Carlo Gavazzi DIA01, PIA01 Technical data

Specifications are subject to change without notice (21.11.05) 1
Monitoring Relays
Product Description Ordering Key
Housing Function Type Item number Output Power supply Range
• AC/DC over current monitoring relay
• Current measured through internal shunt
• Measuring range 0.5 to 5 A AC/DC
• Adjustable current limit on relative scale
• Adjustable hysteresis
• Programmable latching at set level
• Output: 8 A SPDT relay normally de-energized
• For mounting on DIN-rail in accordance with DIN/EN 50 022 (DIA01) or plug-in module (PIA01)
• 22.5 mm Euronorm housing (DIA01) or 36 mm plug-in module (PIA01)
• LED indication for relay and power supply ON
• Galvanically separated power supply
Type Selection
Mounting Output Supply: 24 VDC Supply: 48 VDC Supply: 24/48 VAC Supply: 115/230 VAC
DIN-rail SPDT DIA 01 C 724 5A DIA 01 C 748 5A DIA 01 C B48 5A DIA 01 C B23 5A Plug-in SPDT PIA 01 C 724 5A PIA 01 C 748 5A PIA 01 C B48 5A PIA 01 C B23 5A
Input (current level) DIA01: Terminals Y1, Y2
PIA01: Terminals 5, 7
Measuring ranges
Direct Internal resistance: 0.05
Max. current: 6 A Max. current for 1 s: 25 A
Standard CT (examples) AAC
rms
Max. curr.
TADK2 50 A/5 A 5 to 50 A 60 A TAD2 150 A/5 A 15 to 150 A 180 A TAD6 400 A/5 A 40 to 400 A 480 A TAD12 1000 A/5 A 100 to 1000 A 1200 A TACO200 6000 A/5 A 600 to 6000 A 7200 A
Contact input
DIA01 Terminals Z1, Y1 PIA01 Terminals 8, 9 Disabled > 10 k Enabled < 500 Latch disable > 500 ms
Note:
The input voltage cannot raise over 300 VAC/DC with respect to ground (PIA only)
1-Phase AC/DC Over Current Types DIA01, PIA01
Input Specifications
Output SPDT relay Rated insulation voltage 250 VAC Contact ratings (AgSnO
2
Resistive loads AC 1 8 A @ 250 VAC
DC 12 5 A @ 24 VDC
Small inductive loads AC 15 2.5 A @ 250 VAC
DC 13 2.5 A @ 24 VDC
Mechanical life 30 x 106operations Electrical life 10
5
operations
(at 8 A, 250 V, cos ϕ = 1)
Operating frequency 7200 operations/h Dielectric strength
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Output Specifications
DIA 01 C B23 5A
DIA01 and PIA01 are precise AC/DC over current monitor­ing relays. Direct measuring or through current transformer. Owing to the built-in latch function, the ON-position of the relay output can be
maintained. The red LED indicates the relay status. Through the built-in shunt it is possible to monitor loads up to 5 A AC/DC.
DIA01
PIA01
2 Specifications are subject to change without notice (21.11.05)
Range Setting
Centre knob:
Setting of current on relative scale: from 10 to 110% of the full-scale value.
Hysteresis:
Approx. 4% of set value, it can be extended by inserting a resistor between terminals Z1, Y1 or 8, 9.
Approx. resistor values:
10%: 180 k 25%: 47 k 50%: 22 k 75%: 15 k Latch: < 500
DIA01, PIA01
Mode of Operation
DIA01 and PIA01 monitor both AC and DC over current through an internal shunt. They can monitor AC cur­rents up to 6000 A when connected to a suitable cur­rent transformer.
Example 1
(connection between termi­nals Z1, Y1 or 8, 9 - latch function enabled)
The relay operates and latch­es in operating position when the measured value exceeds the set level. Pro­vided that the current has dropped min. 4% below the set point (see hysteresis) the relay releases when the inter-
connection between termi­nals Z1, Y1 or 8, 9 is inter­rupted or the power supply is interrupted as well.
Example 2 (Stardard CT)
(no connection between ter­minals Z1, Y1 or 8, 9 - latch function disabled)
The relay operates when the current flowing through the transformer exceeds the set level. It releases when the current drops min. 4% below the set level (see hysteresis) or when the power supply is interrupted.
Power supply Overvoltage cat. III
Rated operational voltage (IEC 60664, IEC 60038) through terminals:
A1, A2 or A3, A2 (DIA01) 2, 10 or 11, 10 (PIA01)
724: 24 VDC ± 20%, insulated 748: 48 VDC ± 20%, insulated
B48: 24/48 VAC ± 15%
45 to 65 Hz, insulated
B23: 115/230 VAC ± 15%
45 to 65 Hz, insulated
Dielectric voltage DC supply AC supply
Supply to input 2 kV 4 kV Supply to output 4 kV 4 kV Input to output 4 kV 4 kV
Rated operational power
AC 4 VA DC 2 W
Supply Specifications
Reaction time (input signal variation from
-20% to +20% or from
+20% to -20% of set value) Alarm ON delay < 100 ms Alarm OFF delay < 300 ms
Accuracy (15 min warm-up time)
Temperature drift ± 1000 ppm/°C Repeatability ± 0.5% on full-scale
Indication for
Power supply ON LED, green Output relay ON LED, red
Environment (EN 60529)
Degree of protection IP 20 Pollution degree 3 (DIA01), 2 (PIA01) Operating temperature -20 to 60°C, R.H. < 95% Storage temperature -30 to 80°C, R.H. < 95%
Housing dimensions
DIN-rail version 22.5 x 80 x 99.5 mm Plug-in version 36 x 80 x 94 mm
Weight Approx. 150 g Screw terminals
Tightening torque Max. 0.5 Nm
acc. to IEC 60947
Approvals UL, CSA (except 748 models) CE Marking Ye s EMC
Electromagnetic Compatibillity
Immunity According to EN 61000-6-2 Emission According to EN 61000-6-3
General Specifications