Carrier 10 SEER SPLIT-SYSTEM 38YCW Installation And Start-up Instructions Manual

Visit www.carrier.com
Installation and Start-Up Instructions
NOTE: Read the entire instruction manual before starting the
installation. This symbol indicates a change since the last issue.
SAFETY CONSIDERATIONS
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available. Read these instructions thor­oughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety-alert symbol When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU­TION. These words are used with the safety-alert symbol. DAN­GER identifies the most serious hazards which willresultinsevere personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
Before installing, modifying, or servicing system, main elec­trical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch(es) with a suitable warning label. Electrical shock can cause personal injury or death.
INTRODUCTION AND RECOMMENDATIONS
NOTE: In some cases noise has been traced to improper instal-
lation of equipment.
1. Locate unit away from windows, patios, decks, and so forth where unit operation sounds may disturb customer.
2. Ensure that vapor- and liquid-tubediametersare appropriate to capacity of unit.
3. Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends.
38YCW
10 SEER Split-System
Heat Pump
A98525
Fig. 1—Model 38YCW
.
4. Leave some slack between structure and unit to absorb vibration.
5. When passing refrigerant tubes through the wall, seal opening with RTV or other pliable silicon-based caulk. (See Fig. 2.)
6. Avoid direct refrigerant tubing contact with water pipes, duct work, floor joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap that comes in direct contact with tubing. (See Fig. 2.)
8. Ensure that refrigerant tubing insulation is pliable and com­pletely surrounds vapor tube.
9. When necessary, use hanger straps which are 1 in. wide and conform to shape of tubing insulation. (See Fig. 2.)
10. Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation.
When outdoor unit is connected to factory-approved indoor unit, outdoor unit contains system-refrigerant charge for operation with indoor unit of the same size when connected by 15 ft of field-supplied or factory-accessory tubing. For proper unit opera­tion, check refrigerant charge using charging information located on control-box cover and/or in the Check Charge section of this Instruction.
IMPORTANT: Maximum liquid-line size is 5/8-in. O.D. for all residential applications including long line applications.
IMPORTANT: Always install a liquid-line filter drier. Refer to Product Data Digest for appropriate part number. Obtain filter drier from your distributor or branch.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 5a 5a
PC 101 Catalog No. 533-80020 Printed in U.S.A. Form 38YCW-3SI Pg 1 2-02 Replaces: 38YCC-4SI
Avoid contact between tubing and structureNOTE:
OUTDOOR WALL INDOOR WALL
CAULK
LIQUID TUBE
C
INSULATION
THROUGH THE WALL
HANGER STRAP
(AROUND VAPOR
TUBE ONLY)
1 MIN.
SUSPENSION
VAPOR TUBE
JOIST
INSULATION
VAPOR TUBE
LIQUID TUBE
A94028
Fig. 2Connecting Tubing Installation
INSTALLATION
Step 1Check Equipment and Job Site
UNPACK UNIT Move to final location. Remove carton, taking care not to damage
unit. INSPECT EQUIPMENT
File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit-rating plate on unit-service panel. It contains information needed to properly install unit. Check rating plate to be sure unit matches job specifications.
3
⁄8″D. (9.53) TIEDOWN
A
KNOCKOUTS (2) PLACES
B
A94199
Dimensions (In.)
UNIT
SIZE
018–030 22-1/2 x 22-1/2 3-11/16 18-1/8 14-3/8 036–060 30 x 30 6-1/2 23-1/2 20
MINIMUM
MOUNTING-PAD
DIMENSIONS
TIEDOWN KNOCKOUT LOCATIONS
ABC
Fig. 3Mounting Unit to Pad
Step 4Operating Ambients
The minimum outdoor-operating ambient in cooling mode is 55°F, and the maximum outdoor-operating ambient in cooling mode is 125°F. The maximum outdoor-operating ambient in heating mode is 66°F.
Step 5Elevate Unit
Step 2Install on a Solid, Level Mounting Pad
If conditions or local codes require the unit be attached to pad, tie-down bolts should be used and fastened through knockouts provided in unit base pan. Refer to unit-mounting pattern in Fig. 3 to determine base-pan size and knockout-hole location.
On rooftop applications, mount on level platform or frame 6 in. above roof surface. Place unit above a load-bearing wall and isolate unit and tubing set from structure. Arrange supporting members to adequately support unit and minimize transmission of vibration to building. Consult local codes governing rooftop applications.
