Carrier 30XV user guide manual

Variable Speed Air-Cooled Liquid Chillers
with Greenspeed
Installation Instructions
AquaForce
30XV140-500
®
Intelligence
®

CONTENTS

Page
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . .1,2
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-107
Step 1 — Inspect Shipment . . . . . . . . . . . . . . . . . . . . . . 3
Step 2 — Place, Mount and Rig the Unit . . . . . . . . . 3
•PLACING UNIT
• MOUNTING UNIT
• EXPORT SHIPPING RAILS
• RIGGING UNIT
Step 3 — Make Refrigerant, Evaporator Fluid
and Drain Piping Connections . . . . . . . . . . . . . . . . 83
• GENERAL
• EVAPORATOR PUMP CONTROL
• PREPARATION FOR YEAR-ROUND OPERATION
Step 4 — Fill the Chilled Water Loop . . . . . . . . . . . . 90
• WATER SYSTEM CLEANING
• WATER TREATMENT
• SYSTEM PRESSURIZATION
• FILLING THE SYSTEM
• SET WATER FLOW RATE
• FREEZE PROTECTION
• PREPARATION FOR WINTER SHUTDOWN
Step 5 — Make Electrical Connections . . . . . . . . . . 92
• POWER SUPPLY
• FIELD POWER CONNECTIONS
•POWER WIRING
• FIELD CONTROL POWER CONNECTIONS
• CARRIER COMFORT NETWORK COMMUNICATION BUS WIRING
• NON-CCN COMMUNICATION WIRING
• FIELD CONTROL OPTION WIRING
• DUAL CHILLER LEAVING WATER SENSOR
Step 6 — Install Accessories . . . . . . . . . . . . . . . . . . . 107
• ENERGY MANAGEMENT MODULE
• UNIT SECURITY/PROTECTION ACCESSORIES
• COMMUNICATION ACCESSORIES
• SERVICE OPTIONS
Step 7 — Leak Test Unit. . . . . . . . . . . . . . . . . . . . . . . . 107
• DEHYDRATION
• REFRIGERANT CHARGE
®
WARNING
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation and ser­vice. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.
WARNING
Electrical shock can cause personal injury and death. After unit power is disconnected, wait at least 20 minutes for the VFD (variable frequency drive) capacitors to discharge before opening drive.
WARNING
DO NOT VENT refrigerant relief valves within a building. Outlet from relief valves must be vented in accordance with the latest edition of ANSI/ASHRAE (American National Standards Institute/American Society of Heating, Refrigerating and Air-Conditioning Engineers) 15 (Safety Code for Mechanical Refrigeration). The accumulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation. Provide adequate ventilation in enclosed or low overhead areas. Inhalation of high concen­trations of vapor is harmful and may cause heart irregulari­ties, unconsciousness or death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen avail­able for breathing. Product causes eye and skin irritation. Decomposition products are hazardous.

