FOR 30XW LIQUID CHILLERS . . . . . . . . CL-1 to CL-7
®
DEVICE AND CSM
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be
hazardous due to system pressures, electrical components, and
equipment location. Only trained, qualified installers and service technicians should install, start up, and service this equipment. When working on this equipment, observe precautions in
the literature, on tags, stickers, and labels attached to the equipment, and any other safety precautions that apply. Follow all
safety codes. Wear safety glasses and work gloves. Use care in
handling, rigging, and setting this equipment, and in handling
all electrical components.
WARNING
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation and service. There may be more than one disconnect switch. Tag
all disconnect locations to alert others not to restore power
until work is completed.
WARNING
DO NOT VENT refrigerant relief valves within a building.
Outlet from relief valves must be vented in accordance
with the latest edition of ANSI/ASHRAE (American
National Standards Institute/American Society of Heating,
Refrigerating and Air Conditioning Engineers) 15 (Safety
Code for Mechanical Refrigeration). The accumulation of
refrigerant in an enclosed space can displace oxygen and
cause asphyxiation. Provide adequate ventilation in
enclosed or low overhead areas. Inhalation of high concentrations of vapor is harmful and may cause heart irregularities, unconsciousness or death. Misuse can be fatal. Vapor
is heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation.
Decomposition products are hazardous.
WARNING
DO NOT attempt to unbraze factory joints when servicing
this equipment. Compressor oil is flammable and there is
no way to detect how much oil may be in any of the refrigerant lines. Cut lines with a tubing cutter as required when
performing service. Use a pan to catch any oil that may
come out of the lines and as a gage for how much oil to add
to system. DO NOT re-use compressor oil.
CAUTION
This unit uses a microprocessor-based electronic control
system. Do not use jumpers or other tools to short out
components, or to bypass or otherwise depart from recommended procedures. Any short-to-ground of the control board or accompanying wiring may destroy the
electronic modules or electrical components.
CAUTION
To prevent potential damage to heat exchanger tubes,
always run fluid through heat exchanger when adding or
removing refrigerant charge. Use appropriate antifreeze
solutions in evaporator and condenser fluid loops to prevent the freezing of heat exchangers or interconnecting piping when the equipment is exposed to temperatures below
32 F (0° C). Proof of flow switch is factory installed on all
models. Do NOT remove power from this chiller during
winter shut down periods without taking precaution to
remove all water from heat exchangers. Failure to properly
protect the system from freezing may constitute abuse and
may void warranty.
CAUTION
Compressors require specific rotation. Swap any two
incoming power leads to correct compressor rotation.
2
ENTER
ESCAPE
ENTER
ALARM
INDICATOR
LIGHT
STA RT- STOP
BUTTON
LCD TOUCH
SCREEN
Fig. 1 — Touch Pilot™ Display
a30-4456 (b&w)
GENERAL
This publication contains controls, operation, start-up, service and troubleshooting information for the 30XW150-400
water-cooled liquid chillers with electronic controls. The
30XW chillers are equipped with ComfortLink™ controls and
electronic expansion valves. The AquaForce
®
30XW chillers
offer two different user interface devices, the Touch Pilot™
display and the Navigator ™ display.
Conventions Used in This Manual — The follow-
ing conventions for discussing configuration points for the
Navigator module and Touch Pilot display will be used in this
manual.
Point names for the Touch Pilot display will be shown in
bold. See Appendix A for a complete list of point names. Item
names for the Navigator module will be shown in bold italics.
See Appendix B for the complete path name preceding the item
name. The point and item names in Appendices A and B will
be listed in alphabetical order and the path name for each will
be written with the mode name first, then any sub-modes, each
separated by an arrow symbol ( .
This path name will show the user how to navigate through the
Navigator module or the Touch Pilot display to reach the desired
configuration. The user would scroll through the modes and submodes using the and keys on the Navigator display. For
the Touch Pilot display, the user would simply touch the menu
item on the screen. The arrow symbol in the path name represents
pressing to move into the next level of the menu structure for the Navigator module, or touching the menu item on the
screen for the Touch Pilot display.
When a value is included as part of the point name, it will be
shown after the point name after an equals sign. If the value
represents a configuration setting, an explanation will be
shown in parentheses after the value. The Touch Pilot name
will be shown first with the Navigator name following. As an
example,
(Staged Loading Sequence = 1, LLCS = Circuit A leads).
Press the and keys simultaneously on
the Navigator module to display an expanded text description of
the point name or value. The expanded description is shown in the
Navigator display tables (Appendix B) but will not be shown with
the path names in text. The Touch Pilot display will show an expanded description of the point name. To view the expanded point
name for the Touch Pilot display go to Appendix A.
The Touch Pilot display configures the unit via the CCN
(Carrier Comfort Network
®
) Tables, which are located in Ap-
pendix C of this manual.
Display Module Usage
TOUCH PILOT DISPLAY — The Touch Pilot display is the
standard user interface for the AquaForce 30XW chillers with
the ComfortLink control system. The display includes a large
LCD (liquid crystal display) touch screen for display and user
configuration, a Start/Stop button, and an Alarm Indicator LED
(light-emitting diode). See Fig. 1.
The Touch Pilot display can be used to access various
Carrier Comfort Network
circumstances, contact your Carrier representative.
Operation of the Touch Pilot display is driven from the
displays on the touch screen. The Touch Pilot display uses the
following screen “buttons” to allow the user to operate the display and navigate within and between screens.
“BACK” returns to the next higher screen in the
hierarchy.
®
devices. For operation under these
“HOME” displays the Default Group Display screen
for Touch Pilot display. The Default Screen is a userconfigured display of up to 9 points on each of 8 screens. This
allows for quick access to various, frequently viewed points,
without navigating through the Main Menu structure. This button is available at all menu levels and returns the user to the
first Default Group Display screen.
“MAIN MENU” displays the Main Menu screen. This
allows access for viewing and configuration, where
possible, of all points supported by the controller. This includes
points such as set point and operational configuration. This
button is available at all menu levels and returns the user to the
Main Menu screen.
“PREVIOUS” moves the user to the next earlier
screen in a group of sequential screens of the same
type.
“NEXT” advances the user to the next screen in a
group of sequential screens of the same type.
“OK” agrees with, or says “yes” to a prompt and per-
forms the appropriate processing.
“NO” rejects, or says “no” to a prompt and performs
the appropriate processing.
“CANCEL” terminates an ongoing action and returns
to the current screen without any other processing.
“CLEAR DATA” clears the data value in a data entry
dialog box. This button is used to clear incorrect data.
“RESET DATA” zeros the data value in a data entry
dialog box.
“ADD” adds the active point to a Group Display
screen.
“REMOVE” deletes a point from a Group Display
screen.
“INCREASE” modifies the value of a field within its
defined limits or “SCROLL UP” and shifts the screen
view up by one item.
“DECREASE” modifies the value of a field within its
defined limits or “SCROLL DOWN” and shifts the
screen view down by one item.
“PAGE DOWN” will replace the items currently on
the screen with the next group of items if the current
table or list has more data than will fit on the screen.
“PAGE UP” will replace the items currently on the
screen with the previous group of items if the current
table or list has more data than will fit on the screen.
“FORCE” begins the process of forcing or overriding
the value of a point.
“AUTO” begins the process of removing a force from
a point.
“MODIFY” begins the process of modifying a config-
uration value.
3
“ALARM INDICATOR LIGHT” activates when a
Fig. 2 — Group Display Screen
Fig. 3 — Point Data Dialog Box
Fig. 4 — Main Menu Display
a30-4910.ep
a30-4471
a30-4472
PDS-XAXQXWPDS-XAXQXW
new alarm condition occurs. The alarm indicator light
LED, located on the right side of the display, remains
activated until it is manually reset using the Reset button on the
Main menu.
“START/STOP BUTTON” enables the user to start
or stop the chiller from the Touch Pilot™ display.
See Enable-Off-Remote Contact Switch (SW1) on
page 16 for additional information.
Several items are password protected. When required, a
Password dialog box will be displayed for field input of the
password. The default password is 3333. The password can be
changed if desired.
Power-Up Display
— When the Touch Pilot display is powered up, it displays an initialization progress bar and attaches
(initiates communication) to the Main Base Board. The Touch
Pilot display then shows that controller’s default Group Display screen. See Fig. 2. This is a user-configured display screen
with up to 9 points on 8 separate screens. For more information
on adding or removing points from the Group Display screen,
see the Group Display Screens section on page 7.
Touch any of the screen point buttons and Point Data Dialog
box will be displayed with expanded information. In the example shown, the CTRL_PNT button in the bottom left corner
was selected. See Fig. 2 and 3.
To exit the box, press .
Main Menu Display
— The default screen for the Touch Pilot
controller is the Group Display screen. To access the Main
Menu, press the button. The screen shown in Fig. 4 will be
displayed. Selecting a button will display the screens associated with that category. The user can also access the login screen
from the Main Menu if needed.
Touch Pilot Menu Structure
— The user can navigate through
the Touch Pilot display screens by selecting the buttons that appear on the screen. When a button is selected, either a submenu or a list of point names and values will be shown. Submenus will display a list of associated point names. See Fig. 5
for the Touch Pilot menu structure.
If the list of point names and values are shown, the top line
of the display is the table name. The line and total line counter
is displayed in the upper right corner of the display. Selecting
an item will cause a Point Data dialog box to appear.
Setup Menu Screen
— The Setup Menu screen, shown in
Fig. 6, is accessed by pressing the Setup button from the Main
Menu. This configuration allows the user to configure the basic
operation and look of the display. Table 1 summarizes the Setup Menu functions.
4
User interface
Group display x 8Main menu
Status
GENUNIT
CIRCA_AN
CIRCA_D
CIRCB_AN
CIRCB_D
CIRCC_D
CIRCC_AN
STATEGEN
RECLAIM
MODES
STRTHOUR
FANHOURS
FREECOOL
QCK_TST1
QCK_TST2
SERV_TST
SetpointSchedule
OCC1PO1S
OCC2PO2S
Service
FACTORY
FACTORY2
SERVICE1
CP_UNABL
UPDTHOUR
UPDHRFAN
MAINTCFG
Maint
LOADFACT
FANCTRL
M_MSTSLV
DEFROSTM
LAST_POR
PR_LIMIT
BOARD_PN
SERMAINT
EXV_CTRL
CUR_PHAS
OCCDEFCFM
Config
Ctrl-ID
DISPCONF
USER
MST_SLV
CFG_TAB1
…
…
CFG_TAB8
BRODEFS
OCCDEFCS
HOLIDAY
ALARMDEF
Alarms
ALARHIST
ALARHIS2
ALAM_CUR
ResetTimeAttachSetup
Regional
Language
Contrast
Backlight
Calibrate
Password
Display
CCN
Login
Fig. 5 — Touch Pilot™ Display Menu Structure
a30-4829
5
Table 1 — Setup Menu
Fig. 6 — Setup Menu Display
a30-4474
SETUP MENU BUTTONFUNCTION
This button specifies the time and date format and the base unit of measure. Time display can be configured as
REGIONAL
LANGUAGE
CONTRAST
BACKLIGHTThis button specifies whether backlighting should be kept on at all times or turned off during inactive periods.
CALIBRATE
PASSWORDS
DISPLAY
CCNThis button is used to configure the bus and element numbers and the baud rate of the control on the network.
12-hour AM/PM setting or as a 24-hour setting. The date can be formatted in one of 3 settings, MM-DD-YYYY (MonthDay-Year), DD-MM-YYYY (Day-Month-Year), or YYYY-MM-DD (Year-Month-Day). Units of measure can be either US
(English) or Metric (SI).
This button selects the active language and font of the display. Available languages are English and Spanish (Espanol).
If a preferred language is not available, additional software for the Main Base Board (MBB) and the Touch Pilot™ display are required. Contact your Carrier representative for instructions and software.
This button adjusts the LCD contrast. Press and hold the [MOON] button to increase/darken the contrast or the [STAR]
button to decrease/lighten the current contrast.
