Carrier 09DK054-084 User Manual

Page 1
09DK054-084
HEATING & COOLING
Air-Cooled Condenser Units
50/60 Hz
à
Installation, Start-Up and
Service Instructions
Air-Cooled Packages
Page
SAFETY CONSIDERATIONS ...
INSTALLATION .................................................
Step 1 — Complete Pre-Installation
Checks ............................................................................. 1
Step 2 — Rig and Place Unit ..........................................4
• RIGGING
• PLACING THE UNIT
Step 3 — Complete Refrigerant Piping
• GENERAL
• COIL REFRIGERANT PIPING INSTALLATION
• TUBING PACKAGE INSTALLATION
• THREE AND FOUR COIL SPLIT, COIL CIRCUITING APPLICATIONS; 054-084 UNITS
• REFRIGERANT LINE SIZING
• LIQUID SHUTOFF VALVE AND SIGHT GLASS
• PRESSURE RELIEF
• REFRIGERANT RECEIVER
• LIQUID LIFT
Step 4 — Complete Electrical
Connections..................................................................21
• GENERAL
• FIELD CQNNECTIONS
• MAIN POWER WIRING
• CONTROL CIRCUIT POWER WIRING
• GENERAL WIRING NOTES
• DESCRIPTION OF CONTROLS
Step 5 — Add Accessories as Needed
START-UP..........................................................................29
System Evacuation and
Dehydration ..................................................................29
Charging Procedure........................................................29
Check Operation of Condenser Fan Motor
Controls and Rotation of Fans
SERVICE ......................................................................29-31
Cleaning Condenser Coils
Condenser Fans ..............................................................29
Lubrication
Head Pressure Control ..................................................29
• FAN CYCLING
.......................................................................
........................................
.....................
.....................
................................
SAFETY COIVISIDERATIOIMS
Installing, starting up, and servicing air-conditioning equip
ment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated struc tures, etc.).
Only trained, qualified installers and service mechanics
should install, start up, and service this equipment (Fig. 1).
Untrained personnel can perform basic maintenance func
tions such as cleaning coils. All other operations should be performed by trained service personnel.
,.. 1
1-28
28
29
29. 29
7
Fig. 1 — Model 09DK (084 Shown)
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging and setting bulky equipment.
See Tables lA and IB for Physical Data.
ELECTRIC SHOCK HAZARD Separate power sources (main and control cir
cuit power) are used for these units. Be sure both main and control circuit powers are dis connected before servicing.
INSTALLATION
Step 1 — Complete Pre-Installation Checks —
Examine for damage incurred during shipment. File claim immediately with transit company if damage is found. Ver ify that the nameplate electrical requirements match the avail able power supply. Check the shipment for completeness.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 12 PC 111 Catalog No 530-953 Printed in U.S A Form 09DK-4SI Pg 1 4-93 Replaces: New Tab 4a
Page 2
Table IA — Physical Data 60 fìz
English
09DK NOMINAL TONS OPERATING WEIGHT-lb
Cu-AI* Cu-Cut
SHIPPING WEIGHT-lb“
Cu-AI‘ Cu-Cut
054
50
1695 1983
2010 2298 2569 2938 3403
REFRIGERANTS NOMINAL HEAT REJECTION
(TONS)tt CONDENSER FANS
No. of Blades No. of Fans Fan Diameter-In. 30 AIrflow-cfm Fan Speed-rpm Fan Motor-hp 1
CONDENSER COILS
Quantity 4 FIns/in. 17 No. of Rows Total Face Area (sq ft)
65.8 78.6 95.4 103.5
4 4 4 4 4 4 6 6
35,000
1140 1140
2
80.5
TD — Temperature Difference = Saturated Condensing Temperature - Entering-Air Temperature
‘Copper tubes and aiuminum fins.
TCopper tubes and copper fins.
“Packaging option includes skid and coil protection.
ttNominal heat rejection based on refrigerant R-22, 15° F subcooling, and a 30° F temperature difference (TD).
064
60
1845 2200 2278 2617
2136 2521
R-134A, R-22, R-12, R-500, R-502
30 30 30
35,000 52,000 51,000
1 1 1 4 4 4
17 17 17
3 2
80.5 116.7 1167
074
70
1140 1140
084
80
2421 3099
2725
3
SI
09DK NOMINAL kW OPERATING WEIGHT-kg
Cu-AI* Cu-Cut
SHIPPING WEIGHT-kg“
Cu-AI* Cu-Cut
REFRIGERANTS NOMINAL HEAT REJECTION
(kW)tt CONDENSER FANS
No. of Blades No. of Fans Fan DIameter-mm AIrflow-L/s
Fan Speed-r/s Fan Motor-kW
CONDENSER COILS
Quantity
FIns/m No. of Rows Total Face Area (sq m)
TD — Temperature Difference = Saturated Condensing Temperature - Entering-Air Temperature
‘Copper tubes and aluminum fins.
tCopper tubes and copper fins.
“Packaging option includes skid and coil protection
ttNominal heat rejection based on refrigerant R-22, 8.3° C subcooiing, and a 16.7° C temperature difference (TD).
054 064 074
175.7 210.9 246.0 281.2 769
900 912 969 1144
1042 1165 1333 1544
231.3
4 4
762
16 520
19
.746
4
669
2 3 2 3
7.5
837 998
1033
R-134A, R-22, R-12, R-500, R-502
276 2 335.3
4 4
762 762
16 520 24 540
19 19
.746 .746
• 669 669
4 4 4
75 10.84 10.84
1187
4 6
084
1098 1406
1236
363 8
4 6
762
24 070
19
746
669
Page 3
Table 1B — Physical Data 50 Hz
English
09DK NOMINAL TONS OPERATING WEIGHT-lb
Cu-AI* Cu-Cut
SHIPPING WEIGHT-lb"
Cu-AI* 2010
Cu-Cut REFRIGERANTS NOMINAL HEAT REJECTION (TONS)tt CONDENSER FANS
No. of Blades
No. of Fans
Fan DIameter-ln. 30 30 30 30
AIrflow-cfm
Fan Speed-rpm 950 950 950 950
Fan Motor-hp 1 1 CONDENSER COILS
Quantity
Fins/in.
No. of Rows
Total Face Area (sq ft)
TD — Temperature Difference = Saturated Condensing Temperature - Entering-Air Temperature
'Copper tubes and aluminum fins
tCopper tubes and copper fins.
"Packaging option includes skid and coil protection.
ttNominal heat rejection based on refrigerant R-22, 15° F subcooling, and a 30° F temperature difference (TD).
054 064 074
50 60 70
1695 1845 2200 1983 2278
2298 2569
65.8 78.6
6 6 6 6 4 4 6 6
35,000 35,000 52,000 51,000
4 4 4 4
17 17 17 17
2
80.5 80.5 116.7 1167
2136 2521
R-134A, R-22, R-12, R-500, R-502
3
2617 3099
2938
95 4 103.5
1
2
084
80
2421
2725
3403
1
3
SI
09DK 054 064 074 084 NOMINAL kW OPERATING WEIGHT-kg
Cu-AI* Cu-Cut
SHIPPING WEIGHT-kg"
Cu-AI*
Cu-Cut REFRIGERANTS NOMINAL HEAT REJECTION
(kW)tt CONDENSER FANS
No. of Blades No. of Fans Fan DIameter-mm 762 762 762 762 AIrflow-L/s 16 520 16 520 24 540 24 070 Fan Speed-r/s 15.8 15.8 15.8 15.8 Fan Motor-kW .746
CONDENSER COILS
Quantity Fins/m 669 669 669 669 No. of Rows
Total Face Area (sq m)
TD — Temperature Difference = Saturated Condensing Temperature - Entering-Air Temperature
•Copper tubes and aluminum fins
tCopper tubes and copper fins
"Packaging option includes skid and coil protection.
ttNominal heat rejection based on refrigerant R-22, 8 3° C subcooling.
175 7
769 837 998 900 1033
912 969
1042
231.3 276.2 335.3 363.8
6 4
4 2
7.5
and a 16.7° C temperature difference (TD)
210 9 246 0
1165 1333
R-134A, R-22, R-12,R-500, R-502
6 6 6 4 6 6
746 746
4 4 3 2 3
7.5
281 2
1187 1406 1144
10 84 10 84
1098
1236 1544
.746
4
Page 4
Step 2 — Rig and Place Unit
RIGGING — These units are designed for overhead rig ging and this method should be used. Lifting holes are pro vided in the frame base rails which are marked for rigging (see rigging label on the unit). It is recommended that field supplied pipes of sufficient length that extend beyond the frame are passed through the holes. Attach cables, chains, or straps to both ends of the pipes. Use spreader bars or a frame to keep the cables, chains, or straps clear of the unit sides. All cables should run to a central suspension point so that the angle from the horizontal is not less than 45 degrees. See Fig. 2 and Table 1 for weight distribution information. Standard coil protection packaging will pro vide some protection to the unit. Raise and set the unit down carefully.
Domestic Units With No Overhead Rigging— Standard con denser packaging consists of coil protection only. Skids are not provided as part of the standard packaging. If overhead rigging is not available at the jobsite, place the unit on a skid or pad by using jacks at the rigging points before drag ging or rolling. When rolling, use a minimum of 3 rollers. When dragging, pull the pad or skid. Do not apply pressure
to the unit. Raise from above to lift off the pad or skid
when in final position. See rigging section above for more information.
Export and Domestic Units With Skids— All export units are mounted on skids with vertical coil protection. Leave the unit on the skid until it is in the final position. While on
the skid, the unit can be rolled, dragged or forked; do not
apply force to the unit. Use a minimum of 3 rollers when
rolling, and raise from above to remove the skid when unit is in the final position. See rigging procedure above for more information.
A CAUTION
Do not forklift these units unless attached to a skid de signed for forklifting; damage to unit may occur. If uti lizing a packaging option which includes a skid, the forklift truck must have at least a 60-in. (1524 mm) fork.
PLACING THE UNIT — Locate the condenser where an adequate supply of inlet outdoor air is available. Do not lo cate where the possibility of air recirculation exists, such as under a roof overhang. Also, locate the condenser in an area free from airborne dirt or other foreign material which could clog the condenser coils. Refer to Fig. 3 and 4 for airflow clearances. For multiple units, allow 8 ft (2440 mm) separation between units for airflow and service. Placement area must be level and strong enough to support operating weight of the unit (Fig. 2 and Table 1). It is recommended to bolt unit securely to pad when unit is positioned and lev eled. Fasteners for mounting unit are field supplied. If vi bration isolators are required for a particular installation, refer to the unit weight distribution data table and diagram below to help select the proper isolators.
Y - DIMENSION
UNIT 09DK
054
064
074
084
COIL TYPE*
*Cu-AI — Copper Tubes, Aluminum Fins
Cu-Cu — Copper Tubes, Copper Fins.
UNIT 09DK
054
064
074
084
COIL TYPE*
Cu-AI 1695 (769)
Cu-Cu
Cu-AI
Cu-Cu
Cu-AI
Cu-Cu
Cu-AI
Cu-Cu
TOTAL WEIGHT
1983 (900) 1845 (837)
2278 (1033)
2200 (998)
2617 (1187) 2421 (1098)
3099 (1406) 843 (382) 751 (341)
*Cu-AI — Copper Tubes, Aiuminum Fins.
Cu-Cu — Copper Tubes, Copper Fins.
Cu-AI
Cu-Cu
Cu-AI
Cu-Cu
Cu-AI
Cu-Cu
Cu-AI
Cu-Cu
lb (kg)
X- DIMENSION
CENTER OF GRAVITY In. (mm) X Dimension
48.1 (1222)
48.3 (1227) 48 2 (1224)
44,5 (1232)
56 7 (1440)
57.4 (1458)
57.1 (1450) 581 (1476)
A
452 (205) 425 (193)
524 (238) 497 (225) 489 (222)
598 (271)
618 (280)
722 (328) 673 (305)
Y Dimension
42 7 (1084) 42 9 (1090)
42 8 (1087)
43.1 (1095) 42 5 (1080)
42.8 (1087) 42 6 (1082)
43 0 (1092)
OPERATING CORNER WEIGHTS lb (kg)
B C D
462 (210)
571 (259) 542 (246) 568 (258)
526 (239) 630 (286)
581 (264)
396 (180) 422 (191) 468 (212)
434 (197)
486 (220) 589 (267)
541 (245) 626 (284)
709 (322)
494 (224) 459 (208)
571 (259) 675 (306)
796 (361)

