Carrier 040-420 User Manual

Page 1
Contrc
G
Y
040-420
with
h
CONTENTS
Page
SAFETY CONSIDERATIONS . . .
GENERAL . . . . . . , . . . . , . , . . . , . , . . . . , . , . . . . . . . . 2
MAJOR SYSTEM COMPONENTS . . . . . . . . . . . . 2-4
Processor Module
. . . . . . . . . . . . . . . . . . . . . . . . ...2
Low-Voltage Relay Module . , . . . . . . , . , . , , . . . . . 2
Electronic Expansion Valve Module . . . . . . . . . . . 2
Options Module . . . . . . . . . . . . . . . . *. . . . . . . . . . . . 2
Keypad and Display Module
(Also Called
HSIO
or LID)
Control Switch . + . . . , . . . . . . . . . . . . . . . . . . . . . . . . 2
Electronic Expansion Valve (EXV) . . . , . . . . . . . . 4
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...4
Compressor Protection Control
Module (CPCS) . . , . . . . . . . . . . . . . . . . . . . . . . . . . 4
OPERATION DATA . . . . . . . . . . . . . , . . . . , .
Capacity Control . . . . , , . . . . . . . . . . . . . . . . . .
Head Pressure Control . . 1 . . . . . + . . . . . . . . . . . . . 26
Pumpout
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...27
Keypad and Display Module
(Also Called
HSIO
or
ACCESSING FUNCTIONS AND :tiBFtiN?TI’dNS SUMMARY DISPLAY KEYPAD OPERATING INSTRUCTIONS STATUS FUNCTION TEST FUNCTION HISTORY FUNCTION SET POINT FUNCTION SERVICE FUNCTION SCHEDULE FUNCTION
TROUBLESHOOTING
Checking Display Codes Unit Shutoff
................................ 48
Complete Unit Stoppage Single Circuit Stoppage
Lag Compressor Stoppage .................. 48
+
. . . . , e +. . , . . , .
. . . . . . . . . . . . . . . . . . 2
+
. . . , 5-47
+
. . . . 5
LID)
......................
.....................
....................
.....................
1
28
48-67
48
48 48
l POWER FAILURE EXTERNAL TO THE UNIT
Alarm Codes
Compressor Alarm Circuit . . . . .
l EXV OPERATION l CHECKOUT PROCEDURE
Thermistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...60
a LOCATION
l THERMISTOR REPLACEMENT (Tl, T2, T7, T8)
l TRANSDUCER REPLACEMENT l PROCESSOR MODULE (PSIO), 4IN/40UT
_.-
-
I
Page
Restart Procedure . . . . . . . . . . . . . . . . . . . . . . . ...48
. . . . . . , . . . . . . . , . . . . . . . . . . , . . . . . 49
e +.
. . . . . . . . . . .
50
Electronic Expansion Valve . . . . . . . . . . . . . . . . , . 56
(Compressor and Cooler)
Pressure Transducers . . . , . . . , . . . . . .
l TROUBLESHOOTING
+
. . . + . . . . 60
Control Modules . . . . . . . . . . . . . . . . . . . . . . . , . . . . 64
MODULE (SIO), LOW-VOLTAGE RELAY MODULE (DSIO), AND EXV DRIVER MODULE (DSIO)
. RED LED
l GREEN LED l PROCESSOR MODULE (PSIO) l LOW-VOLTAGE RELAY MODULE (DSIO)
. 4IN/40UT MODULE (SIO)
ACCESSORY UNLOADER INSTALLATION
Installation . . . . . . . , . . . s . . . , . . . . s . . . . . . . .
l 040-110, 130 (60 Hz) UNITS
.‘.‘.
68-7 1
. 68
(and associated modular units)
l 130 (50 Hz), 150-210, 225, 250, and 280 UNITS
(and associated modular units)
FIELD WIRING . . . . . . . . . . . . , . . . . . . . . . . . . . . . 71-73
REPLACING DEFECTIVE PROCESSOR
MODULE (PSIO)
. . . . + s . . . . . . . + . . . . . . * . + .
73,74
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...73
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be hazardous due to system pressures, electrical compo­nents, and equipment location (roof, elevated structures, etc.). Only trained, qualified installers and service mechanics should install, start-up, and service this equipment.
When working on this equipment, observe precautions in the literature, and on tags, stickers, and labels attached to the equipment, and any other safety precautions that apply. Follow all safety codes. Wear safety glasses and work gloves.
Use care in handling, rigging, and setting this equipment, and in handling all electrical components.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5c
--I-
PC 903
Catalog No. 563-015 Printed in U S A.
Electrical shock can cause personal injury and death.
Shut off all power to this equipment during installation and service. There may be more than one disconnect switch. Tag all disconnect locations to alert others not
This unit uses a microprocessor-based electronic con­trol system. Do not use jumpers or other tools to short
out components, or to bypass or otherwise depart from recommended procedures. Any short-to-ground of the control board or accompanying wiring may destroy the electronic modules or electrical components.
Form
30GN-2T
pg
1
1-94 Replaces: 30GB,GT-1 T,
30GN-1T
Page 2
-%a-
GENERAL
IMPORTANT: This publication contains controls, op­eration and troubleshooting data for 3OGNO40-420 and
30GT225, 250, and 280
Circuits are identified as circuits A and B, and com­pressors are identified as Al, A2, etc. in circuit A, and
BI,
B2, etc. in circuit B.
Use this guide in conjunction with separate Instal-
lation Instructions booklet packaged with the
FlotronicTM
II chillers,
unit,
The
contrwsm
a low-voltage relay module (DSIO-LV), 2
consists of a processor module (PSIO)9
EXVs,
an EXV
driver module (DSIO-EXV), a 6-pack relay board, a key­pad and display module (also called HSIO or LID), ther­mistors, and transducers to provide inputs to the microprocessor. An options module (SIO) is used to pro-
vide additional functions. This module is standard on 30GN
modules and is a field-installed accessory on the 30GT
Flo-
tronic II units. See Fig. 1.
The 30G Series standard Flotronic II chillers feature microprocessor-based electronic controls and an electronic expansion valve (EXV) in each refrigeration circuit.
NOTE: The 30GN040 and 045 chillers with a
factory-
installed brine option have thermal expansion valves (TXV) instead of the EXV.
Unit sizes 240,270, and 300-420 are modular units which are shipped as separate sections (modules A and B). Instal­lation instructions specific to these units are shipped inside the individual modules. See Table 1 for a listing of unit sizes and modular combinations. For modules 24OB and follow all general instructions as noted for unit sizes
110.
For all remaining modules, follow instructions for unit
270B,
OSO-
sizes 130-210.
Table 1- Unit Sizes and Modular Combinations
UNIT MODEL
30G NO40 40
3OG NO45
30GN050
30EN060 60 30GN070 30GN080 80
NoT”o’NNs”L SE\WlK&N
45 50
70
-
-
-
-
- -
ssE%~N
-
-
-
Processor Module
ating software and controls the operation of the machine. It continuously monitors information received from the vari­ous transducers and thermistors and communicates with the
relay modules and
crease the active stages of capacity. The processor module also controls the EXV driver module, commanding it to open or close each EXV in order to maintain the proper super­heat entering the cylinders of each lead compressor. Infor­mation is transmitted between the processor module and re­lay module, the EXV driver module, and the keypad and display module through a 3-wire communications bus. When used, the options module is also connected to the commu­nications bus.
For the Flotronic II chillers, the processor monitors sys­tem pressure by means of 6 transducers, 3 in each lead com­pressor. Compressor suction pressure, discharge pressure, and oil pressure are sensed. If the processor senses high discharge pressure or low suction pressure, it immediately
shuts down all compressors in the affected circuit. During operation, if low oil pressure is sensed for longer than one
minute, all compressors in the affected circuit are shut down.
At start-up, the coil pressure signal is ignored for 2 min­utes. If shutdown occurs due to any of these pressure faults, the circuit is locked out and the appropriate fault code is displayed.
Low-Voltage Relay Module
contacts to energize compressor unloaders and/or compres-
30GNlfO 160 30GN190 30GN210
30GT225
30GN240 225 30GN130
30GT250
30GN270 260 30QN170
30GT280 1
30GN300 1 285 1
_...---
30GN330
30GN360
30GN390 30GN420
*60 Hz units/50 Hz units.
1 200 I
180
225
250
280
1
325 350 30GN190 30GNf 90/30GN170* 380 30GN210 400 30GN210
- -
-
-
I
-
-
-
I
30GNi
30 1 30GNf 70
30GNl70
-
-
30GNlOO
-
30GNi
-
30GN170
30GN190
30GN210
00
sors. It also senses the status of the safeties for all compres­sors and transmits this information to the processor.
Electronic Expansion Valve Module
ule receives signals from the processor and operates the elec­tronic expansion valves.
Options Module
tronic II features such as dual set point, remote reset, de-
mand limit, hot gas bypass, and accessory unloaders. The
options module also
activated from a remote 4-20 mA signal. The options mod­ule is installed at the factory on 040-210 and modular 240­420 units. It is a field-installed accessory for 225, 250 and 280 units.
Keypad and Display Module (also called HSlO or LID)
The Flotronic II control system cycles compressor un-
loaders and/or compressors to maintain the selected leaving
water temperature set point. It automatically positions the EXV to maintain the specified refrigerant superheat enter­ing the compressor cylinders. It also cycles condenser fans
on and off to maintain suitable head pressure for each cir­cuit. Safeties are continuously monitored to prevent the unit from operating under unsafe conditions. A scheduling func-
tion, programmed by the user, controls the unit occupied/ unoccupied schedule. The control also operates a test pro-
gram that allows the operator to check output signals and
ensure components are operable.
tion keys, 5 operative keys, 12 numeric keys, and an al­phanumeric g-character LCD. Key usage is explained in Accessing Functions and Subfunctions section
Control Switch
the position of the LOCAL/ENABLE-STOP-CCN switch. This is a 3-position manual switch that allows the chiller to be put under the control of its own Flotronic II controls, manually stopped, or put under the control of a Carrier Corn­fort Network (CCN), Switch allows unit operation as shown
in Table 2.
2
MAJOR SYSTEM COMPONENTS
-
This module contains the oper-
&pack
relay board to increase or de-
-
This module closes
-
This mod-
-
This module allows the use of
aIlows
for reset and demand limit to be
-
This device consists of a keypad with 6 func-
on
-
Control of the chiller is defined by
Flo-
page 28.
,,
:f
c
_.
Page 3
ELECTRONIC EXPANSION VALVES DRIVER MODULE
(DSIO EXV)
LOW-VOLTAGE RELAY MODULE
(DsroiLv)
TB-7
I
d
g-PACK
RELAY BOARD
B
;rt’EFUCER
SOURCE (PSI)
CCN -
TB -1
\- -.-...-
LEGEND
Zarrier
Comfort Network
c
“erminal Block
Fig. 1
KEYPAD;DISPLAY
MODULE (HSIO/LID)
30GN Control Panel (040-110, 240B, 270B Unit Shown)
-
GROUND FAULT INTERRUPTER
208/230-,
460-f%!-3-60-V
ONLY
COOLER
RELAY, B
,TB-3
FIELD
ZEol CONNECl
iEA1
rlON
I
‘ER
Page 4
In the LOCAL/ENABLE position, the chiller is under lo-
cal control and responds to the scheduling configuration and set point data input at its own local interface device (key-
pad and display module).
In the CCN position, the chiller is under remote control and responds only to CCN network commands. The occupied/ unoccupied conditions are defined by the network. All key­pad and display functions can be read at the chiller regard­less of position of the switch.
CCN run or stop condition is established by a command from the CCN network. It is not possible to force outputs from the CCN network, except that an emergency stop com­mand shuts down the chiller immediately and causes ‘ ‘ALARM 52” to be displayed.
Table 2 -LOCAL/ENABLE-STOP-CCN
Switch Positions and Operation
SWITCH
POSITION
STOP LOCAL/ENABLE
CCN :t2 1
I
UNIT
OPERATION
I
Unit Cannot Run Read/Write1 Read Only
Unit Can Run Unit Cannot Run Read Only Unit Can Run Read Onlv
Electronic Expansion Valve (EXV)
CONFIGURATION AND
SET POINT CONTROL
Keypad Control 1 CCN Control
Read/Limited Write Read
Only ReadlWrite
Read/Limited Write
-
The micro­processor controls the EXV through the EXV driver mod­ule. Inside the expansion valve is a linear actuator stepper motor.
The lead compressor in each circuit has a thermistor and a pressure transducer located in the suction manifold after the compressor motor. The thermistor measures the tem­perature of the superheated gas entering the compressor cyl­inders. The pressure transducer measures the refrigerant pressure in the suction manifold. The microprocessor con­verts the pressure reading to a saturated temperature. The
difference between the temperature of the superheated gas and the saturation temperature is the superheat. The micro­processor controls the position of the electronic expansion valve stepper motor to maintain 29 F (16 C) superheat.
At initial unit start-up, the EXV position is at zero. After
that, the microprocessor keeps accurate track of the valve
Compressor Protection Control Module (CPCS)
-
Each compressor on models 30GN070 (50 Hz), 080-
100, and 240B, 270B, has its own CPCS as standard equip- ment. All 30GN040-060 and 070 (60 Hz) units feature the CPCS as an accessory, and CR (control relay) as standard equipment. See Fig. 2. The 30GN130-2 10 and associated modular units and the 30GT225, 250, and 280 Flotronic II units have a CR as standard equipment. The CPCS or CR is used to control and protect the compressors and crankcase heaters. The CPCS provides the following functions:
compressor contactor control crankcase heater control compressor ground current protection status communication to processor board high-pressure protection
The CR provides all of the same functions as the CPCS with the exception of compressor ground current protec­tion. Ground current protection is accomplished by using a CGF (compressor ground fault) board in conjunction with the CR. The CGF provides the same ground fault function as the CPCS for units where the CPCS is not utilized.
One large relay is located on the CPCS board. This relay (or CR) controls the crankcase heater and compressor contactor. The CPCS also provides a set of signal contacts that the microprocessor monitors to determine the operating status of the compressor. If the processor board determines that the compressor is not operating properly through the signal contacts, it will lock the compressor off by gizing the proper 24-v control relay on the relay board. The CPCS board contains logic that can detect if the ground of any compressor winding exceeds 2.5 amps. If this condition occurs, the CPCS module shuts down the compressor.
A high-pressure switch with a trip pressure of 426 +
7
psig (2936 +_ 48 kPa), is wired in series with the CPCS.
If this switch opens during operation, the compressor stops
and the failure is detected by the processor when the signal contacts open. The compressor is locked off. If the lead compressor in either circuit is shut down by the high pres­sure switch or ground current protector, all compressors in
the circuit are locked off. position in order to use this information as input for the other control functions. The control monitors the superheat and the rate of change of superheat to control the position of the valve. The valve stroke is very large, which results in very accurate control of the superheat.
deener-
current-to-
Sensors
The Flotronic TM II chiller control system gath-
-
ers information from sensors to control the operation of the
chiller. The units use 6 standard pressure transducers and 4 standard thermistors to monitor
system
pressures and tem­peratures at various points within the chiller. Sensors are listed in Table 3.
Table 3 -Thermistor and Transducer Locations
THERMISTORS
Sensor
T:
Ti
TIO
Sensor
DPT-A SPT-A OPT-A
DPT-I3
SPT-B OPT-B
Cooler Leaving Water Temp Cooler Entering Water Temp Compressor Suction Gas Temp Circuit A Compressor Suction Gas Temp Circuit B Remote Temperature Sensor (Accessory)
PFIESSURETRANSDUCERS
Compressor Al Discharge Pressure
Compressor Al Suction-Pressure Compressor Al Oil Pressure Compressor Bl Discharge Pressure Compressor Bi Suction Pressure Compressor Bl Oil Pressure
Location
Location
PROTECTION BOARD
Fig. 2 -Compressor Protection Control Module
4
Page 5
OPERATION DATA
Capacity Control
compressor to give capacity control steps as shown in Tables 4A-4D. The unit controls leaving chilled water tem­perature. Entering water temperature is used by the micro­processor in determining the optimum time to add or sub-
tract steps of capacity, but is not a control set point.
The chilled water temperature set point can be automat-
-
The control system cycles
ically reset by the return temperature reset or space and out-
door air temperature reset features. It can also be reset from
an external 4-20 mA signal with a loop isolator, or from a network signal.
The operating sequences shown are some of many pos-
sible loading sequences for the control of the leaving water
temperature. If a circuit has more unloaders than another,
that circuit will always be the lead circuit.
UNIT
30GN
“““ft
Hr)
y-yy
,
040 (60 Hz) 045 (60 Hz)
AIt
040 (50 Hz)
0:; pg~l
,
040 (50 Hz)
o;y;,y
,
045 (50 Hz)
050f”,
Hz)
045 (50 Hz) 050 (60 Hz)
Alt,Bl**
045 (50 Hz)
050A\6$Hz)
045 (50 Hz)
yfyy2
I
045 (50 Hz)
*Unloaded compressor.
tCompressor unloader, standard.
**Compressor unloader, accessory.
ttTwo
unloaders, both unloaded.
CONTROL
STEPS
Table 4A-
: i
: i
:
:
1
:
4 5
1
:
4
i
1
;
4
:
:
5
: ;:
:
5 100
1
: z
6 7 100
1
32
4
i
7
Capacity Control Steps, 040-070
LOADING SEQUENCE A
%
Displacement Compressors
(AwrW
::
1~~
25
%
100
s;
1;:
24
::
1::
- -
- -
-
-
- -
- -
i:
1::
:A 8°F
100
is;
18
::
56
2
-
- -
- -
-
- -
- -
Al*
APB1
Al
:Bl
Al*
Al”B1
Al
,kl
Al”
Al”B1
Al
,k
Al*
Al% *
Al ‘,Bl
Al ,Bl
-
-
Al*
Al
Al *,Bl
Al ,Bl
Al*
Al% *
Al ‘,Bl
Al
,Bl
A2-y
y&tgi
Al
,i31
A2.p
Al;Bl*
Al
+,Bl
Al *,Bl
Al ,Bl
-
-
-
LOADING SEQUENCE
%
Displacement
tAppro
-
-
-
25
50
1::
-
-
-
:; El
100
::
53
i:
100
-
-
-
-
38
::
1%
-
-
-
-
-
-
-
-
-
-
-
-
El z7
64
1::
B
Compressors
-
-
-
-
Bl*
AIBlil
*
Al’,Bl
-
-
-
-
Bl*
Al& *
Al ,‘sl*
Al
.Bl
-
-
-
Bl”
Al%
*
Al,k
Al
.Bl
-
-
-
-
-
-
-
-
-
-
Al
,Bl
5
Page 6
Table 4A
-
Capacity Control Steps, 040-070
(cant)
UNIT
30GN
050 (50 Hz)
060G
Hz)
050 (50 Hz)
“g pgy
I
050 (50 Hz)
060A\~**Hz)
050 (50 Hz)
06g$,y
I
060 (50 Hz)
070fc
Hz)
060 (50 Hz)
07Odpto**Hz)
1
Y
1
6
1
I
I
I
LOADING SEQUENCE A LOADING SEQUENCE B
%
Displacement
tApw0
.
. . a
18
?I
56 73
Compressors
Compressors
1:;
28
-
-
-
-
-
15
Al*
Al”B1
Al
,k
Al*
Al% *
Al’,Bl
Al
,Bl
A&t!
#$Vg,
Al
,‘sl
yi!
-
-
-
-
-
A;p
Al~~Bl*
A$t!g’
Al ,‘sl
Al*
Al”Bl
Al
,i31
Al* Bl*
Al%
*
Al ‘.Bl
Al @I
A:$
AV$B1
Al .Bi
-
-
-
-
18
z:
8600
100
- -
-
- -
-
zi
66
83
100
-
-
-
-
“d,i;t)
-
-
-
-
-
-
Bl*
Al&l’
Al ,‘sl*
Al ,Bl
-
-
-
-
-
Bs’lt,t
Al’,Bi
-
-
-
Al&’
Al
.i31*
Ai,Bl
-
-
-
-
­i
-
-
060 (50 Hz)
oypg~)
,
*Unloaded compressor.
j-Compressor unloader, standard.
**Compressor unloader, accessory.
ttTwo
unloaders, both unloaded.
Ei:
83
100
Page 7
Table 4A- Capacity Control Steps, 040-070 (cant)
UNIT
060
30GN
(50 Hz)
1 _
. .
i
;.
“‘“G Hz)
oy&ya
,
%
Displacement
tApprod
16
2: :i
100
2
65
i;
100
Compressors
Al*
A-FBI
Al
,k
Al l ,A2,Bl
Al
,A2.B1 Al” Bl*
Al%
l
Al fB1
Al
,Bl
Al *,A2,Bl*
Al *,A2,Bl
Al
,A2,Bl Ai’,A2’,Bl
LOADING SEQUENCE A
T
LOADING S
%
Displacement
(Approx)
i! ii:
83
100
-
-
-
-
- -
- -
-
-
-
WENCE
Al*,A2,Bl*
Al
B
Al’,61
--
Al&
Al ,‘sl*
Al
,Bl
.A2.B1*
-
-
-
*
-
- -
- -
-
-
-
-
-
-
-
-
-
-
- -
15
::
-
57
ii
Al&
Al
Al
ylf,t
Al :Bt
,A2,Bl*
.A2.B1
l
070 (50
Hz)
Al
t**,Bl**
*Unloaded compressor.
tCompressor unloader, standard.
**Compressor unloader,
ttTwo
unloaders, both unloaded.
accessory.
A&’
Al
:Bl
Al ,A2,Bl*
Al
,A2,Bl
-
-
Page 8
,
Table 4B- Capacity Control Steps, 080-110 and Associated Modular Units
UNIT
30GN
080 (60 Hz)
Aly*,Blv
08Aqy;,y
,
I
LOADING SEQUENCE A LOADING SEQUENCE B
Compressors Compressors
Al*
Al
Al*,Bl*
Al *,Bi
Al
,Bl
Al
*,A2,Bl
Al
.A2.B1
Aiti
Al”
Al+yBl*
AA’;Jgl
Al ,Bl
Al
*.A2.B1
Al
,A2,Bl
- -
-
- -
-
-
-
-
-
-
Al
tt
Ai*.
Al+yBl*
Al ++,Bl
Al *,Bl
Al
,Bl
Al
*.A2.B1
Al ,k2,Bl
Al*
Al%
*
Al
$1
Al ,Bl
Al *,A2,Bl*
Al *,A2,Bl
Al
,A2,Bl
Al tt
Al*
Al+?Bl*
AWtSg
Al
,Bl
Al
++,A2,Bl
A4l&pi’&
Al
.A2,Bl
-
-
-
-
-
-
-
-
A;.$!
r
%
Displacement
(4wW
z! :: iii
100
-
-
- -
-
-
-
-
-
-
-
l
-
- -
- -
Bl*
Bi
Ai*,Bl*
Al,Bl*
Al
,Bl
Al
.A2.81*
Ai,A2,Bi
-
-
-
-
y-/i+
A$-hJ
Ai,Bl
Al
,A2,61*
Al
,A2,Bl
Be’lt,t
A;{:;:)
Al’,Bl
Ai,A2,Bl*
Al
,A2,Bl
-
Bl*
A&* Al,‘Bl*
Al
,Bl
Al
*,A2,Bi
Al ,A2,Bl*
Al
.A2.B1
,
,
-
-
-
-
-
-
B1
tt
Bl*
AIB:l
*
Ai,61
Al *,A2,Bl++
A;;“A’;“Wt
Ai.A;,Bl
y&f
*
AIBlk
Al+?Bl*
080
(SO Hz)
Aif”*,6if**
*Unloaded compressor.
+Compressor unloader, standard
**Compressor unloader, accessory
++Two
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
AJ&t,$
Al ++,A2,Bl*
AAit,-bA&l
Al
Al ,Bl
,A2,Bl
Ai,Bl
Al
*,A2,B1++
“d;“A’;“B’lt’t
Ai,Ai,Bi
-
-
*
Page 9
Table 4B- Capacity Control Steps, 080-110 and Associated Modular Units (cant)
UNIT CONTROL
30GN
090 (60
Hz)
STEPS
Aly*,Blt
l-
Displacement
LOADING
%
VNwW
:; E
53
65: ii
91
-
-
-
-
-
-
-
-
-
iQUENCE
!
A
Compressors
Al*
Al%
*
Al ‘,Bl
Al ,Bl
Al *,A2,Bl*
Al *,AZ,Bl
Al
,A2,Bl
Al *,A2,Bl
Al *,A2,Bl
Al ,AZ,Bl,B2
A;!tf2UJ$
Al
Al *,A2,Bl
Al
*,B2
,B2
A2.p
A;,%&1
Al*:B 1
Al*A2 bl
tT,A2,i31 ,B2
,B2
,A2,Bl ,B2
-
-
-
-
-
-
-
-
-
-
-
-
LOADING
%
Displacement
(Approx)
;; ii 2; r3: ::
100
-
-
-
-
-
-
-
-
-
-
-
1
:QUENCE B
Compressors
Al
Al
Bl*
Al%*
Al,Bl*
Al ,Bl
Al *,Bl l ,B2
Al
,Bl *,B2
Al,Bl,B2
*,A2,Bl
Al
,A2,Bi *,B2
Al
.A2.B1 .B2
-
-
-
-
-
-
-
-
-
-
-
-
A;,:&>
Al’,Bl
Al
,Bl
tT,B2
Al
,Bl *,B2
Al
,Bl ,B2
,A2,Bl
t-t,82
Al
.A2.B1 *.B2
Al’,A&Bl
Bitt
BP’
*,B2
,B2
090 (60
Hz)
Alt**,BlY*
*Unloaded compressor.
tCompressor
**Compressor unloader, accessory
TtTwo
NOTE: These capacity control steps may vary due to lag compressor sequencing.
unloader, standard.
unloaders, both unloaded.
Al *,A2,Bl
Al
Al tt,A2,Bl
Al*,A2,Bl
Al
,A2,Bl ,B2
Al%1
Al ‘,Bl
Al
Al *,A2,Bl*
Al *,A2,Bl
Al
Al *,A2,Bl:,B2
Al
*.A2.B1 .B2
Al ,k2,Bi
Al;;
Al*,Bl
Al
Al tt,A2,81 l
Al tt,AP,Bl
Al
Al
Altt,A2,Bl*,B2
Al tt,A2,Bi
Al *,A2,Bl
Al
.A2.61 .B2
,A2,Bl
Al*
,Bi
,A2,Bl
A;:!
Bl
,Bl
*,A2,61
,A2,Bl
,B2
*
,B2
,B2
,B2
,B2
80 82
91
-
-
-
-
-
-
-
-
-
-
-
“d,:;tJ
Ai,Bl
AAli
BB’lt,t~~2
Ai,Bl
Al
Al*,A2,Bl
,B2
,A2,Bl TT,B2
Al .A2.Bl*.B2
Al’,Ai, Bl
Al .A2.Bl
Al’,Ai,Bi
Bi*
Al&
Al ,Bl*
Al
,Bl
Al*,Bl*,B2
Al,Bl*,B2
Al ,Bl
,B2
-
-
,B2
*
-
-
-
-
*,B2
*.B2
,B2
9
Page 10
Table 4B- Capacity Control Steps, 080-110 and Associated Modular Units (cant)
UNIT
30GN
090 (50 Hz)
Alt,Bly
090 (50 Hz)
Al t**,Bl t**
100, 2408,
100,24OB,
270B (60 Hz)
Alt**,Blt
CONTROL
STEPS
r
Displacement
LOADING LOADING SEQUENCE B
%
(APPW
-
-
Compressors Compressors
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
T
Displacement
(4wW
100
%
7
:;’ ii
43
Pii
60
7”: Ei
A$!!
Al;;
Bl
Al
+I
Al
,Bl
Al
tt,AZBl
Altt,A2,Bl*
AlTT,A2,Bl
Al *,A2,Bl
Al
Al tt,A2,Bl
Al
TT,A2,Bl ,B2
Al*,A2,Bl
Al
Al *,A2,Bl*
;;*J.p;
Al *,A2,&
Al *,A2,Bl
Al
AltAt Bl
Al Tt,A2,Bl*
Al Tt,A2,Bl
Al
Al
Al tt,A2,Bl
Al Tt,A2,Bl
Al
Al
tt
,A2,Bl
*,B2
,B2
.A2,Bl .B2
Al*
Al%
*
Al (61
Al ,Bl
*,B2
,B2
,A2,Bl ,B2
“Alt!
