and outputs and their channel identifications, see Table 3.
of operating software and controls the operation of the
9
Table 3 — Main Base Board Inputs and Outputs
DESCRIPTION INPUT/OUTPUT I/O TYPE DISPLAY MODULE POINT NAME
Power (24 vac supply) ——
Local Equipment Network ——
Carrier Communication
Network
Chilled Water Flow Switch CWFS Switch Cooler Flow Switch, LOCK
Demand Limit Switch No. 1 Demand Limit SW1 Switch Limit Switch 1 Status, DLS1 MBB-J4-CH13
Condenser Flow Switch CDFS Switch Condenser Flow Switch, COND 16A MBB-J5A-CH16A
Circuit A Discharge
Pressure Transducer
Circuit B Discharge
Pressure Transducer
Dual Chiller
LWT Thermistor
Dual Set Point Input Dual Set Point Switch Remote Setpoint Switch, DUAL MBB-J4-CH12
Heat/Cool Switch HC_SW Switch Heat/Cool Select Contact, HC_SW
Entering Water Thermistor EWT 5k Thermistor Cooler Entering Fluid, EWT MBB-J6-CH2
Leaving Water Thermistor LWT 5k Thermistor Cooler Leaving Fluid, LW T MBB-J6-CH1
Condenser Entering Water
Thermistor
Condenser Leaving Water
Thermistor
External Chilled
Water Pump Interlock
Circuit A Suction
Pressure Transducer
Circuit B Suction
Pressure Transducer
Unit Status Remote Contact-Off-Enable Switch On/Off Remote Switch, ONOF MBB-J4-CH11
Alarm Relay ALM R Relay Alarm Relay Output, ALRM MBB-J3-CH24
Alert Relay ALT R Relay Alert Relay Output, ALRT MBB-J3-CH25 Cooler Pump Relay 1 PMP1 Contactor Cooler Pump 1, CPUMP_1 MBB-J2A-CH19 Cooler Pump Relay 2 PMP2 Contactor Cooler Pump 2, CPUMP_2 MBB-J2A-CH20
Condenser Pump Relay CPMP Contactor Condenser Pump, COND_PMP MBB-J2C-CH22
Pump #1 Interlock Pump #2 Interlock
LEGEND
I/O Input or Output LWT — Leaving Water Temperature
——
DPTA Pressure Transducer Discharge Pressure, DP.A
DPTB Pressure Transducer Discharge Pressure, DP.B
DUAL 5k Thermistor CHWS Temperature, CHWS MBB-J6-CH3
CEWT 5k Thermistor Condenser Entering Fluid, CEWT MBB-J6-CH5
CLWT 5k Thermistor Condenser Leaving Fluid, CLWT MBB-J6-CH4
PMPI Switch Electrical Box Interlock, ELEC MBB-J4-CH15A
SPTA Pressure Transducer Suction Pressure, SP.A
SPTB Pressure Transducer Suction Pressure, SP.B
PMP_1 PMP_2
Switch Cooler Pump Run Status, PUMP MBB-J5C-CH18
CONNECTION POINT
Pin Notation
MBB-J1, MBB-J1A,
MBB-J1B 11 24 vac 12 Ground
MBB-J9A, MBB-J9B,
MBB-J9C, MBBJ9D
+ RS485 Port (D+)
G RS485 Port (Gnd)
- RS485 Port (D-) MBB-J12
+ RS485 Port (D+)
G RS485 Port (Gnd)
- RS485 Port (D-)
MBB-J5B-CH17
17
MBB-J7A-CH6
5V +5 vdc Ref.
SSignal R Return
MBB-J7C-CH8
5V +5 vdc Ref.
SSignal R Return
MBB-J4-CH14
MBB-J7B-CH7
5V +5 vdc Ref.
SSignal R Return
MBB-J7D-CH9
5V +5 vdc Ref.
SSignal R Return
Compressor Protection Module (CPM) — There
is one CPM per compressor. See Fig. 9. The device controls the compressor contactors, oil solenoid, and loading/unloading the solenoid. The CPM also monitors the compressor motor tem­perature, high pressure switch, oil level switch, discharge gas temperature, oil pressure transducer, motor current, MTA (must trip amps) setting and economizer pressure transducer (sizes 175,200,350,400 only). The CPM responds to com­mands from the MBB (Main Base Board) and sends the MBB the results of the channels it monitors via the LEN (Local
Equipment Network). The CPM has three DIP switch input banks, Switch 1 (S1), Switch 2 (S2), and Switch 3 (S3). The CPM board DIP switch (S1) configures the board for the type of starter, the location and type of the current transformers and contactor failure instructions. See Table 4 for description of DIP switch 1 (S1) inputs. See Appendix D for DIP switch settings.
10
DIP
Fig. 9 — Compressor Protection Module
a30-4215
SWITCH 2
(S2)
DIP
SWITCH 3
(S3)
SMT
CT1
CT2
CT3
J8
102
J10B
CH04
5
S
PRESS OIL
100K
J10A
CH03
R
5
S
R
PRESS
ECO
TMP
TMP
J9
DG
CH02
R
R
R20
102
102
0N
S3
123 4
MOT
CH01
J11
12
AUX
151
151
151
102
0N
123 45678
S2
0N
S1
123 45678
11
151
151
151
151
102
MTA
40
K
40
K
J2
13CH14
12
CH
CH
151
151 151 151
151
151
151
151
151
102
10
11
CH
151
06
C
CH
LOADERS OLS MOTOR COOLING
2x
151
151
2
561
561
CH
24 VDC/OLL
05
C
CH
HPS
1
2x
561
2
561
620
101
LOCATION OF SERIAL NUMBER
151
151
151
151
J4
100 K
100 K
101
101
101
101
09
CH
SIO
(LEN)
SI0 STATU S
(LEN)
STAT US
SWITCH 1
– G +
3 2 1
DIP
(S1)
J12
– G +
3 2 1
01
J1
J5
08
07
J3
CH
CH
02
Table 4 — DIP Switch 1 (S1) Inputs
DIP SWITCH POSITION FUNCTION SETTING MEANING
1
2, 3
4, 5, 6
7
8 Not Used
The CPM board DIP switch S2 setting determines the must trip amps (MTA) setting. See Appendix D for DIP switch set­tings. The MTA setting which is calculated using the settings S2 must match the MTA setting in the software or an MTA alarm will be generated.
Starter Configuration OFF Across-the-line Start
ON Wye-Delta Start
Current Transformer (CT) Position OFF (2), OFF (3) CT is located in the main line
ON (2), OFF (3) CT is located in the Delta of the motor OFF (2), ON (3) Reserved for future use ON (2), ON (3) Invalid; will cause MTA configuration alarm
Current Transformer (CT) Selection OFF (4), OFF (5), OFF (6) 100A/1V CT1
ON (4), OFF (5), OFF (6) 100A/0.503V CT2 OFF (4), ON (5), OFF (6) 100A/0.16V CT3 ON (4), ON (5), OFF (6) Invalid; will cause MTA configuration alarm OFF (4), OFF (5), ON (6) Invalid; will cause MTA configuration alarm ON (4), OFF (5), ON (6) Invalid; will cause MTA configuration alarm OFF (4), ON (5), ON (6) Invalid; will cause MTA configuration alarm ON (4), ON (5), ON (6) Invalid; will cause MTA configuration alarm
Contactor Failure Action OFF All units should be off
ON Used when Shunt Trip is available in the unit
See below for CPM board DIP switch S3 address informa-
tion. See Table 5 for CPM inputs and outputs.
CPM-A DIP Switch 3 1 2 3 4
Address: OFF OFF OFF OFF
CPM-B DIP Switch 3 1 2 3 4
Address: OFF OFF ON OFF
11
Table 5 — Compressor Protection Module Inputs and Outputs*
DESCRIPTION INPUT/OUTPUT I/O TYPE DISPLAY MODULE POINT NAME
Power (24 vac supply) ——
Local Equipment Network ——
Circuit X High Pressure Switch HPS-X Switch Not available
Oil Level Switch Oil LS X Switch Circuit X Oil Solenoid, OLS.X
Must Trip Amps† MTA (S2) 8-Pin DIP Switch Must Trip Amps, MTA.X
Configuration Switch† S1 8-Pin DIP Switch S1 Config Switch, C.SW.X
Compressor X Motor Temperature MTR-X NTC Thermistor Motor Temperature, CTP.X
Compressor X Discharge Gas Temperature DGT X NTC Thermistor Discharge Gas Temp, DGT.X
Oil Pressure Transducer OPT X Pressure Transducer Oil Pressure, OP.X
Economizer Pressure Transducer
(sizes 175,200,350,400 only)
Compressor Current X Phase A Current Sensor CUR.A
Compressor Current X Phase B Current Sensor CUR.B
Compressor Current X Phase C Current Sensor CUR.C
Compressor X 1M Contactor C X 1M Contactor Compressor Output, CP.X
Compressor X 2M Contactor C X 2M Contactor Not available
Compressor X S Contactor C X S Contactor Not available
Oil Solenoid X Oil solenoid-X Solenoid Oil Solenoid Output, OLS.X
Load Solenoid X Loading Solenoid-X Solenoid Slide Valve 1 Output, SL1.X
Unload Solenoid X Unloading Solenoid-X Solenoid Slide Valve 2 Output, SL2.X
*“X” denotes the circuit, A or B.
†See Appendix D for MTA settings.
