Carrier 30XV180, 30XV140, 30XV160, 30XV200, 30XV250 Controls, Start-up, Operation, Service And Troubleshooting Instructions

...
Page 1
AquaForce
30XV140-500, Series B
Variable Speed Air-Cooled Liquid Chillers
®
with Greenspeed
Intelligence
and Carrier Controller
Controls, Start-Up, Operation, Service
and Troubleshooting
®
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 2
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Conventions Used in This Manual . . . . . . . . . . . . . . . 3
Abbreviations Used in This Manual . . . . . . . . . . . . . 3
Carrier Controller Display . . . . . . . . . . . . . . . . . . . . . 5
Carrier Controller Display User Interface . . . . . . . . . 5
Input/Output (SIOB) Boards . . . . . . . . . . . . . . . . . . . 15
Auxiliary Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Enable-Off-Remote Switch (SW1) . . . . . . . . . . . . . . 18
Emergency On/Off Switch (SW2) . . . . . . . . . . . . . . . 18
Energy Management Module (EMM) . . . . . . . . . . . . 18
Local Equipment Network . . . . . . . . . . . . . . . . . . . . 19
Board Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Control Module Communication . . . . . . . . . . . . . . . 19
Carrier Comfort Network® Interface . . . . . . . . . . . 19
External Sensor Wiring . . . . . . . . . . . . . . . . . . . . . . . 20
Remote Alarm and Alert Relays . . . . . . . . . . . . . . . . 20
CONFIGURATION (SOFTWARE) . . . . . . . . . . . . . . . . . 20
Carrier Controller Operation Configuration Tables . . 20
Carrier Controller Menu Tables . . . . . . . . . . . . . . . . 20
Machine Control Methods . . . . . . . . . . . . . . . . . . . . 25
Chilled Water Set Point Configuration . . . . . . . . . . 27
Evaporator Pump Control . . . . . . . . . . . . . . . . . . . . 31
Circuit/Compressor Staging and Loading . . . . . . . 32
Dual Chiller Control . . . . . . . . . . . . . . . . . . . . . . . . . 33
Ramp Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Temperature Reset . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Demand Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Machine Start Delay . . . . . . . . . . . . . . . . . . . . . . . . . 45
Fast Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Ice Storage Operation . . . . . . . . . . . . . . . . . . . . . . . . 46
Broadcast Configuration . . . . . . . . . . . . . . . . . . . . . 46
Alarm Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Daylight Savings Time Configuration . . . . . . . . . . . 47
Capacity Control Overrides . . . . . . . . . . . . . . . . . . . 47
Head Pressure Control (Variable Speed Fans) . . . . 48
Head Pressure Control (Fixed Speed Fans) . . . . . . 49
Sound Optimization . . . . . . . . . . . . . . . . . . . . . . . . . 49
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
System Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Actual Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Operating Limitations . . . . . . . . . . . . . . . . . . . . . . . .50
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . 55
Dual Chiller Sequence of Operation . . . . . . . . . . . . .55
Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
Economizer Assembly . . . . . . . . . . . . . . . . . . . . . . . . 64
Electronic Expansion Valve . . . . . . . . . . . . . . . . . . .64
Compressor Assembly . . . . . . . . . . . . . . . . . . . . . . . 67
Evaporator Service . . . . . . . . . . . . . . . . . . . . . . . . . .68
All Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
MCHX Condenser Coil:
Maintenance and Cleaning . . . . . . . . . . . . . . . . . 74
RTPF Condenser Coil:
Maintenance and Cleaning . . . . . . . . . . . . . . . . . 74
Condenser Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
High Static Fan Option . . . . . . . . . . . . . . . . . . . . . . . 75
Refrigerant Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Safety Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
Relief Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76
Variable Frequency Drives . . . . . . . . . . . . . . . . . . . .76
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .208
Recommended Maintenance Schedule . . . . . . . . .208
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . .208
Alarms and Alerts . . . . . . . . . . . . . . . . . . . . . . . . . .208
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Electrical Schematics . . . . . . . . . . . . . . . . . . . . . . .226
Quick Test (Service Test) . . . . . . . . . . . . . . . . . . . .226
APPENDIX A — CARRIER CONTROLLER
DISPLAY TABLES . . . . . . . . . . . . . . . . . . . . . . . . . .249
APPENDIX B — CCN POINT TABLE . . . . . . . . . . . . . .281
APPENDIX C — LON POINT TABLE . . . . . . . . . . . . . .308
APPENDIX D — BACNET/MODBUS
TRANSLATOR POINTS . . . . . . . . . . . . . . . . . . . . .309
APPENDIX E — BACNET IP POINTS . . . . . . . . . . . . . .310
APPENDIX F — PIPING AND INSTRUMENTATION . .328 APPENDIX G — MAINTENANCE SUMMARY
AND LOG SHEETS . . . . . . . . . . . . . . . . . . . . . . . . .330
APPENDIX H — EVAPORATOR HEATER SENSOR
SET POINT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .332
APPENDIX I — CARRIER CONTROLLER WEB AND
NETWORK INTERFACE PARAMETERS. . . . . . .333
APPENDIX J — FACTORY SUPPLIED PUMPS . . . . .336
Catalog No. 04-53300197-01 Printed in U.S.A. Form 30XV-3T Pg 1 6-19 Replaces: New
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Page 2
SAFETY CONSIDERATIONS
WARNING
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation and ser­vice. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.
WARNING
Electrical shock can cause personal injury and death. After unit power is disconnected, wait at least 20 minutes (if compressor VFDs [variable frequency drives] are mounted external to control panel) or 40 minutes (if compressor VFDs are mounted internal to control panel) for the VFD capacitors to discharge before opening drive.
WARNING
DO NOT VENT refrigerant relief valves within a building. Outlet from relief valves must be vented in accordance with the latest edition of ANSI/ASHRAE (American National Standards Institute/American Society of Heating, Refriger­ating and Air-Conditioning Engineers) 15 (Safety Code for Mechanical Refrigeration). The accumulation of refrigerant in an enclosed space can displace oxygen and cause as­phyxiation. Provide adequate ventilation in enclosed or low overhead areas. Inhalation of high concentrations of vapor is harmful and may cause heart irregularities, unconscious­ness or death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irritation. Decomposition products are hazardous.
WARNING
DO NOT USE TORCH to remove any component. System contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and gog­gles and proceed as follows:
a. Shut off electrical power to unit. b. Recover refrigerant to relieve all pressure from system
using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen and the
work area should be well ventilated. Refrigerant in contact with an open flame produces toxic gases.
d. Cut component connection tubing with tubing cutter and
remove component from unit. Use a pan to catch any oil that may come out of the lines and as a gage for how much oil to add to the system.
e. Carefully unsweat remaining tubing stubs when neces-
sary. Oil can ignite when exposed to torch flame.
Failure to follow these procedures may result in personal injury or death.
CAUTION
Standard Tier units (units with S in the 10th position of the model number) without VFDs (units with “-”, “1”, “3”, or “5” in the 13th position of the model number) must have the condenser fan(s) rotation verified to ensure proper phas­ing. Correct rotation is counter-clockwise (reference arrow on fan hub). Swap any two incoming power leads to correct condenser fan rotation before starting chiller. Operating the unit without testing the condenser fan(s) for proper phasing could result in equipment damage.
CAUTION
DO NOT re-use compressor oil or any oil that has been ex­posed to the atmosphere. Dispose of oil per local codes and regulations. DO NOT leave refrigerant system open to air any longer than the actual time required to service the equip­ment. Seal circuits being serviced and charge with dry nitro­gen to prevent oil contamination when timely repairs cannot be completed. Failure to follow these procedures may result in damage to equipment.
CAUTION
This unit uses a microprocessor control system. Do not short or jumper between terminations on circuit boards or modules; control or board failure may result.
Be aware of electrostatic discharge (static electricity) when handling or making contact with circuit boards or module connections. Always touch a chassis (grounded) part to dis­sipate body electrostatic charge before working inside con­trol center.
Use extreme care when handling tools near boards and when connecting or disconnecting terminal plugs. Circuit boards can easily be damaged. Always hold boards by the edges and avoid touching components and connections.
This equipment uses, and can radiate, radio frequency ener­gy. If not installed and used in accordance with the instruc­tion manual, it may cause interference to radio communica­tions. It has been tested and found to comply with the limits for a Class A computing device pursuant to International Standard in North America EN 61000-2/3 which are de­signed to provide reasonable protection against such inter­ference when operated in a commercial environment. Oper­ation of this equipment in a residential area is likely to cause interference, in which case the user, at his own ex­pense, will be required to take whatever measures may be required to correct the interference.
Always store and transport replacement or defective boards in anti-static shipping bag.
CAUTION
To prevent potential damage to heat exchanger tubes, always run fluid through heat exchanger when adding or removing re­frigerant charge. Use appropriate antifreeze solutions in evapo­rator fluid loop to prevent the freezing of heat exchanger or in­terconnecting piping when the equipment is exposed to tem­peratures below 32°F (0°C). Proof of flow switch is factory installed on all models. Do NOT remove power from this chiller during winter shut down periods without taking precau­tion to remove all water from heat exchanger. Failure to prop­erly protect the system from freezing may constitute abuse and may void warranty.
2
Page 3
GENERAL
This publication contains Controls, Operation, Start-Up, Ser­vice and Troubleshooting information for the 30XV140-500 air-cooled liquid chillers with Greenspeed electronic controls. See Table 1. The 30XV chillers are equipped with the Carrier Controller controls, electronic ex­pansion valves, and variable speed fans and compressors.
Table 1 — Unit Sizes
UNIT NOMINAL CAPACITY (TONS) 30XV140 140 30XV160 160 30XV180 180 30XV200 200 30XV225 225 30XV250 250 30XV275 275 30XV300 300 30XV325 325 30XV350 350 30XV400 400 30XV450 450 30XV500 500
ABV — Actuated Ball Valve AI — Analog Input ANSI — American National Standards Institute AO — Analog Output ASHRAE — American Society of Heating, Refrigeration, and Air-Conditioning
AUX — Auxiliary (Board) AV — Analog Value AVM — Asynchronous Vector Modulation AWG — American Wire Gage BACnet — Building Automation and Controls Network BMS — Building Management System BUS TER — Bus Termination BV — Binary Value CB — Circuit Breaker CCN — Carrier Comfort Network CLR HTR — Cooler Heater CMD — Command COM — Communications COV — Change of Value CSR — Current Sensing Relay CWFS — Chilled Water Flow Switch DC — Direct Current DGT — Discharge Gas Temperature DI —Digital Input DNS — Domain Name Server DO — Digital Output DP — Discharge Pressure DPT — Discharge Pressure Transducer DSH — Discharge Superheat ECM — Electronically Commutated Motor ECO EXV — Economizer Electronic Expansion Valve ECO — Economizer ECT — Economizer Temperature EEPROM — Electronically Erasable Programmable Read-Only Memory EMM — Energy Management Module EOR — Enable-Off-Remote EPT — Economizer Pressure Transducer EWT — Entering Water Temperature EWTO — Entering Water Temperature Offset EXV — Electronic Expansion Valve FC — Fan Contactor FM —Fan Motor ft-lb — Foot-pounds FTP — File Transfer Protocol gal — Gallon GLCP — Graphical Local Control Panel gpm — gallons per minute HMI — Human Machine Interface HPS — High Pressure Switch HTTP — Hypertext Transfer Protocol HVAC — Heating, Ventilation and Air-Conditioning Hz —Hertz IGBT — Insultated Gate Bipolar Transistor in.-lb — Inch-pounds IP — Internet Protocol IR — Intrinsic Reporting kg — Kilograms kHz — Kilohertz kPa — Kilopascals
Engineers
®
®
Intelligence and
Conventions Used in This Manual
The following conventions for discussing configuration points for the Carrier Controller display will be used in this manual. The menu items are shown in this document as they appear on the Carrier Controller display. A path name for each item will show the user how to navigate through the Carrier Controller display to reach the desired configuration. The arrow symbol () in the path name represents touching the menu item on the screen of the Carrier Controller display. The path will be shown in bold and italics. See Appendix A for a complete list of Carrier Controller menu items and descriptions. The Carrier Comfort Network trols Network (BACnet)
®
(CCN) and Building Automation and Con-
1
point names are shown in bold. See Appendix B for a list of CCN points, and Appendix D for a list of BACnet points.
Abbreviations Used in This Manual
The following abbreviations are used in this manual:
1. BACnet is a registered trademark of ASHRAE (American Society of
Heating, Refrigerating, and Air-Conditioning Engineers).
kW — Kilowatt L —Liters L/s — Liters per second lb — Pounds LCD — Liquid Crystal Display LCP — Local Control Panel LED LEN — Local Equipment Network LIQT — Liquid Temperature LPT — Liquid Pressure Transducer LWT — Leaving Water Temperature mA — Milliamps MCHX — Microchannel Heat Exchanger mm — Millimeter MOP — Maximum operating temperature N/A — Not Applicable N-m — Newton-Meter NPT — National Pipe Thread OAT — Outdoor Air Temperature OP — Oil Pressure OPT — Oil Pressure Transducer PC — Personal Computer ppm — parts per million PSI — Pounds per square inch Psig — Pounds per square inch gauge PTC — Positive Temperature Coefficient PVC — Polyvinyl Chloride RCD — Replacement Components Division RFI — Radio Frequency Interference RNET — Communication Protocol RO — Read only rpm — revolutions per minute RTPF — Round Tube Plate Fin RW — Read/Write SAE — Society of Automotive Engineers SCT — Saturated Condensing Temperature* SDT — Saturated Discharge Temperature* SGT — Suction Gas Temperature SHD — Shield Wire on Shielded Cable SIOB — Standard Input/Output Board SLT — Saturated Liquid Temperature SP — Suction Pressure Spt — Setpoint SPT — Suction Pressure Transducer SST — Saturated Suction Temperature SSV — Suction Service Valve ST — Space temperature STPR — Stepper Motor SW1 — Switch 1 SW2 — Switch 2 TCP/IP — Transmission Control Protocol/Internet Protocol TL — Trend Log TS — Time Schedule UI — User Interface USB — Universal Serial Bus USDA — United States Department of Agriculture VFD — Variable Frequency Drive VI — Volume Index VPN — Virtual Private Network
*SCT and SDT are used interchangeably by software points.
— Light-Emitting Diode
3
Page 4
CONTROLS
The 30XV Air-Cooled Liquid Chillers contain the Carrier Con­troller electronic control system that controls and monitors all op­erations of the chiller. The control system is composed of several
components as listed in the following sections. All machines have a Carrier Controller module, Standard Input/Output boards, Emer­gency On/Off switch, and an Enable-Off-Remote Contact switch. Table 2 lists power schematics by unit size.
Table 2 — Control and Power Drawings
UNIT DESCRIPTION LOCATION
Typical Field Connections Wiring Schematic Fig. 90, pages 227-228
Power Wiring Schematic (Std) Fig. 91, page 229 Power Wiring Schematic (Mid) Fig. 95, page 235
30XV140
30XV160
30XV180
30XV200
30XV225
30XV250
30XV275
30XV300
Power Wiring Schematic (High) Fig. 96, page 236; Fig. 97, page 237
Communication Wiring Fig. 99, page 240
Control Wiring Schematics Fig. 100-101, pages 241-243
Component Arrangement Fig. 103, pages 246-247
Typical Field Connections Wiring Schematic Fig. 90, pages 227-228
Power Wiring Schematic (Std) Fig. 91, page 229 Power Wiring Schematic (Mid) Fig. 95, page 235; Fig. 97, page 237
Power Wiring Schematic (High) Fig. 96, page 236; Fig. 97, page 237
Communication Wiring Fig. 99, page 240
Control Wiring Schematics Fig. 100-101, pages 241-243
Component Arrangement Fig. 103, pages 246-247
Typical Field Connections Wiring Schematic Fig. 90, pages 227-228
Power Wiring Schematic (Std) Fig. 91, page 229 Power Wiring Schematic (Mid) Fig. 95, page 235; Fig. 97, page 237
Power Wiring Schematic (High) Fig. 96, page 236; Fig. 97, page 237
Communication Wiring Fig. 99, page 240
Control Wiring Schematics Fig. 100-101, pages 241-243
Component Arrangement Fig. 103, pages 246-247
Typical Field Connections Wiring Schematic Fig. 90, pages 227-228
Power Wiring Schematic (Std) Fig. 91, page 229 Power Wiring Schematic (Mid) Fig. 95, page 235; Fig. 97, page 237
Power Wiring Schematic (High) Fig. 96, page 236; Fig. 97, page 237
Communication Wiring Fig. 99, page 240
Control Wiring Schematics Fig. 100-101, pages 241-243
Component Arrangement Fig. 103, pages 246-247
Typical Field Connections Wiring Schematic Fig. 90, pages 227-228
Power Wiring Schematic (Std) Fig. 91, page 229 Power Wiring Schematic (Mid) Fig. 95, page 235
Power Wiring Schematic (High) Fig. 98, page 238-239
Communication Wiring Fig. 99, page 240
Control Wiring Schematics Fig. 100-101, pages 241-243
Component Arrangement Fig. 103, pages 246-247
Typical Field Connections Wiring Schematic Fig. 90, pages 227-228
Power Wiring Schematic (Std) Fig. 91, page 229 Power Wiring Schematic (Mid) Fig. 95, page 235
Power Wiring Schematic (High) Fig. 98, page 238-239
Communication Wiring Fig. 99, page 240
Control Wiring Schematics Fig. 100-101, pages 241-243
Component Arrangement Fig. 103, pages 246-247
Typical Field Connections Wiring Schematic Fig. 90, pages 227-228
Power Wiring Schematic (Std) Fig. 91, page 229 Power Wiring Schematic (Mid) Fig. 95, page 235
Power Wiring Schematic (High) Fig. 98, page 238-239
Communication Wiring Fig. 99, page 240
Control Wiring Schematics Fig. 100-101, pages 241-243
Component Arrangement Fig. 103, pages 246-247
Typical Field Connections Wiring Schematic Fig. 90, pages 227-228
Power Wiring Schematic (Std) Fig. 92, pages 230-231 Power Wiring Schematic (Mid) Fig. 98, page 238-239
Power Wiring Schematic (High) Fig. 98, page 238-239
Communication Wiring Fig. 99, page 240
Control Wiring Schematics Fig. 100-101, pages 241-243
Component Arrangement Fig. 103, pages 246-247
4
Page 5
Table 2 — Control and Power Drawings (cont)
UNIT DESCRIPTION LOCATION
Typical Field Connections Wiring Schematic Fig. 90, pages 227-228
Power Wiring Schematic (Std) Fig. 92, pages 230-231 Power Wiring Schematic (Mid) Fig. 98, page 238-239
30XV325
30XV350
30XV400
30XV450
30XV500
Carrier Controller Display
The Carrier Controller module is the HMI (Human Machine Interface) and core of the control system. It contains the major portion of operating software and controls the operation of the machine. See “Web and Network Interface” on page 13.
The Carrier Controller module continuously monitors input/ output channel information received from the SIOB (Standard Input/Output Board) and AUX (Auxiliary) board. The Carrier Controller module receives inputs from status and feedback switches, pressure transducers and thermistors. The Carrier Controller module, through the communications bus, also con­trols outputs on the SIOB and AUX boards. All inputs and out­puts that control the chiller are located on other boards. Infor­mation is transmitted between modules via a 3-wire communi­cation bus or LEN (Local Equipment Network).
The CCN bus is also supported. Connections to both LEN and CCN buses are made at terminal
board TB3 located within the control box enclosure to the left of the Carrier Controller display. See Fig. 1 and 2 for compo­nent layout showing the display with field connections.
Power Wiring Schematic (High) Fig. 98, page 238-239
Communication Wiring Fig. 99, page 240
Control Wiring Schematics Fig. 100-101, pages 241-243
Component Arrangement Fig. 103, pages 246-247
Typical Field Connections Wiring Schematic Fig. 90, pages 227-228
Power Wiring Schematic (Std) Fig. 93, page 232-233 Power Wiring Schematic (Mid) Fig. 94, page 234
Power Wiring Schematic (High) Fig. 94, page 234
Communication Wiring Fig. 99, page 240
Control Wiring Schematics Fig. 100, 102, pages 241, 244-245
Component Arrangement Fig. 104, page 248
Typical Field Connections Wiring Schematic Fig. 90, pages 227-228
Power Wiring Schematic (Std) Fig. 93, page 232-233 Power Wiring Schematic (Mid) Fig. 94, page 234
Power Wiring Schematic (High) Fig. 94, page 234
Communication Wiring Fig. 99, page 240
Control Wiring Schematics Fig. 100, 102, pages 241, 244-245
Component Arrangement Fig. 104, page 248
Typical Field Connections Wiring Schematic Fig. 90, pages 227-228
Power Wiring Schematic (Std) Fig. 93, page 232-233 Power Wiring Schematic (Mid) Fig. 94, page 234
Power Wiring Schematic (High) Fig. 94, page 234
Communication Wiring Fig. 99, page 240
Control Wiring Schematics Fig. 100, 102, pages 241, 244-245
Component Arrangement Fig. 104, page 248
Typical Field Connections Wiring Schematic Fig. 90, pages 227-228
Power Wiring Schematic (Std) Fig. 93, page 232-233 Power Wiring Schematic (Mid) Fig. 94, page 234
Communication Wiring Fig. 99, page 240
Control Wiring Schematics Fig. 100, 102, pages 241, 244-245
Component Arrangement Fig. 104, page 248
Carrier Controller Display User Interface
The Carrier Controller display is the standard user interface on all 30XV chillers with Greenspeed cludes a large 7-in. LCD (Liquid Crystal Display) touch screen for display and user configuration. A stylus is recommended for use on the touch screen. The stylus is included with the unit.
WELCOME SCREEN The Welcome screen is the first screen shown after Carrier
Controller is powered on. See Fig. 3. The Welcome Screen will automatically change to the Home
Screen when the controller has completed initialization.
HOME SCREEN The Home screen provides an overview of system controls, al-
lowing the user to monitor the vapor-refrigeration cycle. The screen indicates the current status of the unit, giving informa­tion on the unit capacity, refrigerant conditions, occupied sta­tus, capacity limit, compressor A and B status, the active set point, and other information. See Fig. 4 and 5.
®
Intelligence. The display in-
5
Page 6
SEE DETAIL A
DETAIL A
ETHERNET
USB
Fig. 1 — Component Layout Drawing (30XVB140-325 Shown)
Fig. 2 — Component Layout Drawing (30XVB350-500 Shown)
6
Page 7
Fig. 3 — Welcome Screen
LEGEND
1—Evaporator Entering Fluid Temperature 2—Outdoor Air Temperature 3—Evaporator Leaving Fluid Temperature 4—Unit Status 5—Circuit A Status 6—Circuit B Status 7—Circuit A Refrigeration Details 8—Circuit B Refrigeration Details 9—Unit Status Message 10 — Active Setpoint
Start/Stop — Touch to access the machine control method menu. See page 25 for details on available operating modes.
Alarm — The alarm icon turns solid or blinks red when a fault is detected. See page 208 for details on system alarms and alerts.
To display circuit specific information select the desired Cir­cuit Button. See Fig. 5.
Fig. 4 — Home Screen
The following buttons appear on the top panel of the home screen. See Table 3 for more general screen buttons.
Main Menu — Touch the Main Menu button to access all unit functions. See Main Menu Screen on page 9 for details.
Log In — Touch to enter passwords and select language or change the system of measurement. See page 9 for log­in details. The icon shown is for Basic access; it changes based on access level. See Table 3 for Advanced User, Service, and Factory access icons.
Table 3 — Screen Buttons
BUTTON FUNCTION
TOP LEFT PANEL — GENERAL NAVIGATION
Home button: Goes to the home screen.
Main Menu button: Goes to the Main Menu screen from the Home screen. Allows access to unit menus and parameters. See page 9.
Back button: Goes to previous screen.
TOP RIGHT PANEL — SPECIAL NAVIGATION
Start / Stop button: Goes to the chiller start / stop screen. The Start/Stop button is gray, green, or blinking green. See the Machine Control Methods section on page 25.
Alarm button: Goes to the alarm menu screen.The Alarm button is gray, red, or blinking red. See the Alarms and Alerts section on page 208.
Fig. 5 — Home Screen with Saturated Condensing
Temperature (SCT) and Saturated Discharge
Temperature (SDT)
UNIT STATUS MESSAGE BOX Messages may be displayed in the status bar at the bottom of
the screen relevant to the current user action. See Table 4.
BOTTOM LEFT PANEL — ACTIONS SPECIFIC TO CURRENT SCREEN OPERATION
Save/Cancel: Save button confirms changes. Cancel discards changes.
BOTTOM RIGHT PANEL — SCROLLING INSIDE CURRENT SCREEN
Up and Down arrows: Scroll within screen content. A page indicator shows what page is being viewed, and the total number of pages.
Troubleshoot Quick Test and Svc Alerts: only appears in Service or Factory Access Level. Touching the icon opens three icons on the side of
the screen: Service Alerts . Quick Test . and Troubleshoot
7
Page 8
Table 4 — Unit Status Messages
SCREEN MESSAGE FUNCTION
LOGIN SCREEN
DNS CONFIG
GATEWAY CONFIGURATION
ETH0/1 CONFIG
NTP TIME SYNC
SET MANUAL TIME SCREEN
TIME ZONE CONFIG SCREEN
CCN MESSAGES
CURRENT ALARMS Log in as Service or higher to reset alarms CIRCUIT A/B SCREEN Compressor Status : MAIN EXV A/B EXV control mode : ECO EXV A/B ECO Mode :
START/STOP
PUMP CONFIG Unit Must Be OFF Before Modifying Menu
FACTORY PARAMETERS
HOME Trip out : Active alarm description
SERVICE ALERT
Current Login Level = Basic Entered password is 0 or basic login; login is allowed.
Current Login Level = Advanced User
Current Login Level = Service
Current Login Level = Factory
DNS applied successfully DNS IP invalid System call failed Gateway applied successfully failed to execute gateway_wrapper script incorrect arguments to gateway_wrapper invalid gateway ip invalid gateway mask Incorrect option passed to gateway_wrapper Invalid argument to route command Network is unreachable Gateway exists bogus netmask netmask and route address conflict No such gateway ip present gateway_wrapper.sh not found cannot execute gateway_wrapper.sh Gateway deleted IP address applied successfully error, IP address is blank IP address is invalid error, IP address is zero error in setting IP address error , netmask is blank netmask is invalid error, netmask is zero error in setting netmask Time synchronized successfully ntp server address empty Network is unreachable failure in name resolution no response after 1 seconds not in sync, skipping this server system() failed to execute script sntp_wrapper.sh not found cannot execute sntp_wrapper.sh save successfully NO_ERROR Time zone set successfully Invalid time zone settings Platform error in setting time zone SUCCESS CCN Table successfully saved to system. internal communication failure Equipment Controller did not respond while reading table content Value outside lower limit Value was written outside the lower bounds of the data point. Value outside higher limit Value was written outside the upper bounds of the data point.
higher level force is already in action
ACCESS DENIED A read-only data point or table was accessed and the request was denied.
Factory or BACnet changes have been detected. UI must be rebooted.
Reset Alarms Before Starting Chiller Disable Quick Test Before Starting Chiller
Unit Must Be Local OFF Before Modifying Menu UI must be rebooted for changes to take effect.
If oil filter pressure drop is above: High Oil Filter Pressure Drop Alert High Discharge Pressure Alert High Evaporator Delta T Alert If evaporator delta T is above:
Entered password corresponds to the Advanced User Password; login is allowed.
Entered password corresponds to the Service User Password; login is allowed.
Entered password corresponds to Factory User Password; login is allowed.
Equipment controller rejects Force or Auto command due to a higher level force present.
8
Page 9
CARRIER CONTROLLER LOGIN AND DISPLAY SETUP
LEGEND
1—
Arrows indicate selected language
2—
Login button (confirm changes)
3—
System of measurement selection
4—
Password dialog box
Certain control functions and navigation menus are password protected. There are multiple levels of user access on the Carrier Controller display, each with independent password protection:
• Basic — At initial start-up and after a timeout period, the access type defaults to All. In this mode the user can view system operating conditions.
• Advanced User — The Advanced User access level authoriz­es access to modify the Setpoint Table and some Configura­tion Menu parameters, as well as access to all menus accessi­ble with the Basic mode. See menu structure on page 12. The default password for Advanced User level access is 11. To change the Advanced User access password, go to Main
Menu
Configuration Menu  HMI Configuration
Menu
User Password Change, then enter the old pass­word and the new password. Confirm the new password, then press the Submit button. After selecting the Submit button, a pop-up window will indicate that the user password was changed successfully. Select OK to continue.
• Service — The Service access level authorizes access to all menus and parameters needed for operation and service of the machine, including Quick Test and Maintenance Menus as well as additional Configuration Menus. See menu structure on page 12. When logged in under Service access, the service
icon will appear on the Home Screen in the upper right corner. The default password for Service level access is 88. To
change the Service access password, go to Main Menu
Configuration Menu  Service Parameters, then scroll to the password entry area. Enter the new password and touch the Done button to accept the entry and close the pop-up screen, then select the Save button. Use caution when chang­ing the password. If the password is changed and forgotten, in order to retrieve the password a higher level access or external tool is required.
• Factory — The Factory access level authorizes access to all menus and parameters for the unit, including factory settings. See menu structure on page 12. When logged in under Facto-
ry access, the Factory icon will appear on the Home Screen in the upper right corner. The default password for
Factory level access is 113. To change the Factory access password, go to Main Menu
Configuration Menu
Factory Menu, then scroll to the password entry area. Enter the new password and touch the Save button. Use caution when changing the password. If the password is changed and forgotten, in order to retrieve the password an external tool is required.
To log in to the Carrier Controller display, touch the Login but­ton on the Home screen and input the required password on the User Login screen. The Login icon will change to one of
three icons denoting the access level: Basic, Service, or Factory. Then touch the Home button on the User Login screen. Once logged in to the controller, after 6 minutes of inactivity, the
controller will revert back to Basic Access Level. To log out of the controller, touch the Access Level icon. In the password box, type 0, then touch the Done button. See Fig. 6.
Fig. 6 — User Login Screen
Changing the Carrier Controller Display Language
The User Login Screen (Fig. 6) offers 2 language selections for the Carrier Controller Display: English or Spanish .
The factory default language is English. The current language is shown between the arrows . To change the display lan­guage, simply select the desired language icon on the User Login screen. The language can be changed without being
logged into the controller. Then touch the Home button on the User Login screen. See Fig. 6.
Changing the Units of Measurement
The User Login Screen (Fig. 6) offers 2 choices for units of measurement: US Imperial or Metric. The factory default is US Imperial. The current selection is denoted by a blue button. To change the measurement system, select the appropriate system on the User Login screen, then press any other button or icon on the User Login screen. The units can be changed without being logged into the controller. See Fig. 6.
MAIN MENU SCREEN The Main Menu provides access to the main control parame-
ters, including general parameters, temperatures and pressures, inputs and outputs status, and others. Touch the Main Menu
button on the Home screen to access the Main Menu. The Main Menu displayed will depend upon what access level the
user is logged in as. Figure 7 shows the Main Menu. To navigate through the pages,
touch the arrows at the lower right corner of the screen. To view or modify system parameters, touch the appropriate
icon on the Main Menu. For example, to access the General Pa­rameters table, touch the General Parameters button .
Figure 8 shows the first page of the General Parameters table if logged in with Service Access. Use the arrows at the bottom right corner to navigate the General Parameters table.
9
Page 10
Fig. 7 — Main Menu, Page 1 and Page 2
Fig. 9 — Data Entry Keyboard
If a numeric response is required, a keypad will be displayed along with Cancel, Clear, Set, and Relinquish keys (see Fig. 10). Use the keypad to enter the value and touch the Set key. Once complete, Cancel and Save buttons will appear in the lower left section of the Unit Status Line. To accept the change, touch the Save button
. To cancel, touch the Cancel button .
For menu items, a series of limited choices will be displayed on the screen in a separate window. Select the desired value. Once complete, Cancel and Save buttons will appear in the lower left section of the Unit Status Line. To accept the change, touch the
Save button . To cancel, touch the Cancel button .
Fig. 8 — General Parameters, Page 1
Points that can be changed with the current level of user access are outlined by a box. For example, to modify the set point select parameter, select the current set point select value as shown in Fig. 8 and enter the desired parameter.
The data entry screen will be displayed (Fig. 9). For alphanu­meric responses, such as the password screen, a QWERTY key­board is displayed (see Fig. 9). In addition to the normal alpha­numeric keys, arrow, and symbols, there is a Backspace Key
, a Cancel button, and a Done button. Enter the data re-
quired and touch the Done button to accept the change. If re-
quired, Save and Cancel icons will appear in the
Unit Status Line to confirm the changes.
Fig. 10 — Data Entry Keypad
GENERAL CONFIGURATION TABLE This table contains configuration settings for the unit. Select
Main Menu tion to access the table (Fig. 11).
10
Configuration Menu General Configura-
Page 11
Touch the field corresponding to the parameter to be modified
LEGEND
1 — Set the start date 2 — Set the start hour 3 — Set the start minutes 4 — Set the end date 5 — Set the end hour 6 — Set the end minutes 7 — Select Go to graph
and make the necessary changes. When all necessary changes have been made, touch the Save button to confirm or the Cancel button to cancel changes. For a complete list of general parameters, see Appendix A.
TRENDING SCREEN The Trend Display screen allows for easy monitoring of parame-
Select the parameters to be displayed by selecting the box to the left of the parameter name. The scroll bar on the right of the screen can be used to see all possible selections; to save a selection touch the Save Trend Display Options Button. Once the parameters to be trended are selected and saved, touch the Display Trend Log But­ton and the trend graph will be displayed. See Fig. 13.
Fig. 11 — General Configuration
Fig. 12 — Trend Display Screen
Fig. 13 — Trending Configuration Screen
Use the following buttons to adjust the Trendings display:
Navigate across the time line.
Go to beginning or end of selected period.
Zoom in to magnify the view.
Zoom out to expand the viewed area.
Refresh (reload) data.
MENU ARCHITECTURE See Fig. 14-16 for Carrier Controller menu structure. The op-
tions displayed depend on the user’s access level as shown in the figures. The user can navigate through the Carrier Control­ler display screens by selecting the buttons that appear on the screen. When a button is selected, either a submenu or a list of parameters and values will be shown. If the list of parameters and values is shown, the top line of the display will show either the menu item name if sub-menu items appear or the table name when points and values are displayed. Selecting an item will cause a Point Data dialog box to appear. For a complete list of tables and points with display names and CCN point names, see Appendixes A and B.
SETTING TIME AND DATE The date and time for the controls can be set by opening the Main
Menu