NOTE: Touching the screen anywhere for 5 seconds while powering-up will prompt the user to restore contrast and
calibration settings to factory defaults.
This button is used to adjust the LCD touch screen calibration. Touch the screen in the circular targets located first in
the upper left and then in the lower right corner of the screen to adjust.
This button is used to configure the limited and full logged-in access system passwords. In order to change passwords,
the user must be logged in with full access to view and change the passwords. All passwords must consist of 4-digits,
which can be entered using the numeric keypad. Access levels and associated privileges are as follows:
Limited Logged-in Access - Provides the user with read/write access to all available tables (except service configuration tables, where the user will not be permitted to modify point data, and Group Display tables, where the user will not
be permitted to add points.) This access level also provides read/write access to all Touch Pilot display setup properties
except Display, CCN, and Password.
Full Logged-in Access - Provides user with read/write access to all available tables for the attached device and all
Touch Pilot display properties.
If the user does not log in, read-only access to all tables is allowed. The user will be prompted to log in when attempting
to access password-required functions.
This button is used to view the description data and part number from the Ctlr-ID Table and to specify the Operating
Mode. The Operating mode can be configured for Equipment mode or Network mode. For Touch Pilot displays that are
standard with the unit, Operating mode should not be changed from Equipment mode. Equipment mode provides
access only to the chiller’s MBB via the Local Equipment Network (LEN) Bus. For remote access, a remote Touch Pilot
display can be set to Network mode. Network mode provides access to all devices on the CCN (Carrier Comfort Net-
®
work
) bus.
NOTE: When changing the operating mode, a power cycle is required in order for the new operating mode to take
effect. The user should view and correct the following CCN data: address and baud rate, alarm acknowledger, and
broadcast acknowledger designation.
6
Setting the Time and Date
ENTER
ESCAPE
ESCAPE
ENTER
ESCAPE
ENTER
ESCAPE
ESCAPE
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
— The ComfortLink™ control has
a time and date function. This can be useful for diagnostics to
determine when alarms occur. The control is factory configured for the proper date and is set for the Eastern Time Zone.
The date and time zone must be checked and corrected if necessary, to allow the machine to function on an internal time
schedule and to display a proper time and date stamp for
alarms. The time and date is displayed on the Group Display
Screen.
To change the Time and Date, press the Main Menu
button. Select Time. On the display, a day and date box
with a time box will be shown. To change the day and date,
press the day and date box. A calendar will be displayed. If the
correct month is displayed, touch the correct date. If the wrong
month is displayed, use the or to change to the correct
month and select the correct date. The date will highlighted.
Press to accept the change. The previous screen will be
displayed with the corrected day and date shown. To correct
the time, use the or on the left to change the hour. Use
the or on the left to change the minutes. Continuously
touching the or will sequence the numbers. The time is
shown in a 24-hour format. To accept the changes, press the
or buttons. A “Save” dialog box is displayed with the
words, “Do you wish to save changes?” Press to accept
the changes.
Group Display Screens
— The Touch Pilot™ display supports up to eight Group Display screens. Group Display
screens show status information along the top of the screens
and 9 buttons that display 9 point names and point values that
are chosen by the user. All Group Display screen points are
user configurable. The bottom line of the screen contains navigation buttons that can be used to move between the Group
Display screens.
Pressing a point button will show that point’s Point Data
dialog box. See Fig. 2 and 3. This box contains buttons that
remove the point from the group display and apply or remove a
force (point override). When touching any button in the display
screen, the button will be outlined to acknowledge input. There
may be a delay in response to input, but if the button is outlined, do NOT press any other button until the previous input
has been processed.
If there is a communication failure with the MBB (Main
Base Board), all point buttons will be displayed in inverse video and the message Communication Failure will be displayed
in the top left line of the screen.
Default Group Designation — The default group is the first of
the 8 Group Display screens. This is the default screen of the
display. Information on this screen as well as the other 7
screens can be user-modified to meet the needs of the site.
To Add A Point To A Group Display — From the Main Menu,
press the desired menu button (Status, Setpoint, Service,
Maint, or Config) and, if necessary, the sub-menu button to
access the point to be added. Press the point button to show the
source point’s Point Data dialog box. See Fig. 3. From the
Point Data dialog box, press the ADD button. The display will
show the last Group Display accessed. Use the navigation buttons to access the destination Group Display. Press an existing
point button or a blank button to update the highlighted button
with the source point’s name. Press to add the highlighted
point to the group and return to the table display.
To Remove A Point From A Group Display — From the Point
Data Dialog box, press the REMOVE button and follow the
prompts. The display will return to the Group Display screen
from which the point was removed, and the button corresponding to the deleted point will be blank and disabled.
NAVIGATOR™ DISPLAY MODULE — The Navigator display module provides a mobile user interface to the
ComfortLink control system. The display has up and down arrow keys, an key, and an key. These keys
are used to navigate through the different levels of the display
structure. Press the key until ‘Select a Menu Item’ is
displayed. Use the up and down arrow keys to move through
the top 11 mode levels indicated by LEDs on the left side of the
display. See Fig. 7. See Table 2 and Appendix B for more details about the display menu structure.
Once within a mode or sub-mode, a “>” indicates the
currently selected item on the display screen. Pressing the
and keys simultaneously will put the
Navigator module into expanded text mode where the full
meaning of all sub-modes, items, and their values can be displayed. Pressing the and keys when the
display says ‘Select Menu Item’ (Mode LED level) will return
the Navigator module to its default menu of rotating display
items (those items in Run StatusVIEW). In addition, the
password will be disabled, requiring that it be entered again before changes can be made to password protected items. Press
the key to exit out of the expanded text mode.
When a specific item is located, the item name appears on
the left of the display, the value will appear near the middle of
the display and the units (if any) will appear on the far right of
the display. Press the key at a changeable item and
the value will begin to flash. Use the up and down arrow keys
to change the value, and confirm the value by pressing the
key.
Changing item values or testing outputs is accomplished in
the same manner. Locate and display the desired item. Press
so that the item value flashes. Use the arrow keys to
change the value or state and press the key to accept
it. Press the key to return to the next higher level of
structure. Repeat the process as required for other items.
Items in the Configuration and Service Test modes are password protected. The words Enter Password will be displayed
when required, with 1111 also being displayed. The default
password is 0111. Use the arrow keys to change each number
and press to accept the digit. Continue with the
remaining digits of the password. The password can only be
changed through CCN operator interface software such as
ComfortWORKS
Power-Up Display
®
, ComfortVIEW™ and Service Tool.
— When the Navigator display is powered
up it will display:
ComfortLink
Navigator
By
Carrier
7
This indicates an initialization period while the Navigator™
ENTER
ENTER
ENTER
ENTER
ENTER
ESCAPE
ENTER
ENTER
ENTER
ENTER
ENTER
Run Status
Service Test
Temperatures
Pressures
Setpoints
Inputs
Outputs
Configuration
Time Clock
Operating Modes
Alarms
ENTER
ESC
MODE
Alarm Status
Comfort
Link
Fig. 7 — Navigator Display Module
a30-3924
display initiates communication with the Main Base Board.
Once communication is established, the default rotating display will be shown. If communication is not established, the
Navigator module will display:
Communication
Failure
If the Navigator module is connected to a Main Base Board
without software loaded, the display will remain at the
powered-up initialization display.
Setting the Time and Date
— The ComfortLink control has a
time and date function. This can be useful for diagnostics to determine when alarms occur. The control is factory configured
for the proper date and for use in the Eastern Time Zone. The
control must be checked and corrected if necessary. The correct
time is important if the machine is to function on an internal
time schedule and display a proper time and date stamp for
alarms. The time and date will be displayed on the default rotating display of the Navigator module. The time and date can
also be checked and changed under the Time Clock mode as
described below.
ITEMITEM EXPANSIONPATHVALUE
HH.MMTime of DayTime Clock TIMEXX.XX
To change the time, press the arrow key to move to the correct hour and press . The minutes can be changed in a
similar manner.
To check or change the date, the following items must be
checked and changed if necessary.
ITEMITEM EXPANSIONPATHVALUE
MNTHMonth of YearTime Clock DATEWW
DOMDay of MonthTime Clock DATEXX
DAY Day of WeekTime Clock DATEYY
YEARYear of CenturyTime Clock DATEZZ
NOTE: WW is the current month of the controller, (01=January,
02=February, etc.).
XX is the current day of the month
YY is the day of the week, (01=Monday, 02-Tuesday, etc.)
ZZ is the year of the century, (06=2006, 07=2007)
Changing the Unit of Measure — The Navigator display has
two options for unit of measure on the display, English or SI
(metric). The factory default for the units of measure is
English. To change the unit of measure, the following item
must be changed.
Adjusting the Contrast
— The contrast of the display can be
adjusted to suit ambient conditions. To adjust the contrast, enter
the LED Test mode of the device.
ITEMITEM EXPANSIONPATHVALUE
TESTTest Display LEDsConfiguration DISP
Pressing will access the TEST point. Pressing
again will cause the “OFF” to flash. Use the up or
down arrow to change “OFF” to “ON.” Pressing will
illuminate all LEDs and display all pixels in the view screen.
Pressing and simultaneously allows the
user to adjust the display contrast. The display will read:
Adjust Contrast
- - - -+ - - - - - - - - - - - - - - Use the up or down arrows to adjust the contrast. The
screen’s contrast will change with the adjustment. Press
to accept the change. The Navigator module will
keep this setting as long as it is plugged in to the LEN (Local
Equipment Network) bus.
Adjusting the Backlight Brightness
— The backlight of the
display can be adjusted to suit ambient conditions. The factory
default is set to the highest level. To adjust the backlight of the
Navigator module, enter the LED Test mode of the device.
ITEM ITEM EXPANSIONPATHVALUE
TEST Test Display LED’s Configuration Mode DISP
Pressing will access the TEST point. Pressing
again will cause the “OFF” to flash. Use the up or
down arrow to change “OFF” to “ON.” Pressing will
illuminate all LEDs and display all pixels in the view screen.
Pressing the up and down arrow keys simultaneously allows
the user to adjust the display brightness. The display will read:
Adjust Brightness
- - - - - - - - - - - - - - - - - +
Use the up or down arrow keys to adjust screen brightness.
Press to accept the change. The Navigator module
will keep this setting as long as it is plugged in to the LEN bus.
ITEM ITEM EXPANSIONPATHVALUE
METR Metric DisplayConfiguration DISP
Changing the Display Language
— The Navigator display
OFF – English
ON – SI (Metric)
has five language options to select from, English, Espanol,
Francais, Portugues, and Translated. The “Translated” option is
not supported at this time. The factory default language is
English. To change the display language, the following item
must be changed.
ITEMITEM EXPANSIONPATHVALUE
LANG Language Selection Configuration DISP
NOTE: When the Language Selection (Configuration
English
Espanol
Francais
Portugues
Translated
DISP LANG) variable is changed, all appropriate display
expansions will immediately change to the new language. The
four letter/digit code will not change. No power-off or control
reset is required when reconfiguring languages.