EPT X Pressure Transducer Economizer Pressure, ECP.X
CONNECTION POINT
Pin Notation
CPM-X-J1 11 24 vac 12 Ground
CPM-X-JP12 1 RS485 Port (D+) 2 RS485 Port (Gnd) 3 RS485 Port (D-)
CPM-X-J12 1 RS485 Port (D+) 2 RS485 Port (Gnd) 3 RS485 Port (D-)
CPM-X-J7-CH05
1
2
CPM-X-J6-CH06
1
2
CPM-X-J9-CH01
1
2
CPM-X-J9-CH02
1
2
CPM-X-J10B-CH04
5V + 5 vdc ref
S Signal
RReturn
CPM-X-J10A
5V + 5 vdc ref
S Signal
RReturn
CPM-X-J8-CH01
1
2
CPM-X-J8-CH02
1
2
CPM-X-J8-CH3
1
2
CPM-X-J1-CH07 1 2
CPM-X-J2-CH8 1 2
CPM-X-J2-CH9 1 2
CPM-X-J2-CH12 1 2
CPM-X-J2-CH13 1
CPM-X-J2-CH14 1 2
12
1
2
3
4
5
6
7
8
ON
100
100
257-01
712
100K
100K
100
1
2
3
4
5
3
2
1
-
G
+
J3
1
2
3
4
5
J2A EXVA
J2B EXVB
24VAC
STATUS
MOV1
LOCATION OF SERIAL NUMBER
432 1
THA THB
D4
D6
J1
C15
C16
D5
U5
Q2 Q1
L4
U4
12/11
C17
+
Q45
Q42Q37
G2
Q35
Q25
Q27
Q30
Q20
Q22
Q17
Q15
Q12
Q10
C10
Q7
S1
C11
U2
D2
L1
U1
C37C39
SB
D15
U6
C25
C49
Q4
Q5
L2
R2
R3 L3
D1
R9
TEMP
D29
D9 D8
SI0 (LEN)
COMM J4
DIP SWITCH
Fig. 10 — EXV Board
a30-4216
Electronic Expansion Valve (EXV) Board —
The 30XW150-325 units have one EXV board. The 30XW350,400 units have one EXV board per circuit. See Fig. 10. The board is responsible for monitoring the suction gas temperature and economizer gas temperature thermistors. The board also signals the main EXV and economizer EXV (ECEXV) motors to open or close. The electronic expansion valve board responds to commands from the MBB and sends the MBB the results of the channels it monitors via the LEN (Local Equipment Network). See below for DIP switch infor­mation. See Tables 6 and 7 for EXV inputs and outputs.
EXV BOARD 1
(150-400)
123456 7 8
DIP SWITCH
Address: ON ON ON ON ON ON OFF ON
EXV BOARD 2
(350,400)
DIP SWITCH
1 23456 7 8
Address: OFF ON ON ON ON ON OFF ON
13
Table 6 — EXV1 Board Inputs and Outputs (30XW150-325)
DESCRIPTION INPUT/OUTPUT I/O TYPE DISPLAY MODULE POINT NAME
Power (24 vac supply) ——
Local Equipment Network ——
Circuit A Suction Gas Thermistor SGTA 5k Thermistor Compressor Suction Temp, SGT.A
Circuit B Suction Gas Thermistor SGTB 5k Thermistor Compressor Suction Temp, SGT.B
Circuit A EXV EXV-A Stepper Motor EXV Position, EXV.A
Circuit B EXV
(size 325 only)
EXV-B Stepper Motor EXV Position, EXV.B
CONNECTION POINT
Pin Notation
EXVA-J1 11 24 vac 12 Ground
EXVA-J4
1 RS485 Port (D+) 2 RS485 Port (Gnd) 3 RS485 Port (D–)
EXVA-J3
TH
A
EXVA-J3
TH
B
EXVA-J2A 1 2 3 4
EXVA-J2B 1 2 3 4
Table 7 — EXV1,2 Board Inputs and Outputs* (30XW350,400)
DESCRIPTION INPUT/OUTPUT I/O TYPE
Power (24 vac supply) ——
Local Equipment Network ——
Circuit X Suction Gas Thermistor SGT X 5k Thermistor Compressor Suction Temp, SGT.X
Circuit X Economizer Gas Thermistor ECT X 5k Thermistor Economizer Gas Temp, ECT.X
Circuit X EXV EXV-X Stepper Motor EXV Position, EXV.X
Circuit X Economizer EXV ECEXV-X Stepper Motor Cir X Economizer EXV Pos, ECO.X
*“X” denotes the circuit: 1 = Circuit A; 2 = Circuit B.
DISPLAY MODULE POINT NAME
CONNECTION POINT
Pin Notation
EXVX-J1 11 24 vac 12 Ground
EXVX-J4
1 RS485 Port (D+) 2 RS485 Port (Gnd) 3 RS485 Port (D–)
EXVX-J3 TH
A
EXVX-J3 TH
B
EXVX-J2A 1 2 3 4
EXVX-J2A 1 2 3 4
14
MLV/Condenser Board — One auxiliary board is op-
1
2
3
4
5
6
7
8
ON
100K
100K
100K
CH1
CH2 CH3
CH4 CH5 CH6 CH7 CH8
TR1 TR2 TR3 TR4 TR5 TR6 TR7 TR8
STAT US SIO (LEN)
LOCATION OF SERIAL NUMBER
24 VAC
CH13 CH14
J9
J1
CH9
CH10
CH11
CH12
JP2
C61
CH13
D12
JP1
L3
L5
U21
L2
D6
D5
Q5
Y1
D7
D8
S1
D3
U1
Q1
U5
U6
U7
U8
U9
Q10
Q11
U10
J4
J3
J2
U4
U2
Q12
Q60
3 2 1
– G +
3 2 1
– G +
DIP SWITCH
Fig. 11 — Auxiliary Board with Optional Minimum Load Control or Head Pressure Control
a30-4046
tionally installed in each unit. See Fig. 11. The auxiliary board contains an analog output for head pressure control and dis­crete outputs for minimum load control. The auxiliary board responds to commands from the MBB and sends the MBB the results of the channels it monitors via the Local Equipment
Network (LEN). See below for auxiliary board A, B and C DIP switch addresses. See Table 8 for inputs and outputs.
AUX BOARD DIP SWITCH
Address: OFF ON OFF OFF ON OFF ON OFF
123 45678
Table 8 — Auxiliary Board Outputs
DESCRIPTION INPUT/OUTPUT I/O TYPE DISPLAY MODULE POINT NAME
Power (24 vac supply) ——
Local Equipment Network ——
Condenser Head Pressure Control
Speed Signal
Minimum Load Valve A MLV-A Solenoid Minimum Load Valve Circuit A, MLV.A AUX-J2-CH3 Minimum Load Valve B MLV-B Solenoid Minimum Load Valve Circuit B, MLV.B AUX-J2-CH4
HD_A 0-10 VDC Head Press Actuator Pos, SPD.A
CONNECTION POINT
Pin Notation
AUX-J 1 11 24 vac 12 Ground
AUX-J 9
+ RS485 Port (D+) G RS485 Port (Gnd)
-RS485 Port (D-) + RS485 Port (D+) G RS485 Port (Gnd)
-RS485 Port (D-)
AUX-C H9
+ Signal
- Ground
15
Enable-Off-Remote Contact Switch (SW1) —
Fig. 12 — Energy Management Module
221
221
221
221
100K
100K
100K
100K
100K
CH 17
CH 17
CH 16
CH
CH 18
CH 19
CH 20
CH 22
CH 21
CH 23
24 VAC
12 11
CH
11b
CH
12
CH
13
CH
14
CH
15
CH
1
CH
2
CH
3
CH
4
CH 5
CH 6
CH 7
SIO LEN
+ G -
+ G -
SIO LEN
J8
J7B
J7A
J6
J5
J4J3J2B
J2A
J1
J9A
J9B
a30-4911
This switch is installed in all units and provides the owner and service person with a local means of enabling or disabling the machine. It is a 3-position switch and it is used to control the chiller. When switched to the Enable position, the chiller will be under its own control. When switched to the Off position, the chiller will shut down. When switched to the Remote Con­tact position, a field-installed dry contact can be used to start the chiller. The contacts must be capable of handling a 24-vac, 50-mA load. In the Enable and Remote Contact (dry contacts closed) positions, the chiller is allowed to operate and respond to the scheduling configuration, CCN configuration, and set point data.
For units with a Touch Pilot™ display, the position of the Enable/Off/Remote contact switch is ignored except when the Remote Mode operating type is selected. Refer to the Machine Control Methods section on page 20 for more details.
Emergency On/Off Switch (SW2) — This switch is
installed in all units. The Emergency On/Off switch should only be used when it is required to shut the chiller off immedi­ately. Power to all modules is interrupted when this switch is off and all outputs from these modules will be turned off.
Energy Management Module (EMM) — The EMM
is available as a factory-installed option or as a field-installed accessory. See Fig. 12. The EMM receives 4 to 20 mA inputs for the temperature reset, cooling set point and demand limit functions. The EMM also receives the switch inputs for the field-installed second stage 2-step demand limit and ice done functions. The EMM communicates the status of all inputs with the MBB, and the MBB adjusts the control point, capacity limit, and other functions according to the inputs received. See Table 9.
CAUTION
Care should be taken when interfacing with other manufac­turer’s control systems due to possible power supply differ­ences, full wave bridge versus half wave rectification, which could lead to equipment damage. The two different power supplies cannot be mixed. ComfortLink™ controls use half wave rectification. A signal isolation device should be utilized if incorporating a full wave bridge rectifier sig­nal generating device is used.
16
Table 9 — Energy Management Module (EMM) Inputs and Outputs
Fig. 13 — Touch Pilot™ Display Wiring
INPUT/OUTPUT DESCRIPTION I/O TYPE DISPLAY MODULE POINT NAME CONNECTION POINT 4-20 mA Demand Limit 4-20 mA Demand Limit 4-20 mA* Limit 4-20 mA Signal, DMD EMM-J7B-CH6 4-20 mA Temperature
Reset/Cooling Setpoint Demand Limit SW2 Demand Limit Step 2 Switch Input Switch Limit Setpoint 2, DLS2 EMM-J4-CH9 Ice Done Ice Done Switch Switch Input Ice Done Storage Switch, ICE.D EMM-J4-CH11A Occupancy Override Occupied Schedule Override Switch Input Occupied Override Switch, OCCS EMM-J4-CH8 Remote Lockout Switch Chiller Lockout Switch Input Remote Interlock Switch, RLOC EMM-J4-CH10 SPT Space Temperature Thermistor 10k Thermistor Optional Space Temp, SPT EMM-J6-CH2 % Total Capacity Percent Total Capacity Output 0-10 vdc Chiller Capacity Signal, CATO EMM-J8-CH7 RUN R Run Relay Relay Running Status, RUN EMM-J3-CH25 SHD R Shutdown Relay Relay Shutdown Indicator State, SHUT EMM-J3-CH24 CA_S Run Status for Circuit A Relay Compressor A Run Status, Q_RUN_A EMM-J2A-CH17 CB_S Run Status for Circuit B Relay Compressor B Run Status, Q_RUN_B EMM-J2A-CH18
* A field-supplied 1/2 watt 250 ohm resistor is required across terminals TB6-1,2 (CH6) and/or TB6-3, 4 (CH5).
