Carrier 09BY006-024 User Manual

0 (0)
Air-Cooled Condenser Units
Installation, Start-Up and
Service Instructions
09BY006-024
5to20Tons
CONTENTS
SAFETY CONSIDERATIONS .................1
GENERAL ..................................1
INSTALLATION ............................1-12
Step 1 − Complete Pre-Installation Checks ..1
Step 2 − Rig and Place Unit ................7
• PLACING THE UNIT
• VIBRATION ISOLATION
• POSITIONING THE 09BY UNIT
• VERTICAL DISCHARGE
Step 3 − Install Accessory Low-Ambient Kit or
Inlet Filter Kit (If Required) ................8
Step 4 − Install Rain Drain .................8
Step 5 − Complete Refrigerant Piping .......8
• GENERAL
• REFRIGERANT LINE SIZING
• PRESSURE RELIEF
• REFRIGERANT RECEIVER
• LIQUID LIFT
• SWEAT CONNECTIONS
• FIELD PIPING
• MANIFOLDING CIRCUITS
• CHECK VALVE
• SERVICE VALVES
Step 6 − Ductwork ........................10
• CONDENSER AIR DUCT INSULATION
Step 7 − Insulate the Unit .................11
Step 8 − Complete Electrical Connections ..11
• GENERAL
• MAIN POWER WIRING
• CONTROL CIRCUIT POWER WIRING
• GENERAL WIRING NOTES
START-UP .................................13
System Evacuation and Dehydration ........13
Charging Procedure .......................13
Check Operation of Condenser Fan Motor
Controls and Rotation of Fans ...........13
Adjust Fan Speed .........................13
SERVICE .................................13-15
Cleaning Condenser Coils .................13
Lubrication ................................13
Condenser Fan Adjustment ................13
• TO CHANGE FAN SPEED
• PULLEY ALIGNMENT
• BELT TENSION ADJUSTMENT
• TO CHANGE FAN WHEEL
• TO REPLACE FAN BEARING
MAINTENANCE ............................15
Cleaning ..................................15
Inspection .................................15
Air Filters .................................15
Condensate Drain .........................15
TROUBLESHOOTING ......................16
START-UP CHECKLIST ................CL-1,CL-2
Page
SAFETY CONSIDERATIONS
Installing, startingup,and servicing air-conditioning equip­ment can be hazardous due to system pressures, electrical components, and equipment location.
Only trained, qualified installers and service mechanics should install, start-up, and service this 09BY equipment (Fig. 1).
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
Follow all safety codes. Wear safety glassesand workgloves. Keep quenching cloth and fire extinguisher nearby when braz­ing. Use care in handling, rigging, and setting bulky equipment.
ELECTRIC SHOCK HAZARD Separate power sources (main and control
power circuits) are used for these units. Be sure both main and control power circuits are disconnected before servicing.
GENERAL
The 09BY air-cooledcondenser is a remote air-cooled con­denser designed to be used with the 50BZ vertical packaged units. See Table 1. Airflow is horizontal, both into and out from the same face of the unit. The unit is designed to be mounted indoors in a window, through the wall in high-rise buildings, or on the wall on the building exterior. See Fig. 2 for typical applications. Ductwork is not needed, but may be added easily if required by the application. Airflow is pro­vided by centrifugal fans with an adjustable belt drive to meet varying static requirements. Units may also be matched with other compressor and evaporator combinations. Contact your local representative for more details.
Check space requirements, service clearances, floor strength, location of piping, size of power supply,and location of duct­work (if used) before installing. See Fig. 3 for unit dimen­sions and Table 2 for unit operating weights.
