Carrier 06E User Manual

Compressors and Condensing Units
Hermetic, Water-Cooled

PRELIMINARY CHECKS

Inspect shipment for damage. File claim with the shipping company if shipment is damaged or parts are missing.
Local water conditions can cause excessive fouling or pitting of condenser tubes. If such conditions are anticipated, a water treatment analysis is recommended. Refer to Carrier System Design Manual, Part 5, for general water condi tioning information.

PLACING THE UNIT

Locate unit on floor in a well ventilated area. Install unit where it will be warmer than condi tioned area. Position it to allow sufficient space for refrigerant and water connections and to seiwice compressor. Allow space at one end of condenser
for tube cleaning or replacement. Place unit so suction and discharge valves can be easily reached and so oil level can be checked.
Make provision in piping layout to drain and vent condenser if system is to be shut down in
winter.
Level unit and bolt it firmly to foundation.
COMPRESSOR
Remove 4 self-locking bolts from compressor
mounting springs, and reassemble them with
flanged washers and neoprene snubbers as shown in Fig. 1. Flanged washers and neoprene snubbers are shipped in a cloth bag tied to compressor. Tighten
all 4 bolts. Then, loosen each until the flanged washer can be moved sidewise. Check compressor
to see that it floats freely on its mounting springs.»

PIPING CONNECTIONS

Attach water supply and return line to con nections indicated on condensing unit (Fig. 3). Water leaving condenser should not be connected
directly into sewer lines; check local codes.
Attach refrigerant liquid and suction lines to
condensing unit (Fig 3),suction and discharge lines
to compressor unit (Fig. 2) Discharge line muffler
and check valve are factory supplied with 06E com pressor units Install the muffler as close to shutoff valve as possible and install the check valve in the
discharge line close to the muffler, on the down
stream side. When soldering or brazing piping to valves, disassemble the valve or wrap it in wet cloth
to prevent damage by heat Allow flexibility in

Table 1 — Physical Data

COMPRESSOR UNIT 06E
1V022JW027
1 6ÔÔ i 640
CONDENSING UNIT 07E OPERATING WEIGHT (Tb) REFRIGERANT COMPRESSOR 66E (06EV,EW)
(07EA,EB,ED):Di50i N265 i N i /5 i N299
Oil Charge, PP33-2(pt) 14 | i9 1 19 I 19 Normal Oil Pressure* Oil Safety Switch Cut-in
High-Pressure Switch
Cutout Range
A022 :3027 ;B033Jp044_
l235{TM0'[T356JT56b '
D2.50 Ie265 Ie275 Ie?99^
Cutout
2 to 5 psi below cut-
300 to 400 psigt
W033
''650^^
R-22, R-502'
13 to 18 psig
9 to 13 psig
W044
320 pspt,
Differential (cutout,
Factory Settings!
cut-in)
Cutout
95 ± 1 5 psi ifixed)
335 ± 6 psig
260 i 6 psig
Cut-In
Low-Pressure Switch
Cutout Range Differential (cutout, cut-in) Factory Settings! Cutout
Low-Side Max Pressure
CONDENSER 69RE
Refrigerant 22
Max Storage Capacity (lb)** Min Operating Charge (lb)
Max Operating Pressure
Refrig erant Side Water Side
. 07E Condensing Unit Data
'Listed pressuies are above operating suction pressure (pressure
diffeieniial between suction and discharge pressures of oil pump)
fAdjustable, but only by authorized personnel and with special
tool
:j Listed settings for R-22 For other refrigerants, reset to
pressures corresponding to saturation temperatures indicated by the listed pressures
**Condenser 80% filled with liquid refrigerant at 104 F
Cut-in
240 t 7 ps:<3
175 3 7'ps>3‘ ■■■
5 to 1 00 psig (adj )
22 ± 8 psi (fixed)
24+4 psig
66 ± 4 psig 245 psig
022
3G
027
139 f
“j'y i
385 PC.Î9
250 psig
043
Î95
Fig. 1 — Compressor Mounting
670
37
© Carrier Corporation 1975
1276
Form 06E, 07E-5SI
L ODF SUCTION VALVE (MAY BE ROTATED 360° AT 90° INTERVALS)
*1 nstall pressure relief device in discharge line
Pressure relief setting is 465 psig
tOverall width includes projection of fuse
holders
M ODF* DISCHARGE VALVE (MAY BE ROTATED 180°
'A~
OVERALL LENGTH (INCLUDES CONTROL BOX OVERHANG)
DIAM KNOCKOUT
DIAM-4 HOLES
06E Hermetic Compressor Unit Dimensions
UNIT 06E mMENMONS A CONNECT Tons On ) u
M
V022
3-1 1 %
IV«
2-31| OVERALL HEIGHT
W027
3-1IV«
iVa“' IV,
4~VVu
2v; '
iVa
JW0j44_
" 2Va ”■
1 Vs
Fig. 2 —06E Hermetic Compressor Units
UNIT 07E DIMENSIONS (fi
Overall Width
Certified dimension drawings available on request.
HR
A022
A
6- 5 6- 5 6- 5
C 2-1 IV 3- 0
l-nVs
§027
1 -1 1V 1-1IV
07E Water-Cooled Condensing Unit Dimensions
§033
0044 _UNJT 07E^
6-7V CONNECTIONS (ii
2-1 1V2
3-2 Vs 2-3 Vs