Local Equipment Network — Information is trans-
mitted between modules via a 3-wire communication bus or LEN (Local Equipment Network). External connection to the LEN bus is made at TB3.
Board Addresses — All boards (except the Main Base
Board and Energy Management Module Board) have 8-position DIP switches.
Touch Pilot™ Display — The Touch Pilot display port
connections are shown in Table 10. Wiring is shown in Fig. 13.
Control Module Communication
RED LED — Proper operation of the control boards can be visually checked by looking at the red status LEDs (light­emitting diodes). When operating correctly, the red status LEDs will blink in unison at a rate of once every 2 seconds. If the red LEDs are not blinking in unison, verify that correct power is being supplied to all modules. Be sure that the Main Base Board (MBB) is supplied with the current software. If necessary, reload current software. If the problem still persists, replace the MBB. A red LED that is lit continuously or blink­ing at a rate of once per second or faster indicates that the board should be replaced.
GREEN LED — All boards have a green LEN (SIO) LED which should be blinking whenever power is on. If the LEDs are not blinking as described check LEN connections for
4-20 mA Temperature Reset/ Cooling Set point
4-20 mA*
Reset/Setpnt 4-20 mA Signal, RSET
EMM-J7A-CH5
potential communication errors at the board connectors. See input/output Tables 3-10 for LEN connector designations. A 3-wire bus accomplishes communication between modules. These 3 wires run in parallel from module to module. The J9A connector on the MBB provides communication directly to the Navigator™ display module.
YELLOW LED — The MBB has one yellow LED. The Carrier Comfort Network
®
(CCN) LED will blink during times
of network communication.
Table 10 — Touch Pilot™ Display Port
Connections
CONNECTOR PIN FUNCTION
124VAC +
J1 (Power)
J2 (COM1)
J3 (RJ11)
224VAC ­3 Earth Ground 1 RS485 Port (D+) 2 RS485 Port (GND) 3 RS485 Port (D-) 124VAC (+) 2 RS485 Port (D+) 3 RS485 Port (GND) 4 Unused (no connect) 5 RS485 Port (D-) 624VAC(-)
17
Carrier Comfort Network® (CCN) Interface —
Fig. 14 — ComfortLink™ CCN Communication Wiring
(+) (COM) (-) SHIELD
CCN
RED
WHT
BLK
CCNLEN
(+) (COM) (-) SHIELD
CCN
RED
WHT
BLK
CCNLEN
TO NEXT DEVICE
(+) (COM) (-) SHIELD
CCN
RED
WHT
BLK
CCN
LEN
SHIELD
LEGEND
CCN — Carrier Comfort Network
®
LEN — Local Equipment Network
a30-4706
All 30XW units can be connected to a CCN system, if desired. The communication bus wiring is a shielded, 3-conductor cable with drain wire and is field supplied and installed. The system elements are connected to the communication bus in a daisy chain arrangement. The positive pin of each system element communication connector must be wired to the positive pins of the system elements on either side of it. The negative and sig­nal ground pins of each system element must also be wired in the same manner. Wiring connections for CCN should be made at TB3. Consult the CCN Contractor’s Manual for further in­formation. See Fig. 14.
NOTE: Conductors and drain wire must be 20 AWG (Ameri­can Wire Gage) minimum stranded, tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of –20 C to 60 C is required. See Table 11 for recommended wire manufacturers and part numbers.
Table 11 — CCN Communication Bus Wiring
MANUFACTURER
Alpha 1895 American A21451 A48301 Belden 8205 884421 Columbia D6451 Manhattan M13402 M64430 Quabik 6130
Regular Wiring Plenum Wiring
It is important when connecting to a CCN communication bus that a color-coding scheme be used for the entire network to simplify the installation. It is recommended that red be used for the signal positive, black for the signal negative, and white for the signal ground. Use a similar scheme for cables contain­ing different colored wires.
At each system element, the shields of its communication bus cables must be tied together. If the communication bus is entirely within one building, the resulting continuous shield must be connected to a ground at one point only. If the commu­nication bus cable exits from one building and enters another, the shields must be connected to grounds at the lightning suppressor in each building where the cable enters or exits the building (one point per building only). To connect the unit to the network:
PART NU M B E R
1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white (ground), and black (–) conductors. (Substitute appropri­ate colors for different colored cables.)
3. Connect the red wire to (+) terminal on TB3 of the plug, the white wire to COM terminal, and the black wire to the (–) terminal.
4. The RJ14 CCN connector on TB3 can also be used, but is only intended for temporary connection (for example, a laptop computer running Service Tool).
IMPORTANT: A shorted CCN bus cable will prevent some routines from running and may prevent the unit from starting. If abnormal conditions occur, discon­nect the CCN bus. If conditions return to normal, check the CCN connector and cable. Run new cable if necessary. A short in one section of the bus can cause problems with all system elements on the bus.
Remote Alarm and Alert Relays — The 30XW
chiller can be equipped with a remote alert and remote alarm annunciator contacts. Both relays connected to these contacts must be rated for a maximum power draw of 10 va sealed, 25 va inrush at 24 volts. The alarm relay, indicating that the complete unit has been shut down, can be connected to TB5-12 and TB5-13. Refer to unit wiring diagrams. For an alert relay, indicating that at least 1 circuit is off due to the alert, a field­supplied and installed relay must be connected between MBB­J3-CH25-3 and TB5-13. The action of the alarm and alert re­lays can be reversed from normally open to normally closed by using the Reverse Alarms Relay configuration (Reverse Alarms Relay, RV.AL).
CONFIGURATION
Touch Pilot™ Operation Configuration Tables —
configuration information entered in the following configura­tion tables. These tables are accessible by using Network Ser­vice Tool or ComfortVIEW™ software. The tables are the CtrlID (Controller Identification) configuration table and the USERCONF (User Configuration) table. See Tables 12 and 13.
NOTE: Always perform an Upload to obtain the latest config­uration before making configuration table changes.
The Touch Pilot display operation is controlled by
18
Table 12 — Touch Pilot Controller Identification Configuration Table
CONTROLLER ID DATA BLOCK NO. VALUE AND RANGE QUALIFIERS
Device Name 1
Local address 2 115 Default Bus number 2 0 Default
Device (driver) type 2
Primary baud rate 3 38400 Default Secondary baud rate 3 38400 Fixed
Device description 4
Device location 4
Software part number 4 CESR-131363-01 Fixed Model number 4 (Blank) Fixed Serial number 4 (Blank) Fixed Reference number 4 Version 1.0 Fixed
Broadcast address processing list (primary) 5
Broadcast address processing list (secondary) 5 none Not applicable
CHILLDSP 8 character Name field
0 = Non-bridge 3 = Broadcast Acknowledger
Global Chiller Display 24 character text field
(Blank) 24 character text field
241-251, 254, 255 enabled 241-255 enabled/disabled
Default Optional
Default Optional
Default Optional
Default Optional
Defaults Optional
Table 13 — Touch Pilot™ User Configuration (USERCONF) Table
DESCRIPTION LIMITS UNITS NAME DEFAULT
Backlight always on?
Full access password
Limited access password
Active language
Time format
Date format
Units base
Contrast control
Network mode
Network settings
Alarm acknowledger
Broadcast acknowledger
Equipment CCN address
Bus number
Element number
Control variables
Equipment status (Not Used)
Equipment start/stop (Not Used)
Alarm status (Not Used)
Alarm reset (Not Used)
No Ye s
0 9999
0 9999
0 1
0 1
0 2
US Metric
Manual Auto
0 1
No Ye s
No Ye s
0 239
1 239
Name char 8
Name char 8
Name char 8
Name char 8
BACKLITE No
PSWDFULL 3333
PSWDLMTD 2222
ACTLANG 0
TIMEFMT 0
DATEFMT 0
UNITBASE US
CONTRAST Auto
NETWORK 0
ALARMACK No
BROADACK No
EQUIPBUS 0
EQUIPELE 1
EQSTATUS NOT USED
STARSTOP NOT USED
ALSTATUS NOT USED
ALRESET NOT USED
BACKLIGHT ALWAYS ON? — This configuration is used to keep the backlight on continuously or to turn it off after 60 seconds with no activity.
Allowable Entries: No/Yes (No=0 or Yes=1) Default Value: No
FULL ACCESS PASSWORD — This configuration is used to specify the full access password. Refer to Table 1, Setup Menu, for additional information on passwords.
Allowable Entries: 0 through 9999 Default Value: 3333
19
LIMITED ACCESS PANEL — This configuration is used to
Fig. 15 — Equipment Start Screen
specify the limited access password. Allowable Entries: 0 through 9999 Default Value: 2222 ACTIVE LANGUAGE — This configuration is used to spec-
ify the display’s active language. All translatable text will be displayed in this language.
Allowable Entries: 0 (English), 1 (alternate, installed by user) Default Value: 0 TIME FORMAT — This configuration is used to specify the
format for display of time. Allowable Entries: 0 = H:MM AM/PM without leading zero
1 = HH:MM with leading zero when
necessary Default Value: 0 DATE FORMAT — This configuration is used to specify the
format for display of date. Allowable Entries: 0 = MM-DD-YYYY with leading zero
when necessary
1 = DD-MM-YYYY with leading zero
when necessary
2 = YYYY-MM-DD Default Value: 0 UNITS BASE — This configuration is used to specify the for-
mat of the units of measure. Allowable Entries: U.S.
Metric Default Value: U.S. CONTRAST CONTROL — This configuration is used to en-
able or disable the display’s auto contrast adjustment feature. When enabled, the display’s contrast will be automatically ad­justed as required, based on temperature.
Allowable Entries: Manual
(Auto Contrast Adjustment Disabled)
Auto
(Auto Contrast Adjustment Enabled) Default Value: Auto NETWORK MODE — This configuration is used to set the
display’s operating mode. For additional information on oper­ating mode, refer to Display in the Table Setup Menu. This de­cision will be ignored and the mode will default to Equipment when the display is connected to a device (the LEN Bus).
NOTE: A power cycle is required for this decision to take effect.
Allowable Entries: Disable = Equipment Mode
Enable = Network Mode Default Value: Disable ALARM ACKNOWLEDGER — This configuration is used
to specify whether the Touch Pilot™ display will act as the alarm acknowledger for the CCN. There can be only one alarm acknowledger per CCN. Therefore, if another CCN device such as ComfortVIEW™ software, the Autodial Gateway or TeLINK is already set as the alarm acknowledger for the CCN network then this decision should be set to No.
