Carrier 1-808-427-01 User Manual

RRTTUU OOppeenn
IInnssttaallllaattiioonn aanndd SSttaarrtt--uupp GGuuiiddee
CARRIER CORPORATION ©2010 A member of the United Technologies Corporation family · Stock symbol UTX · Catalog No. 11-808-427-01 · 11/19/2010
Table of Contents
Introduction .................................................................................................................................................................. 1
What is the RTU Open controller? ...................................................................................................................... 1
Specifications ........................................................................................................................................................ 3
Safety considerations........................................................................................................................................... 4
Installation ................................................................................................................................................................... 5
Field-supplied hardware ...................................................................................................................................... 5
To mount the RTU Open ....................................................................................................................................... 6
To wire the controller for power.......................................................................................................................... 7
Using the rooftop equipment control power transformer ................................................................... 7
Using an auxiliary control power transformer ...................................................................................... 8
To set the RTU Open's address ........................................................................................................................... 9
To set the RTU Open's communications protocol and baud rate ............................................................... 10
Wiring the RTU Open to the MS/TP network ................................................................................................. 10
Wiring specifications ........................................................................................................................... 11
To wire the controller to the network ................................................................................................. 11
Wiring inputs and outputs ................................................................................................................................ 12
Input wiring specifications .................................................................................................................. 13
Inputs ................................................................................................................................................... 13
Binary outputs ..................................................................................................................................... 14
Analog output ...................................................................................................................................... 14
To wire inputs and outputs ................................................................................................................. 14
Wiring sensors to inputs ................................................................................................................................... 18
Field-supplied sensor hardware ......................................................................................................... 19
Wiring an SPT sensor .......................................................................................................................... 20
Rnet wiring specifications ........................................................................................................ 20
To wire the SPT sensor to the controller ................................................................................. 21
Wiring a Supply Air Temperature sensor ............................................................................................ 21
Wiring specifications ................................................................................................................ 22
To wire the SAT sensor to the controller ................................................................................. 22
Wiring a Duct Air Temperature sensor ............................................................................................... 22
Wiring specifications ................................................................................................................ 22
To wire a duct sensor to the controller ................................................................................... 23
Wiring an Outdoor Air Temperature sensor ....................................................................................... 23
Wiring specifications ................................................................................................................ 23
To wire an OAT sensor to the controller .................................................................................. 23
Wiring a CO2 sensor ............................................................................................................................ 24
Wiring specifications ................................................................................................................ 24
To wire the CO2 sensor to the controller ................................................................................ 24
Wiring an Outdoor Air Quality sensor ................................................................................................. 25
Wiring specifications ................................................................................................................ 26
To wire the OAQ sensor to the controller ................................................................................ 26
Wiring a Relative Humidity sensor ..................................................................................................... 26
Wiring specifications ................................................................................................................ 27
To wire the RH sensor to the controller................................................................................... 27
Wiring a Humidistat ............................................................................................................................. 27
Wiring specifications ................................................................................................................ 27
To wire a humidistat to the controller ..................................................................................... 28
Wiring an enthalpy switch ................................................................................................................... 28
Wiring specifications ................................................................................................................ 28
To wire an enthalpy switch (outdoor air) to the controller ..................................................... 29
To wire an enthalpy switch (differential) to the controller...................................................... 30
RTU Open i
Table of Contents
Wiring a status switch ......................................................................................................................... 31
Wiring specifications ................................................................................................................ 31
To wire a status switch to the controller ................................................................................. 32
Wiring a compressor safety ................................................................................................................ 32
Wiring specifications ................................................................................................................ 32
To wire a compressor safety input to the controller ............................................................... 33
Wiring an occupancy switch or door contact ..................................................................................... 33
Wiring specifications ................................................................................................................ 33
