Carrier 09DC User Manual

Page 1
Carrier
: .¿'K 5:-K , w
ci"' i/''
s io 80 Tons
9AB,09DC

DESCRIPTION

Capacities to 10 Tons
Weather Armor* enclosures (which are also provided
for 09DC016) have a baked enamel finish which pro vides maximum weather protection.

FEATURES

• Multiple Fans and Motors provide inexpensive, re liable system control in intermediate seasons. Standby protection is provided in case one fan motor fails.
• Subcooling permits greater liquid lift in vertical
risers without liquid flashing. Special coil circuiting cools liquid refrigerant below the saturated condensing temperature, extending system capacity without in creasing motor horsepower.
• Direct Drive Fans require no tensioning device or
pulleys. Alignment problems, belt maintenance, and friction loss are eliminated.
• Three Types of Head Pressure Control (Accessory)
are available to maintain a refrigeration load by hold-
Air-Cooled Condensers
Capacities 15 Tons and Over
09DC Air-Cooled Condensers are available in 15-, 20-, 25-, 30- and 40-ton sizes. The 25-, 30- and 40-ton sizes are designed for use in multiples to give capacities of 50, 60 and 80 tons. Each size has three direct drive fans, three motors and motor mounts, three guards, a junction box, and a condenser coil with integral sub cooling circuit. The 20-, 25-, 30- and 40-ton units, all using vertical air flow, may have 2 or 3 circuits, each with an integral subcooling circuit. Each circuit may be used as a separate condenser for a single system. Double-weight, hot dipped, galvanized steel enclosures give maximum protection.
ing a minimum head pressure and reducing condenser capacity at low outdoor temperatures.
1. Motormaster Electronic Control (9AB6, 8, 12 and 09DC016, single-phase) modulates condenser fan motor speed from zero to full rpm.
2. Fan Cycling Control cycles one fan (9AB8, 12) or two fans (09DC) for control during intermediate seasons.
3. Head Pressure Control Damper (09DC024, 084), mounted below unit at the uncontrolled fan section,
further reduces capacity.
• Winter Start Control — Optional package permits start-up of compressor regardless of low temperatures.
© Carrier Corporation 1966
•SINGLE FEATURE SHEET AVAILABLE
Form 9AB, 09DC-2P
Page 2
PHYSICAL DATA
UNIT
RATING (tons)* NET WEIGHT (lb)t
FAN (Prop.), No.
Prop. Diom (in.) Rpm Cfm
MOTORS, No. ... Hp
COILS, Type
No. Face Area (sq ft)
DIMENSIONS (ft-in.)
Length (each) A Width (module) B
Height, w/o Legs Adj Stand (in.) D
9 AB
6 8 12 016
6.8 10.5 13.8
215 315
1
22
1120
410
2 2 3
22 22
1 120
1120
4400 6600 8800
2...Vs 2... Vs
1.. Vs 3-row
1
9 0
3-7Vs 5-2 Vs
13 5
18 0
6-8Vs
3-1 Vs 3-1 Vs 3-1 Vs
C
3-2Vi6
lOV or
3-2 Vs
3-2Vs
16 V.
09DC
024
15.8
22.1
550 854
028
28.0 904
3 3
22 26
1120
13,000
3...V
1140
18,200 25,200
3...%
30
1140 1140
3 . 1
3-row
2
26.2 35.4 39 0 49.6
6-9Vs 4-6 V.
9- 7% 9- 1% 9- 7V. 3-1IV.
3-1IV. 4-lOV.
1-8V. 2- 4 Vs 2- 4 Vs
12Vsor 19Vs 16 or 24
16 or 24
09DC054
034 044
35.8 46.7 56.0
1225
1600
3 3 6
30 32 30
1140 1140 1140
28,200 31,000
3...1 3...1 4-row
2
60.4 78 0 99 2
9-lOV. 9-lOVst
6- OV. 3-1IV.
3- iVs
18 or 26 20 or 28
3- r/s
16 or 24 18 or 26
(T wo
028’s)
(Two
034*s)
71.7
09DC064
1808
2450
6 6
30
50,400 56,400
6...1
6...1
3-row
4
9- 1% 9- 7%
4-lOV.
2- 4 Vs
3- iVs 3- r/s
09DC084
(Two
044’s)
93.4
3200
32
1140
62,000
6...1 4-row
4
120.8
9-lOV. 9-lOVst
6- OV.
20 or 28
Data common to 1- and 2-module units.
*Tons of refrig effect at 30 F temp diff with 1 20 compr heat rejec
tion factor for R-22. tWithout damper or refrigerant. iFor three-circuit coil.

