California Instruments 251TL Programmers Guide

By California Instruments.
Model 251TL / 351TL
AC Power Source
Revision C
November 2001
Copyright 2001
All rights reserved.
P/N 7351-960
TEL: +1 (858) 677-9040 FAX: +1 (858) 677-0940
Email: sales@calinst.com
Web Site: http://www.calinst.com
User and Programming Manual - Rev C
User and Programming Manual AC Power Source California Instruments
Models:
251TL, 351TL
Options: -L22, -OP1, -SKT, -RMS, -EXT
Copyright 2001 California Instruments, Rev C, November 2001
TL Series November 2001 i
User and Programming Manual - Rev C

SAFETY SUMMARY

This power source contains high voltage and current circuits that are potentially lethal. Because of its size and weight, electrical and mechanical stability must be ensured. The following safety guidelines must be followed when operating or servicing this equipment. These guidelines are not a substitute for vigilance and common sense. If this power source is not used as specified in this manual, the protection provided by this equipment may be impaired. California Instruments assumes no liability for the customer's failure to comply with these requirements.
APPLYING POWER AND GROUNDING
Verify the correct voltage is applied to the unit (100 / 115 / 200 or 230 VAC Nominal). Verify that the input power wiring is connected to a properly grounded utility outlet.
FUSES
Use only fuses of the specified current, voltage, and protection speed. Do not short out the fuse holder or use a repaired fuse. The main supplies in the 351TL use a North American ferrule fuse rated at 30A. (Fast Acting)
DO NOT OPERATE IN A VOLATILE ATMOSPHERE
Do not operate the power source in the presence of flammable gases or fumes. This product is designed to operate in a controlled environment. Do not expose to rain or snow.
DO NOT TOUCH ENERGIZED CIRCUITS
Disconnect the power cable before servicing this equipment. Only qualified service personnel may remove covers, replace components or make adjustments.
DO NOT SERVICE ALONE
Do not remove covers, replace components, or make adjustments unless another person, who can administer first aid, is present.
DO NOT EXCEED INPUT RATINGS
Do not exceed the rated input voltage or frequency. Additional hazards may be introduced because of component failure or improper operation.
DO NOT MODIFY INSTRUMENT OR SUBSTITUTE PARTS
Do not modify this instrument or substitute parts. Additional hazards may be introduced because of component failure or improper operation.
MOVING THE POWER SOURCE
When moving the power source, observe the following:
1. Remove all AC power to unit.
2. Use two people to prevent injury.
SURFACE STABILITY
Operate the power source only on a level surface.
ii November 2001 TL Series
User and Programming Manual - Rev C
Electrical Safety Symbols Used in This Manual
TL Series November 2001 iii
User and Programming Manual - Rev C
WARRANTY INFORMATION
CALIFORNIA INSTRUMENTS CORPORATION warrants each instrument manufactured by them to be free from defects in material and workmanship for a period of one year from the date of shipment to the original purchaser. Excepted from this warranty are fuses and batteries that carry the warranty of their original manufacturer where applicable. CALIFORNIA INSTRUMENTS will service, replace, or adjust any defective part or parts, free of charge, when the instrument is returned freight prepaid, and when examination reveals that the fault has not occurred because of misuse, abnormal conditions of operation, user modification, or attempted user repair. Equipment repaired beyond the effective date of warranty or when abnormal usage has occurred will be charged at applicable rates. CALIFORNIA INSTRUMENTS will submit an estimate for such charges before commencing repair, if so requested.
If a fault develops, notify CALIFORNIA INSTRUMENTS at support@calinst.com or its local representative, giving full details of the difficulty, including the model number and serial number. On receipt of this information, service information or a Return Material Authorization (RMA) number will be given. Add the RMA number furnished to the shipping label. Pack the instrument carefully to prevent transportation damage, affix label to shipping container, and ship freight prepaid to the factory. CALIFORNIA INSTRUMENTS shall not be responsible for repair of damage due to improper handling or packing. Instruments returned without RMA No. or freight collect may be refused at California Instruments discretion. Instruments repaired under Warranty will be returned either via prepaid surface freight or low cost airfreight at California Instruments discretion. Instruments repaired outside the Warranty period will be returned freight collect, Ex Works CALIFORNIA INSTRUMENTS 9689 Towne Centre Drive, San Diego, CA 92121-1964. If requested, an estimate of repair charges will be made before work begins on repairs not covered by the Warranty.
SERVICE PROCEDURE
DAMAGE IN TRANSIT
The instrument should be tested when it is received. If it fails to operate properly, or is damaged in any way, a claim should be filed immediately with the carrier. The claim agent should obtain a full report of the damage, and a copy of this report should be forwarded to us by fax or email (Fax: 858 677 0940, Email: support@calinst.com). CALIFORNIA INSTRUMENTS will prepare an estimate of repair cost and repair the instrument when authorized by the claim agent. Please include model number and serial number when referring to the instrument.
SPARE PARTS
To order spare parts, user manuals, or determine the correct replacement part for your California Instruments products, please contact the Customer Service department by phone at + 1 858 677 9040, press 2 or by email support@calinst.com.
iv November 2001 TL Series
User and Programming Manual - Rev C

