CAPTRON CHT1, CHT1-5 Operating Instructions

Page 1
CHT1
CHT1
Original Operating Instructions
Original Operating Instructions
CHT1-1 / CHT1-5
CHT1-1 / CHT1-5
Page 2
This manual has been written for technicians/installers and operators and should be kept for future reference. Read these operating instructions carefully and make sure that you have fully understood the contents before installing or working with the CHT1.
TIP

Safety

General safety

All work on electrical systems or operating equipment may only be carried out by a specially qualified electrician according to the applicable electrotechnical regulations.
The safety of the system in which the SENSORswitch is integrated is the responsibility of the operator.
Page 3

Notes and symbols used

Warning notes in relation to personal injury / material damage are formulated according to the "SAFE” principle. This means they contain information on the type and source of the hazard, potential consequences as well as how to avoid and avert danger. The following hazard classifications apply in the safety notes:
DANGER
Danger designates a hazardous situation, which, if ignored, will lead to death or serious injury. The symbol next to the warning indicates the type and source of the danger.
WARNING
Warning designates a hazardous situation, which, if ignored, may lead to death or serious injury. The symbol next to the warning indicates the type and source of the danger.
Page 4
CAUTION
Caution designates a hazardous situation, which, if ignored, may lead to injury. The symbol next to the warning indicates the type and source of the danger.
NOTICE
Notice designates a situation, which may cause material damages and impair the product’s function if attention is not paid.
TIP
Tip provides additional useful information about the handling of the product.
Symbol Meaning
4
Avoiding and adverting danger in the warning note
Page 5
Symbol Meaning
►
Instructions for action All instructions to be followed within a procedure are
■
always listed in chronological order.
List
WARNING
Improper work on electrical systems!
Electric shock can result in death or life-threatening injuries.
4
Before working on electrical systems, disconnect them from their voltage supply and secure them against being switched on again.
4
Work on electrical installations should be carried out only by qualified personnel in compliance with local and national electrical regulations and specifications.
Page 6

Personnel qualifications

A qualified electrician is a person with suitable technical training, expertise and experience as well as knowledge of relevant standards, who can evaluate the work assigned to them correspondingly and recognize potential risks.

Intended use

The SENSORswitch is intended for use in accordance with the items listed here, the values from the “Technical specifications” chapter and the product description.
■
Only connect the product to a limited energy source as per IEC 61010 or an NEC class 2 power supply unit.
■
Source current < 4 A at maximum operating voltage.

Reasonably foreseeable misuse

The switch is not suitable for:
Page 7
•
use as a safety component in accordance with Machinery Directive 2006/42/EC.
•
use outdoors.
•
use in potentially explosive atmospheres.

Technical specifications

Operating voltage 10…30 V
Load current max. 400 mA
Output PNP-NO
Output pulse optionally dynamic CHT12
Reverse polarity protection Protection of all cables/lines
Short circuit protection Protected against short circuit and
Voltage drop optionally dynamic
Power consumption Max. 20 mA at 24 V / Max. 20 mA at 24
Operating temperature -30...+70°C
Constant signal when actuated approx. 300 ms Toggle flip flop
overload
Max. 2 V at 400 mA Max. 2 V at 200 mA
V
Page 8
Degree of protection IP Front IP69K
Type of actuation Capacitive
Actuation force No actuation force required
max. altitude 2000 m above sea level with "CSA
Relative air humidity Max. 95%, non-condensing
listing"

Connections

CHT1-_7_...
200 mm single strands with wire end ferrules Wire end ferrules with plastic collars DIN 46228 Wire cross-section strands 0.15 mm
2
Page 9
CHT1-_9_...
Plug M12, 4-pin
CHT1-_9_...
Plug M12, 5-pin
CHT1-_K_...
Terminal strip, 5-pin
CHT1-_5_...
Plug M8, 3-pin
CHT1-_5_...
Plug M8, 4-pin
CHT1-_5_...
Plug M8, 5-pin
Page 10

Connection plan

PNP-NO
+VDC
0V
3
4
1
brown
blue
black
LED1
LED2
Load
PNP-NO, 3-pin
Page 11
PNP-NO, 4-pin
3
4
2
1
+VDC / LED1
+VDC
0V
PNP-NO
white
brown
black
LED1
LED2
blue
Load
LED1
LED2
+VDC / LED2
+VDC / LED1
PNP-NO
0V
+VDC
3
4
5
1
2
white
grey
brown
black
blue
Load
PNP-NO, 5-pin
Dimensional drawing
Example representation plug, M8 4-pin
Page 12
All dimensions in mm
CHT1-1_9
CHT1-5_9
Page 13
CHT1-1_8
CHT1-1_8/CPM20
Page 14
CHT1-6_8
Drilling pattern
Page 15

General description

The supplied switch can have options that differ from those shown in this manual. This does not affect the function. The CHT1 is equipped with two different colored LEDs. The LEDs are actuated differently depending on the pin configuration.

Assembly

Requirements: Mounting surface is level and clean.
► Disconnect the system from its voltage
supply and secure it against being switched on again.
► Set the desired position of the
SENSORswitch and drill the hole according to the drilling pattern.
► Unscrew the lock nuts (B) from the
SENSORswitch (A).
► Insert the SENSORswitch into the
prepared hole and screw the lock nuts (B) back on.
Page 16
► Position the SENSORSwitch (A) and
tighten the lock nuts with max. 1 Nm.
► Connect the SENSORswitch (A)
electrically according to the connection plan.

Maintenance

Carry out the following maintenance operations at the specified intervals.
Operation as needed annually
Clean the switch surface X
Check cable for integrity
Check screw connection for tightness
X
X
Page 17
NOTICE
Solvents contained in cleaning agents can attack the plastic of the button!
4
Clean the surface of the button with a neutral cleaning agent or a damp microfiber cloth.

Disassembly

► Disconnect the system from its voltage supply and secure it
against being switched on again.
► Disconnect the electrical connection and remove the lock nuts.

Disposal

Different types of electrical and electronic components must be recycled according to their type. All applicable statutory, state and local laws and regulations must be complied with.
Page 18

Manual updates

CAPTRON reserves the right to make changes to the contents of this manual as needed. The most current version can be found on our website www.captron.com .

Imprint

The operating instructions have been authored and published by
CAPTRON Electronic GmbH
Johann-G.-Gutenberg-Straße 7
82140 Olching – Germany
Tel.: +49 (0)8142 - 44 88 - 160
www.captron.com
Copyright 2020
CHT1 ohne Relais 1.4