Al*,&
Al ,Bl
*,A2,61
,A2,Bt
*,B2
,B2
*.A2.B1 .B2
,A2,i31,‘82
-
-
-
- -
- -
- -
-
-
-
-
- -
-
Al*,BlTT,BZ
“d;B~ltt~~2
A1’,Bl*k
Al *,A2,Bitt,Bl
Al ,A2,BlTt,Bl
A.i‘J;,;;
II
I
BB’.p
A;;:;H
Al’,Bl*
Al*,Bltt,B2
Al
,Bi TT,B2
Al ,Bl”,B2
Al
,Bl ,B2
Al
tt,AZBl
Al *,A2,Bl
Al ,A2,Bl
Al ,A2,61*,62
Al
,A2,Bl
Al*
Al% *
Al ‘,Bl
Al
,Bl
Al *,A2,Bl*
Al *,A2,Bf
Al
,A2,Bl
Al *,A2,Bi*,B2
Al *,A2,Bl
Al
,A2,Bl ,B2
-
-
i;2
tt,B2
j-T,B2
TT,B2
B2
,B2
100,24OB,
270B (60 Hz)
Alt,Blt^*
i
10
-
-
- -
-
-
-
-
*Unloaded compressor
+Compressor unloader, standard.
**Compressor unloader, accessory.
TtTwo unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing
10
-
-
-
-
Ai,-Bi
Al*.Bltt.B2
-
-
Al ,A2,BltT,B2
Al
.A2.B1 *.B2
Al’,A$Bl
,B2
Page 11
Table 40- Capacity Control Steps, 080-I IO and Associated Modular Units (cant)
UNIT
30GN
100, 2406,
270B (60 Hz)
Alr*,Blr
100,
240B,
2708 (50 Hz)
A1tW-t
100,
240B,
2708 (50 Hz)
Aft**,Blt
i ;
9
:: E
14
LOADING SEQUENCE A
%
Displacement
(Awr
ox)
8
100
:;
26
100
7
Compressors
Altt
Al*
A$;g
Al ,bl
Al tt,A2,61*
Al tt,A2,61
Al *,A2,Bl
Al
,A2,Bl
Al tt,A2,Bl
Al tt,A2,Bl
Al *,A2,Bi
Al
.A2.B1 .B2
Al*
Al%
Al :Bl
A1
Al
*,A2,Bl*
Al *,A2,Bl
Al
,A2,Bl
Al
*,A2,Bl *,B2
Al*.A2.81
Al
,‘A2@1,82
Al tt
Al*
Wtf2Z$’
Al
,kI2,i31
Altt,A2,Bl
Al tt,A2,Bl
Al *,A2,Bl
Al .A2.Bl.B2
- -
:
:
5
100, 2408,
270B (50 Hz)
Alt,Blt**
100, 2408,
270B (50 Hz)
Alr*,Blt”*
*Unloaded compressor.
tCompressor unloader, standard
**Compressor unloader, accessory.
tfTwo
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
6
8’
9
::
12
::
: i ii ;
9
:: E ::
16
- -
-
- -
- -
- -
-
- -
- -
-
-
- -
­Altt
A;,;h; 1
Al
Al
tt,AZBl
Al
tt,A2,Bl*
“A’p/pg
A1*iI2
Al tt,/i2,Eil tt,B2
Altt,A2,Bl*,B2
Altt,A2,Bl
Al
l ,AZ,Bl ,B2
Al ,A2,Bl
Al*
,Bl
-
-
-
-
-
-
,‘sl
bl
*,B2
,B2
$32
*
.B2
*,B2
,B2
,B2
,B2
,B2
tt
r
Displacement
%
(Apex)
100
-
-
-
-
-
-
LOADING
8
:i :A 20” :: ;“7 E-
-
-
-
-
-
-
EQUENCE B
Compressors
Bitt
Bl*
Al
“B: tt
Ai,Bl*
Al ,Bl
Al*,Bltt,B2
“A;“B’lt”tb;2
Al’,Bl
Al
*,A2,Bl
Al
,A2,Bi
Al ,A2,Bl l ,BZ
Al
.A2,Bl ,B2
Bl*
Al%
Al,bl*
Al
Ad;g *‘8822
Al’,Bl*b2
Al *,A2$1
Al .A2.B1 l .B2
Al’,Ai,Bl
Bitt
Bl*
Ai,F;hJ
Al’,Bl
Al*,Bl
Al
,‘Bl
Al
,Bl *,B2
Al ,Bl,B2
Al*,A2,Bl tt,B2
Al
,A2,Bl
Al
.A2,Bl *.B2
Al
Ai,Bi*
Al,Bl
Al
tt,Bl
Al *,Bl tt,B2
AAlj
“B’(t;3122
Al’,Bl
Al
tt,AZBl
Al *,A2,Bl tt,B2
Al
,A2,Bl
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
,b2
tt,B2
tt,B2
,Bl
-
-
-
-
-
-
-
-
-
-
-
-
-
-
tt.132
ff,‘B2
tt,B2
:li
t+
tt,B2
,b2
tt,B2
*
*,B2
,B2
tt,B2
11
Page 12
-
Table 48-
Capacity Control Steps, 080-110 and Associated Modular Units (cant)
UNIT
30GN
LOADING SEQUENCE A
%
Displacement
(ApprW
14
;A :: s6: 2
-
-
-
-
-
-
-
-
Compressors
Al*
&I *
Al ‘,Bl
Al
,Bi
Al l ,A2,Bl*
Al *,A2,Bi
Al
,A2,Bl
Al*,A2,Bl*,B2
Al
*.A2.B1 .B2
Al
,A2,Bl ,i32
A/p
A;;;#
Al
,Bl
Al Tt,A2,Bl*
Al
t-/-,A2,Bl
Al*,A2,Bl
Al
,A2,Bi
Al Tt,A2,Bl
Al -ft,A2,Bi
Al
Al ,k2,Bl
*,B2
,B2
*.A2.B1 .B2
,B2
-
-
-
-
-
-
-
-
-
-
A’tt
Al”
r
Displacement
LOADING SEQUENCE B
%
(Amrox)
-
-
-
-
-
-
-
-
-
-
Compressors
81”
Al51 *
Al,Bl*
Al
,Bl
;;*gg
Ai’,Bl
Al ,A2,Bl
Al ,A2,Bl
,B2
*,B2
,B2
Al*,A2,Bl*,B2
-
1
-
-
-
-
-
-
-
-
B1
tt
Bl*
Al !%
tt
Ai ,Bi*’
Al
,Bl
Al*,BlTT,B2
“A;
BB’~t;3”2’
Al’,Bl
,A2,Bl
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
y&v
,B2
tT,B2
Al *,A2,Bl tT,B2
Al
A;;hgl
Al ,Bl
110 (60 Hz)
Al
t**,Bl Y
110 (50 Hz)
Alt,Blt
*Unloaded compressor.
TCompressor unloader, standard
**Compressor unloader, accessory.
TtTwo
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing
A’tt,AZBl
Al tt,A2,Bl*
$-t&Z3
Al
,A2,Bl
Al
tt,A2,Bl
Al Tt,A2,Bl
Al*.A2.B1
Al
,A2,Bl ,B2
Al*
Al% *
Al’,Bl
Al ,Bl
Al *,A2,Bl*
Al l ,A2,Bl
Al
,A2,61
Al
*,A2,Bl *,B2
Al *,A2,Bl
Al .A2Bl
tt
*,B2
,B2
.B2
,B2
.B2
100
A;,=.$
Ai,Bl
Al *,Bl tT,B2
“A;
B!&lW22’
Ai,Bl
Al
Al *,A2,Bl tt,B2
A-l ,A2,Bl
Al *,A2,Bl
,B2
ttNB’ttB2
.A2.B1 *.B2
Al’,Ai,Bl
Bl*
Al%
Al ,Bt*
Al
,Bi
Al l ,Bl
Al ,Bl
Al
,Bl ,B2
A;,Ai,Bl
tT,B2
*,B2
*,B2
Al
Al .A2,Bl*.B2
,i32
*,B2 ,B2
12
Page 13
Table 4B
-
Capacity Control Steps, 080-110 and Associated Modular Units (cant)
UNIT
30GN
110 (50 Hz)
Alt**,Blt
CONTROL
STEPS
LOADING
%
Displacement
UWrW
-
-
SEQUENCE A
Compressors
*$#l
Al ,Bl
“A:tkA2’i3BI~
AleA2
Al tf,A2,Bl
Al *,A2,Bl
Al
,AZ,Bi ,B2
-
-
110 (50 Hz)
Alt,Blv
-
-
-
-
-
-
-
:
a
Al;; Bl
110 (50 Hz) z
Alt**,Blt**
*Unloaded compressor.
TCompressor unloader, standard.
**Compressor unloader,
TTTwo
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing
i 9
::
12
accessory
Al *,Bl
Al ,Bl
*&Wf22il”l’
Al*A2 Bl
Al tt,A2,Bi
Al *,A2,Bl
Al
,A2,Bl ,B2
A2.p
-
-
-
-
-
-
-
-
-
-
-
-
*;$T
Bl
,B2
,B2
,B2
,B2
T
LOADING :
%
Displacement
(Arwox)
-
-
-
-
-
-
-
-
-
-
-
-
a
,QUENCE B
Compressors
Be’lt,t
*;,F;:t
Al’,Bl
“A;W&3$
Ai,Bi
Al
,A2,Bl
Al ,A2,Bf
Al
.A2,Bl ,B2
“B’p
~,;~~J
AI’,Bl
Al ,BltT,B2
Al
,Bl *,B2
Al
Al
,A2,Bl
Al
,A2,B1 *,B2
Al
.A2.B1 .B2
-
-
-
-
-
-
-
-
-
-
-
,B2
tt,B2
,Bi ,B2
tt,B2
*,82
13
Page 14
Table 4C- Capacity Control Steps, 130-210 and Associated Modular Units
30GN
130,
130,
130,
UNIT
240A,
240A,
240A,
T-
Displacement
LOADING
%
Mvrox)
:‘:
:fz
2; ;i Ei
100
-
-
-
-
-
-
-
-
-
-
-
-
-
-
EQUENCE A
Compressors
Al*
Al% *
Al ‘,Bl
Al ,Bl
Al *,A2,Bl*
Al *,A2,Bl
Al
,A2,Bl
Al
*,A2,Bi
Al*,A2,Bl
Al
.A2.B1 .B2 ’
Al’tt
Al*
AlgBl’
A$t;l”i’
Al
Al
tt,A2,Bi
Al tt,A2,B1
Al *,A2,Bl
Al
,A2,Bl
Al tj-,A2,Bi*,B2
Al tt,A2,Bl
Al
*.A2.B1 .B2
A? ,iI2,-Bl ;B2
yp
*,B2
,B2
r
LOAD11
%
Displacement
VVwr ox)
:i z
2; ;: K
100
-
-
-
EQUENCE B
Compressors
Bl*
Al&’
Al
Al ,Bl
Al l ,Bl l ,B2
Al ,Bi
Al ,Bl
Al?,A2,Bl
Al ,A2,Bf*,B2
Al
,A2,Bl ,B2
‘-
-
-
,k*
*,B2
,B2
*,B2
-
-
-
,kH
*
-
-
-
-
-
-
,B2
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
BJ.fJ
;-y;;;;
Ai,Bi*
Al ,Bl
Al *,Bl tt,B2
“A;B&t$&2
Al’,Bl ,k2
Al *,A2,Bl tt,B2
Al ,A2,Bl tt,B2
Al
,A2,Bl
*,B2
Al
,A2,Bl ,B2
BB’!!
AlRBl’
AAlt,t&’
130,
240A,
130,24OA,
*Unloaded compressor
tCompressor unloader, standard.
**Compressor
ttTwo unloaders, both unloaded
NOTE: These capacity control steps may vary due to lag compressor sequencing+
unloader,
accessory
Al
Al
ttA2,Bl
Al tt,A2,Bl*
Al tt,A2,Bi
Al
*.A2.B1
Al
,iI2,‘Bi
Al
ttAW1
Al tt,A2,Bl
Al tt,A2,Bl
Al
*.A2,Bl .B2
Al
,k2&,82
Al*
A&l
Al ‘,Bl
Al ,Bl
Al *,A2,Bl l
Al *,A2,Bl
Al
,A2,Bl
Al
*,A2,Bl
Al*,A2,Bl
Al
,A2,Bl ,B2
Al
*,A2,A3,Bl *,B2
Al
*,A2,A3,Bl ,B2
Al
.A2.A3.Bi .B2
,kl
tt
tt,B2
*,B2
,B2
*
*,B2
,B2
Al*%++
Al.,Bl
Al t-t-41 tt,B2
Al *,Bl tt,B2
“A;
BB’~~~~2
Al’,Bl ,k2
Altt,A2,Bltt,B2
Al l ,A2,Bl
Al ,A2,Bl tt,B2
Al
Al’,A2’,Bl ,i32
Al*,A2,Bl
Al ,A2,Bl*,B2
Al *,A2,A3,Bl
Al qA2qA3.81 *.B2
.A2.B1 *.B2
Bl*
Al&
Al,kl*
Al
,Bl
Al *,Bl
Al ,Bl
Al ,Bl
Al
,A2,Bl ,B2
tt,B2
*
*,B2
*,B2
,B2
*,B2
*,B2
14
Page 15
Table 4C- Capacity Control Steps, 130-210 and Associated Modular Units (cant)
UNIT
30GN
130, 24OA,
130,24OA,
CONTROL
STEPS
r
Displacement
LOADING SEQUENCE A
%
hwrox)
6
-
-
-
-
-
-
-
Compressors
“drt,t
AlPtlBl*
Al
tt,Bl
Al l
,Bl
Al
,Bl
Al tt,A2,Bl*
“A’:t;P22~7El
Al*A2 Bl
Al tt,A2,Bl
Altt,A2,Bl
Al *,A2,Bi
Al
,A2,Bl ,B2
Al tt,A2,A3,Bl
Al tt,A2,A3,Bl
Al *,A2,A3,Bl
Al
,A2,A3,Bl ,B2
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
A$v
*,B2
,B2
,B2
*,B2
,B2
,B2
T
Displacement
LOADING SEQUENCE B
%
(Awrox)
-
-
-
-
-
-
-
-
-
-
-
-
Compressors
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Bitt
Bi*‘
AIB&
Al’,Bl
Al *,Bl tt,B2
Al ,Bl tt,B2
Al
,Bl
Al ,Bl
Al
,A2,Bl
Al ,A2,Bl*,B2
Al
,A2,Bl ,B2
Al
,A2,A3,Bl
Al
,A2,A3,Bi *,B2,B3
Al
,A2,A3,Bl ,B2,B3
B;.p
*
*,B2
,B2
tt,B2
tt,B2,B3
Al;t:Bl*
A;;Jbg’
Al
,Bl
130,
240A,
*Unloaded compressor.
tCompressor unloader, standard.
**Compressor unloader, accessory
ttTwo
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
Al tt,A2,Bl*
A;~tA$2’~1
Al*A2 Bl
Altt,;22,Bl*,B2
Al tt,A2,Bl
Al
*,A2,Bi ,B2
Al
,A2,Bl ,B2
Al tt,A2,A3,Bl*,B2
Altt,A2,A3,Bi
Al*,A2,A3,Bl
Al
,A2,A3,Bl ,B2
Al’
Al
Al *,Bl*
Al *,Bl
Al
,Bl
Ai*,A2,Bl*
Al l ,A2,Bl
Al
,A2,Bi
Al
*,A2,Bi
Al *,A2,Bl
Al
,A2,Bl ,B2
Al*,A2,A3,Bl
Al
*,A2,A3,81 ,B2
Al
,A2,A3,Bl ,B2
,B2
,B2
l ,B2
,B2
*,B2
,B2
AIBIL
*
Ai,Bi
Al l ,Bl
tt,B2
Al .Bl tt.B2
At
,Bf’*;B2
Al ,Bl
Al
Al
Al ,A2,A3,Bl l ,B2
Al
,B2
.A2.B1
tt.B2
Ai
,A2,Bl’*;B2
Al
,A2,Bl ,B2
,A2,A3,Bl
,A2,A3,Bl ,B2
-
-
tt,B2
-
-
-
Bi*
A&l
*
Al ,Bl*
Al ,Bl
Al
*,Bl
*,B2
Al ,Bl
*,B2
Al
,Bl ,B2
Al l ,A2,Bl l ,B2
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
Al l ,A2,A3,Bl *,B2
Al ,A2,A3,Bl*,B2
Al
,A2,A3,Bl ,B2
15
Page 16
Table 4C- Capacity Control Steps, 130-210 and Associated Modular Units (cant)
EQUENCE ALOADING
UNIT
30GN
%
Displacement
(Apwxl
6
::
Compressors
y-p
AlPtlBl’
:“;
zi
49 53
ii i:
ii:
95
100
-
-
-
-
-
- -
-
- -
- -
- -
150 (60 Hz)
Aly*,Blt**
15Aq y4
I
*Unloaded compressor.
tCompressor unloader, standard
**Compressor unloader, accessory.
ttTwo
unloaders, both unloaded
NOTE: These capacity control steps may vary due to lag compressor sequencing
“Att;l”l’
Al
,‘sl
AWh$Y;
Al ,A2,&
Altt,A2,Bi*,B2
Al tt,A2,Bl
Al *,A2,Bl
Al
,A2,Bl ,B2
Al tt,A2,A3,Bl
Al
*,A2,A3,Bl ,B2
Al
.A2.A3.81 .B2
-
-
-
-
-
-
-
-
-
$y!
Al;Bl*
Al tt’,Bl
Al *,Bi
Al ,Bl
Al
tt,A2,Bl
Al *,A2,Bl
Al
,A2,81
Al tt,A2,Bl
Al tt,A2,Bl
Al
*,A2,Bl ,B2
Al
,A2,Bl ,B2
Altt,A2,A3,Bi
Al
*,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2
Ai*
Al%
Al ‘,Bl
Al
Ai*,A2,Bl*
Al
*,A2,Bl
Al
,A2,Bl
Ai*,A2,Bl*,B2
Al*,A2,Bl,B2
Al
,A2,Bl ,B2
Al
*,A2,A3,Bl *,B2
Al
*.A2,A3.B1 .B2
Al ,k2,k3,Bl
Al
Al*
Al;;
Al*,&
Al ,Bl
Wh‘v‘&E&’
Al
,h2,1Bl
Al tt,A2,Bl
Al
*,A2,Bl ,B2
Af
,A2,Bl ,B2
Al tt,A2,A3,Bi
Al
*,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2
16
,Bl
tt
Bl
,B2
,B2
*,B2
,B2
*
,,B2
,B2
,B2
,B2
,B2
r
Displacement
LOADING
%
UQwrox)
EQUENCE 8
-
- -
-
-
-
-
-
-
-
- -
- -
- -
- -
-
-
-
- -
- -
- -
- -
- -
- -
- -
- -
-
-
-
-
- -
-
Compressors
-
-
-
-
-
-
B1
tt
BP-
AIBL
Ai,Bl
Al *,Bl ft,B2
“Ai”B’lt”tb;’
Al’, Bl ,b2
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
Al
,A2,A3,Bl *,B2
Al .A2,A3,Bl
Bitt
Bl*
AIBIL
Al ;kBl
Al *,Bl tt,B2
“A;B~ltti3”2’
Al’,Bl*i32
Al
,A2,Bi
*,B2
Al
,A2,Bl ,B2
Al
,A2,A3,Bl *,B2
Al
,A2,A3,Bl ,B2
-
-
-
-
Bl*
Al&q*
Al ,‘sl*
Al ,Bl
Al *,Bl
*,B2
Al ,Bl
*,B2
Al ,Bl
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
*,A2,A3,Bl
-
,B2
Al *,A2,Bl
Al
Al ,A2,A3,Bl
Al ,A2,A3,Bl
-
*
*
,B2
*,B2
*,B2
*,B2
,B2
Page 17
Table 4C- Capacity Control Steps, 130-210 and Associated Modular Units
(cant)
UNIT SIZE
Displacement
LOADING SEQUENCE A
%
(4wrox)
-
- -
-
- -
- -
150 (50 Hz)
Alt,Bly*
-
- -
-
-
-
- -
-
- -
- -
-
-
--
-
A2.p
A+;~;1
Al
150 (50 Hz)
Alr*,Blt*”
170,
270A, 300B,
330;; fTt Hz)
,
Al tt,A2,81
Al
*,A2,Bl
Al
,A2,Bl
Al tt,A2,Bl
Al *,A2,Bi
Al
,A2,Bl ,B2
Al tt,A2,A3,Bl
Al
*,A2,A3,Bl ,B2
Al
.A2,A3,Bl ,B2
Al*
Al% *
Al*‘.Bl
Al
Al *,A2,Bl*
Al ‘,A2,Bl
Al
,A2,Bl
Al
*,A2,Bl *,B2
Al
*,A2,Bi ,B2
Al
,A2,Bl ,B2
Al
*,A2,A3,Bl *,B2
Al *,A2,A3,Bl
Al
,A2,A3,Bl ,B2
Al*.A2.A3,Bl
Al ‘,Ai,A$Bl,82,83
Al
,A2,A3,Bl ,B2,B3
A$!!
AltyBl*
A&tttt;’
Al
Al tt,A2,Bl*
y&t3g
Al
170,
270A,
3008,
Al tt,A2,A3,Bl
Altt,A2,A3,Bl
*Unloaded compressor.
tCompressor unloader, standard.
**Compressor unloader, accessory
ttTwo
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
,i2,kl
Altt,A2,Bl
Al tt,A2,Bl
Al
*,A2,61 ,B2
Al
,A2,Bl ,B2
Al tt,A2,A3,Bl
Al tt,A2,A3,Bl
Al
*,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2
Al*,A2,A3,Bl
Al
,A2,A3,Bl ,B2,B3
,‘Bl
,‘Bl
,kl
,B2
,B2
,B2
,B2
*.B2.83
*,B2
,B2
*,B2
,B2
*,B2,B3
,B2,B3
,B2,B3
SEQUENCE B
CompressorsCompressors
Bitt
“A;“B’:t;3”2’
Al’,Bl*‘BP
Al ,A2,Bl’tt,B2
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
Al ,A2,A3,Bltt,B2
Al ,A2,A3,Bl*,B2
Al
,A2,A3,Bl ,B2
“B’.p
A~i~~~~
AljBl
Al
.Bl
Ai
,B1’*;[32
Al
Al
,A2,Bl
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
Al
,A2,A3,Bl
Al
,A2,A3,Bl *,B2
Al ,A2,A3,Bl,B2
A&*
Al ,‘sl*
Al
Al
*,Bl
Al
,Bl *,B2
Al
Al
*,A2,Bi
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
Al *,A2,Bl
Al,A2,Bl*,B2,B3
Al
,A2,Bl ,B2,B3
Al
*,A2,A3,Bl *,B2,B3
Al
,A2,A3,Bl *,B2,B3
Al
-
- -
,A2,A3,Bl ,B2,83
- -
-
- -
- -
- -
- -
-
-
-
-
-
- -
Bl-*.
tt.B2
,Bl ,B2
tt,B2
Bl”
,Bl
*,B2
,Bl ,B2
l ,B2
*,B2,83
--
-
--
--
-
-
-
-
-
-
tt,B2
17
Page 18
Table 4C -Capacity Control Steps, 130-210 and Associated Modular Units (cant)
UNIT
SIZE
Displacement
LOADING SEQUENCE A
%
(Aiwrox)
-
Compressors
-
-
-
-
-
-
-
-
-
170,
270A,300B,
-
-
-
-
-
-
-
Al tt
Al;Bl*
“Alt;tbT’
Al ,Bl
Alft,A2,Bl*
A&t$$V;
170,27OA, 300B,
170,27OA, 300B,
33oA/,$cH350
*Unloaded compressor.
tcompressor unloader, standard.