To wire an occupancy switch or door contact ......................................................................... 34
Start-up ....................................................................................................................................................................... 35
Service Test ......................................................................................................................................................... 36
Configuring the RTU Open's properties .......................................................................................................... 37
Unit Configuration properties ............................................................................................................. 37
Setpoint properties.............................................................................................................................. 39
Service Configuration properties ........................................................................................................ 40
Sequence of Operation ............................................................................................................................................. 42
Occupancy ........................................................................................................................................................... 42
Supply fan ........................................................................................................................................................... 43
Cooling ................................................................................................................................................................. 43
Economizer ......................................................................................................................................................... 44
Power Exhaust .................................................................................................................................................... 44
Unoccupied Free Cooling .................................................................................................................................. 45
Optimal Start ...................................................................................................................................................... 45
Enthalpy control ................................................................................................................................................. 46
Indoor Air CO2 .................................................................................................................................................... 46
Heating ................................................................................................................................................................ 47
Heat Pump operation ........................................................................................................................................ 48
Dehumidification ............................................................................................................................................... 48
Demand Limit ..................................................................................................................................................... 49
Door switch ......................................................................................................................................................... 49
Remote occupancy ............................................................................................................................................ 49
Fire Shutdown .................................................................................................................................................... 49
Compressor Safety ............................................................................................................................................ 49
Fan Status ........................................................................................................................................................... 50
Filter Status ........................................................................................................................................................ 50
Alarms ................................................................................................................................................................. 50
Linkage ................................................................................................................................................................ 53
Linkage Air Source Modes ................................................................................................................................ 54
Troubleshooting ......................................................................................................................................................... 55
Serial number ..................................................................................................................................................... 55
LED's .................................................................................................................................................................... 55
Replacing the RTU Open's battery .................................................................................................................. 56
Compliance ................................................................................................................................................................ 57
FCC Compliance ................................................................................................................................................. 57
CE Compliance ................................................................................................................................................... 57
BACnet Compliance........................................................................................................................................... 57
Appendix A: RTU Open Points/Properties .............................................................................................................. 58
Status................................................................................................................................................................... 58
Unit Configuration .............................................................................................................................................. 59
Setpoints ............................................................................................................................................................. 61
Alarm Configuration .......................................................................................................................................... 65
Service Configuration ........................................................................................................................................ 66
Maintenance ....................................................................................................................................................... 68
Alarms ................................................................................................................................................................. 70
ii RTU Open
Table of Contents
Linkage ................................................................................................................................................................ 71
I/O Points ............................................................................................................................................................ 71
Appendix B: Single Point Linkage and Device Address Binding ............................................................................ 73
Single Point Linkage ......................................................................................................................................... 73
Device Address Binding .................................................................................................................................... 74
Index ........................................................................................................................................................................... 75
RTU Open iii

