Installing, starting up and servicing this equipment can be
hazardous due to system pressures, electrical components and
equipment location (roofs, elevated structures, etc.). Only
trained, qualified installers and service mechanics should
install, start up and service this equipment.
When working on the equipment, observe precautions in the
literature, tags, stickers and labels attached to t he equipment
and any other safety precautions that apply. Follow all safety
codes. Wear safety glasses and work gloves. Use care in
handling, rigging and setting bulky equipment.
Electrical shock can cause persona l injury and even death.
Be sure power to equipment is shut off before installing or
servicing this equipment. There may be more than one
disconnect. Tag disconnect(s) to alert others not to turn
power on until work is completed.
BEFORE INSTALLATION
Check Shipment —
if shipment is damaged or incomplete.
Unit Location Considerations —
floor in a well-v entil ated ar ea. Pos itio n unit t o allow sufficien t
space for refrigerant and water connections and to service
compressor. Place unit so suction and discharge valves can be
easily reached and oil level checked. Do not install condensing
unit where temperature will fall below freezing.
Local water can cause excessive fouling or sealing of
condenser tubes. If such conditions are anticipated, a water
treatment analysis is recommended. Refer to Carrier System
Design Manual, Part 5, for general water conditioning
information.
Make provision in piping layout to drain and vent condenser
if system is to be shut down in winter.
File claim with shipping company
Locate unit on
INSTALLATION
Mount Unit —
Loosen compressor mounting bolts and remove shipping
blocks from under compressor. Tighten all 4 bolts on compressor. Next, loosen each bolt until the flanged washer can be
moved sideways with finger pressure.
NOTE: Be sure that compressor floats freely on mounting
springs.
Piping Connections —
lines to connections indicated on condenser unit (Fig. 1). Water
leaving condenser should not be connected directly into sewer
lines. Check local codes.
Attach refrigerant liquid and suction lines to condensing
units (Fig. 1); suction and discharge to compressor unit
(Fig. 2). When soldering or brazing piping to valves, disassemble valve or wrap it in a wet cloth to prevent heat damage.
Allow flexibility in suction line so compressor suction valve
may be moved aside for access to suction strainer.
Level unit and bolt firmly to foundation.
Attach water supply and return
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2244
Tab 1b2a2b3a
PC 802Catalog No. 530-608Printed in U.S.A.Form 06/07D-3SIPg 18027-02Replaces: 06/07D-2SI
Page 2
DIMENSIONS (in.)
UNIT 07DWIDTH A
A203
B205
A208
B210
B212
B215
63
39
51
51
30
30
9
/
16
9
/
16
9
/
16
13
/
16
WATER CONNECTIONS FOR 07DB215 UNIT ONLY.
Fig. 1 — 07D Condensing Unit Dimensions
NOTES:
1. For standard service practices, such as troubleshooting and refrigerant charging, allow a minimum
2′-6″ clearance around the unit.
2. Recommended service space for condenser tube
removal is one condenser length at either end.
3. For compressor removal, allow a minimum 3′ wide
access aisle to and from the unit.
4. Local codes or jurisdiction may prevail for unit
clearances.
2
Page 3
NOTES:
1. For standard service practices, such as troubleshooting and refrigerant charging, allow a minimum
2′-6″ clearance around the unit.
2. For compressor removal, allow a minimum 3′ wide
access aisle to and from the unit.
3. Local codes or jurisdiction may prevail for unit
clearances.
Fig. 2 — 06D Compressor Unit Dimensions
3
Page 4
Install a solenoid valve (field supplied) in liquid line directly
before expansion valve. Solenoid valve is necessary for single
pumpout control used on 06D, 07D units. Refrigerant filter
drier and moisture indicator are shipped with 07D condensing
units for field installation. Install in liquid line according to
manufacturer’s instructions.
Relief valve located on top of condenser (07D units) will
open to relieve excessive pressure, allowing refrigerant to
escape. Most local codes require piping from safe ty device to
outdoors.
Refer to Carrier System Design Manual, Part 3, for standard
piping techniques.
COMPRESSOR UNITS — Connect high- and low-pressure
switch capillary tubes from control box to compressor. See
Fig. 2.
Install discharge line muffler (accessory) in discharge line
as close to compressor shutoff valve as possible.
Electrical Connections
UNBALANCED 3-PHASE SUPPLY VOLTAGE — Never
operate a motor where a phase imbalance in supply voltage
is greater than 2%. Use the following formula to determine
Maximum deviation is 4 volts. Determine % voltage
imbalance:
% Voltage Imbalance =100 x
4
233
= 1.7%
This amount of phase imbalance is satisfactory as it is below
the maximum allowable of 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
ELECTRICAL DATA NOTES
1. All 06D and 07D units are across-the-line start.
2. Wire sizes are based on TW type copper wire. Maximum
wire lengths based on data from Table 1 will result in a
1% voltage drop to compressor. Where up to 3% voltage
drop is allowed, the run length can be increased to 3 times
the length calculated from data in Table 1.
3. The 06D compressor unit electrical data shown in Table 1
does not apply for 06D compressors used as an integral
part of other Carrier equipment. See proper installation
book for electrical information.
WIRI NG — Power supply must correspond with unit nameplate electrical characteristics (units are internally wired at
factory for nameplate voltage). Field wiring must comply with
local and national codes.
Install a branch circuit fused disconnect of adequate size to
handle starting current.
LIN E POWER — Connect line power to the compressor con-
tactor C. For example, connect L1 to terminal 11, L2 to terminal 12 and L3 to terminal 13. See Fig. 3.
Table 1 — Compressor Electrical Data
COMPRESSOR
PART NUMBER
06D*
808
M
313
818
825
A
328
537
LEGEND
LRA —
MCC —
RLA —
*Refer to physical data table to match compressor with correct com-
pressor unit or water-cooled condensing unit.
NOTES:
1. RLA (rated load amps) value shown is: MCC ÷ 1.40 = RLA.
2. For minimum contactor sizing, use RLA value determined by:
Locked Rotor Amps
Maximum Continuous Current
Rated Load Amps
MCC ÷ 1.40 = RLA.
