Carrier 11-808-427-01 User Manual

Page 1
RRTTUU OOppeenn
IInnssttaallllaattiioonn aanndd SSttaarrtt--uupp GGuuiiddee
CARRIER CORPORATION ©2012 A member of the United Technologies Corporation family · Stock symbol UTX · Catalog No. 11-808-427-01 · 6/13/2012
Page 2
Page 3
Introduction .................................................................................................................................................................. 1
Installation ................................................................................................................................................................... 5
Table of Contents
What is the RTU Open controller? ...................................................................................................................... 1
Specifications ........................................................................................................................................................ 3
Safety considerations........................................................................................................................................... 4
Field-supplied hardware ...................................................................................................................................... 5
To mount the RTU Open ....................................................................................................................................... 6
To wire the controller for power.......................................................................................................................... 7
Using the rooftop equipment control power transformer ................................................................... 8
Using an auxiliary control power transformer ...................................................................................... 8
To set the RTU Open's address ........................................................................................................................... 9
To set the RTU Open's communications protocol and baud rate ............................................................... 10
Wiring the RTU Open to the MS/TP network ................................................................................................. 11
Wiring specifications ........................................................................................................................... 11
To wire the controller to the network ................................................................................................. 11
Wiring inputs and outputs ................................................................................................................................ 12
Input wiring specifications .................................................................................................................. 13
Inputs ................................................................................................................................................... 14
Binary outputs ..................................................................................................................................... 14
Analog output ...................................................................................................................................... 14
To wire inputs and outputs ................................................................................................................. 14
Wiring sensors to inputs ................................................................................................................................... 18
Field-supplied sensor hardware ......................................................................................................... 19
Wiring an SPT sensor .......................................................................................................................... 20
Rnet wiring specifications ........................................................................................................ 20
To wire the SPT sensor to the controller ................................................................................. 21
Wiring a Supply Air Temperature sensor ............................................................................................ 22
Wiring specifications ................................................................................................................ 22
To wire the SAT sensor to the controller ................................................................................. 22
Wiring a Duct Air Temperature sensor ............................................................................................... 22
Wiring specifications ................................................................................................................ 23
To wire a duct sensor to the controller ................................................................................... 23
Wiring an Outdoor Air Temperature sensor ....................................................................................... 23
Wiring specifications ................................................................................................................ 24
To wire an OAT sensor to the controller .................................................................................. 24
Wiring a CO2 sensor ............................................................................................................................ 24
Wiring specifications ................................................................................................................ 25
To wire the CO2 sensor to the controller ................................................................................ 25
Wiring an Outdoor Air Quality sensor ................................................................................................. 26
Wiring specifications ................................................................................................................ 27
To wire the OAQ sensor to the controller ................................................................................ 27
Wiring a Relative Humidity sensor ..................................................................................................... 27
Wiring specifications ................................................................................................................ 28
To wire the RH sensor to the controller................................................................................... 28
Wiring a Humidistat ............................................................................................................................. 28
Wiring specifications ................................................................................................................ 29
To wire a humidistat to the controller ..................................................................................... 29
Wiring an enthalpy switch ................................................................................................................... 29
Wiring specifications ................................................................................................................ 30
To wire an enthalpy switch (outdoor air) to the controller ..................................................... 30
To wire an enthalpy switch (differential) to the controller...................................................... 32
RTU Open i
Page 4
Table of Contents
Start-up ....................................................................................................................................................................... 36
Sequence of Operation ............................................................................................................................................. 43
Troubleshooting ......................................................................................................................................................... 56
Compliance ................................................................................................................................................................ 58
Appendix A: RTU Open Points/Properties .............................................................................................................. 59
Wiring a status switch ......................................................................................................................... 32
Wiring specifications ................................................................................................................ 32
To wire a status switch to the controller ................................................................................. 33
Wiring a compressor safety ................................................................................................................ 33
Wiring specifications ................................................................................................................ 33
To wire a compressor safety input to the controller ............................................................... 34
Wiring an occupancy switch or door contact ..................................................................................... 34
Wiring specifications ................................................................................................................ 34
To wire an occupancy switch or door contact ......................................................................... 35
Service Test ......................................................................................................................................................... 37
Configuring the RTU Open's properties .......................................................................................................... 38
Unit Configuration properties ............................................................................................................. 38
Setpoint properties.............................................................................................................................. 40
Service Configuration properties ........................................................................................................ 41
Occupancy ........................................................................................................................................................... 43
Supply fan ........................................................................................................................................................... 44
Cooling ................................................................................................................................................................. 44
Economizer ......................................................................................................................................................... 45
Power Exhaust .................................................................................................................................................... 46
Unoccupied Free Cooling .................................................................................................................................. 46
Optimal Start ...................................................................................................................................................... 46
Enthalpy control ................................................................................................................................................. 47
Indoor Air CO2 .................................................................................................................................................... 47
Heating ................................................................................................................................................................ 48
Heat Pump operation ........................................................................................................................................ 49
Dehumidification ............................................................................................................................................... 49
Demand Limiting ............................................................................................................................................... 50
Door contact ....................................................................................................................................................... 50
Remote occupancy ............................................................................................................................................ 50
Fire Shutdown .................................................................................................................................................... 50
Compressor Safety ............................................................................................................................................ 50
Fan Status ........................................................................................................................................................... 51
Filter status ......................................................................................................................................................... 51
Alarms ................................................................................................................................................................. 51
Linkage ................................................................................................................................................................ 53
Linkage Air Source Modes ................................................................................................................................ 55
Serial number ..................................................................................................................................................... 56
LED's .................................................................................................................................................................... 56
Replacing the RTU Open's battery .................................................................................................................. 57
FCC Compliance ................................................................................................................................................. 58
CE Compliance ................................................................................................................................................... 58
BACnet Compliance........................................................................................................................................... 58
Status................................................................................................................................................................... 59
Unit Configuration .............................................................................................................................................. 60
Setpoints ............................................................................................................................................................. 63
Alarm Configuration .......................................................................................................................................... 67
Service Configuration ........................................................................................................................................ 68
Maintenance ....................................................................................................................................................... 70
Alarms ................................................................................................................................................................. 71
ii RTU Open
Page 5
Table of Contents
Appendix B: Single Point Linkage and Device Address Binding ............................................................................ 75
Index ........................................................................................................................................................................... 77
Linkage ................................................................................................................................................................ 73
I/O Points ............................................................................................................................................................ 73
Single Point Linkage ......................................................................................................................................... 75
Device Address Binding .................................................................................................................................... 76
RTU Open iii
Page 6
Page 7

What is the RTU Open controller?

J12

Introduction

The RTU Open controller is available as an integrated component of a Carrier rooftop unit, or as a field­installed retrofit product. Its internal application programming provides optimum rooftop performance and energy efficiency. RTU Open enables the unit to run in 100% stand-alone control mode or it can communicate to the Building Automation System (BAS).
On board DIP switches allow you to select the baud rate and choose one of the following protocols:
BACnet
Modbus
Johnson N2
LonWorks
Carrier’s diagnostic display tools such as BACview®6 Handheld or Virtual BACview can be used with the RTU Open controller via the
Access Port. See illustration on the following page.
RTU Open 1
Page 8
Introduction
2 RTU Open
Page 9

Specifications

J12
J13
Driver drv_rtuopn_std
Power 24 Vac ±10%, 50–60 Hz
20 VA power consumption (26 VA with a BACview device attached) 26 Vdc (25 V min, 30 V max) Single Class 2 source only, 100 VA or less
Access port
To connect a BACview6 Handheld device, Virtual BACview application, or Field Assistant
Rnet port
For SPT sensors and a BACview6 device in any of the following combinations, wired in a daisy-chain configuration:
1 SPT Plus or SPT Pro
1–4 SPT Standards
1–4 SPT Standards, and 1 SPT Plus or SPT Pro
Any of the above combinations, plus a BACview
6
device, but no more than 6
devices total
Comm Option port For communication with the LonWorks Option Card.
Inputs 12 inputs:
Inputs 1 - 2: 4-20 mA only
Inputs 3, 5, 8, 9: Binary, 24 Vac
Inputs 6 - 7: Thermistor
Inputs 10 - 11: Thermistor
Rnet sensor
Binary outputs 8 relay outputs, contacts rated at 3 A max @ 24 Vac
Configured normally open.
Analog output 1 analog output
AO1: 2 - 10 Vdc or 4-20 mA
Output resolution 10 bit D/A
Real-time clock Battery-backed real-time clock keeps track of time in event of power failure
Battery 10-year Lithium CR2032 battery provides a minimum of 10,000 hours of
data retention during power outages
Protection Incoming power and network connections are protected by non-replaceable
internal solid-state polyswitches that reset themselves when the condition that causes a fault returns to normal.
The power, network, and output connections are also protected against transient excess voltage/surge events lasting no more than 10 msec.
Status indicators LED's indicate status of communications, running, errors, power, and digital
outputs
RTU Open 3
Page 10
Introduction
NOTE

Safety considerations

Environmental operating range
-40 to 158°F (-40 to 70°C), 10–95% relative humidity, non-condensing Controllers should be mounted in a protective enclosure.
Vibration during operation: all planes/directions, 1.5G @ 20–300 Hz Shock during operation: all planes/directions, 5G peak, 11 ms Shock during storage: all planes/directions, 100G peak, 11 ms
Overall dimensions A:
B:
Mounting dimensions 7 mounting holes in various positions
Depth 1-11/16 in. (4.3 cm)
Weight 11.2 oz (0.32 kg)
BACnet support Conforms to the Advanced Application Controller (B-AAC) Standard Device
Profile as defined in ANSI/ASHRAE Standard 135-2004 (BACnet) Annex L
Listed by UL-873, FCC Part 15-Subpart B-Class A, CE EN50082-1997
6-1/2 in. (16.5 cm) 6-1/2 in. (16.5 cm)
Disconnect electrical power to the RTU Open before wiring it. Failure to follow this warning could cause electrical shock, personal injury, or damage to the controller.
4 RTU Open
Page 11

Field-supplied hardware

Installation

To install the RTU Open:
1 Mount the controller (page 6). 2 Wire the controller for power (page 7).
Using the rooftop equipment control power transformer (page 8). Using an auxiliary control power transformer (page 8).
3 Set the controller's address (page 9). 4 Wire inputs and outputs (page 12). 5 Wire sensors to the controller (page 18).
An RTU Open retrofit installation may require the following field-supplied components:
wiring harness: Part #OPN-RTUHRN
transformer – 24 Vac, 20 VA minimum
wiring
Application-dependent components:
carbon dioxide sensors
damper/damper actuator
differential pressure switch
enthalpy switch
fan status switch
door switch
fan section door switch
relative humidity sensor
remote occupancy contact
smoke detector
temperature sensors
RTU Open 5
Page 12
Installation

To mount the RTU Open

We highly recommend that you mount the RTU Open in the unit control panel!
When you handle the RTU Open:
Do not contaminate the printed circuit board with fingerprints, moisture, or any foreign material.
Do not touch components or leads.
Handle the board by its edges.
Isolate from high voltage or electrostatic discharge.
Ensure that you are properly grounded.
When you mount the RTU Open:
Do not locate in an area that is exposed to moisture, vibration, dust, or foreign material.
Follow NEC and local electrical codes.
Do not obstruct access for unit maintenance.
Protect from impact or contact during unit maintenance.
6 RTU Open
Page 13

To wire the controller for power

CAUTIONS
Screw the RTU Open into an enclosed panel using the mounting slots on the cover plate. Leave about 2 in. (5 cm) on each side of the controller for wiring.
The RTU Open is powered by a Class 2 power source. Take appropriate isolation measures when
mounting it in a control panel where non-Class 2 circuits are present.
Do not power pilot relays from the same transformer that powers the RTU Open.
Carrier controllers can share a power supply as long as you:
Maintain the same polarity Use the power supply only for Carrier controllers
The RTU Open has an operating range of 21.6 Vac to 26.4 Vac. If voltage measured at the RTU Open's
input terminals is outside this range, the RTU Open may not work properly.
In most cases, the RTU Open will be powered from the control power transformer provided with the
rooftop equipment. If you must use a separate control power transformer, additional precautions must be taken to ensure that the auxiliary transformer is in-phase with the rooftop equipment’s control power transformer. See Using an auxiliary control power transformer (page 8).
RTU Open 7
Page 14
Installation

Using the rooftop equipment control power transformer

J1
J1
J1
J1
J1
NOTE
Power
Run

Using an auxiliary control power transformer

must
J1
J1
J1
J1
NOTE
Power
Run
1 Remove power from the 24 Vac transformer. 2 Remove connector assembly from RTU Open's 3 If the rooftop equipment has thermostat connection terminals, connect wiring harness
wire 3 to C. Alternately, connect the control power transformer wires to J1 connector wires 1 (24
and
connector.
wire 1 to R,
Vac) and 3 (Gnd).
4 Apply power to the rooftop equipment. 5 Measure the voltage at the RTU Open’s
terminals 1 and 3 to verify that the voltage is within the
operating range of 21.6–26.4 Vac.
6 Attach harness to RTU Open connector
The harness and connector are keyed and must be oriented properly for correct installation.
7 Verify that the
LED is on and the
.
LED is blinking.
If you use a separate control power transformer, it is essential that the auxiliary transformer and the rooftop transformer are in-phase. You
verify this prior to connecting the auxiliary transformer to the RTU Open.
Follow these steps:
1 Verify the available primary voltage at the rooftop equipment. 2 Remove power from the rooftop equipment and install the appropriate auxiliary transformer. Follow the
manufacturer’s installation instructions.
3 Ground one leg of the auxiliary transformer’s secondary wiring. 4 Apply power to the rooftop equipment. Measure the potential between the rooftop equipment control
power and auxiliary transformer's secondary hot (non-grounded) legs. If the voltage measured is less than 5 volts, the transformers are in-phase; proceed to step 7. If you measure a voltage greater than 24 Vac, then the phases are reversed.
5 Correct the phase reversal by either of the following methods:
Remove the ground from the secondary at the auxiliary transformer and connect it to the other
secondary
Reverse the primary wiring at the auxiliary transformer
6 Repeat step 4 to rewire. 7 Remove connector assembly from RTU Open's 8 Connect the auxiliary transformer wires to
connector.
wires 1 (24 Vac) and 3 (Gnd).
9 Apply power to the transformer. 10 Measure the voltage at the RTU Open’s
- 1 and 3 to verify that the voltage is within the operating
range of 21.6–26.4 Vac.
11 Attach harness to RTU Open's connector
The harness connectors are keyed and must be oriented properly for correct installation.
12 Verify that the
LED is on and the
. See illustration below.
LED is blinking.
8 RTU Open
Page 15
Optional
J1
J1

To set the RTU Open's address

CAUTION
* Safety chain devices, field-installed - normally closed. Apply 24 Vac to this terminal
(jumper from
** Fire shutdown device, field-installed, configurable as normally open or closed
*** Enthalpy switch, field-installed - configurable as normally open or closed
The RTU Open's two rotary switches determine the RTU Open's MAC address when it is placed on an MS/TP network. The rotary switches define the MAC address portion of the RTU Open's BACnet device instance number, which is composed of the MS/TP network number and the MAC address. They also set the slave address on a Modbus or N2 network when less than 100. See the RTU Open Integration Guide for additional information on integration.
The MAC address of the controller must be unique on its network.
- 1 to
- 9) where no safety devices are installed.
RTU Open 9
Page 16
Installation
off
MSB (SW1) (10's
LSB (SW2) (1's
EXAMPLE
MSB (SW1
LSB (SW2
CAUTION

To set the RTU Open's communications protocol and baud rate

SW3
SW3
NOTE
1 Turn 2 Using the rotary switches, set the
the RTU Open's power. The controller reads the address each time you apply power to it.
To set the RTU Open’s address to 01, point the arrow on the
arrow on the
) switch to the ones digit.
) switch to 1.
) switch to the tens digit of the address, and set the
) switch to 0 and the
3 Turn on the RTU Open's power.
The factory default setting is 00 and must be changed to successfully install your RTU Open.
RTU Open's selection is determined by the network on which the controller will be installed. For Carrier BACnet implementations, select MS/TP @ 76.8 k as follows:
1 Power down the RTU Open. The controller reads the protocol and baud rate each time you apply power to
2 Set
it.
DIP switches are used to set the controller's protocol and baud rate. The protocol and speed
DIP switches 1, 2, and 4 to On to configure the controller for BACnet MS/TP and 76.8 k baud.
3 Power up the RTU Open.
Other protocols and baud rates are available. See the RTU Open Integration Guide for additional
instructions.
10 RTU Open
Page 17

