Carrier 12, 50LJQ008 User Manual

50LJQ008,012 (50 Hz)
Single-Package Rooftop Heat Pump Units
Installation, Start-Up and Service
Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS .................. 1
INSTALLATION ............................ 1-16
Step 1 — Provide Unit Support .............. 1
• ROOF CURB
• SLAB MOUNT
Step 3 — Make Field Connection for
Condensate Disposal .........................3
Step 4 — Rig and Place Unit ................. 3
Step 5 — Make Electrical Connections ....... 7
• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
• HEAT ANTICIPATOR SETTINGS
Step 6 — Adjust Indoor-Fan Speed ...........13
START-UP ................................17-19
SERVICE ..................................19-21
SAFETY CONSIDERATIONS
Installation and servicing of air conditioning equipment can be hazardous due to system pressure and electrical com­ponents. Only trainedandqualified service personnel should install, repair or service air conditioning equipment.
Untrained personnel can perform basic maintenance func­tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service per­sonnel. When working on air conditioning equipment, ob­serve precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safetycodes. Wearsafety glasses andwork gloves. Use quenching cloth for unbrazing operations. Have fire ex­tinguisher available for all brazing operations.
Before performing service or maintenance operations on unit, turn offmain power switch to unit. Electrical shock could cause personal injury.
INSTALLATION
Unit is shipped in the vertical configuration. To convert to horizontal configuration, remove side duct opening covers. Using the same screws, install covers on vertical duct open­ings with the insulation-side down. Seals around duct open­ings must be tight.
IMPORTANT: An external filter kit MUST be used, or the filters MUST be field-installed outside the unit on horizontal applications with accessory economizer or two-position damper. Otherwise, the economizer or two-position must be partially removed to access the filters. The area of the field-installed filters should be equal to the area of the factory-installed filters.
Step 1 — Provide Unit Support
ROOF CURB — Assemble and install accessory roof curb in accordance with instructions shipped with curb. See Fig. 1. Install insulation, cant strips, roofing and counter flash­ing as shown. Ductwork must be attached to curb, not to the unit. If electric or control power is to be routed through the curb, attach the accessory thru-the-curb service connection plates to the roof curb in accordance with the accessory in­stallation instructions. Connection plates must be installed before unit is set in roof curb.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket sup­plied with the roof curb as shown in Fig. 1. Improp­erly applied gasket also can result in air leaks and poor unit performance.
Curb should be level. Unit leveling tolerances are shown in Fig. 2. This is necessary for unit drain to function prop­erly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
SLAB MOUNT (Horizontal Units Only) — Provide a level concrete slab that extends a minimum of 152 mm (6 in.) be­yond unit cabinet. The slab should be 203 mm (8 in.) thick with 102 mm (4 in.) above grade. Install a gravel apron in front of outdoor coil air inlet to prevent grass and foliage from obstructing airflow. In areas where high snowfall occurs, increase height of slab to ensure that snow does not block coil.
NOTE: Horizontal units may be installed on a roof curb if required.
Step 2 — Field Fabricate Ductwork — On verti-
cal discharge units, secure all ducts to roof curb and building structure. Do not connect ductwork to unit. For horizontal applications, field-supplied flanges should be attached to hori­zontal discharge openings and all ductwork attached to the flanges. Insulate and weatherproof all external ductwork, joints and roof openings with counter flashing and mastic in ac­cordance with applicable codes.
Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with ap­plicable fire codes.
Aminimumclearance to combustibles is not required around ductwork on vertical discharge units. On horizontal dis­charge units, a minimum clearance of 25 mm (one in.) is required for the first 305 mm (12 in.) of ductwork.
Cabinet return-air static shall not exceed −87 Pa (−.35 in. wg) with economizer or −112Pa (−.45 in. wg) with­out economizer.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 015-015 Printed in U.S.A. Form 50LJQ-C1SI Pg 1 1-92 Replaces: New
ROOF CURB
ACCESSORY
50DJ901371
50DJ901381
‘‘A’’ UNIT SIZE
18-29 [356]
50LJQ008,012
28-09 [610]
UNIT SIZE ‘‘F’’ POWER ‘‘G’’ CONTROL
50LJQ008,012
19 [25] NPT or
29 [51] NPT
NOTES:
1. Roof curb accessory is shipped unassembled.
2. Insulated panels: 25 mm (one in.) thick polyure­thane foam, .8 Kg (1
3. Dimensions in [ ] are in millimeters.
4. Roof curb: 16-gage steel.
5. Attachductworktocurb (flanges of duct rest on curb).
6. Service clearance 1219 mm (4 ft) on each side.
3
⁄49 [19] NPT 50DJ901311
7. Direction of airflow.
8. Control and power service plates are part of a sepa­rately shipped accessory package.
3
⁄4lb) density.
CONNECTOR
PKG. ACC.
Fig. 1 — Roof Curb Dimensions
2
MAXIMUM ALLOWABLE DIFFERENCE
A-B B-C A-C
mm in. mm in. mm in.
13 .5 25 1.0 25 1.0
Fig. 2 — Unit Leveling Tolerance
Step 3 — Make Field Connection for Conden­sateDisposal —
See Fig. 3. A3⁄4-in. FPT connection is located on the side of the unit. Use a trap at least 100 mm (4 in.) deep, and protect against freeze-up.
If drain line is run to a drain, pitch line away from unit at 25 mm (one in.) per 3 m (10 ft) of run. Do not use a pipe size smaller than the unit connection.
Units must have an external trap added.
Step4 — Rig andPlace Unit — Inspect unit for trans-
portation damage. File any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a ref­erence. See Tables 1A and 1B and Fig. 4 for additional in­formation. Operating weight is shown in Tables 1A and 1B and Fig. 4.
Lifting holes are provided in base rails as shown in Fig. 4 and 5. Refer to rigging instructions on unit.
All panels must be in place when rigging.
POSITIONING — Maintain clearance around and above unit to provide proper air flow and service access. See Fig. 5.
Position unit on roof curb so that the following clearances
are maintained; 6 mm (
1
⁄4in.) clearance between roof curb and base rails on each side and front of unit: 29 mm (15⁄ in.) clearance between roof curb and rear of unit (see Fig. 1, section C-C).
Do not install unit in an indoor location. Do not locate unit air inlet near exhaust vents or other sources of contami­nated air.
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
After unit is in position, remove polyethylene shipping wrap­per and rigging skid.
NOTE: Trap should be deep enough to offset maximum unit static difference. A 100 mm (4 in.) trap is recommended.
Fig. 3 — External Trap Condensate Drain
32
NOTES:
1. Dimensions in ( ) is in millimeters.
2. Hood rigging shackles through holes in base rail, as shown in detail ‘‘A’’. Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.
3. Weightsdonotincludeeconomizer .SeeTables1A and 1B for econo­mizer weights.
All panels must be in place when rigging.
