Bxterra SP2200LCDRT2U, SP2200LCDRTXL2U, SP1000LCDRTXL2U, SP3000LCDRTXL2U, SP3000LCDRT2U User Manual

...
5 (1)

USER MANUAL

SP SMART SINE WAVE UPS

SP3000LCDRT2U | SP3000LCDRTXL2U SP2200LCDRT2U | SP2200LCDRTXL2U SP1500LCDRT2U | SP1500LCDRTXL2U SP1000LCDRT2U | SP1000LCDRTXL2U

www.bxterra.com

1

TABLE OF CONTENTS

WARRANTY & REGISTRATION...........................

3

SAFETY INSTRUCTIONS.....................................

3-4

INSTALLATION & OPERATION..........................

5-7

PRODUCT OVERVIEW........................................

7-8

BATTERY REPLACEMENT...................................

8-9

BATTERY KIT ASSEMBLY....................................

9-10

BUTTON FUNCTIONS.........................................

10

LCD DISPLAY.......................................................

11

AUDIBLE ALARMS...............................................

11

LCD DISPLAY WORD INDEX...............................

11

UPS SETTINGS.....................................................

12-14

FAULT CODES.....................................................

15

WARNING INDICATORS.....................................

15

TROUBLESHOOTING..........................................

16

STORAGE AND MAINTENANCE.........................

16

TECHNICAL SPECIFICATIONS............................

17-18

BATTERY PACK SPECIFICATIONS......................

18

WARRANTY INFORMATION..............................

18

2

PRODUCT REGISTRATION

This bXterra product is constructed to provide unmatched power protection, quality and performance for the duration of its lifetime. Please take a few minutes to register your new product at www.bxterra.com/registration. Registration certifies your product’s warranty, confirms your ownership in the event of a product loss or theft and entitles you to free technical support. Please register your product now to receive the benefits of bXterra ownership.

SAFETY

SAVE THESE INSTRUCTIONS: This manual contains important instructions that should be followed during installation and maintenance of the UPS and its batteries.

1.This unit is intended for installation in a controlled environment (a temperature-controlled and indoor area free of conductive contaminants). Please avoid installing the UPS in locations where there is standing or running water, dust, direct sunlight or excessive humidity.

2.Use caution when lifting the UPS. Because of the considerable weight of

all rack-mount UPS systems, at least two people should assist in lifting and installing them.

3.Connect your UPS directly to a properly grounded AC power outlet with fuse or circuit breaker protection. Do not plug the unit into an outlet that is not grounded. Turn off and unplug the unit if you need to de-energize it.

4.For best performance, keep the indoor temperature around the unit between

32 F and 104 F (0 C and 40 C).

5.Do not attach medical equipment or non-computer related items, such as lifesupport equipment, microwave ovens or vacuum cleaners to the UPS. bXterra does not sell equipment meant for life-support or medical applications. Visit our website for more information about devices appropriate to plug into this UPS.

6.Only stand or set up the UPS in the direction specified in the Installation and

Operation section of this manual. Do not block fans and leave adequate space around all sides of the UPS for proper ventilation. Do not expose the unit to direct sunlight and do not install the unit near heat-emitting appliances such as a space heater or furnace. This could negatively impact the unit’s internal cooling system and cause product damage not covered under warranty.

7.As defined in the Protection of Information Technology Equipment ANSI/ NFPA 75, this UPS is not for use in a computer room (US installations only). Contact bXterra to order a special battery kit if needed to meet the ANSI/NFPA

75requirement.

8.When mounting the UPS system in a tower orientation, make sure the LCD screen panel is at the top of the UPS, not the bottom.

9.Do not plug the UPS input into its own output. Do not attach a power strip or surge protector to the UPS.

10.Do not modify the UPS’s plug and do not use an adapter that would eliminate the UPS’s ground connection.

11.Do not use extension cords to connect the UPS to an AC outlet.

12.The EPO and USB circuits are an IEC 60950-1 safety extra low voltage (SELV) circuit. This circuit must be separated from any hazardous voltage circuits by reinforced insulation.

13.If the UPS receives power from a motor-powered AC generator, the generator must provide clean, filtered, computer-grade output. Consult your generator’s manual to see if it meets these specifications.

14.The main power outlet that supplies the UPS should be easily accessible and near the UPS.

15.To reduce the risk of fire or electric shock, do not use the unit on any transportation such as airplanes or ships. The effect of shock or vibration caused during transit and the damp environment can cause the unit to short out.

16.When installing the equipment, please ensure that the sum of the leakage current of the UPS and the connected devices does not exceed 3.5mA.

17.Do not disconnect the power cable on the UPS system or the building wiring outlet (grounded outlet) during operation since this would cancel the protective grounding of the UPS system and of all connected loads.

Battery Warnings:

The UPS system operates with hazardous voltages. Repairs should only be performed by qualified maintenance personnel.

Do not operate the UPS without batteries.

Caution - risk of electric shock. Even after the unit is disconnected from the main power source, (building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.

Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high-capability capacitors, such as BUScapacitors.

To avoid electrical shock, turn off the unit and unplug it from the AC power source before servicing the battery.

Only persons who are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.

Do not dismantle the UPS during battery replacement.

Caution - risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present.

When changing batteries, install the same number and same type of batteries.

Do not attempt to dispose of batteries by burning them. This could cause an explosion.

Do not open or destroy batteries. Escaping electrolytes can cause injury to the skin and eyes. It may be toxic.

A battery can may cause a risk of electrical shock and high short-circuit current. The following precautions should be observed when working on batteries:

a)Remove watches, rings, or other metal objects

b)Use tools with insulated handles

c)Wear rubber gloves and boots

d)Do not lay tools or metal parts on top of batteries

e)Disconnect charging source prior to connecting or disconnecting battery terminals

f)Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance.

During hot-swap battery replacement, the UPS will not provide backup power in the event of a blackout or other power interruptions.

External Battery Connection Warnings:

When adding external battery packs to select models with external battery pack connectors, connect only bXterra battery packs of the correct voltage and type. Do not connect or disconnect battery packs when the UPS is operating on battery power. Visit www.bxterra.com to locate the supported battery type(s) for your UPS.

3

COMPATIBLE BATTERIES

MANUFACTURER

TYPE

RATING

CASE FLAMMABILITY

HITACHI Battery (MH14533)

GP 1272

12 V, 7.2 Ah

HB

 

GP 1272 F2

12 V, 7.2 Ah

HB

 

UPS 12360 6

12 V, 6.5 Ah

HB

 

UPS 12360 7

12 V, 6.5 Ah

HB

 

UPS 12460

12 V, 9 Ah

V-0

 

 

 

 

 

UPS 12460 FR

12 V, 8.5 Ah

HB

 

 

 

 

 

HR 1234W

12 V, 8.5 Ah

HB

 

 

 

 

 

HR 1234W FR

12 V, 8.5 Ah

V-0

 

 

 

 

 

UPS 12580

12 V, 9.4 Ah

HB

 

UPS 12580 FR

12 V, 10 Ah

V-0

TAIWAN YUASA (MH28947)

NPW36-12

12 V, 7.0 Ah

HB

 

 

 

 

 

NPW36-12FR

12 V, 7.0 Ah

V-0

 

UXW360-12

12 V, 7.0 Ah

HB

 

UXW360-12FR

12 V, 7.0 Ah

V-0

 

UXW460-12

12 V, 8.0 Ah

HB

 

 

 

 

 

UXW460-12FR

12 V, 8.0 Ah

V-0

 

 

 

 

 

NPW45-12

12 V, 7.5 Ah

HB

 

 

 

 

 

NPW45-12FR

12 V, 7.5 Ah

V-0

 

 

 

 

SHIMASTU (MH28269)

NP7-12

12 V, 7.0 Ah

V-0

 

 

 

 

 

NP9.0-12

12 V, 9.0 Ah

HB

FUJIAN MINHUA (MH47104)

MS7-12

12 V, 7.0 Ah

V-0

 

MS9-12

12 V, 9.0 Ah

HB

SHENZHEN CENTER POWER (MH25860)

CP1270

12 V, 7.0 Ah

HB

 

 

 

 

 

CP1290

12 V, 9.0 Ah

HB

 

 

 

 

SHENZHEN LEOCH BATTERIES (MH26866)

DJW12-7.0

12 V, 7.0 Ah

HB

 

 

 

 

 

DJW12-7.0 FR

12 V, 7.0 Ah

V-0

 

 

 

 

 

DJW12-9.0

12 V, 9.0 Ah

HB

 

 

 

 

 

DJW12-9.0 FR

12 V, 9.0 Ah

V-0

 

DJW12-10

12 V, 10 Ah

HB

 

DJW12-10 FR

12 V, 10 Ah

V-0

 

 

 

 

SHENZHEN RITAR POWER (MH28539)

RT1270

12 V, 7.0 Ah

HB

 

 

 

 

 

RT1290

12 V, 9.0 Ah

HB

 

 

 

 

4

Bxterra SP2200LCDRT2U, SP2200LCDRTXL2U, SP1000LCDRTXL2U, SP3000LCDRTXL2U, SP3000LCDRT2U User Manual

INSTALLATION AND OPERATION

NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use.

What’s included in the box:

1.

UPS System

5.

Screws x 8

2.

User Manual

6.

Tower Stands x 4

3.

USB A+B Type Cable

7.

Phone Line Cable x 1

4.

Ear Racks x 2

8.

Serial Port Cable x 1

The UPS is shipped without the battery connected. Before installing the UPS, please follow the steps below to reconnect the battery wires.

STEP 1: Remove the front panel.

STEP 2: Connect the AC input and reconnect the battery wires.

STEP 3: Put the front panel back on the unit.

Rack-mount Installation

CAUTION – Do NOT use the mounting brackets to lift the unit. The mounting brackets are only for securing the unit to the rack.

Install UPS alone

Install UPS and external battery

5