Cardinal 205 Installation And Technical Manual

205
WEIGHT INDICATOR
INSTALLATION and TECHNICAL MANUAL
8200-M024-O1 Rev G 10/09 www.cardinalscale.com
Technical Support: Ph: 866-254-8261 y techsupport@cardet.com
8200-M024-O1 Rev G y 205 Installation & Technical
PO BOX 151
PH (417) 673-4631
WEBB CITY, MO 64870
Printed in USA
FAX (417) 673-5001
1
2
8200-M024-O1 Rev G y 205 Installation & Technical
TABLE OF CONTENTS
ELECTRICAL
WARNING
STATIC
SENSITVE
SPECIFICATIONS - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Page 1
Standard Features - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Page 2 Optional Features - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Page 2
Certifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Page 2 EUROPEAN DECLARATION OF CONFORMITY - - - - - - - - - - - - - - - - - - - - - - - - - - Page 3 PRECAUTIONS - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Page 4 SITE PREPARATION REQUIREMENTS - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Page 4 INSTALLATION - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Page 6
MOUNTING - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Page 6
LOAD CELL CONNECTION - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Page 7
LOAD CELL CONNECTIONS WITH OVER 30 FEET OF CABLE - - - - - - - - - - - - -Page 8
SERIAL I/O CABLE INSTALLATION - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Page 9
OPTICALLY ISOLATED INPUTS - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Page 9
MAIN PCB (Figure No. 7) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Page 10
MAIN PCB JUMPERS - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Page 11
RE-INSTALLING THE REAR PANEL - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Page 11 KEYPAD FUNCTIONS - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Page 12 ANNUNCIATORS - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Page 15 SETUP AND CALIBRATION - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Page 16 SETUP REVIEW - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Page 33 CALIBRATION "C" NUMBERS - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Page 33 ACCUMULATORS - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Page 34 BEFORE YOU CALL SERVICE - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Page 35 ERROR CODES - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Page 36 CALIBRATION SEAL INSTALLATION - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Page 38 PART IDENTIFICATION - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Page 39
APPENDIX A: MODEL 205DC - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Page 43
SERIAL NUMBER _____________________
DATE OF PURCHASE _________________
PURCHASED FROM __________________
____________________________________
____________________________________
____________________________________
RETAIN THIS INFORMATION FOR FUTURE USE
PRECAUTIONS
Before using this indicator, read this manual and pay special attention to all "WARNING" symbols:
IMPORTANT
8200-M024-O1 Rev G y 205 Installation & Technical
I
I
FCC COMPLIANCE STATEMENT
WARNING! This equipment generates uses and can radiate radio frequency and if not
installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area may cause interference in which case the user will be responsible to take whatever measures necessary to correct the interference.
You may find the booklet “How to Identify and Resolve Radio TV Interference Problems” prepared by the Federal Communications Commission helpful. It is available from the U.S. Government Printing Office, Washington, D.C. 20402. Stock No. 001-000-00315-4.
PROPER DISPOSAL
When this device reaches the end of its useful life, it must be properly disposed of. It must not be disposed of as unsorted municipal waste. Within the European Union, this device should be returned to the distributor from where it was purchased for proper disposal. This is in accordance with EU Directive 2002/96/EC. Within North America, the device should be disposed of in accordance with the local laws regarding the disposal of waste electrical and electronic equipment.
It is everyone’s responsibility to help maintain the environment and to reduce the effects of hazardous substances contained in electrical and electronic equipment on human health. Please do your part by making certain that this device is properly disposed of. The symbol shown below indicates that this device must not be disposed of in unsorted municipal waste programs.
All rights reserved. Reproduction or use, without expressed written permission, of editorial or pictorial content, in any manner, is prohibited. No patent liability is assumed with respect to the use of the information contained herein. While every precaution has been taken in the preparation of this manual, the Seller assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from use of the information contained herein. All instructions and diagrams have been checked for accuracy and ease of application; however, success and safety in working with tools depend to a great extent upon the individual accuracy, skill and caution. For this reason the Seller is not able to guarantee the result of any procedure contained herein. Nor can they assume responsibility for any damage to property or injury to persons occasioned from the procedures. Persons engaging the procedures do so entirely at their own risk.
