Carlo Gavazzi T2000P Catalog Page

PID Controllers Temperature and Process Controls T2000P
Type Selection
Ordering Key
T2016P2 SR R X T 2 XX
Model Output 3rd output Not Used Input Communication Not Used
Specifications are subject to change without notice 1
Input Specifications (cont’d)
Thermocouple (cont’d)
S 32 to 2912°F (0 to 1600°C) T -273 to 482°F (-200 to 250°C) Standards IPTS/68/DIN 43710 CJC rejection 20:1 (0.05%°C) typical External resistance 100W maximum
(RTD)
Pt100/RTD (2 or 3 wire) -273 to 752°F (-200 to 400°C) Standards DIN 43760 (100W 0°C/138.5W
100°C Pt)
Bulb current 0.2 mA maximum
Analog process input
0 to 50mV, +/- 0. 1% 0-20mA, 4-20mA, +/- 0.1% 0-5V, +/- 0.1%, 0-10V, +/-0.1%
Specifications for Both Thermocouples and RTDs
Calibration accuracy +/- 0.25% maximum +/- 1°C Sampling frequency Input 10Hz, CJC 2 sec. Common mode rejection Negligible effect up to 140db,
240V, 50-60Hz Series mode rejection 60db, 50-60Hz Temperature coefficient 150ppm/(C maximum) Reference conditions 22C +/- 2°C, rated voltage after
15 minutes settling time
General Specifications
Power supply 100-240VAC +/- 10%, 50-60Hz Display
Upper display reading 4 digit high brightness green
LED 10mm high
Lower display 4 digit high brightness red
LED 9mm high
Output indicators LED output indicators –
flashing SP1 square green LED output indicators – SP2 round red
Keypad 3 full travel elastomeric
pushbuttons
Approvals UL, CUL, CE
Input Specifications
Thermocouple
B 32 to 3275°F (0 to 1800°C) E 32 to 1112°F (0 to 600°C) J 32 to 1472°F (0 to 800°C) K -58 to 2192°F (-50 to 1200°C) L 32 to 1472°F (0 to 800°C) N -58 to 2192°F (-50 to 1200°C) R 32 to 2912°F (0 to 1600°C)
Product Description
Programmable profiling temperature and process controller. Easy to view dual 4 digit display readout. Constructed in a rugged NEMA4X waterproof housing (front panel only) in the popular 1/16 DIN size. Various inputs from temperature sensors to analog process inputs and various combinations of outputs including analog outputs and a 3rd relay output standard.
• 1/16 DIN
• NEMA 4X
• Programable Process controller
• Autotune automatically sets PID parameters
• Multiple ramp/soak: Upto 31 programs, 126 segments
• Inputs: Thermocouple, RTD, Analog (0-20mA, 0-5VDC, 0-10VDC)
• Outputs: SSR voltage pulse, relay, Analog (0-20mA, 0-5VDC, 0-10VDC)
• 3rd relay output standard
• RS232 or RS485
• MODBUS RTU protocol
• Three year warranty
Type Selection
Model Outputs 3rd Output Not used Input Communication Not use
T2016P2 SR: 6VDC pulse & 2A relay output R: 2A relay output X: not used T: TC-B,E,J,K,L,N,R,S,T & RTD X: None XX: not used
RR: 2 - 2A relay outputs C: 4-20mA input 2: RS232 SS: 2 - 6VDC pulse outputs L: 0-5VDC input 4: RS485 CR: 4-2OmA & 2A relay output H: 0-10VDC input CS: 4-2OmA & 6VDC pulse output LR: 0-5VDC & 2A relay output LS: 0-5VDC & 6VDC pulse output HR: 0-10VDC & 2A relay output HS: 0-10VDC & 6VDC pulse output
T2000P
T2000P
17 18 19 20 21 22 23 24
12345678
(–) (+) LN
S1
Line
Neutral
F1
F2
4.57”
(116.2mm)
4.2”
(106.7mm)
with gasket fitted
1.76” (44.8mm)
2.0”
(51.0mm)
includes gasket
2.0” (51.0mm)
includes gasket
4-20mA
Transducer
(+) (–)
4-20mA
Mains
INPUT
Analog power
controller
Heater
User configurable
alarms
Dimensions
Output Devices (maximum of two outputs)
SSd
(solid state relay driver)
6 VDC, 20mA non-isolated
Relay Form A SPST, 2A/250VAC
resistive load
Analog Output
4-20mA 500max
+/- 0. 1% full scale typical
0-5Vdc 10mA (500min)
+/- 0.1% full scale typical
0-10Vdc 10mA (1Kmin)
+/- 0.1% full scale typical
Housing Specifications
Environmental
Safety UL873, EN61010, CSA 22.2 No.
1010.1-92 Humidity Maximum 95% Altitude Up to 2000m
Housing Specifications (cont’d)
Installations Categories II and III Pollution Degree II Protection NEMA 4X (IP66) EMC emission EN50081-1, FCC Rules 15
subpart J Class A EMC immunity EN50082-2 Ambient 32 to 122°F (0 to 50°C) Moldings Flame retardant polycarbonate
Instrument body
Model T2016P2 1.76 x 1.76” (44.8 x 44.8mm) Overall length 4.57” (116mm)
Weight
T2016P2 6.4 ounces
Dimensions (front fascia)
Model T2016P2 2.0 x 2.0” (51 x 51mm)
includes gasket Sleeve length 4.2” (106.7mm)
includes gasket
Wiring Diagram
T2016P Series
T2016P Series
Programmer Functionality
• Up to 31 programs (profiles)
• Up to 126 segments
• Unlimited use of event outputs via the 2nd and 3rd outputs
• Copy/Paste/Edit/Delete functions to simplify program building
• Call another program as a sub-program segment
• Up to 999 program loop cycles, or continuous loop cycling
• Hold back function, to ensure the next segment is not started until the last segment reaches the set-point
• 3 power fall recovery options, (Hold, Continue or Reset)
• Front panel interrogation of the program position
• Memory usage Indication during programming.
(note: program capacity is a memory function and different
types of segment use more/less memory).
Profile of a single program
Memory Allocation Table
Function Memory Usage
Ramp 4 Bytes Ramp with Holdback 5 Bytes Soak 2 Bytes Step 3 Bytes Loops (1 -3) 1 Byte Loop (4+) 2 Bytes Call 1 Byte Event Output 1 Byte Program Header 1 Byte
Set-point
Segment 1 Segment 2 Segment 4 Segment 5 Segment 6
RAMP SOAK SOAK RAMP SOAK
Segment 3
STEP
Segment 7
EVENT
OUTPUT
Time
Set-point
Segment 1 Segment 2 Segment 3 Segment 5 Segment 7 Segment 8 Segment 10
RAMP SOAK RAMP RAMP SOAK RAMP SOAK
CONTIN-
UOUS
Time
Segment 4
Program LooP
from 1 to 999 cycles
e.g. loop for 25 cycles
Segment 6
Program CALL
to call another program
e.g. Call Prog 5 then go to 7
Segment 9
E.oP Event Output
e.g. Trigger alarm on SP2
Examples
Max. capacity; 351 Bytes, 126 segments per program, 31 programs
Example 1
(349 Bytes) One program of 116 segments (58 ramps, 58 soaks)
Example 2
(340 Bytes) 4 programs of 28 segments (14 ramps, 14 soaks)
Loading...