Camden Door Controls CX-1000-77 User Manual

5502 Timberlea Blvd. Mississauga, Ontario L4W 2T7 905-366-3377 Toll Free: 877-226-3369 www.camdencontrols.com
CX-1000/77 Maximinder
Instructions
FEATURES
Dip switch programmable Adjustable delay from 1 second to 4 hours LED status indicator shows when relay is energized
ELECTRICAL SPECIFICATIONS
Operating voltage: 12 or 24 VDC (Cut Jumper) Relay: DPDT 4 amps at 24 VDC Current consumption: Idle 12mA, operating 60mA
Note: Trigger requires ground input to activate
DIP SWITCH SETTINGS
S1 - Changes the state of the relay. In the off position the relay is as shown. On position the relay mode is reversed OFF position N/C = N/C, ON position N/C = N/O S2 - Determines the switch type for the trigger input OFF requires N/O, ON requires N/C S3 - Determines if the time selected is in seconds or minĀ­utes ON = Minutes, OFF = Seconds
S4 - Determines if the cycle is repeated ON =Cycle repeated OFF =Cycle not repeated S5 - 1 second or minute S9 - 16 seconds or minutes S6 - 2 seconds or minutes S10 - 32 seconds or minute S7 - 4 seconds or minutes S11- 64 seconds or minutes S8 - 8 seconds or minutes S12- 128 seconds or minutes
Example: 10 seconds Set Dip switch S3 OFF (for seconds) Set Dip switch S6 ON Set Dip switch S8 ON 2 + 8 =10 seconds