INSTALLATION
Step 1 — Complete Pre-Installation Checks —
Examine unit for damage incurred during shipment. File claim immediately with transit company if damage is found. Check the shipment for completeness. Verify that the nameplate elec­trical requirements match the available power supply.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 4 Tab 4a 4a
PC 111 Catalog No. 530-969 Printed in U.S.A. Form 09BY-2SI Pg 1 9-96 Replaces: 09BY-1SI
Fig. 1 — 09BY Unit (008-014 Shown)
2
09BY
HANGER RODS
DISCHARGE DUCT
INLET DUCT
TO OUTSIDE
TO RAIN DRAIN (REQUIRED IF RAIN WILL ENTER UNIT)
TO REFRIGERANT PIPING COMPRESSOR/ EVAPORATOR UNIT
INSULATE IF THROUGH CONDITIONED SPACE
09BY IN REMOTE APPLICATION WITH DUCTWORK
(Shown Suspended from Ceiling)
OUTSIDE WALL
OUT
WALL LOUVERS
50BZ
POWER CONNECTION
09BY
(FIELD SUPPLIED)
IN
LEGEND
Refrigerant Connection Field-Supplied Refrigerant Piping
*Field-Supplied Floor Stand (Height to Match Wall Opening).
Fig. 2 — Mounting Applications
HEIGHT AS REQUIRED FOR WINDOW OR WALL OPENING
FLOOR STAND*
TO RAIN DRAIN (REQUIRED IF RAIN WILL ENTER UNIT)
09BY DIRECT CONNECTION TO 50BZ UNIT
3
09BY DIMENSIONS (English)
09BY DIMENSIONS (SI)
DIMENSION
A 2-11 B 1- 7
006
(Ft-in.)
008
(Ft-in.)
1
⁄23- 613⁄163- 613⁄163- 613⁄165- 0
11
⁄161-115⁄81-115⁄81-115⁄82- 97⁄
012
(Ft-in.)
014
(Ft-in.)
C 4- 07⁄164- 8 5- 31⁄25-11 7- 69⁄ D 1-111⁄42- 39⁄162- 39⁄162- 39⁄162-11 E 0-11
1
⁄81- 2 1- 2 1- 2 1- 73⁄
F 0- 63⁄160- 57⁄80- 711⁄160-117⁄161-1111⁄ G 1- 15⁄161- 35⁄81- 47⁄81- 47⁄82- 0 H 0- 9
5
⁄160-11 0-11 0-11 1- 31⁄
J 0- 3 0- 3 0- 3 0- 3 0- 27⁄ K 3- 51⁄84- 01⁄44- 75⁄85- 31⁄47- 01⁄ L 1-105⁄82- 3 2- 3 2- 3 2- 9
M 0- 1
9
⁄160- 19⁄160- 19⁄160- 19⁄160- 31⁄
N 0- 6 0- 7 0- 7 0- 7 0-10 P 2- 5 2- 9 3- 2 3- 7 4- 6 R 1- 2 1- 5 1- 5 1- 5 2- 0
016,024
(Ft-in.)
16 16
4
2 16 4
8
DIMENSION
006
(mm)
008
(mm)
012
(mm)
014
(mm)
016,024
(mm)
A 902 1087 1087 1087 1526 B 500 600 600 600 850 C 1231 1422 1613 1804 2300 D 590 701 701 701 911 E 282 357 357 357 502
16
F 156 150 195 290 347 G 338 396 428 428 610 H 236 280 318 318 394 J 76 76 76 76 63 K 1044 1226 1413 1607 2140 L 575 686 686 686 838 M 40 40 40 40 80 N 152 178 178 178 254 P 737 838 965 1092 1372 R 356 432 432 432 610
Fig. 3 — Base Unit Dimensions
4
CORNER WEIGHTS (Lb)
UNIT SIZE
006 55 73 59 42 008 61 89 73 44 012 86 114 93 64 014 107 142 114 78 016 123 159 127 91 024 132 195 158 95
ABCD
NOTES:
1. Operational clearances are 0 in. on all sides of the unit.
2. Service clearances are 0 in. (minimum) on the top, rear,and front of the unit. A minimum of 3 ft service clearance is required on the unit right side, anda3ftclearance is recommended on the left side (2 ft is the minimum). One side of the unit (either right, left, or rear) should have the following minimum clearance for removal of the blower shaft:
Fig. 3 — Base Unit Dimensions (cont)
UNIT SIZE
006 41.0 008 47.0 012 51.0 014 51.0 016 55.5 024 73.0
APPROX. SHAFT LENGTH
(in.)