Introduction

What is the RTU Open controller?

The RTU Open controller is available as an integrated component of a Carrier rooftop unit, or as a field­installed retrofit product. Its internal application programming provides optimum rooftop performance and energy efficiency. RTU Open enables the unit to run in 100% stand-alone control mode or it can communicate to the Building Automation System (BAS).
On board DIP switches allow you to select the baud rate and choose one of the following protocols:
BACnet
Modbus
Johnson N2
LonWorks
Carrier’s diagnostic display tools such as BACview6 Handheld or Virtual BACview can be used with the RTU Open controller via the
J12 Access Port. See illustration on the following page.
RTU Open 1
Introduction
2 RTU Open
J12
J13
NOTE

Specifications

RTU Open driver drv_rtuopn_std
Power 24 Vac ±10%, 50–60 Hz
20 VA power consumption (26 VA with BACview 26 Vdc (25 V min, 30 V max) Single Class 2 source only, 100 VA or less
attached)
Access port
Rnet port
To connect a BAC
view6 Handheld, Virtual BACview
For SPT sensors and a BAC
, or Field Assistant
6
view
in any of the following combinations, wired
in a daisy-chain configuration:
1 SPT Plus or SPT Pro
1–4 SPT Standards
1–4 SPT Standards, and 1 SPT Plus or SPT Pro
Any of the above combinations, plus a BACview
6,
but no more than 6 devices
total
Comm Option port
For communication with the LonWorks Option Card.
Inputs 12 inputs:
Inputs 1 - 2: 4-20 mA only
Inputs 3, 5, 8, 9: Binary, 24 Vac
Inputs 6 - 7: Thermistor
Inputs 10 - 11: Thermistor
Rnet sensor
Binary outputs 8 relay outputs, contacts rated at 3 A max @ 24 Vac
Configured normally open.
Analog output 1 analog output
AO1: 2 - 10 Vdc or 4-20 mA
Output resolution 10 bit D/A
Real-time clock Battery-backed real-time clock keeps track of time in event of power failure
Battery 10-year Lithium CR2032 battery provides a minimum of 10,000 hours of
data retention during power outages
Protection Incoming power and network connections are protected by non-replaceable
internal solid-state polyswitches that reset themselves when the condition that causes a fault returns to normal. The power, network, and output connections are also protected against voltage transient and surge events.
Status indicators LED's indicate status of communications, running, errors, power, and digital
outputs
Environmental operating range
-40 to 158°F (-40 to 70°C), 10–95% relative humidity, non-condensing Controllers should be mounted in a protective enclosure.
Vibration during operation: all planes/directions, 1.5G @ 20–300 Hz Shock during operation: all planes/directions, 5G peak, 11 ms Shock during storage: all planes/directions, 100G peak, 11 ms
RTU Open 3
Introduction
Overall dimensions A:
B:
Mounting dimensions 7 mounting holes in various positions
Panel depth 2-1/2 in. (6.4 cm)
Weight 11.2 oz (0.32 kg)
BACnet support Conforms to the Advanced Application Controller (B-AAC) Standard Device
Profile as defined in ANSI/ASHRAE Standard 135-2004 (BACnet) Annex L
Listed by UL-873, FCC Part 15-Subpart B-Class A, CE EN50082-1997
6-1/2 in. (16.5 cm) 6-1/2 in. (16.5 cm)

Safety considerations

Disconnect electrical power to the RTU Open before wiring it. Failure to follow this warning could cause electrical shock, personal injury, or damage to the controller.
4 RTU Open

Installation

To install the RTU Open:
1 Mount the controller (page 6). 2 Wire the controller for power (page 7).
Using the rooftop equipment control power transformer (page 7). Using an auxiliary control power transformer (page 8).
3 Set the controller's address (page 9). 4 Wire inputs and outputs (page 12). 5 Wire sensors to the controller (page 18).

Field-supplied hardware

An RTU Open retrofit installation may require the following field-supplied components:
wiring harness: Part #OPN-RTUHRN
transformer – 24 Vac, 20 VA minimum
wiring
Application-dependent components:
carbon dioxide sensors
damper/damper actuator
differential pressure switch
enthalpy switch
fan status switch
door switch
fan section door switch
relative humidity sensor
remote occupancy contact
smoke detector
temperature sensors
RTU Open 5
Installation

To mount the RTU Open

When you handle the RTU Open:
Do not contaminate the printed circuit board with fingerprints, moisture, or any foreign material.
Do not touch components or leads.
Handle the board by its edges.
Isolate from high voltage or electrostatic discharge.
Ensure that you are properly grounded.
When you mount the RTU Open:
Do not locate in an area that is exposed to moisture, vibration, dust, or foreign material.
Follow NEC and local electrical codes.
Do not obstruct access for unit maintenance.
Protect from impact or contact during unit maintenance.
We highly recommend that you mount the RTU Open in the unit control panel!
6 RTU Open
Screw the RTU Open into an enclosed panel using the mounting slots on the cover plate. Leave about 2 in. (5 cm) on each side of the controller for wiring.