Fig. 2 — Weight Distribution

Page 5
NOTES:
1. The approximate operating weight of the unit is: 09DK-054—
09DK-054-C 09DK-064— 09DK-064-C
2. Unit must have clearances for airflow as follows: Top — Do not restrict in any way. Ends — 5 ft [1524 mm] Sides — 6 ft [1829 mm]
3. All units are shipped with a capacity split tubing kit. This kit may be used by the field to obtain 100%, 50%/50% and 67%/33% capacity splits. To obtain a 33%/33%/33% capacity split, coils must be manifolded by the field. Coils' are factory circuited for a 33%/33%/17%/17% capacity split.
________
-------------
-------------
-------------
► 1695 lb [769 kg]
»■ 1983 lb [900 kg]
»• 1845 lb [837 kg]
»-2278 lb [1033 kg]
CONTROL BOX
END
UNIT
09DK-054—
09DK-054-C
09DK-064—
09DK-064-C
DIMENSION Y DIMENSION X
3'-6 11/16”
[1084 mm]
3'-6 7/8"
[1090 mm]
3'-6 3/4"
[1087 mm]
3’-7 1/8"
[1095 mm]
4'-1/8"
[1222 mm]
4'-5/16"
[1227 mm]
4'-3/16"
[1224 mm]
4'-1/2"
[1232 mm]
OPERATING CORNER WEIGHTS A B
452 lb
[205 kg]
524 lb
[238 kg]
489 lb
[222 kg]
598 lb
[271 kg]
425 lb
[193 kg]
497 lb
[225 kg]
462 lb
[210 kg]
571 lb
[259 kg]
C
396 lb
[180 kg]
468 lb
[212 kg]
434 lb
[197 kg]
542 lb
[246 kg]
D
422 lb
[191 kg]
494 lb
[224 kg]
459 lb
[208 kg]
568 lb
[258 kg]
CAPACITY SPLIT
100% 50%/50% 67%/33%
33%/33%/33%
33%/33%/17%/17%
HOT GAS
LIQUID
HOT GAS
LIQUID
HOT GAS
LIQUID
HOT GAS 1
LIQUID
HOT GAS 1 7
LIQUID
TYPE
T-A 1/2'-
C224 7rain3
BASE OVERALL
CONNECTIONS
N0.5
1/3.5,7 2,4.6,8
5,7
1/3
2.4
6.8 7/8 I.D.
1.3,5 7
2.4.5 8 7
2 a 4.5
3 5 4
2 8
SIZE
1 1/8’ I.D.
7/8 I.D.
1 1/8' I.D. 1 1/8' I.D.
7/8 1.0.
3,51 1/8' I.D.
7/8 I.D.
1 1/8' I.D.
6 7/8 I.D.
Fig. 3 — Dimensions; 054 and 064 Units
Page 6
NOTES.
1. The approximate operating weight of the unit is: 09DK-074—
09DK-074-C 09DK-084 09DK-084--C
2. Unit must have clearances for airflow as follows: Top — Do nof restrict in any way. Ends — 5 ft [1524 mm] Sides — 6 ft [1829 mm]
3. All units are shipped with a capacity split tubing kit. This kit may be used by
the field to obtain 100%, 50%/50% and 67%/33% capacity splits. To obtain a 33%/33%/33% capacity split, coils must be manifolded by fhe field. Coils are factory circuited for a 33%/33%/17%/17% capacity split.
_________
----------------
-----------------
--------------
2200 ib [998 kg]
»2617 ib [1187 kg]
»• 2421 ib [1098 kg]
»-3099 Ib [1406 kg]
09DK-074—
09DK-074-C
09DK-084—
09DK-084-C
Ov
DIMENSION Y
3’-6 1/2"
[1080 mm] 3'-6 13/16"
[1087 mm]
3'-6 5/8"
[1082 mm]
3'-7"
[1092 mm]
П6) MTG HOLES
17/32' DIA.—V
C13.5bb3
r-4 7/8'-
С42В.5в>т:
HT6. HOLES
DIMENSION X
Г-5 1/2'-
C444m}
HTG. HOLES
4'-8 11/16" [1440 mm]
4'-9 3/8"
[1458 mm]
4'-9 1/8"
[1450 mm]
4'-10 1/8"
[1476 mm]
С22531ПЛ1
Г-4 3/4'-
L425cnir>3
MTG. HOLES
-?'-4 11/16'-
OPERATING CORNER WEIGHTS
A В
618 Ib
[280 kg]
722 Ib
[328 kg]
673 Ib
[305 kg]
843 Ib
[382 kg]
HINGED ACCESS
PANEL
(CONTROL BOX)
526 Ib
[239 kg]
630 Ib
[286 kg]
581 Ib
[264 kg]
751 Ib
[341 kg]
-Г-5 1/2'
C444nti3
MTG. HOLES
C
486 Ib
[220 kg]
589 Ib
[267 kg]
541 Ib
[245 kg]
709 Ib
[322 kg]
»-1 1/2'
[Se.Snnl
MTG. HOLES
• 7/8'
[428.Siw]
MTG. HOLES
D
571 Ib
[259 kg]
675 Ib
[306 kg]
6261b
[284 kg]
796 Ib
[361 kg]
base overall
(4) RIG HOLES
2 5/8' DIA.
СбТтт]
CAPACITY SPLIT
100%
50%/50%
67%/33%
33%/33%/33%
33%/33%/17%/17%
TYPE
HOT GAS 1,3.5.7
LIQUID 2.4.6,8 7/8 I.D.
HOT GAS
LIQUID
HOT GAS
LIQUID 2.4,5 8 7/8 I.D.
HOT GAS 1 7
LIQUID
HOT GAS17
LIQUID 2
CONNECTIONS
N0.5 SIZE
5,7
1.3 2,4 6,8 7/8 I.D.
7
1.3.S
3.5
2
8 4,6 7/8 I.D.
3 5 4
8
• 7'-4 1/2'
[224?готЗ
BASE Overall
1 3/8' I.D.
1 3/8' I.D.
1 3/8' I.D.
1 3/8' I.D.
1 3/8' I.D.
5 7/8 I.D.
Fig. 4 — Dimensions; 074 and 084 Units
Page 7
Step 3 — Complete Refrigerant Piping
GENERAL — All field leak and pressure testing should be in accordance with local code requirements. If a local code does not exist, use ASHRAE (American Society of Heat ing, Refrigeration and Air Conditioning Engineers) Stan dard 15, Safety Code for Mechanical Refrigeration.
For leak testing procedures, refer to the Carrier’s
“Refrigerant Service Techniques” Book, Form SM-IA.
For any parts that need to be removed, use a mini tubing cutter. Perform phos-copper brazing on all field-made con nections while protecting adjacent joints from heat.
Install or replace filter-drier(s). BEFORE CHARGING THE SYSTEM, INSTALL OR REPLACE THE FILTER­DRIER(S) CONNECTED TO THE LIQUID LINE WITHIN THE INDOOR UNIT(S) TO PREVENT CONTAMINA TION WITHIN THE SYSTEM.
COIL REFRIGERANT PIPING INSTALLATION - Hot gas and liquid connections are located on the same end and are capped from the factory with a heat shrink-type cap, which provides a clean joint for field piping. The coil cir cuiting is designed to provide several selections of coil splits to satisfy various applications (See Table 2), with piping connections made in the field. In all cases where circuits are field connected, the piping connections should be made within the unit cabinet. The hot gas lines should enter and the liquid lines should leave the condenser at the header end of the unit.
As a standard item, a tubing package for headering, in cluding two fan cycle pressure switches (FCPSs) and hard ware is provided for the 100, 50/50, and 67/33% typical condenser coil circuiting options. The tubing also provides the ports for easy FCPS installations. The ports come with a 1/4 in. male flare fitting and check valve for each FCPS replacement. Tubing and FCPSs are field installed regard less of circuiting. Tubing packages are not offered for the
33/33/33% and 33/33/17/17% coil circuiting options; tub ing for these coil circuit options must be field fabricated and installed. See Fig. 5 and 6 for tubing package contents.
NOTE: 67/33, 33/33/33 and 33/33/17/17 represent average coil split combinations. Refer to sections below for actual values for your particular coil split combination.
IMPORTANT: With the 67/33, 33/33/33, and 33/33/
17/17% capacity split options, 3 or 4 FCPSs are used. For these applications, an accessory fan control kit is required. See accessory installation instructions for more information.
Figure 7 shows a typical piping application for a condenser with a multiple-split system. Figure 8 shows the typical field piping arrangements for the 09DK units. See Fig. 9 for coil connection details. Figures 10 and 11 show typical factory supplied coil circuiting and typical field installed 67/33% coil split circuiting respectively.
TUBING PACKAGE INSTALLATION - Before install ing, inspect the package contents. If any parts are missing or damaged, file a claim with the shipping company and notify your Carrier representative. A field supplied 3/8-in.
conduit (Greenfield conduit recommended) is required
according to UL/CSA (Underwriters’ Laboratories/ Canadian Standards Association) code for the FCPS field wiring. Field supplied 3/8-in. conduit connectors are re quired for connection to the junction box.
100% Coil Circuiting Applications: 054. 064 Units
1. Piping — Refer to Fig. 9 and 12 for field piping details
for 100% coil circuiting. Note that tubes 15 and 22 require cut on the longer leg of the tube. Two 7/8-in. OD tubes, approximately 3 in. (76.2 mm) long, must be cut from the remaining tubes (tubes 21, 23, or 25) and brazed between the tees (item 8) and coil header stubs. The remaining tubes are not used in this application and may be discarded.
2. Install Fan Cycle Pressure Switches and Clamps — Braze 2 valve core bodies (item 5) to designated hole locations on tubes 19 and 22. Insert valve cores (item 6), into valve core bodies by threading into place and tightening to 1.5 to 3 in.-lb (169.5 to 339 mN-m). Install FCPSl and FCPS2 (item 7) at designated locations on tubes 19 and 22. Cut the 3/8-in. field-supplied FCPS conduit at a desired length to fit between each FCPS location and the junction box on the unit. Figure 11 shows a typical installation of the conduit. Feed FCPS wires through each conduit and secure at the switch by utilizing each conduit connector. See Fig. 13. Secure the conduit at the junction box with 3/8-in. field­supplied conduit connectors. Wire FCPSl and FCPS2 according to Fig. 14. Clamp hot gas line, tube 27, at the location specified in Fig. 12 using the 1 5/8-in. clamp (item 4) and the 2 screws supplied. Clamp the liquid line, tube 24, using the 1 1/8-in. clamp (item 2) and the 2 screws provided.
50/50% Coil Circuiting Applications: 054 and 064 units
1. Piping — Refer to Fig. 9 and 15 for field piping details
for 50/50% coil circuiting. Note that tubes 21 and 22 require cuts on the longer leg of the tubes. Two 7/8-in. OD tubes, approximately 3 in. (72.6 mm) long, must be cut from the remaining tubes (21, 25, 26, or 29) and brazed between the tees (item 8) and coil header stubs. The re maining tubes are not used in this application and may be discarded.
2. Install Fan Cycle Pressure Switches and Clamps — Braze 2 valve core bodies (item 5) to designated hole locations on tubes 19 and 22. Insert valve cores (item 6) into valve core bodies by threading into place and tightening to 1.5 to
3 in.-lb (169.5 to 339 mN-m). Install FCPSl and FCPS2
(item 7) at designated locations on tubes 19 and 22. Cut the field-supplied 3/8-in. FCPS conduit at a desired length to fit between each FCPS location and the junction box on the unit. Figure 11 shows a typical installation of the conduit. Feed FCPS wires through each conduit and secure at the
switch using each conduit connector. See Fig. 13. Secure
the conduit at the junction box with 3/8-in. field-supplied
conduit connectors. Wire FCPSl and FCPS2 according to
Fig. 14. Clamp hot gas lines, tube 15 at the location spec
ified in Fig. 15 using the two 1 3/8-in. clamps (item 3)
and 4 screws provided. Clamp the liquid lines, tubes 21
and 23, using the two 7/8-in. clamps (item 1) and the
4 screws provided.
09DK
054 064 100% 074 100% 084 100%
100% 50/50%
Table 2 — Coil Circuiting Options
09DK CIRCUITING OPTIONS
66/34 50/50% 50/50% 50/50%
66/34
68/32
67/33
34/34/32 34/34/32 32/32/36 33/33/33
34/34/16/16 34/34/16/16 32/32/18/18 33/33/17/17
Page 8
ITEM
QUANTITY NAME 1 2 a 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 2 18 19 20 21 22 23 24 25 1 26 27 28 29 30
Tube Clamp 1 2 1 Tube Clamp 2 2 2 2 1 1 1 1 2 1 2 Discharge Tuba 2
1 1 1
1
1 Liquid Tube 1 Liquid Tube 1
1 1
8 1 1
Tube Clamp Tube Clamp 1 3/8 in.
Valve Body Valve Core
Switch Fan cycle pressure switch Tee Tee
Tee Solder Coupling 1 1/8 in.
Elbow, 90 Degree 1 1/8 in
Tee
Tee
Discharge Tube’ 1 1/8 in. CD X 32 11/32 in. Lx 5 1/16 in. W Discharge Tube Discharge Tube 1 3/8 in CD Liquid Tube 7/8 in. CD X 16 13/16 in. L X 3 7/16 in. W Discharge Tube Liquid Tube 7/8 in. CD X 17 11/16 in. L
Straight Tube
Straight Tube 7/8 in. CD X 7 3/4 in. L Straight Tube 7/8 in. OD X 18 1/4 in. L Straight Tube 1 5/8 in. OD X 34 in. L
Screw 1/4 - 14 X 5/8 in long
Straight Tube 7/8 in OD X 3 7/8 in long Discharge Tube
DESCRIPTION
7/8 in.
1 1/8 in.
1 5/8 in. 1/4 in. male flare fitting
-
7/8 in. X 7/8 in. X 7/8 in.
1 1/8 in X 1 1/8 in. X 1 1/8 in. 7/8 in. X 7/8 in. X 1 1/8 in.
1 3/8 in. X 1 1/8 in. X 1 1/8 in. 1 5/8 in X 1 3/8 in X 1 3/8 in. 1 3/8 in. CD X 44 23/32 in L x 10 1/16 in. W
1 1/8 in. CD X 24 5/32 in L x 5 1/16 in W
1 1/8 in. CD X 24 1/2 in. L
7/8 in CD X 18 13/16 in L X 3 7/16 in. W 7/8 in. CD x8 11/16 in. Lx 5 1/16 in. W 1 1/8 in. OD X 7 3/4 in. L
1 1/8 in OD X 44 19/32 in. L x 11 9/16 in. W