Fig. 4 — Rigging Details
UNIT
50LJQ
008 840 381 87.38 2219 40.25 1022 41.31 1050 012 940 426 87.38 2219 40.25 1022 48.31 1253
MAX
WEIGHT
lb kg in. mm in. mm in. mm
‘‘A’’ ‘‘B’’ ‘‘C’’
DIMENSIONS
3
Table 1A — Physical Data (SI)
BASE UNIT 50LJQ 008 012 NOMINAL CAPACITY (kW) 23.2 28.8 OPERATING WEIGHT (kg)
Unit 381 426 With Economizer 401 446 Roof Curb 101 101
COMPRESSOR
Quantity 22 Oil (ml) (each compressor) 1627 2071
REFRIGERANT TYPE
Operating Charge (kg)
Circuit 1 3.7 4.0 Circuit 2 3.2 3.9
OUTDOOR FAN
Quantity...Diameter (mm) 1...660 1...660 Nominal L/s 2900 3260 Motor BkW...r/s .25...16.0 .25...16.0
OUTDOOR COIL
Rows...Fins/m 2...669 2...669 Total Face Area (sq m) 1.9 2.3
INDOOR FAN
Size (mm) 381 x 381 381 x 381 Type Drive Belt Belt Nominal L/s 1200 1600 Motor BkW per NEC* 1.12 1.50 Maximum Continuous BkW 1.79 2.16 Motor Frame 56 56 Fan r/s Range 10.30-14.70 11.50-15.00 Motor Bearing Type Ball Ball Maximum Fan r/s 26.7 26.7 Motor Pulley Pitch Diameter
A/B (mm)
Fan Pulley Pitch Diameter (mm) 140 178 Belt — Type...Length (mm) A...1219 A...1295 Pulley Center Line Distance (mm) 425-489 464-527 Fan Shaft Diameter at Pulley (mm) 25 25 Speed Change per Full Turn of
Movable Pulley Flange (r/s)
Movable Pulley Maximum Full
Turns from Closed Position
Factory Setting — Full Turns Open 55 Factory Speed Setting (r/s) 10.3 11.5
INDOOR COIL Enhanced Copper Tubes, Aluminum Double Wavy Fins,
Rows...Fins/m 3...590 3...590 Total Face Area (sq m) .74 .93
OUTDOOR-AIR INLET SCREENS Cleanable
Quantity...Size (mm)
RETURN-AIR FILTERS Disposable
Quantity...Size (mm)
Enhanced Copper Tubes, Aluminum Fins, Acutrol™ Feed Device
61/86 86/112
.88 .70
55
4...406 x 508 x 50 4...508 x 508 x 50
LEGEND
BkW — Brake Kilowatt NEC — National Electrical Code (U.S.A. Standard)
*Used to determine wire sizing per NEC.
Hermetic
R-22
Propeller
Centrifugal
Acutrol Feed Device
1...508 x 635 x 25
1...406 x 635 x 25
4
Table 1B — Physical Data (English)
BASE UNIT 50QJ 008 012 NOMINAL CAPACITY (tons) 6.6 8.2 OPERATING WEIGHT (lb)
Unit 840 940 With Economizer 884 984 Roof Curb 223 223
COMPRESSOR
Quantity 22 Oil (fluid oz) (each compressor) 55 70
REFRIGERANT TYPE
Operating Charge (lb-oz)
Circuit 1 8-2 8-14 Circuit 2 7-0 8-10
OUTDOOR FAN
Quantity...Diameter (in.) 1...26 1...26 Nominal Cfm 6100 6900 Motor Hp...Rpm
OUTDOOR COIL
Rows...Fins/in. 2...17 2...17 Total Face Area (sq ft) 20.5 25.0
INDOOR FAN
Size (in.) 15x15 15x15 Type Drive Belt Belt Nominal Cfm 2600 3400 Horsepower per NEC* 1.5 2.0 Maximum Continuous Bhp 2.4 2.9 Motor Frame 56 56 Fan Rpm Range 622-882 692-896 Motor Bearing Type Ball Ball Maximum Fan Rpm 1600 1600 Motor Pulley Pitch Diameter
A/B (in.)
Fan Pulley Pitch Diameter (in.) 5.5 7.0 Belt — Type...Length (in.) A...48 A...51 Pulley Center Line Distance (in.) 16.75-19.25 18.25-20.75 Fan Shaft Diameter at Pulley (in.) 11 Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full
Turns from Closed Position
Factory Setting — Full Turns Open 55 Factory Speed Setting (Rpm) 620 690
1
⁄3...960
Enhanced Copper Tubes, Aluminum Fins, Acutrol™ Feed Device
2.4/3.4 3.4/4.4
52 42
55
INDOOR COIL Enhanced Copper Tubes, Aluminum Double Wavy Fins,
Rows...Fins/in. 3...15 3...15 Total Face Area (sq ft) 8.0 10.0
OUTDOOR-AIR INLET SCREENS Cleanable
Quantity...Size (in.)
RETURN-AIR FILTERS
Quantity...Size (in.) 4...16 x 20 x 2 4...20 x 20 x 2
LEGEND
Bhp — Brake Horsepower NEC — National Electrical Code (U.S.A. Standard)
*Used to determine wire sizing per NEC.
Hermetic
R-22
Propeller
Centrifugal
Acutrol Feed Device
1...20 x 25 x 1
1...16 x 25 x 1 Disposable
1
⁄3...960
5
UNIT
50LJQ
STD. UNIT
WEIGHT Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Ft-in. mm Ft-in. mm Ft-in. mm
ECONOMIZER
WEIGHT
CORNER
WEIGHT ‘‘A’’
CORNER
WEIGHT ‘‘B’’
CORNER
WEIGHT ‘‘C’’
CORNER
WEIGHT ‘‘D’’
008 840 381 44 20 182 83 156 71 231 105 271 123 2-0 012 940 426 44 20 204 93 174 79 259 117 303 137 1-2
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Center of gravity.
3. Direction of airflow.
4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance (local codes or jurisdiction may prevail): a. Bottom to combustible surfaces (when not using curb) 25 mm
(one in.).
b. Condenser coil, for proper airflow, 914 mm (36 in.) one side,
305 mm (12 in.) the other. The side getting the greater clear­ance is optional.
c. Overhead 1524 mm (60 in.) to assure proper outdoor fan
operation. d. Between units, control box side, 1067 mm (42 in.). e. Between unit and ungrounded surfaces, control box side, 914
mm (36 in.). f. Between unit and block or concrete walls and other grounded
surfaces, control box side 1067 mm (42 in.). g. Horizontal supply and return end, zero mm (zero in.).
6. With the exception of the clearance for the outdoor coil as stated in notes 5b and c, a removable fence or barricade requires no clearance.
‘‘H’’ ‘‘J’’ ‘‘K’’
7
⁄8632 3-55⁄161050 2-911⁄16856
7
⁄8378 4-15⁄161253 3-03⁄8924
CONNECTION SIZES
3
⁄89 dia [35] field power supply hole
A 1
1
⁄29 dia [64] power supply knockout
B 2
3
⁄49 dia [44] charging-port hole
C 1
7
⁄89 dia [22] field control wiring hole
D
3
⁄49-14 NPT condensate drain
E F 29 dia [51] power supply knockout
Fig. 5 — Base Unit Dimensions
6
Step 5 — Make Electrical Connections
Unit cabinet must have uninterrupted, unbroken elec­trical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for elec­trical ground when installed in accordance with U.S.A. National Electrical Code (Ref: ANSI/NFPA 70-1987) or equivalent local electrical codes. Failure to follow this warning could result in the installer being liable for per­sonal injury of others.