To wire the controller for power

CAUTIONS
The RTU Open is powered by a Class 2 power source. Take appropriate isolation measures when
mounting it in a control panel where non-Class 2 circuits are present.
Do not power pilot relays from the same transformer that powers the RTU Open. In most cases, the RTU Open will be powered from the control power transformer provided with the
rooftop equipment. If you must use a separate control power transformer, additional precautions must be taken to ensure that the auxiliary transformer is in-phase with the rooftop equipment’s control power transformer. See Using an auxiliary control power transformer (page 8).

Using the rooftop equipment control power transformer

1 Remove power from the 24 Vac transformer. 2 Remove connector assembly from RTU Open's J1 connector.
RTU Open 7
Installation
3 If the rooftop equipment has thermostat connection terminals, connect wiring harness J1 wire 1 to R,
and
J1 wire 3 to C. Alternately, connect the control power transformer wires to J1 connector wires 1 (24
Vac) and 3 (Gnd).
4 Apply power to the rooftop equipment. 5 Measure the voltage at the RTU Open’s J1 terminals 1 and 3 to verify that the voltage is within the
operating range of 21.6–26.4 Vac.
6 Attach harness to RTU Open connector J1.
NOTE The harness and connector are keyed and must be oriented properly for correct installation.
7 Verify that the Power LED is on and the Run LED is blinking.

Using an auxiliary control power transformer

If you use a separate control power transformer, it is essential that the auxiliary transformer and the rooftop transformer are in-phase. You
Follow these steps:
1 Verify the available primary voltage at the rooftop equipment. 2 Remove power from the rooftop equipment and install the appropriate auxiliary transformer. Follow the
manufacturer’s installation instructions.
3 Ground one leg of the auxiliary transformer’s secondary wiring. 4 Apply power to the rooftop equipment. Measure the potential between the rooftop equipment control
power and auxiliary transformer's secondary hot (non-grounded) legs. If the voltage measured is less than 5 volts, the transformers are in-phase; proceed to step 7. If you measure a voltage greater than 24 Vac, then the phases are reversed.
5 Correct the phase reversal by either of the following methods:
Remove the ground from the secondary at the auxiliary transformer and connect it to the other
secondary
Reverse the primary wiring at the auxiliary transformer
6 Repeat step 4 to rewire. 7 Remove connector assembly from RTU Open's J1 connector. 8 Connect the auxiliary transformer wires to J1 wires 1 (24 Vac) and 3 (Gnd). 9 Apply power to the transformer. 10 Measure the voltage at the RTU Open’s J1 - 1 and 3 to verify that the voltage is within the operating
range of 21.6–26.4 Vac.
11 Attach harness to RTU Open's connector J1. See illustration below.
NOTE The harness connectors are keyed and must be oriented properly for correct installation.
12 Verify that the Power LED is on and the Run LED is blinking.
must verify this prior to connecting the auxiliary transformer to the RTU Open.
8 RTU Open
J1
J1
Optional
* Safety chain devices, field-installed - normally closed. Apply 24 Vac to this terminal
(jumper from
** Fire shutdown device, field-installed, configurable as normally open or closed
*** Enthalpy switch, field-installed - configurable as normally open or closed

To set the RTU Open's address

The RTU Open's two rotary switches determine the RTU Open's MAC address when it is placed on an MS/TP network. The rotary switches define the MAC address portion of the RTU Open's BACnet device instance number, which is composed of the MS/TP network number and the MAC address. They also set the slave address on a Modbus or N2 network when less than 100. See the RTU Open Integration Guide for additional information on integration.
CAUTION The MAC address of the controller must be unique on its network.
- 1 to
- 9) where no safety devices are installed.
RTU Open 9
Installation
1 Turn off the RTU Open's power. The controller reads the address each time you apply power to it. 2 Using the rotary switches, set the MSB (SW1) (10's) switch to the tens digit of the address, and set the
LSB (SW2) (1's) switch to the ones digit.
EXAMPLE To set the RTU Open’s address to 01, point the arrow on the MSB (SW1) switch to 0 and the
arrow on the
LSB (SW2) switch to 1.
3 Turn on the RTU Open's power.
NOTE The factory default setting is "00" and must be changed to successfully install your RTU Open.

