Burnham Hydronics MMII User Manual

5 (1)
DNAGNITAREPO,NOITALLATSNI
ROFSNOITCURTSNIECIVRES
NAMETUNIM
II
TNEVTCERID
RETAEHRETAW/RELIOBDERIF-SAG
.lebaLgnitaRnonwohssarebmuNlaireSdnarebmuNledoMrelioBedivorp
rebmuNledoMrelioB
__-_____IIMM
rotcartnoCgnitaeH
sserddA
rebmuNlaireSrelioB
_______6
etaDnoitallatsnI
rebmuNenohP
,reliobnonoitamrofnignikeesnehW.rotcartnocgnitaehruoyllac,reliobotsriaperroecivresroF
81404025R13-1/07 Price - $3.00
The New York City Department of Buildings has approved the Minuteman® II boiler: Approval No. MEA 332-93-E. The City of New York requires either a Licensed Master Plumber or a Fire Suppression Piping Contractor supervise the
installation of this product. The Massachusetts Board of Plumbers and Gas Fitters has approved the Minuteman® II boiler. See the Massachusetts Board of
Plumbers and Gas Fitters website, http://license.reg.state.ma.us/pubLic/pb_pre_form.asp for the latest Approval Code or ask your local Sales Representative.
The Commonwealth of Massachusetts requires this product to be installed by a Licensed Plumber or Gas Fitter.
The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning product life.
REGNAD
nisuoires
.egamad
ytreporplaitnatsbusroyruj
GNINRAW
ytreporplaitnatsbusroyrujnisuoires
.egamad
Table of Contents
I. Pre-Installation ...............................4
II. Unpack Boiler ................................ 5
NOITUAC
noitautissuodrazahyltnenimminasetacidnI
,htaednitluserlliw,dediovatonfi,hcihw
.
egamad
nitluseryam,dediovatonfi,hcihw
ytreporproyrujnironimroetaredom
noitautissuodrazahyllaitnetopasetacidnI
ECITON
noitautissuodrazahyllaitnetopasetacidnI
,htaednitluserdluoc,dediovatonfi,hcihw
.sd
razahyrujnilanosrep
VI. Venting/Air Intake Piping ............. 11
VII. Electrical ....................................... 17
nosnoitcurtsnilaicepssetacidnI
ecnanetniamro,noitarepo,noitallatsni
otdetalertontubtnatropmierahcihw
III. Boiler Water Piping .........................5
IV. Domestic Hot Water Piping ............ 8
V. Gas Piping ......................................9
2
VIII. System Start-up ............................. 18
IX. Service Instructions ....................... 22
X. Repair Parts ..................................29
NOITUAC
itaeheht,ytilibissopasisepipnezorfoteudegamadfI.ecivres
.evitareponisireliobehtfiegamadtneverpotmetsysgnitaeh
tuohtiwtratsertondnanwodtuhsotreliobehtesuacyamhcihwslortnocsniatnocreliobsihT
tfelebtondluohsmetsysgn
ehtnodellatsniebdluohssmraladnasdraugefasetairporpparo;rehtaewdlocnidednettanu
GNITAEHESUOH
GNIPIP
NOITCENNOC
)SEHCNI(
RELIOB
LEDOM
07-4IIMM
501-4IIMM
501-5IIMM
041-5IIMM
YLPPUS
)TPN(
4
/1-14/1-12/12/12/143
NRUTER
)TPN(
RETAW
)TPN(NI
RETAWCITSEMOD NOITCENNOCLIOC
)SEHCNI(
RETAW
)TPN(TUO
YLPPUSSAG NOITCENNOC
)SEHCNI(
NOI
TSUBMOC
EKATNIRIA
NOITCENNOC
)SEHCNI-.AID(
TNEVEULF
NOITCENNOC
)SEHCNI-.AID(
RELIOB
)SNOLLAG(
2/1-2
38/1-5.BL543
YTICAPACRETAW
'A'
KNAT
)SNOLLAG(
8/7-5.BL703
6.71
.XORPPA
GNIPPIHS
THGIEW
Figure 1: Dimensional Drawing
3
I. Pre-Installation
GNINRAW
erofebsnoitcurtsnilladaerylluferaC
llawollofoteruliaF.reliobgnillatsni
esuacnacredroreporpnisnoitcurtsni
.htaedroyrujnilanosrep
A. Installation must conform to the requirements of the
authority having jurisdiction. In the absence of such requirements, installation must conform to:
USA ANSI Z223.1, National Fuel Gas Code. Where required by the authority having
jurisdiction, the installation must also conform to ANSI/ASME CSD-1 Standard for Controls and
Safety Devices for Automatically Fired Boilers.
