ACCESSING FUNCTIONS AND:tiBFtiN?TI’dNS
SUMMARY DISPLAY
KEYPAD OPERATING INSTRUCTIONS
STATUS FUNCTION
TEST FUNCTION
HISTORY FUNCTION
SET POINT FUNCTION
SERVICE FUNCTION
SCHEDULE FUNCTION
Installing, starting up, and servicing this equipment can
be hazardous due to system pressures, electrical components, and equipment location (roof, elevated structures, etc.).
Only trained, qualified installers and service mechanics should
install, start-up, and service this equipment.
When working on this equipment, observe precautions in
the literature, and on tags, stickers, and labels attached to
the equipment, and any other safety precautions that apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use care in handling, rigging, and setting this equipment,
and in handling all electrical components.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
Tab 5c
--I-
PC 903
Catalog No. 563-015Printed in U S A.
Electrical shock can cause personal injury and death.
Shut off all power to this equipment during installation
and service. There may be more than one disconnect
switch. Tag all disconnect locations to alert others not
This unit uses a microprocessor-based electronic control system. Do not use jumpers or other tools to short
out components, or to bypass or otherwise depart from
recommended procedures. Any short-to-ground of the
control board or accompanying wiring may destroy the
electronic modules or electrical components.
Form
30GN-2T
pg
1
1-94Replaces: 30GB,GT-1 T,
30GN-1T
Page 2
-%a-
GENERAL
IMPORTANT: This publication contains controls, operation and troubleshooting data for 3OGNO40-420 and
30GT225, 250, and 280
Circuits are identified as circuits A and B, and compressors are identified as Al, A2, etc. in circuit A,
and
BI,
B2, etc. in circuit B.
Use this guide in conjunction with separate Instal-
lation Instructions booklet packaged with the
FlotronicTM
II chillers,
unit,
The
contrwsm
a low-voltage relay module (DSIO-LV), 2
consists of a processor module (PSIO)9
EXVs,
an EXV
driver module (DSIO-EXV), a 6-pack relay board, a keypad and display module (also called HSIO or LID), thermistors, and transducers to provide inputs to the
microprocessor. An options module (SIO) is used to pro-
vide additional functions. This module is standard on 30GN
modules and is a field-installed accessory on the 30GT
Flo-
tronic II units. See Fig. 1.
The 30G Series standard Flotronic II chillers feature
microprocessor-based electronic controls and an electronic
expansion valve (EXV) in each refrigeration circuit.
NOTE: The 30GN040 and 045 chillers with a
factory-
installed brine option have thermal expansion valves (TXV)
instead of the EXV.
Unit sizes 240,270, and 300-420 are modular units which
are shipped as separate sections (modules A and B). Installation instructions specific to these units are shipped inside
the individual modules. See Table 1 for a listing of unit
sizes and modular combinations. For modules 24OB and
follow all general instructions as noted for unit sizes
110.
For all remaining modules, follow instructions for unit
270B,
OSO-
sizes 130-210.
Table 1- Unit Sizes and Modular Combinations
UNIT MODEL
30G NO4040
3OG NO45
30GN050
30EN06060
30GN070
30GN08080
NoT”o’NNs”L SE\WlK&N
45
50
70
-
-
-
-
--
ssE%~N
-
-
-
Processor Module
ating software and controls the operation of the machine. It
continuously monitors information received from the various transducers and thermistors and communicates with the
relay modules and
crease the active stages of capacity. The processor module
also controls the EXV driver module, commanding it to open
or close each EXV in order to maintain the proper superheat entering the cylinders of each lead compressor. Information is transmitted between the processor module and relay module, the EXV driver module, and the keypad and
display module through a 3-wire communications bus. When
used, the options module is also connected to the communications bus.
For the Flotronic II chillers, the processor monitors system pressure by means of 6 transducers, 3 in each lead compressor. Compressor suction pressure, discharge pressure,
and oil pressure are sensed. If the processor senses high
discharge pressure or low suction pressure, it immediately
shuts down all compressors in the affected circuit. During
operation, if low oil pressure is sensed for longer than one
minute, all compressors in the affected circuit are shut down.
At start-up, the coil pressure signal is ignored for 2 minutes. If shutdown occurs due to any of these pressure faults,
the circuit is locked out and the appropriate fault code is
displayed.
Low-Voltage Relay Module
contacts to energize compressor unloaders and/or compres-
sors. It also senses the status of the safeties for all compressors and transmits this information to the processor.
Electronic Expansion Valve Module
ule receives signals from the processor and operates the electronic expansion valves.
Options Module
tronic II features such as dual set point, remote reset, de-
mand limit, hot gas bypass, and accessory unloaders. The
options module also
activated from a remote 4-20 mA signal. The options module is installed at the factory on 040-210 and modular 240420 units. It is a field-installed accessory for 225, 250 and
280 units.
Keypad and Display Module (also called HSlO
or LID)
The Flotronic II control system cycles compressor un-
loaders and/or compressors to maintain the selected leaving
water temperature set point. It automatically positions the
EXV to maintain the specified refrigerant superheat entering the compressor cylinders. It also cycles condenser fans
on and off to maintain suitable head pressure for each circuit. Safeties are continuously monitored to prevent the unit
from operating under unsafe conditions. A scheduling func-
tion, programmed by the user, controls the unit occupied/
unoccupied schedule. The control also operates a test pro-
gram that allows the operator to check output signals and
ensure components are operable.
tion keys, 5 operative keys, 12 numeric keys, and an alphanumeric g-character LCD. Key usage is explained in
Accessing Functions and Subfunctions section
Control Switch
the position of the LOCAL/ENABLE-STOP-CCN switch.
This is a 3-position manual switch that allows the chiller to
be put under the control of its own Flotronic II controls,
manually stopped, or put under the control of a Carrier Cornfort Network (CCN), Switch allows unit operation as shown
in Table 2.
2
MAJOR SYSTEM COMPONENTS
-
This module contains the oper-
&pack
relay board to increase or de-
-
This module closes
-
This mod-
-
This module allows the use of
aIlows
for reset and demand limit to be
-
This device consists of a keypad with 6 func-
on
-
Control of the chiller is defined by
Flo-
page 28.
,,
:f
c
’_.
’
Page 3
ELECTRONIC EXPANSION VALVES
DRIVER MODULE
(DSIO EXV)
LOW-VOLTAGE
RELAY MODULE
(DsroiLv)
TB-7
I
d
g-PACK
RELAY BOARD
B
;rt’EFUCER
SOURCE (PSI)
CCN -
TB -1
\- -.-...-
LEGEND
Zarrier
Comfort Network
c
“erminal Block
Fig. 1
KEYPAD;DISPLAY
MODULE (HSIO/LID)
30GN Control Panel (040-110, 240B, 270B Unit Shown)
-
GROUND FAULT INTERRUPTER
208/230-,
460-f%!-3-60-V
ONLY
COOLER
RELAY, B
,TB-3
FIELD
ZEol
CONNECl
iEA1
rlON
I
‘ER
Page 4
In the LOCAL/ENABLE position, the chiller is under lo-
cal control and responds to the scheduling configuration and
set point data input at its own local interface device (key-
pad and display module).
In the CCN position, the chiller is under remote control
and responds only to CCN network commands. The occupied/
unoccupied conditions are defined by the network. All keypad and display functions can be read at the chiller regardless of position of the switch.
CCN run or stop condition is established by a command
from the CCN network. It is not possible to force outputs
from the CCN network, except that an emergency stop command shuts down the chiller immediately and causes ‘ ‘ALARM
52” to be displayed.
Table 2 -LOCAL/ENABLE-STOP-CCN
Switch Positions and Operation
SWITCH
POSITION
STOP
LOCAL/ENABLE
CCN :t2 1
I
UNIT
OPERATION
I
Unit Cannot Run Read/Write1 Read Only
Unit Can Run
Unit Cannot Run Read Only
Unit Can RunRead Onlv
Electronic Expansion Valve (EXV)
CONFIGURATION AND
SET POINT CONTROL
Keypad Control 1 CCN Control
Read/Limited Write Read
Only
ReadlWrite
Read/Limited Write
-
The microprocessor controls the EXV through the EXV driver module. Inside the expansion valve is a linear actuator stepper
motor.
The lead compressor in each circuit has a thermistor and
a pressure transducer located in the suction manifold after
the compressor motor. The thermistor measures the temperature of the superheated gas entering the compressor cylinders. The pressure transducer measures the refrigerant
pressure in the suction manifold. The microprocessor converts the pressure reading to a saturated temperature. The
difference between the temperature of the superheated gas
and the saturation temperature is the superheat. The microprocessor controls the position of the electronic expansion
valve stepper motor to maintain 29 F (16 C) superheat.
At initial unit start-up, the EXV position is at zero. After
that, the microprocessor keeps accurate track of the valve
Compressor Protection Control Module (CPCS)
-
Each compressor on models 30GN070 (50 Hz), 080-
100, and 240B,270B, has its own CPCS as standard equip-
ment. All 30GN040-060 and 070 (60 Hz) units feature the
CPCS as an accessory, and CR (control relay) as standard
equipment. See Fig. 2. The 30GN130-2 10 and associated
modular units and the 30GT225, 250, and 280 Flotronic II
units have a CR as standard equipment. The CPCS or CR is
used to control and protect the compressors and crankcase
heaters. The CPCS provides the following functions:
compressor contactor control
crankcase heater control
compressor ground current protection
status communication to processor board
high-pressure protection
The CR provides all of the same functions as the CPCS
with the exception of compressor ground current protection. Ground current protection is accomplished by using a
CGF (compressor ground fault) board in conjunction with
the CR. The CGF provides the same ground fault function
as the CPCS for units where the CPCS is not utilized.
One large relay is located on the CPCS board. This relay
(or CR) controls the crankcase heater and compressor
contactor. The CPCS also provides a set of signal contacts
that the microprocessor monitors to determine the operating
status of the compressor. If the processor board determines
that the compressor is not operating properly through the
signal contacts, it will lock the compressor off by
gizing the proper 24-v control relay on the relay board. The
CPCS board contains logic that can detect if the
ground of any compressor winding exceeds 2.5 amps. If
this condition occurs, the CPCS module shuts down the
compressor.
A high-pressure switch with a trip pressure of 426 +
7
psig (2936 +_ 48 kPa), is wired in series with the CPCS.
If this switch opens during operation, the compressor stops
and the failure is detected by the processor when the signal
contacts open. The compressor is locked off. If the lead
compressor in either circuit is shut down by the high pressure switch or ground current protector, all compressors in
the circuit are locked off.
position in order to use this information as input for the
other control functions. The control monitors the superheat
and the rate of change of superheat to control the position
of the valve. The valve stroke is very large, which results
in very accurate control of the superheat.
deener-
current-to-
Sensors
The Flotronic TM II chiller control system gath-
-
ers information from sensors to control the operation of the
chiller. The units use 6 standard pressure transducers and
4 standard thermistors to monitor
system
pressures and temperatures at various points within the chiller. Sensors are
listed in Table 3.
Table 3 -Thermistor and Transducer Locations
THERMISTORS
Sensor
T:
Ti
TIO
Sensor
DPT-A
SPT-A
OPT-A
DPT-I3
SPT-B
OPT-B
Cooler Leaving Water Temp
Cooler Entering Water Temp
Compressor Suction Gas Temp Circuit A
Compressor Suction Gas Temp Circuit B
Remote Temperature Sensor (Accessory)
PFIESSURETRANSDUCERS
Compressor Al Discharge Pressure
Compressor Al Suction-Pressure
Compressor Al Oil Pressure
Compressor Bl Discharge Pressure
Compressor Bi Suction Pressure
Compressor Bl Oil Pressure
Location
Location
PROTECTION BOARD
Fig. 2 -Compressor Protection Control Module
4
Page 5
OPERATION DATA
Capacity Control
compressor to give capacity control steps as shown in
Tables 4A-4D. The unit controls leaving chilled water temperature. Entering water temperature is used by the microprocessor in determining the optimum time to add or sub-
tract steps of capacity, but is not a control set point.
The chilled water temperature set point can be automat-
-
The control system cycles
ically reset by the return temperature reset or space and out-
door air temperature reset features. It can also be reset from
an external 4-20 mA signal with a loop isolator, or from a
network signal.
The operating sequences shown are some of many pos-
sible loading sequences for the control of the leaving water
temperature. If a circuit has more unloaders than another,
that circuit will always be the lead circuit.
UNIT
30GN
“““ft
Hr)
y-yy
,
040 (60 Hz)
045 (60 Hz)
AIt
040 (50 Hz)
0:; pg~l
,
040 (50 Hz)
o;y;,y
,
045 (50 Hz)
050f”,
Hz)
045 (50 Hz)
050 (60 Hz)
Alt,Bl**
045 (50 Hz)
050A\6$Hz)
045 (50 Hz)
yfyy2
I
045 (50 Hz)
*Unloaded compressor.
tCompressor unloader, standard.
**Compressor unloader, accessory.
ttTwo
unloaders, both unloaded.
CONTROL
STEPS
Table 4A-
:
i
:
i
:
:
1
:
4
5
1
:
4
i
1
;
4
:
:
5
:;:
:
5100
1
:
z
6
7100
1
32
4
i
7
Capacity Control Steps, 040-070
LOADING SEQUENCE A
%
DisplacementCompressors
(AwrW
::
1~~
25
%
100
s;
1;:
24
::
1::
--
--
-
-
--
--
i:
1::
:A
8°F
100
is;
18
::
56
2
-
--
--
-
--
--
Al*
APB1
Al
:Bl
Al*
Al”B1
Al
,kl
Al”
Al”B1
Al
,k
Al*
Al% *
Al ‘,Bl
Al ,Bl
-
-
Al*
Al
Al *,Bl
Al ,Bl
Al*
Al% *
Al ‘,Bl
Al
,Bl
A2-y
y&tgi
Al
,i31
A2.p
Al;Bl*
Al
+,Bl
Al *,Bl
Al ,Bl
-
-
-
LOADING SEQUENCE
%
Displacement
tAppro
-
-
-
25
50
1::
-
-
-
:;
El
100
::
53
i:
100
-
-
-
-
38
::
1%
-
-
-
-
-
-
-
-
-
-
-
-
El
z7
64
1::
B
Compressors
-
-
-
-
Bl*
AIBlil
*
Al’,Bl
-
-
-
-
Bl*
Al& *
Al ,‘sl*
Al
.Bl
-
-
-
Bl”
Al%
*
Al,k
Al
.Bl
-
-
-
-
-
-
-
-
-
-
Al
,Bl
5
Page 6
Table 4A
-
Capacity Control Steps, 040-070
(cant)
UNIT
30GN
050 (50 Hz)
060G
Hz)
050 (50 Hz)
“g pgy
I
050 (50 Hz)
060A\~**Hz)
050 (50 Hz)
06g$,y
I
060 (50 Hz)
070fc
Hz)
060 (50 Hz)
07Odpto**Hz)
1
Y
1
6
1
I
I
I
LOADING SEQUENCE ALOADING SEQUENCE B
%
Displacement
tApw0
.
..a
18
?I
56
73
Compressors
Compressors
1:;
28
-
-
-
-
-
15
Al*
Al”B1
Al
,k
Al*
Al% *
Al’,Bl
Al
,Bl
A&t!
#$Vg,
Al
,‘sl
yi!
-
-
-
-
-
A;p
Al~~Bl*
A$t!g’
Al ,‘sl
Al*
Al”Bl
Al
,i31
Al*Bl*
Al%
*
Al ‘.Bl
Al @I
A:$
AV$B1
Al .Bi
-
-
-
-
18
z:
8600
100
--
-
--
-
zi
66
83
100
-
-
-
-
“d,i;t)
-
-
-
-
-
-
Bl*
Al&l’
Al ,‘sl*
Al ,Bl
-
-
-
-
-
Bs’lt,t
Al’,Bi
-
-
-
Al&’
Al
.i31*
Ai,Bl
-
-
-
-
i
-
-
060 (50 Hz)
oypg~)
,
*Unloaded compressor.
j-Compressor unloader, standard.
**Compressor unloader, accessory.
ttTwo
unloaders, both unloaded.
Ei:
83
100
Page 7
Table 4A- Capacity Control Steps, 040-070 (cant)
UNIT
060
30GN
(50 Hz)
1 _
. .
i
;.
“‘“G Hz)
oy&ya
,
%
Displacement
tApprod
16
2:
:i
100
2
65
i;
100
Compressors
Al*
A-FBI
Al
,k
Al l ,A2,Bl
Al
,A2.B1
Al”Bl*
Al%
l
Al fB1
Al
,Bl
Al *,A2,Bl*
Al *,A2,Bl
Al
,A2,BlAi’,A2’,Bl
LOADING SEQUENCE A
T
LOADING S
%
Displacement
(Approx)
i!
ii:
83
100
-
-
-
-
--
--
-
-
-
WENCE
Al*,A2,Bl*
Al
B
Al’,61
--
Al&
Al ,‘sl*
Al
,Bl
.A2.B1*
-
-
-
*
-
--
--
-
-
-
-
-
-
-
-
-
-
--
15
::
-
57
ii
Al&
Al
Al
ylf,t
Al :Bt
,A2,Bl*
.A2.B1
l
070 (50
Hz)
Al
t**,Bl**
*Unloaded compressor.
tCompressor unloader, standard.
**Compressor unloader,
ttTwo
unloaders, both unloaded.
accessory.
A&’
Al
:Bl
Al ,A2,Bl*
Al
,A2,Bl
-
-
Page 8
,
Table 4B- Capacity Control Steps, 080-110 and Associated Modular Units
UNIT
30GN
080 (60 Hz)
Aly*,Blv
08Aqy;,y
,
I
LOADING SEQUENCE ALOADING SEQUENCE B
CompressorsCompressors
Al*
Al
Al*,Bl*
Al *,Bi
Al
,Bl
Al
*,A2,Bl
Al
.A2.B1
Aiti
Al”
Al+yBl*
AA’;Jgl
Al ,Bl
Al
*.A2.B1
Al
,A2,Bl
--
-
--
-
-
-
-
-
-
Al
tt
Ai*.
Al+yBl*
Al ++,Bl
Al *,Bl
Al
,Bl
Al
*.A2.B1
Al ,k2,Bl
Al*
Al%
*
Al
$1
Al ,Bl
Al *,A2,Bl*
Al *,A2,Bl
Al
,A2,Bl
Al tt
Al*
Al+?Bl*
AWtSg
Al
,Bl
Al
++,A2,Bl
A4l&pi’&
Al
.A2,Bl
-
-
-
-
-
-
-
-
A;.$!
r
%
Displacement
(4wW
z!
::
iii
100
-
-
--
-
-
-
-
-
-
-
l
-
--
--
Bl*
Bi
Ai*,Bl*
Al,Bl*
Al
,Bl
Al
.A2.81*
Ai,A2,Bi
-
-
-
-
y-/i+
A$-hJ
Ai,Bl
Al
,A2,61*
Al
,A2,Bl
Be’lt,t
A;{:;:)
Al’,Bl
Ai,A2,Bl*
Al
,A2,Bl
-
Bl*
A&*
Al,‘Bl*
Al
,Bl
Al
*,A2,Bi
Al ,A2,Bl*
Al
.A2.B1
,
,
-
-
-
-
-
-
B1
tt
Bl*
AIB:l
*
Ai,61
Al *,A2,Bl++
A;;“A’;“Wt
Ai.A;,Bl
y&f
*
AIBlk
Al+?Bl*
080
(SO Hz)
Aif”*,6if**
*Unloaded compressor.
+Compressor unloader, standard
**Compressor unloader, accessory
++Two
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
AJ&t,$
Al ++,A2,Bl*
AAit,-bA&l
Al
Al ,Bl
,A2,Bl
Ai,Bl
Al
*,A2,B1++
“d;“A’;“B’lt’t
Ai,Ai,Bi
-
-
*
Page 9
Table 4B- Capacity Control Steps, 080-110 and Associated Modular Units (cant)
UNITCONTROL
30GN
090 (60
Hz)
STEPS
Aly*,Blt
l-
Displacement
LOADING
%
VNwW
:;
E
53
65:
ii
91
-
-
-
-
-
-
-
-
-
iQUENCE
!
A
Compressors
Al*
Al%
*
Al ‘,Bl
Al ,Bl
Al *,A2,Bl*
Al *,AZ,Bl
Al
,A2,Bl
Al *,A2,Bl
Al *,A2,Bl
Al ,AZ,Bl,B2
A;!tf2UJ$
Al
Al *,A2,Bl
Al
*,B2
,B2
A2.p
A;,%&1
Al*:B 1
Al*A2 bl
tT,A2,i31 ,B2
,B2
,A2,Bl ,B2
-
-
-
-
-
-
-
-
-
-
-
-
LOADING
%
Displacement
(Approx)
;;
ii
2;
r3:
::
100
-
-
-
-
-
-
-
-
-
-
-
1
:QUENCE B
Compressors
Al
Al
Bl*
Al%*
Al,Bl*
Al ,Bl
Al *,Bl l ,B2
Al
,Bl *,B2
Al,Bl,B2
*,A2,Bl
Al
,A2,Bi *,B2
Al
.A2.B1 .B2
-
-
-
-
-
-
-
-
-
-
-
-
A;,:&>
Al’,Bl
Al
,Bl
tT,B2
Al
,Bl *,B2
Al
,Bl ,B2
,A2,Bl
t-t,82
Al
.A2.B1 *.B2
Al’,A&Bl
Bitt
BP’
*,B2
,B2
090 (60
Hz)
Alt**,BlY*
*Unloaded compressor.
tCompressor
**Compressor unloader, accessory
TtTwo
NOTE: These capacity control steps may vary due to lag compressor sequencing.
unloader, standard.
unloaders, both unloaded.
Al *,A2,Bl
Al
Al tt,A2,Bl
Al*,A2,Bl
Al
,A2,Bl ,B2
Al%1
Al ‘,Bl
Al
Al *,A2,Bl*
Al *,A2,Bl
Al
Al *,A2,Bl:,B2
Al
*.A2.B1 .B2
Al ,k2,Bi
Al;;
Al*,Bl
Al
Al tt,A2,81 l
Al tt,AP,Bl
Al
Al
Altt,A2,Bl*,B2
Al tt,A2,Bi
Al *,A2,Bl
Al
.A2.61 .B2
,A2,Bl
Al*
,Bi
,A2,Bl
A;:!
Bl
,Bl
*,A2,61
,A2,Bl
,B2
*
,B2
,B2
,B2
,B2
80
82
91
-
-
-
-
-
-
-
-
-
-
-
“d,:;tJ
Ai,Bl
AAli
BB’lt,t~~2
Ai,Bl
Al
Al*,A2,Bl
,B2
,A2,Bl TT,B2
Al .A2.Bl*.B2
Al’,Ai, Bl
Al .A2.Bl
Al’,Ai,Bi
Bi*
Al&
Al ,Bl*
Al
,Bl
Al*,Bl*,B2
Al,Bl*,B2
Al ,Bl
,B2
-
-
,B2
*
-
-
-
-
*,B2
*.B2
,B2
9
Page 10
Table 4B- Capacity Control Steps, 080-110 and Associated Modular Units (cant)
UNIT
30GN
090 (50 Hz)
Alt,Bly
090 (50 Hz)
Al t**,Bl t**
100, 2408,
100,24OB,
270B (60 Hz)
Alt**,Blt
CONTROL
STEPS
r
Displacement
LOADINGLOADING SEQUENCE B
%
(APPW
-
-
CompressorsCompressors
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
T
Displacement
(4wW
100
%
7
:;’
ii
43
Pii
60
7”:
Ei
A$!!
Al;;
Bl
Al
+I
Al
,Bl
Al
tt,AZBl
Altt,A2,Bl*
AlTT,A2,Bl
Al *,A2,Bl
Al
Al tt,A2,Bl
Al
TT,A2,Bl ,B2
Al*,A2,Bl
Al
Al *,A2,Bl*
;;*J.p;
Al *,A2,&
Al *,A2,Bl
Al
AltAt Bl
Al Tt,A2,Bl*
Al Tt,A2,Bl
Al
Al
Al tt,A2,Bl
Al Tt,A2,Bl
Al
Al
tt
,A2,Bl
*,B2
,B2
.A2,Bl .B2
Al*
Al%
*
Al (61
Al ,Bl
*,B2
,B2
,A2,Bl ,B2
“Alt!
Al*,&
Al ,Bl
*,A2,61
,A2,Bt
*,B2
,B2
*.A2.B1 .B2
,A2,i31,‘82
-
-
-
--
--
--
-
-
-
-
--
-
Al*,BlTT,BZ
“d;B~ltt~~2
A1’,Bl*k
Al *,A2,Bitt,Bl
Al ,A2,BlTt,Bl
A.i‘J;,;;
II
I
BB’.p
A;;:;H
Al’,Bl*
Al*,Bltt,B2
Al
,Bi TT,B2
Al ,Bl”,B2
Al
,Bl ,B2
Al
tt,AZBl
Al *,A2,Bl
Al ,A2,Bl
Al ,A2,61*,62
Al
,A2,Bl
Al*
Al% *
Al ‘,Bl
Al
,Bl
Al *,A2,Bl*
Al *,A2,Bf
Al
,A2,Bl
Al *,A2,Bi*,B2
Al *,A2,Bl
Al
,A2,Bl ,B2
-
-
i;2
tt,B2
j-T,B2
TT,B2
B2
,B2
100,24OB,
270B (60 Hz)
Alt,Blt^*
i
10
-
-
--
-
-
-
-
*Unloaded compressor
+Compressor unloader, standard.