5
Table 1 — Condenser Unit Application
UNIT 50BZ
006 008 012 014 016 024
09BY
006 S 008 S 012 OS 014 OS 016 OS 024 OS
LEGEND
S—Standard O—Optional
NOTE: Contact your local representative for use with reciprocating air-cooled chillers and other compressor-bearing unit combinations.
Table 2 — Physical Data
UNIT 09BY 006 008 012 014 016 024
NOMINAL TONS 57 OPERATING WEIGHT (Lb) 267 357 441 471 837 970 REFRIGERANT R-22
Number of Circuits 11222 3 Minimum Charge (Lb/Ckt) 6 11 6 6/11 11 11 Optimum Charge (Lb/Ckt) 8.38 14.5 8.38 8.38/14.5 14.5 14.5 Storage Volume Ft Holding Charge Nitrogen Charge
CONDENSER FAN Belt Drive, Centrifutal
Nominal Airflow (Cfm) 3000 4500 6000 7200 9000 12,000 Cfm Range 2000-4500 3400-6400 4500-7000 6000-7600 6700-9750 7500-11,000 Quantity 22222 2 Size (in.) 8.8 × 8.8 11.0 × 11.0 11.0 × 11.0 11.0 × 11.0 12.4 × 12.4 14.0 × 14.0 Pulley Size (in.) 5 Motor Pulley Range (in.) 43⁄16-51⁄ Rpm Range 1365-1566 960-1260 1106-1455 1045-1306 840-1050 686-847 Maximum Fan Rpm 1705 1365 1365 1365 1210 955 Belt Quantity...Size 1...A41 1...B46 1...B45 2...A45 2...B88 3...B90 Pulley Center Line Distance (in.) 11.2/12.6 13.6/15.0 13.6/15.0 13.6/15.0 32.6/33.8 30.0/30.7 Fan Shaft (mm)* 20 25 25 25 25 30 Motor Shaft (in.) Motor Hp...Type 2...TEFC† 3...TEFC 3...TEFC 5...TEFC 5...TEFC 10...TEFC Motor Frame Size 145T 182T 182T 184T 184T 215T Maximum Motor Hp 3555510
CONDENSER COIL
Rows...Fins per in. 4...14 5...14 5...14 5...14 4...15 5...15 Face Area (sq ft) 6.33 8.75 10.12 11.45 19.38 19.38
CONNECTIONS
Hot Gas
Quantity 11222 3 Size (in.)
Liquid Line
Quantity 11222 3 Size (in.)
Condensate Drain (in.)
3
/Ckt) 0.31 0.47 0.31 0.31/0.47 0.47 0.47
11
16
2
7
8
1
2
1
2
CONTROLS 24-V Control Fan Contactor Provided in Unit
*Metric size. †TEFC — Totally Enclosed Fan Cooled.
NOTE: Optimum charge is based on 15° F subcooling. Minimum charge is based on 5° F subcooling.
1
2
75⁄
8
43⁄16-51⁄
2
11⁄
8
3
⁄8-in. OD Enhanced Copper Tube, Aluminum Fin
1
2
1
2
10 12 15 20
65⁄
8
4-5 4-5 43⁄4-6 53⁄8-65⁄
11⁄
8
1
2
1
2
3
⁄4FPT
611⁄
11⁄
1
2
1
2
16
8
10 1311⁄
11⁄
8
1
2
1
2
13⁄
16
8
8
1
2
1
2
6
Loading...
+ 14 hidden pages