Inspect shipment for damage. File claim with
the shipping company if shipment is damaged or
parts are missing.
Local water conditions can cause excessive
fouling or pitting of condenser tubes. If such
conditions are anticipated, a water treatment
analysis is recommended. Refer to Carrier System
Design Manual, Part 5, for general water condi
tioning information.
PLACING THE UNIT
Locate unit on floor in a well ventilated area.
Install unit where it will be warmer than condi
tioned area. Position it to allow sufficient space for
refrigerant and water connections and to seiwice
compressor. Allow space at one end of condenser
for tube cleaning or replacement. Place unit so
suction and discharge valves can be easily reached
and so oil level can be checked.
Make provision in piping layout to drain and
vent condenser if system is to be shut down in
winter.
Level unit and bolt it firmly to foundation.
COMPRESSOR
Remove 4 self-locking bolts from compressor
mounting springs, and reassemble them with
flanged washers and neoprene snubbers as shown in
Fig. 1. Flanged washers and neoprene snubbers are
shipped in a cloth bag tied to compressor. Tighten
all 4 bolts. Then, loosen each until the flanged
washer can be moved sidewise. Check compressor
to see that it floats freely on its mounting springs.»
PIPING CONNECTIONS
Attach water supply and return line to con
nections indicated on condensing unit (Fig. 3).
Water leaving condenser should not be connected
directly into sewer lines; check local codes.
Attach refrigerant liquid and suction lines to
condensing unit (Fig 3),suction and discharge lines
to compressor unit (Fig. 2) Discharge line muffler
and check valve are factory supplied with 06E com
pressor units Install the muffler as close to shutoff
valve as possible and install the check valve in the
discharge line close to the muffler, on the down
stream side. When soldering or brazing piping to
valves, disassemble the valve or wrap it in wet cloth
to prevent damage by heat Allow flexibility in
Table 1 — Physical Data
COMPRESSOR UNIT 06E
1V022JW027
1 6ÔÔ i 640
CONDENSING UNIT 07E
OPERATING WEIGHT (Tb)
REFRIGERANT
COMPRESSOR 66E (06EV,EW)
(07EA,EB,ED):Di50i N265 i N i /5 i N299
Oil Charge, PP33-2(pt) 14 | i9 1 19 I 19
Normal Oil Pressure*
Oil Safety SwitchCut-in
High-Pressure Switch
Cutout Range
A022 :3027 ;B033Jp044_
l235{TM0'[T356JT56b '
D2.50 Ie265 Ie275 Ie?99^
Cutout
2 to 5 psi below cut-
300 to 400 psigt
W033
''650^^
R-22, R-502'
13 to 18 psig
9 to 13 psig
W044
320 pspt,
Differential (cutout,
Factory Settings!
cut-in)
Cutout
95 ± 1 5 psi ifixed)
335 ± 6 psig
260 i 6 psig
Cut-In
Low-Pressure Switch
Cutout Range
Differential (cutout, cut-in)
Factory Settings!Cutout
Low-Side Max Pressure
CONDENSER 69RE
Refrigerant 22
Max Storage Capacity (lb)**
Min Operating Charge (lb)
Max Operating Pressure
Refrig erant Side
Water Side
. 07E Condensing Unit Data
'Listed pressuies are above operating suction pressure (pressure
diffeieniial between suction and discharge pressures of oil
pump)
fAdjustable, but only by authorized personnel and with special
tool
:j Listed settings for R-22 For other refrigerants, reset to
pressures corresponding to saturation temperatures indicated by
the listed pressures
**Condenser 80% filled with liquid refrigerant at 104 F
L ODF
SUCTION VALVE
(MAY BE ROTATED 360°
AT 90° INTERVALS)
*1 nstall pressure relief device in discharge line
Pressure relief setting is 465 psig
tOverall width includes projection of fuse
holders
M ODF*
DISCHARGE VALVE
(MAY BE ROTATED 180°
'A~
OVERALL
LENGTH
(INCLUDES
CONTROL BOX
OVERHANG)
DIAM KNOCKOUT
DIAM-4 HOLES
06E Hermetic Compressor Unit Dimensions
UNIT 06E
mMENMONS A
CONNECT Tons On ) u
M
V022
3-1 1 %
IV«
2-31| OVERALL HEIGHT
W027
3-1IV«
iVa“'
IV,
4~VVu
2v; '
iVa
JW0j44_
" 2Va ”■
1 Vs
Fig. 2 —06E Hermetic Compressor Units
UNIT 07E
DIMENSIONS (fi
Overall Width
Certified dimension drawings available on request.