Roof-mounted units exposed to winds above 5 mph may require wind baffles to achieve adequate defrost. Consult Low-Ambient Guideline for wind-baffle construction.
NOTE: Unit must be level to within ±2° (±3/8 in./ft) per compressor manufacturer specifications.
Step 3Clearance Requirements
When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 30-in. clearance to service end of unit and 48 in. above unit. For proper airflow, a 6-in. clearance on 1 side of unit and 12 in. on all remaining sides must be maintained. Maintain a distance of 24 in. between units. Position so water, snow, or ice from roof or eaves cannot fall directly on unit.
On rooftop applications, locate unit at least 6 in. above roof surface.
Accumulation of water and ice in base pan may cause equipment damage.
In areas where prolonged freezing temperatures are encountered, elevate unit per local climate and code requirements to provide clearance above estimated snowfall level and ensure adequate drainage of unit.
Step 6Check Indoor And Outdoor AccuRater® Piston
Check indoor-coil piston to see if it matches the required piston shown on outdoor unit-rating plate. If it does not match, replace indoor-coil piston with piston shipped with outdoor unit. The piston shipped with outdoor unit is correct for any approved indoor-coil combination.
Remove indoor-coil piston if unit is to be installed on system with a TXV-metering device.
Step 7Check Defrost Thermostat
Check defrost thermostat to ensure it is properly located and securely attached. There is a liquid header with a brass distributor and feeder tube going into outdoor coil. At the end of 1 of the feeder tubes, there is a 3/8-in. O.D. stub tube approximately 3 in. long. The defrost thermostat should be located on stub tube. Note that there is only 1 stub tube used with liquid header, and on most units it is the bottom circuit.
2
Table 1Refrigerant Connections and Recommended Liquid- and Vapor-Tube Diameters (In.)
UNIT
SIZE
018, 024 3/8 3/8 3/4 3/4 3/4 3/4 030, 036 3/8 3/8 3/4 3/4 3/4 7/8 042, 048 3/8 3/8 7/8 7/8 7/8 1-1/8
060 3/8 3/8 7/8 1-1/8 7/8 1-1/8
NOTES:
1. Tube diameters are for lengths up to 50 ft. For tubing lengths greater than 50 ft, consult Long Line section of the Application Guideline.
2. Do not apply capillary-tube indoor coils to these units.
Connection Diameter Tube Diameter Connection Diameter Tube Diameter Connection Diameter Tube Diameter
LIQUID VAPOR VAPOR (LONG LINE)
Step 8Make Piping Connections
Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury or death. Use all service ports and open all flow-control devices, including solenoid valves.
If ANY refrigerant tubing is buried, provide a 6 in. vertical rise at service valve. Refrigerant tubing lengths up to 36 in. may be buried without further special consideration. For lengths above 36 in., consult your local distributor.
To prevent damage to unit or service valves observe the following:
Use a brazing shield.
Wrap service valves with wet cloth or use a heat-sink
material.
Outdoor units may be connected to indoor section using accessory­tubing package or field-supplied refrigerant-grade tubing of cor­rect size and condition. For tubing requirements beyond 50 ft length or 20 ft vertical differential, substantial capacity and performance losses can occur. Following the recommendations in the Residential Split-System Long-Line Application Guideline will reduce these losses. Refer to Table 1 for field-tubing diam­eters.
REFRIGERANT TUBING Connect tubing to fittings on outdoor unit vapor- and liquid-
service valves. (See Table 1.) Use refrigerant-grade tubing. Refer to appropriate section below for type of service valves installed on unit.
SWEAT CONNECTION
non-silver-bearing brazing material. Consult local code re­quirements.
Refrigerant tubing and indoor coil are now ready for leak testing. This check should include all field and factory joints.
PISTON BODY
PISTON
PISTON RETAINER
STRAINER
SWEAT/FLARE ADAPTER
A97512
Fig. 4Liquid-Service Valve with Sweat-Adapter
Tube
FINAL TUBING CHECK IMPORTANT: Check to be certain factory tubing on both indoor
and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.
Step 9Make Electrical Connections
To avoid valve damage while brazing, service valves must be wrapped in a heat-sinking material such as a wet cloth.
