Carlo Gavazzi DIB02, PIB02 Technical data

1
Monitoring Relays
Product Description Ordering Key
Housing Function Type Item number Output Power supply Range
• TRMS AC/DC over or under current monitoring relays
• Current measuring through external shunt or CT
• Selection of measuring range by DIP-switches
• Measuring ranges from 6 to 150 mV AC/DC and
0.4 to 4 V
p
AC (MI or MP range)
• Adjustable current on relative scale
• Adjustable hysteresis on relative scale
• Adjustable delay function (0.1 to 30 s)
• Programmable latching or inhibit at set level
• Output: 8 A SPDT relay N.D. or N.E. selectable
• For mounting on DIN-rail in accordance with DIN/EN 50 022 (DIB02) or plug-in module (PIB02)
• 22.5 mm Euronorm housing (DIB02) or 36 mm plug-in module (PIB02)
• LED indication for relay, alarm and power supply ON
• Galvanically separated power supply
Type Selection
Input
Voltage level DIB02: Terminals Y1, Y2
PIB02: Terminals 5, 7
Measuring ranges Internal resis. Max. volt.
6 to 60 mV AC/DC 1 k 2 V 15 to 150 mV AC/DC 1 k 2 V Max. voltage for 1 s 15 V
0.4 to 4 V
p
AC 50 k 50 V
Max. voltage for 1 s 100 V
MI and MP CT ranges
AAC rms Max. curr.
1-ph.: 3-ph.: MI 5 MP 3005 0.5 to 5 A 20 AAC MI 20 MP 3020 2 to 20 A 50 AAC MI 100 MP 3100 10 to 100 A 250 AAC MI 500 MP 3500 50 to 500 A 750 AAC
Note:
The input voltage cannot raise over 300 VAC/DC with respect to ground (PIB02 only)
1-Phase True RMS AC/DC Over or Under Current Types DIB02, PIB02
Input Specifications
DIB 02 C B23 150mV
DIB02 and PIB02 are precise TRMS AC/DC over or under current (selectable by DIP­switch) monitoring relays. The current is measured through an external shunt. 1-phase and 3-phase current up to 500 AAC can be monitored connecting MI or MP current transformers.
Owing to the built-in latch function, the ON-position of the relay output can be maintained. Inhibit function can be used to avoid relay operation when not desired (maintenance, transitions). The LED's indicate the state of the alarm and the output relay.
DIB02
PIB02
Note:
MP3... current transformers not suitable for under cur­rent measurement due to the output signal of the device (see data sheet)
Contact input
DIB02 Terminals Z1, Y1 PIB02 Terminals 8, 9 Disabled > 10 k Enabled < 500 Latch disable > 500 ms
Input Specifications (cont.)
Mounting Output Supply: 24 VDC Supply: 48 VDC Supply: 24/48 VAC Supply: 115/230 VAC
DIN-rail SPDT DIB 02 C 724 150MV DIB 02 C 748 150MV DIB 02 C B48 150MV DIB 02 C B23 150MV Plug-in SPDT PIB 02 C 724 150MV PIB 02 C 748 150MV PIB 02 C B48 150MV PIB 02 C B23 150MV
2
DIB02, PIB02
Mode of Operation
DIB02 and PIB02 monitor both AC and DC over or under current through an external shunt.
When connected with MI or MP current transformer (using the 0.4 to 4 V
p
range) they can monitor 1-phase or 3­phase AC current up to 500 A.
Example 1
(connection between termi­nals Z1, Y1 or 8, 9 - latching function enabled)
The relay operates and latch­es in operating position when the measured value
exceeds (or drops below) the set level for more than the set delay time. Provided that the current has dropped below (or has exceeded) the set point (see hysteresis setting), the relay releases when the intercon­nection between terminals Z1, Y1 or 8, 9 is interrupted or the power supply is inter­rupted as well. The red LED flashes until the delay time has expired or the measured value comes back to a non-alarm value (see hysteresis setting).
Example 2 (MI CT)
(no connection between ter­minals Z1, Y1 or 8, 9 - latch function disabled)
The relay operates when the current flowing in the CT exceeds (or drops below) the set level for more than the set delay time. It releases when the current drops below (or exceeds) the set level (see hysteresis set­ting) or when power supply is interrupted.
Example 3 (MP CT)
(no connection between ter­minals Z1, Y1 or 8, 9 - latch
function disabled - over cur­rent measurement) The relay operates when the maximum current flowing in the CT exceeds the set level for more than the set delay time. It releases when the maxi­mum current drops below the set level (see hysteresis setting) or when power sup­ply is interrupted.
Note
When the inhibit contact is opened, if the input signal is already in alarm position, the delay time needs to elapse before relay activation.