Table of Contents

1 Introduction.....................................................................................................................................1
1.1 General Description...............................................................................................................................1
1.2 Accessory Equipment/Rack Slides........................................................................................................1
2 Specifications..................................................................................................................................3
2.1 Electrical................................................................................................................................................3
2.2 Measurements [Option].........................................................................................................................6
2.3 System Specification.............................................................................................................................7
2.4 Unit Protection.......................................................................................................................................8
2.5 Mechanical.............................................................................................................................................8
2.6 Environmental........................................................................................................................................9
2.7 Regulatory.............................................................................................................................................9
2.8 Front Panel Controls............................................................................................................................10
2.9 Available Options.................................................................................................................................10
3 Installation and Functional Test....................................................................................................11
3.1 Unpacking............................................................................................................................................11
3.2 Power Requirements...........................................................................................................................11
3.3 Input Voltage Range Selection............................................................................................................13
3.4 Mechanical Installation........................................................................................................................17
3.5 Input Wiring.........................................................................................................................................17
3.6 Output Connections.............................................................................................................................17
3.7 Output Voltage Ranges.......................................................................................................................18
3.8 Functional Test....................................................................................................................................19
3.9 Current Limit - Modes of Operation.....................................................................................................21
4 Front Panel Operation ..................................................................................................................23
4.1 Functional Controls..............................................................................................................................23
4.2 How to Examples.................................................................................................................................28
4.3 Setting the Power on Initialization Values............................................................................................31
4.4 Current Limit Modes............................................................................................................................32
4.5 Function Strobe [Option]......................................................................................................................33
4.6 Remote Inhibit [Option]........................................................................................................................33
5 Principle of Operation ...................................................................................................................35
5.1 General................................................................................................................................................35
5.2 Overall Description..............................................................................................................................35
5.3 Input Power Supply..............................................................................................................................35
5.4 Range Relay Board.............................................................................................................................39
5.5 Amplifier...............................................................................................................................................39
5.6 Controller Module................................................................................................................................39
5.7 IEEE 488/ RS232 Interface [Option]....................................................................................................40
6 Calibration.....................................................................................................................................43
6.1 Calibration Equipment.........................................................................................................................43
6.2 Selecting Calibration Mode..................................................................................................................44
6.3 Routine Calibration..............................................................................................................................45
6.4 Non-Routine Calibration......................................................................................................................49
7 Service..........................................................................................................................................53
7.1 General................................................................................................................................................53
7.2 Basic Operation...................................................................................................................................53
7.3 Module Removal..................................................................................................................................55
7.4 Replaceable Parts...............................................................................................................................58
TL Series November 2001 v
User and Programming Manual - Rev C
8 Remote Control ............................................................................................................................59
8.1 Introduction.........................................................................................................................................59
8.2 PGUI32 Program Requirements.........................................................................................................59
8.3 IEEE Interface.....................................................................................................................................61
8.4 RS232C Interface................................................................................................................................62
8.5 PGUI32 Setup and Installation............................................................................................................ 64
8.6 Trouble Shooting - RS232C................................................................................................................66
8.7 Trouble Shooting - IEEE-488 / GPIB...................................................................................................69
8.8 PGUI32 Distribution Files.................................................................................................................... 70
8.9 Software Registration.......................................................................................................................... 71
9 Introduction to SCPI .....................................................................................................................73
9.1 Conventions Used in This Manual.......................................................................................................73
9.2 The SCPI Commands and Messages.................................................................................................73
9.3 Using Queries .....................................................................................................................................76
9.4 Structure of a SCPI Message..............................................................................................................76
9.5 SCPI Data Formats.............................................................................................................................79
10 SCPI Command Reference......................................................................................................81
10.1 Subsystem Commands....................................................................................................................... 81
10.2 Calibration Subsystem ........................................................................................................................82
10.3 Measurement Subsystem....................................................................................................................87
10.4 Source Subsystem.............................................................................................................................. 90
10.5 Output Subsystem............................................................................................................................... 94
10.6 Limit Subsystem..................................................................................................................................97
10.7 Display Subsystem.............................................................................................................................. 99
10.8 System Commands...........................................................................................................................100
10.9 Common Commands ........................................................................................................................102
11 Programming Examples .........................................................................................................110
11.1 Introduction ....................................................................................................................................... 110
11.2 Programming the Output...................................................................................................................110
11.3 Making Measurements......................................................................................................................112
12 Status Registers......................................................................................................................114
12.1 Power-On Conditions........................................................................................................................114
12.2 Standard Event Status Group ........................................................................................................... 115
12.3 Status Byte Register..........................................................................................................................115
12.4 Examples...........................................................................................................................................116
Appendix A : SCPI Command tree....................................................................................................117
Appendix B : SCPI Conformance Information...................................................................................118
Appendix C : Error Messages............................................................................................................119
Index..................................................................................................................................................120
vi November 2001 TL Series
User and Programming Manual - Rev C

