Carrier 07E User Manual

Carrier
installation, Start-Up ncsc H7F
and Service Instructions WOC,u/C
Compressors and Condensing Units
Hermetic, Water-Cooled
PRELIMINARY SURVEY
Inspect shipment for damage. File claim with the shipping company if shipment is damaged or incomplete.
Locate unit on floor in a well ventilated area. Install unit where it will be warmer than condi tioned area. Position it to allow sufficient space for refrigerant and water connections and to service
compressor. Allow space at one end of condenser for tube cleaning or replacement. Place unit so suction and discharge valves can be easily reached and so oil level can be checked.
Local water conditions can cause excessive fouling or pitting of condenser tubes. If such conditions are anticipated, a water treatment analysis is recommended. Refer to Carrier System Design Manual, Part 5, for general water condi tioning information.
Make provision in piping layout to drain and vent
condenser if system is to be shut down in winter.
Level unit and bolt it firmly to foundation.
Remove 4 self-locking bolts from compressor
mounting springs, and reassemble them with flanged washers and neoprene snubbers as shown in Fig. 1. Flanged washers and neoprene snubbers are shipped in a cloth bag tied to compressor. Tighten all 4 bolts. Then, loosen each until the flanged washer can be moved sidewise. Check compressor to see that it floats freely on its mounting springs.
SMUBBER FLATBED WASHER
MEOPRENE SNUBBER
^COMPRESSOR FOOT
, tSOtATtON SPRiNO
Fig. 1 — Compressor Mounting
PIPING CONNECTIONS
Attach water supply and return line to connec tions indicated on condensing unit (Fig. 3). Water leaving condenser should not be connected directly into sewer lines; check local codes.
Attach refrigerant liquid and suction lines to
condensing unit (Fig. 3); suction and discharge lines to compressor unit (Fig. 2). Discharge line muffler supplied with 06EV,W compressor units is installed in discharge line as close to shutoff valve as possible. When soldering or brazing piping to valves, disassemble the valve or wrap it in wet cloth
to prevent damage by heat. Allow flexibility in suction line so compressor suction valve may be moved aside for access to suction strainer.
Install a solenoid valve (field supplied) in liquid hne directly before expansion valve. Solenoid valve is necessary for single pumpout control used on 06E,07E units (refer to Start-Up and Service Instructions). A filter-drier of adequate size should be installed in liquid line between condenser and solenoid valve.
Pressure relief valve located on side of con denser will open to relieve excessive pressure, allowing refrigerant to escape. Most local codes require piping from valve to outdoors.
Refer to Carrier System Design Manual for standard piping techniques.
Table 1 — Physical Data
COMPRESSOR UNIT 06E
d P E R A fjNjG W E (G H T (fb)
CONDENSING UNIT 07E OPERATING WEIGHT (lb)
refrigeYnt
COMPRESSOR 06E
Oil Charge (pt) (PP33-2) Normal Oil Pressure*
Oil Safety Switch Cut-In
High-Pressure Switch
Cutout Range
Differential (cutout, cut-in) f Factory Settings f Cutout '
Low-Pressure Switch
Cutout Range Differential (cutout, cut-in)
Factory Settings! Cutout
Low Side Max Pressure
CONDENSER DATA
Max Refrigerant (R-22)
Storage Capacity (lb) t
Min Refrigerant (R-22)
Operating Charge (Ib)
Max Operating Pressure
Refrigerant Side Water Side
J 07E Conidensing Unit data
* Pressures noted are above operating suction pressure; i.e , pressure
differential between suction pressure and discharge pressure of oil pump.
Î Pressure switch settings shown are for R-22. When using other
refrigerants, reset high- and low-pressure switch settings to pressures corresponding to satuialion temperatures indicated by the above pressures.
