Burnham Webster Low NOx Data Sheet

SERIES LN3
[3]
[1]
Low Nox Burner Information
Firing
Sequence
Gas and
Gas/#2 Oil
Standard Flame
Safeguard
Minimum Gas
Pressure
Gas Train
Maximum Gas
Pressure
Size
FGR Line Size
Boiler
Size
Webster 30 PPM
Burner Model
Gas and
Gas/#2 Oil
Horsepower
Motor
Oil
Pump
[2]
A/C
LN3-40 JBX-1-*-07 3/4 N/A N/A Full Mod RM7840L 8" 14" w.c. 1.5" 4" LN3-50 JBX2-*-07 3/4 N/A N/A Full Mod RM7840L 7" 14" w.c. 1.5" 4" LN3-60 JBX2-*-10 1 N/A N/A Full Mod RM7840L 7" 28" 1.5" 4" LN3-70 LN3-80 LN3-90 LN3-100 LN3-125
JBX2-*-20 JBX2-*-30 JBX2-*-50 JBX2-*-50 JBX3-*-50
2 N/A N/A Full Mod RM7840L 7" 28" 2" 4" 3 N/A N/A Full Mod RM7840L 7" 28" 2" 6" 5 N/A N/A Full Mod RM7840L 8" 25" 2.5" 6" 5 N/A N/A Full Mod RM7840L 9" 28" 2.5" 6"
5 N/A N/A Full Mod RM7840L 14" 28" 3" 6" LN3-150 JBX3-*-50 5 N/A N/A Full Mod RM7840L 18" 28" 3" 6" LN3-175 JBX3-*-75 7.5 N/A N/A Full Mod RM7840L 18" 28" 3" 6" LN3-200 JBX3-*-100 10 N/A N/A Full Mod RM7840L 2 psi 5 psi 3" 6" LN3-250 HDSX5-*-75A 7.5 N/A N/A Full Mod RM7840L 2 psi 5 psi 3" 8" LN3-300 HDSX5-*-150B 15 1/3 2 Full Mod RM7840L 2 psi 5 psi 3" 8" LN3-350 HDSX5-*-150B 15 1/2 3 Full Mod RM7840L 2 psi 5 psi 3" 8" LN3-400 HDSX5-*-150B 15 1/2 3 Full Mod RM7840L 2 psi 5 psi 3" 8" LN3-500 HDSX7-*-200B 20 1/2 5 Full Mod RM7840L 2 psi 5 psi 3" 10" LN3-600 HDSX7-*-300B 30 1/2 5 Full Mod RM7840L 5 psi 7 psi 3" 10" LN3-700 HDSX9-*-500B 50 1/2 5 Full Mod RM7840L 115" w.c. 8 psi 3" 10" LN3-800 HDSX9-*-500B 50 1/2 7.5 Full Mod RM7840L 77"w.c 9 psi 3" 12" LN3-900 HDSX9-*-500C 50 1 7.5 Full Mod RM7840L 77"w.c 10 psi 3" 12" LN3-1000 HDSX9-*-750C 60 1 7.5 Full Mod RM7840L 77"w.c 11 psi 3" 12"
Gas and Gas/#2Oil Firing Sequence
ALL MODELS: FULL MODULATION WITH PROVEN LOW FIRE START, SYNCHRONIZED FUEL/AIR CONTROL WITH MODULATING MOTOR.
NOTES:
[1]
EXPECTED EMISSIONS ARE 30 PPMVD OR LESS NOx (CORRECTED TO 3.0% O2) AND 400 PPMVD OR LESS CO (CORRECTED TO 3.0% O2) WHEN
FIRING NATURAL GAS
[2]
ALL BLOWER AND AIR COMPRESSOR MOTORS AVAILABLE 208-230-460/60/3, INDICATE JOBSITE ON ORDER. OIL PUMP MOTORS ARE 230/60/1;
CONSULT FACTORY FOR OTHER VOLTAGES
[3] Pressure atomized 40-100 HP. Pressure atomized w/recirc 125-250. Air atomized 300 hp & up.
SERIES LN3
Burner Equipment
Equipment Fuel Description
Control Cabinet Gas, Gas/#2 Oil NEMA 1A with hinged door Control Voltage Transformer Gas, Gas/#2 Oil Included Motor Starter Gas, Gas/#2 Oil Magnetic starter with overload protection Fusing Gas, Gas/#2 Oil Control circuit only Ignition Gas, Gas/#2 Oil Gas/Electric pilot Signal Lights Gas, Gas/#2 Oil (4) - power on, fuel valve open, call for heat, flame failure Air Flow Safety Switch Gas, Gas/#2 Oil All Models Gas Train Gas, Gas/#2 Oil UL gas train for minimum inlet pressure indicated on Burner
Information table. Assembled, wired and mounted on unit consisting of the following: Manual shut off valve Gas pressure Regulator Manual leak test valve 40 & 50: 2 Gas Valves 150 & Larger: 2 Gas Valves Main Gas Valve: Motorized type Auxillary gas valve: Solenoid type 60 -125: Single Motorized Gas Valve with Proof of closure 60 & Larger: High and Low gas pressure switches
Oil Pump Gas/#2 Oil Remote oil pump set with motor and accessories mounted on
boiler skid
Oil Firing Type Gas/#2 Oil 100 - 250: Pressure Atomizing
300 and larger: Air Atomizing
Pilot Gas Controls Gas, Gas/#2 Oil All models have gas/electric pilot, manual pilot shut-off valve, pilot
gas pressure regulator and solenoid gas valve Fuel Changeover Gas/#2 Oil Manual switch Flue Gas Recirculation Gas, Gas/#2 Oil Induced flue gas recirculation, no external fan is required
Loading...