CANADA CAN/CGA B149.1 or .2 Installation Codes
for Gas Burning Appliances and Equipment, and CSA C22.1 Canadian Electrical Code, Part I.
B. Appliance is design certifi ed for installation on
combustible fl ooring. The boiler must not be installed on carpeting.
C. Provide clearance between boiler jacket and
combustible material in accordance with local fi re ordinance. Refer to Figure 2 for minimum listed clearance from combustible material. Recommended service clearance is 24 inches from left side, right side, front and rear. Service clearances may be reduced to minimum clearances to combustible materials.
D. Install on level fl oor. For basement installation provide
concrete base if fl oor is not perfectly level or if water may be encountered on fl oor around boiler.
E. Protect gas ignition system components from water
(dripping, spraying, rain, etc.) during boiler operation and service (circulator replacement, condensate trap, control replacement, etc.).
Figure 2: Minimum Clearances to Combustible Surfaces
4
F. Provide combustion and ventilation air in accordance
with applicable provisions of local building codes, or National Fuel Gas Code, ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation.
GNINRAW
rianoitalitnevdnanoitsubmocetauqedA
reporperussaotdedivorpebtsum
.noitsubmoc
II. Unpack Boiler
This boiler is equipped with a fan which produces an
induced draft through the unit. 100% of combustion air is pulled in from outdoors and the fl ue gases are exhausted to the outdoors through the intake air/vent system. Refer to Section VI.
G. Do not install boiler where gasoline or other fl ammable
vapors or liquids, or sources of hydrocarbons (i.e. bleaches, cleaners, chemicals, sprays, paint removers, fabric softeners, etc.) are used or stored.
NOITUAC
.roolftsniagatekcaj
A. Move boiler to approximate installed position. B. Remove all crate fasteners.
Figure 3: Removal From Skid
III. Water Piping and Trim
C. Remove outside container with all other inside
protective spacers and bracing. Save two of the
reliobpmubtonoD.reliobpordtonoD
wooden slats from the container sleeve for use in Steps E and F.
D. Remove four (4) boiler hold-down fasteners. See
Figure 3.
E. Tilt the boiler to one side and slide a wooden slat under
the two nylon glides.
F. Tilt the boiler to the other side and slide another
wooden slat under the two nylon glides.
G. Slide the boiler forward or backward off the skid using
the two wooden slats as runners.
H. Move boiler to its permanent location.
NOITUAC
nitluseryamreliobepipylreporpoteruliaF
roreliobotegamaddnanoitareporeporpmi
.gnidliub
REDEEFRETAWCITAMOTUAESUTONOD
.RELIOBSIHTHTIW
NOITUAC
lliwretawreliobfonoitanimatnocnegyxO
reliobleetsdnanorifonoisorrocesuac
.eruliafreliobotdaelnacdna,stnenopmoc
tonseodytnarrawdradnatss'mahnruB
negyxoybdesuacsmelborprevoc
.retawreliobfonoitanimatnoc
A. Design and install boiler and system piping to
prevent oxygen contamination of boiler water.
Oxygen contamination sources are system leaks
requiring addition of makeup water, fi ttings, and oxygen permeable materials in distribution system. Eliminate oxygen contamination by repairing system leaks, repairing fi ttings, and using nonpermeable materials in distribution system.
B. Connect system supply and return piping to boiler.
See Figure 4. Also consult I=B=R Installation and Piping Guides. Maintain a clearance between hot water piping and combustible construction as required by local codes. In the absence of local codes, ½" clearance should be used. Note that a system circulator is required and is not supplied with the Minuteman II.
5
C. Install Safety Relief Valve. See Figure 4. Safety Relief
Valve must be installed with spindle in vertical position.
Installation of the relief valve must be consistent with the ASME Boiler and Pressure Vessel Code, Section IV.
Figure 4: Recommended Water Piping for Zone Valve Zoned Heating Systems
GNINRAW
folaitnetopetanimileotroolfraendepip
ves
.sevlavffo-tuhsyna
D. If boiler is used in connection with refrigeration
systems, boiler must be installed with chilled medium
piped in parallel with the heating boiler using appropriate valves to prevent chilled medium from entering boiler, see Figure 5. Also consult I=B=R Installation and Piping Guides.
aeraynaniepiptonoD.snrubere
Refer to Figure 5a for a diagram of the water piping
system inside the Minuteman
ebtsumgnipipegrahcsidevlavfeilerytefaS
llatsnitonoD.ruccodluocgnizeerferehw
E. If boiler is connected to heating coils located in air
handling units where they may be exposed to refrigerated air, boiler piping must be equipped with ow control valves to prevent gravity circulation of boiler water during operation of cooling system.