Fig. 3 — 07E Water-Cooled Condensing Units

A022
K iVs IVs L iVs IV« U
2V
B027 B033
2V 2V
0044
2Vs
2Vs
IVs iVs
3
Table 2 — Electrical Data (60-Hertz, 3-Phase)
(Circuit Breakers Selected for Units Using R-22)
VOLTS
UNIT
Compr
06 E W033
Cond
07 E B033
VOLTS
UNIT
Compr
06 E
Cond B027
07 E
KW — Maximum Power Input
LRA — Locked Rotor Amps MTA — Must Trip Amps MWA — Minimum Wire Amps Complies with NEC Section
RLA — Rated Load Amps Supply Range — Units are suitable for use on electrical systems
NOTES: 1 Control voltage is 115 v for all units
Nomina 1
Supply Range
KW
V022 W027
W044
A022 B027
D044 Nominal Supply Range
V022 24.8 36 W027 W033 W044
A022 22.6 32
B033 34.0 48 205 66
D044
24.8
33.6 103
37.6
55.1
22.6
31.4
34.0
50.4
KW RLA LRA
33.6
37.6
55.1 76
31.4 43 205
50.4
430-22
where voltage supplied to the unit terminals is not below or above the listed range limits
RLA
g2
1 14
164
72 283
96 107 471 150 159 690 222
45
51
70 300
LRA
345 471 144 129 506 160 690
471 134 120 200
150 205 63 56 100 220 71 300
123 45
200
180-229
MTA
114
230 100
460 575 (See Note 5)
414-528
MTA
106
MWA FUSE
102 143
206 350
90
134 198 350 140
MWA
50
60 98 88
45 64
95 40 70 27
54 90 60 100 39 164 54
MÀX
AMPS
175 225 250
150 225 96
MAX MAX FUSE
AMPS
80
no
150 60 240
150 60 240 84
2 Part-winding start all 200-, 230-volt 06E and 07E units; 460-,
575-volt 06EW044 and 07ED044 units Across-the-line start: all 460-, 575-volt units except 06EW044
and 07ED044.
3. Factory wiring is in compliance with National Electrical Code (NEC) Field wiring must comply with NEC and applicable local codes Maximum incoming wire size to control center terminal block is 250 MCM
4 The 06E compressor unit electrical data shown in the table
does not apply to 06E compressors used as an integral part of other Carrier equipment Refer to the electrical data for the particular application
-> 5 Units for use on 575 volts are available on special order
RLA
75
92 103 440 144 150 600
63
85 410 118 106
RLA
29 120 40 37 60 36 164 50 45 80 42
33
LRA MTA MWA
300 410
r 246
410 600
LRA MTA MWA
176
98
164
230
207-264
104
128 115 210
88
134 196
518-660
58 53 90 84 75
37 34 45
129 225 188
120 175
MAX FUSE AMPS
94
79 125
42
48 75
150 200
300
175 200 300
FUSE AMPS
125
60 70 80
125
(Continued from page 1.)
suction line so compressor suction valve may be moved aside for access to suction strainer.
A solenoid valve is necessary for single pump
out control used on 06E and 07E units. Install the
valve (field supplied) in the liquid line, just before
the expansion valve. A filter-drier of adequate size should be installed in liquid line between con denser and solenoid valve.
Pressure relief valve located on side of con denser will open to relieve excessive pressure, allowing refrigerant to escape. Most local codes require piping from valve to outdoors.
Refer to Carrier System Design Manual for
standard piping techniques.