VO LTAGE
(3 Ph-60 Hz)
575
208/23017.412.4710.78
4608.76.235.53.1
575
208/2302719.31000.5
46013.59.6502.1
575
208/2304431.41600.42
4602215.7801.7
575
208/23055.539.61980.31
46027.819.8991.3
575
208/2306244.32280.26
4603122.11141.0
575
208/2308963.62660.18
4604028.61200.72
HPMCCRLALRA
3
5
6.5
7.5
10
15
MOTOR WINDING
RESISTANCE
(Ohms)
7528.45.0
10.87.7403.3
17.612.6642.6
22.215.9792.0
2517.9911.7
3222.9961.2
3. For wiring sizing, the RLA value can be determined by: MCC
÷
1.56 = RLA.
4. Compressor operating amps at any specific conditions can only
be determined from a performance curve.
5. RLA values for 06D compressor protected by a calibrated
circuit breaker will depend on must-trip value of circuit breaker.
6. Ohm values shown for resistance are approximate and shown
for reference only. Motors from different vendors and motors of
different efficiencies can differ up to 15% from data shown.
7. Electrical data for compressor part numbers 06DR and
50 Hz models (not shown) are available from Carrier Sales
Representative.
Auxiliary
Compressor Contactor
Crankcase Heater
Control Relay
Direct Expansion
Equipment
Fuse
Ground
High-Pressure Switch
Internal Protector
Liquid Line Solenoid Valve
Low-Pressure Switch
Cooling Tower Fan
National Electrical Code
Overload
Oil-Pressure Switch
Pumpout Relay
Start-Stop-Reset Switch
LEGEND
TB—
TM—
TR—
Terminal Block
Timer Motor
Timer Relay
Terminal Block Connector
Unmarked Terminal
Marked Terminal
Factory Wiring
Field Control Wiring
To indicate common potential only;
not to represent wiring.
Splice
NOTES:
1. Factory wiring is in compliance with NEC. Any field modifications
or additions must be in compliance with all applicable codes. Use
copper, copper-clad aluminum for field power supply only.
2. Field power supply wiring must be 75 C minimum.
3. Compressor thermally protected. Three-phase motors are protected against primary single-phasing condition.
4. Pilot duty control must be field supplied. Minimum contact rating
must be 25 va.
5. 60 Hz units have 120-volt control circuit. 50 Hz units have
230-volt control circuit. A separate source of supply at the correct
voltage must be field supplied through a fused disconnect device
Fig. 3 — Unit Label Diagram — 06D,07D Units
with a maximum rating of 15 A to TB2 connections
(Hot Side) and (Neutral).
6. Open control circuit disconnect switch for servicing only. Disconnect must remain closed for crankcase heater to operate.
7. A transformer of the following rating may be field supplied for
60 Hz units: 350 va.
8. Transformer must be fused and grounded per applicable codes.
9. If any of the original wiring furnished must be replaced, it must
be replaced with 90 C wire or its equivalent.
L2
5
L1
Page 6
Compressor Unit Connections
— Extend power leads from
control center (contactor terminals) to compressor terminal box
and make connections as shown in Fig. 4.
Terminals 8 and 9 on motor terminal plate are for internal
protector connections. As shown in Fig. 4, run a wire from terminal 9 to terminal 6 on TB2 in control center and a wire from
terminal 1 on OL2 to terminal 2 on HPS in control center.
Run crankcase heater power wiring into control center.
Connect leads to terminal 5 on pumpout relay and terminal 3
on terminal block TB2. See Fig. 5.
Affix power warning label supplied in the installer ’s packet
to fused disconnect which energizes crankcase heater (see unit
label diagram).
CONT ROL WIRING — Control circuit power is 115 volts,
energized from an external source or from unit voltage through
field-supplied transformer. Transformer size required is 350 va
for 60 Hz units. External control power source must be
supplied through a 15-amp fused disconnect. Connect control
circuit power leads to terminal block TB2, terminals L1 and
L2. Terminal L2 is neutral potential (ground).
Compressor Protection
— The 06D and 07D units are factory
wired for single-pumpout control. Field addition and wiring of
line voltage remote control and liquid line solenoid valve is
required. (See unit Fig. 3 and Fig. 6.) Remote control minimum
contact rating must be 25 va. Solenoid valve must have a
maximum load rating of 50 va holding; 200 va inrush. For
applications with cooling tower, air-cooled or evaporative
condensers, add necessary auxiliary contacts in line between
compressor contactor and terminal A1 on timer. Insert desired
interlocks and overloads between terminals 5 and 9 on terminal
block TB2.
Control wiring may be modified as shown in Fig. 6 for
automatic pumpdown control; remove low-pressure switch
between timer relay and terminal 4 on TB2. Wire low-pressure
switch between terminals 9 and 6 on TB2. Add necessary
auxiliary contacts between compressor contactor and ter minal
A1 on timer. Remove wire between terminal 6 on TB2 and
terminal 3 on pumpout relay. Insert required interlocks and
overloads between terminals 5 and 9 on TB2.
Limitations —
Do not use automatic pumpdown control
on direct expansion cooler applications or when compre ssors
are equipped with pressure-type unloader valves. Pressure
unloader valves have built-in high to low passage which allows
compressor to cycle with automatic pumpdown.
LEGEND
C—
CH—
CR—
FU—
GND —
HPS —
IP—
LPS —
NOTES:
1. Factory wiring is in compliance with NEC. Any field modifications or
2. Field power supply wiring must be 75 C minimum.
3. Compressor thermally protected. Three-phase motors are protected
4. Pilot duty control must be field supplied. Minimum contact rating must
5. 60 Hz units have 120-volt control circuit. 50 Hz units have 230-volt con-
6. Open control circuit disconnect switch for servicing only. Disconnect
7. A transformer of the following rating may be field supplied for 60 Hz
8. Transformer must be fused and grounded per applicable codes.
9. If any of the original wiring furnished must be replaced, it must be
additions must be in compliance with all applicable codes. Use copper,
copper-clad aluminum for field power supply only.
against primary single-phasing condition.
be 25 va.
trol circuit. A separate source of supply at the correct voltage must be
field supplied thru a fused disconnect device with a max rating of 15 A
to TB2 connections (Hot Side) and (Neutral).
must remain closed for crankcase heater to operate.
units: 350 va.
replaced with 90 C wire or its equivalent.