1. Remove plastic retainer holding outdoor piston in liquid­service valve.
2. Locate adapter tube shipped with unit.
3. Install strainer in adapter tube and connect tube to service valve. (See Fig. 4.)
4. Connect refrigerant tubing to fittings on outdoor-unit vapor­and liquid-service valves.
5. Service valves are closed from factory and ready for brazing. After wrapping service valve with a wet cloth, tubing set can be brazed to service valve using either silver-bearing or
To avoid personal injury or death, do not supply power to unit with compressor terminal-box cover removed.
Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit-rating plate. Contact local power company for correction of improper voltage. See unit-rating plate for recommended circuit­protection device.
NOTE: Operation of unit on improper line voltage constitutes abuse and could affect unit reliability. See unit-rating plate. Do not install unit in system where voltage or phase imbalance (3 phase) may fluctuate above or below permissible limits.
NOTE: Use copper wire only between disconnect switch and unit.
3
NOTE: Install branch-circuit disconnect of adequate size per NEC to handle unit-starting current. Locate disconnect within sight from and readily accessible from unit, per Section 440-14 of NEC.
only, set thermostat to OFF and close electrical disconnect to outdoor unit. A crankcase heater is required if refrigerant tubing is longer than 50 ft.
ROUTE GROUND AND POWER WIRES Remove access panel and control box to gain access to unit wiring.
Extend wires from disconnect through power-wiring hole provided and into unit-control box.
The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes. Failure to follow this warning can result in an electric shock, fire, or death.
CONNECT GROUND AND POWER WIRES Connect ground wire to ground connection in control box for
safety. Connect power wiring to contactor as shown in Fig. 5.
DISCONNECT PER N.E.C. AND/OR LOCAL CODES
CONTACTOR
FIELD POWER
WIRING
3 PHASE ONLY
BLUE
Step 11Install Electrical Accessories
Refer to the individual instructions packaged with kits or acces­sories when installing.
Step 12Start-Up
To prevent compressor damage or personal injury, observe the following:
Do not overcharge system with refrigerant.
Do not operate unit in a vacuum or at negative pressure.
Do not disable low-pressure switch.
In scroll compressor applications:
Dome temperatures may be hot.
To prevent personal injury wear safety glasses, protective clothing, and gloves when handling refrigerant and observe the following:
Back-seating service valves are not equipped with Schrader valves. Fully back seat (counterclockwise) valve stem before removing gage-port cap.
Front-seating service valves are equipped with Schrader valves.
FIELD GROUND
WIRING
GROUND LUG
A94025
Fig. 5Line Power Connections
CONNECT CONTROL WIRING Route 24v control wires through control-wiring grommet and
connect leads to control wiring. Refer also to Installation Instruc­tions packaged with thermostat.
Use No. 18 AWG color-coded, insulated (35°C minimum) wire. If thermostat is located more than 100 ft from unit, as measured along the control-voltage wires, use No. 16 AWG color-coded wire to avoid excessive voltage drop.
All wiring must be NEC Class 1 and must be separated from incoming power leads.
Use furnace transformer, fan-coil transformer, or accessory trans­former for control power, 24v/40va minimum.
NOTE: Use of available 24v accessories may exceed the mini­mum 40va power requirement. Determine total transformer load­ing and increase the transformer capacity or split the load with an accessory transformer as required.
FINAL WIRING CHECK IMPORTANT: Check factory wiring and field-wire connections
to ensure terminations are secured properly. Check wire routing to ensure wires are not in contact with tubing, sheet metal, and so forth.
Step 10Compressor Crankcase Heater
When equipped with a crankcase heater, furnish power to heater a minimum of 24 hr before starting unit. To furnish power to heater
Do not vent refrigerant to atmosphere. Recover during system repair or final unit disposal.
If refrigerant tubes or indoor coil are exposed to atmosphere, they must be evacuated to 500 microns to eliminate contamination and moisture in the system.
Follow these steps to properly start up the system:
1. Fully back seat (open) liquid- and vapor-tube service valves.
2. Unit is shipped with valve stem(s) front seated (closed) and caps installed. Replace stem caps after system is opened to refrigerant flow. Replace caps finger-tight and tighten with wrench an additional 1/12 turn.
3. Close electrical disconnects to energize system.
4. Set room thermostat to desired temperature. Be sure set point is below indoor ambient temperature.
5. Set room thermostat to HEAT or COOL and fan control to ON or AUTO, as desired. Operate unit for a minimum of 15 minutes. Check system refrigerant charge.
3-phase scroll compressors are rotation sensitive.
A flashing LED on phase monitor indicates reverse rotation.
(See Fig. 7 and Table 2.) This will not allow contactor to be energized.