Configuration Menu HMI Configuration Menu
Date/Time Configuration. Select either the NETWORK TIME
SYNC button or SET TIME MANUALLY button. Choosing the NETWORK TIME SYNC button will allow the controller to syn­chronize the time with a network server if the chiller control sys­tem is connected to a network. See Appendix A, page 258. See Fig. 17 for details required to use Network Time Sync. Selecting SET TIME MANUALLY button allows the user to configure the Time Zone and set the date, time, daylight saving time, and wheth­er today or tomorrow is a holiday. See Fig. 17 for details.
11
Page 12
Fig. 14 — Main Menu and Alarm Menu Structure
HOME
MAIN MENU LOG IN/LOG OUT CONFIRM STOP CHOOSE OPERATING MODE ALARM MENU
General Parameters
1
Input Status
1
Run Times
1
Configuration Menu
2
Trend Display
1
Temperatures
1
Output Status
1
Modes
1
Quick Test Table
3
Pressures
1
Pump Status
1
Setpoint Table
2
Maintenance Menu
3
TO CONFIGURATION MENU
TO MAINTENANCE MENU
Reset Alarms
3
Current Alarms
1
Alarm Historic
1
Major Alarm Historic
1
HMI Configuration Menu
Reset Configuration
Broadcast Menu
Service Parameters
Compressor Enable
2
2
3
3
2
General Configuration
Schedule Menu
Factory Parameters
Update Running Hour
Email Configuration
2
2
4
3
3
Fig. 15 — Configuration Menu Structure
Capacity Control
EXV Control
EXV Eco. Control
3
3
3
Fan Drive Addressing
VLT Drive Maintenance
Control Limits
3
Fan Control
3
Troubleshoot Info
3
3
3
Fig. 16 — Maintenance Menu Structure
Network Conn-eth0
3
Network Conn-eth1
3
Pump Configuration
Holiday Menu
2
2
Factory2 Parameters
Master/Slave Conf ig
3
Last PowerOn Reset
Master/Slave Con trol
Fan Drive Maintenance
CCN Configuration
3
4
3
3
3
LEGEND — FIG. 14-17 All (no password required)
1— 2— 3— 4—
Basic access required (default password = 0) Service access required (default password = 88) Factory access required (default password = 113)
BACnet Configuration
CPU Memory
Screen Brightness
Fig. 17 — HMI Configuration Menu Structure
3
2
2
Date/Time Configuration
Termination Resistor
3
3
Control Identification
System Information
2
2
12
Page 13
WEB AND NETWORK INTERFACE The Carrier Controller control can be configured to allow access
via a standard, java-enabled web browser or over a network. See Appendix I for detailed information on setting up and accessing the Carrier Controller via the web or network interface. See Table 5 for port connections. See Fig. 18 for interface and connectors.
Table 5 — Carrier Controller Display Port
Connections
CONNECTOR
J1 TYPE-A USB-3: Firmware/Software Upgrade
J5 TYPE-A USB-1: Firmware/Software Upgrade
J6
J7
J8
J9
J10
J11 TYPE-A USB-2: Firmware/Software Upgrade
J14
J15 RJ45
J16 RJ45 Ethernet-1: WAN (connectivity)
NOTES:
1. For more information about password access, see Carrier Control­ler Login and Display Setup on page 9.
2. PINOUT is listed as viewed from back of from left to right on connector.
TYPE/
PINOUT
+
C
-
+
-
-
SHD
C
+
12V
-
+
G
-
SHD
C
+
G
+
RS485-1: LEN System Internal I/O Boards
RS485-2: CCNC
RS485-4: BMS Interface, BACnet
RNET Port to Support RNET Devices
RS485-3: Not used
24VAC Power
Ethernet-2: Service Tool, BMS Interface, BACnet, WAN (connectivity)
FUNCTION
13
Page 14
SEE DETAIL A
BRD PWR 24VAC J14
RS485 LEN J6
RS485 CCN J7
RNET J9
(SHARED WITH RS485 J8 XCEIVER)
RS485 J8
RS485
ETHERNET J16
ETHERNET J15
USB J11
USB J1
USB J5
J10
Fig. 18 — Carrier Controller Display Interface and Connectors
DETAIL A
4 PLACES
LOCK CLIP
M5 0.8 X 20 mm FLAT TIP SET SCREW
TORQUE 0.45 - 0.56 Nm
14
Page 15
Input/Output (SIOB) Boards
There are two SIOBs for each unit, SIOB-A (address 49) for Cir­cuit A and SIOB-B (address 50) for Circuit B. See Fig. 19. These boards receive inputs from thermistors, transducers, demand limit switch, dual set point switch, remote on/off switch, chilled water flow switch, oil level switch, pump interlock contact, compressor VFD enable contact, and evaporator heater current sensing switch, and provide output control to expansion valves, oil and variable load matching solenoids, evaporator heater contactor, isolation
valves, oil heater relays, customer supplied pump relays, compres­sor VFD enable relays, and customer-supplied alarm and running relays. Information is transmitted between the SIOBs and the Carrier Controller module via a 3-wire communication bus or LEN bus. Connections for the LEN bus are J12 and J13. Each SIOB has a 4-position DIP switch bank used for addressing of the board. SIOB-A is at address 49 and SIOB-B is at address 50. See Table 6 for SIOB DIP switch settings. See Tables 7 and 8 for a list of inputs and outputs for the two SIOBs.
RED LED - STAT US
DIP SWITCH
GREEN LED - LEN (Local Equipment Network)
a30-5864
LEN CONNECTION
Fig. 19 — SIOB
Table 6 — SIOB A and B DIP Switch Settings
SIOB-A DIP Switch 1 2 3 4
Position OFF OFF OFF OFF
SIOB-B DIP Switch 1 2 3 4
Position ON OFF OFF OFF
15
Page 16
Table 7 — SIOB-A Inputs and Outputs
ITEM IN/OUT TYPE BOARD CONNECTOR CCN POINT DESCRIPTION
DI-01 Dry contact DI-02 Dry contact SETP_SW Dual Setpoint Switch DI-03 Dry contact LIM_SW1 Demand Limit Switch 1 OnOff DI-04 Dry contact — Not Used — DI-05 Dry contact J34 — Not Used — DI-06 Dry contact DI-07 Dry contact FLOW_SW Chilled Water Flow Switch (CWFS) DI-08 Dry contact HEATR_SW Cooler Heater Current Sensing Rly Feedback AI-01 Temp (5000 W) AI-02 Temp (5000 W) COOL_LWT Cooler Leaving Water Temperature AI-03 Temp (5000 W) OAT Outdoor Air Temperature AI-04 Temp (5000 W) CP_TMP_A Compressor A motor temperature AI-05 Temp (5000 W) ECO_T_A Economizer Temperature Circuit A AI-06 Pressure J11 DP_A Discharge Pressure Circuit A AI-07 Pressure J19 SP_A Suction Pressure Circuit A AI-08 Pressure J20 ECO_P_A Economizer Pressure Circuit A AI-09 Pressure J21 OP_A Oil Pressure Circuit A AI-10 4 to 20 mA J9 — Not Used — DO-01 Relay output DO-02 Relay output CPUMP_2 Pump Relay #2 DO-03 Relay output DO-04 Relay output VFD_EN_A VFD Enable Output Circuit A DO-05 Relay contact J23 ALARM Alarm Relay DO-06 Relay contact J22 RUNNING Running Relay DO-07 Triac DO-08 Triac C_HEATER Cooler Heater Contactor DO-09 Triac VI_A VI Solenoid Control Compressor Circuit A DO-10 Triac ISO_POS_A Isolation Valve Relay Circuit A STPR1 Stepper motor J17 EXV_A EXV-A STPR2 Stepper motor J18 ECO_A ECEXV-A AO-01 0 to 10 VDC J10 — Not Used —
J1
J3
J25
J2
J6
J7
ONOFF_ SW Remote On-Off Switch (SW1)
OIL_L_A Oil Level Switch Circuit A
COOL_EWT Cooler Entering Water Temperature
CPUMP_1 Pump Relay #1
OIL_HT_A Oil Heater Contactor Circuit A
OIL_SL_A Oil Solenoid Circuit A
Table 8 — SIOB-B Inputs and Outputs
ITEM IN/OUT TYPE BOARD CONNECTOR CCN POINT DESCRIPTION
DI-01 Dry contact DI-02 Dry contact — Not Used — DI-03 Dry contact — Not Used — DI-04 Dry contact — Not Used — DI-05 Dry contact J34 — Not Used — DI-06 Dry contact DI-07 Dry contact FLOW_SWB Customer Supplied Pump Interlock Relay DI-08 Dry contact — Not Used — AI-01 Temp (5000 ) AI-02 Temp (5000 ) — Not Used — AI-03 Temp (5000 ) CHWSTEMP Dual chiller temperature (accessory) AI-04 Temp (5000 ) CP_TMP_B Compressor motor temperature Circuit B
AI-05 Temp (5000 ) ECO_T_B Economizer temperature Circuit B
AI-06 Pressure
AI-07 Pressure J19 SP_B Suction pressure Circuit B AI-08 Pressure
AI-09 Pressure
AI-10 4 to 20 mA
DO-01 Relay output DO-02 Relay output — Not Used —
DO-03 Relay output
DO-04 Relay output VFD_EN_B VFD enable output Circuit B
DO-05 Relay contact J23 — Not Used — DO-06 Relay contact J22 — Not Used — DO-07 Triac DO-08 Triac BOX_HTR Display heater (accessory) DO-09 Triac VI_B Vi solenoid control compressor Circuit B DO-10 Triac ISO_POS_B Isolation valve relay Circuit B STPR1 Stepper motor J17 EXV_B EXV-B STPR2 Stepper motor
AO-01 0 to 10 VDC
J1
J3
J25
J11
J20
J21
J9
J2
J6
J7
J18
J10
OIL_L_B Oil level Circuit B
DP_B Discharge pressure Circuit B
ECO_P_B Economizer pressure Circuit B
OP_B Oil pressure Circuit B
OIL_HT_B Oil heater contactor Circuit B
OIL_SL_B Oil solenoid Circuit B
ECO_B ECEXV-B
LEGEND
AI — Analog Input AO — Analog Output DI — Discrete Input DO — Discrete Output STPR — Stepper Motor Output
— Not Used —
— Not Used —
— Not Used —
— Not Used —
— Not Used —
16
Page 17
Auxiliary Boards
Two AUX boards, AUX Board A (address 84) and AUX Board B (address 85), are installed in each unit. Each of the AUX boards has a set of jumpers, JP1 and JP2, which must be placed on the "P" terminal and as shown in Fig. 20. The AUX boards
ON
2
5
1
3
7
4
J1
24 VAC
U2
U5
U4
U6
U1
Q1
D3
U9
U8
U7
6
Q12
Q11
Q10
U10
respond to commands from the Carrier Controller module and send the Carrier Controller module the results of the channels they monitor via the LEN. See Table 9 for AUX board A and B DIP switch settings. See Tables 10 and 11 for a list of inputs and outputs for the AUX boards.
RED LED - STAT US
DIP SWITCH
STATU S SIO (LEN)
S1
8
Q60
D7
D8
GREEN LED - LEN (Local Equipment Network)
Q5
Y1
D5
D6
L5
JP2
L2
100K
100K
L3
100K
U21
J9
– G +
3 2 1
– G +
3 2 1
JUMPER JP2 - "P"
JUMPER JP1 - "T"
TR1 TR2 TR3 TR4 TR5 TR6 TR7 TR8
J2
CH1
CH2 CH3
J3
CH4 CH5 CH6 CH7 CH8
C61
CH9
J5
CH10
J4
CH11
D12
CH13
CH12
JP1
J7 J8
J6
CH13 CH14
Fig. 20 — AUX Board
Table 9 — AUX Board A and B DIP Switch Settings
AUX BOARD A DIP SWITCH 12345678
AUX BOARD BDIP SWITCH 12345678
Address ON ON OFF OFF ON OFF ON OFF
Address OFF OFF ON OFF ON OFF ON OFF
Table 10 — AUX Board A Inputs and Outputs
CHANNEL IN/OUT TYPE BOARD CONNECTOR CCN POINT DESCRIPTION (SEE NOTE)
CH 1 DO CH 2 DO FC2_A Fan A Stage 2 CH 3 DO FC3_A Fan A Stage 3
J2
CH 4 DO FC4_A Fan A Stage 4 CH 5 DO CH 6 DO FC6_A Fan A Stage 6 CH 7 DO FC7_A Fan A Stage 7
J3
CH 8 DO FC8_A Fan A Stage 8 CH 9 AO J4 CAPT010A % Capacity Circuit A (0-10 Vdc) CH 10 AO J5 — Not Used CH 11 AI CH 12 AI SUCT_A Suction Gas Temperature Circuit A
J6
CH 13 AI J7 LIQ_T_A Liquid Temperature Circuit A CH 14 AI J8 LIQ_P_A Liquid Pressure Circuit A
FC1_A Fan A Stage 1
FC5_A Fan A Stage 5
DGT_A Discharge Gas Temperature Circuit A
Table 11 — AUX Board B Inputs and Outputs
CHANNEL IN/OUT TYPE BOARD CONNECTOR CCN POINT DESCRIPTION (SEE NOTE)
CH 1 DO CH 2 DO FC2_B Fan B Stage 2 CH 3 DO FC3_B Fan B Stage 3
J2
FC1_B Fan B Stage 1
CH 4 DO FC4_B Fan B Stage 4 CH 5 DO CH 6 DO FC6_B Fan B Stage 6 CH 7 DO FC7_B Fan B Stage 7
J3
FC5_B Fan B Stage 5
CH 8 DO FC8_B Fan B Stage 8 CH 9 AO J4 CAPT010B % Capacity Circuit B (0-10 Vdc) CH 10 AO J5 — Not Used CH 11 AI CH 12 AI SUCT_B Suction Gas Temperature Circuit B
J6
DGT_B Discharge Gas Temperature Circuit B
CH 13 AI J7 LIQ_T_B Liquid Temperature Circuit B CH 14 AI J8 LIQ_P_B Liquid Pressure Circuit B
NOTE: Fan A and B stage outputs are only used on STANDARD TIER units, identified by the 10th position in the model number. Position 10 is S and Position 13 is -, 1, 3, or 5.
17
Page 18
Enable-Off-Remote Switch (SW1)
221
221
221
221
100K
100K
100K
100K
100K
CH 17
CH 17
CH 16
CH
CH 18
CH 19
CH 20
CH 22
CH 21
CH 23
24 VAC
12 11
CH
11b
CH
12
CH
13
CH
14
CH
15
CH
1
CH
2
CH
3
CH
4
CH 5
CH 6
CH 7
SIO LEN
+ G -
+ G -
SIO LEN
J8
J7B
J7A
J6
J5
J4 J3 J2B
J2A
J1
CH 24CH25
CH
8
CH
9
CH 10
CH 11a
J9A
J9B
RED LED - STATU S
GREEN LED - LEN (Local Equipment Network)
The position of the Enable-Off-Remote switch is ignored except when the Remote control type is selected. Refer to the Machine Control Methods section on page 25 for more details. A selection for Machine Control Method must also be made along with the correct position of the Enable-Off-Remote Switch. This switch is installed in all units. It is a 3-position switch used to control the chiller. When switched to the Enable position, the chiller will ig­nore the field-supplied Remote Contacts, enabling the unit all of the time. When switched to the Off position, the chiller will shut down if running. This allows for local (at the unit) override of the Remote Contact input. When switched to the Remote position, a field-installed dry contact can be used to start and stop the chiller. The contacts must be capable of handling a 24 VAC, 50 mA load. In the Enable and Remote Contact (dry contacts closed) positions, the chiller is allowed to operate and respond to the scheduling con­figuration and set point data.
Emergency On/Off Switch (SW2)
This switch is installed in all units. The Emergency On/Off switch should only be used when it is required to shut the chiller off im­mediately. Power to all modules is interrupted when this switch is off and all outputs from these modules will be turned off.
Energy Management Module (EMM)
The EMM is available as a factory-installed option or as a field-installed accessory. See Fig. 21. When the EMM module is field-installed, the Carrier Controller must be set up to com­municate with the EMM module (Main Menu
tion Menu Module
Factory Parameters  Energy Management
Yes). The Energy Management Module allows the
following functions:
• Chilled Water Temperature Reset — Resets the chilled wa­ter set point by the following methods:
a. 4 to 20 mA Input: A field-supplied signal generator
1
and
/2-watt, 250-ohm resistor are required.
b. Space Temperature: A field-supplied space tempera-
ture sensor is required.
• Demand Limit — Limits the capacity of the machine from unit capacity by the following methods:
Configura-
a. 4 to 20 mA Input: A field-supplied signal generator
1
and
/2-watt, 250-ohm resistor are required.
b. 2 or 3-Step Switch Control: A field-supplied dry con-
tact switch is required. (One-Step Demand Limit does not require the EMM.)
• Occupancy Override — Extends the occupied period for machine operation. A field-supplied dry contact switch is required.
• Remote Chiller Lockout — Disables the chiller when closed. A field-supplied dry contact switch is required.
• Ice Done Control Switch — Signals the machine to exit the Ice Build mode and enter an unoccupied time period. A field-supplied dry contact switch is required.
The following status functions are available with the EMM board:
• Capacity Output Signal — A 0 to10 vdc analog output sig­nal indicating chiller capacity is available.
• Shutdown Status Relay — A 24 vac output signal indicat­ing that the machine is shutting down.
• Alert Relay — A 24 vac output signal indicating the unit has an active alert.
• Compressor Run Status — A 24 vac output signal (one for compressor A, one for compressor B), indicating the com­pressor is on.
The EMM communicates the status of all inputs with the Carri­er Controller module, and the controls adjusts the control point, capacity limit, and other functions according to the inputs re­ceived. See Table 12 for EMM board inputs and outputs.
CAUTION
Care should be taken when interfacing with other manufactur­er’s control systems due to possible power supply differences, full wave bridge versus half wave rectification, which could lead to equipment damage. The two different power supplies cannot be mixed. Carrier Controller controls use half wave rectification. A signal isolation device should be utilized if a full wave bridge rectifier signal generating device is used.
Fig. 21 — Energy Management Module
18
Page 19
Table 12 — EMM Board Inputs and Outputs
CHANNEL
CH 01 AI CH 02 AI SPACETMP Space temperature AI-02 10K Thermistor CH 03 AI — — AI-03 5/10K Thermistor CH 04 AI — — AI-04 5/10K Thermistor CH 05 AI J7A SP_RESET Setpoint reset AI-06 0-5V CH 06 AI J7B LIM_ANAL Capacity limit AI-07 0-5V CH 07 AO J8 CAP_T % Total capacity running AO-01 0-10 Vdc CH 08 DI J4, CH8 OCC_OVSW Occupancy override DI-01 — CH 09 DI J4, CH9 LIM_SW2 Demand limit SW2 DI-02 — CH 10 DI J4, CH10 REM_LOCK Remote lockout switch DI-03 — CH 11a DI J4, CH11A ICE_SW Ice done DI-04 — CH 11b DI J4, CH11B — — DI-05 — CH 12 DI J5, CH12 — — DI-06 — CH 13 DI J5, CH13 — — DI-07 — CH 14 DI J5, CH14 — — DI-08 — CH 15 DI J5, CH15 — — DI-09 — CH 16 DO J2A CP_A Compressor A run status DO-01 Triac CH 17 DO J2A CP_B Compressor B run status DO-02 Triac CH 18 DO J2A — — — — CH 19 DO J2A — — — — CH 20 DO J2B — — — — CH 21 DO J2B — — — — CH 22 DO J2B — — — — CH 23 DO J2B — — — — CH 24 DO J3 SHUTDOWN Shutdown relay DO-09 Relay CH 25 DO J3 ALERT Alert relay DO-10 Relay
IN/OUT
TYPE
Local Equipment Network
Information is transmitted between modules via a 3-wire com­munication bus or LEN.
Board Addresses
All boards (except the Carrier Controller display and the Energy Management Module) have DIP switches to set the address.
Control Module Communication
RED LED Proper operation of the control boards can be visually checked
by looking at the red status LEDs (Light-Emitting Diodes). When operating correctly, the red status LEDs will blink in unison at a rate of once every 2 seconds. If the red LEDs are not blinking in unison, verify that correct power is being sup­plied to all modules and that all communication wiring is con­nected securely. Confirm current version of software installed on SmartView panel by navigating to Control Identification Menu (Main Menu
uration Menu  Control Identification Menu  Software Part Number). If a newer version of the software exists, con-
tact your Carrier service representative service to reload current software. If the problem still persists, replace the Carrier Con­troller module. A red LED that is lit continuously or blinking at a rate of once per second or faster indicates that the board should be replaced.
GREEN LED All boards have a green LEN LED which should be blinking
Configuration Menu  HMI Config-
BOARD
CONNECTOR
J6
CCN POINT
— — AI-01 5/10K Thermistor
POINT
DESCRIPTION
I/O POINT
NAME
INPUT/OUTPUT
communication between modules. These 3 wires run in parallel from module to module. They connect to J9 on EMM and AUX boards, and to J12 or J13 on SIOBs. A valid unit config­uration must be in the Carrier Controller module for proper LEN communication.
Carrier Comfort Network® Interface
All 30XV units can be connected to the CCN, if desired. The communication bus wiring is RS-485 Communication Wiring, CM or CMP rated consisting of a shielded, 3 conductor cable with drain wire and is field supplied and installed. The system elements are connected to the communication bus in a daisy chain arrangement. The positive pin of each system element communication connector must be wired to the positive pins of the system elements on either side of it. The negative and signal ground pins of each system element must also be wired in the same manner. Wiring connections for CCN should be made at TB3. See Fig. 22. For noise consideration, communication wir­ing must be separate and not run in parallel with other wiring.
NOTE: Conductors and drain wire must be 20 AWG (American Wire Gage) minimum stranded, tinned copper. Individual con­ductors must be insulated with PVC (Polyvinyl Chloride), PVC/ nylon, vinyl, Teflon 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of –20°C to 60°C is required. High temperature applica­tions may require a higher temperature range. Plenum applica­tions will require plenum rated cable. Cable voltage require­ments must match the application.
1
, or polyethylene. An aluminum/polyester
TYPE
whenever power is on. If the LEDs are not blinking as de­scribed check LEN connections for potential communication errors at the board connectors. A 3-wire bus accomplishes
1. Teflon is a registered trademark of DuPont.
19
Page 20
Fig. 22 — Carrier Controller CCN Communication Wiring
When connecting to a CCN communication bus, it is important that a color-coding scheme be used for the entire network to simplify the installation. It is recommended that red be used for the signal positive, black for the signal negative, and white for the signal ground. Use a similar scheme for cables containing different colored wires.
At each system element, the shields of its communication bus cables must be tied together. If the communication bus is entirely within one building, the resulting continuous shield must be con­nected to a ground at one point only. If the communication bus cable exits from one building and enters another, the shields must be connected to grounds at the lightning suppressor in each building where the cable enters or exits the building (one point per building only). To connect the unit to the network:
1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white (ground), and black (–) conductors. (Substitute appropriate colors for different colored cables.)
3. Connect the red wire to (+) terminal on TB3 of the plug, the white wire to COM terminal, and the black wire to the (–) terminal.
4. The RJ14 CCN connector on TB3 can also be used, but is only intended for temporary connection (for example, a lap­top computer running Network Service Tool).
The remote alarm annunciator relay, indicating that one circuit or the complete unit has been shut down, can be connected to TB5-12 and TB5-21. Refer to unit wiring diagrams. For the re­mote alert annunciator relay, indicating that an alert is active but neither circuit is shut down, a field-supplied and installed relay must be connected between TB6-18 and TB6-26. The Energy Management Module is required for this feature. The unit con­figuration must have the Energy Management Module enabled (Main Menu

Configuration Menu Factory Parameter)
set EMM to YES(1).
CONFIGURATION (SOFTWARE)
Carrier Controller Operation Configuration Tables
The Carrier Controller control system can be configured for a range of operating conditions and equipment arrangements. The following parameters should be configured based on unique system layout and operating requirements.
The system parameters may be configured through the Carrier Controller interface or remotely through the CCN. Table 13 shows the Carrier Controller configuration required to access the unit on the CCN. Figure 23 shows the CCN configuration screen.
Table 13 — Carrier Controller Identification
Configuration Table
IMPORTANT: A shorted CCN bus cable will prevent some routines from running and may prevent the unit from starting. If abnormal conditions occur, disconnect the CCN bus. If conditions return to normal, check the CCN connector and cable. Run new cable if necessary. A short in one section of the bus can cause problems with all system elements on the bus.
External Sensor Wiring
External sensors, such as a Space Temperature Sensor, must be wired to the unit, if values are not communicated. The wiring should be CM or CMP rated depending on the application. Wiring is field supplied and installed. For wiring runs of less than 100 feet (30.5 m), 2-conductor, twisted pair, unshielded wire is acceptable. For wiring runs of 100 feet (30.5 m) or more, 2-conductor, twisted pair, shielded wire is recommend­ed. For noise consideration, sensor wiring must be separate and not run in parallel with other wiring.
NOTE: Conductors and drain wire must be 20 AWG stranded, tinned copper. Individual conductors must be insulated with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An alumi­num/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of –20°C to 60°C is required. High tempera­ture applications may require a higher temperature range. Ple­num applications will require plenum rated cable. Cable volt­age requirements must match the application.
Remote Alarm and Alert Relays
The 30XV chiller can be equipped with remote alert and remote alarm annunciator contacts. Both relays connected to these con­tacts must be rated for a maximum power draw of 10 va sealed, 25 va inrush at 24 volts.
PATH DISPLAY NAME VALUE
Main Menu Configuration Menu HMI Configura­tion MenuCCN Configuration Menu
CCN Address CCN Bus
Primary Bus Baud Rate
Default=1
Default=0
Default=9600
Fig. 23 — CCN Configuration Screen
Carrier Controller Menu Tables
Carrier Controller operation is controlled by configuration in­formation entered in the configuration tables listed in Tables 14-18. Access to different parameters may be available to all users (BASIC) or password-protected (ADVANCED USER, SERVICE, FACTORY). See Appendix A for detailed descrip­tions of all control tables and parameters.
20
Page 21
Table 14 — Main Menu Table
ITEM CCN MENU NAME ACCESS MENU TEXT DESCRIPTION MENU ICON
1
2
3
4
5
6
7
8
GENUINT
TEMP
PRESSURE
INPUTS
OUTPUTS
PUMPSTAT
RUNTIME
MODES
BASIC, ADVANCED USER,
SERVICE, FACTORY
BASIC, ADVANCED USER,
SERVICE, FACTORY
BASIC, ADVANCED USER,
SERVICE, FACTORY
BASIC, ADVANCED USER,
SERVICE, FACTORY
BASIC, ADVANCED USER,
SERVICE, FACTORY
BASIC, ADVANCED USER,
SERVICE, FACTORY
BASIC, ADVANCED USER,
SERVICE, FACTORY
BASIC, ADVANCED USER,
SERVICE, FACTORY
General Parameters
Temperatures
Pressures
Inputs Status
Outputs Status
Pump Status
Run Times
Modes
SETPOINT
9
CONFIG
10
QCK_TEST SERVICE, FACTORY Quick Test Table
11
MAINTAIN SERVICE, FACTORY Maintenance Menu
12
TRENDING
13
ADVANCED USER, SER-
VICE, FACTORY
ADVANCED USER, SER-
VICE, FACTORY
BASIC, ADVANCED USER,
SERVICE, FACTORY
Setpoint Table
Configuration Menu
Trend Display
Table 15 — Alarms Menu Table
ITEM CCN MENU NAME ACCESS MENU TEXT DESCRIPTION MENU ICON
ALARMRST SERVICE, FACTORY Reset Alarms
1
CUR_ALM BASIC, ADVANCED USER, Current Alarms
2
ALMHIST1 BASIC, ADVANCED USER, Alarm Historic
3
ALMHIST2 BASIC, ADVANCED USER, Major Alarm Historic
4
21
Page 22
Table 16 — Configuration Menu Table
ITEM CCN MENU NAME ACCESS MENU TEXT DESCRIPTION MENU ICON
HMI_CONF ADVANCED USER HMI Configuration
1
GEN_CONF ADVANCED USER General Configuration
2
PUMPCONF ADVANCED USER Pump Configuration
3
RESETCFG ADVANCED USER Reset Configuration
4
SCHEDULE ADVANCED USER Schedule Menu
5
HOLIDAY ADVANCED USER Holiday Menu
6
BRODCAST ADVANCED USER Broadcast Menu
7
FACTORY FACTORY Factory Parameters
8
FACTORY2 FACTORY Factory2 Parameters
9
SERVICE SERVICE, FACTORY Service Parameters
10
UPDTHOUR SERVICE, FACTORY Update Running Hour
11
MST_SLV SERVICE, FACTORY Master Slave Config
12
CP_UNABL SERVICE, FACTORY Compressor Enable
13
EMAILCFG SERVICE, FACTORY Email Configuration
14
22
Page 23
Table 17 — Maintenance Menu Table
ITEM CCN MENU NAME ACCESS MENU TEXT DESCRIPTION ICON
1 CAPACTRL SERVICE, FACTORY Capacity Control
2 VLT_DRV SERVICE, FACTORY VLT Drive Maintenance
3 LAST_POR SERVICE, FACTORY Last PowerOn Reset
4 EXV_CTRL SERVICE, FACTORY EXV Control
5 LIMITS SERVICE, FACTORY Control Limits
6 M_MSTSLV SERVICE, FACTORY Master Slave Control
7 ECO_CTRL SERVICE, FACTORY EXV Eco. Control
8 FAN_CTRL SERVICE, FACTORY Fan Control
9 FAN_DRV SERVICE, FACTORY Fan Drive Maintenance
10 FAN_DRV2 SERVICE, FACTORY Fan Drive Addressing
11 TBLSHT SERVICE, FACTORY Troubleshoot Info
23
Page 24
Table 18 — HMI Configuration Menu Table
ITEM CCN MENU NAME ACCESS MENU TEXT DESCRIPTION ICON
1 NET_ETH0 SERVICE, FACTORY Network Conn - eth0
2 NET_ETH1 SERVICE, FACTORY Network Conn - eth1
3 CCN_CONF SERVICE, FACTORY CCN Configuration
4 BAC_CONF SERVICE, FACTORY BACnet Configuration
5 DATETIME SERVICE, FACTORY Date/Time Configuration
6 CTRL_ID ADVANCED USER Control Identification
7 CPU_MEM ADVANCED USER CPU/Memory
8 TERM_RES SERVICE, FACTORY Termination Resistor
9 SYS_INFO ADVANCED USER System Information
10 SCRN_BRT ADVANCED USER Screen Brightness
24
Page 25
Machine Control Methods
This term refers to how the machine is started and stopped. Several Machine Control Methods are available.
• Local On
• Local Schedule
•Network
•Remote
•Master
The Carrier Controller Start/Stop button is used to select one of the above control types; see Fig. 24. The Carrier Con­troller Start/Stop button is used to select one of the above con­trol types. Once the Start/Stop button is touched, and assuming the unit is not running, the current start method will be indicat­ed in green; if this is the case, the option to switch to “Local Off” will also be available. See Fig. 24 for details. In addition, when the Local control type is selected, this button can be used to select a particular functional mode: On, Off, or Schedule mode. If the Start/Stop button is green the unit is running. If the Start/Stop button is gray the unit is not running. If the button is flashing green then the unit is preparing to start.
Fig. 24 — Machine Control Methods
See Fig. 25 for Machine Control Methods Local Off.
LOCAL ON With this mode selected, the unit is under local control and will
be allowed to start. The unit will ignore the Remote Control Contacts, as well as the Enable-Off-Remote Switch (SW1) and any network commands except Emergency Stop, as well as the Enable-Off-Remote (SW1) input. Use this method if the unit is to run all the time without direction from a Building Manage­ment System or network.
LOCAL SCHEDULE With this mode selected, the unit is under local control and will
be allowed to start if Occupancy Schedule 1 Configuration
Menu
time is within an occupied period. Otherwise, the unit will re­main off. See “DEFINING OCCUPANCY SCHEDULE” on page 28 for details on configuring a local schedule. The unit will ignore the Remote Control Contacts, as well as the En­able-Off-Remote (SW1) and any network commands except Emergency Stop. Use this method if the unit is to run based on an occupancy schedule without direction from a Building Man­agement System or network.
NETWORK With this mode selected, the unit is under CCN control and will
be controlled by CCN commands. The unit will ignore the Re­mote Control Contacts, as well as the Enable-Off-Remote (SW1) input. Use this method if the unit is to run based on a Building Management System or network.
REMOTE With this mode selected, the unit is under remote control and will
be allowed to start if the Enable-Off-Remote Switch (SW1) is in the Remote position and the Remote Contacts (TB5-9 and -10) are closed. Alternatively, if the Enable-Off-Remote Switch (SW1) is in the Enable position, the unit will operate regardless of the Re­mote Contact status (TB5-9 and -10), since it will be bypassed. The unit will ignore any network commands except Emergency Stop. Use this method if the unit is to operate the chiller via a con­tact closure from a Building Management System.
MASTER With this mode selected, the unit is operating as the Master unit of
a 2-unit Master-Slave Chiller Plant. The Master unit can be started under Local On, Local Schedule, Network, or Remote. The excep­tions noted for each of the control methods will still apply. Use this method if the unit is to run as the Master unit.
Table 19 summarizes the available operating types.
Schedule Menu  OCCPC01S indicates the current
Fig. 25 — Machine Control Methods showing Current
Start Method and Local Off Option
25
Page 26
Table 19 — Operating Types
MACHINE CONTROL TYPE OPERATING TYPE DESCRIPTION
LOCAL OFF Local
LOCAL ON Local
LOCAL SCHEDULE Local
NETWORK CCN
REMOTE Remote
MASTER Master
The unit is under Local control method. It will remain halted and will ignore all CCN network commands and remote switch contacts.
The unit is under Local control method and will be allowed to start. The control will ignore all remote control contacts and all CCN network force commands (except the Emergency Stop Com­mand).
The unit is under Local control method and will be allowed to start if the schedule no. 1 is occu­pied (CHIL_OCC). Otherwise, the unit will remain off. The control will ignore all remote control contacts and all CCN network force commands (except the Emergency Stop Command).
The unit is under CCN control method and will be controlled by CCN force commands. The con­trol will ignore all remote control contacts.
The unit is under Remote control method and will be controlled by the start/stop. In this mode, no CCN force command can affect the unit control except the Emergency Stop Command.
The unit is configured as the master unit in a two-unit master/slave plant. The master unit con­trol method can be done locally, remotely or through CCN commands upon the master/slave configuration.
MACHINE CONTROL METHOD SELECTION The Machine Control Method is selected through the Carrier
Controller by touching the Start/Stop button .
Start/Stop Selection Screen
The Carrier Controller Start/Stop button is a hotkey, and when touched, opens the Start/Stop selection screen. and displays the list of Machine Control Methods if the unit is off (Fig. 24), or Confirm Stop if the unit is on (Fig. 26).
Start a Stopped Machine
If the unit is off, the Start/Stop button
will be gray. Touch
the icon to display the list of operating modes and select the re­quired mode. Once the unit has been started, the display will return to the home screen.
Stop a Running Machine
To stop a running unit, touch the green Start/Stop button . For Machine Control Methods Local On or Master, confirm the
Fig. 27 — Chiller May Restart Automatically Warning
unit shutdown by touching Confirm Stop or cancel by touching the Back button (Fig. 26).
Screen
Fig. 26 — Confirm Stop
For Machine Control Method Local Schedule, touch the Local Off button to stop the machine or Back button to cancel (Fig. 26).
For Machine Control Method Network, touch the Local Off button to stop the machine or Back button to cancel (Fig. 27).
If the unit was operating when a power failure occurred, the controller initializes when power is restored and displays a Warning screen to indicate the machine may start (Fig. 27). If the Stop Chiller button is touched, the Success screen will be displayed (Fig. 28). When the initialization period is complete, the Warning screen, if the unit is not stopped, or Success screen will clear as the Home Screen is displayed.
Fig. 28 — Chiller in Off Position Screen
Once the unit has been stopped, the Home screen is displayed. If the unit is running, touching the Start/Stop button displays a
screen with a Confirm Stop button (see Fig. 26), which when touched changes the chiller to Local Off mode. If the unit is Off, touching the Start/Stop button shows a list of operating types with the currently selected type corresponding to the last running operating type (Fig. 24).
MACHINE ON/OFF FUNCTION The machine operating state can be viewed by going to Main
Menu
General Parameters  Run Status. Table 20 sum-
marizes possible unit states.
26
Page 27
Table 20 — Unit States
STATE DESCRIPTION
Off Unit is commanded to be off
Stopping
Delay
Running
Ready Unit compressor capacity is 0%. Unit is ready to start.
Override
Tripout Unit is Off due to an alarm Test Unit is in Quick Test
Unit is currently stopping (after a manual, emergency, or shutdown request). Next state will be Off.
Unit is in delay at start-up (waiting for the end of the On/Off delay to be reached). Next state will be Running.
Unit compressor capacity is more that 0% (unit has started running)
The compressor cannot start because of an override (SST, SCT, etc.)
Table 21 summarizes the unit control method and stop or go status with regard to the following parameters set in the Carrier Controller module:
• Machine Control Method: Machine Control Method as se­lected on the unit Start/Stop screen.
• CHIL_S_S: Current CCN chiller start/stop force com­mand (enable/disable). Main Menu
General Parame-
ters  Net:Cmd Start/Stop.
• ONOFF_SW: Start-stop contact status when unit is under re­mote operating type. Main Menu
Inputs Status  Re-
mote On/Off Switch.
• CHIL_OCC: Chiller occupied state. If the occupancy override input switch is closed, the chiller remains occu­pied regardless of the set point scheduled selection. Main
Menu
General Parameters  Net:Cmd Occupied.
• MS_CTRL: Master control type. This parameter status will determine if the master unit is going to be controlled locally, remotely, or through CCN. Main Menu
Menu
Master Slave Control (0=disabled, 1=master,
Maintenance
2=slave).
• EMSTOP: CCN emergency stop command (enable/disable).
Main Menu
General Parameters  Emergency Stop.
• Alarm shutdown: Unit is totally stopped due to alarm.
The Machine Control Method and Parameter Status combina­tions listed in Table 21 will determine the actual unit running state.
NOTE: When changing from one Machine Control Method (Local On, Local Schedule, Network, Remote, or Master) to another, the unit will observe a transition through the Off state before being allowed to start again. At this time the on-to-off delay is always applied.
Chilled Water Set Point Configuration
The chilled water set point and fluid type configuration will de­termine the chiller operating conditions.
FLUID SET POINT CONTROL LOCATION The factory default for the chilled water fluid set point is to
control to the leaving water temperature. An option to config­ure the machine for entering water control is available. To con­figure this option go to Main Menu
Service Parameters. The default for Entering Fluid Con- trol is Off (leaving fluid control is the default condition). To enable Entering Water Control, change Entering Fluid Con­trol to On. Entering Water Control is recommended for con-
stant flow applications only.
COOLING SET POINT SELECTION The Control Point (shown in the lower right corner of the Home
Screen, or Main Menu
General Parameters  Control
Point) represents the water temperature that the unit must pro-
duce. The unit will vary the capacity depending on the load condi­tions in order to satisfy the set point. The Control Point (CTRL_PNT) is calculated based on the Active Setpoint (Main
Menu
General Parameters) [Main Menu and General Param­eters in bold italics]. and the reset calculation, where Control Point = Current Setpoint + Temperature Reset. (See “Temperature Re­set” on page 38.) Control Point can be written to by the Building Management System, instead of the set point calculation only if Network is selected as the Machine Control Method for the unit. See Main Menu
General Parameters  Local=0 Net.-1 Re-
mote=2 to verify operating type.
Configuration Menu
Table 21 — Start/Stop Control
MACHINE CONTROL METHOD PARAMETER STATUS
CHIL_S_S ONOFF_SW MS-CTRL CHIL_OCC EMSTOP
Local Off ——————LocalOff
Local On — — — — Disable No Local On
Local Schedule — — — Yes Disable No Local On
— — — No — — Local Off
Remote —Open————RemoteOff
———No——RemoteOff
Closed Yes — — Remote On
CCN Disable — — — — — CCN Off
———No——CCNOff
Enable — — Yes Disabled No CCN On
Master — — Local No — — Local Off
— Open Remote — — — Remote Off
— — Remote No — — Remote Off
Disable — CCN — — — CCN Off
— — CCN No — — CCN Off
— — Local Yes Disable No Local On
— Closed Remote Yes Disable No Remote On
Enable CCN Yes Disable No CCN On
—
CHIL_OCC — Chiller Occupied State MA St — Master/Slave Operating Type CHIL_S_S — CCN Chiller Start/Stop Command MS-CTRL — Master/Slave Control EMSTOP — Emergency Stop ONOFF_SW — Remote On/Off Switch
————
LEGEND
Enable — — Off
—Yes— Off
Alarm
Shutdown
OPERATING
TYPE
UNIT
STATUS
27
Page 28
DEFINING SET POINTS The cooling set points are set via the Setpoint Table (Main Menu
Setpoint Table). Cooling Setpoint 1, Cooling Setpoint 2,
and Cooling Ice Setpoint are temperature set points that are
available as the Current Setpoint for unit operation. These set points are limited by the type of fluid in the system (see Table 22).
See the Ice Storage Operation section on page 46 for more de­tails about the Cooling Ice Setpoint.
All default set points are based on Leaving Water Control (En­tering Fluid Control, EWTO [Entering Water Temperature Off­set] set to No). Values must be confirmed for the individual set points. Limits for the set points are listed in Table 22. These values depend on the Evaporator Fluid Type and the Brine Freeze Setpoint (see Chilled Water Fluid Type Selection on page 30).
Table 22 — Evaporator Fluid Set Point Limits
Set Point Limits
Minimum* 38°F (3.3°C) 30°F (–1.1°C) 15°F (9.4°C) Maximum 60°F (15.5°C) 60°F (15.5°C) 60°F (15.5°C)
* The minimum set point for brine applications is related to the brine
freeze set point. The set point is limited to be no less than the brine freeze set point + 4°F (2.2°C).
EVAPORATOR FLUID TYPE (flui_typ)
1 = Water 2 = Medium Brine 3 = Low Brine
CURRENT OPERATING SET POINT Depending on the current operation type, the active set point can
be selected manually in the Main Menu, with the dry user con­tacts or with network commands (CCN or BACnet), or automat­ically with the set point time schedule (Occupancy Schedule 2).
Set points can be selected manually through the main interface when the unit is in Local operating type, through contacts when the unit is in Remote operating type, or through the RS485 bus when unit is in CCN mode.
Set points can also be selected automatically through a set point time schedule: when the period is occupied Cooling Set­point 1 will be activated, and when the period is Unoccupied Cooling Setpoint 2 will be active. When in local operating type, time schedule is available if the Setpoint Select Variable is set to AUTO (see below). In remote operating type, the AUTO mode will be available unless the dual set point control through contacts has already been selected. In CCN mode, the set point selection always depends on the time schedule. The set point can be forced through the SP_OCC CCN point (0 = Occupied = Cooling Setpoint 1, 1 = Unoccupied = Cooling Setpoint 2).
Set point selection offers three different control options (Main
Menu
General Parameters  Setpoint Select): Auto, Set-
point 1, and Setpoint 2.
• 0 = Auto: The active cooling set point will be determined by the configured Occupancy Schedules. See the Defining Occupancy Schedule section for details on setting the schedules. Depending on the Ice Storage configuration and ice contact state, the active set point may alternately be set to the Cooling Ice Setpoint.
• 1 = Setpoint 1: The active cooling set point will be Cooling Setpoint 1 defined in the set point table.
• 2 = Setpoint 2: The active cooling set point will be Cooling Setpoint 2 defined in the set point table. Depending on the Ice Storage configuration and ice contact state, the active set point may alternately be set to the Cooling Ice Setpoint.
SETPOINT OCCUPANCY Setpoint Occupancy is the default configuration for the Setpoint
Select variable. When Setpoint Select (Main Menu
General
Parameters  Setpoint Select) is configured to 0 (Auto), the
unit’s active set point is based on the programmed occupancy schedules. Under Time Schedule 1 (OCCPC01S), the unit
controls to Cooling Set Point 1 (csp1) during the occupied peri­ods. If the Time Schedule 2 (OCCPC02S) is in use, the unit’s ac­tive set point is based on Cooling Set Point 1 (csp1) (Main
Menu
Setpoint Table  Cooling Setpoint 1) during the oc-
cupied period and Cooling Set Point 2 (csp2) (Main Menu
Setpoint Table  Cooling Setpoint 2) during the unoccupied period. The two schedules are used together to determine periods when the chiller will be controlling to Setpoint 1, Setpoint 2, or Off. See Table 23 for details on how the active cooling set point is determined based on unit operating type and parameter set­tings.
DEFINING OCCUPANCY SCHEDULE Two internal Time Schedules are available and must be field
programmed. Occupancy Schedule 1 (OCCPC01S) is used for single set point On/Off control. Occupancy Schedule 2 (OC­CPC02S) is used in combination with OCCPC01S for dual set point On/Off and Occupied/Unoccupied set point control. To access the Schedule screens, go to Main Menu
tion Menu
Schedule Menu.
Configura-
If the chiller is to be controlled to a single set point, use Sched­ule 1 (OCCPC01S). This type of schedule will start and stop the machine only. During the unoccupied times, the chiller will be off. The unit start/stop schedule OCCPC01S has a default setting of always occupied. If the chiller is to be controlled to 2 set points, occupied and unoccupied, also use Schedule 2 (OC­CPC02S). Cooling Setpoint 1 will be active during occupied periods, and Cooling Setpoint 2 will be active during unoccu­pied periods.
To set the occupancy schedules, select OCCPC01S or OC­CPC02S and select the applicable days for the displayed time schedule period. The selected period will be displayed as a green band on the timeline. Touch the Save button to confirm or the Cancel button to cancel changes. See Fig. 29.
The schedules consist of 8 user-configurable occupied time pe­riods. The control supports time schedules for local control, re­mote control, and ice building. These time periods can be flagged to be in effect or not in effect on each day of the week. The day begins at 00:00 and ends at 24:00. The machine is in unoccupied mode unless a scheduled time period is in effect. If an occupied period is to extend past midnight, the occupied pe­riod must end at 24:00 hours (midnight) and a new occupied period must be programmed to begin at 00:00 hours.
In the example in Table 24, an early morning pulldown time period is scheduled for Monday morning from 12:00 AM to 3:00 AM. The occupied period starts at 7:00 AM, Monday through Saturday. The occupied time ends at 6:00 PM on Mon­day and Tuesday, 9:30 PM on Wednesday, 5:00 PM on Thurs­day and Friday, and 12:00 PM on Saturday.
NOTE: This example schedule was designed to illustrate the programming of the schedule function and is not intended as a recommended schedule for chiller operation.
Holiday Schedule
The unit control allows up to 16 holiday periods. Each holiday pe­riod is defined by three parameters: the month, the start day, and the duration of the holiday period. During the holiday periods, the controller will be in occupied or unoccupied mode, depending on the periods validated as holidays. The Holiday Configuration Ta­ble is accessed by Main Menu
Configuration Menu  Holi-
day Menu. Select one of the 16 available Holiday periods
(HOLDY_01 through HOLDY_16) to define the holiday.
CCN Global Time Schedule
In addition to the two onboard occupancy schedules (OCCPC01S and OCCPC02S), the Carrier Controller can also receive a time schedule broadcast from another element in the CCN network.
The 30XV with Greenspeed
®
Intelligence chillers can be con­figured to follow a CCN Global Time Schedule broadcast by another system element. The Occupancy Table (OCCPC01S)
28
Page 29
number must be changed to configure the unit to broadcast a Global Time Schedule. The Schedule Number can be set from 65 to 99 (OCCPC65S to OCCPC99S). When OCC1PxxS is set to a value of 65 or greater and all attached schedules are 00:00 (that is, no occupied time periods), an occupancy flag is broad­cast over the CCN every time it transitions from occupied to
Table 23 — Active Cooling Set Point Parameters
unoccupied or vice-versa. The ComfortVIEW™ Network Manager’s Configure and Modify commands or the Service Tool’s Modify/Names function must be used to change the number of the Occupancy Equipment Part Table Name (OC­CPC01E) to the Global Schedule Number. The Schedule Num­ber can be set from 65 to 99 (OCCPC65E to OCCPC99E).
OPERATING
TYPE
Local
Remote
Network
* Ice Storage Configuration and Ice Done Contact apply only to units
with EMM.
Setpoint
Selection
sp-1 Default Any Any Default Cooling Setpoint 1 sp-2 No Any Any Default Cooling Setpoint 2 sp-2 Yes Closed Any N/A Cooling Setpoint 2
sp-2 Yes Open Any N/A Cooling Ice Setpoint automatic Default Any Any Occupied Cooling Setpoint 1 automatic No Any Any Unoccupied Cooling Setpoint 2 automatic Yes Closed Any Unoccupied Cooling Setpoint 2 automatic Yes Open Any Unoccupied Cooling Ice Setpoint
Default Default Any Open Default Cooling Setpoint 1 Default No Any Closed Default Cooling Setpoint 2
N/A Yes Closed Closed N/A Cooling Setpoint 2 Default Yes Open Closed Default Cooling Ice Setpoint Default Default Any Any Occupied Cooling Setpoint 1 Default Default Any Any Unoccupied Cooling Setpoint 2
Ice Storage
Configuration*
PARAMETER STATUS
Ice Done Contact*
Setpoint
Switch
Schedule 2 Status
ACTIVE SETPOINT
29
Page 30
Fig. 29 — Schedule Menu
Table 24 — Configuring Schedules (Example)
ITEM PATH VALUE
Occupied from Occupied to 03:00 Monday Select Yes Tuesday Select No Wednesday Select No Thursday Select No Friday Select No Saturday Select No Sunday Select No Holiday Select No
Occupied from Occupied to 18:00 Monday Select Yes Tuesday Select Yes Wednesday Select No Thursday Select No Friday Select No Saturday Select No Sunday Select No Holiday Select No
Occupied from Occupied to 21:30 Monday Select No Tuesday Select No Wednesday Select Yes Thursday Select No Friday Select No Saturday Select No Sunday Select No Holiday Select No
Occupied from Occupied to 17:00 Monday Select No Tuesday Select No Wednesday Select No Thursday Select Yes Friday Select Yes Saturday Select No Sunday Select No Holiday Select No
Occupied from Occupied to 12:00 Monday Select No Tuesday Select No Wednesday Select No Thursday Select No Friday Select No Saturday Select Yes Sunday Select No Holiday Select No
Period 1
Main Menu
Main Menu
Main Menu
Main Menu
Main Menu

