Camden Door Controls CM-RQE70A, CM-RQE70ABK Installation Instructions

Door Activation Devices
MODE
PARAMETER
ADJUST
LED
LENS
LOCK DOWN SCREW
TAMPER
SWITCH
SOUNDER
OUTPUT
RELAY
J4
J2
CM-RQE70A PIR ‘REQUEST TO EXIT’ DETECTOR
INSTALLATION INSTRUCTIONS
THIS PACKAGE INCLUDES
(2) #6 x 3/4" Screws (2) 3/16" Wall Plugs (2) MOV's
1. GENERAL DESCRIPTION
Camden CM-RQE70A Request-to-Exit Sensor is a passive infrared (PIR) detector designed for interior use. This device is UL listed as an access control device under UL 294 Standard and is listed for Class I for UL Canada under ULC-S319 when it is connected to a UL approved access control system.
BP7175
2. FEATURES
• Compact size, designed to mount on door frames
• On-board programming buttons. No dip switches
• (4) factory default operating modes, with the ability to customize mode attributes
• Makes installation easy and fast
• Selectable Fail Safe/Fail Secure
• (2) Form ‘C’ contacts
• Momentary and latching relay modes
• Secondary activation device input
• Card/keypad input
• Door position switch input
• Request to exit input
• Built-in sounder (adjustable)
• Tamper switch
3. OPERATION
FIGURE 1 - MOUNTING LOCATIONS
Self-Test
When power is rst applied to the CM-RQE70A, the sensor will beep
once, then the unit performs a self-test to ensure its major functions are within acceptable operating parameters. The self-test checks the input voltage, switch operation and sensor function. If the sensor passes all tests, there is a single beep and normal operation begins. If the sensor fails any of the tests, the unit will provide a series of audible beeps indicating the failure. This is take approximately 30 seconds.
Post-Test Failure Beeps
If the sensor fails a test, the unit will perform one or more short beeps, followed by a long beep. This series of beeps is repeated continuously.
# of Short Beeps
1 The IR sensor did not settle to an acceptable level
2 One of the 3 buttons, Mode, Parameter or Select is
3 The Source Voltage to the CM-RQE70A is outside
4 The IR sensor is not changing over a large enough
Description
during the test.
detected as being pressed.
of the range of 12 – 24V
range of values to reach its settle point
FIGURE 1 - COMPONENT LOCATIONS
Fail Safe vs Fail Secure: Field Selectable
These terms are used to describe the normal operating state of the output relays. In Fail Safe Mode, the relays will be normally energized.
The relays will de-energize when a person is in the eld of view (normal
operation) or when the power is removed due to an outage or other external reasons. In Fail Secure Mode, the relays remain de-energized
normally. The relays will energize when a person is in the eld of view
(normal operation). The relays remain de-energized during a power outage, therefore, keeping the controlled device secure.
Page 1 of 6
CM-RQE70A PIR ‘REQUEST TO EXIT’ DETECTOR
INSTALLATION INSTRUCTIONS
Tamper Switch
Dry contact outputs N/C are provided for interface to an alarm or access control systems. The Tamper Switch is connected to a spring that compresses and closes the switch when the housing cover is installed. Removing the cover will open the switch contacts providing a change in state to the monitoring system.
Indicator Lights: LED’s
A Red & Green LED indicates secure vs unsecured status of the REX. The red LED is normally lit to indicate the door is secure. When a person walks within the detectable range of the sensor, the green LED will light and the red will be off.
Access Control Input
Input: Dry N/O A dry contact closure on this input allows a card
reader or keypad on the secure side of the door to activate the REX sensor allowing access through the secured door.
Sounder Control
Input: Dry N/O A dry contact closure from an external device will hold
this sounder on until it is released. The sounder will not affect the operation of the relays or relay timers.
Sequential Logic Input
Input: Dry This mode allows a secondary detection device to be
connected to the REX sensor. The REX sensor is active only while this input is opened or for 10 seconds after it has closed. For example, when the secondary activation device is activated, the REX sensor functions
normally. When a person is in the eld of view, the sensor is activated
and the door is released. If the secondary activation device is de­activated, the REX Sensor will continue to be activated if a person is in
the eld of view for an additional 10 seconds.
Door Monitor Contacts
Input: Dry
Operating Functions
Function 1: Latched
When the REX sensor is activated, the relay will remain active as long as the sensor is activated. Once the sensor is deactivated, the relay will remain on for the duration of the Relay On Time. If the door is opened, the Relay On Time is reduced to 2 seconds.
Function 2: Door Prop Open Alarm
The door contact input is used to monitor the status of the door. If the door is held open during the last 10 seconds of the timer relay set time, the sounder will annunciate until the door is closed again. If the door is opened without the REX being activated the sounder will annunciate until the door is closed or someone has moved into the REX Sensor’s
eld of view.
