damage. File claim with the shipping company if shipment is
damaged or parts are missing.
Local water conditions can cause excessive fouling or
pitting of condenser tubes. If such conditions are anticipated, a
water treatment analysis is recommended. Refer to Carrier
System Design Manual, Part 5, for general water conditioning
information.
Place Unit in Position —
well-ventilate d area. Instal l unit where i t will be war mer than
conditioned area. Position it to allow sufficient space for refrigerant and water connections and to service compressor. Allow
space at one end of condenser for tube cleaning or replacement.
Place unit so suction and discharge valves can be easily
reached and so oil level can be checked.
Make provision in piping layout to drain and vent condenser
if system is to be shut down in winter.
Level unit and bolt firmly to foundation.
Check Compressor Mounting —
sor mounting bolts and remove shipping blocks from under
compressor. Ti ghten all 4 bolts on compressor. Loosen each
bolt just enough until the flanged washer can be moved
sideways with finger pressure. See Fig. 1.
NOTE: Be sure that compressor floats freely on mounting
springs.
Inspect shipment for
Locate unit on floor in a
Loosen compres-
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be
hazardous due to system pressures, electrical components, and
equipment location (roofs, elevated structures, etc.). Only
trained, qualified installers and service mechanics should
install, start up, and service this equipment.
When working on the equipment, observe precautions in the
literature, tag s, stickers and labels at tached to the equipment,
and other safety precautions that apply. Follow all safety codes.
Wear safety glasses and work gloves. Use care when handling,
rigging, and setting bulky equipment.
Electrical shock can cause personal injury and even death.
Be sure power to equipment is shut off before installing or
servicing this equipment. There may be more than one disconnect. Tag disconnect(s) to alert others not to turn power
on until work is completed.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2244
Tab 1b2a2b3a
PC 802Catalog No. 530-607Printed in U.S.A.Form 06/07E-2SIPg 17-02Replaces: 06/07E-1SI
Piping Connections —
lines to connections indicated on condensing unit (Fig. 2).
Wat er leaving condenser should not be conne cted di rectly into
sewer lines; check local codes.
Attach refrigerant liquid and suction lines to condensing
unit (Fig. 2); suction and discharge lines to compressor unit
(Fig. 3 and 4). Discharge line muffler and check valve are
factory supplied with 06E compressor units. Install the muffler
as close to shutoff valve as possible and install the check valve
in the discharge line close to the muffler, on the downstream
side. When soldering or brazing piping to valves, disassemble
the valve or wrap it in wet cloth to prevent damage by heat.
Allow flexibility in suction line so compressor suction valve
may be moved aside for access to suction strainer.
A solenoid valve is necessary for single pumpout control
used on 06E and 07E units. Install the valve (field supplied) in
the liquid line, just before expansion valve. A filter drier of
adequate size should be installed in liquid line between condenser and solenoid valve.
Pressure relief valve located on top of condenser will open
to relieve excessive pressure, allowing refrigerant to escape.
Most local codes require piping from valve to outdoors.
Refer to Carrier System Design Manual for standard piping
techniques.
Attach water supply and return
Electrical Connections
UNBALANCED 3-PHASE SUPPLY VOLTAGE — Never
operate a motor where a phase imbalance in supply voltage
is greater than 2%. Use the following formula to determine
Maximum deviation is 4 volts. Determine % voltage
imbalance:
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below
the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately. Allowing the unit to operate with a voltage
imbalance in excess of 2% may void the warranty.
POWER SUPPLY — Field wiring must comply with local
and national codes. See Table 1.
Install a branch circuit fused disconnect of adequate size to
handle starting current. The disconnect must be within sight
from the unit and readily accessible, in compliance with
National Electrical Code (NEC), Section 440-14.
Line power is brought into control center through indicated
opening. Connect line power supply to terminal block TB1;
connect power leads to terminals L1, L2 and L3. Connect
control circuit power supply (115 volts) to terminals 1 and 15
on terminal block TB2. Refer to Fig. 5.