8
RUN
221
221
221
221
195
195
195
195
195
195
195
CH1CH2 CH3
CH4
CH11 CH12
LOCATION OF
SERIAL NUMBER
CH13
CH14
CH
15A
J4
ANALOG
INPUTS
J3
J2C
J2B
24 VAC
J1A
+ G –
DISCRETE
INPUTS
J5A
CH
15a
11
C16
J2A
TR1 TR2 TR3 TR4 TR5
CH19 CH20 CH21 CH22 CH23 CH24 CH25 CH26
J8
CH17
CH18
J5B
J5C
THERMISERS PRESSURES
CH5
CH6CH7CH8
CH9
J7AJ7B
J7C
J7D
RELAY
OUTPUTS
MOV1
C41
C42 C43
C32
C33
C34
C35
12/11
12/11
J10
LEN
+ G -
STATUS
J9A
K1
K2
D15
J6
CCN
CH10
+ G –
SIO
(LEN)
J9C
J9B
+ G –
LEN
LEN
CCNJ13J9D
+C+CCH
16a+CCH16b
Fig. 8 — Main Base Board
a30-4255
STATUS
Auto Display
(VIEW)
Machine
Starts/Hours
(RUN)
Compressor
Run Hours
(HOUR)
Compressor
Starts
(STRT)
Fan Run
Hours
(FAN)
Compressor
Disable
(CP.UN)
Predictive
Maintenance
(MAIN)
Software Versions
(VERS)
SERVICE
TEST
Manual
Test Mode
(TEST)
Quick
Test Mode
(QUIC)
Table 2 — ComfortLink™ Navigator™ Display Menu Structure
MODE
TEMPERATURES PRESSURES
Unit
Temperatures
(UNIT)
Circuit A
Temperatures
(CIR.A)
Circuit B
Temperatures
(CIR.B)
Circuit C
Temperatures
(CIR.C)
Circuit A
Pressures
(PRC.A)
Circuit B
Pressures
(PRC.B)
Circuit C
Pressures
(PRC.C)
SET
POINTS
Cooling
Setpoints
(COOL)
Heating
Setpoints
(HEAT)
Misc.
Setpoints
(MISC)
INPUTS OUTPUTS CONFIGURATION
General
Inputs
(GEN.I)
Circuit A
Outputs
(CIR.A)
Circuit B
Outputs
(CIR.B)
Circuit C
Outputs
(CIR.C)
General
Outputs
(GEN.O)
Display
Configuration
(DISP)
Unit
Configuration
(UNIT)
Service
Configurations
(SERV)
Options
Configuration
(OPTN)
Reset,
Demand Limit,
Master/Slave
(RSET)
TIME
CLOCK
Time of Day
(TIME)
Day, Date
(DATE)
Schedule 1
(SCH1)
Schedule 2
(SCH2)
Holidays
(HOLI)
Service
Maintenance
Configuration
(MCFG)
OPERATING
MODES
Operating
Control Type
(SLCT)
Operating
Modes
(MODE)
ALARMS
Reset Current
Alarms
(R.ALM)
Current
Alarms
(ALRM)
Alarm
History
(H.ALM)
CONTROLS
General —
the ComfortLink™ electronic control system that controls and
monitors all operations of the chiller. The control system is
composed of several components as listed in the following sections. All machines have a Main Base Board (MBB), Touch Pilot™ module or Navigator™ device, electronic expansion
valve board (EXV), auxiliary board, Compressor Protection
board, Emergency On/Off switch, and an Enable-Off-Remote
Contact switch.
The 30XW water-cooled liquid chillers contain
Main Base Board (MBB) — The MBB is the core of
the ComfortLink control system. It contains the major portion
machine. See Fig. 8. The MBB continuously monitors input/
output channel information received from its inputs and from
all other modules. The MBB receives inputs from status and
feedback switches, pressure transducers and thermistors. The
MBB also controls several outputs. Some inputs and outputs
that control the chiller are located on other boards, but are
transmitted to or from the MBB via the internal communications bus. Information is transmitted between modules via a
3-wire communication bus or LEN (Local Equipment Network). The CCN (Carrier Comfort Network
®
) bus is also supported. Connections to both LEN and CCN buses are made at
TB3. For a complete description of Main Base Board inputs
and outputs and their channel identifications, see Table 3.
of operating software and controls the operation of the
9
Table 3 — Main Base Board Inputs and Outputs
DESCRIPTIONINPUT/OUTPUTI/O TYPEDISPLAY MODULE POINT NAME
Power (24 vac supply)———
Local Equipment Network———
Carrier Communication
Network
Chilled Water Flow SwitchCWFSSwitchCooler Flow Switch, LOCK
is one CPM per compressor. See Fig. 9. The device controls the
compressor contactors, oil solenoid, and loading/unloading the
solenoid. The CPM also monitors the compressor motor temperature, high pressure switch, oil level switch, discharge gas
temperature, oil pressure transducer, motor current, MTA
(must trip amps) setting and economizer pressure transducer
(sizes 175,200,350,400 only). The CPM responds to commands from the MBB (Main Base Board) and sends the MBB
the results of the channels it monitors via the LEN (Local
Equipment Network). The CPM has three DIP switch input
banks, Switch 1 (S1), Switch 2 (S2), and Switch 3 (S3). The
CPM board DIP switch (S1) configures the board for the type
of starter, the location and type of the current transformers and
contactor failure instructions. See Table 4 for description of
DIP switch 1 (S1) inputs. See Appendix D for DIP switch
settings.
10
DIP
Fig. 9 — Compressor Protection Module
a30-4215
SWITCH 2
(S2)
DIP
SWITCH 3
(S3)
SMT
CT1
CT2
CT3
J8
102
J10B
CH04
5
S
PRESS
OIL
100K
J10A
CH03
R
5
S
R
PRESS
ECO
TMP
TMP
J9
DG
CH02
R
R
R20
102
102
0N
S3
123 4
MOT
CH01
J11
12
AUX
151
151
151
102
0N
123 45678
S2
0N
S1
123 45678
11
151
151
151
151
102
MTA
40
K
40
K
J2
13CH14
12
CH
CH
151
151151151
151
151
151
151
151
102
10
11
CH
151
06
C
CH
LOADERS OLS MOTOR COOLING
2x
151
151
2
561
561
CH
24 VDC/OLL
05
C
CH
HPS
1
2x
561
2
561
620
101
LOCATION OF
SERIAL NUMBER
151
151
151
151
J4
100 K
100 K
101
101
101
101
09
CH
SIO
(LEN)
SI0 STATU S
(LEN)
STAT US
SWITCH 1
– G +
3 2 1
DIP
(S1)
J12
– G +
3 2 1
01
J1
J5
08
07
J3
CH
CH
02
Table 4 — DIP Switch 1 (S1) Inputs
DIP SWITCH POSITIONFUNCTIONSETTING MEANING
1
2, 3
4, 5, 6
7
8Not Used——
The CPM board DIP switch S2 setting determines the must
trip amps (MTA) setting. See Appendix D for DIP switch settings. The MTA setting which is calculated using the settings
S2 must match the MTA setting in the software or an MTA
alarm will be generated.
Starter ConfigurationOFFAcross-the-line Start
ONWye-Delta Start
Current Transformer (CT) PositionOFF (2), OFF (3)CT is located in the main line
ON (2), OFF (3)CT is located in the Delta of the motor
OFF (2), ON (3)Reserved for future use
ON (2), ON (3)Invalid; will cause MTA configuration alarm
Current Transformer (CT) SelectionOFF (4), OFF (5), OFF (6)100A/1V CT1
ON (4), OFF (5), OFF (6)100A/0.503V CT2
OFF (4), ON (5), OFF (6)100A/0.16V CT3
ON (4), ON (5), OFF (6)Invalid; will cause MTA configuration alarm
OFF (4), OFF (5), ON (6)Invalid; will cause MTA configuration alarm
ON (4), OFF (5), ON (6)Invalid; will cause MTA configuration alarm
OFF (4), ON (5), ON (6)Invalid; will cause MTA configuration alarm
ON (4), ON (5), ON (6)Invalid; will cause MTA configuration alarm
Contactor Failure ActionOFFAll units should be off
ONUsed when Shunt Trip is available in the unit
See below for CPM board DIP switch S3 address informa-
tion. See Table 5 for CPM inputs and outputs.
CPM-A DIP Switch 31234
Address:OFFOFFOFFOFF
CPM-B DIP Switch 31234
Address:OFFOFFONOFF
11
Table 5 — Compressor Protection Module Inputs and Outputs*
DESCRIPTIONINPUT/OUTPUTI/O TYPEDISPLAY MODULE POINT NAME
Power (24 vac supply)———
Local Equipment Network———
Circuit X High Pressure SwitchHPS-XSwitchNot available
Oil Level SwitchOil LS XSwitchCircuit X Oil Solenoid, OLS.X
Must Trip Amps†MTA (S2)8-Pin DIP SwitchMust Trip Amps, MTA.X
CPM-X-JP12
1RS485 Port (D+)
2RS485 Port (Gnd)
3RS485 Port (D-)
CPM-X-J12
1RS485 Port (D+)
2RS485 Port (Gnd)
3RS485 Port (D-)
CPM-X-J7-CH05
1
2
CPM-X-J6-CH06
1
2
CPM-X-J9-CH01
1
2
CPM-X-J9-CH02
1
2
CPM-X-J10B-CH04
5V+ 5 vdc ref
SSignal
RReturn
CPM-X-J10A
5V+ 5 vdc ref
SSignal
RReturn
CPM-X-J8-CH01
1
2
CPM-X-J8-CH02
1
2
CPM-X-J8-CH3
1
2
CPM-X-J1-CH07
1
2
CPM-X-J2-CH8
1
2
CPM-X-J2-CH9
1
2
CPM-X-J2-CH12
1
2
CPM-X-J2-CH13
1
CPM-X-J2-CH14
1
2
12
1
2
3
4
5
6
7
8
ON
100
100
257-01
712
100K
100K
100
1
2
3
4
5
3
2
1
-
G
+
J3
1
2
3
4
5
J2A EXVA
J2B EXVB
24VAC
STATUS
MOV1
LOCATION OF
SERIAL NUMBER
432 1
THATHB
D4
D6
J1
C15
C16
D5
U5
Q2Q1
L4
U4
12/11
C17
+
Q45
Q42Q37
G2
Q35
Q25
Q27
Q30
Q20
Q22
Q17
Q15
Q12
Q10
C10
Q7
S1
C11
U2
D2
L1
U1
C37C39
SB
D15
U6
C25
C49
Q4
Q5
L2
R2
R3 L3
D1
R9
TEMP
D29
D9 D8
SI0
(LEN)
COMM J4
DIP
SWITCH
Fig. 10 — EXV Board
a30-4216
Electronic Expansion Valve (EXV) Board —
The 30XW150-325 units have one EXV board. The
30XW350,400 units have one EXV board per circuit. See
Fig. 10. The board is responsible for monitoring the suction gas
temperature and economizer gas temperature thermistors. The
board also signals the main EXV and economizer EXV
(ECEXV) motors to open or close. The electronic expansion
valve board responds to commands from the MBB and sends
the MBB the results of the channels it monitors via the LEN
(Local Equipment Network). See below for DIP switch information. See Tables 6 and 7 for EXV inputs and outputs.
EXV BOARD 1
(150-400)
123456 7 8
DIP SWITCH
Address:ON ON ON ON ON ON OFF ON
EXV BOARD 2
(350,400)
DIP SWITCH
1 23456 7 8
Address:OFF ON ON ON ON ON OFF ON
13
Table 6 — EXV1 Board Inputs and Outputs (30XW150-325)
DESCRIPTIONINPUT/OUTPUTI/O TYPEDISPLAY MODULE POINT NAME
Power (24 vac supply)———
Local Equipment Network———
Circuit A Suction Gas ThermistorSGTA5k ThermistorCompressor Suction Temp, SGT.A
Circuit B Suction Gas ThermistorSGTB5k ThermistorCompressor Suction Temp, SGT.B
Circuit A EXVEXV-AStepper MotorEXV Position, EXV.A
Circuit B EXV
(size 325 only)
EXV-BStepper MotorEXV Position, EXV.B
CONNECTION POINT
PinNotation
EXVA-J1
1124 vac
12Ground
EXVA-J4
1RS485 Port (D+)
2RS485 Port (Gnd)
3RS485 Port (D–)
EXVA-J3
TH
A
EXVA-J3
TH
B
EXVA-J2A
1
2
3
4
EXVA-J2B
1
2
3
4
Table 7 — EXV1,2 Board Inputs and Outputs* (30XW350,400)
DESCRIPTIONINPUT/OUTPUTI/O TYPE
Power (24 vac supply)———
Local Equipment Network——
Circuit X Suction Gas ThermistorSGT X5k ThermistorCompressor Suction Temp, SGT.X
Circuit X Economizer Gas ThermistorECT X5k ThermistorEconomizer Gas Temp, ECT.X
Circuit X EXVEXV-XStepper MotorEXV Position, EXV.X
Circuit X Economizer EXVECEXV-XStepper MotorCir X Economizer EXV Pos, ECO.X
*“X” denotes the circuit: 1 = Circuit A; 2 = Circuit B.