List of Figures

Figure 2-1: Output Power Rating as a Function of Voltage and Load PF.............................................5
Figure 3-1: Model 251TL / 351TL AC Power Source..........................................................................11
Figure 3-2: Rear Panel View...............................................................................................................12
Figure 3-3: Connections to T1 for 105 - 125V Line Input....................................................................14
Figure 3-4: Connections to T1 for 210 - 250V Line Input....................................................................16
Figure 3-5: Test Setup 351TL.............................................................................................................20
Figure 4-1: Front Panel View ..............................................................................................................23
Figure 4-2: Voltage Auto Range Switch Over Points..........................................................................25
Figure 4-3: Shuttle Knob.....................................................................................................................26
Figure 5-1: AC Power System Block Diagram....................................................................................37
Figure 6-1: Test Equipment Hookup for Routine Output and Voltage Measurement Calibration.......45
Figure 6-2: Test Equipment Hook-up for Current and Power Measurement Calibration....................46
Figure 6-3: Internal Adjustments.........................................................................................................51
Figure 7-1: Assembly Location ...........................................................................................................56
Figure 8-1: Rear Panel View...............................................................................................................60
Figure 8-2: GPIB Address Selection Switch .......................................................................................61
Figure 8-3: RS232C Interface Cable Wiring Diagram.........................................................................64
Figure 8-4: System Properties Dialog Box..........................................................................................67
Figure 8-5: Advanced Port Settings Dialog Box..................................................................................67
Figure 8-6: COM Port Properties Dialog Box......................................................................................67
Figure 8-7: NI AT-GPIB/TNT Settings ................................................................................................69
Figure 8-8: NI AT-GPIB/TNT Advanced Settings Dialog ....................................................................69
Figure 9-1: Partial Command Tree.....................................................................................................74
Figure 9-2: Command Message Structure..........................................................................................76
Figure 12-1: AC Source Status System Model.................................................................................114
TL Series November 2001 vii
User and Programming Manual - Rev C

List of Tables

Table 4-1: Factory Default Power on Settings....................................................................................31
Table 6-1: Load Resistors and Current...............................................................................................43
Table 6-2: CAL Mode Status LED Indicators......................................................................................44
Table 7-1: Basic Symptoms................................................................................................................53
Table 7-2: Poor Output Voltage Accuracy..........................................................................................53
Table 7-3: Poor Output Voltage Regulation........................................................................................53
Table 7-4: Distorted Output ................................................................................................................54
Table 7-5: Unit Shuts Down After 3-5 Seconds..................................................................................54
Table 7-6: No Output and No Lights on Front Panel ..........................................................................54
Table 7-7: No Output But "Display" Is On..........................................................................................54
Table 7-8: Replaceable Parts .............................................................................................................58
Table 10-1: Mode Command Encoding..............................................................................................99
Table 10-2: Bit Configuration of Standard Event Status Enable Register ........................................103
Table 10-3: Bit Configuration of Standard Event Status Register.....................................................104
Table 10-4: *RST Default Parameter Values....................................................................................106
Table 10-5: Status Registers - Power on Conditions........................................................................106
Table 10-6: Bit Configuration of Status Byte Register ......................................................................108
Table 12-1: Bus Error Messages......................................................................................................119
viii November 2001 TL Series
User and Programming Manual - Rev C
RMS
RMS

1 Introduction

This instruction manual contains information on the installation, operation, calibration and maintenance of the 351TL and 251TL AC power source.