**Compressor unloader, accessory.
ttTwo
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing
Hz)
9
Al
Altt,A2,Bl*,B2
Al tt,A2,Bl
Al
*,A2,B1 ,B2
Al
,A2,Bl ,B2
Al tt,A2,A3,Bi
Al tt,A2,A3,Bl
Al”,A2,A3,Bl
Al
,A2,A3,Bl ,B2
Al tf,A2,A3,Bl
Al tt,A2,A3,Bl
Al*,A2,A3,Bl
Al
.A2,A3.B1 .B2,B3
Al%
Al ‘,Bl
Al ,Bl
Al *,A2,Bl*
Al
Al
Al
*,A2,Bl
Al *,A2,Bl
Al
,A2,Bl ,B2
Al
*,A2,A3,Bl *,B2
Al
*,A2,A3,Bl ,B2
Al
,A2,A3,Bi ,B2
Al
*,A2,A3,Bl *,B2,B3
Al
*,A2,A3,Bl ,B2,B3
Al
,A2,A3,Bl ,B2,83
-
-
-
-
-
-
-
-
-
-
-
Al*
,A2,Bl
Al*
*,A2,Bl
,A2,Bl
*,B2
,B2
*,B2
,B2
*,B2,B3
,B2,B3
,B2,83
*
,B2
,B2
r
LOADING SEQUENCE B
Compressors
yp
;-;,q
Ai,Bi*
Al ,Bl
Al*,BItt,B2
“Ai”B’lttb”2’
Al’,Bl*BP
Al *,A2,Bi tt,B2
Al
,A2,Bl
tt,B2
Al ,A2,Bl l ,B2
Al
,A2,Bl ,B2
Al *,A2,Bi -ft,B2,B3
Al ,A2,Bltt,B2,B3
Al
,A2,Bl *,B2,B3
Al
,A2,Bl ,B2,B3
Al *,A2,A3,Bl tt,B2,B3
Al
,A2,A3,Bl
Al ,A2,A3,Bi l ,B2,B3
Al .A2.A3.Bl
6
tt,B2,63
.B2.B3
B;$+
~l*;;{#
Ai,Bl*
Al
,Bl
Al *,Bl tT,B2
“A’iBe’~~~22
Al’,Bl
Al *,A2,Bl tt,B2
Al ,A2,Bl tt,B2
Al *,A2,Bl tT,B2,B3
Al ,A2,Bltt,B2,B3
Al ,A2,81*,82,83
Al
Al*,A2,A3,Bl tt,B2,B3
Al ,A2,A3,Bltt,B2,B3
Al
,A2,A3,Bl *,B2,B3
Al
Al *,A2,Bl
Al *,AZ,Bl
Al ,A2,Bl*,B2,B3
Al ,A2,Bl
Al *,A2,A3,Bl
Al ,A2,A3,Bl*,B2,B3
Al ,A2,A3,Bl
,B2
Al
,A2,Bi *,B2
Al ,A2,Bl
,A2,A3,Bl ,B2,B3
Al *,Bl
Al
Al ,A2,Bl
,B2
,A2,Bl ,B2,B3
Bl*
A&*
Al ,Bl*
Al ,Bl
*,B2
Al
,Bl *,B2
Al
,Bl ,B2
*,B2
,A2,Bl *,B2
,B2
*+B2,B3
,B2,83
*,B2,B3 ,B2,B3
18
Page 19
Table 4C -Capacity Control Steps, 130210 and Associated Modular Units (cant)
UNIT
SIZE
170,
270A, 300B,
33OA/z, t”fB,:“O Hz)
170,
33OA/z,
I
270A,
3008,
t”609+{,50
,
Hz)
CONTROL
STEPS
l-
Displacement
(Approx)
%
:
11
19
;: :i
37
:i z; ::
72
i:
;:
96
100
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
LOAD11
i SEQUENCE A
Compressors
A)$
Al+yBl*
Altt;3B11
Al
,Bl
Al tt,A2,61*
*‘-J-&W~’
Al
,1A2,Bl
Al tt,A2,Bl
Al tt,A2,Bl
Al *,A2,Bl
Al
,A2,Bl ,B2
Al tt,A2,A3,Bl
AlTt,A2,A3,Bl
Al *,A2,A3,Bl
Al ,A2,A3,Bl
Al
tt,A2,A3,Bl *,B2,83
Altt,A2,A3,Bl
Al*,AZ,A3,Bl
Al ,A2,A3,Bl
*;p
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
*,B2
,B2
,B2
*,B2
,B2
,B2
,B2
,B2,B3
,B2,B3
,B2,B3
r
Displacement
(APP~~x)
%
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
LOAD11
i SEQUENCE B
Compressors
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
I31
Al*,Bltt
*~i~~~~
Al’,Bl
Al *,BlTj-,B2
Al ,Bl tt,B2
Al .Bl *.B2
Ai,Bl
Al*.A2,Bl tt,B2
Al
Al *,A2,BItt,B2,B3
Al ,A2,Bltt,BZ,B3
Al
Al ,A2,Bl,B2,B3
Al *,A2,A3,Bltt,B2,B3
Al
.A2.A3,Bl
Ai ,Ai,A$,Bt’*;82,63
Al
,b2
,A2,Bl
ff,B2
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
,A2,Bl *,B2,83
tt,B2,B3
,A2,A3,Bl ,B2,B3
BB’!J
Al;T’Bl*
Al
+,Bl
Al l ,Bl
Al
Al
t-),*2,61
“A! tA$2f,’
Al*A2 Bl
170,27OA,
330~A~~~f\; ff Hz)
*Unloaded compressor.
j-Compressor unloader, standard
**Compressor unloader, accessory
ttTwo unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
3008,
,
81
ii; :A
100
Alft,A2,B’ltt,B2
Al
tt,A2,Bl
Altt,A2,Bl
Al *,A2,Bl
Al
,A2,Bl ,B2
Al tT,A2,A3,Bl tt,B2
Al tt,A2,AS,Bf
Al tt,A2,A3,Bl
Al
*,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2
Altt,A2,A3,Bltt,B2,B3
Altt,A2,A3,Bl*,B2,B3
Al tt,A2,A3,Bl
Al
*,A2,A3,Bl ,B2,B3
Al
,A2,A3,Bi ,BZ,B3
19
,Bl
*
*,B2
,B2
,B2
*,B2
,B2,B3
,B2
;;*;,’ ‘j
Ai,Bl*
Al
,Bl
Al
tt,Bl
t-t,82
Al *,Bl tt,B2
“d;“B’W@&’
Al’,Bl*‘BZ
Al *,A2,Bi tt,B2
Al
,A2,Bl TT,B2
Al
,A2,Bl*,E32
Al
,A2,Bl ,B2
Al
tt,A2,Bl tt,B2,B3
Al
*,A2,Bl
Al
Al Tt,A2,A3,Bl tt,B2,B3
Ai*,A2,A3,Bltt,B2,B3
Al ,A2,A3,BlTt,B2,B3
Al
Al
tt,B2,B3
,A2,Bi
tt,B2,B3
Al
,A2,Bi *,B2,83
Al
,A2,Bl ,B2,83
,A2,A3,Bl *,B2,B3
,A2,A3,Bl ,B3,83
Page 20
-
Table 4C -Capacity Control Steps, 130-210 and Associated Modular Units (cant)
UNIT SIZE
190,36OA/B,
39oEpt
190,36OA/B,
39;: jfj’;,“”
190,
39;; (BGp*w
Hz)
I
,
360A/B,
,
CKEL
r
Compressors
Ah
Al j2,B-i
Al
,A2,Bl ,B2
Al
,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2,63
Al*
yp;
Al
*,A2,81
Al
,A2,B1
Al *,A2,Bl
Al
Al
*,A2,A3,Bl ,B2
Al
,A2,A3,81 ,B2
Al
*,A2,A3,Bi ,B2,B3
Al
,A2,A3,Bl ,B2,B3
-
-
-
-
Al *,A2,Bl*
Al *,A2,Bl
Al *,A2,Bl
Al
Al l ,A2,A3,Bl *,B2
Al
*,A2,A3,Bl ,B2
Al
Al
l
Al
*,A2,A3,Bl ,B2,B3
Al
,A2,A3,Bl ,B2,83
,B2
,A2,81 ,B2
-
-
-
-
-
-
-
-
-
-
-
-
Al*
Al
Al *,Bl
*
Al *,Bl
Al,Bl
Al *,A2,Bl
Al
,A2,Bi
*,B2
,B2
,A2,Bl ,B2
,A2,A3,Bl ,B2
,A2,A3,Bl*,B2,B3
l-
Displacement
LOADIN<
%
OVvW
2
41
56
1;:
-
-
- -
-
-
-
-
- -
SEQUENCE B
Compressors
A1B’Bl
Al ,&I
Al ,A2,Bl
Al
.A2.B1 .B2.B3
Al ,A2,d3&
-
-
-
-
-
-
-
-
-
Bl*
AIBf& *
Ai,Bl
Al ,Bl
Al,Bl,B2
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
Al
,A2,Bl *,B2,B3
Al
,A2,Bl ,B2,B3
Al ,A2,A3,Bl
Al
,A2,A3,Bl ,B2,B3
Bl*
Al&
Al,i31*
Al
Al *,Bl*,B2
Al ,Bl*,B2
Al ,Bl
Al*,A2,Bi
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
Al
*,A2,Bl
Al
,A2,Bl *,B2,B3
Al
,A2,Bl ,B2,B3
Al
*,A2,A3,Bl *,B2,83
Al
,A2,A3,Bl
Al ,A2,A3,Bl
,B2
,B2 ,@2,B3
*,B2
*,B2,83
l
,Bl
,B2
*,B2
l ,B2,B3
l ,B2,B3
,B2,B3
190,36OA,
39OE31(6CC
39;; j:;,W
*Unloaded compressor.
tCompressor unloader, standard.
**Compressor unloader, accessory.
TtTwo unloaders, both unloaded
NOTE: These capacity control steps may vary due to lag compressor sequencing
Hz)
,
190,36OA,
I
A%1
Al
,A2,Bi
Al
,A2,Bl ,B2
Al
,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2,B3
Al*
fk;
;;*A$&
Al *,A2,&
Al
,A2,Bl ,B2
Al
l ,A2,A3,Bi ,B2
Al
,A2,A3,Bl ,B2
Al
*,A2,A3,Bl ,B2,B3
Al
,A2,A3,Bl ,B2,B3
20
,B2
A%1
Al ,EkB2
Al
,A2,Bl ,B2
Al
,A2,Bl ,B2,B3
Al
,A2,A3,Bl ,B2,B3
-
-
-
-
-
-
-
-
-
-
-
-
--
-
-
-
-
-
-
Page 21
Table 4C -Capacity Control Steps, 130-210 and Associated Modular Units
(cant)
UNIT
SIZE
190,36OA,
39:: (8514w
,
190,36OA,
=J”8”1 y
,
210,39QA,
420%:
(86p
Hz)
I
210,
390A,
42y3g
210,
42of,Bs(f~~ Hz)
*Unloaded compressor.
j-Compressor unloader, standard.
**Compressor unloader, accessory.
ttTwo unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
,
390A,
1
HZ)
CONTROL
STEPS
Displacement
r
LOADING SEQUENCE A
%
UVvW
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Compressors
-
-
-
-
-
-
-
-
-
-
Al*
Al%
Al’,BI
Al ,Bl
Al*,A2,Bi*
Al *,A2,Bl
Al
,A2,Bl
Al *,A2,Bl
Al *,A2,Bl
Al ,A2,Bl
Al
*,A2,A3,Bl *,B2
Al
*,A2,A3,Bi ,B2
Al ,A2,A3,Bl
Al
*,A2,A3,Bl *,B2,83
Al
*,A2,A3,Bl ,B2,63
At ,A2,A3,B t ,B2,B3
A&
Al
,A2,Bl
Al
,A2,Bl ,B2
Al
,A2,A3,81 ,B2
AI
,A2,A3,Bl ,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
Al*
Al”B1
Al
,kl
Al l ,A2,Bl
Al
,A2,Bl
Al l ,A2,Bl ,B2
Al
,A2,Bl ,B2
Al l ,A2,A3,Bl ,B2
At
,A2,A3,Bt ,B2
Al l ,A2,A3,61 ,B2,B3
Al
,A2,A3,Bl ,B2,B3
Al l ,A2,A3,A4,Bi ,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
-
-
-
-
-
-
-
-
-
-
-
l
*,B2 ,B2
,B2
,B2
l-
Displacement
PWprox)
LOAD11
%
11
:;
ii
50
61
7;
a3 94
100
14
-
- -
-
- -
- -
-
- -
-
i SEQUENCE B
Compressors
Al
Al,Bl,B2
Al
Al
Al
,A2,Bl *,B2,B3
Al
.A2,Bl ,B2,B3
Al ,A$,A$,Bi
Al
,A2,A3,Bl ,B2,B3
Al l ,Bl
;-,BB’;g
Al *,i2,B?
Al
Al
Al *,A2,Bl
Al
,A2,Bl *,B2,B3
AI
,A2,Bl ,B2,B3
Al*,A2,A3,Bl*,B2,B3
AI
.A2.A3.Bl *.B2.B3
Al $1
Al
Al
,A2,Bl ,B2,B3
Al
,A2,A3,Bl ,B2,B3
Al
,A2,A3.A4,Bl ,B2.B3
- -
-
- -
- -
Al,Bl*,B2
Al
At ,A2,BI l ,B2
Al
Al ,A2,Bl l ,B2,B3
Al
,A2,Bl ,B2,B3
Al
,A2,A3,Bl *,B2,83
Al
,A2,A3,Bl ,B2,B3
Al
,A2,A3,A4,Bl *,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
Bl*
AIBt& *
Ai,Bl
,Bl *,B2
,A2,Bl
*,B2
,A2,Bl ,B2
l
Bl*
A&*
Al,i31*
Al ,Bl
*,B2
*,B2
,A2,Bi *,B2
,A2,Bi ,B2
*,B2,83
AK1
,B2
,A2,Bl ,B2
-
-
-
-
-
-
Bl*
Al’:1
*
Ai,Bi
,Bl ,B2
,A2,Bl ,B2
,82,83
21
Page 22
r-
A
Table 4C
UNIT SIZE
Capacity Control Steps, 130-210 and Associated Modular Units (cant)
-
LOAD11
Compressors
Al*
Al%
Al ‘,Bl
Al,Bi
Al *,A2,Bl*
Al *,A2,Bl
Al
,A2,Bf
210,
390A,
420AIB (60 Hz)
Al**,Bl**
210,
390A,
420/U;
f-5;
Hz)
,
210,
390A,
42Ofy;; w
,
-
-
-
-
210,
390A,
42Of,~gw
,
210,39OA,
42\yE gyp)
I
*Unloaded compressor
tCompressor unloader, standard
**Compressor unloader, accessory
ttTwo
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
-
-
-
-
- -
-
-
-
- -
Al”,AP,Bi
Al l ,A2,Bl ,B2
Al
,A2,Bl ,B2
Al
*,A2,A3,Bl ‘,B2
Al
*,A2,A3,Bi ,B2
Al
,A2,A3,Bl ,B2
Al *,A2,A3,Bl
Al
*,A2,A3,Bl ,B2,B3
Al
,A2,A3,Bi ,B2,B3
Al
*,A2,A3,A4,Bl *,B2,B3
Al
*.A2.A3.A4.B1 ,B2,B3
Al ,k2,A3,A4,Bl
A&
Al
,A2,Bl
Al
,A2,Bl ,B2
Al
,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
Al”
Al”B1
Al ,Bl
Al *,A2,Bl
Al
,A2,Bl
Al
*,A2,Bl ,B2
Al
,A2,Bl ,B2
Al*,A2,A3,Bl
Al
,A2,A3,Bl ,B2
Al
*,A2,A3,Bl ,B2,B3
Al
,A2,A3,Bi ,B2,83
Al*,A2,A3,A4,Bl
Al
,A2,A3,A4,Bl ,B2,B3
-
-
-
-
-
-
Al*
Al%
Al ‘,Bl
Al
,Bl
Al*,A2,Bl*
Al *,A2,Bl
Al
,A2,Bl
Al l ,A2,Bl *,B2
Al *,A2,Bl
Al
,A2,Bl ,B2
Al
*,A2,A3,Bl *,B2
Al
*,A2,A3,Bi ,B2
Al
,A2,A3,Bl ,B2
Al
*,A2,A3,Bl
Al
*,A2,A3,Bl ,B2,83
Al
,A2,A3,Bl ,B2,83
Al*,A2,A3,A4,Bl*,B2,83
Al
*,A2,A3,A4,Bl
Al
.A2.A3.A4.B1
*
*,B2
*,E32,B3
,B2,B3
,B2
,B2,B3
*
,I32
*,B2,B3
,WB3
BZB3
f
Displacement
(Approx)
LOADING SEQUENCE Bi SEQUENCE A
%
9
i;
Compressors
Al%
Al .Bl*
Al’,Bl
Al*.Bl*,B2
Al ,Bl
Al ,Bl
Al *,A2,Bl
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
Al *,A2,Bl
Al ,A2,Bl*,B2,B3
Al
,A2,Bl ,B2,B3
Al *,A2,A3,Bl
Al
,A2,A3,Bl *,B2,B3
Al
,A2,A3,Bl ,B2,B3
AY*,A2,A3,A4,Bi *,B2,B3
Al ,A2,A3,A4,Bl*,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
Al $1
Al
,A2,B1 ,B2
Al ,A2,Bl
Al .A2.A3.Bl
Al
,A2,A3,A4,Bl ,B2,B3
- -
-
-
-
- -
- -
- -
AIB&
Al ,Bl
Al ,Bl
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
Al ,A2,Bl
Al
,A2,Bl ,B2,B3
Al
,A2,A3,Bl *,B2,B3
Al
,A2,A3,Bl ,B2,B3
Al
,A2,A3,A4,B1 *,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
Al&
Al .Bl*
Al*.Bl*,B2
Al
Al ,Bl
Al l ,A2,Bl *,B2
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
Al *,A2,Bl
Al ,A2,Bl
Al
,A2,Bl ,B2,83
Al *,A2,A3,Bl*,B2,B3
Al
,A2,A3,Bl *,B2,B3
Al ,A2,A3,Bl
Al*,A2,A3,A4,Bl*,B2,83
Al
,A2,A3,A4,81*,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
Bl*
*,B2
A&
-
-
-
-
-
-
-
-
-
-
Bl*
Al’,Bl
Bl*
Al’,Bi
,Bl *,B2
*
,B2
*,B2
*,B2,B3
*,B2,83
,B2 ,B2,B3
.B2.B3
*
*,B2
,B2
*,B2,B3
*
,B2
*,B2,B3
*,B2,B3
,B2,83
22
Page 23
Table 4D- Capacity Control Steps, 225, 250,280
UNIT
30GT
225 (60 Hz)
r
Displacement
(Awox)
1:;
%
12
2
46
E
LOAC
\IG
SEQUENCE A
Compressors
*1A’B1
Al
,A2,61
Al
,A2,Bl ,B2
Al
,A2,A3,Bl ,B2
Al ,A2,A3,Bf
Al
,A2,A3,A4,Bl ,B2,B3
Al.A2.A3.A4.Bl.B2.B3.84
Al
Al
Al l ,A2,A3,Bl ,B2
Al
Al
*,A2,A3,Bl ,B2,B3
Al
,A2,A3,Bl ,B2,83
Al *,A2,A3,A4,Bl
Al
,A2,A3,A4,Bl ,B2,B3
Al*,A2,A3,A4,Bl,B2,B3,B4
Al
,A2,A3,A4,Bl ,B4,63,A4
Al
Al
Al
Al
*,A2,A3,Bl *,B2
Al
Al
Al l ,A2,A3,Bl l ,B2,B3
Al
,A2,A3,Bl *,B2,B3
Al
,A2,A3,Bl ,B2,B3
Al
*,A2,A3,A4,Bl *,B2,B3
Al*,A2,A3,A4,Bl
Al
,A2,A3,A4,Bl ,B2,B3
Al*,A2,A3,A4,Bl*,B2,83,84
Al.A2.A3.A4.Bl*.B2.B3.84
A1’,Ai,A$A4,Bl
,B2,B3
Al*
Al?Bl
Al
,Bl
Al *,A2,Bl
Al
,A2,Bl
*,A2,Bl ,B2
,A2,Bl ,B2
,A2,A3,Bl ,B2
,B2,B3
Al*
Al
_
Al *,Bl*
Al,Bl*
Al,Bl
Al *,A2,Bl*
Al *,A2,Bl
Al ,A2,Bl
*,A2,Bl
*,B2
,A2,Bl *,B2
,A2,Bl ,B2
*,A2,A3,Bl ,B2
,A2,A3,Bl ,B2
,B2,83
,B2,B3,B4
r
Displacement
hwrox)
LOADING SEQUENCE B
%
12
Al
Al,A2,A3,A4,Bl,B2,B3,B4
-
-
-
-
-
-
-
-
-
-
-
-
Al
Al *,A2,A3,Bl
Al *,A2,A3,Bl *,B2,83,84
Al ,A2,A3,Bl*,B2,B3,B4
Al ,A2,A3,Bl
Al*,A2,A3,A4,Bl*,B2,B3,B4
Al*,A2,A3,A4,Bl,B2,83,B4
At
,A2,A3,A4,Bl ,A2,B3,B4
Compressors
A&
Al $1
,B2
Al
,A2,Bl ,B2
Al
,A2,Bl ,B2,B3
Al
,A2,A3,Bl ,B2,B3
,A2,A3,Bl ,B2,B3,B4
-
-
-
-
-
Bl*
Ai&*
Al ‘,Bl
Al ,Bl
Al *,Bl
*,B2
Al
,Bl *,B2
Al,Bl,B2
Al
*,A2,Bl
Al
Al *,A2,Bl
Al ,A2,Bl*,B2,83
Al ,A2,Bl
l
Al
,A2,A3,Bl ,B2,83
*,B2
*,A2,Bl ,B2
Al
,A2,Bl ,B2
*,B2,83 ,B2,B3
,A2,A3,Bl*,B2,B3
,B2,B3,B4
,B2,83
A%
Al
,A2,Bl
Al
225 (50 Hz)
Al,A2,A3,A4,Bi,B2,B3,84
Al*,A2,A3,A4,Bl
Al,A2,A3,A4,Bl,B2,B3,84
*Unloaded compressor.
TCompressor unloader, standard.
**Compressor unloader, accessory
TtTwo
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing
,A2,Bl ,B2
Al
,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
Al*
Ali’Bl
Al
,Bl
Al *,A2,Bl
Al
,A2,Bl
At
*,A2,Bl ,B2
Al
,A2,Bl ,B2
Al *,A2,A3,Bl
Al
,A2,A3,Bl ,B2
Al *,A2,A3,Bl
Al
,A2,A3,Bl ,B2,B3
Al
*,A2,A3,A4,Bl ,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
,B2
,B2,B3
,B2,B3,B4
23
AL
Al $1
,B2
Al
,A2,Bl ,B2
Al
,A2,Bl ,B2,83
Al
,A2,A3,Bl ,B2,B3
Al
,A2,A3,Bl ,B2,B3,B4
Al,A2,A3,A4,Bl,B2,B3,B4
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Page 24
UNIT
30GT
Table 4D
r
-
Capacity Control Steps, 225, 250,280 (cant)
JG
LOAC
SEQUENCE A
l-
Compressors
LOAC
4G
SEQUENCE B
Compressors
Al*
Al%
*
Al ,Bl*
Al
,Bl
Al
*,A2,81*
Al *,A2,Bl
Al
,A2,Bl
Al
*,A2,Bl *,B2
Al
,A2,B1 *,B2
Al
,A2,Bl ,B2
Al
*,A2,A3,Bf*,B2
Al *,A2,A3,Bl
Al
,A2,A3,Bi ,B2
Al*,A2,A3,Bi*,B2,63
Al*,A2,A3,Bl
Al
,A2,A3,Bl ,B2,B3
Al *,A2,A3,A4,Bl*,B2,83
Al *,A2,A3,A4,Bl
Al
,A2,A3,A4,Bl ,B2,B3
Al*,A2,A3,A4,Bl*,B2,83,B4
Al*.A2.A3.A4.Bl.B2.63.84
Al
,A2,A3,A4,Bl
22
32
250 (60
Hz)
29 32
t:
54 57
A1*,A2,A3,A4,Bl
s7: :i
96
100
*Unloaded compressor.
JCompressor
**Compressor unloader, accessory
ttTwo
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
un!oader,
standard
Al*,A2,A3,A4,Bl*,B2,B3,B4
Al
Al
,A2,Bl ,B2
Al
,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2,B3
Al
.A2.A3,A4.B1 .B2.B3
“A:*gB;
Al *,A2,Bl
Al
Al
*,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2
Al *,A2,A3,Bl
Al
,A2,A3,Bl ,B2,B3
Al
*,A2,A3,A4,Bl ,B2,B3
Al
,A2,A3,A4,Bi ,B2,B3
Al,A2,A3,A4,Bl
Al%
Al*,A2,Bl*
Al
Al
Al l ,A2,Bl *,B2
Al ,A2,Bl*,B2
Al
Al *,A2,A3,Bl*,B2
Al
*,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2
Al*,A2,A3,Bl*,B2,B3
Al
,A2,A3,Bl *,B2,63
Al
,A2,A3,Bl ,B2,83
Al *,A2,A3,A4,Bl*,B2,B3
Al*,A2,A3,A4,Bl,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
Al,A2,A3,A4,Bl*,B2,B3,B4
Al,A2,A3,A4,Bl,B2,63,84
,B2,B3
,B2,B3&4
A%1
,A2,Bl
Al*
Al!‘Bl
Al
,Bl
,B2
,A2,Bl ,B2
,B2,B3
,B2,B3,B4
,B2,B3,B4
Al*
*
Al ,bl l
Al
,Bl
*,A2,01
,A2,Bl
,A2,Bl ,B2
,B2
,B2,B3
Bl*
Al*B&*
Al,Bl*
Al
,Bl
Al *,A2,Bl*
Al *,A2,Bl
Al
,A2,Bl
Al *,A2,Bl
Al
Al
Al *,A2,A3,BI
Al*,A2,A3,Bl
Al
Al’,A2,A3,Bi*,B2,B3
Al *,A2,A3,Bl
Al
,A2,A3,Bl ,B2,83
Al*,A2,A3,A4,Bl*,B2,B3
Al
*,A2,A3,A4,B1 ,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
Al*,A2,A3,A4,Bl*,B3,B3,64
Ai*,A2,A3,A4,Bl
Al,A2,A3,A4,Bl,B2,B3,84
Al
Al
Al ,A2,A3,Bl
Al
.A2.A3.Bl .B2,B3.B4
Al ,A2,d3,A4,Bl
-
-
-
-
-
-
-
-
-
*,B2
,A2,Bl *,B2
,A2,Bl ,B2
*,B2
AK31
,B2
,B2,B3
,B2,B3,B4
,B2
,B2,83 ,B2,B3,B4
,A2,A3,Bl ,B2
Al $1
,A2,Bl ,B2
,A2,Bl ,B2,B3
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Bl”
Al% *
Al ‘,Bl
Al ,Bl
Al *,Bl*,B2
Al ,Bl
“,B2
Al
,Bl ,B2
Al l ,A2,Bl *,B2
Al *,A2,Bl
Al ,A2,Bl
Al *,A2,Bl
Al
,A2,Bl *,B2,B3
Al
,A2,Bl ,B2,B3
Al*,A2,A3,Bl*,B2,B3
Al*,A2,A3,Bl
Al ,A2,A3,Bl
Al*,A2,A3,Bl
Al,A2,A3,Bl*,B2,83,84
Al
,A2,A3,Bi ,B2,B3,B4
Al*,A2,A3,A4,Bl*,B2,B3,B4
Al*,A2,A3,A4,Bl,B2,B3,84
Al ,A2,A3,A4,Bl,B2,63,84
,B2
,B2
*,B2,B3
,B2,B3
,B2,83
*,B2,B3,B4
24
Page 25
UNIT
30GT
CONTROL
STEPS
Table 4D- Capacity Control Steps, 225, 250, 280 (cant)
1G
SEQUENCE A
Compressors
r
LOADING SEQUENCE B
Compressors
250 (50 Hz) 280 (60 Hz)
250 f& Hz),
Al**
250 $;; Hz),
Al**,Bl**
*Unloaded compressor.
-/-Compressor unloader, standard.
-
““Compressor unloader, accessory
ttTwo unloaders, both unloaded
NOTE: These capacity control steps may
Al
Al
Al
,A2,Bl ,B2
Al
,A2,A3,Bl ,B2
Al ,A2,A3,Bl
Al
,A2,A3,A4,Bl ,B2,83
Al,A2,A3,A4,Bl,B2,B3,B4
AlA’Bl
Al ,Bl
Al l ,A2,Bl
Al
Al *,A2,Bl
Al
,A2,Bl ,B2
Al*,A2,A3,Bl
Al
,A2,A3,Bl ,B2
At*,A2,A3,Bl
Al
,A2,A3,Bl ,B2,B3
Al l ,A2,A3,A4,Bi ,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
Al*,A2,A3,A4,Bl,B2,83,84
Al,A2,A3,A4,Bl,B2,B3,B4
Al%
Al ,Bi*
Al ,Bl
Al *,A2,Bl*
Al ‘.A2.B-l
Al
Ai
*.A2.B1 *,B2
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
Al
*,A2,A3,Bl *,B2
Al l ,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2
Al*,A2,A3,Bl
Al ,A2,A3,Bi
Al
,A2,A3,Bl ,B2,83
Al
*,A2,A3,A4,Bl *,B2,B3
Al
*,A2,A3,A4,Bl ,B2,83
Al
,A2,A3,A4,Bl ,B2,B3
Ai*,A2,A3,A4,Bl*,B2,B3,B4
Ai,A2,A3,A4,Bl*,B2,B3,B4
Ai,A2,A3,A4,Bl,B2,B3,B4
vary
due to lag compressor sequencing
,A2,61
Al”
,A2,Bl
Al*
,A2,Bl
,B2,B3
,I32
,B2
,B2,B3
*
*,B2,B3
*,B2,B3
AK1
Al $1
,B2
Al
,A2,Bi ,B2
Al
,A2,Bl ,B2,B3
Al ,A2,A3,Bl
Al
,A2,A3,A4,Bl ,B2,83
Al,A2,A3,A4,Bl,B2,B3,84
Al l ,Bl*,B2
Al*,A2,Bl
Al l ,A2,Bl ,B2
Al
Al *,A2,Bl
Al
,A2,Bl *,B2,B3
Al
Al*,A2,A3,Bi
Al*,A2,A3,Bl
Al
,A2,A3,Bl ,B2,B3
Al *,A2,A3,Bi*,B2,B3,B4
Al ,A2,A3,Bl*,B2,B3,B4
Al
,A2,A3,Bl ,B2,B3,B4
Al*,A2,A3,A4,Bl*,B2,B3,B4
Ai*,A2,A3,A4,Bi,B2,83,B4
Al
,A2,A3,A4,Bi ,B2,B3,B4
,B2,B3
-
-
-
-
-
-
-
-
-
-
-
-
-
Bi*
A&*
Al ‘,Bl
Al
,Bi
Al ,Bi
*,B2
Al
,Bl ,B2
*,B2
,A2,Bl ,B2
*,B2,B3
,A2,Bl ,B2,63
*,B2,B3
,B2,B3
25
Page 26
Head Pressure Control
-
The microprocessor con­trols the condenser fans in order to maintain the lowest con­densing temperature possible, thus the highest unit efficiency. Instead of using the conventional head pressure control meth­ods, the fans are controlled by the position of the EXV and
suction superheat.
As the condensing temperature drops, the EXV opens to
maintain the proper suction superheat. Once the EXV is
As the condensing temperature rises, the EXV closes to maintain the proper suction superheat. Once the EXV has closed to 39.5% open (300 steps open), a fan stage is added after 2 minutes.
During start-up, all the condenser fans are started when the condensing temperature reaches 95 F (35 C) to prevent excessive discharge pressure during pulldown. See Table 5
for condenser fan sequence of operation.
fully open, if the condensing temperature continues to drop, the suction superheat begins to rise. Once the suction super-
heat is greater than 40 F (22.2 C), a fan stage is removed
after 2 minutes,
Table 5- Condenser Fan Sequence
FAN ARRANGEMENT FAN NUMBER(S)
30GN040-050
30GN060,070
30GN080,090
30GNl00,110 (and associated modular units)
30GN130-170
WWER
.