FIELD POWER SUPPLY — Pigtails are provided for field wire connections. Use factory-supplied splices or copper/ aluminum connector.
When installing units, provide a disconnect per local codes. All field wiring must comply with local requirements.
Install conduit through side panel openings. For units with­out electric heat, install conduit between disconnect and con­trol box. Install power lines to terminal connections as shown in Fig. 6. For units with electric resistance heat, refer to Table 2 to determine appropriate power wiring figure (Fig.7-13) and route lines as indicated in appropriate figure.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (also see Table 2). On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the for­mula shown in Table 2, Note 3 to determine the % voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty.
When electric heat is installed, remove knockouts for ap­propriate size conduit from unit block-off panel and single point box. Install conduit (rigid or electro-metallic tubing) through conduit drip boot as shown in Fig. 14. Drip boot eliminates the need for water tight conduit fittings at the single point box. Refer to Fig. 15 for component locations.
LEGEND
C—Contactor IFC — Indoor-Fan Contactor TB — Terminal Block
Field Wiring Factory Wiring
Splice Connection (Factory Supplied)
Fig. 6 — Power Wiring Connections
LEGEND FOR FIG. 7-13
EQUIP — Equipment FU Fuse GND Ground HTR Heater TB Terminal Block
Fig. 7 — Electric Heater Power Wiring Connections — 50LJQ, 220-3-50 and 400-3-50;
Single Point Kit 50DJ902021 and 50DJ902071
7
Fig. 8 — Electric Heater Power Wiring Connections — 50LJQ, 400-3-50;
Single Point Kit 50DJ902041 and 50DJ902101
Fig. 9 — Electric Heater Power Wiring Connections — 50LJQ, 400-3-50;
Single Point Kit 50DJ902061 and 50DJ902121
8
Fig. 10 — Electric Heater Power Wiring Connections — 50LJQ, 220-3-50;
Single Point Kit 50DJ902031 and 50DJ902081
Fig. 11 — Electric Heater Wiring Connections — 50LJQ, 220-3-50;
Single Point Kit 50DJ902051 and 50DJ902111
LEGEND FOR FIG. 7-13
EQUIP — Equipment FU Fuse GND Ground HTR Heater TB Terminal Block
9
Fig. 12 — Electric Heater Power Wiring Connections — 50LJQ, 220-3-50;
Single Point Kit 50DJ902091
Fig. 13 — Electric Heater Power Wiring Connections — 50LJQ, 220-3-50;
Single Point Kit 50DJ902131
LEGEND FOR FIG. 7-13
EQUIP — Equipment FU Fuse GND Ground HTR Heater TB Terminal Block
10
Table 2 — Electrical Data
UNIT
50LJQ
008
012
VOLTAGE
NOMINAL
V-PH-HZ
220-3-50 198 242 15.3 82.0 1.5 1.5 5.8
400-3-50 360 440 7.7 41.0 1.5 1.5 2.6
220-3-50 198 242 19.6 105.0 1.5 2.0 7.5
400-3-50 360 440 10.4 55.0 1.5 2.0 3.5
RANGE
Min Max RLA LRA FLA Hp FLA
COMPR
(each)
OFM IFM ELECTRIC HEAT POWER SUPPLY
LEGEND
COMPR — Compressor FLA Full Load Amps HACR Heating, Air Conditioning and Refrigeration IFM Indoor-Fan Motor LRA Locked Rotor Amps MCA Minimum Circuit Amps MOCP Maximum Overcurrent Protection OFM Outdoor-Fan Motor RLA Rated Load Amps
*Heaters are field-installed only. Heater capacity (kW) is based on
heater voltage of 230 v or 400 v.If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.
†Fuse or HACR circuit breaker.
**Requires 2 heater packages. NOTES:
1. MCA and MOCP values are calculated in accordance with NEC
(National Electric Code) (U.S.A. Standard), Article 440.
2. Motor RLA and FLA values are established in accordance with UL
(Underwriters’ Laboratories) Standard 465 (U.S.A. Standard).
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt­age is greater than 2%.
the % voltage imbalance. % Voltage Imbalance
= 100 x
max voltage deviation from average voltage
Use the following formula to determine
average voltage
ELECTRIC HEAT
Nominal
kW*
41.7 50
9.5 24.7 70.3 80 10 711
14.6 38.0 85.7 90 10 601
22.7 59.0 130.0 150 11 611
29.3 76.2 158.5 175 11 621
38.8 100.9 179.5 200 12 711, 621**
10.5 15.2 21.4 25 7 681
12.5 18.0 44.0 45 7 631
21.0 30.3 59.3 60 8 641
25.0 36.1 66.5 70 8 651
31.5 45.5 78.3 80 9 681, 641** — 53.1 60
9.5 24.7 81.6 90 10 711
14.6 38.0 97.1 100 10 601
29.3 76.2 141.3 150 11 621
43.9 114.1 190.9 200 13 601, 621**
10.5 15.2 28.4 35 7 681
12.5 18.0 51.0 60 7 631
21.0 30.3 66.3 70 8 641
25.0 36.1 73.5 80 8 651
31.5 45.5 85.2 90 9 681, 641**
37.5 54.2 96.6 100 9 631, 651**
FLA MCA MOCP†
Example: Supply voltage is 400-3-50.
AB = 393 v BC = 403 v AC = 396 v
Average Voltage =
Determine maximum deviation from average voltage. (AB) 397 − 393=4v
(BC) 403 − 397=6v (AC) 397 − 396=1v
Maximum deviation is 6 v. Determine % voltage imbalance.
% Voltage Imbalance = 100 x = 1.5% This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
POWER WIRING
FIG. NO.
= = 397
6
397
ELECTRIC HEAT
PART NO.
50DJ901—
393 + 403 + 396
3
1192
3
11
DISCONNECT MOUNTING LOCATION
Fig. 14 — Conduit Installation
EMT OR RIGID CONDUIT (FIELD­SUPPLIED)
MAIN CONTROL BOX
BRACKET AND CONDUIT DRIP BOOT
CENTER POST
MANUAL RESET LIMIT SWITCH LOCATION (HIDDEN)
HEATER COVERS
15 to 23 m (51 to 75 ft), use no. 16 AWG insulated wire (35 C minimum). For over 23 m (75 ft), use no. 14 AWG insulated wire (35 C minimum). See Table 3 for wire conversions.
1. If unit is mounted on roof curb and accessory thru-the­curb service plate connection is used, route wire through connection plate.
2. Pass control wires through the hole provided on unit (see connection D, Connection Sizes table, Fig. 5).
3. Feed wire through the raceway built into the corner post to the 24-v barrier located on the left side of the control box. See Fig. 17. The raceway provides the UL (U.S.A. Standard) required clearance between high- and low­voltage wiring.
4. Connect thermostat wires to screw terminals of low­voltage connector. The connector plugs into the control board and may be removed to make connection. Plug con­nector back into the control board after making connec­tion or unit will not operate.