1.1 General Description

The 351TL AC source is a 350 VA programmable AC power source. The 251TL is a 250 VA version of the power source. In addition to the standard models, several options are available that may change the voltage and frequency ranges of the power source. This user manual covers the following models:
Model Voltage ranges Max. Current
351TL 135 V
270 V
251TL 135 V
270 V
The output voltage High and Low terminals are isolated from the chassis, and earth ground. The AC input can be either 105 V 91 V
RMS
to 109 V
RMS
or 182 V
RMS
to 125 V
RMS
to 217 V
RMS
Simple front panel controls enable the voltage, current limit and frequency to be changed. An optional RS232C and IEEE 488 interface is available for applications that require remote control and measurements.

1.2 Accessory Equipment/Rack Slides

General Devices Company Model C300-120-B308 rack slides (option -RMS) may be attached to the sides of the power source using 10-32 X 3/8 flat head screws.
2.8 A
RMS
RMS RMS
AC, 210 V
RMS
1.4 A
2.4 A
1.2 A
RMS
RMS
RMS RMS
to 250 V
at 47 to 67 Hz line frequency.
RMS
AC,
TL Series November 2001 1
User and Programming Manual - Rev C
This page intentionally left blank
2 November 2001 TL Series
User and Programming Manual - Rev C

2 Specifications

All specifications at 23 ±5°C unless noted otherwise.

2.1 Electrical

Input
Line Voltage:
115 V 230 V 100 V 200 V
nominal, 105 V
RMS
nominal, 210 V
RMS
nominal, 91 V
RMS
nominal, 182 V
RMS
RMS RMS
RMS
RMS
to 125 V to 250 V
to 109 V
to 217 V
RMS RMS
RMS
RMS
AC AC
Unit must be configured for correct Line input voltage.
Line Current: 9 A
maximum, line voltage = 115 VAC, full-load
RMS
PF = 0.7
Inrush Current:
150 A 75 A
for 115V line
pk
for 230V line
pk
Input power factor: 0.7 at full-load and 115 VAC input Line Frequency: 47 Hz - 67 Hz Isolation Voltage: Input to output = 2300 VAC, input to chassis = 1350 VAC
Output
Parameter Specification
Voltage
Range 0 to 135 V
or 270 V
RMS
(standard ranges)
RMS
Resolution 0.1 volt Accuracy
± 0.1 % of calibrated range, 45 Hz - 100 Hz ± 0.2 % of calibrated range, 100 Hz - 5000 Hz ± 0.3 % of calibrated range, 5000 Hz - 8000 Hz
Load Regulation 0.1 % of FS. Add 0.05% above 2000 Hz
TL Series November 2001 3
User and Programming Manual - Rev C
Parameter Specification
External Sense Will compensate for up to 5% of voltage drop up to 2kHz Line Regulation 0.02 % of FS Settling time From start of voltage change from 5.0 V
voltage to within 2% of final value:
Distortion (THD into linear load)
<0.5 % maximum 45 to 499 Hz <1.0 % above 500 Hz
<2.0% 1000 to 8000Hz DC Offset voltage AC Coupled transformer output Output noise -73 db typical
( 20 kHz to 1 MHz at full load ) Temperature
± 0.02 % of full scale per degree C coefficient:
Stability (24 hours) ± 0.015 % of full scale under constant load, line and
temperature Total Power
PT = 0.7
351TL: 350 VA from 90 to 100% of V range
251TL: 250 VA from 78 to 100% of V range
Current (Refer to Figure 2-1 for derating)
Output
V Range
351TL 251TL
RMS
No load: 16 msec Full load: 300 msec (16 msec to within 15 % of final value)
Amps rms Amps peak
135 270 135 270
2.8
1.4
2.4
1.2
or higher
6 3 6 3
Adjustable Limit 0.0 to Maximum available RMS current for selected
voltage range. Accuracy Programmed value + 5, -0 % of maximum RMS current
4 November 2001 TL Series
User and Programming Manual - Rev C
Parameter Specification
Frequency
Range 351TL 16.0 - 8000 Hz
Resolution 0.01 Hz from 16.00 to 80.00 Hz
Accuracy
Maximum output voltage available from 45 Hz.
0.1 Hz from 80.1 Hz to 800.0 Hz 1 Hz from 801 Hz to 8000 Hz
± 0.02% of programmed value
Temperature
± 5 ppm per degree Celsius
coefficient Stability ± 15 ppm per year
Figure 2-1: Output Power Rating as a Function of Voltage and Load PF
TL Series November 2001 5
User and Programming Manual - Rev C