II
II
8200-M024-O1 Rev G y 205 Installation & Technical
SPECIFICATIONS
Power Requirements: 90 to 264 VAC (50/60 Hz) at 0.4A Enclosure Type: NEMA 4X/IP66 Enclosure Size: 9 3/16" W x 7 1/2" H x 3 1/8" D
(233mm W x 191mm H x 79mm D) Weight: 8.2lbs - (9.6lb with battery) Operating Environment: Temperature: 14 to 104 ºF (-10 to +40 ºC)
Humidity: 90% non-condensing (maximum) Display: Six digit, seven segment, 0.6" high LED Transducer Excitation: (Jumper selectable) Signal Input Range: 1.0 mV min. to 40 mV max. (with dead load boost) Number of Load Cells: 8 each, 350 OHM minimum resistance Load Cell Cable Length: 1500 feet maximum. Consult factory for other requirements
Division Value: 1, 2, or 5 x 10, 1, 0.1, 0.01, 0.001 commercial
Sensitivity:
NON-COMMERCIAL NTEP CANADA OIML
Scale Divisions:
NON-COMMERCIAL NTEP CANADA
OIML Internal Resolution: 1 part in 16,777,216 Tare Capacity: Scale Capacity Sample Rate: 1 to 100 samples per second, selectable Auto Zero Range: 0.5 or 1 through 9 divisions Weighing Units: Tons, Pounds, Pounds-Ounces, Ounces,
Keypad: Color coded Membrane type, 7 keys Standard I/O: (1) bi-directional RS232 (20mA)
Battery Operation: 205EU - CAM-350 Type, 12V 2Ah
12 VDC 8 VDC with battery operation (jumper selectable)
30 feet maximum without sense lines
0 to 99, non-commercial
0.15 uV/e
0.3uV/e (Class III/IIIL)
0.3uV/e (Class III/IIIHD)
0.7 uV/e (Class III)
100 to 240,000 100 to 10,000 (Class III/IIIL) 100 to 10,000 (Class III/IIIHD) 100 to 10,000 (Class III)
Metric Tons, Kilograms, Grams
(1) output only RS232 (20mA)
CAUTION: RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE OF USED BATTERIES ACCORDING TO THE INSTRUCTIONS.
ATTENTION: RISQUE D'EXPLOSION SI LA BATTERIES EST REMPLACE'E PAR UN TYPE INCORRECT. REJETEZ LES BATTERIES UTILISE'ES SELON LES INSTRUCTIONS.
8200-M024-O1 Rev G y 205 Installation & Technical
1
SPECIFICATIONS, CONT.
Standard Features:
• Push button tare function
• Gross, tare, net conversion
• Selectable key lockout
• Hi-Resolution mode
• Adjustable filtering
• Gross and Net accumulators
• Dual serial ports
• Remote input lines for Zero, Tare, Gross and Print (1000 feet maximum)
• Programmable print format using Visual Print or nControl (2 Visual Tickets available)
• SMA level 2 compliant serial communications (For more information see http://www.scalemanufacturers.org)
• Field re-programmable via PC interconnection
• Test feature (performs display and internal tests)
• Auto Shutoff and Sleep modes
• Battery operation (Requires additional hardware and includes additional documentation)
Optional Features:
Analog Output*, Allen-Bradley Interface*, 10/100 mbps Ethernet Adapter*, Additional Serial Port*, Internal Relay Box*, External Relay Box*, Special Filtering, and Column Mounting
*This feature requires additional hardware and includes additional documentation.
Certifications:
This equipment is certified to comply with the requirements for a Class III/IIIL device by the
National Conference on Weights and Measurements (Certificate No. 01-011)
Measurement Canada (Approval No. AM-5397)
And for a Class III device by OIML R-76 (Certificate No. DK 0199.47).