NOTE: The display must be in Network mode and connected to the primary CCN bus and this decision set to Ye s for alarm acknowledgement to be enabled.
Allowable Entries: No
Ye s Default Value: No
BROADCAST ACKNOWLEDGER — This configuration is used to indicate whether the Touch Pilot display will act as the broadcast acknowledger for its CCN bus. There can be only one broadcast acknowledger per CCN bus.
NOTE: The display must be in Network mode and this deci­sion set to Ye s for broadcast acknowledgement to be enabled.
Allowable Entries: No
Ye s Default Value: 0 EQUIPMENT CCN ADDRESS — When in equipment
mode (USERCONF Table’s Network Mode decision is set to Disable), the Bus Number and Element Number decisions are used to specify the CCN address of the piece of equipment to communicate with. An Attach or power cycle must be performed for changes to take effect. These decisions will be ignored when the display is connected to the LEN bus or in Network mode. In Network mode, specify the bus and element number of the equipment communicate with using the dis­play’s Attach function.
NOTE: In Network mode, these configurations will be over­written with the default device address if it is changed through the Attach process.
BUS NUMBER — This configuration is used to specify the Equipment Controller bus number.
Allowable Entries: 0 through 239 Default Value: 0 ELEMENT NUMBER — This configuration is used to speci-
fy the Equipment Controller element number. Allowable Entries: 1 through 239 Default Value: 1
Machine Control Methods — Three variables con-
trol how the machine operates. These variables control the On-Off function, set point operation, and Heat-Cool operation.
Machine On/Off Control — Machine On/Off control
depends on which interface display is used. The control is dif­ferent for Touch Pilot™ or Navigator™ displays. Select the correct configuration procedure below based on which inter­face is being used.
TOUCH PILOT MACHINE CONTROL — Machine On/Off control is determined locally by pushing the Start/Stop button on the Touch Pilot display. Pressing this button will cause the Equipment Start screen to be displayed. See Fig. 15.
20
Table 14 summarizes the unit control type and stop or go
status with regard to the following parameters:
• Operating type: this is selected by using the start/stop button on the front of the user interface.
• Remote start/stop contacts: these contacts are used when the unit is in remote operating type (Remote mode).
• CHIL_S_S: this network command variable relates to the chiller start/stop when the unit is in CCN control (CCN mode). When this variable forced to Disable, then the unit is stopped. When this variable is forced to Enable, then the unit runs in accordance with schedule 1.
• Start/Stop schedule: occupied or unoccupied status of the unit as determined by the chiller start/stop program (Sched­ule 1).
• Master control type: This parameter is used when the unit is the master unit in a two chiller lead/lag arrangement. The master control type determines whether the unit is to be controlled locally, remotely or through CCN (this parameter is a Service configuration).
• CCN emergency shutdown: if this CCN command is acti­vated, it shuts the unit down whatever the active operating type.
• General alarm: the unit is totally stopped due to failure.
Local Mode
— To start the machine in local mode, press the Start/Stop button on the Touch Pilot display. The Equipment Start screen will be displayed. Select Local On. The control will ignore the position of Enable/Off/Remote Contact switch and all CCN network force commands, except an Emergency Stop Command. The Run Status variable, indicating the cur- rent status of the machine, will change to RUNNING, DELAY or READY. The Chiller Occupied? variable will change to YES. The Control Type variable indicates the type of control. For this configuration, Control Type will be Local. The Oper- ating Type variable will change to L-On (Local On).
Local Schedule
— To start the machine with a local schedule, press the Start/Stop button on the Touch Pilot display. The Equipment Start screen will be displayed. Select Local Sched­ule. The unit will start and stop according to the schedule de­fined in the Time Schedule menu. Two Internal Time Sched­ules are available and must be field programmed. Time Schedule 1 is used for single set point On-Off control. Time
Table 14 — Touch Pilot™ Start/Stop Control
Schedule 2 is used for Dual Set Point/Occupied-Unoccu­pied set point control. The control will ignore the position of Enable/Off/Remote Contact switch and all CCN network force commands, except the Emergency Stop Command.
The Run Status variable will indicate the current status of the machine — OFF, RUNNING, DELAY, or READY. The Chiller Occupied? variable will indicate the occupied state of the machine according to Time Schedule 1 and will be either YES (occupied) or NO (unoccupied). The Control Type vari- able will indicate the type of control. For this configuration, Control Type will be Local. The Operating Type variable will change to L-Sched (Local Schedule).
The schedules consist of 8 user-configurable occupied time periods. The control supports time schedules for local control, remote control, and ice building. These time periods can be flagged to be in effect or not in effect on each day of the week. The day begins at 00.00 and ends at 24.00. The machine will be in unoccupied mode unless a scheduled time period is in effect. If an occupied period extends past midnight, the occupied period will automatically end at 24:00 hours (midnight) and the new occupied period must be programmed to begin at 00:00 hours.
In the following example, the occupied period starts at 6:00 AM, Monday through Friday and 10:00 AM on Saturday and Sunday. The occupied time ends at 6:30 PM on Monday through Friday and 2:00 PM on Saturday and Sunday. See Fig. 16.
NOTE: This schedule was designed to illustrate the program­ming of the schedule function and is not intended as a recommended schedule for chiller operation.
If the chiller is to be controlled to a single set point, use Schedule 1 (OCCPC01S). This will start and stop the machine. During the unoccupied times, the chiller will be off. If the chill­er is to be controlled to 2 set points, occupied and unoccupied, use Schedule 2 (OCCPC02S). This will cause the chiller to control to an occupied set point and an unoccupied set point. The machine will be able to provide cooling at any time.
To configure this option on the Touch Pilot™ display see Table 15.
ACTIVE OPERATING TYPE PARAMETER STATUS
LocalOnLocalOnLocal
-- - - - - - - - - Active - - Off
-- - - - - - - - - - Yes - Off
Active - - - - - - - - - - - Local Off
- - Active - - - - - - Unoccupied - - Local Off
- - - Active - - - Off - - - - Remote Off
- - - Active - - - - - Unoccupied - - Remote Off
- - - - Active - Off - - - - - CCN Off
- - - - Active - - - - - - - CCN Off
- - - - - Active - - Local Unoccupied - - Local Off
- - - - - Active - Off Remote - - - Remote Off
- - - - - Active - - Remote Unoccupied - - Remote Off
- - - - - Active Off - CCN - - - CCN Off
- - - - - Active - - CCN Unoccupied - - CCN Off
- Active - - - - - - - - Disabled No Local On
- - Active - - - - - - Occupied Disabled No Local On
- - - Active - - - On Cool - Occupied Disabled No Remote On
- - - - Active - On - - Occupied Disabled No CCN On
- - - - - Active - - Local Occupied Disabled No Local On
- - - - - Active - On Cool Remote Occupied Disabled No Remote On
- - - - - Active On - CCN Occupied Disabled No CCN On
Schedule
Remote
Mode
CCN
Mode
Master
Mode
CHIL_S_S
Varia ble
Remote
Start/Stop
Contact
Master Unit
Control Type
Start/Stop
Schedule
Mode
CCN
Emergency
Shutdown
General
Alarm
CONTROL
TYPE
UNIT
STATUS
21
on a one-time basis. To configure this option for the Touch
Fig. 16 — Chiller Schedule Screen
Pilot display:
Table 15 — Configuring the Schedule with
Touch Pilot Display
DISPLAY NAME PATH LINE NO. VALUE Period 1 DOW (MTWTFSSH) Occupied from 3 00:00 Occupied to 4 03:00 Period 2 DOW (MTWTFSSH) 5 11000000 Occupied from 6 07:00 Occupied to 7 18:00 Period 3 DOW (MTWTFSSH) 8 00100000 Occupied from 9 07:00 Occupied to 10 21:30 Period 4 DOW (MTWTFSSH) 11 00011000 Occupied from 12 07:00 Occupied to 13 17:00 Period 5 DOW (MTWTFSSH) 14 00000100 Occupied from 15 07:00 Occupied to 16 12:00
Holiday Schedule
— For the Touch Pilot display, the control
Config\
OCCDEFCS\
OCC1P01S
or OCC1P02S
2 10000000
allows up to 16 holiday periods. All holidays are entered with numerical values. To configure, first change the month (Holi- day Start Month), then the day (Holiday Start Day), then the duration (Holiday Duration) of the holiday period in days. If a holiday in included in one of the Occupied Time Periods of the schedule, the machine will follow that operating condition for the holiday. In the following examples, the holidays July 4 and December 25-26 are programmed for Holiday 1 and Holiday 2, respectively. To configure these holidays with the Touch Pilot display, see Table 16. To configure Holidays with the Naviga­tor display, check the H (holiday) schedule on the Schedule screen and program in the desired occupied times. See Fig. 16.
Table 16 — Programming Holiday Schedules with
Touch Pilot Display
DISPLAY NAME PATH LINE NO. VALUE Holiday Start Month Start Day 24 Duration (days) 31 Holiday Start Month Start Day 225 Duration (days) 32
Timed Override
Config\HOLIDAY\HOLDY_01
Config\HOLIDAY\HOLDY_02
— With the Touch Pilot display only, each
17
112
time schedule can be overridden to keep the chiller in an Occupied mode (Timed Override Hours) for 1, 2, 3 or 4 hours
DISPLAY NAME PATH
Timed Override Hours
Config\OCCDEFCS\
OCC1P01S or OCC1P02S
LINE
NO.
1
VAL UE
Range: 0 to 4
Default: 0
If configured for a timed override, the override can be can-
celled by changing the Timed Override Hours to 0. CCN Global Time Schedule
— A CCN global schedule can be used if desired. The schedule number can be set anywhere from 65 to 99 for operation under a CCN global schedule. The 30XW chillers can be configured to follow a CCN Global Time Schedule broadcast by another system element. The ComfortVIEW™ Network Manager’s Configure and Modify commands or the Service Tool’s Modify/Names function must be used to change the number of the Occupancy Equipment Part Table Name (OCC1P01E) to the Global Schedule Num­ber. The Schedule Number can be set from 65 to 99 (OCC1P65E to OCC1P99E).
