CANNON
CANTERBURY INBUILT
CANTIB-02-NG AND CANTIB-02-LP
TO SUIT MOCK FIREPLACE INSTALLATIONS
INSTALLATION INSTRUCTIONS FOR FITMENT
INTO A COMBUSTIBLE ENCLOSURE
This heater is for use with Natural and Propane gases.
Read these instructions in conjunction with heater
installation instructions
SPACE
HEATER
GAS LOG
FIRE
![](/html/8f/8f74/8f745f037bc06cccd90ec92d409e69ff4a7444ee931bd01d225312dd6faf3cc3/bg2.png)
CONTENTS
ITEM PAGE.
Pag
GENERAL e 1
P
MOCK FIREPLACE ENCLOSURE RECOMMENDATIONS age 2
MOCK CAVITY DIMENSIONS age 3
P
4
ag
OVERALL DIMENSIONS OF INSERT CABINET P e
ge
FITMENT OF SPACER BRACKETS AND BLANKET Pa 5
INSTALLATION INTO WALL CAVITY - METHOD A Page 6 & 7
P
INSTALLATION INTO COMBUSTIBLE CAVITY - METHOD B age 8
P
MAINTENANCE age 9
![](/html/8f/8f74/8f745f037bc06cccd90ec92d409e69ff4a7444ee931bd01d225312dd6faf3cc3/bg3.png)
GENERAL
THIS HEATER SHALL ONLY BE INSTALLED BY AN AUTHORIZED
PERSON. THIS APPLIANCE SHALL BE INSTALLED IN ACCORDANCE
WITH THE MANUFACTURERS INSTALLATION INSTRUCTIONS.
AS 5601, MUNICIPAL BUILDINGS CODES, ELECTRICAL
WIRING REGULATIONS AND ANY OTHER STATUTORY
REGULATIONS.
TO CONFORM WITH THE AGA APPROVAL REQUIREMENTS
THE SPACERS MUST BE PERMANENTLY FITTED TO MAINTAIN THE
REQUIRED CLEARANCE FROM COMBUSTIBLE MATERIALS.
THESE INSTRUCTIONS TO BE READ IN CONJUNCTION WITH THE
HEATER INSTALLATION BOOKLET.
THIS HEATER MUST BE INSTALLED CORRECTLY TO PROVIDE
SAFE AND RELIABLE OPERATION.
PLEASE TAKE THE TIME TO READ THESE INSTRUCTIONS AND TO
FAMILIARIZE YOURSELF WITH THE CORRECT INSTALLATION
METHODS.
CORRECT FLUE DESIGN AND ALLOWANCE FOR VENTILATION
MUST BE CONSIDERED.
AVOID THE USE OF FLUE BENDS IF POSSIBLE.
ALWAYS ALLOW FOR THE COMPLETE REMOVAL OF THE HEATER
WITHOUT ANY DIFFICULTIES AND MAKE SURE THAT THE FLUE IS
RIGID AND SELF SUPPORTING. THE BOTTOM LENGTH OF THE FLUE
MUST FIT INSIDE OF THE ADAPTING PIECE. THE FLUE
ADAPTING PIECE MUST BE A SLIP FIT OVER THE RECTANGULAR
SPIGOT ON THE HEATER.
MAKE SURE THAT THE HEATER IS FULLY COMMISSIONED AND
BE CERTAIN TO CONDUCT A TEST OF THE INTEGRITY OF THE
FLUE OPERATION, TAKING INTO ACCOUNT ANY INFLUENCES
CREATED BY RANGE HOODS, EXHAUST FANS, CENTRAL HEATING
ETC.
TO AVOID ANY UNNECESSARY DELAYS AND INCONVENIENCE TO
YOUR CUSTOMER, LEASE CONTACT OUR TECHNICAL SUPPORT
SECTION IF THE INSTALLATION IS UNUSUAL AND REQUIRES
FURTHER ADVICE OR ASSISTANCE.
SPIGOT
Page 1.
![](/html/8f/8f74/8f745f037bc06cccd90ec92d409e69ff4a7444ee931bd01d225312dd6faf3cc3/bg4.png)
Page 2.
FIG 1.
MOCK FIREPLACE ENCLOSURE RECOMMENDATIONS
THE ENCLOSURE CAN BE FABRICATED USING ANY MATERIALS
PROVIDING THAT SPACER BRACKETS ARE FITTED TO THE HEATER
PROVIDING ADEQUATE CLEARANCES TO COMBUSTIBLE MATERIALS.
(SEE FIG 5)
THE AREA OF THE CAVITY MUST NOT EXCEED OUR DIMENSIONS AS
SHOWN IN THE DIAGRAM. (SEE BELOW)
IF THE ENCLOSURE IS LARGER THAT OUR DIMENSIONS ALLOW, A
SEPARATE BOXED SECTION AROUND THE HEATER WILL NEED TO BE
CONSTRUCTED.
THE HEATER MUST SIT ON A SOLID, SEALED BASE AND THE
ENCLOSURE MUST BE SEALED FROM ANY DRAUGHTS AND BE
INSULATED AS NECESSARY TO ELIMINATE LOW TEMPERATURES.
OUR BROCHURE ILLUSTRATES AN ENCLOSURE CONSTRUCTED TO
AN EXISTING ROOM WITH A SOLID FLOOR AND CEILING, ANY OTHER
ENCLOSURE MUST HAVE THE SAME CHARACTERISTICS OF BEING
SEALED FROM ANY DRAUGHTS AND SUITABLY INSULATED FROM
LOW TEMPERATURES. FAILURE TO ADHERE TO THIS REQUIREMENT
WILL RESULT IN UNRELIABLE OPERATION OR FAILURE TO OPERATE
CORRECTLY AND IS NOT COVERED BY OUR WARRANTY CONDITIONS
300mm MAX
2400mm MAX
550mm MAX