Carrier 06D User Manual

Page 1
Compressors and Condensing Units
Installation, Start-Up and
Service Instructions
Hermetic, Water-Cooled
06D,07D
CONTENTS
SAFETY CONSIDERATIONS BEFORE INSTALLATION
Check Shipment Unit Location Considerations
INSTALLATION Mount Unit Piping Connections Electrical Connections Limitations Refrigerant Charging
INITIAL START-UP To St a rt C om p r es s o r
CHECKING OPERATION Oil Charge High-Pressure Switch Low-Pressure Switch Oil Pressure Switch Time Guard® Control
CAPACITY CONTROL Control Set Point To Regulate Control Set Point Pressure Differential Adjustment Capacity Control Pressure
CONDENSER MAINTENANCE SERVICE
Service Notes Testing Oil Pump Cylinder Heads Service Replacement Compressors Suction and Discharge Valve Plate Assembly Cleaning Suction Strainer Motor Replacement Terminal Plate Assembly Compressor Running Gear Removal Compressor Running Gear Replacement
COMPRESSOR MOTOR BURNOUT Clean-Up Procedure
TROUBLESHOOTING
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-17
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
. . . . . . . . . . . . . . . . . . . . . . . . . .18,19
. . . . . . . . . . . . . . . . . . . . . . 1
. . . . . . . . . . . . . . . . . . . . . . . . . 1
. . . . . . . . . . . . . . . . . . . . 1
. . . . . . . . . . . . . . . . . . . . . . . . . . . 4
. . . . . . . . . . . . . . . . . . . . . . . . .8,9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
. . . . . . . . . . . . . . . . . . . . . . . . . .9,10
. . . . . . . . . . . . . . . . . . . . 9
. . . . . . . . . . . . . . . . . 9
. . . . . . . . . . . . . . . . . . . . . . 10
. . . . . . . . . . . . . . . . .10,11
. . . . . . . . . . . . . 14
. . . 15
. . . . . . . . . . . . . . . . . . . . . . . 16
. . . . . . . . . . . . . . . . . . . . . . . . 16
. . . . . . . . . . . . 16
. . . . . . . . 17
. . . . . . . . . . . . . . 17
SAFETY CONSIDERATIONS
Installing, starting up and servicing this equipment can be hazardous due to system pressures, electrical components and equipment location (roofs, elevated structures, etc.). Only trained, qualified installers and service mechanics should install, start up and service this equipment.
When working on the equipment, observe precautions in the literature, tags, stickers and labels attached to t he equipment and any other safety precautions that apply. Follow all safety codes. Wear safety glasses and work gloves. Use care in handling, rigging and setting bulky equipment.
Electrical shock can cause persona l injury and even death. Be sure power to equipment is shut off before installing or servicing this equipment. There may be more than one disconnect. Tag disconnect(s) to alert others not to turn power on until work is completed.
BEFORE INSTALLATION
Check Shipment —
if shipment is damaged or incomplete.
Unit Location Considerations —
floor in a well-v entil ated ar ea. Pos itio n unit t o allow sufficien t space for refrigerant and water connections and to service compressor. Place unit so suction and discharge valves can be easily reached and oil level checked. Do not install condensing unit where temperature will fall below freezing.
Local water can cause excessive fouling or sealing of condenser tubes. If such conditions are anticipated, a water treatment analysis is recommended. Refer to Carrier System Design Manual, Part 5, for general water conditioning information.
Make provision in piping layout to drain and vent condenser if system is to be shut down in winter.
File claim with shipping company
Locate unit on
INSTALLATION
Mount Unit —
Loosen compressor mounting bolts and remove shipping blocks from under compressor. Tighten all 4 bolts on compres­sor. Next, loosen each bolt until the flanged washer can be moved sideways with finger pressure.
NOTE: Be sure that compressor floats freely on mounting springs.
Piping Connections —
lines to connections indicated on condenser unit (Fig. 1). Water leaving condenser should not be connected directly into sewer lines. Check local codes.
Attach refrigerant liquid and suction lines to condensing units (Fig. 1); suction and discharge to compressor unit (Fig. 2). When soldering or brazing piping to valves, disassem­ble valve or wrap it in a wet cloth to prevent heat damage. Allow flexibility in suction line so compressor suction valve may be moved aside for access to suction strainer.
Level unit and bolt firmly to foundation.
Attach water supply and return
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2244 Tab 1b2a2b3a
PC 802 Catalog No. 530-608 Printed in U.S.A. Form 06/07D-3SI Pg 1 802 7-02 Replaces: 06/07D-2SI
Page 2
DIMENSIONS (in.)
UNIT 07D WIDTH A
A203 B205 A208 B210 B212 B215
63
39 51 51
30 30
9
/
16
9
/
16
9
/
16
13
/
16
WATER CONNECTIONS FOR 07DB215 UNIT ONLY.
Fig. 1 — 07D Condensing Unit Dimensions
NOTES:
1. For standard service practices, such as trouble­shooting and refrigerant charging, allow a minimum 2′-6″ clearance around the unit.
2. Recommended service space for condenser tube removal is one condenser length at either end.
3. For compressor removal, allow a minimum 3′ wide access aisle to and from the unit.
4. Local codes or jurisdiction may prevail for unit clearances.
2
Page 3
NOTES:
1. For standard service practices, such as trouble­shooting and refrigerant charging, allow a minimum 2′-6″ clearance around the unit.
2. For compressor removal, allow a minimum 3′ wide access aisle to and from the unit.
3. Local codes or jurisdiction may prevail for unit clearances.
Fig. 2 — 06D Compressor Unit Dimensions
3
Page 4
Install a solenoid valve (field supplied) in liquid line directly before expansion valve. Solenoid valve is necessary for single pumpout control used on 06D, 07D units. Refrigerant filter drier and moisture indicator are shipped with 07D condensing units for field installation. Install in liquid line according to manufacturer’s instructions.
Relief valve located on top of condenser (07D units) will open to relieve excessive pressure, allowing refrigerant to escape. Most local codes require piping from safe ty device to outdoors.
Refer to Carrier System Design Manual, Part 3, for standard piping techniques.
COMPRESSOR UNITS — Connect high- and low-pressure switch capillary tubes from control box to compressor. See Fig. 2.
Install discharge line muffler (accessory) in discharge line as close to compressor shutoff valve as possible.
Electrical Connections
UNBALANCED 3-PHASE SUPPLY VOLTAGE — Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine
the % voltage imbalance: % Voltage Imbalance =
100 x
Example: Supply voltage is 230-3-60
A verage Voltage =
max voltage deviation from average voltage
average voltage
AB = 236 volts BC = 229 volts AC = 234 volts
236 + 229 + 234
3
= 233 volts
Determine maximum deviation from average voltage:
(AB) 236 – 233 = 3 volts (BC) 233 – 229 = 4 volts (AC) 234 – 233 = 1 volt
Maximum deviation is 4 volts. Determine % voltage imbalance:
% Voltage Imbalance =100 x
4
233
= 1.7%
This amount of phase imbalance is satisfactory as it is below the maximum allowable of 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
ELECTRICAL DATA NOTES
1. All 06D and 07D units are across-the-line start.
2. Wire sizes are based on TW type copper wire. Maximum wire lengths based on data from Table 1 will result in a 1% voltage drop to compressor. Where up to 3% voltage drop is allowed, the run length can be increased to 3 times the length calculated from data in Table 1.