The Occupancy Supervisory Part table name (OCC1P01S) number must be changed to configure the unit to broadcast a Global Time Schedule. The Schedule Number can be set from 65 to 99 (OCC1P65S to OCC1P99S). When OCC1PxxS is set to a value greater than 64, an occupancy flag is broadcast over the CCN every time it transitions from occupied to unoccupied or vice-versa. By configuring their appropriate Time Schedule decisions to the same number, other devices on the network can follow this same schedule. The Enable/Off/Remote Contact must be in the Enable position or the Remote Contact position with the contacts closed for the unit to operate. The Unit Run Status (STAT) will indicate the current status of the machine (OFF, RUNNING, STOPPING or DELAY), depending on the schedule. The unit Occupied status (OCC) will indicate the current occupied schedule according to the schedule, either NO or YES. The Status Unit Control Type (CTRL) will be LOCAL OFF when the switch is Off. The Status Unit Control Type will be CCN when the Enable/Off/Remote Contact switch input is On.
Refer to Appendix F for more detailed instructions regard­ing global schedules and the i-Vu
CCN Mode
— To allow machine control by CCN commands,
®
device.
press the Start/Stop button on the Touch Pilot™ display. The Equipment Start screen will be displayed. Select CCN Mode. The unit will be controlled by a CCN command to the CCN Chiller Star t/Stop variable. An external CCN device, such as Chillervisor, controls the On/Off state of the machine. When controlled by a Chillervisor, it is recommended that the Auto Start W hen SM Lost configuration be set to Yes. In the event of a loss of communication with the network, the machine will start and be controlled locally.
Careful evaluation of chilled water plant control should be reviewed. In the event local control is established, be sure that all pumps, valves, and other devices are capable of operating properly. The control will ignore the position of Enable/Off/ Remote Contact switch. The Run Status variable will indicate the current status of the machine — OFF, RUNNING, DELAY, or READY. The Control Type variable will change to CCN. The Operating Type variable will change to CCN.
For dual chiller control applications, the slave chiller must be enabled using the CCN Mode button.
Remote Mode
— To allow machine to start and stop via a remote contact closure, press the Start/Stop button on the Touch Pilot display. The Equipment Start screen will be dis­played. Select Remote Mode. The unit will be controlled by the Enable/Off/Remote Contact switch (SW1). Switching the En­able/Off/Remote Contact switch to the Enable or Remote Contact position (external contacts closed) will force the unit into an occupied state. In this mode, all CCN network force
22
commands, except the Emergency Stop Command will be
Fig. 17 — Equipment Stop Screen
ignored. The Run Status variable will indicate the current sta­tus of the machine (OFF, RUNNING, DELAY, or READY), depending on the position of the Remote/Off/Enable Switch closure. The Chiller Occupied? variable will change to YES. The Control Type variable will change to Remote. The Oper- ating Type variable will change to Remote.
Master Mode
— To activate Dual Chiller Control, each ma­chine must be individually configured for Dual Chiller Control. To operate the machines in Dual Chiller Mode, one machine must be designated as the master unit and one machine as the slave unit. On the master unit, press the Start/Stop button on the Touch Pilot display. The Equipment Start screen will be dis­played. Select Master Mode. Failure to start the Master unit in this manner will cause both machines to operate in local mode.
The Master Unit Control can be done locally, remotely or through CCN commands per the master/slave configuration (Master Control Type). The control will ignore the position of Enable/Off/Remote Contact switch if the Master Control
Type is configured for Local Control or CCN Control. The Run Status variable, Chiller Occupied? variable, and Con­trol Type variable will change based on the Master Control Type configured above and the Machine On/Off Control de-
fined above. The Operating Type variable will change to Master.
To Turn Machine Off
— To turn the machine off, press the Start/Stop button on the Touch Pilot display. See Fig. 17. The machine will shut down. While the unit is in Local Off, it will remain shut down and ignore all CCN commands as well as the position of Enable/Off/Remote Contact switch. The Run Status variable, indicating the current status of the machine, will change to OFF. The Chiller Occupied? variable will change to NO. The Control Type variable will indicate Local. The Operating Type variable will change to L-OFF (Local Off).
NAVIGATOR™ DISPLAY MACHINE CONTROL — Ma­chine On/Off control with the Navigator display is determined by the configuration of the Operating Type Control (OPER). Options to control the machine locally via a switch, from a lo­cal Time Schedule, or via a Carrier Comfort Network
®
com-
mand are offered. See Table 17.
The schedules consist of 8 user-configurable occupied time periods. The control supports time schedules for local control, remote control, and ice building. These time periods can be flagged to be in effect or not in effect on each day of the week. The day begins at 00.00 and ends at 24.00. The machine is in unoccupied mode unless a scheduled time period is in effect. If an occupied period is to extend past midnight, the occupied period must end at 24:00 hours (midnight) and a new occupied period must be programmed to begin at 00:00 hours.
In the following example, a early morning pulldown time period is scheduled for Monday morning from 12:00 AM to 3:00 AM. The occupied period starts at 7:00 AM, Monday through Saturday. The occupied time ends at 6:00 PM on Mon­day and Tuesday, 9:30 PM on Wednesday, 5:00 PM on Thurs­day and Friday, and 12:00 PM on Saturday.
NOTE: This schedule was designed to illustrate the program­ming of the schedule function and is not intended as a recom­mended schedule for chiller operation.
Switch Control
— In the Switch Control operating type, the Enable/Off/Remote Contact switch controls the machine local­ly. All models are factory configured with Operating Type Control (OPER) set to SWITCH CTRL (Switch Control). With SWITCH CTRL, switching the Enable/Off/Remote Contact switch to the Enable or Remote Contact position (ex­ternal contacts closed) will put the chiller in an occupied state. The Unit Run Status (STAT) will indicate the current status of the machine and will change from OFF to RUNNING or DELAY. The unit Occupied Status (OCC) will change from NO to YES. The Status Unit Control Type (CTRL) will change from LOCAL OFF when the switch is Off to LOCAL ON when in the Enable position or in the Remote Contact position with external contacts closed.
CONTROL
METHOD
(OPER)
Switch
Control
Time
Schedule
CCN
Control
OPERATING
All Local Off
ACTI VE
TYPE
Local On
Local
Schedule
CCN
ITEM ITEM EXPANSION PATH VALUE
OPER
Operating Control Ty p e
Operating Modes SLCT OPER
Table 17 — Navigator Start/Stop Control
REMOTE/OFF/ENABLE
SWITCH
Off
Remote Open Off
———EnableOff ———YesOff — Closed Off
Enable Disable On
Remote Closed Disable On
Enable Occupied Disable On
Remote Closed Occupied Disable On
Unoccupied Disable Off Remote Closed Enable Disable On Remote Closed Disable Disable Off
Enable Enable Disable On Enable Disable Disable Off
REMOTE ON/OFF
SWITCH
TIME SCHEDULE 1
CCN CHILLER
START/STOP
(CHIL_S_S)
EMERGENCY
STOP
(EMSTOP)
ALARM
REMOTE
LOCKOUT
SWITCH
SWITCH CTRL
UNIT
STATUS
Off
23
Time Schedule
— With Time Schedule Operating Type con­trol, the machine operates under a local schedule programmed by the user as long as the Enable/Off/Remote Contact switch is in the Enable or Remote Contact position (external contacts closed). To operate under this Operating Type Control (OPER) must be set to TIME SCHED (Time Schedule). Two Internal Time Schedules are available and must be field programmed. Time Schedule 1 (SCH1) is used for single set point On-Off control. Time Schedule 2 (SCH2) is used for dual set point On-Off and Occupied-Unoccupied set point control. The control will use the operating schedules as defined under the Time Clock mode in the Navigator display module.
ITEM ITEM EXPANSION PATH VALUE
OPER
Operating Control Ty pe
Operating Modes SLCT OPER
TIME SCHED
If the chiller is to be controlled to a single set point, use Schedule 1 (SCH1). This type of schedule will start and stop the machine only. During the unoccupied times, the chiller will be off. If the chiller is to be controlled to 2 set points, occupied and unoccupied, use Schedule 2 (SCH2). This will cause the chiller to control to an occupied set point and an unoccupied set point. The machine will be able to provide cooling at any time.
To configure this option while using the Navigator™ dis­play, see Table 18.
Holiday Schedule
— The unit control allows up to 16 holiday periods. All holidays are entered with numerical values. First enter the month (MON.x), then the day (DAY.x), then the duration (DUR.x) of the holiday period in days. If a holiday in included in one of the Occupied Time Periods of the schedule, the machine will follow that operating condition for the holiday. In the following examples, the holidays July 4 and December 25-26 are programmed for Holiday 1 and Holiday 2 respectively.
To configure this option for the Navigator display, see
Table 19. CCN Global Time Schedule
— A CCN global schedule can be used if desired. The schedule number can be set anywhere from 65 to 99 for operation under a CCN global schedule. The 30XW chillers can be configured to follow a CCN Global Time Schedule broadcast by another system element. The ComfortVIEW™ Network Manager’s Configure and Modify commands or the Service Tool’s Modify/Names function must be used to change the number of the Occupancy Equipment Part Table Name (OCC1P01E) to the Global Schedule Num­ber. The Schedule Number can be set from 65 to 99 (OCC1P65E to OCC1P99E).
The Occupancy Supervisory Part table name (OCC1P01S) number must be changed to configure the unit to broadcast a Global Time Schedule. The Schedule Number can be set from 65 to 99 (OCC1P65S to OCC1P99S). When OCC1PxxS is set to a value greater than 64, an occupancy flag is broadcast over the CCN every time it transitions from occupied to unoccupied or vice-versa. By configuring their appropriate Time Schedule decisions to the same number, other devices on the network can follow this same schedule. The Enable/Off/Remote Contact must be in the Enable position or the Remote Contact position with the contacts closed for the unit to operate. The Unit Run Status (STAT) will indicate the current status of the machine (OFF, RUNNING, STOPPING or DELAY), depending on the schedule. The unit Occupied status (OCC) will indicate the current occupied schedule according to the schedule, either NO or YES. The Status Unit Control Type (CTRL) will be LOCAL OFF when the switch is Off. The Status Unit Control Type will be CCN when the Enable/Off/Remote Contact switch input is On.
Refer to Appendix F for more detailed instructions regard­ing global schedules and the i-Vu
®
device.