**Compressor unloader, accessory.
TtTwo unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing
10
-
-
-
-
Ai,-Bi
Al*.Bltt.B2
-
-
Al ,A2,BltT,B2
Al
.A2.B1 *.B2
Al’,A$Bl
,B2
Page 11
Table 40- Capacity Control Steps, 080-I IO and Associated Modular Units (cant)
UNIT
30GN
100, 2406,
270B (60 Hz)
Alr*,Blr
100,
240B,
2708 (50 Hz)
A1tW-t
100,
240B,
2708 (50 Hz)
Aft**,Blt
i
;
9
::
E
14
LOADING SEQUENCE A
%
Displacement
(Awr
ox)
8
100
:;
26
100
7
Compressors
Altt
Al*
A$;g
Al ,bl
Al tt,A2,61*
Al tt,A2,61
Al *,A2,Bl
Al
,A2,Bl
Al tt,A2,Bl
Al tt,A2,Bl
Al *,A2,Bi
Al
.A2.B1 .B2
Al*
Al%
Al :Bl
A1
Al
*,A2,Bl*
Al *,A2,Bl
Al
,A2,Bl
Al
*,A2,Bl *,B2
Al*.A2.81
Al
,‘A2@1,82
Al tt
Al*
Wtf2Z$’
Al
,kI2,i31
Altt,A2,Bl
Al tt,A2,Bl
Al *,A2,Bl
Al .A2.Bl.B2
--
:
:
5
100, 2408,
270B (50 Hz)
Alt,Blt**
100, 2408,
270B (50 Hz)
Alr*,Blt”*
*Unloaded compressor.
tCompressor unloader, standard
**Compressor unloader, accessory.
tfTwo
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
6
8’
9
::
12
::
:
i
ii
;
9
::
E
::
16
--
-
--
--
--
-
--
--
-
-
--
Altt
A;,;h; 1
Al
Al
tt,AZBl
Al
tt,A2,Bl*
“A’p/pg
A1*iI2
Al tt,/i2,Eil tt,B2
Altt,A2,Bl*,B2
Altt,A2,Bl
Al
l ,AZ,Bl ,B2
Al ,A2,Bl
Al*
,Bl
-
-
-
-
-
-
,‘sl
bl
*,B2
,B2
$32
*
.B2
*,B2
,B2
,B2
,B2
,B2
tt
r
Displacement
%
(Apex)
100
-
-
-
-
-
-
LOADING
8
:i
:A
20”
::
;“7
E-
-
-
-
-
-
-
EQUENCE B
Compressors
Bitt
Bl*
Al
“B: tt
Ai,Bl*
Al ,Bl
Al*,Bltt,B2
“A;“B’lt”tb;2
Al’,Bl
Al
*,A2,Bl
Al
,A2,Bi
Al ,A2,Bl l ,BZ
Al
.A2,Bl ,B2
Bl*
Al%
Al,bl*
Al
Ad;g *‘8822
Al’,Bl*b2
Al *,A2$1
Al .A2.B1 l .B2
Al’,Ai,Bl
Bitt
Bl*
Ai,F;hJ
Al’,Bl
Al*,Bl
Al
,‘Bl
Al
,Bl *,B2
Al ,Bl,B2
Al*,A2,Bl tt,B2
Al
,A2,Bl
Al
.A2,Bl *.B2
Al
Ai,Bi*
Al,Bl
Al
tt,Bl
Al *,Bltt,B2
AAlj
“B’(t;3122
Al’,Bl
Al
tt,AZBl
Al *,A2,Bltt,B2
Al
,A2,Bl
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
,b2
tt,B2
tt,B2
,Bl
-
-
-
-
-
-
-
-
-
-
-
-
-
-
tt.132
ff,‘B2
tt,B2
:li
t+
tt,B2
,b2
tt,B2
*
*,B2
,B2
tt,B2
11
Page 12
-
Table 48-
Capacity Control Steps, 080-110 and Associated Modular Units (cant)
UNIT
30GN
LOADING SEQUENCE A
%
Displacement
(ApprW
14
;A
::
s6:
2
-
-
-
-
-
-
-
-
Compressors
Al*
&I *
Al ‘,Bl
Al
,Bi
Al l ,A2,Bl*
Al *,A2,Bi
Al
,A2,Bl
Al*,A2,Bl*,B2
Al
*.A2.B1 .B2
Al
,A2,Bl ,i32
A/p
A;;;#
Al
,Bl
Al Tt,A2,Bl*
Al
t-/-,A2,Bl
Al*,A2,Bl
Al
,A2,Bi
Al Tt,A2,Bl
Al -ft,A2,Bi
Al
Al ,k2,Bl
*,B2
,B2
*.A2.B1 .B2
,B2
-
-
-
-
-
-
-
-
-
-
A’tt
Al”
r
Displacement
LOADING SEQUENCE B
%
(Amrox)
-
-
-
-
-
-
-
-
-
-
Compressors
81”
Al51 *
Al,Bl*
Al
,Bl
;;*gg
Ai’,Bl
Al ,A2,Bl
Al ,A2,Bl
,B2
*,B2
,B2
Al*,A2,Bl*,B2
-
1
-
-
-
-
-
-
-
-
B1
tt
Bl*
Al !%
tt
Ai,Bi*’
Al
,Bl
Al*,BlTT,B2
“A;
BB’~t;3”2’
Al’,Bl
,A2,Bl
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
y&v
,B2
tT,B2
Al *,A2,BltT,B2
Al
A;;hgl
Al ,Bl
110 (60 Hz)
Al
t**,Bl Y
110 (50 Hz)
Alt,Blt
*Unloaded compressor.
TCompressor unloader, standard
**Compressor unloader, accessory.
TtTwo
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing
A’tt,AZBl
Al tt,A2,Bl*
$-t&Z3
Al
,A2,Bl
Al
tt,A2,Bl
Al Tt,A2,Bl
Al*.A2.B1
Al
,A2,Bl ,B2
Al*
Al% *
Al’,Bl
Al ,Bl
Al *,A2,Bl*
Al l ,A2,Bl
Al
,A2,61
Al
*,A2,Bl *,B2
Al *,A2,Bl
Al .A2Bl
tt
*,B2
,B2
.B2
,B2
.B2
100
A;,=.$
Ai,Bl
Al *,BltT,B2
“A;
B!&lW22’
Ai,Bl
Al
Al *,A2,Bltt,B2
A-l ,A2,Bl
Al *,A2,Bl
,B2
ttNB’ttB2
.A2.B1 *.B2
Al’,Ai,Bl
Bl*
Al%
Al ,Bt*
Al
,Bi
Al l ,Bl
Al ,Bl
Al
,Bl ,B2
A;,Ai,Bl
tT,B2
*,B2
*,B2
Al
Al .A2,Bl*.B2
,i32
*,B2
,B2
12
Page 13
Table 4B
-
Capacity Control Steps, 080-110 and Associated Modular Units (cant)
UNIT
30GN
110 (50 Hz)
Alt**,Blt
CONTROL
STEPS
LOADING
%
Displacement
UWrW
-
-
SEQUENCE A
Compressors
*$#l
Al ,Bl
“A:tkA2’i3BI~
AleA2
Al tf,A2,Bl
Al *,A2,Bl
Al
,AZ,Bi ,B2
-
-
110 (50 Hz)
Alt,Blv
-
-
-
-
-
-
-
:
a
Al;; Bl
110 (50 Hz)z
Alt**,Blt**
*Unloaded compressor.
TCompressor unloader, standard.
**Compressor unloader,
TTTwo
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing
i
9
::
12
accessory
Al *,Bl
Al ,Bl
*&Wf22il”l’
Al*A2 Bl
Al tt,A2,Bi
Al *,A2,Bl
Al
,A2,Bl ,B2
A2.p
-
-
-
-
-
-
-
-
-
-
-
-
*;$T
Bl
,B2
,B2
,B2
,B2
T
LOADING :
%
Displacement
(Arwox)
-
-
-
-
-
-
-
-
-
-
-
-
a
,QUENCE B
Compressors
Be’lt,t
*;,F;:t
Al’,Bl
“A;W&3$
Ai,Bi
Al
,A2,Bl
Al ,A2,Bf
Al
.A2,Bl ,B2
“B’p
~,;~~J
AI’,Bl
Al ,BltT,B2
Al
,Bl *,B2
Al
Al
,A2,Bl
Al
,A2,B1 *,B2
Al
.A2.B1 .B2
-
-
-
-
-
-
-
-
-
-
-
,B2
tt,B2
,Bi ,B2
tt,B2
*,82
13
Page 14
Table 4C- Capacity Control Steps, 130-210 and Associated Modular Units
30GN
130,
130,
130,
UNIT
240A,
240A,
240A,
T-
Displacement
LOADING
%
Mvrox)
:‘:
:fz
2;
;i
Ei
100
-
-
-
-
-
-
-
-
-
-
-
-
-
-
EQUENCE A
Compressors
Al*
Al% *
Al ‘,Bl
Al ,Bl
Al *,A2,Bl*
Al *,A2,Bl
Al
,A2,Bl
Al
*,A2,Bi
Al*,A2,Bl
Al
.A2.B1 .B2
’
Al’tt
Al*
AlgBl’
A$t;l”i’
Al
Al
tt,A2,Bi
Al tt,A2,B1
Al *,A2,Bl
Al
,A2,Bl
Al tj-,A2,Bi*,B2
Al tt,A2,Bl
Al
*.A2.B1 .B2
A? ,iI2,-Bl ;B2
yp
*,B2
,B2
’
r
LOAD11
%
Displacement
VVwr ox)
:i
z
2;
;:
K
100
-
-
-
EQUENCE B
Compressors
Bl*
Al&’
Al
Al ,Bl
Al l ,Bl l ,B2
Al ,Bi
Al ,Bl
Al?,A2,Bl
Al ,A2,Bf*,B2
Al
,A2,Bl ,B2
‘-
-
-
,k*
*,B2
,B2
*,B2
-
-
-
,kH
*
-
-
-
-
-
-
,B2
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
BJ.fJ
;-y;;;;
Ai,Bi*
Al ,Bl
Al *,Bltt,B2
“A;B&t$&2
Al’,Bl ,k2
Al *,A2,Bltt,B2
Al ,A2,Bltt,B2
Al
,A2,Bl
*,B2
Al
,A2,Bl ,B2
BB’!!
AlRBl’
AAlt,t&’
130,
240A,
130,24OA,
*Unloaded compressor
tCompressor unloader, standard.
**Compressor
ttTwo unloaders, both unloaded
NOTE: These capacity control steps may vary due to lag compressor sequencing+
unloader,
accessory
Al
Al
ttA2,Bl
Al tt,A2,Bl*
Al tt,A2,Bi
Al
*.A2.B1
Al
,iI2,‘Bi
Al
ttAW1
Al tt,A2,Bl
Al tt,A2,Bl
Al
*.A2,Bl .B2
Al
,k2&,82
Al*
A&l
Al ‘,Bl
Al ,Bl
Al *,A2,Bll
Al *,A2,Bl
Al
,A2,Bl
Al
*,A2,Bl
Al*,A2,Bl
Al
,A2,Bl ,B2
Al
*,A2,A3,Bl *,B2
Al
*,A2,A3,Bl ,B2
Al
.A2.A3.Bi .B2
,kl
tt
tt,B2
*,B2
,B2
*
*,B2
,B2
Al*%++
Al.,Bl
Alt-t-41tt,B2
Al *,Bl tt,B2
“A;
BB’~~~~2
Al’,Bl ,k2
Altt,A2,Bltt,B2
Al l ,A2,Bl
Al ,A2,Bltt,B2
Al
Al’,A2’,Bl ,i32
Al*,A2,Bl
Al ,A2,Bl*,B2
Al *,A2,A3,Bl
Al qA2qA3.81 *.B2
.A2.B1 *.B2
Bl*
Al&
Al,kl*
Al
,Bl
Al *,Bl
Al ,Bl
Al ,Bl
Al
,A2,Bl ,B2
tt,B2
*
*,B2
*,B2
,B2
*,B2
*,B2
14
Page 15
Table 4C- Capacity Control Steps, 130-210 and Associated Modular Units (cant)
UNIT
30GN
130, 24OA,
130,24OA,
CONTROL
STEPS
r
Displacement
LOADING SEQUENCE A
%
hwrox)
6
-
-
-
-
-
-
-
Compressors
“drt,t
AlPtlBl*
Al
tt,Bl
Al l
,Bl
Al
,Bl
Al tt,A2,Bl*
“A’:t;P22~7El
Al*A2Bl
Al tt,A2,Bl
Altt,A2,Bl
Al *,A2,Bi
Al
,A2,Bl ,B2
Al tt,A2,A3,Bl
Al tt,A2,A3,Bl
Al *,A2,A3,Bl
Al
,A2,A3,Bl ,B2
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
A$v
*,B2
,B2
,B2
*,B2
,B2
,B2
T
Displacement
LOADING SEQUENCE B
%
(Awrox)
-
-
-
-
-
-
-
-
-
-
-
-
Compressors
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Bitt
Bi*‘
AIB&
Al’,Bl
Al *,Bl tt,B2
Al ,Bl tt,B2
Al
,Bl
Al ,Bl
Al
,A2,Bl
Al ,A2,Bl*,B2
Al
,A2,Bl ,B2
Al
,A2,A3,Bl
Al
,A2,A3,Bi *,B2,B3
Al
,A2,A3,Bl ,B2,B3
B;.p
*
*,B2
,B2
tt,B2
tt,B2,B3
Al;t:Bl*
A;;Jbg’
Al
,Bl
130,
240A,
*Unloaded compressor.
tCompressor unloader, standard.
**Compressor unloader, accessory
ttTwo
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
Al tt,A2,Bl*
A;~tA$2’~1
Al*A2 Bl
Altt,;22,Bl*,B2
Al tt,A2,Bl
Al
*,A2,Bi ,B2
Al
,A2,Bl ,B2
Al tt,A2,A3,Bl*,B2
Altt,A2,A3,Bi
Al*,A2,A3,Bl
Al
,A2,A3,Bl ,B2
Al’
Al
Al *,Bl*
Al *,Bl
Al
,Bl
Ai*,A2,Bl*
Al l ,A2,Bl
Al
,A2,Bi
Al
*,A2,Bi
Al *,A2,Bl
Al
,A2,Bl ,B2
Al*,A2,A3,Bl
Al
*,A2,A3,81 ,B2
Al
,A2,A3,Bl ,B2
,B2
,B2
l ,B2
,B2
*,B2
,B2
AIBIL
*
Ai,Bi
Al l ,Bl
tt,B2
Al .Bltt.B2
At
,Bf’*;B2
Al ,Bl
Al
Al
Al ,A2,A3,Bll ,B2
Al
,B2
.A2.B1
tt.B2
Ai
,A2,Bl’*;B2
Al
,A2,Bl ,B2
,A2,A3,Bl
,A2,A3,Bl ,B2
-
-
tt,B2
-
-
-
Bi*
A&l
*
Al ,Bl*
Al ,Bl
Al
*,Bl
*,B2
Al ,Bl
*,B2
Al
,Bl ,B2
Al l ,A2,Bl l ,B2
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
Al l ,A2,A3,Bl *,B2
Al ,A2,A3,Bl*,B2
Al
,A2,A3,Bl ,B2
15
Page 16
Table 4C- Capacity Control Steps, 130-210 and Associated Modular Units (cant)
EQUENCE ALOADING
UNIT
30GN
%
Displacement
(Apwxl
6
::
Compressors
y-p
AlPtlBl’
:“;
zi
49
53
ii
i:
ii:
95
100
-
-
-
-
-
--
-
--
--
--
150 (60 Hz)
Aly*,Blt**
15Aq y4
I
*Unloaded compressor.
tCompressor unloader, standard
**Compressor unloader, accessory.
ttTwo
unloaders, both unloaded
NOTE: These capacity control steps may vary due to lag compressor sequencing
“Att;l”l’
Al
,‘sl
AWh$Y;
Al ,A2,&
Altt,A2,Bi*,B2
Al tt,A2,Bl
Al *,A2,Bl
Al
,A2,Bl ,B2
Al tt,A2,A3,Bl
Al
*,A2,A3,Bl ,B2
Al
.A2.A3.81 .B2
-
-
-
-
-
-
-
-
-
$y!
Al;Bl*
Al tt’,Bl
Al *,Bi
Al ,Bl
Al
tt,A2,Bl
Al *,A2,Bl
Al
,A2,81
Al tt,A2,Bl
Al tt,A2,Bl
Al
*,A2,Bl ,B2
Al
,A2,Bl ,B2
Altt,A2,A3,Bi
Al
*,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2
Ai*
Al%
Al ‘,Bl
Al
Ai*,A2,Bl*
Al
*,A2,Bl
Al
,A2,Bl
Ai*,A2,Bl*,B2
Al*,A2,Bl,B2
Al
,A2,Bl ,B2
Al
*,A2,A3,Bl *,B2
Al
*.A2,A3.B1 .B2
Al ,k2,k3,Bl
Al
Al*
Al;;
Al*,&
Al ,Bl
Wh‘v‘&E&’
Al
,h2,1Bl
Al tt,A2,Bl
Al
*,A2,Bl ,B2
Af
,A2,Bl ,B2
Al tt,A2,A3,Bi
Al
*,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2
16
,Bl
tt
Bl
,B2
,B2
*,B2
,B2
*
,,B2
,B2
,B2
,B2
,B2
r
Displacement
LOADING
%
UQwrox)
EQUENCE 8
-
--
-
-
-
-
-
-
-
--
--
--
--
-
-
-
--
--
--
--
--
--
--
--
-
-
-
-
--
-
Compressors
-
-
-
-
-
-
B1
tt
BP-
AIBL
Ai,Bl
Al *,Blft,B2
“Ai”B’lt”tb;’
Al’, Bl ,b2
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
Al
,A2,A3,Bl *,B2
Al .A2,A3,Bl
Bitt
Bl*
AIBIL
Al ;kBl
Al *,Bltt,B2
“A;B~ltti3”2’
Al’,Bl*i32
Al
,A2,Bi
*,B2
Al
,A2,Bl ,B2
Al
,A2,A3,Bl *,B2
Al
,A2,A3,Bl ,B2
-
-
-
-
Bl*
Al&q*
Al ,‘sl*
Al ,Bl
Al *,Bl
*,B2
Al ,Bl
*,B2
Al ,Bl
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
*,A2,A3,Bl
-
,B2
Al *,A2,Bl
Al
Al ,A2,A3,Bl
Al ,A2,A3,Bl
-
*
*
,B2
*,B2
*,B2
*,B2
,B2
Page 17
Table 4C- Capacity Control Steps, 130-210 and Associated Modular Units
(cant)
UNIT
SIZE
Displacement
LOADING SEQUENCE A
%
(4wrox)
-
--
-
--
--
150 (50 Hz)
Alt,Bly*
-
--
-
-
-
--
-
--
--
-
-
--
-
A2.p
A+;~;1
Al
150 (50 Hz)
Alr*,Blt*”
170,
270A, 300B,
330;; fTt Hz)
,
Al tt,A2,81
Al
*,A2,Bl
Al
,A2,Bl
Al tt,A2,Bl
Al *,A2,Bi
Al
,A2,Bl ,B2
Al tt,A2,A3,Bl
Al
*,A2,A3,Bl ,B2
Al
.A2,A3,Bl ,B2
Al*
Al% *
Al*‘.Bl
Al
Al *,A2,Bl*
Al ‘,A2,Bl
Al
,A2,Bl
Al
*,A2,Bl *,B2
Al
*,A2,Bi ,B2
Al
,A2,Bl ,B2
Al
*,A2,A3,Bl *,B2
Al *,A2,A3,Bl
Al
,A2,A3,Bl ,B2
Al*.A2.A3,Bl
Al ‘,Ai,A$Bl,82,83
Al
,A2,A3,Bl ,B2,B3
A$!!
AltyBl*
A&tttt;’
Al
Al tt,A2,Bl*
y&t3g
Al
170,
270A,
3008,
Altt,A2,A3,Bl
Altt,A2,A3,Bl
*Unloaded compressor.
tCompressor unloader, standard.
**Compressor unloader, accessory
ttTwo
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
,i2,kl
Altt,A2,Bl
Al tt,A2,Bl
Al
*,A2,61 ,B2
Al
,A2,Bl ,B2
Al tt,A2,A3,Bl
Al tt,A2,A3,Bl
Al
*,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2
Al*,A2,A3,Bl
Al
,A2,A3,Bl ,B2,B3
,‘Bl
,‘Bl
,kl
,B2
,B2
,B2
,B2
*.B2.83
*,B2
,B2
*,B2
,B2
*,B2,B3
,B2,B3
,B2,B3
SEQUENCE B
CompressorsCompressors
Bitt
“A;“B’:t;3”2’
Al’,Bl*‘BP
Al ,A2,Bl’tt,B2
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
Al ,A2,A3,Bltt,B2
Al ,A2,A3,Bl*,B2
Al
,A2,A3,Bl ,B2
“B’.p
A~i~~~~
AljBl
Al
.Bl
Ai
,B1’*;[32
Al
Al
,A2,Bl
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
Al
,A2,A3,Bl
Al
,A2,A3,Bl *,B2
Al ,A2,A3,Bl,B2
A&*
Al ,‘sl*
Al
Al
*,Bl
Al
,Bl *,B2
Al
Al
*,A2,Bi
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
Al *,A2,Bl
Al,A2,Bl*,B2,B3
Al
,A2,Bl ,B2,B3
Al
*,A2,A3,Bl *,B2,B3
Al
,A2,A3,Bl *,B2,B3
Al
-
--
,A2,A3,Bl ,B2,83
--
-
--
--
--
--
-
-
-
-
-
--
Bl-*.
tt.B2
,Bl ,B2
tt,B2
Bl”
,Bl
*,B2
,Bl ,B2
l ,B2
*,B2,83
--
-
--
--
-
-
-
-
-
-
tt,B2
17
Page 18
Table 4C -Capacity Control Steps, 130-210 and Associated Modular Units (cant)
UNIT
SIZE
Displacement
LOADING SEQUENCE A
%
(Aiwrox)
-
Compressors
-
-
-
-
-
-
-
-
-
170,
270A,300B,
-
-
-
-
-
-
-
Al tt
Al;Bl*
“Alt;tbT’
Al ,Bl
Alft,A2,Bl*
A&t$$V;
170,27OA, 300B,
170,27OA, 300B,
33oA/,$cH350
*Unloaded compressor.
tcompressor unloader, standard.