2
8200-M024-O1 Rev G y 205 Installation & Technical
EUROPEAN DECLARATION OF CONFORMITY
Manufacturer: Cardinal Scale Manufacturing Company
PO Box 151 203 East Daugherty Webb City, Missouri 64870 USA Telephone No. (417) 673-4631 Fax No. (417) 673-5001
Product: Non-automatic Weight Indicating Instrument
Model Numbers 200, 205, 210, 210FE, 215, 220 and 225 Serial Number EXXXYY-ZZZ
where XXX = day of year
YY = last two digits of year ZZZ = sequential number
The undersigned hereby declares, on behalf of Cardinal Scale Manufacturing Company of Webb City, Missouri, that the above-referenced product, to which this declaration relates, is in conformity with the provisions of:
European Standard EN 45501: 1992 and equivalent International Recommendation OIML R76, edition 1992 EU Type Approval Certificate Number DK 0199.159 Report No. DANAK-1910304
Council Directive 2006/95/EC Low Voltage Directive as amended by Council Directive 93/68/EEC (22 July, 1993)
Council Directive 90/384/EEC (20 June, 1990) on the Harmonization Of the Laws of Member States relating to non-automatic weighing Systems as amended by: Council Directive 93/68/EEC (22 July, 1993)
European Standard EN50082: 1995 for radiated emissions and European Standard EN50082-2: 1995 Class B for EMC immunity.
The Technical Construction File required by this Directive is maintained at the corporate headquarters of Cardinal Scale Manufacturing Company, 203 East Daugherty, Webb City, Missouri.
____________________
Ginger Harper Director, Quality Assurance
8200-M024-O1 Rev G y 205 Installation & Technical
3
Static Electricity
CAUTION! This device contains static sensitive circuit cards and components.
Improper handling of these devices or printed circuit cards can result in damage to or destruction of the component or card. Such actual and/or consequential damage IS NOT covered under warranty and is the responsibility of the device owner. Electronic components must be handled only by qualified electronic technicians who follow the guidelines listed below.
ATTENTION! ALWAYS use a properly grounded wrist strap when handling, removing or installing electronic circuit cards or components. Make certain that the wrist strap ground lead is securely attached to an adequate ground. If you are uncertain of the quality of the ground, you should consult a licensed electrician.
ALWAYS handle printed circuit card assemblies by the outermost edges. NEVER touch the components, component leads or connectors. ALWAYS observe warning labels on static protective bags and packaging and never component from the packaging until ready for use. ALWAYS store and transport electronic printed circuit cards and components in anti-static protective bags or packaging.
SITE PREPARATION REQUIREMENTS
PRECAUTIONS
remove the card or
The Cardinal 205 indicator is a precision weight-measuring instrument. As with any precision instrument, it requires an acceptable environment to operate at peak performance and reliability. This section is provided to assist you in obtaining such an environment.
Environmental
The Model 205 indicator meets or exceeds all certification requirements within a temperature range of 14 to 104 °F (-10 to +40 °C).
In order to keep cooling requirements to a minimum, the indicator should be placed out of direct sunlight and to provide adequate air circulation, keep the area around the indicator clear.
Make certain the indicator is not directly in front of a heating or cooling vent. Such a location will subject the indicator to sudden temperature changes, which may result in unstable weight readings.
Insure that the indicator has good, clean AC power and is properly grounded.
In areas subject to lightning strikes, additional protection to minimize lightning damage, such as surge suppressors, should be installed.
4
8200-M024-O1 Rev G y 205 Installation & Technical
SITE PREPARATION REQUIREMENTS
Electrical Power
The 205 indicator has been designed to operate from 90 to 264 VAC at 50/60 Hz. Note that a special order is not
CAUTION! - To avoid electrical hazard and possible damage to the indicator, DO NOT, under any circumstance, cut, remove, alter, or in any way bypass the power cord grounding prong.
The socket-outlet supplying power to the indicator should be on a separate circuit from the
distribution panel and dedicated to the exclusive use of the indicator.
The socket-outlet shall be installed near the equipment and shall be easily accessible.
Note that the power cord on the 205 (without the Battery Option) serves as the power disconnect.
The wiring should conform to national and local electrical codes and ordinances and should
be approved by the local inspector to assure compliance.
On installations requiring 230 VAC power, it is the responsibility of the customer to have
a qualified electrician install the proper power cord plug that conforms to national electrical codes and local codes and ordinances.
Electrical Noise Interference
To prevent electrical noise interference, make certain all other wall outlets for use with air conditioning and heating equipment, lighting or other equipment with heavily inductive loads, such as welders, motors and solenoids are on circuits separate from the indicator. Many of these disturbances originate within the building itself and can seriously affect the operation of the indicator. These sources of disturbances must be identified and steps must be taken to prevent possible adverse effects on the indicator. Examples of available alternatives include isolation transformers, power regulators, uninterruptible power supplies, or simple line filters.
required for operation at 230 VAC.