HEAT ANTICIPATORSETTINGS — Set first-stage heat an­ticipator settings at 1.0. Set second-stage heat anti­cipator settings at 0.6. For units with optional electric heat, set anticipator for second stage as shown in Table 4.
HEATER WIRING LABEL
HEATER MOUNTING BRACKET
SINGLE POINT BOX
SINGLE POINT BOX MOUNTING SCREWS
CONTROL WIRE TERMINAL BLOCK
HEATER MODULE (LOCATION 1)
HEATER MODULE (LOCATION 2)
Fig. 15 — Component Location
FIELD CONTROL WIRING — Install a Carrier-approved accessory thermostat assembly according to installation in­structions included with the accessory. Locate thermostat as­sembly on a solid wall in the conditioned space to sense av­erage temperature in accordance with thermostat installation instructions.
Route thermostat cable or equivalent single leads of col­ored wire from subbase terminals to low-voltage connec­tions on unit (shown in Fig. 16) as described in Steps 1-4 below.
NOTE: For wire runs up to 15 m (50 ft), use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For
Table 3 — American/European Wire Conversions
AMERICAN EUROPEAN
Industry
Standard Size
18 AWG 0.82 1.0 16 AWG 1.30 1.5 14 AWG 2.08 2.5 12 AWG 3.30 4.0 10 AWG 5.25 6.0
8 AWG 6.36 10.0 6 AWG 13.29 16.0 4 AWG 21.14 25.0 3 AWG 26.65 — 2 AWG 33.61 35.0
1 AWG 42.39 50.0 1/0 AWG 53.49 — 2/0 AWG 67.42 70.0 3/0 AWG 85.00 95.0 4/0 AWG 107.19 120.0
250 kcmil 126.64 150.0 300 kcmil 151.97 — 350 kcmil 177.90 185.0 400 kcmil 202.63 240.0 500 kcmil 253.29 300.0 600 kcmil 303.95
LEGEND
AWG — American Wire Gage kcmil — Thousand Circular Mils
American
Conversion
2
(mm
)
Industry
Standard
Size (mm2)
Table 4 — Unit Voltage
220 400
Heater kW Anticipator Setting Part No. 50DJ901— Heater kW Anticipator Setting Part No. 50DJ901—
9.5 0.3 711 10.5 0.3 681
14.6 0.3 601 12.5 0.3 631
22.7 0.6 611 21.0 0.3 641
29.3 0.6 621 25.0 0.3 651
38.8 0.9 711, 621* 31.5 0.6 681, 641*
43.9 0.9 711, 621* 37.5 0.6 631, 651*
*Requires 2 heater packages.
12
UNIT CONTROL BOARD
BAT Battery C—Contactor CB Circuit Breaker DAT Discharge-Air Thermistor EMC/EMFC — Energy Management Closed EMO/EMFO — Energy Management Open EQUIP Equipment GND Ground HR Heater Relay IFC Indoor-Fan Contactor
Fig. 16 — Field Wiring Connections
LEGEND
OFC Outdoor-Fan Contactor P—Plug TB Terminal Board TRAN — Transformer
Field Wiring Factory Wiring
Splice Connection (Factory Supplied)
Tables 5A and 5B show fan rps and rpm at motor pulley settings. Refer to Tables 6-13 to determine fan speed settings.
Fan motor pulleys are factory set for speed shown in Tables 1A and 1B.
RACEWAY
Fig. 17 — Field Control Wiring Raceway
Step 6 — Adjust Indoor-Fan Speed — Adjust in-
door fan speed to meet jobsite conditions.
For units with electric resistance heating, required mini­mum L/s (cfm) is 1062 (2250) for 50LJQ008 and 1416 (3000) or 50LJQ012, with the following exceptions.
UNIT
50LJQ
012
UNIT
VOLTAGE
220 50.0 400 50.0
HEATER
kW
UNIT
CONFIG-
URATION
Horizontal or Vertical
Horizontal or Vertical
REQUIRED
MINIMUM
L/s Cfm
1534 3250 1605 3400
To change fan speed: a. Shut off unit power supply. b. Loosen belt by loosening fan motor mounting nuts. See
Fig. 18.
c. Loosen movable pulley flange setscrew (see Fig. 19). d. Screw movable flange toward fixed flange to increase speed
and away from fixed flange to decrease speed. Increasing fan speed increases load on motor. Do not exceed maxi­mum speed specified in Tables 1A and 1B.
e. Set movable flange at nearest keyway of pulley hub and
tighten setscrew (see Tables 1A and 1B for speed change for each full turn of pulley flange).
To align fan and motor pulleys: a. Loosen fan pulley setscrews. b. Slide fan pulley along fan shaft. c. Make angular alignment by loosening motor from mount-
ing plate.
To adjust belt tension (see Fig. 18): a. Loosen fan motor mounting bolts. b. Slide motor mounting plate away from fan scroll for proper
belt tension (13 mm [
1
⁄2-in.] deflection with one finger)
and tighten mounting bolts.
c. Adjust bolt and nut on motor mounting plate to secure
motor in fixed position.
13
MOTOR MOUNTING NUTS AND BOLTS
Fig. 18 — Belt-Drive Motor Mounting
T able 5A — Fan R/s at Motor Pulley Settings (SI)
Fig. 19 — Indoor-Fan Pulley Adjustment
50LJQ
1
0
2
111⁄2221⁄2331⁄2441⁄25
MOTOR PULLEY TURNS OPEN
008 14.70 14.26 13.82 13.38 12.94 12.50 12.06 11.62 11.18 10.74 10.30 012 15.00 14.65 14.30 13.95 13.60 13.25 12.90 12.55 12.20 1 1.85 11.50
T able 5B — Fan Rpm at Motor Pulley Settings (English)
50LJQ
1
0
2
008 882 856 830 804 778 752 726 700 674 648 622 012 896 875 855 834 814 794 774 753 733 712 692
MOTOR PULLEY TURNS OPEN
1
1
2
221⁄2331⁄2441⁄25
14
Table 6 — Fan Performance (SI), 50LJQ008 (50 Hz) — Horizontal Discharge Units
AIRFLOW
(L/s) 1100 7.9 0.35 9.4 0.50 10.6 0.68 11.7 0.85 12.7 1.03 13.6 1.25 14.4 1.46 14.9 1.69 15.1 1.92 15.0 2.15