DIMENSIONS

9AB6,8,12 09DC016, 024, 028,
034, 044
5/„ ODF LIQUID OUTLET
“ (09DC0I6 ONLY)
AIR FLOW
ELECTRICAL KNOCKOUT
OUTLET
'''a' ODE
S3 SPACE FOR AIR FLOW
**Use 50/50 split for single circuit. 09DC034 coil 40/40/20 split
may be field modified into 40/60 split.
tt80% liquid, 20% vapor at 90 F.
NOTES:
1. For 09DC024 thru 084, use maximum adjustable stand height when using a damper section.
2. Certified dimension drawings available on request.
024,028.034,044
50/50
COIL SPLIT
1/2-024,028
7/"-034, 044
024,028
63/37
COIL SPLIT
ODF
RIGHT END VIEWS
7/^' ODF Vg" ODF
034
40/40/20
COIL SPLIT
044
38/38/24
COIL SPLIT
7/g ODF
Page 3

CONDENSER RATINGS TYPICAL ARRANGEMENTS

(Two-Module Condensers)
la. Select minimum or optimum charge ratings.
Use optimum charge when compressor, condenser, and evaporator may be selected as a package and the com ponents may be balanced* to secure maximum benefits of 15 F subcooling (for example, in selecting 09DC con densers with Carrier compressors rated at 15 F sub cooling). Optimum charge activates the subcooling circuit, resulting in higher system capacity at slightly higher head pressure and corresponding condensing temperature. Liquid refrigerant leaves the system sub cooled to a stable condition to allow greater length of
refrigerant run or lift.
Otherwise, use minimum charge which gives higher heaf rejection, since entire surface of condenser and sub cooling circuit is used for condensing only. Minimum charge ratings, however, do not represent greatest po tential system capacity. They are comparable to com petitive ratings without subcooling.
b. List the refrigerant, total heat rejection (THR), suction
and discharge temperatures as determined from com pressor data.
2. Determine condensing temperature (saturated discharge temperature minus discharge line loss).
3. Determine temperature difference (condensing tempera ture minus entering air temp).
4. Enter Condenser Ratings table (minimum or optimum charge as determined in Step 1) at selected refrigerant and established temperature difference. Read across to total heat rejection equal to or greater than required.
Interpolate if necessary. Read unit size.
Example (Optimum Charge)
1. Given: R-22, Optimum Charge THR (including subcooling)
Saturated Disch Temp................................................................................123.8 F
Saturated Suction Temp..................................................................................40 F
Entering Air Temp............................................................................................95 F
Disch Line Loss.................................................................................................2 F
2. CondTemp^ 123.8F-2F= 121.8F
3. TD = 121.8F-95F- 26.8 F
4. Interpolate in Condenser Ratings table (optimum charge) and obtain capacity of 09DC028 as 30,0 tons and 09DC024 as 23.6 tons. Select the 09DC028.
..........................................................
29.4 Tons
Example (Minimum Charge)
1. Given: R-12, Minimum Charge THR . . ■
....................................................................................
Saturated Disch Temp...................................................................................122 F
Saturated Suction Temp..................................................................................40 F
Entering Air Temp...........................................................................................95 F
Disch Line Loss ............................................................................................2 F
2. Cond Temp = 122 F-2 F - 120 F
3. TD= 120 F-95 F-25 F
4. Enter Condenser Ratings table (minimum charge) and select 09DC016 with 15,2 tons THR. (Note that with optimum charge this unit has THR of 14.8 tons which does not meet specifications).
*See Carrier System Design Manual.
15.0 Tons
Page 4