L1
NEC —
OL—
OPS —
POR —
SW—
TB—
TM—
TR—
National Electrical Code
Overload Relay
Oil Pressure Switch
Pumpout Relay
Switch
Terminal Block
Timer Motor
Timer Relay
L2
Fig. 5 — 06D/07D Control Box Components and Connections (3-Phase)
6
Page 7
AUX —
C—
CR —
HPS —
LLS —
LPS —
M3 —
M4 —
M5 —
Auxiliary
Contactor
Control Relay
High-Pressure Switch
Liquid Line Solenoid Valve
Low-Pressure SwitchFactory Wiring
Evaporator Fan or Chilled Water PumpField Wiring
Cooling Tower Pump, Air-Cooled or
Evaporative Condenser Fan
Cooling Tower Fan or
Evaporative Condenser Pump
When charging, or when removing charge, circulate water
through water-cooled condenser(s) and cooler continuously
to prevent freezing. Freezing damage is considered abuse
and is not covered by Carrier warranty.
EVACUA TE, DEHYDRATE AND LEAK TEST — Entire refrigerant system must be evacuated, dehydrated and leak tested
by methods described in Carrier Standard Service Techniques
Manual, Chapter 1, Sections 1-6 and 1-7. Use sight glass method to charge system. See Section 1-8 of manual for details.
CHARGE THE SYSTEM — Charge to a clear sight glass
while holding saturated condensing pressure constant at 125 F
(air-cooled systems) or 105 F (water-cooled systems). Add
additional refrigerant to fill condenser subcooler coils, where
applicable, for air-cooled applications.
06D Compressor Units
charge required to fill subcooler after clear sight glass is
obtained.
— See condenser data for additional
INITIAL START-UP
CHECKING OPERATION
Refer to Carrier Standard Service Techniques Manual,
Chapter 2 for complete instructions on checking electrical
components.
Oil Charge (See Tables 2A and 2B) —
level in compressor sight glass after 15 to 20 minutes of
operation. If oil level is low, add oil according to methods
described in Carrier Standard Service Techniques Manual,
Chapter 1 (Section 1-11). Add oil through suction manifold
connection on 4-cylinder compressors, and oil port on
6-cylinder compressors.
The preferred method for a complete recharge is to
glass with compressor shut down.
When additional oil, or a complete charge, is required, use
only Carrier-approved compr essor oil.
*Oils approved for R-12, R-22, R-502 Carrier refrigerants.
For other refrigerants, contact Carrier Factory Sales
Representative.
IMPORTANT: Do not reuse drained oil and do not use oil
that has been exposed to atmosphere.
Check oil
1
/2 sight
Do not attempt start-up with terminal cover removed.
Bodily injury or death may result from explosion and/or
fire if power is supplied to compressor with the terminal
cover removed or unsecured. See warning label on terminal cover.
Crankcase heater should be energized a minimum of
24 hours before starting unit. Do not permit crankcase heaters
to be deenergized during normal shutdown periods.
1
Check to see t hat oi l leve l is
glass.
Open water supply valve and allow water to reach condenser. Open pressure line valve of water regulating valve, if used.
(Turn condenser fan on when the compressor unit is applied
with air-cooled condenser.)
Backseat (open) the compressor suction and discharge shutoff valves; open liquid line valve at receiver.
Start evaporator fan or chilled water pump.
To Start Compressor —
control power switch, and unit ON-OFF switch. Time Guard®
control circuit causes a short delay before compressor starts.
Recheck oil level and check oil pressure. See Oil Charge for
details.
With unit operating, voltage at compressor terminals must
be within limits shown on nameplate. Phases must be balanced
within 2% of voltage (refer to Electrical Connections section).
Contact local power company for correction of improper line
voltage or phase imbalance. Operation of unit on improper line
voltage or with excessive phase imbalance constitutes abuse
and is not covered by Carrier Warranty.
NOTE: The 06D, 07D unit safety controls are of the
automatic-reset type. If compressor is shut off by a safety
control, do not permit control to reset more than once before
determining cause of shutdown.
/3 to 2/3 up on compressor sight
Close main power switch,
High-Pressure Switch —
er water or blocking airflow on air-c ooled units, allowing head
pressure to rise gradually. Check discharge pressure constantly
throughout procedure. Compressor should shut off within 10 psi
of values shown in Ta ble 3.
Low-Pressure Switch —
tion shutoff valve or by completely closi ng liquid line shutoff
valve. A decrease of suction pressure will follow. Compressor
should shut off within 4 psi of values shown in Table 3.
Oil Pressure Switch (OPS) —
protects against damage from loss of oil or loss of oil pressure
during unit start-up. If the oil pressure differential sensed by the
OPS is 6 psig or less on unit start-up, the switch remains closed
and the OPS heater is energized.
The switch time delay is approximately 45 seconds. If after
45 seconds the oil pressure differential sensed by the OPS is
less than 11 psig, the heater remains energized. The OPS temperature actuated switch then opens and the compressor is
deenergized. If the differential reaches 11 psig, the OPS opens
and deenergizes the heater and the system operates normally.
IMPORTANT: If the oil pressure switch causes unit lockout, determine and correct the cause of the lockout (such as
loss of compressor oil or flooded compressor) before
restarting the unit. Failure to correct the cause of OPS lockout may constitute abuse. Equipment failure due to abuse is
not covered by warranty.
To restart the unit, push the OPS reset button and then push
the control circuit switch on the unit control box to OF F and
then to ON.
Time Guard® Control —
approximately 5 minutes before restarting compressor after
shutdown for any reason. On starting, the Time Guard control
timer causes a delay of 15 seconds after thermostat closes
before compressor will start.
Check by throttling condens-
Check by slowly closing suc-
The oil pressure switch
Control provides a delay of
8
Page 9
Table 2A — 06D Physical Data
UNIT 06DA8081H3131A8181E8251E3281E5371
OPERATING WEIGHT (lb)
REFRIGERANT
COMPRESSOR — 06D*
Cylinders
Bore (in.)
Stroke (in.)
Displacement (cfm at 1750 rpm)
Maximum Rpm
Oil Charge (pt)
High Side Maximum Pressure
Low Side Maximum Pressure
CONNECTIONS (in.)
Suction Valve (ODF)
Discharge Valve (ODF)
*Compressors listed are for R-22 applications. For R-134a and R-507/
404A an 06DR compressor is standard. Factory compressor substitutes
may be made. Contact Carrier Sales Representative.