SAFETY CONSIDERATIONS

Installing, starting up, and servicing this equipment can
be hazardous due to system pressures, electrical compo­nents, and equipment location (roof, elevated structures, etc.). Only trained, qualified installers and service techni­cians should install, start up, and service this equipment. When working on this equipment, observe precautions in the literature, on tags, stickers, and labels attached to the equipment, and any other safety precautions that apply. Fol­low all safety codes. Wear safety glasses and work gloves. Use care in handling, rigging, and setting this equipment, and in handling all electrical components.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300195-01 Printed in U.S.A. Form 30XV-6SI Pg 1 8-17 Replaces: 30XV-1SI
WARNING
CAUTION
DO NOT USE TORCH to remove any component. System contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and gog­gles and proceed as follows:
a. Shut off electrical power to unit. b. Recover refrigerant to relieve all pressure from sys-
tem using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen and
the work area should be well ventilated. Refrigerant in contact with an open flame produces toxic gases.
d. Cut component connection tubing with tubing cutter
and remove component from unit. Use a pan to catch any oil that may come out of the lines and as a gage for how much oil to add to the system.
e. Carefully unsweat remaining tubing stubs when nec-
essary. Oil can ignite when exposed to torch flame.
Failure to follow these procedures may result in personal injury or death.
CAUTION
Standard Tier units (units with S in the 10th position of the model number) without condenser fan VFDs (units with “-”, “1”, “3”, or “5” in the 13th position of the model number) must have the condenser fan(s) rotation verified to ensure proper phasing. Correct rotation is counter-clockwise (reference arrow on fan cap). Swap any two incoming power leads to correct condenser fan rotation before starting chiller. Operating the unit with­out testing the condenser fan(s) for proper phasing could result in equipment damage.
CAUTION
DO NOT re-use compressor oil or any oil that has been exposed to the atmosphere. Dispose of oil per local codes and regulations. DO NOT leave refrigerant system open to air any longer than the actual time required to service the equipment. Seal circuits being serviced and charge with dry nitrogen to prevent oil contamination when timely repairs cannot be completed. Failure to follow these proce­dures may result in damage to equipment.
This unit uses a microprocessor control system. Do not short or jumper between terminations on circuit boards or modules; control or board failure may result.
Be aware of electrostatic discharge (static electricity) when handling or making contact with circuit boards or module connections. Always touch a chassis (grounded) part to dis­sipate body electrostatic charge before working inside con­trol center.
Use extreme care when handling tools near boards and when connecting or disconnecting terminal plugs. Circuit boards can easily be damaged. Always hold boards by the edges and avoid touching components and connections.
This equipment uses, and can radiate, radio frequency energy. If not installed and used in accordance with the instruction manual, it may cause interference to radio com­munications. It has been tested and found to comply with the limits for a Class A computing device pursuant to Inter­national Standard in North America EN 61000-2/3 which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user, at his own expense, will be required to take whatever measures may be required to correct the interference.
Always store and transport replacement or defective boards in anti-static shipping bag.
CAUTION
To prevent potential damage to heat exchanger tubes, always run fluid through heat exchanger when adding or removing refrigerant charge. Use appropriate antifreeze solutions in evaporator fluid loop to prevent the freezing of heat exchanger or interconnecting piping when the equip­ment is exposed to temperatures below 32 F (0° C). Proof of flow switch is factory installed on all models. Do NOT remove power from this chiller during winter shut down periods without taking precaution to remove all water from heat exchanger. Failure to properly protect the system from freezing may constitute abuse and may void warranty.
IMPORTANT: If the compressor VFD enclosure is removed for service, it must be reinstalled to protect the drive from water intrusion. Failure to reinstall the compressor VFD enclosure may constitute abuse and may void warranty.
2

INTRODUCTION

These instructions cover installation of 30XV140-500 air-
cooled liquid chillers with Greenspeed tronic controls, and units with factory-installed options (FIOPs). See Fig. 1.
®
intelligence and elec-