Wiring the RTU Open to the MS/TP network

Wiring specifications

To wire the controller to the network

Gnd
24 Vac
Hot
Net +, Net -
Shield
NOTE
MSTP
MSTP
NOTE
The RTU Open communicates using BACnet on an MS/TP network segment communications at 9600 bps,
19.2 kbps, 38.4 kbps, or 76.8 kbps.
Wire the controllers on an MS/TP network segment in a daisy-chain configuration.
Install a BT485 on the first and last controller on a network segment to add bias and prevent signal distortions due to echoing.
See the MS/TP Networking and Wiring Installation Guide for more details.
Cable: 22 AWG or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire
Maximum length: 2000 feet (610 meters)
1 Pull the screw terminal connector from the controller's power terminals labeled 2 Check the communications wiring for shorts and grounds. 3 Connect the communications wiring to the BACnet port’s screw terminals labeled
.
Use the same polarity throughout the network segment.
4 Verify that the 5 Set DIP switches 1 and 2 to the appropriate baud rate. See the MSTP baud diagram on the RTU Open.
The default baud rate is 76.8 kbps.
Use the same baud rate for all controllers on the network segment.
jumper is set to
and
or
.
, and
.
RTU Open 11
Page 18
Installation

Wiring inputs and outputs

RTU Open Inputs and Outputs Table
Channel Number
Type
Signal
Function
Part Number
Wire/Terminal Numbers
Alternate Terminals
Input 1
AI
4-20 mA
CO2
33ZCT55CO2
33ZCSENSRH-02
J4
N/A
Input 2
AI
4-20 mA
CO2
33ZCT55CO2
33ZCSENSRH-02
J4 -
N/A
Input 3
BI
24 Vac
Compressor Safety **
N/A
J1 -
J5
Input 4
BI
24 Vac
Safety Chain *
N/A
J1
N/A
Input 5
BI
24 Vac
Fire Shutdown **
Field-supplied
J1
J5
Input 6
AI
10K
Supply Air Temperature
33ZCSENSAT
J2 - 1 & 2
N/A
Input 7
AI
10K
Outside Air Temperature
33ZCSENOAT
J2
N/A
Input 8
BI
24 Vac
Enthalpy **
33SENTHSW
J2
J5
Input 9
BI
24 Vac
Humidistat **
--HL—38MG-029
J5
N/A
Input 10
AI
10K
Space Temperature
33ZCT55SPT 33ZCT56SPT
J20 - 1 & 2
N/A
Input 11
AI
100K
Space Temperature Setpoint Adjust
33ZCT56SPT 33ZCT59SPT
J20
N/A Rnet
AI Zone Temperature
SPS / SPPL / SPP
J13
N/A
AO - 1
AO
Economizer
Economizer
Actuator-Field-supplied
J2
N/A
AO - 2
AO
N/A
Not used
N/A
J22
N/A
BO - 1
BO
N/A - Relay
Fan (G)
N/A
J1
N/A
6 Insert the power screw terminal connector into the RTU Open's power terminals. 7 Verify communication with the network by viewing a module status report.
OAQ Space Relative Humidity
33ZCT56CO2 33ZCSPTCO2 w/
33ZCASPCO2
- 5 & 6
2 & 3 OAQ Space Relative Humidity
33ZCT56CO2 33ZCSPTCO2 w/
33ZCASPCO2
Thermistor
Thermistor
Fan Status Filter Status Remote Occupancy Door Contact
Fan Status Filter Status Remote Occupancy Door Contact
Fan Status Filter Status Remote Occupancy Door Contact
Fan Status Filter Status Remote Occupancy Door Contact
CRSTATUS005A00 CRSTATUS005A00 Field-supplied Field-supplied
CRSTATUS005A00 CRSTATUS005A00 Field-supplied Field-supplied
33ZCSENDAT
CRSTATUS005A00 CRSTATUS005A00 Field-supplied Field-supplied
CRSTATUS005A00 CRSTATUS005A00 Field-supplied Field-supplied
2
- 9
- 10
- 3 & 2
- 6 & 7
- 7 & 8
- 5 & 6
***
- 3 & 4
***
- 1 & 2
***
12 RTU Open
Thermistor
Thermistor
33ZCT59SPT
- 3 & 4
- 1, 2, 3, 4
- 5 & 4
- 1 & 2
- 4
Page 19
Channel Number
Type
Signal
Function
Part Number
Wire/Terminal Numbers
Alternate Terminals
BO - 2
BO
N/A - Relay
Heat 2 (W2) Output
N/A
J1
N/A
BO - 3
BO
N/A - Relay
Heat 1 (W1) Output
N/A
J1
N/A
BO - 4
BO
N/A - Relay
Cool 2 (Y2) Output
N/A
J1
N/A
BO - 5
BO
N/A - Relay
Cool 1 (Y1) Output
N/A
J1
N/A
BO - 6
BO
N/A - Relay
Humidi-MiZer™
N/A
J11
N/A
BO - 7
BO
N/A - Relay
Reversing Valve
N/A
J11
N/A
BO - 8
BO
N/A - Relay
Power Exhaust
N/A
J11
N/A
Legend
AI
AO
BI
BO
Safety Chain Feedback
Run Enabled
J1

Input wiring specifications

Input
Maximum length
Minimum gauge
Shielding
- Analog Input
- Digital Input
* safeties are utilized. See To wire inputs and outputs (page terminations.
** Default input function
*** Parallel screw terminal at J5 (J5 - 1 = J2 - 6, J5 - 3 = J1 - 10, J5 - 5 = J1 - 2) may be used in place of the associated flying leads at the harness (Part #OPN-RTUHRN). See To wire inputs and outputs (page
- Analog Output
- Digital Output
- 24 Vac required at this wire to provide
14) for additional information on the RTU Open wiring harness assembly
status. Provide a jumper from J1 - 1 to
14) for additional information.
- 5
- 6
- 7
- 8
- 7 & 8
- 4 & 6
- 1 & 3
- 9 if no
Thermistor 1000 feet
(305 meters)
4-20 mA 3000 feet
(914 meters)
Binary input
1000 feet (305 meters)
SPT (RNET) 500 feet
(152 meters)
22 AWG Unshielded
22 AWG Unshielded
22 AWG Unshielded
22 AWG
Unshielded
4 conductor
RTU Open 13
Page 20
Installation

Inputs

These inputs...
Support this signal type...
Description

Binary outputs

NOTE

Analog output

To wire inputs and outputs

These RTU Open inputs accept the following signal types:
1, 2 4-20 mA The input resistance on the positive (+) terminal is 250 Ohms.
3, 5, 8, 9 Binary (24 Vac) 24 Vac voltage, resulting in a 25 mA maximum sense current
6, 7, 10 Thermistor 10 kOhm at 77° F
11 100k Potentiometer Typically used for 33CZT56SPT Setpoint Offset Potentiometer
The RTU Open has 8 binary outputs. You can connect each output to a maximum of 24 Vac/Vdc. Each output is a dry contact rated at 3 A, 24 V maximum, and is normally open.
To size output wiring, consider the following:
Total loop distance from the power supply to the controller, and then to the controlled device
Acceptable voltage drop in the wire from the controller to the controlled device
The Aux Power Out terminal is capable of supplying 24 Vdc to a 4-20 mA transducer, but the total current demanded must not exceed 40 mA. If the voltage measured from the Aux Power Out terminal to Gnd is less than 18 Vdc, you need to use an external power supply.
when the contacts are closed
Include the total distance of actual wire. For 2-conductor wires, this is twice the cable length.
Resistance (Ohms) of the chosen wire gauge
Maximum current (Amps) the controlled device requires to operate
The RTU Open has 1 analog output that supports voltage or current devices. The controlled device must share the same ground as the controller and have input impedance of 500 Ohms maximum for the 4-20 mA mode on AO - 1.
1 Turn off the RTU Open's power. 2 Connect the input wiring to the screw terminals on the RTU Open.
3 Turn on the RTU Open's power.
14 RTU Open
Page 21
AO - 1
0 - 10 Vdc/4-20 mA
Battery Jumper
In (Do not remove)
Format Jumper*
Out
W3
Input 11 mA Jumper
Out (mA not utilized on this channel)
Input 11 Thermistor
In (default position)
W5
Input 10 mA Jumper
Out (mA not utilized on this channel)
W6
Input 10 Thermistor Jumper
In (default position)
4 Set the appropriate jumpers on the RTU Open.
J3 W1 W2
W4
*Formatting the controller may result in lost information and should only be done under the guidance of Carrier Control Systems Support.
RTU Open 15
Optional
* Safety chain devices, field-installed - normally closed. Apply 24 Vac to this terminal
(jumper from
J1 - 1 to J1 - 9) where no safety devices are installed.
** Fire shutdown device, field-installed, configurable as normally open or closed
*** Enthalpy switch, field-installed - configurable as normally open or closed
Page 22
Installation
J4 Inputs
1 Turn off the RTU Open's power. 2 Connect the input and output wiring to the screw terminals on the RTU Open.
NOTE When utilizing the controller's 24 Vdc auxiliary power out, the total current demand for these two
input channels must not exceed 40 mA (100mA per channel).
NOTE J4 Analog Inputs 1 and 2 may be set for the following device types:
IAQ Sensor OAQ Sensor Space RH Sensor
J5 Inputs
The terminals for Inputs 3, 5, and 8 are available for use in place of the flying wire leads at Molex
connectors J1 and J2 identified below:
16 RTU Open
Page 23
3
Compressor Safety
Fan Status
5
Fire Shutdown
Fan Status
8
Enthalpy Switch
Fan Status
9
HumidiStat
Fan Status
Door Contact
NOTE J5 binary inputs 3, 5, and 8 are the same input channels as:
J1 wire 2, J5 - Input - 3 (Compressor Safety) J1 wire 10, J5 - Input - 5 (Fire Shutdown) J2 wire 6, J5 - Input - 8 (Enthalpy Switch).
These terminals are available for use in place of the flying wire leads at Molex connectors J1 and J2.
Binary inputs are configurable and may be used for the following functions:
Input Default input function Additional functions
Filter Status Remote Occupancy Door Contact
Filter Status Remote Occupancy Door Contact
J11 Outputs
Filter Status Remote Occupancy Door Contact
Filter Status Remote Occupancy
RTU Open 17
Page 24
Installation

Wiring sensors to inputs

NOTE
NOTE
ELECTRICAL SHOCK HAZARD
NOTE Output relay contacts rated at 3A, 24V maximum. Install pilot relays required by application.
J20 Analog Inputs 10 and 11 are reserved for a 10k Ohm space temperature sensor with an
NOTE
optional 100k Ohm offset potentiometer used for setpoint adjustment.
You may wire various sensors to the RTU Open's inputs. See the table below for details.
This document gives instructions for wiring the sensors to the RTU Open. For specific mounting and
wiring instructions, see the Carrier Sensors Installation Guide.
All field control wiring that connects to the RTU Open must be routed through the raceway built into the corner post. The raceway provides the UL-required clearance between high-and low-voltage wiring.
1 Pass the control wires through the hole provided in the corner post. 2 Feed the wires through the raceway to the RTU Open. 3 Connect the wires to the removable Phoenix connectors. 4 Reconnect the connectors to the board (where removed).
For rooftop unit installation, see the base unit installation instructions.
Failure to follow this warning could cause personal injury, death, and/or equipment damage.
Disconnect all power to the unit before performing maintenance or service. Unit may automatically start if power is not disconnected.
18 RTU Open
Page 25

Field-supplied sensor hardware

Sensor
Part numbers
Notes
The RTU Open controller is configurable with the following field-supplied sensors:
Space temperature sensor (page 20)
Supply air temperature sensor
SPS, SPPL, SPP, 33ZCT55SPT, 33ZCT56SPT, 33ZCT59SPT
33ZCSENSAT Factory-installed
(page 22)
Duct air temperature sensor
33ZCSENDAT
(page 22)
Outdoor air temperature sensor
33ZCSENOAT Factory-supplied with Economizer
(page 23)
CO2 sensor (page 24) 33ZCSENCO2, 33ZCT55CO2,
33ZCT56CO2
Required only for demand control ventilation - a dedicated 24-vac transformer is required
Outdoor air quality sensor (page
26)
Duct relative humidity sensor
33ZCTSENCO2 Optional with demand control
ventilation
33ZCSENDRH-02
(page 27)
Space relative humidity sensor
33ZCSENSRH-02
(page 27)
Humidistat (page 28) --HL—38MG-029
CO2 aspirator box (page 24) 33ZCASPCO2 Required for CO2 return duct/outside
air applications
Outdoor air enthalpy switch
33CSENTHSW
(page 29)
Return air enthalpy sensor (page 29)
33CSENTSEN Optional with
33CSSENTHSW
Filter status switch (page 32) CRSTATUS005A00
Fan status switch (page 32) CRSTATUS005A00 or field-
supplied
For specific details about sensors, see the Carrier Sensors Installation Guide.
RTU Open 19
Page 26
Installation

Wiring an SPT sensor

Sensor
Part #
Features
SPT Standard
Local access port
SPT Plus
Slide potentiometer to adjust setpoint
Local access port
SPT Pro
LCD display
Local access port
Rnet
NOTES
NOTE
The RTU Open is connected to a wall-mounted space temperature sensor to monitor room temperature.
An i-Vu® Open Control System offers the following SPT sensors:
SPS
No operator control
SPPL
MANUAL ON button to override schedule
LED to show occupied status
SPP
MANUAL ON button to override schedule
WARMER and COOLER buttons to adjust setpoint
INFO button to cycle through zone and outside air temperatures,
setpoints, and local override time
You wire SPT sensors to the RTU Open's
port. An Rnet can consist of any of the following combinations
of devices wired in a daisy-chain configuration:
1 SPT Plus or SPT Pro
1–4 SPT Standards
1–4 SPT Standards, and 1 SPT Plus or SPT Pro
6
Any of the above combinations, plus up to 2 BACview
devices, but no more than 6 devices total
If you have 2 BACview
6
devices, the second BACview6 device must have a separate power supply with the
same ground as the controller.
If the Rnet has multiple SPT Standard sensors, you must give each a unique address on the Rnet. See
the Carrier Sensors Installation Guide.
If the Rnet has multiple BACview devices, you must give each a unique address on the Rnet. See the
BACview Installation and User Guide.
Rnet wiring specifications
Use the specified type of wire and cable for maximum signal integrity.
Description 4 conductor, unshielded, CMP, plenum rated cable
Conductor 18 AWG
Maximum length 500 feet (152 meters)
Recommended coloring Jacket: White
UL temperature rating 32–167°F (0–75°C)
20 RTU Open
Wiring: Black, white, green, red
Page 27
Outer Jacket
Inner insulation
.25 in. (.6 cm)
NOTE
Connect this wire...
To this terminal...
Voltage 300 Vac, power limited
Listing UL: NEC CL2P, or better
To wire the SPT sensor to the controller
1 Partially cut, then bend and pull off the outer jacket of the Rnet cable(s). Do not nick the inner insulation.
Strip about .25 inch (.6 cm) of the inner insulation from each wire.
2 Wire each terminal on the sensor to the same terminal on the controller. See diagram below.
Carrier recommends that you use the following Rnet wiring scheme:
Red
Black
White
Green
+12V
Rnet-
Rnet+
Gnd
RTU Open 21
Page 28
Installation

Wiring a Supply Air Temperature sensor

J2

Wiring a Duct Air Temperature sensor

Part #33ZCSENSAT
The RTU Open requires a temperature sensor installed in the supply air stream. The Supply Air Temperature (SAT) sensor is used when the rooftop unit is equipped with electric heating.
Wiring specifications
Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded
If >100 ft (30.5 meters) 22 AWG, shielded
Maximum length: 500 feet (152 meters)
To wire the SAT sensor to the controller
1 Connect the wiring harness (Part #OPN-RTUHRN). For details, see To wire inputs and outputs (page 14). 2 Wire the sensor to the wiring harness. See diagram below. 3 Connect to
wires 1 and 2.
4 Verify your sensor readings.
Part #33ZCSENDAT
The RTU Open requires a temperature sensor installed in the supply air stream. The Duct Temperature (DAT) sensor is generally used when the rooftop unit is NOT equipped with electric heating.
22 RTU Open
Page 29
J2
NOTE

Wiring an Outdoor Air Temperature sensor

Wiring specifications
Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded
Maximum length: 500 feet (152 meters)
To wire a duct sensor to the controller
1 Connect the wiring harness (Part#OPN-RTUHRN). For details, see To wire inputs and outputs (page 14). 2 Wire the sensor to the wiring harness. See diagram below. 3 Connect to 4 Verify your sensor readings. 5 Drill .25" diameter hole. Pass sensor leads through bushing and insert assembly into hole. Secure leads
to ductwork with aluminum tape.
wires 1 and 2.
If >100 ft (30.5 meters) 22 AWG, shielded
Sensor termination requires installation of RTU Open wiring harness assembly (Part #OPN-RTUHRN).
Part #33ZCSENOAT
Outdoor Air Temperature (OAT) is required to utilize all of the RTU Open’s features. OAT may be provided by a local sensor (shown below) or a linked sensor in another controller. See Single Point Linkage (page 75).
RTU Open 23
Page 30
Installation
J2