Wiring connections for field-supplied equipment are shown
on wiring diagram. See Fig. 6.
ACCESSORIES — Field-installed accessories for the 06E
and 07E units are control circuit transformer and gage
panel (3 gages). Refer to accessory literature for installation
instructions.
243 + 236 + 238
717
=
3
=
239 volts
3
4
= 1.7%
239
2
8
16
16
16
16
/
5
5
9
16
/
9
9
121 5
2
/
1
3427
4
/
3
3
2
4
/
3
3
/
9
16
/
34261215
4
/
2
4
/
16
/
5
9
16
/
9
121 5
2
/
1
3427
4
/
3
2
4
/
3
/
5
5
9
16
/
9
9
121 5
2
/
1
3427
4
/
3
3
2
4
/
3
3
/
9
16
/
34261215
4
/
2
4
/
DIMENSIONS (in.)
5
9
3
3
16
/
9
16
/
34261215
4
/
2
4
/
/
5
5
8
8
/
1
1
121 4
2
/
1
1
3427
4
/
3
3
2
4
/
3
3
49
8
/
8
8
/
121 4
2
/
3427
4
/
2
4
/
49
2
2
/
/
1
1
208/2307849
208/2306649
460, 5756643
A022
UNIT 07EVOLTSABCDEFGHI
460, 5757843
B027
208/2307849
460, 5757843
B033
208/23069
460, 57569
D044
shooting and refrigerant charging, allow a minimum
1. For standard service practices, such as trouble-
NOTES:
clearance around the unit.
″
-6
′
2
removal is one condenser length at either end.
2. Recommended service space for condenser tube
wide
′
access aisle to and from the unit.
clearances.
3. For compressor removal, allow a minimum 3
4. Local codes or jurisdiction may prevail for unit
Fig. 2 — 07E Water-Cooled Condensing Units
3
NOTES:
1. For standard service practices, such as troubleshooting
and refrigerant charging, allow a minimum 2′-6″ clearance
around the unit.
2. For compressor removal, allow a minimum 3′ wide access
aisle to and from the unit.
3. Local codes or jurisdiction may prevail for unit clearances.
DIMENSIONS (in.)
06E UNITVOLTAGEABCDEFG
V022
W027
W033
W044
208/23048
460,575481/
208/23050
460,575501/
208/23050
460,575501/
208/23050
460,575501/
1
/
4
4
1
/
4
4
1
/
4
4
1
/
4
4
35367/
29367/
35367/
29367/
35367/
29367/
35367/
35367/
8
8
8
8
8
8
8
8
11/
11/
11/
11/
11/
11/
11/
11/
2
2
2
2
2
2
2
2
271/
2
119
261191/
271/
2
119
261191/
271/
2
119
261191/
271/
271/
2
2
119
119
Fig. 3 — 06E Hermetic Compressor Units
1
/
2
2
1
/
2
2
1
/
2
2
1
/
2
1
/
2
Fig. 4 — 06E Compressors
4
Table 1 — Electrical Data — Compressor Motor With Circuit Breaker
COMPRESSOR MOTOR DATACIRCUIT BREAKER
Compressor
Par t Num ber
06E*
250
265
A
275
299
LRA —
MHA —
MTA —
PW—
RLA —
XL—
*Refer to physical data table to match compressor with correct com-
pressor or water-cooled condensing unit.
NOTES:
1. Compressor MTA and RLA values are maximum figures.
2. LRA values for PW second winding =
3. 3-Pole XL circuit breakers shown, other 3-Pole XL alternates
and 6-Pole PW breakers available. Terminal lugs for circuit
breakers available in package 06EA660152 (not shown).
Locked Rotor Amps
Must Hold Amps
Must-Trip Amps
Part-Winding (Start)
Rated Load Amps
Across-the-Line (Start)
Maximum
Hp
Must Trip
Amps
108873452070.32HH83XB33691 104 35074.3
20
1401124462680.27HH83XC509110 127 42090.7
25
1681355063040.22HH83XC539142 163 507116.4
30
2361896904140.15HH83XC537187 215 636153.6
40
Maximum
RLA
1
/2 the LRA – XL value.