®
II's jacket.
F. Use a boiler bypass if the boiler is to be operated in a
system which has a large volume or excessive radiation where low boiler water temperatures may be encountered (i.e. converted gravity circulation system, etc.).
6
Install pipe tee between circulator and boiler return
along with second tee in supply piping as shown in Figure 4. Bypass should be same size as the supply and return lines with valves located in bypass and supply outlet as illustrated in Figure 4 in order to regulate water fl ow to maintain higher boiler water temperatures.
After the boiler is operational (reference Section VII.
System Start-Up) set by-pass and boiler supply valves to half throttle position to start. Operate boiler until system water temperature reaches normal operating range.
Adjust valves to provide 180° to 200°F supply water
temperature. Opening the boiler supply valve will raise system temperature, while opening the by-pass valve will lower system supply temperature.
G. A hot water boiler installed above radiation level
must be provided with a low water cut-off device as part of installation.
If a low water cut-off is required, it must be mounted in
the system piping above the boiler.
The minimum safe water level of a hot water boiler is
just above the highest water containing cavity of the boiler; that is, a hot water boiler must be full of water to operate safely.
It is required to perform a long term pressure test of the
hydronic system, the boiler should fi rst be isolated to avoid a pressure loss due to the escape of air trapped in the boiler.
To perform a long term pressure test including the
boiler, ALL trapped air must fi rst be removed from the boiler.
A loss of pressure during such a test, with no visible
water leakage, is an indication that the boiler contained trapped air.
H. Oil, grease, and other foreign materials which
accumulate in new hot water boilers and a new or reworked system should be boiled out, and then thoroughly fl ushed. A qualifi ed water treatment chemical specialist should be consulted for recommendations regarding appropriate chemical compounds and concentrations which are compatible with local environmental regulations.
Figure 5: Recommended Piping for Combination
Heating & Cooling (Refrigeration)
Systems
Figure 5a: Internal Water Piping System Diagram
I. After the boiler and system have been cleaned and
ushed, and before refi lling the entire system add appropriate water treatment chemicals, if necessary, to bring the pH between 7 and 11.
Figure 6: Recommended Bypass Piping
7
IV. Domestic Hot Water Performance and Piping
A. Domestic hot water ratings for the Minuteman
based two 5 minute draws with 10 minute recovery period at 100°F average temperature rise. Refer to Table 1 for ratings.
Table 1: Domestic Hot Water Ratings
RELIOB
LEDOM
07-4IIMM9.241
501-4IIMM1.361
501-5IIMM1.361
041-5IIMM3.381
WARDRETAW
)MPG(
B. Drain domestic water system.
1. Shut off cold water supply at main shutoff valve.
2. Open 1 or more system faucets to relieve pressure. Open system drain valve, leaving faucets open to relieve vacuum.
3. Disconnect exiting domestic hot water heating system ( if applicable).
®
)ISP(
II are
PORDERUSSERP
Figure 7: Domestic Hot Water Piping
ECITON
ehtsaherutarepmetretawcitsemoD
erutarepmetderisedehtdeecxeotlaitnetop
.elcycgnitaehecapsagnirud
C. Connect hot water piping to ½" NPT outlet of heater.
See Figure 7.
GNINRAW
gnirepmet(evlavgniximcitamotuanallatsnI
ksirdiovaotteltuoretaehsselknatehtta)evlav
tohylevissecxeoteudgnidlacsrosnrubfo
ehtniatniamdnatsujdA.serutxiftaretaw
ehthtiwecnadroccanievlavgnixim
tcafunam
.snoitcurtsnis'reru
D. Connect cold water piping to ½" NPT inlet of heater.
See Figure 7.
E. Fill domestic hot water system.
1. Open all faucets to allow air to purge from heater and piping.
2. Open domestic hot water shutoff valve (if used).
3. Open cold water inlet shutoff valve.
4. Purge air from domestic water system. Close faucets.
5. Check system for leaks. Repair as necessary.
8
V. Gas Piping
A. Size gas piping. Design system to provide adequate gas
supply to boiler. Consider these factors:
1. Allowable pressure drop from point of delivery to boiler. Maximum allowable system pressure is ½ psig. Actual point of delivery pressure may be less; contact gas supplier for additional information. Minimum gas valve inlet pressure is stamped on the rating label located in the boiler's vestibule compartment.
2. Maximum gas demand. Table 2 lists boiler input rate. Also consider existing and expected future gas utilization equipment (i.e. cooking equipment).