Wiring a CO2 sensor

Wiring specifications
Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded
If >100 ft (30.5 meters) 22 AWG, shielded
Maximum length: 500 feet (152 meters)
To wire an OAT sensor to the controller
1 Connect the wiring harness (Part#OPN-RTUHRN). For details, see To wire inputs and outputs (page 14). 2 Wire the sensor to the wiring harness. See diagram below. 3 Connect to 4 Verify your sensor readings.
wires 3 and 4.
Part #33ZCSPTCO2LCD-01 (Display model) Part #33ZCSPTCO2-01 (No display)
Part #33ZCT55CO2 (No display) Part #33ZCT56CO2 (No display)
A CO
sensor monitors carbon dioxide levels. As CO2 levels increase, the RTU Open adjusts the outside air
2
dampers to increase ventilation and improve indoor air quality. A CO mounted in a return air duct. Duct installation requires an Aspirator Box Accessory (Part #33ZCASPCO2).
The sensor has a range of 0–2000 ppm and a linear 4-20 mA output. The CO2 sensor’s power requirements exceed what is available at J4 - 1 and 4. Provide a dedicated 24Vac transformer or DC power supply
sensor can be wall-mounted or
2
24 RTU Open
Page 31
Wiring diagram for #33ZCSPTCO2:
Wiring specifications
Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded
Maximum length: 500 feet (152 meters)
To wire the CO2 sensor to the controller
1 Wire the sensor to the controller. See appropriate diagram below. 2 Install a field-supplied dedicated 24 Vac transformer or DC power supply. 3 Wire the sensor to the controller.
If >100 ft (30.5 meters) 22 AWG, shielded
RTU Open 25
Page 32
Installation
Wiring diagram for #33ZCT55/56CO2:

Wiring an Outdoor Air Quality sensor

Part #33ZCSPTCO2LCD-01 (Display model) Part #33ZCSPTCO2-01 (No display)
An outdoor air quality (OAQ) sensor monitors outside air carbon dioxide levels. The RTU Open uses this information, in conjunction with a CO An OAQ sensor is typically duct-mounted in the outside air stream. Duct installation requires an Aspirator Box Accessory (Part #33ZCASPCO2).
The sensor has a range of 0–2000 ppm and a linear 4-20 mA output. The CO2 sensor’s power requirements exceed what is available at J4 - 1 and 4. Provide a dedicated 24 Vac transformer or DC power supply.
2
sensor, to adjust the outside air dampers to provide proper ventilation.
26 RTU Open
Page 33
Wiring diagram for #33ZCSENCO2:
NOTE

Wiring a Relative Humidity sensor

NOTE
Wiring specifications
Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded
Maximum length: 500 feet (152 meters)
To wire the OAQ sensor to the controller
1 Wire the sensor to the controller. See appropriate diagram below. 2 Install a field-supplied dedicated 24 Vac transformer or DC power supply. 3 Apply power and verify sensor readings.
If >100 ft (30.5 meters) 22 AWG, shielded
Sensor may be terminated at Input 1 or 2.
Wall sensor - Part #33ZCSENSRH-02 Duct sensor - Part #OPNSENRH-02
The Relative Humidity (RH) sensor may be used for zone humidity control (dehumidification) when applied to a Carrier rooftop unit equipped with the Humidi-MiZer™ option. On units not equipped for dehumidification, the sensor monitors humidity, but provides no control.
You cannot use a relative humidity sensor when using both a CO2 and OAQ sensor on the controller.
RTU Open 27
Page 34
Installation
NOTE

Wiring a Humidistat

Wiring specifications
Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded
If >100 ft (30.5 meters) 22 AWG, shielded
Maximum length: 500 feet (152 meters)
To wire the RH sensor to the controller
1 Strip the outer jacket from the cable for at least 4 inches (10.2 cm). Strip .25 inch (.6 cm) of insulation
from each wire.
2 Wire the sensor to the controller. See diagram below. 3 Apply power and verify sensor readings.
Sensor may be terminated at Input 1 or 2.
Locally Purchased
A humdistat may be used for zone humidity control (dehumidification) when applied to a Carrier rooftop unit equipped with the Humidi-MiZer™ option. On units not equipped for dehumidification, the humidistat will indicate a high humidity condition only.
28 RTU Open
Page 35
NOTE

Wiring an enthalpy switch

Wiring specifications
Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded
Maximum length: 500 feet (152 meters)
To wire a humidistat to the controller
1 Strip the outer jacket from the cable for at least 4 inches (10.2 cm). Strip .25 inch (.6 cm) of insulation
from each wire
2 Wire the humidistat to the controller. See diagram below. 3 Apply power and verify sensor readings.
If >100 ft (30.5 meters) 22 AWG, shielded
Humidistat may be return duct or space mounted.
Outdoor Air - Part #33CSENTHSW
Return air - Part #33CSENTSEN
The 33CSENTHSW is an outdoor air enthalpy switch/receiver. This control determines the suitability of the outdoor air as a cooling source, based on the heat content of the air. Differential enthalpy control requires installing a 33CSENTSEN enthalpy sensor in the rooftop unit's return air duct.
RTU Open 29
Page 36
Installation
Wiring diagram for a field-installed enthalpy switch:
NOTES
J2
Wiring specifications
Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded
If >100 ft (30.5 meters) 22 AWG, shielded
Maximum length: 500 feet (152 meters)
To wire an enthalpy switch (outdoor air) to the controller
An enthalpy switch is typically mounted in the outdoor air inlet.
Factory-installed enthalpy switches terminate at
wires 6 (switch input) and 7 (24 Vac).
Input channel must be configured for the enthalpy contact (N.O. or N.C.) that you use.
30 RTU Open
Page 37
Wiring diagram for factory-installed enthalpy switch:
NOTE
Factory-installed enthalpy switches terminate at J2 wires 6 (switch input) and 7 (24 Vac).
RTU Open 31
Page 38
Installation
Wiring diagram for optional enthalpy sensor mounted in the return air for differential enthalpy:

Wiring a status switch

Dirty Filter
Fan Running
To wire an enthalpy switch (differential) to the controller
Filter - Part #CRSTATUS005A00 or field-supplied
Fan status - Part #CRSTATUS005A00 or field-supplied
Filter and/or fan status switches may be installed to provide a
Wiring specifications
Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded
Maximum length: 500 feet (152 meters)
indication or
If >100 ft (30.5 meters) 22 AWG, shielded
status.
32 RTU Open
Page 39
NOTES
Fan Status, Filter Status, Remote
Occupancy,
Door Contacts

Wiring a compressor safety

To wire a status switch to the controller
Binary inputs 3, 5, 8, and 9 are configurable and may be used for
or
Follow device manufacturer's installation and operating instructions.
This is typically provided by the manufacturer with the rooftop equipment. A compressor safety status may be monitored if available.
Wiring specifications
Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded
Maximum length: 500 feet (152 meters)
, if they have not already been used for their default functions.
If >100 ft (30.5 meters) 22 AWG, shielded
RTU Open 33
Page 40
Installation
NOTES

Wiring an occupancy switch or door contact

To wire a compressor safety input to the controller
An isolation relay may be required if the RTU Open is powered separately from the equipment's control
power circuit.
Follow device manufacturer's installation and operating instructions.
Occupancy switch - field-supplied
Door contact - field-supplied
Occupancy or door contact switches may be installed to provide an alternate means of occupancy determination or heating and cooling lockout. See Sequence of Operation (page 43) for additional details.
Wiring specifications
Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded
If >100 ft (30.5 meters) 22 AWG, shielded
Maximum length: 500 feet (152 meters)
34 RTU Open
Page 41
NOTES
Fan Status, Filter Status, Remote
Occupancy
Door Contacts
To wire an occupancy switch or door contact
Binary Inputs 3, 5, 8, and 9 are configurable and may be used for
Follow device manufacturer's installation and operating instructions.
, or
- provided they have not been utilized for their default functions.
RTU Open 35
Page 42
Start-up
This interface...
Provides a...
i-Vu Open
Field Assistant
Virtual BACview
BACview6 Handheld
BACview6

Start-up

To start up the RTU Open, you need one of the following user interfaces to the controller. These items let you access the controller information, read sensor values, and test the controller.
software Permanent interface
software -
1
runs on a laptop connected to controller's Local Access port
software -
1, 2
runs on a laptop connected to controller's Local Access port
keypad/display device -
connects to controller's Local Access port
1, 2
keypad/display device
connected to controller's Rnet port
1
Requires a USB Link (Part #USB-L).
2
See the BACview Installation and User Guide for instructions on connecting and using the above items.
2
Temporary interface
Temporary interface
Temporary interface
Permanent interface
36 RTU Open
Page 43

Service Test

Navigation:
i-Vu / Field Assistant:
Properties > Equipment > Configuration > Service Configuration > Service Test HOME > CONFIG > SERVICE > TEST
Service Test
Service Test
Service Test
Fire
Safety Chain
Service Test Default Value
Enable
Disable
NOTES
Service Test
Service Test
Binary Service Test
Default Value
Enable
Disable
Analog Service Test
Default
Value
Service Test
Disable
0.00 Compressor 2 Test
Service Test
Disable
Service Test functions
Fan Test
Supply Fan
Service Test
Default Value
Disable
Compressor 1 Test
Supply Fan
Compressor 1 Test
Enable
Compressor 2 Test
Compressor 2 Test
Compressor 1 Test
Enable
Compressor 2 Test
Reversing Valve Test
Dehumidification Test
Heat 1Test
Heat 1Test
Heat 2Test
Heat 2Test
BACview:
exhaust fans, economizer, and dehumidification. It is highly recommended to use system start-up and during troubleshooting. See Appendix A: Points/Properties (page
can be used to verify proper operation of compressors, heating stages, indoor fan, power
59) for more
information.
differs from normal operation as follows:
Outdoor air temperature limits for cooling circuits, economizer, and heating are ignored.
Normal compressor time guards and other staging delays are ignored.
Alarm statuses (except
and
) are ignored, but all alarms and alerts are still broadcast on
the network, if applicable.
can be turned on or off from a BACview device, Field Assistant, or the i-Vu application. Select
of
to turn on and
to turn off.
The output of the
It is recommended to return every
(unless that test variable must be active to test a subsequent function, as in
All outputs return to normal operation when
mode is password-protected when accessed from a BACview device.
allows testing of each controller output.
functions are on when the
is controlled by the percentage (0-100%) entered into the
is set to
.
variable to
is set to
or
and off when set to
after testing each function
.
Use
simultaneously with other
Use
output will be activated and deactivated in conjunction with this output. Leave
if
Use
Compressor 1 output first.
to activate and deactivate the
modes even with its
to activate and deactivate the Compressor 1 (BO - 5) output. The
is required.
to activate and deactivate the Compressor 2 (BO - 4) output. Always test the
(BO - 1) output. Note that this output may enable
output must be set to
set to
for
function.
Use the
to activate and deactivate the reversing valve (BO - 7) output.
at initial
.
).
on
to
.
Use the
to activate and deactivate the Humidi-MiZer™ (BO - 6) output. The Supply
Fan output will be activated and deactivated in conjunction with the Dehumidification Test output.
Use
Use
RTU Open 37
to activate and deactivate the Heat 1 (BO - 3) output. The Supply Fan output is activated
and deactivated in conjunction with the
to activate and deactivate the Heat 2 (BO - 2) output. The Supply Fan output is activated
and deactivated in conjunction with the
output.
output.
Page 44
Start-up
Power Exhaust Test
Economizer Test
Analog Output 2 Test
Disable
0.00
Service Test
Disable

Configuring the RTU Open's properties

Unit Configuration properties

Navigation:
i-Vu / Field Assistant:
Properties > Equipment > Configuration > Unit Configuration HOME > CONFIG > UNIT
Point Name/Description
Default/Range
Fan Mode
Auto Continuous
Always On
Occupancy Source
Always Occupied BACnet Schedule
BAS On/Off Remote Occ Input
Input 1 Function
Use
Use
to set the (AO - 1) economizer output to any value from 0 to 100% of configured
to activate and deactivate the power exhaust (BO - 8) output.
output (2-10 Vdc or 4-20 mA).
(AO - 2) is currently unused and does not require testing.
Service Test mode does not timeout. Return all test variables to
or cycle power to the RTU Open to return to normal operation.
To start up the RTU Open, you must configure certain points and properties. Appendix C is a complete list of all the points and properties, with descriptions, defaults, and ranges. These properties affect the unit operation and/or control. Review and understand the meaning and purpose of each property before changing it.
Unit Configuration properties (page 38)
Setpoint Configuration properties (page 40)
Service Configuration properties (page 41)
See Appendix A (page 59) for a complete list of the controller's points/properties.
or
. Set
to
BACview:
– The supply fan's operating mode.
Options:
- The fan cycles on/off in conjunction with heating or cooling.
- The fan runs continuously during occupancy & intermittently during
unoccupied periods with heating or cooling.
- The fan runs continuously regardless of occupancy or calls for heating and
cooling.
- The method that the controller uses to determine occupancy.
Options:
= Controller operates continuously as occupied.
= Controller follows a schedule set up in the i-Vu application or Field
Assistant.
= Occupancy is set over the network by another device or a third party BAS.
= Occupancy is set by a remote contact.
– The type of sensor (4-20 mA) connected to terminals J4 – 4, 5, & 6. D:
D:
Continuous
R:
Auto Continuous Always On
D:
Always Occupied
R:
Always Occupied BACnet Schedule BAS On/Off Remote Occ Input
No Sensor
R:
No Sensor IAQ Sensor OAQ Sensor Space RH Sensor
38 RTU Open
Page 45
Point Name/Description
Default/Range
Input 2 Function
Input 3 Function
Input 3 Switch Configuration
No Function Compressor Safety Fan Status Filter Status Remote Occupancy Door Contact
Input 3
Switch Configuration
Input 5 Function
Input 5 Switch Configuration
No Function Fire Shutdown Fan Status Filter Status Remote Occupancy Door Contact
Input 5
Switch Configuration
Input 8 Function
Input 8 Switch Configuration
No Function Enthalpy Switch Fan Status Filter Status Remote Occupancy Door Contact
Input 8
Switch Configuration
Input 9 Function
Input 9 Switch Configuration
No Function Humidistat Fan Status Filter Status Remote Occupancy Door Contact
– The type of sensor (4-20 mA) connected to terminals J4 – 1, 2, & 3. D:
– The usage of Input 3. You must also set
Options:
– The input is not used.
– Proves supply fan operation.
– Indicates a dirty filter.
– Disables mechanical cooling and electric or gas heating, when active.
terminated at Input
– The usage of Input 5. You must also set
Options:
– The input is not used.
– Fire Safety device status. Inhibits operation when tripped.
– Proves supply fan operation.
– Indicates a dirty filter.
– Disables mechanical cooling and electric or gas heating, when active.
terminated at Input
– Safety device status.
– Sets occupancy using a hardware contact.
– The normal (de-energized) state for the set of contacts
– Sets occupancy using a hardware contact.
– The normal (de-energized) state for the set of contacts
No Sensor
R:
No Sensor IAQ Sensor OAQ Sensor Space RH Sensor
.
D:
Compressor Safety
R:
No Function Compressor Safety Fan Status Filter Status Remote Occupancy Door Contact
D:
NO
R:
NO/NC (normally open/normally closed)
.
D:
Fire Shutdown
R:
No Function Fire Shutdown Fan Status Filter Status Remote Occupancy Door Contact
D:
NC
R:
NO/NC (normally open/normally closed)
Options:
terminated at Input
Options:
RTU Open 39
– The usage of Input 8. You must also set
– The input is not used.
– Indicates enthalpy status (high or low).
– Proves supply fan operation.
– Indicates a dirty filter.
– Sets occupancy using a hardware contact.
– Sets occupancy using a hardware contact.
– The normal (de-energized) state for the set of contacts
– The usage of Input 9. You must also set
– The input is not used.
– Indicates high humidity condition.
– Proves supply fan operation.
– Indicates a dirty filter.
– Sets occupancy using a hardware contact.
– Sets occupancy using a hardware contact.
.
D:
Enthalpy Switch
R:
No Function Enthalpy Switch Fan Status Filter Status Remote Occupancy Door Contact
D:
NO
R:
NO/NC (normally open/normally closed)
.
D:
Humidistat
R:
No Function Humidistat Fan Status Filter Status Remote Occupancy Door Contact
Page 46
Start-up
Point Name/Description
Default/Range
Input 9
Switch Configuration
Space sensor type