Disconnect power to unit and interchange 2 field-wiring leads on unit contactor.
Step 13Check Charge
Factory charge is shown on unit-rating plate. To check charge in cooling mode, refer to Cooling-Only Procedure on unit wiring and charging label.
4
COOLING-ONLY PROCEDURE NOTE: If superheat- or subcooling-charging conditions are not
favorable, charge must be weighed in accordance with unit-rating plate ±0.6 oz/ft of 3/8-in. liquid line above or below 15 ft respectively.
EXAMPLE: To calculate additional charge required for a 25-ft line set: 25 ft – 15 ft = 10 ft X 0.6 oz/ft=6ozofadditional charge HEATING CHECK-CHART PROCEDURE To check system operation during heating cycle, refer to the
Heating Check Chart on outdoor unit. This chart indicates whether a correct relationship exists between system operating pressure and air temperature entering indoor and outdoor units. If pressure and temperature do not match on chart, system-refrigerant charge may not be correct. Do not use chart to adjust refrigerant charge.
NOTE: When charging is necessary during heating season, charge must be weighed in accordance with unit rating plate ±0.6 oz/ft of 3/8-in. liquid line above or below 15 ft respectively.
Step 14Final Checks IMPORTANT: Before leaving job, be sure to do the following:
1. Securely fasten all panels and covers.
2. Tighten service valve-stem caps to 1/12-turn past finger-tight.
3. Leave Users Manual with owner. Explain system operation and periodic maintenance requirements outlined in manual.
4. Fill out Dealer Installation Checklist and place in customer file.
Table 2Phase-Monitor LED Indicators
LED STATUS OFF
FLASHING Reversed phase
ON Normal
No call for compressor
operation
Fig. 7Phase-Monitor Control
A00010
5
OTHER
HP THERMOSTAT
24 VAC HOT
24 VAC COM
HEAT STAGE 2 COOL/HEAT
STAGE 1 INDOOR FAN
RVS COOLING EMERGENCY
HEAT
NOTE: Remove wires from crimp nut in indoor fan coil when installing outdoor thermostat.
IMPORTANT: When using outdoor thermostat, W2 must be energized when requesting supplemental heat.
W2
FA, FB, FC,
FD, FF, FH
FAN COIL
R
C
Y
G
O
E
W3
W2
HEAT PUMP
R
C
E
G
THERMOSTAT
R
C
W2
Y
O
ONE
OUTDOOR
ODT
OTHER
NON-PROGRAMMABLE
HP THERMOSTAT
24 VAC HOT
24 VAC COM
HEAT STAGE 2 COOL/HEAT
STAGE 1
INDOOR FAN
RVS COOLING
EMERGENCY HEAT
R
C
W
Y
G
O
E
FA, FB, FC,
FD, FF
FAN COIL
R
C
W2
G
HEAT PUMP
R
C
W2
Y
O
CARRIER
PROGRAMMABLE
THERMOSTAT
MODEL HP
24 VAC HOT
INDOOR FAN
HEAT STAGE 2 COOL/HEAT
STAGE 1 RVS COOLING
NOT USED
24 VAC COM NOT USED TROUBLE
OPTIONAL OUTDOOR SENSOR CONNECTION
CARRIER
PROGRAMMABLE
THERMOSTAT
MODEL HP
24 VAC HOT
INDOOR FAN
HEAT STAGE 2 COOL/HEAT
STAGE 1 RVS COOLING
NOT USED
24 VAC COM NOT USED TROUBLE
OPTIONAL OUTDOOR SENSOR CONNECTION
NOTE: Remove wires from crimp nut in indoor fan coil when installing outdoor thermostat.
IMPORTANT: When using outdoor thermostat, W2 must be energized when requesting supplemental heat.