**Compressor unloader, accessory.
ttTwo
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing
Hz)
9
Al
Altt,A2,Bl*,B2
Al tt,A2,Bl
Al
*,A2,B1 ,B2
Al
,A2,Bl ,B2
Al tt,A2,A3,Bi
Al tt,A2,A3,Bl
Al”,A2,A3,Bl
Al
,A2,A3,Bl ,B2
Al tf,A2,A3,Bl
Al tt,A2,A3,Bl
Al*,A2,A3,Bl
Al
.A2,A3.B1 .B2,B3
Al%
Al ‘,Bl
Al ,Bl
Al *,A2,Bl*
Al
Al
Al
*,A2,Bl
Al *,A2,Bl
Al
,A2,Bl ,B2
Al
*,A2,A3,Bl *,B2
Al
*,A2,A3,Bl ,B2
Al
,A2,A3,Bi ,B2
Al
*,A2,A3,Bl *,B2,B3
Al
*,A2,A3,Bl ,B2,B3
Al
,A2,A3,Bl ,B2,83
-
-
-
-
-
-
-
-
-
-
-
Al*
,A2,Bl
Al*
*,A2,Bl
,A2,Bl
*,B2
,B2
*,B2
,B2
*,B2,B3
,B2,B3
,B2,83
*
,B2
,B2
r
LOADING SEQUENCE B
Compressors
yp
;-;,q
Ai,Bi*
Al ,Bl
Al*,BItt,B2
“Ai”B’lttb”2’
Al’,Bl*BP
Al *,A2,Bitt,B2
Al
,A2,Bl
tt,B2
Al ,A2,Bl l ,B2
Al
,A2,Bl ,B2
Al *,A2,Bi-ft,B2,B3
Al ,A2,Bltt,B2,B3
Al
,A2,Bl *,B2,B3
Al
,A2,Bl ,B2,B3
Al *,A2,A3,Bltt,B2,B3
Al
,A2,A3,Bl
Al ,A2,A3,Bil ,B2,B3
Al .A2.A3.Bl
6
tt,B2,63
.B2.B3
B;$+
~l*;;{#
Ai,Bl*
Al
,Bl
Al *,BltT,B2
“A’iBe’~~~22
Al’,Bl
Al *,A2,Bltt,B2
Al ,A2,Bltt,B2
Al *,A2,BltT,B2,B3
Al ,A2,Bltt,B2,B3
Al ,A2,81*,82,83
Al
Al*,A2,A3,Bl tt,B2,B3
Al ,A2,A3,Bltt,B2,B3
Al
,A2,A3,Bl *,B2,B3
Al
Al *,A2,Bl
Al *,AZ,Bl
Al ,A2,Bl*,B2,B3
Al ,A2,Bl
Al *,A2,A3,Bl
Al ,A2,A3,Bl*,B2,B3
Al ,A2,A3,Bl
,B2
Al
,A2,Bi *,B2
Al ,A2,Bl
,A2,A3,Bl ,B2,B3
Al *,Bl
Al
Al ,A2,Bl
,B2
,A2,Bl ,B2,B3
Bl*
A&*
Al ,Bl*
Al ,Bl
*,B2
Al
,Bl *,B2
Al
,Bl ,B2
*,B2
,A2,Bl *,B2
,B2
*+B2,B3
,B2,83
*,B2,B3
,B2,B3
18
Page 19
Table 4C -Capacity Control Steps, 130210 and Associated Modular Units (cant)
UNIT
SIZE
170,
270A, 300B,
33OA/z, t”fB,:“O Hz)
170,
33OA/z,
I
270A,
3008,
t”609+{,50
,
Hz)
CONTROL
STEPS
l-
Displacement
(Approx)
%
:
11
19
;:
:i
37
:i
z;
::
72
i:
;:
96
100
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
LOAD11
i SEQUENCE A
Compressors
A)$
Al+yBl*
Altt;3B11
Al
,Bl
Al tt,A2,61*
*‘-J-&W~’
Al
,1A2,Bl
Al tt,A2,Bl
Al tt,A2,Bl
Al *,A2,Bl
Al
,A2,Bl ,B2
Al tt,A2,A3,Bl
AlTt,A2,A3,Bl
Al *,A2,A3,Bl
Al ,A2,A3,Bl
Al
tt,A2,A3,Bl *,B2,83
Altt,A2,A3,Bl
Al*,AZ,A3,Bl
Al ,A2,A3,Bl
*;p
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
*,B2
,B2
,B2
*,B2
,B2
,B2
,B2
,B2,B3
,B2,B3
,B2,B3
r
Displacement
(APP~~x)
%
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
LOAD11
i SEQUENCE B
Compressors
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
I31
Al*,Bltt
*~i~~~~
Al’,Bl
Al *,BlTj-,B2
Al ,Bl tt,B2
Al .Bl *.B2
Ai,Bl
Al*.A2,Bl tt,B2
Al
Al *,A2,BItt,B2,B3
Al ,A2,Bltt,BZ,B3
Al
Al ,A2,Bl,B2,B3
Al *,A2,A3,Bltt,B2,B3
Al
.A2.A3,Bl
Ai,Ai,A$,Bt’*;82,63
Al
,b2
,A2,Bl
ff,B2
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
,A2,Bl *,B2,83
tt,B2,B3
,A2,A3,Bl ,B2,B3
BB’!J
Al;T’Bl*
Al
+,Bl
Al l ,Bl
Al
Al
t-),*2,61
“A! tA$2f,’
Al*A2Bl
170,27OA,
330~A~~~f\; ff Hz)
*Unloaded compressor.
j-Compressor unloader, standard
**Compressor unloader, accessory
ttTwo unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
3008,
,
81
ii;
:A
100
Alft,A2,B’ltt,B2
Al
tt,A2,Bl
Altt,A2,Bl
Al *,A2,Bl
Al
,A2,Bl ,B2
Al tT,A2,A3,Bl tt,B2
Al tt,A2,AS,Bf
Al tt,A2,A3,Bl
Al
*,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2
Altt,A2,A3,Bltt,B2,B3
Altt,A2,A3,Bl*,B2,B3
Al tt,A2,A3,Bl
Al
*,A2,A3,Bl ,B2,B3
Al
,A2,A3,Bi ,BZ,B3
19
,Bl
*
*,B2
,B2
,B2
*,B2
,B2,B3
,B2
;;*;,’ ‘j
Ai,Bl*
Al
,Bl
Al
tt,Bl
t-t,82
Al *,Bltt,B2
“d;“B’W@&’
Al’,Bl*‘BZ
Al *,A2,Bitt,B2
Al
,A2,Bl TT,B2
Al
,A2,Bl*,E32
Al
,A2,Bl ,B2
Al
tt,A2,Bl tt,B2,B3
Al
*,A2,Bl
Al
Al Tt,A2,A3,Bl tt,B2,B3
Ai*,A2,A3,Bltt,B2,B3
Al ,A2,A3,BlTt,B2,B3
Al
Al
tt,B2,B3
,A2,Bi
tt,B2,B3
Al
,A2,Bi *,B2,83
Al
,A2,Bl ,B2,83
,A2,A3,Bl *,B2,B3
,A2,A3,Bl ,B3,83
Page 20
-
Table 4C -Capacity Control Steps, 130-210 and Associated Modular Units (cant)
UNIT
SIZE
190,36OA/B,
39oEpt
190,36OA/B,
39;: jfj’;,“”
190,
39;; (BGp*w
Hz)
I
,
360A/B,
,
CKEL
r
Compressors
Ah
Al j2,B-i
Al
,A2,Bl ,B2
Al
,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2,63
Al*
yp;
Al
*,A2,81
Al
,A2,B1
Al *,A2,Bl
Al
Al
*,A2,A3,Bl ,B2
Al
,A2,A3,81 ,B2
Al
*,A2,A3,Bi ,B2,B3
Al
,A2,A3,Bl ,B2,B3
-
-
-
-
Al *,A2,Bl*
Al *,A2,Bl
Al *,A2,Bl
Al
Al l ,A2,A3,Bl *,B2
Al
*,A2,A3,Bl ,B2
Al
Al
l
Al
*,A2,A3,Bl ,B2,B3
Al
,A2,A3,Bl ,B2,83
,B2
,A2,81 ,B2
-
-
-
-
-
-
-
-
-
-
-
-
Al*
Al
Al *,Bl
*
Al *,Bl
Al,Bl
Al *,A2,Bl
Al
,A2,Bi
*,B2
,B2
,A2,Bl ,B2
,A2,A3,Bl ,B2
,A2,A3,Bl*,B2,B3
l-
Displacement
LOADIN<
%
OVvW
2
41
56
1;:
-
-
--
-
-
-
-
--
SEQUENCE B
Compressors
A1B’Bl
Al ,&I
Al ,A2,Bl
Al
.A2.B1 .B2.B3
Al ,A2,d3&
-
-
-
-
-
-
-
-
-
Bl*
AIBf& *
Ai,Bl
Al ,Bl
Al,Bl,B2
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
Al
,A2,Bl *,B2,B3
Al
,A2,Bl ,B2,B3
Al ,A2,A3,Bl
Al
,A2,A3,Bl ,B2,B3
Bl*
Al&
Al,i31*
Al
Al *,Bl*,B2
Al ,Bl*,B2
Al ,Bl
Al*,A2,Bi
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
Al
*,A2,Bl
Al
,A2,Bl *,B2,B3
Al
,A2,Bl ,B2,B3
Al
*,A2,A3,Bl *,B2,83
Al
,A2,A3,Bl
Al ,A2,A3,Bl
,B2
,B2
,@2,B3
*,B2
*,B2,83
l
,Bl
,B2
*,B2
l ,B2,B3
l ,B2,B3
,B2,B3
190,36OA,
39OE31(6CC
39;; j:;,W
*Unloaded compressor.
tCompressor unloader, standard.
**Compressor unloader, accessory.
TtTwo unloaders, both unloaded
NOTE: These capacity control steps may vary due to lag compressor sequencing
Hz)
,
190,36OA,
I
A%1
Al
,A2,Bi
Al
,A2,Bl ,B2
Al
,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2,B3
Al*
fk;
;;*A$&
Al *,A2,&
Al
,A2,Bl ,B2
Al
l ,A2,A3,Bi ,B2
Al
,A2,A3,Bl ,B2
Al
*,A2,A3,Bl ,B2,B3
Al
,A2,A3,Bl ,B2,B3
20
,B2
A%1
Al ,EkB2
Al
,A2,Bl ,B2
Al
,A2,Bl ,B2,B3
Al
,A2,A3,Bl ,B2,B3
-
-
-
-
-
-
-
-
-
-
-
-
--
-
-
-
-
-
-
Page 21
Table 4C -Capacity Control Steps, 130-210 and Associated Modular Units
(cant)
UNIT
SIZE
190,36OA,
39:: (8514w
,
190,36OA,
=J”8”1 y
,
210,39QA,
420%:
(86p
Hz)
I
210,
390A,
42y3g
210,
42of,Bs(f~~Hz)
*Unloaded compressor.
j-Compressor unloader, standard.
**Compressor unloader, accessory.
ttTwo unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
,
390A,
1
HZ)
CONTROL
STEPS
Displacement
r
LOADING SEQUENCE A
%
UVvW
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Compressors
-
-
-
-
-
-
-
-
-
-
Al*
Al%
Al’,BI
Al ,Bl
Al*,A2,Bi*
Al *,A2,Bl
Al
,A2,Bl
Al *,A2,Bl
Al *,A2,Bl
Al ,A2,Bl
Al
*,A2,A3,Bl *,B2
Al
*,A2,A3,Bi ,B2
Al ,A2,A3,Bl
Al
*,A2,A3,Bl *,B2,83
Al
*,A2,A3,Bl ,B2,63
At ,A2,A3,B t ,B2,B3
A&
Al
,A2,Bl
Al
,A2,Bl ,B2
Al
,A2,A3,81 ,B2
AI
,A2,A3,Bl ,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
Al*
Al”B1
Al
,kl
Al l ,A2,Bl
Al
,A2,Bl
Al l ,A2,Bl ,B2
Al
,A2,Bl ,B2
Al l ,A2,A3,Bl ,B2
At
,A2,A3,Bt ,B2
Al l ,A2,A3,61 ,B2,B3
Al
,A2,A3,Bl ,B2,B3
Al l ,A2,A3,A4,Bi ,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
-
-
-
-
-
-
-
-
-
-
-
l
*,B2
,B2
,B2
,B2
l-
Displacement
PWprox)
LOAD11
%
11
:;
ii
50
61
7;
a3
94
100
14
-
--
-
--
--
-
--
-
i SEQUENCE B
Compressors
Al
Al,Bl,B2
Al
Al
Al
,A2,Bl *,B2,B3
Al
.A2,Bl ,B2,B3
Al ,A$,A$,Bi
Al
,A2,A3,Bl ,B2,B3
Al l ,Bl
;-,BB’;g
Al *,i2,B?
Al
Al
Al *,A2,Bl
Al
,A2,Bl *,B2,B3
AI
,A2,Bl ,B2,B3
Al*,A2,A3,Bl*,B2,B3
AI
.A2.A3.Bl *.B2.B3
Al $1
Al
Al
,A2,Bl ,B2,B3
Al
,A2,A3,Bl ,B2,B3
Al
,A2,A3.A4,Bl ,B2.B3
--
-
--
--
Al,Bl*,B2
Al
At ,A2,BI l ,B2
Al
Al ,A2,Bl l ,B2,B3
Al
,A2,Bl ,B2,B3
Al
,A2,A3,Bl *,B2,83
Al
,A2,A3,Bl ,B2,B3
Al
,A2,A3,A4,Bl *,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
Bl*
AIBt& *
Ai,Bl
,Bl *,B2
,A2,Bl
*,B2
,A2,Bl ,B2
l
Bl*
A&*
Al,i31*
Al ,Bl
*,B2
*,B2
,A2,Bi *,B2
,A2,Bi ,B2
*,B2,83
AK1
,B2
,A2,Bl ,B2
-
-
-
-
-
-
Bl*
Al’:1
*
Ai,Bi
,Bl ,B2
,A2,Bl ,B2
,82,83
21
Page 22
r-
A
Table 4C
UNIT
SIZE
Capacity Control Steps, 130-210 and Associated Modular Units (cant)
-
LOAD11
Compressors
Al*
Al%
Al ‘,Bl
Al,Bi
Al *,A2,Bl*
Al *,A2,Bl
Al
,A2,Bf
210,
390A,
420AIB (60 Hz)
Al**,Bl**
210,
390A,
420/U;
f-5;
Hz)
,
210,
390A,
42Ofy;; w
,
-
-
-
-
210,
390A,
42Of,~gw
,
210,39OA,
42\yE gyp)
I
*Unloaded compressor
tCompressor unloader, standard
**Compressor unloader, accessory
ttTwo
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
-
-
-
-
--
-
-
-
--
Al”,AP,Bi
Al l ,A2,Bl ,B2
Al
,A2,Bl ,B2
Al
*,A2,A3,Bl ‘,B2
Al
*,A2,A3,Bi ,B2
Al
,A2,A3,Bl ,B2
Al *,A2,A3,Bl
Al
*,A2,A3,Bl ,B2,B3
Al
,A2,A3,Bi ,B2,B3
Al
*,A2,A3,A4,Bl *,B2,B3
Al
*.A2.A3.A4.B1 ,B2,B3
Al ,k2,A3,A4,Bl
A&
Al
,A2,Bl
Al
,A2,Bl ,B2
Al
,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
Al”
Al”B1
Al ,Bl
Al *,A2,Bl
Al
,A2,Bl
Al
*,A2,Bl ,B2
Al
,A2,Bl ,B2
Al*,A2,A3,Bl
Al
,A2,A3,Bl ,B2
Al
*,A2,A3,Bl ,B2,B3
Al
,A2,A3,Bi ,B2,83
Al*,A2,A3,A4,Bl
Al
,A2,A3,A4,Bl ,B2,B3
-
-
-
-
-
-
Al*
Al%
Al ‘,Bl
Al
,Bl
Al*,A2,Bl*
Al *,A2,Bl
Al
,A2,Bl
Al l ,A2,Bl *,B2
Al *,A2,Bl
Al
,A2,Bl ,B2
Al
*,A2,A3,Bl *,B2
Al
*,A2,A3,Bi ,B2
Al
,A2,A3,Bl ,B2
Al
*,A2,A3,Bl
Al
*,A2,A3,Bl ,B2,83
Al
,A2,A3,Bl ,B2,83
Al*,A2,A3,A4,Bl*,B2,83
Al
*,A2,A3,A4,Bl
Al
.A2.A3.A4.B1
*
*,B2
*,E32,B3
,B2,B3
,B2
,B2,B3
*
,I32
*,B2,B3
,WB3
BZB3
f
Displacement
(Approx)
LOADING SEQUENCE Bi SEQUENCE A
%
9
i;
Compressors
Al%
Al .Bl*
Al’,Bl
Al*.Bl*,B2
Al ,Bl
Al ,Bl
Al *,A2,Bl
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
Al *,A2,Bl
Al ,A2,Bl*,B2,B3
Al
,A2,Bl ,B2,B3
Al *,A2,A3,Bl
Al
,A2,A3,Bl *,B2,B3
Al
,A2,A3,Bl ,B2,B3
AY*,A2,A3,A4,Bi *,B2,B3
Al ,A2,A3,A4,Bl*,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
Al $1
Al
,A2,B1 ,B2
Al ,A2,Bl
Al .A2.A3.Bl
Al
,A2,A3,A4,Bl ,B2,B3
--
-
-
-
--
--
--
AIB&
Al ,Bl
Al ,Bl
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
Al ,A2,Bl
Al
,A2,Bl ,B2,B3
Al
,A2,A3,Bl *,B2,B3
Al
,A2,A3,Bl ,B2,B3
Al
,A2,A3,A4,B1 *,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
Al&
Al .Bl*
Al*.Bl*,B2
Al
Al ,Bl
Al l ,A2,Bl *,B2
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
Al *,A2,Bl
Al ,A2,Bl
Al
,A2,Bl ,B2,83
Al *,A2,A3,Bl*,B2,B3
Al
,A2,A3,Bl *,B2,B3
Al ,A2,A3,Bl
Al*,A2,A3,A4,Bl*,B2,83
Al
,A2,A3,A4,81*,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
Bl*
*,B2
A&
-
-
-
-
-
-
-
-
-
-
Bl*
Al’,Bl
Bl*
Al’,Bi
,Bl *,B2
*
,B2
*,B2
*,B2,B3
*,B2,83
,B2
,B2,B3
.B2.B3
*
*,B2
,B2
*,B2,B3
*
,B2
*,B2,B3
*,B2,B3
,B2,83
22
Page 23
Table 4D- Capacity Control Steps, 225, 250,280
UNIT
30GT
225 (60 Hz)
r
Displacement
(Awox)
1:;
%
12
2
46
E
LOAC
\IG
SEQUENCE A
Compressors
*1A’B1
Al
,A2,61
Al
,A2,Bl ,B2
Al
,A2,A3,Bl ,B2
Al ,A2,A3,Bf
Al
,A2,A3,A4,Bl ,B2,B3
Al.A2.A3.A4.Bl.B2.B3.84
Al
Al
Al l ,A2,A3,Bl ,B2
Al
Al
*,A2,A3,Bl ,B2,B3
Al
,A2,A3,Bl ,B2,83
Al *,A2,A3,A4,Bl
Al
,A2,A3,A4,Bl ,B2,B3
Al*,A2,A3,A4,Bl,B2,B3,B4
Al
,A2,A3,A4,Bl ,B4,63,A4
Al
Al
Al
Al
*,A2,A3,Bl *,B2
Al
Al
Al l ,A2,A3,Bl l ,B2,B3
Al
,A2,A3,Bl *,B2,B3
Al
,A2,A3,Bl ,B2,B3
Al
*,A2,A3,A4,Bl *,B2,B3
Al*,A2,A3,A4,Bl
Al
,A2,A3,A4,Bl ,B2,B3
Al*,A2,A3,A4,Bl*,B2,83,84
Al.A2.A3.A4.Bl*.B2.B3.84
A1’,Ai,A$A4,Bl
,B2,B3
Al*
Al?Bl
Al
,Bl
Al *,A2,Bl
Al
,A2,Bl
*,A2,Bl ,B2
,A2,Bl ,B2
,A2,A3,Bl ,B2
,B2,B3
Al*
Al
_
Al *,Bl*
Al,Bl*
Al,Bl
Al *,A2,Bl*
Al *,A2,Bl
Al ,A2,Bl
*,A2,Bl
*,B2
,A2,Bl *,B2
,A2,Bl ,B2
*,A2,A3,Bl ,B2
,A2,A3,Bl ,B2
,B2,83
,B2,B3,B4
r
Displacement
hwrox)
LOADING SEQUENCE B
%
12
Al
Al,A2,A3,A4,Bl,B2,B3,B4
-
-
-
-
-
-
-
-
-
-
-
-
Al
Al *,A2,A3,Bl
Al *,A2,A3,Bl*,B2,83,84
Al ,A2,A3,Bl*,B2,B3,B4
Al ,A2,A3,Bl
Al*,A2,A3,A4,Bl*,B2,B3,B4
Al*,A2,A3,A4,Bl,B2,83,B4
At
,A2,A3,A4,Bl ,A2,B3,B4
Compressors
A&
Al $1
,B2
Al
,A2,Bl ,B2
Al
,A2,Bl ,B2,B3
Al
,A2,A3,Bl ,B2,B3
,A2,A3,Bl ,B2,B3,B4
-
-
-
-
-
Bl*
Ai&*
Al ‘,Bl
Al ,Bl
Al *,Bl
*,B2
Al
,Bl *,B2
Al,Bl,B2
Al
*,A2,Bl
Al
Al *,A2,Bl
Al ,A2,Bl*,B2,83
Al ,A2,Bl
l
Al
,A2,A3,Bl ,B2,83
*,B2
*,A2,Bl ,B2
Al
,A2,Bl ,B2
*,B2,83
,B2,B3
,A2,A3,Bl*,B2,B3
,B2,B3,B4
,B2,83
A%
Al
,A2,Bl
Al
225 (50 Hz)
Al,A2,A3,A4,Bi,B2,B3,84
Al*,A2,A3,A4,Bl
Al,A2,A3,A4,Bl,B2,B3,84
*Unloaded compressor.
TCompressor unloader, standard.
**Compressor unloader, accessory
TtTwo
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing
,A2,Bl ,B2
Al
,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
Al*
Ali’Bl
Al
,Bl
Al *,A2,Bl
Al
,A2,Bl
At
*,A2,Bl ,B2
Al
,A2,Bl ,B2
Al *,A2,A3,Bl
Al
,A2,A3,Bl ,B2
Al *,A2,A3,Bl
Al
,A2,A3,Bl ,B2,B3
Al
*,A2,A3,A4,Bl ,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
,B2
,B2,B3
,B2,B3,B4
23
AL
Al $1
,B2
Al
,A2,Bl ,B2
Al
,A2,Bl ,B2,83
Al
,A2,A3,Bl ,B2,B3
Al
,A2,A3,Bl ,B2,B3,B4
Al,A2,A3,A4,Bl,B2,B3,B4
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Page 24
UNIT
30GT
Table 4D
r
-
Capacity Control Steps, 225, 250,280 (cant)
JG
LOAC
SEQUENCE A
l-
Compressors
LOAC
4G
SEQUENCE B
Compressors
Al*
Al%
*
Al ,Bl*
Al
,Bl
Al
*,A2,81*
Al *,A2,Bl
Al
,A2,Bl
Al
*,A2,Bl *,B2
Al
,A2,B1 *,B2
Al
,A2,Bl ,B2
Al
*,A2,A3,Bf*,B2
Al *,A2,A3,Bl
Al
,A2,A3,Bi ,B2
Al*,A2,A3,Bi*,B2,63
Al*,A2,A3,Bl
Al
,A2,A3,Bl ,B2,B3
Al *,A2,A3,A4,Bl*,B2,83
Al *,A2,A3,A4,Bl
Al
,A2,A3,A4,Bl ,B2,B3
Al*,A2,A3,A4,Bl*,B2,83,B4
Al*.A2.A3.A4.Bl.B2.63.84
Al
,A2,A3,A4,Bl
22
32
250 (60
Hz)
29
32
t:
54
57
A1*,A2,A3,A4,Bl
s7:
:i
96
100
*Unloaded compressor.
JCompressor
**Compressor unloader, accessory
ttTwo
unloaders, both unloaded.
NOTE: These capacity control steps may vary due to lag compressor sequencing.
un!oader,
standard
Al*,A2,A3,A4,Bl*,B2,B3,B4
Al
Al
,A2,Bl ,B2
Al
,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2,B3
Al
.A2.A3,A4.B1 .B2.B3
“A:*gB;
Al *,A2,Bl
Al
Al
*,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2
Al *,A2,A3,Bl
Al
,A2,A3,Bl ,B2,B3
Al
*,A2,A3,A4,Bl ,B2,B3
Al
,A2,A3,A4,Bi ,B2,B3
Al,A2,A3,A4,Bl
Al%
Al*,A2,Bl*
Al
Al
Al l ,A2,Bl *,B2
Al ,A2,Bl*,B2
Al
Al *,A2,A3,Bl*,B2
Al
*,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2
Al*,A2,A3,Bl*,B2,B3
Al
,A2,A3,Bl *,B2,63
Al
,A2,A3,Bl ,B2,83
Al *,A2,A3,A4,Bl*,B2,B3
Al*,A2,A3,A4,Bl,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
Al,A2,A3,A4,Bl*,B2,B3,B4
Al,A2,A3,A4,Bl,B2,63,84
,B2,B3
,B2,B3&4
A%1
,A2,Bl
Al*
Al!‘Bl
Al
,Bl
,B2
,A2,Bl ,B2
,B2,B3
,B2,B3,B4
,B2,B3,B4
Al*
*
Al ,bll
Al
,Bl
*,A2,01
,A2,Bl
,A2,Bl ,B2
,B2
,B2,B3
Bl*
Al*B&*
Al,Bl*
Al
,Bl
Al *,A2,Bl*
Al *,A2,Bl
Al
,A2,Bl
Al *,A2,Bl
Al
Al
Al *,A2,A3,BI
Al*,A2,A3,Bl
Al
Al’,A2,A3,Bi*,B2,B3
Al *,A2,A3,Bl
Al
,A2,A3,Bl ,B2,83
Al*,A2,A3,A4,Bl*,B2,B3
Al
*,A2,A3,A4,B1 ,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
Al*,A2,A3,A4,Bl*,B3,B3,64
Ai*,A2,A3,A4,Bl
Al,A2,A3,A4,Bl,B2,B3,84
Al
Al
Al ,A2,A3,Bl
Al
.A2.A3.Bl .B2,B3.B4
Al ,A2,d3,A4,Bl
-
-
-
-
-
-
-
-
-
*,B2
,A2,Bl *,B2
,A2,Bl ,B2
*,B2
AK31
,B2
,B2,B3
,B2,B3,B4
,B2
,B2,83
,B2,B3,B4
,A2,A3,Bl ,B2
Al $1
,A2,Bl ,B2
,A2,Bl ,B2,B3
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Bl”
Al% *
Al ‘,Bl
Al ,Bl
Al *,Bl*,B2
Al ,Bl
“,B2
Al
,Bl ,B2
Al l ,A2,Bl *,B2
Al *,A2,Bl
Al ,A2,Bl
Al *,A2,Bl
Al
,A2,Bl *,B2,B3
Al
,A2,Bl ,B2,B3
Al*,A2,A3,Bl*,B2,B3
Al*,A2,A3,Bl
Al ,A2,A3,Bl
Al*,A2,A3,Bl
Al,A2,A3,Bl*,B2,83,84
Al
,A2,A3,Bi ,B2,B3,B4
Al*,A2,A3,A4,Bl*,B2,B3,B4
Al*,A2,A3,A4,Bl,B2,B3,84
Al ,A2,A3,A4,Bl,B2,63,84
,B2
,B2
*,B2,B3
,B2,B3
,B2,83
*,B2,B3,B4
24
Page 25
UNIT
30GT
CONTROL
STEPS
Table 4D- Capacity Control Steps, 225, 250, 280 (cant)
1G
SEQUENCE A
Compressors
r
LOADING SEQUENCE B
Compressors
250 (50 Hz)
280 (60 Hz)
250 f& Hz),
Al**
250 $;; Hz),
Al**,Bl**
*Unloaded compressor.