ELECTRICAL REQUIREMENTS

Eield wiring must comply with local and
national codes. See Table 2.
Install a branch circuit fused disconnect of adequate size to handle starting current. The disconnect must be within sight of the unit and readily accessible, in compliance with National Electrical Code (NEC), Section 440—14.
Line power is brought into control center thru indicated opening. Connect line power supply to
terminal block TB1; connect power leads to terminals LI, L2 and L3. Connect control circuit power supply (115 volts) to terminals 1 and 15 on terminal block TB2. Refer to Eig. 4.
Wiring connections for field-supplied equip ment are shown on diagram attached to unit (or in wiring diagram booklet).
Discharge line limit thermostat supplied with
06EV,W compressor units is installed on discharge
line as close to compressor as possible.
1. Place mounting plate on discharge line and solder in place.
Easten the thermostat to plate with screws
2.
supplied. Cover switch with insulation and secure insula
3. tion at each end with straps.
Connect thermostat in series with Ml and M2
4. overloads, between terminals 2 and 4 on termi nal block TB2.

ACCESSORIES

PACKAGE NUMBER
07EA900021 07EA900061
DESCRIPTION
Control Circuit Transformer Gage Panel
1276
REFRIGERANT CHARGING
Evacuate, Dehydrate and Leak Test the entire
refrigerant system by methods described in Carrier Standard Service Techniques Manual, Chapter 1, Sections 1-6 and 1-7. Use sight glass method to charge system. See Section 1-8 of Service Tech niques Manual for details.
CHARGE THE SYSTEM to a clear sight glass while holding saturated condensing pressure constant at
125 F (air-cooled systems) or 105 F (water-cooled systems) Add additional refrigerant to fill con denser subcooler coils.
07E Condensing Units - After clear sight glass is obtained, add charge until liquid refrigerant reaches condenser liquid level test cock.
06E Compressor Units — See condenser data for additional charge required to fill subcooler.
All Units — Stamp type of refrigerant and amount
of charge on unit informative plate