Power supply Overvoltage cat. III
Rated operational voltage (IEC 60664, IEC 60038) through terminals:
A1, A2 or A3, A2 (DIB02) 2, 10 or 11, 10 (PIB02)
724: 24 VDC ± 20%, insulated 748: 48 VDC ± 20%, insulated
B48: 24/48 VAC ± 15%
45 to 65 Hz, insulated
B23: 115/230 VAC ± 15%
45 to 65 Hz, insulated
Dielectric voltage DC supply AC supply
Supply to input 2 kV 4 kV Supply to output 4 kV 4 kV Input to output 4 kV 4 kV
Rated operational power
AC 4 VA DC 3 W
Supply Specifications
Power ON delay 1 s ± 0.5 s or 6 s ± 0.5 s Reaction time (input signal variation from
-20% to +20% or from
+20% to -20% of set value) Alarm ON delay < 100 ms Alarm OFF delay < 100 ms
Accuracy (15 min warm-up time)
Temperature drift ± 1000 ppm/°C Delay ON alarm ± 10% on set value ± 50 ms Repeatability ± 0.5% on full-scale
Indication for
Power supply ON LED, green Alarm ON LED, red (flashing 2 Hz
during delay time) Output relay ON LED, yellow
Environment (EN 60529)
Degree of protection IP 20 Pollution degree 3 (DIB02), 2 (PIB02) Operating temperature -20 to 60°C, R.H. < 95% Storage temperature -30 to 80°C, R.H. < 95%
Housing dimensions
DIn-rail version 22.5 x 80 x 99.5 mm Plug-in version 36 x 80 x 94 mm
Weight Approx. 150 g Screw terminals
Tightening torque Max. 0.5 Nm
acc. to IEC 60947
Approvals UL, CSA (except 748) CE Marking Ye s EMC
Electromagnetic Compatibillity
Immunity According to EN 61000-6-2 Emission According to EN 61000-6-3
General Specifications
Output SPDT relay
Rated insulation voltage 250 VAC
Contact ratings (AgSnO2)µ
Resistive loads AC 1 8 A @ 250 VAC
DC 12 5 A @ 24 VDC
Small inductive loads AC 15 2.5 A @ 250 VAC
DC 13 2.5 A @ 24 VDC
Mechanical life 30 x 106operations Electrical life 105operations
(at 8 A, 250 V, cos ϕ = 1)
Operating frequency 7200 operations/h Dielectric strength
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Output Specifications
3
DIB02, PIB02
Function/Range/Level and Time Delay Setting
Adjust the measuring range set­ting the DIP switches 1 and 2 and select the desired function setting the DIP switches 3 to 6 as shown below. To access the DIP switches open the grey plastic cover as shown below.
Selection of level and time delay:
Upper knob:
Setting of hysteresis on rela­tive scale: 0 to 30% on set value.
Centre knob:
Current level setting on rela­tive scale: 10 to 110% on full scale.
Lower knob:
Setting of delay on alarm time on absolute scale (0.1 to 30 s).
Example 1
Example 2
Example 3
L
N(-)
PE
Z1
Y1
Y2
A1 A3
A2 15
16 18
I
L
N(-)
PE
Z1
Y1
Y2
A1 A3
A2 15
16 18
I
L
N(-)
PE
Z1
Y1
Y2
A1 A3
A2 15
16 18
I
24 VDC (+) 48/230 VAC
24/115 VAC
24 VDC (+)
48/230 VAC
24/115 VAC
24 VDC (+) 48/230 VAC
24/115 VAC
Latch/Inhibit
enable
Example 1
Example 2
Example 3
L
N(-)
PE
µ
5
7
10 1
43
1
43
1
43
I
89
L
N(-)
PE
µ
5
7
10
I
89
L
N(-)
PE
µ
5
7
I
89
24 VDC (+) 48/230 VAC
24/115 VAC
112
24 VDC (+)
48/230 VAC
24/115 VAC
112
24 VDC (+)
48/230 VAC
24/115 VAC
112
Latch/Inhibit
enable
10
Wiring Diagrams
DIB02 PIB02
Measuring range
ON ON: 6 to 60 mV AC/DC OFF ON: 15 to 150 mV AC/DC ON OFF: 0.4 to 4 V
p
Relay working mode
ON: Normally De-Energized OFF: Normally Energized
Power ON delay
ON: 6 s ± 0.5 s OFF: 1 s ± 0.5 s
Contact input
ON: Latch function enable OFF: Inhibit function enable
Monitoring function
ON: Over current OFF: Under current
µ
24/48 VDC (+)
24/48 VDC (+)
24/48 VDC (+)
24/48 VDC (+)
24/48 VDC (+)
24/48 VDC (+)
µ
µ
4
Operation Diagrams
Power supply
Over current Under current - Latch function
Under current
Power supply
Latch ON
Set Level
Relay ON
Red LED ON
Set Level
Relay ON
Red LED ON
Power supply
Red LED ON
Set Level
Hysteresis
Hysteresis
Hysteresis
Relay ON
1 or 6 s
1 or 6 s
Over current - Inhibit function
Power supply
Inhibit ON
Set Level
Relay ON
Red LED ON
Hysteresis
1 or 6 s
1 or 6 s
DIB02, PIB02
Over current - N.D. relay
Under current - N.D. relay
Under current - Latch function - N.D. relay
Over current - Inhibit function - N.D. relay
36
80
94
28.5
63
90
22.5
80
83.5
99.5
63
28.5
Dimensions
DIN-rail
Plug-in