180250265325325330
R-134a, R-22, R-507/404A
M808M313A818A825A328A537
2446 6 6
2222 2 2
1
/
1
4
81318.323.92837.1
11
34.55.5 8 8 8
7
/
8
5
/
8
7/
8
5/
8
→
7
/
16
11/
4
115/
32
115/
1750
450 PSIG
245 PSIG
11/
8
7/
8
NOTE: The 06DE8251 compressor unit with the 06DA825 compressor
replaces the 06DE8241 once inventory of the 06DA824 compressor is
depleted.
13/
7/
8
8
13/
8
7/
8
13/
11/
Table 2B — 07D Physical Data
UNIT 07DA203B205A208B210B212B215
OPERATING WEIGHT (lb)
REFRIGERANT
COMPRESSOR — 06D*
Cylinders
Bore (in.)
Stroke (in.)
Displacement (cfm at 1750 rpm)
Maximum Rpm
Oil Charge (pt)
High Side Maximum Pressure
Low Side Maximum Pressure
CONDENSER (Shell and Tube)† Part Number
Refrigerant Storage
Capacity (lb)
R-134a
R-22
Min Refrigerant Operating
Charge (lb)
REFRIGERANT CONNECTION (in. ODF)
Inlet
Outlet
WATER CONNECTION (in. FPT)
Inlet/Outlet
R-507/404A
LEGEND
FPT —
ODF —
*Compressor listed is the standard compressor for R-22, air conditioning
duty. An 06DR compressor is standard equipment for low temperature
(R-507/404A) or medium temperature (R-134a) applications. Factory
substitutions may be made. Contact Carrier Sales Representative.
†The condenser listed is for R-22, air conditioning duty and may change
based on the application. Maximum condenser operating pressure:
350 psi refrigerant side, 300 psi water side (“CX” models); 350 psi
refrigerant side, 150 psi water side (“AX” models).
NOTE: The 07DB210 with the 06DA825 compressor replaces the
→
07DB210 with the 06DA824 once the compressor inventory is depleted.
15/
11/
8
8
1
/
4
15/
11/
11/
8
8
4
15/
11/
11/
8
8
4
15/
11/
16
8
8
16
8
8
2
Table 3 — Factory Switch Settings
PRESSURE CHANGE AFFECTING
SWITCH TYPE
High Pressure
210 (±10) (psig)290 (±10) (psig)
Low Pressure
Oil Pressure
LEGEND
psid —
psig —
pounds per square inch differential
pounds per square inch gage
NOTES:
1. Values for the high- and low-pressure switches based on R-22.
For other refrigerants, reset to pressure corresponding to saturation temperatures indicated by the listed pressures.
2. Values for oil pressure are above operating suction pressure
(pressure differential between suction and discharge pressures
of oil pump).
SWITCH POSITION
ClosedOpen
70 (±4) (psig)60 (±4) (psig)
6 (psid)11 (psid)
CAPACITY CONTROL (Suction Cutoff Type)
Control Set Point (Cylinder Load Point) —
point is adjustable from 0 to 86 psig. Pressure differential
between cylinder load-up point and cylinder unload point is
adjustable fr om 7 to 19 p si.
To Regulate Control Set Point —
Turn adjustment nut clockwise to its bottom stop (with nut in
this position, set point is 86 psig). Control set point is then
regulated to desired pressure by turning adjustment nut counterclockwise. Every full turn decreases set point by 7.2 psi.
Approximately 12 turns in counterclockwise direction will decrease control set point to 0 psig. Table 4 shows steps of control
for the compressor and condensing unit.
Pressure Differential Adjustment —
ential adjusting screw counterclockwise to its back-stop position (differential in this position is 7 psi). Pressure differential is
set by turning adjustment screw clockwise. Every full turn
increases differential by 1.2 psi. Approximately 10 turns in
clockwise direction will increase pressure differential to 19 psi.
9
Refer to Fig. 7.
Turn differ-
Set
802
Page 10
CONTROL
SET POINT
ADJUSTMENT
NUT
POWER
HEAD
PRESSURE
DIFFERENTIAL
ADJUSTMENT
SCREW
VALVE BODY
BYPASS
PISTON RING
BYPASS PISTON-USED
WITH HOT GAS BYPASS
TYPE OF UNLOADING ONLY.
NOT REQUIRED WITH
SUCTION CUTOFF TYPE
UNLOADING.
DIFFERENTIAL SCREW
SEALING CAP (CAP MUST
BE REPLACED TO PREVENT
REFRIGERANT LEAKAGE)
Fig. 7 — Capacity Control Valve
(Pressure Type)
Table 4 — Capacity Control Reduction Steps
% Full Load Capacity
10067 4932
% Full Load kW
100735746
Number of Active Cylinders
24—2—
464—2
UNIT 06D,07D
ALL 4 CYLINDER
MODELS
ALL 6 CYLINDER
MODELS
NO. OF
CONTR
CYL
Capacity Control Pressure (Fig. 8)
LOADED OPERATION — Pressure-operated control valve
is controlled by suction pressure and actuated by discharge
pressure. Each valve controls 2 cylinders (one bank). On
start-up, controlled cylinders do not load up unt il differential
between suction and discharge pressures is approximately
25 psi.
When suction pressure rises high enough to overcome
control set point spring, the diaphragm snaps to the left and
relieves pressure against the poppet valve. The drive spring
moves the poppet valve to left and it seats in the closed
position.
With poppet valve closed, discharge gas is directed into the
unloader-piston chamber and pressure builds up against the
piston. When pressure against unloader piston is high enough
to overcome the unloader valve spring, piston moves valve to
the right, opening suction port. Suction gas can now be drawn
into the cylinders and the bank is running fully loaded.
UNLOADED OPERATION — As suction pressure drops
below set point, control spring expands, snapping diaphragm to
right. This forces poppet valve open and allows gas from
discharge manifold to vent through base of control valve to
suction side. Loss of full discharge pressure against unloaded
piston allows unloader valve spring to move valve left to
closed position. The suction port is blocked, isolating the
cylinder bank from the suction manifold. The cylinder bank is
now unloaded.
CONDENSER MAINTENANCE
To inspect and clean condenser, drain water and remove
condenser heads. To drain condenser , shut off water supply and
disconnect inlet and outlet piping. Remove drain plugs and
vent plug.
With condenser heads removed, inspect tubes for refrigerant
leaks. (Refer to C arrier Refr igerant Ser vice T e chniques Manual.)
Clean condenser tubes with nylon brush (available from
Carrier Service Department). Flush water through tubes while
cleaning. If hard scale has formed, clean t ubes chemically. Do
not use brushes that will scrape or scratch tubes.