-/-Compressor unloader, standard.
-
““Compressor unloader, accessory
ttTwo unloaders, both unloaded
NOTE: These capacity control steps may
Al
Al
Al
,A2,Bl ,B2
Al
,A2,A3,Bl ,B2
Al ,A2,A3,Bl
Al
,A2,A3,A4,Bl ,B2,83
Al,A2,A3,A4,Bl,B2,B3,B4
AlA’Bl
Al ,Bl
Al l ,A2,Bl
Al
Al *,A2,Bl
Al
,A2,Bl ,B2
Al*,A2,A3,Bl
Al
,A2,A3,Bl ,B2
At*,A2,A3,Bl
Al
,A2,A3,Bl ,B2,B3
Al l ,A2,A3,A4,Bi ,B2,B3
Al
,A2,A3,A4,Bl ,B2,B3
Al*,A2,A3,A4,Bl,B2,83,84
Al,A2,A3,A4,Bl,B2,B3,B4
Al%
Al ,Bi*
Al ,Bl
Al *,A2,Bl*
Al ‘.A2.B-l
Al
Ai
*.A2.B1 *,B2
Al
,A2,Bl *,B2
Al
,A2,Bl ,B2
Al
*,A2,A3,Bl *,B2
Al l ,A2,A3,Bl ,B2
Al
,A2,A3,Bl ,B2
Al*,A2,A3,Bl
Al ,A2,A3,Bi
Al
,A2,A3,Bl ,B2,83
Al
*,A2,A3,A4,Bl *,B2,B3
Al
*,A2,A3,A4,Bl ,B2,83
Al
,A2,A3,A4,Bl ,B2,B3
Ai*,A2,A3,A4,Bl*,B2,B3,B4
Ai,A2,A3,A4,Bl*,B2,B3,B4
Ai,A2,A3,A4,Bl,B2,B3,B4
vary
due to lag compressor sequencing
,A2,61
Al”
,A2,Bl
Al*
,A2,Bl
,B2,B3
,I32
,B2
,B2,B3
*
*,B2,B3
*,B2,B3
AK1
Al $1
,B2
Al
,A2,Bi ,B2
Al
,A2,Bl ,B2,B3
Al ,A2,A3,Bl
Al
,A2,A3,A4,Bl ,B2,83
Al,A2,A3,A4,Bl,B2,B3,84
Al l ,Bl*,B2
Al*,A2,Bl
Al l ,A2,Bl ,B2
Al
Al *,A2,Bl
Al
,A2,Bl *,B2,B3
Al
Al*,A2,A3,Bi
Al*,A2,A3,Bl
Al
,A2,A3,Bl ,B2,B3
Al *,A2,A3,Bi*,B2,B3,B4
Al ,A2,A3,Bl*,B2,B3,B4
Al
,A2,A3,Bl ,B2,B3,B4
Al*,A2,A3,A4,Bl*,B2,B3,B4
Ai*,A2,A3,A4,Bi,B2,83,B4
Al
,A2,A3,A4,Bi ,B2,B3,B4
,B2,B3
-
-
-
-
-
-
-
-
-
-
-
-
-
Bi*
A&*
Al ‘,Bl
Al
,Bi
Al ,Bi
*,B2
Al
,Bl ,B2
*,B2
,A2,Bl ,B2
*,B2,B3
,A2,Bl ,B2,63
*,B2,B3
,B2,B3
25
Page 26
Head Pressure Control
-
The microprocessor controls the condenser fans in order to maintain the lowest condensing temperature possible, thus the highest unit efficiency.
Instead of using the conventional head pressure control methods, the fans are controlled by the position of the EXV and
suction superheat.
As the condensing temperature drops, the EXV opens to
maintain the proper suction superheat. Once the EXV is
As the condensing temperature rises, the EXV closes to
maintain the proper suction superheat. Once the EXV has
closed to 39.5% open (300 steps open), a fan stage is added
after 2 minutes.
During start-up, all the condenser fans are started when
the condensing temperature reaches 95 F (35 C) to prevent
excessive discharge pressure during pulldown. See Table 5
for condenser fan sequence of operation.
fully open, if the condensing temperature continues to drop,
the suction superheat begins to rise. Once the suction super-
heat is greater than 40 F (22.2 C), a fan stage is removed
after 2 minutes,
Table 5- Condenser Fan Sequence
FAN ARRANGEMENTFAN NUMBER(S)
30GN040-050
30GN060,070
30GN080,090
30GNl00,110 (and associated modular units)
30GN130-170
WWER
.
-_----
(and associated modular units)
II
1
2
3
4
I
5
6
1
2FC-81
3FC-A2
4
5,
7,
6, 8
3, 4, 5, 6, 7, aFC-A2,
5 7
6,
8
FAN CONTACTOR
WI
FC-Al
FC-Bi
FC-A2
FGB2
FC-Al
FGB2
FC-Al
FC-Al
F&B2Microprocessor
FC-AS, FGB3
FC-A3
FGB2, FC-B3Microprocessor
FC-AlCompressor Al
FC-BlCompressor Bl
,
CONTROLLED BY
Compressor Al
Compressor Bl
First Stage
Microprocessor
Second Stage
I
MicrODrOceSSOr
Compressor Al
I
Compressor Bi
First Stage
Microprocessor
Second Stage
Microprocessor
Compressor Al
Compressor Bi
Compressor Al
Compressor Bl
First Stage
Second Stage
Compressor
Third Stage
30GN190,210
*Control box.
(and associated modular units)
I
5,
7I
6. 8
3,
9
4,
10
1,
3, 9, 11FC-A2,
2, 4, 10, 12
I
26
FC-A2, FC-A3
FC-Al
FC-Bi
FC-A2
FC-B2
FGA3
FGB2,
FC-B3
Compressor Al
I
Comwessor Bl
I
Frist Stage
Microprocessor
Second Stage
Microprocessor
Page 27
Table 5 -Condenser Fan Sequence
(cant)
FAN ARRANGEMENT
30GT225
30GT250 (60 Hz)
30GT250 (50 Hz) AND 30GT280
L
‘: i
/
/;
k.
w
*Control box.
tPower box.
FAN NUMBER(S)FAN
7, 8
9, 10
5,
6
11, 12
1,
2,
3, 4
13, 14, 15, 16
1,
2, 3, 4, 5, 6FC-2, FC-3
11,
12, f3,
14, 15, 16
7, 8, 10
9, 17, 18
5,
6
11, 12, 19
1,
2, 3, 4,
14, 15, 16, 20
1,
2, 3, 4, 5, 6, 11, 12, 13,
14, 15, 16,
II, 12, 19,20FC-5
1,
14, 15, 16, 21, 22FC-3,
1, 2, 3, 4, 5, 6, 11, 12, 13,
14, 15, 16, 19, 20, 21, 22FC-5,
13,
19, 20
7, 8, 10FC-1
9,
17, 18
5,
6
2, 3, 4, 13,
C~;;jACToR
FC-1
FC-4Compressor
FC-2
FC-5Microprocessor
FC-3
FC-6
FC-5, FC-6
FC-1
FC-4
FC-2
FC-5Microprocessor
FC-3, FC-6,
FC-;&F6c;3kF;-5,
-3 -
FC-4Compressor Bl
FC-2
FC-6, FC-7Microprocessor
FC-2, FC-3, FC-4,Third Stage
FC-6, FC-7
CONTROLLED BY
Compressor Al
First Stage
Second Stage
Microprocessor
Third Stage
Microprocessor
Compressor
Compressor Bl
First Stage
FC-7Microprocessor
Second Stage
Third Stage
Microprocessor
Compressor Al
First Stage
Microprocessor
Second Stage
Microprocessor
61
Al
Pumpout
is started or stopped, that circuit goes through a
When the lead compressor in each circuit
-
pumpout
cycle to purge the cooler and refrigerant suction lines of
refrigerant.
The
pumpout
cycle starts immediately upon starting the
lead compressor and continues until the saturated suction
temperature is 10” F (5.5” C) below the saturated suction
temperature at start-up, is
10”
F (5.5” C) below the cooler
leaving fluid temperature, or reaches a saturated suction temperature of -15 F (-26 C). No
pumpout
is necessary if the
saturated suction temperature is below -15 F (-26 C). At
this point, the EXV starts to open and continues to open
gradually to provide a controlled start-up to prevent liquid
flood-back to the compressor.
At shutdown, the
urated suction temperature for that circuit is 10” F (5.5” C)
below the saturated suction temperature when
initiated, or saturated suction temperature reaches -15 F
(-26 C). At that point, the compressor shuts down and the
EXV continues to move until fully closed.
pumpout
cycle continues until the sat-
pumpout
is
27
Page 28
Keypad and Display Module (Also Called HSIO
or LID)
the operator to communicate with the processor. It is used
-
The only function of this module is to allow
The default display is displayed every 2 seconds if there
has been no manual input from the keypad for 10 minutes.
To return to automatic display, enter
to enter configurations and set points and to read data, perform tests, and set schedules. This device consists of a keypad with 6 function keys, 5 operative keys, 12 numeric keys
(0 to 9, 0, and -), and an alphanumeric g-character LCD
(liquid crystal display). See
Fig+
3. See Table 6 for
Table 6
FUNCTION
key usage.
ACCESSING FUNCTIONS AND SUBFUNCTIONS - See
Tables 6 - 8. Table 7 shows the 6 functions (identified by
name) and the subfunctions (identified by number).
OPERATIVE
-
Keypad and Display Module Usage
KEYS
STAT
0
HIST
q
SRVC
0
EST
El
CHD
El
SET
q
KEYS
EXPN
El
CLA
El
cl
c
cl
ENTR
q
STATUS - For displaying diagnostic codes and
current operating information about the machine.
HISTORY - For displaying run time, cycles and
previous alarms.
SERVICE - For entering specific unit configura-
tion information.
TEST - For checking inputs and outputs for
proper operation.
SCHEDULE - For entering occupied/unoccupied
schedules for unit operation
SET POINT - For entering operating set points
and day/time information.
EXPAND - For displaying a non-abbreviated expansion of the display
CLEAR- For clearing the screen of all displays
t
UP ARROW - For returning to previous display
position,
DOWN ARROW- For advancing to next display
position.
ENTER- For entering data
A
~~~~
at any time.
USE
USE
Fig. 3 -Keypad and Display Module
SUMMARY DISPLAY -When keypad has not been used
for 10 minutes, display automatically switches to the rotating summary display. This display has 4 parts, listed below, which appear in continuous rotating sequence.
DISPLAY1 EXPANSION
TUE
15:45
CLOCK ON
COOL
1
2 ALARMS 1 2 ALARMS DETECTED
TODAY IS TUE, TIME IS 1545
UNIT IS ON VIA CLOCK SCHEDULE
NUMBER OF STAGES IS 1
I
(3:45
PM)
AUTOMATIC DISPLAY OPERATION/DEFAULT DISPLAY - In this mode, the keypad displays the current time
(24”hour
format), current operating modes, cooling capac-
ity stages, and total number of alarms.
MODE X
COOL x
KEYPAD OPERATING INSTRUCTIONS (Refer to
Table 9.)
1.
White keys on left side of keypad are shown and oper-
ated in these instructions according to the following example: keypad entry m
H
means press the q , then
the white key marked H .
2. The standard display uses abbreviations. Expanded information scrolls through the display whenever
q
key
is pressed.
3. All functions are made up of a group of subfunctions.
To enter a subfunction, first press subfunction number
desired. Then press the function key in which the subfunction resides. To move within that subfunction, press
the
q
or
m
arrow. For example, a
mpl
enters
the Temperature Information subfunction.
4. At any time, another subfunction may be entered by entering the subfunction number, then the function key.
5. Prior to starting unit, check leaving fluid set point for
correct setting. Refer to Set Point Function section on
page 39.
6. Depending on system configuration, all displays may not
be shown. All displays are shown unless marked with
the following symbol.
*Must be configured.
For additional unit start-up procedures, see separate In-
stallation, Start-Up and Service Instructions supplied with
unit.
DOW
K
-
Day of Week
-
Hour(s)
-
Minute(s)
28
Page 29
su6FUNFT’oN
1
2Alarm
3
4
5
6
7
8Analog
9
10
II
Table
Status
STAT
0
Automatic
Display
Display
;g;faQeratiw)
plWe$Y
Set Points
(Current Operating)
Temperatures
Pressures
Inputs
outputs
--
Functions and Subfunctions
7
-
FUNCTIONS
Test
outputs
TEST
cl
Schedule
CHD
ICI
OverrideLog On and
Service
SRVC
cl
Log Off
CompressorsClock Set
Version
and Unloaders(Software)
Period
-
-
1
Period 2Field
Factory
Configuration
ConfigurationTime
-
-
-
-
-
Period 3
Period 4
Period 5
Period 6
Period 7
Period 8
HOLIDAYS
Service
Configuration
-
-
-
-
--
-
HistorySet Point
HIST
0
SET
cl
Run TimeSet Points
(Chiller Fluid)
StartsReset
AlarmDemand Limit
History
-
Set Points
Set Points
Date and
--
--
-z
-
--
-
--
Table 8- Accessing Functions and Subfunctions
OPERATION
To access a function, press
subfunction no and function
name key. Display shows
function
To move to other elements,
scroll up or down using arrow
@+oup.
keys. NOTE: These
displays do not show if
control is not configured
for reset.
When the last element in a
subfunction has been dis-
played, the first element is
repeated.
To move to next subfunction
it is not necessary to use
subfunction number Press
function name key to
Vance
display through all
subfunctions within a
function and then back
to the first
To move to another function,
either depress function name
key for desired function
(display shows the first
subfunction),
Access a’ipecif ic sub-
function by’using the subfunction number and the
function name kev.
sub-
ad-
I
I
ENTRYRESPONSE
p--jH
4
El
+
cl
l-i-l
I
4
cl
+
cl
+
cl
SET
cl
SET
cl
SET
III
STAT
III
I
KEYPAD
DISPLAY
RESET
CRST2xx
CREF2xx
CRSTi
xx
CREFlxx
RESET
CRST2xx
DEMAND
TIME
SET
X ALARMS
I
DESCRIPTION
Reset Set Points
Cooling Maximum
-
Reset xx
Cooling Maximum
Reference xx
Cooling Minimum
Reference xx
Cooling Minimum
Reference xx
Reset Set
(ZtZi:SxxMaxirnurn
Demand Set
Points
Current Time and
Day of Week
Unit Set Points
Rotating Display
Capacity Stages
29
Page 30
Table 9- Keypad Directory
KEYPAD ENTRY
STATUS
DISPLAY 1
Refer to Automatic Display Operation on page 28
COMMENT
2 ALARMS
3 MODES
4 STAGE
I
X ALARMS
ALARM X
ALARM X
ALARM X
ALARM X
ALARM X
X MODES
MODE X
MODE X
MODE X
MODE X
STAGE
STAGE X
CAPT X
CAPA X
CAP0 X
LMT X*
Number of Tripped Alarms
Displays Tripped Alarms
>
Number of Modes in Effect
Displays Mode in Effect
>
Capacity Staging Information
Number of Requested Stages
Percent of Total Capacity
Percent Circuit A Capacity
Percent Circuit 6 Capacity
Demand Limit Set Point
;,;
6
5 SET POINT
6 TEMPERATURE
LOAD X*
CIRA X
CIRB X
SMZ X
SET POINT
SP
x
MSP X
TWX
TEMPS
EWTX
LWT X
SCTA X
SSTA X
CTA X
SHA X
Load Limit Set Point
Circuit A Compressor Relay Status
Circuit B Compressor Relay Status
Load/Unload Factor for Compressors
Factor = 1 Unloader Factor = 0 6
Fluid Set Point Information
Set Point
Modified Set Point = Set Point + Reset
Cooler Leaving Fluid Temperature
Temperature Information
Cooler Entering Fluid Temperature
Cooler Leaving Fluid Temperature
Circuit A Saturated Condenser Temperature
Circuit A Saturated Suction Temperature
Compressor Al Suction Temperature
Circuit A Suction Superheat
LEGEND
-
CCN
EXV- Electronic Expansion Valve
MOP- Maximum Operating Pressure
Carrier Comfort Network
*Must be configured
j-If applicable
30
Page 31
SUBFUNCTION
6
TEMPERATURE (cant)cl
KEYPADENTRY
I
Table 9
4
-
Keypad Directory (cant)
STATUS (cant)
DISPLAY
SCTB X
COMMENT
Circuit B Saturated Condenser Temperature
7 PRESSURE
8 ANALOG
t
q
cl
4
cl
4
0 4
SSTB X
CTB X
SHB X
RST X*
PRESSURE
DPA X
SPA X
xxxx
OPA X
DPB X
SPB X
xxxx
OPB X
ANALOG
REF X
Circuit B Saturated Suction Temperature
Compressor Bl Suction Temperature
Circuit B Suction Superheat
Reset Temperature
Refrigerant System Pressure (psig)
Circuit A Discharge Pressure
Circuit A Suction Pressure
Circuit A Discharge/Suction
Circuit A Oil Pressure Differential
Circuit B Discharge Pressure
Circuit 8 Suction Pressure
Circuit B Discharge/Suction
Circuit B Oil Pressure Differential
Status of Analog Inputs
Transducer Supply Voltage
9
1NPUTS
LMT X*
RST X*
INPUT
SPW
x*
DLI
X*
DL2 X*
Demand 4-20 mA Signal
Reset 4-20 mA Signal
Status of Switch Inputs
Dual Set Point Switch
Demand Limit Switch 1
Demand Limit Switch 2
31
Page 32
SUBFUNCTION
Table 9- Keypad Directory (cant)
STATUS (cant)
DISPLAY
COMMENT
10 OUTPUTS
OUTPUTS
ALMR X
FRAI X
FRA2 X
FRBI X
FRB2 X
CHWP X*
ULAI X
ULA2 X*
ULBI X
ULB2 X*
EXVA X
EXVB X
HGBA X*
HGBB X
MMA X*
Status of Outputs
Alarm Relay K3
Fan Relay Kl
Fan Relay K2
Fan Relay K4
Fan Relay K5
Cooler Water Pump Relay K6
Unloader Al
Unloader
Unloader Bl
Unloader
EXVA Percent Open
EXVB Percent Open
Hot Gas Bypass Relay Circuit A
Hot Gas Bypass Relay Circuit B
Motormaster@
t
A2T
t
B2T
A Output Percent
MMB X
Motormaster B Output Percent
TEST
To use Test function, LOCAL/ENABLE-STOP-CCN switch must be in STOP position To operate a test, scroll to desired test
Then, press m to start test. Press m to stop test.
SUBFUNCTION
1
OUTPUTS
KEYPAD ENTRY
DISPLAY
OUTPUTS
8 8 8.8.8 8.8.8
ALMR X
FRAI X
FRA2 X
FRBl X
FRl32
X
CHWP X*
EXVA X
EXVB X
HGBRA X*
Test Outputs
Display Check
Energize Alarm Relay K3
Energize Fan Relay Al Kl
Energize Fan Relay A2 K2
Energize Fan Relay Bi K4
Energize Fan Relay 82 K5
Energize Cooler Water Pump K6
Enter Desired EXVA Position
Enter Desired
Energize Hot Gas Bypass Relay A
EXVB
COMMENT
Position
HGBRB X*
MMA X*
MMB X*
32
Energize Hot Gas 8ypass Relay B
Enter Desired
Enter Desired Motormaster B Output Signal
Motormaster@
A Output Signal
Page 33
-
Table 9
Keypad Directory (cant)
TEST (cant)
During compressor test, compressors start and run for
10 seconds. Compressor service valves and liquid line
valves must be open. Energize crankcase heaters 24 hours
prior to performing compressor tests.
SUBFUNCTION
2 COMPRESSORS AND
UNLOADERS
KEYPAD ENTRY
DISPLAY
COMP
CPA1 X
CPA2 X*
CPA3 X*
CPA4 X*
CPBl X
CPB2
x*
CPB3 X*
CPB4 X*
ULAl X
ULA2 X*
ULBl X
ULB2 X*
COMMENT
Compressor and Unloader Test
Test Compressor Al
Test Compressor
Test Compressor A3t
Test Compressor A4t
Test Compressor Bl
Test Compressor B2t
Test Compressor
Test Compressor
Energize Unloader Al
Energize Unloader
Energize Unloader Bl
Energize Unloader B2t
A2T
B3T
B4T
T
A2T
t
SCHEDULE
The Schedule function key
unoccupied shutdown or unoccupied setback depending on the cooling set point control configuration. The Schedule function
described is for clock 1, which is the internal clock. Password required for all subfunctions except override.
SUBFUNCTION
1 OVERRIDE
For example, to extend current occupied mode for 3 hrs, press:
2 CLOCK SELECT
LEGEND
-
Carrier Comfort Network
-
~~”
MOP
Electronic Expansion Valve
-
Maximum Operating Pressure
CHD
is used to configure the occupancy schedule The clock select subfunction can be used for
El
1
KEYPAD ENTRY
ppii-j
/qzq
I
I
DISPLAY
OVRD XNumber of Override Hrs (0 - 4 Hrs)
OVRD 3
CLOCK XXType of Clock Control
*Must be configured
tlf
applicable.
I
Extended Occupied Time
0 = No Clock, 1 = Clock 1 (Internal)
COMMENT
33
Page 34
-
Table 9
Keypad Directory
SCHEDULE (cant)
DISPLAY
COMMENT
To toggle between inputs (Yes/No) Press:
4 PERIOD 2
5 PERIOD 3 . . . 9 PERIOD 71MH1 Period3 . . . Period 7 Time Schedule. m H (
10 PERIOD 8
Fi Fi
/qH
1 Period 2 Time Schedule1 PERIOD 2
~~( Period 8 Time Schedule1 PERIOD 8
PERIOD
OCC
HH.MM
UN0
HH.MM
MON X
TUE X
WED x
THU X
FRl X
SAT X
SUN X
HOL X
~~$~
y
1
Period 1 Time Schedule
Occupied Time
Unoccupied Time
Monday Flag
Tuesday Flag
Wednesday Flag
Thursday Flag
Friday Flag
Saturday Flag
Sunday Flag
Holiday Flag
’
11 HOLIDAYS
New = Unassigned Holiday Date
For example: To enter July 4th holiday press: 07 04 01
operation, refer to Schedule Function section on page 45.
q
. Display shows Jul 04 For further information on the Schedule function and its
HOLIDAYS
DAT
MM.DD
DAT
MM.DD
NN
SERVICE
To view and modify configurations, the password must be entered under the log on subfunction.
SUBFUNCTION
1 LOG ON AND LOG OFF
At this time, configurations may be modified. When finished viewing and/or modifying configur
2 VERSION
KEYPAD ENTRYDISPLAYCOMMENT
( mmmma
r;lH
p-&q
0
EHTR
0
+
LOG ON
(LOGGEDONILoggedOn
LOG OFF
EXIT LOG
VERSION
Define Calendar Holidays
Holiday Date 1
Holiday Date 30
Enter Password/Disable Password Protection
rtions,
log out as follows:
Disable Password Protection
Logged Off/Enable Password Protection
Software Information
See legend on page 30
4
cl
+
0
xxxxxxxx
34
Version No. of Software (CESRXX)
X
Language Options
Page 35
Table 9- Keypad Directory (cant)
SERVICE (cord)
The next 3 subfunctions provide the ability to modify configurations Refer to separate Installation, Start-Up, and Service Instructions
supplied with unit for further information on changing configurations.
F.-’
To change a configuration, enter the new configuration and press4 while on the correct configuration.
CCN Element Address
CCN Bus Number
CCN Baud Rate
Cooler Fluid Select
Display Unit Select
Display Language Select
No Circuit A Unloaders
No. Circuit B Unloaders
Hot Gas Bypass Select
Loading Sequence Select
Lead/Lag Sequence Select
Oil Pressure Switch Select
Head Pressure Control Method
Motormaster@
Cooling Set Point Control Select
Cooling Reset Control Select
External Reset Sensor Select
Demand Limit Control Select
Ramp Load Select
Cooler Pump Interlock Select
Cooler Pump Control Select
Service Configurations
Configuration Code 7
Configuration Code 8
Refrigerant
Pressure Transducer Select
Oil Transducer Set Point
Low Pressure Set Point
Fan Staging Select
EXV Superheat Set Point
EXV MOP Set Point
Select
35
Page 36
Table 9
-
Keypad Directory (cant)
SUBFUNCTION
1 RUN TIME
2 STARTS
3 ALARM HISTORY
KEYPAD ENTRY
r;lm
+
0
4
cl
b
cl
121
lHlST1
+
cl
+
cl
+
cl
I
I 3 I lH4
DISPLAYCOMMENT
RUN TIME
HR XTotal Hrs Unit Has a Comp Operating
HRA X
HRB X
STARTS
CY xCycles from Stage 0 to Stage
CYA XCircuit A Starts
CYB XCircuit B Starts
1ALRMHIST
ALARM X
ALARM X
ALARM X
ALARM X
ALARM X
1 Last 5 Alarms
SET POINT
To read a set point, go to proper subfunction and read desired set point To
LOCAL/ENABLE-STOP-CCN switch must be in LOCAL or STOP position,
SUBFUNCTIONKEYPAD ENTRY
1 SET POINTS
2 RESET SET POINTS
DISPLAY
SET
POINT
CSPl
x
CSP2
x
HSPA X
HSPB X
CRAMP X
t
RESET
CRST2 X*
CREF2 X*
CRSTI
X*
CREFI X*
Run Time lnformation
Circuit A Run Time
Circuit B Run Time
Starts Information
1
Alarm Description
>
J
change
a set
point, enter
Jnit Set Point
Chiller Fluid Set Point 1
Chiller Fluid Set Point 2
Head
Pressure Set Point Circuit A
Head Pressure Set Point Circuit B
Pulldown
Limit
Reset Set Points
Cooling Max Reset
Max Reset Occurs at X mA or Degree
Cooling Minimum Reset
Min Reset Occurs at X mA or Degree
new set
COMMENT
point
value, then
press
ENTR
cl
3 DEMAND SET POINTS
4 DATE AND TIME
DEMAND
DLSl X*
DLS2 X*
DMAX X*
RMAX X*
DMIN
X*
RMIN
X*
SHED
X”
DATE.TIME
DAY HR.MIN
MM.DD YR
Demand Set Points
Demand Switch 1 Set Point
Demand Switch 2 Set Point
4-20 mA Maximum Demand Limit
Max Demand Limit Occurs at X
4-20
mA Minimum Demand Limit
Minimum Demand Limit Occurs at X
CCN
Loadshed
Date, Time and Day of Week
Day 1 = Mon, 2 = Tues
Hours are displayed in
Month.Day.Year.
point between entries. Each entry must be two numbers.