To set the RTU Open's communications protocol and baud rate

RTU Open's SW3 DIP switches are used to set the controller's protocol and baud rate. The protocol and speed selection is determined by the network on which the controller will be installed. For Carrier BACnet implementations, select MS/TP @ 76.8 k as follows:
1 Power down the RTU Open. The controller reads the protocol and baud rate each time you apply power to
it.
2 Set SW3 DIP switches 1, 2, and 4 to On to configure the controller for BACnet MS/TP and 76.8 k baud.
3 Power up the RTU Open.
NOTE Other protocols and baud rates are available. See the RTU Open Integration Guide for additional instructions.

Wiring the RTU Open to the MS/TP network

The RTU Open communicates using BACnet on an MS/TP network segment communications at 9600 bps,
19.2 kbps, 38.4 kbps, or 76.8 kbps.
Wire the controllers on an MS/TP network segment in a daisy-chain configuration.
10 RTU Open
Install a BT485 on the first and last controller on a network segment to add bias and prevent signal distortions due to echoing.
See the MS/TP Networking and Wiring Installation Guide for more details.

Wiring specifications

Cable: 22 AWG or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire
Maximum length: 2000 feet (610 meters)

To wire the controller to the network

1 Pull the screw terminal connector from the controller's power terminals labeled Gnd and 24 Vac or Hot. 2 Check the communications wiring for shorts and grounds. 3 Connect the communications wiring to the BACnet port’s screw terminals labeled Net +, Net -, and
Shield.
NOTE Use the same polarity throughout the network segment.
4 Verify that the MSTP jumper is set to MSTP. 5 Set DIP switches 1 and 2 to the appropriate baud rate. See the MSTP baud diagram on the RTU Open.
The default baud rate is 76.8 kbps.
NOTE Use the same baud rate for all controllers on the network segment.
6 Insert the power screw terminal connector into the RTU Open's power terminals. 7 Verify communication with the network by viewing a module status report.
RTU Open 11
Installation
Channel Number
Type Signal
Function
Part Number
Wire/Terminal Numbers
Alternate Terminals
33ZCT55CO2
J4
J4
J1 -
J5
J1
J1
J5
J2
J2
J2
J5
J5
J20
J20 J13
AO - 1
AO
Economizer
Economizer
Actuator-Field-supplied
J2
N/A
AO - 2
AO
N/A
Not used
N/A
J22
N/A
J1
J1
J1
J1
J1
J11
J11

