CaptiveAire C-TPF Installation Manual

TECHNICAL MANUAL
FOR
INSTALLATION, OPERATION
Effective Date: 12-04
AND MAINTENANCE
OF
THE CAPTIVE-AIRE
MODEL "C-TPF" SERIES
POLLUTION CONTROL UNITS
W ARNING
Improper installation, adjustment, alteration service or main­tenance can cause property damage, injury or death. Read the installation, operation and maintenance instructions thor­oughly before installing or servicing this equipment. Only trained and qualified service personnel should install or ser­vice this equipment.
CAPTIVE-AIRE SYSTEMS, INC.CAPTIVE-AIRE SYSTEMS, INC.
CAPTIVE-AIRE SYSTEMS, INC.
CAPTIVE-AIRE SYSTEMS, INC.CAPTIVE-AIRE SYSTEMS, INC.
360 NORTHBROOK DRIVE • YOUNGSVILLE, NC 27596 USA
PHONE: 919-554-2414 • TOLL FREE: 866-784-6900 • FAX: 919-554-9374
email:webhome@captiveaire.com • www.captiveaire.com
2
TECHNICAL MANUAL
FOR
INSTALLATION, OPERATION
AND MAINTENANCE
OF
THE CAPTIVE-AIRE
MODEL “C-TPF” SERIES
POLLUTION CONTROL UNITS
WITH CFM-100 SERIES MONITORING STATION
Published by:
CAPTIVE-AIRE SYSTEMS, INC.
Y oungsville, North Carolina 27596
U.S.A.
First Printing: December, 2004
© Copyright 2004, Captive-Aire Systems, Inc.
ALL RIGHTS RESERVED. NO PART OF THIS BOOK MAY BE REPRO­DUCED, STORED IN A RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORM BY AN ELECTRONIC, MECHANICAL, PHOTOCOPYING, RECORD­ING MEANS OR OTHERWISE WITHOUT THE WRITTEN PERMISSION OF CAPTIVE-AIRE SYSTEMS, INC. COPYRIGHT 2004.
The manufacturer reserves the right to modify the materials and specifications resulting from a continuing program of product improvement or the availability of new materials.
The Captive-Aire Unit is designed and engineered by
CAPTIVE-AIRE SYSTEMS, INC.
360 Northbrook Drive, Y oungsville, North Carolina 27596.
3
TABLE OF CONTENTS
INTRODUCTION ..........................................................................................5
SPECIFICATIONS ....................................................................................6-7
MODEL NUBER EXPLANA TION.................................................................8
TYPICAL INST ALLA TION .............................................................................9
SAMPLE C-TPF CONFIGURA TIONS ...................................................10-11
RECEIVING & INST ALLA TION ...................................................................12
EQUIPMENT LIFTING PROCEDURE ........................................................13
ASSEMBLING RSPC HOUSING ON UNITS SPLIT FOR SHIPMENT....14-15
CFM-100 MONITORING ST A TION (P ARTS)..........................................16-17
ODOR CONTROL SECTION ................................................................18-21
EXHAUST F AN SECTION ....................................................................22-23
NAMEPLATE DATA...................................................................................24
OPERA TING MA TRIX ................................................................................25
PRESSURE SWITCH TUBING DIAGRAM .................................................2 6
MAINTENANCE.........................................................................................27
CFM-100 TERMINAL VOL TAGES .............................................................28
WIRING DIAGRAM.....................................................................................29
PARTS-MISCELLANEOUS ......................................................................30
ST ART -UP INSTRUCTIONS.......................................................................31
C-TPF ST ART -UP INSPECTION REPORT ................................................32
WARRANTY........................................................................Inside back cover
4
INTRODUCTION
ir quality is a major concern in many large cities world
A
wide, particularly in America. As a result, many com­mercial kitchens will require pollution control equipment in their exhaust systems to comply with the increasing demands of environmental control agencies. In addition, pollution control equipment is being used for kitchens in high-rise buildings al­lowing the exhaust to discharge out the side of the structure which saves the cost of running the duct up many floors to the roof.