Amount
24-hr
When entering date, enter a decimal
mA
mA
7
= Sun
time. Decimal point serves as colon.
36
Page 37
STATUS FUNCTION - This function shows the rotating
display, current status of alarm (diagnostic) codes, capacity
stages, operating modes, chilled water set point, all measured system temperatures and pressures, superheat values,
pressure switch positions, analog inputs, and switch inputs.
These subfunctions are defined on pages 37 and 38.
i
m Fi
(Rotating Display)
m Fi
(Alarms) - Alarms are messages that one or more
faults have been detected. Each fault is assigned a code number which is reported with the alarm. See Table 10 for code
definitions. The codes indicate failures that cause the unit
to shut down, terminate an option (such as reset) or result
in the use of a default value as set point.
Up to 5 alarm codes can be stored at once. To view them
in sequence, press
mm
to enter the alarm displays
and then press q to move to the individual alarm dis-
plays. Press
ing of the code scrolls across the screen. See Example
q
after a code has been displayed. The mean-
1
Example 1- Reading Alarm Codes
K EYPAD
ENTRY
p-jq
+
cl
EXPH
0
4
Ll
EXPN
0
DISPLAY
RESPONSE
‘MvoEo;2;;5
0 STAGES
2 ALARMS
2 ALARMS
ALARM 9
COOLER LEAVING
FLUID THERMISTOR
FAILURE
ALARM 42
COOLER FREEZE
PROTECTION
COMMENTS
Keypad has not been used for
at least 10 minutes. Alternating
summary display appears on
screen
2 alarms detected
First alarm code
Explanation of alarm code
Second alarm code Cooler
freeze protection
Explanation of alarm code
When a diagnostic (alarm) code is stored in the display
and the machine automatically resets, the code is deleted.
Codes for safeties which do not automatically reset are not
deleted until the problem is corrected and the machine is
switched to STOP, then back to LOCAL/ENABLE or CCN.
mbi
(Modes) - The operating mode codes are displayed to indicate the operating status of the unit at a given
time. See Table 10.
Table 10- Operationat and Mode Display Codes
The operating modes are displayed by name or code number, to indicate the operating status of the unit at a given
time. The modes are:
OFF switch in OFF position
Unit is off due to CCN network command. LOCAL/
ENABLE-STOP-CCN switch is in CCN position.
I
Unit is off due to internal clock schedule. LOCAL/
ENABLE-STOP-CCN switch is in LOCAL position.
Unit is on. LOCAL/ENABLE-STOP-CCN switch is
in LOCAL position If external ON/OFF switch is used,
it will be in ON bosition.
Unit is on due to CCN command LOCAUENABLE-
STOP-CCN switch is in CCN position.
Unit is on due to internal clock schedule or
I
CCN switch is in LOCAL position.
Dual set point is in effect In this mode, unit continues to run in unoccupied condition, but leaving wa-
ter set point is automatically increased to a higher
level (CSP2 set
Temperature reset is in effect. In this mode, unit is
using temperature reset to adjust leaving water set
I
point upward, and unit is currently controlling to the
modified set point. The set point can be modified
based on return water, outdoor-air temperature or
space temperature
Demand limit is in effect. This indicates that capacity of unit is being limited by demand limit con-
trol option Because of this limitation, unit may
not be able to produce the desired leaving water
temperature
Load limit is in effect. This indicates that capacity of
a system of units is being limited by a CCN
shed command Due to this limitation, unit may
not be able to produce the desired leaving water
temperature.
Not
aoalicable.
II
Ramp load (pulldown) limiting is in effect. In this mode,
the
r&e
at which leaving water temperature is dropped
is limited to a predetermined value to prevent compressor overloading, See CRAMP set point in the
SET function in Table 9 The pulldown limit can be
modified, if desired, to any rate from 2 F to 2 F
( lo
to lo Q/minute
Timed override is in effect This is a 1 to 4 hour
temporary override of the programmed schedule,
forcing unit to occupied mode Override can be im-
plemented with unit under LOCAL or CCN control
Override expires after each use
Low cooler suction protection is in effect In this mode,
circuit capacity is not allowed to increase if cooler
saturated suction temperature is
’
water or 30” F (16” C) for brine or more below
ing fluid temperature, and saturated suction temperature is less than 32 F (0’ C). If these conditions
persist beyond 10 minutes, circuit is shut down and
fault code 44 or 45 is displayed.
Point
is in SET function)
20”
F
(11”
occu-
load-
C) for
leav-
To enter the MODES subfunction, depress
use the q key to determine if more than one mode ap-
plies. See Example 2 to read current mode with expansion.
37
MFI
and
Page 38
Example 2
KEYPADIDISPLAY
ENTRYRESPONSE
p-lH
4
cl
+
cl
Reading Current Operating Modes
-
COMMENTS
TUE
15:45
LOCAL ON
COOL 1
0 ALARMS
2 MODES
LOCAL ON
MODE 8
I
Keypad has not been used for at
least 10 minutes Rotating summary
display appears on screen
There are 2 modes currently in effect
Unit is on by chiller on/off switch
Temperature reset is in effect
m H
analog inputs, if any. Enter
transducer supply voltage, 4-20 mA reset signal can be dis-
played. This is useful for problem diagnosis prior to using
the test function.
m bi
(Inputs)- This subfunction displays status
(ON/OFF) of input switch where applicable. Status of dual
set point switch, and demand limit switches 1 and 2 can be
displayed. This is useful for problem diagnosis prior to using the test function.
~~
l-ii 1;;;;1
(Stage)
This subfunction displays the capac-
-
ity stage number. See Tables 4A-4D for compressor loading sequence. To enter the STAGE subfunction, press
p--&qand use the q to display the stage number.
Additional m provides the following information:
Percent of total unit capacity being utilized.
Percent of each circuit capacity being utilized.
tus of alarm relay, all fan relays, and chilled water pump
relay. It also displays ON/OFF status of compressor unloaders (if used). The position of each EXV (in percent open)
can be displayed.
TEST FUNCTION - The test function operates the diagnostic program. To initiate test function, the LOCAL/
ENABLE-STOP-CCN switch must be in STOP position.
To reach a particular test, enter its subfunction number,
then scroll to desired test by pressing the ( key. Press
Demand limit set point in effect (can be any value between 0% and 100%).
Load limit set point in effect. This is a CCN function for
controlling operation of multiple units between 0% and
100% of total capacity of all units combined.
Status of each compressor relay. When a compressor is
on, the number of that compressor is displayed. If a compressor is off, a 0 is displayed. For example: In a given
circuit, if compressors 1 and 3 are running, and 2 and 4
are not running, 0301 is displayed for that circuit.
Load/Unload factor for compressors. This factor is an indication of when a step of capacity is added or subtracted. Its value can range from slightly less than -1 .O
to slightly more than + 1 .O. When load/unload factor
reaches + 1.0, a compressor is added. When the load/
unload factor reaches -1 .O, a compressor is subtracted.
If compressor unloaders are used, at
-.6
a compressor is
unloaded and at +.6, a compressor is loaded up.
mF[
(Set Point) - This subfunction displays leaving
B
exit a test. Pressing the
vances system to next test, whether current test is operating
or has timed out, Once in the next step, you may start
test by pressing H or advance past it by pressing
While the unit is in test, you may leave test function and
access another display or function by pressing appropriate
keys. However, a component that is operating when an-
other function is accessed remains operating. You must
re-enter test function and press the ) key to shut down
the component. Components with a timed operating limit
time out normally even if another function is accessed.
Keypad entry
following checks by using m :
water temperature and leaving chilled water set point. If
unit is programmed for dual set point, the chilled water set
point currently in effect (either occupied or unoccupied) is
displayed. If reset is in effect, the unit operates to the mod-
ified chilled water set point. This means the leaving water
temperature may not equal the chilled water set point The
modified chilled water set point can also be displayed in the
Status function. To enter the set point subfunction, de-
press
mb[
and use the
q
to display modified leaving
compressor unloader
chilled water set point followed by leaving water set point
and actual cooler leaving fluid temperature.
During compressor operational tests, compressor starts
and runs for 10 seconds. Compressor service valves must
F[ F[
(Temperature) - The temperature subfunction displays the readings at temperature sensing thermistors.
be open. Energize crankcase heaters 24 hours prior to
performing compressor tests.
To read a temperature, enter Fi Fi , then scroll to de-
practice to also check all inputs and outputs accessible
m
sired temperature using the
order of readouts.
key. See Table 9 for the
through the status function. These are located at F\ F[ ,
m H,
flH
(Pressure) - This subfunction displays suction,
discharge and net oil pressure at lead compressor of each
for 10 minutes, unit automatically leaves test function and
resumes rotating display. See Example 3.
circuit of unit.
(Analog Inputs) - This subfunction displays
m Fi
, then use the
q
. The
(Outputs) - This function displays ON/OFF sta-
to start a test. Press
riF[
q
q
or
q
or H to terminate or
key after a test has started ad-
allows the operator to make the
I)I
.
LID display check. Propezisplay is 8.8.8.8.8.8.8.8 .
Operation of remote alarm.
Operation of condenser fans.
Operation of chilled water pump.
Operation of EXVs. To drive EXV fully open, enter
m m m
ter u (0% open).
Keypad entry
(100% open). To drive EXV fully closed,
-mH I
accesses the compressor and.
operational
tests.
en-
c
Since test function checks only certain outputs, it is good
and
mm
(see Table 9). If keypad is not used
38
Page 39
Example 3 -Using Test Function
KEYPAD DISPLAY
ENTRY RESPONSE
NOTE: Once a compressor has been run using the
is not allowed to run again for 30 seconds.
cl
+
I
COMP
CPA 1 OFF
CPA 1 ON
CPA 1 OFF
CPA 2 OFF
Factory/field test of compressors
subfunction of test function
Circuit A, Compressor 1A test
Pressing
when the compressor should be running
the display shows CPA1 on
If the test is allowed to time out (10 seconds) the display will show
Pressing the down arrow key advances
the system to Circuit A, compressor 2 test
HISTORY FUNCTION - Keystrokes
COMMENTS
ENTR
starts the test:
mb]
CPA1
off
EST
function, it
El
and sub-
sequent [ keystrokes display total unit run time and total
run time for each circuit.
.
Keystrokesm
m
and subsequent m keystrokes dis-
play total unit starts and the total starts for each circuit.
KeystrokesFi
and subsequent
b[
q
keystrokes dis-
play the last 5 alarms along with a description of each alarm.
SET POINT FUNCTION - Set points are entered through
the keypad. Set points can be changed within the upper and
lower limits, which are fixed. The ranges are listed
below.
Chilled Water Set Point
Water:
38 to 70 F (3.3 to 21 C)
Brine:
15 to 70 F (-9.4 to 21 C)
Pulldown Set Point
0.2 to 2.0 F (0.11 to 1.1 C)/min.
Reset Set Points
Maximum Reset Range:
0”
to 20” F (0” to 11” C)
Maximum Reset Reference Range:
Return Fluid Reset 0” to 20” F
(0” to 11” C)
External Temperature Reset 20 to 125 F
(-6.6 to 51.6 C)
External Signal Reset 4 to 20 mA
Minimum Reset Reference Range:
Return Fluid Reset 0” to 20” F
(0” to 11” C)
External Temperature Reset 20 to 125 F
(-6.6 to 51.6 C)
External Signal Reset 4 to 20 mA
Demand Limit Set Points
Switch Input:
Step 1 - 0 to 100% Capacity Reduction
Step 2 - 0 to 100% Capacity Reduction
External Signal:
Maximum Demand Limit 4 to 20 mA
Minimum Demand Limit 4 to 20 mA
Set points are grouped in subfunctions as follows:
m Fl
Displays chiller water and cooling ramp set points.
a. The first value shown is the occupied chilled water
set point.
b. The next value displayed depends on how the sched-
ule function has been programmed. (See pages 45-
47.) If dual set point has been selected, the next set
point after m has been pressed is the unoccupied
chilled water set point. If single set point or inactive
schedule has been selected in the schedule function,
then when
q
is pressed, the display shows the
modified chilled water set point.
c. The final value displayed when the
q
is pressed
is the cooling ramp loading rate. This is the maximum rate at which the leaving chilled water is allowed to drop, and can be field set from 0.2 to 2.0 F
(.
11” to 1.1” C)/minute. This value is not displayed
unless the function is enabled (see Adjustable Field
Configurations on page 45).
Reading and
Channinrr
Set Points - Example 4 shows how
to read and change the chilled water set point. Other set
points can be changed by following the same procedure.
Refer to Table 9 for the sequence of display of set points in
each subfunction.
Example 4 -Reading and Changing
Chilled Water Set Point
KEYPAD
ENTRY
Temperature Reset Based on Return Water
DISPLAY
RESPONSE
SET POINT
CSPl 44.0
CSPI 420
CSP2
44.0
CSP2
50.0
RESET
COMMENTS
System set points
Present occupied chilled water
set point is 44 0 F
~~~~~~~h~!$w~cupied
chilled water set point is 42 0 F
Present unoccupied chilled water
set point is 44.0 F
Press the Fi ri
shows new unoccupied chilled
water set point is 50.0 F
Displays the maximum reset and
minimum reset set points The
minimum and maximum reference
reset set points can also be
displayed.
These set points are not
accessible when reset type has
been configured for NONE in
the service function
F[
Display
TemDerature -
The control system is capable of providing leaving water
temperature reset based on return water temperature. Because the temperature difference between leaving water temperature and return water temperature is a measure of the
building load, return water temperature reset is essentially
an average building load reset method.
Under normal operation, the chiller maintairis a constant
leaving water temperature approximately equal to chilled
water set point. As building load drops from 100% down to
O%,
entering cooler water temperature drops in proportion
to load. Thus, temperature drop across the cooler drops from
a typical 10 F (5.5 C) at full load to a theoretical 0” F (0” C)
at no load. See Fig. 4.
At partial load, leaving chilled water temperature may be
lower than required. If this is allowed to increase (reset),
the efficiency of the chiller increases. Amount of reset can
be defined as a function of cooler temperature drop, as shown
in Fig. 4. This is a simple linear function that requires 4
pieces of input data for the set function:
39
Page 40
I.
Maximum Reset Amount (CRST2) - allowable range
0” to 20” F (0” to 11” C). This is maximum amount leaving chilled water set point is to be increased.
2. Maximum Reset Reference (CREF2) - allowable range
0” to 20” F (0” to 11” C). This is the cooler temperature
drop at which reset reaches its maximum value.
3. Minimum Reset Amount (CRSTl) - allowable range
0”
to 20” F (0” to 1 I” C). This is minimum amount leaving chilled water set point is to be increased when reset
is initiated.
4. Minimum Reset Reference (CREFl) - allowable range
0” to 20” F (0” to 11” C). This is the cooler temperature
drop at which reset is at its minimum value. (Reset begins here .)
NOTE: Reset set points are not accessible unless the reset
function is enabled first. This is done as a field configuration. Select one of the 3 choices for type of reset: Return
Fluid Reset, External Temperature Reset, or 4-20 mA Ex-
ternal Signal (with a loop isolator) Reset.
If dual set point control is enabled (see Field Wiring sec-
tion on page 7 1), the amount of reset is applied to which-
ever set point is in effect at the time.
Example 5 demonstrates how to activate reset. Example
6 demonstrates how to change the type of reset. Assume
that reset is to be based on return water temperature, the
desired reset range is to be 2” to 10” F (1” to 5.5” C) and
full load is a 10” F (5.5” C) drop across the cooler. See
Fig. 4.
Activating reset based on external temperature or
4-20 mA signal is done the same way, except the reference
set point range is 20” to 125” F (-6.6” to 5 1.6” C), or 4 to
20 mA depending on which method was selected at the field
configuration step.
Example 5- Using Return Water
Temperature Reset
KEYPADDISPLAY
ENTRY
RESPONSE
FLD CFG
CSPTYP X
CRTYP 0
CRTYP 1
SET POINT
CPSl 44.0
CPSl 45 6
RESET
CRST2 0 0
CRST2 10 0
CREF2 0.0
CREF2 1.0
CRSTI
0 0
CRSTI 2.0
CREFl 0.0
CREFl 8 0
COMMENTS
Field configuration
subfunction of
service function
Scroll past single/dual
Display shows no reset
type has been selected
Return water temperature
is selected and activated
System set points
Present occupied chilled
water set point
Enter new chilled water
set point
Reset set points
F;li;g
0
Cooling maximum reset
is 10 F
Cooling maximum reset
reference is 0” F
Cooling maximum reset
reference is 1 F
Cooling minimum reset
is 0” F
Cooling minimum reset
is 2 F
Cooling minimum reset
reference is 0” F
Cooling minimum reset
reference is 8 F
maximum reset
f73c=)
IO
9
8
7
18
16
23456789
RESET REFERENCE TEMPERATURE (COOLER EWT-LWT)
Fig.4-
--/
35.3
MIN RESET REFERENCE(CREF
Cooling Return Water Reset
I ) q 13
100
80
60
0
IO
40
Page 41
Temperature Reset Based on External Temperature - If de-
sired, temperature reset can be based on an external temperature, such as space or outdoor-air temperature. This re-
quires a thermistor (TlO, Part No. 30GB660002) located in
the space or outdoor air and wired to terminals as follows
To change type of reset, first log on as shown in
Table 11. Also refer to Set Point Function section, page 39,
for information on entering reset set points using reset
feature.
(also see Field Wiring section on page 71):
4 in/4 out Module - 57-15 and J7-16.
At the field configuration step, select external tempera-
ture reset by entering
q
when CRTYP 0 appears. Then
enter set points as described previously in Example 5. See
Fig. 5.
Temperature Reset Based on 4-20 mA Signal- If desired,
temperature reset can be based on a 4-20 mA signal. For
proper connections,
refer to Field Wiring section on page
71 and Fig. 6.
At the field configuration step, select 4-20 mA reset by
entering
q
when CRTYP 0 appears. Then enter set points
as described previously in Example 5. See Fig. 7,
Demand Limit, 2-Stage Switch Control - This control has
been designed to accept demand limit signals from a build-
ing load shedding control. The demand limit function provides for 2 capacity steps. The keypad is used to set the 2
demand limit set points, which range from 100 to 0% of
capacity. Capacity steps are controlled by 2 field-supplied
relay contacts connected to the designated chiller terminals.
(See Field Wiring section on page 7 1 and Fig. 6.)
Example 6 -Changing Reset Type
KEYPADDISPLAY
ENTRY
RESPONSE
FLD CFG
CSPTYP 0
CRTYP 0
CRTYP 1
CRTYP 2
CRTYP 3
CRTYP 0Reset is deactivated
COMMENTS
Field configuration
subfunction of
service function
Scroll past single cooling
set point
No reset has been
selected
Return water temperature
reset is selected and
activated
Reset type is changed to
space or outdoor-air
temperature reset and
activated
Reset type is changed to
4-20 mA signal reset
and activated
10 -
Y-
8-
?-
2-
I -
O-
18
16
8
6
RESET REFERENCE TEMPERATURE
Fig. 5
Cooling External Temperature Reset
-
(OUTDOOR
AIR 1OR
SPACE TEMP
41
Page 42
POINT NUMBER OF
FIRST CHANNEL
n
Q
EKE
LIMIT
(ALARM CODE 312
(MODE 91
(MODE 71
RFt!EF
(ALARM
COOE
21)
(MODE
El
Fig 6
PWR
I
In AOt
d
=
RET
DO+
z
“1
rAO+
’
--e-------1-
__-----a
_------
__----
___---c---
---mm-
__----.
---se
---
----
- - - - - _ - - - - - - -
4 nw/4
OUJJU
A
--
-
B
c
D
I-
d
H
4
5
‘-+p--------
COMM -Communications Bus
----__e-
f
__----a-
301
LB---------
4 IN/4 OUT Options Module Wiring for Reset, Demand Limit, an! Dual Set Point
-
----
__----
--
PWR
SW
NOTE: For specific connection points,
see Fig. 24 - 29.
-
-
LEGEND
Power
Switch
Table 11- Service Functions
To view and modify configurations, the password must
be entered under the log on subfunction.
I
KEY FAD
DISPLAY
PASSWORD
LOGGED ON Logged On
COMMENT
Enter Password/
Disable Password
SUB-
FUNCTIONENTRY
NOTE: Configurations may be modified at this time. When
finished viewing and/or modifying configurations, log out
as follows:
LOGGED ON
LOG OFF
EXIT
LOG
VERSION
xxxxxxxx
X
Disable Password
Protection
Logged Off/
Enable Password
Protection
Software
Information
Version No
of Software
Language Options
To use Demand Limit, first enable loadshed, then enter
demand limit set points. See Example 7A. Closing the first
stage demand limit contact puts unit on the first demand
limit level, that is, the unit does not exceed the percentage
of capacity entered as demand limit stage 1. Closing contacts on second-stage demand limit relay prevents unit from
exceeding capacity entered as demand limit stage 2. The
demand limit stage that is set to the lowest demand takes
priority if both demand limit inputs are closed.
The demand limit function must be enabled in order to
function and may be turned off when its operation is not
desired. The demand limit relays can, in off condition, remain connected without affecting machine operation.
-Demand Limit, 4-20 mA Signal - The controls can also
accept a 4-20 mA signal for load shedding. Input for the
signal are terminals shown below:
Externally powered (loop isolator required)
Positive lead to
57-5 -
4 In/4 Out Module
Negative lead to 57-6 - 4 In/4 Out Module
Internally powered
Positive lead to J7-6 - 4 In/4 Out Module
Negative lead to 57-7 - 4 In/4 Out Module
See Field Wiring section on page 71 and Fig. 6.
At field configuration step, select 4-20 mA
loadshed
by
entering q when the LSTYP 0 display appears. See
Example 7B. Then enter set points as follows. In this ex-
ample, set points are coordinates of the demand limit curve
shown in Fig. 8.
42
Page 43
16
8
6
0
02468
RESET REFERENCE SIGNAL (4 -20 MA INPUT)
Fig. 7 -4-20 mA Cooling Temperature Reset
IO
1214
16
18
20
Example 7A- Using Demand Limit
(First Log On as Shown in Table 11)
KEYPAD
ENTRY
DISPLAY
RESPONSE
FLD CFG
ERTYP
0
LSTYP
0
LSTYP 1
DEMAND
DLSl 100
DLSl 60
DLS2 100
DLS2 40
To Disable Demand Limit:
KEYPAD
ENTRY
DISPLAY
RESPONSE
FLD CFG
ERTYP 0
LSTYP 1
LSTYP 0
COMMENTS
Field configuration sub-
function of service function
Scroll past other elements
in the subfunction
Loadshed
Loadshed
for 2-stage switch control
Demand Limit set points
subfunction of set point
function
Loadshed
at 100%
Loadshed
Loadshed
at 100%
Loadshed
Field configuration sub-
function of servicefunction
Scroll past other elements
in the subfunction
I
Loadshed
2-stage switch control
Loadshed
is not enabled
is now enabled
1 currently set
reset to 60%
2 currently set
2 reset to 40%
COMMENTS
is enabled for
is now disabled
Example 7B
Using Demand Limit (4-20 mA)
-
(First Log On As Shown in Table 11)
KEYPAD
ENTRY
ppiq
t
0
Cl
ENTR
q ‘n
MH
DISPLAY
RESPONSE
FLD CFG
ERTYP 0
LSTYP
0
LSTYP 2
DEMAND
DMAX 100
DMAX 90
RMAX 20
RMAX 15
DMIN
0
DMIN
20
RMIN
4
RMlN
6
COMMENTS
Field configuration subfunction
of service function
Scroll past other elements in
the subfunction
Loadshed
Loadshed
for 4-20 mA signal control
Demand Limit set points
Maximum demand limit is 100%
Maximum demand limit is 90%
Maximum demand limit
reference is 20
Maximum demand limit
reference is 15
Minimum demand limit is 0%
Minimum demand limit is 20%
Minimum demand limit
reference is 4
Minimum demand limit
reference is 6
is not enabled
is now enabled
mA
mA
mA
mA
NOTE: Select 3 for Carrier comfort Network (CCN) load limiting
Select 4 for CCN demand limiting.