Wiring inputs and outputs

RTU Open Inputs and Outputs Table
Input 1
Input 2 AI 4-20 mA CO2
Input 3 BI 24 Vac Compressor Safety **
Input 4
Input 5 BI 24 Vac Fire Shutdown **
Input 6
Input 7 AI
Input 8 BI 24 Vac Enthalpy **
Input 9
Input 10 AI
Input 11 AI
Rnet AI
BO - 1 BO N/A - Relay Fan (G) N/A
BO - 2 BO N/A - Relay Heat 2 (W2) Output N/A
BO - 3 BO N/A - Relay Heat 1 (W1) Output N/A
BO - 4 BO N/A - Relay Cool 2 (Y2) Output
BO - 5 BO N/A - Relay Cool 1 (Y1) Output
BO - 6 BO N/A - Relay Humidi-MiZer™
BO - 7 BO N/A - Relay Reversing Valve
AI 4-20 mA CO2
OAQ Space Relative Humidity
OAQ Space Relative Humidity
Fan Status Filter Status Remote Occupancy Door Contact
BI 24 Vac Safety Chain *
Fan Status Filter Status Remote Occupancy Door Contact
AI
BI 24 Vac Humidistat **
10K Thermistor
10K Thermistor
10K Thermistor
100K Thermistor
Supply Air Temperature
Outside Air Temperature 33ZCSENOAT
Fan Status Filter Status Remote Occupancy Door Contact
Fan Status Filter Status Remote Occupancy Door Contact Space Temperature 33ZCT55SPT 33ZCT56SPT
Space Temperature Setpoint Adjust Zone Temperature SPS / SPPL / SPP
33ZCT56CO2 33ZCSENCO2 w/
33ZCASPCO2 33ZCSENSRH-01 33ZCT55CO2
33ZCT56CO2 33ZCSENCO2 w/
33ZCASPCO2 33ZCSENSRH-01 N/A 33CSAS-01 33CSFS=01 Field-supplied Field-supplied
N/A
Field-supplied 33CSAS-01 33CSFS-01 Field-supplied Field-supplied 33ZCSENSAT
33ZCSENDAT
33SENTHSW 33CSAS-01 33CSFS-01 Field-supplied Field-supplied TSTATCCPLH01-B 33CSAS-01 33CSFS-01 Field-supplied Field-supplied
33ZCT59SPT 33ZCT56SPT 33ZCT59SPT
N/A
N/A
N/A
N/A
- 5 & 6
- 2 & 3
2
- 9
- 10
- 1 & 2
- 3 & 2
- 6 & 7
- 7 & 8
- 1 & 2
- 3 & 4
- 1, 2, 3, 4
- 5 & 4
- 1 & 2
- 4
- 5
- 6
- 7
- 8
- 7 & 8
- 4 & 6
N/A
N/A
- 5 & 6
***
N/A
- 3 & 4
***
N/A
N/A
- 1 & 2
***
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
12 RTU Open
Channel Number
Type Signal
Function
Part Number
Wire/Terminal Numbers
Alternate Terminals
J11
AI
AO
BI
BO
Safety Chain Feedback
Run Enabled
J1
J5 (J5
Input Maximum length
Minimum gauge
Shielding
These inputs...
Support this signal type...
Description
BO - 8
Legend
- Analog Input
- Digital Input
* safeties are utilized. See To wire inputs and outputs 14 (page ) for additional information on the RTU Open wiring harness assembly terminations.
** Default input function
*** Parallel screw terminal at the harness (OPN-RTUHRN). See To wire inputs and outputs 14 (page ) for additional information.
BO N/A - Relay Power Exhaust
- Analog Output
- Digital Output
- 24 Vac required at this wire to provide
- 1 = J2 - 6, J5 - 3 = J1 - 10, J5 - 5 = J1 - 2) may be used in place of the associated flying leads at
N/A
- 1 & 3
status. Provide a jumper from J1 - 1 to
N/A
- 9 if no

Input wiring specifications

Thermistor
1000 feet (305 meters)
4-20 mA 3000 feet
(914 meters)
22 AWG Unshielded
22 AWG Unshielded

Inputs

Binary input
1000 feet (305 meters)
22 AWG Unshielded
SPT (RNET) 500 feet
(152 meters)
These RTU Open inputs accept the following signal types:
1, 2
4-20 mA The input resistance on the positive (+) terminal is 250 Ohms.
The Aux Power Out terminal is capable of supplying 24 Vdc to a 4-20 mA transducer, but the total current demanded must not exceed 40 mA. If the voltage measured from the Aux Power Out terminal to Gnd is less than 18 Vdc, you need to use an external power supply.
3, 5, 8, 9 Binary (24 Vac) 24 Vac voltage, resulting in a 25 mA maximum sense current
when the contacts are closed
6, 7, 10 Thermistor 10 kOhm at 77° F
11 100k Potentiometer Typically used for 33CZT56SPT Setpoint Offset Potentiometer
22 AWG 4 conductor
Unshielded
RTU Open 13
Installation
Battery Jumper
In (Do not remove)