Transient Suppression
The following recommendations will help to reduce transients:
y Always use shielded cables to connect signal wires to the weight indicator.
y Secure the cables in the cable clips provided inside the indicator.
y Connect the cable shield (indicator end only) to a ground point inside the indicator. Keep
wires that extend beyond the shield as short as possible.
y Do not run load cell or signal cables from the weight indicator along side or parallel to
wiring carrying AC power. If unavoidable, position the load cell and signal cables a minimum of 24" away from all AC wiring.
y Always use arc suppressors across all AC power relay contacts (see recommendations at
http://www.paktron.com/pdf/Quencharch_QRL.pdf
y Use zero voltage switching relays, optically isolated if possible.
).
8200-M024-O1 Rev G y 205 Installation & Technical
5
INSTALLATION
Battery Access Cover
Load Cells
Before beginning installation of your Model 205 Weight Indicator, make certain that the indicator has been received in good condition. Carefully remove the indicator from the shipping carton and inspect it for any evidence of damage (such as exterior dents or scratches) that may have taken place during shipment. Keep the carton and packing material for return shipment if it should become necessary. It is the responsibility of the purchaser to file all claims for any damages or loss incurred during transit.
Mounting
NOTE! Should your 205 indicator come already installed on a scale, the following information
describing the installation of the indicator does not apply.
The Model 205 indicator is housed in a NEMA 4X/IP66 stainless steel wall or desk-mount enclosure. The gimbal may be mounted on a desktop or other smooth, flat, horizontal surface or may be mounted on a wall. Refer to Figure No. 1 for a layout of wall-mounting bolts.
+
If wall mounted, make certain the mounting surface is strong enough to support the indicator. The mounting location should be where the display is easily viewed while being close enough to provide the operator easy access to the keypad. Carefully lay out the mounting hole locations, then drill and install the anchor bolts. Attach the gimbal to the wall and securely tighten the retaining bolts.
6.00"
Clearance for #10 size screw
+
Figure No. 1
6
8200-M024-O1 Rev G y 205 Installation & Technical
Figure No. 2
INSTALLATION, CONT.
Load Cell Connection
CAUTION! Disconnect any external load cell power supply before connecting
load cells to the indicator. Failure to do so will result in permanent damage to the indicator.
Load Cell Cable Connection for RFI Suppression
The load cell cable should be routed through the special metallic gland connector and the shield wire must be connected to this gland connector for grounding and to eliminate RFI. Refer to Figure No. 2 and Figure No. 3 for the appropriate gland connector.
1. If using a battery, remove the three acorn nuts securing the Battery Access Cover to the bottom of the indicator and remove the battery.
2. After removing the battery, remove the 12 acorn nuts securing the back panel to main housing.
3. Loosen and remove the metal gland connector nut and remove the plastic insert.
4. Route the load cell cable through the nut and plastic insert and into the enclosure.
5. With the load cell cable routed into the enclosure, remove approximately 18 to 20 inches of the outer insulating jacket from the cable exposing the internal wires.
6. Cut the shield wire so that it extends past the outer jacket approximately 3/4 inch.
7. Remove 1/4" of insulation from the end of each of the 4 wires (without sense leads) or 6 wires with sense leads (refer to figure No. 4).
8. Connect each of the wires to terminal block P1 referring to labels on circuit board for terminal connections. Refer to Figure No. 7 for terminal block location.
9. To terminate a wire, press down on release bar for the terminal, insert wire into terminal opening then allow release bar to return to its original position, locking wire in place. Repeat procedure until all wires are in place.
10. Route load cell cable wires through the two cable clips provided on upper and left sides of enclosure interior.
Figure No. 3
Figure No. 4
TERMINAL NO. Function TERMINAL NO. Function
1 + EXCITATION 5 - SIGNAL 2 + SENSE 6 - SENSE 3 + SIGNAL 7 - EXCITATION
NOTE! If the sense leads are NOT used, you must install plug-in jumpers at J4 and J5 adjacent to the terminal block. These jumpers attach the sense leads to the excitation leads. If sense leads ARE used (as in motor truck scales), these plug-in jumpers should be positioned on one plug-in pin only or removed and stored for later use (see Figure No. 8).