43
Page 44
MAX DEMAND
DEMAND LlMlT SIGNAL (4-20 MA INPUT)
KIMAX)
= 90
Fig. 8 -4-20 mA Demand Limiting
Reading and Changing Time Displav - Time is entered
and displayed in 24-hour time. The day of the week is
en-
tered as a number.
1 = Mon, 2 = Tue, 7 = Sun, etc.
m Kev
is used as the colon when entering time. See
I
Ex-
ample 8.
Example 8
Setting Time of Day and
-
Day of Week
KEYPADDISPLAY
ENTRY
RESPONSE
TIME
MON 1600
TUE 13 05
JAN 01 90
APR 15 90
SERVICE FUNCTION - This function allows the
cian
to view and input configuration data. Factory
COMMENTS
Time display subfunction of set point
function
Current setting is
Monday, 4:00 p.m
New setting of
Tuesday, I:05 p m
is entered
and displayed
Current date is
Jan. 1, 1990
New setting
April
15,
is entered
and displayed
1990
techni-
config-
uration data, field configuration data and service configuration data may be viewed or entered through the keypad
and display module. See Table 9 for a complete listing of
configurable items. Whenever a processor module is replaced in the field, the complete list of configuration codes
must be entered.
Logging On/Longing
Off - The service function is
pass-
word protected. Therefore, to gain entry to this function,
this password must be entered. Pressing
allows the technician to view, change or enter
ml rim m
configura-
tion codes. To log off, perform the following keystrokes:
m biF]H
~ The service function is once again
pass-
word protected.
Software Information - Fi
F/VI
displays the version
number of the software that resides in the processor module. Press
m
a second time to display the language op-
tions that are available in the field configuration group.
The
r;lF[
and
firI
bf
-mF[
t
allows entry into
Table 11
Factorv
s
Configuration Codes
2
SRVC
su uric ions are summarized in
the factory configuration subfunction. Under this subfunction, there are 6 groups of configuration codes that are downloaded at the factory. Each group is made up of 8 digits. If
processor module is replaced in the field, these 6 groups of
configuration codes must be entered through the keypad and
display module. Factory configuration codes (groups 1 through
6) that apply to the particular Flotronic’” II chiller being
serviced are found on a label diagram located inside the
control box cover. See Table 12 for a summary of factory
configuration subfunction keystrokes.
44
Page 45
Table 12
Factory Configuration Keystrokes
-
To change a configuration enter the new configuration
and press
3 FACTORY
Adiustable Field Configurations - After logging on, press
ri H
ation of the chiller to be customized to meet the particular
needs of the application. The chiller comes from the factory
Each item should be checked to determine which configuration alternative best meets the needs of a particular application. See Table 13 for factory loaded configuration codes
q
SUB-
FUNCTION
CFG
5 %FE
while on the correct configuration.
DISPLAYCOMMENTS
FACT CFG
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
xxxxxxxx
SRV CFG
xxxxxxxx
xxxxxxxx
FACTORY
CONFlGURATlON
CODES
CJz;;g;ration
Configuration
Code 3
Configuration
Code 4
SERVICE
CONW;;T’ON
to enter subfunction. The subfunction allows oper-
2 = Set Point Control for
3 = Set Point Control for
4 = Set Point Control for
and alternative configurations.
If processor module is replaced, the replacement module
is preloaded with factory default configuration codes. Each
configuration code must be checked and, if necessary, reconfigured to meet needs of the application. See
Table 13 for pre-loaded service replacement configuration
codes.
Service Configuration Codes - Press
r;lH
to enter the
service configuration subfunction. The first 2 items under
this subfunction are 2 groups (8 digits each) of configuration codes that are downloaded at the factory. If processor
module is replaced in the field, the 2 groups of configura-
tion codes must be entered through the keypad and display
module. The 2 groups of configuration codes (groups 7 and
8) that apply to the unit being serviced can be found on a
label diagram inside the control box cover. See Table 12
for keystroke information to enter configuration codes 7
and 8.
SCHEDULE FUNCTION - This function provides a means
to automatically switch chiller from an occupied mode to
an unoccupied mode, When using schedule function, chilled
water pump relay must be used to switch chilled water pump
on and off. Connections for chilled water pump relay are:
TB3-3 and TB3-4 (040-210 and associated modular units)
or TB5-3 and TB5-4 (225, 250, and 280 units). The chilled
water pump relay starts chilled water pump but compres-
Cooling Set Point
Control Select
0 = Single Set Point Control
1 = External Switch
2 = Clock Controlled
Cooling Reset
0 = No Reset
i
= Return Fluid Reset
2 = External Temperature
3 = 4-20 mA Controlled
External Reset Sensor Select
0 = Thermistor Connected to
1 = Obtained Through CCN
Demand Limit Control Select
0 = No Demand Limiting
1 = Two External Switch Input
2 = External 4-20 mA
3 = CCN Load Limiting
4 = CCN Loadshed Interface
Ramo Load Select
~P@os~dol~ntrol)
1 = Enabled
Cooler Pump Interlock Select
0 = No Interlock
1 = With Interlock
Cooler Pump Control Select
0 = Not Controlled
1 = ON/OFF Controlled
sors do not run until remote chilled water pump interlock
contacts are between TB6-1 and TB4-2 on 30GN040-210
and associated modular units, or between TB5-1 and TB5-2
EE
*And associated modular units
on 3OGT225, 250, and 280 Flotronic” units are closed and
leaving chilled water temperature is above set point. If a
remote chilled water pump interlock is not used, the first
compressor starts (upon a call for cooling) approximately
one minute after chilled water pump is turned on.
-
Table 13
FIELD CONFlGURATlON
ITEM AND CODES
[3.3 to 21 C] Set Point)
f-9 to 21 C] Set Point)
Both Circuits
Circuit A; EXV Control
for Circuit B
Circuit B; EXV Control
for Circuit A
Controlled Set Point
Set Point
Reset
Reset
Options Module
(Multi-Unit)
LEGEND
-
Carrier Comfort Network
-
Electronic Expansion Valve
Adjustable Field Configurations
SI
Select
Control
-
Input
FACTORY
CONFF$ikTlON
001001
000000
9600
= Standard Models
I = Brine Models
0
I =
30GN190-HO*;
30GT225,250,280
=
30GN040-170*
)
=
30GN040-070,
190-210';
30GT225,250,280
=
30GN080-170*
0
0
0
0
0
0
SERVICE
IEPLACEMENT
CODE
9600
1
0
1
0
0
0
1
1
0
0
1
0
0
0
0
0
0
0
45
Page 46
The schedule function can be programmed for inactive,
single set point, or dual set point operation.
When schedule is configured for inactive, chilled water
pump relay remains energized continuously but is not used
since chiller is usually controlled by remote chilled water
pump interlock contacts.
When unit is configured for single set point operation,
chilled water pump relay is energized whenever chiller is in
occupied mode regardless of whether chiller is running. When
chiller is in unoccupied mode, chilled water pump relay is
not energized.
When unit is configured for dual set point, chilled water
pump relay is energized continuously, in both occupied and
unoccupied modes. Occupied mode places occupied chilled
water set point into effect; unoccupied mode places unoccupied chilled water set point into effect.
The schedule consists of from one to 8 occupied time periods, set by the operator. These time periods can be flagged
to be in effect or not in effect on each day of the week. The
day begins at 00
.OO
and ends at 24.00. The machine is in
unoccupied mode unless a scheduled time period is in ef-
fect, If an occupied period is to extend past midnight, it
must be programmed in the following manner: occupied pe-
riod must end at
period must be programmed to begin at
24:OO
hours (midnight); a new occupied
0O:OO
hours.
NOTE: This is true only if the occupied period starts at
0O:OO
(midnight). If the occupied period starts at a time
other than midnight, then the occupied period must end at
0O:OO
hours (midnight) and new occupied period must be
programmed to start at
0O:OO
in order for the chiller to stay
in the occupied mode past midnight.
The time schedule can be overridden to keep unit in occupied mode for one, 2, 3 or 4 hours on a one-time basis.
See Example 9.
All subfunctions of schedule function are password protected except the override subfunction, 17 b[ .
word entry into subfunctions
f;l b[
through m m
Pass-
b[,
is done through service function. See page 44, logging on/
logging off.
Figure 9 shows a schedule for an office building with the
chiller operating on a single set point schedule. The schedule is based on building occupancy with a 3-hour off-peak
cool-down period from midnight to 3 a.m. following the
weekend shutdown. To learn how this sample schedule would
be programmed, see Example 9.
NOTE: This schedule was designed to illustrate the pro-
gramming of the schedule function and is not intended as a
recommended schedule for chiller operation.
Example 9
-
Using the Schedule Function
DISPLAY
OVRD 0
OVRD 3
OVRO 0
CLOCK 0
CLOCK 1
CLOCK 65
PERIOD 1
UN0
MON NO
MON YES
TUE YES
TUE NO
PERIOD 2
occ 00 00
occ 7 00
UN0
UN0
MON NO
MON YES
TUE NO
TUE YES
WED YES
WED NO
No schedule override
in effect
3 hours override in effect
Override cancelled
Schedule function is inactive
Schedule function is enabled
through local unit clock
Schedule function is enabled
throuah CCN clock 65
Define schedule period 1
Start of occupied time
For this example, first
period should stat-t here
/;tntnnr$ht)
Start of unoccupied time
(end of period) For this
00.00
&xampl&
end at 3:00 a m.
Period 1 ends at 3:00 a m
Monday is now flagged no
for oeriod 1 To out
into’ effect on
Monday must be flagged
Yes
Monday is now fla
For this example, period
is to be in effect on Monday
only All other days must
checked to be sure that thev
are flagged no. If any day
flagged yes, change to no
Tuesday is now flagged
no for period
Define schedule period 2
Start of occupied time
C$uo$e;;me will start
Start of unoccupied time
(end of period) For this
00.00
example, period 2 should
end at 18:00 (6:00 p m )
Period 2 ends at 18:OO
18 00
(6:00 p m )
Monday is now flagged no
for period 2 To put period 2
into effect on Monday,
Monday must be flagged yes
Monday is now flagged for
period 2 to be in effect
Tuesay is now flagged no
for period 2 To put period 2
into effect on Tuesday,
Tuesday must be flagged
yes
Tuesday is now flagged for
period 2 to be in effect
For this example, period 2
is to be in effect only on
Monday and Tuesday
All other days must be
checked to be sure that
they are flagged no. If
a day is flagged yes,
change to no
Wednesday is now flagged
no for period 2
so no entry
period 1 should
M&day,
1
oeriod I
ged for
aperiod 1 to be in e
ect
1
be
ii
46
CCN
Carrier Comfort Network
-
Example 9 continued next page.
Page 47
Example 9 -Using the Schedule Function (cant)
KEENYTPRAYD
PROGRAMMING PERIOD 3:
DISPLAY
I
PERIOD 3
occ 00
occ 7 00
UN0 00 00
UN0
21 30
MON NO
TUE NO
WED NO
WED YES
THUR NO
FRI NO
SAT NO
SUN NO
a0
COMMENT
Define schedule
period 3
Start of occupied
lime
Tyo$e;;rne
Start of unoccupied time
(end of period 3). For this
example, period 3 should
end at
Period 3 ends at
(9:30 p m )
Check to be sure that
Monday and Tuesday are
flagged for period 3
Wednesday is flagged
no, change to yes
Wednesday is now
flagged yes for period 3
Check to be sure that all
other days are flagged no
will start
21:30 (9:30
p m )
22:30
Example 10
ENTER
Holiday Schedule Function
-
DISPLAY
HOLIDAY
JAN01 02 (Includes Jan
APR17
MAY21 01 (Includes May 21 st)
JUL03 01 (Includes July 3rd)
JULO4 01 (Includes July 4th)
SEP07 01 (Includes Sep 7th)
NOV26
DEC24 02 (Includes
DECBO
NEW
MAY25 01 (Includes May 25th)
NEW
NEW
and 2nd)
01 (Includes April 17th)
02 (Includes Nov 26th
and 27th)
and 25th)
02 (includes
and 3lst)
Dee
Dee
Ist
24th
30th
Period 4 and 5 can be programmed in the same manner,
flagging Thursday and Friday yes for period 4 and Saturday
yes for period 5 a For this example, periods 6, 7, and 8 are
not used: they should be programmed OCC 00.00, UN0
00.00.
NOTE: When a day is flagged yes for 2 overlapping peri-
NEW indicates a holiday that has not been assigned yet.
ods, occupied time will take precedence over unoccupied
time. Occupied times can overlap in the schedule with no
consequence.
To extend an occupied mode beyond its normal termination for a one-time schedule override, program as shown
below:
Holidav Schedule - Press
171 ri b[
to schedule up to
30 holiday periods. All holidays are entered with numerical
values. First, the month (01 to 12), then the day (01 to 3
l),
then the duration of the holiday period in days.
Examples: July 24 is 07.04.01.
Dee
25 - 26 is 12.25.02
If any of the 30 holiday periods are not used, the display
shows NEW.
See Example 10.
oo-
IO -
I3 14
I5
I6
I7
18
19
20
21
I
23-
4-
5-
6t-
89-
II
I2
-
-
-
-
-
-
-
NEW
NEW
NEW (30TH
YEC
-
-
SAT
IlJh
PERIOD
1
I
HOLlDAY)
#30-G3 v
‘EYo[
‘ERIO
3
-
-
m
OCCUPIED
UNOCCUPIED
I
Fig. 9
-
Sample Time Schedule
-
47
Page 48
TROUBLESHOOTING
The
FlotronicTY
technicians in troubleshooting a Flotronic II Chiller. By us-
II control has many features to aid the
13. Cooler entering or leaving fluid thermistor failure
14. Low transducer supply voltage
15. Loss of communications between processor module and
ing keypad and display module and status function, actual
operating conditions of the chiller are displayed while unit
is running. Test function allows proper operation of compressors, compressor unloaders, fans,
EXVs
and other com-
ponents to be checked while chiller is stopped. Service function
displays how configurable items are configured. If an operating fault is detected, an alarm is generated and an
alarm code(s) is displayed under the subfunction m
I;;;;]
,
along with an explanation of the fault. Up to 5 current alarm
codes are stored. For checking specific items, see Table 9.
Checking Display Codes
-
To determine how ma-
chine has been programmed to operate, check diagnostic
16. Low refrigerant pressure
Single Circuit Stoppage
can be caused by the following:
1
2. Open contacts in lead compressor high-pressure switch
3. Low refrigerant pressure
4. Thermistor failure
5. Transducer failure
6. Ground fault in lead compressor indicator (indicator is
information (( w ) and operating mode displays (/ Fi ).
If no
dismay annears,
ules
section+onlpage
follows:
1.
Note all alarm codes displayed, F\ bi .
2. Note all operating mode codes displayed,
3. Note leaving chilled water temperature set point in effect and current leaving water temperature,
If machine is running, compare the “in effect” leaving
water temperature set point with current water temperature. Remember, if reset is in effect, the values may be
different because machine is operating to the modified
chilled water set point, If current temperature is equal to
set point, but set point is not the one desired, remember
that if dual set point has been selected in the schedule
function, there are 2 set points to which the machine can
be operating. Check the programming of schedule function
to
see if occupied or unoccupied set point should be
follow procedures in Control Mod-
64. If display is working, continue as
MH
.
MFI
.
7. High suction superheat
8. Low suction superheat
9. Lead compressor circuit breaker
10. Ground fault for any circuit compressor (130-210,225,
Lag Compressor Stoppage
page can be caused by the following:
1,
Open contacts in high-pressure switch
2. Compressor ground fault (indicator is field-supplied on
040-060, 070 [60 Hz], 080- 110, and associated modular
units)
3. Compressor circuit breaker trip
4. Not required to run to meet cooling load requirement
in effect.
other control modules
-
Single circuit stoppage
Low oil pressure in lead compressor
field-supplied on 040-060, 070 [60 Hz], 080- 110, and
associated modular units)
trip+
Stoppage of one
circuit by a safety device action does not affect other
circuit. When a safety device trips on a lead compressor, circuit is shut down immediately and EXV closes.
250, 280, and associated modular units).
-
Lag compressor stop-
Unit Shutoff
-
To shut unit off, move LOCAL/
ENABLE-STOP-CCN Switch to STOP position. Any refrigeration circuit operating at this time continues to complete the pumpout cycle. Lag compressors stop immediately,
and lead compressors run to complete
Complete Unit Stoppage
page can be caused by any of the following conditions:
1. Cooling load satisfied
pumpout.
-
Complete unit stop-
1
2. Remote ON/OFF contacts open
3. Programmed schedule
4. Emergency stop command from CCN
5. General power failure
6. Blown fuse in control power feed disconnect
7. Open control circuit fuse
8. LOCAL/ENABLE-STOP-CCN switch moved to STOP
position
9. Freeze protection trip
10. Low flow protection trip
11. Open contacts in chilled water flow switch (optional)
12. Open contacts in any auxiliary interlock. Terminals that
are jumpered from factory are in series with control
switch. Opening the circuit between these terminals places
unit in stop mode, similar to moving the control switch
to STOP position. Unit cannot start if these contacts
are open. If they open while unit is running, unit pumps
down and stops.
If stoppage occurs more than once as a result of any of
the above safety devices, determine and correct the cause
before attempting another restart.
Restart Procedure
After cause for stoppage has been
-
corrected, restart is either automatic or manual, depending
on fault. Manual reset requires that LOCAL/ENABLE-
STOP-CCN switch be moved to STOP position, then back
to original operating position. Some typical fault conditions
are described below. For a complete list of fault conditions,
codes, and reset type, see Table 14.
POWER FAILURE EXTERNAL TO THE UNIT - Unit
restarts automatically when power is restored.
Typical Stoppage Faults and Reset Types
Chilled Water, Low Flow
Chilled Water, Low Temperature
Chilled Water Pump Interlock
Control Circuit Fuse Blown
High-Pressure Switch Open
Low Refrigerant Pressure
Low Oil Pressure
Discharne Gas Thermostat Open
Manual reset
Auto reset first time, manual
if repeat
Manual reset
Unit restarts automatically when
power is restored
Manual reset
Auto reset first time, then manual
if within same day
Manual reset
Manual reset
48
Page 49
Alarm Codes
-
Following is a detailed description of
each alarm code error and possible cause. Manual reset of
an alarm is accomplished by moving LOCAWENABLE-
STOP-CCN Switch to STOP position, then back to LOCAL or CCN position. See Table 14 for listing of each alarm
code.
If DSIO-LV or -EXV relay module control relay feed-
back switch or signal is sensed as open during operation of
a compressor, microprocessor detects this and stops com-
Table 14 -Alarm Codes
pressor, energizes alarm light, and displays a code of I,2,
3, 4, 5, 6, 7, or 8 depending on the compressor. Compressor locks off; to reset, use manual reset method.
If lead compressor in a circuit shuts down, the other compressors in the circuit stop and lock off. Only the alarm
mode for lead compressor is displayed.
The microprocessor is also programmed to indicate compressor failure if feedback terminal on DSIO-LV or -EXV
53
terminal strip receives voltage when compressor is not
supposed to be on.
DISPLAY
No Alarms Exist
0
Compressor Al failure
1
2, 3, 4
6,
ES
7,
Compressor A2, A3, A4 failureCompressor shut down
Compressor Bl failure
5
Compressor B2;83,84 failure
8
Leaving water thermistor failureUnit shut down
9
Entering water thermistor failureUnit shut down
10
Compressor Al sensor failure
19
Compressor Bl sensor failureCircuit B shut down
20
Reset thermistor failureNormal set point used
21
Discharge pressure transducer failure, circuit A
22
Discharge pressure transducer failure, circuit B
23
Suction pressure transducer failure, circuit ACircuit A shut down
24
Suction pressure transducer failure, circuit B
25
Oil pressure transducer failure, circuit A
26
Oil pressure transducer failure, circuit B
27
Transducer supply voltage low
28
29
30
31
32
33
34
35
36
37
38
39
40
41
Interlock switch oaenUnit shut down
4-20 mA reset input failureNormal set point used
4-20 mA
Loss of communication with DSIO-LVUnit shut down
Loss of communication with DSIO-EXV
Loss of communication with 4 In/4 Out moduleUnit shut down
Not used
Low refrigerant pressure circuit A
Low refrigerant pressure circuit B
oil pressure circuit ACircuit A shut down
oil pressure circuit BCircuit B shut downNo
42Cooler freeze protectionUnit shut down
Low cooler water flow
43
Low suction temperature circuit A
44
Low suction temperature circuit B
45
High suction superheat circuit ACircuit A shut down
46
High suction superheat circuit BCircuit B shut down
47
Low suction superheat circuit A
48
Low suction superheat circuit B
49
Illegal configuration
50
Initial configuration requiredUnit cannot start
51
Emergency stop by CCN commandUnit shut down
52
-
Compressor Protection Control Module
-
Power Supply
LEGEND
DESCRIPTION
demand limit failure
ACTION TAKEN
BY CONTROL
Circuit A shut down
Circuit B shut down
Compressor shut down
Circuit A shut down
Circuit A shut down
Circuit B shut down
Circuit B shut down
Circuit A shut down
Circuit B shut down
Unit shut down
Demand limit ignored
Unit shut down
I
Unit shut down
Circuit A shut down
after 10 minutes
Circuit B shut down
afler 10 minutes
Circuit A shut down
Circuit 6 shut down
Unit cannot start
*Reset automatic first time, manual if repeated same day
CKT
-
-
PUMPDOWN
-
No
Yes
No
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
No
No
No
NO
No
No
No
No
No
No
Yes
-
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
-
-
Yes
--
Manual
Manual
Manual
Manual
Auto
Auto
Auto
Auto
Auto
Auto.
Auto
Auto
Auto.
Auto.
Auto
AutoUnit voltage low or PSI faulty
Manual
Auto
Auto
Auto.
Auto
Auto
thermostat trip, or wiring error
I
Thermistor or transducer failure
I
*
*
Manual
ManualFaultv EXV, transducer, or thermistor.
Manual
Manual
Manual
Manual
Manual
ManualILow charge, faulty EXV or
Manual
Manual
Manual
Manual
Manual
CCN
PROBABLE CAUSE
High-pressure switch trip, discharge gas
CPCS Ground Fault Protection
or wiring error.
Transducer failure or wiring error
Chilled water pump inoperative
Wiring error
or improper
or faulty module
address code
-
Low refrigerant charge, plugged filter
drier, faulty EXV
Low refri erant charge, plugged filter
drier.I”fau tv EXV
~,
3
Faulty EXV, transducer, or thermistor
Low oil level, circuit breaker trip,
faulty EXV, crankcase heater,
or Pressure Transducer
Low oil level, circuit breaker trip,
fautty EXV, crankcase heater,
or
oressure
transducer
Low water flow or faulty thermistor
Chilled water pump failure
or faulty thermistor
Faulty EXV or thermistor
Faulty EXV or thermistor
thermistor, or plugged filter drier
Low charge, faulty EXV or
thermistor, or plugged filter drier.
Faulty EXV or thermistor
Faultv EXV or thermistor
Configuration error
Configuration omitted
Network command.
49
Page 50
Possible causes of failure:
1.
High-Pressure Switch Open - High-pressure switch for
each compressor is wired in series with 24-v power that
energizes compressor control relay. If high-pressure switch
opens during operation, compressor stops. This is
detected by microprocessor through the feedback
terminals.
3
d.
DSIO-LV or DSIO-EXV Module Failure - If a DSIO-LV
relay module relay fails open or closed, microprocessor
detects this, locks compressor off and indicates an error.
3.
Wiring Errors - If a wiring error exists causing CPCS,
CR, or feedback switch not to function properly, microprocessor indicates an error.
4.
Processor (PSIO) Failure - If hardware that monitors
feedback switch fails, or processor fails to energize relay module relay to on, an error may be indicated.
NOTE: The control does not detect circuit breaker failures. If a circuit breaker trips on lead compressor in a
circuit, a low oil pressure failure is indicated. On the
other compressors, no failure is indicated.
5.
Ground Fault Module on 130-2 10, 225, 250, 280, and
associated modular units (CGFA or CGFB) Open - Module contacts are in lead compressor circuits, but ground
fault could be in any compressor in affected circuit.
Ground fault of any 040-l 10 and associated modular unit
compressor (field-supplied accessory on 040-060 and 070,
60 Hz units; standard on 070, 50 Hz and 80-l 10 and as-
sociated modular units) will cause a trip.
6.
Checkout Procedure - Shut off main power to unit. Turn
on control power,
tion
MFi
to proper compressor number (i.e., failure
code 5 is compressor
then step through subfunc-
Bl).
Next, energize the step. If
step works correctly, then failure code is caused by:
l
HPS (high-pressure switch) open
l Misplaced feedback wire from
0
Ground wire and 24-v feeds reversed on one or more
points on
53
Compressor Alarm Circuit
54
and J5 terminals
-
For compressor Al
alarm circuit, processor closes contacts between 54 terminals 2 and 3 to start compressor. See Fig.
10A -
10D. Safeties shown to left of 54 must be closed in order for power to
reach compressor control relay, and the feedback input terminals on J3.
Failure of power to terminal 1 on 53, when contacts be-
tween 2 and 3 on J4 should be closed, causes a code 1
alarm.
Terminal 2 on 53 is the other leg of the compressor Al
feedback channel. It is connected to the 24-v common.
NOTE: Similar connections for each compressor can be
fol-
lowed on the unit wiring diagrams located on the unit.