Smoke pollution control, in kitchen exhaust systems, has typi­cally been accomplished by any one of the following methods: gas fired incinerators, scrubbers, filtration units or electrostatic precipitators (C-ESP). Incinerators and afterburners literally burn the pollutants and, while effective, can be very costly and haz­ardous to operate. Scrubbers consist of a water bath and ex­traction baffles to remove the pollutants and, though quite effec­tive on grease removal, they typically require the addition of high efficiency filters to abate smoke below control agencies’ standards. Filtration units use a series of impingement filters to remove the pollutants and if done properly can be quite effective on both smoke and grease.
Captive-Aire offers two types of pollution control equipment: the C-TPF Series (triple pass filter) detailed in this manual and the C-ESP Series (electrostatic precipitator) detailed in the C-ESP Series brochure. When initial cost is a greater concern, the C-TPF unit is a sound alternative.
The C-TPF unit is available in several configurations, as il­lustrated on the following pages, ranging in capacity from 1000 to 32,000 CFM (472 to 15,102 L/s). Most models can include an exhaust fan and odor abatement equipment as an option.
Basic Facts About Smoke
Smoke particles are extremely small and not visible to the human eye unless thousands of them are grouped together to form what we see as smoke. Individual particles are mea­sured in units called microns and one micron equals 1/25,400 of an inch (1/64,516 of a cm).
Smoke generated by commercial cooking equipment has a particulate size of between 0.3 and 0.8 microns and it is these very small particles that smoke abatement equipment must remove from the airstream. The amount of smoke be­ing discharged from a kitchen exhaust duct is measured in terms of its density, referred to as opacity - the degree to which emissions block light. A 100% opacity level would be solid black and 0% would be perfectly clear. Control agen­cies that have adopted smoke pollution ordinances are re­quiring an opacity level of no more than 20%, which is a very light blue smoke.
Typically, heavy smoke producing cooking such as char­broiling, creates an opacity level of 60% to 70%. Opacity readings are taken by the human eye by viewing the smoke being discharged and then assigning a percentage of opac­ity to what is seen. Though this method is quite subjective, it is the method practiced by control agency inspectors who are trained and certified in determining opacity percentages. Other more technical methods of determining opacity or par-
ticulate density are achieved through the use of opacity meters and cascade impactors. This level of analysis is usually re­ferred to as source testing. Control agencies occasionally require this type of analysis and if so, the testing is con­ducted by state certified contractors which can be quite costly and time-consuming. The efficiency of a C-TPF is based on how well it reduces the opacity level of a given airstream.The Captive-Aire unit will reduce the opacity level below 20%, thereby meeting the requirements of environmental control agencies.
Basic Facts About Odor
Cooking odors (molecules) generated by the combustion of animal and vegetable matter result in an extremely complex mixture of reactive organic gases (ROG’s). A small percentage of these odors may be absorbed by the grease particles but the vast majority exist separately in the airstream. The ROG mol­ecules are much too small to be removed by any type of filter and therefore, other methods must be used. There are several meth­ods with which to manage the odor. One method is to use a media bed. The two most popular types of media bed are acti­vated charcoal, which absorbs and retains the odor molecules, and the use of an odor-oxidant media (potassium permangan­ate) which oxidizes the molecules to solids and then retains them. The other method involves the use of a liquid delivered with a finely atomized spray. This spray performs a similar function to potas­sium permanganate in that it adsorbs or chemically neutralizes odors. This process has the benefit of the end user being able to adjust the amount of spray and thus the effectiveness and cost of the odor control.
The life of the media bed type of odor control is dependent upon several factors such as how much media is used, type of odor, amount of odor molecules, grease loading and air temperature. Typically, any of the above mentioned types of media can remove 85% - 90% of the molecules. Determining the efficiency of odor control can be very subjective, as testing is usually conducted by the human nose. More scientific test­ing is available through ROG analysis, but this involves con­siderable costs.
Grease Removal - The Important First Step
Grease particles are also measured in terms of microns and grease generated by commercial cooking equipment has a particulate size of 10 microns and up. Pollution control equip­ment is not limited to removing smoke particles, but will also remove a majority of the grease particles remaining in the airstream. Therefore, the grease extraction efficiency of the exhaust hood plays an important role in the operation and performance of pollution control equipment.
Removal of grease particles before they reach smoke and odor control equipment will significantly increase the smoke abatement efficiency and the life of the odor abatement me­dia. It is highly recommended that a Captive-Aire Ventilator be used with the C-TPF unit as it has a grease extraction effi­ciency of 95%. Other high efficiency exhaust hoods and stan­dard filter type hoods may be used with the unit. Contact Cap­tive-Aire Systems for details.
