Cannon Fitzroy canterbury Installation Instructions Manual

Page 1
INBUILT MODELS
INSTALLATION
Pa rt No : F389 3
Revision A -
Cannon
Cannon
This heater is approved for use with
Gmk10025 Gmk10112
AS4553:2008
Natural or Propane gases.
INSTALLATION INSTRUCTIONS
FOR FITMENT INTO A
COMBUSTIBLE ENCLOSURE
TO SUIT MOCK FIREPLACE
INSTALLATIONS
with heater installation instructions
MOCK FIREPLACE
INSTRUCTIONS
FITZROY
FITZROY
CANTERBURY
Page 2
CONTENTS
ITEM PAGE.
Page 9.
INSTALLATION ADVICE OR TECHNICAL ISSUES
SAMPFORD IXL
ON
PH: 1300 727 421
or
FAX: 1300 727 425
CONTACT:
INSTALLATION INTO A COMBUSTIBLE ENCLOSURE
MOCKKITRO ( SINGLE SKIN FLUE )
METHOD B
METHOD.
Pag
General
e 1
P
Mock fireplace enclosure recommendations
age 2
Mock cavity dimensions - Fitzroy
age 3
P
Overall dimensions of heater cabinet Page 4
Fitment of spacer brackets and blanket Page 5
Installation into wall cavity - Method A Page 6 & 7MOCKKITRA
P
Installation into combustible cavity ­Method B
MOCKKITRO
age 8 & 9
1. Mark out vertical centre-line of flue outlet on rear of enclosure.
2. Mark out horizontal centre-line of heater flue outlet on rear of enclosure utilise support brackets to support flue spigot mounting bracket.
3. Measure distance required to engage flue outlet to flue spigot once installed. Tighten adjustment screws as required.
WALL
SUPPORT BRACKETS
FLUE SPIGOT
25 mm FROM COMBUSTIBLES
WALL
36 mm
600 mm
554 mm
Page 3
INSTALL BLANKET
GENERAL
Page 1.
INSTALLATION INTO A COMBUSTIBLE ENCLOSURE
MOCKKIT12 w/ ( SINGLE SKIN FLUE )
METHOD B
FIG 7.
600 mm BETWEEN TOP OF COWL AND NEAREST PART OF ROOF
FLUE COWL APPROVED TO AG604
FLUE CLAMP
FLASHING
ROOF CLADDING
R EA
FT RS
PROVIDE CLEARANCE AROUND CEILING JOISTS
FALSE ENCLOSURE BY OTHERS TO NORMAL BUILDING PRACTICE
MAINTAIN 25mm CLEARANCE FROM ALL COMBUSTIBLES
INSULATION
BLANKET
HEATER
100 mm DIA SINGLE SKIN FLUE
FIT TWO LENGTHS OF VERTICAL FLUE (1.8 M) BEFORE FITTING ANY BENDS. IF BENDS ARE USED, FIT INSIDE OF FLUE PIPE. USE NO MORE THAN TWO BENDS IN THE TOTAL FLUE RUN AND MAINTAIN AT LEAST 250 mm OF STRAIGHT FLUE PIPE BETWEEN THE BENDS.
410 mm MAX
MAKE SURE THERE IS ADEQUATE VENTILATION IN ROOM.
FLUSH WITH INNER ENCLOSURE
FLUE TO BE SUPPORTED INDEPENDENTLY OF THE APPLIANCE FLUE CONNECTION.
This heater shall only be installed by an authorised person. This appliance shall be installed in accordance with the manufacturers installation instructions. Australian Standard 5601, municipal building codes, electrical wiring regulations and any other statutory regulations must be adhered to.
To conform with the gas space heater approval requirements the spacers must be permanently fitted to maintain the required clearance from combustible materials.
These instructions are to be read in conjunction with the heater installation booklet.
The heater must be installed correctly to provide safe and reliable operation.
Please take the time to read these instructions and to familiarise yourself with the correct installation methods.
Correct flue design and allowance for ventilation must be considered.
Avoid the use of flue bends if possible.
Make sure that the heater is fully commissioned and be certain to conduct a test of the integrity of the flue operation. Take into account any influences created by range hoods, exhaust fans, central heating etc.
Always allow for the complete removal of the heater without any difficulties. Make sure that the flue is rigid and self supporting. The bottom length of the flue must fit firmly to the adapting spigot piece. When using rectangular flueing the flue adapting piece must be a slip fit over the rectangular spigot fitted to the heater.
To avoid any unnecessary delays and inconvenience to your customer, please contact our technical support section if the installation is unusual and requires further advice or assistance.
Page 4
STUD
STUD
C.L. OF
HEATER
345 mm TO 610 mm
FLUE OPENING
GAS INLET
325 mm
246 mm
45 mm
30 mm
538 mm
FLUE OPENING DETAIL
METHOD A
600 mm MIN BETWEEN TOP OF COWL AND NEAREST PART OF ROOF
75 mm MAIN STUD WALL
ADJUSTMENT STRAP
HEADER
TWIN SKIN FLUE
TOP PLATE FLUE SUPPORT
FLUE ADAPTER
FLASHING
FLUE CLAMP
FLUE COWL APPROVED TO AG604
ROOF CLADDING
100 mm DIA FLUE PIPE
MAINTAIN 25 mm CLEARANCE BETWEEN FLUE AND WOODWORK
WALL CLADDING
12 mm FROM BOTTOM OF WALL CLADDING TO TOP OF HEATER
MEASURE DISTANCE FROM FLOOR TO TOP OF HEATER FLUE OUTLET PLUS 2 mm
COWL
FIT 3 SCREWS
SMALL DIA END WITH SWAGE
TOP PLATE FLUE SUPPORT
FLUE ADAPTER
SINGLE SKIN FLUE
Page 2.