Schedule Menu OCCPC01S or
Schedule Menu OCCPC01S or
Schedule Menu OCCPC01S or
Schedule Menu OCCPC01S or
Schedule Menu OCCPC01S or
Configuration Menu
OCCPC02S
Page 1
Period 2

Configuration Menu
OCCPC02S
Page 2
Period 3

Configuration Menu
OCCPC02S
Page 3
Period 4

Configuration Menu
OCCPC02S
Page 4
Period 5

Configuration Menu
OCCPC02S
Page 5
00:00

07:00

07:00

07:00

07:00

When OCC1PxxS is set to a value of 65 or greater and a time schedule is configured for at least one occupancy period, the system will assume that the unit is going to be the master ele­ment for this schedule (the system element doing the broad­casting). In that case the unit Equipment and Supervisory part table names will be automatically modified to OCCPCxxE and OCCPCxxS.
By configuring their appropriate Time Schedule decisions to the same number, other devices on the network can follow this same schedule. The Enable-Off-Remote Contact must be in the Enable position or the Remote Contact position with the con­tacts closed for the unit to operate.
The Unit Run Status (Main Menu
General Parameters
Run Status) will indicate the current status of the machine de­pending on the schedule. The unit Occupied status (Main
Menu
General Parameters  Setpoint Occupied) will in-
dicate the current occupied schedule according to the schedule, either NO or YES.
The Status Unit Control Type (Main Menu
General Pa-
rameters) will be 0 when the switch is Off. The Status Unit
Control Type will be 2 when the Enable-Off-Remote Contact switch input is On.
CCN Control
To operate under this control, Network must be selected under the Select Machine Mode accessed by touching the Start/Stop button (see “MACHINE CONTROL METHOD SELECTION” on page 26).
An external CCN device such as Chillervisor controls the On/ Off state of the machine. Careful evaluation of Chilled Water Plant control is necessary. In the event Local Control is estab­lished, be sure that all pumps, valves, and other devices are ca­pable of operating properly. In the event of a loss of communi­cation with the network, the machine will start and be con­trolled locally. The CCN device forces the variable CHIL_S_S to control the chiller. The Unit Run Status (Main Menu
General Parameters  Run Status) will indicate the current status of the machine (OFF, RUNNING, STOPPING or DE­LAY), depending on the CCN command. The unit Occupied status (Main Menu
General Parameters) will indicate the current occupied state according to the CCN command and will be displayed as either NO or YES. The Status Unit Control Type (ctrl_typ) will be LOCAL OFF when the Start/Stop but­ton is Off. The Status Unit Control Type will be CCN when the Enable-Off-Remote Contact switch input is Closed and the CHIL_S_S variable is Stop or Start. For dual chiller control applications, the slave chiller must be enabled using the CCN CONTROL option.
CHILLED WATER FLUID TYPE SELECTION The chilled water fluid type must be configured to obtain the
proper leaving water set point control range and freeze protec­tion. The Evaporator Fluid Type (flui_typ) (Main Menu
Configuration Menu  Service Parameters  Evaporator Fluid Type) can be set to water or brine.
To configure this option:
DISPLAY
NAME
Evaporator Fluid Type
PATH VALUE
Main Menu Configuration Menu Service Parameters
1 = Water 38 to 60°F
2 = Medium
brine 3 = Low brine 15° to 60°F
SETPOINT
RANGE
(3.3 to 15.5°C) 30 to 60°F
(–1.1 to 15.5°C)
(9.4° to 15.5°C)
Fresh Water
Configure the unit Evaporator Fluid Type to Water for units with­out brine or glycol installed in the chilled water loop. The factory default fluid type is fresh water. This option will allow for a water
30
Page 31
temperature set point range of 38 to 60°F (3.3 to 15.5°C). With water as the selection, the freeze point is fixed at 34°F (1.1°C).
Brine or Glycol
Configure the unit Evaporator Fluid Type to Medium Brine or Low Brine for units with brine or glycol added to the chilled water loop. The Low Brine option will allow for a set point temperature range of 14 to 36°F (–10 to 2.2°C).
See chart on page 30 for temperature limits for brine options. Before making this selection, confirm suitable antifreeze has
been added and is of sufficient concentration to protect the loop. In addition, the Brine Freeze Setpoint (Main Menu
Configuration Menu  Service Parameters  Brine Freeze Setpoint) must be set for proper freeze protection operation.
Set the Brine Freeze Setpoint to the freeze protection provided by the antifreeze concentration. This value will be the freeze point of the fluid.
Evaporator Pump Control
Evaporator pump control is required on all units unless the chilled water pump runs continuously or the chilled water sys­tem contains a suitable antifreeze solution. For units supplied with the pump option, this is set up from the factory. The 30XV units with Greenspeed gle or dual external evaporator pump control with the standard controls. In addition to the pumps, all wiring including connec­tions to the pump contactor and a feedback circuit from the contactor must be field supplied. Table 25 summarizes evapo­rator pump configuration parameters. Fig. 30 shows the wiring.
PUMP SELECTION The Evaporator Pump Sequence mode can be reached by fol-
lowing Main Menu uration. The available settings are:
• 0 = No Pump: The evaporator pump will not be controlled by the chiller. This is the default setting.
• 1 = One Pump Only, Factory Supplied Pumps: Use for a single remote pump or for factory supplied pumps. (“1” is also used for factory supplied pumps.)
• 2 = Two Pump Auto: When two pumps are selected in auto mode, only one pump will be allowed to run at a time and the control will determine the On/Off state of each pump. The control will start the pumps and automatically alter­nate the operation of the pumps to even the wear on the pumps, based on the hours configured under Pump Auto Rotation Delay (Main Menu Pump Configuration  Pump Auto Rotation Delay). If the difference between the operating hours of the two pumps exceeds the Pump Auto Rotation Delay, the lead pump will change. If a flow failure is detected, the other pump will attempt to start.
• 3 = Pump #1 Manual: Pump #1 will be the active pump.
• 4 = Pump #2 Manual: Pump #2 will be the active pump.
Table 25 — Evaporator Pump Configuration
DISPLAY NAME PATH VALUE
Evaporator Pumps Sequence
Pump Auto Rotation Delay
Pump Sticking Protection
Flow Checked If Pump Off
®
Intelligence can be configured for sin-
Configuration Menu  Pump Config-
Configuration Menu
Parameters
0 = No Pump (Default) 1 = One Pump Only ("1" is also used for factory supplied pumps.) 2 = Two Pumps Auto
Main Menu Configuration Menu Pump Configuration
3 = Pump no. 1 Manual 4 = Pump no. 2 Manual
Default: 48 hrs. (Range 24 to 3000 hrs.)
Default: No
Default: Yes
Fig. 30 — Wiring for Evaporator Pump Control
Factory supplied pumps should have this configuration set to 1. There is only one “on” signal to the pumps. The pumps run si­multaneously. Speed is controlled in the pump software and communication between the pumps sets the appropriate speed for each pump.When the Evaporator Pumps Sequence is con­figured, the evaporator pump output will be energized when the chiller enters an On state. Proof of flow from the chilled water flow switch (CWFS) is required for the unit to start me­chanical cooling. The evaporator pump output is also energized when certain alarms are generated. The evaporator pump out­put should be used as an override to the external pump control if evaporator pump control is not utilized. The evaporator pump output is energized if a 10001 Evaporator Freeze Protec­tion alarm is generated, which provides additional freeze pro­tection if the system is not protected with a suitable antifreeze solution.
If the Master/Slave function is not active for the chiller or if the Master/Slave function is active and the unit is the lead, the pump will be turned on when the unit is in On, Stopping, or Delay state. In addition, when the unit is turned off the pump will continue operating for 20 seconds after the last compressor is turned off. The pump will be turned on when requested by the evaporator heater function (see the Evaporator Freeze Pro­tection section on page 71).
FACTORY-SUPPLIED PUMPS Pumps supplied by the factory are piped in a parallel arrangement.
These pumps are driven with ECM variable speed motors. All of the pumps may run simultaneously. Sensorless control based in the pump motor is used to determine the speed of each pump. The chiller control treats the pump assembly as a single pump with re­gard to starting and stopping the pump system. For setup and oper­ating details, see “Factory-Supplied Pumps” on page 336.
PERIODIC PUMP QUICK START The control system has the ability to start the pumps periodi-
cally to maintain bearing lubrication and seal integrity. This function will be used when the unit is stopped for a long time
31
Page 32
period (e.g., during the winter season). If Pump Sticking Pro-
NOTE: After compressors are fully loaded, they will both load and unload equally with the VFDs (variable frequency drives).
tection (Main Menu
figuration
Pump Sticking Protection) is set to YES and if
Configuration Menu  Pump Con-
the unit is off at 2:00 PM, a pump will be started once each day for 45 seconds. If the unit has 2 pumps, Pump 1 will be started on even days (such as day 2, 4, or 6 of the month); Pump 2 will be started on odd days (such as day 1, 3 or 5 of the month). The default for this option is NO.
MASTER/SLAVE CHILLER PUMP OPERATION If the Master/Slave function is active and if the chiller is the
lag unit, then the pump will be turned on when the unit is in On mode and if the unit active lag demand limit is greater than 1%. Otherwise, the pump will be stopped 30 seconds after the last compressor is turned off. However, if the lag unit pump has been configured to run even if the unit is commanded to stop (Main Menu
Lag Unit Pump Control = 1 [Run if Unit Stops]) then the
Configuration Menu  Master/Slave Config
above condition will be ignored and the lag pump will run all the time.
CHILLED WATER FLOW SWITCH STATUS If Flow Checked if Pump Off (Main Menu
Configuration
Menu  Pump Configuration  Flow Checked if Pump Off) is set to YES, the control will monitor the chilled water
flow switch status and will send an alarm if the pump is com­manded off and the chilled water flow switch is closed. This can provide the user with information about a faulty evaporator pump contactor or a failed chilled water flow switch. This pa­rameter should be set to NO for series flow machines. The fac­tory default for this item is YES.
MANUAL OPERATION The evaporator pumps can be forced ON through the CCN
when the chiller is off. This allows the unit to run with no delay and for an unlimited length of time for flow rate calculations when the unit is installed on site. Manual operation of the pumps is controlled through CCN points CPUMP_1 (Main
Menu
Pump Status) and CPUMP_2 (Main Menu
Pump Status (0 = OFF, 1 = ON).
Circuit/Compressor Staging and Loading
The AquaForce® 30XV chillers with Greenspeed® Intelligence employ one compressor per circuit. As a result, circuit and compressor staging are the same. The control has several con­trol option parameters to load the compressors. The circuit/
compressor start can be configured as well as the loading of each circuit/compressor.
CIRCUIT/COMPRESSOR STAGING The control can be configured to decide which circuit/com-
pressor starts first. Three options for this variable are allowed: Automatic Lead-Lag, Circuit A Leads, or Circuit B Leads. The factory default is Automatic Lead-Lag.
The automatic lead-lag function determines which circuit/com­pressor starts first to even the wear on the compressors. The con­trol system determines the lead circuit to equalize the operating time of each circuit (value weighted by the number of start-ups of each circuit). As a result, the circuit with the lowest number of op­erating hours always starts first. The parameter can also be config­ured to always start a particular circuit/compressor first.
To configure this option:
DISPLAY NAME PATH
Circuit Priority Sequence
Main Menu Configuration Menu
General
Configuration
LINE
NO.
1 0 = Auto
VALUE
1 = Ckt A Priority 2 = Ckt B Priority
CIRCUIT/COMPRESSOR LOADING/UNLOADING The control uses an equal compressor loading and unloading
scheme as described below to optimize the efficiency of the unit. At start-up, the control starts the lead compressor at the lowest
frequency and then continues to load it up by increasing fre­quency output of the corresponding VFD. If the load reaches 65% of circuit load, then the control starts the lag compressor at its minimum frequency. While the lag compressor starts to load up, the lead compressor may ramp down to equalize with lag compressor, depending on conditions. When the loading of both compressors match, they continue to load up or load down in unison in response to the capacity demand.
In the process of unloading, if both the compressors reach min­imum frequency/load level, any further drop in capacity will cause the lag compressor to switch off and the lead compressor to ramp up until load is met again. Eventually with decrease in load the compressor goes down to minimum frequency/load and then shuts down. See Fig. 31 for a graphical representation of initial system loading and unloading. (Figure 31 shows an example of possible compressor loading for a given scenario. Since the controls are adaptive, actual loading may vary.)
Fig. 31 — Initial Compressor Loading/Unloading Method
32
Page 33
Dual Chiller Control
The dual chiller function allows for master/slave control of two units installed in parallel or series arrangement supplying chilled fluid on a common loop. The chillers must be linked by the Carrier Comfort Network same bus.
When the units are installed for parallel operation and chilled water control is done on the outlet side of the units, the dual chiller accessory kit (P/N 00EFN900044000A) is required. The kit includes additional leaving fluid temperature thermistors that must be installed on the common chilled water leaving piping as described in the Installation Instructions for the kit. The leaving fluid temperature sensors will be connected to each chiller as described in the installation instructions. When the chilled water control is done on the inlet side of the parallel units no additional temperature sensor is required. See the Field Wiring section in the 30XV Installation Instructions for dual chiller LWT sensor control wiring. When chillers are con­figured to operate in series mode no additional chilled water temperature sensor is required.
The master chiller will monitor all external commands such as start/stop, demand limiting, or set point select, and needs to be started in Master operating type. The commands are transmitted automatically to the slave unit, which must operate in CCN (Net­work) mode. The slave chiller has no action in the master/slave operations; it will only verify that CCN communication with the master chiller is correct. If the master chiller is turned off while the master/slave function is active, then the slave chiller will be stopped. Under certain circumstances, the slave unit may be start­ed first to balance the run times of the two units. In the event of a communication failure between the two units, each unit will return to an autonomous operating mode until the fault is cleared. If the master unit is stopped due to an alarm, the slave unit is authorized to start and therefore the slave unit configurations should be veri­fied with desired set points.
The CCN communication port for the Master and Slave chillers must be joined using a shielded cable in order to avoid communication issues.
The master/slave linkage will not be allowed to operate if any one of the slave chiller CTRL_PNT, DEM_LIM, LAG_LIM, or LCW_STPT variables has a force priority higher than a control force. In that case, the master/slave operations will not be allowed or will be disabled.
The control algorithm relies on several parameters that must be field configured for operation. Both chillers must be on the same CCN bus with different addresses. On both chillers, Mas­ter/Slave Select (Main Menu Master/Slave Config  Master/Slave Select) must be enabled (set to 1 [Master] or 2 [Slave]). The water piping arrangement must be specified with the Chiller in Series variable (Main
Menu
Chiller in Series). The Master chiller must be programmed with the Slave Address (Main Menu
al programming parameters may be configured to meet appli­cation requirements.
The Lead Lag Select variable (Main Menu Menu  Master/Slave Config  Lead Lag Select) determines which chiller is the lead machine. The options are: Always Lead, Lag Once Failed Only, and Lead/Lag Runtime Select. Under Run­time Select control, the lead chiller will change based on the time increment selected in the Lead/Lag Balance Delta configuration (Main Menu
the master and the slave remains less than the Lead/ Lag Balance Delta, the chiller designated as the lead will remain the lead chiller. The Lead/Lag changeover between the master and the slave chiller due to hour balance will occur during chiller operat­ing odd days, such as day 1, day 3, and day 5 of the month, at
Configuration Menu  Master/Slave Config
Master/Slave Config  Slave Address). Additional option-
Lead/Lag Balance Delta). If the run hour difference between
Configuration Menu  Master/Slave Config
®
network and operate on the
Configuration Menu
Configuration Menu
Configuration
12:00 a.m. If a lead chiller is not designated, the master chiller will always be designated the lead chiller.
The dual chiller control algorithm has the ability to delay the start of the lag chiller in two ways. The Lead Pulldown Time parameter (Main Menu
Slave Config
tiated after starting the lead chiller, before checking whether to start an additional chiller. This time delay gives the lead chiller a chance to remove the heat that the chilled water loop picked up while inactive during an unoccupied period. The second time delay, Lead/Lag Start Timer (Main Menu
tion Menu
is a time delay imposed between the last stage of the lead chiller and the start of the lag chiller. This prevents enabling the lag chiller until the lead/lag delay timer has expired.
A quicker start of the lag chiller can be accomplished by con­figuring the Lag Unit Pump Control parameter (Main Menu
Configuration Menu  Master/Slave Config  Lag Unit Pump Control). If the difference between the common leaving
water temperature and the set point is greater than the config­ured value, then the lag chiller will start.
A minimum on time for the lag chiller can be programmed with the Lag Minimum Running Time configuration (Main
Menu Lag Minimum Running Time). This parameter causes the
control to run the lag chiller for the programmed minimum on time. The Lag Unit Pump Control (Main Menu
tion Menu trol) can be configured such that the pump can be on or off
while the chiller is off. This parameter is only active in Parallel Chiller Operation.
The lead chiller is started first and the lag chiller will be main­tained at zero percent capacity through master forcing the lag demand limit value (LAG_LIM) to 0%. The lag water pump will be maintained off. When the lead chiller cannot be loaded anymore (because it is loaded at its full available capacity or at the master demand limit value) then the lag start timer is start­ed. When the lag start time has elapsed, if the error on the mas­ter controlled set point is greater than the dead band (start_di) and if the pulldown time is elapsed, then the lag chiller water pump will be turned on (if required by configuration) and the lag chiller will be allowed to start through the master chiller forcing the lag chiller demand limit value (LAG_LIM) to its own demand limit value. To ensure that the lag chiller will be unloaded first in case of water load decrease, the lead chiller set point error will be reset downwards by 4°F (2.2°C) provid­ed that the lead capacity is not zero.
Each dual chiller application, Parallel and Series, is described separately below.
DUAL CHILLER CONTROL FOR PARALLEL APPLICA­TIONS
To configure the master chiller for parallel applications, see Ta­ble 26. To configure the slave chiller for parallel applications, see Table 27.
Lead Pulldown Time) is a one-time delay ini-
Master/Slave Config  Lead/Lag Start Timer)
Configuration Menu  Master/Slave Config
Master/Slave Config  Lag Unit Pump Con-
Configuration Menu  Master/
Configura-
Configura-
33
Page 34
Table 26 — Dual Master Chiller Control Parameters for Parallel Applications
DISPLAY NAME PATH VALUE
Master/Slave Select
Master Control Type
Slave Address
Lead Lag Select
Lead/Lag Balance Delta
Lead/Lag Start Timer
Lead Pulldown Time
Start If Error Higher
Lag Minimum Running Time
Lag Unit Pump Control
Chiller In Series
Main Menu

Configuration Menu Master/Slave Config
1 (Master) Default: 0 (Disable)
1=Local Control 2=Remote Control 3=CCN Control Default: 1(Local) Configure for proper control type.
Must be set to the Slave Chiller’s address. The Master and Slave chiller must have different addresses and be on the same Bus Number Default: 2
0 (Master Always Leads) 1 (Lag One Failed Only) 2 (Lead/Lag Runtime Select) Default: 0 (Master Always Leads)
Range: 40 to 400 hours Default: 168 hours
Range: 2 to 30 minutes Default: 10 minutes
Range: 0 to 60 minutes Default: 0 minutes
Range: 3.0 to 18°F (1.7 to 10.0°C) Default: 4.0°F (2.2°C)
Range: 0 to 150 minutes Default: 0 minutes
0 (Stop If Unit Stops) 1 (Run If Unit Stops) Default: 0 (Stop If Unit Stops)
No (Not in Series) Default: No
Table 27 — Dual Slave Chiller Control Parameters for Parallel Applications
DISPLAY NAME PATH VALUE
Master/Slave Select
Master Control Type
Slave Address
Lead Lag Select

Lead/Lag Balance Delta
Lead/Lag Start Timer
Lead Pulldown Time
Start If Error Higher
Lag Minimum Running Time
Lag Unit Pump Control
Chiller In Series
NOTE: If pump control is configured to OFF (Master), then Lag Unit (Slave) Pump Control = 1. If pump control is set to any other value, then Lag Unit (Slave) Pump Control = 0. This configuration must be set consistently for both master and slave chillers.
Main Menu
Configuration Menu Master/Slave Config
2 (Slave) Default: 0 (Disable)
1=Local Control 2=Remote Control 3=CCN Control Default: 1(Local) Configure for proper control type.
Must be set to the Slave Chiller’s address. The master and slave chiller must have different addresses and be on the same Bus Number Default: 2
0 (Master Always Leads) 1 (Lag Once Failed Only) 2 (Lead/Lag Runtime Select) Default: 0 (Master Always Leads)
Range: 40 to 400 hours Default: 168 hours
Range: 2 to 30 minutes Default: 10 minutes
Range: 0 to 60 minutes Default: 0 minutes
Range: 3.0 to 18°F (1.7 to 10.0°C) Default: 4.0°F (2.2°C)
Range: 0 to 150 minutes Default: 0 minutes
0 (Stop If Unit Stops) 1 (Run If Unit Stops) Default: 0 (Stop If Unit Stops)
No (Not in Series) Default: No
34
Page 35
Parallel chiller control with dedicated pumps is recommended. The chiller must start and stop its own water pump located in its own piping. If pumps are not dedicated for each chiller’s piping, chiller isolation valves are required; each chiller must open and close its own isolation valve through the control. Fig­ures 32-35 show typical pump arrangements for dual chiller parallel applications.
Although not recommended, it is possible to configure the sys­tem with no individual pump control. In applications where the unit is configured for fresh water (Main Menu
tion Menu Service Parameters, Evaporator Fluid Type=1 [Fresh Water]), and Set Point temperature is close to the lower
limit of the fresh water range, it is possible for changeable leaving water conditions as the chilled water flow rate drops to an operating unit, causing the leaving chilled water tempera­ture to drop and initiate the evaporator freeze protection over­ride. Constant flow applications may alleviate this issue.