Setpoint properties

Navigation:
i-Vu / Field Assistant:
Properties > Equipment > Configuration > Setpoints HOME > CONFIG > SETPOINT
Heating
Cooling
Point Name/Description
Default/Range
Occupied Heating
Occupied Cooling
Unoccupied Heating
Unoccupied Cooling
– The normal (de-energized) state for the set of contacts
terminated at Input
- The type of local space temperature sensor. D:
BACview:
Select a color band on the setpoint graph to see the current setpoints in the descriptions below.
and
D:
NO
R:
NO/NC (normally open/normally closed)
T55
R:
T55 T56 (Use for T59) SPT Sensor None
fields. See setpoint
– Green
The heating setpoint the controller maintains while in occupied mode.
– Green
The cooling setpoint the controller maintains while in occupied mode.
– Gray
The heating setpoint the controller maintains while in unoccupied mode.
– Gray
The cooling setpoint the controller maintains while in unoccupied mode.
40 RTU Open
D:
R:
D:
R:
D:
R:
D:
R:
70°F
-40 to 245°F
74°F
-40 to 245°F
55°F
45 to 100°F
90°F
-40 to 245°F
Page 47
Point Name/Description
Default/Range
Optimal Start
Occ Relative Humidity Setpoint
Unocc Relative Humidity Setpoint
DCV Max Ctrl Setpoint
Power Exhaust Setpoint
Configuration >Service Configuration
Economizer Exists
Yes
Configuration >Service Configuration > Continuous Occupied Exhaust
No

Service Configuration properties

Navigation:
i-Vu / Field Assistant:
Properties > Equipment > Configuration > Service Configuration HOME > CONFIG > SERVICE
Point Name/Description
Default/Range
Unit Type
Heat/Cool HP O/B Ctrl
HP Y1/W1 Ctrl
Compressor Stages Economizer Exists
Yes
Reversing Valve Output
O = Reversing Valve
B =
Reversing Valve
Heat Type
Number Of Heat Stages
– The number of hours prior to occupancy, at which the Optimal Start function may begin to adjust the effective setpoints to achieve the occupied setpoints by the time scheduled occupancy begins. Enter 0 to disable Optimal Start.
– The percentage of relative humidity in the space during
occupancy that will energize BO - 6 (Humidi-MiZer™).
– The percentage of relative humidity in the space during
the unoccupied time period that starts the unit and energizes BO - 6 (Humidi-MiZer™).
– The design difference between indoor and outdoor CO2 levels. D:
- The outside air damper position at which the controller energizes the Power Exhaust relay. set to be set to
, and
.
>
must be
BACview:
must
D:
4 hr
R:
0 to 4 hr
D:
60%rh
R:
0 to Unoccupied RH Control Setpoint
D:
95%
R:
30 to 100%
650ppm
R:
0 to 9999 ppm
D:
50% Open
R:
20 to 90% Open
– The type of equipment that the RTU Open is controlling.
Options:
– Standard rooftop air handling unit.
– Heat Pump application, uses reversing valve output to control heating and
cooling.
– Carrier Heat Pump application only.
economizer damper.
output on with heating.
– The type of heating that the unit has.
– The number of mechanical cooling stages.
– Set to
– Set to
to enable economizer control for units equipped with an
output on with cooling. Set to
– The number of heat stages.
D:
Heat/Cool
R:
Heat/Cool HP O/B Ctrl HP Y1/W1 Ctrl
D:
One Stage
R:
One Stage Two Stages
D:
No
R:
No/Yes
D:
R: O O / B
D:
Electric
R:
Electric/Gas
D:
R: 2 1 /2 /0 (no heating)
RTU Open 41
Page 48
Start-up
Point Name/Description
Default/Range
Continuous Occupied Exhaust
Yes
No
Power Exhaust Setpoint.
Indoor CO2 Sensor Value @min (ma)
Indoor CO2 Sensor Value @max (ma)
The CO2 value that corresponds to a 20mA input at
Outdoor CO2 Sensor Value @min (ma)
Outdoor CO2 Sensor Value @max (ma)
The CO2 value that corresponds to a 20 mA input
– Configures the exhaust fan control strategy (BO-8). If
the power exhaust runs continuously in occupied mode and is off in unoccupied mode. If
, the power exhaust is controlled by the
– The CO2 value that corresponds to a 4mA input at
the appropriate input channel.
the appropriate input channel.
– The CO2 value that corresponds to a 4 mA input
at the appropriate input channel.
at the appropriate input channel.
,
D:
No
R:
No/Yes
D:
0 ppm
R:
0 to 9999 ppm
D:
2000 ppm
R:
0 to 9999 ppm
D:
0 ppm
R:
0 to 9999 ppm
D:
2000 ppm
R:
0 to 9999 ppm
42 RTU Open
Page 49

Occupancy

Occupied/Unoccupied
Occupied
NOTE
Occupancy Source
Always Occupied
BAS On/Off
Remote Occ Input
Unit Configuration
Occupancy Source
Remote Occ Input
Input Switch Configuration
Remote Occupancy

Sequence of Operation

The RTU Open supports various types of constant volume air source configurations:
Standard heat/cool unit types with up to 2-stages of mechanical cooling and gas or electric heating
Heat pump units utilizing a reversing valve output for heating and cooling control
Heat pump unit (Carrier) with an OEM control board
Economizer, CO2, Demand Limiting, and RH control strategies are available for appropriately equipped
The RTU Open may operate as part of a linked VVT system or as a stand-alone controller.
units
The RTU Open’s operation depends upon its occupancy state ( operates continuously in the
mode until you configure an occupancy schedule.
). The RTU Open
An occupancy schedule may be:
A local schedule configured in the controller using a BACview device or Field Assistant
A BACnet schedule configured in the i-Vu application, networked through an i-Vu Open Router
A BACnet or local schedule configured for subordinate VVT Zones, networked through an i-Vu Open
Router(s) and employing Linkage
To set up occupancy schedules, consult the documentation for your user interface.
A BACnet schedule, downloaded from the i-Vu application will overwrite a local schedule that was set
up with a BACview device or Field Assistant.
Options:
- the following settings determine occupancy. See Unit configuration (page 60).
– Controller operates continuously, regardless of any configured schedule
– Occupancy is set over the network by another device or a third party BAS. Refer to the RTU
Open Integration Guide for additional instructions in communication protocols.
configured to receive it. You must set one
– Controller monitors an input contact connected to one of the available binary inputs
to
>
.
to
and
RTU Open 43
Page 50
Sequence of Operation

Supply fan

Fan Modes
Auto
Continuous
Always On
Fan Off Delay
Fire Shutdown Safety chain SAT SPT
Supply Fan Status
Supply Fan Alarm Service Timer

Cooling

Outdoor Air Temperature
Cooling Lockout Temperature
Supply Air Temperature
Space Temperature
Minimum Cooling SAT
Effective
Cooling Setpoint
The RTU Open supply fan may be configured for 1 of 3
- The fan cycles on/off in conjunction with heating or cooling
with heating or cooling
Occupancy can be determined by Linkage, BACnet schedules, BAS schedules, or in response to a remote occupancy switch.
A
If the following alarms are active, the fan turns off immediately, regardless of the occupancy state or demand:
The RTU Open does not include smoke-control functions such as smoke-purge, zone-pressurization, or smoke­ventilation. Each of these modes require a field-designed circuit to operate the following, as required by local fire codes:
RTU supply fan
RTU economizer
RTU power exhaust
The RTU Open may be configured to accept a operating. When enabled, a loss or lack of fan status will stop heating and cooling operation.
A generate an alarm when the accumulated runtime exceeds the set threshold.
- The fan runs continuously during occupancy and intermittently during unoccupied periods
- The fan runs continuously regardless of occupancy or calls for heating and cooling
allows the supply fan to continue operating after heating or cooling stops.
alarm
alarms
function is available to track the number of supply fan run hours and
:
input to provide proof the supply fan is
The RTU Open's application and configuration determines the specific cooling sequence. The RTU Open can control up to two stages of cooling with an additional output for a reversing valve (heat pump applications).
The following conditions must be true for the cooling algorithm to operate:
The indoor fan has been on for at least 30 seconds
The unit has a valid
The unit has a valid
Heat mode is not active and the time guard between modes has expired
Economizer is active and open > 85% with SAT > (
44 RTU Open
+ 0.5°F, or the Economizer is unavailable
is greater than the
input
input
setpoint
+ 5°F) and SPT >
Page 51
Space Temperature
Effective Occupied Cooling Setpoint
Effective Unoccupied Cooling Setpoint
Minimum Cooling SAT Setpoint
Supply Air Temperature
Minimum Cooling SAT Setpoint
Compressor 2 Service Alarm Timer

Economizer

Outdoor Air Temperature
Space Temperature
Economizer High
OAT Lockout Temp
Supply Air Temperature
Space Temperature
Vent Dmpr Pos / DCV Min
Pos
Vent Dmpr
Pos / DCV Min Pos
Vent Dmpr Pos / DCV Min Pos
Minimum
Cooling SAT
The cooling relays are controlled by the Cooling Control PID Loop and Cooling Stages Capacity algorithm. They calculate the desired number of stages needed to satisfy the space by comparing the
to
the:
when occupied
when unoccupied
When the cooling algorithm preconditions have been met, the compressors are energized in stages, as applicable. Anti-recycle timers are employed to protect the equipment from short-cycling. There are fixed three-minute minimum on-times, and five-minute off-times for each compressor output.
During compressor operation, the RTU Open may reduce the number of active stages if the rooftop supply air temperature falls below the started again after the normal time-guard period has expired, if the above the
. A compressor staged off in this fashion may be
has increased
.
functions are available (one for each stage of compression). This function tracks the number of compressor run hours and generates an alarm when the accumulated runtime exceeds the threshold set by the adjustable compressor service alarm timers.
The RTU Open provides an analog economizer output for rooftop units with economizer dampers. Economizer dampers may be used to provide indoor air quality control and free cooling when outside air conditions are suitable.
The following conditions must be true for economizer operation:
The
The indoor fan has been on for at least 30 seconds
The unit has a valid
The unit has a valid
If any of the preceding conditions are not true, the economizer will be set to the
setpoint.
If all preceding conditions are true, the economizer PID loop will modulate the damper from the
The economizer moves to the
setpoint.
(+ 5°F).
is less than the
setpoint
input
input
setpoint if the SAT falls below the
and less than the
RTU Open 45
Page 52
Sequence of Operation

Power Exhaust

Continuous Occupied Exhaust
Yes
Power Exhaust
Continuous Occupied Exhaust
Power Exhaust
Power Exhaust Setpoint
Power Exhaust Setpoint

Unoccupied Free Cooling

Unocc Free Cool Enable
Unocc Free Cool Enable
Enable
Economizer High OAT Lockout Temp
Enthalpy
Low
Occupied
Cooling Setpoint

Optimal Start

Optimal Start. Optimal Start
Properties
Equipment
Configuration
Setpoints
Optimal Start
Default Value
0
0.00
Optimal Start
NOTE
The RTU Open may enable and disable an exhaust fan, based on either the controller’s occupancy or its economizer damper position.
If
is
, the
binary output (BO-8) is energized while theRTU
Open is occupied and de-energized when unoccupied.
If economizer damper output exceeds the energized until the economizer output falls below the
is No, the
binary output (BO-8) is energized when the
value (default = 50%). The output remains
value by a fixed hysteresis of
10%.
cooling during unoccupied periods.
The following conditions must be true for unoccupied free cooling to operate:
The system is unoccupied
The outside air temperature is below the
The outside air temperature is less than the space temperature
When the RTU Open schedule is unoccupied and the space temperature rises at least 1° above the
RTU Open continues to operate in this mode until the space is satisfied or the outside air conditions are no longer suitable for free cooling.
The RTU Open may utilize setpoints by the time scheduled occupancy begins.The Optimal Start recovery period may begin as early as 4 hours prior to occupancy. The algorithm works by moving the unoccupied setpoints toward the occupied setpoints. The rate at which the setpoints move is based on the outside air temperature, design temperatures, and capacities.
The following conditions must be true for optimal start to operate:
On the
must be set greater than
The system is unoccupied
If the Open controller does not have a valid outside air temperature, then a constant of 65° F is used.
This value is not adjustable.
allows rooftop equipment with an economizer damper to utilize outdoor air for free
set to
(if enabled) is
setpoint
, the supply fan starts. The economizer damper opens as necessary to cool the space. The
page >
and less than or equal to 4 (
tab >
adjusts the effective setpoints to achieve the occupied
>
disables
>
, the
).
46 RTU Open
Page 53
Optimal Start
Optimal Start
Properties
Equipment
Configuration
Setpoints

Enthalpy control

Enthalpy
Enthalpy Status
High
Enthalpy Status
Low

Indoor Air CO2

Indoor Air CO2
Indoor Air CO2
The actual equation that the controller uses to calculate
is nonlinear. An approximation of the
result is shown below.
To change
settings:
1 In the navigation tree, select the equipment that you want to change. 2 Click
page >
tab >
>
.
You may use an enthalpy switch to indicate the suitability of outdoor air for economizer cooling. You can use either an outdoor air or differential enthalpy switch. A differential enthalpy switch has a sensing device in both the outdoor and return air streams. A differential enthalpy switch indicates when outside air is cooler than the return air, and is available for economizer cooling. If no enthalpy switch is configured, a network point (Object Name: oae) is available. This point is displayed in the i-Vu application and a BACview device as (BACnet).
The sequence of operation for economizer cooling is the same with or without an enthalpy switch, except that an enthalpy switch imposes one more validation on the suitability of outside air for economizer cooling. An
position. An preconditions are met.
by installing an air quality (CO2) sensor. A CO2 sensor may be terminated at the RTU Open, or a subordinate zone controller, when part of a zoned system.
An outdoor air quality sensor may also be installed and terminated at the RTU Open, but it is not required. When an outdoor air quality sensor is not installed, the algorithm uses 400ppm as the fixed outdoor air CO2 level.
that is
disables the economizer and the outside air damper goes to its minimum
that is
enables the economizer if a call for cooling exists and the remaining
is controlled on rooftop equipment with an economizer.
sequence is enabled
RTU Open 47
Page 54
Sequence of Operation
Indoor Air CO2
Indoor Air CO2
Vent Dmpr Pos / DCV Min Pos
Indoor Air CO2
DCV Max Vent Damper Pos

Heating

Reversing Valve
Outdoor Air Temperature
Heating Lockout Temperature
Supply Air Temperature
Space Temperature
Space Temperature
Effective Occupied Heating Setpoint
Effective Unoccupied Heating Setpoint
Supply Air
Temperature
Maximum Heating SAT
Supply Air Temperature
Maximum Heating SAT
The following conditions must be true for the
algorithm to operate:
The system is occupied
The supply fan has been started for at least 30 seconds
The CO2 sensor has a valid reading
As the air quality within the space changes, the minimum position of the economizer damper changes, which allows more or less outdoor air into the space, depending on the relationship of the indoor air CO2 level to the differential setpoint.
The damper position is then compared against the
algorithm calculates a minimum position value using a PID loop. The CO2 minimum
setpoint and the greatest value
becomes the final minimum damper position of the economizer output.
The degree to which the outside air damper may be opened by the
setpoint, which is adjustable between ten and sixty percent (10 – 60%).
algorithm is limited by the
The specific heating sequence is determined by the controller's application and configuration. The RTU Open controls up to two stages of gas or electric heating with an additional output for a
(Heat
Pump applications).
The following conditions must be true for the heating algorithm to operate:
The
is less than the
setpoint
The indoor fan has been ON for at least 30 seconds
The unit has a valid
The unit has a valid
input
input
Neither Cool mode nor economizer are active and the time guard between modes has expired
The heating relays are controlled by the Heating Control PID Loop and Heating Stages Capacity algorithm, which calculate the desired number of stages to satisfy the space by comparing the
to
the:
when occupied
when unoccupied
When the heating algorithm preconditions have been met, the heating is energized in stages. Anti-recycle timers are employed to protect the equipment from short-cycling. There are fixed one minute minimum on and off times for each heating output.
During heating operation, the RTU Open may reduce the number of active stages if the rooftop
started again after the normal time-guard period has expired, if the below the
exceeds the
setpoint. A heat stage turned off in this fashion may be
setpoint.
has decreased
48 RTU Open
Page 55

