Camille Bauer SINEAX B 812 Operating Instructions Manual

14
Operating Instructions Transmitter
Power Supply Unit SINEAX B 812
B 812 Be 152 025-01 11.05
Camille Bauer LTD Aargauerstrasse 7 CH-5610 Wohlen/Switzerland Phone +41 56 618 21 11 Fax +41 56 618 35 35 e-mail: info@camillebauer.com http://www.camillebauer.ch
Contents
1. Safety instructions ......................................................................... 1
1.1 Symbols ...............................................................................1
1.2 Proper use ........................................................................... 1
1.3 Qualifications of the personnel ............................................1
1.4 Repairs and modifications ................................................... 1
2. Short description ........................................................................... 1
3. Indicator LEDs ............................................................................... 1
4. Installation instructions .................................................................. 2
5. Mounting the device ...................................................................... 2
6. Removal of the device ................................................................... 2
7. Dimension drawings ...................................................................... 2
8. Electrical connections ...................................................................2
8.1 Connection without HART® terminal .................................... 2
8.2 Connection with HART® terminal ......................................... 2
9. Commissioning .............................................................................. 3
10. Technical data ...............................................................................3
10.1 Input .....................................................................................3
10.2 Intrinsically safe input (Ex version) .......................................3
10.3 Output .................................................................................. 3
10.4 Accuracy .............................................................................. 3
10.5 Power supply ....................................................................... 3
10.6 Transfer ................................................................................ 3
10.7 Galvanic isolation .................................................................3
10.8 Ambient conditions .............................................................. 3
10.9 Various ................................................................................. 3
11. Versions ......................................................................................... 4
12. Maintenance .................................................................................. 4
13. Declaration of conformity ..............................................................4
1. Safety instructions
1.1 Symbols
The symbols used in this operating instruction indicate dangers and they have the following meanings:
Non-compliance could result in functional failures.
Non-compliance could result in functional failures and injury to personnel.
1.2 Proper use
The device is a transducer power supply for the safe isolation of 4…20 mA signal circuits.
The device is intended for mounting in industrial installations and fulfils the requirements according to EN 61010-1.
The manufacturer is not liable for damage that is caused by improper handling, modifications, or improper use.
Optional with intrinsically safe input (blue terminals).
This is an “associated apparatus” and must not be installed in
explosion hazardous areas. The output is not intrinsically safe.
1.3 Qualifications of the personnel
Mounting, installation, and commissioning must only be carried out by properly trained and authorized personnel, who have read and understood these operating instructions.
1.4 Repairs and modifications
Repairs and modifications must only be carried out at our factory. The housing must not be opened. There are no configuration or adjusting elements inside the housing.
We reserve the right to make changes to improve the product.
2. Short description
The device supplies the passive 2-wire transducer (4…20 mA) which is connected to the input with a DC voltage, and transmits the signal current galvanically isolated 1:1 to the output. The current in the output circuit is also supplied by the device. Therefore a passive signal receiver (4…20 mA) must be connected.
The device is transparent for HART® signals in both directions. The 250 resistor integrated in the output circuit permits communication with SMART transmitters.
Open circuit and short circuit in the input circuit are indicated locally by a red LED.
The device is single channel execution and is suitable for mounting on a top-hat rail.
3. Indicator LEDs
There are two LEDs on the front of the device, which have the following meaning:
Marking Color Meaning
ON Green
The LED is on when the power supply is on
Red
The LED is on when the signal is outside the normal measuring range of 4…20 mA
Fig. 1
12. Maintenance
The device is maintenance free. Recalibration of the measured signal is not possible.
13. Declaration of conformity
11. Versions
Device Ex-versions [EEx ia] IIC
Power supply Connection terminals Order number 60 – 253 V AC / 125 V DC not plugable 155 102 60 – 253 V AC / 125 V DC plugable 155 144 20 – 70 V AC/DC not plugable 155 095 20 – 70 V AC/DC plugable 155 136
Device standard versions
Power supply Connection terminals Order number 60 – 265 V AC/DC not plugable 155 087 60 – 265 V AC/DC plugable 155 128 20 – 70 V AC/DC not plugable 155 079 20 – 70 V AC/DC plugable 155 110
The instruments must only be disposed of in the correct way!
32
4. Installation instructions
The maximum ambient temperature must be obser­ved.
There must be sufficient circulation of air. Neighboring devices that produce heat must be mounted
at a suitable distance. The preferred mounting method is on a horizontal rail. The device must be protected from vibrations.
8. Electrical connections
Terminals without internal connections (1, 2, 3, 6 and 12) must remain free and must not be used for other purposes.