5
SPECIFICATIONS
General
Furnish one (1) Captive-Aire Pollution Control Unit model C­TPF series as manufactured by Captive-Aire Systems, Inc. of Y oungsville, North Carolina in accordance with the following:
The pollution control unit shall consist of a smoke control section, odor control section (optional) and an exhaust fan section (optional) all built on a common base as an integral unit. Smoke control shall be accomplished by a three stage high efficiency filter section (C-TPF). The unit shall be ETL listed and labeled.
Smoke Control Section
The smoke control section shall have three phases of filters The filters shall consist of replaceable 30% pre-filter, 95% bag filter and a replaceable 99% final filter. Replaceable fil­ters shall be mounted in filter slide tracks to prevent air by­pass around the ends of the installed filter bank. Filters shall be accessed through removable side access panels with lift and turn latches.
Phase one filters shall have an average efficiency of 25 to 30% and an average arrestance of 90 to 92% in accordance with ASHRAE test standard 52.1-1992. Media support grid shall be on 1" centers with an open area 96%. Filter enclos­ing frame shall be a rigid, high wet strength beverage board, with diagonal support members 4" deep.
Phase two filters shall have an average efficiency of 90 to 95% in accordance with ASHRAE test standard 52.1-1992. Sealing surface and pocket retainers shall be configured to provide 84% open area. Seams in bag filters shall be sealed with foamseal adhesive to completely eliminate air leakage through stitch holes.
Phase three filters shall be 95% efficient on .03 micron par­ticles (DOP smoke test), 97% efficient on nebulized staphy­lococcus aerosols, 99+% efficient on atmospheric test dust (ASHRAE standard 52.1-92). The casing shall be 16 gauge steel with corrugated aluminum separators to insure media stability. Media shall be fine-fiber, high strength microfiberglass paper. Media end cut s shall be encapsulated in urethane potting adhesive.
Fire Detection
A thermostat, set at 250o F, shall also be located in the filter section to shut down the exhaust fan in the event of a fire.
Optional Fire Damper for use in Canada
The unit shall include a UL listed fire damper, with a 280o F fusible link, located downstream of the filters to prevent pas­sage of fire to the duct downstream of the unit
Filter Monitoring Panel
A monitor panel, for remote location, shall be supplied for the operation and monitoring of the unit. The panel shall be con­structed of 18 gauge stainless steel, number 4 finish, and be suitable for surface or recessed mounting. The panel face shall be a hinged door with a lift and turn flush latch. The panel shall include an air proving time delay , relays and indi­cator lights to continuously monitor the unit. Indicator lights shall be “Fan On”, “Normal Air”, “Low Air”, “Replace Pre-Fil­ters”, “Replace Bag Filters”, “Replace Final Filter”, “Missing
Filter”, and “Fire In Unit”. An audible alarm, with an alarm cancel button, shall be included and shall activate whenever the unit status is low air, replace filters, missing filters or fire in the unit. Status other than “Fire In The Unit” shall not shut down the exhaust fan.
Specifier Note: If the C-TPF unit is used in conjunction with a water wash ventilator, the monitor p anel is built into the main water wash control cabinet model CGPC-6000 series.
Odor Control Options
Media bed of 50/50 Blend Potassium Permanganate and
Carbon Blend
The unit shall be provided with odor control utilizing a media bed of 50% potassium permanganate 50% carbon blend. The odor removal media shall be housed in slide out reusable steel modules. There shall be a 30% pleated media after filter lo­cated immediately downstream of the odor control media. Re­placeable filters shall be mounted in filter slide tracks to pre­vent air bypass around the ends of the installed filter bank. The odor control media and after filters shall be removable through side access doors with lift and turn latches.
Spray Odor Control
The unit shall be provided with a spray odor control system utilizing an odor neutralizer chemical. The odor spray con­trol cabinet shall be mounted on the side of the unit and shall contain a liquid spray compressor piped to the spray nozzle in the fan plenum, adjustable delay timers with fuse protected circuitry factory wired to the unit electrical panel. The cabinet shall include one 5 gallon container of Formula GS-710 Odor Neutralizer. The cabinet shall cont ain a heater to prevent freezing of the odor neutralizer.