-_----
(and associated modular units)
I I
1
2 3
4
I
5
6
1
2 FC-81 3 FC-A2
4
5,
7,
6, 8
3, 4, 5, 6, 7, a FC-A2,
5 7
6,
8
FAN CONTACTOR
WI
FC-Al
FC-Bi
FC-A2
FGB2
FC-Al
FGB2
FC-Al
FC-Al
F&B2 Microprocessor
FC-AS, FGB3
FC-A3
FGB2, FC-B3 Microprocessor
FC-Al Compressor Al FC-Bl Compressor Bl
,
CONTROLLED BY
Compressor Al Compressor Bl
First Stage
Microprocessor
Second Stage
I
MicrODrOceSSOr
Compressor Al
I
Compressor Bi
First Stage
Microprocessor
Second Stage
Microprocessor Compressor Al Compressor Bi
Compressor Al
Compressor Bl
First Stage
Second Stage
Compressor
Third Stage
30GN190,210
*Control box.
(and associated modular units)
I
5,
7 I
6. 8 3,
9
4,
10
1,
3, 9, 11 FC-A2,
2, 4, 10, 12
I
26
FC-A2, FC-A3
FC-Al
FC-Bi
FC-A2 FC-B2
FGA3
FGB2,
FC-B3
Compressor Al
I
Comwessor Bl
I
Frist Stage
Microprocessor
Second Stage
Microprocessor
Page 27
Table 5 -Condenser Fan Sequence
(cant)
FAN ARRANGEMENT
30GT225
30GT250 (60 Hz)
30GT250 (50 Hz) AND 30GT280
L
‘: i
/
/;
k.
w
*Control box.
tPower box.
FAN NUMBER(S) FAN
7, 8
9, 10
5,
6
11, 12
1,
2,
3, 4
13, 14, 15, 16
1,
2, 3, 4, 5, 6 FC-2, FC-3
11,
12, f3,
14, 15, 16
7, 8, 10
9, 17, 18
5,
6
11, 12, 19
1,
2, 3, 4,
14, 15, 16, 20
1,
2, 3, 4, 5, 6, 11, 12, 13,
14, 15, 16,
II, 12, 19,20 FC-5
1,
14, 15, 16, 21, 22 FC-3,
1, 2, 3, 4, 5, 6, 11, 12, 13,
14, 15, 16, 19, 20, 21, 22 FC-5,
13,
19, 20
7, 8, 10 FC-1
9,
17, 18
5,
6
2, 3, 4, 13,
C~;;jACToR
FC-1 FC-4 Compressor FC-2
FC-5 Microprocessor FC-3
FC-6
FC-5, FC-6
FC-1
FC-4
FC-2 FC-5 Microprocessor
FC-3, FC-6,
FC-;&F6c;3kF;-5,
-3 -
FC-4 Compressor Bl FC-2
FC-6, FC-7 Microprocessor
FC-2, FC-3, FC-4, Third Stage
FC-6, FC-7
CONTROLLED BY
Compressor Al
First Stage
Second Stage
Microprocessor
Third Stage
Microprocessor
Compressor Compressor Bl
First Stage
FC-7 Microprocessor
Second Stage
Third Stage
Microprocessor
Compressor Al
First Stage
Microprocessor
Second Stage
Microprocessor
61
Al
Pumpout
is started or stopped, that circuit goes through a
When the lead compressor in each circuit
-
pumpout
cycle to purge the cooler and refrigerant suction lines of refrigerant.
The
pumpout
cycle starts immediately upon starting the lead compressor and continues until the saturated suction temperature is 10” F (5.5” C) below the saturated suction temperature at start-up, is
10”
F (5.5” C) below the cooler leaving fluid temperature, or reaches a saturated suction tem­perature of -15 F (-26 C). No
pumpout
is necessary if the
saturated suction temperature is below -15 F (-26 C). At this point, the EXV starts to open and continues to open gradually to provide a controlled start-up to prevent liquid
flood-back to the compressor.
At shutdown, the
urated suction temperature for that circuit is 10” F (5.5” C)
below the saturated suction temperature when
initiated, or saturated suction temperature reaches -15 F (-26 C). At that point, the compressor shuts down and the EXV continues to move until fully closed.
pumpout
cycle continues until the sat-
pumpout
is
27
Page 28
Keypad and Display Module (Also Called HSIO
or LID)
the operator to communicate with the processor. It is used
-
The only function of this module is to allow
The default display is displayed every 2 seconds if there
has been no manual input from the keypad for 10 minutes.
To return to automatic display, enter to enter configurations and set points and to read data, per­form tests, and set schedules. This device consists of a key­pad with 6 function keys, 5 operative keys, 12 numeric keys
(0 to 9, 0, and -), and an alphanumeric g-character LCD (liquid crystal display). See
Fig+
3. See Table 6 for
Table 6
FUNCTION
key usage.
ACCESSING FUNCTIONS AND SUBFUNCTIONS - See Tables 6 - 8. Table 7 shows the 6 functions (identified by name) and the subfunctions (identified by number).
OPERATIVE
-
Keypad and Display Module Usage
KEYS
STAT
0
HIST
q
SRVC
0
EST
El
CHD
El
SET
q
KEYS
EXPN
El
CLA
El
cl
c
cl
ENTR
q
STATUS - For displaying diagnostic codes and current operating information about the machine.
HISTORY - For displaying run time, cycles and
previous alarms. SERVICE - For entering specific unit configura-
tion information. TEST - For checking inputs and outputs for
proper operation. SCHEDULE - For entering occupied/unoccupied
schedules for unit operation SET POINT - For entering operating set points
and day/time information.
EXPAND - For displaying a non-abbreviated ex­pansion of the display
CLEAR- For clearing the screen of all displays
t
UP ARROW - For returning to previous display
position, DOWN ARROW- For advancing to next display
position. ENTER- For entering data
A
~~~~
at any time.
USE
USE
Fig. 3 -Keypad and Display Module
SUMMARY DISPLAY -When keypad has not been used for 10 minutes, display automatically switches to the rotat­ing summary display. This display has 4 parts, listed be­low, which appear in continuous rotating sequence.
DISPLAY 1 EXPANSION
TUE
15:45
CLOCK ON
COOL
1
2 ALARMS 1 2 ALARMS DETECTED
TODAY IS TUE, TIME IS 1545
UNIT IS ON VIA CLOCK SCHEDULE NUMBER OF STAGES IS 1
I
(3:45
PM)
AUTOMATIC DISPLAY OPERATION/DEFAULT DIS­PLAY - In this mode, the keypad displays the current time
(24”hour
format), current operating modes, cooling capac-
ity stages, and total number of alarms.
MODE X
COOL x
KEYPAD OPERATING INSTRUCTIONS (Refer to Table 9.)
1.
White keys on left side of keypad are shown and oper-
ated in these instructions according to the following ex­ample: keypad entry m
H
means press the q , then
the white key marked H .
2. The standard display uses abbreviations. Expanded in­formation scrolls through the display whenever
q
key
is pressed.
3. All functions are made up of a group of subfunctions.
To enter a subfunction, first press subfunction number desired. Then press the function key in which the sub­function resides. To move within that subfunction, press
the
q
or
m
arrow. For example, a
mpl
enters
the Temperature Information subfunction.
4. At any time, another subfunction may be entered by en­tering the subfunction number, then the function key.
5. Prior to starting unit, check leaving fluid set point for correct setting. Refer to Set Point Function section on page 39.
6. Depending on system configuration, all displays may not be shown. All displays are shown unless marked with the following symbol.
*Must be configured.
For additional unit start-up procedures, see separate In-
stallation, Start-Up and Service Instructions supplied with unit.
DOW
K
-
Day of Week
-
Hour(s)
-
Minute(s)
28
Page 29
su6FUNFT’oN
1
2 Alarm
3
4
5
6 7
8 Analog
9
10
II
Table
Status
STAT
0
Automatic Display
Display
;g;faQeratiw)
plWe$Y
Set Points (Current Operating)
Temperatures
Pressures
Inputs
outputs
- -
Functions and Subfunctions
7
-
FUNCTIONS
Test
outputs
TEST
cl
Schedule
CHD
ICI
Override Log On and
Service
SRVC
cl
Log Off
Compressors Clock Set
Version
and Unloaders (Software)
Period
-
-
1
Period 2 Field
Factory Configuration
Configuration Time
-
-
-
-
-
Period 3
Period 4 Period 5 Period 6 Period 7 Period 8 HOLIDAYS
Service Configuration
-
-
-
-
- -
-
History Set Point
HIST
0
SET
cl
Run Time Set Points
(Chiller Fluid)
Starts Reset
Alarm Demand Limit History
-
Set Points
Set Points
Date and
- -
- -
- ­z
-
- -
-
- -
Table 8- Accessing Functions and Subfunctions
OPERATION
To access a function, press subfunction no and function name key. Display shows function
To move to other elements, scroll up or down using arrow
@+oup.
keys. NOTE: These displays do not show if control is not configured for reset.
When the last element in a subfunction has been dis-
played, the first element is repeated.
To move to next subfunction
it is not necessary to use subfunction number Press function name key to
Vance
display through all subfunctions within a function and then back to the first
To move to another function, either depress function name key for desired function
(display shows the first
subfunction), Access a’ipecif ic sub-
function by’using the sub­function number and the function name kev.
sub-
ad-
I
I
ENTRY RESPONSE
p--jH
4
El
+
cl
l-i-l
I
4
cl
+
cl
+
cl
SET
cl
SET
cl
SET
III
STAT
III
I
KEYPAD
DISPLAY
RESET
CRST2xx
CREF2xx
CRSTi
xx
CREFlxx
RESET
CRST2xx
DEMAND
TIME
SET
X ALARMS
I
DESCRIPTION
Reset Set Points
Cooling Maximum
-
Reset xx
Cooling Maximum
Reference xx Cooling Minimum
Reference xx Cooling Minimum
Reference xx Reset Set
(ZtZi:SxxMaxirnurn
Demand Set Points
Current Time and Day of Week
Unit Set Points
Rotating Display
Capacity Stages
29
Page 30
Table 9- Keypad Directory
KEYPAD ENTRY
STATUS
DISPLAY 1
Refer to Automatic Display Operation on page 28
COMMENT
2 ALARMS
3 MODES
4 STAGE
I
X ALARMS ALARM X ALARM X
ALARM X ALARM X ALARM X
X MODES
MODE X MODE X MODE X MODE X
STAGE
STAGE X CAPT X
CAPA X
CAP0 X
LMT X*
Number of Tripped Alarms
Displays Tripped Alarms
>
Number of Modes in Effect
Displays Mode in Effect
>
Capacity Staging Information Number of Requested Stages
Percent of Total Capacity Percent Circuit A Capacity Percent Circuit 6 Capacity Demand Limit Set Point
;,;
6
5 SET POINT
6 TEMPERATURE
LOAD X*
CIRA X CIRB X
SMZ X
SET POINT
SP
x
MSP X
TWX
TEMPS
EWTX LWT X
SCTA X SSTA X CTA X SHA X
Load Limit Set Point
Circuit A Compressor Relay Status Circuit B Compressor Relay Status Load/Unload Factor for Compressors
Factor = 1 Unloader Factor = 0 6 Fluid Set Point Information Set Point
Modified Set Point = Set Point + Reset
Cooler Leaving Fluid Temperature
Temperature Information Cooler Entering Fluid Temperature Cooler Leaving Fluid Temperature
Circuit A Saturated Condenser Temperature Circuit A Saturated Suction Temperature
Compressor Al Suction Temperature Circuit A Suction Superheat
LEGEND
-
CCN
EXV- Electronic Expansion Valve MOP- Maximum Operating Pressure
Carrier Comfort Network
*Must be configured
j-If applicable
30
Page 31
SUBFUNCTION
6
TEMPERATURE (cant) cl
KEYPADENTRY
I
Table 9
4
-
Keypad Directory (cant)
STATUS (cant)
DISPLAY
SCTB X
COMMENT
Circuit B Saturated Condenser Temperature
7 PRESSURE
8 ANALOG
t
q
cl
4
cl
4
0 4
SSTB X
CTB X
SHB X
RST X*
PRESSURE
DPA X
SPA X
xxxx
OPA X
DPB X
SPB X
xxxx
OPB X
ANALOG
REF X
Circuit B Saturated Suction Temperature
Compressor Bl Suction Temperature
Circuit B Suction Superheat
Reset Temperature
Refrigerant System Pressure (psig)
Circuit A Discharge Pressure
Circuit A Suction Pressure
Circuit A Discharge/Suction
Circuit A Oil Pressure Differential
Circuit B Discharge Pressure
Circuit 8 Suction Pressure
Circuit B Discharge/Suction
Circuit B Oil Pressure Differential
Status of Analog Inputs
Transducer Supply Voltage
9
1NPUTS
LMT X*
RST X*
INPUT
SPW
x*
DLI
X*
DL2 X*
Demand 4-20 mA Signal
Reset 4-20 mA Signal
Status of Switch Inputs
Dual Set Point Switch
Demand Limit Switch 1
Demand Limit Switch 2
31
Page 32
SUBFUNCTION
Table 9- Keypad Directory (cant)
STATUS (cant)
DISPLAY
COMMENT
10 OUTPUTS
OUTPUTS ALMR X
FRAI X
FRA2 X
FRBI X
FRB2 X
CHWP X*
ULAI X
ULA2 X*
ULBI X
ULB2 X* EXVA X
EXVB X
HGBA X*
HGBB X MMA X*
Status of Outputs Alarm Relay K3
Fan Relay Kl Fan Relay K2 Fan Relay K4 Fan Relay K5 Cooler Water Pump Relay K6
Unloader Al Unloader Unloader Bl Unloader EXVA Percent Open
EXVB Percent Open Hot Gas Bypass Relay Circuit A Hot Gas Bypass Relay Circuit B
Motormaster@
t
A2T
t
B2T
A Output Percent
MMB X
Motormaster B Output Percent
TEST
To use Test function, LOCAL/ENABLE-STOP-CCN switch must be in STOP position To operate a test, scroll to desired test Then, press m to start test. Press m to stop test.
SUBFUNCTION
1
OUTPUTS
KEYPAD ENTRY
DISPLAY
OUTPUTS
8 8 8.8.8 8.8.8 ALMR X
FRAI X
FRA2 X
FRBl X
FRl32
X CHWP X* EXVA X EXVB X HGBRA X*
Test Outputs
Display Check Energize Alarm Relay K3 Energize Fan Relay Al Kl Energize Fan Relay A2 K2
Energize Fan Relay Bi K4 Energize Fan Relay 82 K5
Energize Cooler Water Pump K6
Enter Desired EXVA Position
Enter Desired Energize Hot Gas Bypass Relay A
EXVB
COMMENT
Position
HGBRB X* MMA X*
MMB X*
32
Energize Hot Gas 8ypass Relay B Enter Desired Enter Desired Motormaster B Output Signal
Motormaster@
A Output Signal
Page 33
-
Table 9
Keypad Directory (cant)
TEST (cant)
During compressor test, compressors start and run for
10 seconds. Compressor service valves and liquid line valves must be open. Energize crankcase heaters 24 hours prior to performing compressor tests.
SUBFUNCTION
2 COMPRESSORS AND
UNLOADERS
KEYPAD ENTRY
DISPLAY
COMP
CPA1 X
CPA2 X*
CPA3 X*
CPA4 X*
CPBl X
CPB2
x*
CPB3 X*
CPB4 X*
ULAl X
ULA2 X*
ULBl X
ULB2 X*
COMMENT
Compressor and Unloader Test
Test Compressor Al
Test Compressor
Test Compressor A3t
Test Compressor A4t
Test Compressor Bl
Test Compressor B2t
Test Compressor
Test Compressor
Energize Unloader Al
Energize Unloader
Energize Unloader Bl
Energize Unloader B2t
A2T
B3T
B4T
T
A2T
t
SCHEDULE
The Schedule function key unoccupied shutdown or unoccupied setback depending on the cooling set point control configuration. The Schedule function
described is for clock 1, which is the internal clock. Password required for all subfunctions except override.
SUBFUNCTION
1 OVERRIDE
For example, to extend current occupied mode for 3 hrs, press:
2 CLOCK SELECT
LEGEND
-
Carrier Comfort Network
-
~~”
MOP
Electronic Expansion Valve
-
Maximum Operating Pressure
CHD
is used to configure the occupancy schedule The clock select subfunction can be used for
El
1
KEYPAD ENTRY
ppii-j
/qzq
I
I
DISPLAY
OVRD X Number of Override Hrs (0 - 4 Hrs)
OVRD 3
CLOCK XX Type of Clock Control
*Must be configured
tlf
applicable.
I
Extended Occupied Time
0 = No Clock, 1 = Clock 1 (Internal)
COMMENT
33
Page 34
-
Table 9
Keypad Directory
SCHEDULE (cant)
DISPLAY
COMMENT
To toggle between inputs (Yes/No) Press:
4 PERIOD 2
5 PERIOD 3 . . . 9 PERIOD 7 1 MH1 Period 3 . . . Period 7 Time Schedule. m H (
10 PERIOD 8
Fi Fi
/qH
1 Period 2 Time Schedule1 PERIOD 2
~~( Period 8 Time Schedule1 PERIOD 8
PERIOD
OCC
HH.MM
UN0
HH.MM
MON X
TUE X
WED x
THU X
FRl X
SAT X
SUN X
HOL X
~~$~
y
1
Period 1 Time Schedule
Occupied Time
Unoccupied Time
Monday Flag
Tuesday Flag
Wednesday Flag
Thursday Flag
Friday Flag
Saturday Flag
Sunday Flag
Holiday Flag
11 HOLIDAYS
New = Unassigned Holiday Date
For example: To enter July 4th holiday press: 07 04 01 operation, refer to Schedule Function section on page 45.
q
. Display shows Jul 04 For further information on the Schedule function and its
HOLIDAYS
DAT
MM.DD
DAT
MM.DD
NN
SERVICE
To view and modify configurations, the password must be entered under the log on subfunction.
SUBFUNCTION
1 LOG ON AND LOG OFF
At this time, configurations may be modified. When finished viewing and/or modifying configur
2 VERSION
KEYPAD ENTRY DISPLAY COMMENT
( mmmma
r;lH
p-&q
0
EHTR
0
+
LOG ON
(LOGGEDONILoggedOn
LOG OFF
EXIT LOG
VERSION
Define Calendar Holidays
Holiday Date 1
Holiday Date 30
Enter Password/Disable Password Protection
rtions,
log out as follows:
Disable Password Protection
Logged Off/Enable Password Protection
Software Information
See legend on page 30
4
cl
+
0
xxxxxxxx
34
Version No. of Software (CESRXX)
X
Language Options
Page 35
Table 9- Keypad Directory (cant)
SERVICE (cord)
The next 3 subfunctions provide the ability to modify configurations Refer to separate Installation, Start-Up, and Service Instructions supplied with unit for further information on changing configurations.
F.-’
To change a configuration, enter the new configuration and press4 while on the correct configuration.
SUBFUNCTiON
3 FACTORY
CONFIGURATION
KEYPAD ENTRY
t
Cl
DISPLAY COMMENT
FACT CFG xxxxxxxx
xxxxxxxx xxxxxxxx xxxxxxxx xxxxxxxx xxxxxxxx
Factory Configuration Codes Configuration Code 1
Configuration Code 2 Configuration Code 3 Configuration Code 4 Configuration Code 5 Configuration Code 6
i j,
I’ .
Fc,s;B,:
4 FIELD
CONFIGURATION
5 SERVICE
CONFIGURATION
t
Cl
t
c
t
c
t
[I
t
cl
t
cl
t
0
t
q
t
0
t
a
t
Cl
t
cl
t
cl
t
q
t
cl
+
cl
+
Cl
t
Cl
p-&q
t
cl
t
cl
t
Cl
t
cl
t
cl
t
cl
+
cl
t
q
t
cl
FLD CFG
EN0 X
BUS X BAUD X FLUID X UNITS X
LANG X NULA X NULB X HGB X SEQT X SEQF X
OPS
x HEADM X MM X CSPTYP X
CRTYP X ERTYP X LSTYP X RAMP X LOCK X
CPC
x
SRV CFG xxxxxxxx
xxxxxxxx
REFRIG X
TDTYP X
OPS
x
LPS x
FANTYP X SH X MOP X
Adjustable Field Configuration
CCN Element Address CCN Bus Number CCN Baud Rate Cooler Fluid Select Display Unit Select Display Language Select No Circuit A Unloaders No. Circuit B Unloaders Hot Gas Bypass Select
Loading Sequence Select Lead/Lag Sequence Select
Oil Pressure Switch Select
Head Pressure Control Method
Motormaster@
Cooling Set Point Control Select Cooling Reset Control Select External Reset Sensor Select Demand Limit Control Select Ramp Load Select Cooler Pump Interlock Select Cooler Pump Control Select
Service Configurations Configuration Code 7
Configuration Code 8
Refrigerant Pressure Transducer Select
Oil Transducer Set Point
Low Pressure Set Point Fan Staging Select EXV Superheat Set Point EXV MOP Set Point
Select
35
Page 36
Table 9
-
Keypad Directory (cant)
SUBFUNCTION
1 RUN TIME
2 STARTS
3 ALARM HISTORY
KEYPAD ENTRY
r;lm
+
0
4
cl
b
cl
1 2 1
lHlST1
+
cl
+
cl
+
cl
I
I 3 I lH4
DISPLAY COMMENT
RUN TIME HR X Total Hrs Unit Has a Comp Operating HRA X HRB X
STARTS
CY x Cycles from Stage 0 to Stage
CYA X Circuit A Starts CYB X Circuit B Starts
1 ALRMHIST
ALARM X
ALARM X ALARM X ALARM X ALARM X
1 Last 5 Alarms
SET POINT
To read a set point, go to proper subfunction and read desired set point To
LOCAL/ENABLE-STOP-CCN switch must be in LOCAL or STOP position,
SUBFUNCTION KEYPAD ENTRY
1 SET POINTS
2 RESET SET POINTS
DISPLAY
SET
POINT
CSPl
x
CSP2
x HSPA X HSPB X CRAMP X
t
RESET CRST2 X* CREF2 X*
CRSTI
X*
CREFI X*
Run Time lnformation
Circuit A Run Time Circuit B Run Time
Starts Information
1
Alarm Description
>
J
change
a set
point, enter
Jnit Set Point Chiller Fluid Set Point 1
Chiller Fluid Set Point 2
Head
Pressure Set Point Circuit A Head Pressure Set Point Circuit B
Pulldown
Limit
Reset Set Points Cooling Max Reset Max Reset Occurs at X mA or Degree Cooling Minimum Reset Min Reset Occurs at X mA or Degree
new set
COMMENT
point
value, then
press
ENTR
cl
3 DEMAND SET POINTS
4 DATE AND TIME
DEMAND
DLSl X*
DLS2 X* DMAX X* RMAX X*
DMIN
X*
RMIN
X*
SHED
X”
DATE.TIME
DAY HR.MIN
MM.DD YR
Demand Set Points Demand Switch 1 Set Point Demand Switch 2 Set Point
4-20 mA Maximum Demand Limit
Max Demand Limit Occurs at X
4-20
mA Minimum Demand Limit
Minimum Demand Limit Occurs at X CCN
Loadshed
Date, Time and Day of Week Day 1 = Mon, 2 = Tues
Hours are displayed in
Month.Day.Year.
point between entries. Each entry must be two numbers.
Amount
24-hr
When entering date, enter a decimal
mA
mA
7
= Sun
time. Decimal point serves as colon.
36
Page 37
STATUS FUNCTION - This function shows the rotating display, current status of alarm (diagnostic) codes, capacity stages, operating modes, chilled water set point, all meas­ured system temperatures and pressures, superheat values, pressure switch positions, analog inputs, and switch inputs. These subfunctions are defined on pages 37 and 38.
i
m Fi
(Rotating Display)
m Fi
(Alarms) - Alarms are messages that one or more faults have been detected. Each fault is assigned a code num­ber which is reported with the alarm. See Table 10 for code definitions. The codes indicate failures that cause the unit to shut down, terminate an option (such as reset) or result in the use of a default value as set point.
Up to 5 alarm codes can be stored at once. To view them
in sequence, press
mm
to enter the alarm displays
and then press q to move to the individual alarm dis-
plays. Press ing of the code scrolls across the screen. See Example
q
after a code has been displayed. The mean-
1
Example 1- Reading Alarm Codes
K EYPAD
ENTRY
p-jq
+
cl
EXPH
0
4
Ll
EXPN
0
DISPLAY
RESPONSE
‘MvoEo;2;;5
0 STAGES 2 ALARMS
2 ALARMS ALARM 9
COOLER LEAVING
FLUID THERMISTOR
FAILURE ALARM 42 COOLER FREEZE
PROTECTION
COMMENTS
Keypad has not been used for at least 10 minutes. Alternating summary display appears on screen
2 alarms detected
First alarm code
Explanation of alarm code
Second alarm code Cooler freeze protection
Explanation of alarm code
When a diagnostic (alarm) code is stored in the display and the machine automatically resets, the code is deleted. Codes for safeties which do not automatically reset are not deleted until the problem is corrected and the machine is switched to STOP, then back to LOCAL/ENABLE or CCN.
mbi
(Modes) - The operating mode codes are dis­played to indicate the operating status of the unit at a given time. See Table 10.
Table 10- Operationat and Mode Display Codes
The operating modes are displayed by name or code num­ber, to indicate the operating status of the unit at a given time. The modes are:
CODE 1 DESCRlPTlON
Unit is off. LOCAL/ENABLE-STOP-CCN switch is
LOCAL OFF
CCN OFF
CLOCK OFF
LOCAL ON
CCN ON
CLOCK ON pied override function. LOCALIENABLE-STOP-
MODE 7
MODE 8
MODE 9
MODE 10
MODE II
MODE 12
MODE 13
MODE 14
1
CCN - CarrierComfort Network
in OFF position, or LOCAL/ENABLE-STOP-CCN
switch may be in LOCAL position with external ON/
OFF switch in OFF position Unit is off due to CCN network command. LOCAL/
ENABLE-STOP-CCN switch is in CCN position.
I
Unit is off due to internal clock schedule. LOCAL/ ENABLE-STOP-CCN switch is in LOCAL position.
Unit is on. LOCAL/ENABLE-STOP-CCN switch is in LOCAL position If external ON/OFF switch is used, it will be in ON bosition.
Unit is on due to CCN command LOCAUENABLE- STOP-CCN switch is in CCN position.
Unit is on due to internal clock schedule or
I
CCN switch is in LOCAL position.
Dual set point is in effect In this mode, unit contin­ues to run in unoccupied condition, but leaving wa-
ter set point is automatically increased to a higher
level (CSP2 set
Temperature reset is in effect. In this mode, unit is
using temperature reset to adjust leaving water set
I
point upward, and unit is currently controlling to the modified set point. The set point can be modified based on return water, outdoor-air temperature or space temperature
Demand limit is in effect. This indicates that ca­pacity of unit is being limited by demand limit con-
trol option Because of this limitation, unit may
not be able to produce the desired leaving water
temperature
Load limit is in effect. This indicates that capacity of a system of units is being limited by a CCN
shed command Due to this limitation, unit may
not be able to produce the desired leaving water
temperature.
Not
aoalicable.
I I
Ramp load (pulldown) limiting is in effect. In this mode,
the
r&e
at which leaving water temperature is dropped is limited to a predetermined value to prevent com­pressor overloading, See CRAMP set point in the SET function in Table 9 The pulldown limit can be modified, if desired, to any rate from 2 F to 2 F
( lo
to lo Q/minute
Timed override is in effect This is a 1 to 4 hour temporary override of the programmed schedule, forcing unit to occupied mode Override can be im-
plemented with unit under LOCAL or CCN control Override expires after each use
Low cooler suction protection is in effect In this mode, circuit capacity is not allowed to increase if cooler
saturated suction temperature is
water or 30” F (16” C) for brine or more below ing fluid temperature, and saturated suction tem­perature is less than 32 F (0’ C). If these conditions persist beyond 10 minutes, circuit is shut down and
fault code 44 or 45 is displayed.