HEAD PRESSURE CONTROL
General Efficient operation of evaporator expansion
valves requires a 90 F minimum condensing temperature for
100% compressor capacity, 80 F for 75% capacity, and 70 F for 50% and 25% capacity. The capacity of an air-cooled condenser increases with increased temperature difference (cond temp minus entering air temp) and decreases with decreased temperature difference. Therefore, a drop in en tering air temperature lowers the condensing temperature for a given heat rejection. When outdoor air temperatures drop below prescribed minimums, some form of head pres sure control is required. (See Head Pressure Control Data table for minimum outdoor temperatures and specific head pressure controls for 9AB and 09DC units.)
9AB, 09DC Head Pressure Controls — Head pressure on
9AB and 09DC condensers may be controlled by the Motor-
master Electronic Control, by fan cycling, or by fan cycling
supplemented by the Motormaster or a modulating damper.
Motormaster — When outdoor temperatures are low enough
to cause low condensing pressures, the Motormaster modu
lates the motor speed of one condenser fan from full to zero rpm to maintain a constant saturated condensing tempera ture. The Motormaster, available only with single-phase
motors (on unit sizes thru 09DC016), may be the sole con trol on single fan units or may be used in conjunction with fan cycling control on multiple fan units for full year-round head pressure control.
Fan Cycling — The fan cycling control, used primarily during intermediate seasons, cycles one fan or two fans. On two-module condensers (09DC034, 064, 024), the fan cycling control cycles four of the six condenser fans (two
of three in each module) from a two-step thermostat respond
ing to variations in ambient temperature. The first step of
the thermostat cuts out two corresponding fan motors, one in each module; the second step cuts out a second pair of cor
responding fan motors. The two condenser modules are controlled from a single, completely wired fan cycling con
trol box consisting of one two-stage thermostat, one power and one control terminal block, and two quick-connect re ceptacles (one at the end of a 10-foot flexible conduit).
HEAD PRESSURE CONTROL DATA
HEAD
UNIT
SIZES
All
9AB6 Motormaster
^ABS,Ï2
9AB8,12
024j,028,
OH 044i
09DC016
09DC024, 028, 034,
044t
PRESSURE
CONTROL
Far\
Ort i'<>>
Fan Cycling,
One Fan with
Motormaster
Tw«^ FiTK,
Fan Cycl ing,
Two Fans with
Motormaster
Fan Cyc 1 ing,
With Mod Damper
Winter Season
None
С/с''в^ j,
Two Fans
TD
30 25 20
30 25 20
3Q 2S 20 :
30 25 20
: 30 : 25
ГС
30 25 20
30
25 20
Ш
TD - Temperature Diff (cond temp minus ent air temp)
* Interpolation permitted. t Based on 90 F minimum cond temp at 100% capacity, 80 F at 75%
and 70 F at 50% and 25%. (Motormaster holds cond temp to 100 ±
10 F at all loads and at temperatures down to -20 F.) On some ap plications with multiple DX coils, the compressor may be unloaded while individual coil(s) are still fully loaded. In this case, expan sion valve selection must be based on condensing temperatures
listed, or the minimum outdoor air temperature must be raised by the difference between listed cond temp and cond temp used for valve selection.
t Applied also to each module of 09DC054, 064 and 084.
COMPR CAP. (%)*
100 75 50 25
Min Outdoor Temp (F)t
57 61 65
-20 -20
38
42
45
4?
5i
52
-20 -20
26
30
! m
55 57 60
60 65 70
-20
1 S3 i
43
52
-20 -20
3
1 4'i
-20 -20
-20 -20
-20 -20
-20-213
62 64 65
-20
'S3
43 S2 ­SS
25
SCHEMATIC WIRING DIAGRAM
— CONDENSER CONTROL
(Single Refrigerant Circuit, Single Phase)
Head Pressure Control Damper An accessory head pressure control damper is available to supplement the fan cycling control on the 09DC024 and larger units. The 09DC054, 064, and 084 require two damper packages in stalled for parallel throttling of air to the two uncontrolled fans. Each damper assembly has a pressure-operated actu ator to operate the damper blades which modulate inlet air flow to the uncontrolled fan in response to head pressure variations. The pressure sensing tubing (capillary) for both pressure actuators is connected to the same point in the