3. Length of piping and number of fi ttings. Refer to Table 3 for maximum capacity of Schedule 40 pipe. Table 4 lists equivalent pipe length for standard ttings.
Table 2: Rated Input
relioB
ledoM
rebmuN
07-4IIMM078
501-4IIMM5012
501-5IIMM5012
041-5IIMM0416
larutaN
saG
etaRtupnI
]ruohrepteefcibuc[
saGPL
saG
noitcennoC
4. Specifi c gravity of gas. Gas piping systems for gas with a specifi c gravity of 0.70 or less can be sized directly from Table 3, unless authority having jurisdiction specifi es a gravity factor be applied. For specifi c gravity greater than 0.70, apply gravity factor from Table 5. If exact specifi c gravity is not shown choose next higher value.
For materials or conditions other than those listed
above, refer to National Fuel Gas Code, NFPA 54/ ANSI Z223.1, or size system using standard engineering methods acceptable to authority having jurisdiction.
B. Connect boiler gas valve to gas supply system.
1. Use methods and materials in accordance with local plumbing codes and requirements of gas supplier. In absence of such requirements, follow National Fuel Gas Code, ANSI Z223.1.
2. Use thread (joint) compounds (pipe dope) resistant to action of liquefi ed petroleum gas.
3. Install sediment trap, ground-joint union and manual
)sehcnI(eziS
shut-off valve upstream of boiler gas control valve and outside of jacket. See Figure 8.
4. All above ground gas piping upstream from manual shut-off valve must be electrically continuous and bonded to a grounding electrode. Do not use gas piping as grounding electrode. Refer to National Electrical Code, ANSI/NFP A 70.
Table 3: Maximum Capacity of Schedule 40 Pipe in CFH For Gas Pressures of 0.5 psig or Less
htgneL ]teeF[
01231872025050,1571063086004,1
0229091053037021052564059
033725158209579002573077
043603154200528071023066
056551151204437151582085
0605501591004668310620
07646908107316521042094
08340907105375811022064
09044806102335011502034
001839705150305301591004
½¾ 1 ¼1½¾1¼1
porDerusserP.c.whcni3.0 porDerusserP.c.whcni5.0
35
9
ECITON
neebevahlevelaesevobateef000,2nahtretaergsedutitlatanoitallatsniroftliubsreliobASU
ehtreplevelaesevobateef000,1reptnecrep4etartupnisagecuderotdecifiroyllaiceps
tceS,1.322ZISNA,edoCsaGleuFlanoitaN
.lebalgnitarehtno"H"xiffusrebmun
ecifiro'sreliobnaidanaC.FxidneppAdna2.1.8noi
ledomehtybelbaifitnedierasledomreliobedutitlahgiH.lebalgnitarehtnodetacidnisignizis
Table 4: Fitting Equivalent Lengths
eziSepiPlanimoN
gnittiF
½¾ 1 ¼1
llE°547.012.16.1
llE°096.11.26.25.3
)woblEsA(eeT1.31.42.59.6
C. Pressure test. The boiler and its gas connection must be
leak tested before placing boiler in operation.
1. Protect boiler gas control valve. For all testing over ½ psig, boiler and its individual shutoff valve must be disconnected from gas supply piping. For testing at ½ psig or less, isolate boiler from gas supply piping by closing boiler's individual manual shutoff valve.
Table 5: Specifi c Gravity Correction Factors
cificepS
ytivarG
05.001.103.170.1
55.040.104.140.1
06.000.105.100.1
56.069.006.179.0
07.039.007.149.0
57.009.0
08.078.0
noitcerroC
rotcaF
cificepS
ytivarG
2. Locate leaks using approved combustible gas detector, soap and water, or similar nonfl ammable solution. Do not use matches, candles, open fl ames, or other ignition source.