FA, FB, FC, FD, FF, FH
R
G
W/W1
Y/Y2
O/W2
Y1/W2
C
B L
S1
S2
R
G
W/W1
Y/Y2
O/W2
Y1/W2
C
B
L
S1
S2
40FKA
FK4C
FAN COIL
FAN COIL
DH
R G
W1 W2
Y/Y2
O
C
Y1
W3
R
G
W2
E
C
HEAT PUMP
J1 JUMPER
J2 JUMPER
HEAT PUMP
CARRIER
PROGRAMMABLE
THERMOSTAT
MODEL HP
24 VAC HOT
R
W2
Y
O
C
W2
OUTDOOR
THERMOSTAT
R
Y
O
C
ONE
ODT
INDOOR FAN
R
G
Y/Y2
C
B
S1
S2
W/W1
Y/Y2
O/W2
Y1/W2
S1
S2
EHR
EHR
EHR
L
HEAT STAGE 2 COOL/HEAT
STAGE 1 RVS COOLING
NOT USED
24 VAC COM NOT USED TROUBLE
OPTIONAL OUTDOOR SENSOR CONNECTION
CARRIER
PROGRAMMABLE
THERMOSTAT
MODEL HP
24 VAC HOT
INDOOR FAN
HEAT STAGE 2 COOL/HEAT
STAGE 1 RVS COOLING
NOT USED
24 VAC COM NOT USED TROUBLE
OPTIONAL OUTDOOR SENSOR CONNECTION
NOTE: Remove wires from crimp nut in indoor fan coil when installing outdoor thermostats.
IMPORTANT: When using outdoor thermostats, W2 must be energized when requesting supplemental heat.
W/W1
O/W2
Y1/W2
Fig. 6Typical 24v Circuit Connections
6
R
G
C
B
L
FA, FB, FC,
FD, FF, FH
FAN COIL
FA, FB, FC,
FD, FF, FH
FAN COIL
IF AVAILABLE
*
W3
R
G
W2
E
C
R
G
W2
E
W3
C
* *
*
HEAT PUMP
HEAT
PUMP
OUTDOOR
THERMOSTATS
ODT
R
W2
Y
O
ODT
C
R
W2
Y
O
C
TWO
A01384
WIRING DIAGRAM NOTES:
1. CARRIER THERMOSTAT-WIRING DIAGRAMS ARE ONLY ACCURATE FOR MODEL NUMBERS BEGINNING WITH TSTAT_______.
2. WIRING MUST CONFORM TO NEC OR LOCAL CODES.
3. SOME UNITS ARE EQUIPPED WITH PRESSURE SWITCH(ES), TEMPERATURE SWITCH, OR 5–MINUTE COMPRESSOR-CYCLE PROTECTION. CONNECT 24V FIELD WIRING TO FACTORY-PROVIDED STRIPPED LEADS.
4. THERMOSTATS ARE FACTORY CONFIGURED WITH 5-MINUTE COMPRESSOR-CYCLE PROTECTION AND 4-CYCLES-PER-HR LIMIT. SEE THERMOSTAT­INSTALLATION INSTRUCTIONS FOR DETAILS.
5. TO STAGE ELECTRIC-RESISTANCE HEAT, CONSULT OUTDOOR THERMOSTAT-INSTALLATION INSTRUC­TIONS.
6. UNDERLINED LETTER ON DUAL TERMINAL INDI­CATES ITS USAGE. FOR EXAMPLE: O/W2 MEANS O; O/W2MEANS W2
7. OUTDOOR-TEMPERATURE SENSOR MUST BE AT­TACHED IN ALL DUAL-FUEL INSTALLATIONS. JUMPER WIRE BETWEEN O/W2 AND L THERMOSTAT TERMINALS MUST BE PRESENT.
8. Y1 AND O CONNECTIONS TO 2–STAGE FURNACES MAY NOT EXIST OR MAY ONLY BE A WIRE RATHER THAN A SCREW TERMINAL.
SEQUENCE OF OPERATION
NOTE: Defrost-control board is equipped with 5-minute lockout
timer that may be initiated upon any interruption of power. With power supplied to indoor and outdoor units, transformer is
energized. Cooling On a call for cooling, thermostat makes circuits R-O, R-Y, and
R-G. Circuit R-O energizes reversing valve, switching it to cooling position. On 3-phase models with scroll compressors, the units are equipped with a phase monitor to detect if the incoming power is correctly phased for compressor operation. If phasing is correct, circuit R-Y energizes contactor, starting outdoor-fan motor and compressor circuit. R-G energizes indoor unit-blower relay, start­ing indoor-blower motor on high speed.
NOTE: If the phasing is incorrect, the contactor will not be energized. To correct the phasing, interchange any 2 of the 3 power connections on the field side.
When thermostat is satisfied, its contacts open, de-energizing the contactor and blower relay. Compressor and motors should stop.
NOTE: If indoor unit is equipped with a time-delay relay circuit, the blower runs an additional 90 sec to increase system efficiency.