Function 3: Unauthorized Access Mode
In this mode, when the REX sensor is activated but the door is not opened, the relay returns to a secured state in 10 seconds. If the REX sensor is activated and the door opens, then closes, the relay returns to secured state in 2 seconds.
Function 4: Timed
When the REX sensor is activated, the relay will remain active for the duration of the Relay On Time. Once the Relay On Time has expired, the relay drops out. If motion continues, the relay will activate for another full cycle. If the door is opened, the Relay On Time is reduced to 2 seconds.
External Disable/Enable
Input: Dry
In this mode, the REX is enabled or disabled by an external device, such as an access control system or security alarm panel. While this input is held open, the REX sensor will function normally. When this input is closed, the REX sensor operates the same as in Sequential Logic Input Mode.
Rex Sensor Default Modes
In an effort to make installation easier, we have dened different
installation modes. These modes will cover 90+% of the applications. For the other 10%, there will be a Custom Mode where all settable functions can be adjusted.
Mode 1: Normal Latched REX Sensor
The most common mode, the sensor, when activated will enable the output relay for the duration of the Relay On Time (30 seconds). If a door contact is connected to Input #1, when the door is sensed to be opened, then closed, the Relay On Time is reduced to 2 seconds.
Relay On Time: 30s (If the door is opened and closed, the timer is reduced to 2s)
Fail Mode: Fail Safe Operating Function: Latched PIR Sensitivity: 4 Sound Vol: 3 Input #1: Door Contact Input #2: Press to Exit Input #3: Sounder Input
Mode 2: Door Prop Alarm
The sensor monitors the status of the door. When activated, the sensor enables the output relay for 30 seconds. If the door is held open during the last 10 seconds of the Relay On Time, the piezo will sound until the door is closed. This mode requires a Door Contact to be connected to Input #1.
Relay On Time: 30s (If the door is opened and closed, the timer is reduced to 2s) If the door is held open during the last 10 seconds of the relay on time, the piezo will sound until the door is closed.
Fail Mode: Fail Safe Operating Function: Door Prop Open Alarm PIR Sensitivity: 4 Sound Vol: 3 Input #1: Door Contact Input #2: Press to Exit Input #3: Sounder Input
Mode 3: Access Control
The sensor will activate normally on motion. Input #3 is used to connect to an access control system. A contact closure on Input #3 will activate the sensor. A maintained closure on Input #3 will activate the sensor
indenitely.
Relay On Time: 0.5 sec (If the door is opened and closed, the timer is reduced to 2s)
Fail Mode: Fail Safe Operating Function: Timed PIR Sensitivity: 4 Sound Vol: 3 Input #1: Door Contact Input #2: Press to Exit Input #3: Card Keypad
Page 2 of 6
CM-RQE70A PIR ‘REQUEST TO EXIT’ DETECTOR
INSTALLATION INSTRUCTIONS
Mode 4: Secondary Activation Mode
The sensor requires activation of Input #3 before activating the output relay.
Relay On Time: 30s (If the door is opened and closed, the timer is reduced to 2s)
Operating Function: Latched, Door Prop Open Alarm or Unauthorized PIR Sensitivity: 4 Sound Vol: 3 Input #1: Door Contact Input #2: Press to Exit
IInput #3: Sequential Input In this mode, the sensor would behave as described above.
Mode 5: Custom Settings
The sensor may be programmed as required by the installation.
Relay On Time: 0.5, 1, 2.5, 5, 15, 30 45, and 60 seconds (unauthorized mode is 10 sec)
Fail Mode: Fail Safe or Fail Secure Operating Function: Latched, Door Prop Open, Unauthorized or Timed PIR Sensitivity: 1 to 5 Sound Vol: 0 to 4 Input #1: Unused, Door Contact, Sounder Input, Sequential
Input, External Disable, Press to Exit, Card Keypad Input #2: Unused, Door Contact, Sounder Input, Sequential Input, External Disable, Press to Exit, Card Keypad Input #3: Unused, Door Contact, Sounder Input, Sequential Input, External Disable, Press to Exit, Card Keypad
4. INSTALLATION
Remove the sensor cover
1. Insert a small at
screwdriver into the bottom end of the housing cover and gently pry the cover from the main assembly.
2. Loosen the sensor vertical
adjustment screw.
3. Rotate the sensor PCB
assembly until it is removed from the back plate.
Install the Back Plate
3. Align the sensor back plate with the mounting holes and screw in the 2 x #6 screws, securely fastening the sensor back plate to the wall.
4. Rotate the sensor PCB assembly into the back plate.
Wiring the Sensor
The Camden CM-RQE70A uses a plug-in wiring harness for all electrical connections. The Pin out is described below.