2.2 Measurements [Option]

Parameter Specification Unit True RMS Current
Available on standard unit. Range 0.000 - 4.000 A Accuracy 0.2 % FS + 0.3 % reading Resolution 0.001 A Temp
Coefficients
Peak Current Requires Option -OP1
Range 0.00 – 12.00 A Accuracy 0.5 % FS + 0.5 % reading Resolution 0.01 A
Crest Factor
Available over bus only. Requires interface Option -OP1 Range 0.00 - 4.00 Accuracy 0.05 Resolution 0.01
True RMS Voltage Standard Unit: Available over bus only.
-OP1 option: Front Panel and bus. Range 0.0 - 300.0 V Accuracy 0.1 % FS + 0.05 % reading Resolution 0.1 V Temp
Coefficients
Real Power Requires Option -OP1
Range 0 - 400.0 W Accuracy 0.2 % FS + 0.5 % reading Resolution 0.2 W Temp
Coefficients
Apparent Power
Available over bus only. Requires -OP1 option Range (Remote only) 0 - 400.0 VA Accuracy 0.3 % FS + 0.8 % reading Resolution 2 VA
Power Factor
Requires -OP1 option Range 0.00 - 1.00 Resolution 0..01
0.016
0.05
0.06
RMS
RMS
% FS / °C
PEAK
PEAK
RMS
RMS
V / °C
% FS /°C
6 November 2001 TL Series
User and Programming Manual - Rev C

2.3 System Specification

Parameter Specification
Setup storage Eight non volatile front panel setup registers available through
interface. Power on setting register available from front panel.
Interface (Option package -OP1 required) RS-232C Bi-directional serial interface
Rear panel connector: 9 pin D shell Handshake: CTS, RTS Data bits: 8 Stop bits: 1 Parity: None Baud rate: 19200 Command syntax: IEEE 488.2 commands and SCPI
IEEE-488 GPIB Interface
Rear panel connector: 24 pin D-shell IEEE address: set using dip switch on rear panel from
0 to 31
IEEE functions: SH1, AH1, T8, L4, RL2, SRQ 0, PP 0,
DC 0, DT 0, C0 Terminators: LF, CRLF, EOI Command syntax: IEEE 488.2 commands and SCPI
Remote Inhibit (Option package -OP1 required)
Rear panel connector: BNC Input Contact closure to ground or logic low TTL
signal required to turn off output.
Automatic recovery when RI signal is
removed.
Function Strobe (Option package -OP1 required)
Rear panel connector: BNC Output Active low TTL signal. Signal driven low for
approximately 400 µsec any time output
voltage or frequency programmed value
changes. Signal level may be changed by
removing jumpers to open collector.
TL Series November 2001 7
User and Programming Manual - Rev C

2.4 Unit Protection

Parameter Specification
Input Overcurrent: Electronic current limit with circuit breaker. Transients: Surge protection to withstand EN50082-1 (IEC 801-4, 5) levels. Output Overcurrent: Constant current operation. (Standard)
0.1 Second shutdown (constant voltage mode Option)
Output Short Circuit: Peak current limit.
Shutdown (constant voltage mode Option).
Overtemperature: Automatic shutdown.

2.5 Mechanical

Parameter Specification
Dimensions: Height Width Depth Unit
13.26 48.26 56.62 cm
5.22 19 22.29 inches Unit Weight: 34 Kg / 75 lbs Material: Steel chassis and panels.
Aluminum cover. Finish: Yellow iridite, painted semi-gloss polyurethane Cooling: Fan cooled with air intake on the sides and exhaust to the rear. Internal Construction: Modular sub assemblies. Chassis Slides: P/N 210960 / Option -RMS
General Devices Model CTS-1-20-B307-2 Front Panel Mounted Output Connection:
Wonpro Universal outlet socket (option -SKT) Rear Panel Mounted Connectors:
RS232C I/F DB 9
IEEE-488 I/F D-shell 24 pin
Remote Inhibit BNC (requires -OP1 option package)
Function Strobe BNC (requires -OP1 option package)
AC Output Amp 1-480705-1
External Sense Amp 1-480705-1
Line Input Kulka 9-85-3 Terminal block
8 November 2001 TL Series
User and Programming Manual - Rev C

2.6 Environmental

Parameter Specification
Operating Temp: 0 degrees to + 40 degrees Celsius. Storage Temp: - 40 degrees to + 85 degrees Celsius. Humidity:
Altitude Operating: 15000 feet / 6000 meters maximum.
Creepage and Clearance:
Insulation: Rated to Installation Category (Overvoltage Category) II Vibration: Designed to meet NSTA 1A transportation levels. Shock: Designed to meet NSTA 1A transportation levels.