Heat Pump operation

HP O/B
Y1/W1
HP O/B
(B)
Y2
W1
Y1/W1
W1

Dehumidification

Outside Air Temperature
Cooling Lockout Temperature
Indoor Fan
Supply Air Temperature
Space Temperature
Space Relative Humidity Sensor
Humidistat
The RTU Open can control heat pumps
provides a separate output (BO-7) to control a reversing valve. The reversing valve control may be
configured to be energized with a call for heating
The sequence of operations are as previously described for heating and cooling except that the Y1 and outputs are compressor outputs, energizing mechanical heating or cooling, depending on the state of the reversing valve.
Selection sequences of operations are as described for Heating (page output is not utilized in this application. available.
The RTU Open provides occupied and unoccupied dehumidification on units that are equipped with the Carrier Humidi-MiZer™ option from the factory. This requires a space relative humidity sensor or a humidistat for control.
The following conditions must be true for the dehumidification control to operate:
The
and
.
, or energized with a call for cooling (O).
and W2 are used for auxiliary heat. Up to two stages are available.
is for heat pumps that do not require a O terminal to energize the reversing valve. The
48) and Cooling (page 44). The reversing valve
and W2 are used for auxiliary heat. Up to two stages are
is greater than the
setpoint
The
The unit has a valid
The unit has a valid
The unit has a valid
has been ON for at least 30 seconds
input
input
or
input
Heat mode is not active and the time guard between modes has expired
Dehumidification alone will not enable the unit. The unit must be running (Fan On), while occupied or unoccupied, for Dehumidification to become active. When using a relative humidity sensor to control dehumidification, occupied and unoccupied dehumidification setpoints are used.
When using a humidistat, the setpoints are not used. The humidistat indicates a high-humidity condition.
When a high indoor relative humidity condition is indicated and the above conditions are satisfied, the RTU Open enters the dehumidification mode, energizing the Humidi-MiZer™ output.
The mode continues until the space relative humidity falls below the active setpoint by a 5% fixed Hysteresis when a humidity sensor is used, or when there is no longer a call for dehumidification where a humidistat is used.
See the base unit / Humidi-MiZer™ operations manual for additional information.
RTU Open 49
Page 56
Sequence of Operation

Demand Limiting

Demand Level Setpoints
Demand Level
Demand 1
Demand 2
Demand 3
Demand Limit
Level 0

Door contact

Door Contact
Door Contact

Remote occupancy

Remote occupancy
Remote Occupancy
Remote Occupancy
Occupancy Source
Remote Occ Input
Remote Occupancy

Fire Shutdown

Fire Shutdown

Compressor Safety

Compressor Safety
Compressor Safety Alarm
Properties
Equipment
Alarms
The RTU Open may employ a demand limit strategy. Demand limiting in the RTU Open works through setpoint expansion. The controller’s heating and cooling setpoints are expanded in steps or levels. The degree to which the setpoints are expanded is defined by the
Each yields a 1° expansion,
The BACnet
leaves the standard occupied and unoccupied heating and cooling setpoints in effect. Levels 1
(1 through 3) adjusts the heating and cooling setpoints outwards. By default,
yields a 2° expansion, and
variable sets the desired level of setpoint expansion in the receiving controller.
yields a 4° expansion.
.
through 3 expands occupied heating and cooling setpoints.
A mounted within the space served by a single zone rooftop. electric or gas heating, when active. Economizer cooling, if available, continues to operate.
may be configured on any unused binary input. A typical application is an occupancy sensor
disables mechanical cooling and
contact, controlled by a third party, to set the controller's occupied mode. The requires both an input configured for operate.
Once configured, the controller will operate in the occupied or unoccupied mode, as determined by the state of the
shutdown contact, which, when active, immediately shuts down equipment operation.
may be configured on Binary Input 5. A typical application involves a smoke detector or fire
available on most Carrier rooftop equipment.
A equipment requires attention.
Cooling, heating, and supply fan outputs are not interrupted except where the RTU Open is configured for Heat Pump operation. When configured for Heat Pump, and in the heating mode, a compressor safety fault will cause the available stages of electric heating to be enabled in place of mechanical heating.
Normal operation resumes when the compressor safety circuit is de-energized.
may be configured on any unused binary input channel. A typical application is a remote
, and
set to
function
input.
may be configured on Binary Input 3. A compressor safety tripped indicator circuit is
is shown on
page >
tab >
and indicates that the
to
50 RTU Open
Page 57

Fan Status

Fan Status

Filter status

Filter
Filter
Dirty

Alarms

NOTE
Alarms
Properties
Equipment
Alarms
Safety Chain
Fire Shutdown
Fire Shutdown
Compressor Safety
switch, current sensing relay, or other device that provides a supply fan running verification.
Enabling this function displays the supply fan’s status on the equipment graphic.
If the controller loses fan status during operation, heating and cooling are disabled, the economizer damper (if available) is closed, and an alarm for loss of status is indicated.
If the fan status is on when the controller is commanding the fan off, the unit remains in the off state. An alarm is generated indicating that the fan is running when it should be off.
pressure switch that senses the pressure drop across a filter bank.
When the pressure across the filter bank exceeds the setpoint of the differential pressure switch, the status is displayed as
may be configured on any unused binary input channel. A typical application would be an airflow
status may be configured on any unused binary input channel. A typical application is a differential
on the controller graphic. An alarm indicates a dirty filter.
Some of the
tab >
functions described in this section will only be visible on the
when the appropriate inputs are configured. Alarms are not initiated when the input
page >
is not configured.
Examples: Low or High Temperature Cutouts (Freezestat / Firestat). See To wire inputs and outputs (page
- You may use the RTU Open's safety chain circuit to shut down the unit for a safety condition.
14) for additional wiring instructions. This alarm indicates the safety chain circuit (Input 4) is open. Cooling, heating, and supply fan operation stop after appropriate time guards. Normal operation resumes when the safety chain circuit is complete.
– You may configure the RTU Open to accept a
contact on Input 5. Examples: Smoke detectors or fire shutdown relays. This alarm indicates this device (Input 5) has tripped. Cooling, heating, and supply fan operation immediately stop. Reset fire shutdown contact to resume normal operation.
– You may configure the RTU Open to monitor the base unit’s compressor safety circuit. This alarm indicates the base unit's compressor safety circuit is energized. Cooling, heating, and supply fan outputs are not interrupted except when the RTU Open is configured for Heat Pump. Normal operation resumes when the compressor safety circuit is de-energized.
If the Heat Pump is in the heating mode, it will automatically replace the compressor stage(s) with the equivalent number of auxiliary heat stages, as available.
If it's a Carrier Heat Pump, there is only one auxiliary heat stage output and the staging is done by the
machine itself, if it's two-stage gas or electric.
For a non-Carrier Heat Pump, when configured for two stages of aux heat and two compressors,
Compressor 1 is replaced by Aux Heat Stage 1 and Compressor 2 is replaced by Aux Heat Stage 2.
The compressor output stays on when the safety alarm is present. For cooling, the alarm indicates the compressors are down. See Heat Pump operation (page 49) for further information.
RTU Open 51
Page 58
Sequence of Operation
Space Temp Sensor
Supply Air Temp Sensor
Outdoor Air Temp Sensor Alarm
Space Relative Humidity Sensor
IAQ Sensor
IAQ Sensor
OAQ Sensor
OAQ Sensor
Space Temperature
Occupied -
Low Space Temperature
High Space Temperature
Unoccupied
Alarm Configuration
Unoccupied Low SPT Alarm Limit
Alarm Configuration
Unoccupied High SPT Alarm Limit
Space Temperature
Alarming Temperature
Alarm Limit Exceeded
High Supply Air Temperature
Alarm Configuration
High SAT Alarm Limit
Low Supply Air Temperature
Alarm Configuration
Low SAT Alarm Limit
Setpoint Slider
Configuration
Unit Configuration
Input Configuration
Space sensor type
Unit Configuration
Setpoint Adjustment Range
Switch Configuration
Unit Configuration
Input
Functions 3, 5, 8,
Analog Input Configuration
Unit Configuration
Input
Functions 1
– This alarm indicates an invalid sensor condition in a physically connected space temperature sensor (SPT Sensor/T5*). Cooling, heating, and supply fan operation stop after the appropriate time guards. Normal operation resumes when the controller detects a valid sensor.
– This alarm indicates a shorted or open circuit in the SAT input. Cooling, heating, and supply fan operation stops after the appropriate time guards. Normal operation resumes when the controller detects a valid sensor.
- This alarm indicates a shorted or open circuit in the OAT input. Cooling, heating, and supply fan operation continues. OAT lockouts will not operate while the sensor is in alarm. Normal operation resumes when the controller detects a valid sensor.
- This alarm indicates if the mA input at the associated channel falls below
3.5 mA or rises above 21 mA. Cooling, heating, and supply fan operation continues, however, the controller’s Humidi-MiZer™ binary output is disabled until the fault condition is corrected.
- The RTU Open generates an
alarm if the mA input at the associated channel falls below 3.5 mA or rises above 21 mA. Cooling, heating, and supply fan operation continues. However, the controller’s IAQ control function is disabled until the fault condition is corrected.
- The RTU Open generates an
alarm if the mA input at the associated channel falls below 3.5 mA or rises above 21 mA. Cooling, heating, and supply fan operation continues. However, the controller’s IAQ control function uses 400ppm as the fixed outdoor air CO2 level until the fault condition is corrected.
below the lower limit of the blue color bar. A
The RTU Open generates a
alarm if the space temperature falls
alarm is generated if the space
temperature rises above the upper limit of the orange color bar.
below the temperature alarm is generated when the space temperature rises above the
The following values are related to the
An unoccupied low space temperature alarm is generated when the space temperature falls
>
. An unoccupied high space
>
.
alarm:
– This variable displays the value of the space temperature that is in alarm and is
only visible when the space temperature is in an alarm state.
– This variable displays the value of the alarm setpoint that is exceeded by the
alarming space temperature and is only visible when the space temperature is in an alarm state.
the
– The RTU Open generates this alarm when the supply air temperature exceeds
>
setpoint for 5 minutes. This alarm is inhibited until the RTU
has been running for 30 minutes to allow for system stabilization after startup.
below the
- The RTU Open generates this alarm when the supply air temperature falls >
setpoint for 5 minutes. This alarm is inhibited until the
RTU has been running for 30 minutes to allow for system stabilization after startup.
RTU Open
– The RTU Open generates this alarm when an open circuit is detected at Input 11 and the
>
>
>
is set to T56. Note that only an open circuit results in an alarm. A short across this input offsets the setpoints negatively by the amount configured in the
or 9 are configured identically. Neither input may work reliably and downstream control may
>
.
- The RTU Open generates this alarm when any two of the
>
be affected, depending on the function duplicated. The alarm clears and normal control is restored when the input function duplication is corrected.
and 2 are configured identically. Neither input may work reliably and downstream control may be
- The RTU Open generates this alarm when the
>
affected, depending on the function duplicated. The alarm clears and normal control is restored when the input function duplication is corrected.
52 RTU Open
Page 59
High Space Relative Humidity Alarm Configuration > High Space Humidity Alarm Limit
Low Space Relative Humidity Alarm Configuration
Low Space Humidity Alarm Limit
High CO2
Alarm Configuration
Occupied High CO2 Alarm Limit
Supply Fan Runtime
Unit
Configuration
Supply Fan Service Alarm Timer
Maintenance
Reset Supply Fan Runtime Alarm
Clear
Run
OK
Unit Configuration
Supply
Fan Service Timer
Compressor 1 Runtime Unit Configuration
Compressor 1 Service Alarm Timer
Compressor 1 Runtime
Maintenance
Reset Comp 1 Runtime Alarm
Clear
Run
Unit
Configuration
Compressor 1 Service Timer
Compressor 1 Runtime
Compressor 2 Runtime Unit Configuration
Compressor 2 Service Alarm Time
Maintenance
Reset Comp 2 Runtime Alarm
Clear
Run
Unit
Configuration
Compressor 2 Service Timer
Service Configuration
Compressor States
Two
Stages
Filter
Unit Configuration
Filter Service Alarm Timer
Maintenance
Reset Filter
Runtime Alarm
Off
Unit Configuration
Filter Service Alarm Timer
Airside Linkage Alarm

Linkage

- The RTU Open generates this alarm when the space humidity exceeds the setpoint for 10 minutes. This alarm is inhibited until
the RTU runs for 15 minutes to allow for system stabilization after startup.
>
- The RTU Open generates this alarm when the space humidity falls below the setpoint for 5 minutes. This alarm is inhibited until
the RTU runs for 5 minutes to allow for system stabilization after startup.
- The RTU Open generates this alarm when the space CO2 level exceeds the setpoint for 1-minute. This alarm will be inhibited until the RTU has been
>
running for 2-minutes to allow for system stabilization after startup.
- The RTU Open generates a this alarm when the accumulated runtime exceeds the
>
value (when not set to 0). This alarm is most commonly used to indicate an equipment maintenance interval is due. The supply fan runtime accumulator may be reset by setting the acknowledging each selection by clicking the
commonly used to indicate an equipment maintenance interval is due. The accumulator may be reset by setting the back to
>
button when it appears. Setting
to
, and then back to
value to 0 disables the supply fan runtime alarm function.
- The RTU Open generates this alarm when the accumulated runtime exceeds the
>
value (when not set to 0). This alarm is most
– acknowledging each selection by clicking the OK button when it appears. Setting
>
value to 0 disables the
>
- The RTU Open generates this alarm when the accumulated runtime exceeds the
>
r value (when not set to 0). This alarm is most
to
, and then
alarm function.
>
commonly used to indicate an equipment maintenance interval is due. The Compressor 2 runtime accumulator may be reset by setting the back to
– acknowledging each selection by clicking the OK button when it appears. Setting
>
Note that this function is unavailable if the
.
- The RTU Open generates this alarm when the accumulated runtime exceeds the value (when not set to 0). This alarm is most commonly used to indicate a filter
replacement is due. Reset the filter service runtime accumulator by setting the
to On, back to
value to 0 disables the filter service alarm function.
- An RTU Open may act as an air source in a zoned system. Carrier systems utilize a
>
value to 0 disables the Compressor 2 runtime alarm function.
>
, and clicking the OK button after each setting. Setting
to
, and then
value is not set to
>
>
>
function called Linkage™ to pass data between a master zone and its air source via an MS/TP network connection. When the RTU Open is part of a linked system, it will indicate an airside linkage alarm if it loses communications with its linkage master or if it receives invalid data.
The RTU Open may serve as an air source to an Open Variable Volume Terminal (VVT) system. When the RTU Open is part of a VVT system and the controllers are wired together to form a network, the controllers may use a method of communication known as Linkage™. Linkage is a method by which an air source and its subordinate zone terminals exchange data to form a coordinated HVAC system. The system's air source controller, zone controllers, and bypass controller are linked so that their data exchange can be managed by one zone controller configured as the VVT Master.
The VVT Master gathers the following information from the slave zone controllers:
occupancy status
setpoints
RTU Open 53
Page 60
Sequence of Operation
NOTE
Linkage
Callers
Linkage Callers
zone temperature
relative humidity
CO
level
2
damper position
optimal start data
The VVT Master performs mathematical calculations and algorithms on the data and then sends the composite information to the air source. The VVT Master receives information from the air source such as mode, supply air temperature, and outside air temperature, and passes that information to all linked controllers.
The following paragraphs describe the interaction between the air source (RTU Open) and its subordinate zones. Additional information regarding Open Zoned Systems may be found in the VVT Zone and VVT Bypass Controller Installation Guides.
The VVT Master determines system operation by prioritizing heating and cooling requirements from all the zones based on their occupancy and demand. The VVT Master scans the system continuously to determine if any zones are occupied. Occupied zones are a higher priority than unoccupied zones. The VVT Master evaluates all the occupied zones' heating or cooling demands and sends a request to the air source (RTU Open) for:
Cooling, if the number of occupied zones with cooling demands exceeds the number of occupied zones
with heating demands, and the demand is greater than or equal to the number of configured
.
Heating, if the number of occupied zones with a heating demand exceeds or is equal to the number of
.
If no zones are occupied or no occupied zones require heating or cooling, the VVT Master performs the evaluation described above for the unoccupied zones.
The VVT Master then gathers the following information and sends it to the air source (RTU Open):
The system mode
The setpoints and zone temperature from the zone with the greatest demand for the requested air
source mode (heating or cooling). (This zone is called the reference zone.)
The system occupancy status
Most open damper position from any zone
RH and CO2 values (if applicable)
The air source responds by sending the air source mode, supply air temperature, and outside air temperature. The air source verifies the mode by comparing its supply air temperature to the space temperature received through Linkage. See the air source documentation for operation and parameters used to verify its mode. This verification allows the VVT system to determine if the desired air source mode is actually being provided. For example, if the VVT Master sends a request for heating and the air source does not have heat or it’s heat has failed, the air source's actual mode indicates that and it's current mode is sent to the zones so that they can control accordingly.
The system remains in that mode until all zones of that demand are satisfied or until a fixed 30 minute mode reselect timer causes a forced re-evaluation of the system. If there is no demand for the opposite mode, the reselect timer starts again and the current mode continues until all zones are satisfied or until the reselect timer expires, repeating the process. If there is a demand for the opposite mode, the VVT Master sends the reference zone's space temperature and setpoints to the air source and restarts the reselect timer. The air source re-evaluates its demand based on the new information and goes to the Vent mode until the new mode can be verified as described above. The amount of time this takes is determined by the air source’s operating parameters.
The VVT Master continuously evaluates the system and updates the air source with the most current system demand. Based on the evaluation, the reference zone can change from one zone to another. The evaluation process continues until there is no demand from any zone or the 30 minute timer causes a re-evaluation of the system conditions.
54 RTU Open
Page 61