Because the condenser water circuit is usually an open
system, the condenser tubes may be subject to contamination
by foreign matter. Local water conditions may cause excessive
fouling or pitting of tubes. Condenser tubes, therefore, should
be cleaned at least once a year or more often i f the water is
contaminated.
Proper water treatment can minimize tube fouling and
pitting. If such conditions are anticipated, water treatment
analysis is recommended. Refer to the Carrier System Design
Manual, Part 5, for general water conditioning information.
If hard scale has formed, clean the tubes chemically. Consult an experienced and reliable water-treatment firm in your
area for treatment recommendations. Clean the condenser by
gravity or by forced circulation as shown in Fig. 9 and 10.
IMPORTANT: If the ambient temperature is below 32 F
during a shutdown period; protect the condenser from
freezing by draining the water from the system or by adding antifreeze to the water.
10
Page 11
LEGEND
Fig. 11 — Compressor
(Bottom Plate Removed)
1—
Oil Pressure Relief Valve
5—
Eccentric Shaft
2—
Piston and Eccentric Strap Assembly
6—
Eccentric Strap Side Shield
3—
Motor End Counterweight
7—
Oil Suction Tube
4—
Oil ReturnCheck Valve
8—
Pump End Counterweight
FILL CONDENSER WITH
SUCTION
PUMP
SUPPORT
TANK
FINE MESH
SCREEN
RETURN
GAS VENT
PUMP
PRIMING
CONN.
GLOBE
VALV ES
1” PIPE
CONDENSER
REMOVE WATER
REGULATING VALVE
CENTRIFUGAL PUMP 1/2 HP
30 GPM AT 35’ HEAD
CLOSE VENT PIPE
VALVE WHEN
PUMP IS
RUNNING
CLEANING SOLUTION. DO
NOT ADD SOLUTION
MORE RAPIDLY THAN
VENT CAN EXHAUST
GASES CAUSED BY
CHEMICAL ACTION.
3’ TO 4’
1”
VENT
PIPE
PIPE
5’ APPROX
Fig. 9 — Gravity Circulation
Fig. 8 — Capacity Control Valve Operation
CONDENSER
Fig. 10 — Forced Circulation
11
Page 12
SERVICE
LEGEND
Fig. 11 — Compressor
(Bottom Plate Removed)
1—
Oil Pressure Relief Valve
5—
Eccentric Shaft
2—
Piston and Eccentric
Strap Assembly
6—
Eccentric Strap Side
Shield
3—
Motor End Counterweight
7—
Oil Suction Tube
4—
Oil Return Check Valve
8—
Pump End Counterweight
Do not remove the compressor terminal box cover until
all electrical power is disconnected and pressure is
relieved. Terminal pins may blow out causing injuries,
death, and/or fire.
Service Notes
1. Where compressor components are shown, they are in
normal order of removal from compressor.
2. For replacement items, use Carrier specified parts.
See Carrier 06D Specified Parts list for c ompressor part
interchangea b ilit y.
3. Before compressor is opened, the refrigerant must be
removed from it by the Pumpdown method.
a. Start compressor, close suction shutoff valve, and
reduce crankcase pressure to 2 psig (bypass low
pressurestat with jumper).
b. Stop compressor and isolate from system by
closing discharge shutoff valve.
c. Bleed any residual refrigerant. Drain oil if
necessary.
4. After disassembly, clean all parts with solvent. Use
mineral spirits, white gasoline or naphtha.
5. Before assembly, coat all parts with compressor oil and
clean and inspect all gasket surfaces . Replace all gaskets
with new standard specified gaskets, coated with
compressor oil. See Table 5 for typical torque values.
6. After reassembly, evacuate compressor and open suction
and discharge valves. Restart compressor and adjust
refrigerant charge.
Table 5 — Torque Values
Testing Oil Pump —
Observe oil level sight glass. The
oil pressure relief valve line is positioned to discharge oil
against sight glass. When oil does not discharge from this line,
it is an indication of low oil pump pressure.
If oil pump pressure is low, remove and check oil filter
screen, oil pressure regulator and oil return check valve.
OIL PRESSURE RELIEF VAL VE (Fig. 1 1) — Uns cr ew re-
lief valve assembly from motor partition plate, and be sure
assembly is not clogged or the plunger is not stuck.
OIL RETURN CHECK VALVE (Fig. 11) — Unscrew check
valve from motor partition plate. Be sure flutter valve is not
sticking and that it seats tightly .
OIL FILTER SCREEN (Fig. 12) — Screen is accessible
through bottom cover plate. Remove and inspect strainer for
holes and dirt. Clean it with solvent and replace.
OIL PUMP AND BEARING HEAD (Fig. 12) — The oil
pump assembly is contained in the pump end bearing head
aluminum casting. The pump end main bearing is a machined
part of this casting. An insert bearing is not required.
Remove Bearing Head Assembly from Crankcase
— Remove
in sequence (refer to Fig. 12 and 13): oil pump cover, oil feed
guide retaining spring, oil feed guide, pump drive segment. If
damage to the oil pump or main bearing is found, a new pump
end bearing head assembly should be installed.
Replace (Refer to Fig. 12 and 13)
— For torque values, refer
to Ta ble 5. Following steps are used to replace bearing head:
1. Bolt bearing head to crankcase. Place pump drive segment into position and secure to end of crankshaft with
cap screws and lock washers that were removed (see
Fig. 13).
2. Insert oil feed guide with large diameter inward and place
guide retainer spring over small diameter of guide.
3. Install gasket and oil pump cover.
SIZE
DIAM
(in.)
1
/
16
1
/
8
1
/
4
5
/
16
3
/
8
7
/
16
1
/
2
5
/
8
No. 10
1
1
/
2
NEF —
THREADS
PER IN.
27 (pipe)8-12Pipe Plug — Crankshaft
20 (pipe)6-10
20 (pipe)20-25Pipe Plug — Press. Gage Conn.