noitcerroC
rotcaF
10
Figure 8: Recommended Gas Piping
VI. Venting / Air Intake Piping
:swollofsaerasnoitcurtsnieseht
stnenopmoctnevfogniniojynA)1
saeltasevlovnitaht
enot
tnenopmoctnevssel-teksag
tnalaesehtseriuqersyawla
.noitacilppa
ehT)2
.tnenopmoc
ssel-teksagafodneelamef
seriuqersyawlatnenopmoctnev
ehtfosseldrager,dnabpmalca
tnevelamgnitamehtfongised
ECITON
hcaednanidesahpgnieberaAerugiFniwolebderutcipstnenopmocmetsystnevdeteksagehT
gnitnevssel-teksagdeilppusylsuoiverpehthtiwelbaegnahcretnisitnenopmoctnev
odyehtsa,niojotreisaednarekciuqyllarenegerastnenopmoctnevrewenehT.stnenopmoc
.dehcattaerasdnabpmalcriehtdnanoitacilppatnalaesehteriuqerton
adnatnenopmoctnevdeteksagatneveehtnI
-nocretniebtsumtnenopmoctnevssel-teksag
htiwdetaicossasnoitcurtsniehtwollof,detcen
f
oselpicnirpgnidiugowtehT.C01roB01erugiF
Figure A: Burnham Vent
.tnalaesfoebutecnuo
A. General Guidelines.
1. Vent system installation must be in accordance with National Fuel Gas Code, ANSI Z223.1, Venting of Equipment, or applicable provisions of local building codes. Contact local building or fi re offi cials about restrictions and installation inspection in your area.
2. This appliance requires a Special Gas Vent. The product is designed to use Burnham supplied AL 29-4C® Stainless Steel vent system components. The following manufacturer's offer similar AL 29­4C® components and are approved for use with this product: Heat-Fab Inc. - Saf-T-Vent, Flex-L International Inc. - Star-34, Protech Systems, Inc. ­FasNSeal™, and Z-Flex U. S., Inc. - Z-Vent. The use of these alternate manufacturer's venting systems will require adapters to connect to the Burnham supplied vent connector and vent terminal. These adapters are not supplied with this unit and should be obtained from the supplier of the alternate manufacturer's venting system. See Table 7 for complete parts list.
.tnalaesdnadnabpmalcahtiwdeilppussitnenopmoctnevssel-teksaghcaE
GNINRAW
®
C4-92LA
3. Vent length restrictions are based on equivalent length of vent pipe (total length of straight pipe plus equivalent length of fi ttings). Maximum vent length is listed in Table 6. Do not exceed maximum vent/ air intake lengths. Table 7 lists equivalent length for ttings. Do not include Vent Terminal or Vent Connector in equivalent feet calculation.
Table 6: Vent/Air Intake Length
).tF.viuqE(epiPtneV"3"4epiPekatnIriA).tF.viuqE(
.niM.xaM.niM.xaM
8078 07
.smetsystnevdesab
3enodnadnabpmalcenosniatnoctahtelbaliavasi,2036116rebmuntrap,tiKnoitisnarTtneVA
403,dezinavlaghtiwreliobsihtesutonoD
nonrehtoynaroleetssselniats613ro
11
Table 7: Burnham Vent System Components
mahnruB
metsyStneV
tnenopmoC
tF1xepiP.aiD"3U69261181
tF3xepiP.aiD"3U89261183
tF5xepiP.aiD"3U00361185
elbatsujdAxepiP.aiD"3U9136118
woblE°09.aiD"3U49261185
woblE°54.aiD"3U29261185
eeTniarDlatnoziroH.aiD"3U2036118½
eeTn
iarDlacitreV.aiD"3U4036118½7
elbmihTllaWelgniS"36116118---
elbmihTllaWelbuoD"35116118---
mahnruB
traP
rebmuN
otlauqE
neLdellatsnI
4. Do not install venting system components on the exterior of the building except as specifi cally required by these instructions.
5. Thickness of exterior walls through which vent-air intake system may be installed: Minimum: 3", Maximum: 12".
B. Removal of Existing Boiler. For installations not
involving the replacement of an existing boiler, proceed to Step C.
When an existing boiler is removed from a common
venting system, the common venting system is likely to be too large for proper venting of the remaining appliances. At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation:
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion, and other defi ciencies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range-hoods and bathroom exhausts, so they will operate at maxi mum speed. Do not operate a summer exhaust fan. Close replace dampers.
4. Place in operation the appliance being inspected. Follow the Lighting (or Operating) Instructions.
tnelaviuqE
epiPfoteeF
Adjust thermo stat so appliance will operate continuously.
5. Test for spillage at the drafthood relief opening after 5 minutes of main burner operation. Use the fl ame of a match or candle, or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each appliance remain ing connected to the common venting system
htg
)46.1ot60.1(
properly vents when tested as outlined above, return doors, win dows, exhaust fans, fi replace dampers and any other gas burning appliance to their previous conditions of use.
7. Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1 and/or CAN/CGA B149, Installation Codes. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part 11 in the National Fuel Gas Code, ANSI Z223.1 and/or CAN/CGA B149, Installation Codes.
C. Install Vent Connector.
1. Remove vent connector from vent accessory carton.
2. Remove gaskets, orifi ce plate and hardware from blower outlet fl ange.
3. Assemble orifi ce plate gaskets, orifi ce plate, and vent connector. See Figure 9.
Figure 9: Vent Connector Installation
12
Loading...
+ 28 hidden pages