Fig. 5 — 09DK054,064 Tubing Package Contents

8
Page 9
16
ITEM
QUANTITY NAME
1 2
Tube Clamp
2 1 Tube Clamp 3 4 5 6 7 8 9
1 Tube Clamp 2 1 2 2 2 Siwitch 2
Tube Clamp Tube Clamp Valve Body Valve Core -
Tee
10 1 Coupling 11 1 Tee 12 1 Tee 13 2 Tee 14 1 Tee 15 16 17 2 18 19
1
2
2 1
Discharge Tube Discharge Tube Discharge Tube Discharge Tube Discharge Tube
20 1 Liquid Tube 21 1
Discharge Tube
22 1 Liquid Tube 23 24 25 26
1 Liquid Tube 1 1 Straight Tube 1 1/8 in OD X 7 3/4 in L 1 Straight Tube 7/8 in. OD X 8 1/4 in. L
Liquid Tube 7/8 in. OD X 14 13/16 in. L X 3 7/16 in W
27 1 Straight Tube 28 29 8
1 Straight Tube 2 1/8 in OD X 40 in. L
Screw
DESCRIPTION
7/8 in
1 1/8 in. 1 3/8 in 1 5/8 in
2 1/8 in
1/4 in. male flare fitting
Fan cycle pressure switch
7/8 in. X 7/8 in X 7/8 in.
1 3/8 in. X 1 3/8 in.
7/8 in. X 7/8 in. X 1 1/8 in.
1 3/8 in. X 1 3/8 in X 1 3/8 in. 1 5/8 in. X 1 3/8 in. X 1 3/8 in
2 1/8 in X 1 5/8 in X 1 5/8 in
1 3/8 in CD X 50 25/32 in. L x 14 1/8 in. W 1 5/8 in CD X 50 29/32 in. L x 12 1/16 in. W 1 3/8 in CD X 34 1/2 in L X 4 3/4 in. W 1 3/8 in CD X 19 7/8 in. L X 4 3/4 in. W 1 5/8 in CD
7/8 in. OD X 23 13/16 in L X 3 7/16 in. W 1 3/8 in OD X 28 3/8 in. L 7/8 in OD X 23 1/4 in. L (074 Units only) 7/8 in. OD X 18 1/4 in L
7/8 in. OD X 17 7/8 in. L
1/4 in.-14 X 5/8 in long