2010-12Connecting Rod Capscrew
28
18
16
1455-60Motor End Cover — Crankcase
1380-90Suction Service Valve
1125-30Crankshaft Spinner Tube
324- 6Oil Pump Drive Segment
CAP SCREWS
(NONINTERCHANGEABLE
WITH FLANGE COVER
CAP SCREWS)
BYPASS PISTON PLUG
SPRING
TAB
FLANGE COVER
CAP SCREWS
(NONINTERCHANGERABLE
WITH CONTROL VALVE
CAP SCREWS)
GASKET
GAS PORT
Fig. 14 — Removal of Capacity Control Valve
Fig. 15 — Removal of Bypass Piston Plug
Motor Cover Gasket
1—
Motor End Cover
2—
Discharge Manifold Connection
3—
Valve Plate Gasket
4—
Valve Plate Assembly
5—
Cylinder Head Gasket
6—
Cylinder Head
7—
Cylinder Head Washer
8—
and Cap Screw
Suction Manifold Connection*
9—
Suction Valve Positioning Spring
10 —
Suction Strainer
11 —
Bearing Head Gasket
12 —
Oil Pump Inlet Passage
13 —
Bearing Head Washer
14 —
and Cap Screw
Oil Pump Cover
15 —
Pump End Bearing Head
16 —
LEGEND FOR FIG. 12
Oil Drain Plug
17 —
Crankcase
18 —
Bottom Plate Gasket
19 —
Bottom Plate
20 —
Bottom Plate Washer and Cap Screw
21 —
Oil Filter Screen
22 —
Oil Return Check Valve
23 —
Oil Level Sight Glass
24 —
Motor Terminal Plate
25 —
Dowel Pins (For Suction Valve
26 —
Positioning)
Equalizing Tube and Lock Screw Assembly
27 —
Lockwasher
28 —
Rotor Lockwasher
29 —
Rotor Drive Key
30 —
Piston Pin Lock Ring
31 —
Piston Pin
32 —
Piston
33 —
Oil Ring
34 —
Compression Rings
35 —
Eccentric Strap
36 —
Eccentric Strap Side Shield
37 —
Pump End Counterweight
38 —
Oil Pump Drive Segment
39 —
Drive Segment Cap Screws
40 —
and Lockwashers
Oil Feed Guide
41 —
Oil Feed Guide Retainer Spring
42 —
Cover Gasket
43 —
Pump Cover Cap Screw and Washer
44 —
Counterweight Bolt
45 —
Eccentric Strap Side Shield
46 —
Motor End Counterweight
47 —
Locknut
48 —
Eccentric Shaft (or Crankshaft)
49 —
*Used to add compressor oil.
TOP
8
Suction Strainer
1—
Assembly
Oil Pump Bearing Head
2—
Assembly
Rotor Retaining Ring
3—
Oil Pump Drive Segment
4—
Fig. 13 — Removing Pump End Bearing Head
LEGEND
Oil Pump Rotor
5—
Drive Segment Cap
6—
Screws
Bearing Head Cap
7—
Screws
Oil Pump Inlet Passage
8—
Three Allen head cap screws hold capacity control valve in
1
place (Fig. 14). Remove screws using a cut-down
wrench, and pull valve from cylinder head.
3
/16-in. Allen
Remove same number of piston plugs from replacement
compressor as number of unloaders supplied with original
compressors. Three Allen head cap screws hold piston plug
2
assembly in place. Remove flange cover, gasket, spring and
bypass piston plug (Fig. 15). A tapped hole is provided in
piston to allow it to be pulled out. Hole has same thread
3
4
5
6
7
diameter as cap screws removed above.
Cylinder Heads —
Disassemble cylinder heads by re-
moving cap screws and prying up on side between cylinder
head and valve plate to break heads loose from valve plate. Do
not strike cylinder heads to break loose.
Check heads for warping, cracks and damage to gasket
surfaces. When replacing cylinder head, torque cap screws
30 to 35 lb-ft to prevent high to low side leak in center portion
of cylinder head gasket.
Service Replacement Compressors —
ment compressors are not equipped with control valves. One or
both side bank cylinder head(s) is plugged with a spring loaded
plug piston assembly. Compressor will run fully loaded with
piston plug(s) in place.
compressor (ensures proper val ves are used with correct set-
Transfer original capacity control valve(s) to replacement
ting). For sealing purposes, install a plug piston assembly into
each cylinder head of original compressor f rom which a control valve was removed.
Replace-
14
Page 15
Suction and Discharge Valve Plate Assembly
CYLINDER HEAD
GASKET
VALVE PLATE
GASKET
DISCHARGE VALVE
SCREW AND
LOCK WASHER
DISCHARGE
VALV E
VALVE PLATE
VALVE PLATE ASSEMBLY
DISCHARGE
VALVE STOP
DISCHARGE
PORT
HIGH-PRESSURE
CONNECTION
LOW-PRESSURE
CONNECTION
SUCTION
VALV E
VALVE PLATE
DOWEL PIN
SUCTION VALVE
POSITIONING
SPRING
Fig. 16 — Valve Plate Assembly
Fig. 17 — Suction Valve and Positioning
Springs in Place
(Fig. 16) —
compressor down and observing suction and discharge
pressure equalization. If a discharge valve is leaking, the
pressures will equalize rapidly. Maximum allowable discharge
pressure drop is 3 psi per minute after an initial drop of 10 to
15 psi in the first half minute.
If there is an indicated loss of capacity and discharge valves
check properly, remove suction and discharge valve plate
assembly and inspect suction valves.
IMPORTANT: This test procedure is not applicable to
compressors equipped with pressure actuated or solenoid
unloader valves due to rapid pressure equalization rate.
Check suction and discharge valves by disassembling
valve plate (see Fig. 16).
DISASSEMBLY — Remove cylinder head.
1. Remove discharge valve assembly: cap screws, valve
stops, valve stop supports and valves.
2. Pry up on side of valve plate, between valve plate and
cylinder deck, to remove valve plat e and expose suction
valves. Remove suction valves and suction valve positioning springs from dowel pins.
Inspect valves and valve seats for wear and dam age. See
Table 6. Check cylinder deck valve stops for uneven wear.
Replace valves if cracked or worn. If valve seats are worn,
replace complete valve plate assembly. If cylinder deck valve
stops are worn, replace compressor.
REAS S E M BLY — Do not interchange valves. Install suction
valve positioning springs on dowel pins. Assemble positioning
springs with spring ends bearing against cylinder deck
(Fig. 17). Springs bow upward. Place suction valves on dowel
pins, over positioning springs. Place valve plate on cylinder
deck, and reinstall discharge valve plate assembly. Retorque
discharge valve stop cap screws to 16 lb-ft. Replace cylinder
head. Be sure cylinder head gasket is lined up correctly with
cylinder head and valve plate.