liquid line serving the last refrigerant circuit to shut down. Each capillary is provided with a 1/4-inch flare connection. A single shut-off valve at the liquid line is recommended, for service.
Multiple Circuit Condensers — Multiple circuit conden
sers applied to separate refrigeration cycles present special problems when head pressure is controlled from a single control point. For such applications, more positive system control may be ensured by using individual condensers and
head pressure controls.
LP — Low Pressure Switch ^ HP — High Pressure Switch
NOTES:
1. For three-phase service, holding coils are wired in parallel.
2. Multicircuit units may be similarly controlled by wiring fan motor holding coil(s) in series with thermostat, compressor overloads, and low pressurestat of each refrigerant circuit
3. Two or more condensers, piped in parallel on a single refrig erant circuit, must be of equal size and wired in parallel.
Page 5
SCHEMATIC WIRING —HEAD PRESSURE CONTROL
ТШЙЙОЗТЙТ i i
COMMON FOR
ALL WIRING
JiNTERLOCKED
[FC
[with СОМРЙ
■9AB WITH MOTORMASTER
,^5-9AB8,12 fan cycling ONE FAN / MOTORMASTER iSl+m - 09DC0I6 FAN CYCLING TWO FANS/MOTORMASTER
CONTROL TERMINAL BLOCK (FAN CYCLING CONTROL BOX)
2-STAGE
THERMOSTAT
FAN CYCLING TWO FANS (EACH MODULE) 09DC0I6, 024.028,034,044
QUICK-CONNECT
INTERLOCKED WITH COMPR
BULB
LOCATED IN AIRSTREAM
OF FM|
PLUG -Л
208/230/ i
TO fUSED DISCONNECT
3-PHASE POWER
TO FUSED DISCONNECT
\
FC| [
FM|)
" ; 1
____
a;
FM,
___
hi
1 i u
FC2
FC3
'I'
POWER
TERMINAL
BLOCK
(FAN CYCLING CONTROL
BOX)
QUICK-CONNECT_J
PLUG
FM|
(FM^
(FM3,
“i±:
TO FUSED DISCONNECT
_FLEXIBLE
CONDUIT
(PART OF
FAN CYCLING
CONTROL BOX
PACKAGE)
208/230 V
LEGEND
— Fan Contactor — Fan Motor
Ad(d this wiring for 054,064,084
TYPICAL PIPING AND WIRING CONNECTIONS (09DC Units shown)
l-CIRCUIT
FUSED DISCONNECT SWITCHES
FROM POWER SOURCE
3 WIRES (Зф) OIG, _
024,028,034,044
2 WIRES(lф)OI6
1
NOTES:
1. Single-phase motors (9AB, 09DC016) require one field-supplied contactor to start all fans. Three-phase motors (09DC016, 024,
028, 034 and 044) require one field-supplied contactor for each fan unless supplied with accessory fan cycling control.
2. All pip ing between two mocdule units is fielid supplied.
3. Wiring and piping shown are general points-of-connection guides only and do not include detai is required for specific instaI lotions,
4. All wiring must comply with appl ¡cable notional and local codes.
HOT GAS
2-CIRCUIT
ACCESSORY FAN
CYCLING CONTROL
(INCLUDES CONTACTORS;
THREE-PHASE)
JUNCTION BOX
LIQUID TO EVAPORATOR
WIRE AS IN EITHER OF ABOVE DIAGRAMS
3-ClRCUIT
ACCESSORY DAMPER
SECTION 024, 028, 034
"3
LIQUID
All piping must follow standard refrigerant piping practices. Piping to two-module units (09DC054, 064 and 084) should
follow standard proctice for multiple condensers. See Carrier
System Design Manual for details.
For pressure relief requirements, see latest revision of Safety
Code for Mechanical Refrigeration - ASA-B9 1.
AND 044 (USE ONLY WITH
FAN CYCLING CONTROL)
Page 6
ELECTRICAL DATA (60-cycle)
UNIT
9AB6
9AB8
9AB12
09DC016
09DC024
VOLTS
208/230 208/230
208/230 208/230
208/230 208/230
208/230
460 575
208 230 3 460
575 208 3
PHASE
09DC028, 230 3 034, 044
460 575 3
1
1
1 2 1
1 1
3 3 1.0
3 4 0
3 3 1.6
3
FANS FLA
No.
1
2
T otal
T Ota 1
3
T otal
1
1
1
1 1
2
3
3
3
Hp
(ea)
2 1*
V3
2.1*
V3
2.4
/3
2.1*
V3
2 4
%
V3 3 3*
4 0
V2
1 2
V2
3 8
/4
1.9
5 3
4 8
2 4
1 9
FLA - Full Load Amps
*These are special motors suitable for use with Motormaster head pres
sure control.
NOTE: All 208/230-volt single-phase units are suitable for operation on either voltage.