\ Condenser 80% filled with liquid refrigerant at 104 F,
Cutout
Cut-in i
Cut-in
V022
W027 1 W033 W044
6Ô0
BO 22
D250 D150 N265 ;
B027^
1275 1340 1 1350
R-22, R-502^
14
230 to 400 psiq (adj) 23G to 340 p'ji ;g (ccj)
, 80 ± 10 psi (fi xed) 370 ± 7 Dsig 28C i 290 + 7 psig
200 ± 7 psic
20 in Hg vac to 60 psig (adj) 20 in Hg vac to 70 psig (adj)
31 psi (adj 13 to 50)
650
B033 D044
.1,
0265 I F 275 E299
N175
16 i Î9
psig
12-18
psig
8-10
psig
4- 5
36 + 4 psig 67 + 4 psig
245 psig
135
' 33
335 psig 250 psig
' 670
1560
N599
193
37
© Carrier Corporation 1972
Form 06E,07E-4SI
E SUCTION VALVE ODF
(ROTATES 360°AT ,
90° INTERVALS)
* Install pressure relief device in discharge line
Pressure relief setting is 465 psig
tOverall width includes projection of fuse
holders and/or switches
j.Maximum height is to top of unloader valve on
06EV022 and W044
F DISCHARGE VALVE ODF^
'• . (ROTATES 180°) n
D DIAM CONCEN
DIAM-4 HOLES
RIG KNOCKOUT
Fig. 2 — 06E Hermetic Compressor Units
06E Hermetic Compressor Unit Dimensions
UNIT 06E DIMENSIONS (ff-in.)
CONNECTIONS (in.)
■k KNOCKOUTS .
2" FPT OUTLET (6-PASS) INLET (3-PASS)*
2 FPT INLET «”>■ (3-PASS*a6-PASS)~
V022
A
3-9V2
B
2-0 2-0
C
2-r/a 2-2Va
1% &
2V,
E
IVa
F
1 %
L DIAM CONCENTRIC KNOCKOUT
W027
2-9%
2, 2%
& 3
IVs 1%
W033
3-11% 2- 0 1-1 1%
2- 1%
]% &
2% 2Va
1%
W044
4- 0%
2- 2 2, 2%
& 3
2Va
1%
07E Water-Cooled Condensing Unit Dimensions
2Va
2Va
D044 6- 7%
4-10%
2%a
2, 2Va
& 3
UNIT 07E DIMENSIONS (ft-in.) G
CONNECTIONS (In.)
B022 B027 B033
6- 5 6- 5 6- 5
H
2-11% 2-1 r/2
J
4- 8% K L
1%
1% &
2%
4-IOV4
1%
2, 2%
& 3
2-1 1% 3- 2Va 4- 8%
1% &
I PIPE PLUG TUBE
SIDE DRAIN EITHER END
DIAM-4 HOLES WIDTH DIM I'-5"
ifc^TO
*Use both inlets for 3-pass operation.
Fig. 3 — 07E Water-Cooled Condensing Units
Table 2 — Electrical Data
volts/phaU
NDSV
COND
UNIT KW LRA FLA
07 E
B022 B027 31.4 B033 34 0 DO 44 50.4
COMPR
06 E
V022 24 8 387 W027 W033 W044 55.1
VOLTS/PHASE NDSV
COND
UNIT KW LRA
07 E (AWG No.) Wire
B022 B027
B033 34 0 175 48 66 0 D044 50.4 265 61 85.4
COMPR
06 E
V022 24 8 175 35 48 3 WO 27 W033 37 6 210 W044 55 1 300 69 96.0
FLA — Full Load Amps LRA — Locked Rotor Amps IMDSV — Nominal Distribution System Voltage (Application Range)
OLTA — Overload Trip Amps
*Wire size to terminal box (line side) NOTES:
1. 208-, 230-volt 06E compressor units and 07E condensing units
22 6
33.6 457 37 6
22 6 31 4
33 6 205 43 60 2
-- Motorsand controlswill operate satisfactorily 10% above
and 10% below the NDSV (Application Range)
have part-winding start 460-, 575-volt units have across-the-line start, except 06EW044 and 07ED044 which have part-winding start Control circuit voltage is 11 5 volts for all units.