Point
is in SET function)
20”
F
(11”
occu-
load-
C) for
leav-
To enter the MODES subfunction, depress
use the q key to determine if more than one mode ap-
plies. See Example 2 to read current mode with expansion.
37
MFI
and
Page 38
Example 2
KEYPADIDISPLAY
ENTRY RESPONSE
p-lH
4
cl
+
cl
Reading Current Operating Modes
-
COMMENTS
TUE
15:45
LOCAL ON COOL 1 0 ALARMS
2 MODES
LOCAL ON MODE 8
I
Keypad has not been used for at least 10 minutes Rotating summary
display appears on screen
There are 2 modes currently in effect
Unit is on by chiller on/off switch
Temperature reset is in effect
m H
analog inputs, if any. Enter transducer supply voltage, 4-20 mA reset signal can be dis-
played. This is useful for problem diagnosis prior to using the test function.
m bi
(Inputs)- This subfunction displays status (ON/OFF) of input switch where applicable. Status of dual
set point switch, and demand limit switches 1 and 2 can be displayed. This is useful for problem diagnosis prior to us­ing the test function.
~~
l-ii 1;;;;1
(Stage)
This subfunction displays the capac-
-
ity stage number. See Tables 4A-4D for compressor load­ing sequence. To enter the STAGE subfunction, press
p--&q and use the q to display the stage number.
Additional m provides the following information:
Percent of total unit capacity being utilized. Percent of each circuit capacity being utilized.
tus of alarm relay, all fan relays, and chilled water pump relay. It also displays ON/OFF status of compressor unload­ers (if used). The position of each EXV (in percent open) can be displayed.
TEST FUNCTION - The test function operates the diag­nostic program. To initiate test function, the LOCAL/ ENABLE-STOP-CCN switch must be in STOP position.
To reach a particular test, enter its subfunction number,
then scroll to desired test by pressing the ( key. Press
Demand limit set point in effect (can be any value be­tween 0% and 100%).
Load limit set point in effect. This is a CCN function for
controlling operation of multiple units between 0% and
100% of total capacity of all units combined.
Status of each compressor relay. When a compressor is
on, the number of that compressor is displayed. If a com­pressor is off, a 0 is displayed. For example: In a given circuit, if compressors 1 and 3 are running, and 2 and 4 are not running, 0301 is displayed for that circuit.
Load/Unload factor for compressors. This factor is an in­dication of when a step of capacity is added or sub­tracted. Its value can range from slightly less than -1 .O to slightly more than + 1 .O. When load/unload factor reaches + 1.0, a compressor is added. When the load/ unload factor reaches -1 .O, a compressor is subtracted. If compressor unloaders are used, at
-.6
a compressor is
unloaded and at + .6, a compressor is loaded up.
mF[
(Set Point) - This subfunction displays leaving
B
exit a test. Pressing the vances system to next test, whether current test is operating
or has timed out, Once in the next step, you may start test by pressing H or advance past it by pressing
While the unit is in test, you may leave test function and
access another display or function by pressing appropriate
keys. However, a component that is operating when an-
other function is accessed remains operating. You must re-enter test function and press the ) key to shut down
the component. Components with a timed operating limit time out normally even if another function is accessed.
Keypad entry
following checks by using m :
water temperature and leaving chilled water set point. If unit is programmed for dual set point, the chilled water set point currently in effect (either occupied or unoccupied) is displayed. If reset is in effect, the unit operates to the mod-
ified chilled water set point. This means the leaving water temperature may not equal the chilled water set point The modified chilled water set point can also be displayed in the Status function. To enter the set point subfunction, de-
press
mb[
and use the
q
to display modified leaving
compressor unloader
chilled water set point followed by leaving water set point
and actual cooler leaving fluid temperature.
During compressor operational tests, compressor starts and runs for 10 seconds. Compressor service valves must
F[ F[
(Temperature) - The temperature subfunction dis­plays the readings at temperature sensing thermistors.
be open. Energize crankcase heaters 24 hours prior to performing compressor tests.
To read a temperature, enter Fi Fi , then scroll to de-
practice to also check all inputs and outputs accessible
m
sired temperature using the order of readouts.
key. See Table 9 for the
through the status function. These are located at F\ F[ ,
m H,
flH
(Pressure) - This subfunction displays suction,
discharge and net oil pressure at lead compressor of each
for 10 minutes, unit automatically leaves test function and resumes rotating display. See Example 3.
circuit of unit.
(Analog Inputs) - This subfunction displays
m Fi
, then use the
q
. The
(Outputs) - This function displays ON/OFF sta-
to start a test. Press
riF[
q
q
or
q
or H to terminate or
key after a test has started ad-
allows the operator to make the
I)I
.
LID display check. Propezisplay is 8.8.8.8.8.8.8.8 . Operation of remote alarm. Operation of condenser fans. Operation of chilled water pump. Operation of EXVs. To drive EXV fully open, enter
m m m
ter u (0% open). Keypad entry
(100% open). To drive EXV fully closed,
-mH I
accesses the compressor and.
operational
tests.
en-
c
Since test function checks only certain outputs, it is good
and
mm
(see Table 9). If keypad is not used
38
Page 39
Example 3 -Using Test Function
KEYPAD DISPLAY
ENTRY RESPONSE
NOTE: Once a compressor has been run using the is not allowed to run again for 30 seconds.
cl
+
I
COMP
CPA 1 OFF CPA 1 ON
CPA 1 OFF
CPA 2 OFF
Factory/field test of compressors subfunction of test function
Circuit A, Compressor 1A test
Pressing when the compressor should be running the display shows CPA1 on
If the test is allowed to time out (10 sec­onds) the display will show
Pressing the down arrow key advances the system to Circuit A, compressor 2 test
HISTORY FUNCTION - Keystrokes
COMMENTS
ENTR
starts the test:
mb]
CPA1
off
EST
function, it
El
and sub-
sequent [ keystrokes display total unit run time and total run time for each circuit.
.
Keystrokesm
m
and subsequent m keystrokes dis-
play total unit starts and the total starts for each circuit. KeystrokesFi
and subsequent
b[
q
keystrokes dis-
play the last 5 alarms along with a description of each alarm.
SET POINT FUNCTION - Set points are entered through the keypad. Set points can be changed within the upper and lower limits, which are fixed. The ranges are listed below.
Chilled Water Set Point
Water:
38 to 70 F (3.3 to 21 C)
Brine:
15 to 70 F (-9.4 to 21 C)
Pulldown Set Point
0.2 to 2.0 F (0.11 to 1.1 C)/min.
Reset Set Points
Maximum Reset Range:
0”
to 20” F (0” to 11” C)
Maximum Reset Reference Range:
Return Fluid Reset 0” to 20” F
(0” to 11” C)
External Temperature Reset 20 to 125 F
(-6.6 to 51.6 C)
External Signal Reset 4 to 20 mA
Minimum Reset Reference Range:
Return Fluid Reset 0” to 20” F
(0” to 11” C)
External Temperature Reset 20 to 125 F
(-6.6 to 51.6 C)
External Signal Reset 4 to 20 mA
Demand Limit Set Points
Switch Input:
Step 1 - 0 to 100% Capacity Reduction Step 2 - 0 to 100% Capacity Reduction
External Signal:
Maximum Demand Limit 4 to 20 mA Minimum Demand Limit 4 to 20 mA
Set points are grouped in subfunctions as follows:
m Fl
Displays chiller water and cooling ramp set points.
a. The first value shown is the occupied chilled water
set point.
b. The next value displayed depends on how the sched-
ule function has been programmed. (See pages 45-
47.) If dual set point has been selected, the next set point after m has been pressed is the unoccupied
chilled water set point. If single set point or inactive schedule has been selected in the schedule function,
then when
q
is pressed, the display shows the
modified chilled water set point.
c. The final value displayed when the
q
is pressed
is the cooling ramp loading rate. This is the maxi­mum rate at which the leaving chilled water is al­lowed to drop, and can be field set from 0.2 to 2.0 F
(.
11” to 1.1” C)/minute. This value is not displayed unless the function is enabled (see Adjustable Field Configurations on page 45).
Reading and
Channinrr
Set Points - Example 4 shows how to read and change the chilled water set point. Other set points can be changed by following the same procedure. Refer to Table 9 for the sequence of display of set points in each subfunction.
Example 4 -Reading and Changing
Chilled Water Set Point
KEYPAD
ENTRY
Temperature Reset Based on Return Water
DISPLAY
RESPONSE
SET POINT
CSPl 44.0
CSPI 420
CSP2
44.0
CSP2
50.0
RESET
COMMENTS
System set points Present occupied chilled water
set point is 44 0 F
~~~~~~~h~!$w~cupied
chilled water set point is 42 0 F Present unoccupied chilled water
set point is 44.0 F
Press the Fi ri
shows new unoccupied chilled water set point is 50.0 F
Displays the maximum reset and
minimum reset set points The
minimum and maximum reference reset set points can also be
displayed. These set points are not
accessible when reset type has
been configured for NONE in
the service function
F[
Display
TemDerature -
The control system is capable of providing leaving water
temperature reset based on return water temperature. Be­cause the temperature difference between leaving water tem­perature and return water temperature is a measure of the building load, return water temperature reset is essentially an average building load reset method.
Under normal operation, the chiller maintairis a constant leaving water temperature approximately equal to chilled water set point. As building load drops from 100% down to
O%,
entering cooler water temperature drops in proportion to load. Thus, temperature drop across the cooler drops from a typical 10 F (5.5 C) at full load to a theoretical 0” F (0” C) at no load. See Fig. 4.
At partial load, leaving chilled water temperature may be lower than required. If this is allowed to increase (reset), the efficiency of the chiller increases. Amount of reset can
be defined as a function of cooler temperature drop, as shown
in Fig. 4. This is a simple linear function that requires 4 pieces of input data for the set function:
39
Page 40
I.
Maximum Reset Amount (CRST2) - allowable range
0” to 20” F (0” to 11” C). This is maximum amount leav­ing chilled water set point is to be increased.
2. Maximum Reset Reference (CREF2) - allowable range
0” to 20” F (0” to 11” C). This is the cooler temperature
drop at which reset reaches its maximum value.
3. Minimum Reset Amount (CRSTl) - allowable range
0”
to 20” F (0” to 1 I” C). This is minimum amount leav­ing chilled water set point is to be increased when reset is initiated.
4. Minimum Reset Reference (CREFl) - allowable range
0” to 20” F (0” to 11” C). This is the cooler temperature drop at which reset is at its minimum value. (Reset be­gins here .)
NOTE: Reset set points are not accessible unless the reset function is enabled first. This is done as a field configura­tion. Select one of the 3 choices for type of reset: Return Fluid Reset, External Temperature Reset, or 4-20 mA Ex-
ternal Signal (with a loop isolator) Reset.
If dual set point control is enabled (see Field Wiring sec-
tion on page 7 1), the amount of reset is applied to which-
ever set point is in effect at the time.
Example 5 demonstrates how to activate reset. Example 6 demonstrates how to change the type of reset. Assume that reset is to be based on return water temperature, the desired reset range is to be 2” to 10” F (1” to 5.5” C) and full load is a 10” F (5.5” C) drop across the cooler. See Fig. 4.
Activating reset based on external temperature or 4-20 mA signal is done the same way, except the reference set point range is 20” to 125” F (-6.6” to 5 1.6” C), or 4 to 20 mA depending on which method was selected at the field configuration step.
Example 5- Using Return Water
Temperature Reset
KEYPAD DISPLAY
ENTRY
RESPONSE
FLD CFG
CSPTYP X
CRTYP 0
CRTYP 1 SET POINT
CPSl 44.0
CPSl 45 6
RESET CRST2 0 0
CRST2 10 0
CREF2 0.0
CREF2 1.0
CRSTI
0 0
CRSTI 2.0
CREFl 0.0
CREFl 8 0
COMMENTS
Field configuration subfunction of service function
Scroll past single/dual
Display shows no reset type has been selected
Return water temperature
is selected and activated
System set points
Present occupied chilled water set point
Enter new chilled water
set point
Reset set points
F;li;g
0
Cooling maximum reset
is 10 F
Cooling maximum reset
reference is 0” F
Cooling maximum reset
reference is 1 F
Cooling minimum reset
is 0” F
Cooling minimum reset
is 2 F
Cooling minimum reset
reference is 0” F
Cooling minimum reset
reference is 8 F
maximum reset
f73c=)
IO
9
8
7
18
16
2 3 4 5 6 7 8 9
RESET REFERENCE TEMPERATURE (COOLER EWT-LWT)
Fig.4-
-- /
35.3
MIN RESET REFERENCE (CREF
Cooling Return Water Reset
I ) q 13
100
80
60
0
IO
40
Page 41
Temperature Reset Based on External Temperature - If de-
sired, temperature reset can be based on an external tem­perature, such as space or outdoor-air temperature. This re-
quires a thermistor (TlO, Part No. 30GB660002) located in
the space or outdoor air and wired to terminals as follows
To change type of reset, first log on as shown in Table 11. Also refer to Set Point Function section, page 39, for information on entering reset set points using reset feature.
(also see Field Wiring section on page 71):
4 in/4 out Module - 57-15 and J7-16.
At the field configuration step, select external tempera-
ture reset by entering
q
when CRTYP 0 appears. Then
enter set points as described previously in Example 5. See Fig. 5.
Temperature Reset Based on 4-20 mA Signal- If desired, temperature reset can be based on a 4-20 mA signal. For
proper connections,
refer to Field Wiring section on page
71 and Fig. 6.
At the field configuration step, select 4-20 mA reset by
entering
q
when CRTYP 0 appears. Then enter set points
as described previously in Example 5. See Fig. 7,
Demand Limit, 2-Stage Switch Control - This control has been designed to accept demand limit signals from a build-
ing load shedding control. The demand limit function pro­vides for 2 capacity steps. The keypad is used to set the 2 demand limit set points, which range from 100 to 0% of capacity. Capacity steps are controlled by 2 field-supplied relay contacts connected to the designated chiller terminals. (See Field Wiring section on page 7 1 and Fig. 6.)
Example 6 -Changing Reset Type
KEYPAD DISPLAY
ENTRY
RESPONSE
FLD CFG
CSPTYP 0
CRTYP 0
CRTYP 1
CRTYP 2
CRTYP 3
CRTYP 0 Reset is deactivated
COMMENTS
Field configuration subfunction of service function
Scroll past single cooling set point
No reset has been selected
Return water temperature
reset is selected and activated
Reset type is changed to space or outdoor-air temperature reset and
activated Reset type is changed to
4-20 mA signal reset and activated
10 -
Y-
8-
?-
2-
I -
O-
18
16
8
6
RESET REFERENCE TEMPERATURE
Fig. 5
Cooling External Temperature Reset
-
(OUTDOOR
AIR 1 OR
SPACE TEMP
41
Page 42
POINT NUMBER OF FIRST CHANNEL
n
Q
EKE
LIMIT
(ALARM CODE 312
(MODE 91
(MODE 71
RFt!EF
(ALARM
COOE
21)
(MODE
El
Fig 6
PWR
I
In AOt
d
=
RET
DO+
z “1
rAO+
--e-------1-
__-----a
_------
__----
___---c---
---mm-
__----.
---se
---
----
- - - - - _ - - - - - - -
4 nw/4
OUJJU
A
--
-
B
c D
I-
d
H 4
5
‘-+p--------
COMM -Communications Bus
----__e-
f
__----a-
301
LB---------
4 IN/4 OUT Options Module Wiring for Reset, Demand Limit, an! Dual Set Point
-
----
__----
--
PWR
SW NOTE: For specific connection points,
see Fig. 24 - 29.
-
-
LEGEND
Power Switch
Table 11- Service Functions
To view and modify configurations, the password must
be entered under the log on subfunction.
I
KEY FAD
DISPLAY
PASSWORD
LOGGED ON Logged On
COMMENT
Enter Password/
Disable Password
SUB-
FUNCTION ENTRY
NOTE: Configurations may be modified at this time. When finished viewing and/or modifying configurations, log out as follows:
LOGGED ON
LOG OFF
EXIT
LOG
VERSION
xxxxxxxx
X
Disable Password Protection
Logged Off/
Enable Password Protection
Software Information
Version No of Software
Language Options
To use Demand Limit, first enable loadshed, then enter demand limit set points. See Example 7A. Closing the first stage demand limit contact puts unit on the first demand limit level, that is, the unit does not exceed the percentage of capacity entered as demand limit stage 1. Closing con­tacts on second-stage demand limit relay prevents unit from exceeding capacity entered as demand limit stage 2. The demand limit stage that is set to the lowest demand takes priority if both demand limit inputs are closed.
The demand limit function must be enabled in order to function and may be turned off when its operation is not desired. The demand limit relays can, in off condition, re­main connected without affecting machine operation.
-Demand Limit, 4-20 mA Signal - The controls can also accept a 4-20 mA signal for load shedding. Input for the signal are terminals shown below:
Externally powered (loop isolator required)
Positive lead to
57-5 -
4 In/4 Out Module
Negative lead to 57-6 - 4 In/4 Out Module
Internally powered
Positive lead to J7-6 - 4 In/4 Out Module Negative lead to 57-7 - 4 In/4 Out Module
See Field Wiring section on page 71 and Fig. 6.
At field configuration step, select 4-20 mA
loadshed
by
entering q when the LSTYP 0 display appears. See
Example 7B. Then enter set points as follows. In this ex-
ample, set points are coordinates of the demand limit curve shown in Fig. 8.
42
Page 43
16
8
6
0
0 2 4 6 8
RESET REFERENCE SIGNAL (4 -20 MA INPUT)
Fig. 7 -4-20 mA Cooling Temperature Reset
IO
12 14
16
18
20
Example 7A- Using Demand Limit
(First Log On as Shown in Table 11)
KEYPAD
ENTRY
DISPLAY
RESPONSE
FLD CFG
ERTYP
0
LSTYP
0
LSTYP 1
DEMAND
DLSl 100
DLSl 60
DLS2 100
DLS2 40
To Disable Demand Limit:
KEYPAD
ENTRY
DISPLAY
RESPONSE
FLD CFG
ERTYP 0
LSTYP 1
LSTYP 0
COMMENTS
Field configuration sub-
function of service function
Scroll past other elements in the subfunction
Loadshed Loadshed
for 2-stage switch control Demand Limit set points
subfunction of set point function
Loadshed
at 100%
Loadshed Loadshed
at 100%
Loadshed
Field configuration sub-
function of servicefunction
Scroll past other elements
in the subfunction
I
Loadshed
2-stage switch control
Loadshed
is not enabled is now enabled
1 currently set
reset to 60% 2 currently set
2 reset to 40%
COMMENTS
is enabled for
is now disabled
Example 7B
Using Demand Limit (4-20 mA)
-
(First Log On As Shown in Table 11)
KEYPAD
ENTRY
ppiq
t
0
Cl
ENTR
q ‘n
MH
DISPLAY
RESPONSE
FLD CFG
ERTYP 0 LSTYP
0
LSTYP 2
DEMAND DMAX 100 DMAX 90 RMAX 20
RMAX 15
DMIN
0
DMIN
20
RMIN
4
RMlN
6
COMMENTS
Field configuration subfunction
of service function
Scroll past other elements in
the subfunction
Loadshed Loadshed
for 4-20 mA signal control
Demand Limit set points
Maximum demand limit is 100%
Maximum demand limit is 90% Maximum demand limit
reference is 20 Maximum demand limit
reference is 15 Minimum demand limit is 0%
Minimum demand limit is 20% Minimum demand limit
reference is 4
Minimum demand limit
reference is 6
is not enabled is now enabled
mA
mA
mA
mA
NOTE: Select 3 for Carrier comfort Network (CCN) load limiting
Select 4 for CCN demand limiting.
43
Page 44
MAX DEMAND
DEMAND LlMlT SIGNAL (4-20 MA INPUT)
KIMAX)
= 90
Fig. 8 -4-20 mA Demand Limiting
Reading and Changing Time Displav - Time is entered and displayed in 24-hour time. The day of the week is
en-
tered as a number.
1 = Mon, 2 = Tue, 7 = Sun, etc.
m Kev
is used as the colon when entering time. See
I
Ex-
ample 8.
Example 8
Setting Time of Day and
-
Day of Week
KEYPAD DISPLAY
ENTRY
RESPONSE
TIME
MON 1600
TUE 13 05
JAN 01 90
APR 15 90
SERVICE FUNCTION - This function allows the
cian
to view and input configuration data. Factory
COMMENTS
Time display sub­function of set point function
Current setting is Monday, 4:00 p.m
New setting of Tuesday, I:05 p m is entered and displayed
Current date is Jan. 1, 1990
New setting April
15,
is entered and displayed
1990
techni-
config-
uration data, field configuration data and service configu­ration data may be viewed or entered through the keypad
and display module. See Table 9 for a complete listing of configurable items. Whenever a processor module is re­placed in the field, the complete list of configuration codes must be entered.
Logging On/Longing
Off - The service function is
pass-
word protected. Therefore, to gain entry to this function,
this password must be entered. Pressing allows the technician to view, change or enter
ml rim m
configura-
tion codes. To log off, perform the following keystrokes:
m biF]H
~ The service function is once again
pass-
word protected. Software Information - Fi
F/VI
displays the version
number of the software that resides in the processor mod­ule. Press
m
a second time to display the language op-
tions that are available in the field configuration group.
The
r;lF[
and
firI
bf
-mF[
t
allows entry into
Table 11
Factorv
s
Configuration Codes
2
SRVC
su uric ions are summarized in
the factory configuration subfunction. Under this subfunc­tion, there are 6 groups of configuration codes that are down­loaded at the factory. Each group is made up of 8 digits. If processor module is replaced in the field, these 6 groups of configuration codes must be entered through the keypad and display module. Factory configuration codes (groups 1 through
6) that apply to the particular Flotronic’” II chiller being serviced are found on a label diagram located inside the
control box cover. See Table 12 for a summary of factory
configuration subfunction keystrokes.
44
Page 45
Table 12
Factory Configuration Keystrokes
-
To change a configuration enter the new configuration
and press
3 FACTORY
Adiustable Field Configurations - After logging on, press
ri H
ation of the chiller to be customized to meet the particular needs of the application. The chiller comes from the fac­tory Each item should be checked to determine which configu­ration alternative best meets the needs of a particular appli­cation. See Table 13 for factory loaded configuration codes
q
SUB-
FUNCTION
CFG
5 %FE
while on the correct configuration.
DISPLAY COMMENTS
FACT CFG
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
SRV CFG
xxxxxxxx
xxxxxxxx
FACTORY
CONFlGURATlON
CODES
CJz;;g;ration
Configuration Code 3
Configuration Code 4
SERVICE
CONW;;T’ON
to enter subfunction. The subfunction allows oper-
preconfigured
to meet the needs of most applications.
CCN element address (Entered by CCN Technician)
CCN Bus Number (Entered by CCN Technician)
CCN Baud Rate (Entered by CCN Technician)
Cooler Fluid Select
1 = Water (38 to 70 F
2 = Medium Brine (15 to 70 F
Display Unit Select
0 = English 1 = Metric
Display Language Select 1 = English
No. Circuit A Unloaders
0 = No Unloaders
1 = One Unloader 2 = Two Unloaders
No. Circuit B Unloaders
0 = No Unloaders
1 = One Unloader
2 = Two Unloaders
Hot Gas Bypass Select 0 = No Valve
Loading Sequence Select
1
= Equal Circuit Loading
2 = Staged Circuit Loading Lead/Lag Sequence Select
1 = Automatic
Oil Pressure Switch Select
0 = Not Used
1 = Air Cooled Head Pressure Control Type
0 = Not Used
1 = Air Cooled Head Pressure Control Method
1 = EXV Controlled
2 = Set Point Control for 3 = Set Point Control for
4 = Set Point Control for
and alternative configurations.
If processor module is replaced, the replacement module is preloaded with factory default configuration codes. Each configuration code must be checked and, if necessary, re­configured to meet needs of the application. See Table 13 for pre-loaded service replacement configuration codes.
Service Configuration Codes - Press
r;lH
to enter the
service configuration subfunction. The first 2 items under this subfunction are 2 groups (8 digits each) of configura­tion codes that are downloaded at the factory. If processor module is replaced in the field, the 2 groups of configura-
tion codes must be entered through the keypad and display module. The 2 groups of configuration codes (groups 7 and
8) that apply to the unit being serviced can be found on a label diagram inside the control box cover. See Table 12 for keystroke information to enter configuration codes 7 and 8.
SCHEDULE FUNCTION - This function provides a means to automatically switch chiller from an occupied mode to an unoccupied mode, When using schedule function, chilled water pump relay must be used to switch chilled water pump on and off. Connections for chilled water pump relay are:
TB3-3 and TB3-4 (040-210 and associated modular units)
or TB5-3 and TB5-4 (225, 250, and 280 units). The chilled
water pump relay starts chilled water pump but compres-
Cooling Set Point Control Select 0 = Single Set Point Control
1 = External Switch 2 = Clock Controlled
Cooling Reset 0 = No Reset
i
= Return Fluid Reset
2 = External Temperature 3 = 4-20 mA Controlled
External Reset Sensor Select 0 = Thermistor Connected to
1 = Obtained Through CCN
Demand Limit Control Select
0 = No Demand Limiting
1 = Two External Switch Input 2 = External 4-20 mA 3 = CCN Load Limiting
4 = CCN Loadshed Interface
Ramo Load Select
~P@os~dol~ntrol)
1 = Enabled
Cooler Pump Interlock Select
0 = No Interlock
1 = With Interlock
Cooler Pump Control Select
0 = Not Controlled
1 = ON/OFF Controlled
sors do not run until remote chilled water pump interlock contacts are between TB6-1 and TB4-2 on 30GN040-210 and associated modular units, or between TB5-1 and TB5-2
EE
*And associated modular units
on 3OGT225, 250, and 280 Flotronic” units are closed and leaving chilled water temperature is above set point. If a remote chilled water pump interlock is not used, the first compressor starts (upon a call for cooling) approximately one minute after chilled water pump is turned on.
-
Table 13
FIELD CONFlGURATlON
ITEM AND CODES
[3.3 to 21 C] Set Point)
f-9 to 21 C] Set Point)
Both Circuits Circuit A; EXV Control
for Circuit B Circuit B; EXV Control
for Circuit A
Controlled Set Point
Set Point
Reset Reset
Options Module
(Multi-Unit)
LEGEND
-
Carrier Comfort Network
-
Electronic Expansion Valve
Adjustable Field Configurations
SI
Select
Control
-
Input
FACTORY
CONFF$ikTlON
001 001 000 000 9600
= Standard Models
I = Brine Models
0
I =
30GN190-HO*; 30GT225,250,280
=
30GN040-170*
)
=
30GN040-070,
190-210';
30GT225,250,280
=
30GN080-170*
0
0
0
0
0
0
SERVICE
IEPLACEMENT
CODE
9600
1
0
1
0
0
0
1
1
0
0
1
0
0
0
0
0
0
0
45
Page 46
The schedule function can be programmed for inactive,
single set point, or dual set point operation.
When schedule is configured for inactive, chilled water pump relay remains energized continuously but is not used since chiller is usually controlled by remote chilled water pump interlock contacts.
When unit is configured for single set point operation, chilled water pump relay is energized whenever chiller is in occupied mode regardless of whether chiller is running. When chiller is in unoccupied mode, chilled water pump relay is not energized.
When unit is configured for dual set point, chilled water pump relay is energized continuously, in both occupied and unoccupied modes. Occupied mode places occupied chilled water set point into effect; unoccupied mode places unoc­cupied chilled water set point into effect.
The schedule consists of from one to 8 occupied time pe­riods, set by the operator. These time periods can be flagged to be in effect or not in effect on each day of the week. The day begins at 00
.OO
and ends at 24.00. The machine is in
unoccupied mode unless a scheduled time period is in ef-
fect, If an occupied period is to extend past midnight, it must be programmed in the following manner: occupied pe-
riod must end at
period must be programmed to begin at
24:OO
hours (midnight); a new occupied
0O:OO
hours.