Test for leaking discharge valves by pumping
COMPRESSOR PART
MOTOR END
Main Bearing DiameterMax
Journal DiameterMin
PUMP END
Main Bearing DiameterMax
Journal DiameterMin
CRANKPIN DIAMETERMin
THROWMax
THRUSTWASHERMax
ECCENTRIC DIAMETERMax
CONN. ROD DIAMETERMax
PISTON PIN BEARINGMin
CYLINDERS
BoreMax
Piston DiameterMin
Piston Pin DiameterMin
Piston Pin Bearing
Piston Ring GapMax
Piston Ring Side ClearanceMax
*Maximum allowable wear above maximum or below minimum factory tolerances
shown. For example: difference between pump end main bearing diameter and
journal diameter is .001 in. (1.3745 – 1.3735) per factory tolerances. Maximum
allowable difference is .004 in. (.002 + .002).
2. Remove motor end cover and screws holding disc type
strainer (Fig. 1 8) to c ove r.
3. Clean strainer with solvent or replace if broken or
corroded.
4. Replace strainer and motor end cover. Purge or evacuate
compressor before starting.
Motor Replacement —
replaceable. Stator is a press fit into motor housing. If compressor motor is damaged, replace compressor.
Terminal Plate Assembly —
bly is shown in Fig. 19. Do not disassemble for any reason except to replace the phase barrier, which may become damaged.
If refrigerant leakage or a ground short occurs, the entire terminal plate assembly must be replaced.
If it becomes necessary to remove the phase barrier, proceed
as follows:
1. Loosen and remove all terminal nuts.
2. Remove lock washers and wire terminals.
3. Loosen and disengage the center screw. (Do not try to
remove the screw.)
4. Lift the phase barrier off the terminal screws (the spacers
and the center screw are removed with the phase barrier).
IMPORTANT: Do not disturb the jam nuts on which the
phase barrier rests.
S
tator and rotor are not field
The terminal plate assem-
STRAINER SCREWS & WASHERS
SUCTION STRAINER
MOTOR END COVER
SUCTION SERVICE VALVE
BARRIER POSITIONING KEY (THIS SIDE IS
ADJACENT TO THE CYLINDER HEAD)
PHASE BARRIER
NO TERMINAL IN
THIS SECTION
TERMINAL NUMBERS ON
THIS SURFACE
VALVE GASKET
VALVE CAP
SCREW
TERMINAL
NUT(TYP)
Procedure for reassembling the phase barrier:
1. Place phase barrier over the terminal screws. B e sure po-
sitioning key is in the recess in the terminal plate before
proceeding further.
2. Place the spacers and wire terminals on the terminal
screws.
3. Place the lock washers and terminal nuts over the wire
terminals and tighten to specified torque (18 to 30 lb-in.).
4. Install the center screw through the phase barrier and
tighten to the specified torque (15 to 25 lb-in.).
NOTE: The design allows for clearance between the center
screw head and the phase barrier. Thus, the torque limit may
be reached before the screw head contacts the phase barrier.
This condition is acceptable.
Compressor Running Gear Removal
1. Remove pump end bearing head.
2. Remove motor end cover carefully to prevent damage to
stator. Support cover and lift of f horizontally until it clears
windings.
3. Remove bottom cover plate.
4. Remove equalizer tube assembly from motor end of
crankshaft (or eccentric shaft). If shaft turns , preventing
tube assembly from being loosened, block shaft with a
piece of wood.
5. Remove rotor using a jackbolt. Insert a brass plug into
rotor hole to protect end of crankshaft from jackbolt.
Support rotor while it is being removed to prevent stator
damage.
6. Remove connection rod caps from compressors using
connecting rods and crankshafts. Label caps and rods so
they may be reinstalled in same plate on crankshaft.
BLACK JAM NUTS
ON TERMINALS 8 & 9;
BRASS JAM NUTS ON
TERMINALS 1, 2 AND 3
CENTRAL SCREW (THREADS
INTO TERMINAL PLATE)
SPACER
(TYP)
LOCK WASHER
(TYP)
7. Remove bolts holding counterweights and eccentric strap
side shields to eccentric shaft. Remove eccentric strap
side shields. Remove pump end counterweight through
pump end bearing head opening. Motor end counterweight will remain on eccentric shaft until shaft is
removed.
8. Pull eccentric shaft or crankshaft out through pump end
opening. Guide eccentric straps from eccentric shaft
during removal process. Rotate shaft and tap it lightly to
prevent straps from jamming.
9. Remove eccentric straps or connecting rods and pistons
through bottom cover plate opening.
10. Disassemble connecting rods or eccentric straps from
pistons by removing lock ring(s) and piston pins. Remove
oil and compression rings from piston. Keep each piston
assembly together for proper reassembly.
Check all parts for wear and tolerances shown in Ta ble 6.
Check crankshaft (eccentric shaft) oil passages and clean if
clogged.
16
Page 17
PUMP END MAIN BEARING — This bearing is a machined part of the new aluminum oil pump and bearing head
casting. Disassemble bearing head. If bearing is scored or
worn, replace complete bearing head.
CRANKCASE AND MOTOR END MAIN BEARINGS — These bearings are not field replaceable. If bearings
are worn or damaged, replace compressor.
Compressor Running Gear Replacement
CRANKSHAFT — Install crankshaft through pump end,
carefully guiding it through main bearings. Replace rotor.
Attach equalizer tube assembly to motor end of shaft.
Eccentric shafts must be installed after piston assemblies.
Place motor end counterweight on shaft before inserting shaft
into compressor. See Piston Assembly Replacement.
PISTON ASSEMBLY — Attach connecting rods or eccentric
straps to pistons with piston pins and lock in place with piston
pin lock rings. Place lock rings with gap on the side.
They should be tight enough so they cannot be rotated by
finger pressure.
RINGS
1. Check ring gap by inserting each ring separately in
cylinder, approximately
be between .013 and .005 inch.
2. Install compression rings in top piston grooves with side
marked “Top” toward piston head. Install oil ring below
compression ring with notched end on bottom. Stagger
ring gaps around piston.
3. Measure side clearance between ring and piston
(T able 6). Check for free action.