Configura-
CHWS TEMP SENSORS
CHECK VALVES
In constant water flow applications, the master chiller should be the primary control source for the chilled water pump. The slave chiller should have override capability. In the event of a communication failure between the master and slave chillers, the slave chiller will operate as a stand-alone machine and therefore must be able to enable the chilled water pump.
DUAL CHILLER CONTROL FOR SERIES CHILLER APPLICATIONS
When chillers are configured to work in series mode no addi­tional chilled water supply sensor is required. The master chiller will be installed downstream of the slave chiller (the slave chiller outlet fluid is the master inlet fluid). If pump con­trol is required, it will be controlled by the master chiller.
To configure the master chiller for series applications, see Ta­ble 28. To configure the slave chiller for series applications, see Table 29.
CONTROL BOX
SLAVE
CHILLER
SLAVE PUMP
CONTROL BOX
MASTER CHILLER
MASTER PUMP
FIELD WIRING FIELD COMMUNICATION WIRING
Fig. 32 — Typical Parallel Master/Slave Chillers
Dedicated Primary Pumping, Variable Flow, Leaving Water Control
NOTE: This is a simplified piping diagram. Not all hydronic specialties are shown.
LOAD
35
Page 36
ISOLATION VALVES
CONTROL BOX
SLAVE CHILLER
CONTROL BOX
MASTER CHILLER
LOAD
CHECK VALVES
FIELD WIRING FIELD COMMUNICATION WIRING
NOTE: This is a simplified piping diagram. Not all hydronic specialties are shown.
SLAVE PUMP
MASTER PUMP
CHWS TEMP SENSORS
CONTROL BOX
SLAVE CHILLER
ISOLATION VALVES
CONTROL BOX
MASTER CHILLER
MASTER PUMP
FIELD WIRING FIELD COMMUNICATION WIRING
Fig. 33 — Typical Parallel Master/Slave Chillers
Common Primary Pumping, Constant Flow, Leaving Water Control
NOTE: This is a simplified piping diagram. Not all hydronic specialties are shown.
LOAD
Dedicated Primary Pumping, Variable Flow, Entering Water Control
Fig. 34 — Typical Parallel Master/Slave Chillers
36
Page 37
Master/Slave Select
CONTROL BOX
SLAVE CHILLER
CONTROL BOX
MASTER CHILLER
LOAD
ISOLATION VALVES
FIELD WIRING FIELD COMMUNICATION WIRING
NOTE: This is a simplified piping diagram. Not all hydronic specialties are shown.
MASTER PUMP
ISOLATION VALVES
Master Control Type
Slave Address
Lead Lag Select
Lead/Lag Balance Delta
Lead/Lag Start Timer
Lead Pulldown Time
Start If Error Higher
Lag Minimum Running Time
Lag Unit Pump Control
Chiller In Series
Common Primary Pumping, Variable Flow, Entering Water Control
Fig. 35 — Typical Parallel Master/Slave Chillers
Table 28 — Master Chiller Configuration in Series Applications
DISPLAY NAME PATH VALUE
1 (Master) Default: 0 (Disable)
1=Local Control 2=Remote Control 3=CCN Control Default: 1(Local) Configure for proper control type.
Must be set to the Slave Chiller’s address. The Master and Slave chiller must have different addresses and be on the same Bus Number
Main Menu

Configuration Menu Master/Slave Config
Default: 2 0 (Master Always Leads)
1 (Lag One Failed Only) 2 (Lead/Lag Runtime Select) Default: 0 (Master Always Leads)
Range: 40 to 400 hours Default: 168 hours
Range: 2 to 30 minutes Default: 10 minutes
Range: 0 to 60 minutes Default: 0 minutes
Range: 3.0 to 18°F (1.7 to 10.0°C) Default: 4.0°F (2.2°C)
Range: 0 to 150 minutes Default: 0 minutes
0 (Stop If Unit Stops) 1 (Run If Unit Stops) Default: 0 (Stop If Unit Stops)
Yes (In Series) Default: No
37
Page 38
Table 29 — Slave Chiller Configuration in Series Applications
DISPLAY NAME PATH VALUE
Master/Slave Select
Master Control Type
Slave Address
Lead Lag Select

Lead/Lag Balance Delta
Lead/Lag Start Timer
Lead Pulldown Time
Start If Error Higher
Lag Minimum Running Time
Lag Unit Pump Control
Chiller In Series
NOTES:
1. If pump control is configured to OFF (Master), then LAG UNIT (Slave) PUMP SELECT (page 3 of the Master/Slave Config menu) = 1. If pump control is set to any other value, then LAG UNIT (Slave) PUMP SELECT = 0. This con­figuration must be set consistently for both master and slave chillers.
2. For Master/Slave Series Chiller Application, Master Chiller should always be downstream of Slave.
Main Menu
Configuration Menu Master/Slave Config
2 (Slave) Default: 0 (Disable)
1=Local Control 2=Remote Control 3=CCN Control Default: 1(Local) Configure for proper control type.
Must be set to the Slave Chiller’s address. The master and slave chiller must have different addresses and be on the same Bus Number Default: 2
0 (Master Always Leads) 1 (Lag Once Failed Only) 2 (Lead/Lag Runtime Select) Default: 0 (Master Always Leads)
Range: 40 to 400 hours Default: 168 hours
Range: 2 to 30 minutes Default: 10 minutes
Range: 0 to 60 minutes Default: 0 minutes
Range: 3.0 to 18°F (1.7 to 10.0°C) Default: 4.0°F (2.2°C)
Range: 0 to 150 minutes Default: 0 minutes
0 (Stop If Unit Stops) 1 (Run If Unit Stops) Default: 0 (Stop If Unit Stops)
Yes (In Series) Default: No
DUAL CHILLER PUMP CONTROL FOR SERIES CHILLER APPLICATIONS
Pump control for series chiller applications is controlled by the master chiller only. The control of the slave chiller is directed through commands transmitted by the master chiller. The slave chiller has no action in master/slave operations. The slave chiller only verifies that CCN communication with the master chiller is present. See the Dual Chiller Sequence of Operation section on page 55. Figure 36 shows a typical pump arrange­ment for dual chiller series applications.
Ramp Loading
The Ramp Loading function limits the rate of change of the leav­ing fluid temperature. The minimum compressor speed is calculat­ed based on saturated condensing temperature and saturated suc­tion temperature. To enable the Ramp Loading sequence:
DISPLAY NAME PATH VALUE
Ramp Loading Enable
Cooling Ramp Loading
Main Menu Configuration Menu General Configuration
Main Menu Setpoint Table

Yes
Range: 0.2 to 2.0°F/min (0.1 to
1.1°C/min) Default: 1.0°F/min (0.5°C/min)
Temperature Reset
The temperature reset function will determine the cooling con­trol point. This control point is the active set point adjusted with the current reset value:
Control Point = Setpoint + Reset
The purpose of this reset value is to decrease the required ca­pacity if it is allowed by unit load operating conditions. When a non-zero temperature reset is applied, the chiller controls to the new control point instead of the set point. The type of tem­perature reset is configured with the Cooling Reset Select vari­able. Four types of temperature reset are available: Outdoor Air Temperature, Return Water Reset (Delta T), 4 to 20mA control, and Space Temperature control:
DISPLAY
NAME
Cooling Reset Select
Main Menu Configuration Menu Reset Configuration
PATH VALUE
0 = None 1 = OAT 2 = Delta T 3 = 4 to 20 mA Control 4 = Space Temp
Under normal operation, the chiller will maintain a constant entering or leaving fluid temperature, based on the configura­tion, approximately equal to the chilled fluid set point. As the evaporator load varies, the evaporator fluid temperature differ­ence will change in proportion to the load. For example, if the chiller was selected for an entering to leaving water tempera­ture difference of 10°F (5.5°C) at full load, at 50% load the temperature difference would be 5°F (2.2°C). See Fig. 37. Be­cause the change in temperature through the evaporator is a measure of the building load, the temperature difference reset is the average building load. Usually the chiller size and fluid temperature set point are selected based on a full load condi­tion. At part load, the fluid temperature set point may be lower than required. When the fluid temperature is allowed to in­crease at part load, the efficiency of the machine will increase. The chiller can also be set for return water temperature control. See Fig. 38.
Other indirect means of estimating building load and con­trolling temperature reset are also available and are discussed below.
To verify that reset is functioning correctly, subtract the Cur­rent Setpoint (Main Menu
Setpoint) from the Control Point (Main Menu rameters
Control Point) to determine the degrees reset.
General Parameters  Current
General Pa-
38
Page 39
BYPASS LOOP
a30-4066
LEGEND
EWT —
Entering Water Temperature
LWT —
Leaving Water Temperature
SLAVE CHILLER
MASTER PUMP
FIELD WIRING FIELD COMMUNICATION WIRING
Fig. 36 — Typical Series Master/Slave Chillers
Dedicated Primary Pumping, Constant Flow, Leaving Water Control
65
CONTROL BOX
CONTROL BOX
MASTER CHILLER
ISOLATION VALVES
LOAD
NOTE: This is a simplified piping diagram. Not all hydronic specialties are shown.
5
4
25
05
4
8
EWT
DESIGN RISE (TYPICAL)
64
44
FLUID TEMPERATURE (deg F)
4
2
4
0
1
0
0
2
0
3
0
40
LOADING (%)
LWT
0010908070605
Fig. 37 — Leaving Chilled Water Temperature Control
39
Page 40
56
a30-4478
LEGEND
EWT —
Entering Water Temperature
LWT —
Leaving Water Temperature
g F)
FLUID TEMPERATURE (de
54
52
50
48
46
44
42
40
EWT
DESIGN
LWT
0
302010
LOADING %
RISE (TYPICAL)
100908070605040
Fig. 38 — Return Water Temperature Control Load Profile
40
Page 41
OUTSIDE AIR TEMPERATURE RESET
0
2
4
6
8
10
12
14
16
Outdoor Temperature (deg F)
Reset Amount (de
g F)
Cooling Reset
Deg. Value
= 15 F (8.3 C)
(cr_deg)
OAT No Reset Value
= 85 F (29.4 C)
(oat_hrno)
OAT Full Reset Value
= 55 F (12.8 C)
(oat_hrfu)
20 40 60 80 100 120 0
a30-5887
The control system is capable of temperature reset based on OAT. Typically as the outdoor temperature decreases so does building cooling load. The chilled water temperature can be in­creased to lower energy usage while still meeting load demand.
To use OAT Reset, four variables must be configured: Cooling Reset Select, OAT No Reset Value (outdoor temperature at which no reset is required), OAT Full Reset Value (outdoor temperature at which full reset is required), and Cooling Reset Deg Value (the amount of temperature reset desired).
To configure this option with the Carrier Controller display:
DISPLAY NAME PATH VALUE
Default = 1 0=None,
Cooling Reset Select
OAT No Reset Value
OAT Full Reset Value
Cooling Reset Deg. Value
Main Menu Configuration Menu Reset Configuration
1=OAT 2=Delta T, 3=4 to 20mA control 4=Space Temp
Default = 14°F (7.8°C) Range 14 to 125°F
(7.8 to 69.4°C) Default = 14°F (7.8°C)
Range 14 to 125°F (7.8 to 69.4°C)
Default = 0°F (0°C) Range –30 to 30°F (–16.7 to 16.6°C)
In the example in Fig. 39, the OAT reset provides 0°F (0°C) chilled water set point reset at 85°F (29.4°C) OAT and 15°F (8.3°C) reset at 55°F (12.8°C) OAT.
Fig. 39 — Example: OAT Reset
41
Page 42
DELTA T RESET (RETURN WATER RESET) The control system is also capable of performing fluid tem-
perature reset based on evaporator fluid temperature difference (Delta T), sometimes called return water reset. Because the change in temperature through the evaporator is a measure of the building load, the temperature difference reset is, in effect, an average building load reset method.
Delta T Reset allows for the chilled water temperature set point to be reset upward as a function of the fluid temperature differ­ence (building load).
NOTE: Delta T (Return Water) Temperature Reset should not be used with variable evaporator flow rate systems.
To use Delta T Reset, four variables must be configured: Cool­ing Reset Select, Delta T No Reset Value (evaporator tempera­ture difference at which no chilled water temperature reset should occur), Delta T Full Reset Value (evaporator tempera­ture difference at which the maximum chilled water tempera­ture reset should occur), and Cooling Reset Deg Value (the maximum amount of temperature reset desired).
6
5
To configure this option with the Carrier Controller display:
DISPLAY
NAME
Cooling Reset Select
Delta T No Reset Temp
Delta T Full Reset Temp
Cooling Reset Deg Value
Main Menu Configuration Menu Reset Configuration
PATH VALUE
Default = 2 0=None, 1=OAT 2=Delta T, 3=4 to 20mA control 4=Space Temp
Default = 0°F (0°C) Range 0°F to 25°F
(0°C to 13.8°C) Default = 0°F (0°C)
Range 0°F to 25°F (0°C to 13.8°C)
Default = 0°F (0°C) Range –30 to 30°F (–16.7 to 16.6°C)
In the example in Fig. 40 using Return Water Temperature Re­set, the chilled water temperature will be reset by 5°F (2.8°C) when the Fluid Temperature Difference is 2°F (1.1°C) and 0°F (0°C) reset when the Temperature Difference is 10°F (5.6°C).
DEGREES RESET (deg F)
4
3
2
1
0
Deg. Value
0
Cooling
Reset
(cr_deg)
Delta T Full Reset Temp
(dt_hr_fu)
2 4
ENTERING-LEAVING WATER TEMPERATURE (deg F)
Fig. 40 — Example: Return Water Reset
Delta T No Reset Temp
(dt_hr_no)
6 8
a30-5886
10
42
Page 43
4 TO 20 MA TEMPERATURE RESET
0
1
2
3
4
5
6
0241010
mA Signal
Degrees Reset (deg F)
2
Cooling Reset
Deg. Value
(cr_deg)
Current No Reset Value
(v_hr_no)
Current Full Reset Value
(v_hr_fu)
46 8
12 16 18
a30-5885
The control system is also capable of temperature reset based on an externally powered 4 to 20 mA signal. The EMM is re­quired for temperature reset using a 4 to 20 mA signal.
To use 4 to 20 mA Temperature Reset, four variables must be configured: Cooling Reset Select, Current No Reset Value (milliamp signal at which no temperature reset is required), Current Full Reset Value (milliamp signal at which full tem­perature reset is required), and Cooling Reset Deg Value (the
maximum amount of temperature reset desired).
CAUTION
Care should be taken when interfacing with other control systems due to possible power supply differences such as a full wave bridge versus a half wave rectification. Connection of control devices with different power supplies may result in permanent damage. Carrier Controller controls incorporate power supplies with half wave rectification. A signal isola­tion device should be utilized if the signal generator incorpo­rates a full wave bridge rectifier.
To configure this option with the Carrier Controller display:
DISPLAY NAME PATH VALUE
Default = 3 0=None,
Cooling Reset Select
Current No Reset Value
Current Full Reset Value
Cooling Reset Deg Value
Main Menu Configuration Menu Reset Configuration
1=OAT 2=Delta T, 3=4 to 20mA control 4=Space Temp
Default = 0mA
Range 0 to 20mA Default = 0mA
Range 0 to 20mA Default = 0°F (0°C)
Range –30 to 30°F (–16.7 to 16.6°C)
In the example in Fig. 41, at 4 mA no reset takes place and at 20 mA, 5°F (2.8°C) chilled water set point reset is required.
SPACE TEMPERATURE RESET The control system is also capable of temperature reset
based on space temperature. The EMM and accessory sen­sor (P/N 33ZCT55SPT) are required for temperature reset using space temperature. This sensor measures the space (room) temperature for the purpose of set point reset. Only units with the optional energy management module are fit­ted with this sensor.
To use Space Temperature Reset, four variables must be con­figured: Cooling Reset Select, Space T No Reset Value (space temperature at which no temperature reset is required), Space T Full Reset Value (space temperature at which full temperature reset is required), and Cooling Reset Deg Value (the maximum amount of temperature reset desired).
To configure this option with the Carrier Controller display:
DISPLAY NAME PATH VALUE
Cooling Reset Select
Space T No Reset Value
Space T Full Reset Value
Cooling Reset Deg Value
Main Menu Configuration Menu Reset Configuration
Default = 4 0=None, 1=OAT 2=Delta T, 3=4 to 20mA control 4=Space Temp
Default = 14°F (7.8°C) Range 14 to 125°F
(7.8 to 69.4°C) Default = 14°F (7.8°C)
Range 14 to 125°F (7.8 to 69.4°C)
Default = 0°F (0°C) Range –30 to 30°F (–16.7 to 16.6°C)
In the space temperature reset example in Fig. 42, a reset of 6°F (3.3°C) is applied when the space temperature is 68°F (20.0°C) and no reset takes place when the space temperature is 72°F (22.2°C).
Fig. 41 — Example: 4 to 20 mA Temperature Reset
43
Page 44
0
1
2
3
4
5
6
7
57 07 56 06 80
Space Temperature (deg F)
De
g
ree
s
Res
et (deg
F)
Cooling Reset
Deg. Value
(cr_deg)
Space T Full Reset Value
(spahr_fu)
Space T No Reset Value
(spahr_no)
a30-5884
Fig. 42 — Example: Space Temperature Reset
Demand Limit
There are three types of demand limiting that can be config­ured. The first type is through switch control, which will re­duce the maximum capacity to up to 3 user-configurable per­centages. The second type is by 4 to 20 mA signal input which will reduce the maximum capacity linearly between 100% at a 4 mA input signal (no reduction) down to the user-configurable level at a 20 mA input signal. The third type uses the CCN Loadshed module and has the ability to limit the current oper­ating capacity to maximum and further reduce the capacity if required. Demand limit control can be based on a calculated capacity level. If the Demand Limit is enabled and the current capacity requirement meets or exceeds the current Demand Limit level, the unit will unload and display Override #9: De­mand Limit section on page 48.
If the demand limit percentage is set below minimum unit op­eration, the unit will go into override mode. See Override #91: Demand Limit section on page 48.
SWITCH CONTROLLED DEMAND LIMIT The control system is capable of demand limit based on a field-
supplied switch for 1-step demand limit or 2 switches for 3-step demand limit. One-step demand limit is standard. The 2 or 3-step switch control of demand limiting requires the EMM. Demand limit steps are controlled By two relay switch inputs field wired to TB5-5 and TB5-14 for Switch 1 (LIM_SW1) and TB6-14 and TB6-15 for Switch 2 (LIM_SW2).
For demand limit by switch control, closing the first demand limit contact (LIM_SW1) will put the unit on the first demand limit (LIMIT 1) by capacity. The unit will not exceed the per­centage of capacity entered as Demand Limit Switch 1 set point. Closing contacts on the second demand limit switch (LIM_SW2) and opening the Demand Limit Switch 1 prevents the unit from exceeding the demand limit (LIMIT 2) entered as Demand Limit Switch 2 set point. If both demand limit switch (LIM_SW1 and LIM_SW2) contacts are closed the unit will not exceed the limit (LIMIT 3) set by the switch limit set point 3. See the table below.
CONTACT
LIM_SW1 Open Close Open Close LIM_SW2 Open Open Close Close
ACTIVE DEMAND LIMIT
NONE LIMIT 1 LIMIT 2 LIMIT 3
To use demand limit, select the type of demand limiting to use by configuring the Demand Limit Select variable (Main Menu
Configuration Menu  General Configuration  Demand
Limit Type Select) to Switch. Configure the demand limit set
points based on the type selected. If using 2 or 3-step demand limit control, an energy management
module must be installed. The energy management module must be enabled in the controls. To enable the EMM navigate to Fac­tory Parameters menu (Main Menu Factory Parameters) and set Energy Management Module to YES (1).One-step demand limit control does not require the en­ergy management module. To configure demand limit for switch control, three parameters for 1-step switch control must be con­figured. For 2 or 3-step control, additional set point parameters must be configured. The parameters are: the type of Demand Limit Selection, the setting for Switch Limit Setpoint 1, the set­ting for Switch Limit Setpoint 2 (if required) and the setting for Switch Limit Setpoint 3 (if required).
To configure this option with the Carrier Controller display:
DISPLAY NAME PATH VALUE
Demand Limit Type Select
Switch Limit Setpoint 1
Switch Limit Setpoint 2
Switch Limit Setpoint 3
In the following example, 2-step demand limit based on capac­ity is desired with the first switch closure limiting the capacity to 60%. The second switch closure is to limit the capacity to 40%. Demand Limit Switch 1 is 60% and Demand Limit Switch 2 is 40%. Since no third-step demand limit is required, Switch Limit Setpoint 3 is set at 0%.
Demand Limit Type Select 1 Switch Limit Setpoint 1 60% Switch Limit Setpoint 2 40% Switch Limit Setpoint 3 0%

Configuration Menu
Main Menu Configuration Menu
General Configura­tion
Main Menu Setpoint Table
Main Menu Setpoint Table
Main Menu Setpoint Table
DISPLAY NAME VALUE
Default = 0 (None) Range None = 0 Switch = 1 4 to 20mA = 2
Default = 100% Range 0 to 100%
Default = 100% Range 0 to 100% (Not required for 1-Step Control)
Default = 100% Range 0 to 100% (Not required for 1 or 2-Step Control)
44
Page 45
EXTERNALLY POWERED (4 TO 20 MA) DEMAND LIMIT
0
10
20
30
40
50
60
70
80
90
100
12 14 16 18
20
mA Demand Limit Signal
% Demand Limit
0
2
4 6
8 10
mA for Demand Limit = 100%
(lim_mx)
mA for Demand Limit = 0%
(lim_ze)
a30-5883
The energy management module is required for 4 to 20 mA demand limit control. An externally powered 4 to 20 mA sig­nal must be connected to TB6-1 and TB6-2. This signal is read by a transducer type (0 to 5 vdc) on the EMM board via a field-installed 0.5 W 250-ohm resistor.
CAUTION
Care should be taken when interfacing with other control sys­tems due to possible power supply differences such as a full wave bridge versus a half wave rectification. Connection of control devices with different power supplies may result in permanent damage. Carrier Controller controls incorporate power supplies with half wave rectification. A signal isola­tion device should be utilized if the signal generator incorpo­rates a full wave bridge rectifier.
To configure demand limit for 4 to 20 mA control based on unit capacity, one parameter must be configured. The parameter is Demand Limit Type Select. The value of the capacity limit will vary linearly for 0% to 100% based on the input signal where 4 mA is 100% and 20 mA is 0% of total unit capacity.
To configure this option with the Carrier Controller display:
DISPLAY NAME PATH VALUE
Demand Limit Type Select
Main Menu Configuration Menu General Configuration
In the example in Fig. 43, a 4 mA signal is Demand Limit 100% and a 20 mA Demand Limit signal is 0%. The 4 to 20 mA signal is connected to TB6-1 and TB6-2. The demand limit is a linear interpolation between the two values entered. If the machine receives a 12 mA signal, the machine controls will limit the capacity to 50%.
CCN LOADSHED CONTROLLED DEMAND LIMIT To configure Demand Limit for CCN Loadshed control, the unit
Operating Type Control must be in CCN control. With the Carrier

Default = 0 (None) 4 to 20mA Control = 2
Controller display, the machine must be started in Network Mode. Network control can be executed from the GENUNIT table.
The unit must be controlled by a Chillervisor module. The Chillervisor module can force the demand limit variable and directly control the capacity of the machine. Additionally, the unit’s set point will be artificially lowered to force the chiller to load to the demand limit value.
Machine Start Delay
An option to delay the start of the machine is available. This parameter is useful in keeping multiple machines from starting at the same time in case of a power failure. The parameter has a factory default of 1 minute. This parameter also has a role in the timing for a chilled water flow switch alarm. To configure this option with the Carrier Controller display, select Main
Menu
Configuration Menu  General Configuration and
select Unit Off to On Delay.
Fast Loading
The Fast Capacity Recovery function allows for an accelerated unit start-up. This is especially useful following brief power out­ages at data centers where rapid restart can keep data center op­erating. This should not be used on normal comfort cooling ap­plications. To activate the Fast Capacity Recovery, go to Main
Menu
Configuration Menu  Service Parameters and set
Fast Capacity Recovery. The available options are as follows:
• Disabled (normal loading sequence): Follows the set delays for unit and circuit start up
• Quick start Load - (Quick Start Loading): With Flow es­tablished, ignores Capacity Control Override #53 (ON­OFF-ON Delay)
• Fast Capacity Recov (Fast Capacity Recovery): With Flow established, ignores Capacity Control Override #53 (ON­OFF-ON Delay), and allows both compressors to start at the same time (with a 10-second delay between starts)
NOTE: Unit cannot operate with Ramp Loading enabled if Fast Capacity Recovery is set to Quick start Load or Fast Ca­pacity Recov.
Fig. 43 — Example: 4 to 20 mA Demand Limit
45
Page 46
Ice Storage Operation
Chiller operation can be configured to make and store ice. The en­ergy management module and an Ice Done Switch are required for operation in the Ice Mode. In this configuration, the machine can operate with up to three cooling set points: Cooling Setpoint 1 is used during the Occupied period, Cooling Setpoint 2 is used during the Unoccupied period when the ice build is complete (Ice Done Switch is closed), and Cooling Ice Setpoint is used during the unoccupied period while ice is building (Ice Done Switch is open). Refer to the 30XV Typical Field Wiring Schematic figure on page 227 for Ice Done Switch wiring.
To configure this option with the Carrier Controller display:
DISPLAY NAME PATH VALUE
Ice Mode Enable
Cooling Ice Setpoint
Main Menu Configuration Menu General Configura­tion
Main Menu Setpoint Table


Drop Down Selection (YES/NO) Default = No
Default = 44°F (6.7°C) Range = –20 to 78.8°F (–29 to 26°C)
Broadcast Configuration
The 30XV chiller with Greenspeed® Intelligence is capable of broadcasting OAT, time, date, and holiday status to all elements in the CCN system. In the stand-alone mode, broadcast must be acti­vated to utilize holiday schedules and adjust for daylight saving time. If the chiller is to be connected to a CCN system, determine which system element is to be the network broadcaster and acti­vate broadcast in all other system elements. Broadcast is activated and deactivated in the Carrier Controller Broadcast Menu (Main
Menu
Configuration Menu  Broadcast Menu Brocasts).
Only one element should be configured as a broadcaster. If a broadcast is activated by a device that has been designated as a network broadcaster, then broadcast time, date, and holiday status will be updated over the CCN system. If broadcast is enabled, a broadcast acknowledger must also be enabled. The acknowledger cannot be the same machine as the broadcasting machine.
ACTIVATE The Activate variable enables the broadcast function of the Carrier
Controller controls. If this variable is set to 0, this function is not used and holiday schedules and daylight savings compensation are not possible. Setting this variable to 1 allows the machine to broadcast and receive broadcasts on the network. The following information is broadcast: the time with compensation for daylight savings, date, holiday flag, and the Outdoor Air Temperature.
Set this variable to 2 for stand-alone OAT broadcast. With this configuration, daylight saving time and holiday determination will be done without broadcasting through the bus.
To configure this option with the Carrier Controller display:
DISPLAY
NAME
Activate
Main Menu Configuration Menu Broadcast Menu Brocasts
PATH VALUE

0 = Disabled
1 = Broadcast time, date, holiday flag, and OAT 2 = OAT broadcast only (Daylight savings time and holiday determina­tion will be done without broadcast­ing through the bus)
OAT BROADCAST To enable the OAT broadcast, the unit broadcasting the tempera-
ture must be configured with its own CCN Bus and CCN Address. Leaving the parameters at the factory default of 0 for the CCN Bus and CCN Address disables the OAT Broadcast function. Once configured, the first broadcast of OAT will be within 5 minutes.
To configure this option with the Carrier Controller display:
DISPLAY NAME PATH VALUE
Activate
OAT Broadcast
Bus #
Element #
Main Menu Configuration Menu Broadcast Menu Brocasts

Range = 0 to 2 Default = 2
Range = 0 to 239 Default = 0
Range = 0 to 239 Default = 0
BROADCAST ACKNOWLEDGER This configuration defines if the chiller will be used to ac-
knowledge broadcast messages on the CCN bus. One broadcast acknowledger is required per bus, including secondary buses created by the use of a bridge. The broadcast acknowledger must be configured through the Network Service Tool.
Alarm Control
ALARM ROUTING CONTROL Alarms recorded on the chiller can be routed through the CCN. To
configure this option, the Carrier Controller controls must be con­figured to determine which CCN elements will receive and pro­cess alarms. Input for the decision consists of eight digits, each of which can be set to either 0 or 1. Setting a digit to 1 specifies that alarms will be sent to the system element that corresponds to that digit. Setting all digits to 0 disables alarm processing. The factory default is 00000000. See Fig. 44. The default setting is based on the assumption that the unit will not be connected to a network. If the network does not contain a ComfortVIEW™, Comfort­WORKS this feature will only add unnecessary activity to the CCN com­munication bus.
Typical configuration of the Alarm Routing variable is
11010000. This Alarm Routing status will transmit alarms to ComfortVIEW
This option cannot be configured with the Carrier Controller display. To change the alarm control routing through the Net­work Service Tool, navigate to point ALRM_CNT in table ALARMDEF.
™
, TeLink, DataLINK™, or BACLink module, enabling
™
software, TeLink, BACLink, and DataLINK.
DESCRIPTION STATUS POINT
Alarm Routing 0 0 0 0 0 0 0 0 ALRM_CNT
ComfortVIEW™ or ComfortWORKS™
TeLink
Unused
BACLink or DataLINK™
Unused
Fig. 44 — Alarm Routing Control
46
Page 47
ALARM EQUIPMENT PRIORITY The ComfortVIEW software uses the equipment priority value
when sorting alarms by level. The purpose of the equipment priority value is to determine the order in which to sort alarms that have the same level. A priority of 0 is the highest and would appear first when sorted. A priority of 7 would appear last when sorted. For example, if two chillers send out identical alarms, the chiller with the higher priority would be listed first. The default is 4. This variable can only be changed when using the ComfortVIEW software, or Network Service Tool. This variable cannot be changed with the Carrier Controller display. To configure this option with the Network Service Tool, navi­gate to point EQP_TYP in table ALARMDEF.
COMMUNICATION FAILURE RETRY TIME This variable specifies the amount of time that will be allowed
to elapse between alarm retries. Retries occur when an alarm is not acknowledged by a network alarm acknowledger, which may use either ComfortVIEW software or TeLink. If acknowl­edgment is not received, the alarm will be re-transmitted after the number of minutes specified in this decision. This variable can only be changed when using the ComfortVIEW software, or Network Service Tool. This variable cannot be changed with the Carrier Controller display. To configure this option with the Network Service Tool, navigate to point RETRY_TM in table ALARMDEF.
RE-ALARM TIME This variable specifies the amount of time that will be allowed
to elapse between re-alarms. A re-alarm occurs when the con­ditions that caused the initial alarm continue to persist for the number of minutes specified in this decision. Re-alarming will continue to occur at the specified interval until the condition causing the alarm is corrected. This variable can only be changed when using the ComfortVIEW software, or Network Service Tool. This variable cannot be changed with the Carrier Controller display. To configure this option with the Network Service Tool, navigate to point RE_ALARM in table ALARMDEF.
ALARM SYSTEM NAME This variable specifies the system element name that will ap-
pear in the alarms generated by the unit control. The name can be up to 8 alphanumeric characters in length. This variable can only be changed when using the ComfortVIEW™ software or Network Service Tool. This variable cannot be changed with the Carrier Controller display. To configure this option with the Network Service Tool, navigate to point ALRM_NAM in ta­ble ALARMDEF.
Daylight Savings Time Configuration
The 30XV chiller with Greenspeed® Intelligence control con­tains software which can automatically correct for daylight sav­ings time. This software is accessible from the Carrier Controller display, ComfortVIEW software, or Network Service Tool.
To enable this feature, Daylight Savings Select must be set to
1. The start of daylight saving must be configured by setting the Month, Day of Week, and Week of Month. The end for Daylight Saving must also be configured. To configure this op­tion with the Carrier Controller display, see Table 30.
Table 30 — Daylight Savings Time Configuration
DISPLAY NAME PATH VALUE
Activate
Daylight Savings Select
Entering
Month
Day of Week (1=Monday)
Week of Month
Leaving
Month
Day of Week (1=Monday)
Week of Month
Main Menu Configuration Menu Broadcast Menu Brocasts