3. The 06D compressor unit electrical data shown in Table 1 does not apply for 06D compressors used as an integral part of other Carrier equipment. See proper installation book for electrical information.
WIRI NG — Power supply must correspond with unit name­plate electrical characteristics (units are internally wired at factory for nameplate voltage). Field wiring must comply with local and national codes.
Install a branch circuit fused disconnect of adequate size to
handle starting current. LIN E POWER — Connect line power to the compressor con-
tactor C. For example, connect L1 to terminal 11, L2 to termi­nal 12 and L3 to terminal 13. See Fig. 3.
Table 1 — Compressor Electrical Data
COMPRESSOR
PART NUMBER
06D*
808
M
313
818
825
A
328
537
LEGEND
LRA — MCC — RLA —
*Refer to physical data table to match compressor with correct com-
pressor unit or water-cooled condensing unit.
NOTES:
1. RLA (rated load amps) value shown is: MCC ÷ 1.40 = RLA.
2. For minimum contactor sizing, use RLA value determined by:
Locked Rotor Amps Maximum Continuous Current Rated Load Amps
MCC ÷ 1.40 = RLA.
VO LTAGE
(3 Ph-60 Hz)
575
208/230 17.4 12.4 71 0.78
460 8.7 6.2 35.5 3.1 575
208/230 27 19.3 100 0.5
460 13.5 9.6 50 2.1 575
208/230 44 31.4 160 0.42
460 22 15.7 80 1.7 575
208/230 55.5 39.6 198 0.31
460 27.8 19.8 99 1.3 575
208/230 62 44.3 228 0.26
460 31 22.1 114 1.0 575
208/230 89 63.6 266 0.18
460 40 28.6 120 0.72
HP MCC RLA LRA
3
5
6.5
7.5
10
15
MOTOR WINDING
RESISTANCE
(Ohms)
7 5 28.4 5.0
10.8 7.7 40 3.3
17.6 12.6 64 2.6
22.2 15.9 79 2.0
25 17.9 91 1.7
32 22.9 96 1.2
3. For wiring sizing, the RLA value can be determined by: MCC
÷
1.56 = RLA.
4. Compressor operating amps at any specific conditions can only be determined from a performance curve.
5. RLA values for 06D compressor protected by a calibrated circuit breaker will depend on must-trip value of circuit breaker.
6. Ohm values shown for resistance are approximate and shown for reference only. Motors from different vendors and motors of different efficiencies can differ up to 15% from data shown.
7. Electrical data for compressor part numbers 06DR and 50 Hz models (not shown) are available from Carrier Sales Representative.
4
Page 5
AUX — C— CH — CR — DX — EQUIP — FU — GND — HPS — IP — LLS — LPS — M3 — NEC — OL — OPS — POR — SW
Auxiliary Compressor Contactor Crankcase Heater Control Relay Direct Expansion Equipment Fuse Ground High-Pressure Switch Internal Protector Liquid Line Solenoid Valve Low-Pressure Switch Cooling Tower Fan National Electrical Code Overload Oil-Pressure Switch Pumpout Relay Start-Stop-Reset Switch
LEGEND
TB — TM — TR
Terminal Block Timer Motor Timer Relay
Terminal Block Connector
Unmarked Terminal
Marked Terminal
Factory Wiring
Field Control Wiring To indicate common potential only;
not to represent wiring. Splice
NOTES:
1. Factory wiring is in compliance with NEC. Any field modifications or additions must be in compliance with all applicable codes. Use copper, copper-clad aluminum for field power supply only.
2. Field power supply wiring must be 75 C minimum.
3. Compressor thermally protected. Three-phase motors are pro­tected against primary single-phasing condition.
4. Pilot duty control must be field supplied. Minimum contact rating must be 25 va.
5. 60 Hz units have 120-volt control circuit. 50 Hz units have 230-volt control circuit. A separate source of supply at the correct voltage must be field supplied through a fused disconnect device
Fig. 3 — Unit Label Diagram — 06D,07D Units
with a maximum rating of 15 A to TB2 connections (Hot Side) and (Neutral).
6. Open control circuit disconnect switch for servicing only. Discon­nect must remain closed for crankcase heater to operate.
7. A transformer of the following rating may be field supplied for 60 Hz units: 350 va.
8. Transformer must be fused and grounded per applicable codes.
9. If any of the original wiring furnished must be replaced, it must be replaced with 90 C wire or its equivalent.
L2
5
L1
Page 6
Compressor Unit Connections
— Extend power leads from control center (contactor terminals) to compressor terminal box and make connections as shown in Fig. 4.
Terminals 8 and 9 on motor terminal plate are for internal protector connections. As shown in Fig. 4, run a wire from ter­minal 9 to terminal 6 on TB2 in control center and a wire from terminal 1 on OL2 to terminal 2 on HPS in control center.
Run crankcase heater power wiring into control center. Connect leads to terminal 5 on pumpout relay and terminal 3 on terminal block TB2. See Fig. 5.
Affix power warning label supplied in the installer ’s packet to fused disconnect which energizes crankcase heater (see unit label diagram).
LEGEND
HPS — OL — TB
High-Pressure Switch Overload Relay Terminal Block Factory Wiring
Fig. 4 — Compressor Terminal Diagram
CONT ROL WIRING — Control circuit power is 115 volts, energized from an external source or from unit voltage through field-supplied transformer. Transformer size required is 350 va for 60 Hz units. External control power source must be supplied through a 15-amp fused disconnect. Connect control circuit power leads to terminal block TB2, terminals L1 and L2. Terminal L2 is neutral potential (ground).
Compressor Protection
— The 06D and 07D units are factory wired for single-pumpout control. Field addition and wiring of line voltage remote control and liquid line solenoid valve is required. (See unit Fig. 3 and Fig. 6.) Remote control minimum contact rating must be 25 va. Solenoid valve must have a maximum load rating of 50 va holding; 200 va inrush. For applications with cooling tower, air-cooled or evaporative condensers, add necessary auxiliary contacts in line between compressor contactor and terminal A1 on timer. Insert desired interlocks and overloads between terminals 5 and 9 on terminal block TB2.
Control wiring may be modified as shown in Fig. 6 for automatic pumpdown control; remove low-pressure switch between timer relay and terminal 4 on TB2. Wire low-pressure switch between terminals 9 and 6 on TB2. Add necessary auxiliary contacts between compressor contactor and ter minal A1 on timer. Remove wire between terminal 6 on TB2 and terminal 3 on pumpout relay. Insert required interlocks and overloads between terminals 5 and 9 on TB2.
Limitations —
Do not use automatic pumpdown control on direct expansion cooler applications or when compre ssors are equipped with pressure-type unloader valves. Pressure unloader valves have built-in high to low passage which allows compressor to cycle with automatic pumpdown.