INSTALLATION

Storage —
fore installation or start-up, be sure to protect the machine from construction dirt. Keep protective shipping covers in place until the machine is ready for installation.
If the unit is to be stored for a period of time be-
Step 1 — Inspect Shipment — Inspect unit for dam-
age upon arrival. If damage is found, immediately file a claim with the shipping company, and contact your local Carrier representative.
Step 2 — Place, Mount, and Rig the Unit —
When considering a location for the unit, be sure to consult NEC (National Electrical Code, U.S.A.) and/or local code requirements. Allow sufficient space for airflow, wiring, pip­ing, and service. See Fig. 2-20.
NOTE: To facilitate refrigerant vent piping, all units have fus­ible plugs with flares and pressure reliefs with 3/4 in. NPT and 3/8 in. SAE flare fittings (if required by local codes).
PLACING UNIT — Locate the unit so that the condenser airflow is unrestricted both above and on the sides of the unit. Airflow and service clearances are 6 ft (1.8 m) around the unit. Acceptable clearance on the sides or ends without control boxes or VFDs can be reduced to 3 ft (1 m) without sacrificing performance as long as the remaining three sides
1
/4 in. SAE (Society of Automotive Engineers)
are unrestricted. Acceptable clearance on the side with a control box or VFD can be reduced to 4 ft (1.3 m) due to NEC regulations, without sacrificing performance as long as the remaining three sides are unrestricted. Provide ample room for servicing and removing the evaporator. See Fig. 2­20 for required clearances. Local codes for clearances take precedence over the manufacturer’s recommendations when local codes call for greater clearances.
If multiple units are installed at the same site, a minimum separation of 10 ft (3 m) between the sides of the machines is required to maintain proper airflow and minimize the chances of condenser air recirculation.
MOUNTING UNIT — The unit may be mounted on a level pad directly on the base rails, on a raised mounting rail around the unit, or on vibration isolation springs. For all units, ensure placement area is strong enough to support unit operating weight. See Table 1. Mounting holes are pro­vided for securing the unit to the pad, mounting rail or vi­bration isolation springs. Bolt the unit securely to pad or rails. If vibration isolators (field-supplied) are required for a particular installation, refer to unit weight distribution in Fig. 21 to aid in the proper selection of isolators. Once in­stalled, the unit must be level to within
1
/8-in. per ft (1 cm per meter) along the long axis of the oil separator. This is re­quired for oil return to the compressor(s). For more details about physical data, see Tables 2 and 3.
NOTE: For units that are point loaded, such as those using rub­ber and shear isolators, the base rail must be supported with a 24 x 4 in. (610 x 102 mm) plate at each mounting location, or base rail deflection may result. Fasten the unit to the plates using the mounting holes.
3
LEGEND
*BACnet is a registered trademark of ASHRAE (American Society of Heating, Refrigerating, and Air-Conditioning Engineers).
CFSP — Coil Face Shipping Protection EMM Energy Management Module GFI Ground Fault Interrupter LON Local Operating Network SCCR — Short Circuit Current Rating
Fig. 1 — AquaForce® Chiller with GreenSpeed® Intelligence Model Number Designation
30XV – AquaForce® Air-Cooled Chiller
Design Series
Nominal Capacity
140 225 325 500 160 250 350 180 275 400 200 300 450
Voltage 1 – 575-3-60 2 – 380-3-60
5 – 208/230-3-60
6 – 460-3-60
Product Tiers & Evaporator Configuration
S – Standard Tier / Flooded Evaporator
M – Mid Tier / Flooded Evaporator H – High Tier / Flooded Evaporator
- – Flooded Evaporator, 2 pass, without Heater 0 – Flooded Evaporator, 2 pass, with Heater 1 – Flooded Evaporator with Heater, Minus One Pass
2 – Flooded Evaporator with Heater for Brine Application
Evaporator Options
-
Packaging Options L – Coil Face Shipping Protection (CFSP) 0 – CFSP, Coil Trim Panels 1 – CFSP, Coil Trim Panels, Security Grilles 2 – CFSP, Coil Trim Panels, Security Grilles, Hail Guards (End)
3 – Full Hail Guard
9 – CFSP, Coil Trim Panels, Skid + Bag B – CFSP, Coil Trim Panels, Security Grilles, Skid + Bag C – CFSP, Coil Trim Panels, S
ecurity Grilles, Hail Guards (End), Skid + Bag
D – Full Hail Guard, Skid, Bag
Controls Options