Table 18 — Configuring Schedules with
Navigator™ Display
ITEM ITEM EXPANSION PATH VALUE OCC.1 Occupied Time UNO.1 Unoccupied Time 03:00 MON.1 Monday Select Yes TUE.1 Tuesday Select No WED.1 Wednesday Select No THU.1 Thursday Select No FRI.1 Friday Select No SAT.1 Saturday Select No SUN.1 Sunday Select No HOL.1 Holiday Select No OCC.2 Occupied Time UNO.2 Unoccupied Time 18:00 MON.2 Monday Select Yes TUE.2 Tuesday Select Yes WED.2 Wednesday Select No THU.2 Thursday Select No FRI.2 Friday Select No SAT.2 Saturday Select No SUN.2 Sunday Select No HOL.2 Holiday Select No OCC.3 Occupied Time UNO.3 Unoccupied Time 21:30 MON.3 Monday Select No TUE.3 Tuesday Select No WED.3 Wednesday Select Yes THU.3 Thursday Select No FRI.3 Friday Select No SAT.3 Saturday Select No SUN.3 Sunday Select No HOL.3 Holiday Select No OCC.4 Occupied Time UNO.4 Unoccupied Time 17:00 MON.4 Monday Select No TUE.4 Tuesday Select No WED.4 Wednesday Select No THU.4 Thursday Select Yes FRI.4 Friday Select Yes SAT.4 Saturday Select No SUN.4 Sunday Select No HOL.4 Holiday Select No OCC.5 Occupied Time UNO.5 Unoccupied Time 12:00 MON.5 Monday Select No TUE.5 Tuesday Select No WED.5 Wednesday Select No THU.5 Thursday Select No FRI.5 Friday Select No SAT.5 Saturday Select Yes SUN.5 Sunday Select No HOL.5 Holiday Select No
Clock SCH1 PER.1
Clock SCH2 PER.1
Clock SCH1 PER.2
Clock SCH2 PER.2
Clock SCH1 PER.3
Clock SCH2 PER.3
Clock SCH1 PER.4
Clock SCH2 PER.4
Clock SCH1 PER.5
Clock SCH2 PER.5
Time
or Time
Time
or Time
Time
or Time
Time
or Time
Time
or Time
00:00
07:00
07:00
07:00
07:00
Table 19 — Configuring Holiday Schedules
for Navigator Display
ITEM ITEM EXPANSION PATH VALUE
MON.1 Holiday Start Month DAY.1 Holiday Start Day 4 DUR.1 Holiday Duration in Day 1 MON.2 Holiday Start Month DAY.2 Holiday Start Day 25 DUR.2 Holiday Duration in Day 2
Clock HOLI HOL.1
Clock HOLI HOL.2
Time
Time
12
7
24
CCN Control
— With CCN Operating Type control, the ma­chine operates under CCN control as long as the Enable/Off/ Remote Contact Switch is in the Enable or Remote Contact position (external contacts closed.) To operate under this Operating Control, OPER must be set to CCN CONTROL. An external CCN device, such as Chillervisor, controls the On/Off state of the machine. When controlled by a Chillervisor, it is recommended that the Auto Start When SM Lost (AU.SM) be set to Yes.
Careful evaluation of Chilled Water Plant control should be reviewed. In the event Local Control is established, be sure that all pumps, valves, and other devices are capable of operating properly. In the event of a loss of communication with the net­work, the machine will start and be controlled locally. The CCN device forces the variable CHIL_S_S to control the chill­er. The Unit Run Status (STAT) will indicate the current status of the machine (OFF, RUNNING, STOPPING or DELAY), depending on the CCN command. The unit Occupied status (OCC) will indicate the current occupied state according to the CCN command and will be displayed as either NO or YES. The Status Unit Control Type (CTRL) will be LOCAL OFF when the Enable/Off/Remote Contact switch is Off. The Status Unit Control Type will be CCN when the Enable/Off/Remote Contact switch input is Closed and the CHIL_S_S variable is Stop or Start.
For Dual Chiller Control applications, the Slave Chiller must be enabled using the CCN CONTROL option.
ITEM ITEM EXPANSION PATH VALUE
OPER
AU.S M
Operating Control Ty pe
Auto Start when SM Lost
Operating Modes SLCT OPER
Configuration SERV YES
CCN CONTROL
Entering Fluid Control Option — The factory de-
fault for the chilled water fluid set point is controlling to the leaving water temperature. An option to configure the machine for entering water control is available. The control operation remains the same except the control point is focused on the entering water temperature, rather than the leaving water tem­perature when configured.
To configure this option for the Touch Pilot™ display:
DISPLAY NAME PATH
Entering Fluid Control
Service\ SERVICE1
LINE
NO.
No = Leaving Water Control
5
Yes = Entering Water Control
VAL UE
To configure this option for the Navigator™ display:
ITEM ITEM EXPANSION PATH VALUE
EWTO Entering Water
Control
Configuration SERV No = Leaving
Water Control Yes = Entering Water Control
Cooling Set Point Selection — Several options for
controlling the Leaving Chilled Water Set Point are offered and are configured by the Cooling Set Point Select (Setpoint Se- lect, SP.SE) variable. In addition to the Cooling Set Point Se- lect, Ice Mode Enable discussed later in this book, and Heat Cool Select (Heat/Cool Select, HC.SE) variables also have a role in determining the set point of the machine. All units are shipped from the factory with the Heat Cool Select set to 0.
All default set points are based on Leaving Water Control (Entering Fluid Control, EWTO) set to No. Values must be confirmed for the individual set points. Limits for the set points are listed in the configurations noted below.
To configure these options for the Touch Pilot display, see Table 20A. To configure these options for the Navigator dis­play, see Table 20B.
Table 20A — Cooling Set Point Selection
with Touch Pilot Display
DISPLAY NAME PATH LINE NO. VALUE
Cooling Setpoint 1 Setpoint 2 Range: 14 to 70 F
Cooling Setpoint 2 Setpoint 3 Range: 14 to 70 F
Cooling Ice Setpoint Setpoint 4 Range: -20 to 32 F
(–10.0 to 21.1 C) Default: 44 F (6.6 C)
(–10.0 to 21.1 C) Default: 44 F (6.6 C)
(–28.9 to 0 C) Default: 44 F (6.6 C)
Table 20B — Cooling Set Point Selection
with Navigator Display
ITEM ITEM EXPANSION PATH VALUE
CSP.1 Cooling Setpoint 1 Setpoints COOL
CSP.2 Cooling Setpoint 2 Setpoints COOL
CSP.3 Ice Setpoint Setpoints COOL
Range: 14 to 70 F (–10.0 to 21.1 C) Default: 44 F (6.6 C)
Range: 14 to 70 F (–10.0 to 21.1 C) Default: 44 F (6.6 C)
Range: -20 to 32 F (–28.9 to 0 C) Default: 44 F (6.6 C)
In all cases, there are limits on what values are allowed for each set point. These values depend on the Cooler Fluid Type and the Brine Freeze Set point, discussed later. See Table 21.
Table 21 — Configuration Set Point Limits
COOLER FLUID TYPE
SET POINT LIMITS
Minimum * 38 F (3.3 C) 14 F (–10.0 C) Maximum 60 F (15.5 C)
*The minimum set point for Medium Temperature Brine applications
is related to the Brine Freeze Point. The set point is limited to be no less than the Brine Freeze Point +5° F (2.8° C).
(COOLER FLUID TYPE, FLUD)
1, Water 2, Brine
The Setpoint Select configuration can be set to five different control options: Set Point Occupancy, Set Point 1, Set Point 2, 4-20 mA Input, and Dual Switch.
CAUTION
Brine duty application (below 40 F [4.4 C] LCWT) for chiller normally requires factory modification. Contact a Carrier Representative for details regarding specific applications. Operation below 40 F (4.4 C) LCWT with­out modification can result in compressor failure.
SET POINT OCCUPANCY — Set Point Occupancy is the default configuration for the Setpoint Select variable. When Setpoint Select (Setpoint Select, SP.SE) is configured to 0 (Setpoint Occ), the unit’s active set point is based on Cooling Set Point 1 (Cooling Setpoint 1, CSP.1) during the occupied period while operating under Time Schedule 1 (SCH1). If the Time Schedule 2 (SCH2) is in use, the unit’s active set point is based on Cooling Set Point 1 (Cooling Setpoint 1, CSP.1) dur- ing the occupied period and Cooling Set Point 2 (Cooling Set- point 2, CSP.2) during the unoccupied period. See Tables 22 and 23.
To configure this option while using a Touch Pilot display:
DISPLAY NAME PATH LINE NO. VALUE
Setpoint select Status GENUNIT 25 0 (Setpoint Occupied)
To change this value, a Control Point Force must be applied. When configured correctly, Setpoint Control (Setpoint Con- trol, SP.SE) will indicate Auto.
To configure this option while using a Navigator display:
ITEM ITEM EXPANSION PATH VALUE
SP.SE Setpoint Select Operating Modes SLCT Setpoint Occ
25
Table 22 — Cooling Set Point Selection Touch Pilot™ Parameters
SET POINT
CONFIGURATION
(Setpoint Select)
0
(Auto)
1 (Setp 1) Cooling Setpoint 1 2 (Setp 2) Cooling Setpoint 2
3 (4-20 mA) 4 to 20 mA Input
4 (Setp Sw)
ICE MODE
ENABLE
(ice_cnfg)
NO
YES
NO
YES
DUAL SET
POINT INPUT
(SETP_SW)
Occupied Cooling Setpoint 1 — Unoccupied Cooling Setpoint 2 — Open Unoccupied Cooling Ice Setpoint — Closed Unoccupied Cooling Setpoint 2 — Occupied Cooling Setpoint 1
Open Cooling Setpoint 1
Closed Cooling Setpoint 2
Open Cooling Setpoint 1 Closed Open Cooling Ice Setpoint Closed Closed Cooling Setpoint 2
ICE DONE INPUT
(ICE_SW)
TIME
SCHEDULE 2
Table 23 — Cooling Set Point Selection Navigator™ Parameters
PARAMETER STATUS
Control Method
(OPER)
LOCAL COOL
CCN COOL
Select (HC.SE)
Heat/Cool
Setpoint
Select (SP.SE)
Setpoint Occ Occupied CSP.1 Setpoint Occ Unoccupied CSP.2 Setpoint Occ Enable Open Unoccupied CSP.3
Setpoint 1 CSP.1 Setpoint 2 CSP.2
4-20mA Setp 4_20mA
Enable Open Closed CSP.3 — Enable Closed Closed CSP.2 — Open CSP.1
Dual Setp Sw Closed CSP.2
Occupied CSP.1 — Unoccupied CSP.2
Ice Mode
Enable (ICE.M)
Ice Done
(ICE.D)
Dual Setpoint
Switch (DUAL)
Setpoint
Occupied
(SP.OC)
ACTIVE
SET POINT
ACTIVE
SET POINT
Set Point 1
— When Set Point Select (Setpoint Select, SP.SE) is configured to 1 (Setpoint 1), the unit’s active set point is based on Cooling Set Point 1 (Cooling Setpoint 1, CSP.1).