LEGEND
C— CH — CR — FU — GND — HPS — IP — LPS —
NOTES:
1. Factory wiring is in compliance with NEC. Any field modifications or
2. Field power supply wiring must be 75 C minimum.
3. Compressor thermally protected. Three-phase motors are protected
4. Pilot duty control must be field supplied. Minimum contact rating must
5. 60 Hz units have 120-volt control circuit. 50 Hz units have 230-volt con-
6. Open control circuit disconnect switch for servicing only. Disconnect
7. A transformer of the following rating may be field supplied for 60 Hz
8. Transformer must be fused and grounded per applicable codes.
9. If any of the original wiring furnished must be replaced, it must be
Contactor, Compressor Crankcase Heater Control Relay Fuse Ground Connection High-Pressure Switch Internal Protector Low-Pressure Switch
additions must be in compliance with all applicable codes. Use copper, copper-clad aluminum for field power supply only.
against primary single-phasing condition.
be 25 va.
trol circuit. A separate source of supply at the correct voltage must be field supplied thru a fused disconnect device with a max rating of 15 A to TB2 connections (Hot Side) and (Neutral).
must remain closed for crankcase heater to operate.
units: 350 va.
replaced with 90 C wire or its equivalent.
L1
NEC — OL — OPS — POR — SW — TB — TM — TR
National Electrical Code Overload Relay Oil Pressure Switch Pumpout Relay Switch Terminal Block Timer Motor Timer Relay
L2
Fig. 5 — 06D/07D Control Box Components and Connections (3-Phase)
6
Page 7
AUX — C— CR — HPS — LLS — LPS — M3 — M4 —
M5 —
Auxiliary Contactor Control Relay High-Pressure Switch Liquid Line Solenoid Valve Low-Pressure Switch Factory Wiring Evaporator Fan or Chilled Water Pump Field Wiring Cooling Tower Pump, Air-Cooled or Evaporative Condenser Fan Cooling Tower Fan or Evaporative Condenser Pump
LEGEND
OL — POR — SW — TB — TR —
*Optional.
Overload Relay Pumpout Relay Switch Terminal Block Timer Relay
Fig. 6 — Recommended Field Wiring
7
Page 8
Refrigerant Charging
When charging, or when removing charge, circulate water through water-cooled condenser(s) and cooler continuously to prevent freezing. Freezing damage is considered abuse and is not covered by Carrier warranty.
EVACUA TE, DEHYDRATE AND LEAK TEST — Entire re­frigerant system must be evacuated, dehydrated and leak tested by methods described in Carrier Standard Service Techniques Manual, Chapter 1, Sections 1-6 and 1-7. Use sight glass meth­od to charge system. See Section 1-8 of manual for details.
CHARGE THE SYSTEM — Charge to a clear sight glass while holding saturated condensing pressure constant at 125 F (air-cooled systems) or 105 F (water-cooled systems). Add additional refrigerant to fill condenser subcooler coils, where applicable, for air-cooled applications.
06D Compressor Units charge required to fill subcooler after clear sight glass is obtained.
— See condenser data for additional
INITIAL START-UP
CHECKING OPERATION
Refer to Carrier Standard Service Techniques Manual, Chapter 2 for complete instructions on checking electrical components.
Oil Charge (See Tables 2A and 2B) —
level in compressor sight glass after 15 to 20 minutes of operation. If oil level is low, add oil according to methods described in Carrier Standard Service Techniques Manual, Chapter 1 (Section 1-11). Add oil through suction manifold connection on 4-cylinder compressors, and oil port on 6-cylinder compressors.
The preferred method for a complete recharge is to glass with compressor shut down.
When additional oil, or a complete charge, is required, use only Carrier-approved compr essor oil.
Approved* oils are:
Witco. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..Suniso 3GS
T exaco, Inc. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Capella WF-32
*Oils approved for R-12, R-22, R-502 Carrier refrigerants.
For other refrigerants, contact Carrier Factory Sales Representative.
IMPORTANT: Do not reuse drained oil and do not use oil that has been exposed to atmosphere.
Check oil
1
/2 sight
Do not attempt start-up with terminal cover removed. Bodily injury or death may result from explosion and/or fire if power is supplied to compressor with the terminal cover removed or unsecured. See warning label on termi­nal cover.
Crankcase heater should be energized a minimum of
24 hours before starting unit. Do not permit crankcase heaters
to be deenergized during normal shutdown periods.
1
Check to see t hat oi l leve l is
glass.
Open water supply valve and allow water to reach condens­er. Open pressure line valve of water regulating valve, if used. (Turn condenser fan on when the compressor unit is applied with air-cooled condenser.)
Backseat (open) the compressor suction and discharge shut­off valves; open liquid line valve at receiver.
Start evaporator fan or chilled water pump.
To Start Compressor —
control power switch, and unit ON-OFF switch. Time Guard® control circuit causes a short delay before compressor starts.
Recheck oil level and check oil pressure. See Oil Charge for details.
With unit operating, voltage at compressor terminals must be within limits shown on nameplate. Phases must be balanced within 2% of voltage (refer to Electrical Connections section). Contact local power company for correction of improper line voltage or phase imbalance. Operation of unit on improper line voltage or with excessive phase imbalance constitutes abuse and is not covered by Carrier Warranty.
NOTE: The 06D, 07D unit safety controls are of the
automatic-reset type. If compressor is shut off by a safety control, do not permit control to reset more than once before determining cause of shutdown.
/3 to 2/3 up on compressor sight
Close main power switch,
High-Pressure Switch —
er water or blocking airflow on air-c ooled units, allowing head pressure to rise gradually. Check discharge pressure constantly throughout procedure. Compressor should shut off within 10 psi of values shown in Ta ble 3.
Low-Pressure Switch —
tion shutoff valve or by completely closi ng liquid line shutoff valve. A decrease of suction pressure will follow. Compressor should shut off within 4 psi of values shown in Table 3.
Oil Pressure Switch (OPS) —
protects against damage from loss of oil or loss of oil pressure during unit start-up. If the oil pressure differential sensed by the OPS is 6 psig or less on unit start-up, the switch remains closed and the OPS heater is energized.
The switch time delay is approximately 45 seconds. If after 45 seconds the oil pressure differential sensed by the OPS is less than 11 psig, the heater remains energized. The OPS tem­perature actuated switch then opens and the compressor is deenergized. If the differential reaches 11 psig, the OPS opens and deenergizes the heater and the system operates normally.
IMPORTANT: If the oil pressure switch causes unit lock­out, determine and correct the cause of the lockout (such as loss of compressor oil or flooded compressor) before restarting the unit. Failure to correct the cause of OPS lock­out may constitute abuse. Equipment failure due to abuse is not covered by warranty.
To restart the unit, push the OPS reset button and then push the control circuit switch on the unit control box to OF F and then to ON.
Time Guard® Control —
approximately 5 minutes before restarting compressor after shutdown for any reason. On starting, the Time Guard control timer causes a delay of 15 seconds after thermostat closes before compressor will start.
