Installing, starting up and servicing this equipment can be
hazardous due to system pressures, electrical components and
equipment location (roofs, elevated structures, etc.). Only
trained, qualified installers and service mechanics should
install, start up and service this equipment.
When working on the equipment, observe precautions in the
literature, tags, stickers and labels attached to t he equipment
and any other safety precautions that apply. Follow all safety
codes. Wear safety glasses and work gloves. Use care in
handling, rigging and setting bulky equipment.
Electrical shock can cause persona l injury and even death.
Be sure power to equipment is shut off before installing or
servicing this equipment. There may be more than one
disconnect. Tag disconnect(s) to alert others not to turn
power on until work is completed.
BEFORE INSTALLATION
Check Shipment —
if shipment is damaged or incomplete.
Unit Location Considerations —
floor in a well-v entil ated ar ea. Pos itio n unit t o allow sufficien t
space for refrigerant and water connections and to service
compressor. Place unit so suction and discharge valves can be
easily reached and oil level checked. Do not install condensing
unit where temperature will fall below freezing.
Local water can cause excessive fouling or sealing of
condenser tubes. If such conditions are anticipated, a water
treatment analysis is recommended. Refer to Carrier System
Design Manual, Part 5, for general water conditioning
information.
Make provision in piping layout to drain and vent condenser
if system is to be shut down in winter.
File claim with shipping company
Locate unit on
INSTALLATION
Mount Unit —
Loosen compressor mounting bolts and remove shipping
blocks from under compressor. Tighten all 4 bolts on compressor. Next, loosen each bolt until the flanged washer can be
moved sideways with finger pressure.
NOTE: Be sure that compressor floats freely on mounting
springs.
Piping Connections —
lines to connections indicated on condenser unit (Fig. 1). Water
leaving condenser should not be connected directly into sewer
lines. Check local codes.
Attach refrigerant liquid and suction lines to condensing
units (Fig. 1); suction and discharge to compressor unit
(Fig. 2). When soldering or brazing piping to valves, disassemble valve or wrap it in a wet cloth to prevent heat damage.
Allow flexibility in suction line so compressor suction valve
may be moved aside for access to suction strainer.
Level unit and bolt firmly to foundation.
Attach water supply and return
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2244
Tab 1b2a2b3a
PC 802Catalog No. 530-608Printed in U.S.A.Form 06/07D-3SIPg 18027-02Replaces: 06/07D-2SI
DIMENSIONS (in.)
UNIT 07DWIDTH A
A203
B205
A208
B210
B212
B215
63
39
51
51
30
30
9
/
16
9
/
16
9
/
16
13
/
16
WATER CONNECTIONS FOR 07DB215 UNIT ONLY.
Fig. 1 — 07D Condensing Unit Dimensions
NOTES:
1. For standard service practices, such as troubleshooting and refrigerant charging, allow a minimum
2′-6″ clearance around the unit.
2. Recommended service space for condenser tube
removal is one condenser length at either end.
3. For compressor removal, allow a minimum 3′ wide
access aisle to and from the unit.
4. Local codes or jurisdiction may prevail for unit
clearances.
2
NOTES:
1. For standard service practices, such as troubleshooting and refrigerant charging, allow a minimum
2′-6″ clearance around the unit.
2. For compressor removal, allow a minimum 3′ wide
access aisle to and from the unit.
3. Local codes or jurisdiction may prevail for unit
clearances.
Fig. 2 — 06D Compressor Unit Dimensions
3
Install a solenoid valve (field supplied) in liquid line directly
before expansion valve. Solenoid valve is necessary for single
pumpout control used on 06D, 07D units. Refrigerant filter
drier and moisture indicator are shipped with 07D condensing
units for field installation. Install in liquid line according to
manufacturer’s instructions.
Relief valve located on top of condenser (07D units) will
open to relieve excessive pressure, allowing refrigerant to
escape. Most local codes require piping from safe ty device to
outdoors.
Refer to Carrier System Design Manual, Part 3, for standard
piping techniques.
COMPRESSOR UNITS — Connect high- and low-pressure
switch capillary tubes from control box to compressor. See
Fig. 2.
Install discharge line muffler (accessory) in discharge line
as close to compressor shutoff valve as possible.