DISPLAY MODULE POINT NAME
—
CONNECTION POINT
PinNotation
EXVX-J1
1124 vac
12Ground
EXVX-J4
1RS485 Port (D+)
2RS485 Port (Gnd)
3RS485 Port (D–)
EXVX-J3
TH
A
EXVX-J3
TH
B
EXVX-J2A
1
2
3
4
EXVX-J2A
1
2
3
4
14
MLV/Condenser Board — One auxiliary board is op-
1
2
3
4
5
6
7
8
ON
100K
100K
100K
CH1
CH2CH3
CH4CH5 CH6CH7CH8
TR1TR2TR3TR4TR5TR6TR7TR8
STAT USSIO (LEN)
LOCATION OF
SERIAL NUMBER
24 VAC
CH13 CH14
J9
J1
CH9
CH10
CH11
CH12
JP2
C61
CH13
D12
JP1
L3
L5
U21
L2
D6
D5
Q5
Y1
D7
D8
S1
D3
U1
Q1
U5
U6
U7
U8
U9
Q10
Q11
U10
J4
J3
J2
U4
U2
Q12
Q60
3 2 1
– G +
3 2 1
– G +
DIP SWITCH
Fig. 11 — Auxiliary Board with Optional Minimum Load Control or Head Pressure Control
a30-4046
tionally installed in each unit. See Fig. 11. The auxiliary board
contains an analog output for head pressure control and discrete outputs for minimum load control. The auxiliary board
responds to commands from the MBB and sends the MBB the
results of the channels it monitors via the Local Equipment
Network (LEN). See below for auxiliary board A, B and C DIP
switch addresses. See Table 8 for inputs and outputs.
AUX BOARD
DIP SWITCH
Address:OFF ON OFF OFF ON OFF ON OFF
123 45678
Table 8 — Auxiliary Board Outputs
DESCRIPTIONINPUT/OUTPUTI/O TYPEDISPLAY MODULE POINT NAME
-RS485 Port (D-)
+RS485 Port (D+)
GRS485 Port (Gnd)
-RS485 Port (D-)
AUX-C H9
+Signal
-Ground
15
Enable-Off-Remote Contact Switch (SW1) —
Fig. 12 — Energy Management Module
221
221
221
221
100K
100K
100K
100K
100K
CH
17
CH
17
CH
16
CH
CH
18
CH
19
CH
20
CH
22
CH
21
CH
23
24 VAC
12 11
CH
11b
CH
12
CH
13
CH
14
CH
15
CH
1
CH
2
CH
3
CH
4
CH 5
CH 6
CH 7
SIO LEN
+ G -
+ G -
SIO LEN
J8
J7B
J7A
J6
J5
J4J3J2B
J2A
J1
J9A
J9B
a30-4911
This switch is installed in all units and provides the owner and
service person with a local means of enabling or disabling the
machine. It is a 3-position switch and it is used to control the
chiller. When switched to the Enable position, the chiller will
be under its own control. When switched to the Off position,
the chiller will shut down. When switched to the Remote Contact position, a field-installed dry contact can be used to start
the chiller. The contacts must be capable of handling a 24-vac,
50-mA load. In the Enable and Remote Contact (dry contacts
closed) positions, the chiller is allowed to operate and respond
to the scheduling configuration, CCN configuration, and set
point data.
For units with a Touch Pilot™ display, the position of the
Enable/Off/Remote contact switch is ignored except when the
Remote Mode operating type is selected. Refer to the Machine
Control Methods section on page 20 for more details.
Emergency On/Off Switch (SW2) — This switch is
installed in all units. The Emergency On/Off switch should
only be used when it is required to shut the chiller off immediately. Power to all modules is interrupted when this switch is
off and all outputs from these modules will be turned off.
Energy Management Module (EMM) — The EMM
is available as a factory-installed option or as a field-installed
accessory. See Fig. 12. The EMM receives 4 to 20 mA inputs
for the temperature reset, cooling set point and demand limit
functions. The EMM also receives the switch inputs for the
field-installed second stage 2-step demand limit and ice done
functions. The EMM communicates the status of all inputs
with the MBB, and the MBB adjusts the control point, capacity
limit, and other functions according to the inputs received. See
Table 9.
CAUTION
Care should be taken when interfacing with other manufacturer’s control systems due to possible power supply differences, full wave bridge versus half wave rectification,
which could lead to equipment damage. The two different
power supplies cannot be mixed. ComfortLink™ controls
use half wave rectification. A signal isolation device should
be utilized if incorporating a full wave bridge rectifier signal generating device is used.
16
Table 9 — Energy Management Module (EMM) Inputs and Outputs
Fig. 13 — Touch Pilot™ Display Wiring
INPUT/OUTPUTDESCRIPTIONI/O TYPEDISPLAY MODULE POINT NAMECONNECTION POINT
4-20 mA Demand Limit4-20 mA Demand Limit4-20 mA*Limit 4-20 mA Signal, DMDEMM-J7B-CH6
4-20 mA Temperature
Reset/Cooling Setpoint
Demand Limit SW2Demand Limit Step 2Switch InputSwitch Limit Setpoint 2, DLS2EMM-J4-CH9
Ice DoneIce Done SwitchSwitch InputIce Done Storage Switch, ICE.DEMM-J4-CH11A
Occupancy Override Occupied Schedule OverrideSwitch InputOccupied Override Switch, OCCSEMM-J4-CH8
Remote Lockout SwitchChiller LockoutSwitch InputRemote Interlock Switch, RLOCEMM-J4-CH10
SPTSpace Temperature Thermistor10k ThermistorOptional Space Temp, SPTEMM-J6-CH2
% Total CapacityPercent Total Capacity Output0-10 vdcChiller Capacity Signal, CATOEMM-J8-CH7
RUN RRun RelayRelayRunning Status, RUNEMM-J3-CH25
SHD RShutdown RelayRelayShutdown Indicator State, SHUTEMM-J3-CH24
CA_SRun Status for Circuit ARelayCompressor A Run Status, Q_RUN_AEMM-J2A-CH17
CB_SRun Status for Circuit BRelayCompressor B Run Status, Q_RUN_BEMM-J2A-CH18
* A field-supplied 1/2 watt 250 ohm resistor is required across terminals TB6-1,2 (CH6) and/or TB6-3, 4 (CH5).
Local Equipment Network — Information is trans-
mitted between modules via a 3-wire communication bus or
LEN (Local Equipment Network). External connection to the
LEN bus is made at TB3.
Board Addresses — All boards (except the Main Base
Board and Energy Management Module Board) have
8-position DIP switches.
Touch Pilot™ Display — The Touch Pilot display port
connections are shown in Table 10. Wiring is shown in Fig. 13.
Control Module Communication
RED LED — Proper operation of the control boards can be
visually checked by looking at the red status LEDs (lightemitting diodes). When operating correctly, the red status
LEDs will blink in unison at a rate of once every 2 seconds. If
the red LEDs are not blinking in unison, verify that correct
power is being supplied to all modules. Be sure that the Main
Base Board (MBB) is supplied with the current software. If
necessary, reload current software. If the problem still persists,
replace the MBB. A red LED that is lit continuously or blinking at a rate of once per second or faster indicates that the board
should be replaced.
GREEN LED — All boards have a green LEN (SIO) LED
which should be blinking whenever power is on. If the LEDs
are not blinking as described check LEN connections for
4-20 mA Temperature Reset/
Cooling Set point
4-20 mA*
Reset/Setpnt 4-20 mA Signal, RSET
EMM-J7A-CH5
potential communication errors at the board connectors. See
input/output Tables 3-10 for LEN connector designations. A
3-wire bus accomplishes communication between modules.
These 3 wires run in parallel from module to module. The J9A
connector on the MBB provides communication directly to the
Navigator™ display module.
YELLOW LED — The MBB has one yellow LED. The
Carrier Comfort Network
®
(CCN) LED will blink during times
of network communication.
Table 10 — Touch Pilot™ Display Port
Connections
CONNECTORPINFUNCTION
124VAC +
J1 (Power)
J2 (COM1)
J3 (RJ11)
224VAC 3Earth Ground
1RS485 Port (D+)
2RS485 Port (GND)
3RS485 Port (D-)
124VAC (+)
2RS485 Port (D+)
3RS485 Port (GND)
4Unused (no connect)
5RS485 Port (D-)
624VAC(-)
17
Carrier Comfort Network® (CCN) Interface —
Fig. 14 — ComfortLink™ CCN Communication Wiring
(+) (COM) (-) SHIELD
CCN
RED
WHT
BLK
CCNLEN
(+) (COM) (-) SHIELD
CCN
RED
WHT
BLK
CCNLEN
TO NEXT
DEVICE
(+) (COM) (-) SHIELD
CCN
RED
WHT
BLK
CCN
LEN
SHIELD
LEGEND
CCN — Carrier Comfort Network
®
LEN — Local Equipment Network
a30-4706
All 30XW units can be connected to a CCN system, if desired.
The communication bus wiring is a shielded, 3-conductor cable
with drain wire and is field supplied and installed. The system
elements are connected to the communication bus in a daisy
chain arrangement. The positive pin of each system element
communication connector must be wired to the positive pins of
the system elements on either side of it. The negative and signal ground pins of each system element must also be wired in
the same manner. Wiring connections for CCN should be made
at TB3. Consult the CCN Contractor’s Manual for further information. See Fig. 14.
NOTE: Conductors and drain wire must be 20 AWG (American Wire Gage) minimum stranded, tinned copper. Individual
conductors must be insulated with PVC, PVC/nylon, vinyl,
Teflon, or polyethylene. An aluminum/polyester 100% foil
shield and an outer jacket of PVC, PVC/nylon, chrome vinyl,
or Teflon with a minimum operating temperature range of
–20 C to 60 C is required. See Table 11 for recommended wire
manufacturers and part numbers.
It is important when connecting to a CCN communication
bus that a color-coding scheme be used for the entire network
to simplify the installation. It is recommended that red be used
for the signal positive, black for the signal negative, and white
for the signal ground. Use a similar scheme for cables containing different colored wires.
At each system element, the shields of its communication
bus cables must be tied together. If the communication bus is
entirely within one building, the resulting continuous shield
must be connected to a ground at one point only. If the communication bus cable exits from one building and enters another,
the shields must be connected to grounds at the lightning
suppressor in each building where the cable enters or exits the
building (one point per building only). To connect the unit to
the network:
PART NU M B E R
1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white
(ground), and black (–) conductors. (Substitute appropriate colors for different colored cables.)
3. Connect the red wire to (+) terminal on TB3 of the plug,
the white wire to COM terminal, and the black wire to the
(–) terminal.
4. The RJ14 CCN connector on TB3 can also be used, but is
only intended for temporary connection (for example, a
laptop computer running Service Tool).
IMPORTANT: A shorted CCN bus cable will prevent
some routines from running and may prevent the unit
from starting. If abnormal conditions occur, disconnect the CCN bus. If conditions return to normal,
check the CCN connector and cable. Run new cable if
necessary. A short in one section of the bus can cause
problems with all system elements on the bus.
Remote Alarm and Alert Relays — The 30XW
chiller can be equipped with a remote alert and remote alarm
annunciator contacts. Both relays connected to these contacts
must be rated for a maximum power draw of 10 va sealed,
25 va inrush at 24 volts. The alarm relay, indicating that the
complete unit has been shut down, can be connected to TB5-12
and TB5-13. Refer to unit wiring diagrams. For an alert relay,
indicating that at least 1 circuit is off due to the alert, a fieldsupplied and installed relay must be connected between MBBJ3-CH25-3 and TB5-13. The action of the alarm and alert relays can be reversed from normally open to normally closed by
using the Reverse Alarms Relay configuration (ReverseAlarms Relay, RV.AL).