Check by throttling condens-
Check by slowly closing suc-
The oil pressure switch
Control provides a delay of
8
Page 9
Table 2A — 06D Physical Data
UNIT 06D A8081 H3131 A8181 E8251 E3281 E5371 OPERATING WEIGHT (lb) REFRIGERANT COMPRESSOR — 06D*
Cylinders Bore (in.) Stroke (in.) Displacement (cfm at 1750 rpm)
Maximum Rpm Oil Charge (pt) High Side Maximum Pressure Low Side Maximum Pressure
CONNECTIONS (in.)
Suction Valve (ODF) Discharge Valve (ODF)
*Compressors listed are for R-22 applications. For R-134a and R-507/
404A an 06DR compressor is standard. Factory compressor substitutes may be made. Contact Carrier Sales Representative.
180 250 265 325 325 330
R-134a, R-22, R-507/404A
M808 M313 A818 A825 A328 A537
2446 6 6 2222 2 2
1
/
1
4
8 13 18.3 23.9 28 37.1
11
34.55.5 8 8 8
7
/
8
5
/
8
7/
8
5/
8
7
/
16
11/
4
115/
32
115/
1750
450 PSIG 245 PSIG
11/
8
7/
8
NOTE: The 06DE8251 compressor unit with the 06DA825 compressor replaces the 06DE8241 once inventory of the 06DA824 compressor is depleted.
13/
7/
8
8
13/
8
7/
8
13/ 11/
Table 2B — 07D Physical Data
UNIT 07D A203 B205 A208 B210 B212 B215 OPERATING WEIGHT (lb) REFRIGERANT COMPRESSOR — 06D*
Cylinders Bore (in.) Stroke (in.) Displacement (cfm at 1750 rpm) Maximum Rpm Oil Charge (pt) High Side Maximum Pressure Low Side Maximum Pressure
CONDENSER (Shell and Tube)† Part Number
Refrigerant Storage Capacity (lb)
R-134a
R-22
Min Refrigerant Operating Charge (lb)
REFRIGERANT CONNECTION (in. ODF) Inlet Outlet
WATER CONNECTION (in. FPT) Inlet/Outlet
R-507/404A
LEGEND
FPT — ODF —
*Compressor listed is the standard compressor for R-22, air conditioning
duty. An 06DR compressor is standard equipment for low temperature (R-507/404A) or medium temperature (R-134a) applications. Factory substitutions may be made. Contact Carrier Sales Representative.
Female Pipe Thread Outside Diameter, Female
270 395 420 545 595 620
R-134a, R-22, R-507/404A
M808 M313 A818 A825 A328 A537
244666 222222
1
/
1
4
8 13 18.3 23.9 28 37.1
11
34.55.58 8 8
7
/
16
1750
450 PSIG 245 PSIG
11/
4
115/
32
115/
P701-0605CX P701-0607CX P701-0610CX P701-0615CX P701-0620CX P701-0625AX
17.20 15.90 24.40 31.60 27.40 39.80
2.86 3.16 5.00 7.55 8.47 9.18
17.00 15.70 24.10 31.20 27.10 39.30
2.80 3.10 4.90 7.40 8.30 9.00
14.70 13.60 20.90 27.10 23.50 34.10
2.80 3.10 4.90 7.40 8.30 9.00
5
/
1
8
1
/
1
8
111
15/
8
11/
8
†The condenser listed is for R-22, air conditioning duty and may change
based on the application. Maximum condenser operating pressure: 350 psi refrigerant side, 300 psi water side (“CX” models); 350 psi refrigerant side, 150 psi water side (“AX” models).
NOTE: The 07DB210 with the 06DA825 compressor replaces the
07DB210 with the 06DA824 once the compressor inventory is depleted.
15/ 11/
8 8
1
/
4
15/ 11/
11/
8 8
4
15/ 11/
11/
8 8
4
15/ 11/
16
8 8
16
8 8
2
Table 3 — Factory Switch Settings
PRESSURE CHANGE AFFECTING
SWITCH TYPE
High Pressure
210 (±10) (psig) 290 (±10) (psig)
Low Pressure
Oil Pressure
LEGEND
psid — psig —
pounds per square inch differential pounds per square inch gage
NOTES:
1. Values for the high- and low-pressure switches based on R-22. For other refrigerants, reset to pressure corresponding to satura­tion temperatures indicated by the listed pressures.
2. Values for oil pressure are above operating suction pressure (pressure differential between suction and discharge pressures of oil pump).
SWITCH POSITION
Closed Open
70 (±4) (psig) 60 (±4) (psig)
6 (psid) 11 (psid)
CAPACITY CONTROL (Suction Cutoff Type)
Control Set Point (Cylinder Load Point) —
point is adjustable from 0 to 86 psig. Pressure differential between cylinder load-up point and cylinder unload point is adjustable fr om 7 to 19 p si.
To Regulate Control Set Point —
Turn adjustment nut clockwise to its bottom stop (with nut in this position, set point is 86 psig). Control set point is then regulated to desired pressure by turning adjustment nut coun­terclockwise. Every full turn decreases set point by 7.2 psi. Approximately 12 turns in counterclockwise direction will de­crease control set point to 0 psig. Table 4 shows steps of control for the compressor and condensing unit.
Pressure Differential Adjustment —
ential adjusting screw counterclockwise to its back-stop posi­tion (differential in this position is 7 psi). Pressure differential is set by turning adjustment screw clockwise. Every full turn increases differential by 1.2 psi. Approximately 10 turns in clockwise direction will increase pressure differential to 19 psi.
9
Refer to Fig. 7.
Turn differ-
Set
802
Page 10
CONTROL SET POINT ADJUSTMENT NUT
POWER HEAD
PRESSURE DIFFERENTIAL ADJUSTMENT SCREW
VALVE BODY
BYPASS PISTON RING
BYPASS PISTON-USED WITH HOT GAS BYPASS TYPE OF UNLOADING ONLY. NOT REQUIRED WITH SUCTION CUTOFF TYPE UNLOADING.
DIFFERENTIAL SCREW SEALING CAP (CAP MUST BE REPLACED TO PREVENT REFRIGERANT LEAKAGE)
Fig. 7 — Capacity Control Valve
(Pressure Type)
Table 4 — Capacity Control Reduction Steps
% Full Load Capacity
100 67 49 32
% Full Load kW
100 73 57 46
Number of Active Cylinders
24—2—
464—2
UNIT 06D,07D
ALL 4 CYLINDER MODELS
ALL 6 CYLINDER MODELS
NO. OF
CONTR
CYL
Capacity Control Pressure (Fig. 8)
LOADED OPERATION — Pressure-operated control valve is controlled by suction pressure and actuated by discharge pressure. Each valve controls 2 cylinders (one bank). On start-up, controlled cylinders do not load up unt il differential between suction and discharge pressures is approximately 25 psi.
When suction pressure rises high enough to overcome control set point spring, the diaphragm snaps to the left and relieves pressure against the poppet valve. The drive spring
moves the poppet valve to left and it seats in the closed position.