2.7 Regulatory

Parameter Specification
Electromagnetic Emissions and Immunity:
Acoustic Noise: 65 dBA maximum at 0% to 50% load, 75 dBA maximum greater
Operating: 90% RH up to 40° C., non condensing Storage: 90% RH up to 40° C, 75% RH up to 70° C.
VA Power: Full VA power output :0 - 6000 feet / 0 - 2000
meters. Derate VA power 5 % per 1000 feet from 6000 to 15000 feet / 2000 to 6000 meters.
Rated for Pollution Degree 2.
Designed to EN50081-1 and EN50082-1 European Emissions and Immunity standards as required for the “CE” marking.
than 50% load to 100% load. Measured at one meter.
Safety: Designed to EN61010-1 European safety standards as required
for the “CE” marking.
Remote Control
TL Series November 2001 9
User and Programming Manual - Rev C

2.8 Front Panel Controls

Parameter Specification
Controls: Shuttle knobs:
Allows continuous change of Voltage, Frequency and Current
limit. Voltage change is inactive on single voltage range
configuration units.
Function keys:
Controls Output state, Voltage range and Display mode. Displays: Two, 4 digits, 0.5” LCD display. For viewing programmed voltage,
frequency, current limit and for displaying measured current. Status Indicators: 10 LEDs to indicate:
REMOTE, FAULT, OUTPUT (ON/OFF), VOLTAGE RANGE
HIGH, VOLTAGE RANGE AUTO
FREQUENCY, CURRENT, PEAK CURRENT, POWER, POWER
FACTOR DISPLAY MODES (Refer to paragraph 4.1.2).

2.9 Available Options

Option Description
-OP1 Option package 1 includes:
-RMS Rack mount slides
-SKT Universal front panel dual outlet socket.
-EXT Removes controller and allows external oscillator input.
1
Measurement Functions
Combined IEEE-488 / RS232C interface.
Remote Inhibit Input
Function Strobe Output
P/N 211045 / Option -RMS
General Devices Model C300S-120-B308
1
Additional options may have been made available since this manual revision. Installed options are listed on
the power source’s type sticker. A manual addendum may be issued for new options not covered by this manual.
10 November 2001 TL Series
User and Programming Manual - Rev C

3 Installation and Functional Test

3.1 Unpacking

Inspect the unit for any possible shipping damage immediately upon receipt. If damage is evident, notify the carrier. DO NOT return an instrument to the factory without prior approval. Do not destroy the packing container until the unit has been inspected for damage in shipment.

3.2 Power Requirements

The AC Power System has been designed to operate from a single phase AC line voltage. The nominal operating voltage is 100V, 115V, 200V or 230V line input. The Power Source line input setting is shown on the type sticker located on the rear panel.
Figure 3-1: Model 251TL / 351TL AC Power Source
WARNING: Do not connect the unit to a 400-480 service, as the result will be a severely
damaged unit.
Do not connect the unit to AC line input unless the nominal line input settings match those of the available AC line voltage.
TL Series November 2001 11
User and Programming Manual - Rev C
3.2.1 AC Line Voltage
The AC Power Source has been designed to operate from either of the following AC line voltage ranges:
1) 91 to 109 V
2) 82 to 217 V
3) 105 to 125 V
4) 210 to 250 V
RMS RMS
RMS RMS
CAUTION: The AC Power Source will be damaged if it is operated at an input voltage
that is outside its configured input range.
The input voltage range is set at the factory. Section 3.3 gives the procedure to change the input voltage range. The location for connection of the INPUT line is shown in Figure 3-2.
3.2.2 Line Frequency Operating Range
The AC Power Source has been designed to operate with a line frequency from 47Hz to 67 Hz.
3.2.3 Input Power
The input power to the AC Power Source depends upon line and load conditions and may be as high as 1000 watts.
Figure 3-2: Rear Panel View
12 November 2001 TL Series
User and Programming Manual - Rev C
4
5