Fig. 6 — 09DK074,084 Tubing Package Contents

Page 10
66/34% Coil Circuiting Applications: 054 and 064 Units
NOTE: To operate the 054 and 064 condenser units with 66/34% coil circuiting, an accessory fan control kit is required. Refer to fan control kit installation instruc tions for more information.
1. Piping — Refer to Fig. 9 and 16 for field piping details
for 66/34% coil circuiting. Note that tube 16 will require cuts on the longer leg of the tube. Tube 16 will be used in the two specified locations. A 7/8-in. OD tube, approxi mately 3 in. (72.6 mm) long, must be cut from the remain ing tubes (23 or 26) and brazed between the tee (item 8) and coil header stub. The remaining tubes are not used in this application and may be discarded.
2. Install Fan-Cycle Pressure Switches and Clamps — Braze 3 valve core bodies (item 5) to designated hole locations on tubes 19, 21, and 22. Insert valve cores (item 6) into valve core bodies by threading into place and tightening to 1.5 to 3 in.-lb (169.5 to 339 mN-m). Note that the accessory fan control kit is required for this coil circuiting. An extra FCPS and valve assembly is provided with the kit. Install FCPSl, FCPS2, and FCPS4 (item 7) at designated locations on tubes
19, 21, and 22. Cut the field-supplied 3/8-in. FCPS conduit at a desired length to fit between each FCPS location and the junction box on the unit. See Fig. 11 for typical conduit installation. Feed FCPS wires through each conduit and se cure at the switch by utilizing each conduit connector. See Fig. 13. Secure the conduit at the junction box with 3/8-in., field-supplied conduit connectors. Wire FCPSl, FCPS2, and FCPS4 according to Fig. 14 Note that FCPS2 and FCPS4 are wired in parallel. Fan 4 is shared by the 34% and 66% refrigeration circuit. If either circuit needs the fan to be on, it will be on. At the location specified in Fig. 16, clamp hot gas lines, tubes 15 and 30, using a 1 3/8-in. clamp (item 3) and a 1 1/8-in. clamp (item 2) with the 4 screws supplied. Clamp the liquid lines, tubes 21 and 25, with 7/8-in. clamps (item 1) and 4 screws provided.
100% Coil Circuiting Applications: 074 Units
1. Piping — Refer to Fig. 9 and 17 for field piping details
for 100% coil circuiting. Note that tube 16 requires a cut on the longer leg of the tube. Two 7/8-in. OD tubes approxi mately 3 in. (72.6 mm) long, must be cut from the remain ing tubes (22 or 23) and brazed between the tees (item 9)
and coil header stubs. The remaining tubes are not used and may be discarded.
2. Install Fan Cycle Pressure Switches and Clamps — Braze 2 valve core bodies (item 6) to designated hole locations on tubes 20 and 24. Insert valve cores (item 7) into valve core bodies by threading into place and tightening to 1.5 to
3 in.-lb (169 to 339 mN-m). Install FCPSl and FCPS2
(item 8) at designated locations on tubes 20 and 24. Cut the
3/8-in. field-supplied FCPS conduit at a desired length to
fit between each FCPS location and the junction box on the
unit. See Fig. 11 for typical conduit installation. Feed FCPS
wires through each conduit and secure at the switch by uti
lizing each conduit connector. See Fig. 13. Secure the con
duit at the junction box with 3/8-in. field-supplied conduit
connectors. Wire FCPSl and FCPS2 according to Fig. 18.
Clamp hot gas line, tube 28, using 2 1/8-in. clamp (item 5)
at the location specified in Fig. 17 with the 2 screws sup
plied. Clamp the liquid line, tube 25, using 1 1/8-in. clamp
(item 2) and the 2 screws provided.
50/50% Coil Circuiting Applications: 074 Units
1. Piping — Refer to Fig. 9 and 19 for field piping details
for 50/50% coil circuiting. Note that tube 23 will require a cut, located exactly at the location of the hole in the tube. Tube 23 will be used in the two locations specified. Two 7/8-in. OD tubes, approximately 3 in. (72.6 mm) long, must be cut from the remaining tubes (22, 26, or 27) and brazed between the tees (item 9) and coil header stubs. The re
maining tubes are not used in this application and may be
discarded.
2. Install Fan Cycle Pressure Switches and Clamps — Braze 2 valve core bodies (item 6) to designated hole locations on tubes 20 and 24. Insert valve cores (item 7) into valve core bodies by threading into place and tightening to 1.5 to
3 in.-lb (169.5 to 339 mN-m). Install FCPSl and FCPS2 (item 8) at designated location on tubes 20 and 24. Cut the 3/8-in. field-supplied FCPS conduit at a desired length to fit between each FCPS location and the junction box on the unit. See Fig. 11 for typical conduit installation. Feed FCPS wires through each conduit and secure at the switch by us
ing each conduit connector. See Fig. 13. Secure the con
duit at the junction box with 3/8-in. field-supplied conduit connectors. Wire FCPSl and FCPS2 according to Fig. 18. Clamp hot gas line, tube 16, at the location specified in Fig. 19 using two 1 5/8-in. clamps (item 4) and 4 screws supplied. Clamp the liquid lines, tubes 23, using the two
7/8-in. clamps (item 1) and the 4 screws provided.
68/32% Coil Circuiting Applications: 074 Units
NOTE: To operate the 074 condenser units with 68/32% coil circuiting, an accessory fan control kit is required. See accessory installation instructions for more infor mation.
1. Piping — Refer to Fig. 9 and 20 for field piping details
for 68/32% coil circuiting. Note that tubes 17 and 20 re quire euts on the longer leg of the tubes. Tube 17 will be used in the two locations specified. Also, a 7/8-in. OD tube, approximately 3 in. (72.6 mm) long, must be cut from the remaining tubes (23 or 27) and brazed between the tee (item 9) and eoil header stub. The remaining tubes are not used in this application and may be discarded.
2. Install Fan Cycle Pressure Switches and Clamps — Braze 3 core bodies (item 6) to designated hole locations on tubes 20, 22, and 24. Insert valve cores (item 7) into valve core bodies by threading into place and tightening to 1.5 to 3 in.-lb (169.5 to 339 mN-m). Note that the accessory fan control kit is required for this coil circuiting. An extra FCPS and valve assembly is provided with the kit. Install FCPSl, FCPS2, and FCPS4 (item 8) at designated locations on tubes 20, 22, and 24. Cut the 3/8-in. field-supplied FCPS conduit at a desired length to fit between each FCPS location and the junction box on the unit. See Fig. 11 for typical conduit installation. Feed FCPS wires through each conduit and se cure at the switch by utilizing each conduit connector. See Fig. 13. Secure the conduit at the junction box with 3/8-in. field-supplied conduit connectors. Wire FCPSl, FCPS2 and FCPS4 according to Fig. 18. Note that FCPS2 and FCPS4 are wired in parallel. Fan 4 is being shared by the 32% and 68% refrigeration circuit. If either circuit needs the fan to be on, it will be on. At the location specified in Fig. 20, clamp hot gas lines, tube 15 with a 1 3/8 in. clamp (item 3) and tube 16 with a 1 5/8 in. clamp (item 4) with the 4 screws supplied. Clamp the liquid lines, tube 22 with a 7/8 in. clamp (item 1) and tube 25 with a 1 1/8 in. clamp (item 2) with the 4 screws supplied.
10
Page 11
COMPRESSORS
SEE NOTE 1
09DK084 UNIT (LOCATED ABOVE OTHER COMPONENTS)
PRESSURE RELIEF DEVICES*
FILTER-DRIERS*
SEE NOTE 4
Fig. 7 — Typical Piping for 09DK Condenser With a Dual Split System
'Field supplied. NOTES
1. Hot gas lines should rise above refrigerant level in con denser circuit.
2. Trap should be installed on hot gas lines to prevent condenser oil and refrigerant vapor migration from ac cumulating on compressor heads during off cycle.
3. Pitch all horizontal lines downward in the direction of refrigerant flow.
4. Refer to Carrier System Design Manual, part 3 for proper piping sizes and design.
MOISTURE
■ INDICATORS* (SIGHT GLASS)
SEE NOTE 4
Page 12
O-
054,064 Units
..
..........
O
FCPS2■
FCPS2■
FCPS2•
„1..
O
--------
T
1 1
fel-
0
A
' ii
1 FCPS4
34% 66%
li
50% / 50%
--------
100%
i i
r—o--*--o
til
—*-o
FCPS1
FCPS1
FCPS1
FCPS2
FCPS2
t a
34%
FCPS — Fan Cycle Pressure Switch
1-0
16%
FCPS4