With poppet valve closed, discharge gas is directed into the unloader-piston chamber and pressure builds up against the piston. When pressure against unloader piston is high enough to overcome the unloader valve spring, piston moves valve to the right, opening suction port. Suction gas can now be drawn into the cylinders and the bank is running fully loaded.
UNLOADED OPERATION — As suction pressure drops below set point, control spring expands, snapping diaphragm to right. This forces poppet valve open and allows gas from discharge manifold to vent through base of control valve to suction side. Loss of full discharge pressure against unloaded piston allows unloader valve spring to move valve left to closed position. The suction port is blocked, isolating the cylinder bank from the suction manifold. The cylinder bank is now unloaded.
CONDENSER MAINTENANCE
To inspect and clean condenser, drain water and remove condenser heads. To drain condenser , shut off water supply and disconnect inlet and outlet piping. Remove drain plugs and vent plug.
With condenser heads removed, inspect tubes for refrigerant leaks. (Refer to C arrier Refr igerant Ser vice T e chniques Manual.)
Clean condenser tubes with nylon brush (available from Carrier Service Department). Flush water through tubes while cleaning. If hard scale has formed, clean t ubes chemically. Do not use brushes that will scrape or scratch tubes.
Because the condenser water circuit is usually an open system, the condenser tubes may be subject to contamination by foreign matter. Local water conditions may cause excessive fouling or pitting of tubes. Condenser tubes, therefore, should be cleaned at least once a year or more often i f the water is contaminated.
Proper water treatment can minimize tube fouling and pitting. If such conditions are anticipated, water treatment analysis is recommended. Refer to the Carrier System Design Manual, Part 5, for general water conditioning information.
If hard scale has formed, clean the tubes chemically. Con­sult an experienced and reliable water-treatment firm in your area for treatment recommendations. Clean the condenser by gravity or by forced circulation as shown in Fig. 9 and 10.
IMPORTANT: If the ambient temperature is below 32 F during a shutdown period; protect the condenser from freezing by draining the water from the system or by add­ing antifreeze to the water.
10
Page 11
LEGEND
Fig. 11Compressor
(Bottom Plate Removed)
1—
Oil Pressure Relief Valve
5—
Eccentric Shaft
2—
Piston and Eccentric Strap Assembly
6—
Eccentric Strap Side Shield
3—
Motor End Counterweight
7—
Oil Suction Tube
4—
Oil Return Check Valve
8—
Pump End Counterweight
FILL CONDENSER WITH
SUCTION
PUMP SUPPORT
TANK
FINE MESH SCREEN
RETURN
GAS VENT
PUMP
PRIMING CONN.
GLOBE VALV ES
1 PIPE
CONDENSER
REMOVE WATER REGULATING VALVE
CENTRIFUGAL PUMP 1/2 HP 30 GPM AT 35 HEAD
CLOSE VENT PIPE VALVE WHEN PUMP IS RUNNING
CLEANING SOLUTION. DO NOT ADD SOLUTION MORE RAPIDLY THAN VENT CAN EXHAUST GASES CAUSED BY CHEMICAL ACTION.
3 TO 4
1
VENT PIPE
PIPE
5 APPROX
Fig. 9 — Gravity Circulation
Fig. 8 — Capacity Control Valve Operation
CONDENSER
Fig. 10 — Forced Circulation
11
Page 12
SERVICE
LEGEND
Fig. 11 — Compressor
(Bottom Plate Removed)
1—
Oil Pressure Relief Valve
5—
Eccentric Shaft
2—
Piston and Eccentric Strap Assembly
6—
Eccentric Strap Side Shield
3—
Motor End Counterweight
7—
Oil Suction Tube
4—
Oil Return Check Valve
8—
Pump End Counterweight
Do not remove the compressor terminal box cover until all electrical power is disconnected and pressure is relieved. Terminal pins may blow out causing injuries, death, and/or fire.
Service Notes
1. Where compressor components are shown, they are in normal order of removal from compressor.
2. For replacement items, use Carrier specified parts. See Carrier 06D Specified Parts list for c ompressor part interchangea b ilit y.
3. Before compressor is opened, the refrigerant must be removed from it by the Pumpdown method.
a. Start compressor, close suction shutoff valve, and
reduce crankcase pressure to 2 psig (bypass low pressurestat with jumper).
b. Stop compressor and isolate from system by
closing discharge shutoff valve.
c. Bleed any residual refrigerant. Drain oil if
necessary.
4. After disassembly, clean all parts with solvent. Use mineral spirits, white gasoline or naphtha.
5. Before assembly, coat all parts with compressor oil and clean and inspect all gasket surfaces . Replace all gaskets with new standard specified gaskets, coated with compressor oil. See Table 5 for typical torque values.
6. After reassembly, evacuate compressor and open suction and discharge valves. Restart compressor and adjust refrigerant charge.
Table 5 — Torque Values
Testing Oil Pump —
Observe oil level sight glass. The oil pressure relief valve line is positioned to discharge oil against sight glass. When oil does not discharge from this line, it is an indication of low oil pump pressure.
If oil pump pressure is low, remove and check oil filter
screen, oil pressure regulator and oil return check valve. OIL PRESSURE RELIEF VAL VE (Fig. 1 1) — Uns cr ew re-
lief valve assembly from motor partition plate, and be sure assembly is not clogged or the plunger is not stuck.
OIL RETURN CHECK VALVE (Fig. 11) — Unscrew check valve from motor partition plate. Be sure flutter valve is not sticking and that it seats tightly .
OIL FILTER SCREEN (Fig. 12) — Screen is accessible through bottom cover plate. Remove and inspect strainer for holes and dirt. Clean it with solvent and replace.
OIL PUMP AND BEARING HEAD (Fig. 12) — The oil pump assembly is contained in the pump end bearing head aluminum casting. The pump end main bearing is a machined part of this casting. An insert bearing is not required.
Remove Bearing Head Assembly from Crankcase
— Remove in sequence (refer to Fig. 12 and 13): oil pump cover, oil feed guide retaining spring, oil feed guide, pump drive segment. If damage to the oil pump or main bearing is found, a new pump end bearing head assembly should be installed.
Replace (Refer to Fig. 12 and 13)
— For torque values, refer
to Ta ble 5. Following steps are used to replace bearing head:
1. Bolt bearing head to crankcase. Place pump drive seg­ment into position and secure to end of crankshaft with cap screws and lock washers that were removed (see Fig. 13).
2. Insert oil feed guide with large diameter inward and place guide retainer spring over small diameter of guide.
3. Install gasket and oil pump cover.
SIZE
DIAM
(in.)
1
/
16
1
/
8
1
/
4
5
/
16
3
/
8
7
/
16
1
/
2
5
/
8
No. 10
1
1
/
2
NEF —
THREADS
PER IN.
27 (pipe) 8-12 Pipe Plug Crankshaft
20 (pipe) 6-10
20 (pipe) 20-25 Pipe Plug Press. Gage Conn.