Heating On a call for heating, thermostat makes circuits R-Y and R-G. If
phasing is correct, circuit R-Y energizes contactor, starting outdoor-fan motor and compressor. Circuit R-G energizes indoor­blower relay, starting blower motor on high speed.
Should temperature continue to fall, R-W2 is made through second-stage room-thermostat bulb. Circuit R-W2 energizes a sequencer, bringing on first bank of supplemental electric heat and providing electrical potential to second heater sequencer (if used). If outdoor temperature falls below setting of outdoor thermostat (field-installed option), contacts close to complete circuit and bring on second bank of supplemental electric heat.
When thermostat is satisfied, its contacts open, de-energizing contactor and sequencer. All heaters and motors should stop.
When the thermostat is satisfied, its contacts open, de-energizing contactor and sequencer. All heaters and motors should stop.
Quiet Shift
Quiet Shift is a field-selectable defrost mode, which will eliminate occasional noise that could be heard at the start of the defrost cycle and restarting of heating cycle. It is selected by placing DIP switch 3 (on defrost board) in ON position.
When Quiet Shift switch is placed in ON position, and a defrost is initiated, the following sequence of operation will occur. Revers­ing valve will energize, compressor will turn off for 30 sec, then turn back on to complete defrost. At the start of heating cycle after conclusion of defrost mode, reversing valve will de-energize, the compressor will turn off for another 30 sec, and the fan will turn off for 40 sec, before starting in the heating mode.
T2 C C O
OF2
CESO130076–00
→ →
O R W
2
Y C
SPEEDUP
Defrost
P1
J1
DFT
Speedup Pins
DFT
T1 Y
30
60
INTERVAL TIMER
120
90
60
30
P3
ON
OFF
QUIET
SHIFT
Quiet Shift
Defrost interval DIP switches
Fig. 8Defrost Control
The defrost control is a time/temperature control which includes a field-selectable time period (DIP switch 1 and 2 on the board) between defrost cycles of 30, 60, 90, or 120 minutes (factory set at 90 minutes).
To initiate a forced defrost, two options are available depending on the status of the defrost thermostat.
If defrost thermostat is closed, speedup pins (J1) must be shorted by placing a flat head screwdriver in between for 5 sec and releasing, to observe a complete defrost cycle. When the Quiet Shift switch is selected, compressor will be turned off for two 30 sec intervals during this complete defrost cycle as explained previously. When Quiet Shift switch is in factory default OFF position, a normal and complete defrost cycle will be observed.
If defrost thermostat is in open position, and speedup pins are shorted (with a flat head screwdriver) for 5 sec and released, a short defrost cycle will be observed (actual length is dependent upon the selected Quiet Shift position). When Quiet Shift switch is in ON position, the length of defrost is 1 minute (30 sec compressor off period followed by 30 sec of defrost with com­pressor operation). On return to heating operation, compressor will again turn off for an additional 30 sec and the fan for 40 sec. When the Quiet Shift is in OFF position, only a brief 30 sec cycle will be observed.
OF1
A91444
7
If it is desirable to observe a complete defrost in warmer weather, the thermostat must be closed as follows:
1. Turn off power to outdoor unit.
2. Disconnect outdoor fan motor lead from OF2 on control board. (See Fig. 8.) Tape to prevent grounding.
3. Restart unit in heating mode, allowing frost to accumulate on outdoor coil.
4. After a few minutes in heating mode, liquid line temperature should drop below closing point of defrost thermostat (ap­proximately 30°F).
NOTE: Unit will remain in defrost until defrost thermostat reopens at approximately 80°F coil temperature at liquid line or remainder of defrost cycle time.
5. Turn off power to outdoor and reconnect fan motor lead to OF2 on control board after above forced defrost cycle.
Step 1Final Checks IMPORTANT: Before leaving job, be sure to do the following:
1. Securely fasten all panels and covers.
2. Tighten service valve stem caps to 1/12-turn past finger tight.
3. Leave Users Manual with owner. Explain system operation and periodic maintenance requirements outlined in manual.
CARE AND MAINTENANCE
For continuing high performance and to minimize possible equip­ment failure, periodic maintenance must be performed on this equipment.
Frequency of maintenance may vary depending upon geographic areas, such as coastal applications.
Copyright 2002 CARRIER Corp. 7310 W. Morris St. Indianapolis, IN 46231 38ycw3si
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 5a 5a
PC 101 Catalog No. 533-80020 Printed in U.S.A. Form 38YCW-3SI Pg 8 2-02 Replaces: 38YCC-4SI
Loading...