To configure this option with the Touch Pilot display:
DISPLAY NAME PATH
Setpoint Select Status GENUNIT 25 1 (Set Point 1)
LINE
NO.
VAL UE
To change this value, a Control Point Force must be applied. When configured correctly, Setpoint Control will indicate Setp 1.
To configure this option with the Navigator™ display:
ITEM ITEM EXPANSION PATH VALUE
SP.SE Setpoint Select Operating Modes SLCT Setpoint 1
Set Point 2
— When Set Point Select (Setpoint Select, SP.SE) is configured to 2 (Setpoint 2), the unit’s active set point is based on Cooling Set Point 2 (Cooling Setpoint 2, CSP.2).
To configure this option with the Touch Pilot™ display:
DISPLAY NAME PATH
Setpoint Select Status GENUNIT 25 2 (Set Point 2)
LINE
NO.
VAL UE
To change this value, a Control Point Force must be applied. When configured correctly, Setpoint Control (Status GENUNIT) will indicate Setp 2.
To configure this option with the Navigator display:
ITEM ITEM EXPANSION PATH VALUE
SP.SE Setpoint Select Operating Modes SLCT Setpoint 2
4 to 20 mA Input
— When Set Point Select (Setpoint Select, SP.SE) is configured to 3 (4-20 mA Setp), the unit’s active set point is based on an field supplied, external 4 to 20 mA signal input to the Energy Management Module (EMM). Care should be taken when interfacing with other manufacturer’s control systems, due to power supply differences of full wave bridge versus half wave rectification. The two different power sup­plies cannot be mixed. ComfortLink™ controls use half wave rectification. A signal isolation device should be utilized if a full wave bridge signal generating device is used.
The following equation is used to control the set point. See
Fig. 18.
Fahrenheit Set Point = 10 + 70(mA – 4)/16 (deg F) Celsius Set Point = –12.2 + 38.9(mA – 4)/16 (deg C) To configure this option while using a Touch Pilot display:
DISPLAY NAME PATH
Setpoint Select Status GENUNIT 25 3 (4-20 mA Input)
LINE
NO.
VAL UE
To change this value, a Control Point Force must be applied. When configured correctly, Setpoint Control will indicate 4-20 mA.
26
To configure this option while using a Navigator display:
Fig. 18 — 4 to 20 mA Set Point Control
0
10
20
30
40
50
60
70
80
90
10 12 14 16 18 20
mA Signal
Set Point
Min LWT, Cooler Fluid Type = 1, FLUD=Brine
Min LWT, Cooler Fluid Type = 1, FLUD=Water
02468
Max LWT
A30-4830
To configure this option with the Touch Pilot display:
ITEM ITEM EXPANSION PATH VALUE
SP.SE Setpoint Select Operating Modes SLCT 4-20 mA Setp
Dual Switch
— When Set Point Select (Setpoint Select, SP.SE) is configured to 4 (Dual Setp Sw), the unit’s active set point is based on Cooling Set Point 1 (Cooling Setpoint 1, CSP.1) when the Dual Set Point switch contact is open and Cooling Set Point 2 (Cooling Setpoint 2, CSP.2) when it is closed.
To configure this option while using a Touch Pilot display:
DISPLAY NAME PATH
Setpoint Select Status GENUNIT 25
LINE
NO.
4 (Dual Setpoint Switch)
VAL UE
To change this value, a Control Point Force must be applied. When configured correctly, Setpoint Control will indicate Setp Sw.
To configure this option while using a Navigator display:
ITEM ITEM EXPANSION PATH VALUE
SP.SE Setpoint Select Operating Modes SLCT
Dual Setp Sw
Chilled Water Fluid Type Selection — The chilled
water fluid must be configured. The fluid type must be config­ured to obtain the proper leaving water set point control range and freeze protection. The Cooler Fluid Type (Cooler Fluid Type , FLUD) can be set to water or brine.
FRESH WATER — Configure the unit for Cooler Fluid Type (Cooler Fluid Type, FLUD) to water for units without brine or glycol installed in the chilled water loop. The factory default fluid type is fresh water. Use this option for fresh water sys­tems. This will allow for a water temperature set point of 38 to 60 F (3.3 to 15.5 C). With water as the selection, the Freeze Point is fixed at 34 F (1.1 C).
DISPLAY
NAME
Cooler Fluid Type
PATH
Main Menu Service SERVICE1 1 1 = Water
LINE
NO.
VAL UE
To configure this option with the Navigator display:
ITEM ITEM EXPANSION PATH VALUE
FLUD Cooler Fluid Type Configuration SERV Water
BRINE OR GLYCOL OPERATION — Configure the unit for Cooler Fluid Type (Cooler Fluid Type, FLUD) to brine for brine or glycol chilled water loops. This option will allow for a set point temperature range of 14 to 60 F (–10.0 to 15.5 C). Before configuring this selection, confirm that a suitable anti­freeze has been added and is at a sufficient concentration to protect the loop. Additionally, the Brine Freeze Set Point (Brine Freeze Setpoint, LOSP) must be set for proper freeze protection operation. Set the Brine Freeze Set Point to the burst protection provided by the glycol concentration. This value will be Freeze Point for the fluid.
To configure this option with the Touch Pilot display:
DISPLAY
NAME
Cooler Fluid Type
Brine Freeze Setpoint
PATH
Main Menu
Service SERVICE1
Main Menu
Service SERVICE1
LINE
NO.
12 = Brine
3
VALU E
Dependent on fluid concentration
To configure this option with the Navigator display:
ITEM ITEM EXPANSION PATH VALUE
FLUD Cooler Fluid Type Configuration SERV Brine
LOSP
Brine Freeze Setpoint
Configuration SERV
Dependent on fluid concentration
27
Cooler Pump Control — It is required for all chillers
that the cooler pump control be utilized unless the chilled water pump runs continuously or the chilled water system contains a suitable concentration of antifreeze solution. When the Cooler Pumps Sequence is configured, the cooler pump output will be energized when the chiller enters an "ON" mode. The cooler pump output is also energized when certain alarms are generat­ed. The cooler pump output should be used as an override to the external pump control if cooler pump control is not utilized. The cooler pump output is energized if a P.01 Water Exchanger Freeze Protection alarm is generated, which provides addition­al freeze protection if the system is not protected with a suitable antifreeze solution.
The 30XW units can be configured for external cooler pump control. Cooler Pumps Sequence is the variable that must be confirmed in the field. Proper configuration of the cooler pump control is required to provide reliable chiller oper­ation. The factory default setting for Cooler Pumps Sequence is 0 (No Pump). The configuration settings for Cooler Pumps Se­quence are 1 (1 pump only) for single pump control and 2 (2 pumps auto). Configuration settings 3 (PMP 1 Manual) and 4 (PMP 2 Manual) are for dual pump control only.
If the Cooler Pumps Sequence (PUMP) is set to 1, the con­trol will start the pump. If a flow failure is detected, the unit will shut down and must be manually reset. If the Cooler Pumps Sequence (PUMP) is set to 2, the control will start the lead pump and automatically alternate the operation of the pumps to even the wear. If a flow failure is detected, the unit will shut down and the lag pump will attempt to start. If flow is established within the Unit Off to On Delay (DELY) period the unit will restart automatically.
Two manual control options are also available. When the Cooler Pumps Sequence (PUMP) is set to 3, Cooler Pump 1 will always operate. If a flow failure is detected, the unit will shut down and must be manually reset. When the Cooler Pumps Sequence (PUMP) is set to 4, Cooler Pump 2 will al­ways operate. If a flow failure is detected, the unit will shut down and must be manually reset.
For all Cooler Pumps Sequence (PUMP) settings (including
0), closure of both the chilled water flow switch (CWFS) and the chilled water pump interlock contact (connected across TB5 terminals 1 and 2) are required. In addition, for Cooler Pumps Sequence settings of PUMP = 1, 2, 3, 4, normally open auxiliary contacts for Pump 1 and Pump 2 (wired in parallel) must be connected to the violet and pink wires located in the harness from the MBB-J5C-CH18 connector. The wires in the harness are marked "PMP1-13" and "PMP1-14". See the field wiring diagram in the 30XW Installation Instructions.
Regardless of the cooler pump control option selected, if the chilled water flow switch/interlock does not close within the Unit Off to On Delay period after the unit is enabled and in an ON mode, alarm P.91 will be generated. Other conditions which will trigger this alarm include:
• Cooler pump interlock is open for at least 15 seconds during
chiller operation.
• Lag chiller in Master/Slave Control pump interlock does not
close after 1 minute of the pump start command.
• Cooler pump control is enabled and the chilled water flow
switch/interlock is closed for more than 2 minutes following
a command to shut down the pump.
The last alarm criterion can be disabled. If Flow Checked if Pmp Off (Configuration OPTN P.LOC) is set to NO, the con­trol will ignore the pump interlock input if the cooler pump output is OFF.
The ComfortLink™ controls have the ability to periodically start the pumps to maintain the bearing lubrication and seal in­tegrity. If Pump Sticking Protection (Configuration OPTN PM.PS) is set to YES, and if the unit is off at 2:00 PM, a pump will be started once each day for 2 seconds. If the unit has
2 pumps, Pump 1 will be started on even days (such as day 2, 4, or 6 of the month); Pump 2 will be started on odd days. The de­fault for this option is PM.PS=NO.
The pump will continue to run for 60 seconds after an off
command is issued. COOLER PUMP CONTROL CONFIGURATIONS No Pump Control
— To configure cooler pump control op-
tions with the Touch Pilot™ display:
DISPLAY NAME PATH
Cooler Pumps Sequence
Main Menu Config USER
LINE
NO.