1200 8.3 0.42 9.8 0.59 11.0 0.78 12.0 0.95 13.0 1.15 13.9 1.36 14.8 1.58 15.5 1.82 16.0 2.06 16.4 2.31 1300 8.8 0.51 10.2 0.69 11.3 0.88 12.4 1.08 13.3 1.28 14.2 1.49 15.0 1.72 15.8 1.96 16.5 2.21 17.1 2.47 1400 9.2 0.60 10.6 0.80 11.7 0.99 12.7 1.22 13.7 1.42 14.5 1.63 15.3 1.87 16.1 2.12 16.9 2.38 1500 9.7 0.71 11.0 0.91 12.1 1.12 13.0 1.35 14.0 1.59 14.8 1.81 15.6 2.04 16.4 2.30 1600 10.1 0.82 11.3 1.04 12.5 1.28 13.4 1.49 14.3 1.75 15.2 2.00 15.9 2.24 1700 10.6 0.93 11.8 1.20 12.9 1.44 13.8 1.67 14.7 1.92 15.5 2.20
50 100 150 200 250 300 350 400 450 500
r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW
EXTERNAL STATIC PRESSURE (Pa)
Table 7 — Fan Performance (SI), 50LJQ012 (50 Hz) — Horizontal Discharge Units
AIRFLOW
(L/s) 1300 7.6 0.30 8.9 0.41 10.2 0.56 11.1 0.64 12.1 0.77 13.1 0.92 13.9 0.93 14.0 0.52 15.0 1.13 15.6 1.32
1400 8.0 0.40 9.3 0.51 10.5 0.64 11.4 0.75 12.4 0.88 13.3 1.01 14.1 1.11 14.6 0.96 15.4 1.32 16.0 1.42 1500 8.4 0.48 9.6 0.60 10.7 0.72 11.8 0.86 12.7 0.99 13.5 1.12 14.3 1.26 15.1 1.35 15.7 1.49 16.4 1.54 1600 8.8 0.58 10.0 0.69 11.1 0.82 12.1 0.96 12.9 1.10 13.8 1.24 14.5 1.38 15.3 1.54 16.0 1.64 16.7 1.72 1700 9.1 0.69 10.3 0.78 11.3 0.93 12.3 1.07 13.2 1.22 14.0 1.37 14.8 1.52 15.5 1.66 16.3 1.84 17.0 1.95 1800 9.5 0.81 10.7 0.90 11.7 1.05 12.6 1.20 13.5 1.36 14.3 1.52 15.0 1.67 15.8 1.83 16.4 1.99 17.2 2.17 1900 9.9 0.95 11.0 1.02 12.0 1.18 12.9 1.34 13.8 1.50 14.6 1.68 15.3 1.83 16.0 2.00 16.7 2.16 17.3 2.33 2000 10.3 1.11 11.4 1.17 12.3 1.32 13.2 1.48 14.1 1.66 14.9 1.83 15.6 2.01 16.3 2.18 17.0 2.36 17.6 2.53 2100 10.7 1.29 11.8 1.33 12.7 1.47 13.5 1.65 14.4 1.84 15.1 2.00 15.9 2.20 16.6 2.38 2200 11.2 1.48 12.1 1.51 13.1 1.64 13.9 1.83 14.6 2.01 15.4 2.20 16.2 2.38 2300 11.6 1.70 12.5 1.71 13.4 1.83 14.2 2.01 15.0 2.20 15.7 2.41
50 100 150 200 250 300 350 400 450 500
r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW
EXTERNAL STATIC PRESSURE (Pa)
Table 8 — Fan Performance (SI), 50LJQ008 (50 Hz) — Vertical Discharge Units
AIRFLOW
(L/s) 1100 8.7 0.42 10.1 0.59 11.1 0.75 12.2 0.93 13.1 1.12 14.0 1.30 14.8 1.51 15.7 1.77 16.4 2.02 17.2 2.35
1200 9.3 0.52 10.5 0.69 11.6 0.87 12.6 1.05 13.5 1.26 14.3 1.46 15.1 1.66 15.9 1.88 16.7 2.14 17.4 2.44 1300 9.8 0.64 11.0 0.81 12.1 1.01 13.0 1.20 13.9 1.41 14.7 1.63 15.5 1.84 16.2 1.98 16.9 2.29 17.6 2.56 1400 10.4 0.77 11.5 0.94 12.6 1.16 13.5 1.37 14.3 1.58 15.1 1.80 15.9 2.04 16.6 2.27 17.3 2.51 1500 11.0 0.92 12.0 1.10 13.0 1.33 13.9 1.56 14.7 1.78 15.5 2.00 16.3 2.25 17.0 2.50 1600 11.6 1.08 12.6 1.28 13.5 1.50 14.4 1.76 15.2 2.00 16.0 2.23 16.7 2.47 1700 12.2 1.26 13.1 1.48 14.0 1.70 14.9 1.97 15.7 2.23 16.4 2.48
50 100 150 200 250 300 350 400 450 500
r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW
EXTERNAL STATIC PRESSURE (Pa)
Table 9 — Fan Performance (SI), 50LJQ012 (50 Hz) — Vertical Discharge Units
AIRFLOW
(L/s) 1300 8.4 0.37 9.6 0.51 10.8 0.61 11.7 0.69 12.6 0.81 13.3 0.90 14.3 1.05 15.1 1.27 15.9 1.48 16.7 1.67
1400 8.8 0.46 10.0 0.59 11.1 0.71 12.0 0.82 12.9 0.93 13.7 1.04 14.5 1.17 15.4 1.35 16.2 1.56 16.8 1.75 1500 9.2 0.55 10.4 0.68 11.5 0.81 12.4 0.94 13.2 1.06 14.0 1.19 14.8 1.26 15.6 1.44 16.4 1.62 17.1 1.83 1600 9.7 0.65 10.8 0.79 11.8 0.93 12.8 1.07 13.6 1.19 14.4 1.33 15.1 1.46 15.8 1.59 16.5 1.72 17.3 1.91 1700 10.2 0.75 11.2 0.91 12.2 1.06 13.1 1.20 13.9 1.34 14.7 1.48 15.4 1.63 16.1 1.76 16.7 1.89 17.4 2.04 1800 10.6 0.87 11.7 1.05 12.6 1.20 13.5 1.35 14.3 1.51 15.0 1.65 15.7 1.80 16.4 1.95 17.1 2.10 17.7 2.24 1900 11.1 1.01 12.1 1.19 13.0 1.35 13.9 1.52 14.7 1.68 15.4 1.84 16.1 1.99 16.8 2.14 17.4 2.31 18.0 2.46 2000 11.6 1.16 12.5 1.35 13.4 1.52 14.3 1.69 15.0 1.86 15.8 2.04 16.5 2.21 17.1 2.36 17.7 2.53 2100 12.0 1.32 13.0 1.53 13.8 1.70 14.6 1.88 15.4 2.07 16.1 2.25 16.8 2.43 2200 12.5 1.50 13.4 1.71 14.3 1.91 15.1 2.09 15.8 2.29 16.5 2.48 2300 13.0 1.70 13.9 1.91 14.7 2.13 15.5 2.31 16.2 2.52
r/s Wheel Speed (Revolutions per Second) Bkw — Fan Shaft Power (kW)
NOTES:
1. Boldface indicates field-supplied drive required.
2. indicates field-supplied motor and drive required.
3. Maximumusableoutput power (BkW) on the 50LJQ008 unit is1.79
(2.40 Bhp) with standard 1.12 BkW (1.5 hp) motor. The maximum usable output power (BkW) increases to 2.16 (2.90 Bhp) on the 50LJQ012 unit with standard 1.5 BkW (2 hp) motor. Extensive
50 100 150 200 250 300 350 400 450 500
r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW r/s BkW
LEGEND
EXTERNAL STATIC PRESSURE (Pa)
motor and electrical testing on the Weathermaker I units ensures that the full power range of the motor can be utilized with confi­dence. Using the fan motors up to the power ratings shown will not result in nuisance tripping orprematuremotor failure. Unit war­ranty will not be affected.