NOTE: This is true only if the occupied period starts at
0O:OO
(midnight). If the occupied period starts at a time other than midnight, then the occupied period must end at
0O:OO
hours (midnight) and new occupied period must be
programmed to start at
0O:OO
in order for the chiller to stay
in the occupied mode past midnight.
The time schedule can be overridden to keep unit in oc­cupied mode for one, 2, 3 or 4 hours on a one-time basis. See Example 9.
All subfunctions of schedule function are password pro­tected except the override subfunction, 17 b[ . word entry into subfunctions
f;l b[
through m m
Pass-
b[,
is done through service function. See page 44, logging on/ logging off.
Figure 9 shows a schedule for an office building with the chiller operating on a single set point schedule. The sched­ule is based on building occupancy with a 3-hour off-peak cool-down period from midnight to 3 a.m. following the weekend shutdown. To learn how this sample schedule would be programmed, see Example 9.
NOTE: This schedule was designed to illustrate the pro-
gramming of the schedule function and is not intended as a recommended schedule for chiller operation.
Example 9
-
Using the Schedule Function
DISPLAY
OVRD 0
OVRD 3
OVRO 0
CLOCK 0
CLOCK 1
CLOCK 65
PERIOD 1
UN0
MON NO
MON YES
TUE YES
TUE NO
PERIOD 2
occ 00 00
occ 7 00
UN0
UN0
MON NO
MON YES
TUE NO
TUE YES
WED YES
WED NO
No schedule override in effect
3 hours override in effect
Override cancelled
Schedule function is inactive
Schedule function is enabled through local unit clock
Schedule function is enabled throuah CCN clock 65
Define schedule period 1
Start of occupied time
For this example, first period should stat-t here
/;tntnnr$ht)
Start of unoccupied time (end of period) For this
00.00
&xampl&
end at 3:00 a m. Period 1 ends at 3:00 a m
Monday is now flagged no for oeriod 1 To out into’ effect on Monday must be flagged
Yes
Monday is now fla For this example, period
is to be in effect on Monday only All other days must checked to be sure that thev are flagged no. If any day flagged yes, change to no
Tuesday is now flagged no for period
Define schedule period 2
Start of occupied time
C$uo$e;;me will start
Start of unoccupied time (end of period) For this
00.00
example, period 2 should end at 18:00 (6:00 p m )
Period 2 ends at 18:OO
18 00
(6:00 p m )
Monday is now flagged no
for period 2 To put period 2
into effect on Monday, Monday must be flagged yes
Monday is now flagged for period 2 to be in effect
Tuesay is now flagged no for period 2 To put period 2
into effect on Tuesday,
Tuesday must be flagged
yes
Tuesday is now flagged for
period 2 to be in effect For this example, period 2
is to be in effect only on Monday and Tuesday All other days must be checked to be sure that
they are flagged no. If
a day is flagged yes, change to no
Wednesday is now flagged no for period 2
so no entry
period 1 should
M&day,
1
oeriod I
ged for
aperiod 1 to be in e
ect
1
be
ii
46
CCN
Carrier Comfort Network
-
Example 9 continued next page.
Page 47
Example 9 -Using the Schedule Function (cant)
KEENYTPRAYD
PROGRAMMING PERIOD 3:
DISPLAY
I
PERIOD 3
occ 00
occ 7 00
UN0 00 00
UN0
21 30
MON NO
TUE NO
WED NO
WED YES
THUR NO
FRI NO
SAT NO
SUN NO
a0
COMMENT
Define schedule period 3
Start of occupied lime
Tyo$e;;rne
Start of unoccupied time
(end of period 3). For this example, period 3 should end at
Period 3 ends at
(9:30 p m )
Check to be sure that
Monday and Tuesday are flagged for period 3
Wednesday is flagged
no, change to yes
Wednesday is now
flagged yes for period 3
Check to be sure that all other days are flagged no
will start
21:30 (9:30
p m )
22:30
Example 10
ENTER
Holiday Schedule Function
-
DISPLAY HOLIDAY JAN01 02 (Includes Jan
APR17
MAY21 01 (Includes May 21 st)
JUL03 01 (Includes July 3rd)
JULO4 01 (Includes July 4th)
SEP07 01 (Includes Sep 7th)
NOV26
DEC24 02 (Includes
DECBO
NEW
MAY25 01 (Includes May 25th)
NEW
NEW
and 2nd)
01 (Includes April 17th)
02 (Includes Nov 26th
and 27th)
and 25th)
02 (includes
and 3lst)
Dee
Dee
Ist
24th
30th
Period 4 and 5 can be programmed in the same manner, flagging Thursday and Friday yes for period 4 and Saturday yes for period 5 a For this example, periods 6, 7, and 8 are not used: they should be programmed OCC 00.00, UN0
00.00. NOTE: When a day is flagged yes for 2 overlapping peri-
NEW indicates a holiday that has not been assigned yet.
ods, occupied time will take precedence over unoccupied time. Occupied times can overlap in the schedule with no consequence.
To extend an occupied mode beyond its normal termina­tion for a one-time schedule override, program as shown below:
Holidav Schedule - Press
171 ri b[
to schedule up to
30 holiday periods. All holidays are entered with numerical values. First, the month (01 to 12), then the day (01 to 3
l),
then the duration of the holiday period in days. Examples: July 24 is 07.04.01.
Dee
25 - 26 is 12.25.02
If any of the 30 holiday periods are not used, the display
shows NEW.
See Example 10.
oo-
IO -
I3 ­14
I5 I6 I7 18
19
20
21
I 2­3-
4-
5-
6­t-
8­9-
II
I2
-
-
-
-
-
-
-
NEW
NEW
NEW (30TH
YEC
-
-
SAT
IlJh
­PERIOD
1
I
HOLlDAY)
#30-G3 v
‘EYo[
‘ERIO
3
-
-
m
OCCUPIED
UNOCCUPIED
I
Fig. 9
-
Sample Time Schedule
-
47
Page 48
TROUBLESHOOTING
The
FlotronicTY
technicians in troubleshooting a Flotronic II Chiller. By us-
II control has many features to aid the
13. Cooler entering or leaving fluid thermistor failure
14. Low transducer supply voltage
15. Loss of communications between processor module and
ing keypad and display module and status function, actual operating conditions of the chiller are displayed while unit is running. Test function allows proper operation of com­pressors, compressor unloaders, fans,
EXVs
and other com-
ponents to be checked while chiller is stopped. Service function
displays how configurable items are configured. If an op­erating fault is detected, an alarm is generated and an
alarm code(s) is displayed under the subfunction m
I;;;;]
,
along with an explanation of the fault. Up to 5 current alarm codes are stored. For checking specific items, see Table 9.
Checking Display Codes
-
To determine how ma-
chine has been programmed to operate, check diagnostic
16. Low refrigerant pressure
Single Circuit Stoppage
can be caused by the following:
1
2. Open contacts in lead compressor high-pressure switch
3. Low refrigerant pressure
4. Thermistor failure
5. Transducer failure
6. Ground fault in lead compressor indicator (indicator is
information (( w ) and operating mode displays (/ Fi ). If no
dismay annears,
ules
section+onlpage
follows:
1.
Note all alarm codes displayed, F\ bi .
2. Note all operating mode codes displayed,
3. Note leaving chilled water temperature set point in ef­fect and current leaving water temperature,
If machine is running, compare the “in effect” leaving water temperature set point with current water tempera­ture. Remember, if reset is in effect, the values may be different because machine is operating to the modified chilled water set point, If current temperature is equal to
set point, but set point is not the one desired, remember that if dual set point has been selected in the schedule function, there are 2 set points to which the machine can be operating. Check the programming of schedule func­tion
to
see if occupied or unoccupied set point should be
follow procedures in Control Mod-
64. If display is working, continue as
MH
.
MFI
.
7. High suction superheat
8. Low suction superheat
9. Lead compressor circuit breaker
10. Ground fault for any circuit compressor (130-210,225,
Lag Compressor Stoppage
page can be caused by the following:
1,
Open contacts in high-pressure switch
2. Compressor ground fault (indicator is field-supplied on 040-060, 070 [60 Hz], 080- 110, and associated modular units)
3. Compressor circuit breaker trip
4. Not required to run to meet cooling load requirement
in effect.
other control modules
-
Single circuit stoppage
Low oil pressure in lead compressor
field-supplied on 040-060, 070 [60 Hz], 080- 110, and associated modular units)
trip+
Stoppage of one circuit by a safety device action does not affect other circuit. When a safety device trips on a lead compres­sor, circuit is shut down immediately and EXV closes.
250, 280, and associated modular units).
-
Lag compressor stop-
Unit Shutoff
-
To shut unit off, move LOCAL/ ENABLE-STOP-CCN Switch to STOP position. Any re­frigeration circuit operating at this time continues to com­plete the pumpout cycle. Lag compressors stop immediately, and lead compressors run to complete
Complete Unit Stoppage
page can be caused by any of the following conditions:
1. Cooling load satisfied
pumpout.
-
Complete unit stop-
1
2. Remote ON/OFF contacts open
3. Programmed schedule
4. Emergency stop command from CCN
5. General power failure
6. Blown fuse in control power feed disconnect
7. Open control circuit fuse
8. LOCAL/ENABLE-STOP-CCN switch moved to STOP position
9. Freeze protection trip
10. Low flow protection trip
11. Open contacts in chilled water flow switch (optional)
12. Open contacts in any auxiliary interlock. Terminals that are jumpered from factory are in series with control
switch. Opening the circuit between these terminals places unit in stop mode, similar to moving the control switch to STOP position. Unit cannot start if these contacts are open. If they open while unit is running, unit pumps down and stops.
If stoppage occurs more than once as a result of any of the above safety devices, determine and correct the cause before attempting another restart.
Restart Procedure
After cause for stoppage has been
-
corrected, restart is either automatic or manual, depending on fault. Manual reset requires that LOCAL/ENABLE- STOP-CCN switch be moved to STOP position, then back
to original operating position. Some typical fault conditions
are described below. For a complete list of fault conditions, codes, and reset type, see Table 14.
POWER FAILURE EXTERNAL TO THE UNIT - Unit restarts automatically when power is restored.
Typical Stoppage Faults and Reset Types
Chilled Water, Low Flow Chilled Water, Low Temperature
Chilled Water Pump Interlock Control Circuit Fuse Blown
High-Pressure Switch Open Low Refrigerant Pressure Low Oil Pressure
Discharne Gas Thermostat Open
Manual reset
Auto reset first time, manual if repeat
Manual reset Unit restarts automatically when
power is restored
Manual reset Auto reset first time, then manual
if within same day Manual reset Manual reset
48
Page 49
Alarm Codes
-
Following is a detailed description of
each alarm code error and possible cause. Manual reset of
an alarm is accomplished by moving LOCAWENABLE- STOP-CCN Switch to STOP position, then back to LO­CAL or CCN position. See Table 14 for listing of each alarm code.
Code 0 No alarms exist Codes 1 - 8 Compressor failure
If DSIO-LV or -EXV relay module control relay feed-
back switch or signal is sensed as open during operation of
a compressor, microprocessor detects this and stops com-
Table 14 -Alarm Codes
pressor, energizes alarm light, and displays a code of I, 2,
3, 4, 5, 6, 7, or 8 depending on the compressor. Compres­sor locks off; to reset, use manual reset method.
If lead compressor in a circuit shuts down, the other com­pressors in the circuit stop and lock off. Only the alarm mode for lead compressor is displayed.
The microprocessor is also programmed to indicate com­pressor failure if feedback terminal on DSIO-LV or -EXV
53
terminal strip receives voltage when compressor is not
supposed to be on.
DISPLAY
No Alarms Exist
0
Compressor Al failure
1
2, 3, 4
6,
ES
7,
Compressor A2, A3, A4 failure Compressor shut down
Compressor Bl failure
5
Compressor B2; 83, 84 failure
8
Leaving water thermistor failure Unit shut down
9
Entering water thermistor failure Unit shut down
10
Compressor Al sensor failure
19
Compressor Bl sensor failure Circuit B shut down
20
Reset thermistor failure Normal set point used
21
Discharge pressure transducer failure, circuit A
22
Discharge pressure transducer failure, circuit B
23
Suction pressure transducer failure, circuit A Circuit A shut down
24
Suction pressure transducer failure, circuit B
25
Oil pressure transducer failure, circuit A
26
Oil pressure transducer failure, circuit B
27
Transducer supply voltage low
28 29
30
31
32
33 34
35 36
37
38 39 40
41
Interlock switch oaen Unit shut down 4-20 mA reset input failure Normal set point used
4-20 mA
Loss of communication with DSIO-LV Unit shut down
Loss of communication with DSIO-EXV
Loss of communication with 4 In/4 Out module Unit shut down Not used
Low refrigerant pressure circuit A
Low refrigerant pressure circuit B
oil pressure circuit A Circuit A shut down
oil pressure circuit B Circuit B shut down No
42 Cooler freeze protection Unit shut down
Low cooler water flow
43
Low suction temperature circuit A
44
Low suction temperature circuit B
45
High suction superheat circuit A Circuit A shut down
46
High suction superheat circuit B Circuit B shut down
47
Low suction superheat circuit A
48
Low suction superheat circuit B
49
Illegal configuration
50
Initial configuration required Unit cannot start
51
Emergency stop by CCN command Unit shut down
52
-
Compressor Protection Control Module
-
Power Supply
LEGEND
DESCRIPTION
demand limit failure
ACTION TAKEN
BY CONTROL
Circuit A shut down
Circuit B shut down Compressor shut down
Circuit A shut down
Circuit A shut down Circuit B shut down
Circuit B shut down Circuit A shut down Circuit B shut down
Unit shut down
Demand limit ignored
Unit shut down
I
Unit shut down
Circuit A shut down after 10 minutes
Circuit B shut down afler 10 minutes
Circuit A shut down Circuit 6 shut down
Unit cannot start
*Reset automatic first time, manual if repeated same day
CKT
-
-
PUMPDOWN
-
No
Yes
No
Yes
Yes Yes Yes Yes
No
Yes
Yes
No No No
NO
No No No No No
No
Yes
-
No
No
No No
No
No No
No
No
Yes
Yes
Yes Yes
-
-
Yes
- -
Manual Manual
Manual Manual
Auto Auto Auto Auto Auto
Auto. Auto Auto Auto. Auto. Auto
Auto Unit voltage low or PSI faulty
Manual
Auto Auto Auto.
Auto
Auto
thermostat trip, or wiring error
I
Thermistor or transducer failure
I
­*
*
Manual
Manual Faultv EXV, transducer, or thermistor. Manual
Manual
Manual Manual
Manual
ManualILow charge, faulty EXV or Manual
Manual Manual Manual Manual
CCN
PROBABLE CAUSE
High-pressure switch trip, discharge gas CPCS Ground Fault Protection
or wiring error.
Transducer failure or wiring error
Chilled water pump inoperative
Wiring error or improper
or faulty module
address code
-
Low refrigerant charge, plugged filter
drier, faulty EXV
Low refri erant charge, plugged filter
drier.I”fau tv EXV
~,
3
Faulty EXV, transducer, or thermistor
Low oil level, circuit breaker trip,
faulty EXV, crankcase heater,
or Pressure Transducer Low oil level, circuit breaker trip,
fautty EXV, crankcase heater, or
oressure
transducer
Low water flow or faulty thermistor Chilled water pump failure
or faulty thermistor Faulty EXV or thermistor
Faulty EXV or thermistor
thermistor, or plugged filter drier
Low charge, faulty EXV or thermistor, or plugged filter drier.
Faulty EXV or thermistor Faultv EXV or thermistor Configuration error Configuration omitted Network command.
49
Page 50
Possible causes of failure:
1.
High-Pressure Switch Open - High-pressure switch for each compressor is wired in series with 24-v power that energizes compressor control relay. If high-pressure switch opens during operation, compressor stops. This is detected by microprocessor through the feedback terminals.
3
d.
DSIO-LV or DSIO-EXV Module Failure - If a DSIO-LV
relay module relay fails open or closed, microprocessor detects this, locks compressor off and indicates an error.
3.
Wiring Errors - If a wiring error exists causing CPCS, CR, or feedback switch not to function properly, micro­processor indicates an error.
4.
Processor (PSIO) Failure - If hardware that monitors feedback switch fails, or processor fails to energize re­lay module relay to on, an error may be indicated.
NOTE: The control does not detect circuit breaker fail­ures. If a circuit breaker trips on lead compressor in a circuit, a low oil pressure failure is indicated. On the other compressors, no failure is indicated.
5.
Ground Fault Module on 130-2 10, 225, 250, 280, and associated modular units (CGFA or CGFB) Open - Mod­ule contacts are in lead compressor circuits, but ground fault could be in any compressor in affected circuit.
Ground fault of any 040-l 10 and associated modular unit compressor (field-supplied accessory on 040-060 and 070, 60 Hz units; standard on 070, 50 Hz and 80-l 10 and as-
sociated modular units) will cause a trip.
6.
Checkout Procedure - Shut off main power to unit. Turn on control power,
tion
MFi
to proper compressor number (i.e., failure
code 5 is compressor
then step through subfunc-
Bl).
Next, energize the step. If
step works correctly, then failure code is caused by:
l
HPS (high-pressure switch) open
l Misplaced feedback wire from
0
Ground wire and 24-v feeds reversed on one or more
points on
53
Compressor Alarm Circuit
54
and J5 terminals
-
For compressor Al alarm circuit, processor closes contacts between 54 termi­nals 2 and 3 to start compressor. See Fig.
10A -
10D. Safe­ties shown to left of 54 must be closed in order for power to reach compressor control relay, and the feedback input ter­minals on J3.
Failure of power to terminal 1 on 53, when contacts be-
tween 2 and 3 on J4 should be closed, causes a code 1
alarm.
Terminal 2 on 53 is the other leg of the compressor Al
feedback channel. It is connected to the 24-v common. NOTE: Similar connections for each compressor can be
fol-
lowed on the unit wiring diagrams located on the unit.
Code 9 Leaving water thermistor failure Code 10 Entering water thermistor failure
If temperature measured by these thermistors is outside range of -40 to 240 F (-40 to 116 C), unit shuts down after going through a normal
pumpout.
Reset is automatic if tem­perature returns to the acceptable range, and unit start-up follows normal sequence. Cause of fault is usually a bad thermistor, wiring error, or loose connection.
Code 19 Compressor Al suction sensor failure Code 20 Compressor Bl suction sensor failure
On units with thermistors, if temperature measured by these thermistors is outside the range of -40 to 240 F (-40 to 116 C), affected circuit shuts down after going through a
normal
pumpout.
Other circuit continues to run. Reset is
automatic if temperature returns to the acceptable range,
and circuit start-up follows normal sequence. Cause of
this-
fault is usually a bad thermistor, wiring error or loose connection.
On units with transducers, if the saturated suction tem-
perature is greater than the leaving water temperature plus
10” F (5.5 C) for more than 5 minutes, the affected circuit shuts down (after going through normal pumpout). The re­set is automatic if the saturated suction temperature returns to the acceptable range and start-up follows the normal se­quence. Cause of this fault is usually a bad transducer, a wiring error, or a loose connection.
Code 21 Reset thermistor failure (applies only to installa-
tions having external temperature reset)
If temperature measured by this thermistor is outside range of 40 to 240 F (-40 to 116 C), reset function is disabled and unit controls to normal set point. If temperature returns to the acceptable range, reset function is automatically en­abled. Cause of this fault is usually a bad thermistor, wir­ing error or loose connection.
Code 22
Compressor A 1 discharge pressure transducer failure
Code 23
Compressor B 1 discharge pressure transducer failure
Code 24
Compressor A 1 suction pressure transducer failure
Code 25
Compressor B 1 suction pressure transducer failure
Code 26 Code 27
Compressor Al oil pressure transducer failure Compressor Bl oil pressure transducer failure
If output voltage of any of these transducers is greater than 5 v, affected circuit shuts down without going through
pumpout
process. Other circuit continues to run. Reset is automatic if output voltage returns to the acceptable range, and circuit start-up follows normal sequence. Cause of fault is usually a bad transducer or a wiring error.
Code 28 Low transducer supply voltage
If transducer supply voltage is less than 4.5 v or greater than 5.5 v, unit shuts down without going through pumpout process. Reset is automatic if supply voltage returns to the
acceptable range, and circuit start-up follows normal se­quence. Cause of fault is usually a faulty transformer, or primary voltage is out of range.
The voltage supplied to the processor is polarized. When checking for proper voltage supply, be sure to consider this polarity. If voltage appears to be within acceptable toler-
ance, check to be sure the transformer supplying PSl is not grounded. Grounding the supply transformer can result in
serious damage to the control system.
Code 29 Chilled water pump interlock switch open
(applies only if unit is configured for use with a chilled water pump interlock).
Code can occur under any of these conditions:
1. Interlock switch fails to close
within
one
minute after
chilled water pump starts
2. Interlock switch opens during unit operation
3. Interlock voltage is detected, but unit is not configured for interlock
4. Interlock voltage is outside its valid range
If any of these conditions occur, all compressors are dis-
abled and, if running, shutdown occurs without
pumpout.
Chilled water pump also shuts down. Reset is manual, with LOCAL/ENABLE-STOP-CCN switch. Most probable cause of this fault is shutdown or failure of chilled water pump to start. Other possibilities are improper configuration or wir­ing errors.
50
Page 51
Code 30 Reset input failure (4 to 20 Code 31 Demand limit input failure (4 to 20
mA)
mA)
These codes apply only if unit is configured for these functions. If 4-20 mA signal is less than 4 or more than 20
mA,
reset or demand limit function is disabled and unit functions normally. If mA signal returns to the acceptable range, function is automatically enabled.
Code 32 Loss of communication with compressor
relay module (DISO-LV)
Code 33 Loss of communication with EXV relay
module (DSIO-EXV)
If communication is lost with either of these modules,
unit shuts down without
pumpout.
This alarm resets auto- matically when communication is restored. The unit starts up normally after alarm condition is reset. Probable cause of condition is a faulty or improperly connected plug, wir­ing error, or faulty module.
Loss of communication can be attributed to a grounded transformer with a secondary voltage of 21 vat supplying the PSIO, DSIO-LV, or 4 IN/4 OUT modules; the 12.5-vat transformer supplying the DSIO-EXV module; or the
24-vat
transformer supplying PS 1 for the transformers. These
transformers should not be grounded, or serious damage to controls can result. Check to be sure the transformers are
not grounded. NOTE: If a blank PSI0 module is downloaded without be-
ing connected to the modules DSIO, this alarm is energized.
Code 34 Loss of communication with 4 In/4 Out module
This applies only if one or more of the following options
are used:
0
external temperature reset
l 4-20 mA temperature reset l external switch controlled dual set point
l switch controlled demand limit l 4-20 mA demand limit
l
hot gas bypass
If communication is lost with 4 IN/4 OUT module, the
unit shuts off automatically, after finishing
pumpout.
Reset of alarm is automatic when communication is restored. Start-up after alarm is remedied follows a normal sequence. Proba­ble cause of condition is a faulty or improperly connected
plug, wiring error, or faulty module.
Loss of communication can be attributed to a grounded transformer with a secondary voltage of 21 vat supplying the PSIO, DSIO-LV, or 4 IN/4 OUT; the 12.5vat trans­former supplying the DSIO-EXV module, or the
24-vat
trans-
former supplying PS 1 for the transformers. These transformers
should not be grounded, or serious damage to controls can
result. Check to be sure the transformers are not grounded. Code 36 Low refrigerant pressure, Circuit A
Code 37 Low refrigerant pressure, Circuit B
If suction pressure transducer senses a pressure below set
point for more than 5 minutes at start-up or more than 2 minutes during normal operation, affected circuit shuts down without going through the
pumpout
process. Reset is automatic when pressure reaches 10 psig above set point if there have been no previous occurrences of this fault on the
same day. If this is a repeat occurrence on same day, then
reset is manual, with LOCAL/ENABLE-STOP-CCN switch,
Factory configured set point is 27 psig for standard chillers and 12 psig for brine chillers.
Possible causes of fault are low refrigerant charge, faulty
EXV, plugged filter drier, or faulty transducer. Code 38 Failure to pump out, Circuit A
Code 39 Failure to pump out, Circuit B
The
pumpout
tion temperature is 10” F (5.5” C) below temperature at
process is terminated when saturated suc-
be-
ginning of temperature or reaches a saturated suction temperature of
-15 F (-26 C). If appropriate saturated suction temperature is not met within 3 minutes (on 2 consecutive tries}, circuit shuts down without pumpout. Reset is manual with LOCAL/ ENABLE-STOP-CCN Switch, and start-up follows normal
sequence.
Possible causes for this alarm are a bad thermistor or trans-
ducer or a faulty EXV. Code 40 Low oil pressure, Circuit A
Code 41 Low oil pressure, Circuit
If oil pressure differential is less than set point for more than 2 minutes at start-up, or more than one minute during normal operation, affected circuit shuts down without go­ing through pumpout process, Reset is manual with LOCAL/ ENABLE-STOP-CCN switch, and start-up follows normal sequence. 6 psig.
Possible causes of fault are faulty compressor, EXV, crank­case heater or transducer, refrigerant overcharge, insuffi­cient oil charge, or tripped circuit breaker.
Code 42 Cooler freeze protection
If cooler entering or leaving water temperature is below 34 F (1.1 C) for water or more than 8” F (4.4” C) below set point for brine, unit shuts down without water pump continues to run if controlled by chiller con­trols. Reset is automatic when leaving water temperature reaches 6” F (3” C) above set point, providing there has been no prior occurrence of this fault the same day. If fault has occurred previously the same day, reset is manual with LOCAL/ENABLE-STOP-CCN switch.
Possible causes of fault are low water flow or faulty
thermistor. Code 43 Low water flow
If any compressors are operating and entering water tem-
perature is 3” F (1.7” C) or more below leaving water tem-
perature for more than one minute, unit shuts down without
pumpout.
manual with LOCAL/ENABLE-STOP-CCN switch, and start-up follows normal sequence.
This is a suitable method for sensing low water flow be­cause entering water thermistor is in the cooler shell and responds more quickly to compressor operation than the leav­ing water thermistor in the leaving water nozzle, Possible causes of fault are faulty chilled water pump, control or thermistor.
Code 44 Low cooler suction temperature, Circuit A
Code 45 Low cooler suction temperature, Circuit B
If saturated suction temperature is less than 32 F (0°C) and is 20” F (11” C) for water or 30” F (16” C) for brine or more below leaving fluid temperature, mode 14 is dis-
played. Unit continues to run, but additional compressors
are not allowed to start, If condition persists for more than
10 minutes, fault code is displayed, and unit shuts down without STOP-CCN switch, and start-up follows normal sequence.
Possible causes of fault are low refrigerant charge, plugged
filter drier, or a faulty EXV or thermistor. Code 46 High suction superheat, Circuit A
Code 47
If EXV is fully open, suction superheat is greater than 75 F (42 C) and saturated evaporator temperature is less than MOP (maximum operating pressure) for more than 5 minutes, unit shuts down after normal Reset is manual with LOCAL/ENABLE-STOP-CCN switch,
and start-up follows normal sequence.
51
pumpout,
or
10”
F (5.5” C) below leaving water
B
Factory configured differential oil pressure is
pumpout.
Chilled
Chilled water pump also shuts down. Reset is
pumpout.
Reset is manual with LOCAL/ENABLE-
High suction superheat, Circuit B
pumpout
process.
Page 52
Possible causes of fault are low refrigerant charge, plugged
filter drier, or a faulty EXV or thermistor. Code 48 Low suction superheat, Circuit A
Code 49
Low suction superheat, Circuit B
If EXV is at minimum position, suction superheat is less
than
10”
F (5.5” C) or saturated evaporator temperature is greater than MOP (maximum operating pressure) for more than 5 minutes, affected circuit shuts down after going through
pumpout
process, Reset is manual with LOCAL/ENABLE-
STOP-CCN switch, and start-up follows normal sequence.
Possible causes of fault are faulty EXV or thermistor.
Code 50 Illegal configuration
This fault indicates a configuration error. Unit is not al­lowed to start. Check all configuration data and set points and correct any errors.
Code 51 Initial configuration required
i2G7
This fault indicates factory configuration has not been done, and unit is not allowed to start. Refer to unit wiring label diagrams for factory configuration codes, There are 8 groups of S-digit numbers that must be entered. The first
4
groups must be entered under17 asubfunction. Groups
7 and 8 must be entered under MHsubfunction.