1 or 2 Default = 2
Enable Default = Disable
Enter Starting Month for Daylight Saving
Enter the Day of the Week Daylight Saving Starts
Enter Week of the Month Daylight Saving Starts
Enter Ending Month for Daylight Saving
Enter the Day of the Week Daylight Saving ends
Enter Week of the Month Daylight Saving ends
Capacity Control Overrides
The following capacity control overrides (Main Menu Maintenance Menu  Capacity Control  Override Capaci­ty Nb A, B) will modify the normal operation routine. If any of
the override conditions listed below is satisfied, the override will determine the capacity change instead of the normal con­trol. Overrides are listed by priority order and are often linked to unit operating modes. See Table 31 for a list of capacity con­trol overrides. See the Operating Modes section on page 56 for more information regarding operating modes.
Table 31 — Capacity Control Overrides
NO. DESCRIPTION
0 Normal Operation 2 Low Suction Pressure 6 EWT < control point 7 Ramp Loading
9 Demand Limit Reached 10 Flow switch is open 11 Customer Interlock is closed 12 Flow Available Delay 14 Low LWT 15 Compressor Disabled 16 High Discharge Pressure 23 Low SP 25 Oil Recovery 34 Low SST 53 ON-OFF-ON Delay 56 Evaporator Heater Isolation Valve Opening Delay 59 Low Oil Level 62 High Compressor Motor Temperature 66 High Discharge Gas Temperature 67 DGT Off Protection 70 Low Refrigerant Protection 71 Low Refrigerant Protection 77 Oil Pressure at Start 78 Bad VFD Spd At Start 91 Demand Limit
Override #2: Low Suction Pressure
This override is activated when the Expansion Valve (EXV) is not in DSH (discharge superheat) mode and the Saturated Suc­tion Temperature (SST) goes below 13.25°F (–10.4°C) for wa­ter or below (13.25°F – (34°F – Brine Freeze Setpoint)) for units configured with brine. The controller at this point starts to unload the unit until the SST exceeds 34°F (1.1°C).
Override #6: EWT < Control Point
This override stops the compressors without alarms.
Override #7: Ramp Loading
No capacity increase will be made if the unit is configured for ramp loading and the rate of change of the leaving water is greater than Ramp Loading Rate.
47
Page 48
Override #9: Demand Limit
This override mode is active when a command to limit the ca­pacity is received and the current capacity requirement meets or exceeds the demand limit value. If the current unit capacity is greater than the active capacity limit value, the unit unloads per unloading scheme. The current capacity will stop increas­ing when it reaches the capacity limit value minus 3%.
Override #10: Flow Switch is Open
This override prohibits compressor operation until the evapora­tor flow switch is closed.
Override #11: Customer Interlock is Closed
This override prohibits compressor operation until the custom­er interlock is opened.
Override #12: Flow Available Delay
This override prohibits chiller operation until flow has started.
Override #14: Low LWT (Leaving Water Temperature)
This override stops the compressors if LWT < freeze + freeze_ov (freeze = Main Menu
rameters Configuration Menu  Service Parameters  Freeze Override Offset). The goal is to stop the unit without having an alarm if the
LWT goes too low so that the unit can start automatically without the need to reset alarm. For example, freeze is 34°F (1.1°C); the user can decide to add a threshold to force the compressors to stop immediately without alarm at 35°F (1.7°C).
Override #15: Compressor Disabled
This override is shown when either of the compressors are dis­abled through Main Menu
pressor Enable menu. Override #16: High Discharge Pressure
This override attempts to avoid a high pressure failure. If the saturated condensing temperature for the circuit is above the high pressure threshold the compressor is unloaded while the fan is run at maximum frequency.
Override #23: Low SP (Suction Pressure)
When the unit is configured with evaporator fluid as water (Main Menu
SP <22.7 psig (156.5 kPa) (6°F SST). In this mode the circuit will not be allowed to load further until the SST goes above 30°F (–1.1°C). When the unit is configured with evaporator fluid as brine (Main Menu ters  Evaporator Fluid Type = Med Brine), this override is activated when SST < Brine Freeze Setpoint (Main Menu
Configuration Menu  Service Parameters  Brine Freeze Setpoint) minus 5 psig (34.5 kPa).
Override #34: Low SST (Saturated Suction Temperature)
The compressor is not allowed to start if the SST is lower than –13°F (–25°C).
Override #53: ON OFF ON Delay
This override is activated when the unit is in off state (recycle, manually stopped, or because of alarm shutdown). The control will remain in this state for the next 3 minutes. This is to re­duce short cycling.
Override #56: Isolation Valve Opening Delay
This override mode is activated when the actuated ball valves (if equipped) on the discharge lines are opening (approximate­ly 2-minute delay).
Override #59: Low Oil Level
This override is only effective when the circuit is not running. The override will prevent the circuit from starting up with a low oil level.
Brine Freeze Setpoint; freeze_ov = Main Menu
Evaporator Fluid Type = Water), this override is activated at
Configuration Menu  Service Pa-
Configuration Menu Com-
Configuration Menu  Service Parameters
Configuration Menu  Service Parame-
Override #62: High Compressor Motor Temperature
This override prevents the compressor motor temperature from rising above the high compressor motor temperature limit, but still allows the chiller to run close to the high temperature limit by unloading the compressor. If the motor temperature is great­er than 195.8°F (91°C), the compressor will not load. This override will control the loading to the compressor to maintain a maximum motor temperature of 194°F (90°C). The circuit will come out of this mode if the motor temperature falls below
190.4°F (88°C) or if motor temperature is below 195.8°F (91°C) and water temperature is established.
Override #66: High Discharge Gas Temperature (DGT)
This override avoids high DGT tripout by either increasing compressor capacity or decreasing the capacity and stopping the compressor depending on the conditions. The increase in capacity happens when the DGT > 201°F (93.9°C) to lower DGT. The control seeks to control the DGT at 190°F (87.8°C) and if the DGT goes below 186.4°F (85.8°C) the unit goes to normal control. The decrease in capacity followed by unit stop happens if Override 66 is activated and evaporator leaving wa­ter temperature is close to the Brine Freeze Setpoint (Main
Menu
Configuration MenuService Parameters) or lower
than the Control Point (Main Menu The compressor restarts if the DGT goes below 186.4°F (85.8°C) and more than 5 minutes have passed. This override has priority over almost every other one (including the De­mand Limit override).
Override #67: DGT off Protection (Discharge Gas Temperature)
This override is activated before the unit starts and prevents the unit from starting if the DGT is still greater than DGT activa­tion point or if 5 minutes has not passed since the last high DGT shutdown.
Override #77: Oil Pressure at Start
In this override the unit freezes the compressor loading and waits until the oil pressure exceeds the above conditions and then exits to normal mode of operation.
Override #91: Demand Limit
This override is activated when the demand limit is set lower than the minimum possible unit capacity. The unit shuts down and/or is on hold until the demand limit is changed to higher than the minimum unit capacity.
General Parameters).
Head Pressure Control (Variable Speed Fans)
The head pressure is controlled through the Carrier Controller display by adjusting fan speed through variable speed drive(s). The command sent to the drive is at a frequency to maintain the lowest condensing temperature possible, and thus, the highest unit efficiency. The frequency command sent is based on a func­tion of compressor capacity, OAT, and leaving fluid temperature. If the capacity is stable and no overrides have occurred recently, an algorithm attempts to optimize fan frequency based on total power feedback. The optimization control can be turned on and off through the Network Service Tool (Service Optimization Enable On, Off [xt_enable]).
Fan control continuously monitors all inputs and outputs and the transitions between the modes are defined based on continuous measurements of 2 inputs (Discharge Pressure and Discharge Gas Temperature).
Fan modes of operation include the following:
• STANDARD: Normal mode of operation before using the optimum-seeking algorithm.
• WAITOPT, OPTIMZE: Trying to optimize the fan fre­quency during the optimum-seeking algorithm.
• FREEZE: Fan frequencies are frozen after completion of the optimum-seeking algorithm cycle. The fan control
Fan_CFG
48
Page 49
remains in this mode until the LWT, the compressor load, or the outdoor temperature changes by a defined amount. If the change conditions are met the fan control goes back to the WAITOPT mode followed by the OPTIMZE modes.
• DGT: High Discharge Gas Temperature mode. The VFD increases the speed of the fan to reduce DGT.
• DP_HIGH, DP_LOW: High Discharge Pressure (DP) Mode, Low Discharge Pressure Mode: The VFD controls the speed of the fan to bring SCT (Saturated Condensing Temperature) into normal operating range.
• OFF: Fans are not running.
• START: Start mode. The frequency of the fans is defined based on the OAT.
Head Pressure Control (Fixed Speed Fans)
The head pressure is controlled through the Carrier Controller display by adjusting the number of fans running. The controller determines the minimum number of fans required to support unit operation so the unit can run at the most efficient point. At start up the number of fans on is calculated using OAT. After 60 seconds, an equation is used to determine the number of fan required based on OAT, EWT, and circuit capacity.
There are additional modes used for fixed speed fans:
DP HIGH Mode decreases the discharge pressure as fast as possible to
prevent high pressure trips. This mode turns on all fans.
DP HIGH DISCHARGE PRESSURE Mode avoids high discharge pressure that would cause the com-
pressor to run outside of the compressor envelope. In this mode, the pressure is controlled to a Discharge Pressure set point.
DGT HIGH Mode decreases the discharge temperature as fast a possible to
prevent high DGT alarms. This mode turns on all fans.
Sound Optimization
This option runs the chiller at a lower sound level by limiting the compressor and fan speed. The factors in Table 32 control this option. The factors are set from the factory and should not be lowered, as this may cause operational issues. The set points for this option are on a label inside the door of the control panel.
The compressor speed, fMaxOvrA or B, can be set to a lower max frequency. The max frequency is limited by the max fre­quency of the base unit. This option is enabled by changing fMaxEnA or B to “yes”.
The fan speed limitation is enabled by setting fan_fact to any value other than 1.00. The factor will be applied to the fan curve calculation for the fan speed in Hz. If the factor is 0.7, the fan speed will be 70% of the calculated fan speed. If high saturated condensing temperature occurs, the controls will override this feature and increase fan speed to keep the chiller running.
Table 32 — Sound Optimization Factor Settings
FACTOR COMPRESSOR SPEED RANGE DEFAULT
Enable Max Frequency A fMaxEnA no/yes 0 (no) Enable Max Frequency B fMaxEnB no/yes 0 (no) Max Frequency Override A fMaxOvrA 30 to 105 75 Max Frequency Override B fMaxOvrB 30 to 105 75 Fan Freq Fctor (0.7-1.1) fan_fact 0.7 to 1.1 1.00
PRE-START-UP
Complete the Start-Up Checklist for 30XV Liquid Chillers at the end of this publication. The checklist assures proper start-up of a unit, and provides a record of unit condition, application requirements, system information, and opera­tion at initial start-up.
Do not attempt to start the chiller until the following checks have been completed.
System Check
1. Check that auxiliary components, such as the chilled fluid circulating pump, air-handling equipment, or other equip­ment to which the chiller supplies liquid are operational. Consult manufacturer’s instructions. If the unit has field­installed accessories, be sure all are properly installed and wired correctly. Refer to unit wiring diagrams.
2. Open compressor suction service valves (if equipped).
3. Open discharge line, liquid line, oil line, and economizer (if equipped) service valves.
4. Fill the chiller fluid circuit with clean water (with recom­mended inhibitor added) or other non-corrosive fluid to be cooled. Bleed all air out of high points of system. If outdoor temperatures are expected to be below 32°F (0°C), sufficient inhibited propylene glycol or other suitable corrosion inhibit­ed antifreeze should be added to the chiller water circuit to prevent possible freeze-up.
The chilled water loop must be cleaned before the unit is connected. It is recommended that the chiller pumps be equipped with a start-up filter screen to remove particulates from the loop. The start-up filter should be replaced after 24 hours of operation
5. Check tightness of all electrical connections.
6. Electrical power source must agree with unit nameplate.
7. Oil separator heaters must be energized for 24 hours prior to start-up.
START-UP
Actual Start-Up
Actual start-up should be done only under supervision of a qualified refrigeration technician.
1. Be sure all oil, suction valves, discharge valves (if equipped) and liquid line service valves are open.
2. Using the Carrier Controller control, set leaving-fluid set point (Main Menu
1). No cooling range adjustment is necessary.
3. If optional control functions or accessories are being used, the unit must be properly configured. Refer to Configuration Options section for details.
4. Start the chilled fluid pump, if unit is not configured for pump control (Main Menu
Pump Configuration Evaporator Pumps Sequence = No Pumps (0)).
5. Complete the Start-Up Checklist to verify all components are operating properly.
6. Touch the Start/Stop button located in the upper right cor­ner of the Carrier Controller display and then select Local On.
7. Allow unit to operate and confirm that everything is func­tioning properly. After unit operation stabilizes, check to see that leaving set-point Control Point (Main Menu
point Table fluid temperature (Main Menu Leaving Fluid).
Setpoint Table  Cooling Setpoint
Configuration Menu
Cooling Setpoint 1) agrees with leaving
Temperatures  Evap
Set-
49
Page 50
Operating Limitations
TEMPERATURES Unit operating temperature limits are listed in the table below.
TEMPERATURE F C Maximum Ambient Temperature 125 52 Minimum Ambient Temperature* 32 0 Maximum Evaporator EWT† 95 35 Maximum Evaporator LWT 60 15 Minimum Evaporator LWT 38** 3.3 Maximum Evaporator Glycol EWT† 95 35 Minimum Evaporator Glycol LWT 30 16.7
LEGEND
EWT — LWT —
* Lowest allowable ambient temperature for the standard unit to start
† For sustained operation, EWT should not exceed 70°F (21.1°C). ** Unit requires brine fluid for operation below this temperature.
Low Ambient Temperature Operation
If unit operating temperatures below 32°F (0°C) are expected, the following measures are recommended:
• Consider higher loop volumes, 6 to 10 gallons per nominal ton.
• Loop freeze protection with glycol is strongly recommend-
• Chilled water pump control is required.
• If wind velocity is expected to be greater than 5 mph
VOLTAGE
Main Power Supply
Minimum and maximum acceptable supply voltages are listed in the Installation Instructions.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance between phases is greater than 2%.
To determine percent voltage imbalance:
% Voltage Imbalance = 100 x max voltage deviation from avg voltage
The maximum voltage deviation is the largest difference be­tween a voltage measurement across 2 legs and the average across all 3 legs.
Example: Supply voltage is 240-3-60.
Entering Fluid (Water) Temperature Leaving Fluid (Water) Temperature
and operate is 32°F (0°C). With the inclusion of wind baffles and vari­able speed fans (field fabricated and installed), the unit is capable to start as low as 0°F (–17.8°C) and to operate as low as –20°F (–29°C) ambient temperature.
ed to a minimum of 15°F (8.3°C) below lowest anticipated ambient temperature.
(8 km/h) wind baffles and brackets must be field fabricated and installed. See the 30XV Installation Instructions for more information.
average voltage
AB = 243v BC = 236v AC = 238v
2. Determine maximum deviation from average voltage:
(AB) 243 – 239 = 4 v (BC) 239 – 236 = 3 v (AC) 239 – 238 = 1 v
Maximum deviation is 4 v.
8. Determine percent voltage imbalance:
% Voltage Imbalance = 100 x 4
=
239
1.7%
This voltage imbalance is satisfactory as it is below the maximum allowable of 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact the local electric utility company immediately. Do not operate unit until imbalance condition is corrected.
MINIMUM FLUID LOOP VOLUME To obtain proper temperature control, loop fluid volume must be
FLOW RATE REQUIREMENTS Standard chillers should be applied with nominal flow rates
within those listed in the Minimum and Maximum Evaporator Flow Rates table. Higher or lower flow rates are permissible to obtain lower or higher temperature rises. Minimum flow rates must be exceeded to assure turbulent flow and proper heat transfer in the evaporator. See Tables 33 and 34. See Fig. 45-50 for evaporator pressure drop curves.
CAUTION
Operation below minimum flow rate could generate alarms, which could result in damage to the evaporator.
Consult application data section in the Product Data literature and job design requirements to determine flow rate require­ments for a particular installation.
Corner Grounded Delta Supply
The Compressor and Fan VFDs used on 30XV units are automati­cally compatible with a Corner Grounded Delta Power Supply to the system. No changes are required to be made to the VFDs.
1. Determine average voltage:
Average voltage = 243+236+238
3
= 717
3
= 239
50
Page 51
Table 33 — Min/Max Water Flow, Standard Evaporator
30XV TIERS
140 All 170.4 10.8 681.6 43.0 160 All 193.2 12.2 772.8 48.8 180 All 204.0 12.9 816.0 51.5 200 All 236.4 14.9 945.6 59.7 225 All 266.4 16.8 1065.6 67.2 250 All 308.4 19.5 1233.6 77.8 275 All 327.6 20.7 1310.4 82.7 300 All 349.2 22.0 1396.8 88.1 325 All 379.2 23.9 1516.8 95.7 350 All 419.0 26.4 1676.0 105.7 400 All 483.0 30.5 1932.0 121.9 450 All 543.5 34.3 2174.0 137.2 500 All 600.0 37.9 2400.0 151.4
MINIMUM FLOW RATE MAXIMUM FLOW RATE
(gpm) (L/s) (gpm) (L/s)
Table 34 — Min/Max Water Flow, Minus-1-Pass Evaporator
30XV TIERS
140 All 340.8 21.6 1363.2 86.0 160 All 386.4 24.4 1545.6 97.6 180 All 408.0 25.8 1632.0 103.0 200 All 472.8 29.8 1891.2 119.4 225 All 532.8 33.6 2131.2 134.4 250 All 616.8 39.0 2467.2 155.6 275 All 655.2 41.4 2620.8 165.4 300 All 698.4 44.0 2793.6 176.2 325 All 758.4 47.8 3033.6 191.4 350 All 838.0 52.8 3352.0 211.4 400 All 966.0 61.0 3864.0 243.8 450 All 1087.0 68.6 4348.0 274.4 500 All 1200.0 75.8 4800.0 302.8
MINIMUM FLOW RATE MAXIMUM FLOW RATE
(gpm) (L/s) (gpm) (L/s)
51
Page 52
Fig. 45 — Evaporator Pressure Drop Curves (English), Standard Pass Flooded Evaporator (30XV140-225)
Unit Sizes 30XV140, 160, 180, 200, 225
Unit Sizes 30XV250, 275, 300, 325
Fig. 46 — Evaporator Pressure Drop Curves (English), Standard Pass Flooded Evaporator (30XV250-325)
52
Page 53
Fig. 47 — Evaporator Pressure Drop Curves (English), Standard Pass Flooded Evaporator (30XV350-500)
Unit Sizes 30XV350, 400, 450, 500
Unit Sizes 30XV140, 160, 180, 200, 225
0
50
100
150
200
250
0.00 10.00 20.00 30.00 40.00 50.00 60.00 70.00 80.00
Pressure drop, kPa
Evaporator Flow Rate, l/s
140 Std Tier
140 Mid, High, & 160 Std Tier
160 Mid, High, & 180 Std Tier
180 Mid, High, & 200 Std Tier
200 Mid, & High Tier
225 Std Tier
225 Mid, & High Tier
Fig. 48 — Evaporator Pressure Drop Curves (SI), Standard Pass Flooded Evaporator (30XV140-225)
53
Page 54
Fig. 49 — Evaporator Pressure Drop Curves (SI), Standard Pass Flooded Evaporator (30XV250-325)
Unit Sizes 30XV250, 275, 300, 325
0
50
100
150
200
250
0.00 20.00 40.00 60.00 80.00 100.00 120.00
Pressure drop, kPa
Evaporator Flow Rate, l/s
250 Std Tier
250 Mid, High, & 275 Std Tier
275 Mid, High, & 300 Std Tier
300 Mid, High, & 325 Std Tier
325 Mid, & High Tier
Unit Sizes 30XV350, 400, 450, 500
0
50
100
150
200
250
300
0.00 20.00 40.00 60.00 80.00 100.00 120.00 140.00 160.00
Pressure drop, kPa
Evaporator Flow Rate, l/s
350 Std Tier
400 Std Tier
350 Mid, High, 400 Mid, High, & 450 Std
500 Mid Tier
450 Mid, High, & 500 Std Tier
Fig. 50 — Evaporator Pressure Drop Curves (SI), Standard Pass Flooded Evaporator (30XV350-500)
54
Page 55
a30-4236
VALVE SHAFT
a30-4237
CLAMPING SCREW
ACTUATOR ARM
DISENGAGEMENT BUTTON
MOUNTING - FULLY CLOSED
MOUNTING - FULLY OPEN
a30-4238
OPERATION
Sequence of Operation
With a command to start the chiller, the evaporator pump will start. After verifying water flow, the control will monitor the entering and leaving water temperature. If the need for me­chanical cooling is determined, the control decides which cir­cuit and compressor to start. The control will start the required compressor completely unloaded and de-energize the oil sep­arator heater (if already energized). The control will continue to load this circuit by increasing the VFD frequency to satisfy cooling requirements. Once fully loaded, the control will start the second circuit to satisfy load as required. Shutdown of each circuit under normal conditions occurs in the opposite se­quence to loading. Once a circuit is fully unloaded the com­pressor is shut off and the EXV will close completely.
ACTUATED BALL VALVE (ABV) For chillers equipped with this option (standard in most re-
gions), either one or two discharge ABVs are located in the dis­charge line of each circuit of the unit. See Fig. 51 for a typical ABV assembly with enclosure. The ABV is a motorized ball valve, which is used to close the discharge line to prevent re­frigerant migrating from condenser to the evaporator when the circuit is off. The valve will be opened before the compressor is started and will normally close when pressure equalizes be­tween suction and discharge lines.
The actuated ball valves are linked to the evaporator heater op­eration in the controls. Evaporator Heater option (Main Menu

Configuration Menu Factory Parameters Evaporator
Heater Installed = yes) must be enabled for the actuated ball
valve to operate. See Fig. 52 for a view of a fully open ball valve with the actua-
tor removed. The flat surface at the top of the valve shaft is parallel to the discharge line. The ball valve motor mounting plate should be perpendicular to the discharge line at all times. If not, adjust it by loosening the set screw on the side of the valve, reposition assembly and tighten set screw.
See Fig. 53 for a view of the ball valve motor mounting with a fully open valve. The motor actuator arm should be at a coun­terclockwise position, with the valve shaft in a parallel posi­tion. If not in a parallel position, loosen the clamping screw and push the disengagement button to rotate the actuator arm until it stops. Retighten the clamping screw.
ABV Manual Operation
The ABV can be operated manually as a discharge service valve by completing the following steps:
1. Remove the actuator cover.
2. With the compressor off hold down the Disengagement (Push) button. See Fig. 53.
3. Close the ABV by turning the shaft adapter by hand or with a wrench so that the flats on the end of the shaft are perpen­dicular to the discharge line.
4. Release the Push button.
5. Disconnect the control power cable to the ABV.
Dual Chiller Sequence of Operation
With a command to start the chiller, the master chiller determines which chiller will become the lead chiller based on the configura­tion of Lead Lag Select (lead_sel) and Lead/Lag Balance Delta (ll_bal_d). The lead chiller is always started first and the lag chiller is held at zero percent capacity by the master chiller forcing the lag demand limit value to 0%. If Lead Pulldown Time (lead_pul) has been configured, the lead chiller will continue to operate alone for that specified time. After the Lead Pulldown Time timer has elapsed and when the lead chiller is fully loaded, either all available compression is on or at the master demand lim­it value, then the lag start timer (lstr_tim) is initiated.
VALVE MOTOR COVER
VALVE MOTOR
BASE PLATE
Fig. 51 — Typical ABV Assembly with Enclosure
Fig. 52 — Fully Open Ball Valve
with Actuator Removed
Fig. 53 — Ball Valve Motor
55
Page 56
When the pulldown time and lag start time have elapsed and the Combined Leaving Chilled Water Temperature is more than 3°F (1.7°C) above the set point, then the lag chiller is started. If the lag chiller’s water pump was not started when the machines went into occupied mode, the lag chiller water pump will be started. The lag chiller will start with the master chiller forcing the lag chiller demand limit value (LAG_LIM) to the master’s demand limit value. If lead/lag capacity balance is selected, once the lag chiller has started, the master will try to keep the differ­ence in capacity between lead and lag less than 20%. The master will then be responsible for water loop capacity calculation, and will determine which chiller, the lead or lag, will increase or de­crease capacity. When the load reduces, the lag chiller will be the first chiller to unload. To accomplish this, the lead chiller set point is decreased by 4°F (–2.2°C) until the lag chiller unloads.
PUMP OPERATION For parallel chiller pump operation, the lead chiller’s water pump
will be started. The lag chiller’s water pump will be maintained off if Lag Unit Pump Control = 0 (Main Menu
Configuration
Menu  Master/Slave Config Lag Unit Pump Control). The
internal algorithm of the lead chiller will control capacity of the lead chiller.
Operating Modes
Operating modes are override modes that affect normal opera­tion of the equipment. More than one operating mode can be in effect at the same time. Some operating modes have corre­sponding capacity control overrides (see the Capacity Control Overrides section on page 47).
For the Carrier Controller display, the status of the operating modes can be found by accessing the Modes Menu (Main Menu
Modes). Each operating mode and its status (Yes = active, No =
inactive) is listed. See Table 35 for a list of operating modes.
Table 35 — 30XV with Greenspeed
Operating Modes
OPERATING
MODE NUMBER
1 Startup Delay in Effect Yes/No 2 Second Setpoint in Use Yes/No 3 Reset in Effect Yes/No 4 Demand Limit Active Yes/No 5 Evaporator Pump Rotation Yes/No 6 Pump Periodic Start Yes/No 7 Night Mode Active Yes/No 8 Master Slave Active Yes/No
12 Ice Mode in Effect Yes/No
DESCRIPTION STATUS
STARTUP DELAY IN EFFECT This mode is checked for when the unit is started. This mode is
active when the Minutes Off Time (Main Menu
tion Menu  General Configuration  Unit Off to On De­lay) timer is active. The unit will not start until the timer has
expired. The mode will terminate when the timer expires.
SECOND SETPOINT IN USE This mode is checked for when the unit is ON. The mode is ac-
tive when Cooling Setpoint 2 (Main Menu
Cooling Setpoint 2) or Cooling Ice Setpoint (Main Menu
Setpoint Table  Cooling Ice Setpoint) is in use. While in
this mode, the Current Setpoint (Main Menu  General Pa-
rameters
Current Setpoint) will show the Cooling Setpoint
2 or Cooling Ice Setpoint value. While in this mode the unit will operate to the Cooling Setpoint
2 or Cooling Ice Setpoint. The mode will terminate when the second setpoint is no longer in use.
RESET IN EFFECT This mode is checked for when the unit is ON. The mode will be
active when Cooling Reset Select (Main Menu
®
Intelligence
Configura-
Setpoint Table
Configuration