Linkage Air Source Modes

Supply Air Temperature
Off
Fan Only
Economizer Cooling
Cooling
Heating
Dehumidification
Test
Service Test
Shutdown
Unocc Free Cooling
If no heating or cooling is required or the current air source mode is satisfied, the VVT Master calculates the weighted average of the occupied and unoccupied heating and cooling setpoints. It also calculates a zone temperature that is midway between the setpoints (occupied or unoccupied based on the system’s current occupancy status). This information, plus the occupancy status, is sent to the air source so that its current mode is disabled and the unit ceases heating or cooling operation. If the system is occupied, the air source fan and OA damper, if applicable, operate to maintain proper ventilation.
In a linked system, the air source determines its operating mode and qualifies that mode based on its own
configuration:
– Air source fan is off
– Air source fan is on and providing ventilation (neutral SAT) without heating or cooling
– Air source fan is on and cooling is provided by economizer and mechanical cooling
(SAT). The following modes can be sent by the air source depending on its
– Air source fan is on and providing cooling, using economizer only
– Air source fan is on and heating is provided (gas or electric)
– The RTU Open
– Air source fan is on and Humidi-MiZer™ is active
mode is active
– Air source fan is off due to Safety Chain, Fire Shutdown, or invalid SAT sensor
– Air source fan is on, with the economizer providing cooling while unoccupied
RTU Open 55
Page 62
Troubleshooting

Serial number

LED's

If this LED is on...
Status is...
Power
Rx
Tx
DO#
Run
Error
If Run LED shows...
And Error LED shows...
Status is..
Run

Troubleshooting

If you have problems mounting, wiring, or addressing the RTU Open, contact Carrier Control Systems Support.
If you need the RTU Open's serial number when troubleshooting, the number is on:
a sticker on the back of the main controller board
a Module Status report (modstat) from your user interface
The LED's on the RTU Open show the status of certain functions.
The RTU Open has power
The RTU Open is receiving data from the network segment
The RTU Open is transmitting data over the network segment
The binary output is active
The
and
LED's indicate controller and network status.
2 flashes per second Off Normal
2 flashes per second 2 flashes,
alternating with
2 flashes per second 3 flashes, then off The controller has just been
2 flashes per second On Exec halted after frequent system
5 flashes per second Off Firmware transfer in progress,
LED
Five minute auto-restart delay after system error
formatted
errors or control programs halted
Boot is running
56 RTU Open
Page 63
If Run LED shows...
And Error LED shows...
Status is..
Run
Run

Replacing the RTU Open's battery

CAUTION
7 flashes per second 7 flashes per second,
alternating with
14 flashes per second 14 flashes per second,
alternating with
On On Failure. Try the following solutions:
*Formatting the controller may result in lost information and should only be done under the guidance of Carrier Control Systems Support.
LED
LED
Ten second recovery period after brownout
Brownout
Turn the RTU Open off, then
on.
Format the RTU Open.*
Download memory to the RTU
Open.
Replace the RTU Open.
The RTU Open's 10-year Lithium CR2032 battery provides a minimum of 10,000 hours of data retention during power outages.
Power must be ON to the RTU Open when replacing the battery, or your date, time, and trend data
will be lost.
1 Remove the battery from the controller, making note of the battery's polarity. 2 Insert the new battery, matching the battery's polarity with the polarity indicated on the RTU Open.
RTU Open 57
Page 64
Compliance

FCC Compliance

CAUTION

CE Compliance

WARNING

BACnet Compliance

Compliance

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
could void the user’s authority to operate the equipment.
Changes or modifications not expressly approved by the responsible party for compliance
This is a Class A product. In a domestic environment, this product may cause radio
interference in which case the user may be required to take adequate measures.
BACnet® is a registered trademark of ASHRAE. ASHRAE does not endorse, approve or test products for compliance with ASHRAE standards. Compliance of listed products to requirements of ASHRAE Standard 135 is the responsibility of the BACnet manufacturers Association (BMA). BTL BMA.
®
is a registered trademark of the
58 RTU Open
Page 65
NOTE

Status

Navigation:
i-Vu / Field Assistant:
Properties > Equipment > Status HOME > STATUS
Point Name/Description
Range
System Mode
Operating Mode
Supply Fan Status
Fan Status
Space Temperature - Prime Variable Supply Air Temperature
Outdoor Air Temperature
Space Relative Humidity
Configuration > Unit
Configuration
Input 1
Function
Space RH Sensor
Indoor Air CO2
Configuration >Unit
Configuration > Input 1
Function
IAQ Sensor
Outdoor Air CO2
Configuration >Unit
Configuration >Input 1
Function
OAQ Sensor
Economizer Output

Appendix A: RTU Open Points/Properties

Engineering units shown in this document in the defaults and ranges are strictly for reference. You must enter an integer only.
BACview:
– The controller's current operating status. R: Disabled
– The controller's current operating mode. R: Off
– The current fan status if an input is configured for
control.
>
– The current indoor air CO2 concentration if the
– The current outdoor air CO2 concentration if the
– The current economizer output with respect to the outdoor air
damper (if equipped).
Test Run
Fan Only Economizer Cooling Heating Dehumidification Test Shutdown Unocc Free Cooling (NTFC)
. R: Off/Running
– The space temperature value currently used for
– Displays the current supply air temperature. R: -56 to 245°F
– The outdoor air temperature value used for control. R: -56 to 245°F
– The current space relative humidity if
(or 2)
(or 2)
(or 2)
is set to
is set to
is set to
.
.
.
R: -56 to 245°F
R: 0 to 100%rh
R: 0 to 5000ppm
R: 0 to 5000ppm
R: 0 to 100% Open
RTU Open 59
Page 66
Appendix A: RTU Open Points/Properties

Unit Configuration

Navigation:
i-Vu / Field Assistant:
Properties > Equipment > Configuration > Unit Configuration HOME > CONFIG > UNIT
Point Name/Description
Default/Range
Fan Mode
Auto Continuous
Always On
Unit Start Delay Fan Off Delay
Minimum Cooling SAT
Maximum Heating SAT
Vent Dmpr Pos / DCV Min Pos
DCV Max Vent Damper Pos
Supply Fan Service Alarm Timer
Compressor 1 Service Alarm Timer
Compressor 2 Service Alarm Timer
Filter Service Alarm Timer Filter Alarm
Pushbutton Override
Cooling Lockout Temp
Economizer High OAT Lockout
BACview:
– The supply fan's operating mode.
Options:
- The fan cycles on/off in conjunction with heating or cooling.
- The fan runs continuously during occupancy & intermittently during
unoccupied periods with heating or cooling.
- The fan runs continuously regardless of occupancy or calls for heating and
cooling.
– How long the controller delays normal operation after power is restored. Typically used to prevent excessive demand when recovering from a power failure.
– How long the supply fan runs after receiving a valid stop command. D:
– In cooling mode, the cooling outputs are controlled so that the
supply air temperature does not drop below this value.
– In heating mode, the heating outputs are controlled so the
supply air temperature does not rise above this value.
– The minimum outdoor air damper position maintained
during occupied periods.
– The maximum outdoor air damper position allowed while
DCV is active.
– A Supply Fan Runtime alarm is generated when the
supply fan run hours exceed this value. Set to 0 to disable.
– A Compressor 1 Runtime alarm is generated when
the compressor 1 run hours exceed this value. Set to 0 to disable.
– A Compressor 2 Runtime alarm is generated when
the compressor 2 run hours exceed this value. Set to 0 to disable.
D:
Continuous
R:
Auto Continuous Always On
D:
5 sec
R:
0 to 30 sec
90 seconds
R:
0 to 180 seconds
D:
50°F
R:
45 to 75°F
D:
120°F
R:
85 to 150°F
D:
50% Open
R:
0 to 100% Open
D:
50% Open
R:
10 to 60% Open
D:
600 hr
R:
0 to 9999 hr
D:
0 hr
R:
0 to 9999 hr
D:
0 hr
R:
0 to 9999 hr
– The amount of time the fan will run before generating a
. Set to 0 to disable the alarm and reset accumulated fan hours.
– Enables or disables the use of a pushbutton override from a local
space temperature sensor.
– The outdoor air temperature at which cooling is inhibited. D:
– The outdoor air temperature at which economizer
cooling is inhibited.
60 RTU Open
D:
600 hr
R:
0 to 9999 hr
D:
Enable
R:
Disable/Enable
45°F
R:
0 to 80°F
D:
75°F
R:
55 to 80°F
Page 67
Point Name/Description
Default/Range
HP Rev Cycle Lockout Temp
Heating Lockout Temperature
Unocc Free Cool Enable
Occupancy Source
Always Occupied BACnet Schedule
BAS On/Off Remote Occ Input
Input Configuration
Input 1 Function
Input 2 Function
Input 3 Function
Input 3 Switch Configuration
No Function Compressor Safety Fan Status Filter Status Remote Occupancy Door Contact
Input 3 Switch Configuration
Input 5 Function
Input 5 Switch Configuration
No Function Fire Shutdown Fan Status Filter Status Remote Occupancy Door Contact
– The outdoor air temperature at which reverse cycle
heating is locked out. Requires that the unit is configured as a Heat Pump.
– The outdoor air temperature at which heating is
inhibited.
– Enable to allow the unit to use economizer to provide
unoccupied free cooling (NTFC).
- The method that the controller uses to determine occupancy.
Options:
= Controller operates continuously as occupied.
= Controller follows a schedule set up in the i-Vu application or Field
Assistant.
= Occupancy is set over the network by another device or a third party BAS.
= Occupancy is set by a remote contact.
– The type of sensor (4-20 mA) connected to terminals J4 – 4, 5, & 6. D:
– The type of sensor (4-20 mA) connected to terminals J4 – 1, 2, & 3. D:
– The usage of Input 3. You must also set
Options:
– The input is not used.
– Safety device status.
– Proves supply fan operation.
– Indicates a dirty filter.
– Sets occupancy using a hardware contact.
– Disables mechanical cooling and electric or gas heating, when active.
D:
-3°F
R:
-20 to 30°F
D:
65°F
R:
35 to 150°F
D:
Disable
R:
Disable/Enable
D:
Always Occupied
R:
Always Occupied BACnet Schedule BAS On/Off Remote Occ Input
No Sensor
R:
No Sensor IAQ Sensor OAQ Sensor Space RH Sensor
No Sensor
R:
No Sensor IAQ Sensor OAQ Sensor Space RH Sensor
.
D:
Compressor Safety
R:
No Function Compressor Safety Fan Status Filter Status Remote Occupancy Door Contact
terminated at Input
Options:
RTU Open 61
– The normal (de-energized) state for the set of contacts
– The usage of Input 5. You must also set
– The input is not used.
– Fire Safety device status. Inhibits operation when tripped.
– Proves supply fan operation.
– Indicates a dirty filter.
– Sets occupancy using a hardware contact.
– Disables mechanical cooling and electric or gas heating, when active.
D:
NO
R:
NO/NC (normally open/normally closed)
.
D:
Fire Shutdown
R:
No Function Fire Shutdown Fan Status Filter Status Remote Occupancy Door Contact
Page 68
Appendix A: RTU Open Points/Properties
Point Name/Description
Default/Range
Input 5 Switch Configuration
Input 8 Function
Input 8 Switch Configuration
No Function Enthalpy Switch Fan Status Filter Status Remote Occupancy Door Contact
Input 8 Switch Configuration
Input 9 Function
Input 9 Switch Configuration
No Function Humidistat Fan Status Filter Status Remote Occupancy Door Contact
Input 9 Switch Configuration
Space sensor type
T5x Override Duration
Sensor Calibration
Space Temp Calibration
A calibration offset value to allow the local space temperature
Supply Air Temp Calibration
Outside Air Temp Calibration
terminated at Input
– The usage of Input 8. You must also set
Options:
– The input is not used.
– Indicates enthalpy status (high or low).
– Proves supply fan operation.
– Indicates a dirty filter.
– Sets occupancy using a hardware contact.
terminated at Input
– The usage of Input 9. You must also set
Options:
– The input is not used.
– Indicates high humidity condition.
– Proves supply fan operation.
– Indicates a dirty filter.
– Sets occupancy using a hardware contact.
terminated at Input
– The normal (de-energized) state for the set of contacts
– Sets occupancy using a hardware contact.
– The normal (de-energized) state for the set of contacts
– Sets occupancy using a hardware contact.
– The normal (de-energized) state for the set of contacts
D:
NC
R:
NO/NC (normally open/normally closed)
.
D:
Enthalpy Switch
R:
No Function Enthalpy Switch Fan Status Filter Status Remote Occupancy Door Contact
D:
NO
R:
NO/NC (normally open/normally closed)
.
D:
Humidistat
R:
No Function Humidistat Fan Status Filter Status Remote Occupancy Door Contact
D:
NO
R:
NO/NC (normally open/normally closed)
- The type of local space temperature sensor. D:
– If using a T55, T56, or T59 sensor, this is the amount of time that the controller runs in the occupied mode when a user presses the sensor's override button for 1 to 10 seconds.
– sensor to be adjusted to match a calibrated standard measuring the temperature in the same location.
– A calibration offset value to allow the supply air temperature sensor to be adjusted to match a calibrated standard measuring the temperature in the same location.
– A calibration offset value to allow the outside air temperature sensor to be adjusted to match a calibrated standard measuring the temperature in the same location.
T55
R:
T55 T56 (Use for T59) SPT Sensor None
D:
1 hr
R:
0 to 24 hours
D:
0°F
R:
-9.9 to 10°F
D:
0°F
R:
-9.9 to 10°F
D:
0°F
R:
-9.9 to 10°F
62 RTU Open
Page 69