Enter each group, then press the H key. Use the
down arrow +0
after each group to bring up the next
empty screen. Unit should start after factory and field con­figurations are correctly entered.
The usual cause of this fault is replacement of the pro­cessor module. Refer to instructions accompanying the re­placement module.
Code 52 Emergency stop by CCN command.
Unit goes through normal shutdown when this command is received, and goes through normal start-up when com- mand is cancelled.
STANDARD: 040-060 50 Hz
040-070 60 Hz
r
----I------
,
1 CR’S
[CPCS Sl
Fig.
IOA -
STANDARD: 070 50 Hz ACCESSORY: 040-060 50 Hz
040-070 60 Hz
&I
COMM
CPCS
CR DGT
DSIO
HPS
K
PWR SNB
TB
TRAN
U
24-V Safety Circuit Wiring (040-070)
52
LEGEND
Contactor Circuit Breaker Communications Bus Compressor Protection Control Module Compressor Contactor Relay
Discharge Gas Thermostat (Optional) Relay Module (Low Voltage) High-Pressure Switch
-
Low
Vottage
Plug Power Snubber
-
Terminal Block
-
Transformer
-
Unloader
Page 53
TE7 REO
CONTROL
I
24VAC
32MP
CN5
I
IlEO2
5CtlEliATIC
TNANZ
-
w
21V
SECONDARY
1
]TE?
DGT
DSIO
HPS
E!
PWR
GLN
U
LEGEND
-
Contactor
-
Communications Bus
-
Compressor Protection Control Module
-
Discharge Gas Thermostat (Optional)
-
Relay Module (Low Voltage)
-
l-tigh-Pressure Switch
-
Low Voltage
-
Plug
-
Power
-
Terminal Block
-
Transformer
-
Unloader
Fig.
1OB -
24-V Safety Circuit Wiring (080-110 and Associated Modular Units)
53
Page 54
P
CGF
EM” E? kL
SNB
TB
TRAN
U
LEGEND
Ground Fault Module Communications Bus Compressor Contactor Relay
Relay Module (Low Voltage) High-Pressure Switch Low Voltage
Plug Snubber Terminal Block Transformer
Unloader
Fig.
IOC -
24-V Safety Circuit Wiring (130-210 and Associated Modular Units)
54
Page 55
c -
CGF
Z” 1
DGT
DSIO -
EXV HPS
/$
::
;b I:
TB
LEGEND
Contactor
Ground Fault Module
-
Common Control Relay
Discharge Gas Thermostat (Optional)
-
Relay Module (Low Voltage)
-
Electronic Expansion Valve High-Pressure Switch
-
Low Volta Normally Plug Reset Button Terminal Board
-
8
e
losed
Fig.
IOD -
PL12-7 Poll-7
24-V Safety Circuit Wiring (225, 250, and 280 Units)
55
Page 56
1.
Electronic Expansion Valve
EXV OPERATION - These valves control the flow of liq­uid refrigerant into the cooler. They are operated by pro­cessor to maintain a specified superheat at lead compressor entering gas thermistor (located between compressor motor
and cylinders). There is one EXV per circuit. See Fig. 11.
High-pressure liquid refrigerant enters valve through bot­tom. A series of calibrated slots are located in side of ori­fice assembly. As refrigerant passes through orifice, pres-
sure drops and refrigerant changes to a 2-phase condition (liquid and vapor). To control refrigerant flow for different operating conditions, sleeve moves up and down over ori-
fice, thereby changing orifice size. Sleeve is moved by a linear stepper motor. Stepper motor moves in increments and is controlled directly by processor module. As stepper motor rotates, motion is transferred into linear movement by lead screw. Through stepper motor and lead screws, 760 discrete steps of motion are obtained. The large num­ber of steps and long stroke result in very accurate control of refrigerant flow.
The
biF\
subfunction shows EXV valve position as
CHECKOUT PROCEDURE - Follow steps below to di-
agnose and correct EXV problems.
1,
Check EXV driver outputs. Check EXV output signals
at appropriate terminals on EXV driver module (see Fig. 12) as follows:
Connect positive test lead to terminal 1 on EXV driver. Set meter for approximately 20 vdc. Enter outputs
subfunction of test function by pressing advance to EXVA test by pressing
T;ip--p-&q*
fully open. During next several seconds connect nega­tive test lead to pins 2, 3, 4 and 5 in succession. Voltage should rise and fall at each pin. If it remains constant at a voltage or at zero v, remove connector to valve and recheck.
Press m H to close circuit A EXV. If a problem still exists, replace EXV driver module. If voltage reading is
correct, expansion valve should be checked. Next, test EXVB. Connect positive test lead to pin 7 and the neg-
a percent of full open. Position should change constantly
while unit operates. If a valve stops moving for any reason
(mechanical or electrical) other than a processor or ther-
2. Check EXV wiring, Check wiring to electronic expan-
mistor failure, the processor continues to attempt to open or close the valve to correct the superheat. Once the calcu-
Fig. 12.
lated valve position reaches 60 (fully closed) for 040-210
and associated modular units, 145 (fully closed) for 225,
250, and 280 units, or 760 (fully open) it remains there. If EXV position reading remains at 60, 145 or 760, and the
thermistors and pressure transducers are reading correctly,
the EXV is not moving. Follow EXV checkout procedure
below to determine cause.
b. Check for continuity and tight connection at all pin
c. Check plug connections at driver and at EXVs to be
The EXV is also used to limit cooler suction temperature to 50 F (10 C). This makes it possible for chiller to start at higher cooler water temperatures without overloading com­pressor. This is commonly referred to as MOP (maximum operating pressure), and serves as a load limiting device to
EXV DRIVER
BOARD - J4
I
prevent compressor motor overloading, This MOP or load limiting feature enables the 30G
FlotronicT’
II chillers to operate with up to 95 F (35 C) entering water temperatures during start-up and subsequent pull-down.
riF[
, then
q
8 times. Press
The driver should drive the circuit A EXV
ative test lead to pin 8, 9, 10, 11 in succession during EXVB test.
sion valves from terminal strip on EXV driver. See
a. Check color coding and wire connections. Make sure
they are connected to correct terminals at driver and EXV plug connections.
terminals.
sure EXV cables are not crossed.
ORIFICE ASSEMBLY (INSIDE PISTON SLEEVE)
Fig. 11 -
STEPPER
‘DC)
Electronil c Expansion Valve (EXV)
T
EXV -Electronic Expansion Valve
Fig. 12 -EXV Cable Connections to
EXV Driver Module,
3. Check resistance of EXV motor windings. Remove plug at 54 terminal strip and check resistance between com-
mon lead (red wire, terminal D) and remaining leads, A, B , C, and E (see Fig. 12). Resistance should be
25 ohms
-1-
2 ohms.
Control of valve is by microprocessor. A thermistor and
a pressure transducer located in lead compressor are used to determine superheat. The thermistor measures tem­perature of the superheated gas entering the compressor cylinders. The pressure transducer measures refrigerant pressure in the suction manifold. The microprocessor con­verts pressure reading to a saturation temperature. The difference between temperature of superheated gas and saturation temperature is the superheat.
56
DSIO (EXV)
Page 57
,/:.
::.
i .‘I
_I.:
Because the EXVs are controlled by the processor mod­ule, it is possible to track valve position. During initial
start-up, EXV is fully closed. After start-up, valve po­sition is tracked by processor by constantly observing amount of valve movement.
The processor keeps track of EXV position by counting the number of open and closed steps it has sent to each
valve. It has no direct physical feedback of valve posi­tion. Whenever unit is switched from STOP to RUN po-
sition, both valves are initialized, allowing the proces-
sor to send enough closing pulses to the valve to move it from fully open to fully closed, then reset the position counter to zero.
4. The EXV test can be used to drive EXV to any desired position. When EXV opens, the metering slots begin to provide enough refrigerant for operation at these steps:
step 60 for sizes 040-210 and associated modular units, or
145
for sizes 225, 250, and 280. This is fully closed
position when circuit is operating. The fully open posi-
tion is 760 steps.
5. Check thermistors and pressure transducers that control EXV. Check thermistors and pressure transducers that
control processor output voltage pulses to EXVs. See Fig, 13 for locations.
Circuit A - Thermistor T7, Suction Pressure Trans­ducer SPTA
Circuit B - Thermistor T8, Suction Pressure Trans­ducer SPTB
a. Use temperature subfunction of the status function
(m bi )
to determine if thermistors are reading
correctly.
b. Check thermistor calibration at known temperature
by measuring actual resistance and comparing value
measured with values listed in Tables 15 and 16.
c. Make sure thermistor leads are connected to proper
pin terminals at 57 terminal strip on processor mod­ule and that thermistor probes are located in proper position in refrigerant circuit. See Fig. 14 and 15.
d. Use the pressure subfunction of the Status function
( m
Fl)
to determine if pressure transducers are reading correctly. Connect a calibrated gage to lead compressor suction or discharge pressure connection
to check transducer reading.
e. Make sure transducer leads are properly connected in
junction box and at processor board. Check trans-
former 5 output. Check voltage transducer 5 vdc +
.2 v.
When above checks have been completed, check ac­tual operation of EXV by using procedures outlined
in Step 5.
6. Check operation of EXV. a. Close liauid line service valve of circuit to be checked,
and run ihrough the test step ( 17 Fi ) for lead com-
nressor
in that circuit to pump down low side of
iem. Repeat test step 3
tcmes-to
ensure all refrigerant
sys-
has been pumped from low side. NOTE: Be sure to allow compressors to run for the
full
pumpout
period.
b. Turn off compressor circuit breaker(s). Close com-
pressor discharge service valves and remove any re-
maining refrigerant from low side of system.
c. Remove screws holding top cover of EXV. Carefully
remove top cover. If EXV plug was disconnected dur­ing this process, reconnect it after cover is removed.
When removing top cover, be careful to avoid dam­aging motor leads.
d. Enter appropriate EXV test step for EXVA or
EXVB in the outputs subfunction of the test function
(jlF[). Press-mmriH
to initiate test. With
cover lifted off EXV valve body, observe operation of valve motor and lead screw. The motor should turn counterclockwise, and the lead screw should move up out of motor hub until valve is fully open. Lead screw movement should be smooth and uniform from
fully closed to fully open position. Press
l-+$0
check open to closed operation. If valve is properly connected to processor and re-
ceiving correct signals, yet does not operate as de-
scribed above, valve should be replaced. Operation of EXV valve can also be checked without
removing top cover. This method depends on oper-
ator’s skill in determining whether or not valve is moving. To use this method, initiate EXV test and open valve. Immediately grasp EXV valve body. As valve drives open, a soft, smooth pulse is felt for ap­proximately 26 seconds as valve travels from fully closed to fully open. When valve reaches end of its opening stroke, a hard pulse is felt momentarily. Drive valve closed and a soft, smooth pulse is felt for the 26 seconds necessary for valve to travel from fully open to fully closed. When valve reaches end of its stroke, a hard pulse is again felt as valve overdrives by 50 steps. Valve should be driven through at least
2 complete cycles to be sure it is operating properly. If a hard pulse is felt for the 26 second duration, valve is not moving and should be replaced.
The EXV test can be repeated as required by enter-
ing any percentage from 0 (
r;l )
to 100 to initiate
movement.
If operating problems persist after reassembly, they may be due to out-of-calibration thermistor(s) or inter­mittent connections between processor board terminals and EXV plug. Recheck all wiring connections and volt-
age
signals,
Other possible causes of improper refrigerant flow con­trol could be restrictions in liquid line, Check for plugged filter drier(s) or restricted metering slots in the EXV. Formation of ice or frost on lower body of electronic ex­pansion valve is one symptom of restricted metering slots. However, frost or ice formation is normally expected when leaving fluid temperature from the cooler is below 40 F. Clean or replace valve if necessary.
NOTE: Frosting of valve is normal during compressor Test steps and at initial start-up. Frost should dissipate after 5 to 10 minutes operation in a system that is oper­ating properly. If valve is to be replaced, wrap valve with a wet cloth to prevent excessive heat from damag-
ing internal components.
57
Page 58
MUFFLERS
COMPRESSORS
LEGEND
DPT
:ppTT
T
Discharge Pressure Transducer
-
-
Oil Pressure Transducer
-
Suction Pressure Transducer
-
Thermistor Number
FILTER
c
I
I
CIRCUIT
r
Fig. 13
-
CIRCUIT A
Thermistor and Pressure Transducer Locations
B
DRIER
-
J
58
Page 59
AIR VENT
:
LEAVING WATER/BRINE THERMISTOR (Tl)
COOLER FLUID BAFFLE CONNECTION
ENTERING
WATER/BRINE
SUCTION
CONNECTION
LEAVING
WATER/BRINE
CONNECTION
I
COOLER TUBE (TYPICAL)
ENTERING WATER/BRINE THERMISTOR
INLET
CONNECTIONDRAIN
Fig. 14 -Thermistor Locations
(Circuits A and B, Lead Compressor Only)
COUPLING ACCESSORY
poi-i,
(~~~%~~
FERRULES INSIDE
WATER-SIDE TEMPERATURE SENSOR (Tl, T2, - ALL UNITS),
3/16” (4 8) DIA 114” (6.4)
(T7, T8 - 225, 250, 280)
1
f
JACKETED
I
OD COUPLING
Fig. 15
I
REFRIGERANT TEMPERATURE SENSOR (T7, T8 - 040-210 AND
Thermistors
-
59
JACKETED SENSOR CABLE TUBE
AY
NOTE: BEND
FOR INSERTION INTO WELL
SLIGHTLY-
ASSOCIATED MODULAR UNITS)
(76)
(4 6)
THERMISTOR WELL
Page 60
Thermistors
perature vs. resistance performance. Resistance at various temperatures are listed in Tables 15 and 16.
LOCATION - General location of thermistor sensors are shown in Fig. 13.
Cooler Leaving Water Thermistor (Tl) - Tl is located in leaving water nozzle. The probe is immersed directly in the
water. All thermistor connections are made through a
coupling. See Fig. 15. Actual location is shown in Fig. 13
and 14.
Cooler Entering Water Thermistor (T2) - T2 is located in cooler shell in first baffle space near tube bundle. Ther-
mistor connection is made through a
Fig. 15. Actual location is shown in Fig. 13 and 14.
Compressor Suction Gas Temperature Thermistors
T8) - T7 and T8 are located in lead compressor in each
circuit in suction passage between motor and cylinders, above oil pump. They are well-type thermistors on 040-210 and associated modular units, or ferrule-type on 225, 250, 280 units. See Fig. 13 and 14.
THERMISTOR REPLACEMENT (Tl , T2, T7, TS) (Com­pressor and Cooler)
Thermistors are installed directly in fluid or refrigerant circuit. Relieve all refrigerant pressure using standard refrigerant practices or drain fluid before removing.
Proceed as follows (see Fig. 15): To replace sensors
(225,250,280)
1. Remove and discard original thermistor and coupling. IMPORTANT: Do not disassemble new coupling.
Install as received.
2. Apply pipe sealant to ment coupling and install in place of original. Do not use packing nut to tighten coupling. This damages fer­rules (see Fig. 15).
3. Insert new thermistor in coupling body to its full depth. If thermistor bottoms out before full depth is reached, pull thermistor back out
nut. Hand tighten packing nut to position ferrules, then finish tightening are now attached to thermistor which can be withdrawn
from coupling for unit servicing.
To replace thermistors T7 and T8 (040-210 and associated
modular units):
Add a small amount of thermal conductive grease to ther­mistor well. Thermistors are friction-fit thermistors, which must be slipped into receiver located in the compressor pump end.
All thermistors are identical in their tem-
-
%-in.
%-in.
coupling. See
(T7
and
Tl,
T2, T7 (225,250,280), and
‘/a-in.
NPT threads on replace-
I/s
in, before tightening packing
19’4
turns with a suitable tool. Ferrules
T8
I
Pressure Transducers
ducers are used on 30G Flotronic’” sure transducer and a high pressure transducer. The low pressure transducer is identified by a white dot on the body of the transducer, and the high pressure transducer by a red dot. See Fig. 16.
Three pressure transducers are mounted on each lead com-
pressor: 2 low-pressure transducers to monitor compressor
suction pressure and oil pressure, and a high-pressure trans-
ducer to monitor compressor discharge pressure (see Fig. 17 for exact locations on compressor). Each transducer is supplied with 5 vdc power from a rectifier which changes 24 vat to 5 vdc.
TROUBLESHOOTING - If transducer is suspected of be-
ing faulty, first check supply voltage to transducer. Supply
voltage should be 5 vdc + .2 v. If supply voltage is cor­rect, compare pressure reading displayed on keypad and dis-
play module against pressure shown on a calibrated pres-
sure gage. If the 2 pressure readings are not reasonably close, replace pressure transducer.
TRANSDUCER REPLACEMENT
Transducers are installed directly in the refrigerant cir­cuit. Relieve all refrigerant pressure using standard re­frigeration practices before removing.
r
1. Relieve refrigerant pressure using standard refrigeration
2. Disconnect transducer wiring at transducer by pulling
3. Unscrew transducer from
4. Insert weathertight wiring plug into end of transducer
5. Check for refrigerant leaks.
WHITE DOT-LOW PRESSURE TRANSDUCER RED DOT -HIGH PRESSURE TRANSDUCER
SAE
-
TWO
tvpes
of pressure trans-
Ii*chille&:
practices.
up on locking tab while pulling weather-tight connection
pfug from end of transducer. Do not pull on trans-
ducer wires.
!&in.
male flare fitting. When installing new pressure transducer, do not use thread sealer. Thread sealer can plug transducer and render it inoperative.
until locking tab snaps in place.
a low pres-
-75”
l/4”
SAE FEMALE FLARE
Society of Automotive Engineers
-
60
Fig. 16 -Pressure Transducer
Page 61
Table 15-
Thermistor Temperature
(OF)
vs Resistance/Voltage Drop;
Flotronic’”
II
TEMP:;fTURE
-2i.b
-24.0
-23.0
-22.0
-21.0
-20.0
-18.0
-17.0
-16.0
-
15.0
-
14.0
-13.0
-12.0
-11.0
-
10.0
-9.0
-8.0
-7.0
-6.0
-5.0
-4.0
I;.;
-l:o
0.0
::: too
5:o
7x
8:0
9.0
10.0
11.0
12.0
13.0
14.0
i5.0
16.0
17.0
18.0
19.0
20.0
21.0
22.0
23.0
24.0
25.0
26.0
27.0
28.0
29.0
30.0
31 .o
32.0
33.0
34.0
35.0
36.0
37.0
38.0
39.0
40.0
41.0
42.0
43.0
44.0
45.0
46.0
47.0
48.0
49.0
50.0
51.0
52.0
53.0
54.0
55.0
56.0
57.0
58.0
!
59.0
60.0
62.0
63.0
64.0
65.0
66.0
67.0
68.0
69.0
VOLTAGE
DROP (V)
4821
4818 4814 4806
4.800 4793 4786 4779 4772 4764
4.757 4749 4740 4734 4724 4715 4705 4696
4.688 4676
4666 4657
4648
EEi
4'613 4602 4592 4579
4.567 4554 4540 4527
4.514
4.501
4487 4472 4457
4442
4427
4413
4397
4.381
4366
4348
4.330
4313
4.295
4278
4258
4241
4223
4202
4184
4.165
4145
4125
4103
4082
4.059
4037
4017
3994
3.968
3.948
3927
3902
3.878
3854
3828
3805
3781
3757
3729
3705
3.679
3653
3627
3600
3.575 3547 3520
3493
3464 3437 3409 3382
3.353
3.323 3295
3.267 3238 3210 3 181 3152 3123
RESISTANCE
(OHMS)
98010 94707
91522 88449 85486 82627
79871 77212
74648 72175 69790
67490
65272
63133
61070
59081
57162
55311
53526
51804
50143
48541
46996
45505 44066 42679
41339
40047
38800 37596
36435
35313
34231
33185
32176
31202
30260
29351
28473
27624
26804
26011
25245
24505
23789
23096
22427 21779 21153
20547
19960 19393 18843 18311 17796 17297 16814 16346 15892 15453 15027 14614 14214 13826 13449
13084 12730
12387 12053 11730 11416 11112 10816 10529 10250
9979 9717 9461 9213 8973 8739 8511 8291 8076 7868 7665 7468 7277 7091 6911
6735 6564 6399 6238 6081 5929
TEMPERATURE
(5
TX ;: TZ TI
79
EY
82
zi ii5 :3
89
x: E xi
96
3;:
;i;
102
:::
105 106
2:
109 110 111 112
113
114 115 116 117 118 119 120 121
122
123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143
144 145
146 147 146 149 150 151
152 153 154
155
156
157
158
159
160
161
162
163
164
165
166
VOLTAGE
DROP (V)
3.093
3.064 3034 3005 2977
2.947
2.917 2884 2857
2.827 2797 2766 2738 2708 2679 2 650 2622 2593 2563 2533 2505
2.476 2447 2417 2388 2360 2332
2.305 2277 2 251 2217 2189
2.162 2136 2107 2080 2053 2028
2 001
1 973
1.946 1 919 1897
1870
1.846
1.822
1792 1 771
1.748 1724
1.702 1676' 1653
1 630 1 607
1
585
1562 1538 1 517 1496 1474 1453
1.431
1
408
1389 1369 1348 1 327 1308 1291
1
289
1
269
1
250 1230 1 211 1192
1173
1 155 1 136 1 118
1
100
1.082
f
064 1 047
1 029
1.012 0 995 0978 0 962 0945 0 929 0914 0 898 0883 0868 0853
RESISTANCE
(OHMS)
5781 5637 5497 5361 5229 5101 4976 4855 4737 4622 4511 4403 4298 4196 4096 4000 3906 3814 3726 3640 3556 3474 3395 3318 3243 3170 3099 3031 2964 2898 2835
2773 2713 2655 2597 2542 2488 2436
ZE
2286 2239 2192 2147 2103 2060 2018
1977 1937 1898 1860 1822 1786 1750 1715 1680 1647
t614
1582 1550 1519 1489
t
459 1430 1401 1373 1345 1318 1291 1265 1240 1214 1190 1165
1141 1118
1095 1072 1050 1029 1007
986 965 945 925 906 887 868 850 832 815 798 782 765 750 734
TEMPERATURE
F)
167 168
169
170 171 172 173 174 175 176 177 178 179
180 181 182 183 184 185 186 187 188 189
190 191 192 193
194
195 196
197
198
199
200
201 202 203 204 205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
VOLTAGE
DROP (V)
0.838
0824
0.810
0.797
0.783 0770 0758 0745 0734
0722
0.710
0.700
0.689 0678 0668 0659 0 649 0640 0632
0.623
0.615 0607 0600 0592
0.585 0579 0572 0566
0560 0554 0548
0542
:
2:
0526
0.520
0515
0.510
:%s
0 494
0488
z;;
0471
0465
0 459
0.453
0.446
0439
0432
0.425
0417
0 409
0401
0393
0384
0375
0366
REWSTANCE
(OHMS)
719
705
690
677 663 650 638
626 614
602 591
581 570 561
551
542 533 524 516
508
501
494 487
1;:
467 461 456
450 445 439 434 429 424
419
415 410 405 401
398
391
386
382
377
372
367
361
356
350
344
338
332
325
318
311
304
297
289
282
61
Page 62
-
Table 16 -Thermistor Temperature
(“C)
vs Resistance/Voltage Drop; Flotronic’” II
TEMPERATURE
(C)
-40
-39
-38
-37
-36
-35
-34
-33
-32
-31
-30
-29
-28
-27
-26
-25
-24
-23
-22
-21
-20
-19
-18
-17
-16
-15
-14
-13
-12
-11
-10
1;
-7
1; 1;
-2
-1
0
: i z
3
109
VOLTAGE
DROP (V)
4.896
Z~
4.874
4.866 4 857 4 848 4 838
4.828
4.817
4.806 4 794
4.782
4.769
4.755
4.740 4 725 4710
4.693
4.676 4 657 4 639 4
619
4 598
4.577 4 554
4.531
4.507 4482
4.456
4.428 4400 4371 4341 4310
4.278
4.245
4.211
4.176
4.140
4.103
4.065 4026
3.986
3.945
3.903 3860 3816
3.771 3726 3 680
3.633
3.585
3.537
3.487 3438 3387
3.337 3285 3234
3.181
3.129
3.076
3.023
2.970
2.917
2.864
2.810
2.757
2.704
2.651
2.598
2.545
2.493
2.441
2.389 2337
2.286 2236
2.186
2.137 2087
2.039
1.991
RESISTANCE
(Ohms)
168230 157440 147410
138090
129 410
121 330 113810 106 880 100 260
94165 88 480
83 170 78125 73 580
69 250
E
3:; 57 875 54 555
51 450
48 536 45 807
43 247 40 845 38 592 38 476 34 489 32 621
30 866
29 216 27 633 26 202 24 827 23 532 22313 21 163 20 079 19 058 18 094
17184 16 325 15515 14749 14026 13 342 12 696 12085
II
506
IO 959
10441
9 949 9485 9 044 8 627 8 231 7 855 7 499 7 161 6 840 6 536 6 246 5 971 5 710 5 461 5 225 5 000 4 786 4 583 4389 4 204 4 028 3 861 3 701 3 549 3 404 3 266 3134 3 008
2 888 2 773 2 663 2 559
2 459
2 363
TEMPERATURE
(Cl
46 47 48
6i
62
78 79 80
101
102
to3
104 105 106 107
VOLTAGE
DROP (V)
1.944 1898
1.852
1.807
1.763
1.719
1.677 1635 1594 1553 1513 1474 1436
1.399
1.363
1.327
1.291
1.258
:
:;;
I:160
1.129
: E:
1040 1012
0.984 0 949
0.920 0 892
0.865
0.838 0813 0 789
0765 0743 0722 0702
0.683 0665
0648
0.632
0.617
0.603
0.590
0.577
0.566
0555
0545
0.535
0.525
0.515
0.506
0.496
0.486
0.476
0466
0454
0.442
0 429
0.416
0401
0386
0370
RESISTANCE
(Ohms)
2 272 2184
1 871 1 801 1 734 1670 1609 1 550 1 493 1 439 1 387 1 337 1 290 1 244
1
200 1 158
1
118 1 079 1 041 1006
971
938 906
876 836 805 775 747 719 693
669
645 623 602 583 564 547 531 516 502 489 477 466 456 446 436 427
419 410
402 393 385 376 367 357 346 335 324 312
285
r
t;
I
. .
c.
i
62
Page 63
THERMISTOR* REFRIGERANT
ENTERING TEMPERATURE CYLINDERS
DISCHARGE PRESSURE
TRANSDUCER*
EQUALIZER LINE
OIL PRESSURE
TRANSDUCER*
SUCTION PRESSURE TRANSDUCER*
SIGHT GLASS (EACH COMPRESSOR)
Fig. 17 -Lead Compressor Transducer and Thermistor Locations
63
*Lead compressor only
Page 64
Control Modules
Turn controller power off before servicing controls. This ensures safety and prevents damage to controller.
PROCESSOR MODULE (PSIO). 4 IN/4 OUT MODULE
(SIO), LOW-VOLTAGE TiELAY’MODULE (DSIO), AND
EXV DRIVER MODULE (DSIO) - The PSIO, DSIO and
SIO modules all perform continuous diagnostic evaluations of the condition of the hardware. Proper operation of these modules is indicated by LEDs (light emitting diodes) on the front surface of the DSIOs, and on the top horizontal sur­face of the PSI0 and SIO.
RED LED - Blinking continuously at a 3- to
indicates proper operation. Lighted continuously indicates a problem requiring replacement of module. Off continu­ously indicates power should be checked. If there is no in­put power, check fuses. If fuse is bad, check for shorted secondary of transformer or for bad module. On the PSI0 module, if the light is blinking at a rate of twice per sec­ond, the module should be replaced.
GREEN LED - On a PSI0 and an SIO, this is the green LED closest to COMM connectors. The other green LED on module indicates external communications, when used. Green LED should always be blinking when power is on. It indicates modules are communicating properly. If green LED
is not blinking, check red LED. If red LED is normal, check module address switches. See Fig.