Page 7.
FIG 6.
MOCK FIREPLACE ENCLOSURE RECOMMENDATIONS
FIG 1.
300mm MAX
2400mm MAX
550mm MAX
MAKE SURE THERE IS ADEQUATE VENTILATION IN ROOM.
The enclosure can be fabricated using any standard building materials, providing that spacer brackets are fitted to the heater to provide adequate clearances to combustible materials. (see Fig 5).
The area of the cavity must not exceed our dimensions as shown in the diagram. (see Fig 1). If the enclosure is larger than our dimensions allow, a separate boxed section around the heater will need to be constructed.
The heater must sit on a solid, sealed base and the enclosure must be sealed from any draughts and be insulated as necessary to eliminate low temperatures.
An enclosure constructed to an existing room with a solid floor and ceiling, and any other enclosure must have the same characteristics of being sealed from any draughts and suitably insulated from low temperatures. Failure to adhere to this requirement will result in unreliable operation or failure to operate correctly and is not covered by our warranty conditions.
CANTEBURY WITH RECTANGULAR FLUE ADAPTOR FITTED
Page 5
Page 6.
Page 3.
INSTALLATION INTO WALL CAVITY. ( TWIN SKIN FLUE )
METHOD A
METHOD.
MOCK CAVITY DIMENSIONS - FITZROY INBUILT
HEIGHT 630 mm to 640mm
WIDTH 730 mm to 750 mm
CLEARANCE FROM COMBUSTIBLES
FIG 2.
DEPTH OF CAVITY = HEATER + ADAPTOR + FLUE CLEARANCE
MIN 495 mm = 345mm + 125mm + 25mm MAX 550 mm = 345mm + 125mm + 80mm
1. Cut flue opening central to wall studs in the wall cladding.
2. Cut away top wall plate and any existing noggins between studs.
3. Cut clearance hole for 100mm diameter flue pipe in the roof.
4. Fit header assembly into flue opening leaving a 12mm gap between top of the header assembly and wall cladding as shown. (see Fig 6).
5. Drill 4 holes through header flanges at stud centres and use clouts or screws to attach to the wall.
6. Measure distance from floor to top of flue outlet of the heater.
7. Adjust elbow to the distance measured plus 2mm and tighten screw. Ensure flue elbow is horizontal.
8. Bend tabs in at the base of the twin skin flue and lower twin skin flue down the wall cavity.
9. Slide top plate flue support over twin skin flue, centralise and nail to the top plate.
10. Slide flue adapter inside inner skin at top of twin skin flue.
11. Fit small end of the 100mm dia flue pipe into flue adapter. Fit further lengths with small end downward as required. (The small end has a swage 35mm from the end).
12. Flash between flue pipe and roof cladding using either lead flashing or an approved silicone rubber pipe flashing boot.
13. Fit cowl to the top of the flue pipe, align the screw holes and fasten the 3 screws supplied.
The minimum wall cavity depth required is 450mm. Select a pair of studs in front of which the heater is to be installed. The gap between the studs should be no less than 345mm and no greater than 610mm. Ensure ceiling and roof members will not obstruct vertical path of flue.
Between heater cabinet and other combustible surfaces.
*20mm clearance from both top and side surfaces.
*50mm clearance from rear.
*100mm clearance between side of the heater front and combustibles.
Additional clearances are specified in the heater installation instruction booklet.
Page 6
FITMENT OF SPACER BRACKETS AND BLANKET.
FLUE OUTLET (HEATER SUPPLIED)
OVERALL DIMENSIONS OF THE HEATER CABINET.
(SEE FIG 3 AND 4. )
735mm
FIG 4.
FIG 3.
Page 4.
* WIDTH 735 mm(INCLUDING SPACERS)
620 mm
380mm
470mm
100mm
CLEARANCE FROM COMBUSTIBLES 25mm
FLUE SPIGOT
SUPPORT BRACKET
FLUE SPIGOT MTG BRKT
WHEN FLUE SPIGOT ENGAGED
Page 5.
FIXING SCREWS No8 x 3/8" SELF TAPPING
TOP & SIDE BRACKETS
FIG 5.
DIAGONAL CORNERS
REAR BRACKETS
1. Fit top and side brackets to heater cabinet on diagonal corners as shown each side. (see Fig 5). Use existing screw positions.
2.
When using twin skin flue (Method A):
3. Remove the flue outlet supplied with heater and replace with flue outlet supplied with mock kit.
Position insulation blanket on heater top aligned with edges. Secure with aluminium tape (see Fig 5).
4. Fit rear spacer brackets to heater cabinet on diagonal corners
as shown (see Fig 5). Use existing screw positions.
(SEE FIG 3 AND 4. )
Page 4.
* HEIGHT 620 mm 620mm(INCLUDING SPACERS)
* WIDTH 735 mm(INCLUDING SPACERS) * DEPTH mm 342 mm(WHEN FLUE SPIGOT ENGAGED) 387
Page 5.
FIXING SCREWS No8 x 3/8" SELF TAPPING
TOP & SIDE BRACKETS
FIG 5.
INSULATION
BLANKET
DIAGONAL CORNERS
SECURE INSULATION BLANKET TO TOP OF HEATER USING ALUMINIUM TAPE
REAR BRACKETS
FITZROY CANTERBURY