HR
A022
A
6- 56- 56- 5
C2-1 IV3- 0
l-nVs
§027
1 -1 1V1-1IV
07E Water-Cooled Condensing Unit Dimensions
§033
0044 _UNJT 07E^
6-7V CONNECTIONS (ii
2-1 1V2
3-2 Vs
2-3 Vs
Fig. 3 — 07E Water-Cooled Condensing Units
A022
KiVsIVs
LiVsIV«
U
2V
B027B033
2V2V
0044
2Vs
2Vs
IVsiVs
3
Table 2 — Electrical Data (60-Hertz, 3-Phase)
(Circuit Breakers Selected for Units Using R-22)
VOLTS
UNIT
Compr
06 EW033
Cond
07 EB033
VOLTS
UNIT
Compr
06 E
CondB027
07 E
KW — Maximum Power Input
LRA — Locked Rotor Amps
MTA — Must Trip Amps
MWA — Minimum Wire Amps Complies with NEC Section
RLA — Rated Load Amps
Supply Range — Units are suitable for use on electrical systems
NOTES:
1 Control voltage is 115 v for all units
Nomina 1
Supply Range
KW
V022
W027
W044
A022
B027
D044
Nominal
Supply Range
V02224.836
W027
W033
W044
A02222.632
B03334.04820566
D044
24.8
33.6103
37.6
55.1
22.6
31.4
34.0
50.4
KWRLALRA
33.6
37.6
55.176
31.443205
50.4
430-22
where voltage supplied to the unit terminals is
not below or above the listed range limits
RLA
g2
1 14
164
72283
96
107471150
159690222
45
51
70300
LRA
345
471144129
506160
690
471134120200
150
2056356100
22071
300
12345
200
180-229
MTA
114
230
100
460575 (See Note 5)
414-528
MTA
106
MWAFUSE
102
143
206350
90
134
198350140
MWA
50
60
9888
45
64
95
407027
5490
601003916454
MÀX
AMPS
175
225
250
150
22596
MAXMAX
FUSE
AMPS
80
no
15060240
1506024084
2 Part-winding start all 200-, 230-volt 06E and 07E units; 460-,
575-volt 06EW044 and 07ED044 units
Across-the-line start: all 460-, 575-volt units except 06EW044
and 07ED044.
3. Factory wiring is in compliance with National Electrical Code
(NEC) Field wiring must comply with NEC and applicable
local codes Maximum incoming wire size to control center
terminal block is 250 MCM
4 The 06E compressor unit electrical data shown in the table
does not apply to 06E compressors used as an integral part of
other Carrier equipment Refer to the electrical data for the
particular application
-> 5 Units for use on 575 volts are available on special order
RLA
75
92
103440144
150600
63
85410118106
RLA
29120403760
36164504580
42
33
LRAMTAMWA
300
410
r 246
410
600
LRAMTAMWA
176
98
164
230
207-264
104
128115
210
88
134
196
518-660
585390
8475
3734
45
129225
188
120
175
MAX
FUSE
AMPS
94
79125
42
48
75
150
200
300
175
200
300
FUSE
AMPS
125
60
70
80
125
(Continued from page 1.)
suction line so compressor suction valve may be
moved aside for access to suction strainer.
A solenoid valve is necessary for single pump
out control used on 06E and 07E units. Install the
valve (field supplied) in the liquid line, just before
the expansion valve. A filter-drier of adequate size
should be installed in liquid line between con
denser and solenoid valve.
Pressure relief valve located on side of con
denser will open to relieve excessive pressure,
allowing refrigerant to escape. Most local codes
require piping from valve to outdoors.
Refer to Carrier System Design Manual for
standard piping techniques.
ELECTRICAL REQUIREMENTS
Eield wiring must comply with local and
national codes. See Table 2.
Install a branch circuit fused disconnect of
adequate size to handle starting current. The
disconnect must be within sight of the unit and
readily accessible, in compliance with National
Electrical Code (NEC), Section 440—14.
Line power is brought into control center thru
indicated opening. Connect line power supply to
terminal block TB1; connect power leads to
terminals LI, L2 and L3. Connect control circuit
power supply (115 volts) to terminals 1 and 15 on
terminal block TB2. Refer to Eig. 4.