Menu
Reset Configuration  Cooling Reset Select) is en-
abled by setting the value to 1 = Outside Air Temperature, 2 = Flu­id Delta T, 3 = 4 to 20 mA Input, 4 = Space Temperature) and reset is active.
While in this mode, the Current Setpoint (Main Menu
eral Parameters
Current Setpoint) will be modified ac-
Gen-
cording to the programmed information and will be displayed as the Control Point (Main Menu
General Parameters
Control Point). The mode will terminate when the Tempera­ture Reset is not modifying the active leaving water set point, causing the Current Setpoint to equal the Control Point.
DEMAND LIMIT ACTIVE This mode is checked for when the unit is ON. The mode is active
when Demand Limit Type Select (Main Menu
Menu
General Configuration  Demand Limit Type Select)
Configuration
is enabled either by setting the value to 1 = Switch Control or 2 = 4 to 20mA Control, or setting the Night Capacity Limit (Main
Menu
Configuration Menu  General Configuration
Night Capacity Limit). The Active Demand Limit Value (Main Menu  General Parameters  Active Demand Limit Value)
will display the current demand limit according to the pro­grammed information and the unit’s capacity will be reduced to the amount shown or lower. The mode will terminate when the Demand Limit command has been removed.
EVAPORATOR PUMP ROTATION This mode is always checked. The mode is active when the
Evaporator Pump Sequence (Main Menu
Configuration
Menu  Pump Configuration  Evaporator Pumps Se­quence) value is set to 2 = Two Pumps Automatic Changeover, and the Pump Auto Rotation Delay (Main Menu
Configura-
tion Menu  Pump Configuration  Pump Auto Rotation Delay) has expired. The control will switch the operation of the
pumps. The lead pump will operate normally. The lag pump will be started, becoming the lead, and then the original lead pump will be shut down. This mode will terminate when the pump op­eration has been completed.
PUMP PERIODIC START This mode is active when the evaporator pump is started due to
the periodic pump start configuration (Main Menu
uration Menu
Pump Configuration  Pump Sticking
Config-
Protection = YES). If the pump has not run that day, a pump
will be started and will run for 2 seconds at 2:00 PM. If the ma­chine is configured for dual pumps, Pump 1 will run on even days (such as the day 2, 4, 6 of the month). Pump 2 will run on odd days (such as day 1,3, 5 of the month). The mode will ter­minate when the pump shuts down.
MASTER SLAVE ACTIVE This mode is checked for if the machine is ON. This mode is
active if Master Slave Control has been enabled. This occurs when two machines are programmed, one as the master (Main
Menu
Configuration Menu  Master/Slave Config
Master/Slave select = Master (1)) and the other as a slave (Main Menu
Master/Slave select = Slave (2)). Both the master and slave
Configuration Menu  Master/Slave Config
machines will respond to the capacity control commands is­sued by the master controller. This may include control point changes and demand limit commands. This mode will termi­nate when Master Slave Control has been disabled (Main
Menu
Configuration Menu  Master Slave Config
Master/Slave Select = Disable (0)).
ICE MODE IN EFFECT This mode is checked for when the unit is ON. This mode is
active when the Cooling Ice Setpoint (Main Menu
Table
Cooling Ice Setpoint) is in use. While in this mode,
the Current Setpoint (Main Menu  General Parameters
Setpoint
Current Setpoint) will show the Cooling Ice Setpoint value
56
Page 57
and the unit will operate to that value. This mode will termi-
MINIMUM SPEED
TRIGGER SPEED RECOVERY SPEED
SERVICE1_odtrgspd SERVICE1_odrecspd
COMPRESSOR SPEED (Hz)
nate when the Ice Cooling Ice Set-point is no longer in use (ICE DONE switch is closed).
OIL RECOVERY The oil recovery mode is enabled when the compressor speed
falls below the threshold (Trigger Speed) for a continuous peri­od of time (Trigger Time). The mode will ramp the compressor speed to an objective speed (Recover Speed) for a period of time (Recover Time) and then return the compressor speed to automatic control. This mode takes precedence over other WA­TER_T overrides: ramp loading (Override 7), Low SP (Over­ride 23), and Demand Limit (Override 9). See Fig. 54.
Fig. 54 — Oil Recovery Diagram
Sensors
The electronic control uses up to 15 thermistors to sense tem­peratures and up to 10 transducers to sense pressure for con­trolling chiller operation. These sensors are outlined below.
THERMISTORS (TABLES 36-40) Thermistors that monitor the chiller’s operation include: evapo-
rator entering water, evaporator leaving water, dual chiller leav­ing water, compressor suction gas temperature, compressor dis­charge gas temperature, economizer temperature, liquid line temperature, compressor motor temperature, and Outdoor Air Temperature thermistors. These thermistors are 5,000 ohmsat 77°F (25°C) and are identical in temperature versus resistance. The space temperature thermistor is 10,000 ohmsat 77°F (25°C) and has a different temperature vs. resistance. See Fig. 55 for thermistor locations.
Evaporator Leaving Water Sensor (LWT)
On all sizes, this thermistor is installed in a threaded well in the leaving water nozzle of the evaporator. See Fig. 56.
Evaporator Entering Water Sensor (EWT)
On all sizes, this thermistor is factory-installed in a threaded well in the entering water nozzle of the evaporator.
Suction Gas Temperature (SGT)
On all sizes, this thermistor is factory-installed in a threaded well located on the compressor of each circuit. There is one thermistor for each circuit.
Compressor Discharge Gas Temperature (DGT)
On all sizes, this thermistor is factory-installed in a threaded well located in the discharge end of the compressor for the cir­cuit. There is one thermistor for each circuit.
Liquid Line Temperature (LIQT)
This thermistor is factory-installed in a threaded well located in the liquid line of the circuit. There is one thermistor for each circuit.
Economizer Temperature (ECT)
On all sizes, this thermistor is factory-installed in a threaded well located in the economizer line for the circuit. There is one thermistor for each circuit.
Compressor Motor Temperature (Comp Temp)
On all sizes, this thermistor is embedded in the motor wind­ings. There are two thermistors in each compressor. One spare is provided.
Outdoor Air Temperature (OAT)
This sensor is factory-installed to the back of the control box.
Space Temperature
This sensor (part no. 33ZCT55SPT) is a field-installed accessory mounted in the indoor space and is used for water temperature re­set. The sensor should be installed as a wall-mounted thermostat would be (in the conditioned space where it will not be subjected to either a cooling or heating source or direct exposure to sunlight, and 4 to 5 ft above the floor).
Space temperature sensor wires are to be connected to terminals in the unit main control box. See Fig. 57. The space temperature sensor includes a terminal block (SEN) and a RJ11 female con­nector. The RJ11 connector is used as access into the Carrier Comfort Network
®
at the sensor.
To connect the space temperature sensor (see Fig. 57):
1. Using a 20 AWG twisted pair conductor cable rated for the application, connect one wire of the twisted pair to one SEN terminal and connect the other wire to the other SEN termi­nal located under the cover of the space temperature sensor.
2. Connect the other ends of the wires to terminals 7 and 8 on TB6 located in the unit control box.
Units on the CCN can be monitored from the space at the sen­sor through the RJ11 connector, if desired. To wire the RJ11 connector into the CCN:
1. Cut the CCN wire and strip ends of the red (+), white (ground), and black (–) conductors. (If another wire color scheme is used, strip ends of appropriate wires.)
2. Insert and secure the red (+) wire to terminal 5 of the space temperature sensor terminal block.
3. Insert and secure the white (ground) wire to terminal 4 of the space temperature sensor.
4. Insert and secure the black (–) wire to terminal 2 of the space temperature sensor.
5. Connect the other end of the communication bus cable to the remainder of the CCN communication bus.
NOTE: The EMM is required for this accessory.
TRANSDUCERS There are 5 pressure transducers per circuit, and two different
types of transducers: low pressure (green connector) and high pressure (black connector).
Low Pressure Type: Suction Pressure Transducer (SPT), Econ­omizer Pressure Transducer (EPT).
High Pressure Type: Discharge Pressure Transducer (DPT), Oil Pressure Transducer (OPT), Liquid Pressure Transducer (LPT). See Fig. 58 for transducer locations.
57
Page 58
Table 36 — Thermistor Identification
THERMISTOR ID DESCRIPTION RESISTANCE AT 77°F (25°C) CONNECTION POINT
EWT Entering Water Temperature Thermistor 5k SIOBA-J25-AI01 LWT Leaving Water Temperature Thermistor 5k SIOBA-J25-AI02
OAT Outdoor Air Temperature Thermistor 5k SIOBA-J25-AI03 SGTA Circuit A Suction Gas Temperature Thermistor 5k AUXA-J6-CH12 SGTB Circuit B Suction Gas Temperature Thermistor 5k AUXB-J6-CH12 DGTA Circuit A Discharge Gas Temperature Thermistor 5k AUXA-J6-CH11 DGTB Circuit B Discharge Gas Temperature Thermistor 5k AUXB-J6-CH11
LIQT_A Circuit A Liquid Line Temperature Thermistor 5k AUXA-J7-CH13 LIQT_B Circuit B Liquid Line Temperature Thermistor 5k AUXB-J7-CH13
ECTA Circuit A Economizer Temperature Thermistor 5k SIOBA-J25-AI05 ECTB Circuit B Economizer Temperature Thermistor 5k SIOBB-J25-AI05 DUAL Dual Chiller Leaving Water Temperature Thermistor 5k SIOBB-J25-AI03
Comp A Temp Circuit A Compressor Motor Temperature Thermistor 5k SIOBA-J25-AI04 Comp B Temp Circuit B Compressor Motor Temperature Thermistor 5k SIOBB-J25-AI04
SPT Space Temperature Thermistor 10k EMM-J6-CH2
Table 37 — Compressor Thermistor Temperature vs. Resistance
°F °C Nominal Resistance, Ohms –22 –30 88,500 –13 –25 65,210
–4 –20 48,535
5 –15 36,477 14 –10 27,665 23 –5 21,162 32 0 16,325 41 5 12,696 50 10 9,950 59 15 7,854 68 20 6,245 77 25 5,000 86 30 4,029 95 35 3,266
104 40 2,664 113 45 2,185 122 50 1,802 131 55 1,493 140 60 1,244 149 65 1,042 158 70 876 167 75 741 176 80 629 185 85 536 194 90 459 203 95 394 212 100 340 221 105 294 230 110 256 239 115 223 248 120 195 257 125 171 266 130 151 275 135 133 284 140 117 293 145 104 302 150 93
58
Page 59
Table 38 — 5K Thermistor Temperature vs.
Resistance
°F °C RESISTANCE, OHMS
–40 –40 166,781 –38 –39 156,158 –36 –38 146,275 –35 –37 137,078 –33 –36 128,514 –31 –35 120,536 –29 –34 113,101 –27 –33 106,170 –26 –32 99,705 –24 –31 93,672 –22 –30 88,041 –20 –29 82,781 –18 –28 77,868 –17 –27 73,275 –15 –26 68,980 –13 –25 64,963 –11 –24 61,203
–9 –23 57,683 –8 –22 54,387 –6 –21 51,299 –4 –20 48,404 –2 –19 45,689
0 –18 43,143 1 –17 40,754 3 –16 38,511 5 –15 36,404 7 –14 34,426
9 –13 32,566 10 –12 30,818 12 –11 29,173 14 –10 27,626 16 –9 26,171 18 –8 24,800 19 –7 23,509 21 –6 22,292 23 –5 21,146 25 –4 20,065 27 –3 19,045 28 –2 18,084 30 –1 17,177 32 0 16,320 34 1 15,511 36 2 14,746 37 3 14,024 39 4 13,341 41 5 12,695 43 6 12,084 45 7 11,506 46 8 10,959 48 9 10,441 50 10 9,951 52 11 9,486 54 12 9,046 55 13 8,628 57 14 8,232 59 15 7,857 61 16 7,500 63 17 7,152 64 18 6,841 66 19 6,536 68 20 6,247
Table 38 — 5K Thermistor Temperature vs.
Resistance (cont)
°F °C RESISTANCE, OHMS
70 21 5,972 72 22 5,710 73 23 5,461 75 24 5,225 77 25 5,000 79 26 4,786 81 27 4,582 82 28 4,389 84 29 4,204 86 30 4,028 88 31 3,860 90 32 3,701 91 33 3,549 93 34 3,403 95 35 3,265 97 36 3,133
99 37 3,007 100 38 2,887 102 39 2,772 104 40 2,662 106 41 2,558 108 42 2,458 109 43 2,362 111 44 2,271 113 45 2,183 115 46 2,100 117 47 2,020 118 48 1,943 120 49 1,870 122 50 1,800 124 51 1,733 126 52 1,669 127 53 1,608 129 54 1,549 131 55 1,492 133 56 1,438 135 57 1,386 136 58 1,337 138 59 1,289 140 60 1,243 142 61 1,199 144 62 1,157 145 63 1,117 147 64 1,078 149 65 1,041 151 66 1,005 153 67 971 154 68 938 156 69 906 158 70 876 160 162 72 818 163 73 791 165 74 765 167 75 740 169 76 716 171 77 692 172 78 670 174 79 649 176 80 628 178 81 608 180 82 589
71 846
59
Page 60
Table 38 — 5K Thermistor Temperature vs.
Resistance (cont)
Table 38 — 5K Thermistor Temperature vs.
Resistance (cont)
°F °C RESISTANCE, OHMS
181 83 570 183 84 552 185 85 535 187 86 518 189 87 502 190 88 487 192 89 472 194 90 458 196 91 444 198 92 431 199 93 418 201 94 405 203 95 393 205 96 382 207 97 370 208 98 360 210 99 349 212 100 339 214 101 329 216 102 320 217 103 311 219 104 302 221 105 293 223 106 285 225 107 277 226 108 269 228 109 262 230 110 255 232 111 248 234 112 241 235 113 234 237 114 228 239 115 222 241 116 216
°F °C RESISTANCE, OHMS
243 117 210 244 118 205 246 119 199 248 120 194 250 121 189 252 122 184 253 123 179 255 124 175 257 125 170 259 126 166 261 127 162 262 128 157 264 129 154 266 130 150 268 131 146 270 132 142 271 133 139 273 134 135 275 135 132 277 136 129 279 137 126 280 138 123 282 139 120 284 140 117 286 141 114 288 142 111 289 143 109 291 144 106 293 145 104 295 146 101 297 147 99 298 148 97 300 149 94 302 150 92
60
Page 61
Table 39 — 10K Thermistor Temperature (°F) vs Resistance
TEMP
(F)
VOLTAGE
DROP
(V)
RESISTANCE
(OHMS)
–25 4.758 196,453 –24 4.750 189,692 –23 4.741 183,300 –22 4.733 177,000 –21 4.724 171,079 –20 4.715 165,238 –19 4.705 159,717 –18 4.696 154,344 –17 4.686 149,194 –16 4.676 144,250 –15 4.665 139,443 –14 4.655 134,891 –13 4.644 130,402 –12 4.633 126,183 –11 4.621 122,018 –10 4.609 118,076
–9 4.597 114,236 –8 4.585 110,549 –7 4.572 107,006 –6 4.560 103,558 –5 4.546 100,287 –4 4.533 97,060 –3 4.519 94,020 –2 4.505 91,019 –1 4.490 88,171
0 4.476 85,396 1 4.461 82,729 2 4.445 80,162 3 4.429 77,662 4 4.413 75,286 5 4.397 72,940 6 4.380 70,727 7 4.363 68,542 8 4.346 66,465
9 4.328 64,439 10 4.310 62,491 11 4.292 60,612 12 4.273 58,781 13 4.254 57,039 14 4.235 55,319 15 4.215 53,693 16 4.195 52,086 17 4.174 50,557 18 4.153 49,065 19 4.132 47,627 20 4.111 46,240 21 4.089 44,888 22 4.067 43,598 23 4.044 42,324 24 4.021 41,118 25 3.998 39,926 26 3.975 38,790 27 3.951 37,681 28 3.927 36,610 29 3.903 35,577 30 3.878 34,569 31 3.853 33,606 32 3.828 32,654 33 3.802 31,752 34 3.776 30,860 35 3.750 30,009 36 3.723 29,177 37 3.697 28,373 38 3.670 27,597 39 3.654 26,838 40 3.615 26,113 41 3.587 25,396 42 3.559 24,715 43 3.531 24,042 44 3.503 23,399 45 3.474 22,770 46 3.445 22,161 47 3.416 21,573 48 3.387 20,998 49 3.357 20,447 50 3.328 19,903 51 3.298 19,386 52 3.268 18,874 53 3.238 18,384 54 3.208 17,904 55 3.178 17,441 56 3.147 16,991 57 3.117 16,552 58 3.086 16,131 59 3.056 15,714 60 3.025 15,317
TEMP
(F)
VOLTAGE
DROP
(V)
RESISTANCE
(OHMS)
61 2.994 14,925 62 2.963 14,549 63 2.932 14,180 64 2.901 13,824 65 2.870 13,478 66 2.839 13,139 67 2.808 12,814 68 2.777 12,493 69 2.746 12,187 70 2.715 11,884 71 2.684 11,593 72 2.653 11,308 73 2.622 11,031 74 2.592 10,764 75 2.561 10,501 76 2.530 10,249 77 2.500 10,000 78 2.470 9,762 79 2.439 9,526 80 2.409 9,300 81 2.379 9,078 82 2.349 8,862 83 2.319 8,653 84 2.290 8,448 85 2.260 8,251 86 2.231 8,056 87 2.202 7,869 88 2.173 7,685 89 2.144 7,507 90 2.115 7,333 91 2.087 7,165 92 2.059 6,999 93 2.030 6,838 94 2.003 6,683 95 1.975 6,530 96 1.948 6,383 97 1.921 6,238 98 1.894 6,098
99 1.867 5,961 100 1.841 5,827 101 1.815 5,698 102 1.789 5,571 103 1.763 5,449 104 1.738 5,327 105 1.713 5,210 106 1.688 5,095 107 1.663 4,984 108 1.639 4,876 109 1.615 4,769 110 1.591 4,666 111 1.567 4,564 112 1.544 4,467 113 1.521 4,370 114 1.498 4,277 115 1.475 4,185 116 1.453 4,096 117 1.431 4,008 118 1.409 3,923 119 1.387 3,840 120 1.366 3,759 121 1.345 3,681 122 1.324 3,603 123 1.304 3,529 124 1.284 3,455 125 1.264 3,383 126 1.244 3,313 127 1.225 3,244 128 1.206 3,178 129 1.187 3,112 130 1.168 3,049 131 1.150 2,986 132 1.132 2,926 133 1.114 2,866 134 1.096 2,809 135 1.079 2,752 136 1.062 2,697 137 1.045 2,643 138 1.028 2,590 139 1.012 2,539 140 0.996 2,488 141 0.980 2,439 142 0.965 2,391 143 0.949 2,343 144 0.934 2,297 145 0.919 2,253 146 0.905 2,209
TEMP
(F)
VOLTAGE
DROP
(V)
RESISTANCE
(OHMS)
147 0.890 2,166 148 0.876 2,124 149 0.862 2,083 150 0.848 2,043 151 0.835 2,003 152 0.821 1,966 153 0.808 1,928 154 0.795 1,891 155 0.782 1,855 156 0.770 1,820 157 0.758 1,786 158 0.745 1,752 159 0.733 1,719 160 0.722 1,687 161 0.710 1,656 162 0.699 1,625 163 0.687 1,594 164 0.676 1,565 165 0.666 1,536 166 0.655 1,508 167 0.645 1,480 168 0.634 1,453 169 0.624 1,426 170 0.614 1,400 171 0.604 1,375 172 0.595 1,350 173 0.585 1,326 174 0.576 1,302 175 0.567 1,278 176 0.558 1,255 177 0.549 1,233 178 0.540 1,211 179 0.532 1,190 180 0.523 1,169 181 0.515 1,148 182 0.507 1,128 183 0.499 1,108 184 0.491 1,089 185 0.483 1,070 186 0.476 1,052 187 0.468 1,033 188 0.461 1,016 189 0.454 998 190 0.447 981 191 0.440 964 192 0.433 947 193 0.426 931 194 0.419 915 195 0.413 900 196 0.407 885 197 0.400 870 198 0.394 855 199 0.388 841 200 0.382 827 201 0.376 814 202 0.370 800 203 0.365 787 204 0.359 774 205 0.354 762 206 0.349 749 207 0.343 737 208 0.338 725 209 0.333 714 210 0.328 702 211 0.323 691 212 0.318 680 213 0.314 670 214 0.309 659 215 0.305 649 216 0.300 639 217 0.296 629 218 0.292 620 219 0.288 610 220 0.284 601 221 0.279 592 222 0.275 583 223 0.272 574 224 0.268 566 225 0.264 557
61
Page 62
Table 40 — 10K Thermistor Temperature (°C) vs Resistance
TEMP
(C)
VOLTAGE
DROP
(V)
RESISTANCE
(OHMS)
–32 4.762 200,510 –31 4.748 188,340 –30 4.733 177,000 –29 4.716 166,342 –28 4.700 156,404 –27 4.682 147,134 –26 4.663 138,482 –25 4.644 130,402 –24 4.624 122,807 –23 4.602 115,710 –22 4.580 109,075 –21 4.557 102,868 –20 4.533 97,060 –19 4.508 91,588 –18 4.482 86,463 –17 4.455 81,662 –16 4.426 77,162 –15 4.397 72,940 –14 4.367 68,957 –13 4.335 65,219 –12 4.303 61,711 –11 4.269 58,415 –10 4.235 55,319
–9 4.199 52,392 –8 4.162 49,640 –7 4.124 47,052 –6 4.085 44,617 –5 4.044 42,324 –4 4.003 40,153 –3 3.961 38,109 –2 3.917 36,182 –1 3.873 34,367
0 3.828 32,654 1 3.781 31,030 2 3.734 29,498 3 3.686 28,052 4 3.637 26,686 5 3.587 25,396 6 3.537 24,171 7 3.485 23,013 8 3.433 21,918
9 3.381 20,883 10 3.328 19,903 11 3.274 18,972 12 3.220 18,090 13 3.165 17,255 14 3.111 16,464
TEMP
(C)
VOLTAGE
DROP
(V)
RESISTANCE
(OHMS)
15 3.056 15,714 16 3.000 15,000 17 2.944 14,323 18 2.889 13,681 19 2.833 13,071 20 2.777 12,493 21 2.721 11,942 22 2.666 11,418 23 2.610 10,921 24 2.555 10,449 25 2.500 10,000 26 2.445 9,571 27 2.391 9,164 28 2.337 8,776 29 2.284 8,407 30 2.231 8,056 31 2.178 7,720 32 2.127 7,401 33 2.075 7,096 34 2.025 6,806 35 1.975 6,530 36 1.926 6,266 37 1.878 6,014 38 1.830 5,774 39 1.784 5,546 40 1.738 5,327 41 1.692 5,117 42 1.648 4,918 43 1.605 4,727 44 1.562 4,544 45 1.521 4,370 46 1.480 4,203 47 1.439 4,042 48 1.400 3,889 49 1.362 3,743 50 1.324 3,603 51 1.288 3,469 52 1.252 3,340 53 1.217 3,217 54 1.183 3,099 55 1.150 2,986 56 1.117 2,878 57 1.086 2,774 58 1.055 2,675 59 1.025 2,579 60 0.996 2,488 61 0.968 2,400
TEMP
(C)
VOLTAGE
DROP
(V)
RESISTANCE
(OHMS)
62 0.940 2,315 63 0.913 2,235 64 0.887 2,157 65 0.862 2,083 66 0.837 2,011 67 0.813 1,943 68 0.790 1,876 69 0.767 1,813 70 0.745 1,752 71 0.724 1,693 72 0.703 1,637 73 0.683 1,582 74 0.663 1,530 75 0.645 1,480 76 0.626 1,431 77 0.608 1,385 78 0.591 1,340 79 0.574 1,297 80 0.558 1,255 81 0.542 1,215 82 0.527 1,177 83 0.512 1,140 84 0.497 1,104 85 0.483 1,070 86 0.470 1,037 87 0.457 1,005 88 0.444 974 89 0.431 944 90 0.419 915 91 0.408 889 92 0.396 861 93 0.386 836 94 0.375 811 95 0.365 787 96 0.355 764 97 0.345 742 98 0.336 721
99 0.327 700 100 0.318 680 101 0.310 661 102 0.302 643 103 0.294 626 104 0.287 609 105 0.279 592 106 0.272 576 107 0.265 561
62
Page 63
SUCTION GAS
5/8 in. HEX
6 in. MINIMUM
CLEARANCE FOR
THERMISTOR
REMOVAL
1.188 in.
2.315 in.
1/4-18 NPT
WIRE TIE
LOOP
THERMISTOR WIRE
AND SECURE
TO CHILLED WATER PIPE
INSERT THERMISTOR UNTIL
O-RING MEETS THE
THERMISTOR WELL BODY.
7
8
TB6
SEN
SEN
SENSOR
TEMPERATURE (SGTA)
ECONOMIZER TEMPERATURE (ECTA)
DISCHARGE GAS TEMPERATURE (DGTA)
OUTDOOR AIR TEMPERATURE (OAT)
LIQUID TEMP (LIQT B)
COMPRESSOR A TEMPERATURE
ECONOMIZER TEMPERATURE (ECTB)
Fig. 55 — Thermistor Locations
SUCTION GAS TEMPERATURE (SGTB)
LIQUID TEMP (LIQT A)
LEAVING WATER TEMPERATURE (LWT)
ENTERING WATER TEMPERATURE (EWT)
DISCHARGE GAS TEMPERATURE (DGTB)
COMPRESSOR B TEMPERATURE
Fig. 56 — Dual Chiller Accessory Kit Leaving Water Thermistor and Well (P/N 00EFN900044000A)
Fig. 57 — Typical Space Temperature Sensor (33ZCT55SPT) Wiring
63
Page 64
Fig. 58 — Transducer and Switch Locations
SUCTION PRESSURE TRANSDUCER (SPT A)
OIL PRESSURE TRANSDUCER (OPT A)
ECONOMIZER PRESSURE TRANSDUCER (EPT A)
LIQUID PRESSURE TRANSDUCER (LPT A)
EVAPORATOR (B)
COMPRESSOR (B)
DISCHARGE PRESSURE TRANSDUCER (DPT A)
SUCTION PRESSURE TRANSDUCER (SPT B)
OIL PRESSURE TRANSDUCER (OPT B)
ECONOMIZER PRESSURE TRANSDUCER (EPT B)
LIQUID PRESSURE TRANSDUCER (LPT B)
DISCHARGE PRESSURE TRANSDUCER (DPT B)
OIL LEVEL SWITCH (OIL LS B)
EVAPORATOR (A)
COMPRESSOR (A)
HIGH PRESSURE SWITCH (HPS B)
HIGH PRESSURE SWITCH (HPS A)
EVAPORATOR FLOW SWITCH (CWFS)
OIL SEPARATOR (B)
OIL LEVEL SWITCH (OIL LSA)
POWERBOX END
Economizer Assembly
Each circuit on the unit has an economizer assembly, which in­cludes a brazed plate heat exchanger, EXVs, and other compo­nents. See Fig. 59.
Electronic Expansion Valve
See Fig. 60 for a cutaway view of the EXV. High-pressure liq­uid refrigerant enters the valve through the top. As refrigerant passes through the orifice, pressure drops and refrigerant changes to a 2-phase condition (liquid and vapor). The elec­tronic expansion valve operates through electronically con­trolled activation of a stepper motor. The stepper motor stays in position unless power pulses initiate the two discrete sets of motor stator windings for rotation in either direction. The di­rection depends on the phase relationship of the power pulses. The motor directly operates the spindle, which has rotating movements that are transformed into linear motion by the transmission in the cage assembly. The valve cone is a V-port type which includes a positive shut-off when closed. The large number of steps and long stroke results in very accurate control of the refrigerant flow. The stepper motor has either 3810 (main) or 2625 (economizer) steps.
MAIN EXV CONTROL The main EXV is controlled by the SIOB (J17-STPR1). Each
circuit has thermistors located in the compressor discharge (DGT), compressor motor cavity (SGT) and liquid line leaving the condenser (LIQT). Each circuit also has a DPT, SPT, and LPT. All the pressure readings as measured by the transducers are converted to saturated temperatures. Liquid pressure trans­ducer (LPT) is converted to saturated liquid temperature (SLT). The main control logic for the EXV uses liquid line subcool­ing, which is the difference between the liquid line saturation temperature and the liquid line temperature, to control the
SERVICE
position of the EXV. The SIOB module controls the position of the electronic expansion valve stepper motor to maintain the subcooling set point. The EXV control logic has several over­rides, which are also used to control the position of the EXV.
• Normal Mode (SUBCOOL)
• Low Discharge Superheat (DSH)
• Low Suction Pressure (SPMIN)
• Maximum Suction Pressure (SPMAX)
• EXV Start (START)
To view EXV overrides: Main Menu
EXV Control or Main Menu  Maintenance Menu
EXVECO Control. Normal Mode (SUBCOOL)
This is the normal mode of operation of the EXV. Based on the operating condition and loading of the compressor, the control calculates an optimal subcooling setting to maximize the sys­tem efficiency. The controls accordingly adjust the EXV open­ing to meet this calculated subcooling setting. The range of the subcooling setting can be altered by using the Network Service Tool in the Configuration
Low Discharge Superheat (DSH)
This mode is disabled for 100 sec after the start of the circuit. Control enters this mode when DSH is below 12°F ( The control attempts to drive DSH above 15°F (–9.4°C) by closing the EXV. In this mode the setpoint is modified and driven to a value that supports a higher DSH value upon exit of the mode. This prevents mode cycling. Mode is exited when the DSH is greater than 18 within 1.25° (0.7°C) of 15°F ( above the subcooling setpoint.
64
EXV_CFG table.
°F (–7.8°C) or the average DSH is
–9.4°C) and the subcooling is
Maintenance Menu
–11.1°C).
Page 65
LIQUID LINE SHUT OFF VALVE
MAIN EXV
SIGHT GLASS
MAIN FLOW TO EVAPORATOR
ECONOMIZER EXV
FILTER DRIER
BRAZED PLATE HEAT EXCHANGER (ECONOMIZER)
ECONOMIZER RELIEF
ECONOMIZER FLOW TO COMPRESSOR
1. Cable
2. Glass Seal
3. Motor Housing
4. Stepper Motor
5. Bearing
6. Lead Screw
7. Insert
8. Valve Piston
9. Valve Seat
10. Valve Port
a30-4241
Low Suction Pressure (SPMIN)
The EXV control tries to open up the EXV to increase the suction pressure and come out of this mode. The SST setting to enter this mode is dependent on the fluid type. With water the EXV enters this mode if SST is less than SST_Freeze – 6.5°F ( normal discharge superheat or less than SST_Freeze – 18.75°F (–28.2°C) in low DSH condition. It remains in this mode until SST is greater than SST_Freeze + 2°F (1.1°C). SST_Freeze is 32°F (0°C) for water and freeze set point for brine.
Maximum Suction Pressure (SPMAX)
This mode is disabled for 300 sec after start. The EXV enters this mode if the SST is greater than 55°F (13°C) and the circuit is not in DP mode. The EXV closes down to regulate the SST at about 53.2°F (11.8°C). If the SST is less than 52.3°F (11.3°C) or the circuit is in DP mode, then the EXV returns to the normal mode of operation.
Fig. 59 — Economizer Assembly
Fig. 60 — Cutaway Views of the Electronic Expansion Valve
ECONOMIZER EXV CONTROL The economizer EXV is controlled by the SIOB (J18-STPR2). An
economizer gas temperature thermistor (ECT) and an economizer
–21.4°C) in
pressure transducer (EPT) are located in the line running from the economizer assembly to the compressor. The economizer pressure is converted to saturated temperature and is used to calculate econ­omizer superheat. Economizer superheat equals economizer tem­perature minus saturated economizer temperature. The control system controls the economizer EXV to maintain the economizer superheat setpoint, which is approximately 18°F (–7.8°C). The economizer will start operation when circuit capacity is at 55% or above. It will turn off at 45%.
EXV TROUBLESHOOTING PROCEDURE There are two different economizer EXVs. Both of the econo-
mizer EXVs have a total of 2625 steps. There are three differ­ent main EXVs, which all have a total of 3810 steps. The EXV motor moves at 150 steps per second. Commanding the valve
65
Page 66
to either 0% or 100% will add an additional 160 steps to the move, to ensure the valve is open or closed completely.
CAUTION
Do not remove EXV cables from the SIOB with the power applied to the board. Damage to the board may occur.
Follow the steps below to diagnose and correct EXV problems. Check EXV motor operation first. Switch the Enable-Off-Re­mote (EOR) Contact switch to the Off position.
Check the appropriate circuit EXV, EXV Position Circuit A % Open (Main Menu or EXV Position Circuit B % Open (Main Menu nance Menu  EXV Control). Use Quick Test procedure on page 226. The current value of 0 will be displayed. Increase the EXV position to select 100% valve position. The actuator should be felt moving through the EXV. To close the valve, se­lect 0%. The actuator should knock when it reaches the bottom of its stroke.
If the valve is not working properly, continue with the follow­ing test procedure:
1. Check the EXV output signals at appropriate terminals on SIOB-A (J17-STPR1) and SIOB-B (J17-STPR1). Refer to Tables 7 and 8 for additional information.
2. Connect positive test lead to SIOB(X)-J17 terminal 12V for EXV(X) and SIOB(X)-J18 terminal 12V for economizer EXV(X). Using the Quick Test procedure on page 226, move the valve output under test to 100%. DO NOT short meter leads together or pin 12V to any other pin, as board damage will occur. During the next several seconds, careful­ly connect the negative test lead to pins A,B,C and D in suc­cession. Digital voltmeters will average this signal and dis­play approximately 6 vdc. If the output remains at a constant voltage other than 6 vdc or shows 0 volts, remove the con­nector to the valve and recheck.
3. Select 0% to close the valve.
NOTE: The output is 12 vdc from the SIOB when the valve is stationary.
If a problem still exists, replace the SIOB. If the reading is cor­rect, the expansion valve and EXV wiring should be checked. Check the EXV connector and interconnecting wiring.
1. Check color-coding and wire connections. Make sure they are connected to the correct terminals at the EXV board and EXV plug and that the cables are not crossed.
2. Check for continuity and tight connection at all pin terminals.
Check the resistance of the EXV motor windings. Remove the EXV module plug SIOB(X)-J17 for main EXV and SIOB(X)­J18 for economizer EXV. Check the resistance of the two windings between pins A and C for one winding and pins B and D for the other winding. The resistance should be 52 ohms (± 5.2 ohms). Also check pins A-D for any shorts to ground.
Inspecting/Opening Electronic Expansion Valves
IMPORTANT: Obtain replacement gaskets before open­ing EXV. Do not re-use gaskets.
To check the physical operation of an EXV, the following steps should be performed. Charge not isolated within the unit must be recovered using proper refrigerant recovery techniques.
1. Isolate refrigerant within the chiller and recover remain­ing charge. This will allow access to internal EXV com­ponents. Closing the valves will minimize the amount of refrigerant that will need to be removed.
For units without isolation valve option: Close the liquid line ball valve directly above the filter drier as well as the discharge line ball valves (see the Actuated Ball Valve
Quick Test  Circuit A EXV Position)
Mainte-
section on page 55 for instructions). Remove any remain­ing refrigerant from the system low side using proper re­covery techniques. The evaporator liquid line inlet has an access port that can be used to remove charge from the evaporator. The economizer assembly has a
1
/4-in. access connection which can be used to remove charge from the inlet of the EXVs. Turn off the line voltage power supply to the compressors.
For units with isolation valve option: Close the ball valves on the liquid line directly above the filter drier, after the main EXV before the evaporator, and on the economizer line to the compressor. Remove any remaining refrigerant from the economizer assembly using proper recovery techniques. The economizer assembly has a
1
/4-in. access connection which can be used to remove charge from the inlet of the EXVs. Turn off the line voltage power supply to the compressors.
CAUTION
Ensure refrigerant is removed from both the inlet and outlet of EXV assemblies. Equipment damage could result.
2. The expansion valve motor is hermetically sealed inside the top portion of the valve. See Fig. 60. Disconnect the EXV plug. Carefully unscrew the motor portion from the body of the valve. The EXV operator will come out with the motor portion of the device. Reconnect the EXV plug.
3. Enter the appropriate EXV test step under the Test mode (Main Menu rameter for the Main EXVs: Circuit A EXV Position, Circuit B EXV Position or Economizer EXVs: EXV Eco Position Cir A, EXV Eco Position Cir B. Change the position to 100%. Observe the operation of the lead screw. See Fig. 60. Motor actuator movement should be smooth and uniform from fully closed to fully open position. Select 0% and check open to closed operation. If the valve is properly connected to the processor and receiving correct signals, yet does not operate as described above, the sealed motor portion of the valve should be replaced.
Installing EXV Motor
IMPORTANT: Obtain replacement gasket before opening EXV. Do not re-use gaskets.
Moisture Liquid Indicator Clear flow of liquid refrigerant indicates sufficient charge in sys-
tem. Bubbles in the sight glass indicate undercharged system or presence of noncondensables. Moisture in system, measured in parts per million (ppm), changes color of indicator. See Table 41. Change filter drier at first sign of moisture in system.
IMPORTANT: Unit must be in operation at least 12 hours before moisture indicator can give an accurate reading.
With unit running, indicating element must be in contact with liquid refrigerant to give true reading.
Filter Drier Whenever moisture-liquid indicator shows presence of mois-
ture, replace filter drier(s). There is one filter drier assembly on each circuit with two cores. Refer to the Carrier Standard Ser­vice Techniques Manual, Chapter 1, Refrigerants, for details on servicing filter driers.
Quick Test Table). Locate the desired pa-
66
Page 67
CLOSED
OPEN
CLOSED
OPEN
GASKET
OPEN VALVE IN QUICK TEST SUB-MODE BEFORE DISASSEMBLING
EF05BD271 NV 32.5mm EF05BD331 NV 36mm
50Nm (36 ft-lb)+ 30°
27mm / 1
1
/16''
27mm / 1
1
/16''
ADAPTER
NOTES:
1. Push down on valve piston to close valve before assembling.
2. After valve is assembled close valve in Quick Test sub-mode or cycle power before opening service valve.
a30-4072
DISASSEMBLY
ASSEMBLY
Fig. 61 — Disassembly and Assembly of EXV Motor
Table 41 — Color Indicators When Moisture Is Present in Refrigerant
COLOR INDICATOR R-134a, 75°F (24°C) (ppm) R-134a, 125°F (52°C) (ppm) Green — Dry < 30 < 45 Yellow-green — Caution 30-100 45-170 Yellow — Wet >100 >170
Liquid Line Service Valve This valve is located immediately ahead of filter drier, and has a
1
/4-in. access connection for field charging. In combination with
compressor discharge service valve, each circuit can be pumped down into the high side for servicing with plate fin coils. Micro­channel Heat Exchanger (MCHX) coils have much smaller vol­ume and cannot accommodate the entire circuit charge.
Compressor Assembly
The 30XV units utilize Greenspeed Intelligence for efficient operation. The compressor is controlled by a VFD. See Fig. 62 for a view of a typical 06Z compressor. For optimal efficiency the compressor uses a VI valve to change the inlet area of the lobes at different loading points. The valve is opened or closed by a solenoid on the compressor. The control logic looks at cal­culated parameters to determine the switch point of the valve.
VI VALVE TROUBLESHOOTING Use the quick test table (Main Menu
Quick Test Table
Circuit X VI) to enable the VI valve output. Enable the valve
output and verify the coil solenoid is energized.
SUCTION VICTAULIC COUPLING INSTALLATION
1. The outside surface of the pipe, between the groove and the pipe end, must be smooth and free from indentations, projections (including weld seams), and roll marks to en­sure a leak-tight seal. All oil, grease, loose paint, and dirt
must be removed. The Victaulic gasket used for refriger­ant system piping will have a yellow mark on one side of the gasket lips.
2. Apply a thin coat of Victaulic lubricant or silicone lubricant to the gasket sealing lips and exterior.
3.
CAUTION
Always use a compatible lubricant to prevent the gasket from pinching or tearing during installation. Failure to fol­low this instruction could result in joint leakage.
4. Position the gasket over the pipe end. Make sure the gasket does not overhang the pipe end.
5. Align and bring the two pipe ends together. Slide the gasket into position and center it between the grooves in each pipe end. Make sure no portion of the gasket extends into the groove in either pipe end.
6. Install the housings over the gasket. Make sure the housings’ keys engage the grooves completely on both pipe ends.
CAUTION
Make sure the gasket does not become rolled or pinched while installing the housings. Failure to follow this instruction could cause damage to the gasket, resulting in joint leakage.
67
Page 68
7. Install the bolts, and thread a nut finger-tight onto each bolt. For couplings supplied with stainless steel hardware, apply an anti-seize compound to the bolt threads. Make sure the oval neck of each bolt seats properly in the bolt hole.
8. Tighten the nuts evenly by alternating sides until metal-to­metal contact occurs at the bolt pads. Make sure the hous­ings’ keys engage the grooves completely. It is important to tighten the nuts evenly to prevent gasket pinching.
9. Visually inspect the bolt pads at each joint to ensure metal­to-metal contact is achieved.
COMPRESSOR OIL SYSTEM Each compressor/circuit has its own oil system which includes an
oil filter, oil solenoid, check valve, oil level switch, oil separator heater, oil pressure transducer, and an oil shut-off valve. A typical oil system is shown in Fig. 63 and 64. See Table 42 for required oil quantity per circuit, initially included from the factory.
Table 42 — Unit Oil Quantities
30XV UNIT SIZE
140-325 5.5 [20.8] 5.5 [20.8
350 7.5 [28.4] 5.5 [20.8
400-500 7.5 [28.4] 7.5 [28.4]
OIL CHARGE (gal, [liters])
Circuit A Circuit B
Oil Charge
When additional oil or a complete charge is required it must meet the following specifications:
• . .Manufacturer . . . . . . . . . Emkarate RL220XL
• Oil Type . . . . . . . . . . . . . Inhibited polyolester-based syn-
thetic compressor lubricant for use with screw compressors.
• ISO Viscosity Grade . . . 220
Do not reuse drained oil or any oil that has been exposed to the atmosphere.
Oil is available in the following quantities from your local Carrier representative:
QUANTITY TOTALINE PART NO. 1 Quart P903-2325 1 Gallon P903-2301 5 Gallon P903-2305
If unsure if there is low oil charge in the system, follow the steps below:
1. If the unit shuts off repeatedly from a low oil level alert, it may be an indication of inadequate oil charge: however, it could also indicate the oil is not being reclaimed from the low-side of the system.
2. Run the circuit at full load for 1
1
/2 hours.
NOTE: An adequate load must be available.
3. After running the unit for 1
1
/2 hours at full load, stop the unit. Check the oil level in the oil separator sight glass. An oil lev­el should be visible in the upper sight glass. If level is not visible, the unit is low on oil charge.
4. Add oil until the oil is at the center of the upper sight glass. Make sure not to add oil beyond this level as excess oil will be carried out of the oil separator into the system and might lead to system instabilities at certain conditions.
5. The factory oil charging stations are programed to add pre­cise amount of oil to the oil separator and if the oil level while inspection shows higher than middle of the top sight glass then it could be due to refrigerant mixed in it. Do not remove any oil.
Add oil to the oil separator using the
1
/4-in. access fitting on
the side of the separator.
NOTE: To facilitate the oil charging process, ensure that the unit is not running when adding oil. The system is un­der pressure even when the unit is not running, so it is nec­essary to use a suitable pump to add oil to the system. Us­ing a suitable pump, add Continue adding oil in
1
/2 gal (1.9 L) of oil to the system.
1
/2 gal (1.9 L) increments until the
problem is resolved, up to a maximum of 1.5 gal (5.7 L).
6. Larger units (350 Circuit A and 400-500 ton units) will not have sight glasses for reference. The same procedure should be followed. To check for oil in the evaporator, determine the approach, LWT - SST. This should be less than 10°F for fresh water for a circuit running in steady state condition at full load. If over this amount, there is still oil logged in the evaporator. Continue to run at full load to remove it. If the approach is low (less than 6) and there are low oil level alarms, add 0.5 gal. to the circuit.
Oil Filter Maintenance
Each circuit has one oil filter bolted externally to the compres­sor. Oil line pressure drop is monitored by the control. Oil line pressure drop is calculated by subtracting oil pressure (OPT) from discharge pressure (DPT). If the oil line pressure drop ex­ceeds 30 psig (206.8 kPa) for 5 minutes the control will gener­ate a High Oil Filter Pressure Drop alert. The High Oil Filter Pressure Drop alert will not shut down the compressor, but in­stead indicates that the oil filter is dirty. If oil pressure line losses exceed 50 psig (344.7 kPa) for more than 30 seconds then the control will shut down the circuit on Maximum Oil Filter Differential Pressure Failure.
CAUTION
Compressor oil is pressurized. Use proper safety precautions when relieving pressure.
Replacing the Oil Filter
Close the oil service valves on either side of filter by removing the cap and closing the valve. One is connected to the oil filter and the other is mounted on the compressor. Connect a charging hose to the ¼-in. access fitting port located between the filter and compressor. Bleed off the oil located in this sec­tion. A quart of oil is typically removed during this process. Unscrew the nuts on either side of the filter. Remove the filter and install the new one. Make sure to remove the plastic caps from the new filter before installation. Take care not to lose or damage the new O-rings on the new filter. Draw a vacuum at the service port. Remove the charging hose and open the oil service valves. Replace caps on access port and service valves. Check both fittings for leaks.
Evaporator Service
The 30XV units use flooded style evaporators.
ISOLATION VALVE The isolation valve is a factory-installed option for 30XV units.
The option includes a butterfly-style suction service valve on the suction lines, and manual ball valves on discharge, evaporator inlet and economizer lines. The butterfly valve is connected to the suction line by Victaulic connections. See Fig. 65 and 66 for details on the butterfly suction service valve operation. The valve locks into place when fully opened or fully closed. See Table 43 for compressor usage.
Table 43 — Compressor Usage
30XV UNIT SIZE
140 - 200 06ZCE1 06ZCE1
225 06ZFC2 06ZCE1
250 - 325 06ZFC2 06ZFC2
350 06ZJG3 06ZFC2
400-500 06ZJG3 06ZJG3
COMPRESSOR MODELS
CKT A CKT B
68
Page 69
MOTOR THERMISTOR TERMINALS
OIL PRESSURE TRANSDUCER LOCATION
HIGH PRESSURE SWITCH LOCATION
HIGH PRESSURE TRANSDUCER LOCATION
ECONOMIZER PORT
DISCHARGE PRESSURE TAP
SIDE VIEW
SUCTION PRESSURE TRANSDUCER LOCATION
VI SOLENOID VALVE
OIL SOLENOID VALVE
COMPRESSOR TERMINALS
OIL INLET PORT
TOP VIEW
COMPRESSOR TERMINALS
DISCHARGE GAS THERMISTOR
SUCTION TEMPERATURE THERMISTOR LOCATION
Fig. 62 — Typical 06Z Compressor (All Units)
69
Page 70
OIL FILTER
OIL SERVICE VALVES
OIL SOLENOID
OIL SEPARATOR
OIL SEPARATOR
OIL SOLENOID
OIL SERVICE VALVES
OIL FILTER
OIL HEATER
OIL LEVEL SWITCH
Fig. 63 — Typical Oil System (140-325, 350 Circuit B)
Fig. 64 — Typical Oil System (350 Circuit A, 400-500)
Fig. 65 — Suction Service Valve
Butterfly Valve Closed
Fig. 66 — Suction Service Valve
Butterfly Valve Open
70
Page 71
EVAPORATOR FREEZE PROTECTION
LEGEND
1—
Overcurrent Adjusting Potentiometer
2—
Power Supply Status LED (green)
3—
Relay Output Supply Status LED (yellow)
4—
35 mm Rail Clip-in Spring
a30-5648
All evaporators are equipped with evaporator heaters (unless re­moved as an option for Middle Eastern regions). The control logic uses the unit status, OAT, and SST for all circuits to decide if the evaporator heater should be energized. The evaporator heaters can only be energized when the state of the unit is OFF. The evaporator heaters will be energized according to the fol­lowing logic:
1. The Evaporator Heater Setpoint is the Brine Freeze Setpoint + Evaporator Heater Delta Setpoint.
2. If the OAT is below the Evaporator Heater Setpoint or if the SST of any one circuit is lower than the Evaporator Heater Setpoint + 6°F (3.3°C), the evaporator heater is activated, or if already activated, will remain on.
3. If the SST of all circuits is higher than the Evaporator Heater Setpoint + 10°F (5.5°C), and if OAT is higher than the Evap­orator Heater Setpoint +2°F, the evaporator heater will be turned off, or if already off, will remain off.
4. If either condition 2 or condition 3 above is not met, the heat­er mode remains unchanged.
If the entering or leaving water temperature is less than the Brine Freeze Setpoint (Main Menu
Service Parameters  Brine Freeze Setpoint) +1.0°F
Configuration Menu
(0.5°C), then the heater will be turned on along with the pump. A current sensing relay monitors the current to the evaporator
heaters. If a heater fails, the reduction in current will switch the relay and produce a Evaporator Freezer Alarm (EVAPORA­TOR_FREEZE, 10001). In addition, the pump signal will ener­gize. See Appendix H for relay set points. See Fig. 67 for evapo­rator heater current sensing relay set point adjustment location.
LOW FLUID TEMPERATURE The Carrier Controller control is programmed to shut chiller
down if leaving fluid temperature drops below 34°F (1.1°C) for evaporator fluid type water or below the Brine Freeze Set­point (Main Menu
rameters
Brine Freeze Setpoint) for the evaporator fluid
Configuration Menu  Service Pa-
type brine. When fluid temperature rises to 6°F (3.3°C) above the leaving fluid set point, the alarm will reset and the chiller restarts. Reset is automatic as long as this is the first occur­rence. For repeat occurrences within 24 hours the alarm must be manually reset.
LOSS OF FLUID FLOW PROTECTION All 30XV machines include an integral flow switch that pro-
tects the evaporator against loss of evaporator flow.
TUBE PLUGGING A leaky tube can be plugged until retubing can be done. The num-
ber of tubes plugged determines how soon the evaporator must be retubed. All tubes in the evaporator may be removed. Loss of unit capacity and efficiency as well as increased pump power will re­sult from plugging tubes. Failed tubes should be replaced as soon as possible. Up to 10% of the total number of tubes can be plugged before retubing is necessary. Figure 68 shows an Elliott tube plug and a cross-sectional view of a plug in place. See Tables 44 and 45 for plug components. If the tube failure occurs in both circuits us­ing tube plugs will not correct the problem. Contact your local Carrier representative for assistance.
CAUTION
Use extreme care when installing plugs to prevent damage to the tube sheet section between the holes.
Fig. 67 — Evaporator Heater Set Point Adjustment
To configure this option with the Carrier Controller controls:
DISPLAY
NAME
Evaporator Heater Installed
NOTE: Evaporator Heater must be configured to YES for the ABVs to operate.
IMPORTANT: If unit is installed in an area where ambi­ent temperatures fall below 32°F (0°C), a suitable corro­sion-inhibited antifreeze solution or evaporator heater must be used in the chilled water circuit.
PATH VALUE
Main Menu Configuration Menu Factory Parameters