Code 9Leaving water thermistor failure
Code 10Entering water thermistor failure
If temperature measured by these thermistors is outside
range of -40 to 240 F (-40 to 116 C), unit shuts down after
going through a normal
pumpout.
Reset is automatic if temperature returns to the acceptable range, and unit start-up
follows normal sequence. Cause of fault is usually a bad
thermistor, wiring error, or loose connection.
On units with thermistors, if temperature measured by
these thermistors is outside the range of -40 to 240 F (-40
to 116 C), affected circuit shuts down after going through a
normal
pumpout.
Other circuit continues to run. Reset is
automatic if temperature returns to the acceptable range,
and circuit start-up follows normal sequence. Cause of
this-
fault is usually a bad thermistor, wiring error or loose
connection.
On units with transducers, if the saturated suction tem-
perature is greater than the leaving water temperature plus
10” F (5.5 C) for more than 5 minutes, the affected circuit
shuts down (after going through normal pumpout). The reset is automatic if the saturated suction temperature returns
to the acceptable range and start-up follows the normal sequence. Cause of this fault is usually a bad transducer, a
wiring error, or a loose connection.
Code 21Reset thermistor failure (applies only to installa-
tions having external temperature reset)
If temperature measured by this thermistor is outside range
of 40 to 240 F (-40 to 116 C), reset function is disabled
and unit controls to normal set point. If temperature returns
to the acceptable range, reset function is automatically enabled. Cause of this fault is usually a bad thermistor, wiring error or loose connection.
Code 22
Compressor A 1 discharge pressure
transducer failure
Code 23
Compressor B 1 discharge pressure
transducer failure
Code 24
Compressor A 1 suction pressure transducer
failure
Code 25
Compressor B 1 suction pressure transducer
failure
If output voltage of any of these transducers is greater
than 5 v, affected circuit shuts down without going through
pumpout
process. Other circuit continues to run. Reset is
automatic if output voltage returns to the acceptable range,
and circuit start-up follows normal sequence. Cause of fault
is usually a bad transducer or a wiring error.
Code 28Low transducer supply voltage
If transducer supply voltage is less than 4.5 v or greater
than 5.5 v, unit shuts down without going through pumpout
process. Reset is automatic if supply voltage returns to the
acceptable range, and circuit start-up follows normal sequence. Cause of fault is usually a faulty transformer, or
primary voltage is out of range.
The voltage supplied to the processor is polarized. When
checking for proper voltage supply, be sure to consider this
polarity. If voltage appears to be within acceptable toler-
ance, check to be sure the transformer supplying PSl is not
grounded. Grounding the supply transformer can result in
serious damage to the control system.
Code 29Chilled water pump interlock switch open
(applies only if unit is configured for use with
a chilled water pump interlock).
Code can occur under any of these conditions:
1. Interlock switch fails to close
within
one
minute after
chilled water pump starts
2. Interlock switch opens during unit operation
3. Interlock voltage is detected, but unit is not configured
for interlock
4. Interlock voltage is outside its valid range
If any of these conditions occur, all compressors are dis-
abled and, if running, shutdown occurs without
pumpout.
Chilled water pump also shuts down. Reset is manual, with
LOCAL/ENABLE-STOP-CCN switch. Most probable cause
of this fault is shutdown or failure of chilled water pump to
start. Other possibilities are improper configuration or wiring errors.
50
Page 51
Code 30Reset input failure (4 to 20
Code 31Demand limit input failure (4 to 20
mA)
mA)
These codes apply only if unit is configured for these
functions. If 4-20mA signal is less than 4 or more than
20
mA,
reset or demand limit function is disabled and unit
functions normally. If mA signal returns to the acceptable
range, function is automatically enabled.
Code 32Loss of communication with compressor
relay module (DISO-LV)
Code 33Loss of communication with EXV relay
module (DSIO-EXV)
If communication is lost with either of these modules,
unit shuts down without
pumpout.
This alarm resets auto-
matically when communication is restored. The unit starts
up normally after alarm condition is reset. Probable cause
of condition is a faulty or improperly connected plug, wiring error, or faulty module.
Loss of communication can be attributed to a grounded
transformer with a secondary voltage of 21 vat supplying
the PSIO, DSIO-LV, or 4 IN/4 OUT modules; the 12.5-vat
transformer supplying the DSIO-EXV module; or the
24-vat
transformer supplying PS 1 for the transformers. These
transformers should not be grounded, or serious damage to
controls can result. Check to be sure the transformers are
not grounded.
NOTE: If a blank PSI0 module is downloaded without be-
ing connected to the modules DSIO, this alarm is
energized.
Code 34Loss of communication with 4 In/4 Out module
This applies only if one or more of the following options
are used:
0
external temperature reset
l 4-20 mA temperature reset
l external switch controlled dual set point
l switch controlled demand limit
l 4-20 mA demand limit
l
hot gas bypass
If communication is lost with 4 IN/4 OUT module, the
unit shuts off automatically, after finishing
pumpout.
Reset
of alarm is automatic when communication is restored. Start-up
after alarm is remedied follows a normal sequence. Probable cause of condition is a faulty or improperly connected
plug, wiring error, or faulty module.
Loss of communication can be attributed to a grounded
transformer with a secondary voltage of 21 vat supplying
the PSIO, DSIO-LV, or 4 IN/4 OUT; the 12.5vat transformer supplying the DSIO-EXV module, or the
24-vat
trans-
former supplying PS 1 for the transformers. These transformers
should not be grounded, or serious damage to controls can
result. Check to be sure the transformers are not grounded.
Code 36Low refrigerant pressure, Circuit A
Code 37Low refrigerant pressure, Circuit B
If suction pressure transducer senses a pressure below set
point for more than 5 minutes at start-up or more than
2 minutes during normal operation, affected circuit shuts
down without going through the
pumpout
process. Reset is
automatic when pressure reaches 10 psig above set point if
there have been no previous occurrences of this fault on the
same day. If this is a repeat occurrence on same day, then
reset is manual, with LOCAL/ENABLE-STOP-CCN switch,
Factory configured set point is 27 psig for standard chillers
and 12 psig for brine chillers.
Possible causes of fault are low refrigerant charge, faulty
EXV, plugged filter drier, or faulty transducer.
Code 38Failure to pump out, Circuit A
Code 39Failure to pump out, Circuit B
The
pumpout
tion temperature is 10” F (5.5” C) below temperature at
process is terminated when saturated suc-
be-
ginning of
temperature or reaches a saturated suction temperature of
-15 F (-26 C). If appropriate saturated suction temperature
is not met within 3 minutes (on 2 consecutive tries}, circuit
shuts down without pumpout. Reset is manual with LOCAL/
ENABLE-STOP-CCN Switch, and start-up follows normal
sequence.
Possible causes for this alarm are a bad thermistor or trans-
ducer or a faulty EXV.
Code 40Low oil pressure, Circuit A
Code 41Low oil pressure, Circuit
If oil pressure differential is less than set point for more
than 2 minutes at start-up, or more than one minute during
normal operation, affected circuit shuts down without going through pumpout process, Reset is manual with LOCAL/
ENABLE-STOP-CCN switch, and start-up follows normal
sequence.
6 psig.
Possible causes of fault are faulty compressor, EXV, crankcase heater or transducer, refrigerant overcharge, insufficient oil charge, or tripped circuit breaker.
Code 42 Cooler freeze protection
If cooler entering or leaving water temperature is below
34 F (1.1 C) for water or more than 8” F (4.4” C) below set
point for brine, unit shuts down without
water pump continues to run if controlled by chiller controls. Reset is automatic when leaving water temperature
reaches 6” F (3” C) above set point, providing there has
been no prior occurrence of this fault the same day. If fault
has occurred previously the same day, reset is manual with
LOCAL/ENABLE-STOP-CCN switch.
Possible causes of fault are low water flow or faulty
thermistor.
Code 43 Low water flow
If any compressors are operating and entering water tem-
perature is 3” F (1.7” C) or more below leaving water tem-
perature for more than one minute, unit shuts down without
pumpout.
manual with LOCAL/ENABLE-STOP-CCN switch, and
start-up follows normal sequence.
This is a suitable method for sensing low water flow because entering water thermistor is in the cooler shell and
responds more quickly to compressor operation than the leaving water thermistor in the leaving water nozzle, Possible
causes of fault are faulty chilled water pump, control or
thermistor.
Code 44Low cooler suction temperature, Circuit A
Code 45Low cooler suction temperature, Circuit B
If saturated suction temperature is less than 32 F (0°C)
and is 20” F (11” C) for water or 30” F (16” C) for brine or
more below leaving fluid temperature, mode 14 is dis-
played. Unit continues to run, but additional compressors
are not allowed to start, If condition persists for more than
10 minutes, fault code is displayed, and unit shuts down
without
STOP-CCN switch, and start-up follows normal sequence.
Possible causes of fault are low refrigerant charge, plugged
filter drier, or a faulty EXV or thermistor.
Code 46High suction superheat, Circuit A
Code 47
If EXV is fully open, suction superheat is greater than
75 F (42 C) and saturated evaporator temperature is less
than MOP (maximum operating pressure) for more than 5
minutes, unit shuts down after normal
Reset is manual with LOCAL/ENABLE-STOP-CCN switch,
and start-up follows normal sequence.
51
pumpout,
or
10”
F (5.5” C) below leaving water
B
Factory configured differential oil pressure is
pumpout.
Chilled
Chilled water pump also shuts down. Reset is
pumpout.
Reset is manual with LOCAL/ENABLE-
High suction superheat, Circuit B
pumpout
process.
Page 52
Possible causes of fault are low refrigerant charge, plugged
filter drier, or a faulty EXV or thermistor.
Code 48Low suction superheat, Circuit A
Code 49
Low suction superheat, Circuit B
If EXV is at minimum position, suction superheat is less
than
10”
F (5.5” C) or saturated evaporator temperature is
greater than MOP (maximum operating pressure) for more
than 5 minutes, affected circuit shuts down after going through
pumpout
process, Reset is manual with LOCAL/ENABLE-
STOP-CCN switch, and start-up follows normal sequence.
Possible causes of fault are faulty EXV or thermistor.
Code 50 Illegal configuration
This fault indicates a configuration error. Unit is not allowed to start. Check all configuration data and set points
and correct any errors.
Code 51Initial configuration required
i2G7
This fault indicates factory configuration has not been
done, and unit is not allowed to start. Refer to unit wiring
label diagrams for factory configuration codes, There are 8
groups of S-digit numbers that must be entered. The first
4
groups must be entered under17 asubfunction. Groups
7 and 8 must be entered under MHsubfunction.
Enter each group, then press the H key. Use the
down arrow +0
after each group to bring up the next
empty screen. Unit should start after factory and field configurations are correctly entered.
The usual cause of this fault is replacement of the processor module. Refer to instructions accompanying the replacement module.
Code 52Emergency stop by CCN command.
Unit goes through normal shutdown when this command
is received, and goes through normal start-up when com-
mand is cancelled.
STANDARD:040-060 50 Hz
040-070 60 Hz
r
----I------
,
1 CR’S
[CPCS ’Sl
Fig.
IOA -
STANDARD:070 50 Hz
ACCESSORY: 040-060 50 Hz
040-070 60 Hz
&I
COMM
CPCS
CR
DGT
DSIO
HPS
K
PWR
SNB
TB
TRAN
U
24-V Safety Circuit Wiring (040-070)
52
LEGEND
Contactor
Circuit Breaker
Communications Bus
Compressor Protection
Control Module
Compressor Contactor Relay
Discharge Gas Thermostat (Optional)
Relay Module (Low Voltage)
High-Pressure Switch
-
Low
Vottage
Plug
Power
Snubber
-
Terminal Block
-
Transformer
-
Unloader
Page 53
TE7REO
CONTROL
I
24VAC
32MP
CN5
I
IlEO2
5CtlEliATIC
TNANZ
-
w
21V
SECONDARY
1
]TE?
DGT
DSIO
HPS
E!
PWR
GLN
U
LEGEND
-
Contactor
-
Communications Bus
-
Compressor Protection Control Module
-
Discharge Gas Thermostat (Optional)
-
Relay Module (Low Voltage)
-
l-tigh-Pressure Switch
-
Low Voltage
-
Plug
-
Power
-
Terminal Block
-
Transformer
-
Unloader
Fig.
1OB -
24-V Safety Circuit Wiring (080-110 and Associated Modular Units)
53
Page 54
P
CGF
EM”
E?
kL
SNB
TB
TRAN
U
LEGEND
Ground Fault Module
Communications Bus
Compressor Contactor Relay
Relay Module (Low Voltage)
High-Pressure Switch
Low Voltage
Plug
Snubber
Terminal Block
Transformer
Unloader
Fig.
IOC -
24-V Safety Circuit Wiring (130-210 and Associated Modular Units)
54
Page 55
c -
CGF
Z” 1
DGT
DSIO -
EXV
HPS
/$
::
;b I:
TB
LEGEND
Contactor
Ground Fault Module
-
Common
Control Relay
Discharge Gas Thermostat (Optional)
-
Relay Module (Low Voltage)
-
Electronic Expansion Valve
High-Pressure Switch
-
Low Volta
Normally
Plug
Reset Button
Terminal Board
-
8
e
losed
Fig.
IOD -
PL12-7 Poll-7
24-V Safety Circuit Wiring (225, 250, and 280 Units)
55
Page 56
1.
Electronic Expansion Valve
EXV OPERATION - These valves control the flow of liquid refrigerant into the cooler. They are operated by processor to maintain a specified superheat at lead compressor
entering gas thermistor (located between compressor motor
and cylinders). There is one EXV per circuit. See Fig. 11.
High-pressure liquid refrigerant enters valve through bottom. A series of calibrated slots are located in side of orifice assembly. As refrigerant passes through orifice, pres-
sure drops and refrigerant changes to a 2-phase condition
(liquid and vapor). To control refrigerant flow for different
operating conditions, sleeve moves up and down over ori-
fice, thereby changing orifice size. Sleeve is moved by a
linear stepper motor. Stepper motor moves in increments
and is controlled directly by processor module. As stepper
motor rotates, motion is transferred into linear movement
by lead screw. Through stepper motor and lead screws,
760 discrete steps of motion are obtained. The large number of steps and long stroke result in very accurate control
of refrigerant flow.
at appropriate terminals on EXV driver module (see
Fig. 12) as follows:
Connect positive test lead to terminal 1 on EXV driver.
Set meter for approximately 20 vdc. Enter outputs
subfunction of test function by pressing
advance to EXVA test by pressing
T;ip--p-&q*
fully open. During next several seconds connect negative test lead to pins 2, 3, 4 and 5 in succession. Voltage
should rise and fall at each pin. If it remains constant at
a voltage or at zero v, remove connector to valve and
recheck.
Press m H to close circuit A EXV. If a problem still
exists, replace EXV driver module. If voltage reading is
correct, expansion valve should be checked. Next, test
EXVB. Connect positive test lead to pin 7 and the neg-
a percent of full open. Position should change constantly
while unit operates. If a valve stops moving for any reason
(mechanical or electrical) other than a processor or ther-
2. Check EXV wiring, Check wiring to electronic expan-
mistor failure, the processor continues to attempt to open or
close the valve to correct the superheat. Once the calcu-
Fig. 12.
lated valve position reaches 60 (fully closed) for 040-210
and associated modular units, 145 (fully closed) for 225,
250, and 280 units, or 760 (fully open) it remains there. If
EXV position reading remains at 60, 145 or 760, and the
thermistors and pressure transducers are reading correctly,
the EXV is not moving. Follow EXV checkout procedure
below to determine cause.
b. Check for continuity and tight connection at all pin
c. Check plug connections at driver and at EXVs to be
The EXV is also used to limit cooler suction temperature
to 50 F (10 C). This makes it possible for chiller to start at
higher cooler water temperatures without overloading compressor. This is commonly referred to as MOP (maximum
operating pressure), and serves as a load limiting device to
EXV DRIVER
BOARD - J4
I
prevent compressor motor overloading, This MOP or load
limiting feature enables the 30G
FlotronicT’
II chillers to
operate with up to 95 F (35 C) entering water temperatures
during start-up and subsequent pull-down.
riF[
, then
q
8 times. Press
The driver should drive the circuit A EXV
ative test lead to pin 8, 9, 10, 11 in succession during
EXVB test.
sion valves from terminal strip on EXV driver. See
a. Check color coding and wire connections. Make sure
they are connected to correct terminals at driver and
EXV plug connections.
terminals.
sure EXV cables are not crossed.
ORIFICE
ASSEMBLY
(INSIDE PISTON
SLEEVE)
Fig. 11 -
STEPPER
‘DC)
Electronil c Expansion Valve (EXV)
T
EXV -Electronic Expansion Valve
Fig. 12 -EXV Cable Connections to
EXV Driver Module,
3. Check resistance of EXV motor windings. Remove plug
at 54 terminal strip and check resistance between com-
mon lead (red wire, terminal D) and remaining leads,
A, B , C, and E (see Fig. 12). Resistance should be
25 ohms
-1-
2 ohms.
Control of valve is by microprocessor. A thermistor and
a pressure transducer located in lead compressor are used
to determine superheat. The thermistor measures temperature of the superheated gas entering the compressor
cylinders. The pressure transducer measures refrigerant
pressure in the suction manifold. The microprocessor converts pressure reading to a saturation temperature. The
difference between temperature of superheated gas and
saturation temperature is the superheat.
56
DSIO (EXV)
Page 57
,/:.
::.
i .‘I
_I.:
Because the EXVs are controlled by the processor module, it is possible to track valve position. During initial
start-up, EXV is fully closed. After start-up, valve position is tracked by processor by constantly observing
amount of valve movement.
The processor keeps track of EXV position by counting
the number of open and closed steps it has sent to each
valve. It has no direct physical feedback of valve position. Whenever unit is switched from STOP to RUN po-
sition, both valves are initialized, allowing the proces-
sor to send enough closing pulses to the valve to move it
from fully open to fully closed, then reset the position
counter to zero.
4. The EXV test can be used to drive EXV to any desired
position. When EXV opens, the metering slots begin to
provide enough refrigerant for operation at these steps:
step 60 for sizes 040-210 and associated modular units,
or
145
for sizes 225, 250, and 280. This is fully closed
position when circuit is operating. The fully open posi-
tion is 760 steps.
5. Check thermistors and pressure transducers that control
EXV. Check thermistors and pressure transducers that
control processor output voltage pulses to EXVs. See
Fig, 13 for locations.
Circuit A - Thermistor T7, Suction Pressure Transducer SPTA
Circuit B - Thermistor T8, Suction Pressure Transducer SPTB
a. Use temperature subfunction of the status function
(m bi )
to determine if thermistors are reading
correctly.
b. Check thermistor calibration at known temperature
by measuring actual resistance and comparing value
measured with values listed in Tables 15 and 16.
c. Make sure thermistor leads are connected to proper
pin terminals at 57 terminal strip on processor module and that thermistor probes are located in proper
position in refrigerant circuit. See Fig. 14 and 15.
d. Use the pressure subfunction of the Status function
( m
Fl)
to determine if pressure transducers are
reading correctly. Connect a calibrated gage to lead
compressor suction or discharge pressure connection
to check transducer reading.
e. Make sure transducer leads are properly connected in
junction box and at processor board. Check trans-
former 5 output. Check voltage transducer 5 vdc +
.2 v.
When above checks have been completed, check actual operation of EXV by using procedures outlined
in Step 5.
6. Check operation of EXV.
a. Close liauid line service valve of circuit to be checked,
and run ihrough the test step ( 17 Fi ) for lead com-
nressor
in that circuit to pump down low side of
iem. Repeat test step 3
tcmes-to
ensure all refrigerant
sys-
has been pumped from low side.
NOTE: Be sure to allow compressors to run for the
full
pumpout
period.
b. Turn off compressor circuit breaker(s). Close com-
pressor discharge service valves and remove any re-
maining refrigerant from low side of system.
c. Remove screws holding top cover of EXV. Carefully
remove top cover. If EXV plug was disconnected during this process, reconnect it after cover is removed.
When removing top cover, be careful to avoid damaging motor leads.
d. Enter appropriate EXV test step for EXVA or
EXVB in the outputs subfunction of the test function
(jlF[). Press-mmriH
to initiate test. With
cover lifted off EXV valve body, observe operation
of valve motor and lead screw. The motor should
turn counterclockwise, and the lead screw should move
up out of motor hub until valve is fully open. Lead
screw movement should be smooth and uniform from
fully closed to fully open position. Press
l-+$0
check open to closed operation.
If valve is properly connected to processor and re-
ceiving correct signals, yet does not operate as de-
scribed above, valve should be replaced.
Operation of EXV valve can also be checked without
removing top cover. This method depends on oper-
ator’s skill in determining whether or not valve is
moving. To use this method, initiate EXV test and
open valve. Immediately grasp EXV valve body. As
valve drives open, a soft, smooth pulse is felt for approximately 26 seconds as valve travels from fully
closed to fully open. When valve reaches end of its
opening stroke, a hard pulse is felt momentarily. Drive
valve closed and a soft, smooth pulse is felt for the
26 seconds necessary for valve to travel from fully
open to fully closed. When valve reaches end of its
stroke, a hard pulse is again felt as valve overdrives
by 50 steps. Valve should be driven through at least
2 complete cycles to be sure it is operating properly.
If a hard pulse is felt for the 26 second duration, valve
is not moving and should be replaced.
The EXV test can be repeated as required by enter-
ing any percentage from 0 (
r;l )
to 100 to initiate
movement.
If operating problems persist after reassembly, they
may be due to out-of-calibration thermistor(s) or intermittent connections between processor board terminals
and EXV plug. Recheck all wiring connections and volt-
age
signals,
Other possible causes of improper refrigerant flow control could be restrictions in liquid line, Check for plugged
filter drier(s) or restricted metering slots in the EXV.
Formation of ice or frost on lower body of electronic expansion valve is one symptom of restricted metering slots.
However, frost or ice formation is normally expected
when leaving fluid temperature from the cooler is below
40 F. Clean or replace valve if necessary.
NOTE: Frosting of valve is normal during compressor
Test steps and at initial start-up. Frost should dissipate
after 5 to 10 minutes operation in a system that is operating properly. If valve is to be replaced, wrap valve
with a wet cloth to prevent excessive heat from damag-
ing internal components.
57
Page 58
MUFFLERS
COMPRESSORS
LEGEND
DPT
:ppTT
T
Discharge Pressure Transducer
-
-
Oil Pressure Transducer
-
Suction Pressure Transducer
-
Thermistor Number
FILTER
c
I
I
CIRCUIT
r
Fig. 13
-
CIRCUIT A
Thermistor and Pressure Transducer Locations
B
DRIER
-
J
58
Page 59
AIR
VENT
:
LEAVING
WATER/BRINE
THERMISTOR (Tl)
COOLER
FLUID
BAFFLECONNECTION
ENTERING
WATER/BRINE
SUCTION
CONNECTION
LEAVING
WATER/BRINE
CONNECTION
I
COOLER
TUBE
(TYPICAL)
ENTERING
WATER/BRINE
THERMISTOR
INLET
CONNECTIONDRAIN
Fig. 14 -Thermistor Locations
(Circuits A and B, Lead Compressor Only)
COUPLING
ACCESSORY
poi-i,
(~~~%~~
FERRULES
INSIDE
WATER-SIDE TEMPERATURE SENSOR (Tl, T2, - ALL UNITS),
3/16” (4 8) DIA114” (6.4)
(T7, T8 - 225, 250, 280)
1
f
JACKETED
I
OD COUPLING
Fig. 15
I
REFRIGERANT TEMPERATURE SENSOR (T7, T8 - 040-210 AND
Thermistors
-
59
JACKETEDSENSOR
CABLETUBE
AY
NOTE: BEND
FOR INSERTION
INTO WELL
SLIGHTLY-
ASSOCIATED MODULAR UNITS)
(76)
(4 6)
THERMISTOR
WELL
Page 60
Thermistors
perature vs. resistance performance. Resistance at various
temperatures are listed in Tables 15 and 16.
LOCATION - General location of thermistor sensors are
shown in Fig. 13.
Cooler Leaving Water Thermistor (Tl) - Tl is located in
leaving water nozzle. The probe is immersed directly in the
water. All thermistor connections are made through a
coupling. See Fig. 15. Actual location is shown in Fig. 13
and 14.
Cooler Entering Water Thermistor (T2) - T2 is located in
cooler shell in first baffle space near tube bundle. Ther-
mistor connection is made through a
Fig. 15. Actual location is shown in Fig. 13 and 14.
Compressor Suction Gas Temperature Thermistors
T8)- T7 and T8 are located in lead compressor in each
circuit in suction passage between motor and cylinders, above
oil pump. They are well-type thermistors on 040-210 and
associated modular units, or ferrule-type on 225, 250, 280
units. See Fig. 13 and 14.
THERMISTOR REPLACEMENT (Tl , T2, T7, TS) (Compressor and Cooler)
Thermistors are installed directly in fluid or refrigerant
circuit. Relieve all refrigerant pressure using standard
refrigerant practices or drain fluid before removing.
Proceed as follows (see Fig. 15):
To replace sensors
(225,250,280)
1. Remove and discard original thermistor and coupling.
IMPORTANT: Do not disassemble new coupling.
Install as received.
2. Apply pipe sealant to
ment coupling and install in place of original. Do not
use packing nut to tighten coupling. This damages ferrules (see Fig. 15).