CONFIGURATION
Touch Pilot™ Operation Configuration
Tables —
configuration information entered in the following configuration tables. These tables are accessible by using Network Service Tool or ComfortVIEW™ software. The tables are the
CtrlID (Controller Identification) configuration table and the
USERCONF (User Configuration) table. See Tables 12 and 13.
NOTE: Always perform an Upload to obtain the latest configuration before making configuration table changes.
The Touch Pilot display operation is controlled by
18
Table 12 — Touch Pilot Controller Identification Configuration Table
CONTROLLER ID DATABLOCK NO.VALUE AND RANGEQUALIFIERS
Table 13 — Touch Pilot™ User Configuration (USERCONF) Table
DESCRIPTIONLIMITSUNITSNAMEDEFAULT
Backlight always on?
Full access password
Limited access password
Active language
Time format
Date format
Units base
Contrast control
Network mode
Network settings
Alarm acknowledger
Broadcast acknowledger
Equipment CCN address
Bus number
Element number
Control variables
Equipment status (Not Used)
Equipment start/stop (Not Used)
Alarm status (Not Used)
Alarm reset (Not Used)
No
Ye s
0
9999
0
9999
0
1
0
1
0
2
US
Metric
Manual
Auto
0
1
No
Ye s
No
Ye s
0
239
1
239
Name
char 8
Name
char 8
Name
char 8
Name
char 8
BACKLITENo
PSWDFULL3333
PSWDLMTD2222
ACTLANG0
TIMEFMT0
DATEFMT0
UNITBASEUS
CONTRASTAuto
NETWORK0
ALARMACKNo
BROADACKNo
EQUIPBUS0
EQUIPELE1
EQSTATUSNOT USED
STARSTOPNOT USED
ALSTATUSNOT USED
ALRESETNOT USED
BACKLIGHT ALWAYS ON? — This configuration is used
to keep the backlight on continuously or to turn it off after 60
seconds with no activity.
Allowable Entries: No/Yes (No=0 or Yes=1)
Default Value: No
FULL ACCESS PASSWORD — This configuration is used
to specify the full access password. Refer to Table 1, Setup
Menu, for additional information on passwords.
Allowable Entries: 0 through 9999
Default Value:3333
19
LIMITED ACCESS PANEL — This configuration is used to
Fig. 15 — Equipment Start Screen
specify the limited access password.
Allowable Entries: 0 through 9999
Default Value:2222
ACTIVE LANGUAGE — This configuration is used to spec-
ify the display’s active language. All translatable text will be
displayed in this language.
Allowable Entries: 0 (English), 1 (alternate, installed by user)
Default Value:0
TIME FORMAT — This configuration is used to specify the
format for display of time.
Allowable Entries: 0 = H:MM AM/PM without leading zero
1 = HH:MM with leading zero when
necessary
Default Value: 0
DATE FORMAT — This configuration is used to specify the
format for display of date.
Allowable Entries: 0 = MM-DD-YYYY with leading zero
when necessary
1 = DD-MM-YYYY with leading zero
when necessary
2 = YYYY-MM-DD
Default Value: 0
UNITS BASE — This configuration is used to specify the for-
mat of the units of measure.
Allowable Entries: U.S.
Metric
Default Value: U.S.
CONTRAST CONTROL — This configuration is used to en-
able or disable the display’s auto contrast adjustment feature.
When enabled, the display’s contrast will be automatically adjusted as required, based on temperature.
Allowable Entries: Manual
(Auto Contrast Adjustment Disabled)
Auto
(Auto Contrast Adjustment Enabled)
Default Value: Auto
NETWORK MODE — This configuration is used to set the
display’s operating mode. For additional information on operating mode, refer to Display in the Table Setup Menu. This decision will be ignored and the mode will default to Equipment
when the display is connected to a device (the LEN Bus).
NOTE: A power cycle is required for this decision to take
effect.
Allowable Entries: Disable = Equipment Mode
Enable = Network Mode
Default Value: Disable
ALARM ACKNOWLEDGER — This configuration is used
to specify whether the Touch Pilot™ display will act as the
alarm acknowledger for the CCN. There can be only one alarm
acknowledger per CCN. Therefore, if another CCN device
such as ComfortVIEW™ software, the Autodial Gateway or
TeLINK is already set as the alarm acknowledger for the CCN
network then this decision should be set to No.
NOTE: The display must be in Network mode and connected
to the primary CCN bus and this decision set to Ye s for alarm
acknowledgement to be enabled.
Allowable Entries: No
Ye s
Default Value: No
BROADCAST ACKNOWLEDGER — This configuration
is used to indicate whether the Touch Pilot display will act as
the broadcast acknowledger for its CCN bus. There can be only
one broadcast acknowledger per CCN bus.
NOTE: The display must be in Network mode and this decision set to Ye s for broadcast acknowledgement to be enabled.
Allowable Entries: No
Ye s
Default Value: 0
EQUIPMENT CCN ADDRESS — When in equipment
mode (USERCONF Table’s Network Mode decision is set to
Disable), the Bus Number and Element Number decisions are
used to specify the CCN address of the piece of equipment to
communicate with. An Attach or power cycle must be
performed for changes to take effect. These decisions will be
ignored when the display is connected to the LEN bus or in
Network mode. In Network mode, specify the bus and element
number of the equipment communicate with using the display’s Attach function.
NOTE: In Network mode, these configurations will be overwritten with the default device address if it is changed through
the Attach process.
BUS NUMBER — This configuration is used to specify the
Equipment Controller bus number.
Allowable Entries: 0 through 239
Default Value: 0
ELEMENT NUMBER — This configuration is used to speci-
fy the Equipment Controller element number.
Allowable Entries: 1 through 239
Default Value: 1
Machine Control Methods — Three variables con-
trol how the machine operates. These variables control the
On-Off function, set point operation, and Heat-Cool operation.
Machine On/Off Control — Machine On/Off control
depends on which interface display is used. The control is different for Touch Pilot™ or Navigator™ displays. Select the
correct configuration procedure below based on which interface is being used.
TOUCH PILOT MACHINE CONTROL — Machine On/Off
control is determined locally by pushing the Start/Stop button
on the Touch Pilot display. Pressing this button will cause the
Equipment Start screen to be displayed. See Fig. 15.
20
Table 14 summarizes the unit control type and stop or go
status with regard to the following parameters:
• Operating type: this is selected by using the start/stop button
on the front of the user interface.
• Remote start/stop contacts: these contacts are used when the
unit is in remote operating type (Remote mode).
• CHIL_S_S: this network command variable relates to the
chiller start/stop when the unit is in CCN control (CCN
mode). When this variable forced to Disable, then the unit is
stopped. When this variable is forced to Enable, then the
unit runs in accordance with schedule 1.
• Start/Stop schedule: occupied or unoccupied status of the
unit as determined by the chiller start/stop program (Schedule 1).
• Master control type: This parameter is used when the unit is
the master unit in a two chiller lead/lag arrangement. The
master control type determines whether the unit is to be
controlled locally, remotely or through CCN (this parameter
is a Service configuration).
• CCN emergency shutdown: if this CCN command is activated, it shuts the unit down whatever the active operating
type.
• General alarm: the unit is totally stopped due to failure.
Local Mode
— To start the machine in local mode, press the
Start/Stop button on the Touch Pilot display. The Equipment
Start screen will be displayed. Select Local On. The control
will ignore the position of Enable/Off/Remote Contact switch
and all CCN network force commands, except an Emergency
Stop Command. The Run Status variable, indicating the cur-
rent status of the machine, will change to RUNNING, DELAY
or READY. The Chiller Occupied? variable will change to
YES. The Control Type variable indicates the type of control.
For this configuration, Control Type will be Local. The Oper-ating Type variable will change to L-On (Local On).
Local Schedule
— To start the machine with a local schedule,
press the Start/Stop button on the Touch Pilot display. The
Equipment Start screen will be displayed. Select Local Schedule. The unit will start and stop according to the schedule defined in the Time Schedule menu. Two Internal Time Schedules are available and must be field programmed. Time
Schedule 1 is used for single set point On-Off control. Time
Table 14 — Touch Pilot™ Start/Stop Control
Schedule 2 is used for Dual Set Point/Occupied-Unoccupied set point control. The control will ignore the position of
Enable/Off/Remote Contact switch and all CCN network force
commands, except the Emergency Stop Command.
The Run Status variable will indicate the current status of
the machine — OFF, RUNNING, DELAY, or READY. The
Chiller Occupied? variable will indicate the occupied state of
the machine according to Time Schedule 1 and will be either
YES (occupied) or NO (unoccupied). The Control Type vari-
able will indicate the type of control. For this configuration,
Control Type will be Local. The Operating Type variable
will change to L-Sched (Local Schedule).
The schedules consist of 8 user-configurable occupied time
periods. The control supports time schedules for local control,
remote control, and ice building. These time periods can be
flagged to be in effect or not in effect on each day of the week.
The day begins at 00.00 and ends at 24.00. The machine will be
in unoccupied mode unless a scheduled time period is in effect.
If an occupied period extends past midnight, the occupied
period will automatically end at 24:00 hours (midnight) and the
new occupied period must be programmed to begin at 00:00
hours.
In the following example, the occupied period starts at 6:00
AM, Monday through Friday and 10:00 AM on Saturday and
Sunday. The occupied time ends at 6:30 PM on Monday
through Friday and 2:00 PM on Saturday and Sunday. See
Fig. 16.
NOTE: This schedule was designed to illustrate the programming of the schedule function and is not intended as a
recommended schedule for chiller operation.
If the chiller is to be controlled to a single set point, use
Schedule 1 (OCCPC01S). This will start and stop the machine.
During the unoccupied times, the chiller will be off. If the chiller is to be controlled to 2 set points, occupied and unoccupied,
use Schedule 2 (OCCPC02S). This will cause the chiller to
control to an occupied set point and an unoccupied set point.
The machine will be able to provide cooling at any time.
To configure this option on the Touch Pilot™ display see
Table 15.
on a one-time basis. To configure this option for the Touch
Fig. 16 — Chiller Schedule Screen
Pilot display:
Table 15 — Configuring the Schedule with
Touch Pilot Display
DISPLAY NAMEPATHLINE NO.VALUE
Period 1 DOW (MTWTFSSH)
Occupied from300:00
Occupied to403:00
Period 2 DOW (MTWTFSSH)511000000
Occupied from607:00
Occupied to718:00
Period 3 DOW (MTWTFSSH)800100000
Occupied from907:00
Occupied to1021:30
Period 4 DOW (MTWTFSSH)1100011000
Occupied from1207:00
Occupied to1317:00
Period 5 DOW (MTWTFSSH)1400000100
Occupied from1507:00
Occupied to1612:00
Holiday Schedule
— For the Touch Pilot display, the control
Config\
OCCDEFCS\
OCC1P01S
or OCC1P02S
210000000
allows up to 16 holiday periods. All holidays are entered with
numerical values. To configure, first change the month (Holi-day Start Month), then the day (Holiday Start Day), then the
duration (Holiday Duration) of the holiday period in days. If a
holiday in included in one of the Occupied Time Periods of the
schedule, the machine will follow that operating condition for
the holiday. In the following examples, the holidays July 4 and
December 25-26 are programmed for Holiday 1 and Holiday 2,
respectively. To configure these holidays with the Touch Pilot
display, see Table 16. To configure Holidays with the Navigator display, check the H (holiday) schedule on the Schedule
screen and program in the desired occupied times. See Fig. 16.
time schedule can be overridden to keep the chiller in an
Occupied mode (Timed Override Hours) for 1, 2, 3 or 4 hours
DISPLAY NAMEPATH
Timed Override
Hours
Config\OCCDEFCS\
OCC1P01S or OCC1P02S
LINE
NO.