3.3 Input Voltage Range Selection

WARNING: The line voltage is present in certain sections of this Power Source.
DEATH: On contact may result if personnel fail to observe safety precautions.
Do not touch electric circuits when power is applied. Servicing should only be performed by trained personnel.
The input voltage range is configured by changing the taps on the input transformer. See Figure 3-3 or Figure 3-4 for the location of the jumpers and input wires.
3.3.1 Voltage Range Configuration (105 – 125 V)
In order to change the voltage range configuration:
1. Turn off the input circuit breaker.
2. Disconnect AC input power to the source by unplugging the power cord.
3. Remove the AC Power Source top cover by removing (14) #6-32 x 5/16” FLH screws. There are 7 screws on the sides and 7 screws on the top that hold the cover.
Remove the (2) #6-32 x 1” PHN screws and lock washers that hold the amplifier near the outside panel.
Remove the (2) #6-32 x 3/8” PHN screws and lock washers located near the connector, attaching the red insulator to the center bracket.
The line input voltage range is set by the configuration of the Input Transformer, T1. To configure T1 for the 105-125 volt range, make the following connections to T1 (refer to Figure 3-3) :
Jumper terminals 1 and 4. Jumper terminals 3 and 6. Connect the input line from the Circuit Breaker to Terminals 1 and 6.
TL Series November 2001 13
User and Programming Manual - Rev C
Figure 3-3: Connections to T1 for 105 - 125V Line Input
14 November 2001 TL Series
User and Programming Manual - Rev C
3.3.2 High Input Voltage Range Configuration (210 – 250 V)
In order to change the voltage range configuration:
1. Turn off the input circuit breaker.
2. Disconnect AC input power at TB1.
3. Remove the AC Power Source top cover by removing (14) #6-32 x 5/16” FLH screws. There are a total of 7 screws on the sides and another 7 screws on the top that secure the top cover.
The line input voltage range is set by the configuration of the Input Transformer, T1. To configure T1 for the 210-250 volt range, make the following connections to T1 (refer to Figure 3-4) :
Jumper terminals 3 and 4. Connect the input line from the Circuit Breaker to Terminals 1 and 6. Remove all other connections to Terminals 1 through 6.
TL Series November 2001 15
User and Programming Manual - Rev C
Figure 3-4: Connections to T1 for 210 - 250V Line Input
16 November 2001 TL Series
User and Programming Manual - Rev C

3.4 Mechanical Installation

The power source has been designed for rack mounting in a standard 19 inch rack. The unit must be supported from the sides with optional rack slides. See Accessory Equipment/Rack Slides in Section 1.2. The cooling fan at the rear of the unit must be free of any obstructions which would interfere with the flow of air. A 2.5 inch (6.35cm) clearance should be maintained between the rear of the unit and the rear panel of the mounting cabinet. Keep in mind that adequate ventilation of the mounting cabinet must be maintained for sufficient cooling of the power source. Use louvered side panels, and/or perforated rear panels to assure adequate airflow. Also, the air intake holes on the sides of the power source must not be obstructed when mounted inside cabinet. See Figure 3-1.

3.5 Input Wiring

The AC Power Source must be operated from a three-wire single-phase service. The mains source must have a current rating greater than or equal to 10 A for the low input range. Use the supplied safety cover/strain relief when connecting the input wires to the power source. Refer to Figure 3-2 for the input power connections. When connecting the input wires to input terminal block, make sure the safety grounding wire from the strain relief grommet is longer than the Line and Neutral wire so that the ground wire will be the last one to take any strain. For low-range input operation (115V) we recommend #12 AWG input wires as a minimum. For high-range input operation (230V) #14AWG is recommended. For European applications (230V), the following input cordset may also be used:
Panel Components # 86518030 Rated 16A, 250V, 70° C, 3x 1.5mm² conductor size. VDE approved. Install as described above for discreet wiring.

3.6 Output Connections

The output terminal block is located at the rear of the power source or on the front panel with Option -SKT. All load connections must be made on the rear panel terminal block or from the front panel socket if the -SKT Option is installed. The remote sense inputs are normally jumpered directly to the adjacent power output pins on the output connector. If the sense terminals are not connected to the power output pins, the output voltage may rise significantly above the programmed value. When connecting the output wires, use the supplied safety cover/strain relief and mount over the output connector. Also mount the supplied snap-on ferrite filter around the output wiring between the output terminals and the strain relief grommet. Enclose ferrite filter with the safety cover.
If the load is a significant distance from the output terminal strip it may be desirable to sense the output voltage directly at the load. If remote sensing is to be used, then the size of the output power wiring must be heavy enough to prevent a voltage difference greater than 7% of the programmed value from the power output pins to the sense input pins.
The Remote Sense inputs must be connected or an output voltage 7% higher than the programmed output will be generated. If the Power Source is configured for constant voltage, a fault will be generated.
TL Series November 2001 17
User and Programming Manual - Rev C