Fig. 8

1. FCPS1 = Fan cycle pressure switch 1 cycles fan 3 in response to condensing pressure.
2. FCPS2 = Fan cycle pressure switch 2 cycles fan 4 in response to condensing pressure.
3. FCPS3 = Fan cycle pressure switch 3 cycles fan 3 in
O— -n
FCPS3
response to condensing pressure.
4. FCPS4 = Fan cycle pressure switch 4 cycles fan 4 in response to condensing pressure.
5. In the above applications where a fan is being shared by two different refrigeration circuits, the FCPSs (FCPS1 and 3 or FCPS2 and 4) are in parallel so that if either circuit needs the fan to be on, it will be on.
r-0
___a- - --
t- t
s_
FCPS1
ii
16%
Typical Field Piping Arrangements
34%
12
Page 13
074 Units
FCPS2■
FCPS2■
o-
;i
..........
--------------------------
O
--------
— o
I
i i
100%
■ ?—1 ^ lili
ill' 1 1 1 > 1 1 1 > 1 1 1 1 III
ill 1 1 1 1
--------------------------------------
tij
50% / 50%
1
o
■o
FCPS1
FCPS1
FCPS
FCPS2•
o
FCPS2-
r---0
Î
32%
Fan Cycle Pressure Switch
I I
r
fel.
0
V
1 FCPS4
32%
----------
1 1
1 1 1
1 FCPS4 1 , 1 /
U !t ii It
32% 36%.
FCPS2 FCPS4
1—0
Í4
itii
68%.
FCPS3 1
|-0
__a.__
\ 1
FCPS3
1
----­1 1 1 1
\r\
32%
o
O- -
a_
FCPS1
FCPS1
NOTES: 1 FCPS1 = Fan cycle pressure switch 1 cycles fan 3 in
response to condensing pressure.
2. FCPS2 = Fan cycle pressure switch 2 cycles fan 4 in response to condensing pressure
3. FCPS3 = Fan cycle pressure switch 3 cycles fan 3 in response to condensing pressure.
4. FCPS4 = Fan cycle pressure switch 4 cycles fan 4 in response to condensing pressure
5 In the above applications where a fan is being shared by two
different refrigeration circuits, the FCPSs (FCPS1 and 3 or
FCPS2 and 4) are in parallel so that if either circuit needs the
fan to be on, it will be on
FCPS1
t a ¡i
18%.
18%
Fig. 8 — Typical Field Piping Arrangements (cent)
32%
13
Page 14
084 Units
........O
FCPS2-
FCPS2■
FCPS2 ■
ZI
..........
...................■ T"'"! r—^
O
î
33%
t i U
100%
1 '
1 »
ill*
1 1 1 1
1 1 1 1 1 1 ! I : ! ! !
H
li
50% / 50%
—-O- - L _
ÎÜ
■O
[4
FCPS4
lî il
67%
FCPS1
FCPS1
FCPS1
FCPS2
r---0
FCPS2
Î !i
33%
FCPS — Fan Cycle Pressure Switch
1 FCPS1 = Fan cycle pressure switch 1 cycles fan 3 in
response to condensing pressure.
2 FCPS2 = Fan cycle pressure switch 2 cycles fan 4 in
response to condensing pressure
3. FCPS3 = Fan cycle pressure switch 3 cycles fan 3 in response to condensing pressure.
4. FCPS4 = Fan cycle pressure switch 4 cycies fan 4 in response to condensing pressure
5. In the above applications where a fan is being shared by two different refrigeration circuits, the FCPSs (FCPS1 and 3 or FCPS2 and 4) are in parallel so that if either circuit needs the
fan to be on, it will be on.
FCPS4
O- -1
FCPS3
|-0
î a
17%
__a__
Î !
17%
a_
¡1
FCPS1
33%
Fig. 8 — Typical Field Piping Arrangements (cent)
14
Page 15
LEFTSIDE COILS
RIGHT SIDE COILS
054,064
PERCENT CAPACITY
SPLIT NUMBER
100
50/50
66/34
34/34/32
34/34/16/16
•Connection sizes reflect size of each coil header nozzle.
fA tubing package is factory supplied to facilitate field piping installation for the 100, 50/50 and 66/34 capacity split applications See installation instructions for more
information
LINE TYPE
Hot Gas 1,3,5,7
Liquid 2,4,6,8
Hot Gas
Liquid 2,4/6,8
Hot Gas 1,3,5/7
Liquid 2,4,6/8
Hot Gas
Liquid
Hot Gas
Liquid
COIL CONNECTION
1,3/5,7
1/7/3,5 2/8/4,6
1/7/3/5 2/8/4/6
COIL CONNECTION
in.-ODM*
1 1/8
7/8
1 1/8 1 3/8
7/8 7/8
1 1/8
7/8 7/8
1 1/8
7/8
1 1/8
7/8
TUBING CONNECTION
in. ODMf
1 5/8 1 1/8
1 3/8
(3) 1 1/8
(3) 7/8
074
PERCENT CAPACITY
SPLIT
100
50/50
68/32
32/32/36
32/32/18/18
•Connection sizes reflect size of each coil header nozzle tA tubing package is factory supplied to facilitate field piping installation for the 100, 50/50 and 68/32 capacity split applications. See installation instructions for more
information.
LINE TYPE
Hot Gas
Liquid
Hot Gas 1,3/5,7
Liquid
Hot Gas 1,3,5/7
Liquid
Hof Gas
Liquid
Hot Gas
Liquid
COIL CONNECTION
NUMBER
1,3,5,7 2,4,6,8
2,4/6,8 7/8
2,4,6/8 1/7/3,5
2/8/4,6 1/7/3/5
2/8/4/6
COIL CONNECTION
in.-ODM* in.-ODMf
1 3/8
7/8 1 1/8
1 3/8 1 5/8
1 3/8 1 5/8 1 3/8
7/8 7/8
1 3/8
7/8
1 3/8
7/8
TUBING CONNECTION
7/8 7/8
2 1/8
(3) 1 3/8
(3) 7/8
084
PERCENT CAPACITY
SPLIT
100
50/50
67/33
33/33/33
33/33/17/17
•Connection sizes reflect size of each coil header nozzle tA tubing package is factory supplied to facilitate field piping installation for the 100, 50/50 and 67/33 capacity split applications See installation instructions for more
information.
LINE TYPE
Hot Gas
Liquid 2,4,6,8 7/8 1 1/8
Hot Gas 1,3/5,7 1 3/8
Liquid 2,4/6,8
Hot Gas 1,3,5/7 1 3/8
Liquid 2,4,6/8
Hot Gas 1/7/3,5
Liquid 2/8/4,6
Hot Gas
Liquid
COIL CONNECTION
NUMBER in.-ODM*
1,3,5,7 1 3/8
1/7/3/5
2/8/4/6
COIL CONNECTION TUBING CONNECTION
7/8 7/8
7/8
1 3/8
7/8
1 3/8
7/8
in.-ODMt
2 1/8 1 5/8
1 5/8 1 1/8 7/8
(3) 1 3/8
(3) 7/8
Fig. 9 — Coil Connection Data
15
1 3/8
7/8
1 1/8
7/8
1 5/8
7/8
1 5/8
7/8
1 3/8
Page 16
100% Coil Circuiting Applications: 084 Units
1. Piping — Refer to Fig. 9 and 21 for field piping details
for 100% coil circuiting. Note that tubes 16 and 20 require a cut on the longer leg of the tubes. Two 7/8-in. OD tubes, approximately 3 in. (72.6 mm) long, must be cut from the remaining tubes (22 or 23) and brazed between the tees (item 9) and coil header stubs. The remaining tubes are not used in this application and may be discarded.
2. Install Fan Cycle Pressure Switches and Clamps — Braze 2 valve core bodies to designated hole locations on tubes 20 and 24. Insert valve cores into valve core bodies by thread ing into place and tightening to 1 5 to 3 in.-lb (169.5 to 339 mN-m) Install FCPSl and FCPS2 at designated loca tions on tubes 20 and 24. Cut the 3/8-in. field-supplied FCPS conduit at a desired length to fit between each FCPS loca tion and the junction box on the unit. See Fig. 11 for typ ical conduit installation. Feed FCPS wires through each conduit and secure at the switch by utilizing each conduit connec tor. See Fig. 13. Secure the conduit at the junction box with 3/8-in. field-supplied conduit connectors. Wire FCPSl and FCPS2 according to Fig. 18. At the location specified in Fig. 21, clamp hot gas line, tube 28, using 2 1/8-in. clamp and 2 screws provided. Clamp the liquid line, tube 25, using 1 1/8-in. clamp and 2 screws provided.
50/50% Coil Circuiting Applications: 084 Units
1. Piping — Refer to Fig. 9 and 22 for field piping details
for 50/50% coil circuiting. Note that tube 20 requires a cut on the longer leg of the tube. Tube 23 will require a cut located exactly at the location of the hole in the tube, and will be used at the two locations specified. Two 7/8-in. OD tubes, approximately 3 in. (72.6 mm) long, must be cut from the remaining tubes (22, 26, and 27) and be brazed between the tees (item 9) and coil header stubs. The re maining tubes are not used in this application and may be discarded.
2. Install Fan Cycle Pressure Switches and Clamps — Braze 2 valve core bodies (item 6) to designated hole locations on tubes 20 and 24. Insert valve cores (item 7) into valve core bodies by threading into place and tightening to 1.5 to 3 in.-lb (169.5 to 339 mN-m). Install FCPSl and FCPS2 (item 8) at designated locations on tubes 20 and 24. Cut the 3/8-in. field-supplied FCPS conduit at a desired length to fit between each FCPS location and the junction box on the unit. See Fig. 11 for typical conduit installation. Feed FCPS wires through each conduit and secure at the switch by us ing each conduit connector. See Fig. 13. Secure the con duit at the junction box with 3/8-in. field-supplied conduit connectors. Wire FCPSl and FCPS2 according to Fig. 18. At the location specified in Fig. 22, clamp hot gas line, tube 16, using two 1 5/8-in. clamps and 4 screws provided. Clamp the liquid lines, tubes 23, using two 7/8-in. clamps (item 1) and 4 screws provided.
Fig. 10 — Typical Factory-Supplied Coil Circuiting,
09DK054-084 Units (084 Shown)
CONDUITS
Fig. 11 — Typicai Coil Circuiting for 09DK054-084
Units (67/33% Split Option; 084 Unit Shown)
16
Page 17
6113?)% Coil Circuiting Applications: 084 Units
NOTE: To operate 084 condenser units with 67/33% coil circuiting, an accessory fan control kit is required. See accessory installation instructions for more information.
1. Piping — Refer to Fig. 9 and 23 for field piping details
for 67/33% coil circuiting. Note that tubes 17 and 20 require a cut on the longer leg of the tubes. Tube 17 will be used in the two locations specified. Also, a 7/8-in. OD tube, approximately 3 in. (72.6 mm) long must be cut from the remaining tubes (22 or 27) and brazed between the tee
(item 9) and coil header stub. The remaining tubes are not used in this application and may be discarded.
2 Install Fan Cycle Pressure Switches and Clamps — Braze 3 valve core bodies (item 6) to designated hole locations on tubes 20, 23, and 24. Insert valve cores (item 7) into valve core bodies by threading into place and tightening to 1.5 to
3 in.-lb (169.5 to 339 mN-m). Note that the accessory fan control kit is required for this coil circuiting. An extra FCPS and valve assembly is provided with the kit. Install FCPSl, FCPS2, and FCPS4 (item 8) at designated loca tions on tubes 20, 23, and 24. Cut the 3/8-in. field-supplied FCPS conduit at a desired length to fit between each FCPS location and the junction box on the unit. See Fig. 11 for
typical conduit installation. Feed FCPS wires through each conduit and secure at the switch by utilizing each conduit connector. See Fig. 13. Secure the conduit at the junction box with 3/8-in. field-supplied conduit connector. Wire FCPSl, FCPS2, and FCPS4 according to Fig. 18. Note that FCPS2 and FCPS4 are wired in parallel. Fan 4 is shared by the 33% and 67% refrigeration circuit. If either circuit needs the fan to be on, it will be on. At the location specified in Fig. 23, clamp hot gas lines, tube 15 with a 1 3/8-in. clamp (item 3) and tube 16 with a 1 5/8-in. clamp (item 4) with the 4 screws supplied Clamp the liquid lines, tube 23 with a 7/8-in. clamp (item 1) and tube 25 with a 1 1/8-in. clamp (item 2) with 4 screws supplied.
THREE AND FOUR COIL SPLIT, COIL CIRCUITING APPLICATIONS; 054-084 UNITS
NOTE: To operate 054-084 condenser units with the 3 and 4 coil split coil circuiting, the fan control kit is re quired. See accessory installation instructions for more information.
1. Piping — Piping is not provided in the tubing package
for these coil circuiting options. Tubing is field fabricated and installed, according to the coil circuiting shown in Fig. 8. For pipe sizing information, refer to Refrigerant Line Sizing, page 18. To secure the piping, it should be routed to the brackets supplied on the unit.
100%
FCPS — Fan Cycle Pressure Switch

Fig. 12 — 100% Coil Circuiting; 054 and 064 Units

NOTES:
1. Dimensions in ( ) are in millimeters
2. See Fig 5 for tubing package contents.
17
Page 18
2. Install Fan Cycle Pressure Switches and Clamps — Four FCPSs should be used. Locate holes, valve core assem blies, and FCPS’s 1, 2, 3, and 4 at the specified locations. See Fig. 8. Insert valve cores into valve core bodies by threading into place and tightening to 1.5 to 3 in.-lb (169.5 to 339 mN-m). The additional two FCPSs and valve core assemblies are provided with the accessory fan control kit. Cut the 3/8-in. field-supplied FCPS conduit at a desired length to fit between each FCPS location and the junction box on the unit. See Fig. 11 for typical conduit installation. Feed FCPS wires through each conduit and secure at the switch by utilizing each conduit connector. See Fig. 13. Secure the conduit at the junction box with 3/8-in. field-supplied conduit connectors. Wire the FCPSs according to Fig. 14 and 18. Note that FCPS2 and 4 and FCPSl and 3 are wired in parallel. Fans 3 and 4 are being shared by two different refrigeration circuits. If either refrigeration circuit needs the fan to be on, it will be on. Clamp all lines to brackets sup plied on the unit.
REFRIGERANT LINE SIZING - Sizing depends on length of lines between various sections of the refrigerant system. See Fig. 9 for coil connection details. Consider the amount of liquid lift and drop in the system as well as proper com pressor oil return. See Liquid Lift section for more infor mation. Consult Carrier System Design Manual, Part 3, or Carrier E20-II Refrigerant Piping Computer Program for proper piping sizes and design
LIQUID SHUTOFF VALVE AND SIGHT GLASS - A
shutoff valve is not supplied with 09DK condensers. It is
strongly recommended that a full line size liquid shutoff valve be field supplied near condenser to allow for servic ing parts of the refrigerant circuit A field-supplied mois ture indicating sight glass is recommended for use in charg
ing and servicing the system. Refer to Fig. 7. PRESSURE RELIEF - The ASHRAE Standard 15, Safety
Code for Mechanical Refrigeration states; “Every refriger
ating system shall be protected by a pressure relief device
or some other means designed to safely relieve pressure due
to fire or other abnormal conditions ” Since 09DK con
densers do not have pressure relief devices, one must be
field supplied and installed just before the liquid line ser
vice valve. (See Fig. 7.) When the split coil is used with
multiple systems, each system must have its own pressure
relief.
Procedure for Using the Refrigerant Receiver — See Fig. 24.
1. During normal operation — Valve A is open and valves B and C are closed. Receiver is isolated from the system.
2. For servicing — Valves A and C are closed and valve B is open. Run unit until all the refrigerant is in the re ceiver and then close valve B. Unit is now ready for ser vicing.
3. To resume operation — Leave valve A closed and open valves B and C. Run unit until the stored refrigerant is drawn into the system. To completely remove the re frigerant from the receiver, throttle valve B while noting condition of refrigerant in the liquid line sight glass; also, watch the suction pressure. A sudden surge of bubbles in the sight glass and a rapid decrease in suction pres sure indicates that all the refrigerant has been withdrawn from the receiver. Immediately close valves B and C and then open valve A. The unit should now be ready for normal operation, with the receiver isolated from the
system. The system should be charged to a clear sight
glass when under normal operation.
LIQUID LIFT — Amount of liquid lift available before re frigerant flashing occurs depends on amount of liquid sub cooling in the system.
All 09DK condensers have positive subcooling when ap plied with optimum charge. With subcooling, it is possible to overcome an appreciable friction drop and/or static head
(due to elevation of the liquid metering device above the
condenser).
When 09DK condensers are applied with minimum charge,
no positive subcooling in condenser is realized; therefore, if subcooling is required it must be obtained by external means such as a liquid suction interchanger.
The average amount of liquid lift available is shown in Table 3 for refrigerants R-22, R-502, and R-134A. Avail
able subcooling is greatly reduced when R-12 and R-500 are used in these units. It is recommended that the evapo rator be at the same level as the condenser, or lower.
1/4 SAE FLARE WITH
56 (14 2) HEX
REFRIGERANT RECEIVER — A refrigerant receiver is
not furnished with 09DK condensers and is not recom
mended for normal applications as its use will be detrimen tal to the desired effects of subcooling. However, if a par ticular application requires a receiver to increase refrigerant holding capacity of the condenser, a receiver can be used. When a receiver is to be used year-round, it should be in stalled indoors. Carrier recommends the following installa tion in such a case (see Fig 24): locate valves on each side of the receiver so receiver may be isolated from system for normal operation.
SAE — Society of Automotive Engineers