4. Use of field-supplied motor may affect wire sizing. Contact Carrier representative to verify.
5. Values include losses for filters, unit casings and wet coils.
6. Motor drive range is 10.30 to 14.70 r/s (622 to 882 rpm) on the 50LJQ008and11.50to 15.00 r/s (692 to 896 rpm) on the 50LJQ012. All other r/s (rpms) will require a field-supplied drive.
15
Table 10 — Fan Performance (English), 50LJQ008 (50 Hz) — Horizontal Discharge Units
AIRFLOW
(Cfm)
2200 459 0.42 549 0.62 625 0.83 691 1.06 753 1.31 805 1.58 842 1.87 857 2.16 851 2.45 823 2.70 2400 482 0.50 569 0.71 645 0.95 708 1.18 768 1.40 824 1.72 872 2.01 909 2.32 931 2.64 935 2.96 2600 507 0.59 592 0.82 663 1.08 727 1.32 784 1.58 839 1.87 891 2.17 936 2.49 973 2.82 999 3.16 2800 533 0.71 615 0.95 683 1.20 747 1.49 802 1.75 855 2.04 906 2.35 954 2.67 997 3.01 1034 3.36 3000 559 0.83 637 1.09 704 1.35 765 1.66 823 1.94 872 2.22 921 2.54 969 2.88 1014 3.22 3200 585 0.96 660 1.24 727 1.52 785 1.83 841 2.15 892 2.45 939 2.76 984 3.10 ———— 3400 610 1.10 682 1.41 750 1.72 806 2.01 860 2.36 912 2.69 958 3.01 1002 3.34 ———— 3600 636 1.25 707 1.60 772 1.93 828 2.23 880 2.57 930 2.95 978 3.29 —————— 3800 661 1.41 733 1.82 795 2.15 852 2.48 901 2.80 949 3.20 ———————
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
EXTERNAL STATIC PRESSURE (in. wg)
Table 11 — Fan Performance (English), 50LJQ012 (50 Hz) — Horizontal Discharge Units
AIRFLOW
(Cfm)
3000 484 0.55 560 0.70 631 0.87 690 1.03 747 1.20 800 1.38 850 1.52 879 1.38 925 1.81 964 1.92 3200 505 0.66 579 0.81 646 0.98 708 1.16 761 1.34 812 1.51 862 1.71 908 1.85 944 2.01 984 2.09 3400 527 0.78 599 0.93 664 1.11 724 1.30 775 1.48 827 1.67 873 1.85 920 2.07 963 2.21 1001 2.31 3600 548 0.92 619 1.05 680 1.24 738 1.43 794 1.64 840 1.83 888 2.04 931 2.23 976 2.47 1017 2.62 3800 571 1.08 639 1.19 698 1.39 756 1.60 810 1.81 856 2.02 901 2.23 945 2.44 986 2.65 1029 2.89 4000 593 1.25 659 1.35 717 1.56 773 1.78 823 1.98 875 2.22 915 2.42 960 2.65 1000 2.87 1039 3.10 4200 616 1.45 680 1.53 737 1.74 789 1.95 841 2.18 889 2.41 934 2.65 972 2.87 1015 3.12 1053 3.34 4400 639 1.67 701 1.73 757 1.92 807 2.16 858 2.41 903 2.62 951 2.89 990 3.12 1028 3.36 4600 662 1.91 722 1.95 777 2.13 827 2.38 874 2.62 921 2.87 965 3.11 1008 3.39 ———— 4800 686 2.17 744 2.20 797 2.36 846 2.62 891 2.85 938 3.14 980 3.37 —————— 5000 710 2.45 766 2.47 816 2.61 866 2.86 910 3.12 934 3.39 ———————
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
EXTERNAL STATIC PRESSURE (in. wg)
Table 12 — Fan Performance (English), 50LJQ008 (50 Hz) — Vertical Discharge Units
AIRFLOW
(Cfm)
2200 503 0.50 585 0.71 653 0.92 716 1.15 772 1.38 824 1.63 884 1.95 934 2.30 916 2.64 1019 3.09 2400 534 0.61 613 0.84 677 1.06 738 1.30 794 1.55 844 1.81 892 2.08 944 2.40 987 2.76 1039 3.20 2600 565 0.74 639 0.97 703 1.20 761 1.46 816 1.74 866 2.01 913 2.29 957 2.58 1004 2.91 1050 3.31 2800 597 0.89 665 1.12 731 1.40 786 1.66 839 1.93 889 2.23 935 2.52 978 2.62 1019 3.13 1061 3.47 3000 629 1.06 694 1.29 759 1.59 812 1.88 862 2.15 911 2.46 957 2.78 1000 3.09 1040 3.41 3200 662 1.25 724 1.50 785 1.80 840 2.11 887 2.41 934 2.71 980 3.04 1022 3.38 ———— 3400 696 1.46 756 1.73 811 2.02 868 2.37 914 2.69 959 3.00 1003 3.32 —————— 3600 729 1.69 787 1.98 839 2.27 894 2.64 942 2.99 984 3.32 ———————— 3800 763 1.95 819 2.27 869 2.56 920 2.92 970 3.31 —————————
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
EXTERNAL STATIC PRESSURE (in. wg)
Table 13 — Fan Performance (English), 50LJQ012 (50 Hz) — Vertical Discharge Units
AIRFLOW
(Cfm)
3000 532 0.64 605 0.81 670 0.97 725 1.12 778 1.28 825 1.43 874 1.60 926 1.82 974 2.11 1012 2.36 3200 557 0.75 628 0.93 690 1.10 746 1.28 796 1.44 844 1.61 888 1.70 934 1.94 988 2.18 1025 2.47 3400 583 0.88 651 1.06 711 1.25 767 1.44 815 1.61 863 1.79 907 1.97 947 2.14 991 2.32 1038 2.57 3600 609 1.01 674 1.22 732 1.42 787 1.61 836 1.80 880 1.98 926 2.18 966 2.36 1004 2.54 1045 2.74 3800 535 1.16 698 1.39 755 1.59 808 1.80 857 2.01 901 2.20 943 2.39 985 2.60 1023 2.79 1059 2.98 4000 662 1.33 722 1.57 778 1.78 829 2.01 878 2.22 922 2.44 962 2.63 1003 2.84 1042 3.06 1078 3.26 4200 689 1.52 746 1.77 801 1.99 851 2.23 898 2.45 943 2.69 983 2.91 1021 3.11 1060 3.34 4400 715 1.72 772 1.99 825 2.22 873 2.46 919 2.71 963 2.94 1004 3.19 1042 3.41 ———— 4600 742 1.94 797 2.22 848 2.48 896 2.72 940 2.98 984 3.22 1025 3.48 —————— 4800 770 2.18 823 2.46 872 2.75 919 3.00 963 3.27 ————————— 5000 797 2.44 849 2.73 897 3.04 943 3.30 ————————————
Rpm — Wheel Speed (Revolutions per Minute) Bhp — Fan Shaft Power (Brake Horsepower)
NOTES:
1. Boldface indicates field-supplied drive required.
2. indicates field-supplied motor and drive required.