Electrical Connections
UNBALANCED 3-PHASE SUPPLY VOLTAGE — Never
operate a motor where a phase imbalance in supply voltage
is greater than 2%. Use the following formula to determine
Maximum deviation is 4 volts. Determine % voltage
imbalance:
% Voltage Imbalance =100 x
4
233
= 1.7%
This amount of phase imbalance is satisfactory as it is below
the maximum allowable of 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
ELECTRICAL DATA NOTES
1. All 06D and 07D units are across-the-line start.
2. Wire sizes are based on TW type copper wire. Maximum
wire lengths based on data from Table 1 will result in a
1% voltage drop to compressor. Where up to 3% voltage
drop is allowed, the run length can be increased to 3 times
the length calculated from data in Table 1.
3. The 06D compressor unit electrical data shown in Table 1
does not apply for 06D compressors used as an integral
part of other Carrier equipment. See proper installation
book for electrical information.
WIRI NG — Power supply must correspond with unit nameplate electrical characteristics (units are internally wired at
factory for nameplate voltage). Field wiring must comply with
local and national codes.
Install a branch circuit fused disconnect of adequate size to
handle starting current.
LIN E POWER — Connect line power to the compressor con-
tactor C. For example, connect L1 to terminal 11, L2 to terminal 12 and L3 to terminal 13. See Fig. 3.
Table 1 — Compressor Electrical Data
COMPRESSOR
PART NUMBER
06D*
808
M
313
818
825
A
328
537
LEGEND
LRA —
MCC —
RLA —
*Refer to physical data table to match compressor with correct com-
pressor unit or water-cooled condensing unit.
NOTES:
1. RLA (rated load amps) value shown is: MCC ÷ 1.40 = RLA.
2. For minimum contactor sizing, use RLA value determined by:
Locked Rotor Amps
Maximum Continuous Current
Rated Load Amps
MCC ÷ 1.40 = RLA.
VO LTAGE
(3 Ph-60 Hz)
575
208/23017.412.4710.78
4608.76.235.53.1
575
208/2302719.31000.5
46013.59.6502.1
575
208/2304431.41600.42
4602215.7801.7
575
208/23055.539.61980.31
46027.819.8991.3
575
208/2306244.32280.26
4603122.11141.0
575
208/2308963.62660.18
4604028.61200.72
HPMCCRLALRA
3
5
6.5
7.5
10
15
MOTOR WINDING
RESISTANCE
(Ohms)
7528.45.0
10.87.7403.3
17.612.6642.6
22.215.9792.0
2517.9911.7
3222.9961.2
3. For wiring sizing, the RLA value can be determined by: MCC
÷
1.56 = RLA.
4. Compressor operating amps at any specific conditions can only
be determined from a performance curve.
5. RLA values for 06D compressor protected by a calibrated
circuit breaker will depend on must-trip value of circuit breaker.
6. Ohm values shown for resistance are approximate and shown
for reference only. Motors from different vendors and motors of
different efficiencies can differ up to 15% from data shown.
7. Electrical data for compressor part numbers 06DR and
50 Hz models (not shown) are available from Carrier Sales
Representative.
Auxiliary
Compressor Contactor
Crankcase Heater
Control Relay
Direct Expansion
Equipment
Fuse
Ground
High-Pressure Switch
Internal Protector
Liquid Line Solenoid Valve
Low-Pressure Switch
Cooling Tower Fan
National Electrical Code
Overload
Oil-Pressure Switch
Pumpout Relay
Start-Stop-Reset Switch
LEGEND
TB—
TM—
TR—
Terminal Block
Timer Motor
Timer Relay
Terminal Block Connector
Unmarked Terminal
Marked Terminal
Factory Wiring
Field Control Wiring
To indicate common potential only;
not to represent wiring.
Splice
NOTES:
1. Factory wiring is in compliance with NEC. Any field modifications
or additions must be in compliance with all applicable codes. Use
copper, copper-clad aluminum for field power supply only.
2. Field power supply wiring must be 75 C minimum.
3. Compressor thermally protected. Three-phase motors are protected against primary single-phasing condition.
4. Pilot duty control must be field supplied. Minimum contact rating
must be 25 va.
5. 60 Hz units have 120-volt control circuit. 50 Hz units have
230-volt control circuit. A separate source of supply at the correct
voltage must be field supplied through a fused disconnect device
Fig. 3 — Unit Label Diagram — 06D,07D Units
with a maximum rating of 15 A to TB2 connections
(Hot Side) and (Neutral).