Fig. 13 — Fan Cycle Pressure Switch

18
CONDUIT CONNECTOR
Page 19
09DK05^.054 POWER SCHEMATIC
09Dk:054.064 standard control schematic
nOO% 8 50X/50X CAPACITY SPLITS)
ir FW CONTROI. (IT IS USED. SEE FW CONTRa CIt (tCCESSOAri SOOUTIC
09DIC054.064 FAN CONTROL KIT CACCESSOftYJ SCHEMATIC
C67X/33X.33X/33X/33X g 33X/33X/17X/17% CAPACITY SPLITS)
l2Xi CDNIML VCL1ACE Oi«.r>
o
2
09PK054.064 COMPONENT ARRANGEMENT
& cSl
& cui
(D>®® oO o
M2 №1
®®<32) o
0 0
0U2 Ml
o>
o
NOTES.
1
Units are factory wired for a 50%/50% capacity split. If 100% capacity is required, con
nect the factory-supplied jumpers from TB2-1 to TB3-1 and from TB2-2 to TB3-2.
2. When a fan control kit is used, the jumper from TB2-1 to TB3-1 and from TB2-2 to TB3-2 must be connected. The fan control kit is factory wired for 67%/33% capacity split. If a 33%/33%/33% capacity split is required, remove the jumper from TB4-1 to TB5-1 and from TB4-2 to TB5-2. If a 33%/33%h 7%/17% capacity split is required, remove the jump ers from TB4-1 to TB5-1 to TB7-1 and from TB4-2 to TB5-2 to TB7-2.
3. On fan control kits, 208/230 v units are factory wired for 230 v power supply. For 208 v power supply, connect yellow wire to terminal marked H2.
4. Terminal blocks TB2, TB3, TB4, TBS, TB6 and TB7 are for external field control connec tions. Control connections are to be class 1 wiring, 14 AWG copper conductors only.
5. Wiring for field power supply must be rated 75° C minimum. Use copper, copper-clad aluminum, or aluminum conductors. Maximum incoming wire size for each terminal block
IS 2/0.
6. Replacement of factory wires must be with 105° C wire or its equivalent.
7. Factory wiring is in accordance with National Electrical Code (NEC). Field modifications or additions must be in compliance with all applicable codes.
8. Fan motors are thermally protected. Three-phase motors are protected against primary single phasing conditions.
9. Line numbers on the left side of the label diagrams indicate the contact number. The numbers on the right side of label diagrams match the contacts with their corresponding coils. A plain number indicates normally open contacts. An underlined number indicates normally closed contacts.

Fig. 14 — Wiring Diagram and Component Arrangement; 054 and 064 Units

dXJKD
<D®<D
O
o
o0
□= C
CONTRCC RELIT outrr TERnlNii.
’ EOUIRHENT
FAN COKTACIOA FAN CTCLINC FRESSURE S FACJ9ST INSIALLEB »Hi
NOIOfi NASTER SENSOR PRINAftr
SCCCMOAAT TERNiNAL eiOCi: TRV6FCFUCR
r~l TERNINAL 8L0CC CC»»«C1ICN O "*»F£D TERNINAl
O LMURCED TERnlNAL
Page 20
50 / 50%
FCPS — Fan Cycle Pressure Switch
Fig. 15 — 50/50% Coil Circuiting; 054 and 064 Units
NOTES:
1. Dimensions in ( ) are in millimeters 2 See Fig. 5 for tubing package contents.
FCPS — Fan Cycle Pressure Switch

Fig. 16 — 66/34% Coil Circuiting; 054 and 064 Units

NOTES:
1. Dimensions in ( ) are in millimeters
2. See Fig 5 for tubing package contents
20
Page 21
Table 3 — Available Liquid Lift Ft (m)
REFRIGERANT R-22
UNIT
054
09DK
NOTES: 1 The liquid lift data allows for a 7 psi (48 kpa) drop for liquid line
accessories, and a 2° F (1.rC), iiquid line ioss with maximum change.
2. Temperature difference = Saturated condensing temperature (en tering) — Entering-air temperature (dry buib) in degree F (° C)
3. The liquid iift data is based on 15° F (8 3° C) subcooiing, 95 F
(35 C) entering-air temperature, and a 50/50% capacity split ap­piication Subcooling based on condenser subcooling = Satu rated condensing temperature entering - Actual temperature leaving the coii
064 074 084
Temperature Difference F (C)
20
30
(16.7)
(11.1)
50
60
(15 2)60(18.3)
(18.3)
41
(12 5)31(9.5)
44
(13.4)34(10.4)
51
(15.6)41(12.5)51(15.6)
R-502 R-134A
20
30
(16.7)20(11.1)
(11.1)
44
(13.4)
41
(12.5)
44
(13.4)28(8.5)18(5.5)7(2.1)
(10.7)22(6.7)
25
(7 6)
35
(8.8)26(7.9) (6.1)6(1.8)
29 20
30
(16.7)
10
(3 1)
Example: Supply voltage is 240-3-60.
AB = 243 V BC = 236 V AC = 238 V
Average Voltage
243 -F 236 -f 238
^ 717
3
= 239 V
Determine maximum deviation from average voltage:
(AB) 243 - 239 = 4 V (BC) 239 - 236 = 3 V (AC) 239 - 238 = 1 V
Maximum deviation is then 4 v. To determine the percent voltage imbalance:
% Voltage Imbalance = 100 x----------
4
239
= 1.7%
This amount of phase imbalance is satisfactory since it is
below the maximum allowable of 2%.
Step 4 — Complete Electrical Connections
GENERAL — Verify nameplate electrical requirements match available power supply. Voltage at condenser must be within the minimum and maximum shown in Table 4 and phases must be balanced within 2%. Contact local power company for line voltage corrections. Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent voltage imbalance:
max voltage deviation
% Voltage _ from average voltage
Imbalance ^ average voltage
IMPORTANT: If supply voltage phase imbalance is more than 2%, contact your local electric utility com pany immediately.
Condenser operation on improper line voltage or exces sive phase imbalance may be considered abuse and any re sulting damage may not be covered by Carrier warranty.
All wiring must be in accordance with local or NEC (National Electrical Code) regulations.
FIELD CONNECTIONS - Refer to Table 4 and Fig. 14,
18, and 25 for field wiring details.
100%
Fig. 17 - 100% Coil Circuiting; 074 Units
21
Page 22
09DK074.0B4 POWER SCHEMATIC
090K074.084 FAN CONTROL KIT CACCESSORY^ SCHEMATIC
C67X/33-4.33X/33X/33X g 33X/33X/1 7X/1 7% CAPACITY SPLITS)
09DK074.0B4 COMPONENT ARRANGEMENT
Ni to
FIELD COKlAa.
COMCTIWS CN.T
09DK074.084 STANDARD CONTROL SCHEMATIC
(^00% 8 50X/50X CAPACITY SPLIT53
[|F PM nwrttx Ell IS USED. SEE PM CMTUX Ell (UCESSOftr) SCICIUtK)
FUSTE»
- BBN TO FNI cowccT Piuo Fca aeovtsoHz)
- «CES50BT
«-.JL
(H5V CWiaOL YOtTIGE 0*T
—©
----------------------------------------------------
230V CONTROL ONLY
-----------»-------
-HI —O FC3
NOTES:
1. Units are factory wired for a 50%/50% capacity split. If 100% capacity is required, con nect the factory-supplied jumpers from TB2-1 to TB3-1 and from TB2-2 to TB3-2.
2. When a fan control kit is used, the jumper from TB2-1 to TB3-1 and from TB2-2 to TB3-2 must be connected. The fan control kit is factory wired for 67%/33% capacity split, if a 33%/33%/33% capacity split is required, remove the jumper from TB4-1 to TB5-1 and from TB4-2 to TB5-2. If a 33%/33%/17%/17% capacity split Is required, remove the jump ers from TB4-1 to TB5-1 to TB7-1 and from TB4-2 to TB5-2 to TB7-2.
3. On fan control kits, 208/230 v units are factory wired for 230 v power supply. For 208 v power supply, connect yellow wire to terminal marked H2.
^S0D
---
4. Terminal blocks TB2, TB3, TB4, TBS, TB6 and TB7 are for external field control connec tions. Control connections are to be class 1 winng, 14 AWG copper conductors only.
5. Wiring for field power supply must be rated 75° C minimum. Use copper, copper-clad aluminum, or alurTwnum conductors. Maximum incoming wire size for each terminal block
IS 2/0.
6. Replacement of factory wires must be with 105° C wire or its equivalent.
7. Factory wiring is in accordance with National Electncal Code (NEC). Field modifications or additions must be in compliance with all applicable codes.
8. Fan motors are thermally protected. Three phase motors are protected against primary single phasing conditions.
9. Line numbers on the left side of the label diagrams indicate the contact number. The numbers on the nght side of label diagrams match the contacts with their corresponding coils. A plain number indicates normally open contacts. An underlined number indicates normally closed contacts.