18,
Proper addresses are:
PSI0 (Processor Module) - 01 (different when CCN
connected) DSIO (Relay Module) - 19 DSIO (EXV Driver Module) - 31
SIO (4 In/4 Out Module) - 59
If
all
modules indicate communication failure, check COMM plug on PSI0 module for proper seating. If a good connec- tion is assured and condition persists, replace PSI0 module.
If only DSIO or SIO module indicates communication failure, check COMM plug on that mode for proper seat­ing. If a good connection is assured and condition persists, replace DSIO or SIO module.
All system operating intelligence rests in PSI0 module , the module that controls unit. This module monitors con­ditions through input and output ports and through DSIO modules (low-voltage relay module and EXV driver module).
The machine operator communicates with microproces-
sor through keypad and display module. Communication
between
PSI0
and other modules is accomplished by a 3-wire
sensor bus. These 3 wires run in parallel from module to
module.
On sensor bus terminal strips, terminal 1 of PSI0
ule is connected to terminal 1 of each of the other modules. Terminals 2 and 3 are connected in the same manner. See Fig, 19, If a terminal 2 wire is connected to terminal 1, sys­tem does not work.
In
FlotronicTM
II Chillers, processor module, low-voltage relay module, and keypad and display module are all pow­ered from a common 21-vat power source which connects to terminals 1 and 2 of power input strip on each module. A
separate source of 21-vat power is used to power options module through terminals 1 and 2 on power input strip. A separate source of 12.5 vat power is used to power EXV driver module through terminals 1 and 2 on power input
strip.
5-second
rate
mod-
Fig. 18
-
Module Address
Selector Switch Locations
PSIO,
SIO
ADDRESS SELECTOR
64
Page 65
PSI0
( pRocEMssOp (RELAY)
DSIO DSIO
Fig. 19
-
(Communications)
HSIO
(EXV
DRIVER)
(LID) (4
Sensor Bus Wiring
SIO
I;W;UT
LOW VOLTAGE RELAY MODULE (DSIO) (Fig. 21)
Inputs When
Inputs on strip 53 are discrete inputs (ON/OFF).
-
24vat
power is applied across the 2 terminals in a
channel it reads as on signal. Zero v reads as an off signal.
Outputs - Terminal strips J4 and JS are internal relays whose
coils are powered-up and powered-off by a signal from micro­processor. The relays switch the circuit to which they are connected. No power is supplied to these connections by DSIO module.
L
--/%o-6
SENSOR BUS CONNECTOR
/
93
-
PROCESSOR MODULE (PSIO) (Fig. 20) Inputs
terminals are
Each input channel has 3 terminals; only 2 of the
-
used.
Application of machine determines which terminals are used. Always refer to individual unit wiring for terminal numbers.
Outputs
-
Output is 24 vdc. There are 3 terminals, only 2 of which are used, depending on application. Refer to unit wiring diagram.
NOTE: Address switches (see Fig. 20) must be set at 01 (different when CCN connected).
fL.w--
P
I
0
ADDRESS
SWITCHES
PSI0
6%2
0
<
0
0
P-
CHASSIS
GROUND
-( REAR) NETWORK
SNNECTOR
(FORWARD)
SENSOR BUS CONNECTOR
J8
1 $i 1
RED STATUS LIGHT
7
LEGEND
-
ii!“”
I%
Communications Bus
-
Normally Closed
1
bb;n$ly Open
Fig. 21 -Low-Voltage Relay Module
-
b
2,4,6,
9e
ZTPUT “7
RELAYS “,
:
I
:
I
%YoN
C&MON
2:
COMMON
NO
&MON
2:
/
ADDRESS ADJUSTMENT (NOT SHOWN) ON UNDERSIDE
!;i
AND 8 ARE GRQUND (C)
NEL I2
I I
IO
9
8
7
6
5
(DSIO)
PWR - Power
Fig. 20 -Processor Module
I-
(PSIO)
65
Page 66
4
IN/4
OUT MODULE (SIO) (Fig. 22) - 4 In/4 Out mod-
ule allows the following features to be utilized:
1.
Temperature Reset by outdoor air or space temperature.
A remote thermistor (Part No, 30GB660002) is also re­quired.
NOTE: This accessory is not required for return water temperature reset.
2. Temperature Reset by remote 4-20 mA signal.
3. Demand Limit by remote 2-stage switch.
4. Demand Limit by remote 4-20 mA signal
5. Dual Set Point by remote switch. The options module is standard on 30GN040-210 and
associated modular chillers and is available as a field-installed accessory on 3OGT225, 250, and 280 Flotronic T” II chillers.
Remember to reconfigure the chiller for each feature se-
lected (see Table 13). For temperature reset, demand limit, and dual set point, desired set points must be entered through keypad and display module (see Set Point Function section on page 39).
See Table 17 for overall troubleshooting information.
L
I
i
N
+
P
:
U
:
i : :
a
II
a :
*
l l l l
: a
: a
!8
r
J7
T
S
0
u
T
P
J6
U
T S
COMM
ADDRESS SWITCHES
PWR
EEM
-
-
LEGEND
Communications Bus Power
Fig. 22 -4 In/4 Out Module
(SIO)
66
Page 67
Table 17
Troubleshooting
-
SYMPTOMS
COMPRESSOR DOES
NOT RUN
COMPRESSOR CYCLES OFF ON LOW PRESSURE
COMPRESSOR SHUTS DOWN
~N&-l;l;PFlESSURE
UNIT OPERATES LONG OR CONTINUOUSLY
SYSTEM NOISES
COMPRESSOR LOSES OIL
FROSTED SUCTION LINE
HOT LIQUID LINE FROSTED LIQUID LINE COMPRESSOR DOES NOT
UNLOAD
fgF;RESSOR
DOES NOT
CAUSE
Power line open
Control fuse open
High Pressure Switch (HPS)
tripped Tripped power breaker
Loose terminal connection
Improperly wired controls
Low line voltage
Compressor motor defective
Seized compressor Loss of charge
Bad transducer Low refrigerant charge High-pressure control erratic in action
Compressor discharge valve partially closed
Condenser fan(s) not operating Condenser coil
Low refrigerant charge Control contacts fused
Partially plugged or plugged expansion
valve or filter driver Defective insulation Service load
Piping vibration Expansion valve hissing
Compressor noisy
Leak in system Mechanical damage (blown piston or
broken discharge valve) Crankcase heaters not energized
durina shutdown
Expansion valve admitting excess refrigerant
Shortaae of refriaerant due to leak Shutoff valve partially closed or restricted Burned out coil Defective capacity control valve Miswired solenoid Weak, broken, or wrong valve body spring Miswired solenoid Defective capacity control valve Plugged strainer (high side) Stuck or damaged unloader piston or
piston ring(s)
oluaaed
or
dirtv
REMEDY
Reset circuit breaker Check control circuit for ground or short.
Replace fuse
Move LOCAL/ENABLE-STOP-CCN switch to STOP position then back to RUN or CCN position.
Check the controls. Find cause of trip
and reset breaker Check connections Check wiring and rewire.
Check line voltage. Determine location of voltage drop and remedy deficiency
Check motor winding for open or shot-t.
Replace compressor if necessary.
Replace compressor.
Repair leak and recharge
Replace transducer. Add refrigerant.
Replace control
Open
valve
or replace if defective.
Check wiring. Repair or replace motor(s)
if defective.
Clean coil.
Add refrigerant,
Replace control
Clean or replace
Replace or repair. Keep doors and windows closed.
Check valves. Replace if necessary.
Support piping as required
Add refrigerant.
Check for plugged liquid line filter drier. Check valve plates for valve noise. Replace compressor (worn bearings). Check for loose compressor Repair leak. Repair damage or replace compressor.
Replace heaters, check wiring and
crankcase heater relay contacts. Check cooler and compressor thermistors.
Test EXV.
Repair leak and recharge
Open valve or remove restriction.
Replace coil Replace valve Rewire correctly. Replace spring Rewire correctly Replace valve. Clean or replace strainer. Clean or replace the necessary parts.
holddown
bolts.
67
Page 68
ACCESSORY UNLOADER INSTALLATION
Some of the 30G unloader(s), and many permit additional unloader(s) to be added if desired. See Table 18.
IMPORTANT: Accessory hot gas bypass cannot be installed with accessory unloaders on units with more than 4 compressors.
FlotronicT”
II units come standard with
Wire the primary side of the transformer in parallel with TRAN3. See Fig. 23. This supplies transformer with proper line voltage. Be sure to connect proper tap of the trans­former to ensure supply of proper secondary voltage.
Wire the secondary side of transformer to DSIO-LV
J5-9, and a jumper from DSIO-LV - J5-9 to DSIO-LV
-
-
54-9. Wire the secondary common to TB7-2. Connect
the transformer ground to ground hole supplied near the transformer. These connections provide DSIO with nec-
If accessory unloaders are desired, an accessory unloader package is used. Package includes a suction cutoff unloader head package. The 24-v coil in the package can be used for 040-l 10, 130 (60 Hz) and associated modular units. A
115 v or 230 v coil must be used for 130 (50 Hz), 150-210, 225, 250, 280, and associated modular units. Coil voltage depends on control circuit voltage, Consult current Carrier price pages for appropriate part numbers.
NOTE: The accessory package will include all necessary
components and wiring with the following exceptions: The
field must provide screws, and on the 130-2 10, 225, 250, 280, and associated modular units, the field must also sup­ply a 20 vdc (part number HK356ABOOl) unloader relay
and wire (90” C or equivalent).
Table 18 -Standard and Accessory Unloaders
essary power to energize the solenoid coils.
3.
When all connections are made, check for proper wiring and tight connections. Replace and secure inner panel. Restore power to unit.
4.
Configure the processor. With the addition of extra un­loaders, the unit configuration has changed. To change the configuration of the processor, enter the service func­tion using the keypad and display module. Before any changes can be made, the LOCAL/ENABLE-STOP- CCN switch must be in the STOP position, and the ser­vicer must log on to the processor.
Press
pJl,,,l*
Keypad LCD displays the word
a.
PASSWORD.
b,
Enter m ri m m
[;;;;;I
.displays
Keypad
LCD
LOGGEDON.
I
1 NO. OF ACCESSORY
To change configuration, pressm H. Keypad LCD
C.
displays FLD CFG.
Circuit A Circuit B
30GN190-210* 0
3OGT225,250,280
*And associated modular units
1
1 1
1 1
0
1 1
1
or2
Installation
1.
Be sure all electrical disconnects are open and tagged before any work begins. Inspect the package contents for any damage during shipping. File a claim with the
shipper if damage has occurred.
2.
For ease of installation, factory-supplied wiring for the
additional unloader is provided in the compressor
harness.
Install the additional unloader cylinder head on the lead
3. compressor, Al or
El,
according to instructions pro­vided by the compressor manufacturer in the accessory package.
4.
Continue installation per either 040-l 10, 130 (60 Hz)
1
units or 130 (50 Hz), 150-210, 225, 250, and 280 units
section as appropriate.
04
-0-l 10, 130 (60 Hz) UNITS (and associated modular units)
1.
Wire the solenoid before any field wiring begins. Wir-
ing between components and control box must be en­closed in conduit. All local electrical codes and National Electrical Code (NEC) must be followed. Factory wires
d.
If an additional unloader was added to compressor
Al, press m until NULA 1 appears in keypad dis-
play. Press m Fifor the number of unloaders on
circuit A. Keypad display now reads NULA 2.
If an additional unloader was added to compressor B 1, press
q
until NULB 1 appears in keypad dis-
play. Press m bi for the number of unloaders on
circuit B. Keypad display now reads NULB 2.
When configuration is complete, press
mM.
pad display reads LOGGEDON. Press m until
Key-
key-
pad display reads LOG OFF. Press H . Keypad dis­play reads EXIT LOG.
5.
Using test function, check unloaders. Press 1 2 1 pad display reads OUTPUTS. Press reads ULA 2 OFF. Press
a
and relay deenergizes. Press
ULB2 OFF. Press
q
. Relay energizes. Press
Li_]
H
. Relay energizes. Press q
III
pEsTI.
Key-
I)I
until display
until display reads
and relay deenergizes.
6.
When unloader check has been performed, return LOCAL/
ENABLE-STOP-CCN to proper position. Close and se­cure control box door.
are provided in the compressor harness to connect the solenoid. These wires are in the compressor control box.
2. Wire the control side. Open the left side control box door and remove inner panel. Using the holes provided
and field-supplied screws, install field-supplied trans-
former above the DSIO-LV on the control panel.
68
Page 69
~13014 115v 0R
230y;f;~RO~
SCHEMATIC
i
-- 13
6
r--‘---------‘-‘-“--“‘-“-----------~
1 !
-9RA
1 1’
! I
I I
I I
I 1
I L--a---
-
VI0
FROM 115V OR 23OV CONTROL SCHEMATIC
y
IDS00
(LWl
0
0
0
0
TRAN
‘.
\
\
\
\
\
\
\
ERCS
RED-
-
Contactor
-
Compressor Protection Control System
-
Control Relay
-
Rela
Module
u,
-
Low
oltage
LEGEND
080-110
k TL
U
(SO/SO
z
~~.?ther
-
Terminal Block
-
Transformer
-
Unloader
Hz) and 130 (60
Hz)
Fig. 23- Accessory Unloader Control Wiring
69
Page 70
130 (50 Hz), 150-210, 225, 250, AND 280 UNITS (and
associated modular units)
1.
Install control wiring. The minimum wire size for
stallation is 16
AWC
(American Wire Gage). Refer to
in-
Fig. 24 and 25 for proper wiring. Open the control box door. Locate unloader relays A and B (URA, URB) in place of the hot gas bypass relays as shown on the com­ponent arrangement diagram on the unit. Mount the re-
lays with the field-supplied screws. Be careful not to damage the components and wiring in the area when mount­ing the relays.
Wire the control side. Wire the URA coil in series be-
2
tween 56-18 and J6- 19 of the 4 IN/4 OUT module with the wires provided. Wire the URB coil in series be­tween J6-21 and J6-22 of the same module with the wires provided.
Locate the black wire in the control harness originating from
TRANS
labeled HGBPR-A-COM. Connect this wire to the URA terminal COM. Connect the wire labeled HGBPR-A-NO to URA-NO. Connect the wire from
URA-NO to TB3-5. For an extra unloader on circuit
B,
5
connect the wire labeled HGBPR-B-COM to UR-B- COM, and the wire labeled HGBPR-B-NO to URB- NO. Connect the wire from URB-NO to TB3-6.
3. Wire in the solenoid valves. NOTE: Wires external to the control box must be run in
conduit
+
Terminal blocks are provided for easy field wiring. Use one of the isolated
‘/s-in.
(22-mm) holes in the side of the compressor electrical box with a strain relief to run the wires to the solenoid coil. Connect URA between
TB3-5 and TB3-8. Connect URB between TB3-6 and TB3-8. Check all of the electrical connections for proper
location and tightness, and replace and secure the elec­trical box of the compressor,
4. Configure the microprocessor, Once the relays are mounted in the control box, the microprocessor must be config-
ured for the unloader option. ‘To do so: a. Be sure the LOCAL/ENABLE-STOP-CCN switch is
in the STOP position.
b. Log into the processor and enter the service func-
tion using the keypad and display module. Type r\
“PASSWORD.” Enter
I;;;;E]
. The keypad LCD will display
~~1~~~~,
and the
6. Once the check has been performed, return the LOCAL/
7. Close and secure the control box door.
8. Start the unit and confirm that the chiller operates
keypad LCD will display “LOGGEDON.
C,
To change the configuration, type14 H, and the keypad LCD will display “FLD CFG.” Press
m
until either “NULA 0” or “NULA I” is displayed (depending on the number of unloaders provided as
standard), Then press m H (for 1 unloader on Al) or
FiFi
(for 2 unloaders on compressor Al). The
display will now read either “NULA 1” or
‘NULA 2, as appropriate, Press
I)I
to get to the
NULB display, and change this setting in the same
manner as with circuit A.
d.
Once the configuration is complete, press m
Fi,
and the keypad LCD will display “LOGGEDON,” Press @ until the keypad LCD display reads “LOG
OFF.” Press H and the keypad LCD will display
“EXIT LOG.”
Once the unloader heads are installed, the unit is checked
._--
for leaks, and the system is prepared for operation per
instructions for the compressor unloader head instal-
the lation, check the output of the relays using the test func­tion as follows:
a. Press
b. Press the
T;1H,
q
and the display will read “COMP.”
to scroll down until the display reads
“CPA1 OFF.”
c. Press
ENTR
,0and the compressor should start. d. Press + ,aand the compressor should stop. e. Press
+cluntil the display reads “ULAl OFF.”
f. Press H , and the solenoid should energize.
g. Press q and the solenoid should deenergize.
h. Use the a and H keys to check the remainder of
the unloader coils.
ENABLE-STOP-CCN switch to the proper position.
properly.
COM
HGBPR -
KB
1
LEGEND
-
Communications Bus
Hot Gas Bypass Relay Normally Open
Snubber
Fig. 24 - Flotronic’”
-
TLN- Transformer kl
Terminal Block
-
Unloader
-
Unloader Relay
II 115/230-V Unloader Wiring, 130 (50 Hz), 150-210, 225, 250, 280
70
Page 71
GdYEL
&
EE
Lfh]f
- - - - - - - -
cALARncooE31~
~gl
Fam&&
tRoDEn
(AIJM
CODE 21,301
o(oocm
balToysTER
lmyTEF4- - - - -
-
Contactor
-
EB
COMM -Communications Bus UR
Circuit Breaker
Fig. 25
--------­w---m----
1
r--------
SWITCH
{
‘-%F-----
---------
~~
------II-
r - - - - - - -
L-B-----
I
qg&#g’
I-)o
M-wT~r- - - - - - -
--
---------------A--
{
4-20 HA OUTPUT
-----I----------------Y--
LEGEND
5&N
Accessory Unloader Control Wiring, 130 (50 Hz), 150~210,225,250, 280
-
CALAM CWE
-
Switch
-
Transformer
-
Unloader Relay
211
--------m-w-------
-
-
----
43
m
----
---‘I
a
Qb
i
-
----------a
-
-----
I
I
l ’
I
I
I
I
I
! I I
I ’
l
I
I
I 1
I
;
’ ]
I
’ ’
I
I
FIELD WIRING
Refer to Fig, 26 - 36 for field wiring.
-k367
!------ it ----
STAGE11
L
v--w
-----
STAGE2 1
NOTE: Contacts must be rated for dry circuit application, capable of reliably switching a 5 vdc, 1 mA to 20 mA load
Fig. 26A Inputs,
i-
L
--------
Demand Limit -Two External Switch
-
30GN040-210
_--B-B
--m-w
i I
and Associated Modular Units
4 IN/4 OUT
MODULE
1
0
fl
--­u
J7-2
57-3
57-6
J7-7
STAGE11
STAGE2 1
-
Terminal Block
TB
NOTES: 1
Requires accessory options module package.
2 Contacts must be rated for dry circuit application, capable of re-
liably switching a 5 vdc, 1 mA to 20 mA load
Fig. 26B
71
4368
l-
-----
L
------------cl 5
em---
r
L
-------m-_
Demand Limit
-
Inputs, 30GT225, 250, 280 Units
-I I
-----
---
H-
Two External Switch
-
cl 4
I
-cl
2 TB7
cl
TB7
TB7
TB7
Page 72
r--
--- --
EXTERNAL
3OGN040-210
AND ASSOCIATED MODULAR UNITS
---
----
30GT225,250,280
TB- Terminal Block
NOTE: The sory options module package for this feature
30GT225,250,280
Fig. 27 -Demand Limit- 4-20 mA Signal
(Externally Powered)
FLOTRONIC II UNITS
Flotronic’” II units require the acces-
u
4
-cl
FIELD SUPPLIED LOOP ISOLATOR
UNlTS
+
3
-u
4 l-E-11
J7-13
37-14
I-B11
EXTERNAL POWER
+
3
m-7
TB-7
30GN040-210
TB - Terminal Block
NOTE: The
sory options module package for this feature.
Fig. 30 -Remote Reset from 4-20 mA Signal
AND ASSOCIATED MODULAR
FIELD SUPPLIED LOOP ISOLATOR
-III-
30GT225,250,280
30GT225,250,280
(Externally Powered)
FLOTRONIC II UNITS
Flotronic II units require the acces-
-
-
-El
--j370
30GN040-210
AND ASSOCIATED MODULAR UNITS
---
---
30GT225,250,280
TB- Terminal Block
NOTE: The sory options module package for this feature.
r1-- 63 -------- cl
I,
30GN040-210
30GT225,250,280
Fig. 28
REMOTE
--- --- ---
Demand Limit- 4-20 mA Signal
-
(Internally Powered)
THERMISTOR
AND ASSOCIATED MODULAR UNITS
FLOTRONIC II UNITS
Flotronic II units require the acces-
- /$W
4
IN/4
MODULE
---
4 IN/4 OUT
MODULE
+
4
-cl
5
--cl
OUT
El
m-7
J7-15
J7-16
l-B-11
TB-7
-a3
-73
+
4-2omA
SIGNAL
GENERATOR
30GN040-210
--
---
t
AND ASSOCIATED MODULAR UNITS
-
-cl
-
El
+
----
-----
30GT225,250,280
TB - Terminal Block
NOTE: The sory options module package for this feature
Fig. 31- Remote Reset from 4-20 mA Signal
30GNO40-210
30GT225,250,280
(Internally Powered)
CONTACTS
r+
+--A
L
------$--
AND ASSOCIATED MODULAR UNITS
FLOTRONIC II UNITS
Flotronic II units require the acces-
REMOVE JUMPER
,REMOVE JUMPER
\
---- g
3
-0
-
4
I
3
T&6
4
TB6
TB-7
J7-13
J7-t4
TB-11
TE11
----
3OGT225,250,280
TB- Terminal Block
NOTE: The sory options module package for this feature.
30GT225,250,280
Fig. 29
Remote Reset from Space or
-
Outdoor-Air Temperature
FLOTRONIC II UNITS
Flotronic II units require the acces-
6
--El
TB-11
----
30GT225,250,280
TB- Terminal Block
NOTES: 1 The
30GT225,250,280
tions module for this feature.
2. Contacts must be rated for dry circuit application, capable of
liably
switching a 5 vdc, 1 mA to 20 mA load
Fig. 32
72
FLOTRONIC I
Flotronic II units require the accessory op-
Remote On/Off
-
10
3
TE7
UNITS
re-
Page 73
&-jQ
-
13 a--
-43
-78
,~,. $$
&
c,: *
4
IN/4
OUT
SWITCH
,- -
m
i-
- ___ -
30GN040-210
30GT225,250,280
TB- Terminal Block
NOTE: The
sory options module for this feature
AND ASSOCIATED MODULAR UNITS
30GT225,250,280
- - -
----
--a-
FLOTRONIC’” II UNITS
Flotronic II units require the acces-
MODULE
-f-J J7-10
_-a
-El
2
-0
J7-lf
1
TB-11
TBI1
;-+--y----
I-------
30GN040-210
CWPI- Chilled Water Pump Interlock
CWFS- Chilled Water Flow Switch (not required - low flow TB
NOTE: Contacts must be rated for dry circuit application, capable of reliably switching a 5 vdc, 1 mA to 20 mA load.
Fig. 33 -Remote Dual Set Point Control
43
7
6
1
------
115/23ovv
-------_--
f
30GN040-210
CWP- Chilled Water Pump
TB- Terminal Block NOTE: The maximum load allowed for the chilled water pump circuit
is 125 va sealed, 1250 va inrush at 115 or 230 v
AND ASSOClATED MODULAR UNITS
30GT225,250,280
CWP
-----
cl-
__--
--v-w
WI--
FLOTRONIC II UNITS
-cl
4
-t-l
3
El
u
3
-rB$J
T5-3
TE5
4 TE5
The replacement part number is printed on a small label
on front of the PSI0 module. The model and serial num­bers are printed on the unit nameplate located on an exte­rior corner post. The proper software and unit configuration
data is factory installed by Carrier in the replacement mod-
ule. Therefore, when ordering a replacement processor mod-
ule (PSIO), specify complete replacement part number, full
unit model number, and serial number. If these numbers
are not provided, the replacement module order is config-
ured instead as a generic Flotronic’” 11 replacement mod-
ule. This requires reconfiguration of the module by the
installer.
Electrical shock can cause personal injury, Disconnect
all electrical power before servicing.
CWPl (CWFS)
------
AND ASSOCIATED MODULAR UNITS
-----
-----
30GT225,250,280 FLOTRONIC I I UN ITS
protection is provided by Flotronic II controls)
-
Terminal Block
--a
TB-6
2
TB-6
-cl
7
TB-7
-El
8 TE7
u
Fig. 36 -Interlocks
REPLACING DEFECTIVE
PROCESSOR MODULE
Fig. 34 -Chilled Water Pump
-43 77
ALARM SHUTOFF
-------a--­I­I
i
L
30GN040-210
30GT225,250,280
TB -Terminal Block
NOTE: The maximum load allowed for the alarm circuit is 125 va sealed, 1250 va inrush at 115 or 230 v
SWITCH
------2
AND ASSOCIATED MODULAR UNITS
_d--
----
FLOTRONIC II UNITS
1 TB-3
-cl
cl
2 TB-5
u
T8-3
Fig. 35 -Remote Alarm
Installation
1.
Verify the existing PSI0 module is defective by using the procedure described in the Control Modules sec­tion on page 64.
2.
Refer to Start-Up Checklist for Flotronic II Chiller Sys­tems (completed at time of original start-up) found in
job folder. This information is needed later in this
procedure. If checklist does not exist, fill out the ri
and Fi F\ configuration code sections on a new check-
list. Tailor the various options and configurations as
needed for this particular installation.
3.
Check that all power to unit is off. Carefully discon­nect all wires from defective module by unplugging the 6 connectors. It is not necessary to remove any of the individual wires from the connectors. Remove the green ground wire.
4.
Remove defective
PSI0
by removing its mounting screws with a Phillips screwdriver, and removing the module from the control box, Save the screws for later use.
5.
Use a small screwdriver to set address switches Sl and
S2 on the new PSI0 module to exactly match the set-
tings on the defective module.
6.
Package the defective module in the carton of the new module for return to Carrier.
7.
Mount the new module in the unit control box using a Phillips screwdriver and the screws saved in Step 4 above.
H
73
Page 74
8. Reinstall all 6 wire connectors and the green ground wire.
9. Carefully check all wiring connections before restoring power.
10. Verify the LOCAL/ENABLE-STOP-CCN switch is in STOP position
11. Restore control power. Verify the red and green lights on top of PSI0 and front of each DSIO module re-
spond as described in Control Modules section on
page 64. The keypad and display module @IS10 or LID)
should also begin its rotating display.
12. Using the keypad and display module, press
to verify that the software version number matches the ER (engineering requirement) number shown on the label.
13. Press
[qn
SRVC
to verify that the 6 factory configuration
codes (CODE 1 through CODE 6) exactly match the codes listed for this unit model on the component ar­rangement label diagram on the control box door. If they are different or are all zeros, reenter the 6 codes. If any changes are required, the PSI0 display becomes
blank and reconfigures itself after pressing the H key
[p-&q,
PSI0
while displaying CODE 6. The display returns in ap­proximately 15 seconds.
NOTE: Codes with leading zeros in the configuration will be displayed starting with the first number greater than zero.
14. Press nn4 sRvc for this particular installation. Table 9 shows the fac-
tory configuration code default settings. Table 9 also
shows the service replacement code default settings which
are used if no model number was specified when or­dering the replacement gested that the Start-Up Checklist for Flotronic’” II Chiller Systems (completed at time of original start-up) be used at this time to verify and/or reprogram the various op­tions and configurations required for this job.
15. After completing the configuration steps outlined above,
restore main power and perform a unit test as
scribed in m H and
16,
Complete this procedure and restore chiller to normal
operation by returning the LOCAL/ENABLE-STOP- CCN switch to desired position.
to verify each item is configured as needed
PSI0
module. It is strongly sug-
de-
r;lFl
sections on page 38.
74
Page 75
Page 76
Copyright 1994 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5c
-I-
PC 903
Catalog No 563-015
Printed in U S A Form
30GN-2T Pg 76 l-94
Replaces: 30GEl,GT-1 T,
30GN-1T
Loading...