3. Maximumusable output power (Bhp) on the50LJQ008 unit is 2.40 (1.79 BkW) with standard 1.5hp (1.12 BkW) motor. The maximum usable output power (Bhp) increases to 2.90 Bhp (2.16 BkW) on the 50LJQ012 unit with standard 2 hp (1.5 BkW) motor.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
LEGEND
EXTERNAL STATIC PRESSURE (in. wg)
Extensive motor and electrical testing ontheWeathermakerI units ensures that the full power range of the motor can be utilized with confidence. Using the fan motors up to the power ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
4. Use of field-supplied motor may affect wire sizing. Contact Carrier representative to verify.
5. Values include losses for filters, unit casings, and wet coils.
6. Motor drive range is 622 to 882 rpm (10.30 to 14.70 r/s) on the 50LJQ008and692to896rpm (11.50to 15.00 r/s) on the 50LJQ012. All other rpms (r/s) will require a field-supplied drive.
16
START-UP
IMPORTANT:Energizecrankcase heaters 24 hours prior to base unit start-up to remove entrapped refrigerant from the oil. Heaters are energized as long as there is power to the unit.
Unit Preparation — Make sure that unit has been in-
stalled in accordance with these installation instructions and applicable codes.
Return-Air Filters — Make sure correct filters are in-
stalled in unit (see Tables 1A and 1B). Do not operate unit without return-air filters.
Compressor Mounting — Compressors are inter-
nally spring mounted. Do not loosen or remove compressor holddown bolts.
Internal Wiring — Check all electrical connections in
unit control boxes; tighten as required.
Refrigerant Service Ports — Each refrigerant sys-
tem has 3 Schrader-type service gage ports: one on the suc­tion line, one on the liquid line and one on the compressor discharge line. Be sure that caps on the ports are tight.
Cooling — To start unit, turn on main power supply. Set
system selector switch at COOL position and fan switch at AUTO. position. Adjust thermostat to a setting below room temperature. Compressor starts on closure of contactor.
Check unit charge. Refer to Refrigerant Charge section on
page 20.
Reset thermostat at a position above room temperature.
Compressor will shut off. TO SHUT OFF UNIT — Set system selector switch at OFF
position. Resetting thermostat at a position above room tem­perature shuts unit off temporarily until space temperature exceeds thermostat setting.
Heating — To start unit, turn on main power supply.
Set thermostat at HEATposition and a setting above room
temperature, fan at AUTO. position.
First stage of thermostat energizes Compressor no. 1 and Compressor no. 2; second stage energizes the electric heat (where applicable). Check heating effectsat air supply grille(s).
If unit does not energize, reset limit switch (located on indoor-fan scroll) by depressing button located between ter­minals on the switch.
TO SHUT OFF UNIT — Set system selector switch at OFF position. Resetting heating selector lever below room tem­perature will shut unit off temporarily until the space tem­perature falls below thermostat setting.
Safety Relief — A soft-solder joint at the suction line
fitting provides pressure relief under abnormal temperature and pressure conditions.
Ventilation (Continuous Fan) — Set fan and sys-
tem selector switches at ON and OFF positions, respec­tively. Indoor fan operates continuously to provide constant air circulation.
Operating Sequence (See Fig. 20)
COOLING — With accessory economizer — Upon a re- quest for cooling from the space thermostat, terminals Y1 and G will be energized with 24 v.As a result, the indoor-fan contactor (IFC), indoor-fan motor (IFM), and reversing valve solenoids (RVS1 and RVS2) will be energized and the
economizer damper blade will open to minimum position. Note that if the indoor fan is on when the space thermostat calls for cooling, terminal G is already energized and the economizer damper blade is at minimum position.
If the outdoor-air temperature is below the outdoor-airther­mostat (OAT) setting, then the position of the damper blade will be determined by the temperature of the discharge air as sensed by the discharge-air thermistor (DAT). The damper blade will slide open for 5 seconds, and rest for 30 seconds until the proper discharge-air temperature is obtained. The damper blade will modulate to different positions to main­tain this discharge-air temperature.
If the thermostat calls for a second stage of cooling by supplying 24 v to Y2, the outdoor-fan contactor (OFC) and Compressor contactor no. 1 (C1) will be energized, which will bring on the outdoor fan and Compressor no. 1, respectively.
When the thermostat is satisfied, Y2 will be deenergized first, which will deenergize the outdoor fan and Compressor no. 1. When the indoor fan is deenergized, the economizer will return to a fully closed position.
If the outdoor-air temperature is above the OAT setting, the economizer will move to the minimum position and the unit will operate as described in Cooling, Units Without Accessory Economizer section below.
Without accessory economizer — Upon a request for cool­ing from the space thermostat, terminals Y1 and G will be energized with 24 v. As a result, the indoor-fan contactor (IFC), outdoor-fan contactor (OFC) and Compressor con­tactor no. 1 (C1) will be energized, which in turn will en­ergize the indoor fan, outdoor fan and Compressor no. 1, respectively.
If the space thermostat calls for a second stage of cooling by supplying 24 v to Y2, Compressor contactor no. 2 (C2) will be energized, thus energizing Compressor no. 2.
When the space thermostat is satisfied, Y2 will be de­energized first, which will deenergize Compressor no. 2.
Upon a further drop in space temperature, Y1 will be de­energized which will deenergize Compressor no. 1, and the outdoor and indoor fans.
HEATING — Upon a request for heating from the space ther­mostat, terminal W1 will be energized with 24 v. On units with economizer, the economizer damper blade will move to minimum position regardless of the outdoor-air tempera­ture, and the unit will operate as described in Cooling, With­out Accessory Economizer section above. The IFC, OFC, C1 and C2 will be energized. The reversing valves switch position and the indoor fan, outdoor fan, Compressor no. 1, and Compressor no. 2 are energized.
If the space temperature continues to fall while W1 is en­ergized, W2 will be energized with 24 v, and the heater con­tactor(s) (HC) willbe energized, which will energize the electric heater(s).
When the space thermostat is satisfied, W2 will be de­energized first, and the electric heater(s) will be deenergized.
Upon a further rise in space temperature, W1 will be de­energized,and the reversing valve solenoids (RVS1and RVS2) will be energized. On units with economizer, the econo­mizer damper blade will move to the fully closed position.
DEFROST — When the temperature of the outdoor coil drops below 28 F as sensed by the defrost thermostat (DFT2) and the defrost timer is at the end of a timed period (adjustable at 30, 50 or 90 minutes). RVS1 and RVS2 are energized and the OFC is deenergized. This switches the
17
NOTES:
1. In heating mode, economizer damper blade will move to the mini­mum position, and unit will operate as described for units without economizer, regardless of outdoor air temperature.
2. The temperatures given in the graph are for demonstration pur­poses only and may vary depending on which thermostat is used.