J2 Description
1 Power +
2 Input 1
3 Input 2
4 Input 3
5 Ground
6 Tamper Switch 1
7 Tamper Switch 2
J4 Description
1 Relay 1b – Normally Closed (NC2)
2 Relay 1b – Normally Open (NO2)
3 Relay 1b – Common (C2)
4 Relay 1a – Normally Closed (NC1)
5 Relay 1a – Normally Open (NCO1)
6 Relay 1a – Common (C1)
7 Power -
EMF spike protected relay
Adjusting the Sensor Detectable Range
The sensor’s detectable range can be adjusted vertically and horizontally.
Horizontal Adjustment
The horizontal adjustment of the sensor is accomplished by adjusting the 2 louvers inside the lens area. The louvers are adjusted using a
small at head screwdriver. On the bottom of the sensor housing
there are 2 adjustment screws. Turning the screws adjusts the louvers left and right horizontally, therefore changing the beam direction and width. Once the horizontal adjustment is complete, place the tamper label (provided) over the set screws to avoid accidental adjustment.
1. Using a 3/16” drill, drill 2 mounting holes 3 ¼” apart at the
desired height of installation.
2. Insert the 2 x 3/16” wall plugs into the holes
Vertical Adjustment
The sensor beam is vertically adjusted by rotating the PCB assembly barrel within the mounting back plate. Once the vertical adjustment is complete, tighten the lock down screw to prevent the barrel from moving.
Once all adjustments are made, install the sensor cover and install the set screw provided.
Page 3 of 6
CM-RQE70A PIR ‘REQUEST TO EXIT’ DETECTOR
MODE
PARAMETER
ADJUST
LED
LENS
LOCK DOWN SCREW
TAMPER
SWITCH
SOUNDER
OUTPUT
RELAY
J4
J2
INSTALLATION INSTRUCTIONS
Programming Buttons
There are no DIP switches to set on this Rex Sensor. 3 buttons are used for all setup and programming.
Mode Beeps
Red LED Flashes
Description
1 1 1 Latched Mode
2 2 2 Door Prop Alarm Mode
3 3 3 Access Control Mode
The MODE Button (top):
The MODE button is used to select 1 of 4 pre-set modes or a fully
congurable custom Mode. Pressing the MODE button for the rst time
will indicate which Mode the REX sensor is currently in. The REX sensor
will BEEP and the LED will ash red the number of times equal to the
MODE number. I.E. 1 Beep/Flash = Mode 1.
The Parameters Button (Middle)
This button selects the available parameters in each mode that can be customized. From within any Mode, press this button to cycle through the parameters.
4 4 4 Secondary Activation Mode
5 5 5 Custom Settings Mode
The Adjust Button (Bottom)
The adjust button is used to change the value of the Parameter. Once a Parameter is selected, use the Adjust button to cycle through the available options for each parameter as described in the below table.
Parameter 1 beep 2 beeps 3 beeps 4 beeps 5 beeps 6 beeps 7 beeps 8 beeps LED
Relay On Time
0.5 1 2.5 5 15 30 45 60 Yellow Solid
Fail Mode Safe Secure
Operation Mode
PIR Sensitivity
Sound Volume
Latched
1 2 3 4 5
0 1 3 3 4
Input #1 Unused Press to Exit
Input #2 Unused Press to Exit
Input #3 Unused Press to Exit
Door Prop Open Alarm
Unauthor­ized Access
Card/ Keypad
Card/ Keypad
Card/ Keypad
Timed
Door Contact
Door Contact
Door Contact
Factory Reset
The Camden CM-RQE70A Request to Exit sensor can be reset to factory defaults by pressing and holding the MODE and Adjust buttons. The Sensor will start to beep. Continue holding the MODE and ADJUST buttons while the beeping gets progressively faster until it reaches a steady tone. When the tone stops, the REX sensor has been reset to factory defaults and the MODE and ADJUST buttons may be released.
Red/Yellow Flashing
Green/Yel­low Flashing
Red/Green Flashing
Red/Green/ Yellow Flashing
Sounder Input
Sounder Input
Sounder Input
Sequential Input
Sequential Input
Sequential Input
External Disable
External Disable
External Disable
External Disable
External Disable
External Disable
Red Flashing
Green Flashing
Yellow Flashing
Regulatory Information
The unit shall be installed in accordance with National Electrical Code ANSI/NFPA 70 and part 1 of the Canadian Electrical Code CSA C22.1, Safety Standard for Electrical Installations and authorities having jurisdiction (AHJ’s).