Fig. 18 — Wiring Diagram and Component Arrangement; 074 and 084 Units

FN, 3S §
1
HNinOL BOX
(D<D(Z>
0X2)0
(KCESSoen
Jn C
©o®
o o
FIELD CCmaOL PI
0 o o o
o o
CONTROL EIT 0W.T)
|o
>m TE>MBlTL(lf SKITCK COKTOOL RELIT DLPTIT TERXINIL
' EauiPHENT
FIN CCMTICTOR FICTWT II6IILLED S>1l<
lEmiNiL euXE
®®®
®®®
o
o
r~l TEftBlNAl ÍL0CE CC*»«CTIi»l
C
O
Page 23
50 / 50%
FCPS — Fan Cycle Pressure Switch
Fig. 19 — 50/50% Coil Circuiting; 074 Units
32 / 68%
Page 24
100%
50 / 50%
FCPS — Fan Cycle Pressure Switch
Fig. 22 — 50/50% Coil Circuiting; 084 Units
24
Page 25
33 / 67%
1 Dimensions in ( ) are in millimeters. 2 See Fig. 6 for tubing package contents.
A — Bypass valve B — Receiver inlet valve C — Receiver outlet valve
Fig. 24 — Piping for Optional Receiver
Fig. 23 — 67/33% Coil Circuiting; 084 Units
25
Page 26
09DK
054
-500 208/230-3-60
-600 460-3-60
-100 575-3-60
-200
-900
064
-500
-600
-100 575-3-60 518
-200 380-3-60
-900 380/415-3-50
074
-500 208/230-3-60 187
-600
-100
-200
-900
NAMEPLATE
V-PH-HZ
380-3-60 342
380/415-3-50 208/230-3-60
460-3-60
460-3-60 414 575-3-60 518 380-3-60
380/415-3-50 342
084
-500 208/230-3-60
-600 460-3-60
-100 575-3-60 518
-200
-900
380-3-60
380/415-3-50

Control Circuit Information

09DK
CONTROL POWER
ALL
UNITS
-500
-600
-100 115-1-60
-200
-900
V-PH-HZ
115-1-60 103 115-1-60 103 127
230-1-60 230-1-50 207 253
Table 4 — 09DK Electrical Data
SUPPLY VOLTAGE*
Min
187 414 518
342
187 414
342 342 440
342
187
414
342
342
SUPPLY
VOLTAGE*
103 127 207
OVERCURRENT
PROTECTION
127
253
Max
254 508 632 14.5 418 440
254 508 632 418
254 34 0 508 632 21.3 418 440
254 34.0 508 632 418 440
MCA MOCP NO. FANS
23.2 25 4
11.7 166
128
23.2 25 11 7 15 4
14.5 15 166 20 128 15
17.1 20 6 93 (1,2) 2.8 (3-6) 2.7
24.4 25 6 93 (1-6)3 9
18.8 20 6 9.3 (1-6)3 0
17.1 20
21 3 24 4
188 20
AMPS
10 10 10 10 10
FAN MOTORS
Total Kw
6.2 (1,2) 5.5 (3,4) 5.4 15 4 15 4 20 4 15 4
4 6.2 (1,2) 5 5 (3,4) 5 4 4 62
4 6.2 (1-4) 3.9 4 6.2 (1-4) 3.0
35 6 93 (1,2) 5.5 (3-6) 5.4 25 6 93
35 6 9.3 (1,2) 5.5 (3-6) 5 4 25 6 9.3 (1-6) 3.4
25
LEGEND
FLA
— Full Load Amps
MCA
— Minimum Circuit Amps; Used for wire sizing
6 93 (1,2)2 8(3-6) 2.7 6
6 93 (1-6) 3.0
(Complies with NEC Sectien 430-24)
6.2
6.2
62 62
62
9.3 (1-6) 3.9
(Fan no.)
FLA for ea. fan
(1,2) 2.8 (3,4) 2.7
(1-4) 3.4 (1-4) 3.9 (1-4) 3.0
(1,2) 2.8 (3,4)2 7
(1-4) 3.4
(1-6)3 4
MOCP — Maximum Overcurrent Protection NEC — National Electrical Code
'Units are suitable for use on electrical systems where voltage sup plied to the unit terminals is within listed minimum and maximum limits.
NOTES:
1. Maximum allowable phase imbalance: Voltage ± 2%; Amps ± 10%
2. Maximum incoming wire size for power circuit is 2/0 max
3. Control Circuit: Uses no. 8 screws for wire connections at the ter minal block.
4. 100 va is required for the 09DK054-084 control circuit
26
Page 27
NOTES:
1. Factory wiring is in accordance with National Electrical Code (NEC), field modifications or additions must be in compliance with all ap
plicable codes.
2. Wiring for field power supply must be rated 75 C minimum. Use copper, copper-clad aluminum, or aluminum conductors. Maxi mum incoming wire size for each terminal block is 2/0.
3. Terminal blocks TB2, TBS, TB4, TBS, TB6, and TB7 are for external field control connections. Control connections are to be class 1 wiring.
4. Replacement of factory wires must be with type 105 C wire or its equivalent.
5. Units are factory wired for a 50%/50% capacity split. If 100% ca pacity is required, connect the factory-supplied jumpers from TB2-1
to TB3-1 and from TB2-2 to TB3-2.
6. If a fan control kit is to be used, the jumper from TB2-1 to TB3-1 and the jumper from TB2-2 to TB3-2 must be connected. The
fan control kit is factory wired for a 67%/33% capacity split. If a 33%/33%/33% capacity split is required, remove the jumper from TB4-1 to TB5-1 and from TB4-2 to TB5-2. If a 33%/33%/17%/17% capacity split is required, remove the jumpers from TB4-1 to TB5-1 to TB7-1 and from TB4-2 to TB5-2 to TB7-2.
K)
CONTROL BOX
STANDARD UNITS
Fig. 25 — Field Wiring; 054-084 Units
UNITS WITH FAN CONTROL LIT tACCESSORV)
CONTROL BOX
Page 28
MAIN POWER WIRING — These units must have ade quate overcurrent protection, fuses, or HACR (Heating, Air Conditioning and Refrigeration) breakers, according to the national and applicable local codes.
For field power connections, all main power wiring en ters the unit through a factory-punched access hole under the control box. Two access holes are provided, the larger should be used for 208/230 v applications. See Fig. 26. Wiring must be rated at 75 C minimum. Use copper, copper­clad aluminum, or aluminum conductors. Field power sup ply connections are made at terminal block 1 (TBl). Max imum incoming wire size for each terminal connection on TBl is 2/0, and all power wiring must comply with appli cable local and national codes. Refer to the unit power cir cuit information to determine incoming wire sizes. (See Table 4.) Refer to Table 5 for American and European wire conversion information.
CONTROL CIRCUIT POWER WIRING - Provide a sep arate single phase power source for each control circuit (de pending on the coil refrigerant circuit split), with the re quired overcurrent protection (fuses or circuit breakers). See Table 4 for control circuit overcurrent protection amps.
For field control circuit connections, units are factory wired for a 50/50% capacity split and would utilize terminal blocks 2 and 3 (TB2 and TB3). TB2 will control fans 1, 3, and 5; TB3 will control fans 2, 4, and 6. Fans 5 and 6 are on 074 and 084 units only. If 100% condenser application is re quired, connect the factory supplied jumpers from TB2-1 to TB3-1 and from TB2-2 to TB3-2, and bring incoming con nections to either TB2 or TB3. Factory-punched access holes under the control box are provided for the incoming wires. See Fig. 26 for access hole details. Terminal block connec tions utilize no. 8 screws. Wiring must be class 1, 14 AWG (American Wire Gage) copper conductors only. Power re quired for control circuits is 100 va. See Table 4 for control circuit voltage data.
GENERAL WIRING NOTES
1. Power entry is at one end only.
2. Fan motors are thermally protected. Three-phase motors
are protected against primary single-phasing conditions.
3. Replacement of factory wires must be with appliance
wiring material, rated 105 C, or its equivalent.
4 Factory wiring is in accordance with NEC. Field mod
ifications or additions must be in compliance with all applicable codes.
DESCRIPTION OF CONTROLS - The condenser units utilize a dual voltage control scheme: a 3-phase power cir cuit for the fan system operation and a single-phase control circuit voltage for fan cycling control. The number of con trol circuit voltages will depend on the coil split application used. See head pressure control description in the service section for a detailed description of the controls function.
Table 5 — American/European Wire Conversions
AMERICAN EUROPEAN
Industry
Standard Size 18 AWG 0.82
16 AWG 1 30 1.5 14 AWG 2.08 2.5 12 AWG 3 30 40
10 AWG 5 25
8 AWG 6.36 100 6 AWG 13.29 16.0 4 AWG 21.14 25.0 3 AWG 26.65 2 AWG 33.61 35 0 1 AWG 42.39 50.0
1/0 AWG 53.49 2/0 AWG 67.42 70.0 3/0 AWG 85.00 95.0 4/0 AWG 107.19 120.0
250 kcmil 126 64
300 kcmil 151 97
350 kcmil 177 90
400 kcmil 202 63
500 kcmil 253 29
600 kcmil 303 95
LEGEND
AWG — American Wire Gage kcmil — Thousand Circular Mils
American
Conversion
(mm^)
Industry
Standard
Size (mm^)
1.0
60
150.0
185 0 240 0 300 0
Step 5 Add Accessories As Needed — The
following accessories are available for the 09DK054-084 condensers: fan sound reduction kit, condenser coastal coil filter, security grille package, condenser coil hail guard pack age, accessory control transformer, Motormaster® III de vice, Motormaster III Relay/Sensor Kit, and accessory fan­control kit. Winter Start and any special electrical interlock must be considered separately. Refer to installation instruc tions furnished with each accessory for more information.
2 13/32"
Fig. 26 — Power Wiring Access Holes; 054-084 Units
28
Page 29
START-UP
System Evacuation and Dehydration — Refer
to GTAC II, Module 4, “Dehydration for Proper Evacua tion and Dehydration techniques.”
Charging Procedure — Charge to a clear sight glass.
Refer to GTAC II, Module 5 “Charging, Recovery, Recy cling, and Reclamation” for proper charging techniques. Add 10 lbs (4.5 kg) of R-22 over clear sight glass to flood subcooler sections of the condenser coils. This 10 lbs (4.5 kg) is added to the total unit charge, and must be pro portioned by the percentage of circuits when multiple cir cuits are employed. For example, in Table 2, add .67 x
10 lbs (4.5 kg) (approximately 6.7 lbs [3.0 kg]) for the 67% circuit. Refer to Table 6 for condenser coil refrigerant circuit data.
Check Operation of Condenser Fan Motor Con trols and Rotation of Fans — Rotation should be
clockwise as viewed from top of unit.

A CAUTION

Before starting unit, be sure wire fan guards are secured in place over each fan; personal injury may result.
SERVICE
Cleaning Condenser Coils — Clean coils with a vac
uum cleaner, fresh water, compressed air, or a bristle brush (not wire). Units installed in corrosive environments should have coil cleaning as a part of a planned maintenance sched ule. In this type of application, all accumulations of dirt should be cleaned off the coil.