Evap Heater Installed YES/ NO DEFAULT= NO
Fig. 68 — Elliott Tube Plug
Table 44 — Plug Component Parts
(Evaporator Units Only)
COMPONENT PART NUMBER
For Tubes
Brass Pin 853103-1*
Brass Ring
Loctite No. 675 † Locquic “N”† Roller Extension S82-112/11
*Order directly from Elliot Tool Technologies, Dayton, OH or RCD.
†Can be obtained locally.
853002-640 or 657* (measure tube ID
before ordering)
Table 45 — Evaporator Tube Components
COMPONENT
Tube sheet hole diameter 0.756 19.20 Tube OD 0.750 19.05 Tube ID after rolling (includes
expansion due to clearance.)
NOTE: Tubes replaced along heat exchanger head partitions must be flush with tube sheet (both ends).
0.650 to
0.667
SIZE
in. mm
16.51 to 16.94
71
Page 72
EVAPORATOR RETUBING When retubing is required, obtain the service of qualified per-
sonnel experienced in boiler maintenance and repair. Most standard procedures can be followed when retubing the evapo­rators. An 8% crush is recommended when rolling replacement tubes into the tube sheet. Place one drop of Loctite No. 675 or equivalent on top of tube prior to rolling. This material is in­tended to “wick” into the area of the tube that is not rolled into the tube sheet, and prevent fluid from accumulating between the tube and the tube sheet. New tubes must also be rolled into the center tube sheet to prevent circuit to circuit leaks.
TIGHTENING EVAPORATOR HEAD BOLTS
Preparation
When reassembling evaporator heads, always check the condi­tion of the O-rings first. The O-ring should be replaced if there are visible signs of deterioration, cuts or damage. Apply a thin film of grease to the O-ring before installation. This will aid in holding the O-ring in the groove while the head is installed. Torque all bolts to the following specification and in sequence:
5
/8-in. Diameter Perimeter Bolts (Grade 5). . . . 150 to 170 ft-lb
(203 to 230 N-m)
3
/4-in. Diameter Perimeter Bolts (Grade 5). . . . 200 to 225 ft-lb
(271 to 305 N-m)
1. Install all bolts finger tight.
2. Bolt tightening sequence is outlined in Fig. 69. Follow the numbering or lettering sequence so that pressure is evenly applied to O-ring.
3. Apply torque in one-third steps until required torque is reached. Load all bolts to each one-third step before pro- ceeding to next one-third step.
4. No less than one hour later, retighten all bolts to required torque values.
5. After refrigerant is restored to system, check for refrigerant leaks using recommended industry practices.
6. Replace evaporator insulation.
INSPECTING/CLEANING HEAT EXCHANGERS Inspect and clean evaporator tubes at the end of the first operat-
ing season. Because these tubes have internal ridges, a rotary­type tube cleaning system is necessary to fully clean the tubes. Tube condition in the evaporator will determine the scheduled frequency for cleaning, and will indicate whether water treat­ment is adequate in the chilled water/brine circuit. Inspect the entering and leaving water thermistor wells for signs of corro­sion or scale. Replace the well if corroded or remove any scale if found.
CAUTION
Hard scale may require chemical treatment for its preven­tion or removal. Consult a water treatment specialist for proper treatment procedures.
1
3
5
9
13
17
19
24
22
16
12
8
4
24" EVAPORATOR – 5/8" BOLTS
(30XA350M THRU 30XA500M)
1
5
9
13
16
12
8
4
20" & 18" EVAPORATOR – 3/4" BOLTS
(30XA200M THRU 30XA350S)
7
11
15
17
21
23
18
14
10
6
2
3
7
11
14
10
6
2
3
1
5
9
12
8
4
16" EVAPORATOR – 3/4" BOLTS
(30XA160M THRU 30XA200S)
1
5
9
13
15
12
8
4
14" EVAPORATOR – 3/4" BOLTS
(30XA140S THRU 30XA160S)
7
11
10
6
2
3
7
11
14
10
6
2
Fig. 69 — Flooded Evaporator Unit Head Recommended Bolt Torque Sequence
72
Page 73
EVAPORATOR CHILLED WATER FLOW SWITCH
24 VAC
N
L1
BRN
WHT
BLK
BLU
1
2
3
4
OUT
IN
FLOW SWITCH (NOT TO SCALE)
a30-5854
A thermal-dispersion flow switch is factory-installed in the en­tering water nozzle for all machines. See Fig. 70 and 71. Figure 71 shows typical installation. If nuisance trips of the sensor are occurring, follow the steps below to correct:
1. Check to confirm that all strainers are clean, valves are open and pumps are running. For the case of VFD-controlled pumps, ensure the minimum speed setting has not been changed.
2. Measure the pressure drop across the evaporator. Use the evaporator pressure drop curves on page 52 to calculate the flow and compare this to system requirements. The pressure drop curves are for water only.
Fig. 70 — Chilled Water Flow Switch
PREPARATION FOR WINTER SHUTDOWN If the unit is not operational during the winter months, at the
end of the cooling season complete the following steps.
CAUTION
Failure to remove power before draining heater equipped evaporators can result in heater damage.
Evaporator to be drained for winter shutdown
1. To prepare the system for winter shutdown, draining the flu­id from the system is highly recommended. Isolate the evap­orator from the rest of the system with water shutoff valves. Be sure to deenergize heaters (if installed) by opening circuit breaker (CB-7) or shut off power to the chiller to prevent damage if the evaporator is drained.
2. Remove the evaporator drain plug. Follow all local codes and regulations regarding the fluid disposal.
3. Once fully drained, replace the drain plug(s) and completely fill the evaporator, and hydronic package if equipped, with suitable corrosion-inhibited antifreeze solution such as pro­pylene glycol. The concentration should be adequate to pro­vide freeze protection to 15°F (8.3°C) below the expected low ambient temperature conditions. Antifreeze can be add­ed through the vent on top of the evaporator head. Evapora­tor fluid volumes can be found in the Installation Instructions for the unit.
4. Leave the evaporator filled with the antifreeze solution for the winter to provide corrosion protection during the off season. The evaporator may be drained if desired. Follow all local codes and regulations regarding the fluid disposal.
5. At the beginning of the next cooling season, be sure that there is refrigerant pressure in each circuit before refilling evaporator, add recommended inhibitor, and reset the circuit breaker for the heater (CB-7) if opened or restore power.
Evaporator to remain filled for winter shutdown
1. If the evaporator will not be drained, do not shut off power disconnect during off-season shutdown.
2. If the chilled water loop is not protected with a suitable cor­rosion-inhibited antifreeze solution such as propylene glycol, the unit must have evaporator pump control. In the event of a power failure with sub-freezing temperatures, the unit will not have any evaporator freeze protection and may be sub­ject to damage.
Fig. 71 — Flow Switch Location
All Units
EVAPORATOR WATER TREATMENT Untreated or improperly treated water may result in corrosion,
scaling, erosion or algae. The services of a qualified water treatment specialist should be obtained to develop and monitor a treatment program.
CAUTION
Water must be within design flow limits, clean and treated to ensure proper machine performance and reduce the potential of tubing damage due to corrosion, scaling, and algae. Carrier assumes no responsibility for evaporator damage resulting from untreated or improperly treated water.
CAUTION
Operation or winter shutdown with fresh water is not fail­safe should there be a loss of power to the chiller or to the circulating pump. Freeze damage due to power loss or dis­abling chiller pump control in fresh water systems will im­pair or otherwise negatively affect the warranty.
3. It is recommended that the loop be protected with a suit­able corrosion-inhibited antifreeze solution such as pro­pylene glycol. The concentration should be adequate to provide freeze protection to 15°F (8.3°C) below the ex­pected low ambient temperature conditions. Evaporator heaters will not protect the evaporator from freeze-up in the event of power loss.
73
Page 74
MCHX Condenser Coil: Maintenance and Cleaning
Routine cleaning of coil surfaces is essential to maintain proper operation of the unit. Elimination of contamination and remov­al of harmful residues will greatly increase the life of the coil and extend the life of the unit. The following steps should be taken to clean MCHX condenser coils.
CAUTION
Do not apply any chemical cleaners to MCHX condenser coils. These cleaners can accelerate corrosion and damage the coil.
1. Remove any foreign objects or debris attached to the coil face or trapped within the mounting frame and brackets.
2. Put on personal protective equipment including safety glass­es and/or face shield, waterproof clothing and gloves. Full coverage clothing is recommended.
3. Start high pressure water sprayer and purge any soap or in­dustrial cleaners from sprayer before cleaning condenser coils. Only clean potable water is authorized for cleaning condenser coils.
4. Clean condenser face by spraying the coil steady and uni­formly from top to bottom while directing the spray straight toward the coil. Do not exceed 900 psig (6205 kPa), 104°F (40°C) water temperature, or 45 degree angle. The nozzle must be at least 12 in. (304.8 mm) from the coil face. Reduce pressure and use caution to prevent damage to air centers.
CAUTION
Excessive water pressure will fracture the braze between air centers and refrigerant tubes.
RTPF Condenser Coil: Maintenance and Cleaning
Routine cleaning of coil surfaces is essential to maintain proper operation of the unit. Elimination of contamination and remov­al of harmful residues will greatly increase the life of the coil and extend the life of the unit. The following maintenance and cleaning procedures are recommended as part of the routine maintenance activities to extend the life of the RTPF (round tube plate fin) coil.
REMOVE SURFACE LOADED FIBERS Surface loaded fibers or dirt should be removed with a vacuum
cleaner. If a vacuum cleaner is not available, a soft non-metal­lic bristle brush may be used. In either case, the tool should be applied in the direction of the fins. Coil surfaces can be easily damaged (fin edges can be easily bent over and damage to the coating of a protected coil) if the tool is applied across the fins.
NOTE: Use of a water stream, such as a garden hose, against a surface loaded coil will drive the fibers and dirt into the coil. This will make cleaning efforts more difficult. Surface loaded fibers must be completely removed prior to using low velocity clean water rinse.
PERIODIC CLEAN WATER RINSE A periodic clean water rinse is very beneficial for coils that are
applied in coastal or industrial environments. However, it is very important that the water rinse is made with very low ve­locity water stream to avoid damaging the fin edges. Monthly cleaning as described below is recommended.
ROUTINE CLEANING OF RTPF COIL SURFACE
Routine cleaning with Totaline cleaner is essential to extend the life of coils. This cleaner is available from Carrier Replacement Parts division as part num­ber P902-0301 for a one gallon container, and part number
®
environmentally balanced coil
P902-0305 for a five gallon container. It is recommended that all coils, including the standard copper tube aluminum fin, pre­coated fin, copper fin, or e-coated coils be cleaned with the To­taline environmentally balanced coil cleaner as described be­low. Coil cleaning should be part of the unit’s regularly sched­uled maintenance procedures to ensure long life of the coil. Failure to clean the coils may result in reduced durability in the environment. Avoid the use of:
• coil brighteners
• acid cleaning prior to painting
• high pressure washers
• poor quality water for cleaning
Totaline environmentally balanced coil cleaner is non-flamma­ble, hypoallergenic, nonbacterial, and a USDA accepted biode­gradable agent that will not harm the coil or surrounding com­ponents such as electrical wiring, painted metal surfaces, or in­sulation. Use of non-recommended coil cleaners is strongly discouraged since coil and unit durability could be affected.
Totaline Environmentally Balanced Coil Cleaner Application Equipment
1
•2
/2 gallon garden sprayer
• Water rinse with low velocity spray nozzle
CAUTION
Harsh chemicals, household bleach or acid or basic cleaners should not be used to clean outdoor or indoor coils of any kind. These cleaners can be very difficult to rinse out of the coil and can accelerate corrosion at the fin/tube interface where dissimilar materials are in contact. If there is dirt below the surface of the coil, use the Totaline environmentally bal­anced coil cleaner as described above.
CAUTION
High velocity water from a pressure washer, garden hose, or compressed air should never be used to clean a coil. The force of the water or air jet will bend the fin edges and increase air­side pressure drop. Reduced unit performance or nuisance unit shutdown may occur.
Totaline Environmentally Balanced Coil Cleaner Application Instructions
1. Proper eye protection such as safety glasses is recommended during mixing and application.
2. Remove all surface loaded fibers and dirt with a vacuum cleaner as described above.
3. Thoroughly wet finned surfaces with clean water and a low velocity garden hose, being careful not to bend fins.
4. Mix Totaline environmentally balanced coil cleaner in a
1
2
/2 gallon garden sprayer according to the instructions included with the cleaner. The optimum solution tempera­ture is 100°F (37.8°C).
NOTE: Do NOT enzymatic activity will be destroyed.
5. Thoroughly apply Totaline environmentally balanced coil cleaner solution to all coil surfaces including finned area, tube sheets and coil headers.
6. Hold garden sprayer nozzle close to finned areas and apply cleaner with a vertical, up-and-down motion. Avoid spraying in horizontal pattern to minimize potential for fin damage.
7. Ensure cleaner thoroughly penetrates deep into finned areas.
8. Interior and exterior finned areas must be thoroughly cleaned.
USE water in excess of 130°F (54.4°C), as the
74
Page 75
9. Finned surfaces should remain wet with cleaning solution
WIRE GUARD
FAN BLADE
FAN DECK
FORMED METAL MOUNT
MOTOR
a30-5863
for 10 minutes.
10. Ensure surfaces are not allowed to dry before rinsing. Reap­ply cleaner as needed to ensure 10-minute saturation is achieved.
11. Thoroughly rinse all surfaces with low velocity clean water using downward rinsing motion of water spray nozzle. Pro­tect fins from damage from the spray nozzle.
Condenser Fans
A formed metal mount bolted to the coil caps supports each fan and motor assembly. A shroud and a wire grille provide protection from the rotating fan. See Fig. 72. To remove the fan a special puller (RCD part no. 30RB680082) can be used. The fan utilizes a set screw and does not require the use of retaining compound in the keyway. The fan can be removed without the puller, but its use eases disassembly. The exposed end of the fan motor shaft is pro­tected from weather by grease. If fan motor must be removed for service or replacement, re-grease the fan shaft. The fan needs to be positioned fully down against the step on the motor shaft. Apply blue thread locker (Loctite 243) to the threads of both the axial bolt and the set screw. Install the thick washer and M8 axial bolt; do not fully tighten. Install set screw and tighten to 16 ± 2 ft-lbs (21.7 ± 2.7 Nm). Torque the axial bolt to 24 ± 2 ft-lbs (32.5 ± 2.7 Nm). Reinstall shroud and wire grille.
High Static Fan Option
A different fan blade is used for the high static fan option. It does not have the set screw to retain the key, so retaining com­pound must be used. The same puller is required to remove this fan blade. Use Loctite 603 retaining compound on the shaft and keyway during re-assembly. Remove any grease or con­taminates from the fan motor shaft before installation.
Refrigerant Circuit
LEAK TESTING Units are shipped with complete operating charge of refriger-
ant R-134a (see Physical Data tables supplied in the 30XV in­stallation instructions) and should be under sufficient pressure to conduct a leak test. If there is no pressure in the system, in­troduce enough nitrogen to search for the leak. Repair the leak using good refrigeration practices. After leaks are repaired, system must be evacuated and dehydrated.
REFRIGERANT CHARGE Refer to Physical Data tables supplied in the 30XV installation in-
structions. Immediately ahead of filter drier in each circuit is a fac­tory-installed liquid line service valve. Each valve has a cess connection for charging liquid refrigerant.
1
/4-in. ac-
Charging with Unit Off and Evacuated
Close liquid line service valve before charging. Weigh in charge shown on unit nameplate. Open liquid line service valve; start unit and allow it to run several minutes fully loaded. Check for a clear sight glass. Be sure clear condition is liquid and not vapor.
Charging with Unit Running
If charge is to be added while unit is operating, all condenser fans and compressors must be operating. It may be necessary to block condenser coils at low ambient temperatures to raise condensing pressure to approximately 198 psig (1365 kPa) to turn all condenser fans on. Do not totally block a coil to do this. Partially block all coils in uniform pattern. Charge each circuit until sight glass shows clear liquid, and has a liquid line tem­perature of 103°F (39°C).
Add 3 to 5 lb (1.36 to 2.27 kg), depending on unit size and coil type, of liquid charge into the fitting located on the tube enter­ing the evaporator. This fitting is located between the electron­ic EXV and the evaporator.
Allow the system to stabilize and then recheck the liquid tem­perature. If needed, add additional liquid charge, 3 to 5 lb at a time, allowing the system to stabilize between each charge ad­dition. Slowly add charge as the sight glass begins to clear to avoid overcharging.
IMPORTANT: When adjusting refrigerant charge, circulate fluid through evaporator continuously to prevent freezing and possible damage to the evaporator. Do not overcharge, and never charge liquid into the low-pressure side of system.
Safety Devices
The 30XV chillers contain many safety devices and protection logic built into the electronic control. Following is a descrip­tion of the major safeties.
COMPRESSOR PROTECTION
Motor Overload
The compressor VFD fuses and drive logic protect each com­pressor against overcurrent.
All compressors have factory-installed high-pressure switches. See Table 46. Each high-pressure switch is connected directly to its associated VFD (terminals 12 and 37). If the switch opens during operation, the compressor will be shut down. Manual reset of the high pressure switch, VFD, and the control is required to restart the compressor.
Table 46 — High-Pressure Switch Settings
UNIT
30XV 323.5 + 0.0 –14.0 2230 + 0.0 –14.0
SWITCH SETTING
psig kPa
Fig. 72 — Fan Mounting
75
Page 76
OIL SEPARATOR HEATERS Each oil separator circuit has a heater mounted on the side of
the vessel. Oil heater operation uses the following criteria:
1. The circuit’s Oil Heater (Oil Heater Output A or Oil Heat­er Output B) will be ON if the circuit’s compressor status (Compressor A or Compressor B) is OFF and the Oil Level Switch (Oil Level Input A or Oil Level Input B) is CLOSED.
2. The circuit’s Oil Heater (Oil Heater Output A or Oil Heater Output B) will be ON if the OAT is less than 99°F (37.2°C) and either of the following conditions is true:
a. The OAT minus the circuit’s SST (SST A or SST B) is
less than 30°F (16.6°C) and the circuit’s Discharge Pressure Temperature (Discharge Pressure A or Dis­charge Pressure B) is less than 203 psig (1400 kPa).
b. The OAT minus the LWT is less than 30°F (16.6°C)
and the circuit’s Discharge Pressure Temperature (Discharge Pressure A or Discharge Pressure B) is less than 203 psig (1400 kPa).
3. The circuit’s Oil Heater (Oil Heater Output A or Oil Heater Output B) will be OFF if the OAT is less than 99°F (37.2°C) and either of the following conditions is true:
a. The OAT minus the circuit’s SST (SST A or SST B) is
less than 30°F (16.6°C) and the circuit’s Discharge Pressure Temperature (Discharge Pressure A or Dis­charge Pressure B) is less than 275.5 psig (1900 kPa).
b. The OAT minus the LWT is less than 30°F (16.6°C)
and the circuit’s Discharge Pressure Temperature (Discharge Pressure A or Discharge Pressure B) is less than 275.5 psig (1900 kPa).
4. The circuit’s Oil Heater (Oil Heater Output A or Oil Heater Output B) will be OFF if the OAT is greater than 100°F (37.8°C) and either of the following conditions is true:
a. The OAT minus the circuit’s Saturated Suction Tem-
perature (Saturated Suction Temp A or Saturated Suc­tion Temp B) is greater than 32°F (17.7°C).
b. The OAT minus the LWT is less than 32°F (17.7°C).
Relief Devices
Fusible plugs are located in each circuit between the condenser and the liquid line shutoff valve.
PRESSURE RELIEF VALVES Valves are installed in each circuit and are located on the evap-
orators and oil separators. These valves are designed to relieve if an abnormal pressure condition arises. Relief valves on all evaporators relieve at 220 psig (1517 kPa). Relief valves on oil separators relieve at 350 psig (2413 kPa). These valves should not be capped. If a valve relieves, it should be replaced. If the valve is not replaced, it may relieve at a lower pressure, or leak due to trapped dirt from the system which may prevent reseal­ing. See Table 47. Some local building codes require that re­lieved gases be exhausted to a specific location. This connec­tion allows conformance to this requirement.
Table 47 — Relief Valve Connection Specifications
LOCATION CONNECTION SIZES
Oil Separator 3/8 SAE Flare
Evaporator 3/4 in. NPT Female
Inspection and Maintenance
The relief valves on this chiller protect the system against the potentially dangerous effects of overpressure. To ensure against damage to the equipment and possible injury to person­nel, these devices must be kept in peak operating condition. As a minimum, the following maintenance is required:
1. At least once a year, disconnect the vent piping at the valve outlet if equipped. Inspect the vent piping for corrosion, a restriction or blockage. If any is found, clean or replace the affected vent piping.
2. Carefully inspect the valve body and mechanism for any evi­dence of internal corrosion or rust, dirt, scale, leakage, etc. If corrosion or foreign material is found, do not attempt to re­pair or recondition; replace the valve.
3. If the chiller is installed in a corrosive atmosphere or the relief valves are vented into a corrosive atmosphere, in­spect relief valves and piping at more frequent intervals.
Variable Frequency Drives
The 30XV units with Greenspeed® Intelligence are equipped with VFDs to control the compressors and condenser fans. The Danfoss VLT face display. However, all necessary functions and statuses can be accessed from within the Carrier Controller menus. The VFDs are configured through the Carrier Controller controls, and parameters should not be changed manually.
ADDRESSING The 30XV units with Greenspeed Intelligence use Danfoss
VFDs that operate by communicating commands to the drive. As a result, each drive must have a unique address as shown in Table 48. Addresses must be set in VFD Parameter 8-31.
COMMUNICATION The 30XV units use Danfoss VFDs that operate by communi-
cating commands to the drive over the LEN bus. As a result, each drive must have a unique address.
COMMUNICATION WIRING LEN wiring is connected to each drive at VFD Terminals 61
(Ground), 68 (+) and 69 (-). See Fig. 73. VFDs should be arranged in a daisy-chain pattern, meaning the
communication wiring is connected to one drive, exits and is connected to the next. This pattern repeats until the last drive on the communication bus is reached. See Table 49 to deter­mine correct Communications Wiring in Fig. 75-79.
1
HVAC drives each include an LCD user inter-
Table 48 — VFD Addresses
VFD Address
Compressor A 181
Compressor B 182 Circuit A Fan Drive 1 184 Circuit A Fan Drive 2 185 Circuit B Fan Drive 1 187 Circuit B Fan Drive 2 188
1. VLT is a registered trademark of Danfoss Group Global.
76
Page 77
Fig. 73 — VFD LEN Wiring Termination
Table 49 — 30XV VFD Communication Wiring
TIER (POSITION 10)
30XV VOLTAGE
208/230-3-60 Figure 74 Figure 75 Figure 75 Figure 76
380-3-60 Figure 74 Figure 75 Figure 75 Figure 75 400-3-60 Figure 74 Figure 75 Figure 75 Figure 75
140
160
180
200
225
575-3-60 Figure 74 Figure 75 Figure 75 Figure 75 380-3-50 Figure 74 Figure 75 Figure 75 Figure 75 400-3-50 Figure 74 Figure 75 Figure 75 Figure 75 415-3-50 Figure 74 Figure 75 Figure 75 Figure 75 440-3-50 Figure 74 Figure 75 Figure 75 Figure 75
208/230-3-60 Figure 74 Figure 75 Figure 76 Figure 76
380-3-60 Figure 74 Figure 75 Figure 75 Figure 75 460-3-60 Figure 74 Figure 75 Figure 75 Figure 75 575-3-60 Figure 74 Figure 75 Figure 75 Figure 75 380-3-50 Figure 74 Figure 75 Figure 75 Figure 75 400-3-50 Figure 74 Figure 75 Figure 75 Figure 75 415-3-50 Figure 74 Figure 75 Figure 75 Figure 75 440-3-50 Figure 74 Figure 75 Figure 75 Figure 75
208/230-3-60 Figure 74 Figure 75 Figure 76 Figure 76
380-3-60 Figure 74 Figure 75 Figure 75 Figure 75 460-3-60 Figure 74 Figure 75 Figure 75 Figure 75 575-3-60 Figure 74 Figure 75 Figure 75 Figure 75 380-3-50 Figure 74 Figure 75 Figure 75 Figure 75 400-3-50 Figure 74 Figure 75 Figure 75 Figure 75 415-3-50 Figure 74 Figure 75 Figure 75 Figure 75 440-3-50 Figure 74 Figure 75 Figure 75 Figure 75
208/230-3-60 Figure 74 Figure 75 Figure 76 Figure 76
380-3-60 Figure 74 Figure 75 Figure 75 Figure 75 460-3-60 Figure 74 Figure 75 Figure 75 Figure 75 575-3-60 Figure 74 Figure 75 Figure 75 Figure 75 380-3-50 Figure 74 Figure 75 Figure 75 Figure 75 400-3-50 Figure 74 Figure 75 Figure 75 Figure 75 415-3-50 Figure 74 Figure 75 Figure 75 Figure 75 440-3-50 Figure 74 Figure 75 Figure 75 Figure 75 380-3-60 Figure 74 Figure 75 Figure 75 Figure 76 460-3-60 Figure 74 Figure 75 Figure 75 Figure 76 575-3-60 Figure 74 Figure 75 Figure 75 Figure 76 380-3-50 Figure 74 Figure 75 Figure 75 Figure 76 400-3-50 Figure 74 Figure 75 Figure 75 Figure 76 415-3-50 Figure 74 Figure 75 Figure 75 Figure 76 440-3-50 Figure 74 Figure 75 Figure 75 Figure 76
S
S W/ LOW
AMBIENT
OPTION
MH
Table 49 — 30XV VFD Communication Wiring (cont)
TIER (POSITION 10)
30XV VOLTAGE
380-3-60 Figure 74 Figure 75 Figure 75 Figure 76 460-3-60 Figure 74 Figure 75 Figure 75 Figure 76
250
275
300
325
350
400
450
500
575-3-60 Figure 74 Figure 75 Figure 75 Figure 76 380-3-50 Figure 74 Figure 75 Figure 75 Figure 76 400-3-50 Figure 74 Figure 75 Figure 75 Figure 76 415-3-50 Figure 74 Figure 75 Figure 75 Figure 76 440-3-50 Figure 74 Figure 75 Figure 75 Figure 76 380-3-60 Figure 74 Figure 75 Figure 75 Figure 76 460-3-60 Figure 74 Figure 75 Figure 75 Figure 76 575-3-60 Figure 74 Figure 75 Figure 75 Figure 76 380-3-50 Figure 74 Figure 75 Figure 75 Figure 76 400-3-50 Figure 74 Figure 75 Figure 75 Figure 76 415-3-50 Figure 74 Figure 75 Figure 75 Figure 76 440-3-50 Figure 74 Figure 75 Figure 75 Figure 76 380-3-60 Figure 74 Figure 75 Figure 76 Figure 76 460-3-60 Figure 74 Figure 75 Figure 76 Figure 76 575-3-60 Figure 74 Figure 75 Figure 76 Figure 76 380-3-50 Figure 74 Figure 75 Figure 76 Figure 76 400-3-50 Figure 74 Figure 75 Figure 76 Figure 76 415-3-50 Figure 74 Figure 75 Figure 76 Figure 76 440-3-50 Figure 74 Figure 75 Figure 76 Figure 76 380-3-60 Figure 74 Figure 76 Figure 76 Figure 76 460-3-60 Figure 74 Figure 76 Figure 76 Figure 76 575-3-60 Figure 74 Figure 76 Figure 76 Figure 76 380-3-50 Figure 74 Figure 76 Figure 76 Figure 76 400-3-50 Figure 74 Figure 76 Figure 76 Figure 76 415-3-50 Figure 74 Figure 76 Figure 76 Figure 76 440-3-50 Figure 74 Figure 76 Figure 76 Figure 76 380-3-60 Figure 74 Figure 77 Figure 78 Figure 78 460-3-60 Figure 74 Figure 77 Figure 78 Figure 78 575-3-60 Figure 74 Figure 77 Figure 78 Figure 78 380-3-50 Figure 74 Figure 77 Figure 78 Figure 78 400-3-50 Figure 74 Figure 77 Figure 78 Figure 78 415-3-50 Figure 74 Figure 77 Figure 78 Figure 78 440-3-50 Figure 74 Figure 77 Figure 78 Figure 78 380-3-60 Figure 74 Figure 78 Figure 78 Figure 78 460-3-60 Figure 74 Figure 78 Figure 78 Figure 78 575-3-60 Figure 74 Figure 78 Figure 78 Figure 78 380-3-50 Figure 74 Figure 78 Figure 78 Figure 78 400-3-50 Figure 74 Figure 78 Figure 78 Figure 78 415-3-50 Figure 74 Figure 78 Figure 78 Figure 78 440-3-50 Figure 74 Figure 78 Figure 78 Figure 78 380-3-60 Figure 74 Figure 78 Figure 78 Figure 78 460-3-60 Figure 74 Figure 78 Figure 78 Figure 78 575-3-60 Figure 74 Figure 78 Figure 78 Figure 78 380-3-50 Figure 74 Figure 78 Figure 78 Figure 78 400-3-50 Figure 74 Figure 78 Figure 78 Figure 78 415-3-50 Figure 74 Figure 78 Figure 78 Figure 78 440-3-50 Figure 74 Figure 78 Figure 78 Figure 78 380-3-60 Figure 74 Figure 78 Figure 78 — 460-3-60 Figure 74 Figure 78 Figure 78 — 575-3-60 Figure 74 Figure 78 Figure 78 — 380-3-50 Figure 74 Figure 78 Figure 78 — 400-3-50 Figure 74 Figure 78 Figure 78 — 415-3-50 Figure 74 Figure 78 Figure 78 — 440-3-50 Figure 74 Figure 78 Figure 78 —
S W/ LOW
S
AMBIENT
OPTION
MH
77
Page 78
Fig. 74 — VFD Communication Wiring (Compressor
A-B) For All Standard Tier Units without Low
Ambient Option
Fig. 75 — VFD Communication Wiring (Compressor A-B-Fan VFD A1-B1)
78
Page 79
Fig. 76 — VFD Communication Wiring (Compressor A-B-Fan VFD A1-A2-B1-B2)
79
Page 80
Fig. 77 — VFD Communication Wiring (Compressor A-B, Fan VFD A1-A2-B1)
Fig. 78 — VFD Communication Wiring (Compressor A-B, Fan VFD A1-A2-B1-B2)
80
Page 81
At each drive where the LEN wiring enters, connects, and exits to the next drive, the LEN shield must be connected together to form a continuous ground, but not grounded in the drive itself. At the last VFD of the daisy chain, the LEN shield must be grounded at the drive. To do this, strip the LEN wire cable to expose the shield under the jacket and pinch LEN wire cable within the clamp as shown in Fig. 79.
Additionally, it is recommended that the BUS TER (Bus Ter­mination) DIP Switch be turned ON at the last VFD in the dai­sy chain. This switch is located behind the Local Control Panel (LCP). See Fig. 80.
COMPRESSOR DRIVES Each unit is equipped with two VFDs to control the compres-
sor operation, one for each circuit. The VFDs vary the operat­ing speed of the compressors by changing the input power fre­quency over a programmed range. The compressor VFDs should not be operated below minimum programmed frequen­cy, to ensure adequate oil return on the unit. See Fig. 81 for compressor VFD locations.
For all chillers, the VFDs are inside the control panel. The right and left doors allow access to the drives and displays.
CONDENSER FAN DRIVES Chillers with M or H in the 10th position of the model number
or with the Low Ambient option will have condenser fans on each circuit which are controlled by one or two VFDs. The fans on each circuit all operate together at the same prepro­grammed frequency. Table 50 shows the standard tier fan se­quences. Tables 51-53 show which condenser fans are con­trolled by each drive. See Tables 51-53 for typical fan VFD ar­rangement. See Fig. 82 for typical fan VFD location.
Fig. 80 — BUS TER Location
Fig. 79 — LEN Shield Grounding
81
Page 82
30XV225-325
30XV350-500
30XV140-325
COMPRESSOR A VFD
COMPRESSOR B VFD
Fig. 81 — VFD Compressor Locations
82
Page 83
Control Box End
FM A1
FM A2
FM A3
FM A4
FM B3
FM B4
FM B1
FM B2
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM B5
FM B3
FM B4
FM B1
FM B2
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM B3
FM B4
FM B1
FM B2
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM B5
FM B6
FM B3
FM B4
FM B1
FM B2
Control
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM A8
FM B7
FM B8
FM B5
FM B6
FM B3
FM B4
FM B1
FM B2
Box End
FM A1
FM A2
Table 50 — Standard Tier Fan Sequence
FANS CKT 140-180
FAN STAGE A 1 2 3 4
A
CONTACTOR # FC A1 FC A2 FC A3 FC A4
FAN POSITION FMA1 FMA2 FMA3 FMA4
FAN STAGE B 1 2 3 4
B
CONTACTOR # FC B1 FC B2 FC B3 FC B4
FAN POSITION FMB1 FMB2 FMB3 FMB4
FAN STAGE A 1 2 3 4 5
A
CONTACTOR # FC A1 FC A2 FC A3 FC A4 FC A5
FAN POSITION FMA1 FMA2 FMA3 FMA4 FMA5
FAN STAGE B 1 2 3 4 5
B
CONTACTOR # FC B1 FC B2 FC B3 FC B4 FC B5
FAN POSITION FMB1 FMB2 FMB3 FMB4 FMB5
FAN STAGE A 1 2 3 4 5 6
A
CONTACTOR # FC A1 FC A2 FC A3 FC A4 FC A5 FC A6
FAN POSITION FMA1 FMA2 FMA3 FMA4 FMA5 FMA6
FAN STAGE B 1 2 3 4
B
CONTACTOR # FC B1 FC B2 FC B3 FC B4
FAN POSITION FMB1 FMB2 FMB3 FMB4
FAN STAGE A 1 2 3 4 5 6
A
CONTACTOR # FC A1 FC A2 FC A3 FC A4 FC A5 FC A6
FAN POSITION FMA1 FMA2 FMA3 FMA4 FMA5 FMA6
FAN STAGE B 1 2 3 4 5 6
B
CONTACTOR # FC B1 FC B2 FC B3 FC B4 FC B5 FC B6
FAN POSITION FMB1 FMB2 FMB3 FMB4 FMB5 FMB6
FAN STAGE A 1 2 3 4 5 6 7
A
FM A3
FM A4
FM A5
FM A6
FM A7
FM B7
FM B5
FM B6
FM B3
FM B4
FM B1
FM B2
CONTACTOR # FC A1 FC A2 FC A3 FC A4 FC A5 FC A6 FC A7
FAN POSITION FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7
FAN STAGE B 1 2 3 4 5 6 7
B
CONTACTOR # FC B1 FC B2 FC B3 FC B4 FC B5 FC B6 FC B7
FAN POSITION FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7
FAN STAGE A 1 2 3 4 5 6 7
A
CONTACTOR # FC A1 FC A2 FC A3 FC A4 FC A5 FC A6 FC A7
FAN POSITION FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 | FMA8
FAN STAGE B 1 2 3 4 5 6 7
B
CONTACTOR # FC B1 FC B2 FC B3 FC B4 FC B5 FC B6 FC B7
FAN POSITION FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7 | FMB8
200
225
250-275
300
325
83
Page 84
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM A8
FM B7
FM A9
FM B5
FM B6
FM B3
FM B4
FM B1
FM B2
Control
FM B6
FM B8
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM A8
FM A9
FM A10
FM B9
FM B10
FM B7
FM B5
FM B4
FM B3
FM B2
FM B1
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM A8
FM A9
FM A10
FM B11
FM A11
FM B9
FM B10
FM B7
FM B8
FM B5
FM B6
FM B3
FM B4
FM B1
FM B2
Box End
Table 50 — Standard Tier Fan Sequence (cont)
FANS CKT 350
FAN STAGE A 1 2 3 4 5 6 7 8
A
CONTACTOR # FC A1 FC A2 FC A3 FC A4 FC A5 FC A6 FC A7 FC A8
FAN POSITION FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 FMA8 FMA9
FAN STAGE B 1 2 3 4 5 6 7
B
CONTACTOR # FC B1 FC B2 FC B3 FC B4 FC B5 FC B6 FC B7
FAN POSITION FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7
400
FAN STAGE A 1 2 3 4 5 6 7 8
A
FM A1
FM A2
FM
FM A3
FM A4
FM
A5
A7
FM
FM
A6
A8
FM
FM B9
FM A9
FM
B7
B5
FM
FM
B8
B6
FM
FM
B1
B3
FM
FM
B2
B4
CONTACTOR # FC A1 FC A2 FC A3 FC A4 FC A5 FC A6 FC A7 FC A8
FAN POSITION FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 FMA8 FMA9
FAN STAGE B 1 2 3 4 5 6 7 8
B
CONTACTOR # FC B1 FC B2 FC B3 FC B4 FC B5 FC B6 FC B7 FC B8
FAN POSITION FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7 FMB8 FMB9
450
FAN STAGE A 1 2 3 4 5 6 7 8
A
CONTACTOR # FC A1 FC A2 FC A3 FC A4 FC A5 FC A6 FC A7 FC A8
FAN POSITION FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 FMA8 FMA9 FMA10
FAN STAGE B 1 2 3 4 5 6 7 8
B
CONTACTOR # FC B1 FC B2 FC B3 FC B4 FC B5 FC B6 FC B7 FC B8
FAN POSITION FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7 FMB8 FMB9 FMB10
500
FAN STAGE A 1 2 3 4 5 6 7 8
A
CONTACTOR # FC A1 FC A2 FC A3 FC A4 FC A5 FC A6 FC A7 FC A8
FAN POSITION FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 FMA8 FMA9 FMA10 FMA11
FAN STAGE B 1 2 3 4 5 6 7 8
B
CONTACTOR # FC B1 FC B2 FC B3 FC B4 FC B5 FC B6 FC B7 FC B8
FAN POSITION FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7 FMB8 FMB9 FMB10 FMB11
84
Page 85
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM B5
FM B3
FM B4
FM B1
FM B2
Control
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM A8
FM B7
FM B8
FM B5
FM B6
FM B3
FM B4
FM B1
FM B2
Box End
Control Box End
Table 51 — Condenser Fan Drive Arrangement, Standard Tier with Low Ambient Option
FANS CKT 30XV140, 160, 180 (ALL VOLTAGES)
VFD Designation A1
A
Fan Position FMA1 FMA2 FMA3 FMA4
VFD Designation B1
B
Fan Position FMB1 FMB2 FMB3 FMB4
30XV200 (208/230V)
VFD Designation A2 A1
A
Fan Position FMA1 FMA2 FMA3 FMA4 FMA5
VFD Designation B2 B1
B
Fan Position FMB1 FMB2 FMB3 FMB4 FMB5
30XV200 (380-575V)
VFD Designation A1
A
Fan Position FMA1 FMA2 FMA3 FMA4 FMA5
VFD Designation B1
B
Fan Position FMB1 FMB2 FMB3 FMB4 FMB5
30XV 225 (380-575V)
VFD Designation A1
A
Fan Position FMA1 FMA2 FMA3 FMA4 FMA5 FMA6
VFD Designation B1
B
Fan Position FMB1 FMB2 FMB3 FMB4
30XV 250,275 (380-575V)
VFD Designation A1
A
Fan Position FMA1 FMA2 FMA3 FMA4 FMA5 FMA6
VFD Designation B1
B
Fan Position FMB1 FMB2 FMB3 FMB4 FMB5 FMB6
30XV300 (380-575V)
VFD Designation A1
A
Fan Position FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7
VFD Designation B1
B
Fan Position FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7
30XV325 (380V-575V)
VFD Designation A2 A1
A
Fan Position FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 FMA8
Control Box End
Control Box End
FM A1
FM A2
FM A1
FM A2
FM A1
FM A3
FM A4
FM A2
FM A1
FM A2
FM A3
FM A4
FM A3
FM A5
FM A6
FM A4
FM A3
FM A5
FM A4
FM A6
FM A5
FM A7
FM B7
FM A6
FM B3
FM B5
FM B4
FM B6
FM B3
FM B5
FM B6
FM B4
FM B1
FM B2
FM B3
FM B4
FM B1
FM B3
FM B2
FM B4
FM B1
FM B2
FM B1
FM B2
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM A8
FM B7
FM A9
FM B5
FM B6
FM B3
FM B4
FM B1
FM B2
VFD Designation B2 B1
B
Fan Position FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7 FMB8
30XV350 (380-575V)
VFD Designation A2 A1
A
Fan Position FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 FMA8 FMA9
VFD Designation B1
B
Fan Position FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7
85
Page 86
Control
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM A8
FM A9
FM A10
FM B11
FM A11
FM B9
FM B10
FM B7
FM B8
FM B5
FM B6
FM B3
FM B4
FM B1
FM B2
Box End
Control Box End
Table 51 — Condenser Fan Drive Arrangement, Standard Tier with Low Ambient Option (cont)
FANS CKT 30XV400 (380-575V)
VFD Designation A2 A1
FM A1
FM A1
FM A2
FM A2
FM
FM A3
FM A4
FM A3
FM A4
FM
A5
A7
FM
FM
A6
A8
FM A5
FM A6
FM
FM
A9
A7
FM
FM
A10
A8
FM B9
FM A9
FM B9
FM B10
FM B7
FM B8
FM
FM
B5
B3
FM
FM
B6
B4
FM
FM B7
FM B8
FM
B5
FM B6
FM
B3
B1
FM
FM
B4
B2
FM B1
FM B2
A
Fan Position FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 FMA8 FMA9
VFD Designation B2 B1
B
Fan Position FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7 FMB8 FMB9
30XV450 (380-575V)
VFD Designation A2 A1
A
Fan Position FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 FMA8 FMA9 FMA10
VFD Designation B2 B1
B
Fan Position FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7 FMB8 FMB9 FMB10
30XV500 (380-575V)
VFD Designation A2 A1
A
Fan Position FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 FMA8 FMA9 FMA10 FMA11
VFD Designation B2 B1
B
Fan Position FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7 FMB8 FMB9 FMB10 FMB11
86
Page 87
Table 52 — Condenser Fan Drive Arrangement, Mid Tier
Control Box End
FM A1
FM A2
FM A3
FM A4
FM B3
FM B4
FM B1
FM B2
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM B5
FM B3
FM B4
FM B1
FM B2
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM B5
FM B6
FM B3
FM B4
FM B1
FM B2
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM B5
FM B3
FM B4
FM B1
FM B2
FANS CKT 30XV 140 (ALL VOLTAGES)
VFD Designation A1
A
Fan Position FMA1 FMA2 FMA3 FMA4
VFD Designation B1
B
Fan Position FMB1 FMB2 FMB3 FMB4
30XV 160,180 (208/230V)
VFD Designation A2 A1
A
Fan Position FMA1 FMA2 FMA3 FMA4 FMA5
VFD Designation B2 B1
B
Fan Position FMB1 FMB2 FMB3 FMB4 FMB5
30XV 160,180 (380-575V)
VFD Designation A1
A
Fan Position FMA1 FMA2 FMA3 FMA4 FMA5
VFD Designation B1
B
Fan Position FMB1 FMB2 FMB3 FMB4 FMB5
30XV200 (208/230V)
VFD Designation A2 A1
A
Fan Position FMA1 FMA2 FMA3 FMA4 FMA5 FMA6
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM B7
FM B5
FM B6
FM B3
FM B4
FM B1
FM B2
VFD Designation B2 B1
B
Fan Position FMB1 FMB2 FMB3 FMB4 FMB5 FMB6
30XV200 (380-575V)
VFD Designation A1
A
Fan Position FMA1 FMA2 FMA3 FMA4 FMA5 FMA6
VFD Designation B1
B
Fan Position FMB1 FMB2 FMB3 FMB4 FMB5 FMB6
30XV225 (380V-575V)
VFD Designation A1
A
Fan Position FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7
VFD Designation B1
B
Fan Position FMB1 FMB2 FMB3 FMB4 FMB5
30XV250,275 (380-575V)
VFD Designation A1
A
Fan Position FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7
VFD Designation B1
B
Fan Position FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7
87
Page 88
Table 52 — Condenser Fan Drive Arrangement, Mid Tier (cont)
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM A8
FM B7
FM B8
FM B5
FM B6
FM B3
FM B4
FM B1
FM B2
FM B4
Control
Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM A8
FM B9
FM A9
FM B7
FM B8
FM B5
FM B6
FM B3
FM B2
FM B1
FM B4
Control
Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM A8
FM
FM
A9
FM B7
FM B8
FM B5
FM B6
FM B3
FM B2
FM B1
A10
FM B6
FM B8
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM A8
FM A9
FM A10
FM B9
FM B10
FM B7
FM B5
FM B4
FM B3
FM B2
FM B1
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM A8
FM A9
FM A10
FM A11
FM B10
FM B9
FM B11
FM B7
FM B10
FM B5
FM B6
FM B3
FM B4
FM B1
FM B2
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM A8
FM A9
FM A10
FM A11
FM A12
FM B11
FM B12
FM B9
FM B10
FM B7
FM B8
FM B5
FM B6
FM B3
FM B4
FM B1
FM B2
FANS CKT 30XV300 (380V-575V)
A
B
A
B
A
B
A
B
A
B
A
B
VFD
Designation
Fan
Position
VFD
Designation
Fan
Position
VFD
Designation
Fan
Position
VFD
Designation
Fan
Position
VFD
Designation
Fan
Position
VFD
Designation
Fan
Position
VFD
Designation
Fan
Position
VFD
Designation
Fan
Position
VFD
Designation
Fan
Position
VFD
Designation
Fan
Position
VFD
Designation
Fan
Position
VFD
Designation
Fan
Position
FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 FMA8
FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7 FMB8
FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 FMA8 FMA9
FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7 FMB8 FMB9
FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 FMA8 FMA9 FMA10
FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7 FMB8
FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 FMA8 FMA9 FMA10
FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7 FMB8 FMB9 FMB10
FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 FMA8 FMA9 FMA10 FMA11
FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7 FMB8 FMB9 FMB10 FMB11
FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 FMA8 FMA9 FMA10FMA11FMA12
FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7 FMB8 FMB9 FMB10FMB11FMB12
A2 A1
B2 B1
30XV325 (380-575V)
A2 A1
B2 B1
30XV350 (380V-575V)
A2 A1
B2 B1
30XV400 (380-575V)
A2 A1
B2 B1
30XV450 (380V-575V)
A2 A1
B2
30XV500 (380-575V)
A2
B2
B1
A1
B1
88
Page 89
Control
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM B5
FM B6
FM B3
FM B4
FM B1
FM B2
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM B7
FM B5
FM B6
FM B3
FM B4
FM B1
FM B2
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM A8
FM B5
FM B6
FM B3
FM B4
FM B1
FM B2
Box End
Table 53 — Condenser Fan Drive Arrangement, High Tier
FANS CKT 30XV140 (208/230V)
FM A1
FM A2
FM A3
FM A4
FM A5
FM B5
FM B3
FM B4
FM B1
FM B2
Designation
A
Designation
B
Designation
A
Designation
B
Designation
A
Designation
B
Designation
A
Designation
B
Designation
A
Designation
B
Designation
A
Designation
B
Designation
A
Designation
B
VFD
Fan
Position
VFD
Fan
Position
VFD
Fan
Position
VFD
Fan
Position
VFD
Fan
Position
VFD
Fan
Position
VFD
Fan
Position
VFD
Fan
Position
VFD
Fan
Position
VFD
Fan
Position
VFD
Fan
Position
VFD
Fan
Position
VFD
Fan
Position
VFD
Fan
Position
A2 A1
FMA1 FMA2 FMA3 FMA4 FMA5
B2 B1
FMB1 FMB2 FMB3 FMB4 FMB5
30XV140 (380-575V)
FMA1 FMA2 FMA3 FMA4 FMA5
FMB1 FMB2 FMB3 FMB4 FMB5
FMA1 FMA2 FMA3 FMA4 FMA5 FMA6
FMB1 FMB2 FMB3 FMB4 FMB5 FMB6
30XV160,180 (380-575V)
FMA1 FMA2 FMA3 FMA4 FMA5 FMA6
FMB1 FMB2 FMB3 FMB4 FMB5 FMB6
FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7
FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7
FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7
FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7
FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 FMA8
FMB1 FMB2 FMB3 FMB4 FMB5 FMB6
A1
B1
30XV160,180 (208/230V)
A2 A1
B2 B1
A1
B1
30XV200 (208/230V)
A2 A1
B2 B1
30XV200 (380-575V)
A1
B1
30XV225 (380-575V)
A2 A1
B1
89
Page 90
Table 53 — Condenser Fan Drive Arrangement, High Tier (cont)
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM A8
FM B7
FM B8
FM B5
FM B6
FM B3
FM B4
FM B1
FM B2
FM B4
Control
Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM A8
FM A9
FM B9
FM B7
FM B8
FM B5
FM B6
FM B3
FM B2
FM B1
FM B6
FM B8
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM A8
FM A9
FM A10
FM B9
FM B10
FM B7
FM B5
FM B4
FM B3
FM B2
FM B1
FM B6
FM B8
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM A8
FM A9
FM A10
FM B9
FM A11
FM B7
FM B5
FM B4
FM B3
FM B2
FM B1
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM A8
FM A9
FM A10
FM A11
FM B10
FM B9
FM B11
FM B7
FM B10
FM B5
FM B6
FM B3
FM B4
FM B1
FM B2
Control Box End
FM A1
FM A2
FM A3
FM A4
FM A5
FM A6
FM A7
FM A8
FM A9
FM A10
FM A11
FM A12
FM B11
FM B12
FM B9
FM B10
FM B7
FM B8
FM B5
FM B6
FM B3
FM B4
FM B1
FM B2
FANS CKT 30XV250, 275 (380V-575V)
Designation
A
Designation
B
Designation
A
Designation
B
Designation
A
Designation
B
Designation
A
Designation
B
Designation
A
Designation
B
Designation
A
Designation
B
VFD
Fan
FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 FMA8
Position
VFD
Fan
FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7 FMB8
Position
VFD
Fan
FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 FMA8 FMA9
Position
VFD
Fan
FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7 FMB8 FMB9
Position
VFD
Fan
FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 FMA8 FMA9 FMA10
Position
VFD
Fan
FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7 FMB8 FMB9 FMB10
Position
VFD
Fan
FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 FMA8 FMA9 FMA10 FMA11
Position
VFD
Fan
FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7 FMB8 FMB9
Position
VFD
Fan
FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 FMA8 FMA9 FMA10 FMA11
Position
VFD
Fan
FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7 FMB8 FMB9 FMB10 FMB11
Position
VFD
Fan
FMA1 FMA2 FMA3 FMA4 FMA5 FMA6 FMA7 FMA8 FMA9 FMA10 FMA11 FMA12
Position
VFD
Fan
FMB1 FMB2 FMB3 FMB4 FMB5 FMB6 FMB7 FMB8 FMB9 FMB10 FMB11 FMB12
Position
A2 A1
B2 B1
30XV300 (380-575V)
A2 A1
B2 B1
30XV325 (380-575V)
A2 A1
B2 B1
30XV350 (380V-575V)
A2 A1
B2 B1
30XV400 (380-575V)
A2 A1
B2 B1
30XV450 (380-575V)
A2 A1
B2 B1
90
Page 91
Fig. 82 — Typical Fan VFD Location
Fan VFD A1
Fan VFD B2
Fan VFD B1 Fan VFD A2
a
b
c
1
2
3
4
a30-5862
LEGEND
1—Graphical display with status lines 2—Menu keys and indicator lights 3—Navigation keys and indicator lights 4—Operation keys and indicator lights a—Status line b—Operator data lines c—Status messages
VFD DISPLAY NAVIGATION
displayed with fewer digits after the decimal point. For exam-
ple, a current readout might be 5.25 A,15.2 A, or 105 A. IMPORTANT: The VFDs are configured through the Carrier Controller controls, and parameters should not be changed manually. This section is included for informa-
tion and troubleshooting purposes only.
Status Display I is standard after start-up or initialization.
Touch [INFO] to obtain information about the value/measure-
ment linked to the displayed operating variables 1.1, 1.2, 1.3,
2, and 3). See the operating variables shown in the display in
Fig. 84. Variables 1.1, 1.2, and 1.3 are shown in small size.
NOTE: The following instructions apply to the Danfoss VLT
Variables 2 and 3 are shown in medium size.
VFD. The VFD can be operated in 2 ways:
• Graphical Local Control Panel (GLCP)
• RS-485 serial communication for PC connection
Graphical Local Control Panel
The LCD display is divided into 4 functional groups:
1. Graphical display with Status lines
2. Menu keys and indicator lights (LEDs) — selecting mode, changing parameters and switching between display func­tions
3. Navigation keys and indicator lights (LEDs)
4. Operation keys and indicator lights (LEDs)
See Fig. 83. The display is backlit with a total of 6 alpha-nu­meric lines. All data is displayed on the GLCP, which can show up to 5 operating variables while in Status mode.
The display lines (see items a-c in Fig. 83) function as follows:
a. The status line at the top of the display shows VFD
status when in [Status] mode or up to 2 variables when not in [Status] mode, or in case of an alarm or warning (alert).
b. The operator data line in the middle section shows up
to 5 variables with their related units, regardless of status. In the case of an alarm or warning, the warning is shown instead of the variables.
c. The status line in the bottom section always shows the
state of the VFD in Status mode.
The operator can toggle among 3 status read-out screens by touching the Status key. Several values or measurements can be linked to each of the displayed operating variables. The val­ues/measurements to be displayed can be defined via parame­ter 0-20 Display Line 1.1 Small, 0-21 Display Line 1.2 Small, 0-22 Display Line 1.3 Small, 0-23 Display Line 2 Large and 0­24 Display Line 3 Large. The settings are accessed by selecting
tings