20 10-12 Connecting Rod Capscrew
28
18
16
14 55-60 Motor End Cover Crankcase 13 80-90 Suction Service Valve 11 25-30 Crankshaft Spinner Tube 32 4- 6 Oil Pump Drive Segment
18 NEF 35-45 Oil Level Sight Glass
LEGEND
National Extra Fine
TORQUE
RANGE
(lb-ft)
Oil Return Check Valve
Crankcase
12-15 Baffle Plate Crankcase 12-15 Side Shield 12-15 Oil Pump Drive Segment 12-15 Unloader Valve
16-20
16-20 Terminal Block Cap Screws 20-25 Suction Service Valve 20-25 Discharge Service Valve
30-35 Pump End Bearing Head 30-35 Bottom Plate Crankcase 30-35 Compressor Foot 30-35 Cylinder Head 30-35 Motor End Cover Crankcase
Cover Plate Pump End
Bearing Head
USAGE
1
8
7
6
5
2
3
4
12
Page 13
87 6 5 4
9
10
11
12
13
3 26 2
24
23
22
PHASE BARRIER POSITIONING KEY (SEE FIG. 19)
1
25
14
44 42 41 16 38 37 36 35
15
394043
16
15
45
17
18
46
47
48 49 27
Fig. 12 — 06D Compressor Components (4-Cylinder with Eccentric Shaft Shown)
2019
34 33 32 31 30
21
29
28
13
Page 14
CAPACITY CONTROL VALV E
CAP SCREWS (NONINTERCHANGEABLE WITH FLANGE COVER CAP SCREWS)
BYPASS PISTON PLUG
SPRING
TAB
FLANGE COVER
CAP SCREWS (NONINTERCHANGERABLE WITH CONTROL VALVE CAP SCREWS)
GASKET
GAS PORT
Fig. 14 — Removal of Capacity Control Valve
Fig. 15 — Removal of Bypass Piston Plug
Motor Cover Gasket
1—
Motor End Cover
2—
Discharge Manifold Connection
3—
Valve Plate Gasket
4—
Valve Plate Assembly
5—
Cylinder Head Gasket
6—
Cylinder Head
7—
Cylinder Head Washer
8—
and Cap Screw Suction Manifold Connection*
9—
Suction Valve Positioning Spring
10 —
Suction Strainer
11 —
Bearing Head Gasket
12 —
Oil Pump Inlet Passage
13 —
Bearing Head Washer
14 —
and Cap Screw Oil Pump Cover
15 —
Pump End Bearing Head
16 —
LEGEND FOR FIG. 12
Oil Drain Plug
17 —
Crankcase
18 —
Bottom Plate Gasket
19 —
Bottom Plate
20 —
Bottom Plate Washer and Cap Screw
21 —
Oil Filter Screen
22 —
Oil Return Check Valve
23 —
Oil Level Sight Glass
24 —
Motor Terminal Plate
25 —
Dowel Pins (For Suction Valve
26 —
Positioning) Equalizing Tube and Lock Screw Assembly
27 —
Lockwasher
28 —
Rotor Lockwasher
29 —
Rotor Drive Key
30 —
Piston Pin Lock Ring
31 —
Piston Pin
32 —
Piston
33 —
Oil Ring
34 —
Compression Rings
35 —
Eccentric Strap
36 —
Eccentric Strap Side Shield
37 —
Pump End Counterweight
38 —
Oil Pump Drive Segment
39 —
Drive Segment Cap Screws
40 —
and Lockwashers Oil Feed Guide
41 —
Oil Feed Guide Retainer Spring
42 —
Cover Gasket
43 —
Pump Cover Cap Screw and Washer
44 —
Counterweight Bolt
45 —
Eccentric Strap Side Shield
46 —
Motor End Counterweight
47 —
Locknut
48 —
Eccentric Shaft (or Crankshaft)
49 —
*Used to add compressor oil.
TOP
8
Suction Strainer
1—
Assembly Oil Pump Bearing Head
2—
Assembly Rotor Retaining Ring
3—
Oil Pump Drive Segment
4—
Fig. 13 — Removing Pump End Bearing Head
LEGEND
Oil Pump Rotor
5—
Drive Segment Cap
6—
Screws Bearing Head Cap
7—
Screws Oil Pump Inlet Passage
8—
Three Allen head cap screws hold capacity control valve in
1
place (Fig. 14). Remove screws using a cut-down wrench, and pull valve from cylinder head.
3
/16-in. Allen
Remove same number of piston plugs from replacement compressor as number of unloaders supplied with original compressors. Three Allen head cap screws hold piston plug
2
assembly in place. Remove flange cover, gasket, spring and bypass piston plug (Fig. 15). A tapped hole is provided in piston to allow it to be pulled out. Hole has same thread
3
4
5
6
7
diameter as cap screws removed above.
Cylinder Heads —
Disassemble cylinder heads by re-
moving cap screws and prying up on side between cylinder
head and valve plate to break heads loose from valve plate. Do not strike cylinder heads to break loose.
Check heads for warping, cracks and damage to gasket surfaces. When replacing cylinder head, torque cap screws 30 to 35 lb-ft to prevent high to low side leak in center portion of cylinder head gasket.
Service Replacement Compressors —
ment compressors are not equipped with control valves. One or both side bank cylinder head(s) is plugged with a spring loaded plug piston assembly. Compressor will run fully loaded with piston plug(s) in place.
compressor (ensures proper val ves are used with correct set-
Transfer original capacity control valve(s) to replacement
ting). For sealing purposes, install a plug piston assembly into each cylinder head of original compressor f rom which a con­trol valve was removed.
Replace-
14
Page 15
Suction and Discharge Valve Plate Assembly
CYLINDER HEAD GASKET
VALVE PLATE GASKET
DISCHARGE VALVE SCREW AND LOCK WASHER
DISCHARGE VALV E
VALVE PLATE
VALVE PLATE ASSEMBLY
DISCHARGE VALVE STOP
DISCHARGE PORT
HIGH-PRESSURE CONNECTION
LOW-PRESSURE CONNECTION
SUCTION VALV E
VALVE PLATE DOWEL PIN
SUCTION VALVE POSITIONING SPRING
Fig. 16 — Valve Plate Assembly
Fig. 17 — Suction Valve and Positioning
Springs in Place
(Fig. 16) —
compressor down and observing suction and discharge pressure equalization. If a discharge valve is leaking, the pressures will equalize rapidly. Maximum allowable discharge pressure drop is 3 psi per minute after an initial drop of 10 to 15 psi in the first half minute.
If there is an indicated loss of capacity and discharge valves check properly, remove suction and discharge valve plate assembly and inspect suction valves.
IMPORTANT: This test procedure is not applicable to compressors equipped with pressure actuated or solenoid unloader valves due to rapid pressure equalization rate. Check suction and discharge valves by disassembling valve plate (see Fig. 16).
DISASSEMBLY — Remove cylinder head.
1. Remove discharge valve assembly: cap screws, valve stops, valve stop supports and valves.
2. Pry up on side of valve plate, between valve plate and cylinder deck, to remove valve plat e and expose suction valves. Remove suction valves and suction valve posi­tioning springs from dowel pins.