8
VAL UE
0 (No Pump Control)
To configure cooler pump control options with the Naviga-
tor™ display:
ITEM ITEM EXPANSION PATH VALUE
PUMP
Single Pump Control
Cooler Pumps Sequence
Configuration OPTN No Pump
— To configure cooler pump control
options with the Touch Pilot display:
DISPLAY NAME PATH
Cooler Pumps Sequence
Pump Sticking Protection
Flow Checked if C Pump Off
Main Menu Config USER
Main Menu Config USER
Main Menu Config USER
LINE
NO.
8
15
17
VAL UE
1 (Single Pump Control)
Default = No No = Disabled Yes = Enabled
Default = Yes No = Disabled Yes = Enabled
To configure cooler pump control options with the Naviga-
tor display:
ITEM ITEM EXPANSION PATH VALUE
Cooler Pumps
PUMP
Sequence
Periodic Pump
PM.PS
Start
Flow Checked
P. LO C
if Pmp Off
Dual Pump and Manual Control
Configuration OPTN 1 Pump Only
Configuration OPTN
Configuration OPTN
Default = No No = Disabled Yes = Enabled
Default = Yes No = Disabled Yes = Enabled
— To configure cooler
pump control options with the Touch Pilot™ display:
DISPLAY NAME PATH
Cooler Pumps Sequence
Pump Auto Rotation Delay
Pump Sticking Protection
Flow Checked if C Pump Off
Main Menu
Config USER
Main Menu
Config USER
Main Menu
Config USER
Main Menu
Config USER
LINE
NO.
8
14 Default = 48 hours
15
17
VAL UE
2 (2 Pumps Automatic) 3 (Pump 1 Manual) 4 (Pump 2 Manual)
Default = No No = Disabled Yes = Enabled
Default = Yes No = Disabled Yes = Enabled
To configure cooler pump control options with the Naviga-
tor™ display:
ITEM ITEM EXPANSION PATH VALUE
PUMP
ROT.P
PM.PS
P. LO C
Cooler Pumps Sequence
Pump Rotation Delay
Periodic Pump Start
Flow Checked if Pmp Off
Configuration OPTN
Configuration OPTN
Configuration OPTN
Configuration OPTN
2 Pumps Auto PMP1 Manual PMP2 Manual
Default = 48 hours
Default = No No = Disabled Yes = Enabled
Default = Yes No = Disabled Yes = Enabled
28
Machine Start Delay — An option to delay the start of
the machine is also available. This parameter is useful in keep­ing multiple machines from starting at the same time in case of a power failure. The parameter has a factory default of 1 minute. This parameter also has a role in the timing for a chilled water flow switch alarm. The flow switch status is not checked until the delay time has elapsed.
To configure this option with the Touch Pilot display:
DISPLAY NAME PATH
Unit Off to On Delay
Main Menu
Config USER
LINE
NO.
6 Default = 1 Minute
VAL UE
To configure this option with the Navigator display:
ITEM ITEM EXPANSION PATH VALUE
DELY Minutes Off Time Configuration OPTN
Default = 1 Minute
Circuit/Compressor Staging and Loading —
The AquaForce® 30XW chillers employ one compressor per circuit. As a result, circuit and compressor staging are the same. The control has several control option parameters to load the compressors. The circuit/compressor start can be config­ured as well as the loading of each circuit/compressor.
CIRCUIT/COMPRESSOR STAGING — The control can be configured to decide which circuit/compressor starts first, by configuring Lead/Lag Circuit Select (Staged Loading Sequence, LLCS). Three options for this variable are allowed: Automatic Lead-Lag, Circuit A Leads or Circuit B Leads. The factory default is Automatic Lead-Lag.
The automatic lead-lag function determines which circuit/ compressor starts. When enabled, the control will determine which circuit/compressor starts to even the wear of the com­pressor. The compressor wear factor (combination of starts and run hours) is used to determine which compressor starts.
Compressor Wear Factor = (Compressor Starts) + 0.1 (Com­pressor Run Hours)
The circuit/compressor with the lowest compressor wear factor is the circuit that starts first.
If starting a particular circuit/compressor first is desired, that can also be configured with the same variable.
To configure this option with the Touch Pilot display:
DISPLAY NAME PATH
Circuit Loading Sequence
Main Menu
Config USER
To configure this option with the Navigator display:
ITEM ITEM EXPANSION PATH VALUE
Lead/Lag
LLCS
Circuit Select
CIRCUIT/COMPRESSOR LOADING — The control can be configured to stage the circuit/compressors. The Loading Sequence Select (Circuit Loading Sequence, LOAD) setting determines how the control will perform loading. The configu­ration can be set to Equal or Staged.
Equal Loading
— With Equal loading, the circuit which starts first will maintain the minimum stage of capacity with the slide valve fully unloaded. When additional capacity is required, the next circuit with the lowest compressor wear factor is started with its slide valve at minimum position. As additional capaci­ty is required, the slide valve for a circuit will be adjusted in approximately 5% increments to match capacity requirements.
LINE
NO.
1
Configuration
OPTN
VAL UE
0 (Automatic Lead-lag) 1 (Circuit A Leads) 2 (Circuit B Leads) Default = 0 (Automatic Lead-lag)
Range: Automatic, Cir A Leads, Cir B Leads, Cir C Leads Default – Automatic
The control will alternate between circuits to maintain the same percentage of capacity on each circuit.
Staged Loading
— If staged loading is selected, the circuit which starts first will gradually load its slide valve to match capacity requirements until the circuit is fully loaded. Once the circuit is fully loaded and additional capacity is required, the control will start an additional circuit fully unloaded. The con­trol will gradually unload the circuit which was fully loaded to match capacity requirements.
To configure this option with the Touch Pilot™ display:
DISPLAY NAME PATH
Staged Loading Sequence
Main Menu Config USER
LINE
NO.
4
VAL UE
Default = No No (Equal) Yes (Staged)
To configure this option with the Navigator™ display:
ITEM ITEM EXPANSION PATH VALUE
Loading Sequence
LOAD
Select
Configuration OPTN
Default = Equal Equal Staged
Minimum Load Control — Minimum Load Control
can be a factory-installed option or a field-installed accessory. If installed, and its operation is desired, the Minimum Load Control must be enabled. Once enabled, the valve will be oper­ational only during the first stage of cooling.
To configure this option with the Touch Pilot display:
DISPLAY NAME PATH
Hot Gas Bypass Select
Main Menu Service
FAC TORY
LINE
NO.
Default = No No (No Minimum
14
Load Control) Yes (Minimum Load Control Installed)
VAL UE
A power cycle is required for the values to take effect. To configure this option with the Navigator display:
ITEM
HGBP
ITEM
EXPANSION
Hot Gas Bypass Select
PATH VALUE
Configuration UNIT
No = No Minimum Load Control Yes = Minimum Load Control Installed
A power cycle is required for the values to take effect.
Dual Chiller Control — The dual chiller routine is
available for the control of two units installed in series or paral­lel supplying chilled fluid on a common loop. One chiller must be configured as the master chiller, the other as the slave chill­er. An additional leaving fluid temperature thermistor (dual chiller LWT) must be installed in the common chilled water piping as described in the Installation Instructions for both the master and slave chillers. See the Field Wiring section in the 30XW Installation Instructions for dual chiller LWT sensor control wiring.
The control algorithm relies on several parameters that must be field configured for operation. Both chillers must be on the same Carrier Comfort Network On both chillers, Master/Slave Select (Master/Slave Select, MSSL) must be enabled. The water piping arrangement, Chill­ers in Series (Chiller in Series, SERI), must be configured. The master chiller must be programmed with the Slave Chiller Address (Slave Address, SLVA). Additional optional pro- gramming parameters may be configured to meet application requirements.
Lead/Lag Balance Select (Lead Lag Select, LLBL) deter­mines which chiller is the lead machine. The options are Al­ways Lead, Lag if Fail, and Runtime Select. Under Runtime Select control, the lead chiller will change based on the time in­crement selected in the Lead/Lag Balance Delta configuration (Lead/Lag Balance Data, LLBD). If the run hour difference
®
bus with different addresses.
29
between the master and the slave remains less than the Lead/ Lag Balance Delta, the chiller designated as the lead will remain the lead chiller. The Lead/Lag changeover between the master and the slave chiller due to hour balance will occur dur­ing chiller operating odd days, such as day 1, day 3, and day 5 of the month, at 12:00 a.m. If a lead chiller is not designated, the master chiller will always be designated the lead chiller.
The dual chiller control algorithm has the ability to delay the start of the lag chiller in two ways. The Lead Pulldown Time parameter (Lead Pulldown Type, LPUL) is a one-time time delay initiated after starting the lead chiller, before checking whether to start an additional chiller. This time delay gives the lead chiller a chance to remove the heat that the chilled water loop picked up while being inactive during an un­occupied period. The second time delay, Lead/Lag Delay (Lag Start Timer, LLDY) is a time delay imposed between the last stage of the lead chiller and the start of the lag chiller. This pre­vents enabling the lag chiller until the lead/lag delay timer has expired.
A quicker start of the lag chiller can be accomplished by configuring the Start if Error Higher parameter (Start if Erro r Higher, LL.ER). If the difference between the common leav- ing water temperature and the set point is greater than the con­figured value, then the lag chiller will start.
A minimum on time for the lag chiller can be programmed with the Lag Minimum Running Time configuration (Lag
Minimum Running Time, LAG.M). This parameter causes the control to run the lag chiller for the programmed minimum on time. The Lag Unit Pump Select (Lag Unit Pump Control, LAGP) can be configured such that the pump can be on or off while the chiller is off. This parameter is only active in Parallel Chiller Operation.
For units with a Touch Pilot display, two additional steps must be completed to start the machine. On the master chiller, the Master Control Type must be configured for the start con­trol defined in the Machine Control configuration. To start the machines, the master chiller must be started with the Start/Stop button and Master Mode selected. The slave chiller must be started with the CCN Mode selected.
Each application, Parallel and Series, are described sepa­rately below.
DUAL CHILLER CONTROL FOR PARALLEL APPLI­CATIONS — To configure the master chiller for parallel applications using the Touch Pilot display, see Table 24. To configure the master chiller for parallel applications using the Navigator display, see Table 25. A power cycle is required for the values to take effect.
To configure the slave chiller for parallel applications using the Touch Pilot display, see Table 26. To configure the slave chiller for parallel applications using the Navigator display, see Table 27.
30
Loading...
+ 118 hidden pages