Binary outputs

The RTU Open has 8 binary outputs. You can connect each output to a maximum of 24 Vac/Vdc. Each output is a dry contact rated at 3 A, 24 V maximum, and is normally open.
To size output wiring, consider the following:
Total loop distance from the power supply to the controller, and then to the controlled device
NOTE Include the total distance of actual wire. For 2-conductor wires, this is twice the cable length.
Acceptable voltage drop in the wire from the controller to the controlled device
Resistance (Ohms) of the chosen wire gauge
Maximum current (Amps) the controlled device requires to operate

Analog output

The RTU Open has 1 analog output that supports voltage or current devices. The controlled device must share the same ground as the controller and have input impedance of 500 Ohms maximum for the 4-20 mA mode on AO - 1.

To wire inputs and outputs

1 Turn off the RTU Open's power. 2 Connect the input wiring to the screw terminals on the RTU Open.
3 Turn 4 Set the appropriate jumpers on the RTU Open.
on the RTU Open's power.
J3
AO - 1
W1 W2 W3 W4 W5 W6
*Formatting the controller may result in lost information and should only be done under the guidance of Carrier Control Systems Support.
Format Jumper*
Input 11 mA Jumper
Input 11 Thermistor
Input 10 mA Jumper
Input 10 Thermistor Jumper
0 - 10 Vdc/4-20 mA
Out
Out (mA not utilized on this channel)
In (default position)
Out (mA not utilized on this channel)
In (default position)
14 RTU Open
Optional
* Safety chain devices, field-installed - normally closed. Apply 24 Vac to this terminal
(jumper from
** Fire shutdown device, field-installed, configurable as normally open or closed
*** Enthalpy switch, field-installed - configurable as normally open or closed
J1 - 1 to J1 - 9) where no safety devices are installed.
J4 Inputs
1 Turn off the RTU Open's power. 2 Connect the input and output wiring to the screw terminals on the RTU Open.
NOTE When utilizing the controller's 24 Vdc auxiliary power out, the total current demand for these two
input channels must not exceed 40 mA (100mA per channel).
RTU Open 15
Installation
NOTE J4 Analog Inputs 1 and 2 may be set for the following device types:
IAQ Sensor OAQ Sensor Space RH Sensor
J5 Inputs
The terminals for Inputs 3, 5, and 8 are available for use in place of the flying wire leads at Molex
connectors J1 and J2 identified below:
NOTE J5 binary inputs 3, 5, and 8 are the same input channels as:
J1 wire 2, J5 - Input - 3 (Compressor Safety) J1 wire 10, J5 - Input - 5 (Fire Shutdown) J2 wire 6, J5 - Input - 8 (Enthalpy Switch).
16 RTU Open
These terminals are available for use in place of the flying wire leads at Molex connectors J1 and J2. Binary inputs are configurable and may be used for the following functions:
Input Default input function Additional functions 3
5
8
Compressor Safety
Fire Shutdown
Enthalpy Switch
Fan Status Filter Status Remote Occupancy Door Contact Fan Status Filter Status Remote Occupancy Door Contact Fan Status Filter Status Remote Occupancy Door Contact
9
J11 Outputs
HumidiStat
Fan Status Filter Status Remote Occupancy Door Contact
RTU Open 17
Installation
NOTE Output relay contacts rated at 3A, 24V maximum. Install pilot relays required by application.
J20 Analog Inputs 10 and 11 are reserved for a 10k Ohm space temperature sensor with an
NOTE
optional 100k Ohm offset potentiometer used for setpoint adjustment.