- – 7-in. Touch Pilot™ Display 0 – 7-in. Touch Pilot Display, EMM, GFI 1 – 7-in. Touch Pilot Display, BACnet* (MS/TP) Translator 2 – 7-in. Touch Pilot Display, EMM, GFI, BACnet (MS/TP) Translator
3 – 7-in. Touch Pilot Display, LON Translator
4 – 7-in. Touch Pilot Display, EMM, GFI, LON Translator
Electrical Options
- – Single Point Power, No Control Transformer, Std SCCR 0 – Single Point Power with Dis
connect, No Control Transformer, Std SCCR
1 – Dual Point Power, No Control Transformer, Std SCCR 2 – Dual Point Power with Disconnect, No Control Transformer, Std SCCR
3 – Single Point Power, Control Transformer, Std SCCR
4 – Single Point Power with Disconnect, Control Transformer, Std SCCR 5 – Dual Point Power, Control Transformer, Std SCCR 6 – Dual Point Power with Disconnect, Control Transformer, Std SCCR 8 – Single Point Power with Disconnect, No Control Transformer, High SCCR B – D
ual Point Power with Disconnect, No Control Transformer, High SCCR
D – Single Point Power with Disconnect, Control Transformer, High SCCR G – Dual Point Power with Disconnect, Control Transformer, High SCCR
Valve & Insulation Options
- – No Suction Service Valve, Actuated Discharge Valves,
No Suction Line Insulation 0 Suction Service Valve, Actuated Discharge Valves, No Suction Line Insulation 1 – No Suction Service Valve, Manual Discharge Valves (Middle East only), No Suction Line Insulation 2 Suction Service Valve, Manual Discharge Va
lves (Middle East only), No Suction Line Insulation 5 – No Suction Service Valve, Actuated Discharge Valves, Suction Line Insulation 6 – Suction Service Valve, Actuated Discharge Valves, Suction Line Insulation 7 – No Suction Service Valve, Manual Discharge Valves (Middle East only), Suction Line Insulation 8 – Suction Service Valve, Ma
nual Discharge Valves
(Middle East only), Suction Line Insulation
XV
140
Condenser Options
- – Aluminum Fin/Copper Tube 0 – Copper Fin/Copper Tube 1 – Aluminum Pre-Coat Fin/Copper Tube 2 – Aluminum E-Coat Fin/Copper Tube
3 – Copper E-Coat Fin/Copper Tube
4 – Microchannel 5 – E-Coat Microchannel
Condenser Fans & Sound Options
6 3H
- – Fixed Speed Condenser Fans (Std Tier) / Variable Speed Fans (Mid and High-Tier),
Std Sound
0 – Variable Speed Condenser Fans (Std Tier only), Std Sound 1 – Fixed Speed Condenser Fans (Std Tier) / Variable Speed Fans (Mid and High-Tier),
Low Sound Kit
2 – Variable Speed Condenser Fans (Std Tier only), Low
Sound Kit
3 – Fixed Speed Condenser Fans (Std Tier) / Variable Speed Fans (Mid and High-Tier), Std Sound, Sound Optimization
4 – Variable Speed Condenser Fans (Std Tier only), Std Sound, Sound Optimization 5 – Fixed Speed Condenser Fans (Std Tier) / Variable Speed Fans (Mid and High-Tier),
Low Sound Kit, Sou
nd Optimization
6 – Variable Speed Condenser Fans (Std Tier only), Low Sound Kit, Sound Optimization
4
Fig. 2 — 30XV 140,160,180 Std Tier; 140 Mid Tier Air-Cooled Chiller
5
Fig. 2 — 30XV 140,160,180 Std Tier; 140 Mid Tier Air-Cooled Chiller (cont)
6
Fig. 2 — 30XV 140,160,180 Std Tier; 140 Mid Tier Air-Cooled Chiller (cont)
7
Fig. 3 — 30XV 140 High Tier; 160,180 Mid Tier; 200 Std Tier Air-Cooled Chiller
8
Fig. 3 — 30XV 140 High Tier; 160,180 Mid Tier; 200 Std Tier Air-Cooled Chiller (cont)
9
10
Fig. 3 — 30XV 140 High Tier; 160,180 Mid Tier; 200 Std Tier Air-Cooled Chiller (cont)
11
Fig. 4 — 30XV 160,180 High Tier; 200 Mid Tier Air-Cooled Chiller
12
Fig. 4 — 30XV 160,180 High Tier; 200 Mid Tier Air-Cooled Chiller (cont)
13
Fig. 4 — 30XV 160,180 High Tier; 200 Mid Tier Air-Cooled Chiller (cont)
14
Fig. 5 — 30XV 200 High Tier Air-Cooled Chiller
15
Fig. 5 — 30XV 200 High Tier Air-Cooled Chiller (cont)
16
Fig. 5 — 30XV 200 High Tier Air-Cooled Chiller (cont)
17
Fig. 6 — 30XV 225 Std Tier Air-Cooled Chiller
18
Fig. 6 — 30XV 225 Std Tier Air-Cooled Chiller (cont)
19
Fig. 6 — 30XV 225 Std Tier Air-Cooled Chiller (cont)
20
Fig. 7 — 30XV 225 Mid Tier Air-Cooled Chiller
21
Fig. 7 — 30XV 225 Mid Tier Air-Cooled Chiller (cont)
22
Fig. 7 — 30XV 225 Mid Tier Air-Cooled Chiller (cont)
23
Fig. 8 — 30XV 225 High Tier Air-Cooled Chiller
24
Fig. 8 — 30XV 225 High Tier Air-Cooled Chiller (cont)
25
Fig. 8 — 30XV 225 High Tier Air-Cooled Chiller (cont)
26
Fig. 9 — 30XV 250,275 Std Tier Air-Cooled Chiller
27
Fig. 9 — 30XV 250,275 Std Tier Air-Cooled Chiller (cont)
28
Fig. 9 — 30XV 250,275 Std Tier Air-Cooled Chiller (cont)
29
Fig. 10 — 30XV 250,275 Mid Tier; 300 Std Tier Air-Cooled Chiller
30
Fig. 10 — 30XV 250,275 Mid Tier; 300 Std Tier Air-Cooled Chiller (cont)31Fig. 10 — 30XV 250,275 Mid Tier; 300 Std Tier Air-Cooled Chiller (cont)
Loading...
+ 78 hidden pages