1
VAL UE
Range: 0 to 4
Default: 0
If configured for a timed override, the override can be can-
celled by changing the Timed Override Hours to 0.
CCN Global Time Schedule
— A CCN global schedule can
be used if desired. The schedule number can be set anywhere
from 65 to 99 for operation under a CCN global schedule. The
30XW chillers can be configured to follow a CCN Global
Time Schedule broadcast by another system element. The
ComfortVIEW™ Network Manager’s Configure and Modify
commands or the Service Tool’s Modify/Names function must
be used to change the number of the Occupancy Equipment
Part Table Name (OCC1P01E) to the Global Schedule Number. The Schedule Number can be set from 65 to 99
(OCC1P65E to OCC1P99E).
The Occupancy Supervisory Part table name (OCC1P01S)
number must be changed to configure the unit to broadcast a
Global Time Schedule. The Schedule Number can be set from
65 to 99 (OCC1P65S to OCC1P99S). When OCC1PxxS is set
to a value greater than 64, an occupancy flag is broadcast over
the CCN every time it transitions from occupied to unoccupied
or vice-versa. By configuring their appropriate Time Schedule
decisions to the same number, other devices on the network can
follow this same schedule. The Enable/Off/Remote Contact
must be in the Enable position or the Remote Contact position
with the contacts closed for the unit to operate. The Unit Run
Status (STAT) will indicate the current status of the machine
(OFF, RUNNING, STOPPING or DELAY), depending on the
schedule. The unit Occupied status (OCC) will indicate the
current occupied schedule according to the schedule, either NO
or YES. The Status Unit Control Type (CTRL) will be LOCAL
OFF when the switch is Off. The Status Unit Control Type will
be CCN when the Enable/Off/Remote Contact switch input is
On.
Refer to Appendix F for more detailed instructions regarding global schedules and the i-Vu
CCN Mode
— To allow machine control by CCN commands,
®
device.
press the Start/Stop button on the Touch Pilot™ display. The
Equipment Start screen will be displayed. Select CCN Mode.
The unit will be controlled by a CCN command to the CCNChillerStar t/Stop variable. An external CCN device, such as
Chillervisor, controls the On/Off state of the machine. When
controlled by a Chillervisor, it is recommended that the AutoStart W hen SM Lost configuration be set to Yes. In the event
of a loss of communication with the network, the machine will
start and be controlled locally.
Careful evaluation of chilled water plant control should be
reviewed. In the event local control is established, be sure that
all pumps, valves, and other devices are capable of operating
properly. The control will ignore the position of Enable/Off/
Remote Contact switch. The Run Status variable will indicate
the current status of the machine — OFF, RUNNING, DELAY,
or READY. The Control Type variable will change to CCN.
The Operating Type variable will change to CCN.
For dual chiller control applications, the slave chiller must
be enabled using the CCN Mode button.
Remote Mode
— To allow machine to start and stop via a
remote contact closure, press the Start/Stop button on the
Touch Pilot display. The Equipment Start screen will be displayed. Select Remote Mode. The unit will be controlled by the
Enable/Off/Remote Contact switch (SW1). Switching the Enable/Off/Remote Contact switch to the Enable or Remote
Contact position (external contacts closed) will force the unit
into an occupied state. In this mode, all CCN network force
22
commands, except the Emergency Stop Command will be
Fig. 17 — Equipment Stop Screen
ignored. The Run Status variable will indicate the current status of the machine (OFF, RUNNING, DELAY, or READY),
depending on the position of the Remote/Off/Enable Switch
closure. The Chiller Occupied? variable will change to YES.
The Control Type variable will change to Remote. The Oper-ating Type variable will change to Remote.
Master Mode
— To activate Dual Chiller Control, each machine must be individually configured for Dual Chiller Control.
To operate the machines in Dual Chiller Mode, one machine
must be designated as the master unit and one machine as the
slave unit. On the master unit, press the Start/Stop button on the
Touch Pilot display. The Equipment Start screen will be displayed. Select Master Mode. Failure to start the Master unit in
this manner will cause both machines to operate in local mode.
The Master Unit Control can be done locally, remotely or
through CCN commands per the master/slave configuration
(Master Control Type). The control will ignore the position of
Enable/Off/Remote Contact switch if the Master Control
Type is configured for Local Control or CCN Control. The
Run Status variable, Chiller Occupied? variable, and Control Type variable will change based on the Master Control
Type configured above and the Machine On/Off Control de-
fined above. The Operating Type variable will change to
Master.
To Turn Machine Off
— To turn the machine off, press the
Start/Stop button on the Touch Pilot display. See Fig. 17. The
machine will shut down. While the unit is in Local Off, it will
remain shut down and ignore all CCN commands as well as
the position of Enable/Off/Remote Contact switch. The RunStatus variable, indicating the current status of the machine,
will change to OFF. The Chiller Occupied? variable will
change to NO. The Control Type variable will indicate
Local. The Operating Type variable will change to L-OFF
(Local Off).
NAVIGATOR™ DISPLAY MACHINE CONTROL — Machine On/Off control with the Navigator display is determined
by the configuration of the Operating Type Control (OPER).
Options to control the machine locally via a switch, from a local Time Schedule, or via a Carrier Comfort Network
®
com-
mand are offered. See Table 17.
The schedules consist of 8 user-configurable occupied time
periods. The control supports time schedules for local control,
remote control, and ice building. These time periods can be
flagged to be in effect or not in effect on each day of the week.
The day begins at 00.00 and ends at 24.00. The machine is in
unoccupied mode unless a scheduled time period is in effect. If
an occupied period is to extend past midnight, the occupied
period must end at 24:00 hours (midnight) and a new occupied
period must be programmed to begin at 00:00 hours.
In the following example, a early morning pulldown time
period is scheduled for Monday morning from 12:00 AM to
3:00 AM. The occupied period starts at 7:00 AM, Monday
through Saturday. The occupied time ends at 6:00 PM on Monday and Tuesday, 9:30 PM on Wednesday, 5:00 PM on Thursday and Friday, and 12:00 PM on Saturday.
NOTE: This schedule was designed to illustrate the programming of the schedule function and is not intended as a recommended schedule for chiller operation.
Switch Control
— In the Switch Control operating type, the
Enable/Off/Remote Contact switch controls the machine locally. All models are factory configured with Operating Type
Control (OPER) set to SWITCH CTRL (Switch Control).
With SWITCH CTRL, switching the Enable/Off/Remote
Contact switch to the Enable or Remote Contact position (external contacts closed) will put the chiller in an occupied state.
The Unit Run Status (STAT) will indicate the current status of
the machine and will change from OFF to RUNNING or
DELAY. The unit Occupied Status (OCC) will change from
NO to YES. The Status Unit Control Type (CTRL) will change
from LOCAL OFF when the switch is Off to LOCAL ON
when in the Enable position or in the Remote Contact position
with external contacts closed.
— With Time Schedule Operating Type control, the machine operates under a local schedule programmed
by the user as long as the Enable/Off/Remote Contact switch is
in the Enable or Remote Contact position (external contacts
closed). To operate under this Operating Type Control (OPER)
must be set to TIME SCHED (Time Schedule). Two Internal
Time Schedules are available and must be field programmed.
Time Schedule 1 (SCH1) is used for single set point On-Off
control. Time Schedule 2 (SCH2) is used for dual set point
On-Off and Occupied-Unoccupied set point control. The
control will use the operating schedules as defined under the
Time Clock mode in the Navigator display module.
ITEMITEM EXPANSIONPATHVALUE
OPER
Operating Control
Ty pe
Operating
Modes SLCT OPER
TIME
SCHED
If the chiller is to be controlled to a single set point, use
Schedule 1 (SCH1). This type of schedule will start and stop
the machine only. During the unoccupied times, the chiller will
be off. If the chiller is to be controlled to 2 set points, occupied
and unoccupied, use Schedule 2 (SCH2). This will cause the
chiller to control to an occupied set point and an unoccupied set
point. The machine will be able to provide cooling at any time.
To configure this option while using the Navigator™ display, see Table 18.
Holiday Schedule
— The unit control allows up to 16 holiday
periods. All holidays are entered with numerical values. First
enter the month (MON.x), then the day (DAY.x), then the
duration (DUR.x) of the holiday period in days. If a holiday in
included in one of the Occupied Time Periods of the schedule,
the machine will follow that operating condition for the
holiday. In the following examples, the holidays July 4 and
December 25-26 are programmed for Holiday 1 and Holiday 2
respectively.
To configure this option for the Navigator display, see
Table 19.
CCN Global Time Schedule
— A CCN global schedule can
be used if desired. The schedule number can be set anywhere
from 65 to 99 for operation under a CCN global schedule. The
30XW chillers can be configured to follow a CCN Global
Time Schedule broadcast by another system element. The
ComfortVIEW™ Network Manager’s Configure and Modify
commands or the Service Tool’s Modify/Names function must
be used to change the number of the Occupancy Equipment
Part Table Name (OCC1P01E) to the Global Schedule Number. The Schedule Number can be set from 65 to 99
(OCC1P65E to OCC1P99E).
The Occupancy Supervisory Part table name (OCC1P01S)
number must be changed to configure the unit to broadcast a
Global Time Schedule. The Schedule Number can be set from
65 to 99 (OCC1P65S to OCC1P99S). When OCC1PxxS is set
to a value greater than 64, an occupancy flag is broadcast over
the CCN every time it transitions from occupied to unoccupied
or vice-versa. By configuring their appropriate Time Schedule
decisions to the same number, other devices on the network can
follow this same schedule. The Enable/Off/Remote Contact
must be in the Enable position or the Remote Contact position
with the contacts closed for the unit to operate. The Unit Run
Status (STAT) will indicate the current status of the machine
(OFF, RUNNING, STOPPING or DELAY), depending on the
schedule. The unit Occupied status (OCC) will indicate the
current occupied schedule according to the schedule, either NO
or YES. The Status Unit Control Type (CTRL) will be LOCAL
OFF when the switch is Off. The Status Unit Control Type will
be CCN when the Enable/Off/Remote Contact switch input is
On.
Refer to Appendix F for more detailed instructions regarding global schedules and the i-Vu
— With CCN Operating Type control, the machine operates under CCN control as long as the Enable/Off/
Remote Contact Switch is in the Enable or Remote Contact
position (external contacts closed.) To operate under this
Operating Control, OPER must be set to CCN CONTROL. An
external CCN device, such as Chillervisor, controls the On/Off
state of the machine. When controlled by a Chillervisor, it is
recommended that the Auto Start When SM Lost (AU.SM) be
set to Yes.
Careful evaluation of Chilled Water Plant control should be
reviewed. In the event Local Control is established, be sure that
all pumps, valves, and other devices are capable of operating
properly. In the event of a loss of communication with the network, the machine will start and be controlled locally. The
CCN device forces the variable CHIL_S_S to control the chiller. The Unit Run Status (STAT) will indicate the current status
of the machine (OFF, RUNNING, STOPPING or DELAY),
depending on the CCN command. The unit Occupied status
(OCC) will indicate the current occupied state according to the
CCN command and will be displayed as either NO or YES.
The Status Unit Control Type (CTRL) will be LOCAL OFF
when the Enable/Off/Remote Contact switch is Off. The Status
Unit Control Type will be CCN when the Enable/Off/Remote
Contact switch input is Closed and the CHIL_S_S variable is
Stop or Start.
For Dual Chiller Control applications, the Slave Chiller
must be enabled using the CCN CONTROL option.
ITEMITEM EXPANSIONPATHVALUE
OPER
AU.S M
Operating Control
Ty pe
Auto Start when
SM Lost
Operating
Modes SLCT OPER
Configuration SERVYES
CCN
CONTROL
Entering Fluid Control Option — The factory de-
fault for the chilled water fluid set point is controlling to the
leaving water temperature. An option to configure the machine
for entering water control is available. The control operation
remains the same except the control point is focused on the
entering water temperature, rather than the leaving water temperature when configured.