Inspect valves and valve seats for wear and dam age. See Table 6. Check cylinder deck valve stops for uneven wear. Replace valves if cracked or worn. If valve seats are worn, replace complete valve plate assembly. If cylinder deck valve stops are worn, replace compressor.
REAS S E M BLY — Do not interchange valves. Install suction valve positioning springs on dowel pins. Assemble positioning springs with spring ends bearing against cylinder deck (Fig. 17). Springs bow upward. Place suction valves on dowel pins, over positioning springs. Place valve plate on cylinder deck, and reinstall discharge valve plate assembly. Retorque discharge valve stop cap screws to 16 lb-ft. Replace cylinder head. Be sure cylinder head gasket is lined up correctly with cylinder head and valve plate.
Test for leaking discharge valves by pumping
COMPRESSOR PART
MOTOR END
Main Bearing Diameter Max Journal Diameter Min
PUMP END
Main Bearing Diameter Max
Journal Diameter Min CRANKPIN DIAMETER Min THROW Max
THRUSTWASHER Max
ECCENTRIC DIAMETER Max CONN. ROD DIAMETER Max PISTON PIN BEARING Min CYLINDERS
Bore Max
Piston Diameter Min
Piston Pin Diameter Min
Piston Pin Bearing
Piston Ring Gap Max
Piston Ring Side Clearance Max
*Maximum allowable wear above maximum or below minimum factory tolerances
shown. For example: difference between pump end main bearing diameter and journal diameter is .001 in. (1.3745 – 1.3735) per factory tolerances. Maximum allowable difference is .004 in. (.002 + .002).
Tolerance for the 06DA825 same as 06DA824.
Table 6 — Compressor Wear Limits (Factory Tolerances) (in.)
COMPRESSOR MODEL
06DM808 06DM313 06DA818 06DA825† 06DA328 06DA537
1.3755 1.6240 0.002
1.3735 1.6233 0.002
1.3745 0.002
1.3735 0.002
2.2030 1.3735 2.2030 1.3735 0.0025
1.2500 1.0000 1.4374 1.2500 1.9396
Min
Min
Min
Min
1.2460 1.4344 1.246 —— 0.1570 0.025
0.1550 0.025
2.2035 2.2035 0.002 1.3755 1.3755 0.002
0.6878 0.001
2.0005 0.002
1.996 0.002
0.6873 0.001
Press Fit
0.0130 0.025
0.0050 0.025
0.0020 0.002
0.0010 0.002
15
MAX* ALLOW
WEAR
Page 16
Cleaning Suction Strainer
Fig. 18 — Motor End Cover Assembly
ACROSS-THE-LINE APPLICATION (5 TERMINALS)
Fig. 19 — Terminal Plate Assembly
1. Pump down compressor.
2. Remove motor end cover and screws holding disc type strainer (Fig. 1 8) to c ove r.
3. Clean strainer with solvent or replace if broken or corroded.
4. Replace strainer and motor end cover. Purge or evacuate compressor before starting.
Motor Replacement —
replaceable. Stator is a press fit into motor housing. If compres­sor motor is damaged, replace compressor.
Terminal Plate Assembly —
bly is shown in Fig. 19. Do not disassemble for any reason ex­cept to replace the phase barrier, which may become damaged.
If refrigerant leakage or a ground short occurs, the entire ter­minal plate assembly must be replaced.
If it becomes necessary to remove the phase barrier, proceed
as follows:
1. Loosen and remove all terminal nuts.
2. Remove lock washers and wire terminals.
3. Loosen and disengage the center screw. (Do not try to remove the screw.)
4. Lift the phase barrier off the terminal screws (the spacers and the center screw are removed with the phase barrier).
IMPORTANT: Do not disturb the jam nuts on which the phase barrier rests.
S
tator and rotor are not field
The terminal plate assem-
STRAINER SCREWS & WASHERS
SUCTION STRAINER
MOTOR END COVER
SUCTION SERVICE VALVE
BARRIER POSITIONING KEY (THIS SIDE IS ADJACENT TO THE CYLINDER HEAD)
PHASE BARRIER
NO TERMINAL IN THIS SECTION
TERMINAL NUMBERS ON THIS SURFACE
VALVE GASKET
VALVE CAP SCREW
TERMINAL NUT(TYP)
Procedure for reassembling the phase barrier:
1. Place phase barrier over the terminal screws. B e sure po-
sitioning key is in the recess in the terminal plate before proceeding further.
2. Place the spacers and wire terminals on the terminal screws.
3. Place the lock washers and terminal nuts over the wire terminals and tighten to specified torque (18 to 30 lb-in.).
4. Install the center screw through the phase barrier and tighten to the specified torque (15 to 25 lb-in.).
NOTE: The design allows for clearance between the center
screw head and the phase barrier. Thus, the torque limit may be reached before the screw head contacts the phase barrier. This condition is acceptable.
Compressor Running Gear Removal
1. Remove pump end bearing head.
2. Remove motor end cover carefully to prevent damage to stator. Support cover and lift of f horizontally until it clears windings.
3. Remove bottom cover plate.
4. Remove equalizer tube assembly from motor end of crankshaft (or eccentric shaft). If shaft turns , preventing tube assembly from being loosened, block shaft with a piece of wood.
5. Remove rotor using a jackbolt. Insert a brass plug into rotor hole to protect end of crankshaft from jackbolt. Support rotor while it is being removed to prevent stator damage.
6. Remove connection rod caps from compressors using connecting rods and crankshafts. Label caps and rods so
they may be reinstalled in same plate on crankshaft.
BLACK JAM NUTS ON TERMINALS 8 & 9; BRASS JAM NUTS ON TERMINALS 1, 2 AND 3
CENTRAL SCREW (THREADS INTO TERMINAL PLATE)
SPACER (TYP)
LOCK WASHER (TYP)
7. Remove bolts holding counterweights and eccentric strap side shields to eccentric shaft. Remove eccentric strap side shields. Remove pump end counterweight through pump end bearing head opening. Motor end counter­weight will remain on eccentric shaft until shaft is removed.
8. Pull eccentric shaft or crankshaft out through pump end opening. Guide eccentric straps from eccentric shaft during removal process. Rotate shaft and tap it lightly to prevent straps from jamming.
9. Remove eccentric straps or connecting rods and pistons through bottom cover plate opening.
10. Disassemble connecting rods or eccentric straps from pistons by removing lock ring(s) and piston pins. Remove oil and compression rings from piston. Keep each piston
assembly together for proper reassembly.
Check all parts for wear and tolerances shown in Ta ble 6. Check crankshaft (eccentric shaft) oil passages and clean if clogged.
16
Page 17
PUMP END MAIN BEARING — This bearing is a ma­chined part of the new aluminum oil pump and bearing head casting. Disassemble bearing head. If bearing is scored or worn, replace complete bearing head.
CRANKCASE AND MOTOR END MAIN BEAR­INGS — These bearings are not field replaceable. If bearings are worn or damaged, replace compressor.
Compressor Running Gear Replacement
CRANKSHAFT — Install crankshaft through pump end, carefully guiding it through main bearings. Replace rotor. Attach equalizer tube assembly to motor end of shaft.
