Camden Door Controls CX-93M-12LS User Manual

This Package Includes:
#8 x 8” Self Tapping Screws
M5 x 8 Flatwashers
Specifications
CX-93M-12LS
Electromagnetic Shear Lock
Installation Instructions
Shear Holding Force
Voltage Input
Current Draw
Lock and Armature Gap
Operating Temperature
Door Monitor Contact Rating
Lock Dimensions
Armature Dimensions
Important Notice:
Up to 1200lbs. (545kg)
12VDC / 24VDC
310mA / 180mA
5/64” (2mm)
-4°F to 122°F (-20°C to +50°C)
0.5A @ 28V DC
7 1/4” L x 1 3/16” W x 1” D (181mm x 30mm x 25mm)
7 1/4” L x 1 3/16” W x 3/4” D (181mm x 30mm x 20mm)
Basic Installation Concept & Accessories
Electromagnetic Shear Lock Diagram
Magnetic Contact
Assembled Armature Plate Horizontal Diagram
1. Open pocket hole for armature plate in the door frame using the sticker template provided.
2. Attach the armature plate to the door with the hardware provided to right.
4. Mortise a hole in the door frame for the lock (7 1/4”L x 1 3/8”W x 1”D)
Page 1 of 2
Kick Off Button
Magnet
3/4”
(20mm)
CX- 93M-12LS Electromagnetic Shear Lock
General Installation Steps and Maintainance:
1. Mark a center line on the door header frame, where the assembled armature is to be installed.
2. Cut and drill according to the size of the mounting bracket.
3. Connect wiring according to wiring instruction shown below; then mount the shear lock and assembled armature onto the door frame and door.
4. For a wider gap between the door & door frame, use steel
at washers to adjust the gap between lock and armature.
5. Connect the power wires according to the instructions and test the system.
6. It is recommended to apply a light coat of silicon lubricant to the mating surfaces on a monthly basis to prevent rust.
Flat Washer
Flat Washer
Gap 5/64” (2mm)
(25mm)
1”
7 1/4”
(181mm)
6 5/8”
(168mm)
7 1/4”
(181mm)
6 5/8”
(168mm)
1 3/16”
(30mm)
5/8”
(16mm)
1 3/16”
(30mm)
5/8”
(16mm)
Flat Washer
Flat Washer
NOTE: Flat washers are only used to adjust armature magnet when the door frame has more than a 5/64” (2mm) gap.
Setting
24 VDC Setting
IMPORTANT!
Set the jumper position according to the power input before turning ON the power.
12 VDC
Time SW1 SW2
3 ON ON
6 ON OFF
9 OFF ON
12 OFF OFF
+
1
ON
2
-
C N.C
12 / 24 VDC Power Input
Door Monitoring Sensor Output
N.O
Push Buttons Keypads
5502 Timberlea Blvd., Mississauga, ON Canada L4W 2T7
Strikes
Magnetic Locks Key Switches Relays & Timers Access Control
www.camdencontrols.com Toll Free: 1.877.226.3369
File: CX-93M-12LS ManualR1.indd Revised: 06/02/2018 Part No.: 40-82B214
Page 2 of 2