6. Open control circuit disconnect switch for servicing only. Disconnect must remain closed for crankcase heater to operate.
7. A transformer of the following rating may be field supplied for
60 Hz units: 350 va.
8. Transformer must be fused and grounded per applicable codes.
9. If any of the original wiring furnished must be replaced, it must
be replaced with 90 C wire or its equivalent.
L2
5
L1
Compressor Unit Connections
— Extend power leads from
control center (contactor terminals) to compressor terminal box
and make connections as shown in Fig. 4.
Terminals 8 and 9 on motor terminal plate are for internal
protector connections. As shown in Fig. 4, run a wire from terminal 9 to terminal 6 on TB2 in control center and a wire from
terminal 1 on OL2 to terminal 2 on HPS in control center.
Run crankcase heater power wiring into control center.
Connect leads to terminal 5 on pumpout relay and terminal 3
on terminal block TB2. See Fig. 5.
Affix power warning label supplied in the installer ’s packet
to fused disconnect which energizes crankcase heater (see unit
label diagram).
CONT ROL WIRING — Control circuit power is 115 volts,
energized from an external source or from unit voltage through
field-supplied transformer. Transformer size required is 350 va
for 60 Hz units. External control power source must be
supplied through a 15-amp fused disconnect. Connect control
circuit power leads to terminal block TB2, terminals L1 and
L2. Terminal L2 is neutral potential (ground).
Compressor Protection
— The 06D and 07D units are factory
wired for single-pumpout control. Field addition and wiring of
line voltage remote control and liquid line solenoid valve is
required. (See unit Fig. 3 and Fig. 6.) Remote control minimum
contact rating must be 25 va. Solenoid valve must have a
maximum load rating of 50 va holding; 200 va inrush. For
applications with cooling tower, air-cooled or evaporative
condensers, add necessary auxiliary contacts in line between
compressor contactor and terminal A1 on timer. Insert desired
interlocks and overloads between terminals 5 and 9 on terminal
block TB2.
Control wiring may be modified as shown in Fig. 6 for
automatic pumpdown control; remove low-pressure switch
between timer relay and terminal 4 on TB2. Wire low-pressure
switch between terminals 9 and 6 on TB2. Add necessary
auxiliary contacts between compressor contactor and ter minal
A1 on timer. Remove wire between terminal 6 on TB2 and
terminal 3 on pumpout relay. Insert required interlocks and
overloads between terminals 5 and 9 on TB2.
Limitations —
Do not use automatic pumpdown control
on direct expansion cooler applications or when compre ssors
are equipped with pressure-type unloader valves. Pressure
unloader valves have built-in high to low passage which allows
compressor to cycle with automatic pumpdown.
LEGEND
C—
CH—
CR—
FU—
GND —
HPS —
IP—
LPS —
NOTES:
1. Factory wiring is in compliance with NEC. Any field modifications or
2. Field power supply wiring must be 75 C minimum.
3. Compressor thermally protected. Three-phase motors are protected
4. Pilot duty control must be field supplied. Minimum contact rating must
5. 60 Hz units have 120-volt control circuit. 50 Hz units have 230-volt con-
6. Open control circuit disconnect switch for servicing only. Disconnect
7. A transformer of the following rating may be field supplied for 60 Hz
8. Transformer must be fused and grounded per applicable codes.
9. If any of the original wiring furnished must be replaced, it must be
additions must be in compliance with all applicable codes. Use copper,
copper-clad aluminum for field power supply only.
against primary single-phasing condition.
be 25 va.
trol circuit. A separate source of supply at the correct voltage must be
field supplied thru a fused disconnect device with a max rating of 15 A
to TB2 connections (Hot Side) and (Neutral).
must remain closed for crankcase heater to operate.
units: 350 va.
replaced with 90 C wire or its equivalent.
L1
NEC —
OL—
OPS —
POR —
SW—
TB—
TM—
TR—
National Electrical Code
Overload Relay
Oil Pressure Switch
Pumpout Relay
Switch
Terminal Block
Timer Motor
Timer Relay
L2
Fig. 5 — 06D/07D Control Box Components and Connections (3-Phase)
6
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.