INITIAL START-UP

Crankcase heater should be energized a mini
mum of 24 hours before starting unit.
Check to see that oil level is approximately 1/3
up on the compressor sight glass.
Open water supply valve and allow water to reach condenser. (Turn condenser fan on when the compressor unit is applied with air-cooled con denser.)
Backseat the compressor suction and discharge shutoff valves, open liquid line valve at receiver.
Start evaporator fan or chilled water pump.
Start Compressor — Push the control circuit
START-STOP-RESET switch to “Start.” The timer motor starts immediately. Depending on the posi tion of the timer, the compressor start is delayed for 12 seconds to approximately 8 minutes. Check oil pressure after compressor has run a few minutes, the pressure should be 12—18 psi above the suction pressure After about 20 minutes of operation, stop the compressor. Allow it to be idle for about 5 minutes, then observe the oil level in the sight glass. If the oil level is below the bottom of the sight glass, refer to the Carrier Standard Service Techniques Manual, Chapter 1, Section
1-11, for adding oil. The proper oil level for the 06E compressor is approximately 1/3 up on sight glass.
CONTROL POWER TERMINAL STRIP (TBg)
GROUND SCREW
START-STOP-RESET SWITCH
CONTROL CIRCUIT FUSE(S)
(2 ON 50-Hz UNITS)
CONTROL RELAYS SENSOR MODULE
(SOLID STATE COMPRESSOR MOTOR
PROTECTION)
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
TIMER MOTOR (4-FUNCTION TIMER)
MAIN POWER INLET,
MAIN POWER TERMINAL BLOCK (TB|)
EQUIPMENT GROUND
'connection
COMPRESSOR CONTACTOR
OUTLET FOR WIRING TO COMPRESSOR 06E
07E
OIL PRESSURE SAFETY SWITCH
1276
ACCESSORY TRANSFORMER (60-Hz UNITS ONLY)
MAIN POWER CIRCUIT BREAKER
Fig. 4 — Control Center — 06E and 07E
4
COMPRESSOR CONTACTOR (PART-WIND)
Timer Functions (See Fig. 5 — Tinier Cycle)
1. Switch A (contacts A-Al and A-A2) provides Time Guard® function. Start of compressor is
delayed approximately 5.5 minutes after shut off. The minimum time between starts of compressor is 8 minutes.
2. Switch B (contacts B1 and B—B2) starts compressor and de-energizes the crankcase
heater. These contacts also provide one-second
time delay for part-winding start.
3. Switch E (contacts E—El) provides approxi
mately 40-second bypass of oil-pressure switch (OPS) at start-up. Compressor will shut off if sufficient oil pressure does not build up.
4. Switch D (contacts D—Dl) bypasses the low­pressure switch (EPS) for 2.5 minutes at start up for winter start control.
(BLACK DENOTES CLOSED CONTACTS)
0 MIN OR
8 MIN
»TT?*
-'E-El-
-xA-
High-Pressure Switch — Check by throttling con
40 SEC +5
2-6 SEC
---
150 SEC
Fig. 5 — Timer Cycle
PROTECTION DEVICES
TIMER POSITION DURING
UNIT OPERATION-
denser water or blocking air flow on air-cooled units, allowing head pressure to rise gradually. Check discharge pressure constantly throughout procedure. Compressor should shut off within 10 psi of values shown in Table 1.
Low-Pressure Switch — Check by slowly closing
suction shutoff valve or by completely closing liquid line shutoff valve. A decrease of suction pressure will follow. Compressor should shut off within 4 psi of values shown in Table 1.
Oil Pressure Switch (OPS) protects against damage
from loss of oil and failure of pressure buildup during start-up. Switch time delay (approximately 35 seconds) is derived from being properly wired to the ambient and voltage insensitive Time Guard timer. If OPS locks out unit, det e rm ine an d c o r r e c t
th e c a u s e (such as loss of compressor oil or flooded
compressor) be f o r e r e s ta r t in g uni t Restart by pushing the control circuit switch on unit control box to “Stop” then to “Reset.” Failure to correct
the cause of the OPS lockout will constitute abuse.
Eq ui p m e n t f a il u r e d u e to a b u s e i s n o t c o v e re d by th e Warr a n t y .
Time Guard Control protects compressor against
short cycling. See Start Compressor.
Crankcase Heater prevents absorption of liquid
refrigerant by oil in crankcase during brief or extended shutdown periods. Source of 115-volt power is the auxiliary control power, independent of the main unit power. This assures compressor protection even when main unit power disconnect switch is off.
N ev e r o p e n any s w it c h o r d i sc o n ne c t t h a t w i ll de - e n e rg i z e th e c r a n k c a s e h e a te r u n l e ss u n i t i s be i n g se r v ic e d or is to be s h u t d o w n fo r a
pr o lo ng e d pe r io d Af te r a p r o l o n g e d s h u t d o w n or a se r vi c e jo b , en e r g iz e th e cr a n k c a se he a t e r f o r 2 4 ho u r s b e f o r e s ta r t ing th e co m pre s s o r .
Compressor Motor Protection consists of 3 tem
perature sensors embedded in motor windings and connected to a solid state module in unit control box.
When an overtemperature condition causes module to shut compressor off, push control circuit STOP switch. Investigate cause of compressor shut down and correct. After compressor cools, push control circuit START-RESET switch. Compressor will restart after Time Guard delay period.
SOLID STATE MODULE is checked by applying unit control voltage to terminals T1 and T2 (see label diagram), then checking for continuity across terminals Ml and M2. If no continuity between Ml and M2, check temperature sensor resistance using a volt-ohmmeter. If all sensors check below 95 ohms (180 F) and there is no continuity between module terminals Ml and M2, replace module.
CAUTI O N: D o no t u s e a ba t te r y p o w e r ed t e s t la m p t o ch e c k s e n so r s E x c e s si v e cu r r e n t ca n ca u s e d a ma g e
If one sensor fails, it can be jumpered out of the circuit with a 75 ohm, or higher, resistor (rated at 2 watts or higher) across the proper sensor terminal and common terminal. If a short to ground in sensor circuit is indicated, replace
compressor motor.

CAPACITY CONTROL SYSTEM

Capacity Control Valve(s) is controlled by suction
pressure and actuated by discharge pressure. Each
valve controls 2 cylinders. On start-up, controlled
cylinders do not load up until differential between suction and discharge pressure is 10 psi (see Fig. 6).
D o no t us e au t o m a t i c p u m p d o wn c o n tr o l on
06 E , 0 7 E u n i ts e q u i p p ed wi th u n l o a d e r va l v e s . U s e
sing l e p u m p o u t o r s o le n o i d d r o p (mi n im um p r o 
te ct i o n ) c o n tr o l

Capacity Control Valve Adjustments

CONTROL SET POINT (cylinder load point) is
adjustable from 0 psig to 85 psig. Pressure differ ential between cylinder load-up point and cylinder
unload point is adjustable from 6 psi to 22 psi.
Loading...
+ 11 hidden pages