Eccentric shafts must be installed after piston assemblies.
Place motor end counterweight on shaft before inserting shaft into compressor. See Piston Assembly Replacement.
PISTON ASSEMBLY — Attach connecting rods or eccentric straps to pistons with piston pins and lock in place with piston pin lock rings. Place lock rings with gap on the side. They should be tight enough so they cannot be rotated by finger pressure.
RINGS
1. Check ring gap by inserting each ring separately in cylinder, approximately be between .013 and .005 inch.
2. Install compression rings in top piston grooves with side marked “Top” toward piston head. Install oil ring below compression ring with notched end on bottom. Stagger ring gaps around piston.
3. Measure side clearance between ring and piston (T able 6). Check for free action.
PISTON ASSEMBLY REPLACEMENT Compressors Using Crankshafts
and piston assemblies into cylinders. Place chamfered sides of connecting rods against radius of crankpins. Install connecting rod caps to matching connecting rods through bottom of crank­case. Be sure chamfered sides of caps are against radius of crankpins. Caps are locked in plac e with cap screw s. Use 8 to 10 lb-ft to tighten cap screws.
Compressors Using Eccentric Shafts strap and piston assemblies into cylinders. Install eccentric shaft through pump end, carefully guiding it through eccentric straps and main bearings. Install pump end counter­weight to eccentric shaft and replace eccentric strap side shields.
Turn crankshaft or eccentric shaft to be sure there is no binding between bearing surfaces and journals. Replace oil screen, bottom cover plate, valve plates and cylinder heads.
3
/8 in. from top. Ring gap should
— Install connecting rod
— Install eccentric
COMPRESSOR MOTOR BURNOUT
Do not attempt start-up with terminal cover removed. Bodily injury or death may result from explosion and/or fire if power is supplied to compressor with the terminal cover removed or unsecured. See warning label on termi­nal cover.
Clean-Up Procedure —
the stator winding decomposes, forming carbon, water and acid which contaminate refrigerant systems. Remove these contam­inants from system to prevent repeat motor failures.
1. Close compressor suction and discharge service valves, and bleed refrigerant from compressor. Save remaining refrigerant in system.
2. Check control box for welded contactor contacts, welded overload contacts or burned out heater elements. Che ck terminal plate for burned or damaged terminals, insula­tion, and shorted or grounded terminals. Repair or replace where nece ssa ry.
3. Remove suction and discharge shutoff valve bolts and all other connections to damaged compressor. Remove damaged compressor and replace with new compressor. Replace liquid line filter drier with a drier of one size larger.
4. Purge new compressor . Tri ple-evacuate, using the follow­ing procedure:
a. Evacuate to 5000 microns. b. Break vacuum with system refrigerant. Pressurize
to 15 psig. Wait 20 minutes to remove moisture. c. Re-evacuate to 5000 microns. d. Repeat Step b. e. Evacuate to 1000 microns or below if possible.
5. Place compressor in operation. After 2 to 4 hours of operation, check compressor oil for signs of discoloration and/or acidity. If oil shows signs of contamination, replace oil charge, filter driers, and cl ean suction st rainer with solvent. Repeat this procedure until oil stays clean and acid free for 48 hours of operation.
If a hermetic motor burns out,
17
Page 18
PROBLEM CAUSE REMEDY
Compressor does not run.
Compressor cycles on low-pressure control.
Compressor cycles on high-pressure control.
Insufficient capacity.
Unit operates long or continuously.
LEGEND
Thermostatic Expansion Valve
TXV —
TROUBLESHOOTING
Read Safety Considerations on page 1 before proceeding with troubleshooting.
Main power line open. Replace fuse or reset circuit breaker. Safety thermostat tripped. Reset thermostat. Condenser water pump not running power off. Restart. Pump binding. Free pump. Incorrect wiring. Rewire. Motor burned out. Replace. Control stuck open. Replace control. Loose terminal connection. Check connections. Improperly wired controls. Check wiring and rewire. Low line voltage. Check line voltage determine location of
Compressor motor defective. Check motor winding for open or short.
Seized compressor. Replace compressor. Low-pressure control erratic in action. Raise differential setting, check capillary for
Suction shutoff valve partially closed. Open valve. Low refrigerant charge. Add refrigerant. Plugged suction strainer. Clean strainer. Defective TXV. Replace. High-pressure control erratic in action. Check capillary tube for pinches. Set control as
Discharge valve partially closed. Open valve. Air in system. Purge. Condenser scaled (or airflow restricted). Clean condenser. Receiver not properly vented, refrigerant backs
up into evap condenser. Condenser water pump or fans not
operating. Refrigerant overcharge. Purge. Low refrigerant charge. Add refrigerant. Control set too high. Reset control. Expansion valve plugged. Clean or replace. Inefficient compressor. Check valves and pistons. Expansion valve setting too high. Lower setting. Iced or dirty evaporator. Defrost or clean. Evaporator too small. Add surface or replace. Condensing unit too small. Add unit or replace. Expansion valve too small. Raise suction pressure with larger valve. Restricted or small gas lines. Clear restriction or increase line size. Low refrigerant charge. Add refrigerant. Control contacts fused. Replace control. Air in system. Purge. Partially plugged or plugged expansion valve or
strainer. Defective insulation. Replace or repair. Service load. Keep doors and windows closed. Inefficient compressor. Check valves. Condenser scaled. Clean condenser. Restricted evaporator air. Defrost coil, clean filters and ductwork.
voltage drop.
Replace compressor if necessary.
pinches, replace control.
required.
Repipe as required.
Start pump or fans.
Clean or replace.
18
Page 19
PROBLEM CAUSE REMEDY
System noises.
Compressor loses oil.
Frosted suction line.
Hot liquid line. Frosted liquid line.
Frosted expansion valve.
LEGEND
Thermostatic Expansion Valve
TXV —
Piping vibration. Support piping as required, check for loose pipe
Expansion valve hissing. Add refrigerant, check for plugged liquid line
Compressor noisy. Check valve plates for valve noise, replace
Insufficient compressor oil. Add oil. Leak in system. Repair leak. Plugged or stuck compressor oil return
check valve. Oil trapping in line. Check piping for oil traps. Crankcase heaters not energized during
shutdown. Expansion valve admitting excess
refrigerant. Shortage of refrigerant. Repair leak and recharge. Receiver shutoff valve partially closed or
restricted. Restricted catchall. Replace. Restricted strainer drier. Replace. Ice plugging TXV orifice. Apply hot wet cloth to TXV. Moisture indicated by increase in suction
pressure. Plugged TXV strainer. Clean strainer or replace TXV.
connectors.
strainer.
compressor (worn bearings), check for loose compressor holddown bolts.
Repair or replace.
Replace heaters.
Adjust expansion valve.
Open valve or remove restriction.
Install drier.
19
Page 20
Copyright 2002 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book2244 Tab 1b2a2b3a
PC 802 Catalog No. 530-608 Printed in U.S.A. Form 06/07D-3SI Pg 20 802 7-02 Replaces: 06/07D-2SI
Loading...