Wiring connections for field-supplied equip
ment are shown on diagram attached to unit (or in
wiring diagram booklet).
Discharge line limit thermostat supplied with
06EV,W compressor units is installed on discharge
line as close to compressor as possible.
1. Place mounting plate on discharge line and
solder in place.
Easten the thermostat to plate with screws
2.
supplied.
Cover switch with insulation and secure insula
3.
tion at each end with straps.
Connect thermostat in series with Ml and M2
4.
overloads, between terminals 2 and 4 on termi
nal block TB2.
ACCESSORIES
PACKAGE NUMBER
07EA900021
07EA900061
DESCRIPTION
Control Circuit Transformer
Gage Panel
1276
REFRIGERANT CHARGING
Evacuate, Dehydrate and Leak Test the entire
refrigerant system by methods described in Carrier
Standard Service Techniques Manual, Chapter 1,
Sections 1-6 and 1-7. Use sight glass method to
charge system. See Section 1-8 of Service Tech
niques Manual for details.
CHARGE THE SYSTEM to a clear sight glass while
holding saturated condensing pressure constant at
125 F (air-cooled systems) or 105 F (water-cooled
systems) Add additional refrigerant to fill con
denser subcooler coils.
07E Condensing Units - After clear sight glass is
obtained, add charge until liquid refrigerant
reaches condenser liquid level test cock.
06E Compressor Units — See condenser data for
additional charge required to fill subcooler.
All Units — Stamp type of refrigerant and amount
of charge on unit informative plate
INITIAL START-UP
Crankcase heater should be energized a mini
mum of 24 hours before starting unit.
Check to see that oil level is approximately 1/3
up on the compressor sight glass.
Open water supply valve and allow water to
reach condenser. (Turn condenser fan on when the
compressor unit is applied with air-cooled con
denser.)
Backseat the compressor suction and discharge
shutoff valves, open liquid line valve at receiver.
Start evaporator fan or chilled water pump.
Start Compressor — Push the control circuit
START-STOP-RESET switch to “Start.” The timer
motor starts immediately. Depending on the posi
tion of the timer, the compressor start is delayed
for 12 seconds to approximately 8 minutes. Check
oil pressure after compressor has run a few
minutes, the pressure should be 12—18 psi above
the suction pressure After about 20 minutes of
operation, stop the compressor. Allow it to be idle
for about 5 minutes, then observe the oil level in
the sight glass. If the oil level is below the bottom
of the sight glass, refer to the Carrier Standard
Service Techniques Manual, Chapter 1, Section
1-11, for adding oil. The proper oil level for the
06E compressor is approximately 1/3 up on sight
glass.
là
CONTROL POWER TERMINAL STRIP (TBg)
GROUND SCREW
START-STOP-RESET
SWITCH
CONTROL CIRCUIT
FUSE(S)
(2 ON 50-Hz UNITS)
CONTROL RELAYS
SENSOR MODULE
(SOLID STATE
COMPRESSOR MOTOR
PROTECTION)
HIGH PRESSURE
SWITCH
LOW PRESSURE
SWITCH
TIMER MOTOR
(4-FUNCTION TIMER)
MAIN POWER
INLET,
MAIN POWER
TERMINAL
BLOCK (TB|)
EQUIPMENT GROUND
'connection
COMPRESSOR
CONTACTOR
OUTLET FOR
WIRING TO
COMPRESSOR
06E
07E
OIL PRESSURE
SAFETY SWITCH
1276
ACCESSORY TRANSFORMER
(60-Hz UNITS ONLY)
MAIN POWER
CIRCUIT BREAKER
Fig. 4 — Control Center — 06E and 07E
4
COMPRESSOR
CONTACTOR
(PART-WIND)
Timer Functions (See Fig. 5 — Tinier Cycle)
1. Switch A (contacts A-Al and A-A2) provides
Time Guard® function. Start of compressor is
delayed approximately 5.5 minutes after shut
off. The minimum time between starts of
compressor is 8 minutes.
2. Switch B (contacts B1 and B—B2) starts
compressor and de-energizes the crankcase
heater. These contacts also provide one-second
time delay for part-winding start.
3. Switch E (contacts E—El) provides approxi
mately 40-second bypass of oil-pressure switch
(OPS) at start-up. Compressor will shut off if
sufficient oil pressure does not build up.
4. Switch D (contacts D—Dl) bypasses the lowpressure switch (EPS) for 2.5 minutes at start
up for winter start control.