Page 4 of 6
CM-RQE70A PIR ‘REQUEST TO EXIT’ DETECTOR
12 - 24 V
12 - 24 V
12 - 24 V
MODE 4 WIRING DIAGRAM
INSTALLATION INSTRUCTIONS
DC
Power
DC
Power
Vin-C1NO1
-
+
Vin+I1I2I3GNDT1T2
Door Contact Request to Exit
-
+
Door Contact Request to Exit
Push Button
MODE 1&2 WIRING DIAGRAM
Vin-C1NO1
Vin+I1I2I3GNDT1T2
Push Button
MOV
NC1C2NO2
MOV
NC1C2NO2
Maglock
Notes:
1. Relay is set to Safe Mode in
NC2
this application
J4
2. Relay O/P2 is EMF protected. If using O/P1a diode should be place across the maglock
J2
power connections.
Sounder Control
Maglock
Notes:
1. Relay is set to Safe Mode in
NC2
this application
J4
2. Relay O/P2 is EMF protected. If using O/P1a diode should be place across the maglock
J2
power connections.
REX Sensor Keypad Eye Beams
DC
Power
J2
1 2 3 4 5 6 7
J4
1 2 3 4 5 6 7
MOV
Vin-C1NO1
NC1C2NO2
-
+
Vin+I1I2I3GNDT1T2
Door Contact Request to Exit
Description
Power + Input 1 Input 2 Input 3 Ground Tamper Switch 1 Tamper Switch 2
Description
Relay 1b - Normally Closed (NC2) Relay 1b - Normally Open (NO2) Relay 1b - Common (C2) Relay 1a - Normally Closed (NC1) Relay 1a - Normally Open (NO1) Relay 1a - Common (C1) Power -
Push Button
MODE 3 WIRING DIAGRAM
NC2
J4
J2
1 2 3
4 5 6
7 8 9
Maglock
Notes:
1. Relay is set to Safe Mode in this application
2. Relay O/P2 is EMF protected. If using O/P1a diode should be place across the maglock power connections.
Access Control Keypad/ Reader
EMF Spike protected relay
5. SPECIFICATIONS
Voltage: 12 /24V DC operation Current Draw: 50mA (max) Relays: (2) Form ‘C’ (DPDT) Contact Rating: 3A @ 30VDC Programming: On-board push buttons
and status LED Modes: - (4) Factory Default
- (1) Fully Custom
- Selectable Fail Safe/ Fail Secure
Coverage: - Max. 10’ W x 10’ H
- Horizontal & vertical adjustment (mechanical)
- Sensor sensitivity/range (electronic)
Time Delay: Adjustable, 0.5, 1, 2.5, 5, 15, 30, 45 & 60 second
Sounder: On/Off, with adjustable volume
Piezo Buzzer: 92db.@ 10cm.
Indicator: Activation LED
Card or Keypad Input: (1) N/O
Door Position Switch Input: (1) N/O
Request to Exit Input: (1) N/O
Tamper Switch Contact Rating: 50mA @ 12VDC
Temp Operating Range: 32°F - 120°F (0 - 50°C)
Humidity Range: 0 - 93% non-condensing Dimensions: 1 3/4”H x 7” W x 1 3/4” D
(43mm x 176mm x 43mm)
Weight: 0.25 lbs. (0.12kg.) Colors: White and black models
UL 294 Access Control Performance Levels
1) Access Controls, Destructive Attack Level I (No Attack)
2) Line Security - Level I (No Line Security)
3) Endurance - Level IV (100,000 cycles)
4) Standby Power - Level I (No Stand by Power)
Power is to be supplied by a compatible UL294 Listed control unit, or by a UL294 Listed or UL603 Listed Class 2 low-voltage power limited power supply that is capable of 4 hours of standby power, as described in the installation guide.
The products shall not be installed in the fail-secure mode unless permitted by the local authority having jurisdiction and shall not interfere with the operation of Listed panic hardware.
Page 5 of 6
6. COVERAGE INFORMATION
7’5” Ceiling - Above Single Door
8’ Ceiling - Over the Ceiling
CM-RQE70A PIR ‘REQUEST TO EXIT’ DETECTOR
INSTALLATION INSTRUCTIONS
The detection area changes depending on the mounting height and angle of the lens of the REX sensor. If the REX sensor is mounted on the wall above a door with the lens pointing straight, the detection areas against the wall are not detected and not shown in the illustrations. Mounting the REX sensor at higher heights,results.
Front View
in a larger detection area typically. The illustrations show the REX sensor mounted at 7.5 (2.3m) Feet on a wall with the lens pointing straight down and at 8 Feet (2.4m) on a ceiling with the lens pointing straight down.
Front View
Bird’s-Eye View
11’ 6”
(3.5m)
Side View
2 ft.
(0.6m)
Bird’s-Eye View
(3.6m)
Side View
12’
3 ft.
(0.9m)
Opening New Doors to Innovation, Quality and Support!
Call: 1.877.226.3369 / 905.366.3377 Visit: www.camdencontrols.com
File: CM-RQE70A Detector Manual.indd-R2 Rev. Label/Date: 1/07-26-17 Part No: 40-82B203-A
Page 6 of 6