Setpoints

Navigation:
i-Vu / Field Assistant:
Properties > Equipment > Configuration > Setpoints HOME > CONFIG > SETPOINT
Heating
Cooling
Occupied Setpoints
Default Demand Level
Point Name/Description
Occupied
1
2
3
Occupied Heating
Occupied Cooling
Occupied Heating 1
Occupied Heating 1
Occupied Heating
Occupied Heating 1
Occupied Heating
BACview:
Select a color band on the setpoint graph to see the current setpoints in the descriptions below.
and
fields. See setpoint
The occupied setpoints described below are the setpoints under normal operating conditions. The Demand Level 1–3 setpoints apply if demand limiting is used.
Demand limiting is a cost-saving strategy to reduce energy consumption. The strategy expands the occupied heating and cooling setpoints when the system reaches one of 3 levels of consumption. With the expanded setpoints, the equipment works less, thereby saving energy. By default, Demand Level 1 expands the occupied heating and cooling setpoints by 1°F, Demand Level 2 by 2°F, and Demand Level 3 by 4°F. If the occupied heating or cooling setpoints change, the (effective) demand level setpoints automatically change by the same amount. See Sequence of Operation (page 43) for more information.
Range: -40 to 245°F
– Green
The heating setpoint the controller maintains while in occupied mode.
– Green
The cooling setpoint the controller maintains while in occupied mode.
– Light Blue The space temperature must be less than the VVT Master to consider the zone a heating caller in a linked system. In a single­zone application, the heating requirement begins as soon as the space temperature falls below the
value be set no less than 0.5°F below the setpoint.
setpoint. We recommend that the
setpoint for the
70°F 69°F 68°F 66°F
74°F 75°F 76°F 78°F
69°F 68°F 67°F 65°F
RTU Open 63
Page 70
Appendix A: RTU Open Points/Properties
Default Demand Level
Point Name/Description
Occupied
1
2
3
Occupied Heating 2
Occupied Heating 2
Occupied Heating 1
Occupied Cooling 1
Occupied Cooling 1
Occupied Cooling
Occupied Cooling 1
Occupied Cooling
Occupied Cooling 2
Occupied Cooling 2
Occupied Cooling 1
Unoccupied Setpoints
Point Name/Description
Default/Range
Unoccupied Heating
Unoccupied Cooling
Unoccupied Heating 1
Unoccupied Heating 1
application, the unoccupied heating requirement begins as soon as the space temperature falls
Unoccupied Heating
Unoccupied Heating 1
Unoccupied Heating
Unoccupied Heating 2
Unoccupied Heating 2
Unoccupied Heating 1
Unoccupied Cooling 1
Unoccupied Cooling 1
Unoccupied Cooling
Unoccupied Cooling 1
Unoccupied Cooling
Unoccupied Cooling 2
Unoccupied Cooling 2
Unoccupied Cooling 1
Range: -40 to 245°F
– Dark Blue The space temperature must be less than the generate a low space temperature alarm. We recommend that this value be set no less than 0.5°F below the
– Yellow The space temperature must be greater than the the VVT Master to consider the zone a cooling caller in a linked system. In a single­zone application, the cooling requirement begins as soon as the space temperature exceeds the
value be set no less than 0.5°F above the setpoint.
– Orange The space temperature must be greater than the generate a high space temperature alarm. We recommend that this value be set no less than 0.5°F above the
setpoint.
setpoint. We recommend that the
setpoint.
setpoint to
setpoint for
setpoint to
68°F 67°F 66°F 64°F
75°F 76°F 77°F 79°F
76°F 78°F 78°F 81°F
– Gray
The heating setpoint the controller maintains while in unoccupied mode.
– Gray
The cooling setpoint the controller maintains while in unoccupied mode.
– Light Blue The space temperature must be less than the Master to consider the zone an unoccupied heating caller in a linked system. In a single-zone
setpoint for the VVT
D:
55°F
R:
45 to 100°F
D:
90°F
R:
-40 to 245°F
D:
54°F
R:
-40 to 245°F
below the be set no less than 0.5°F below the
– Dark Blue The space temperature must be less than the unoccupied low space temperature alarm. We recommend that this value be set no less than
0.5°F below the
– Yellow The space temperature must be greater than the Master to consider the zone an unoccupied cooling caller in a linked system. In a single-zone application, the unoccupied cooling requirement begins as soon as the space temperature exceeds the be set no less than 0.5°F above the
– Orange The space temperature must be greater than the unoccupied high space temperature alarm. We recommend that this value be set no less than
0.5°F above the
setpoint. We recommend that the
setpoint.
setpoint to generate an
setpoint.
setpoint for the VVT
setpoint. We recommend that the
setpoint.
setpoint to generate an
setpoint.
64 RTU Open
value
value
D:
52°F
R:
-40 to 245°F
D:
91°F
R:
-40 to 245°F
D:
93°F
R:
-40 to 245°F
Page 71
Point Name/Description
Default/Range
Heating Capacity
Heating Design Temp
Cooling Capacity
Cooling Design Temp
Hysteresis
Time
Temp
Occupied heating setpoint: 70°
75.5°
70.5°
Occupied cooling setpoint: 76°
.5° hysteresis
.5° hysteresis
– Used for Optimal Start, this is the rate at which the zone temperature changes when the heating system runs at full capacity to maintain designed occupied heating setpoint.
– The geographically-based outdoor air temperature at which the heating system must run constantly to maintain comfort. This information is available in ASHRAE publications and most design references.
– Used for Optimal Start, this is the rate at which the zone temperature changes when cooling system runs at full capacity to maintain designed occupied cooling setpoint.
– The geographically-based outdoor air temperature at which the cooling system must run constantly to maintain comfort. This information is available in ASHRAE publications and most design references.
– The desired difference between the temperature at which the zone color changes as the zone temperature departs from the acceptable range between the heating and cooling setpoints (green) into the Cooling 1 (yellow) or Heating 1 (light blue) and the temperature at which the zone color changes back to the acceptable range between the heating and cooling setpoints.
For example, the following graph shows the zone color that results as the zone temperature departs from and returns to the acceptable range in a zone with the following settings:
Color Change Hysteresis = .5° (applies as the temperature returns to the acceptable
range)
Occupied cooling setpoint = 76°
Occupied heating setpoint = 70°
D:
5°F/hr
R:
0 to 120°F/hr
D:
0°F
R:
-100 to 150°F
D:
5°F/hr
R:
0 to 140°F/hr
D:
100°F
R:
-100 to 150°F
D:
0.5°F
R:
0 to 120°F
RTU Open 65
Page 72
Appendix A: RTU Open Points/Properties
Effective Setpoints
Effective Setpoints
Point Name/Description
Default/Range
Heating –
Heating
Cooling –
Cooling
Optimal Start
Occ Relative Humidity Setpoint
Unocc Relative Humidity Setpoint
DCV Max Ctrl Setpoint
Power Exhaust Setpoint
Configuration >Service Configuration
Economizer Exists
Yes
Configuration >Service Configuration > Continuous Occupied Exhaust
No
The
graph shows the current occupied or unoccupied setpoints. If occupied, these values are the current programmed setpoints plus the offset of any setpoint adjustment that may be in effect. If unoccupied, the values are the programmed unoccupied setpoints.
(Occupied or Unoccupied, depending on mode) The current programmed
setpoint adjusted by any offset that may be in effect.
(Occupied or Unoccupied, depending on mode) The current programmed
setpoint adjusted by any offset that may be in effect.
– The number of hours prior to occupancy, at which the Optimal Start function may begin to adjust the effective setpoints to achieve the occupied setpoints by the time scheduled occupancy begins. Enter 0 to disable Optimal Start.
– The percentage of relative humidity in the space during
occupancy that will energize BO - 6 (Humidi-MiZer™).
– The percentage of relative humidity in the space during the
unoccupied time period that starts the unit and energizes BO - 6 (Humidi-MiZer™).
– The design difference between indoor and outdoor CO2 levels. D:
- The outside air damper position at which the controller energizes the
Power Exhaust relay.
, and
>
must be set to must be set to
.
R: 0 to 120°F
R: 0 to 120°F
D:
4 hr
R:
0 to 4 hr
D:
60%rh
R:
0 to Unoccupied RH Control Setpoint
D:
95%
R:
30 to 100%
650ppm
R:
0 to 9999 ppm
D:
50% Open
R:
20 to 90% Open
66 RTU Open
Page 73

Alarm Configuration

Navigation:
i-Vu / Field Assistant:
Properties > Equipment > Configuration
Alarm Configuration
HOME > CONFIG > ALARMS
Point Name/Description
Default/Range
Space Temperature Alarm
Occupied Alarm Hysteresis
Alarm Delay (min/deg) Unoccupied Low SPT Alarm Limit
Space Temperature Alarm
Unoccupied High SPT Alarm Limit
Space Temperature Alarm
Supply Air Temperature Alarm
Low SAT Alarm Limit
Supply Air Temp Alarm
High SAT Alarm Limit
Supply Air Temp Alarm
Space Humidity Alarm
Low Space Humidity Alarm Limit
Configuration >Unit Configuration >Input 1
Function
Space RH Sensor
High Space Humidity Alarm Limit
Configuration >Unit Configuration >Input 1
Function
Space RH Sensor
IAQ/Ventilation Alarm
BACview:
>
– This value is added to the occupied high effective setpoint and subtracted from the occupied low effective setpoint to establish the occupied high and low limits that the space temperature must exceed before an occupied SPT alarm is generated. The alarm returns to normal when the space temperature drops below the high effective setpoint or rises above the low effective setpoint.
– Determines the amount of delay before an occupied space temperature alarm is generated when the controller transitions to the occupied mode. The delay time equals this value multiplied by the difference between the sensor temperature and occupied alarm setpoint plus 15 minutes.
–The value that the space temperature must drop below to generate a fixed hysteresis of 1° F for return to normal.
– The value that the space temperature must exceed to generate a fixed hysteresis of 1° F for return to normal.
– The value that the supply air temperature must drop below to generate a normal.
– The value that the supply air temperature must exceed to generate a normal.
. There is a fixed hysteresis of 1° F for return to
. There is a fixed hysteresis of 1° F for return to
in the unoccupied mode. There is a
in the unoccupied mode. There is a
D:
3°F
R:
0 to 20°F
D:
10 minutes
R:
0 to 60 minutes
D:
45°F
R:
-60 to 250°F
D:
90°F
R:
-60 to 250°F
D:
45°F
R:
-60 to 250°F
D:
120°F
R:
-60 to 250°F
below to generate a Low Space Humidity Alarm. Requires a space relative humidity transmitter and
.
above to generate a High Space Humidity Alarm. Requires a space relative humidity transmitter and
.
RTU Open 67
– The value that the relative humidity must drop
– The value that the relative humidity must rise
(or 2)
(or 2)
set to
set to
D:
R:
D:
R:
30%
0 – 99 %
70%
0 – 99 %
Page 74
Appendix A: RTU Open Points/Properties
Point Name/Description
Default/Range
Occupied High CO2 Alarm Limit
IAQ Alarm
Configuration >Unit
Configuration >Input 1
Function
IAQ Sensor

Service Configuration

Navigation:
i-Vu / Field Assistant:
Properties > Equipment > Configuration > Service Configuration HOME > CONFIG > SERVICE
Point Name/Description
Default/Range
Unit Type
Heat/Cool HP O/B Ctrl
HP Y1/W1 Ctrl
Compressor Stages Economizer Exists
Yes
Heat Type
Number Of Heat Stages
Continuous Occupied Exhaust Yes
No
Power Exhaust Setpoint.
Indoor CO2 Sensor Value @min (ma)
Indoor CO2 Sensor Value @max (ma)
Outdoor CO2 Sensor Value @min (ma)
Outdoor CO2 Sensor Value @max (ma)
generate an for return to normal. Requires a space CO2 sensor and
D:
– The value that the CO2 sensor must exceed to
in the occupied mode. There is a fixed hysteresis of 100ppm
(or 2)
set to
.
1200ppm
R:
0 to 9999 ppm
BACview:
– The type of equipment that the RTU Open is controlling.
Options:
– Standard rooftop air handling unit.
– Heat Pump application, uses reversing valve output to control heating
and cooling.
– Carrier Heat Pump application only.
– The number of mechanical cooling stages. D:
– Set to
to enable economizer control for units equipped with
an economizer damper.
– The type of heating that the unit has. D:
– The number of heat stages. D:
– Configures the exhaust fan control strategy (BO-8). If
, the power exhaust runs continuously in occupied mode and is off in unoccupied
mode. If
, the power exhaust is controlled by the
– The CO2 value that corresponds to a 4mA
input at the appropriate input channel.
– The CO2 value that corresponds to a 20mA
input at the appropriate input channel.
– The CO2 value that corresponds to a 4 mA
input at the appropriate input channel.
D:
Heat/Cool
R:
Heat/Cool HP O/B Ctrl HP Y1/W1 Ctrl
One Stage
R:
One Stage Two Stages
D:
No
R:
No/Yes
Electric
R:
Electric/Gas
R: 2 1 /2 /0 (no heating)
D:
No
R:
No/Yes
D:
0 ppm
R:
0 to 9999 ppm
D:
2000 ppm
R:
0 to 9999 ppm
D:
0 ppm
R:
0 to 9999 ppm
– The CO2 value that corresponds to a 20 mA
input at the appropriate input channel.
68 RTU Open
D:
2000 ppm
R:
0 to 9999 ppm
Page 75
Point Name/Description
Default/Range
System Space Temperature
System Cool Demand Level
System Heat Demand Level
System Outside Air Temperature
network readable when enabled. Requires controller be equipped with an outdoor air
Service Test
Service Test
Disable
Fan Test
Enable to test the controller's fan speeds. Sequences fan from low to high
Disable
Service Test
Enable
Compressor 1 Test
Service
Test
Enable
Compressor 2 Test
Service
Test
Enable
Heat 1 Test
Service Test
Enable
Heat 2 Test
Service Test
Enable
Reversing Valve Test
Service
Test
Enable
Dehumidification Test
Service
Test
Enable
Power Exhaust Test
Service Test
Enable
Economizer Test
Service Test
Enable
Analog Output 2 Test
– The network space temperature value that the
controller is using for control (if applicable).
– The system cool demand level being received over the
network.
– The system heat demand level being received over the
network.
– Allows the outside air temperature value to be
temperature sensor.
– Enable to stop automatic control so you can test the controller's
outputs. Automatically resets to
after 1 hour.
speed and operates at each speed for 1 minute. Resets to
must be set to
.
– Enable to test the controller's compressor 1 output.
must be set to
.
– Enable to test the controller's compressor 2 output.
must be set to
.
– Enable to test the controller's heat 1 output.
to
.
when complete.
must be set
D:
-999.00 °F
R:
N/A
D:
0.00
R:
0 - 3
D:
0.00
R:
0 - 3
D:
-999.0°F
R:
N/A
D:
Disable
R:
Disable/Enable
D:
Disable
R:
Disable/Enable
D:
Disable
R:
Disable/Enable
D:
Disable
R:
Disable/Enable
D:
Disable
R:
Disable/Enable
– Enable to test the controller's heat 2 output.
to
.
must be set to
must be set to
must be set to
– Set to a value between 0 and 100% to test the controller's
economizer output.
must be set
– Enable to test the controller's reversing valve output.
.
– Enable to test the controller's humidimizer output.
.
– Enable to test the controller's exhaust fan output.
.
must be set to
.
– Analog Output 2 (0-10 Vdc) is currently unused. D:
D:
Disable
R:
Disable/Enable
D:
Disable
R:
Disable/Enable
D:
Disable
R:
Disable/Enable
D:
Disable
R:
Disable/Enable
D:
0% Open
R:
0 to 100% Open
0%
R:
0 to 100%
RTU Open 69
Page 76
Appendix A: RTU Open Points/Properties

Maintenance

Navigation:
i-Vu / Field Assistant:
Properties > Equipment > Maintenance HOME > MAINT
Point Name/Description
Default/Range
Unit
Occupancy Status
Space Temp Sensor –
Sensor Failure SPT Sensor T55/56 Network
Airside Linkage Locked Value
Safety Chain Feedback
Fire Shutdown
Shutdown
Compressor Safety Status
Trouble
Enthalpy Status
Humidistat Input Status
Reset Supply Fan Runtime Alarm
Clear
Supply Fan Runtime
Reset Comp 1 Runtime Alarm
Clear
Compressor 1 Runtime
Reset Comp 2 Runtime Alarm
Clear
Compressor 2 Runtime
Reset Filter Runtime Alarm
On
Filter Runtime
Occupancy
BACview:
– The controller's occupancy status as determined by a network
schedule, a local schedule, or a timed override.
The source of the controlling space temperature value.
Options:
– No valid space temperature or sensor status = failed.
– An SPT sensor is connected to the controller’s Rnet port. – A T55, T56, or T59 sensor is connected to the controller’s J20 terminals. – A network temperature sensor is bound to the controller’s space temperature
AV.
– The space temperature from a linked terminal.
–The controller’s space temperature input has been manually locked at a
value.
- Indicates a completed circuit from J1, 1 to J1, 9. This circuit is
typically used for safety devices that immediately stop unit operation when tripped.
tripped.
– The enthalpy status determined by an enthalpy switch. R: High/Low
indicates that a fire shutdown is in effect. R: Run Enabled/
– The humidity status determined by a humidistat. R: High/Low
indicates that the compressor safety device has
– Set to
– Set to
to reset
to reset
to 0. D:
to 0. D:
R: Occupied/Unoccupied
R: Sensor Failure
SPT Sensor T55/T56 Network Airside Linkage Locked Value
R: Off/Run Enabled
Shutdown
R: Normal/Trouble
Run
R:
Run/Clear
Run
R:
Run/Clear
70 RTU Open
– Set to
– Set to
to reset
to reset
to 0. D:
R:
to 0. D:
R:
Run
Run/Clear
Off
Off/On
Page 77
Point Name/Description
Default/Range
BAS On/Off
Inactive
Occupied
Unoccupied
NOTE
BAS On/Off
Unoccupied
Occupied
Optimal Start
Schedules
Pushbutton Override
Active
Override Time Remaining Runtime
Supply Fan Runtime
Reset Supply Fan Runtime Alarm
Compressor 1 Runtime
Reset Comp 1 Runtime Alarm
Compressor 2 Runtime
Reset Comp 2 Runtime Alarm
Filter Runtime
Reset Filter Runtime Alarm