8200-M024-O1 Rev G y 205 Installation & Technical
LOAD CELL TERMINAL BLOCK P1
7
INSTALLATION, CONT.
Load Cell Cable Shield Wire Connection for RFI Suppression
1. After all terminations have been made, remove the excess cable from the enclosure.
2. Referring to Figure No. 5, fold the shield wire back over the plastic insert and then insert the plastic insert (with the shield wire) into the gland connector.
3. The shield wire is secured when tightening the gland connector nut.
4. Do not over-tighten the connector but make certain it is snug.
5. DO NOT USE TOOLS! Finger tighten only!
Load Cell Cable Connection (Standard Gland Connector)
The following instructions describe the load cell connection should it be desired to route the load cell cable through a standard gland connector. If a standard gland connector is used, the shield wire should be connected to the threaded stud inside the indicator enclosure.
1. Remove the 12 acorn nuts securing the back panel to main housing, then loosen a gland connector for the load cell cable. Refer to Figure No. 2 for illustration of connector layout.
2. Slip the single cable from the load cell or load cell junction box through the gland connector and into the enclosure.
3. Remove 3" of the outer insulation jacket then remove 1/4" of insulation from each of the 4 wires and shield (without sense leads) or 6 wires and shield (with sense leads). Refer to Figure No. 4.
4. Connect each of the wires to terminal block P1 referring to labels on circuit board for terminal connections. Refer to Figure No. 7 for terminal block location.
5. To terminate a wire, first press down on release bar for the terminal, insert wire into terminal opening then allow release bar to return to its original position, locking wire in place. Repeat procedure until all of wires are in place.
6. Route load cell cable through the two cable clips provided on upper and left sides of enclosure interior.
Figure No. 5
Load Cell Cable Shield Wire Connection (Standard Gland Connector)
The load cell cable shield wire should be connected to the threaded stud inside the indicator. This stud is located on the top inside of the indicator near the load cell connector P1. See Figure No.6.
The shield wire should be wrapped around the stud between the 2 flat washers and secured using hex nut.
Load Cell Connections With Over 30 Feet Of Cable
For installations with over 30 feet of cable between the indicator and the load cells, sense wires should be used. The sense wires must be connected between the +SENS, -SENS terminals on the indicator and the +EXCITATION, -EXCITATION wires of the load cells or the +SENS, -SENS terminals of the load cell trim board or the section seal trim board.
8
8200-M024-O1 Rev G y 205 Installation & Technical
Threaded Stud
P1 Load Cell
Figure No. 6
INSTALLATION, CONT.
Serial I/O Cable Installation
The 205 indicator may be connected to a printer to record weight and associated data or it may be connected to a remote display or even to a computer for transmission of weight data. The weight data may be transmitted on demand (pressing the PRINT key or on receipt of a command from the computer). Refer to the Setup, SIO Serial I/O section of this manual.
1. Remove the 12 acorn nuts securing the back panel to main housing, then loosen a gland connector for the serial cable. Refer to Figure No. 2 for illustration of connector layout.
2. Slip the serial cable through the gland connector and into the enclosure.
3. Remove 2" of the outer insulation jacket then remove 1/4" of insulation from each of the wires (refer to Figure No. 4).
4. Connect each of the wires to the Serial Data terminal block (P11) referring to Figure No. 7 for terminal block locations.
5. To terminate, first press down on the release bar for the terminal, insert the wire into the opening then allow the release bar to return to its original position, locking the wire in place. Repeat the procedure until all of the wires are in place.
BI-DIRECTIONAL SERIAL INTERFACE SERIAL OUTPUT
TERMINAL NO.
1 TXD 1 - RS232 5 TXD 2 - RS232 2 RXD 1 - RS232 6 TXD 2 – 20 mA Active 3 TXD 1 – 20 mA Active 7 GROUND 4 GROUND
Function TERMINAL NO. Function
Optically Isolated Inputs
Included with the I/O are 4 programmable inputs that may be used to remotely (up to 100 feet) initiate various functions within the indicator. These inputs are accessed via a terminal block (P9) on the back of the PC board (see Figure No. 7). The 4 inputs are defined as follows:
TERMINAL NO.
1 Gross 2 Print 3 Zero 4 Tare 5 Common
NOTE! The input must be connected to Gnd to initiate the function.
Function
8200-M024-O1 Rev G y 205 Installation & Technical
9
Main PCB
INSTALLATION, CONT.