LRA-XL
LRA-PW
(first
winding)
Motor
Winding
Resistance
(Ohms)
4. Recommended RLA value shown is determined by: circuit
breaker must trip value ÷ 1.40. Use this recommended (and
minimum) RLA value to determine nameplate stamping, minimum contactor sizing, and wire sizing. RECOMMENDED RLA
FOR 06E COMPRESSORS EQUALS: MUST-TRIP (MTA) OF
CARLYLE APPROVED OVERCURRENT DEVICE BEING
USED ÷ 1.40
5. Compressor operating amps at any specific condition can only
be determined from a performance curve.
6. Ohm values for resistance are approximate and shown for reference purposes only. Motors from different vendors and
motors of different efficiencies can differ up to 15% from data
shown.
7. Electrical data for compressor part numbers 06ER, 06EM and
50 Hz models (not shown) are available from Carrier Sales
Representative.
Compressor Contactor
Compressor Contactor (PW)
Compressor Circuit Breaker
Crankcase Heater Relay
Control Relay
Fuse
Ground
High-Pressure Switch
Low-Pressure Switch
National Electrical Code
National Electrical
Manufacturer’s Association
Oil Pressure Switch
Pumpout Relay
Terminal Block
Time Delay Relay
Timer Motor
Timer Relay
Fig. 5 — Component Location
5
AUX —
C—
C1—
C2—
CH—
CHR —
CR—
DTS —
DX—
FU—
HPS —
LLS —
LPS —
Auxiliary
Compressor Contactor
Compressor Contactor
(XL start and first step of PW start)
Compressor Contactor
(PW second step)
Crankcase Heater
Crankcase Heater Relay
Control Relay
Discharge Temperature Sensor
Direct Expansion
Fuse
High-Pressure Switch
Liquid Line Solenoid Valve
Low-Pressure Switch
M1—
M2—
M3—
NEC —
OPS —
POR —
PW—
SW—
TB—
TDR —
TM—
TR—
XL—
LEGEND
Evaporator Fan or
Chilled Water Pump
Cooling Tower Pump
Cooling Tower Fan
National Electrical Code
Oil-Pressure Switch
Pumpout Relay
Par t Wind
Start-Stop-Reset Switch
Terminal Block
Time Delay Relay
Timer Motor
Timer Relay
Across-the-Line
Terminal Block Connector
Unmarked Terminal
Marked Terminal
Factory Wiring
Field Control Wiring
To indicate common potential only;
not to represent wiring.
Splice
NOTES:
1. Factory wiring is in compliance with NEC. Any field modifications
or additions must be in compliance with all applicable codes. Use
copper, copper-clad aluminum for field power supply only.
2. Field power supply wiring must be 75 C minimum.
3. Compressor thermally protected. Three-phase motors are protected against primary single-phasing condition.
4. Pilot duty control must be field supplied. Minimum contact rating
must be 25 va.
5. 60 Hz units have 120 volt control circuit. 50 Hz units have 230 volt
control circuit. A separate source of supply at the correct voltage
must be field supplied through a fused disconnect device with a
Fig. 6 — Control Circuit Wiring for 06E/07E Units
maximum rating of 15 A to TB2 connections (Hot Side)
and (Neutral).
6. Open control circuit disconnect switch for servicing only. Discon-
7. A transformer of the following rating may be field supplied for
8. Transformer must be fused and grounded per applicable codes.
9. If any of the original wiring furnished must be replaced, it must be
10. Wiring is shown for single pumpout control. Single pumpout
L2
nect must remain closed for crankcase heater to operate.
60 Hz units: 350 va.
replaced with 90 C wire or its equivalent.
control should not be used on direct-expansion (DX) cooler applications (see lower diagram for wiring when applied with DX
cooler).
L1
6
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.