310 71 99 457 387 105 586 126
464
664
FLA OLTA Size*
140 205
OLTA
86 121
78 109
93 115 160 137
32
44 5 8 102
41 57 8 6 122
52 71 6
208/3 230/3
208
Wire Size*
(AWG No.)
146 00 176
129 192
00
00 00
460/3
440-480
Wire
4
6 143 6 4
2
0
1 0
2
2
Max Fusetron Wire
Ft
Wire
73 100 62 125 84
71 200 530
79 79 150 410 77 175 420
65
Max
Ft
158 70
132
116 145 75 121
220-240
Si ze
(Amps) (AWG No.)
150
110 350
200 600 137
Fusetron
Si ze
(Amps)
45 60 164
90 212 53 73.4 4 185
50 140 28 38 6 70
100 240 56 78 0
LRA
280 65 90 8 410 350 96 134 0 0
LRA
1 12 140 38 53 3 6 165 60
164 34 168
Factory wiring is in compliance with National Electrical Code.
Field wiring must comply with appiicable local codes Maximum
wire size to control center line terminal block is 250 MCM.
Where compressor FLA is under 100 amps, wire sizes are based
on type TW wire. Where compressor FLA is over 100 amps, wire sizes are based on type TFIW wire Maximum wire lengths tabulated will result in a 1% voltage drop
to compressor A 3% voltage drop is maximum allowed.Therefore,
the run length can be increased to three times the value given.
5.
Above 06E compressor unit electrical data does not apply for 06E compressors used as an integral part of other Carrier equip ment See proper Start-Up and Service book for electrical information
FLA OLTA
116 0
82
126 176.0 00
71
86
105 146
FLA
27 36 7 8 151 34 48 3
42
99
120 192 00
OLTA
48 3
58 0
Size* Ft Size
2 0
2 80 100 1 78
00
575/3
550-600
Wire Size*
(AWG No.)
6 183
8 147 40 6 6 150 60 4 171 80
Max Fusetron
Wire
Max
Ft
Wire
183
(Amps)
88 100 78 87 150 80 200
94 72
125
125 150
200
Fusetron
Size
(Amps)
40
SO
80
50
ELECTRICAL REQUIREMENTS
Field wiring must comply with local and
national codes.
Install a branch circuit fused disconnect of
adequate size to handle starting current.
Line power is brought into control center thru indicated opening. Connect line power supply to terminal block 1; connect power leads to terminals
LI, L2 and L3. Connect control circuit power supply (115 volt) to terminals 1 and 2 on terminal block 2. Refer to Fig. 4 and 5.
Wiring connections for field-supplied equip ment are shown on diagram attached to unit (or in wiring diagram booklet).
Discharge line limit thermostat supplied with
06EV,W compressor units is installed on discharge hne as close to compressor as possible.
1. Place mounting
plate on discharge line and
solder in place.
2. Fasten the thermostat
to plate with screws
supplied.
3. Cover switch with insulation and secure insula tion at each end with straps.
4. Connect thermostat leads to control circuit terminals 4 and 5.
ACCESSORIES
PACKAGE NUMBER DESCRIPTION
07EA900021 Control Circuit Transformer 07EA900001
Gage Panel
KNOCKOUTS
DISCHARGE LINE THERMOSTAT CONN
PART-WINDING
START UNITS ONLY
CONTROL CIRCUIT
POWER CONN.* (TERMINAL BLOCK
N0.2)
ACCESSORY TRANSFORMER
CONNECT TO LI a L2
TERMINALS ON LINE
SIDE OF CONTACTOR
*Refer to unit label wiring diagram for connections when accessory
transformer or interlocks are used
Fig. 4 - Control Center - Used on: 06EV022, 06EW033, 07EB022, 07EB033
FIELD POWER CONN. (TERMINAL BLOCK NO. I)
PART-WINDING START UNITS
ONLY
OIL PRESSURE SAFETY SWITCH
DISCHARGE LINE THERMOSTAT CONN.*
PART-WINDING
START UNITS
ONLY
ACCESSORY TRANSFORMER CONNECT TO LI a L2 TERMINALS
ON LINE SIDE OF CONTACTOR
KNOCKOUTS
MOTOR PROTECTION MODULE
CONTROL CIRCUIT POWER CONN.*
(TERMINAL
BLOCK N0.2)
FIELD POWER CONN.