GUIDE SPECIFICATIONS

Furnish and Install as shown on the drawing—^—air
cooled condensers suitable for tons each of total heat rejection, when condensing refrigerant at , F saturated condensing temperature with air entering at«
F dry-bulb temperature. Units shall be arranged for hori zontal (vertical) air flow.
Units shall consist of: coils, with integral subcooling, 2.
supporting casing with stand, and wind deflector (9AB only). Coil shall be constructed of plate aluminum fins on mechani cally expanded copper tubes, cleaned, dehydrated, sealed, and leak tested at 400 psig (9AB), 410 psig (09DC016), or 420 psig (09DC024 and larger).
Fans shall be direct drive, propeller type, protected by
guards. Motors shall be permanent split-capacitor (9AB, 09DC016) or 3-phase, 60-cycle (09DC016, 024, 028, 034, 044, 054, 064, 084). All motors shall be resiliently mounted and prelubricated, with built-in overload protection. Fan shaft shall be corrosion protected and mounted in prelubri cated bearings. Fan blades shall have an iridite finish. A magnetic contactor shall be field supplied for 9AB, 09DC- 3. 016, and shall be field supplied for 09DC024, 028, 034, 044, 054, 064, 084 if head pressure control is not used.
Casing shall be painted, Galvanneal steel (9AB, 09DC-
016) or heavy-gage, double-weight (2-1/2 oz zinc/sq ft) galvanized steel (09DC024, 028, 034, 044). Access panels shall be provided for electrical connections.
Accessories (To specify from Items 1 thru 4 below, refer to 4.
Head Pressure Control Data table.)
1. Motormaster Electronic Head Pressure Control Units shall be provided with a completely transistorized vari able speed fan control to modulate unit capacity in re sponse to variations in head pressure. The control en- 5.
Manufacturer reserves the right to change any
closure shall be weathertight and shall have Weather Armor finish. Mounting hardware shall also be provided. Control shall modulate fan motor speed from full to zero rpm to maintain a saturated condensing temperature of approximately 100 F at outdoor temperatures down to —20 F.
Fan Cycling Control — Unit(s) shall be provided with a control to cycle one of two fans (9AB8,12), two of three fans (09DC016,024,028,034,044), or four of six fans (09DC054,064,084), in response to outdoor ambient temp erature. Control package shall include; thermostat and remote bulb (9AB8,12); contactor(s), terminal strip(s), plug, and two-stage thermostat (09DC016,024,028,034,
044); contactors, two-stage thermostat, power control terminal blocks and two quick-connect receptacles, one at end of 10-foot flexible conduit (09DC054,064,084). Controls shall be enclosed in weathertight sheet metal box with cover. Necessary mounting hardware shall be
provided. Head Pressure Control Damper — Unit(s) shall be pro
vided with a control for further reduction in condenser capacity to meet system part load operation or lower outdoor ambient temperatures. This assembly shall in clude: flanged damper frame, movable damper blades, operating linkages, self-contained pressure-operated damper actuator with capillary, and necessary mounting
hardware. Winter Start Control (required when minimum ambient
temperature is below design coil suction temperature) — Unit(s) shall be provided with a Winter Start Control
Package which shall temporarily bypass the system low pressurestat to permit start-up at low temperature.
Floor Mounting Stand (9AB8 and 12).
product specifications without notice.
CARRIER AIR CONDITIONING
Tab 5
Form 9AB,09DC-2P Supersedes 9AB,09DC-1P
COMPANY • SYRACUSE, NEW YORK
Printed in U.S.A.
2-66
Codes C and MC (520902)
Loading...