PISTON ASSEMBLY REPLACEMENT
Compressors Using Crankshafts
and piston assemblies into cylinders. Place chamfered sides of
connecting rods against radius of crankpins. Install connecting
rod caps to matching connecting rods through bottom of crankcase. Be sure chamfered sides of caps are against radius of
crankpins. Caps are locked in plac e with cap screw s. Use 8 to
10 lb-ft to tighten cap screws.
Compressors Using Eccentric Shafts
strap and piston assemblies into cylinders. Install eccentric
shaft through pump end, carefully guiding it through
eccentric straps and main bearings. Install pump end counterweight to eccentric shaft and replace eccentric strap side
shields.
Turn crankshaft or eccentric shaft to be sure there is no
binding between bearing surfaces and journals. Replace oil
screen, bottom cover plate, valve plates and cylinder heads.
3
/8 in. from top. Ring gap should
— Install connecting rod
— Install eccentric
COMPRESSOR MOTOR BURNOUT
Do not attempt start-up with terminal cover removed.
Bodily injury or death may result from explosion and/or
fire if power is supplied to compressor with the terminal
cover removed or unsecured. See warning label on terminal cover.
Clean-Up Procedure —
the stator winding decomposes, forming carbon, water and acid
which contaminate refrigerant systems. Remove these contaminants from system to prevent repeat motor failures.
1. Close compressor suction and discharge service valves,
and bleed refrigerant from compressor. Save remaining
refrigerant in system.
2. Check control box for welded contactor contacts, welded
overload contacts or burned out heater elements. Che ck
terminal plate for burned or damaged terminals, insulation, and shorted or grounded terminals. Repair or replace
where nece ssa ry.
3. Remove suction and discharge shutoff valve bolts and all
other connections to damaged compressor. Remove
damaged compressor and replace with new compressor.
Replace liquid line filter drier with a drier of one size
larger.
4. Purge new compressor . Tri ple-evacuate, using the following procedure:
a. Evacuate to 5000 microns.
b. Break vacuum with system refrigerant. Pressurize
to 15 psig. Wait 20 minutes to remove moisture.
c. Re-evacuate to 5000 microns.
d. Repeat Step b.
e. Evacuate to 1000 microns or below if possible.
5. Place compressor in operation. After 2 to 4 hours of
operation, check compressor oil for signs of discoloration
and/or acidity. If oil shows signs of contamination,
replace oil charge, filter driers, and cl ean suction st rainer
with solvent. Repeat this procedure until oil stays clean
and acid free for 48 hours of operation.
If a hermetic motor burns out,
17
Page 18
PROBLEMCAUSEREMEDY
Compressor does not run.
Compressor cycles on low-pressure
control.
Compressor cycles on high-pressure
control.
Insufficient capacity.
Unit operates long or continuously.
LEGEND
Thermostatic Expansion Valve
TXV —
TROUBLESHOOTING
Read Safety Considerations on page 1 before proceeding
with troubleshooting.
Main power line open.Replace fuse or reset circuit breaker.
Safety thermostat tripped.Reset thermostat.
Condenser water pump not running — power off.Restart.
Pump binding.Free pump.
Incorrect wiring.Rewire.
Motor burned out.Replace.
Control stuck open.Replace control.
Loose terminal connection.Check connections.
Improperly wired controls.Check wiring and rewire.
Low line voltage.Check line voltage — determine location of
Compressor motor defective.Check motor winding for open or short.
Seized compressor.Replace compressor.
Low-pressure control erratic in action.Raise differential setting, check capillary for
Suction shutoff valve partially closed.Open valve.
Low refrigerant charge.Add refrigerant.
Plugged suction strainer.Clean strainer.
Defective TXV.Replace.
High-pressure control erratic in action.Check capillary tube for pinches. Set control as
Discharge valve partially closed.Open valve.
Air in system.Purge.
Condenser scaled (or airflow restricted).Clean condenser.
Receiver not properly vented, refrigerant backs
up into evap condenser.
Condenser water pump or fans not
operating.
Refrigerant overcharge.Purge.
Low refrigerant charge.Add refrigerant.
Control set too high.Reset control.
Expansion valve plugged.Clean or replace.
Inefficient compressor.Check valves and pistons.
Expansion valve setting too high.Lower setting.
Iced or dirty evaporator.Defrost or clean.
Evaporator too small.Add surface or replace.
Condensing unit too small.Add unit or replace.
Expansion valve too small.Raise suction pressure with larger valve.
Restricted or small gas lines.Clear restriction or increase line size.
Low refrigerant charge.Add refrigerant.
Control contacts fused.Replace control.
Air in system.Purge.
Partially plugged or plugged expansion valve or
strainer.
Defective insulation.Replace or repair.
Service load.Keep doors and windows closed.
Inefficient compressor.Check valves.
Condenser scaled.Clean condenser.
Restricted evaporator air.Defrost coil, clean filters and ductwork.
voltage drop.
Replace compressor if necessary.
pinches, replace control.
required.
Repipe as required.
Start pump or fans.
Clean or replace.
18
Page 19
PROBLEMCAUSEREMEDY
System noises.
Compressor loses oil.
Frosted suction line.
Hot liquid line.
Frosted liquid line.
Frosted expansion valve.
LEGEND
Thermostatic Expansion Valve
TXV —
Piping vibration.Support piping as required, check for loose pipe
Expansion valve hissing.Add refrigerant, check for plugged liquid line
Compressor noisy.Check valve plates for valve noise, replace
Insufficient compressor oil.Add oil.
Leak in system.Repair leak.
Plugged or stuck compressor oil return
check valve.
Oil trapping in line.Check piping for oil traps.
Crankcase heaters not energized during
shutdown.
Expansion valve admitting excess
refrigerant.
Shortage of refrigerant.Repair leak and recharge.
Receiver shutoff valve partially closed or
restricted.
Restricted catchall.Replace.
Restricted strainer drier.Replace.
Ice plugging TXV orifice.Apply hot wet cloth to TXV.
Moisture indicated by increase in suction
pressure.
Plugged TXV strainer.Clean strainer or replace TXV.
connectors.
strainer.
compressor (worn bearings), check for loose
compressor holddown bolts.
Repair or replace.
Replace heaters.
Adjust expansion valve.
Open valve or remove restriction.
Install drier.
19
Page 20
Copyright 2002 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book2244
Tab 1b2a2b3a
PC 802Catalog No. 530-608Printed in U.S.A.Form 06/07D-3SIPg 208027-02Replaces: 06/07D-2SI
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.