Exhaust Fan Options
Exhaust Fan (Standard Centrifugal Fan)
The unit shall include a centrifugal exhaust fan. The exhaust fan shall be an SWSI upblast arrangement #9 or #10 with a non-overloading BI or AF wheel. The motor, drives, bearings and fan mounting base shall be located out of the exhaust air stream as required by the IMC (International Mechanical Code) and NFP A-96. The fan shall be AMCA certified and bear the AMCA seal for performance. The fan housing shall be constructed of heavy gauge steel. The fan bearings shall be heavy duty self-aligning pillow block type rigidly mounted on heavy structural steel supports. The motor shall be ODP three phase mounted on a common base with the fan and shall be pre-wired to the electrical cabinet located on the unit. The electrical cabinet shall include a disconnect switch, motor starter, overloads and fuses. The factory provided drive assembly shall be adjustable pitch on 5 HP and smaller, fixed pitch on 7.5 HP and larger . It shall also be sized for a minimum 1.5 service factor. After final system balancing, fixed pitch sheaves shall be provided and installed by the air balancing contractor to provide proper flow at actual installed conditions.
Exhaust Fan (Optional Tubular Fan)
The unit shall include a tubular centrifugal exhaust fan. The exhaust fan shall be an arrangement #10 with a non-overload­ing BI, AF wheel. The motor, drives, bearings and fan mounting
6
SPECIFICATIONS
base shall be located out of the exhaust air stream as required by the IMC (International Mechanical Code) and NFPA-96. The fan shall be AMCA certified and bear the AMCA seal for perfor­mance. The fan housing shall be constructed of heavy gauge steel. The fan bearings shall be heavy duty rigidly mounted on heavy structural steel supports. The motor shall be ODP three phase mounted on a common base with the fan and shall be pre-wired to the electrical cabinet located on the unit. The electri­cal cabinet shall include a disconnect switch, motor starter, over­loads and fuses. The factory provided drive assembly shall be adjustable pitch on 5 HP and smaller and fixed pitch on 7.5 HP and larger. It shall also be sized for a minimum 1.5 service factor. After final system balancing, fixed pitch sheaves shall be pro­vided and installed by the air balancing contractor to provide proper flow at actual installed conditions.
Exhaust Fan Housing
The exhaust fan section of the unit shall be enclosed with the same material as the smoke control section. There shall be a removable panel for access to the fan.
Unit Construction
The unit housing shall be constructed of a minimum of 16 gauge G90 bright galvanized steel. The perimeter base shall be 12 gauge formed channel with lifting lugs at each corner and along the length as required. The internal housing shall be externally welded liquid tight for compliance to the Inter­national Mechanical Code and NFPA-96 grease duct con­struction requirements.
Fire Extinguishing System Options
Specifier Note: NFPA-96 requires a fire extinguishing sys­tem for protection of the smoke and odor control sections and protection of the duct down stream of any filters or damp­ers. Not all authorities having jurisdiction require protection. Check with your AHJ. If required, specify one of the following systems.
Wet chemical system
Provide a complete factory mounted Ansul wet chemical fire extinguishing system, including nozzles piping and detec­tion runs. Pipe penetrating the unit cabinet shall use a UL listed fitting. System shall be installed in accordance with the systems listing and NFP A-96. The Ansul Automan cabi­net shall be mounted on the side of the unit for easy access, certification and service.
Water spray sprinkler fire system
Specifier Note: Units that are located indoors may be factory pre-piped for a wet pipe building sprinkler system.
Check Out and Demonstration
Upon completion of installation, the entire pollution control system, including the kitchen exhaust hoods, shall be com­missioned by a factory certified service technician. Start-up shall include checking all filters, filter monitoring station, odor control and exhaust fan. The appropriate maintenance per­sonnel shall be given a technical manual and a complete demonstration of the system, including operation and main­tenance procedures. Upon completion of the commission­ing, a detailed start-up report shall be made available to the architect and owner certifying proper system operation. Changes required in fan drive components shall be performed by the air balancing contractor under the direction of the fac­tory certified person(s) performing the start-up.
FIL TER MONITORING ST A TION
CFM-100
Green Green Clear
Clear
Clear
Clear
Red Red
Red
Provide a pre-piped water spray fire system installed in accor­dance with NFP A-96. The unit shall be piped with one pen­dent type sprinkler nozzle located in the smoke control sec­tion, one in the odor control section, if equipped with 50/50 media bed, and one in the exhaust fan section for interconnec­tion to the building sprinkler system by the appropriate trades. Pipe penetrating the unit cabinet shall use a UL listed fitting. Nozzles shall be the bulb type rated at 325o F.