Ex devices may only be operated with a DC power supply of upto Um = 125 V DC.
5. Mounting the device
The SINEAX B 812 device is mounted on a top-hat rail. Snap the device housing onto the top-hat rail (EN 50 022) (see Fig. 2).
Fig. 2. Mounting on a top-hat rail 35 ×15 or 35×7.5 mm.
6. Removal of the device
Remove the device from the top-hat rail as shown in Fig. 3.
Fig. 3
7. Dimension drawings
Fig. 4. The SINEAX B 812 in a top-hat rail housing P12/17 mounted on a top-hat rail (35 × 15 mm or 35 × 7.5 mm to EN 50 022) with fixed connection screw
terminals.
63
69.2
17.5
114
Fig. 5. The SINEAX B 812 in a top-hat rail housing P12/17 St mounted on a top-hat rail (35 × 15 mm or 35 × 7.5 mm to EN 50 022) with plug-in connection screw
terminals.
63
85
17.5
114
5
4
10
11
9
8
7
Two-wire
transmitter
B 812
DCAC–N+
L
Signal
receiver
+
+
8.2 Connection with HART® terminal
5
4
10
11
9
8
7
Two-wire
transmitter
B 812
DCAC–N+
L
Signal
receiver
HART®­Terminal
+
+
For the cor rect functioning o f the communicatio n, a 250 communication resistor is required in series with the measuring circuit. Please observe that the maximum load on the B 812 output resulting from additional devices and the resistance of the wires is not exceeded.
Internal communication resistor
External communication resistor
5
4
10
11
9
8
7
B 812
DCAC–N+
L
HART®­Terminal
250
+
+
Two-wire
transmitter
Signal
receiver
9. Commissioning
The installation and wiring must be checked before commissioning, and in particular the permitted power supply voltage must be checked (see the rating label).
10. Technical data
10.1 Input
Signal range 4…20 mA Power supply voltage (I = 20 mA) 18.0 V ± 1 V No-load voltage (I = 0 mA) 25.5 V ± 1 V Short circuit current limitation 25 mA ± 2 mA Source resistance 330 ± 5 Open circuit detection 3.5 mA ± 0.1 mA Short circuit detection 21.2 mA ± 0.2 mA
10.2 Intrinsically safe input (Ex version)
Provisional data
U
o
28,2 V
I
o
95 mA
P
o
0.67 W Type of protection [EEx ia] IIC Marking
II (1) GD
10.4 Accuracy
Reference conditions
Tamb = 23°C, load = 300 Warm up time 20 minutes Power supply = 24 V DC or 230 V AC Range = 16 mA 100%
Error tolerance incl. linearity error under reference conditions
± 0.2%
Effect of output load < 0.1% Temperature effect < 0.1% / 10°K Effect of power supply < 0.05%
10.5 Power supply
Universal power supply for DC and AC
Low-range version
High-range version
Voltage range AC/DC (absolute limits)
20 – 70 V 60 – 265 V *)
Switching-on current Î / τ
2.5 Â / 1.0 ms at 24 V DC
20 Â / 0.15 ms
at 325 V DC Frequency range AC 45 … 400 Hz Power consumption max. 3 VA / 2.4 W
*) Voltages > 125 V DC require external protection with max. 10 A trip current. For the Ex version, the data in the EC type examination certi­ficate are valid (Um = 253 V AC or 125 V DC).
10.6 Transfer
Signal current over-range 10 % Response time < 0.3 ms HART
®
Transparent for HART® signals in both directions
10.3 Output
Signal range 4…20 mA No load voltage (I = 0 mA) 17.0 V ± 1 V Internal
communication resistor Rc
250
Permitted load
0…750 0…500 (via Rc)
10.7 Galvanic isolation
All three circuits (input / power supply / output) are galvanically isolated from each other.
Electrical safety
To IEC / EN 61010-1 Double isolation Measuring and overvoltage category III
Contamination level 2 Working voltage < 300 V Test voltage 3.6 kV / 50 Hz / 1 minute
10.8 Ambient conditions
Operating temperature – 20 … +50 °C Storage temperature – 20 … +70 °C Rel. humidity avarage 75% Protection type IP 20, EN 60 523 EMV EN 61 000-6-2 / -4
10.9 Various
Weight 100 g Terminal cross section 2.5 mm
2
Plug-in terminals (alternative)
Coded to prevent incorrect connection
1 2 3
4 5
6
7 8
9
10 11 12
Fig. 6. Arrangement of the terminals
8.1 Connection without HART® terminal