readout parameter selected in 0-20 Display Line 1.1 Small to 0-24 Display Line 3 Large has its own scale and number of digits after a possible decimal point. Larger numeric values are
QUICK MENU
Q3 Function Setups  Q3-1 General Set-
Q3-13 Display Settings. Each value/measurement
Fig. 83 — VFD Graphical Local Control Panel
91
Page 92
Fig. 84 — Status Display I
a30-5857
a30-5935
Status Display II shows the operating variables 1.1, 1.2, 1.3 and 2. In the example shown in Fig. 85, Speed, Motor Current, Motor Power, and Frequency are selected as variables in the first and second lines. Variables 1.1, 1.2, and 1.3 are shown in small size. Variable 2 is shown in large size.
Fig. 85 — Status Display II
Status Display III shows events and actions of the Smart Logic Control. Figure 86 shows an example.
Fig. 86 — Status Display III
The operator can adjust the display brightness by touching Sta­tus and ▲ to darken the display or ▼ to lighten it.
• Green LED (On): Control section is working. The On LED is activated when the VFD receives power from mains voltage, a DC bus terminal, or an external 24 V supply. At the same time, the back light is on.
• Yellow LED (Warn.): Indicates a warning.
• Flashing Red LED (Alarm): Indicates an alarm.
The warning and/or alarm LEDs light up if certain threshold values are exceeded. A status message and alarm text also ap­pear on the control panel. See Fig. 87.
a30-5856
Fig. 87 — Indicator Lights
The menu keys below the display and indicator lights include Status, Quick Menu, Main Menu, and Alarm Log. The Status menu indicates the status of the frequency converter and/or the motor. Three display modes are available (see Fig. 84-86). Use the Status key for selecting mode of display or for changing back to display mode from the Quick Menu Mode, the Main Menu Mode, or the Alarm Log mode. The operator can also use the Status key to toggle between single or double read-out mode.
The Quick Menu key allows quick set-up of the frequency con­verter. The most common HVAC functions can be programmed here. Menu options include:
• My Personal Menu
• Quick Set-up
• Function Set-up
• Changes Made
• Loggings
The Function Set-up option provides quick and easy access to all parameters required for most HVAC applications. Among other features it also includes parameters for selecting which variables to display on the local control panel, digital preset speeds, scaling of analog references, closed loop single-zone and multi-zone applications, and specific functions related to fans, pumps and compressors.
The Quick Menu parameters can be accessed immediately un­less a password has been created via 0-60 Main Menu Pass­word, 0-61 Access to Main Menu without Password, 0-65 Per­sonal Menu Password, or 0-66 Access to Personal Menu with­out Password. It is possible to switch directly between Quick Menu mode and Main Menu mode.
The Main Menu key is used for programming all parameters. These can be accessed immediately unless a password has been created via 0-60 Main Menu Password, 0-61 Access to Main Menu without Password, 0-65 Personal Menu Password, or 0­66 Access to Personal Menu without Password. For most HVAC applications it is not necessary to access the Main Menu parameters but instead use the Quick Menu. Quick Set-up and Function Set-up provides the simplest and quickest access to the typical required parameters.
It is possible to switch directly between Main Menu mode and Quick Menu mode. The parameter shortcut can be carried out by touching the Main Menu key for 3 seconds. The parameter shortcut allows direct access to any parameter.
Touch Alarm Log to display a list of the 10 latest alarms (num­bered A1-A10). To obtain additional details about an alarm, touch the navigation keys to reach the alarm number and touch OK. Information is displayed about the condition of the fre­quency converter before it enters the alarm mode. The Alarm Log key also provides access to a Maintenance log.
92
Page 93
At the middle part of the local control panel, the Back key re­verts to the previous step or layer in the navigation structure. The Cancel key cancels the last change or command as long as the display has not changed. The Info Key displays informa­tion about a command, parameter, or function in any display window, providing detailed information when needed. The four arrow keys are used among menu options by moving the cursor in the direction indicated. Touch OK to select a parame­ter marked by the cursor or to enable a parameter change.
Operation keys for local control are found at the bottom of the control panel (see Fig. 83). Hand On enables control of the fre­quency converter via the local control panel. Hand On also starts the motor, and it is possible to enter the motor speed data by means of the navigation keys. The key can be selected as [1] Enable or [0] Disable via 0-40 Hand On Key on the local con­trol panel.
NOTE: External stop signals activated by means of control sig­nals or a serial bus override a start command via the local con­trol panel.
The Off key stops the connected motor. If no external stop function is selected and Off key is inactive, the motor can only be stopped by disconnecting the mains supply.
Auto On enables the frequency converter to be controlled via the control terminals and/or serial communication. When a start signal is applied on the control terminals and/or the bus, the frequency converter starts.
NOTE: An active HAND-OFF-AUTO signal via digital inputs has higher priority than the local control keys Hand On –Auto On.
The Reset key resets the frequency converter after an alarm (trip).
VFD STATUS The current operating status and conditions of the VFDs can be
viewed with the Carrier Controller controls.
Compressor VFD Status
To view the operating status of the compressor VFDs, follow the Carrier Controller path: Main Menu
Menu
operating conditions for both drives: Drive Power, Amps, Volt­age, Speed, Frequency, Torque, DC Link Voltage, Heat Sink Temperature, Control Card Temperature, Heater Status, and Communication Status.
Fan VFD Status
To view the operating status of the fan VFDs, follow the Carri­er Controller path: Main Menu Drive Maintenance. This menu shows current operating condi­tions for both drives: Drive Power, Amps, Voltage, Speed, Fre­quency, Torque, DC Link Voltage, Heat Sink Temperature and Control Card Temperature. To view the communication status of the fan VFDs, use the Carrier Controller (Main Menu Maintenance Menu  Fan Drive Addressing).
VFD CONFIGURATION TABLES The configuration parameters for the VFDs are stored in the
control system and are automatically sent to the drives when addressed. The parameters should not need to be changed, but are included as a reference for verification and troubleshooting. See Tables 54-165 for compressor and fan VFD parameters.
VLT Drive Maintenance. This menu shows current
Maintenance Menu Fan
Maintenance
93
Page 94
Table 54 — VFD Parameters, Standard Tier, for 208/230 V/60 Hz Units, 30XV140-200
PARAMETER
NUMBER
0-40 hand on button
1-03 torque profile
1-20 motor kW
1-22 motor volts
1-23 motor frequency
1-24 motor amperage
1-25 motor rpm
1-71 compressor start delay
1-78 starting frequency
1-79 Comp start max time to trip
1-80 function at stop
1-90 motor thermal protection
3-02 min ref
3-03 max reference
3-13 type reference
3-15 src ref#1
3-16 src ref#2
3-41 ramp up
3-42 ramp down
3-82 starting ramp time
4-10 motor speed direct
4-12 motor speed low limit
4-14 motor speed high limit
4-16 torque limit
4-18 current limit
4-19 max output frequency
5-12 DI #27
5-19 DI#37 safe stop
5-40[36] relay 1
5-40[5] relay 2
8-01 control site
8-02 control source
8-03 time out time
8-04 time out function
14-01 switching frequency
14-03 overmodulation
14-10 main failure
14-11 Mains voltage at Mains fault
14-50 RFI Filter
14-60 function at overtemp
14-61 inverter overload
PARAMETER
DESCRIPTION
SETTING
DESCRIPTION
disabled 00000000
Compressor Torque 00000000
size dependent 97 97 97 97 97 97 97 97
motor dependent 200 200 200 200 200 200 200 200
motor dependent 105 105 105 105 105 105 105 105
size dependent 323 323 387 387 451 451 460 460
size dependent 6240 6240 6240 6240 6240 6240 6240 6240
0s 00000000
26hz 26 26 26 26 26 26 26 26
5s 55555555
coast 00000000
[0] no protection 00000000
0 00000000
size dependent 75 75 85 85 95 95 105 105
remote 11111111
no function 00000000
no function 00000000
100s 100 100 100 100 100 100 100 100
100s 100 100 100 100 100 100 100 100
3s 33333333
clockwise 00000000
26Hz 26 26 26 26 26 26 26 26
95Hz 75 75 85 85 95 95 105 105
size dependent 150 150 150 150 150 150 150 150
size dependent 110 110 110 110 110 110 110 110
size dependent 76 76 86 86 96 96 106 106
Coast Inverse 22222222
safe stop alarm 11111111
control word bit 11 36 36 36 36 36 36 36 36
running 55555555
digital & control word
FC port=RS485 11111111
10s 10 10 10 10 10 10 10 10
stop and trip 55555555
3kHz 44444444
yes 11111111
alarm 66666666
345V 180V 180V 180V 180V 180V 180V 180V 180V
on 11111111
derate 11111111
derate 11111111
30XV140 30XV160 30XV180 30XV200
COMPRESSOR COMPRESSOR COMPRESSOR COMPRESSOR
ABABABAB
00000000
94
Page 95
Table 55 — VFD Parameters, Standard Tier, for 380 V/60 Hz Units, 30XV140-225
PARAMETER
NUMBER
0-40 hand on button
1-03 torque profile
1-20 motor kW
1-22 motor volts
1-23 motor frequency
1-24 motor amperage
1-25 motor rpm
1-71 compressor start delay
1-78 starting frequency
1-79 Comp start max time to trip
1-80 function at stop
1-90 motor thermal protection
3-02 min ref
3-03 max reference
3-13 type reference
3-15 src ref#1
3-16 src ref#2
3-41 ramp up
3-42 ramp down
3-82 starting ramp time
4-10 motor speed direct
4-12 motor speed low limit
4-14 motor speed high limit
4-16 torque limit
4-18 current limit
4-19 max output frequency
5-12 DI #27
5-19 DI#37 safe stop
5-40[36] relay 1
5-40[5] relay 2
8-01 control site
8-02 control source
8-03 time out time
8-04 time out function
14-01 switching frequency
14-03 overmodulation
14-10 main failure
14-11 Mains voltage at Mains fault
14-50 RFI Filter
14-60 function at overtemp
14-61 inverter overload
PARAMETER
DESCRIPTION
SETTING
DESCRIPTION
disabled 0000000000
Compressor Torque 0000000000
size dependent 97 97 97 97 97 97 97 97 160 97
motor dependent 380 380 380 380 380 380 380 380 380 380
motor dependent 105 105 105 105 105 105 105 105 98 105
size dependent 177 177 211 211 246 246 252 252 354 226
size dependent 6240 6240 6240 6240 6240 6240 6240 6240 5830 6240
0s 0000000000
26hz 26 26 26 26 26 26 26 26 26 26
5s 5555555555
coast 0000000000
0 0000000000
0 0000000000
size dependent 75 75 85 85 95 95 105 105 83 93
remote 1111111111
no function 0000000000
no function 0000000000
100s 100 100 100 100 100 100 100 100 100 100
100s 100 100 100 100 100 100 100 100 100 100
3s 3333333333
clockwise 0000000000
26Hz 26 26 26 26 26 26 26 26 26 26
95Hz 75 75 85 85 95 95 105 105 83 93
size dependent 150 150 150 150 150 150 150 150 150 150
size dependent 110 110 110 110 110 110 110 110 110 110
size dependent 76 76 86 86 96 96 106 106 84 94
Coast Inverse 2222222222
safe stop alarm 1111111111
control word bit 11 36 36 36 36 36 36 36 36 36 36
running 5555555555
digital & control word
FC port=RS485 1111111111
10s 10 10 10 10 10 10 10 10 10 10
stop and trip 5555555555
3kHz 4444444444
yes 1111111111
alarm 6666666666
345V 300 300 300 300 300 300 300 300 300 300
on 1111111111
derate 1111111111
derate 1111111111
30XV140 30XV160 30XV180 30XV200 30XV225
COMPRESSOR COMPRESSOR COMPRESSOR COMPRESSOR COMPRESSOR
ABABABABAB
0000000000
95
Page 96
Table 56 — VFD Parameters, Standard Tier, for 380 V/60 Hz Units, 30XV250-325
PARAMETER
NUMBER
0-40 hand on button
1-03 torque profile
1-20 motor kW
1-22 motor volts
1-23 motor frequency
1-24 motor amperage
1-25 motor rpm
1-71 compressor start delay
1-78 starting frequency
1-79 Comp start max time to trip
1-80 function at stop
1-90 motor thermal protection
3-02 min ref
3-03 max reference
3-13 type reference
3-15 src ref#1
3-16 src ref#2
3-41 ramp up
3-42 ramp down
3-82 starting ramp time
4-10 motor speed direct
4-12 motor speed low limit
4-14 motor speed high limit
4-16 torque limit
4-18 current limit
4-19 max output frequency
5-12 DI #27
5-19 DI#37 safe stop
5-40[36] relay 1
5-40[5] relay 2
8-01 control site
8-02 control source
8-03 time out time
8-04 time out function
14-01 switching frequency
14-03 overmodulation
14-10 main failure
14-11 Mains voltage at Mains fault
14-50 RFI Filter
14-60 function at overtemp
14-61 inverter overload
PARAMETER
DESCRIPTION
SETTING
DESCRIPTION
disabled 00000000
Compressor Torque 00000000
size dependent 160 160 160 160 160 160 160 160
motor dependent 380 380 380 380 380 380 380 380
motor dependent 98 98 98 98 98 98 98 98
size dependent 333 333 360 360 365 365 399 399
size dependent 5830 5830 5830 5830 5830 5830 5830 5830
0s 00000000
26hz 26 26 26 26 26 26 26 26
5s 55555555
coast 00000000
0 00000000
0 00000000
size dependent 80 80 85 85 90 90 98 98
remote 11111111
no function 00000000
no function 00000000
100s 100 100 100 100 100 100 100 100
100s 100 100 100 100 100 100 100 100
3s 33333333
clockwise 00000000
26Hz 26 26 26 26 26 26 26 26
95Hz 80 80 85 85 90 90 98 98
size dependent 150 150 150 150 150 150 150 150
size dependent 110 110 110 110 110 110 110 110
size dependent 81 81 86 86 91 91 99 99
Coast Inverse 22222222
safe stop alarm 11111111
control word bit 11 36 36 36 36 36 36 36 36
running 55555555
digital & control word
FC port=RS485 11111111
10s 10 10 10 10 10 10 10 10
stop and trip 55555555
3kHz 44444444
yes 11111111
alarm 66666666
345V 300 300 300 300 300 300 300 300
on 11111111
derate 11111111
derate 11111111
30XV250 30XV275 30XV300 30XV325
COMPRESSOR COMPRESSOR COMPRESSOR COMPRESSOR
ABABABAB
00000000
96
Page 97
Table 57 — VFD Parameters, Standard Tier, for 380 V/60 Hz Units, 30XV350-500
PARAMETER
NUMBER
0-40 hand on button
1-03 torque profile
1-20 motor kW
1-22 motor volts
1-23 motor frequency
1-24 motor amperage
1-25 motor rpm
1-71 compressor start delay
1-78 starting frequency
1-79 Comp start max time to trip
1-80 function at stop
1-90 motor thermal protection
3-02 min ref
3-03 max reference
3-13 type reference
3-15 src ref#1
3-16 src ref#2
3-41 ramp up
3-42 ramp down
3-82 starting ramp time
4-10 motor speed direct
4-12 motor speed low limit
4-14 motor speed high limit
4-16 torque limit
4-18 current limit
4-19 max output frequency
5-12 DI #27
5-19 DI#37 safe stop
5-40[36] relay 1
5-40[5] relay 2
8-01 control site
8-02 control source
8-03 time out time
8-04 time out function
14-01 switching frequency
14-03 overmodulation
14-10 main failure
14-11 Mains voltage at Mains fault
14-50 RFI Filter
14-60 function at overtemp
14-61 inverter overload
PARAMETER
DESCRIPTION
SETTING
DESCRIPTION
disabled 00000000
Compressor Torque 00000000
size dependent 242 160 242 242 242 242 242 242
motor dependent 380 380 380 380 380 380 380 380
motor dependent 95 98 95 95 95 95 95 95
size dependent 548 397 516 516 599 599 629 629
size dependent 5650 5830 5650 5650 5650 5650 5650 5650
0s 00000000
26hz 26 26 26 26 26 26 26 26
5s 55555555
coast 00000000
0 00000000
0 00000000
size dependent 75 90 75 75 84 84 94 94
remote 11111111
no function 00000000
no function 00000000
100s 100 100 100 100 100 100 100 100
100s 100 100 100 100 100 100 100 100
3s 33333333
clockwise 00000000
26Hz 26 26 26 26 26 26 26 26
95Hz 75 90 75 75 84 84 94 94
size dependent 150 150 150 150 150 150 150 150
size dependent 110 110 110 110 110 110 110 110
size dependent 76 91 76 76 85 85 95 95
Coast Inverse 22222222
safe stop alarm 11111111
control word bit 11 36 36 36 36 36 36 36 36
running 55555555
digital & control word
FC port=RS485 11111111
10s 10 10 10 10 10 10 10 10
stop and trip 55555555
3kHz 44444444
yes 11111111
alarm 66666666
345V 300 300 300 300 300 300 300 300
on 11111111
derate 11111111
derate 11111111
30XV350 30XV400 30XV450 30XV500
COMPRESSOR COMPRESSOR COMPRESSOR COMPRESSOR
ABABABAB
00000000
97
Page 98
Table 58 — VFD Parameters, Standard Tier, for 400 V/60 Hz Units, 30XV140-225
PARAMETER
NUMBER
0-40 hand on button
1-03 torque profile
1-20 motor kW
1-22 motor volts
1-23 motor frequency
1-24 motor amperage
1-25 motor rpm
1-71 compressor start delay
1-78 starting frequency
1-79 Comp start max time to trip
1-80 function at stop
1-90 motor thermal protection
3-02 min ref
3-03 max reference
3-13 type reference
3-15 src ref#1
3-16 src ref#2
3-41 ramp up
3-42 ramp down
3-82 starting ramp time
4-10 motor speed direct
4-12 motor speed low limit
4-14 motor speed high limit
4-16 torque limit
4-18 current limit
4-19 max output frequency
5-12 DI #27
5-19 DI#37 safe stop
5-40[36] relay 1
5-40[5] relay 2
8-01 control site
8-02 control source
8-03 time out time
8-04 time out function
14-01 switching frequency
14-03 overmodulation
14-10 main failure
14-11 Mains voltage at Mains fault
14-50 RFI Filter
14-60 function at overtemp
14-61 inverter overload
PARAMETER
DESCRIPTION
NOTE: Compressor motor voltage is 380V.
SETTING
DESCRIPTION
disabled 0000000000
Compressor Torque 0000000000
size dependent 97 97 97 97 97 97 97 97 160 97
motor dependent 380 380 380 380 380 380 380 380 380 380
motor dependent 105 105 105 105 105 105 105 105 98 105
size dependent 177 177 211 211 246 246 252 252 354 226
size dependent 6240 6240 6240 6240 6240 6240 6240 6240 5830 6240
0s 0000000000
26hz 26 26 26 26 26 26 26 26 26 26
5s 5555555555
coast 0000000000
0 0000000000
0 0000000000
size dependent 75 75 85 85 95 95 105 105 83 93
remote 1111111111
no function 0000000000
no function 0000000000
100s 100 100 100 100 100 100 100 100 100 100
100s 100 100 100 100 100 100 100 100 100 100
3s 3333333333
clockwise 0000000000
26Hz 26 26 26 26 26 26 26 26 26 26
95Hz 75 75 85 85 95 95 105 105 83 93
size dependent 150 150 150 150 150 150 150 150 150 150
size dependent 110 110 110 110 110 110 110 110 110 110
size dependent 76 76 86 86 96 96 106 106 84 94
Coast Inverse 2222222222
safe stop alarm 1111111111
control word bit 11 36 36 36 36 36 36 36 36 36 36
running 5555555555
digital & control word
FC port=RS485 1111111111
10s 10 10 10 10 10 10 10 10 10 10
stop and trip 5555555555
3kHz 4444444444
yes 1111111111
alarm 6666666666
345V 320 320 320 320 320 320 320 320 320 320
on 1111111111
derate 1111111111
derate 1111111111
30XV140 30XV160 30XV180 30XV200 30XV225
COMPRESSOR COMPRESSOR COMPRESSOR COMPRESSOR COMPRESSOR
ABABABABAB
0000000000
98
Page 99
Table 59 — VFD Parameters, Standard Tier, for 400 V/60 Hz Units, 30XV250-325
PARAMETER
NUMBER
0-40 hand on button
1-03 torque profile
1-20 motor kW
1-22 motor volts
1-23 motor frequency
1-24 motor amperage
1-25 motor rpm
1-71 compressor start delay
1-78 starting frequency
1-79 Comp start max time to trip
1-80 function at stop
1-90 motor thermal protection
3-02 min ref
3-03 max reference
3-13 type reference
3-15 src ref#1
3-16 src ref#2
3-41 ramp up
3-42 ramp down
3-82 starting ramp time
4-10 motor speed direct
4-12 motor speed low limit
4-14 motor speed high limit
4-16 torque limit
4-18 current limit
4-19 max output frequency
5-12 DI #27
5-19 DI#37 safe stop
5-40[36] relay 1
5-40[5] relay 2
8-01 control site
8-02 control source
8-03 time out time
8-04 time out function
14-01 switching frequency
14-03 overmodulation
14-10 main failure
14-11 Mains voltage at Mains fault
14-50 RFI Filter
14-60 function at overtemp
14-61 inverter overload
PARAMETER
DESCRIPTION
NOTE: Compressor motor voltage is 380V.
SETTING
DESCRIPTION
disabled 00000000
Compressor Torque 00000000
size dependent 160 160 160 160 160 160 160 160
motor dependent 380 380 380 380 380 380 380 380
motor dependent 98 98 98 98 98 98 98 98
size dependent 333 333 360 360 365 365 399 399
size dependent 5830 5830 5830 5830 5830 5830 5830 5830
0s 00000000
26hz 26 26 26 26 26 26 26 26
5s 55555555
coast 00000000
0 00000000
0 00000000
size dependent 80 80 85 85 90 90 98 98
remote 11111111
no function 00000000
no function 00000000
100s 100 100 100 100 100 100 100 100
100s 100 100 100 100 100 100 100 100
3s 33333333
clockwise 00000000
26Hz 26 26 26 26 26 26 26 26
95Hz 80 80 85 85 90 90 98 98
size dependent 150 150 150 150 150 150 150 150
size dependent 110 110 110 110 110 110 110 110
size dependent 81 81 86 86 91 91 99 99
Coast Inverse 22222222
safe stop alarm 11111111
control word bit 11 36 36 36 36 36 36 36 36
running 55555555
digital & control word
FC port=RS485 11111111
10s 10 10 10 10 10 10 10 10
stop and trip 55555555
3kHz 44444444
yes 11111111
alarm 66666666
345V 320 320 320 320 320 320 320 320
on 11111111
derate 11111111
derate 11111111
30XV250 30XV275 30XV300 30XV325
COMPRESSOR COMPRESSOR COMPRESSOR COMPRESSOR
ABABABAB
00000000
99
Page 100
Table 60 — VFD Parameters, Standard Tier, for 400 V/60 Hz Units, 30XV350-500
PARAMETER
NUMBER
0-40 hand on button
1-03 torque profile
1-20 motor kW
1-22 motor volts
1-23 motor frequency
1-24 motor amperage
1-25 motor rpm
1-71 compressor start delay
1-78 starting frequency
1-79 Comp start max time to trip
1-80 function at stop
1-90 motor thermal protection
3-02 min ref
3-03 max reference
3-13 type reference
3-15 src ref#1
3-16 src ref#2
3-41 ramp up
3-42 ramp down
3-82 starting ramp time
4-10 motor speed direct
4-12 motor speed low limit
4-14 motor speed high limit
4-16 torque limit
4-18 current limit
4-19 max output frequency
5-12 DI #27
5-19 DI#37 safe stop
5-40[36] relay 1
5-40[5] relay 2
8-01 control site
8-02 control source
8-03 time out time
8-04 time out function
14-01 switching frequency
14-03 overmodulation
14-10 main failure
14-11 Mains voltage at Mains fault
14-50 RFI Filter
14-60 function at overtemp
14-61 inverter overload
PARAMETER
DESCRIPTION
NOTE: Compressor motor voltage is 380V.
SETTING
DESCRIPTION
disabled 00000000
Compressor Torque 00000000
size dependent 242 160 242 242 242 242 242 242
motor dependent 380 380 380 380 380 380 380 380
motor dependent 95 98 95 95 95 95 95 95
size dependent 548 397 516 516 599 599 629 629
size dependent 5650 5830 5650 5650 5650 5650 5650 5650
0s 00000000
26hz 26 26 26 26 26 26 26 26
5s 55555555
coast 00000000
0 00000000
0 00000000
size dependent 75 90 75 75 84 84 94 94
remote 11111111
no function 00000000
no function 00000000
100s 100 100 100 100 100 100 100 100
100s 100 100 100 100 100 100 100 100
3s 33333333
clockwise 00000000
26Hz 26 26 26 26 26 26 26 26
95Hz 75 90 75 75 84 84 94 94
size dependent 150 150 150 150 150 150 150 150
size dependent 110 110 110 110 110 110 110 110
size dependent 76 91 76 76 85 85 95 95
Coast Inverse 22222222
safe stop alarm 11111111
control word bit 11 36 36 36 36 36 36 36 36
running 55555555
digital & control word
FC port=RS485 11111111
10s 10 10 10 10 10 10 10 10
stop and trip 55555555
3kHz 44444444
yes 11111111
alarm 66666666
345V 320 320 320 320 320 320 320 320
on 11111111
derate 11111111
derate 11111111
30XV350 30XV400 30XV450 30XV500
COMPRESSOR COMPRESSOR COMPRESSOR COMPRESSOR
ABABABAB
00000000
100
Loading...