To configure this option for the Touch Pilot™ display:
DISPLAY NAMEPATH
Entering Fluid
Control
Service\
SERVICE1
LINE
NO.
No = Leaving Water Control
5
Yes = Entering Water Control
VAL UE
To configure this option for the Navigator™ display:
ITEMITEM EXPANSIONPATHVALUE
EWTO Entering Water
Control
Configuration SERVNo = Leaving
Water Control
Yes = Entering
Water Control
Cooling Set Point Selection — Several options for
controlling the Leaving Chilled Water Set Point are offered and
are configured by the Cooling Set Point Select (Setpoint Se-lect, SP.SE) variable. In addition to the Cooling Set Point Se-
lect, Ice Mode Enable discussed later in this book, and Heat
Cool Select (Heat/Cool Select, HC.SE) variables also have a
role in determining the set point of the machine. All units are
shipped from the factory with the Heat Cool Select set to 0.
All default set points are based on Leaving Water Control
(Entering Fluid Control, EWTO) set to No. Values must be
confirmed for the individual set points. Limits for the set points
are listed in the configurations noted below.
To configure these options for the Touch Pilot display, see
Table 20A. To configure these options for the Navigator display, see Table 20B.
Table 20A — Cooling Set Point Selection
with Touch Pilot Display
DISPLAY NAMEPATHLINE NO.VALUE
Cooling Setpoint 1Setpoint2Range: 14 to 70 F
Cooling Setpoint 2Setpoint3Range: 14 to 70 F
Cooling Ice SetpointSetpoint4Range: -20 to 32 F
(–10.0 to 21.1 C)
Default: 44 F (6.6 C)
(–10.0 to 21.1 C)
Default: 44 F (6.6 C)
(–28.9 to 0 C)
Default: 44 F (6.6 C)
Table 20B — Cooling Set Point Selection
with Navigator Display
ITEM ITEM EXPANSIONPATHVALUE
CSP.1 Cooling Setpoint 1Setpoints COOL
CSP.2 Cooling Setpoint 2Setpoints COOL
CSP.3 Ice SetpointSetpoints COOL
Range: 14 to 70 F
(–10.0 to 21.1 C)
Default: 44 F (6.6 C)
Range: 14 to 70 F
(–10.0 to 21.1 C)
Default: 44 F (6.6 C)
Range: -20 to 32 F
(–28.9 to 0 C)
Default: 44 F (6.6 C)
In all cases, there are limits on what values are allowed for
each set point. These values depend on the Cooler Fluid Type
and the Brine Freeze Set point, discussed later. See Table 21.
Table 21 — Configuration Set Point Limits
COOLER FLUID TYPE
SET POINT LIMITS
Minimum *38 F (3.3 C)14 F (–10.0 C)
Maximum60 F (15.5 C)
*The minimum set point for Medium Temperature Brine applications
is related to the Brine Freeze Point. The set point is limited to be no
less than the Brine Freeze Point +5° F (2.8° C).
(COOLER FLUID TYPE, FLUD)
1, Water2, Brine
The Setpoint Select configuration can be set to five different
control options: Set Point Occupancy, Set Point 1, Set Point 2,
4-20 mA Input, and Dual Switch.
CAUTION
Brine duty application (below 40 F [4.4 C] LCWT) for
chiller normally requires factory modification. Contact a
Carrier Representative for details regarding specific
applications. Operation below 40 F (4.4 C) LCWT without modification can result in compressor failure.
SET POINT OCCUPANCY — Set Point Occupancy is the
default configuration for the Setpoint Select variable. When
Setpoint Select (Setpoint Select, SP.SE) is configured to 0
(Setpoint Occ), the unit’s active set point is based on Cooling
Set Point 1 (Cooling Setpoint 1, CSP.1) during the occupied
period while operating under Time Schedule 1 (SCH1). If the
Time Schedule 2 (SCH2) is in use, the unit’s active set point is
based on Cooling Set Point 1 (Cooling Setpoint 1, CSP.1) dur-
ing the occupied period and Cooling Set Point 2 (Cooling Set-point 2, CSP.2) during the unoccupied period. See Tables 22
and 23.
To configure this option while using a Touch Pilot display:
To change this value, a Control Point Force must be applied.
When configured correctly, Setpoint Control (Setpoint Con-trol, SP.SE) will indicate Auto.
To configure this option while using a Navigator display:
— When Set Point Select (Setpoint Select, SP.SE)
is configured to 1 (Setpoint 1), the unit’s active set point is
based on Cooling Set Point 1 (Cooling Setpoint 1, CSP.1).
To configure this option with the Touch Pilot display:
DISPLAY NAMEPATH
Setpoint SelectStatus GENUNIT251 (Set Point 1)
LINE
NO.
VAL UE
To change this value, a Control Point Force must be applied.
When configured correctly, Setpoint Control will indicate
Setp 1.
To configure this option with the Navigator™ display:
— When Set Point Select (Setpoint Select, SP.SE)
is configured to 2 (Setpoint 2), the unit’s active set point is
based on Cooling Set Point 2 (Cooling Setpoint 2, CSP.2).
To configure this option with the Touch Pilot™ display:
DISPLAY NAMEPATH
Setpoint SelectStatus GENUNIT252 (Set Point 2)
LINE
NO.
VAL UE
To change this value, a Control Point Force must be applied.
When configured correctly, Setpoint Control (StatusGENUNIT) will indicate Setp 2.
To configure this option with the Navigator display:
— When Set Point Select (Setpoint Select,SP.SE) is configured to 3 (4-20 mA Setp), the unit’s active set
point is based on an field supplied, external 4 to 20 mA signal
input to the Energy Management Module (EMM). Care should
be taken when interfacing with other manufacturer’s control
systems, due to power supply differences of full wave bridge
versus half wave rectification. The two different power supplies cannot be mixed. ComfortLink™ controls use half wave
rectification. A signal isolation device should be utilized if a
full wave bridge signal generating device is used.
The following equation is used to control the set point. See
Fig. 18.
Fahrenheit Set Point = 10 + 70(mA – 4)/16 (deg F)
Celsius Set Point = –12.2 + 38.9(mA – 4)/16 (deg C)
To configure this option while using a Touch Pilot display:
DISPLAY NAMEPATH
Setpoint Select Status GENUNIT253 (4-20 mA Input)
LINE
NO.
VAL UE
To change this value, a Control Point Force must be applied.
When configured correctly, Setpoint Control will indicate
4-20 mA.
26
To configure this option while using a Navigator display:
Fig. 18 — 4 to 20 mA Set Point Control
0
10
20
30
40
50
60
70
80
90
101214161820
mA Signal
Set Point
Min LWT, Cooler Fluid Type = 1, FLUD=Brine
Min LWT, Cooler Fluid Type = 1, FLUD=Water
02468
Max LWT
A30-4830
To configure this option with the Touch Pilot display:
ITEM ITEM EXPANSIONPATHVALUE
SP.SE Setpoint SelectOperating Modes SLCT 4-20 mA Setp
Dual Switch
— When Set Point Select (Setpoint Select,
SP.SE) is configured to 4 (Dual Setp Sw), the unit’s active set
point is based on Cooling Set Point 1 (Cooling Setpoint 1,
CSP.1) when the Dual Set Point switch contact is open and
Cooling Set Point 2 (Cooling Setpoint 2, CSP.2) when it is
closed.
To configure this option while using a Touch Pilot display:
DISPLAY NAMEPATH
Setpoint SelectStatus GENUNIT25
LINE
NO.
4 (Dual
Setpoint Switch)
VAL UE
To change this value, a Control Point Force must be applied.
When configured correctly, Setpoint Control will indicate
Setp Sw.
To configure this option while using a Navigator display:
ITEM ITEM EXPANSIONPATHVALUE
SP.SE Setpoint SelectOperating Modes SLCT
Dual
Setp Sw
Chilled Water Fluid Type Selection — The chilled
water fluid must be configured. The fluid type must be configured to obtain the proper leaving water set point control range
and freeze protection. The Cooler Fluid Type (Cooler FluidType , FLUD) can be set to water or brine.
FRESH WATER — Configure the unit for Cooler Fluid Type
(Cooler Fluid Type, FLUD) to water for units without brine or
glycol installed in the chilled water loop. The factory default
fluid type is fresh water. Use this option for fresh water systems. This will allow for a water temperature set point of 38 to
60 F (3.3 to 15.5 C). With water as the selection, the Freeze
Point is fixed at 34 F (1.1 C).
DISPLAY
NAME
Cooler
Fluid Type
PATH
Main Menu Service SERVICE111 = Water
LINE
NO.
VAL UE
To configure this option with the Navigator display:
ITEMITEM EXPANSIONPATHVALUE
FLUDCooler Fluid TypeConfiguration SERVWater
BRINE OR GLYCOL OPERATION — Configure the unit
for Cooler Fluid Type (Cooler Fluid Type, FLUD) to brine for
brine or glycol chilled water loops. This option will allow for a
set point temperature range of 14 to 60 F (–10.0 to 15.5 C).
Before configuring this selection, confirm that a suitable antifreeze has been added and is at a sufficient concentration to
protect the loop. Additionally, the Brine Freeze Set Point
(Brine Freeze Setpoint, LOSP) must be set for proper freeze
protection operation. Set the Brine Freeze Set Point to the burst
protection provided by the glycol concentration. This value
will be Freeze Point for the fluid.
To configure this option with the Touch Pilot display:
DISPLAY
NAME
Cooler Fluid
Type
Brine Freeze
Setpoint
PATH
Main Menu
Service SERVICE1
Main Menu
Service SERVICE1
LINE
NO.
12 = Brine
3
VALU E
Dependent on
fluid concentration
To configure this option with the Navigator display:
ITEM ITEM EXPANSIONPATHVALUE
FLUD Cooler Fluid Type Configuration SERV Brine
LOSP
Brine Freeze
Setpoint
Configuration SERV
Dependent on
fluid concentration
27
Cooler Pump Control — It is required for all chillers
that the cooler pump control be utilized unless the chilled water
pump runs continuously or the chilled water system contains a
suitable concentration of antifreeze solution. When the Cooler
Pumps Sequence is configured, the cooler pump output will be
energized when the chiller enters an "ON" mode. The cooler
pump output is also energized when certain alarms are generated. The cooler pump output should be used as an override to
the external pump control if cooler pump control is not utilized.
The cooler pump output is energized if a P.01 Water Exchanger
Freeze Protection alarm is generated, which provides additional freeze protection if the system is not protected with a suitable
antifreeze solution.
The 30XW units can be configured for external cooler
pump control. Cooler Pumps Sequence is the variable that
must be confirmed in the field. Proper configuration of the
cooler pump control is required to provide reliable chiller operation. The factory default setting for Cooler Pumps Sequence is
0 (No Pump). The configuration settings for Cooler Pumps Sequence are 1 (1 pump only) for single pump control and 2 (2
pumps auto). Configuration settings 3 (PMP 1 Manual) and 4
(PMP 2 Manual) are for dual pump control only.
If the Cooler Pumps Sequence (PUMP) is set to 1, the control will start the pump. If a flow failure is detected, the unit
will shut down and must be manually reset. If the Cooler
Pumps Sequence (PUMP) is set to 2, the control will start the
lead pump and automatically alternate the operation of the
pumps to even the wear. If a flow failure is detected, the unit
will shut down and the lag pump will attempt to start. If flow is
established within the Unit Off to On Delay (DELY) period the
unit will restart automatically.
Two manual control options are also available. When the
Cooler Pumps Sequence (PUMP) is set to 3, Cooler Pump 1
will always operate. If a flow failure is detected, the unit will
shut down and must be manually reset. When the Cooler
Pumps Sequence (PUMP) is set to 4, Cooler Pump 2 will always operate. If a flow failure is detected, the unit will shut
down and must be manually reset.