Alarms

Navigation:
i-Vu / Field Assistant:
Properties > Equipment > Alarms HOME > ALARM
Point Name/Description
Range
Safety Chain
Fire Shutdown
Compressor Safety
Space Temp Sensor –
– Determines the occupancy state of the controller and can be set over the
network by another device or third party BAS.
Options:
– Occupancy is determined by a configured schedule.
– The controller is always in the occupied mode.
– The controller is always in the unoccupied mode.
If
is set to either
or
automatically disabled.
– The controller's occupancy status based on the local schedule. R: Occupied/Unoccupied
override the occupancy state.
indicates if a user pushed the sensor's override button to
– The amount of time remaining in an override period.
– The total number of hours that the supply fan relay has been
energized since the runtime was last reset to 0 using
– The total number of hours that the Compressor 1 relay has
been energized since the runtime was last reset 0 using
, the
routine is
.
.
D:
Inactive
R:
Inactive Occupied Unoccupied
R: Off/Active
R: 0 to 240 minutes
R: ___ hr
R: ___ hr
– The total number of hours that the Compressor 2 relay has
been energized since the runtime was last reset using
– The total number of hours that the unit has been operating since the
runtime was last reset to 0 using
BACview:
– Indicates if the Safety Chain circuit trips. R: Normal/Alarm
– Indicates if the Fire Shutdown circuit trips. R: Normal/Alarm
– Indicates if the Compressor Safety circuit trips. R: Normal/Alarm
Indicates if the space temperature sensor fails. R: Normal/Alarm
R: ___ hr
.
R: ___ hr
.
RTU Open 71
Page 78
Appendix A: RTU Open Points/Properties
Point Name/Description
Range
Supply Air Temp Sensor –
Outdoor Air Temp Sensor Alarm –
Space Relative Humidity Sensor –
IAQ Sensor –
OAQ Sensor –
Space Temperature –
Alarming Temperature
Alarm Limit Exceeded
High Supply Air Temperature
High SAT
Alarm Limit
Low Supply Air Temperature
Low SAT
Alarm Limit
Setpoint Slider
Switch Configuration
Analog Input Configuration
High Space Relative Humidity
High
Space Humidity Alarm Limit
Low Space Relative Humidity
Low
Space Humidity Alarm Limit
High CO2
Occupied High CO2 Alarm Limit
Supply Fan Runtime
Supply Fan
Service Alarm Timer
Compressor 1 Runtime Compressor 1 Service Alarm Timer
Compressor 2 Runtime Compressor 2 Service Alarm Timer
Filter
Filter
Service Alarm Timer
Airside Linkage Alarm
Indicates if the supply air temperature sensor fails. R: Normal/Alarm
Indicates if the outdoor air temperature sensor fails. R: Normal/Alarm
Indicates if the space relative humidity sensor fails. R: Normal/Alarm
Indicates if the indoor air quality (CO2) sensor fails.
Indicates if the outdoor air quality (CO2) sensor fails.
Indicates if the space temperature sensor exceeds the high or low alarm
limit.
– The value of the alarming space temperature sensor. (Visible only in
an alarm condition.)
– The alarm limit that the alarming space temperature sensor exceeded.
(Visible only in an alarm condition.)
– Indicates if the supply air temperature exceeds the
.
– Indicates if the supply air temperature falls below the
.
– Indicates if the T56 sensor's setpoint slider potentiometer fails. R: Normal/Alarm
– Indicates if a duplicate configuration exists for two or more binary Input
3, 5, 8, & 9 Functions.
– Indicates if a duplicate configuration exists at the analog Input 1
& 2 Functions.
– Indicates if the space relative humidity exceeds the
.
– Indicates if the space relative humidity falls below the
.
R: Normal/Alarm
R: Normal/Alarm
R: Normal/Alarm
R: The sensor's
range
R: -60 to 250°F
R: Normal/Alarm
R: Normal/Alarm
R: Normal/Alarm
R: Normal/Alarm
R: Normal/Alarm
R: Normal/Alarm
– Indicates if the indoor CO2 level rises above the
– Indicates a dirty filter condition when the filter runtime exceeds the value of the
72 RTU Open
. R: Normal/Alarm
– Indicates if the supply fan runtime exceeds the value of the
R: Normal/Alarm
.
– Indicates if the compressor 1 runtime exceeds the value of the
R: Normal/Alarm
.
– Indicates if the compressor 1 runtime exceeds the value of the
R: Normal/Alarm
.
R: Clean/Dirty
or in response to a filter status switch binary input.
– Indicates if Linkage fails in a zoned system using Linkage. R: Normal/Alarm
Page 79

Linkage

Navigation:
i-Vu / Field Assistant:
Properties > Equipment > Linkage Properties > Equipment > Linkage
Point Name/Description
Range
Airside Linkage Status
Active
Not
Active
Airside Linkage Status
Active
Occupancy Status Space Temperature Occupied Cooling Setpoint Occupied Heating Setpoint Unoccupied Cooling Setpoint Unoccupied Heating Setpoint Indoor Air CO2 Space Relative Humidity

I/O Points

I/O Points Properties
Power User
Navigation:
i-Vu / Field Assistant:
Properties > I/O Points N/A
Point Name/Description
Space Temp input 1
input 2
input 6
input 7
input 10
BACview:
Linkage Collector – Allows access to the Collector's details.
– If
, the controller is a stand-alone device.
If the VVT Master (as applicable):
is
, the controller is part of a linked system. If
, the following provide information received from
The values shown on the values shown on status displays that are affected by control program logic.
i-Vu users logged in as channels and the display names for all channels.
We strongly recommend that you leave these parameters at their defaults. The RTU Open is not a programmable controller. I/O can only be used for the purpose designed in the equipment control program. Modifying these parameters may result in unpredictable equipment control.
See Wiring inputs and outputs (page 12) for more information. This table lists each of the I/O Channels, their functions, associated hardware, and terminal numbers.
and above are able to edit various parameters associated with the input
R: Active/Not Active
page are the raw values at the I/O objects and may not match
– The value of the Optional SPT (Rnet) sensor. Also allows i-Vu and Field Assistant users access to
sensor configuration. See Carrier Sensors Installation Guide for additional details.
– Input Channel 1; 4 - 20 mA only. User-configurable for IAQ, OAQ, or Space RH.
– Input Channel 2; 4 - 20 mA only. User-configurable for IAQ, OAQ, or Space Relative Humidity.
– Input Channel 6; 10K Thermistor only. Supply Air Temperature.
RTU Open 73
– Input Channel 7; 10K Thermistor only. Outside Air Temperature.
– Input Channel 10; 10K Thermistor only. Space Temperature (T55, 56, 59).
BACview:
Page 80
Appendix A: RTU Open Points/Properties
Point Name/Description
input 11
slidepot voltage reading
input 3 input 4
input 5
input 8
input 9
Sensor Invalid ao 1
ao 2
relay 1
relay 2
relay 3
relay 4
relay 5
relay 6
relay 7
relay 8
– Input Channel 11; 100K Potentiometer only. Setpoint adjust (T56, 59).
– Input Channel 11; used to detect an open circuit (faulty Setpoint adjustment mechanism).
– Input Channel 3; Dry Contact only. User-configurable for No Function, Compressor Safety, Fan Status, Filter
Status, Remote Occupancy, or Door Contact.
– Input Channel 4; Dry Contact only. Safety Chain.
– Input Channel 5; Dry Contact only. User-configurable for No Function, Fire Shutdown, Fan Status, Filter
Status, Remote Occupancy, or Door Contact.
– Input Channel 8; Dry Contact only. User-configurable for No Function, Enthalpy, Fan Status, Filter Status,
Remote Occupancy, or Door Contact.
– Input Channel 9; Dry Contact only. User-configurable for No Function, Humidistat, Fan Status, Filter Status,
Remote Occupancy, or Door Contact.
– Reflects the status of the Space Temp (Rnet) input. On = Space Temp invalid,
Off = Space Temp valid.
– Analog Output Channel 1; jumper selectable.
– Analog Output Channel 2; 0 - 10 Vdc. Not Utilized.
– Binary Output 1; Fan (G) Output.
– Binary Output 2; Heat 2 (W2) Output.
– Binary Output 3; Heat 1 (W1) Output.
– Binary Output 4; Cool 2 (Y2) Output.
– Binary Output 5; Cool 1 (Y1) Output.
– Binary Output 6; Humidi-MiZer ™ Output.
– Binary Output 7; Reversing Valve Output.
– Binary Output 8; Power Exhaust Output.
74 RTU Open
Page 81

Single Point Linkage

System Cool Demand Level
System Heat Demand Level
System Outside Air Temperature
Properties
Network Points
System Heat & Cool Demand Level
Address
Properties
Network Points

Appendix B: Single Point Linkage and Device Address Binding

The RTU Open receives data from other Open controllers when they are installed as part of an Open system. The data transfer may take the form of Single Point Linkage (SPL), which is automatic, or Device Address Binding, which you must configure.
Currently, the RTU Open implements Single Point Linkage for 3 variables: Refer to configuration section -
complete list - make list to system system configuration1.....might be different for RTU - might be unit config
Network Points for which SPL has been implemented are displayed in the i-Vu application and Field Assistant on the
The following example involves outside air temperature. similarly, except that their usage involves a specific application loaded on a Universal Controller Open. See UC Open Installation Guide for additional information. In either case, note that the BACnet type and instance numbers specified in the
Network variables for which SPL is used are easily identified on the The asterisk in the BACnet address invokes the SPL function. These addresses cause the controller to issue a BACnet “who has” command for this variable. The controller binds to the closest of the first five devices from which it receives a valid response.
page >
field of these variables have been predefined.
tab.
page >
behaves
tab.
RTU Open 75
Page 82
Appendix B: Single Point Linkage and Device Address Binding

Device Address Binding

Device Address Binding
Device Address Binding
System Space Temperature
Properties
Network Points
As described previously, controllers when they are connected by a network. You must configure this method.
Currently, the RTU Open allows
Network Points on which DAB may be implemented are displayed in the i-Vu application and Field Assistant on the
page >
allows the RTU Open to receive data from other Open
(DAB) only for
tab with an undefined BACnet address.
.
76 RTU Open
Page 83
Index

Index

#
#CRSTATUS005A00 • 32 #33CSENTHSW • 29 #33ZCSENCO2 • 24, 26 #33ZCSENOAT • 23 #33ZCSENSAT • 22 #33ZCSENSRH-02 • 27 #33ZCT55CO2 • 24 #33ZCT56CO2 • 24 #3CSENTSEN • 29 #33ZCSENDRH-02 • 27
A
Analog outputs • 3 Auxiliary control power transformer • 8
B
BACnet compliance • 58 BACnet objects • 3 BACnet port • 11 Battery • 3 BT485 • 11
C
Compliance • 58
D
Device Address Binding • 76 Dimensions • 3 Duct Air Temperature sensor • 22
Duct sensors
Duct Air Temperature sensor • 22
Supply Air Temperature sensor • 22
E
Environmental operating range • 3
F
FCC compliance • 58 Field Assistant • 59 Field-supplied hardware • 20
I
I/O Points • 12 Inputs • 3, 13 Inputs and outputs • 12 i-Vu • 59
L
LED's • 56 Linkage • 75
M
Module Status report • 56 Mounting the controller • 6
MS/TP Baud Rate • 10 MS/TP network, wiring • 11
O
Output resolution • 3 Outputs • 3
P
Points/Properties • 59
Airside Linkage Alarm • 71 Airside Linkage Status • 73 Alarm Delay (min/deg) • 67 Alarm Limit Exceeded • 71 Alarming Temperature • 71 Analog Input Configuration • 71 Analog Output 2 Test • 67 BAS On/Off • 70 Compressor 1 Runtime • 70 Compressor 1 Runtime alarm • 71 Compressor 1 Service Alarm Timer • 60 Compressor 1 Test • 68 Compressor 2 Runtime • 70 Compressor 2 Runtime alarm • 71 Compressor 2 Service Alarm Timer • 60 Compressor 2 Test • 68 Compressor Safety alarm • 71 Compressor Safety Status • 70 Compressor Stages • 41, 68 Continuous Occupied Exhaust • 41, 68 Cooling Capacity • 63 Cooling Design Temp • 63 Cooling Lockout Temp • 60 DCV Max Ctrl Setpoint • 40, 60 DCV Max Vent Damper Pos • 60 Dehumidification Test • 68 Economizer Exists • 41, 68 Economizer High OAT Lockout • 60 Economizer Output • 59 Economizer Test • 68 Enthalpy Status • 70 Fan Mode • 38, 60 Fan Off Delay • 60 Fan Test • 68 Filter Alarm • 71 Filter Runtime • 70 Filter Service Alarm Timer • 60 Fire Shutdown • 70 Fire Shutdown alarm • 71 Heat 1 Test • 68 Heat 2 Test • 68 Heat Type • 41, 68 Heating Capacity • 63 Heating Design Temp • 63
RTU Open 77
Page 84
Index
Heating Lockout Temperature • 60
High CO2 alarm • 71
High SAT Alarm Limit • 67
High Space Humidity Alarm Limit • 67
High Space Relative Humidity alarm • 71
High Supply Air Temperature alarm • 71
HP Rev Cycle Lockout Temmp • 60
Humidistat Input Status • 70
Hysteresis • 63
IAQ Sensor alarm • 71
Indoor Air CO2 • 59, 73
Indoor CO2 Sensor Value @max (ma) • 41, 68
Indoor CO2 Sensor Value @min (ma) • 41, 68
Input # Function • 38, 60
Input # Switch Configuration • 38, 60
LAT Airflow Increase • 59
Linkage Collector • 73
Low SAT Alarm Limit • 67
Low Space Humidity Alarm Limit • 67
Low Space Relative Humidity alarm • 71
Low Supply Air Temperature alarm • 71
Maximum Heating SAT • 60
Minimum Cooling SAT • 60
Number of Heat Stages • 41, 68
OAQ Sensor alarm • 71
OAT System Sensor • 68
Occ Relative Humidity Setpoint • 40, 63
Occupancy Source • 38, 60
Occupancy Status • 70, 73
Occupied Alarm Hysteresis • 67
Occupied Cooling • 40, 63
Occupied Cooling 1 • 63
Occupied Cooling 2 • 63
Occupied Cooling Setpoint • 73
Occupied Heating • 40, 63
Occupied Heating 1 • 63
Occupied Heating 2 • 63
Occupied Heating Setpoint • 73
Occupied High CO2 Alarm Limit • 67
Operating Mode • 59
Optimal Start • 40, 63
Outdoor Air CO2 • 59
Outdoor Air Temp Sensor Alarm • 71
Outdoor Air Temperature • 59
Outdoor CO2 Sensor Value @max (ma) • 41, 68
Outdoor CO2 Sensor Value @min (ma) • 41, 68
Outside Air Temp Calibration • 60
Override Time Remaining • 70
Power Exhaust Setpoint • 40, 63
Power Exhaust Test • 68
Pushbutton Override • 60, 70
Reset Comp 1 Runtime Alarm • 70
Reset Comp 2 Runtime Alarm • 70
Reset Filter Runtime Alarm • 70
Reset Supply Fan Runtime Alarm • 70
Reversing Valve Test • 68
Safety Chain alarm • 71
Safety Chain Feedback • 70
Schedules • 70
Service Test • 68
Setpoint Slider • 71
Space Relative Humidity • 59, 73
Space Relative Humidity Sensor alarm • 71
Space sensor type • 38, 60 Space Temp Calibration • 60 Space Temp Sensor • 71 Space Temp Sensor Alarm • 71 Space Temperature • 73 Space Temperature - Prime Variable • 59 Space Temperature Alarm • 71 Supply Air Temp Calibration • 60 Supply Air Temp Sensor alarm • 71 Supply Air Temperature • 59 Supply Fan Runtime • 70 Supply Fan Runtime alarm • 71 Supply Fan Service Alarm Timer • 60 Supply Fan Status • 59 Switch Configuration • 71 System Cool Demand Level • 68 System Heat Demand Level • 68 System Mode • 59 System Outside Air Temperature • 68 System Space Temperature • 68 T5x Override Duration • 60 Unit Start Delay • 60 Unit Type • 41, 68 Unocc Free Cool Enable • 60 Unocc Relative Humidity Setpoint • 40, 63 Unoccupied Cooling • 40, 63 Unoccupied Cooling 1 • 63 Unoccupied Cooling 2 • 63 Unoccupied Cooling Setpoint • 73 Unoccupied Heating • 40, 63 Unoccupied Heating 1 • 63 Unoccupied Heating 2 • 63 Unoccupied Heating Setpoint • 73 Unoccupied High SPT Alarm Limit • 67 Unoccupied Low SPT Alarm Limit • 67
Vent Dmpr Pos / DCV Min Pos • 60 Power specifications • 3 Protection • 3
R
Replacing battery • 57 Rnet • 20 Rnet wiring specifications • 20 Rooftop equipment control power transformer • 8
S
Sequence of operation
Alarms • 51
Compressor Safety • 50
Cooling • 44
Dehumidification • 49
Demand limiting • 50
Door switch • 50
Economizer • 45
Enthalpy control • 47
Fan Status • 51
Filter Status • 51
Fire Shutdown • 50
Heat Pump operation • 49
Heating • 48
Indoor Air Quality • 47
Linkage • 53
78 RTU Open
Page 85
Index
Linkage Air Source Modes • 55
Occupancy • 43 Optimal Start • 46 Power Exhaust • 46 Remote occupancy • 50 Supply Fan • 44
Unoccupied Free Cooling • 46 Serial number • 56 Service Test • 37 Set communications protocol and baud rate • 10 Single Point Linkage • 75 Specifications • 3 SPT sensors • 20 Start-up • 36 Supply Air Temperature sensor • 22
T
T55 / T56 • 24 temperature sensors
Duct Air Temperature sensor • 22
SPT sensors • 20
Supply Air Temperature sensor • 22 Troubleshooting • 56
W
Weight • 3 Wiring
CO2 sensor • 24
Inputs • 3, 13
Outdoor air temperature sensor • 23
Output • 14
Supply air temperature sensor • 22
Wiring for power • 7 Wiring specifications • 11
Network • 11
Rnet • 20
RTU Open 79
Page 86
Page 87
Page 88
CARRIER CORPORATION ©2012
A member of the United Technologies Corporation family · Stock symbol UTX · Catalog No. 11-808-427-01 · 6/13/2012
Loading...