Wiring sensors to inputs

You may wire various sensors to the RTU Open's inputs. See the table below for details.
NOTE This document gives instructions for wiring the sensors to the RTU Open. For specific mounting and wiring instructions, see the Carrier Sensors Installation Guide.
All field control wiring that connects to the RTU Open must be routed through the raceway built into the corner post. The raceway provides the UL-required clearance between high-and low-voltage wiring.
1 Pass the control wires through the hole provided in the corner post. 2 Feed the wires through the raceway to the RTU Open. 3 Connect the wires to the removable Phoenix connectors. 4 Reconnect the connectors to the board (where removed).
18 RTU Open
Sensor
Part numbers
Notes
NOTE For rooftop unit installation, see the base unit installation instructions.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury, death, and/or equipment damage.
Disconnect all power to the unit before performing maintenance or service. Unit may automatically start if power is not disconnected.

Field-supplied sensor hardware

The RTU Open controller is configurable with the following field-supplied sensors:
Space temperature sensor (page 20)
Supply air temperature sensor
SPS, SPPL, SPP, 33ZCT55SPT, 33ZCT56SPT, 33ZCT59SPT
33ZCSENSAT Factory-installed
(page 21)
Duct air temperature sensor
33ZCSENDAT
(page 22)
Outdoor air temperature sensor
33ZCSENOAT Factory-supplied with Economizer
(page 23)
CO2 sensor (page 24) 33ZCSENCO2, 33ZCT55CO2,
33ZCT56CO2
Required only for demand control ventilation - a dedicated 24-vac transformer is required
Outdoor air quality sensor (page
25)
Duct relative humidity sensor
33ZCTSENCO2 Optional with demand control
ventilation
33ZCSENDRH-01
(page 26)
Space relative humidity sensor
33ZCSENSRH-01
(page 26)
Humidistat (page 27) TSTATCCPLH01-B
CO2 aspirator box (page 24) C33ZCCASPCO2 Required for CO2 return duct/outside
air applications
Outdoor air enthalpy switch
33CSENTHSW
(page 28)
Return air enthalpy sensor (page 28)
33CSENTSEN Optional with
33CSSENTHSW
Filter status switch (page 31) 33CSFS-01
Fan status switch (page 31) 33CSAS-01 or field-supplied
For specific details about sensors, see the Carrier Sensors Installation Guide.
RTU Open 19
Installation
Sensor
Part #
Features
SPT Standard
SPT Plus
SPT Pro
LCD display

Wiring an SPT sensor

The RTU Open is connected to a wall-mounted space temperature sensor to monitor room temperature.
An i-Vu Open Control System offers the following SPT sensors:
SPS
Local access port
No operator control
SPPL
Slide potentiometer to adjust setpoint
MANUAL ON button to override schedule
LED to show occupied status
Local access port
SPP
MANUAL ON button to override schedule
WARMER and COOLER buttons to adjust setpoint
INFO button to cycle through zone and outside air temperatures,
setpoints, and local override time
Local access port
You wire SPT sensors to the RTU Open's Rnet port. An Rnet can consist of any of the following combinations of devices wired in a daisy-chain configuration:
1 SPT Plus or SPT Pro
1–4 SPT Standards
1–4 SPT Standards, and 1 SPT Plus or SPT Pro
6
Any of the above combinations, plus up to 2 BACview
's but no more than 6 devices total
NOTES
If you have 2 BACview
6
's, the second BACview6 must have a separate power supply with the same
ground as the controller.
If the Rnet has multiple SPT Standard sensors, you must give each a unique address on the Rnet. See
the Carrier Sensors Installation Guide.
If the Rnet has multiple BACviews, you must give each a unique address on the Rnet. See the BACview
Installation and User Guide.
Rnet wiring specifications
NOTE Use the specified type of wire and cable for maximum signal integrity.
Description 4 conductor, unshielded, CMP, plenum rated cable
Conductor 18 AWG
Maximum length 500 feet (152 meters)
Recommended coloring Jacket: White
Wiring: Black, white, green, red
UL temperature rating 32–167°F (0–75°C)
20 RTU Open
Loading...
+ 58 hidden pages