For all Cooler Pumps Sequence (PUMP) settings (including
0), closure of both the chilled water flow switch (CWFS) and
the chilled water pump interlock contact (connected across
TB5 terminals 1 and 2) are required. In addition, for Cooler
Pumps Sequence settings of PUMP = 1, 2, 3, 4, normally open
auxiliary contacts for Pump 1 and Pump 2 (wired in parallel)
must be connected to the violet and pink wires located in the
harness from the MBB-J5C-CH18 connector. The wires in the
harness are marked "PMP1-13" and "PMP1-14". See the field
wiring diagram in the 30XW Installation Instructions.
Regardless of the cooler pump control option selected, if the
chilled water flow switch/interlock does not close within the
Unit Off to On Delay period after the unit is enabled and in an
ON mode, alarm P.91 will be generated. Other conditions
which will trigger this alarm include:
• Cooler pump interlock is open for at least 15 seconds during
chiller operation.
• Lag chiller in Master/Slave Control pump interlock does not
close after 1 minute of the pump start command.
• Cooler pump control is enabled and the chilled water flow
switch/interlock is closed for more than 2 minutes following
a command to shut down the pump.
The last alarm criterion can be disabled. If Flow Checked if
Pmp Off (Configuration OPTN P.LOC) is set to NO, the control will ignore the pump interlock input if the cooler pump
output is OFF.
The ComfortLink™ controls have the ability to periodically
start the pumps to maintain the bearing lubrication and seal integrity. If Pump Sticking Protection (Configuration OPTN
PM.PS) is set to YES, and if the unit is off at 2:00 PM, a pump
will be started once each day for 2 seconds. If the unit has
2 pumps, Pump 1 will be started on even days (such as day 2, 4,
or 6 of the month); Pump 2 will be started on odd days. The default for this option is PM.PS=NO.
The pump will continue to run for 60 seconds after an off
command is issued.
COOLER PUMP CONTROL CONFIGURATIONS
No Pump Control
— To configure cooler pump control op-
tions with the Touch Pilot™ display:
DISPLAY NAMEPATH
Cooler Pumps
Sequence
Main
Menu Config USER
LINE
NO.
8
VAL UE
0 (No Pump
Control)
To configure cooler pump control options with the Naviga-
tor™ display:
ITEMITEM EXPANSIONPATHVALUE
PUMP
Single Pump Control
Cooler Pumps
Sequence
Configuration OPTNNo Pump
— To configure cooler pump control
options with the Touch Pilot display:
DISPLAY NAMEPATH
Cooler Pumps
Sequence
Pump Sticking
Protection
Flow Checked
if C Pump Off
Main
Menu Config USER
Main
Menu Config USER
Main
Menu Config USER
LINE
NO.
8
15
17
VAL UE
1 (Single
Pump Control)
Default = No
No = Disabled
Yes = Enabled
Default = Yes
No = Disabled
Yes = Enabled
To configure cooler pump control options with the Naviga-
tor display:
ITEMITEM EXPANSIONPATHVALUE
Cooler Pumps
PUMP
Sequence
Periodic Pump
PM.PS
Start
Flow Checked
P. LO C
if Pmp Off
Dual Pump and Manual Control
Configuration OPTN1 Pump Only
Configuration OPTN
Configuration OPTN
Default = No
No = Disabled
Yes = Enabled
Default = Yes
No = Disabled
Yes = Enabled
— To configure cooler
pump control options with the Touch Pilot™ display:
To configure cooler pump control options with the Naviga-
tor™ display:
ITEMITEM EXPANSIONPATHVALUE
PUMP
ROT.P
PM.PS
P. LO C
Cooler Pumps
Sequence
Pump Rotation
Delay
Periodic Pump
Start
Flow Checked
if Pmp Off
Configuration OPTN
Configuration OPTN
Configuration OPTN
Configuration OPTN
2 Pumps Auto
PMP1 Manual
PMP2 Manual
Default =
48 hours
Default = No
No = Disabled
Yes = Enabled
Default = Yes
No = Disabled
Yes = Enabled
28
Machine Start Delay — An option to delay the start of
the machine is also available. This parameter is useful in keeping multiple machines from starting at the same time in case of
a power failure. The parameter has a factory default of
1 minute. This parameter also has a role in the timing for a
chilled water flow switch alarm. The flow switch status is not
checked until the delay time has elapsed.
To configure this option with the Touch Pilot display:
DISPLAY NAMEPATH
Unit Off to
On Delay
Main Menu
Config USER
LINE
NO.
6Default = 1 Minute
VAL UE
To configure this option with the Navigator display:
ITEMITEM EXPANSIONPATHVALUE
DELYMinutes Off TimeConfiguration OPTN
Default =
1 Minute
Circuit/Compressor Staging and Loading —
The AquaForce® 30XW chillers employ one compressor per
circuit. As a result, circuit and compressor staging are the
same. The control has several control option parameters to load
the compressors. The circuit/compressor start can be configured as well as the loading of each circuit/compressor.
CIRCUIT/COMPRESSOR STAGING — The control can be
configured to decide which circuit/compressor starts first, by
configuring Lead/Lag Circuit Select (Staged LoadingSequence, LLCS). Three options for this variable are allowed:
Automatic Lead-Lag, Circuit A Leads or Circuit B Leads. The
factory default is Automatic Lead-Lag.
The automatic lead-lag function determines which circuit/
compressor starts. When enabled, the control will determine
which circuit/compressor starts to even the wear of the compressor. The compressor wear factor (combination of starts and
run hours) is used to determine which compressor starts.
The circuit/compressor with the lowest compressor wear
factor is the circuit that starts first.
If starting a particular circuit/compressor first is desired, that
can also be configured with the same variable.
To configure this option with the Touch Pilot display:
DISPLAY NAMEPATH
Circuit Loading
Sequence
Main Menu
Config USER
To configure this option with the Navigator display:
ITEMITEM EXPANSIONPATHVALUE
Lead/Lag
LLCS
Circuit Select
CIRCUIT/COMPRESSOR LOADING — The control can
be configured to stage the circuit/compressors. The Loading
Sequence Select (Circuit Loading Sequence, LOAD) setting
determines how the control will perform loading. The configuration can be set to Equal or Staged.
Equal Loading
— With Equal loading, the circuit which starts
first will maintain the minimum stage of capacity with the slide
valve fully unloaded. When additional capacity is required, the
next circuit with the lowest compressor wear factor is started
with its slide valve at minimum position. As additional capacity is required, the slide valve for a circuit will be adjusted in
approximately 5% increments to match capacity requirements.
LINE
NO.
1
Configuration
OPTN
VAL UE
0 (Automatic Lead-lag)
1 (Circuit A Leads)
2 (Circuit B Leads)
Default = 0
(Automatic Lead-lag)
Range: Automatic,
Cir A Leads,
Cir B Leads,
Cir C Leads
Default – Automatic
The control will alternate between circuits to maintain the same
percentage of capacity on each circuit.
Staged Loading
— If staged loading is selected, the circuit
which starts first will gradually load its slide valve to match
capacity requirements until the circuit is fully loaded. Once the
circuit is fully loaded and additional capacity is required, the
control will start an additional circuit fully unloaded. The control will gradually unload the circuit which was fully loaded to
match capacity requirements.
To configure this option with the Touch Pilot™ display:
DISPLAY NAMEPATH
Staged Loading
Sequence
Main
Menu Config USER
LINE
NO.
4
VAL UE
Default = No
No (Equal)
Yes (Staged)
To configure this option with the Navigator™ display:
ITEMITEM EXPANSIONPATHVALUE
Loading Sequence
LOAD
Select
Configuration OPTN
Default = Equal
Equal
Staged
Minimum Load Control — Minimum Load Control
can be a factory-installed option or a field-installed accessory.
If installed, and its operation is desired, the Minimum Load
Control must be enabled. Once enabled, the valve will be operational only during the first stage of cooling.
To configure this option with the Touch Pilot display:
DISPLAY NAMEPATH
Hot Gas
Bypass Select
Main
Menu Service
FAC TORY
LINE
NO.
Default = No
No (No Minimum
14
Load Control)
Yes (Minimum Load
Control Installed)
VAL UE
A power cycle is required for the values to take effect.
To configure this option with the Navigator display:
ITEM
HGBP
ITEM
EXPANSION
Hot Gas
Bypass Select
PATHVALUE
Configuration UNIT
No = No Minimum
Load Control
Yes = Minimum Load
Control Installed
A power cycle is required for the values to take effect.
Dual Chiller Control — The dual chiller routine is
available for the control of two units installed in series or parallel supplying chilled fluid on a common loop. One chiller must
be configured as the master chiller, the other as the slave chiller. An additional leaving fluid temperature thermistor (dual
chiller LWT) must be installed in the common chilled water
piping as described in the Installation Instructions for both the
master and slave chillers. See the Field Wiring section in the
30XW Installation Instructions for dual chiller LWT sensor
control wiring.
The control algorithm relies on several parameters that must
be field configured for operation. Both chillers must be on the
same Carrier Comfort Network
On both chillers, Master/Slave Select (Master/Slave Select,MSSL) must be enabled. The water piping arrangement, Chillers in Series (Chiller in Series, SERI), must be configured.
The master chiller must be programmed with the Slave Chiller
Address (Slave Address, SLVA). Additional optional pro-
gramming parameters may be configured to meet application
requirements.
Lead/Lag Balance Select (Lead Lag Select, LLBL) determines which chiller is the lead machine. The options are Always Lead, Lag if Fail, and Runtime Select. Under Runtime
Select control, the lead chiller will change based on the time increment selected in the Lead/Lag Balance Delta configuration
(Lead/Lag Balance Data, LLBD). If the run hour difference
®
bus with different addresses.
29
between the master and the slave remains less than the Lead/
Lag Balance Delta, the chiller designated as the lead will
remain the lead chiller. The Lead/Lag changeover between the
master and the slave chiller due to hour balance will occur during chiller operating odd days, such as day 1, day 3, and day 5
of the month, at 12:00 a.m. If a lead chiller is not designated,
the master chiller will always be designated the lead chiller.
The dual chiller control algorithm has the ability to delay
the start of the lag chiller in two ways. The Lead Pulldown
Time parameter (Lead Pulldown Type, LPUL) is a one-time
time delay initiated after starting the lead chiller, before
checking whether to start an additional chiller. This time delay
gives the lead chiller a chance to remove the heat that the
chilled water loop picked up while being inactive during an unoccupied period. The second time delay, Lead/Lag Delay (LagStart Timer, LLDY) is a time delay imposed between the last
stage of the lead chiller and the start of the lag chiller. This prevents enabling the lag chiller until the lead/lag delay timer has
expired.
A quicker start of the lag chiller can be accomplished by
configuring the Start if Error Higher parameter (Start if Erro rHigher, LL.ER). If the difference between the common leav-
ing water temperature and the set point is greater than the configured value, then the lag chiller will start.
A minimum on time for the lag chiller can be programmed
with the Lag Minimum Running Time configuration (Lag
Minimum Running Time, LAG.M). This parameter causes
the control to run the lag chiller for the programmed minimum
on time. The Lag Unit Pump Select (Lag Unit Pump Control,LAGP) can be configured such that the pump can be on or off
while the chiller is off. This parameter is only active in Parallel
Chiller Operation.
For units with a Touch Pilot display, two additional steps
must be completed to start the machine. On the master chiller,
the Master Control Type must be configured for the start control defined in the Machine Control configuration. To start the
machines, the master chiller must be started with the Start/Stop
button and Master Mode selected. The slave chiller must be
started with the CCN Mode selected.
Each application, Parallel and Series, are described separately below.
DUAL CHILLER CONTROL FOR PARALLEL APPLICATIONS — To configure the master chiller for parallel
applications using the Touch Pilot display, see Table 24. To
configure the master chiller for parallel applications using the
Navigator display, see Table 25. A power cycle is required for
the values to take effect.
To configure the slave chiller for parallel applications using
the Touch Pilot display, see Table 26. To configure the slave
chiller for parallel applications using the Navigator display, see
Table 27.
30
Loading...
+ 118 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.