A CAUTION

Do not use high-pressure water or air. Damage to fins may result.
Condenser Fans — Each fan is supported by a formed
wire mount bolted to the fan deck and covered with a wire guard. The exposed end of the fan motor shaft is protected by grease. If the fan motor must be removed for service or re placement, be sure to grease fan shaft, and reinstall fan guard. For proper performance, fan should be 7/8 in. (22 mm) be low the top of the venturi on the fan deck for 60 Hz units, and 1/2 in. (13 mm) to top of the fan hub for 50 Hz units. Tighten set screws to 15 ± 1 ft-lbs (20 ±1.3 N-m). Fig ure 27 shows the proper position of the mounted fan.
IMPORTANT: Check for proper fan rotation (clock wise viewed from above). If rotation needs to be re versed on one motor, disconnect main power supply and switch motor leads at the fan contactor. If rota tion needs to be reversed on all motors, disconnect main power supply and switch two leads at TBl.
rated condenser temperature minus entering outdoor-air tem perature) and decreases with decreased temperature differ ence. A drop in entering outdoor-air temperature results in a lower saturated condensing temperature. When outdoor­air temperature drops below the minimum temperatures listed in Table 7 for standard units, additional head pressure con trol is required.
Model 09DK units have fully automatic intermediate­season head pressure control through condenser fan cycling using electromechanical fan cycling controls. Standard head
pressure controls will control the 100 and 50/50% con
denser capacity applications. Head pressure can also be con
trolled by fan cycling controls supplemented by the acces
sory Motormaster® III solid-state head pressure controller. See Motormaster III installation instructions for more infor mation. Other circuit split applications (67/33, 33/33/33, 33/33/17/17% capacity splits) will require the accessory fan
control kit which includes a control panel and additional fan cycling pressure switches. See fan control installation
instructions for more information.
In the standard control scheme, fans 1 and 2 will be on
when there is a call for cooling from the respective coil cir cuits. Fans 1 and 2 are non-cycling. On 054 and 064 units, fans 3 and 4 will be controlled by using a fan cycling pres
sure switch on each of the primary coil circuits in response
to condensing pressure. On 074 and 084 units, fans 3 and 4 will also be controlled using a fan cycling pressure switch in each of the primary coil circuits in response to condens ing pressure. Fans 5 and 6 will be controlled by using two air temperature switches, which respond to the outdoor am bient temperature. The air temperature switches are located on the control box shelf. For temperature and pressure set ting details, see Table 8.
With respect to the fan cycling pressure switch control,
fans 3 and 4 are on above 260 ± 15 psig (1793 ± 103 kPa) and off below 160 ± 10 psig (1103 ± 69 kPa). If pressure is rising between 160 psig (1103 kPa) and 260 psig (1793 kPa), fans 3 and 4 are off. If pressure is reducing from 260 psig (1793 kPa) to 160 psig (1103 kPa) fans 3 and 4 are on. With respect to the air temperature switch control on the 074 and 084 condensers, below 70 ± 3° F (21.1 ± 1.7° C) outdoor ambient, fans 5 and 6 are off; above
80 ± 3° F (26.7 ± 1.7° C) fans 5 and 6 are on. Between
70 F (21.1 C) and 80 F, (26.7 C) whether fans 5 and 6 are on or off depends on whether temperature is rising or fall ing. If the temperature is rising from 70 F (21.1 C) to 80 F (26.7 C), fans 5 and 6 are off. If the temperature is falling from 80 F (26.7 C) to 70 F (21.1 C), fans 5 and 6 are on.
TOP OF VENTURI
ON FAN DECK
TOP OF VENTURI ON FAN DECK
L
HUB
ALL 50-Hz
UNITS
ALL 60-Hz
UNITS
Lubrication — Fan motors have permanently lubricated
bearings.
Head Pressure Control — Reduce condensing capac
ity under low ambient temperature conditions. See Fan Cycling section below.
FAN CYCLING — Efficient operation of evaporator ther mostatic expansion valves require a 90 F (32 C) minimum saturated condensing temperature when compressors are op erating at 100% capacity, 80 F (27 C) for 75% compressor capacity, and 70 F (21 C) for 50 and 25% compressor capacity.
The capacity of an air-cooled condenser increases with
increased temperature difference (defined as entering satu
NOTE: Fan rotation is ciockwise as viewed from top of unit

Fig. 27 — Condenser Fan Adjustment

29
Page 30
UNIT
COIL
No. of Ckts
Cap. (% Ckt)
REFRIGERANT
Min Chg/Ckt
Oper Chg/Ckt Vol/Ckt
STORAGE CAPACITY
R-12 R-22 R-500 R-502 R-134A
Table 6 — Condenser Coil Refrigerant Circuit Data
09DK054 09DK064
2 2
34 16
7 51
16 53
8.83
19.45 013
0.46
13 46
29.64
12.31
27.11
11.61
25.56
12.89
28.37
13.46 29 64
3.61
7.64 4 08
8.99 0 21
6 22
13 69
5.69
12 52
5 36
11.81
5.95
13.11
6.22
13.69
006
kg lb
kg
lb
cu ft
kg
lb
kg
lb
kg
lb
kg
lb
kg
lb
2
50
10.98
24.17 12 92
28 44
019
0.68
19.67
43.33 18 00
39.63
16.97
37.37
18.84
41.48
19.73
43.33
1
66
14 45 31 81
17.00
37.42 .025
0.89
25.90
57.02
23.69
52.16
22.34 49 16
24.79
54.59
25.9 57 02
2
50
16.48
36.28
19.38
42.68 029
1.01
29.19
64.28
26.77
58.94
25.09 55 24
27.89
61.40
29.19 64 28
1 2
66 34
21.68
47.74
25.51 56 17
.037
1.32
38.42 84 59
35 23 77 56
33.02 72 70
36.70
80.80
38.42 84 59
11.27
24.81
13.26
29.19 .02
0.69
19 97
43.97
18 31 40 31
17.16
37.78
19.08
42.00
19.97
43 97
2
16
5.21
11.46
6.13
13.49 .009
0.32
9.22
20.31
8.46
18 62
7.93
17 46
8.81
19 40
9 22
20 31
UNIT
COIL
No. of Ckts
Cap. (% Ckt)
REFRIGERANT
Min Chg/Ckt
Oper Chg/Ckt Vol/Ckt
STORAGE CAPACITY
R-12 R-22 R-500 R-502 R-134A
NOTE: Storage capacity calculated for 80% liquid,
kg
lb
kg
lb
cu ft
kg
lb
kg
lb
kg
lb
kg
lb
kg
lb
2
50
15 91
35.04
18.73
41.23 .028
0 97
28.53
62.82
26.10 57 46
24 61
54.18
27 31 60 14
28.53
62.82
1
68
21.61
47.58 25 43
55 98
037
1 32
38.74
85.30 35 44
78.03
33.42 73 58
37.09
81.66
38.74
85.30
09DK074
10.22
22.50
26.47
36.89
2
32 18
12.02 .018
0 62
18.32
40.33
16.75
15 80 34 78
17.54
38 61
18.32
40.33
2
5.70
12 54
6.70
14.76 .010
0.35
10.21
22.49 9 34
20.57
8.81
19 40
9.78
21.53
10.21
22.49
2 1
50
23 87 52 22
28.08
61.83 .041
1.46
43.26
95.25
39.51
87.00
37.24
82.00
41.33
91.00
43.26
95.25
09DK084
67 33
31.84
70.11
37.46
82.48 .055
1.95
57.63
127 00
52.68
116 00
49.65
109.33
55.11
121.33
57.68
127.00
2
15.90
35.00
18.70
41.18 .028
0.97
28 84 63 50
26.34
58.00
24.83 54 67
27 55
60.67
28.84
63.50
2
17
7.97
17.55
9.39
20 65
.014
0 49
14.42
31.75
13.17 29 00
12 41
27 33
13.78
30.33
14.42
31.75
30
Page 31
Table 7 — Minimum Outdoor-Air Operating
Temperature

English

COMPRESSOR CAPACITY (%)*
TD
100 1 75 1 50 1 25
°F
30 25
20
30
25 20
30
25 20
Minimum Outdoor-Air
Temperature ° F
29 38 47
12 22
-20 -20
31
34 40 47
19 25
38 42 46
22 29 36
-20
31
-20 51
53 56
43 47
51
09DK—
All
Sizes
054,
064
074,
084
HEAD
PRESSURE
CONTROL
FCPSs and
Motormaster®
III
FCPSst
2 Fans
FCPSst
2 Fans
ATSs
2 Fans
SI
HEAD
All
064
084
PRESSURE
CONTROL
FCPSs and
Motormaster
III
FCPSst
2 Fans
FCPSst
2 Fans
ATSs
2 Fans
LEGEND
09DK—
Sizes
054,
074,
ATS — Air Temperature Switch
FCPS — Fan Cycling Pressure Switch
TD — Temperature Difference = Saturated Condensing
'Interpolation permitted. tAdditional FCPSs needed for 67/33, 33/33/33, and 33/33/17/17%
capacity split applications
NOTES:
1. Fans or the 09DK054-084 units are controlled by ATSs and FCPSs.
2 Minimum outdoor temperatures are determined for indoor and out
Temperature Entering - Entering-Air Temperature
See Table 8 for more details. door unit combinations of the same capacity.
COMPRESSOR CAPACITY (%)*
TD
100 1 75 1 50 1 25
°C
Minimum Outdoor-Air
Temperature ° C
16.7
13.9 11 1
16.7 139 11 1
167 139 11 1
-29
-11
-29 -29 -29
-2 3 8
-6
-1
1
4 8
-7
-4
-1
11
3 6
12
8
13
-6
-2 2
6 8
11
Table 8 — Fan Cycling Controls Temperature/
Pressure Settings
English
UNIT 09DK—
054,064 074,084
FCPS
OPENS AT 160
±10 psig
CLOSES AT 260
±15 psig
FM 3,4' FM 3,4'
CLOSES AT 80 ± 3° F
ATS
OPENS AT 70 ± 3° F
FM 5,6t
SI
FCPS
UNIT 09DK— ± 69 kPa OPENS AT 21.1 ± 1.7°C
054,064 074,084 FM 3,4*
ATS — Air Temperature Switch FCPS — Fan Cycle Pressure Switch FM — Fan Motor
'Fan motors 3 and 4 are each controlled by a FCPS for 100 and
50/50% capacity split applications. For other capacity split options, the accessory fan control kit must be used and additional FCPS's
are required. See accessory fan control kit installation instructions
for more information
fFan motors 5 and 6 are each controlled by an ATS.
OPENS AT 1103 ATS
CLOSES AT 1793
± 103 kPa
FM 3,4*
LEGEND
CLOSES AT 26.7 ± 1.7° C
FM 5,6t
...
31
Page 32
PACKAGED SERVICE TRAINING
Our packaged service training programs provide an excellent way to increase your knowledge of the equipment discussed in this manual. Product programs cover:
• Unit Familiarization • Maintenance
• Installation Overview • Operating Sequence
A large selection of product, theory, and skills programs is available. All programs include a video cassette and/or slides and a companion booklet. TJse these for self teaching or to conduct full training sessions.
For a free Service Training Material Catalog (STM), call 1-800-962-9212. Ordering instructions are included.
Copyright 1993 Carrier Corporation
Book 12 PC 111 Catalog No. 530-953 Printed in U.S A. Form 09DK-4SI Pg 32 4-93 Replaces: New
Tab 4a
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Loading...