10
8200-M024-O1 Rev G y 205 Installation & Technical
Figure No. 7
INSTALLATION, CONT.
Main PCB Jumpers
J1 – BATTERY CHARGE MODE
Place jumper J1 in the F only recharging the battery pack when it is low. Place jumper J1 in the T operating the indicator from commercial power and using the battery pack to supply power only in the event of a power loss.
J2 – AUTO-ON JUMPER
The AUTO-ON jumper J2, when connected, will cause the indicator to power on automatically whenever power is applied to the power input connector. If power is lost momentarily and then reapplied, the indicator will turn on without pressing the ON key.
J3 – 8V EXCITATION JUMPER
The 8V EXCITATION jumper J3, when connected, sets the load cell excitation voltage to 8V for operation with the 12 VDC battery. To operate from the 12 VDC battery, the load cell excitation voltage MUST be set to 8 VDC (J3 closed). Battery operation with the load cell excitation voltage set to 12V will result in an unstable weight display.
J4 AND J5 – SENSE JUMPERS
If the sense leads are NOT used, you must install plug-in jumpers at J4 and J5 adjacent to the terminal block. These jumpers attach the sense leads to the excitation leads. If sense leads ARE used (as in motor truck scales), these plug-in jumpers should be positioned on one plug­in pin only or removed and stored for later use.
ull position when operating the indicator totally from battery power and
rickle position when
J10 – DEAD LOAD BOOST JUMPER
For very low dead loads (less than 10% of the combined load cell capacity) connect the dead load boost jumper J10 on the printed circuit board.
J11 – 12V PWC SRC (SOURCE)
The J11 jumper, when connected (CLOSED) supplies 12 VDC @ 25mA from the 205 indicator to a solid-state relay or other load of 200 ohms or greater. When J11 is OPEN (positioned on one plug-in pin only or removed), the 12 to 24 VDC must be provided from an external source to P10-6. The load must still be 200 ohms or greater.
Re-Installing The Rear Panel
After all terminations have been made, remove the excess cable from the indicator enclosure and securely tighten each of the cable gland connectors. Do not over-tighten these connectors but make certain they are snug. DO NOT USE TOOLS! Finger tighten only! Insure any unused gland connectors are plugged.
1. Make certain no cables or wires are exposed between the main housing and rear panel and then place the rear panel onto the main housing.
2. Secure with the 12 acorn nuts removed earlier. Follow a diagonal pattern when tightening the acorn nuts.
3. If using a battery, slide the battery into the opening, until you feel resistance and the edge of the battery is flush with the bottom of the indicator.
4. Replace the Battery Access Cover and install the three acorn nuts removed earlier, securing the battery in place.
8200-M024-O1 Rev G y 205 Installation & Technical
11
KEYPAD FUNCTIONS
The Model 205 is equipped with a 7-key keypad. The keypad is used to enter commands and data into the indicator. This section describes each key along with its normal function. It is helpful to refer to the actual indicator while reading this section.
Figure No. 8
DO NOT operate the keypad with pointed objects (pencils, pens, etc). Damage to keypad resulting from this practice is NOT covered under warranty.
ON/OFF KEY
This key performs two functions. Pressing it when the indicator is off will apply power to the indicator. If the indicator is already on, pressing this key will turn the indicator off.
ZERO KEY/
REVIEW
Pressing this key will cause an immediate zeroing of the weight display up to the selected limit of 4% or 100% of the scale’s capacity. This selection is made during the setup and calibration of the indicator. Note the indicator will not respond to this command unless the weight display is stable.
Pressing the ASTERISK key before the ZERO KEY/
REVIEW key will enter the Review
mode of Setup and Calibration. Refer to the Setup Review section of this manual.
TARE/
ENTER
Pressing the TARE key alone will store the current gross weight as the new tare weight and the weight display will change to the net weight display mode (
Pressing the ASTERISK key before the TARE/
ENTER key serves two purposes. First,
when reviewing setup parameters, pressing the TARE/ current setting of the parameter. Second, the TARE/
Net annunciator will turn on).
ENTER key will display the
ENTER key is used to signal
completion of the entry of data and causes the indicator to process the data entered.
12
8200-M024-O1 Rev G y 205 Installation & Technical
Loading...
+ 36 hidden pages