3. Insert new thermistor in coupling body to its full depth.
If thermistor bottoms out before full depth is reached,
pull thermistor back out
nut. Hand tighten packing nut to position ferrules, then
finish tightening
are now attached to thermistor which can be withdrawn
from coupling for unit servicing.
To replace thermistors T7 and T8 (040-210 and associated
modular units):
Add a small amount of thermal conductive grease to thermistor well. Thermistors are friction-fit thermistors, which
must be slipped into receiver located in the compressor pump
end.
All thermistors are identical in their tem-
-
%-in.
%-in.
coupling. See
(T7
and
Tl,
T2, T7 (225,250,280), and
‘/a-in.
NPT threads on replace-
I/s
in, before tightening packing
19’4
turns with a suitable tool. Ferrules
T8
I
Pressure Transducers
ducers are used on 30G Flotronic’”
sure transducer and a high pressure transducer. The low
pressure transducer is identified by a white dot on the body
of the transducer, and the high pressure transducer by a red
dot. See Fig. 16.
Three pressure transducers are mounted on each lead com-
pressor: 2 low-pressure transducers to monitor compressor
suction pressure and oil pressure, and a high-pressure trans-
ducer to monitor compressor discharge pressure (see
Fig. 17 for exact locations on compressor). Each transducer
is supplied with 5 vdc power from a rectifier which changes
24 vat to 5 vdc.
TROUBLESHOOTING - If transducer is suspected of be-
ing faulty, first check supply voltage to transducer. Supply
voltage should be 5 vdc +.2 v. If supply voltage is correct, compare pressure reading displayed on keypad and dis-
play module against pressure shown on a calibrated pres-
sure gage. If the 2 pressure readings are not reasonably close,
replace pressure transducer.
TRANSDUCER REPLACEMENT
Transducers are installed directly in the refrigerant circuit. Relieve all refrigerant pressure using standard refrigeration practices before removing.
r
1. Relieve refrigerant pressure using standard refrigeration
2. Disconnect transducer wiring at transducer by pulling
3. Unscrew transducer from
4. Insert weathertight wiring plug into end of transducer
5. Check for refrigerant leaks.
WHITE DOT-LOW PRESSURE TRANSDUCER
RED DOT -HIGH PRESSURE TRANSDUCER
SAE
-
TWO
tvpes
of pressure trans-
Ii*chille&:
practices.
up on locking tab while pulling weather-tight connection
pfug from end of transducer. Do not pull on trans-
ducer wires.
!&in.
male flare fitting. When
installing new pressure transducer, do not use thread
sealer. Thread sealer can plug transducer and render it
inoperative.
Fig. 17 -Lead Compressor Transducer and Thermistor Locations
63
*Lead compressor only
Page 64
Control Modules
Turn controller power off before servicing controls. This
ensures safety and prevents damage to controller.
PROCESSOR MODULE (PSIO). 4 IN/4 OUT MODULE
(SIO), LOW-VOLTAGE TiELAY’MODULE (DSIO), AND
EXV DRIVER MODULE (DSIO) - The PSIO, DSIO and
SIO modules all perform continuous diagnostic evaluations
of the condition of the hardware. Proper operation of these
modules is indicated by LEDs (light emitting diodes) on the
front surface of the DSIOs, and on the top horizontal surface of the PSI0 and SIO.
RED LED - Blinking continuously at a 3- to
indicates proper operation. Lighted continuously indicates
a problem requiring replacement of module. Off continuously indicates power should be checked. If there is no input power, check fuses. If fuse is bad, check for shorted
secondary of transformer or for bad module. On the PSI0
module, if the light is blinking at a rate of twice per second, the module should be replaced.
GREEN LED - On a PSI0 and an SIO, this is the green
LED closest to COMM connectors. The other green LED
on module indicates external communications, when used.
Green LED should always be blinking when power is on. It
indicates modules are communicating properly. If green LED
is not blinking, check red LED. If red LED is normal, check
module address switches. See Fig.
modules indicate communication failure, check COMM
plug on PSI0 module for proper seating. If a good connec-
tion is assured and condition persists, replace PSI0
module.
If only DSIO or SIO module indicates communication
failure, check COMM plug on that mode for proper seating. If a good connection is assured and condition persists,
replace DSIO or SIO module.
All system operating intelligence rests in PSI0 module ,
the module that controls unit. This module monitors conditions through input and output ports and through DSIO
modules (low-voltage relay module and EXV driver
module).
The machine operator communicates with microproces-
sor through keypad and display module. Communication
between
PSI0
and other modules is accomplished by a 3-wire
sensor bus. These 3 wires run in parallel from module to
module.
On sensor bus terminal strips, terminal 1 of PSI0
ule is connected to terminal 1 of each of the other modules.
Terminals 2 and 3 are connected in the same manner. See
Fig, 19, If a terminal 2 wire is connected to terminal 1, system does not work.
In
FlotronicTM
II Chillers, processor module, low-voltage
relay module, and keypad and display module are all powered from a common 21-vat power source which connects
to terminals 1 and 2 of power input strip on each module. A
separate source of 21-vat power is used to power options
module through terminals 1 and 2 on power input strip. A
separate source of 12.5 vat power is used to power EXV
driver module through terminals 1 and 2 on power input
strip.
5-second
rate
mod-
Fig. 18
-
Module Address
Selector Switch Locations
PSIO,
SIO
ADDRESS
SELECTOR
64
Page 65
PSI0
( pRocEMssOp (RELAY)
DSIODSIO
Fig. 19
-
(Communications)
HSIO
(EXV
DRIVER)
(LID) (4
Sensor Bus Wiring
SIO
I;W;UT
LOW VOLTAGE RELAY MODULE (DSIO) (Fig. 21)
Inputs
When
Inputs on strip 53 are discrete inputs (ON/OFF).
-
24vat
power is applied across the 2 terminals in a
channel it reads as on signal. Zero v reads as an off signal.
Outputs - Terminal strips J4 and JS are internal relays whose
coils are powered-up and powered-off by a signal from microprocessor. The relays switch the circuit to which they are
connected. No power is supplied to these connections by
DSIO module.
L
--/%o-6
SENSOR BUS CONNECTOR
/
93
-
PROCESSOR MODULE (PSIO) (Fig. 20)
Inputs
terminals are
Each input channel has 3 terminals; only 2 of the
-
used.
Application of machine determines which
terminals are used. Always refer to individual unit wiring
for terminal numbers.
Outputs
-
Output is 24 vdc. There are 3 terminals, only 2
of which are used, depending on application. Refer to unit
wiring diagram.
NOTE: Address switches (see Fig. 20) must be set at 01
(different when CCN connected).
fL.w--
P
I
0
ADDRESS
SWITCHES
PSI0
6%2
0
<
0
0
P-
CHASSIS
GROUND
-( REAR)
NETWORK
SNNECTOR
’ (FORWARD)
SENSOR BUS
CONNECTOR
J8
1 $i 1
RED STATUS LIGHT
7
LEGEND
-
ii!“”
I%
Communications Bus
-
Normally Closed
1
bb;n$ly Open
Fig. 21 -Low-Voltage Relay Module
-
b
2,4,6,
9e
ZTPUT “7
RELAYS “,
:
I
:
I
%YoN
C&MON
2:
COMMON
NO
&MON
2:
/
ADDRESS ADJUSTMENT
(NOT SHOWN) ON UNDERSIDE
!;i
AND 8 ARE GRQUND (C)
NEL I2
I I
IO
9
8
7
6
5
(DSIO)
PWR- Power
Fig. 20 -Processor Module
I-
(PSIO)
65
Page 66
4
IN/4
OUT MODULE (SIO) (Fig. 22) - 4 In/4 Out mod-
ule allows the following features to be utilized:
1.
Temperature Reset by outdoor air or space temperature.
A remote thermistor (Part No, 30GB660002) is also required.
NOTE: This accessory is not required for return water
temperature reset.
2. Temperature Reset by remote 4-20 mA signal.
3. Demand Limit by remote 2-stage switch.
4. Demand Limit by remote 4-20 mA signal
5. Dual Set Point by remote switch.
The options module is standard on 30GN040-210 and
associated modular chillers and is available as a
field-installed accessory on 3OGT225, 250, and 280
Flotronic T” II chillers.
Remember to reconfigure the chiller for each feature se-
lected (see Table 13). For temperature reset, demand limit,
and dual set point, desired set points must be entered through
keypad and display module (see Set Point Function section
on page 39).
See Table 17 for overall troubleshooting information.
L
I
i
N
+
P
:
U
:
i
:
:
a
II
a
:
*
l
l
l
l
:
a
:
a
!8
r
J7
T
S
0
u
T
P
J6
U
T
S
COMM
ADDRESS
SWITCHES
PWR
EEM
-
-
LEGEND
Communications Bus
Power
Fig. 22 -4 In/4 Out Module
(SIO)
66
Page 67
Table 17
Troubleshooting
-
SYMPTOMS
COMPRESSOR DOES
NOT RUN
COMPRESSOR CYCLES OFF
ON LOW PRESSURE
COMPRESSOR SHUTS DOWN
~N&-l;l;PFlESSURE
UNIT OPERATES LONG OR
CONTINUOUSLY
SYSTEM NOISES
COMPRESSOR LOSES OIL
FROSTED SUCTION LINE
HOT LIQUID LINE
FROSTED LIQUID LINE
COMPRESSOR DOES NOT
UNLOAD
fgF;RESSOR
DOES NOT
CAUSE
Power line open
Control fuse open
High Pressure Switch (HPS)
tripped
Tripped power breaker
Loose terminal connection
Improperly wired controls
Low line voltage
Compressor motor defective
Seized compressor
Loss of charge
Bad transducer
Low refrigerant charge
High-pressure control erratic in action
Compressor discharge valve partially closed
Condenser fan(s) not operating
Condenser coil
Low refrigerant charge
Control contacts fused
Partially plugged or plugged expansion
valve or filter driver
Defective insulation
Service load
Piping vibration
Expansion valve hissing
Compressor noisy
Leak in system
Mechanical damage (blown piston or
broken discharge valve)
Crankcase heaters not energized
durina shutdown
Expansion valve admitting excess
refrigerant
Shortaae of refriaerant due to leak
Shutoff valve partially closed or restricted
Burned out coil
Defective capacity control valve
Miswired solenoid
Weak, broken, or wrong valve body spring
Miswired solenoid
Defective capacity control valve
Plugged strainer (high side)
Stuck or damaged unloader piston or
piston ring(s)
oluaaed
or
dirtv
REMEDY
Reset circuit breaker
Check control circuit for ground or short.
Replace fuse
Move LOCAL/ENABLE-STOP-CCN switch to STOP
position then back to RUN or CCN position.
Check the controls. Find cause of trip
and reset breaker
Check connections
Check wiring and rewire.
Check line voltage. Determine location
of voltage drop and remedy deficiency
Check motor winding for open or shot-t.
Replace compressor if necessary.
Replace compressor.
Repair leak and recharge
Replace transducer.
Add refrigerant.
Replace control
Open
valve
or replace if defective.
Check wiring. Repair or replace motor(s)
if defective.
Clean coil.
Add refrigerant,
Replace control
Clean or replace
Replace or repair.
Keep doors and windows closed.
Check valves. Replace if necessary.
Support piping as required
Add refrigerant.
Check for plugged liquid line filter drier.
Check valve plates for valve noise.
Replace compressor (worn bearings).
Check for loose compressor
Repair leak.
Repair damage or replace compressor.
Replace heaters, check wiring and
crankcase heater relay contacts.
Check cooler and compressor thermistors.
Test EXV.
Repair leak and recharge
Open valve or remove restriction.
Replace coil
Replace valve
Rewire correctly.
Replace spring
Rewire correctly
Replace valve.
Clean or replace strainer.
Clean or replace the necessary parts.
holddown
bolts.
67
Page 68
ACCESSORY UNLOADER INSTALLATION
Some of the 30G
unloader(s), and many permit additional unloader(s) to be
added if desired. See Table 18.
IMPORTANT: Accessory hot gas bypass cannot be
installed with accessory unloaders on units with more
than 4 compressors.
FlotronicT”
II units come standard with
Wire the primary side of the transformer in parallel with
TRAN3. See Fig. 23. This supplies transformer with proper
line voltage. Be sure to connect proper tap of the transformer to ensure supply of proper secondary voltage.
Wire the secondary side of transformer to DSIO-LV
J5-9, and a jumper from DSIO-LV - J5-9 to DSIO-LV
-
-
54-9. Wire the secondary common to TB7-2. Connect
the transformer ground to ground hole supplied near the
transformer. These connections provide DSIO with nec-
If accessory unloaders are desired, an accessory unloader
package is used. Package includes a suction cutoff unloader
head package. The 24-v coil in the package can be used for
040-l 10, 130 (60 Hz) and associated modular units. A
115 v or 230 v coil must be used for 130 (50 Hz), 150-210,
225, 250, 280, and associated modular units. Coil voltage
depends on control circuit voltage, Consult current Carrier
price pages for appropriate part numbers.
NOTE: The accessory package will include all necessary
components and wiring with the following exceptions: The
field must provide screws, and on the 130-2 10, 225, 250,
280, and associated modular units, the field must also supply a 20 vdc (part number HK356ABOOl) unloader relay
and wire (90” C or equivalent).
Table 18 -Standard and Accessory Unloaders
essary power to energize the solenoid coils.
3.
When all connections are made, check for proper wiring
and tight connections. Replace and secure inner panel.
Restore power to unit.
4.
Configure the processor. With the addition of extra unloaders, the unit configuration has changed. To change
the configuration of the processor, enter the service function using the keypad and display module. Before any
changes can be made, the LOCAL/ENABLE-STOP-
CCN switch must be in the STOP position, and the servicer must log on to the processor.
Press
pJl,,,l*
Keypad LCD displays the word
a.
PASSWORD.
b,
Enter m ri m m
[;;;;;I
.displays
Keypad
LCD
LOGGEDON.
I
1 NO. OF ACCESSORY
To change configuration, pressm H. Keypad LCD
C.
displays FLD CFG.
Circuit A Circuit B
30GN190-210*0
3OGT225,250,280
*And associated modular units
1
11
11
0
11
1
or2
Installation
1.
Be sure all electrical disconnects are open and tagged
before any work begins. Inspect the package contents
for any damage during shipping. File a claim with the
shipper if damage has occurred.
2.
For ease of installation, factory-supplied wiring for the
additional unloader is provided in the compressor
harness.
Install the additional unloader cylinder head on the lead
3.
compressor, Al or
El,
according to instructions provided by the compressor manufacturer in the accessory
package.
4.
Continue installation per either 040-l 10, 130 (60 Hz)
1
units or 130 (50 Hz), 150-210, 225, 250, and 280 units
section as appropriate.
04
-0-l 10, 130 (60 Hz) UNITS (and associated modular units)
1.
Wire the solenoid before any field wiring begins. Wir-
ing between components and control box must be enclosed in conduit. All local electrical codes and National
Electrical Code (NEC) must be followed. Factory wires
d.
If an additional unloader was added to compressor
Al, press m until NULA 1 appears in keypad dis-
play. Press m Fifor the number of unloaders on
circuit A. Keypad display now reads NULA 2.
If an additional unloader was added to compressor
B 1, press
q
until NULB 1 appears in keypad dis-
play. Press m bi for the number of unloaders on
circuit B. Keypad display now reads NULB 2.
When configuration is complete, press
mM.
pad display reads LOGGEDON. Press m until
Key-
key-
pad display reads LOG OFF. Press H . Keypad display reads EXIT LOG.
5.
Using test function, check unloaders. Press 12 1
pad display reads OUTPUTS. Press
reads ULA 2 OFF. Press
a
and relay deenergizes. Press
ULB2 OFF. Press
q
. Relay energizes. Press
Li_]
H
. Relay energizes. Press q
III
pEsTI.
Key-
I)I
until display
until display reads
and relay deenergizes.
6.
When unloader check has been performed, return LOCAL/
ENABLE-STOP-CCN to proper position. Close and secure control box door.
are provided in the compressor harness to connect the
solenoid. These wires are in the compressor control box.
2. Wire the control side. Open the left side control box
door and remove inner panel. Using the holes provided
and field-supplied screws, install field-supplied trans-
former above the DSIO-LV on the control panel.
68
Page 69
~13014115v 0R
230y;f;~RO~
SCHEMATIC
i
-- 13
6
r--‘---------‘-‘-“--“‘-“-----------~
1
!
-9RA
1
1’
!
I
I
I
I
I
I
1
I
L--a---
-
VI0
FROM 115V OR 23OV CONTROL SCHEMATIC
y
IDS00
(LWl
0
0
0
0
TRAN
‘.
\
\
\
\
\
\
\
ERCS
RED-
-
Contactor
-
Compressor Protection Control System
-
Control Relay
-
Rela
Module
u,
-
Low
oltage
LEGEND
080-110
k
TL
U
(SO/SO
z
~~.?ther
-
Terminal Block
-
Transformer
-
Unloader
Hz) and 130 (60
Hz)
Fig. 23- Accessory Unloader Control Wiring
69
Page 70
130 (50 Hz), 150-210, 225, 250, AND 280 UNITS (and
associated modular units)
1.
Install control wiring. The minimum wire size for
stallation is 16
AWC
(American Wire Gage). Refer to
in-
Fig. 24 and 25 for proper wiring. Open the control box
door. Locate unloader relays A and B (URA, URB) in
place of the hot gas bypass relays as shown on the component arrangement diagram on the unit. Mount the re-
lays with the field-supplied screws. Be careful not to
damage the components and wiring in the area when mounting the relays.
Wire the control side. Wire the URA coil in series be-
2
tween 56-18 and J6- 19 of the 4 IN/4 OUT module with
the wires provided. Wire the URB coil in series between J6-21 and J6-22 of the same module with the wires
provided.
Locate the black wire in the control harness originating
from
TRANS
labeled HGBPR-A-COM. Connect this wire
to the URA terminal COM. Connect the wire labeled
HGBPR-A-NO to URA-NO. Connect the wire from
URA-NO to TB3-5. For an extra unloader on circuit
B,
5
connect the wire labeled HGBPR-B-COM to UR-B-
COM, and the wire labeled HGBPR-B-NO to URB-
NO. Connect the wire from URB-NO to TB3-6.
3. Wire in the solenoid valves.
NOTE: Wires external to the control box must be run in
conduit
+
Terminal blocks are provided for easy field wiring. Use
one of the isolated
‘/s-in.
(22-mm) holes in the side of
the compressor electrical box with a strain relief to run
the wires to the solenoid coil. Connect URA between
TB3-5 and TB3-8. Connect URB between TB3-6 and
TB3-8. Check all of the electrical connections for proper
location and tightness, and replace and secure the electrical box of the compressor,
4. Configure the microprocessor, Once the relays are mounted
in the control box, the microprocessor must be config-
ured for the unloader option. ‘To do so:
a. Be sure the LOCAL/ENABLE-STOP-CCN switch is
in the STOP position.
b. Log into the processor and enter the service func-
tion using the keypad and display module.
Type r\
“PASSWORD.” Enter
I;;;;E]
. The keypad LCD will display
~~1~~~~,
and the
6. Once the check has been performed, return the LOCAL/
7. Close and secure the control box door.
8. Start the unit and confirm that the chiller operates
keypad LCD will display “LOGGEDON. ”
C,
To change the configuration, type14 H, and the
keypad LCD will display “FLD CFG.” Press
m
until either “NULA 0” or “NULA I” is displayed
(depending on the number of unloaders provided as
standard), Then press m H (for 1 unloader on Al)
or
FiFi
(for 2 unloaders on compressor Al). The
display will now read either “NULA 1” or
‘
‘NULA 2, ” as appropriate, Press
I)I
to get to the
NULB display, and change this setting in the same
manner as with circuit A.
d.
Once the configuration is complete, press m
Fi,
and the keypad LCD will display “LOGGEDON,”
Press @ until the keypad LCD display reads “LOG
OFF.” Press H and the keypad LCD will display
“EXIT LOG.”
Once the unloader heads are installed, the unit is checked
._--
for leaks, and the system is prepared for operation per
instructions for the compressor unloader head instal-
the
lation, check the output of the relays using the test function as follows:
a. Press
b. Press the
T;1H,
q
and the display will read “COMP.”
to scroll down until the display reads
“CPA1 OFF.”
c. Press
ENTR
,0and the compressor should start.
d. Press + ,aand the compressor should stop.
e. Press
NOTE: Contacts must be rated for dry circuit application, capable of
reliably switching a 5 vdc, 1 mA to 20 mA load.
Fig. 33 -Remote Dual Set Point Control
43
7
6
1
------
115/23ovv
-------_--
f
30GN040-210
CWP- Chilled Water Pump
TB- Terminal Block
NOTE: The maximum load allowed for the chilled water pump circuit
is 125 va sealed, 1250 va inrush at 115 or 230 v
AND ASSOClATED MODULAR UNITS
30GT225,250,280
CWP
-----
cl-
__--
--v-w
WI--
FLOTRONIC II UNITS
-cl
4
-t-l
3
El
u
3
-rB$J
T5-3
TE5
4 TE5
The replacement part number is printed on a small label
on front of the PSI0 module. The model and serial numbers are printed on the unit nameplate located on an exterior corner post. The proper software and unit configuration
data is factory installed by Carrier in the replacement mod-
ule. Therefore, when ordering a replacement processor mod-
ule (PSIO), specify complete replacement part number, full
unit model number, and serial number. If these numbers
are not provided, the replacement module order is config-
ured instead as a generic Flotronic’” 11 replacement mod-
ule. This requires reconfiguration of the module by the
installer.
Electrical shock can cause personal injury, Disconnect
all electrical power before servicing.
CWPl(CWFS)
------
AND ASSOCIATED MODULAR UNITS
-----
-----
30GT225,250,280 FLOTRONIC I I UN ITS
protection is provided by Flotronic II controls)
-
Terminal Block
--a
TB-6
2
TB-6
-cl
7
TB-7
-El
8 TE7
u
Fig. 36 -Interlocks
REPLACING DEFECTIVE
PROCESSOR MODULE
Fig. 34 -Chilled Water Pump
-43 77
ALARM SHUTOFF
-------a--II
i
L
30GN040-210
30GT225,250,280
TB -Terminal Block
NOTE: The maximum load allowed for the alarm circuit is 125 va
sealed, 1250 va inrush at 115 or 230 v
SWITCH
------2
AND ASSOCIATED MODULAR UNITS
_d--
----
FLOTRONIC II UNITS
1 TB-3
-cl
cl
2 TB-5
u
T8-3
Fig. 35 -Remote Alarm
Installation
1.
Verify the existing PSI0 module is defective by using
the procedure described in the Control Modules section on page 64.
2.
Refer to Start-Up Checklist for Flotronic II Chiller Systems (completed at time of original start-up) found in
job folder. This information is needed later in this
procedure. If checklist does not exist, fill out the ri
and Fi F\ configuration code sections on a new check-
list. Tailor the various options and configurations as
needed for this particular installation.
3.
Check that all power to unit is off. Carefully disconnect all wires from defective module by unplugging the
6 connectors. It is not necessary to remove any of the
individual wires from the connectors. Remove the green
ground wire.
4.
Remove defective
PSI0
by removing its mounting screws
with a Phillips screwdriver, and removing the module
from the control box, Save the screws for later use.
5.
Use a small screwdriver to set address switches Sl and
S2 on the new PSI0 module to exactly match the set-
tings on the defective module.
6.
Package the defective module in the carton of the new
module for return to Carrier.
7.
Mount the new module in the unit control box using a
Phillips screwdriver and the screws saved in Step 4 above.
H
73
Page 74
8. Reinstall all 6 wire connectors and the green ground
wire.
9. Carefully check all wiring connections before restoring
power.
10. Verify the LOCAL/ENABLE-STOP-CCN switch is in
STOP position
11. Restore control power. Verify the red and green lights
on top of PSI0 and front of each DSIO module re-
spond as described in Control Modules section on
page 64. The keypad and display module @IS10 or LID)
should also begin its rotating display.
12. Using the keypad and display module, press
to verify that the software version number matches the
ER (engineering requirement) number shown on the
label.
13. Press
[qn
SRVC
to verify that the 6 factory configuration
codes (CODE 1 through CODE 6) exactly match the
codes listed for this unit model on the component arrangement label diagram on the control box door. If
they are different or are all zeros, reenter the 6 codes.
If any changes are required, the PSI0 display becomes
blank and reconfigures itself after pressing the H key
[p-&q,
PSI0
while displaying CODE 6. The display returns in approximately 15 seconds.
NOTE: Codes with leading zeros in the configuration
will be displayed starting with the first number greater
than zero.
14. Press nn4sRvc
for this particular installation. Table 9 shows the fac-
tory configuration code default settings. Table 9 also
shows the service replacement code default settings which
are used if no model number was specified when ordering the replacement
gested that the Start-Up Checklist for Flotronic’” II Chiller
Systems (completed at time of original start-up) be used
at this time to verify and/or reprogram the various options and configurations required for this job.
15. After completing the configuration steps outlined above,
restore main power and perform a unit test as
scribed in m H and
16,
Complete this procedure and restore chiller to normal
operation by returning the LOCAL/ENABLE-STOP-
CCN switch to desired position.
to verify each item is configured as needed
PSI0
module. It is strongly sug-
de-
r;lFl
sections on page 38.
74
Page 75
Page 76
Copyright 1994 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
Tab 5c
-I-
PC 903
Catalog No 563-015
Printed in U S AForm
30GN-2TPg 76l-94
Replaces: 30GEl,GT-1 T,
30GN-1T
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.