7
MODEL NUMBER EXPLANATION
The assigned model number of a C-TPF unit will indicate the number of Filter Banks and if it has spray odor control, single or double pass odor control, if it has an exhaust fan plus other data. The following example shows the make-up of a model number .
The model number of your unit along with other data can be found on the nameplate which is attached to the electrical control panel on the unit. Refer to page 24.
Standard Prefix Series of ClearAirTM System (Remote Smoke Pollution Control)
Triple Pass Filter
Filter Configuration (W x H) - 1x1, 2x1, 3x1, 2x2, 3x2, 4x2, 3x3, 4x3, 3x4, 4x4
Odor Control Option: SO = Single Pass Odor Control DO = Double Pass Odor Control SPO = Spray Odor
T otal CFM (1000 - 32,000)
Exhaust Fan Option: EFS = Exhaust Fan, unhoused, spring isolated EFN = Exhaust Fan, unhoused, not spring isolated
EFHS = Exhaust Fan, housed, spring isolated EFHN = Exhaust Fan, housed, not spring isolated
(BLANK) = No Exhaust Fan
Fan T ype = C (Centrifugal), T (T ubular)
Fan Size (ie. 100 - 490)
Fan Motor H.P. (ie. 1 - 75)
Hand - R = Right Hand
L = Left Hand
C - TPF - 3x2 - DO - CFM - EFN - C - 300 - 15 - R
BLOCK 1 2 3 4 5 6 7 8 9
All Blank, if no exhaust fan
8
TYPICAL INSTALLATION
9
SAMPLE C-TPF CONFIGURATIONS
The C-TPF unit is available in sizes ranging in capacity from 1000 to 32,000 CFM (472 to 15,102 L/s). Each unit is equipped with Three Phase Filters for smoke control, and may include an exhaust fan, odor abatement equip­ment and Quencher System, or Ansul System as an op­tion. The following illustrations are examples of the most common configurations.
C-TPF
SMOKE CONTROL ONL Y
KEY
AF = 30% After Filter BF = 95% Bag Filter DO = Double Pass Odor
Kor48/Carbon blend EF = Exhaust Fan–un-housed EFH = Exhaust Fan–housed
FD = Optional Curtain Fire
Damper FF = 99% Final Filter PF = 30% Pre-Filter SO = Single Pass Odor
Kor48/Carbon blend SPO = Spray Odor Cabinet
AF
C-TPF-SO
SMOKE CONTROL
WITH SINGLE PASS MEDIA BED ODOR CONTROL
C-TPF
SMOKE CONTROL
WITH PLENUM
C-TPF-DO
SMOKE CONTROL
WITH DOUBLE P ASS MEDIA BED ODOR CONTROL AND
OPTIONAL FIRE DAMPER
O
C-TPF-SPO
SMOKE CONTROL WITH SPRA Y ODOR CONTROL
AND OPTIONAL FIRE DAMPER
(Remote Fan)
10
C-TPF-EF
C-TPF-SO-EF
SAMPLE C-TPF CONFIGURATIONS
KEY
AF = 30% After Filter BF = 95% Bag Filter DO = Double Pass Odor
Kor48/Carbon blend EF = Exhaust Fan—un-housed EFH = Exhaust Fan—housed
SMOKE CONTROL WITH EXHAUST F AN
AND OPTIONAL FIRE DAMPER
FD = Optional Curtain Fire
Damper FF = 99% Final Filter PF = 30% Pre-Filter SO = Single Pass Odor
Kor48/Carbon blend SPO = Spray Odor Cabinet
C-TPF-DO-EFH
C-TPF-SPO-EF
SMOKE CONTROL WITH SINGLE P ASS MEDIA
BED ODOR CONTROL, EXHAUST FAN
AND OPTIONAL FIRE DAMPER
H
SMOKE CONTROL WITH DOUBLE P ASS MEDIA BED
ODOR CONTROL, EXHAUST FAN
AND OPTIONAL FIRE DAMPER
O
SMOKE CONTROL WITH SPRA Y ODOR CONTROL, EXHAUST
FAN AND OPTIONAL FIRE DAMPER
11
Loading...
+ 23 hidden pages