LEGEND
C—Contactor HC Heater Contactor IFC — Indoor-Fan Contactor OAT — Outdoor-Air Thermostat OFC — Outdoor-Fan Contactor RVS — Reversing Valve Solenoid W—Heating Stage X—Contact Energized Y—Cooling Stage
UNITS WITH ECONOMIZER
AVERAGE OUTDOOR-AIR TEMPERATURE GREATER THAN OAT SETTING
Thermostat Demand G Y1 Y2 W1 W2 C1 C2 IFC OFC RVS1 RVS2 HC Second Stage Cooling XX X X X X X X X
First Stage Cooling XX X X X X X Deadband (Offset) First Stage Heating XXXX Second Stage Heating XXXXX X
AVERAGE OUTDOOR-AIR TEMPERATURE LESS THAN OAT SETTING, BUT GREATER THAN −2 C (28 F)
Thermostat Demand G Y1 Y2 W1 W2 C1 C2 IFC OFC RVSI RVS2 HC Second Stage Cooling XXX X X X X X
First Stage Cooling XX X X X Deadband(Offset) First Stage Heating XXXX Second Stage Heating XXXXX X
UNITS WITHOUT ECONOMIZER
AVERAGE OUTDOOR-COIL TEMPERATURE LESS THAN −2C (28 F)
Thermostat Demand G Y1 Y2 W1 W2 C1 C2 IFC OFC RVSI RVS2 HC Second Stage Cooling XX X X X X X X X
First Stage Cooling XX X X X X X Deadband (Offset) First Stage Heating XXXX Second Stage Heating XXXXX X
AVERAGE OUTDOOR-COIL TEMPERATURE GREATER THAN −2 C (28 F)
Thermostat Demand G Y1 Y2 W1 W2 C1 C2 IFC OFC RVSI RVS2 HC Second Stage Cooling XX X X X X X X X
First Stage Cooling XX X X X X X Deadband (Offset) First Stage Heating XXXX Second Stage Heating XXXXX X
Fig. 20 — Typical Operating Sequence
18
position of the reversing valves and shuts off the outdoor fan. The electric heaters (if installed) will be energized. On units with economizer,the economizer damperblade will move to the fully closed position.
The unit continues to defrost until the coil temperature as measured by DFT2 reaches 65 F or the duration of defrost cycle completes a 10-minute period.
During the defrost mode, if circuit 1 defrosts first, RVS1 will oscillate between heating and cooling modes until the defrost mode is complete.
At the end of the defrost cycle, the electric heaters (if in­stalled) will be deenergized; the reversing valves switch and the outdoor-fan motor will be energized. On units with econo­mizer, the economizer damper blade will move to the mini­mum position. The unit will now operate in the heating mode.
If the space thermostat is satisfied during a defrost cycle, the unit will continue in the defrost mode until the time or temperature constraints are satisfied.
SERVICE
When servicing unit, shut off all electrical power to unit to avoid shock hazard or injury from rotating parts.
Cleaning — Inspect unit interior at the beginning of each
heating and cooling season and as operating conditions require.
Fig. 21 — Cleaning Outdoor Coil
INDOOR COIL
1. Turn unit power off. Remove indoor coil access panel.
2. If accessory economizer is installed, remove economizer
by disconnecting Molex plug and removing economizer mounting screws. Refer to Accessory Economizer Instal­lation Instructions for more details.
3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dishwasher
detergent in a pressurized spray canister.Washboth sides of coil and flush with clean water. For best results, back­flush toward return-air section to remove foreign material.
5. Flush condensate pan after completion.
6. Reinstall economizer and filters.
7. Reconnect wiring.
8. Replace access panels. OUTDOOR COIL — Inspect coil monthly. Clean outdoor
coil annually, and as required by location and outdoor air conditions.
2-Row Coils— Clean coil as follows:
1. Turn off unit power.
2. Remove top panel screws on outdoor-coil end of unit.
3. Remove outdoor-coil corner post. See Fig. 21. To hold
top panel open, place coil corner post between top panel and center post. See Fig. 22.
4. Remove device holding coil sections together at return
end of outdoor coil. Carefully separate the outer coil sec­tion 75 to 100 mm (3 to 4 in.) from the inner section. See Fig. 23.
5. Use a water hose or other suitable equipment to flush down
between the 2 coil sections to remove dirt and debris. Clean the outer surfaces with a stiff brush in the normal manner.
Fig. 22 — Propping Up Top Panel
Fig. 23 — Separating Coil Sections
6. Reposition the outer coil panel section and remove the coil corner post from between the top panel and center post. Secure the sections together.
7. Install the coil corner post, coil center post and replace all screws.
19
CONDENSATE DRAIN — Check and clean each year at start of cooling season. In winter, keep drain dry or protect against freeze-up.
FILTERS — Clean or replace at start of each heating and cooling season, or more often if operating conditions require it. Replacement filters must be same dimensions as original filters.
OUTDOOR-AIR INLET SCREENS — Clean screens with steam or hot water and a mild detergent. Do not use dis­posable filters in place of screens.
Lubrication
COMPRESSORS — Each compressor is charged with cor­rect amount of oil at the factory.
FAN-MOTOR BEARINGS — Fan motor bearings are of
the permanently-lubricated type. No further lubrication is required. No lubrication of outdoor- or indoor-fan motors is
required.
Outdoor-Fan Adjustment (Fig. 24)
Refrigerant Charge — Amount of refrigerant charge
is listed on the unit nameplate (also refer to Tables 1A and 1B). Refer to Carrier Standard Service Techniques Manual, Chapter 1, Refrigerants section.
Unit panels must be in place when unit is operating dur-
ing charging procedure. LOW CHARGE HEATING OR NO CHARGE — Use stand-
ard evacuating techniques. After evacuating system, weigh in the specified amount of refrigerant (refer to Tables 1A and 1B).
LOW CHARGE COOLING — Use Cooling Charging Chart, Fig. 25 and 26. Vary refrigerant until the conditions of the chart are met. Note the charging chart is different from type normally used. Chart is based on charging the units to the correct superheat for the various operating conditions. Ac­curate pressure gage and temperature sensing device are re­quired. Connect the pressure gage to the service port on the suction line. Mount the temperature sensing device on the suction line and insulate is so that outdoor ambient tempera­ture does not affect the reading. Indoor-air L/s (cfm) must be within the normal operating range of the unit.
TO USE COOLING CHARGING CHART— Take the out­door ambient temperature and read the suction pressure gage. Refer to chart to determine what suction temperature should be. If suction temperature is high, add refrigerant. If suction temperature is low, carefully blow some of the charge. Re­check the suction pressure as charge is adjusted.
Example: (Fig. 26) (Circuit 1)
Outdoor Temperature ....................29C(85F)
Suction Pressure ...................483kPa(70psig)
Suction Temperature should be .............7C(46F)
(Suction Temperature may vary ± 3° C (5° F)
Fig.24 — Outdoor-Fan Adjustment
1. Shut off unit power supply.
2. Remove outdoor-fan assembly (grille, motor,motor cover and fan) and loosen fan hub setscrews.
3. Adjust fan height as shown in Fig. 24.
4. Tighten setscrews and replace outdoor-fan assembly.
If Chargemastert charging device is used, temperature and pressure readings must be accomplished using the charging chart.
20
Fig. 25 — Cooling Charging Charts, 50LJQ008
Fig. 26 — Cooling Charging Charts, 50LJQ012
21
Copyright 1992 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 015-015 Printed in U.S.A. Form 50LJQ-C1SI Pg 24 1-92 Replaces: New
Loading...