(BLACK DENOTES CLOSED CONTACTS)
0 MIN OR
8 MIN
»TT?*
-'E-El-
-xA-
High-Pressure Switch — Check by throttling con
40 SEC +5
2-6 SEC
---
150 SEC
Fig. 5 — Timer Cycle
PROTECTION DEVICES
TIMER POSITION DURING
UNIT OPERATION-
denser water or blocking air flow on air-cooled
units, allowing head pressure to rise gradually.
Check discharge pressure constantly throughout
procedure. Compressor should shut off within 10
psi of values shown in Table 1.
Low-Pressure Switch — Check by slowly closing
suction shutoff valve or by completely closing
liquid line shutoff valve. A decrease of suction
pressure will follow. Compressor should shut off
within 4 psi of values shown in Table 1.
Oil Pressure Switch (OPS) protects against damage
from loss of oil and failure of pressure buildup
during start-up. Switch time delay (approximately
35 seconds) is derived from being properly wired
to the ambient and voltage insensitive Time Guard
timer. If OPS locks out unit, det e rm ine an d c o r r e c t
th e c a u s e (such as loss of compressor oil or flooded
compressor) be f o r e r e s ta r t in g uni t Restart by
pushing the control circuit switch on unit control
box to “Stop” then to “Reset.” Failure to correct
the cause of the OPS lockout will constitute abuse.
Eq ui p m e n t f a il u r e d u e to a b u s e i s n o t c o v e re d by
th e Warr a n t y .
Time Guard Control protects compressor against
short cycling. See Start Compressor.
Crankcase Heater prevents absorption of liquid
refrigerant by oil in crankcase during brief or
extended shutdown periods. Source of 115-volt
power is the auxiliary control power, independent
of the main unit power. This assures compressor
protection even when main unit power disconnect
switch is off.
N ev e r o p e n any s w it c h o r d i sc o n ne c t t h a t w i ll
de - e n e rg i z e th e c r a n k c a s e h e a te r u n l e ss u n i t i s
be i n g se r v ic e d or is to be s h u t d o w n fo r a
pr o lo ng e d pe r io d Af te r a p r o l o n g e d s h u t d o w n or a
se r vi c e jo b , en e r g iz e th e cr a n k c a se he a t e r f o r 2 4
ho u r s b e f o r e s ta r t ing th e co m pre s s o r .
Compressor Motor Protection consists of 3 tem
perature sensors embedded in motor windings and
connected to a solid state module in unit control
box.
When an overtemperature condition causes
module to shut compressor off, push control circuit
STOP switch. Investigate cause of compressor shut
down and correct. After compressor cools, push
control circuit START-RESET switch. Compressor
will restart after Time Guard delay period.
SOLID STATE MODULE is checked by applying
unit control voltage to terminals T1 and T2 (see
label diagram), then checking for continuity across
terminals Ml and M2. If no continuity between Ml
and M2, check temperature sensor resistance using
a volt-ohmmeter. If all sensors check below 95
ohms (180 F) and there is no continuity between
module terminals Ml and M2, replace module.
CAUTI O N: D o no t u s e a ba t te r y p o w e r ed t e s t
la m p t o ch e c k s e n so r s E x c e s si v e cu r r e n t ca n
ca u s e d a ma g e
If one sensor fails, it can be jumpered out of
the circuit with a 75 ohm, or higher, resistor (rated
at 2 watts or higher) across the proper sensor
terminal and common terminal. If a short to
ground in sensor circuit is indicated, replace
compressor motor.
CAPACITY CONTROL SYSTEM
Capacity Control Valve(s) is controlled by suction
pressure and actuated by discharge pressure. Each
valve controls 2 cylinders. On start-up, controlled
cylinders do not load up until differential between
suction and discharge pressure is 10 psi (see Fig. 6).
D o no t us e au t o m a t i c p u m p d o wn c o n tr o l on
06 E , 0 7 E u n i ts e q u i p p ed wi th u n l o a d e r va l v e s . U s e
sing l e p u m p o u t o r s o le n o i d d r o p (mi n im um p r o
te ct i o n ) c o n tr o l
Capacity Control Valve Adjustments
CONTROL SET POINT (cylinder load point) is
adjustable from 0 psig to 85 psig. Pressure differ
ential between cylinder load-up point and cylinder
unload point is adjustable from 6 psi to 22 psi.
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.