2
DIB02, PIB02
Mode of Operation
DIB02 and PIB02 monitor
both AC and DC over or
under current through an
external shunt.
When connected with MI or
MP current transformer (using
the 0.4 to 4 V
p
range) they
can monitor 1-phase or 3phase AC current up to 500 A.
Example 1
(connection between terminals Z1, Y1 or 8, 9 - latching
function enabled)
The relay operates and latches in operating position
when the measured value
exceeds (or drops below) the
set level for more than the
set delay time.
Provided that the current has
dropped below (or has
exceeded) the set point (see
hysteresis setting), the relay
releases when the interconnection between terminals
Z1, Y1 or 8, 9 is interrupted
or the power supply is interrupted as well.
The red LED flashes until the
delay time has expired or the
measured value comes back
to a non-alarm value (see
hysteresis setting).
Example 2 (MI CT)
(no connection between terminals Z1, Y1 or 8, 9 - latch
function disabled)
The relay operates when the
current flowing in the CT
exceeds (or drops below) the
set level for more than the
set delay time.
It releases when the current
drops below (or exceeds) the
set level (see hysteresis setting) or when power supply
is interrupted.
Example 3 (MP CT)
(no connection between terminals Z1, Y1 or 8, 9 - latch
function disabled - over current measurement)
The relay operates when the
maximum current flowing in
the CT exceeds the set level
for more than the set delay
time.
It releases when the maximum current drops below
the set level (see hysteresis
setting) or when power supply is interrupted.
Note
When the inhibit contact is
opened, if the input signal is
already in alarm position, the
delay time needs to elapse
before relay activation.
Power supply Overvoltage cat. III
Rated operational voltage (IEC 60664, IEC 60038)
through terminals:
A1, A2 or A3, A2 (DIB02)
2, 10 or 11, 10 (PIB02)
724: 24 VDC ± 20%, insulated
748: 48 VDC ± 20%, insulated
B48: 24/48 VAC ± 15%
45 to 65 Hz, insulated
B23: 115/230 VAC ± 15%
45 to 65 Hz, insulated
Dielectric voltage DC supply AC supply
Supply to input 2 kV 4 kV
Supply to output 4 kV 4 kV
Input to output 4 kV 4 kV
Rated operational power
AC 4 VA
DC 3 W
Supply Specifications
Power ON delay 1 s ± 0.5 s or 6 s ± 0.5 s
Reaction time (input signal variation from
-20% to +20% or from
+20% to -20% of set value)
Alarm ON delay < 100 ms
Alarm OFF delay < 100 ms
Accuracy (15 min warm-up time)
Temperature drift ± 1000 ppm/°C
Delay ON alarm ± 10% on set value ± 50 ms
Repeatability ± 0.5% on full-scale
Indication for
Power supply ON LED, green
Alarm ON LED, red (flashing 2 Hz
during delay time)
Output relay ON LED, yellow
Environment (EN 60529)
Degree of protection IP 20
Pollution degree 3 (DIB02), 2 (PIB02)
Operating temperature -20 to 60°C, R.H. < 95%
Storage temperature -30 to 80°C, R.H. < 95%
Housing dimensions
DIn-rail version 22.5 x 80 x 99.5 mm
Plug-in version 36 x 80 x 94 mm
Weight Approx. 150 g
Screw terminals
Tightening torque Max. 0.5 Nm
acc. to IEC 60947
Approvals UL, CSA (except 748)
CE Marking Ye s
EMC
Electromagnetic Compatibillity
Immunity According to EN 61000-6-2
Emission According to EN 61000-6-3
General Specifications
Output SPDT relay
Rated insulation voltage 250 VAC
Contact ratings (AgSnO2)µ
Resistive loads AC 1 8 A @ 250 VAC
DC 12 5 A @ 24 VDC
Small inductive loads AC 15 2.5 A @ 250 VAC
DC 13 2.5 A @ 24 VDC
Mechanical life ≥ 30 x 106operations
Electrical life ≥ 105operations
(at 8 A, 250 V, cos ϕ = 1)
Operating frequency ≤ 7200 operations/h
Dielectric strength
Dielectric voltage
≥ 2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Output Specifications