3.7 Output Voltage Ranges

The standard 351TL AC power source has two output voltage ranges 0-135 VAC and 0-270 VAC. The operator may switch from one range to the other at will with no special precautions except to remember that the output voltage will go to zero voltage whenever a range change takes place.
Certain options available on the 351TL series may result in different voltage range values or a single voltage range only. Certain models may be ordered with a single voltage range only. On single voltage range units, the Range change button has no function and the LED indicator is not used.
351TL AC power source models with dual voltage ranges offer an auto voltage range change mode. In this mode, the voltage range is automatically changed when the user sets a voltage above 135 or below 131 V
The AUTO mode can be selected by pressing the range change button until the AUTO mode LED illuminates. To take the AC power source out of the AUTO voltage range mode, press the Voltage range button briefly. This will put the unit in the present range but takes it out of auto mode.
RMS
.
Note: Even in AUTO mode, the output temporarily goes to zero volts when a
voltage range change occurs. If this is not acceptable, the AC source should be operated in the high voltage range only and not in AUTO mode.
18 November 2001 TL Series
User and Programming Manual - Rev C

3.8 Functional Test

CAUTION: Work carefully when performing these tests - hazardous voltages are
present on the input and output during this test.
Refer to Figure 3-5 for the test set up. Use the following load resistor values:
Model Voltage Range Resistor Current (A
351TL 135
270
251TL 135
270
52
208
72.9 292
2.60
1.30
1.85 .92
RMS
)
1. Connect an oscilloscope, voltmeter and/or distortion analyzer to the AC source output at the rear panel output terminal.
2. Connect the AC power input voltage connections to the AC source input terminals. Connect the sense input to the adjacent power pin on the rear panel connector. Turn on the power switch located at the rear panel.
3. Verify that the front panel LCD display reads out the initial start up voltage and frequency.
4. Select the low voltage range. Set the frequency to 60 Hz with the right shuttle. Select the current function with the Frequency/Current selector. Set the current limit to the maximum value using the right shuttle. Set the output voltage to 135V with the left shuttle.
5. Enable the output by pressing the output “on/off” button in the top right of the front panel. The green LED above the button will illuminate when the output is on. The output should be a clean 135V AC sinewave having less than 0.5 % distortion.
6. Apply full load (refer to table on Figure 3-5) to the output of the source and verify the output remains within 0.05 % of the initial 135V . The output should still be clean and the distortion should still be less than 0.5 % at 60 Hz.
7. Using the right shuttle set the output current limit value to 2 amps (1 amp for the 251TL). If the unit is configured for Constant Current mode, the system should go into current limit and reduce the output voltage. This may create additional distortion on the output voltage. If the unit is configured for Constant Voltage mode (factory default), an error message will appear on the display (err. -300) that indicates an output fault condition and the output will go off. Return the current value to the maximum current and disconnect the load.
8. Repeat steps 4 through 7 but set the output for the following: Hi voltage range and the current limit to maximum value. Refer to the table above for the relevant resistor values. For units that are factory configured with a single voltage range, these steps do not have to be repeated.
In the event the power source does not pass the functional test, refer to the calibration procedure in Section 6 or call California Instrument’s customer satisfaction department for further assistance.
TL Series November 2001 19
User and Programming Manual - Rev C
Figure 3-5: Test Setup 351TL
20 November 2001 TL Series
User and Programming Manual - Rev C

3.9 Current Limit - Modes of Operation

When the Power Source is shipped from the factory, it is configured for the Constant Current Mode of operation. This mode means if the load current exceeds the programmed Current Limit value, the output current will continue at the programmed value.
The Power Source can be configured to operate in the Constant Voltage mode. In this mode of operation, if the load current exceeds the Current Limit value, the output voltage will default with the output relay open. The Constant Voltage mode is only usable if the default voltage is set for 5.0 volts. If the default is any other voltage, the power source may display a fault at power up.
To configure the Power Source, remove the input line voltage connection from the rear panel. Remove the top cover. Install jumpers W1 and W2 on the front panel controller. Reinstall the top cover.
TL Series November 2001 21
Loading...
+ 101 hidden pages