(TERMINAL BLOCK N0.1)
PART-WINDING
START UNITS ONLY
OIL PRESSURE SAFETY SWITCH
*Refer to unit label wiring diagram for connections when accessory transtoriT.er or
interlocks are used
Fig. 5 - Control Center - Used on: 06EW027, 06EW044, 07EB027, 07ED044
REFRIGERANT CHARGING
Evacuate, ' Dehydrate and Leak Test the entire
refrigerant system by methods described in Carrier
Standard Service Techniques Manual, Chapter 1, Sections 1-6 and 1-7. Use sight glass method to charge system. See section 1-8 of Service Tech
niques Manual for details.
CHARGE THE SYSTEM to a clear sight glass while holding saturated condensing pressure constant at
125 F (air-cooled systems) or 105 F (water-cooled systems). Add additional refrigerant to fill con denser subcooler coils.
07E Condensing Units obtained.
add charge
After clear sight glass is
until liquid refrigerant
reaches condenser liquid level test cock.
06E Compressor Units — See condenser data for additional charge required to fill subcooler.
INITIAL START-UP
Crankcase heater should be energized a mini
mum of 24 hours before starting unit.
Check to see that oil level is 1/3 to 2/3 up on
compressor sight glass.
Open water supply valve and allow water to
reach condenser. (Turn condenser fan on when the
compressor unit is applied with air-cooled condenser.)
Backseat the compressor suction and discharge
shutoff valves; open liquid line valve at receiver.
Start evaporator fan or chilled water pump.
To Start Compressor, place control center start-
stop switch in “Start” position, and push motor
protector relay start-reset button. (Time Guard
circuit will cause a short delay before compressor starts.) If compressor does not start in a 5-minute
period, reset oil pressure safety switch and over load relays.
Recheck oil level and check oil pressure which
should be 12-18 psig above suction pressure.
NOTE: If compressor is shut off by motor protection relay, current overloads, oil safety switch or if control circuit power is opened, reset button(s) must be pushed before compressor will restart. Do not reset safety controls more than once before determining cause of shutdown.
CHECKING OPERATIONS
Refer to Carrier Standard Service Techniques
Manual, Chapter 2 for complete instructions on
checking electrical components.
Oil Pressure Safety Switch (Fig. 6 and 7) may be
checked by moving arm on left side of switch forward. Compressor should stop in approximately 45 seconds. (If compressor continues to run, check wiring to safety switch. If wiring is correct, the switch is faulty and should be replaced.)
After completing test, press reset button on
front of safety switch and restart compressor.
(Allow 3 minutes before attempting to reset
switch.)
NOTE Check oil level in compressor sight glass after 15-20 minutes of operation. If oil level is low, add oil according to methods described in Carrier Standard Service Techniques Manual, Chapter 1 (Section 1-11).
LOW PRESSURE
CONNECT TO OIL PUMP DISCHARGE
CONNECT TO
(Switch shown is Penn Controls )
CRANKCASE
Fig. 6 — Oil Pressure Safety Switch Used on;
06EV022, 06EW033, 07EB022, 07EB033
RESISTANCE
I
■f
120
V^C
CONNECT IN 240 SERIES WITH VAC CONTROL CIRCUIT
(REFER TO UNIT LABEL
WIRING DIAGRAM)
HIGH-PRESSURE CONNECTION TO
0|LPUMP '" LOW-PRESSURE DISCHARGE CONNECTION
TO CRANKCASE
Fig. 7 — Oil Pressure Safety Switch Used on:
06EW027, 06EW044, 07EB027, 07ED044
Dual Pressurestat (Fig. 8) — High-pressure safety
switch is checked by throttling condenser water or blocking air flow on air-cooled units, allowing head pressure to rise gradually. Check discharge pressure
constantly throughout procedure. Compressor should shut off within 10 psi of values shown in Table 1.
Loading...
+ 11 hidden pages